FM Approval Standards for
Sandwich panels:
Fire & Natural Hazards
Colin Hill
FM Approvals Europe
![Page 2: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/2.jpg)
What’s in a name?
![Page 3: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/3.jpg)
Research Campus
Engineering Research
The FM Global Solution………
![Page 4: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/4.jpg)
• Risk Identification
• Risk quantification
• Share recommendations and agree on solutions
• Assist in
implementation
FM Global Insurance
![Page 5: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/5.jpg)
What do we FM APPROVALS do?
![Page 6: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/6.jpg)
In June 1897, the Inspection Department of the
Associated Factory Mutual Fire Insurance
Companies Approved its first Electrical Fittings.
FM Approvals History
![Page 7: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/7.jpg)
• Expanding the availability of FM Approved products locally available and serviced, and accepted by local jurisdictions
• Offering clients choices in these products (wide availability)
• Influencing product testing standards in Europe and Asia.
• Enhancing relationships with other certification organizations.
• Offering technical support to local FM Global Operations.
Reduce barriers to property loss prevention for our clients by…….
FM Approval’s Strategy
![Page 8: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/8.jpg)
FM Approvals responsibilities in Europe
• Notified Body under the ATEX Directive &
Construction Products Directive
• EOTA member for innovative CPD products.
• IECEx Certification Body
• UKAS Accredited Certification Body
• Member of Standards Committees & Industry
Groups
• Undertaking FM Approval projects for US,
Canadian, European & International Markets
• Conducting Facilities and Procedures Audits.
![Page 9: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/9.jpg)
Approval Guide
![Page 10: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/10.jpg)
Approval Standards
Over 150 FM Approvals
Standards
All publicly available
through the website.
![Page 11: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/11.jpg)
• Roofing Products
• Insulated and non-insulated walls and ceilings
• Clean Room Materials
• Cooling Towers and Air handling Equipment
• Pipe Insulation and Ducts
• Cables
• Fire Stopping Materials
• Explosion Venting and Construction
• Fire Doors and Frames
• Less Flammable Hydraulic Fluids
Building Materials – “Passive”
![Page 12: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/12.jpg)
Materials
Lab
Fire Technology Lab Hydraulics Lab
Electrical Lab
Natural Hazards Lab
EQ Lab
Multimedia
Center
2009 FM Global Research Campus
Training Lab
![Page 13: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/13.jpg)
Research Campus
![Page 14: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/14.jpg)
From small to large scale fire tests
![Page 15: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/15.jpg)
FM Approval Standards for
Sandwich panels:
Fire & Natural Hazards
![Page 16: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/16.jpg)
4471 Class 1 Panel Roofs
4880 Class 1 Insulated Wall and Ceiling
Panels - Fire
4881 Class 1 Exterior Wall systems
4882 Class 1 Interior Wall and ceiling
systems – Smoke Sensitive
occupancies
FM Standards – Sandwich Panels
![Page 17: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/17.jpg)
FM Standards - Roofs and Walls
![Page 18: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/18.jpg)
FM Class 4880
![Page 19: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/19.jpg)
Insulated Panels - FM 4880
FM 4880 Fire Performance of internal wall, roof and
ceiling panels – developed in 1970’s
• Witness production & sample selection
• Flammability characterisation of core (FPA)
• Large scale 25ft or 50ft corner test
• Large scale room test (UBC 26-3 or ISO 9705)
• Small scale identification tests
• Result is Class 1 approval :
‘limited combustibility’
![Page 20: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/20.jpg)
FM 4880 25ft Corner Test
• Developed in the 1970’s to evaluate fire
spread performance of various assemblies
• Full scale, not “modeling” test
• 15.2 x 11.5 x 7.6 m high (50 x 38 x 25 ft)
• 15 minute test and 750lbs (340kg)
conditioned oak pallets
![Page 21: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/21.jpg)
FM Approvals 25ft Corner Test
![Page 22: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/22.jpg)
FM Approvals 25ft Corner Test
![Page 23: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/23.jpg)
Flammability test
on Core FPA
25ft corner Test
Exception 1:
dependant on
FSPc value
Room Test
UBC 26-3 or ISO9705
Small scale
“code” Tests
e.g. ASTM E84
Combustible Core
9.1m Approval
Satisfy the 30ft tests
50ft corner Test
Exception 2:
Parallel Panel Test
No Height Restriction
Ignition of the ceiling
shall not occur
ASTM D482
(ash content)
Combustible Core
Unlimited Height or
15.2m Approval
Non-combustible Core Unlimited
Height Approval
Room Test
UBC 26-3 or ISO9705
ISO 1716
(heat of combustion)
E2058
(core combustion)
4880: CLASS 1 Test Route
![Page 24: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/24.jpg)
Fire Propagation
Apparatus:- FPA
Used to determine
FSPc value
ASTM E2058
ISO 12136
Now
BS ISO 12136:2011
![Page 25: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/25.jpg)
Technical Innovation
Low smoke yield wall/ceiling panels
– Pharmaceutical warehouses
– Food warehouses
– Clean Rooms
![Page 26: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/26.jpg)
FM 4882 approval and test options
Cleanrooms Pharmaceutical, food
prep. & others
Test Method
Class1 4880 Approval ht 4880 Approval ht
Fire Propagation Index FPI
Or 8ft Parallel panel test (60kW)
[FM4910]
≤ 6(m/s1/2)/(kW/m)2/3
or Propagation ≤ 6ft
Max heat flux @4ft ≤ 40 kW/m²
Chemical heat release rate
decay ≥1/2 @1min. & decay ≤ 25%
@2min
Smoke Development Index SDI
or 8ft Parallel panel test (60kW)
[FM4910]
≤ 0.4 [(m/s1/2)/(kW/m)2/3] [g/g]
or Max. smoke generation ≤ 0.23g/s
Smoke generation @12min
≤ 0.07g/s
Total smoke generation ≤ 60g
Avg Smoke emission rate Gsmoke
16ft parallel panel test (360 kW)
≤ 120mg/s ≤ 240mg/s
ASTM E84
Flame spread index FSI
Smoke Developed Index SDI
≤ 25
≤ 450
≤ 25
≤ 450
![Page 27: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/27.jpg)
4882: 16 ft. (4.9 m) Parallel Panel
![Page 28: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/28.jpg)
4882: 16 ft. (4.9 m) Parallel Panel
![Page 29: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/29.jpg)
FM Approval Standards for
Sandwich panels:
Wall Panels
Fire & Natural Hazards
![Page 30: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/30.jpg)
FM 4881 External Walls
• FM Global Research Approval Standard 4881 developed
as a consequence of losses suffered post Hurricane
Andrew 1992.
• Addresses ‘natural hazards’ other than fire for external
walls
• Applicable to all areas of the world, whether a hurricane
zone or not
• Minimum rating Class 1 Fire and 30psf (1.45kPa) in
ward wind resistance.
![Page 31: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/31.jpg)
![Page 32: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/32.jpg)
Damage to wall panels from windstorm.
Test #1
![Page 33: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/33.jpg)
FM 4881 External Walls
FM 4881(2005) Class 1 Exterior Walls
• Witness production & sample selection
• Must satisfy FM 4880 for fire performance first
• Simulated Hail resistance test
• Static & cyclic pressure tests (~4m x 5m sample)
• Cyclic pressure test for hurricane zones following
missile impact
• Factory Audit
![Page 34: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/34.jpg)
Large Burn Lab
Research Labs
Approvals
Materials Labs
Approvals
Natural Hazards Labs Approvals
Hydraulics Labs
Approvals
Electrical Labs
FM 4881 Wall Panel Test
Insulation core has failed under simulated wind
pressure.
![Page 35: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/35.jpg)
Class 1 Exterior Wall Systems
– Class 4881
• Customer will choose the pressure and pressure coefficient to test. See FM Global Property Loss Prevention Data Sheet 1-28.
• Calculation and wind maps are included in this document
• There are many factors that are used to find the design pressures including: ground roughness, building roof height, building width, etc. Data sheet 1-28 is considered by FM field engineers when determining building materials installation applicability.
• Minimum wall rating is - +30psf. (1.45kPa)
• 4880 Approval (fire) is a requirement of 4881.
![Page 36: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/36.jpg)
• If you were to tell us, for example, to test your panels
per FM Approval Standard 4881 at a pressure of 30 psf with a pressure coefficient of 1.4 and were successful, your Approved pressure rating would be:
• 30psf inward • 42psf outward (30 x 1.4)
![Page 37: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/37.jpg)
Wall panel being tested. Purlin thickness and spacing must be selected by customer
![Page 38: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/38.jpg)
FM Approvals Pipe Chase Test Fire grows. Crib will burn for 15 minutes. Wall panel being pressure tested.
![Page 39: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/39.jpg)
FM Approvals Pipe Chase Test Fire does not propagate, flames die down. Wall panel tested to failure.
![Page 40: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/40.jpg)
FM Approvals Pipe Chase Test After test, most of test sample material is unburned. Wall panel tested to failure.
![Page 41: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/41.jpg)
FM Approvals Pipe Chase Test Test material meets acceptance criteria.
![Page 42: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/42.jpg)
FM Approval Standards for
Sandwich panels:
Roof Panels
Fire & Natural Hazards
![Page 43: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/43.jpg)
FM Approval 4471 Roof Panels
• Interior Combustibility (4880)
• Exterior Combustibility (ASTM E108)
• Natural Hazards
![Page 44: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/44.jpg)
External fire: ASTM E108
![Page 45: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/45.jpg)
FM Approval 4471 Roof Panels
• Interior Combustibility (4880)
• Exterior Combustibility (ASTM E108)
• Wind
• Hail
• Water Leakage
• Foot Traffic
• The minimum Windstorm Classification
Class1-60
• = a minimum Uplift pressure 60 psf (2.9kpa)
![Page 46: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/46.jpg)
• The Roof Field Area Design Pressure is calculated in
Data sheet 1-28, based on wind speeds and design coefficients building heights etc.
![Page 47: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/47.jpg)
Roof pressures
![Page 48: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/48.jpg)
A picture is worth a thousand words …….
![Page 49: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/49.jpg)
12 X 24 Simulated Wind Uplift
Test
![Page 50: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/50.jpg)
Joint Failure – cannot calculate
![Page 51: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/51.jpg)
Impact testing
![Page 52: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/52.jpg)
Prof. Peter Sparks, Clemson
University
“There has not been a hurricane in North
America in the last 25 years which would
have damaged a building constructed in
accordance with FM Global design
guidelines.”
![Page 53: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/53.jpg)
RoofNav®
THE SOURCE FOR FM APPROVED ROOF ASSEMBLY DETAILS
•Ratings Calculator wizard that determines the required roof ratings
for any building and roof area.
•An online database of FM Approved roof products and assemblies
that meet specific criteria.
•FM Global Property Loss Prevention Data Sheets provide
installation guidelines.
www.roofnav.com
![Page 54: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/54.jpg)
RoofNav®
Suite of Tools • FM Approved Product Search
• FM Approved Assembly Search Tools
• Ratings Calculator
• Glossary • FM Global Property Loss Prevention Data Sheets
• Approval Standards
• Project Files
• FREE Training
RoofNav®
![Page 55: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/55.jpg)
FM Approval Standards for
Sandwich panels:
FM Approval and CE Marking
![Page 56: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/56.jpg)
FM Diamond CE Marking
Reaction to Fire
Large Scale Tests
•calorimeter
•corner tests
•room tests
Reaction to Fire
Small Scale Tests
• EN 13501-1 classification ( A1
to F)
• SBI test and others (small scale)
F&PA audit FPC audit
Sample witnessing and
selection by FM Approvals
Sample witnessing and selection
depends on AoC system
FM Diamond and the CE Mark
![Page 57: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/57.jpg)
The FM Approvals Solution…
FM
APPROVED
![Page 58: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/58.jpg)
FM Approvals Certification Marks
![Page 59: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/59.jpg)
Reduce Clients’ Risks
Global Loss Prevention Solutions
Global Acceptance of FM Approved
Products
![Page 60: FM Approval Standards for Sandwich panels: Fire & …...4882 Class 1 Interior Wall and ceiling systems – Smoke Sensitive occupancies FM Standards – Sandwich Panels FM Standards](https://reader034.vdocuments.mx/reader034/viewer/2022050607/5fae14e5aa13e81ff243d230/html5/thumbnails/60.jpg)
Thank You
Over 45,000 products
and services specified
worldwide.
www.fmapprovals.com
www.roofnav.com
www.approvalguide.com