ECE 5984: Power Distribution System Analysis
Lecture 1: Introduction to Power Distribution Systems Reference: Textbook, Chapter 1
Instructor: V. Kekatos
1
![Page 2: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/2.jpg)
2
The big picture
![Page 3: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/3.jpg)
Distribution substations and feeders
3
• Switching
• Voltage regulation
• Voltage transformation
• Protection
• Metering § analog current recordings § meters on substation and/or feeder § digital meters record min/max/avg of
current, voltage, power, power factor over 15 min, 30 min, or 1 hr
![Page 4: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/4.jpg)
Switching and protective devices
4
• Switching devices § manual switches
§ remote controlled switches
• Protective devices § circuit breakers
§ fuses § overcurrent relays
§ reclosers § sectionalizers
Photo courtesy of K. Schneider (PNNL)
![Page 5: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/5.jpg)
Switches
5
• Simple devices; no control/communication
• Cannot interrupt fault currents and lack synchronization equipment
Photo courtesy of K. Schneider (PNNL)
• Isolate equipment for maintenance at substation, or reconfigure feeders
• Located at substation or feeder
• Manual control, or remote control via SCADA signals
• Control equipment located at bottom of supporting structure or utility pole
![Page 6: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/6.jpg)
Circuit breakers
6
• They can be operated remotely
• Similar to switches, but can break fault currents
• Located at substation due to size (rating)
• Classified based on material used to quench arc (air, oil, vacuum, SF6)
• Used to protect rather than disconnect
Photo courtesy of K. Schneider (PNNL)
![Page 7: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/7.jpg)
Detailed structure
7
138:69 kV
Distribution substation 15-200 MVA @ 2-46 kV • Typical distribution feeders
4 MVA @ 4 kV 12 MVA @ 12.47 kV 20 MVA @ 23 kV 30 MVA @ 34 kV
[Glover, Sarma, Overbye]
69:14 kV
14:480/208 kV
• sub-transmission is optional e.g., 115:4 kV [IEEE 123-bus]
• Inline transformers 14:4 kV
![Page 8: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/8.jpg)
Breaker-and-a-half scheme
8
![Page 9: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/9.jpg)
Voltage transformers
9
On-Load Tap-Changing (OLTC) transformer § a.k.a. Tap Changing Under-Load Transf. (TCUL)
§ located at the substation; can serve multiple feeders
§ maintains constant low-voltage side under varying distribution load or transmission-side conditions
§ can be substituted with transformer & regulator
In-line transformer and regulators
Distribution transformers
![Page 10: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/10.jpg)
Primary and secondary distribution
10
Distribution transformers (pole/pad-mounted) form the boundaries
Classes change: IEEE 1547 defines MV as 1-35 kV …
![Page 11: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/11.jpg)
Distribution lines
11
three-phase four-wire multi-grounded Y
three-phase Delta (under replacement)
[Blume]
![Page 12: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/12.jpg)
240/120 V single-phase distribution transformers
12
[Blume]
![Page 13: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/13.jpg)
208/120 V three-phase distribution transformers
13
[Blume]
![Page 14: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/14.jpg)
480/277 V three-phase distribution transformers
14
[Blume]
Small single-phase transformers provide 120 V from 480 V for lighting/office
![Page 15: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/15.jpg)
Voltage regulation
15
• Capacitors: power factor correction (include switching and protective elements)
• Voltage regulators: induction devices in shunt or series with regulated circuit for the control of its voltage
• Voltage magnitude should lie within ±5% of nominal (114-126 for 120 V)
![Page 16: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/16.jpg)
Radial feeders
16
primary ‘main’ feeder: 2-30 MVA @ 2-46 kV
secondaries: 5-500 kVA @ 120-480 V
3, V, single-phase laterals
in-line transformers
protection devices
regulators and cap banks
distribution transformers 240/120 V 1-phase (split-phase) 208/120 V 3-phase 480/277/120 V 3-phase 400/230 V 3-phase (Europe)
![Page 17: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/17.jpg)
Distribution feeder map
17
• Transformers (kVA rating, connection)
• Shunt capacitors (kVAR rating, phase)
• Voltage regulators (phase, ratios, compensator settings)
• Lines (OH/UG, distance, conductor, phase)
• Switches (NO/NC)
• Geographical distances
• Conductors (radius, diameter, resistance)
See e.g., the actual IEEE 123-bus benchmark…
![Page 18: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/18.jpg)
Fuses
18
• Low-cost devices used to interrupt fault currents
• Operate on an inverse time curve: the higher the fault current, the quicker the fuse will blow
Photo courtesy of K. Schneider
• Once fuse interrupts overcurrent, it has to be manually replaced by a line crew
• Fuse coordination: the practice of selecting fuse sizes so that fuse closest to the fault blows first
• Fuse coordination requires knowledge of system load and gets complicated with distributed resources
![Page 19: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/19.jpg)
Example: fuse protection
19
• Permanent line to ground fault on line 705-712
• Fuse blows due to overcurrent, thus isolating single-phase lateral
• Customers at node 712 and 742 call in to report power outage
• Utility dispatches a line crew to investigate
• Line crew locates fault and repairs condition
• Line crew replaces blown fuse with a new one
• Single-phase lateral us back to service Photo courtesy of K. Schneider
![Page 20: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/20.jpg)
Protection relays
20
• Use local measurements to generate control signals
Photo courtesy of K. Schneider
• Fuses measure only current; relays measure voltage and current so can also estimate - real and reactive power - sequence components - phasor measurements
• They can be accessed remotely for maintenance and updates
![Page 21: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/21.jpg)
Reclosers
21
Photo courtesy of K. Schneider
• Not needed in transmission or underground distribution systems
Operation
1. Fault occurs 2. Recloser interrupts fault current and remains
open for a time period (1-2 sec) to allow momentary faults to clear
3. Recloser closes back into fault and sees if fault has cleared
4. If fault has cleared, recloser stays closed; otherwise, recloser reopens
5. Number of tries to reconnect is user-configurable (usually 3)
6. After final ‘shot’, recloser locks open 7. Utility crew must locally reset the unit
• Designed to minimize number of customers affected by momentary fault
![Page 22: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/22.jpg)
Sectionalizers
22
Photo courtesy of K. Schneider
Operation
1. Sectionalizer detects overcurrent but cannot interrupt fault
2. It starts counting recloser shots 3. During the second/third recloser shots, the
sectionalizer opens under no load
• Operate on local measurements and with proper coordination of upstream reclosers
Recloser
Sectionalizer #1
Sectionalizer #2
Sectionalizer #3
• Combination of reclosers and sectionalizers is ideal for system with permanent and temporary faults
![Page 23: ECE 5984: Power Distribution System Analysis · distribution systems Operation 1. Fault occurs 2. Recloser interrupts fault current and remains open for a time period (1-2 sec) to](https://reader034.vdocuments.mx/reader034/viewer/2022042611/5f3a0b5c4f45f77130307ac0/html5/thumbnails/23.jpg)
Example: sectionalizer protection
23
• Permanent line to ground fault on line 710-735
• Overcurrent causes recloser 730-709 to open
• Sect. 708-733 detects overcurrent and prepares to open
• Sect.738-711 does not detect overcurrent
• Recloser waits and closes back in; repeats 2-3 times
• Sect. 708-733 opens after 2nd or 3rd shot during no load
• Recloser closes back in, sees no fault, and remains closed
• Customers downstream of 708 report power outage and utility dispatches line crew
• Line crew locates fault; repairs condition; and recloses sect.
• Lateral back to service
Photo courtesy of K. Schneider