Download - Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit
Dosing system for dosing fire fighting foamstandard unit of 0,5 to 24 l/min
Kompletteinheit
Dosing system for dosing fire fighting foamstandard unit of 0,5 to 24 l/min
→ highest foam performance up to 24 l/min at 24 V DC
→ world wide unique foam dosing system with “extern prime function“
→ high precision dosing by using VS flow meter measurement
→ no flushing necessary
→ large extent independent of viscosity
→ easiest handling
→ meet greatest demands by using external gear pumps
→ unique pressure dosing unit with the widest available range in one unit
→ continuously adjustable in ratio water stream to foam.
Dosing system for dosing fire fighting foamstandard unit of 0,5 to 24 l/min
technical data:
foam dosing pump: external gear pump made in bronze with internal parts in stainless steel
drive: 24 V DC / 12 V DC / AC-motors
kind of dosing: volumetric dosing by injecting foam into the fire water stream
flow measurement: fire water AND foam medium
measurement range: fire water: 50 - 2400 l/min // faom: 0.5 – 24 l/min
dosing range: 0,1 - 6 % - infinitely variable
foam: Class A and B; inclusive shear thinning foam
special solution with 100 bar inlet pressure possible
Dosing system for dosing fire fighting foamfurther units – still growing…
Kompletteinheit BILD
Dosing system for dosing fire fighting foaminclusive flow measurement via VS flow meter
available sizes:
dosing range drive power
0,25 - 10 l/min DC-motor 12 VDC 0,55 kW
0,4 - 16 l/min DC-motor 12 VDC 0,55 kW
0,5 - 24 l/min DC-motor 24 VDC 0,75 kW
0,9 - 36 l/min AC-motor with FD / 230 VAC 1,5 kW
Dosing system for dosing fire fighting foamwithout flow measurement
available sizes:
dosing range drive power
12 - 60 l/min AC-motor with FD / 400 VAC 3 kWor hydraulic-motor
34 - 170 l/min hydraulic-motor 15 kW
100 - 500 l/min hydraulic-motor 37 kW
140 - 700 l/min hydraulic-motor 50 kW