Transcript
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    1/71

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS

    by

    G. Martinez-Saucedo

    and

    J. A. Packer

    Department of Civil Engineering, University of Toronto, Canada

    FINAL REPORT TO CIDECT ON PROGRAMME 8G

    CIDECT Report 8G-10/06

    August 2006

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    2/71

    ii

    ABSTRACT

    This Report deals with the structural behaviour and design of concentrically-aligned single

    gusset plate welded connections to the ends of steel hollow section members. Such

    connections are commonly found in diagonal brace members of steel framed buildings and also

    in roof truss web-to-chord member connections. The types of sections considered are circular

    hollow sections and elliptical hollow sections, with the plate either slotted and welded into the

    tube or the tube welded into a slotted plate. In addition, the presence (or lack) of an open slot at

    the end of a slotted tube connection - a fabrication method particularly favoured in North

    America - is evaluated within the scope of this work.

    Under quasi-static loading, the behaviour of the connection has been rigorously studied

    under both axial tension and axial compression loadings, by both large-scale laboratory

    experiments and numerical (finite element) analysis. In addition, an exhaustive review and

    analysis of all prior international work in this field has been made. Non-linear finite element

    models, validated for all 13 laboratory test specimens, formed the basis of an extensive

    parametric study resulting in a further 891 "numerical tests" to supplement the data base of

    experiments by the author and other international researchers. In tension the tube failure modes

    of circumferential fracture (with or without the presence of shear lag) and tear out (or "block

    shear" failure) were clearly identified by both experimental and numerical investigations and theparameters influencing these limit states were thus clarified. As a result, new unified design

    provisions for such connections in tension are presented, which are shown to be a significant

    improvement over current international design provisions. In compression, the tube failure

    mode of local buckling governed throughout the connection study and the influence of the shear

    lag phenomenon - hitherto completely disregarded by all design provisions under compression

    loading - has been highlighted. A new static design method for slotted end connections in

    compression is hence advocated, which is shown to be applicable to circular, elliptical, square

    and rectangular hollow sections. Guidance on the proportioning of the longitudinal fillet welds,

    so that these do not govern the connection capacity, is also presented.

    The above static design recommendations, which now more truly reflect the actual

    connection performance, allow connections to be designed in a more efficient manner.

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    3/71

    iii

    TABLE OF CONTENTS

    ABSTRACT ..............................................................................................................................ii

    TABLE OF CONTENTS ..........................................................................................................iii

    NOTATION................................................................................................................................x

    CHAPTER 1:INTRODUCTION............................................................................................. 1-1

    1.1 Project overview......................................................................................................... 1-2

    CHAPTER 2:LITERATURE REVIEW................................................................................... 2-1

    2.1 The shear lag phenomenon....................................................................................... 2-1

    2.2 Tear-out failure........................................................................................................... 2-4

    2.3 International specifications......................................................................................... 2-6

    2.4 Summary of Chapter 2............................................................................................. 2-10

    CHAPTER 3:EXPERIMENTAL PROGRAM......................................................................... 3-1

    3.1 Material properties ..................................................................................................... 3-1

    3.1.1 Stub column tests.......................................................................................... 3-4

    3.2 Test specimens and instrumentation.......................................................................... 3-6

    3.3 Experimental test results ......................................................................................... 3-10

    3.3.1 Slotted CHS connection - slot end not filled (type A).................................. 3-10

    3.3.2 Slotted CHS connection - slot end filled (with a weld return) (type B) ........ 3-13

    3.3.3 Slotted EHS connection - slot end not filled (gusset plate oriented

    to give a large eccentricity) .........................................................................3-15

    3.3.4 Slotted EHS connection - slot end not filled (gusset plate oriented

    to give small eccentricity)............................................................................ 3-18

    3.3.5 Slotted gusset plate to tube connections in tension.................................... 3-21

    3.3.5.1 Slotted gusset plate to CHS connection (type C)........................................ 3-21

    3.3.5.2 Slotted gusset plate to EHS connection (gusset plate oriented to

    give a large eccentricity) ............................................................................ 3-24

    3.3.6 Connections under compression load......................................................... 3-27

    3.3.6.1 Slotted CHS to gusset plate connection - slot end not filled ....................... 3-28

    3.3.6.2 Slotted gusset plate to CHS connection ..................................................... 3-30

    3.4 Summary of this experimental program................................................................... 3-32

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    4/71

    iv

    CHAPTER 4:EVALUATION OF EXPERIMENTS AGAINST DESIGN PROVISIONS ......... 4-1

    4.1 Experimental program by British Steel (1992) ........................................................... 4-2

    4.2 Experimental program by Korol et al. (1994) ............................................................. 4-3

    4.3 Experimental program by Zhao and Hancock (1995) ................................................ 4-4

    4.4 Experimental program by Cheng et al. (1996)........................................................... 4-74.5 Experimental program by Zhao et al. (1999) ............................................................. 4-8

    4.6 Experimental program by Wilkinson et al. (2002) .................................................... 4-10

    4.7 Experimental program by the Authors ..................................................................... 4-10

    4.8 Experimental program by Ling (2005)...................................................................... 4-12

    4.9 Summary of Chapter 4............................................................................................. 4-14

    CHAPTER 5:FE MODELLING OF CONNECTIONS ........................................................... 5-1

    5.1 Material properties ..................................................................................................... 5-1

    5.2 Connection modelling ................................................................................................ 5-4

    5.2.1 Element selection.......................................................................................... 5-6

    5.2.2 Analysis considerations ............................................................................... 5-6

    5.3 Evaluation of FE models against experimental results .............................................. 5-8

    5.3.1 Slotted CHS connection - slot end not filled (Type A)................................... 5-9

    5.3.2 Slotted CHS connection - slot end filled (weld return) (Type B).................. 5-12

    5.3.3 Slotted EHS connection - slot end not filled (gusset plate oriented

    to give a large eccentricity) .........................................................................5-16

    5.3.4 Slotted EHS connection - slot end not filled (gusset plate oriented

    to give small eccentricity)............................................................................ 5-20

    5.3.5 Slotted gusset plate to tube connections in tension.................................... 5-23

    5.3.5.1 Slotted gusset plate to CHS connection (Type C)....................................... 5-23

    5.3.5.2 Slotted gusset plate to EHS (gusset plate oriented

    to give a large eccentricity) .........................................................................5-26

    5.3.6 Connections under compression load......................................................... 5-30

    5.3.6.1 Slotted CHS to gusset plate connection - slot end not filled ....................... 5-30

    5.3.6.2 Slotted gusset plate to CHS connection ..................................................... 5-32

    5.4 Summary of Chapter 5............................................................................................. 5-35

    CHAPTER 6:PARAMETRIC FINITE ELEMENT ANALYSIS............................................... 6-1

    6.1 Parametric analysis results of slotted CHS connection - slot end not filled ............... 6-1

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    5/71

    v

    6.2 Parametric analysis results of slotted CHS connection -

    slot end filled (weld return)......................................................................................... 6-7

    6.3 Parametric analysis results of slotted EHS connection -

    slot end not filled (gusset plate oriented to give a large eccentricity)....................... 6-11

    6.4 Parametric analysis results of slotted EHS connection -

    slot end not filled (gusset plate oriented to give small eccentricity) .........................6-14

    6.5 Slotted gusset plate to tube connection in tension...................................................6-17

    6.5.1 Parametric analysis results of slotted gusset plate to

    CHS connection.......................................................................................... 6-17

    6.5.2 Parametric analysis results of slotted gusset plate to

    EHS connection (gusset plate oriented to give a large eccentricity)........... 6-23

    6.6 Connections under compression load......................................................................6-29

    6.6.1 Parametric analysis results of slotted CHS connection -

    slot end not filled......................................................................................... 6-29

    6.6.2 Parametric analysis results of slotted gusset plate to

    CHS connection.......................................................................................... 6-32

    6.7 Weld design ............................................................................................................. 6-35

    6.8 Summary of Chapter 6............................................................................................. 6-38

    CHAPTER 7: ANALYSIS OF FE AND EXPERIMENTAL RESULTS................................... 7-1

    7.1 CHS connections in tension - CF failure.................................................................... 7-1

    7.1.1 Shear lag equations suggested for CSA design provision format................. 7-1

    7.1.1.1 Equation suggested for slotted CHS to gusset plate connections ................ 7-1

    7.1.1.2 Equation suggested for slotted gusset plate to CHS connections

    based on ultimate strength............................................................................ 7-3

    7.1.1.3 Equation suggested for slotted gusset plate connections based on

    deformation limit (0.03D)............................................................................... 7-5

    7.1.2 Shear lag equations suggested for AISC design provision format................ 7-6

    7.1.2.1 Equation suggested for slotted CHS to gusset plate connections ................ 7-7

    7.1.2.2 Equation suggested for slotted gusset plate to CHS connections

    based on ultimate strength............................................................................ 7-8

    7.1.2.3 Equation suggested for slotted gusset plate connections based on

    deformation limit (0.03D)............................................................................... 7-9

    7.2 EHS connections in tension - CF failure.................................................................. 7-11

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    6/71

    vi

    7.2.1 Shear lag equations suggested for CSA design provision format............... 7-11

    7.2.1.1 Equation suggested for slotted EHS to gusset plate connections .............. 7-11

    7.2.1.2 Equation suggested for slotted gusset plate to EHS connections

    based on ultimate strength.......................................................................... 7-12

    7.2.1.3 Equation suggested for slotted gusset plate connections based on

    deformation limit (0.03D2) ........................................................................... 7-14

    7.2.2 Shear lag equations suggested for AISC design provision format.............. 7-15

    7.2.2.1 Equations suggested for slotted EHS to gusset plate connections............. 7-15

    7.2.2.2 Equations suggested for slotted gusset plate to EHS connections

    based on ultimate strength.......................................................................... 7-17

    7.2.2.3 Equation suggested for slotted gusset plate to EHS connections

    based on deformation limit (0.03D2) ...........................................................7-18

    7.3 CHS and EHS connections in tension - TO failure .................................................. 7-19

    7.4 CHS connections in compression............................................................................ 7-29

    7.4.1 Equation suggested for slotted CHS to gusset plate connections

    (under compression loading) ...................................................................... 7-29

    7.4.2 Equation suggested for slotted gusset plate connections

    (under compression loading) ...................................................................... 7-30

    7.5 Evaluation of recommended equations against experimental data ......................... 7-31

    7.5.1 Experimental program by British Steel (1992) ............................................ 7-337.5.2 Experimental program by Korol (1994) ....................................................... 7-34

    7.5.3 Experimental program by Cheng et al. (1996)............................................ 7-34

    7.5.4 Experimental program by the Authors ........................................................ 7-35

    7.6 Derivation of reduction (resistance) factors for the recommended equations.......... 7-37

    7.6.1 Reduction factors for CHS connections in tension - CF failure................... 7-37

    7.6.1.1 Reduction factors for suggested equations for slotted

    CHS connections (CSA design provision format) ....................................... 7-37

    7.6.1.2 Reduction factors for suggested equations for slotted gusset plate to

    CHS connections based on ultimate strength

    (CSA design provision format).................................................................... 7-38

    7.6.1.3 Reduction factors for suggested equations for slotted gusset plate to

    CHS connections based on deformation limit

    (CSA design provision format).................................................................... 7-39

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    7/71

    vii

    7.6.1.4 Reduction factors for suggested equations for

    slotted CHS connections (AISC design provision format)........................... 7-39

    7.6.1.5 Reduction factors for suggested equations for slotted gusset plate to

    CHS connections based on ultimate strength

    (AISC design provision format)................................................................... 7-40

    7.6.1.6 Reduction factors for suggested equations for slotted gusset plate to

    CHS connections based on deformation limit

    (AISC design provision format)................................................................... 7-40

    7.6.2 Reduction factors for EHS connections in tension - CF failure................... 7-41

    7.6.2.1 Reduction factors for suggested equations for

    slotted EHS connections (CSA design provision format)............................ 7-41

    7.6.2.2 Reduction factors for suggested equations for slotted gusset plate to

    EHS connections based on ultimate strength

    (CSA design provision format).................................................................... 7-41

    7.6.2.3 Reduction factors for suggested equations for slotted gusset plate to

    EHS connections based on deformation limit

    (CSA design provision format).................................................................... 7-41

    7.6.2.4 Reduction factors for suggested equations for slotted EHS connections (AISC

    design provision format).............................................................................. 7-42

    7.6.2.5 Reduction factors for suggested equations for slotted gusset plate to

    EHS connections based on ultimate strength

    (AISC design provision format)................................................................... 7-42

    7.6.2.6 Reduction factors for suggested equation for slotted gusset plate to

    EHS connections based on deformation limit

    (AISC design provision format)................................................................... 7-43

    7.6.3 Reduction factors for CHS and EHS connection in tension - TO failure ..... 7-44

    7.6.3.1 Reduction factors for slotted CHS connections - TO failure ....................... 7-44

    7.6.3.2 Reduction factors for slotted gusset plate to CHS connections -

    TO failure .................................................................................................... 7-44

    7.6.3.3 Reduction factors for slotted EHS connections - TO failure........................ 7-44

    7.6.3.4 Reduction factors for slotted gusset plate to EHS connections -

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    8/71

    viii

    TO failure .................................................................................................... 7-45

    7.6.4 Reduction factors for CHS connections in compression............................. 7-45

    7.6.4.1 Reduction factors for slotted CHS connections in compression ................. 7-45

    7.6.4.2 Reduction factors for slotted gusset plate to CHS connections

    in compression............................................................................................ 7-46

    7.7 Summary of Chapter 7- recommended static design methods................................ 7-46

    7.7.1 Recommended static design method for CHS connections in tension ....... 7-47

    7.7.2 Recommended static design method for EHS connections in tension ....... 7-49

    7.7.3 Recommended static design method for CHS connections in compression7-50

    CHAPTER 8:CONCLUSIONS AND RECOMMENDATIONS FOR FURTHER RESEARCH8-1

    8.1 Overview.................................................................................................................... 8-1

    8.2 Recommended static design methods...................................................................... 8-2

    8.2.1 Recommended static design method for CHS connections in tension ......... 8-2

    8.2.2 Recommended static design method for EHS connections in tension ......... 8-4

    8.2.3 Recommended static design method for CHS connections in compression 8-5

    8.3 Design recommendation for seismic applications...................................................... 8-6

    8.4 Recommendations for further research ..................................................................... 8-6

    CHAPTER 9:REFERENCES................................................................................................ 9-1

    APPENDIX A: EXPERIMENTAL PROGRAM ......................................................................A-1

    A.1 Slotted end connections to CHS ................................................................................ A-1

    A.2 Slotted end connection to EHS .................................................................................. A-3

    APPENDIX B: EVALUATION OF EXPERIMENTS ..............................................................B-1

    B.1 Experimental program by British Steel (1992) ...........................................................B-1

    B.2 Experimental program by Korol el al. (1994) .............................................................B-2

    B.3 Experimental program by Zhao and Hancock (1995) ................................................B-3

    B.4 Experimental program by Cheng et al. (1996) ...........................................................B-5

    B.5 Experimental program by Zhao et al. (1999) .............................................................B-6

    B.6 Experimental program by the Authors .......................................................................B-8

    B.7 Experimental program by Ling (2005)........................................................................B-9

    APPENDIX C: STRAIN READINGS ....................................................................................C-1

    C.1 Connections under tension ........................................................................................C-1

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    9/71

    ix

    C.1.1 Slotted CHS connections - slot end not filled (A1 and A2).........................................C-1

    C.1.2 Slotted CHS connections - slot end filled (weld return) (B1 and B2) .........................C-3

    C.1.3 Slotted EHS connections - slot end not filled (E1 and E2).........................................C-5

    C.1.4 Slotted EHS connections - slot end not filled (E5) .....................................................C-7

    C.1.5 Slotted gusset plate to CHS connection (C1 and C2)................................................C-8

    C.1.6 Slotted gusset plate to EHS connection (E3 and E4) ..............................................C-10

    C.2 Connections under compression .............................................................................C-12

    C.2.1 Slotted CHS to gusset plate connection - slot end not filled (A3C)..........................C-12

    C.2.2 Slotted gusset plate to CHS connection (C3C)........................................................C-13

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    10/71

    x

    NOTATION

    Ag = gross cross-sectional area of hollow section

    Agt = gross area in tension for block failure

    Agv = gross area in shear for block failure

    al = weld leg length (size)

    An = net cross-sectional area of hollow section

    A'ne = effective net cross-sectional area of hollow section

    Ant = net area in tension for block failure

    Anv = net area in shear for block failure

    Aw = area of effective weld throat

    B = width of overlapped gusset plate

    b = overall width of RHS and SHS, measured 90 degrees to the plane of the connection

    CSC = compressive strength of stub column

    CHS = Circular Hollow Section

    D = outside diameter of CHS

    D1 = larger dimension of EHS

    D2 = smaller dimension of EHS

    Davg = average between larger and smaller dimension of EHS

    D/t = ratio between outside diameter and wall thickness of CHS

    E = modulus of elasticity

    EHS = Elliptical Hollow Section

    Fy

    = yield tensile stress

    Fu = ultimate tensile stress

    h = overall height of RHS and SHS, measured in the plane of the connection

    HAZ = Heat Affected Zone

    HSS = Hollow Structural Section

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    11/71

    xi

    K = effective length factor

    LVDT = Linear Variable Differential Transformer

    Lw = weld length

    Lw

    /w = ratio between weld length and distance between welds

    Lw/D = ratio between weld length and outside diameter of CHS

    lsl = length of slot in hollow section

    Nu = calculated connection strength according to design provisions

    Nux = measured connection strength

    NuFE = connection strength from FE analysis

    NuFE-D= connection strength from FE analysis based on distortion limit

    RHS = Rectangular Hollow Section

    Rt = tension area mean stress correction factor

    Rv = shear area mean stress correction factor

    SHS = Square Hollow Section

    t = wall thickness of CHS

    tp = thickness of gusset plate

    Tr = factored tensile resistance

    tsl = width of slot in CHS

    T-T= uniaxial true stress - true strain curve

    U = reduction coefficient for shear lag in net section fracture calculation

    Ubs = reduction factor for non-uniform stress in block shear

    Vr = factored shear resistance

    VR = coefficient of variation

    w = distance between the welds, measured around the perimeter of the CHS

    wp = width of gusset plate

    = eccentricityx

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    12/71

    xii

    = eccentricity reduced by half of flange-plate thickness (= - tp /2)

    /Lw = ratio between the eccentricity and weld length

    /Lw= ratio between the reduced eccentricity and weld length

    z = longitudinal distance between strain gauges

    = safety index or reliability index

    M0 = Eurocode 3 partial safety factor when neither buckling phenomena nor ultimate

    resistance in tension is under consideration (= 1.0)

    M2 = Eurocode 3 partial safety factor when ultimate resistance in tension is under

    consideration (= 1.25)

    u = ultimate strain at rupture

    ef = equivalent fracture strain

    = mean actual-to-predicted ratio

    = resistance factor

    x' x

    x

    x'

    m

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    13/71

    1-1

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH1: INTRODUCCION

    CHAPTER 1: INTRODUCTION

    Circular hollow sections (CHS) have gained in popularity in recent years, particularly for

    architecturally exposed structural steel. Architects appreciate the clear form of CHS as well as

    their excellent structural properties in compression and torsion. In order to take full advantage of

    these properties, the complete tube cross-section should ideally be engaged at the connection.

    However, the feasibility of doing this is determined by the shape of the elements merging at the

    connection, which may result in a complicated task for detailing and fabrication. As a result, the

    use of a simplified connection detail will always be desirable whenever possible.

    Gusset plate connections represent one of the easiest methods to connect CHS used as

    web members in roof trusses and brace members in buildings. During the fabrication of these

    connections, the gusset plate or the CHS can be slotted resulting in several possible fabrication

    details. The application of either detail will depend on existing tolerances during the process of

    fabrication and erection of the structure. Despite these connection details providing the simplest

    manner for connecting CHS, it is important to recognize that an incorrect understanding of their

    behaviour may result in their failure or an expensive conservative design. As a consequence of

    only part of the CHS cross-section being connected, an uneven stress distribution around the

    tube circumference always occurs during the load transfer at the connection. Shear lag (see

    Figure 1.1) leads to stress peaks at the beginning of the weld which may result in connection

    failure by a circumferential failure (CF) mode. Moreover, a tear-out (or block shear) failure

    (TO) may also occur under tension loading.

    Beginning of theweld

    Figure 1.1 Shear lag in slotted CHS connection

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    14/71

    1-2

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH1: INTRODUCCION

    Despite both these limit states being addressed in current North American design

    provisions (AISC 2005 and CSA 2001), it has been found that the predicted connection strength

    (in the parameter range when CF is governing failure mode) will always differ as these two

    design provisions use dissimilar methods to account for this phenomenon. Although it is

    expected that these AISC and CSA design methods will always predict conservative connection

    capacities when CF governs, it has been found that the number of studies (specifically in slotted

    end connections to hollow sections) is limited to verify the accuracy and validity limits for each

    method. Moreover, the model currently used in design provisions (AISC 2005, CEN 2005 and

    CSA 2001) to account for TO failure, which was initially developed for bolted connections, lacks

    studies verifying its accuracy and validity limits for these connection types. In a similar manner

    to tension loading, an uneven stress distribution can be expected at the connection under

    compression loading. However, it has been found that this phenomenon is completely

    disregarded by design provisions, despite the fact that it may induce tube local buckling at the

    beginning of the welds.

    1.1 Project overview

    This Report is directed to clarify the behaviour of slotted end connections fabricated with

    CHS and Elliptical Hollow Sections (EHS), their possible failure mechanisms and the relation of

    these failure modes to the connection geometrical dimensions, under tension and compression

    loading. In order to verify the accuracy of models currently used by design provisions, these are

    compared against available experimental data from previous studies and data from an

    experimental program undertaken at the University of Toronto. Results from these comparisons

    revealed the deficiency of these provisions to correctly predict the connection strength and

    governing failure mechanisms. A further parametric analysis based on finite element models of

    CHS and EHS connections has provided information on the behaviour of these connections and

    also provided further evidence of the imprecision of current design provisions. Therefore, a new

    comprehensive static design method is recommended here which also illustrates the possibility

    of effectively diminishing the influence of shear lag in these connections.

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    15/71

    2-1

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    CHAPTER 2: LITERATURE REVIEW

    The use of slotted end connections to hollow sections is very popular nowadays.

    However, the design methods against the most frequent failure modes such as circumferential

    tensile fracture (CF) of the HSS (see Figure 2.2) and tear-out (TO) failure along the weld (see

    Figure 2.3), seem to still require further attention. During the load transfer from the tube to the

    gusset plate, a nonuniform strain distribution takes place in the tube cross-section as the

    unconnected material is less able to participate in the load transfer. This phenomenon, known

    as Shear Lag, creates a high strain concentration at the weld region which eventually can

    trigger the fracture of the tube material there. Moreover, the propagation of this crack (defining a

    typical failure mode) and the connection strength are strongly influenced by the weld length

    (Lw).

    2.1 The shear lag phenomenon

    Since the first model to account for the shear lag phenomenon was proposed by Chesson

    and Munse (1963), it has been included in several design specifications. Initially it was applied

    to riveted and bolted connections. Afterwards, the same model was utilized for the design of

    welded connections. Even though this phenomenon has been studied extensively for open

    structural sections, studies from Easterling and Giroux (1993) and Kirkham and Miller (2000)

    Figure 2.2 Circumferential tensile fracture Figure 2.3 Tear-out failure

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    16/71

    2-2

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    have revealed that existing design approaches are overly conservative and that further

    research may be required. In addition, this model has been applied to tubular connections.

    However, the research for these connection types is relatively recent and limited in scope.

    To allow for shear lag on connections fabricated with Hollow Structural Sections (HSS),

    Packer and Henderson (1992) proposed that the distance between the welds (w) be measured

    along the developed perimeter of the HSS (see Figure 2.4). In addition, they also suggested an

    efficiency coefficient for connections with Lw/w ratios less than unit. At this time, the use of small

    ratios was not considered for CAN/CSA-S16.1-M89 (CSA 1989) since it was estimated that the

    weld was critical for Lw/w ratios less than one.

    A specific study of shear lag-induced fracture in tubular connections started in early 1990swhen British Steel (1992) studied gusset plate connections to circular hollow sections (CHS),

    square hollow sections (SHS) and rectangular hollow sections (RHS) under tension and

    compression loading. An experimental program on slotted SHS and RHS to gusset plate

    connections was undertaken by Korol et al. (1994). In this program, a total of 18 specimens with

    Lw/w ratios ranging from 0.40 to 1.00 were tested. Their results confirmed that a net section

    failure can occur in connections with ratios Lw/w < 1.00. Moreover, a ratio of Lw/w = 0.60 was

    proposed as a lower limit for the net section failure mode. A FE analysis of these connections

    was made considering only their elastic response, hence the FE models could not predict the

    failure mode. Based on these models, a further parametric analysis determined the influence

    that geometrical ratios have on the shear lag phenomenon; the Lw/w ratio was shown to have

    the major influence and tube effective depth-to-width ratio a minor influence. Finally, the results

    indicated the need for variable shear lag factors for slotted SHS and RHS connections.

    Figure 2.4 Important dimensions in slotted end connections

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    17/71

    2-3

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    Girard et al. (1995) generated a FE model of a connection between a SHS and a gusset

    plate. Even though this FE model exhibited some limitations, their results displayed differences

    with the equations in CAN/CSA-S16.1-M89 (CSA 1989). Cheng et al. (1996) studied the

    phenomenon in CHS, undertaking an experimental program and a FE analysis of these

    connections. A total of nine connections were tested, these connections were fabricated with a

    slotted tube and, except for one, all had a weld return. The results showed the inaccuracy of the

    shear lag factors in CAN/CSA-S16.1-94 (CSA 1994) for this type of connection. Additionally, the

    results for the connection with no weld return always presented an uneven strain distribution at

    the slotted end. For the same CAN/CSA-S16.1-94 (CSA 1994), Korol (1996) reached a similar

    conclusion for slotted gusset plate connections fabricated with SHS and RHS. Cheng et al.

    (1998) and Cheng and Kulak (2000) suggested that the reduction in the effective net area would

    be eliminated for CHS connections if a minimum weld length (Lw) of 1.3 times the tube diameter

    is provided.

    Experimental programs in gusset plates slotted into RHS were also undertaken by Zhao

    and Hancock (1995), Zhao et al. (1999) and Wilkinson et al. (2002). Although the failure mode

    in the latter was not directly related to the shear lag effect, the results suggested the need to

    verify the factors to account for shear lag. Recently, CHS connections with very high strength

    tubes have been studied by Ling (2005), resulting in a design method which considers the heat

    affected zone. However, due to the characteristics of the tube material used during this

    experimental program these results may not be suitable for regular grade HSS connections.

    Humphries and Birkemoe (2004) studied primarly double channel to gusset plate connections

    but these were compared with RHS to gusset plate connections. The results showed that the

    channels had a better behaviour than the RHS as they were able to deform reducing the

    eccentricity ( ), thus increasing the connection effiency. This study also pointed out the

    influence that the weld leg size (al) has on the connection strength, as an increase in this was

    associated with an enhancement of the connection efficiency.

    Although these research studies have contributed information related to the influence that

    shear lag has in tubular connections, they have also showed the need to continue with more

    definitive studies in order to provide design provisions with formulae that accurately reflects this

    phenomenon.

    x

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    18/71

    2-4

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    2.2 Tear-out failure

    In general, the research on tear-out failure or block failure has been mainly aimed at

    bolted connections, using gusset plates, coped beams or angles. The first model for tear-out

    failure (based on tests of coped beam connections) was proposed by Birkemoe and Gilmor

    (1978) and was eventually included in the AISC specification (1978). This model calculates the

    connection resistance by adding the shear resistance of the shear area and the tensile

    resistance of the net tensile area. Since then, several investigations have been undertaken on

    different bolted connections types.

    In order to verify the accuracy of the AISC specification (1978), Yura et al. (1982) tested

    twelve beam web shear connections. During these tests, several parameters such as: the edge

    distance, standard and slotted holes, coped beams, uncoped beams and bolt arrangement

    were studied. The results revealed a decrease in the connection capacity (approximately 20%)

    when slotted holes were used, and the use of two rows of bolts clustered at the top of the web

    produced a lower safety factor than that expected. Finally, for a connection with a single row of

    bolts, a recommendation to calculate the connection capacity as the sum of the bolts single

    capacity rather than a group capacity was made. In a further study (Ricles and Yura 1983), a

    finite element analysis of these connections (considering only the connection elastic response)

    showed a uneven stress distribution along the vertical plane at the cope. These results

    disagreed with an ideal stress distribution calculated by simple beam theory. In general, fracture

    initially started at the tension region where an uneven stress distribution was taking place and it

    was combined with a substantial material yielding along the shear plane. Based on these

    results, a new block shear model (with a triangular stress distribution on the tension region) was

    proposed for double row bolted connections. Hardash and Bjorhovde (1985) evaluated the

    application of the block-shear concept in gusset plates connections via the testing of 28

    specimens. The test specimens were fabricated with two lines of bolts with various bolt rows,

    pitch spacing and bolt diameters. During these tests, the dominating failure mode corresponded

    to the attainment of the ultimate stress along the net area in tension (at the last row of bolts) and

    yielding of the gross area in shear (outside of the line of the bolts). In addition to this, the data

    from experimental programs at the University of Illinois and the University of Alberta were

    combined with these results to develop a new block shear model. In general, this new model

    followed the original block failure model. Nevertheless, it included several new factors to

    calculate the ultimate resistance of the connection which made its use difficult.

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    19/71

    2-5

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    Epstein (1992) undertook an experimental program to study block shear failure in angles,

    with a total of 38 angle connection tests. These results showed variations with the values

    recommended by AISC design provisions (1986, 1989) at that time. These differences were

    mainly associated with the effect that the unconnected leg eccentricity had over the connection

    behavior, modifying the failure mechanism. Gross et al. (1995) tested 13 angle connections

    fabricated with a single line of bolts and steel grades A-36 and A588. In general, the results

    showed good correlation with AISC design provisions (1989, 1994) based on agreement with

    the failure load. However, an inconsistency was observed between the failure mechanism

    predicted by design provisions and experimental test. Based on data published in previous

    experimental programs, Cunningham et al. (1995) suggested a model to predict block shear

    failure in connections fabricated with angles and bolts. Orbison et al. (1999) tested several

    angles, WT and W sections which failed in block shear (a total of 17 specimens). The failure

    mechanism observed during the tests consisted of a fracture at the tension area which was

    combined with a considerable inelastic deformation along the gross shear area. Even though

    the predicted connection capacity by the (then-current) design provision (AISC 1994) resulted in

    conservative values, the expected failure mechanism disagreed with the tests results.

    Additionally, several factors such as: low ductility, hole fabrication (punched or drilled) and large

    in plane and out-of-plane eccentricities were found to have an influence on the connection

    capacity. Finally, a further study of these factors was suggested since they were not considered

    in design provisions. Swanson and Leon (2000) tested 48 T-stub specimens under monotonic

    and cyclic loading. From all these test specimens, only one failed by block failure (this specimen

    was tested under cyclic loading). For this test specimen, the predicted failure mechanism (AISC

    1994) did not coincide with the failure observed during the test. Aalberg and Larsen (2000)

    tested splice plates, beam web connections loaded in shear and beams connections with a

    coped end using high strength steels. The results were compared with design provisions such

    as: Eurocode (CEN 1992), CSA (1989) and AISC (1994). In general, an important decrease in

    the connection ductility was observed as a result of the use of these steel types and the

    importance of limiting the deformation of these connections was addressed. For block shear

    failure, only the CSA (1989) method was found to be suitable for high strength steels. A review

    of the rules for block shear design (AISC 1999) by Kulak and Grondin (2001) suggested that

    these may be conservative for gusset plates, acceptable for angles and non-conservative for

    coped beams. This study recommended that further research of this failure mode was required.

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    20/71

    2-6

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    In addition to these experimental programs, several studies have been undertaken with

    the assistance of finite element models by Epstein and Chamarajanagar (1996), Epstein and

    McGinnis (2000), Barth et al. (2002) and Topkaya (2004). In this last study, new models to

    calculate the tear out failure have been suggested.

    As result of these research programs, the governing failure criteria defining the block

    shear as well as resistance factors have experienced several modifications in existing design

    provisions (Geschwindner, 2004). However, the initial model (suggested by Birkemoe and

    Gilmor) which adds the resistances in tension and shear continues in use. Nowadays, the new

    trend to design by block shear follows this model, but with the use of several reduction factors.

    As an example of this, the AISC design provision (2005) has suggested a reduction factor (Ubs)

    to consider the uneven stress distribution that can be found in coped beams. Finally, a unified

    equation suitable for all types of connections has been recently proposed by Driver et al. (2006),

    wherein the initial model is used but several factors are applied depending on the connection

    type.

    2.3 International specifications

    When the capacity of a tension member is governed by the limit state of tensile fracture

    affected by shear lag, several values can be calculated from current design provisions as they

    do exhibit differences. In general, these provisions consider the non-uniform stress distribution

    caused by shear lag by including an efficiency factor (U). This factor decreases the tube net

    area (An) at the connection to an effective net area (Aeor A'ne).

    Ae= An U (as in AISC 2000, 2005) (2-1)

    A'ne= An U (as in CSA 2001) (2-2)

    This effective net are is then used to calculate the connection strength. In order to

    calculate this efficiency factor (U), two general methods are currently most common. The first

    method can be found in American specifications (AISC 2000, 2005), where the connection

    eccentricity ( ) is compared with the weld length (Lw), as proposed by Cheeson and Munse

    (1963) to allow for the shear lag phenomenon in riveted and bolted connections. Specifications

    using this approach are summarized in Table 2.1. By this method:

    x

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    21/71

    2-7

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    where for CHS; (2-3)

    and for EHS (see Figure 2.5). (2-4)

    Equation 2-4considers that the gusset plate is aligned with the dimension D2(see Figure

    2.5). When the gusset plate orientation is parallel to the dimension D1, the dimension D12

    should be replaced by D22. The conventional interpretation of has been the measurement

    from the tube centroidal axis. However, when a thick gusset plate is utilized. It may be feasible

    to consider a reduced , which is the distance from the gusset plate surface to the centre of

    gravity of the half tube as shown in Figure 2.4.

    The second method compares the circumferential distance between the welds (w) with

    the weld length (Lw). Here the efficiency factor (U) is determined by values assigned to the ratio

    Lw/w (see Table 2.1). This method can be found in the Canadian specification (CSA 1994,

    2001) as well as in the design guide for hollow structural sections by Packer and Henderson

    (1997). Moreover, for slotted connections to hollow sections the distance w equals half of the

    HSS circumference minus the gusset plate thickness (tp) or the slot width (tsl). Eurocode3 (CEN

    2005) only considers the effect of shear lag on bolted connections using angles connected by

    U 1x

    Lw------=

    xD

    ----=

    x2

    3------

    D12 2D1D2+

    D1 D2+------------------------------=

    x

    x'

    Figure 2.5 Eccentricity of top half, for EHS.x

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    22/71

    2-8

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    one leg and other unsymmetrically connected tension members. Eurocode3 (2005) hence is not

    listed in Table 2.1.

    Tr= AeFu(AISC Specification, = 0.75) or Tr= 0.85 A'neFu (CSA Specification, = 0.9).

    For block shear failure, the connection resistance is calculated by adding the portion of

    the load transferred as tension load, Tr, and the portion of load transferred as shear load, Vr.

    The different national/regional design specifications (AISC, CSA, Eurocode) either use the

    gross or net area for the calculation of Trand Vr(see Table 2.2). In welded connections, the

    gross area becomes equal to the net area for the calculation or T rand Vrdue the absence of

    bolt holes. For the calculation of the shear load, the material strength is reduced to 0.60 Fyor Fy

    Table 2.1 Shear lag design provisions for round (and elliptical) hollow sections

    Specification or design

    guide

    Effective net

    areaShear lag coefficients

    Range of

    validity

    AISC (1999):

    LRFD Specification for

    Structural Steel Buildings

    Ae= An U

    with (for CHS)

    (EHS, see Figure 2.5)

    no restric-

    tionsAISC (2000):

    LRFD Specification for

    Steel Hollow Structural

    Sections

    AISC (2005):Specification for Structural

    Steel Buildings

    U = 1- for

    U = 1 for (only CHS)

    CSA (1994):

    Limit States Design of

    Steel Structures

    A'ne= An U

    U = 1.0 for

    U = 0.87 for 2.0 >

    U = 0.75 for 1.5 >

    CSA (2001):

    Limit States Design of

    Steel Structures

    U = 1.0 for

    U = 0.5 + 0.25 for 2.0>

    U = 0.75 for < 1.0

    no restric-

    tions

    Packer and Henderson

    (1997):

    Hollow Structural Section

    Connections and Trusses -

    A Design Guide

    U = 1.0 for

    U = 0.87 for 2.0 >

    U = 0.75 for 1.5 >

    U = 0.62 for 1.0 >

    shear lag

    not critical

    for

    < 0.6

    U 1x

    Lw------ 0.90=

    xD

    ----=

    x2

    3------

    D12

    2D1D2+

    D1 D2+------------------------------=

    xLw------ 1.3D Lw> D

    Lw 1.3D

    Lw D

    Lw w 2.0

    Lw w 1.5

    Lw w 1.0

    Lw w

    Lw w 2.0

    Lw w Lw w 1.0

    Lw w Lw w

    Lw w 1.0

    Lw w 1.5

    Lw w 1.0

    Lw w 0.6Lw w

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    23/71

    2-9

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    / . The factor Ubs used in the American specification (AISC 2005) has been introduced to

    account for the stress distribution that can be found in coped beams, where Ubs=0.5 is

    recommended. In gusset plate connections Ubsis taken equal to unity.

    The Canadian specification (CSA 2001) uses a separate design formula for coped beams

    but it also results in the same reduction factor as the American specification. It is worthwhile

    noting that the latest Canadian and American specifications, while having essentially the same

    model for the block shear limit state, result in considerably different safety levels due to their

    different resistance factors ( ), as shown in Table 2.2(although the Canadian value is currently

    under review). This is not the case for the shear lag design provisions (Table 2.1), where

    .

    a)Design rule for bolted connections differs slightly.

    Table 2.2 Block shear design provisions

    Specification or design guide Block shear strength

    AISC (1999):

    LRFD Specification for Struc-

    tural Steel Buildings

    When AntFu 0.6Anv Fu:

    Tr + Vr = [AntFu + 0.6AgvFy] [AntFu + 0.6 Anv Fu]

    When Ant Fu< 0.6Anv Fu:

    Tr + Vr = [AgtFy+ 0.6 AnvFu] [Ant Fu+ 0.6Anv Fu]

    with = 0.75

    AISC (2000):

    LRFD Specification for Steel

    Hollow Structural Sections

    AISC (2005):

    Specification for Structural Steel

    Buildings

    Tr + Vr = UbsAnt Fu + 0.6 AgvFy UbsAnt Fu + 0.6 Anv Fu

    with = 0.75 and Ubs= 1

    CSA (2001):

    Limit States Design of Steel

    Structures

    Tr + Vr = Ant Fu + 0.6 Agv Fy Ant Fu+ 0.6 Anv Fu

    with = 0.9

    Eurocode (CEN 2005):

    Design of Steel Structures

    - General Rules - Part 1-8:

    Design of Jointsa)

    Tr + Vr = Ant Fu Anv Fy

    = 1.0 and = 1.25

    3

    0.9( ) 0.85( ) 0.75

    2

    1

    M 3

    11

    0M+

    0M 2M

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    24/71

    2-10

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH2: LITERATURE REVIEW

    2.4 Summary of Chapter 2

    As has been exposed throughout this chapter, research on TO failure has been mainly

    focused on several types of bolted connections. As a result of this, the first model suggested to

    predict the connection strength has experienced several modifications throughout the years.

    Nevertheless, the accuracy of this model still seems to need further attention or verification

    (especially for welded tubular connections).

    To account for shear lag (inducing a CF) in tubular connections, two general approaches

    are prevalent nowadays in current design provisions. However, the accuracy of these models

    has not been totally verified for slotted end connections to CHS or EHS.

    In order to asses the accuracy and suitability of the models recommended in current

    design provisions (which are suggested for the TO failure limit state and to account for shear lag

    phenomenon), these models are compared against the results from an experimental program

    carried out at the University of Toronto (Chapter 3 of this Report) and other relevant research

    programs undertaken on tubular connections (Chapter 4 of this Report).

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    25/71

    3-1

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    CHAPTER 3: EXPERIMENTAL PROGRAM

    An experimental program has been undertaken at the University of Toronto on slotted end

    connections to hollow sections (CHS and EHS). The objective of this study was to identify the

    influence of parameters such as: the weld length (Lw), the eccentricity of the connection ( ), the

    gusset plate orientation (for the EHS) and fabrication detail on the connection strength. In

    general, these parameters have been shown to affect the shear lag phenomenon in previous

    experimental programs and the calculated connection strength by current design codes is

    based on these parameters. As part of this program, a total of 13 connections were fabricated

    and tested under quasi-static tension and compression loading. A description of the

    connections, the material properties, the testing arrangement and results from the tests are

    given in this chapter.

    3.1 Material properties

    For the fabrication of the connections, a CHS with a nominal size of 168 x 4.8mm was

    used and it was cold-formed Class C material with a minimum specified yield stress of 350MPa

    (CSA 2004). An EHS with a nominal size of 220x110x6.3mm was used and it was hot-finished

    with a minimum specified yield stress of 355MPa (EN 10210-1, CEN 1994). Plates with 25mm

    and 32mm thickness were required for the fabrication of the gusset plates; these plates had a

    minimum specified yield stress of 300MPa (CSA 2004). A group of test coupons was fabricated

    from tubes and plates in order to determine their material properties. Seven test coupons were

    taken from the CHS with two of them cut from the Heat Affected Zone (HAZ). A 25mm plate was

    used in the fabrication of the CHS connections and two test coupons were cut from this plate.

    Four test coupons were cut from the EHS and three 32mm plates were used in the fabrication of

    these connections so a total of six coupons were tested from these plates. The size and location

    of these coupons were made according to ASTM (2003).

    During testing, the engineering stress-strain relationship was acquired before the coupontest developed a neck. Afterwards, the clip gauge was removed from the test coupon. In some

    test coupons from the CHS, it was possible to acquire information beyond the formation of the

    neck but eventually the clip gauge had to be removed. In all the cases, the load and maximum

    elongation at rupture were determined for each coupon test. The engineering stress-strain

    curves from the materials are shown in Figures 3.1 to 3.4 and their measured material

    x

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    26/71

    3-2

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    properties are given in Table 3.1. Additional information from the tube and gusset plate material

    is given in Appendix A.

    Figure 3.1 Coupon tests for CHS

    Figure 3.2 Coupon tests for 25 mm plate

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    27/71

    3-3

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    Figure 3.3 Coupon tests for EHS

    Figure 3.4 Coupon tests for 32 mm plate

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    28/71

    3-4

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    a) Properties determined by the average measurements from several tensile coupon tests.b) Using the 0.2% offset method, as material was cold-formed.

    3.1.1 Stub column tests

    In addition to the test coupons, a stub column test was performed on both the CHS and

    the EHS to determine their properties under compression load. The specimen size and the

    testing procedure were as recommended by SSRC (Galambos 1998). Before testing, four strain

    gauges were placed around the tubes circumference at the mid-height (see Figure 3.5). This

    allowed the generation of an average -relationships for the tube materials. Results from the

    tests are given in Table 3.2

    a)Measured area obtained by weighing a tube segment and using a density of 7850 kg/m3.b)Average length measured with a caliper.c)Csc= Stub column ultimate compressive strength.

    Table 3.1 Measured material properties

    E(GPa) a) Fy(MPa)a) Fu(MPa)

    a)u(%)

    a)

    CHS 196 498b) 540 25.9

    EHS 216 421 530 34.7

    Plate (tp=25.7mm) 201 358 482 28.0

    Plate (tp=32.0mm) 214 356 472 30.0

    Table 3.2 Stub column properties and test results

    Length (mm) Weight (Kg) Area a) (mm2) Cscc) (kN)

    CHS 150 b) 2.91 2471 -1213

    EHS 104.7 b) 2.51 3053 -1393

    Figure 3.5 Strain gauges on stub columns

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    29/71

    3-5

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    Using the data acquired through the test of the CHS (see Figure 3.6), the calculation of

    average Youngs Modulus agreed with the value previously determined from the tensile test

    coupons. A similar conclusion was achieved from the computation of the average yield stress.

    For the EHS, the average Youngs Modulus (see Figure 3.7) also agreed well with the value

    previously determined by tensile test coupons. However, an increase of 8% was observed when

    the EHS stub column yield stress was compared to the tensile test coupons. This difference has

    been attributed to the uneven manner in which the EHS stub column changed its shape through

    the test, which likely resulted in a higher value.

    Figure 3.6 Stub column response of CHS

    http://-/?-http://-/?-
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    30/71

    3-6

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    3.2 Test specimens and instrumentation

    A total of six connection types were examined throughout this experimental program (see

    Figure 3.8). Connection type A was fabricated with a slotted CHS which was connected to a

    25mm thick gusset plate by longitudinal fillet welds. Connection type B was originally fabricated

    as connection type A, however, the slot was filled in when the weld return was included. This

    connection type eliminates the reduction in the gross cross-sectional area of the tube due to

    slotting. For connection type C, a 25mm thick gusset plate was slotted so the CHS gross cross-

    sectional area remained unaffected. For this connection type, the tube and the gusset plate

    were connected by longitudinal fillet welds too.

    For the CHS tension tests, two specimens were fabricated for each connection type (A, B

    and C) and the main difference between specimens (from a similar connection type) was their

    weld length. Hence, they were labelled in a progressive order as the weld length increased.

    Additionally, specimens from the connection types A and C were fabricated and tested under

    compression loading.

    Five EHS specimens were fabricated for tensile testing. In order to avoid confusion

    amongst the EHS connections, these were simple labelled in a progressive order (E1 to E5)

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 0.0002 0.0004 0.0006 0.0008 0.001 0.0012 0.0014 0.0016 0.0018 0.002

    Strain (mm/mm)

    Stress

    (MPa

    )

    SGE SGW

    SGN SGS

    Figure 3.7 Stub column response of EHS

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    31/71

    3-7

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    depending on their connection type and weld length. The connection types E1 and E2 were

    fabricated with a slotted EHS, with the gusset plates oriented to give a large eccentricity and

    only longitudinal weld lengths were used to transfer the load. Connection type E5 was similar to

    these connections, however the orientation of the gusset plate was changed to give a smaller

    eccentricity. In general, the connection types E3 and E4 were similar to connection type C, but

    the EHS was oriented to produce a large eccentricity.

    In all cases, the test specimens had a Lw/w ratio within the range from 0.60 to 0.90 which

    guaranteed the presence of the shear lag phenomenon during the tests. All gusset plates and

    welds were dimensioned so as not to be critical. Fillet welds had a nominal size of 10 or 15 mm

    and they were fabricated using E480XX electrodes (CSA 2003). The tube lengths were 1.5 and

    2.0 metres for the CHS and EHS respectively. In order to facilitate the tests, two identical

    connections were fabricated at each tube end, which allowed the testing of two connections

    with very similar weld lengths simultaneously (see Figure 3.9). The average dimensions and

    properties of the specimens are shown in Table 3.3. Additionally, all measured dimensions from

    the test specimens are given in Appendix A.

    Figure 3.8 Connection types examined

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    32/71

    3-8

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    a) Measured area calculated by weighing a piece of HSS and using a density of 7850 kg/m3

    All the specimens were loaded in quasi-static axial tension to failure in a universal testing

    machine and displacement control was used throughout each test. Four LVDTs (linear variable

    differential transformers) were placed on each specimen to measure deformations during the

    test. The tube deformation reported herein corresponds to the average deformation measured

    by two LDVTs from the centre of the tube to the gusset plate. Each specimen was also equipped

    with 10 strain gauges to establish the strains in the connection region (see Figure 3.10). All thisinformation was acquired with a computer during the tests and the use of white-washing

    allowed the identification of regions with high strain concentration that in most cases induced an

    early fracture in the tube material.

    For the compression tests performed on specimens A3C and C3C, a minimum free

    distance of 2tp was provided in the gusset plate between the machine clamps and the tube

    ends. In addition to the instrumentation used in the tension tests, a fifth LVDT was placed at the

    test specimen mid-height to measure its out-of-straightness during the test.

    Table 3.3 Measured dimensions and geometric properties of test specimens

    Specimen Tubeal

    (mm)

    Lw

    (mm)

    w

    (mm)

    Lw/w

    (mm)

    tp

    (mm)

    Wp

    (mm)

    A1

    CHS

    168.5x4.89

    Aa)=2471 mm2

    10 156

    238

    0.65

    25.7

    197

    A2 10 192 0.80 198

    A3C 10 206 0.86 197

    B1 9 169 0.71 197

    B2 9 208 0.87 198

    C1 14 162

    239

    0.67 2 x 74.3

    C2 14 195 0.81 2 x 75.5

    C3C 14 200 0.83 2 x 74.3

    E1

    EHS

    110.9x221.2x5.94

    Aa)=3054 mm2

    13 145234

    0.61

    32.0

    161

    E2 14 182 0.77 161

    E3 15 146237

    0.61 2 x 94.0

    E4 15 175 0.73 2 x 93.8

    E5 15 185 234 0.79 270

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    33/71

    3-9

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    Figure 3.9 Experiment setup for tests

    Figure 3.10 Location of strain gauges on test specimens

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    34/71

    3-10

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    3.3 Experimental test results

    During the tests, the connection strength was determined principally by one of the

    following failure mechanisms: a) a tear out failure (TO) where the crack initiated at the weld

    termination then propagated through the tube base material near the weld toes, b) a

    circumferential fracture (CF), where the crack initiated at the weld termination then propagated

    around the tube circumference, and c) a combination of both failure modes (TO-CF). In the

    latter, both failure mechanisms occurred simultaneously at the connection end. The four LVDTs

    installed on each test specimen measured the overall elongation from the mid-length of the test

    specimen to the gusset plates. Even though two connections were fabricated alike for each test

    specimen (one at each tube end), failure was generally concentrated at one end. This

    behaviour has been attributed to variations in actual weld lengths and imperfections included

    during fabrication. The load-deformation response shown for the test results corresponds to the

    failed connection. In general, all the connections exhibited an uneven strain distribution along

    the connection and around the tube circumference. From the data acquired during the test, the

    strain distribution in the connections is only presented for a stage near the end of the

    connection elastic response. The rest of the strain readings are given in Appendix C.

    3.3.1 Slotted CHS connection - slot end not filled (type A)

    The use of this connection type is advantageous since the fabrication tolerance for the

    slot makes assembly of the parts easier. However, the presence of an open slot end can affect

    the overall connection behaviour, as seen by the tests. In general, the behaviour of these

    connections can be described in several stages. Initially, the connections showed an elastic

    response with an equivalent constant stiffness. Afterwards, the strain concentration in the slot

    region (due to the presence of the shear lag phenomenon) induced yielding of the tube material

    there, thus modifying the overall connection stiffness. The magnitude of the shear lag (affecting

    each connection), which is determined by the weld length, increases as the weld length

    decreases, and the weld length was the only distinction between the two test specimens.

    (Figure 3.11shows a superior performance for the test specimen with the longer weld length,

    A2). At this yielding stage, whitewash flaking confirmed the strain concentration taking place in

    the tube base material near the weld start (in the slot region). The strain gauge readings from

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    35/71

    3-11

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    the test specimens also confirmed this, as they showed an uneven strain distribution around the

    tube circumference and along the connection (see Figure 3.12).

    As the test specimens elongated, deformation was concentrated in the slot region

    producing a gradual change of the tube shape (inducing the formation of a neck there). In

    addition, the uneven strain distribution at the slot cross-section (due to the shear lagphenomenon) stimulated a quick increase in the strains at the weld start location, where

    straining of the tube material continued until fracture occurred. In general, a longer weld length

    allowed a better load transfer over the connection which diminished the connection

    deformation, however tube material fracture always governed the connection behaviour. Once

    fracture started, the crack continued to propagate gradually from the weld heel to its toe. Then,

    depending of the load level and the strain distribution in the connection, the crack would

    continue to propagate over the weld length (TO) or around the tube circumference (CF).

    Specimen A1 showed both failure modes and specimen A2 only CF (see Figure 3.13). The

    maximum load and deformation attained by these test specimens are shown in Table 3.4.

    Figure 3.11 Load-deformation response for connections type A

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    36/71

    3-12

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    Table 3.4 Ultimate capacity for connections type A

    Weld Length

    (mm)

    Test Load

    Nux(kN)

    Deformation @

    Max Load

    (mm)

    Failure

    ModeNux/AnFu

    Specimen A1 156 1032 8.8 TO-CF 0.87

    Specimen A2 192 1154 8.8 CF 0.97

    Figure 3.12 Strain distribution for test specimens A1 and A2 at 800kN

    Figure 3.13 Failure in test specimens A1 and A2

  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    37/71

    3-13

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    3.3.2 Slotted CHS connection - slot end filled (with a weld return) (type B)

    The addition of a weld return to these test specimens eliminated the possibility of a failure

    through the tube net area. Moreover, it allowed the attainment of the maximum load with small

    deformations (see Figure 3.14). In both tests, the load increase produced a strain concentration

    that was located at the weld return region (specifically at the weld toe). This behaviour has been

    attributed to the difference in the ductility of the return welds, since these were loaded at 90

    with respect to their longitudinal axis which creates a region of high stiffness.

    Whitewash flaking confirmed the strain concentration taking place at the weld return

    region as the tube material yielded there at an early stage of the tests. Moreover, the readings

    of the strain gauges always exhibited very uneven strain distributions around the connections.

    Figure 3.15shows the strain distribution around the tube and along the connection length, at the

    end of the elastic response.

    The strain gauge readings around the tube circumference showed an improvement

    compared to the strain distribution from connections type A. However, the strains experienced

    an increase right at the weld return region, relative to connections type A (see Figures 3.15and

    3.12at z=+50mm). For specimens B1 and B2, the strain distribution presented a dependency

    Figure 3.14 Load-deformation response for connections type B

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    38/71

    3-14

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    on the weld length and the specimen B1 (which had the smaller weld length) showed higher

    strain at z=+50mm (see Figure 3.15).

    Once the overall connection stiffness noticeably changed, any load increment was

    associated with a gradual increase of the strains in the weld return region and a change in the

    tube cross-section shape. The maximum load was limited by the propagation of a crack in the

    tube material near the weld return toe. This crack spread gradually at a 45 degree angle from

    the gusset plate. Finally, specimen B1 showed a TO failure and specimen B2 a CF (see Figure

    3.16). The maximum load and deformation attained by these test specimens are shown in Table

    3.5.

    Table 3.5 Ultimate capacity for connections type B

    Weld Length

    (mm)

    Test Load

    Nux(kN)

    Deformation @

    Max Load

    (mm)

    Failure

    Mode

    Nux/AnFu(An=Ag)

    Specimen B1 169 1087 6.1 TO 0.91

    Specimen B2 208 1211 6.1 CF 1.02

    Figure 3.15 Strain distribution in test specimens B1 and B2 at 800kN

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    39/71

    3-15

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    3.3.3 Slotted EHS connection - slot end not filled (gusset plate oriented to give a large

    eccentricity)

    The behaviour of these connections emulated the response of specimens type A.

    However, some differences occurred herein which have been associated mainly to the tube

    geometry. During these tests, the overall connection response can be described by several

    stages. At first, the test specimens had a similar elastic stiffness, while strain concentrations

    developed at the slot region (specifically in the tube near the weld start). This eventually caused

    tube material yielding at that location and affected the overall connection response. In general,

    the magnitude of this strain concentration was directly determined by the weld length. As a

    consequence, the elastic response of specimen E1 had an early ending (relative to specimen

    E2) as it had the shorter weld length (see Figure 3.17).

    Figure 3.16 Failure in test specimens B1 and B2

    http://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdfhttp://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdfhttp://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdf
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    40/71

    3-16

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    At a load of 600 kN (near the end of the elastic response), the strain gauge readings

    around the tube circumference showed an uneven strain distribution (as expected for this

    connection type). In both tests, the maximum strain along the longitudinal weld took place at the

    weld beginning and a much lower value was recorded at the slot open end (see Figure 3.18). At

    this load level, considerable differences were observed between the readings from specimens

    E1 and E2 in the weld region. E2 had higher local strains than E1, despite having a longer weld

    length, which initially represented an inconsistency with the results from other connections

    (where the strain concentration decayed as the weld length increased). A further examination of

    specimen E1 revealed that during the fabrication of specimen E1 the tube was over-slotted, with

    a slot length of 268 mm. This dimension far exceeded the required weld length which was only

    145 mm. Moreover, the weld fabrication started near the slot end leaving a considerable portion

    of the slotted tube free behind the welds (see Figure 3.19). Hence, the progressive deformation

    of connection E1 was accompanied by a bowing outwards of the free slotted tube portion as the

    load increased. This may have positively affected the strain distribution in the connection since

    it modified the strain concentration at the slot end. The bowing in the slotted tube E1 did not

    eliminate the shear lag phenomenon, but was sufficient to change the connection strain

    distribution.

    Figure 3.17 Load-deformation response for connectionstype E1 and E2

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    41/71

    3-17

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    Once the tube material started to yield, the connection deformation began to concentrate

    near the open slot region (adjacent to the beginning of the welds). This local straining was

    combined with gradual propagation of material yielding in surrounding areas, illustrated by

    flaking of the whitewash along the connection. In addition, yield lines emanated from the slot

    into the tube. In both test specimens, these yield lines were neatly depicted on the tube surface

    (this contrasted with the CHS connections where material yielding was mainly exemplified by a

    region rather than lines). This different behaviour has been attributed to the EHS tube materialproperties, which exhibited a clear yield plateau unlike the CHS material. Finally, close to the

    attainment of the maximum load, the tube started to neck at the open slot region, slowing the

    load increase. Then, the connection distortion stopped as the tube material fractured (see

    Figure 3.19).

    Figure 3.18 Strain distribution for test specimens E1 and E2 at 600kN

    http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    42/71

    3-18

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    The crack continued propagating around the tube circumference (CF) in both specimens

    until complete tube rupture. Although the maximum load in specimen E2 nearly reached the

    tube gross cross-sectional area yield load (AgFy=1286 kN), the capacity was still limited by the

    uneven strain distribution induced by shear lag. Finally, the maximum load and deformation

    attained by these test specimens are shown in Table 3.6.

    Table 3.6 Ultimate capacity for connections type E1 and E2

    3.3.4 Slotted EHS connection - slot end not filled (gusset plate oriented to give smalleccentricity)

    The change in the gusset plate orientation significantly improved the behaviour of this test

    specimen relative to its counterpart with a large eccentricity (see Figure 3.20).

    Weld Length

    (mm)

    Test Load

    Nux(kN)

    Deformation @

    Max Load

    (mm)

    Failure

    Mode

    Nux/

    AnFu

    Specimen E1 145 1109 9.9 CF 0.81

    Specimen E2 182 1236 11.1 CF 0.90

    Figure 3.19 Failure in test specimens E1 and E2

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    43/71

    3-19

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    At a load of 1040 kN (near the end of the elastic response), the strain gauge readings

    around the tube circumference showed a very uneven strain distribution, illustrated by Figure

    3.21(as was observed previously in specimens E1 and E2). Along the parallel welds, the strain

    distribution again reached its maximum value at the beginning of the weld as before.

    Figure 3.20 Load-deformation response for connection type E5

    Figure 3.21 Strain distribution in test specimen E5 at 1040 kN

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    44/71

    3-20

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    As part of the transition from an elastic response to a distinct yield plateau, the connection

    deformation began to concentrate at the open slot region and shear yield lines (visible due to

    the whitewash flaking) also emanated from this region towards the tube mid-length. The low

    connection eccentricity significantly improved the load transfer from the EHS to the gusset

    plate, relative to its counterpart with a large eccentricity. This also decreased the strain

    concentration occurring at the beginning of the weld, thus allowing the attainment of the yield

    stress across the tube net section. At this load level, shear yield lines continued to propagate

    but now over the entire tube length, increasing the overall deformation from 12 to almost 27mm.

    In contrast with test specimens E1 and E2 (where the overall deformation was mainly

    concentrated at the slot region), the total deformation here was a combination of the

    deformation at the slot region plus the overall tube elongation due to material yielding. In order

    to continue increasing the load, the material at the net section started to strain harden. The

    uneven strain distribution taking place at the open slot, aggravated by the shear lag

    phenomenon, eventually caused tube fracture there (see Figure 3.22).

    Once material fracture began, the load decreased as a consequence of the crack

    propagation around the tube circumference (CF), until complete tube rupture. Even though the

    tube material reached strain hardening, the maximum connection efficiency (Nux/AnFu) was

    restrained to only 94%. Nevertheless, this connection did allow the attainment of complete tube

    yielding (AgFy=1286 KN) which may represent an advantage of this structural shape over the

    CHS. The maximum load and deformation attained by this test specimen is shown in Table 3.7.

    Table 3.7 Ultimate capacity for connection type E5

    Weld

    Length

    (mm)

    Test Load

    Nux(kN)

    Deformation @

    Max Load

    (mm)

    Failure

    Mode

    Nux/

    AnFu

    Specimen E5 185 1282 31.8 CF 0.94

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    45/71

    3-21

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    3.3.5 Slotted gusset plate to tube connections in tension

    This connection type avoids any loss of the tube cross-sectional area and its potential

    effect on connection strength. Even though this may be considered its principal advantage over

    slotted tube connections, the slot in the gusset plate can negatively affect the connection

    stiffness, leading to excessive deformation of the gusset plate and consequently to the tube

    cross-section (as was observed during the tests).

    3.3.5.1 Slotted gusset plate to CHS connection (type C)

    A strain concentration took place at the beginning of the welds (in the CHS) and interior

    corners of the gusset plate. Close to 600 kN, the gusset plate yielded and caused flaking of the

    whitewash there and a change in the overall connection stiffness (see Figure 3.23).

    Figure 3.22 Failure in test specimen E5

    http://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdfhttp://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdfhttp://0.0.0.0/http://0.0.0.0/http://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdfhttp://ch6_parametrical_fe_analysis/CH6_Parametric_Analysis.pdf
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    46/71

    3-22

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    For both test specimens, this happened at a lower load level than for the slotted tube

    connections. At this load stage, the strain gauge readings around the tube circumference

    showed an uneven strain distribution and the maximum strain value took place at the beginning

    of the welds (see Figure 3.24). In addition, the minimum value (near zero) was detected for thestrain gauge located at 90 (see Figure 3.24), as for slotted tube connections. Moreover, close

    to attainment of the maximum load the readings at 90 switched to negative values (indicating

    compressive strains). This initially-unexpected behaviour was attributed to the excessive

    distortion of the tube cross-section, due to the gusset plate bowing and the necking of the tube.

    The readings along the parallel welds also showed typical variations, with the highest strain

    concentration occurring at the beginning of the weld (see Figure 3.24). Of the two tests, the

    higher strains were registered in specimen C1 which has the shorter weld length.

    Figure 3.23 Load-deformation response for connections type C

    http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/http://0.0.0.0/
  • 8/13/2019 CIDECT Final Report 8G-10_06(1of4)

    47/71

    3-23

    SLOTTED END CONNECTIONS TO HOLLOW SECTIONS, CH 3: EXPERIMENTAL PROGRAM

    Beyond the elastic response, each load increment resulted in increasing distortion of the

    tube cross-section. Moreover, the bowing outwards of the gusset plate introduced out-of-plane

    strains at the tube surface which are believed to have induced a triaxial state of stress at the

    beginning of the weld. This behaviour continued throughout the tests until the material fractured

    (see Figure 3.25).

    Once the fracture started (at the beginning of the welds), the crack continued propagating

    around the tube circumference (CF) in both tests. These tests again corroborated how the

    presence of shear lag can affect the strain distribution in such connections. Nevertheless, the

    magnitude of this strain concentration (which triggers the material fracture) is a consequence of

    factors such as: magnitude of the shear lag, bowing of the gusset plate, tube cross-section

    distortions and tube necking. Based on these two tests, it seems necessar


Top Related