GeniSys™ 7505 120V Oil Burner ControlPart 2
September 2, 2020
Beckett Online Training | Series 3: Beckett Controls | Session 2
OilPrimaries
OilIgniters
Gas Ignition & Control
AquaSmart
12 VDC
24 VDC
120 Potted
240 Potted
120 Volt
12 VDC24 VDC
240 Volt
120 Volt 120/24 Volt
Outdoor Reset
7590 Gas Control
120 Volt Gas ignitor
Beckett Family of Controls
7586 Intermittent Pilot Gas Control
Series Overview
• Basic Features of the GeniSys 7505 Primary Control.• Model Designation, Installation and Wiring for
Proper Operation.• Understanding the Sequence of Operation.• Resetting the Control from a Safety Lock-out Condition.• The 4 Minute Pump Prime Feature.• Viewing and Reading the 15 cycles of History for
Advanced Diagnostics.
• Field wiring of the 7505 Oil Burner Primary Control for Pre- Purge and Post Purge.
• Why a CleanCut Fuel Pump or solenoid valve is required when programming for Pre-Purge and Post Purge.
• Learn how to set the purge features using the 4 keys on the Contractor tool.
• 7610 Features and Benefits.• Warm and Cold Start Boiler Operation.• Freeze Up Protection.• Easy Programming of the Aquasmart Control.• Reset Information Including:• Heat Manager (Indoor Reset)• Circulators On and Off Delays for Purging the system• Outdoor Temperature Reset
• 7590 Features and Benefits• Various Models Available• Status and Diagnostics LED’S• Flame Supervision• Air Pressure Switch Monitoring• 7590 Important Terms• Auto Retry Feature• Beckett Link Configuration and Diagnostics Tool
Module 1
Module 2
Module 3
Module 4
Class OverviewUpon completion of this web-based instruction module you should be able to:
Set the pre-purge and post-purge on the Genisys Control utilizing the Contractor Tool
Please feel free to submit questions after the end of each session
GeniSys Electronic Primary
Finally-a universal control that saves time, control inventory and delivers on the promise of:
GeniSys Control
“Technology made simple”
GeniSys Display Service Tool
52082 display provides a sealed pushbutton keypad for control interface:• Customizable pre-time • (valve on delay)
• Customizable post-time • (motor off delay)
• Allows navigation through current & historical data • 32-character backlit alphanumeric display
• Low voltage operation
• Continuous real-time cycle monitoring
• Continuous cad cell resistance reading
• Continuous AC line voltage readout
• Real-time error notification
• 15 cycle history monitoring
• 18- month warranty
• Customizable lockout service message
CALL FOR SERVICE1 800 645 2876
CALL FOR SERVICE1 800 645 2876
GeniSys Display Service Tool
Two communication ports for add-on modules.
GeniSys Control
Basic FeaturesRecessed wiring terminals
• Saves room in wiring box
• Fewer pinched wires
• Easy removal
• Shipped with pigtails and spade flag terminals
• Room to use typical straight insulated spade terminals
Wiring terminals recessed inside case
Color coded recessed wiring terminals
• Same colors as legacy controls
• Matches wire colors of Beckett components
• Reduces wiring mistakes
• Separate L2 terminals to aid trouble shooting
Basic Features
Wiring / Installation
L1/Limit jumper
• For A and B model GeniSys controls programed without motor-off delay (postpurge), the L1 and Limit terminals must be jumpered.
• L1/Limit jumper is supplied with the control.
• The control will not work if 120VAC is not present at L1 or Limit
• If no jumper is available simply add a wire to Limit and connect to line input
Universal Applications Replace 3 wire control with 7505A0000Or simply reprogram an existing GeniSys and rewire
Burner has pump with valve. Program control for Pre-Time valve on delay and wire the valve to the valve terminalUniversal Applications
Need motor off delay?One control does it all. Remove jumper, wire as shown, then program “Pre” and “Post” time
GeniSys Control
7505A • No delays (purge)
7505B• Valve-on delay (prepurge) only
7505P• Valve on delay (prepurge) and motor-off delay (postpurge)
Model Designation
Part Number Valve-On Delay Motor-Off Delay
7505A 0000 None None
7505B 1500 15 seconds None
7505P 1515 15 seconds 15 seconds
7505P 1530 15 seconds 30 seconds
7505P 152M 15 seconds 2 minutes
STOCK 1 AND YOU’RE DONE
PICK A CONTROL MODEL NUMBER
Model Designation
UP
Begin by plugging in the Contractors Tool.
COM port 1
GeniSys Control
The keysGeniSys Control
GeniSys Control
STANDBY 8:15> 50 K OHMS 115 V
Press the NEXT key
VIEWHISTORY
Press and hold the NEXT key for 3 secondsGeniSys Control
PRE-TIME 0:00SEL TO CHANGE
Press the SEL key GeniSys Control
VALVE INSTALLED?NO YES
Notice: To continue the burner must have an oil valve or CleanCut pump to add purgesGeniSys Control
The GeniSys Control requires an oil valve to program both the valve on delay (pre purge) and motor off delay (post purge) features.
GeniSys Control
LOCK OUT 0:45 PRE-TIME FLAME
The cad cell detected flame at theend of the Valve On Delay state.GeniSys Control
VALVE NEEDEDSEE IO MANUAL
Press the BACK (NO) key if an oil valve is not available and see messageGeniSys Control
CHANGED CANCELLED
The changed cancelled message will be displayedGeniSys Control
PRE-TIME 0:00SEL TO CHANGE
Press the SEL key GeniSys Control
VALVE INSTALLED?NO YES
Press the SEL (YES) key GeniSys Control
PRE-TIME 0:30NO YES
Press the next key to set the timing 0, 5, 10, 15, 30 OR 45 SecondsGeniSys Control
ACCEPT 0:30NO YES
Press SEL(YES) to acceptGeniSys Control
PRE-TIME 0:30SEL TO CHANGE
The Pre-Time is now setPress the NEXT key to set the post time GeniSys Control
POST-TIME 0:00SEL TO CHANGE
Press the SEL key GeniSys Control
VALVE INSTALLED?NO YES
Press the SEL (YES) key GeniSys Control
POST TIME 0:30NO YES
Press the next key to set the timing 0, 5, 15, 30, 1, 2, 4 or 8 minutesGeniSys Control
ACCEPT 0:30NO YES
Press SEL (YES) to acceptGeniSys Control
POST TIME 0:30SELECT TO CHANGE
The Post Time is now set.Press the BACK key to exit GeniSys Control
STANDBY 1:15> 50 K OHMS 115 V
You just set the Pre-Time and Post TimeGeniSys Control
THIS QUICK TUTORIALWILL GUIDE YOU
THROUGH THE STEPSON SETTING THE PRE
PURGE AND POST PURGE ON A GENISYS CONTROL
Download right to yoursmart phone or tabletTutorials
www.beckettcorp.com
Beckett Website
Any questions?Thank You!
Jeff Rozga Jim Todd
If you have any questions that weren’t answered – Email at