Energy Recovery Ventilation: the proven
advantages of heat and humidity transfer
Improves Indoor Air QualityBy providing simultaneous exhaust and fresh air supply, RenewAire reduces the concentration of harmful pollutants in indoor air - an absolute must in schools, offices and smoking environments.
Meets Ventilation Codes for Air ExchangeProvides ample ventilation to meet ASHRAE 62 and the International Mechanical Code that now requires two to three more air exchanges than in the past.
Controls Excess MoistureUnlike conventional ventilation or basic heat exchangers, RenewAire moderates not only the temperature but the humidity content of incoming air, limiting humidity swings and associated biologic growths.
Optimum Cold Weather PerformanceRecaptures heat otherwise lost to exhaust air while controlling humidity extremes. This greatly reduces the demand on heating equipment - lowering both initial costs and energy bills. Also protects heating coils from freeze damage.
Optimum Warm Weather PerformancePre-cools and dehumidifies the fresh airstream by transfer of heat and humidity to the exhaust airstream. This greatly reduces air conditioning demand - lowering both initial costs and energy bills. On retrofits, the ventilation rate of exisitng A/C equipment can be as much as doubled.
Energy Saved = Dollars SavedRenewAire’s all-weather performance can cut annual energy bills for heating, cooling and dehumidification of ventilation air by 50% or more.
Indoor Air Quality Problems Solved!
Ideal for Hot or Cold Environments
Catalog Page Reference2 Residential Products4 BR705 BR1306 EV707 EV1308 EV2009 EV30010 Commercial Indoor Products12 EV450IN14 HE1XINH16 HE1XINV18 HE2XINH20 HE2XINV22 HE3XINH24 HE3XINV26 HE4XINH28 HE4XINV30 HE6XIN32 HE8XIN34 Commercial Outdoor Products
36 EV450RT38 HE1XRT40 HE1XRTC42 HE2XRT44 HE2XRTC46 HE3XRT48 HE3XRTC50 HE4XRT52 HE4XRTC54 HE6XRT56 HE8XRT58 Applied Products60 CA-Series62 PA-Series64 Commercial Controls66 HVI Certified67 AHRI Certified67 CA/PA Model
Number Guide68 EV/HE Model
Number Guide69 Company History
For Technical Support E-mail: [email protected] Place an Order E-mail: [email protected]
Why RenewAirE?
The Static-Plate Core is the Key!Since the early 1980’s, RenewAire has pioneered the use of the patented Lossnay (Registered trademark of Mitsubishi Electric Corporation) exchange core throughout the Americas. Listed below are some of the many reasons why this technology has become the ERV system preferred by leading HVAC professionals around the world.
Positive Airstream SeparationIn the RenewAire core, fresh air never comes in contact with exhaust air passages. Hydroscopic resin plates separate the two airstreams so effectively that AHRI certifies zero exhaust air transfer at normal, balanced operating conditions. As a result, RenewAire is perfect for controlled exhaust applications such as toilet areas, as well as for food service and health care occupancies.
No Condensate or Active DefrostDirect water vapor transfer, driven by vapor pressure, eliminates condensation - and frosting - in virtually all applications and climate zones. No condensation allows for closer plate spacing, resulting in higher efficiencies and easier installations. It also means no need for the dampers or electrical defrost elements that reduce ventilation and rob energy efficiency in competing technologies.
Maintenance - Nothing Could Be EasierThe scheduled maintenance for RenewAire is so simple, it can be performed by any janitorial staff. No expensive service contracts are necessary because there is no wheel disassembly and washing, no seal or belt adjustments and no complex controls to calibrate. The result is the lowest maintenance cost of any ERV.
The Unbeatable RenewAire WarrantyAn investment in RenewAire is protected by a 10-year core warranty (2 years on balance of the unit). This commitment - twice as long as coverage on the best wheel products - speaks volumes about RenewAire’s reliability, durability and consistently high performance.
Award-Winning Service and SupportRenewAire’s team of professionals knows ERV. And our nationwide network of Sales Reps and quality Distributors are ready to serve you locally. When you call our support number, you’ll talk to a knowledgeable factory expert - someone who knows not only our product line, but the best ways to integrate RenewAire with your preferred lines of heating and air conditioning equipment.
INSIDEFresh Air to Room
OUTSIDEStale Room Air
(exhausted to outside)
Stale Room Air Outside Air
Fixed Partitionand Spacer Plates(proprietary resincomposite media)
RenewAire’s remarkable performance is independently certified by:
G5 Enhanced Humidity Transfer
RenewAire is proud to introduce the fifth generation energy
recovery ventilation (ERV) core.
Over 22% more humidity transfer • at AHRI summer conditions
reduced pressure drop - among • the lowest for static-plate ERV
HE1X = 0.65” @ 750 SCFM EV450 = 0.6” @ 450 SCFM
Try RenewAire’s ERV Calculation Software
at www.ervcalc.renewaire.com
(800) 627-4499 • Fax: (608) 221-28242
Residential/Small
Commercial Products
Commercial quality, ducted equipment • sized to meet required ventilation rates for homes and small commercial buildings.
Static-plate technology makes total energy • savings practical for small-capacity systems.
May be mounted in any orientation.•
Quiet, powerful blowers eliminate the need • for air balancing in most applications.
Positive airstream separation that is • critical for smoking environments and bathroom exhaust.
No condensate pan or drain required.•
Easiest maintenance of any ERV.•
Performance certified by HVI.•
Ten year core warranty.•
primary control for EV70, • EV130, EV200 & EV300 runs unit an adjustable • amount of time each hour two wire, low voltage • connection to ERV
PTL Controlpush button control turns on • unit from bathrooms or other intermittent exhaust locations 20 minute run-time • with one touch push 2x for 40 or • 3x for 60 minutes two wire, low voltage • connection to PTL Control
PBL Controlalternate primary control for • EV70, EV130, EV200 & EV300 wires to EV unit and either • thermostat or furnace control to turn on furnace blower six wire, low voltage • connection
FM Control
EA: Exhaust Air to outdoors
FA: Fresh Air to insideRA: Room Air to be exhaustedOA: Outdoor Air intakeCentral Exhaust - Use EV Series
General Exhaust - EV Series (or BR Series mounted to furnace return air which requires furnace blower interconnect)
NOTE: ERV Blower may be operated separately from Furnace Blower
NOTE: ERV Blower may be operated separately from Furnace Blower
(See manual for additional installation methods.)
www.RenewAire.com3
Part I - General
A. Product Specification
1. Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured by RenewAire and shall transfer both heat and humidity using static plate core technology.
B. Quality Assurance
1. The energy recovery ventilator shall be Certified by the Home Ventilating Institute (HVI) under CSA 439. Both a heating and a cooling test must be run to demonstrate year round energy recovery.
2. Manufacturer shall be able to provide evidence of independent testing of the core by Underwriters Laboratory (UL), verifying a maximum flame spread index (FSI) of 25 and a maximum smoke developed index (SDI) of 50 thereby meeting NFPA 90A and NFPA 90B requirements for materials in a compartment handling air intended for circulation through a duct system. The method of test shall be UL Standard 723.
3. Unit shall be Listed under UL 1812 Standard for Ducted Air to Air Heat Exchangers. The unit must pass commercial flammability requirements and shall not be labeled “For Residential Use Only”.
4. The ERV core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. The balance-of-unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase.
Part II – Performance
A. Energy TransferThe ERV shall be capable of transferring both sensible and latent energy between airstreams. Latent energy transfer shall be accomplished by direct water vapor transfer from one airstream to the other, without exposing transfer media in succeeding cycles directly to the exhaust air and then to the fresh air.
B. Passive Frost ControlThe ERV core shall perform without condensing or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional more extreme conditions shall not affect the usual function, performance or durability of the core. No condensate drains will be allowed.
C. Continuous VentilationUnit shall have the capacity to operate continuously without the need for bypass, recirculation, pre-heaters or defrost cycles under normal operating conditions.
D. Positive Airstream SeparationWater vapor transfer shall be through molecular transport by hydroscopic resin and shall not be accomplished by “porous plate” mechanisms. Exhaust and fresh airstreams shall travel at all times in separate passages and airstreams shall not mix.
E. Laminar FlowAirflow through the ERV core shall be laminar over the products entire operating airflow range, avoiding deposition of particulates on the interior of the energy exchange plate material.
Part III – Product
A. Construction
1. The energy recovery component shall be of fixed-plate cross-flow construction, with no moving parts.
2. No condensate drain pans or drains shall be allowed and unit shall be capable of operating in both winter and summer conditions without generating condensate.
3. The unit case shall be constructed of 24-gauge steel, with lapped corners and zinc plated screw fasteners. The case shall be finished with textured, powder coat paint.
4. Access doors shall provide easy access to blowers, ERV cores and filters. Doors shall have an airtight compression seal using closed cell foam gaskets.
5. Case walls and doors shall be fully insulated with 1 inch, expanded polystyrene foam insulation faced with a cleanable foil face on all exposed surfaces.
6. The ERV cores shall be protected by a MERV-8 rated, spun polyester, disposable filter in both airstreams.
7. The unit shall have a line cord power connection and be supplied with an internal 24 VAC transformer and relay.
8. Standby power draw shall not exceed 1 Watt for the unit along with an optional automatic control. B. Options (Select options based on application requirements)
1. For BR-Series: Through the wall kit and duct collar kit (automatic control is built into the unit standard).
2. For EV-Series: Controls including proportional run time, push button and furnace interlock and a variety of weather hoods.
Part IV – Installation
A. Unit Location
1. Locate and orient unit to provide the shortest and most straight duct connections. Provide service clearances as indicated on the plans. Locate units distant from sound critical occupancies.
2. Use integral mounting flange and hanging bar system to mount the unit to a structurally suitable surface. The units may be mounted in any orientation.
B. Vibration Isolation
1. Utilize factory supplied vibration isolation kit following instructions.
2. Provide flexible duct connections at unit duct flanges.
C. Duct Design
1. All ductwork shall be designed, constructed, supported and sealed in accordance with SMACNA HVAC Duct Construction Standards and pressure classifications.
2. At a minimum all duct runs to the outdoors shall be thermally insulated at levels appropriate to the local climate. A continuous vapor barrier shall also be provided on warm surface of the insulation.
D. Sound Control
1. To control sound radiated from the unit: a. Provide acoustic treatment in mechanical room walls and ceilings.
2. To control sound associated with the two blower outlets: a. Utilize insulated, flexible duct. b. In sound critical applications provide increased duct sizing and consider the use of sound attenuators.
E. Test and Balancing
1. Test and Balancing may not begin until 100% of the installation is complete and fully functional.
2. Follow National Comfort Institute (NCI) air test and balance procedures specific to Heat Recovery Ventilator Balancing Procedure including standard reports to the owner’s representative.
Residential Energy Recovery Ventilators: BR70, BR130, EV70, EV130, EV200 and EV300
(800) 627-4499 • Fax: (608) 221-28244
BR70Specifications
G4 Performance
Dimensions
Indoor UnitVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 40-70 CFM
Number Motors: One, 0.08 hp
V HZ Phase Input Watts FLA
120 60 Single 94 @ 69 CFM 0.9
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 7 1/2” x 10 1/2” x 1”
Weight: 39 lbs (unit), 50 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 29”L x 14 1/2”H
Options: Thru-the-Wall Kit Duct Collar Kit
Airflow CFM ESP in H20 Temp EFF% Total EFF% Winter/Summer*
35 0.50 84 75/60
51 0.40 80 71/56
63 0.30 77 68/53
79 0.20 73 64/48
90 0.10 70 61/45
* (See HVI certification report on page 66 for complete certified rating).
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
TW: Thru WallDH: Duct Hung
18 1/4
54 1/2
27 1/8
36" LINE CORD
24 VAC CONTROL TERMINAL
18 1/2SERVICE
AREA
RIGHTVIEW
SIDE VIEW
BOTTOM VIEW(DOOR REMOVED)
10 5/8
2
1 1/8
EA (TW)FA (DH)
OA (TW)RA (DH)
TOP VIEW
6
17 5/8CUT HOLE IN DUCT(MINIMUM SIZE)
OA (TW)RA (DH) EA (TW)
FA (DH)
RA (TW)OA (DH)
FA (TW)EA (DH)
8 DIA6 DIA
PROPORTIONALRUNTIME
CONTROL
www.RenewAire.com5
BR130Specifications
G4 Performance
Dimensions
Indoor UnitVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 50-140 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.1 hp
V HZ Phase Input Watts FLA
120 60 Single 121 @ 124 CFM 1.3
Control Voltage: Built in proportional runtime control and switched terminals for furnace / AC interconnect
Filters: MERV 8, spun polyester media. 10 1/2” x 10 1/2” x 1”
Weight: 49 lbs (unit), 60 lbs (in carton)
Shipping Dimensions: 21”W x 32”L x 17 1/2”H
Options: Thru-the-Wall Kit Duct Collar Kit
Airflow CFM ESP in H20 Temp EFF% Total EFF% Winter/Summer*
52 0.70 83 75/60
69 0.60 80 72/57
94 0.50 76 67/52
113 0.40 73 64/48
132 0.30 70 60/44
141 0.20 68 59/43
148 0.10 67 57/41
* (See HVI certification report on page 66 for complete certified rating).
18 1/4
54 1/2
6 1/8 4 3/4
13 3/8
30 7/8
36" LINE CORD
24 VAC CONTROL TERMINAL 18 1/2
SERVICEAREA
RIGHTVIEW
SIDE VIEW
BOTTOM VIEW(DOOR REMOVED)
2
1 1/8
EA (TW)FA (DH)
OA (TW)RA (DH)
TOP VIEW
CUT HOLE IN DUCT(MINIMUM SIZE)
20 1/2
6
OA (TW)RA (DH) EA (TW)
FA (DH)
FA (TW)EA (DH)
OA (DH)RA (TW) 6 DIA
8 DIA
PROPORTIONALRUNTIME
CONTROL
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
TW: Thru WallDH: Duct Hung
EV70Specifications
G4 Performance
Dimensions
Indoor UnitVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 40-70 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.08 hp
V HZ Phase Input Watts FLA
120 60 Single 94 @ 69 CFM 0.9
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 7 1/2” x 10 1/2” x 1”
Weight: 39 lbs (unit), 48 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 29”L x 14 1/2”H
Options: PTL - Percentage Timer Control PBL - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control Wall Caps
* (See HVI certification report on page 66 for complete certified rating).
20 1
/8"
27 7/8" Service Access
RA
OA
FA
EA
BlowersInterlock Switch
Energy Transfer CoreFilters
34" Line Cord
24 Volt ACControl Terminal
Line Cord
4 1/
2"5
1/2"
9 1/
8"
5 1/
2"
6"6"
8 1/
8"
6"8"
FRONT VIEW RIGHT VIEW
TOP VIEW10 1/8"
4 1/
8"
25 1/8"
Airflow CFM ESP in H20 Temp EFF% Total EFF% Winter/Summer*
46 0.40 81 74/60
59 0.30 78 71/57
73 0.20 74 68/53
86 0.10 71 64/49
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
(800) 627-4499 • Fax: (608) 221-28246
EV130Specifications
G4 Performance
Dimensions
Indoor UnitVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 50-140 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.1 hp
V HZ Phase Input Watts FLA
120 60 Single 121 @ 124 CFM 1.2
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10 1/2” x 10 1/2” x 1”
Weight: 49 lbs (unit), 58 lbs (in carton)
Shipping Dimensions: 21”W x 32”L x 17 1/2”H
Options: PTL - Percentage Timer Control PBL - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control Wall Caps
Airflow CFM ESP in H20 Temp EFF% Total EFF% Winter/Summer*
52 0.70 83 75/60
69 0.60 80 72/57
94 0.50 76 67/52
113 0.40 73 64/48
132 0.30 70 60/44
141 0.20 68 59/43
148 0.10 67 57/41
* (See HVI certification report on page 66 for complete certified rating).
13"
20 1
/8"
30 5/8" Service Access
RA
OA
FA
EA
BlowersInterlock Switch
Energy Transfer CoreFilters
34" Line Cord
24 Volt ACControl Terminal
Line Cord
6 3/
8"
4 1/
8"
5 1/
2"9
1/8"
5 1/
2"
6"6"
8 1/
8"
6"8"
28 3/4"
FRONT VIEW RIGHT VIEW
TOP VIEW
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
www.RenewAire.com7
(800) 627-4499 • Fax: (608) 221-28248
EV200Specifications
G4 Performance
Dimensions
Indoor UnitVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 100-200 CFM
Number Motors: One, 0.1 hp
V HZ Phase Input Watts FLA
120 60 Single 157 @ 181 CFM 1.5
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10 1/2” x 21 3/4” x 1”
Weight: 70 lbs (unit), 82 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 32”L x 29”H
Options: PTL - Percentage Timer Control PBL - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control Wall Caps
Airflow CFM ESP in H20 Temp EFF% Total EFF% Winter/Summer*
122 0.70 82 74/59
149 0.65 80 72/56
168 0.50 79 70/55
176 0.40 78 69/54
186 0.30 77 68/53
192 0.20 77 68/52
200 0.10 76 67/52
* (See HVI certification report on page 66 for complete certified rating).
Blowers
34" Line Cord
Interlock Switch
Energy Transfer CoreFilters
24 Volt ACControl Terminal
Line Cord
RA
OA
FA
EA
23 7/8"
20 1
/8"
41 1/2" Service Access
11 7
/8"
11 7
/8"
5 1/
2"5
1/2"
9 1/
8"
6"6"
8 1/
8"
6"8"
28 3/4"
FRONT VIEW RIGHT VIEW
TOP VIEW
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
www.RenewAire.com9
EV300Specifications
G4 Performance
Dimensions
Indoor UnitVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 150-300 CFM
Number Motors: One, 0.2 hp
V HZ Phase Input Watts FLA
120 60 Single 310 @ 293 CFM 3.3
Control Voltage: 24 VAC
Filters: MERV 8, spun polyester media. 10 1/2” x 21 3/4” x 1”
Weight: 72 lbs (unit), 85 lbs (in carton)
Shipping Dimensions: 21 1/2”W x 32”L x 29”H
Options: PTL - Percentage Timer Control PBL - Push Button Point-of-Use Controls FM - Percentage Timer Control with Furnace Interlock DH24 - Dehumidistat Control 8” Wall Caps
Airflow CFM ESP in H20 Temp EFF% Total EFF% Winter/Summer*
155 1.0 80 70/51
199 0.9 76 67/48
249 0.8 72 62/44
268 0.7 71 61/42
289 0.6 69 58/39
300 0.5 68 57/38
310 0.4 67 56/37
* (See HVI certification report on page 66 for complete certified rating).
Blowers
34" Line Cord
Interlock Switch
Energy Transfer CoreFilters
24 Volt ACControl
Terminal
Line Cord
RA
OA
FA
EA
23 7/8"
20 1/8"
41 1/2" Service Access
9 3/4"10"
5 1/2"
5 1/2"
9 1/8"
5 1/2"
5 1/2"
9 1/8"
7 3/8"
8 3/4"
To Fit 8" Duct
FRONT VIEW
28 3/4"
TOP VIEW
RIGHT VIEW
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
(800) 627-4499 • Fax: (608) 221-282410
Commercial
INDOOR Products
Horizontal and v• ertical configuration.
Wide range of airflow and static capacities.•
AHRI certified per• formance data for efficiency and cross leakage.
UL tested fla• mmability and smoke generation that meets NFPA 90A and 90B test standards for commercial applications.
Easy installation and service.•
Ten year core warranty.•
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
RenewAire means Trouble-Free ERV.
www.RenewAire.com11
Part I - General
A. Product Specification
1. Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured by RenewAire and shall transfer both heat and humidity using static plate core technology.
B. Quality Assurance
1. The energy recovery cores used in these products shall be third party Certified by AHRI under its Standard 1060 for Energy Recovery Ventilators. AHRI published certifications shall confirm manufacture’s published performance for airflow, static pressure, temperature and total effectiveness, purge air (OACF) and exhaust air leakage (EATR). Products that are not currently AHRI Certified will not be accepted.
2. Manufacturer shall be able to provide evidence of independent testing of the core by Underwriters Laboratory (UL), verifying a maximum flame spread index (FSI) of 25 and a maximum smoke developed index (SDI) of 50 thereby meeting NFPA 90A and NFPA 90B requirements for materials in a compartment handling air intended for circulation through a duct system. The method of test shall be UL Standard 723.
3. Unit shall be Listed under UL 1812 Standard for Ducted Air to Air Heat Exchangers. (Note that a few low volume product or product configurations are not UL Listed.)
4. The ERV core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. The balance-of-unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase.
Part II – Performance
A. Energy TransferThe ERV shall be capable of transferring both sensible and latent energy between airstreams. Latent energy transfer shall be accomplished by direct water vapor transfer from one airstream to the other, without exposing transfer media in succeeding cycles directly to the exhaust air and then to the fresh air.
B. Passive Frost ControlThe ERV core shall perform without condensing or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional more extreme conditions shall not affect the usual function, performance or durability of the core. No condensate drains will be allowed.
C. Continuous VentilationUnit shall have the capacity to operate continuously without the need for bypass, recirculation, pre-heaters or defrost cycles under normal operating conditions.
D. Positive Airstream SeparationWater vapor transfer shall be through molecular transport by hydroscopic resin and shall not be accomplished by “porous plate” mechanisms. Exhaust and fresh airstreams shall travel at all times in separate passages and airstreams shall not mix.
E. Laminar FlowAirflow through the ERV core shall be laminar over the products entire operating airflow range, avoiding deposition of particulates on the interior of the energy exchange plate material.
Part III – Product
A. Construction
1. The energy recovery component shall be of fixed-plate cross-flow construction, with no moving parts.
2. No condensate drain pans or drains shall be allowed and unit shall be capable of operating in both winter and summer conditions without generating condensate.
3. The unit case shall be constructed of G90 galvanized, 20-gauge steel, with lapped corners and zinc plated screw fasteners.
4. Access doors shall provide easy access to blowers, ERV cores and filters. Doors shall have an airtight compression seal using closed cell foam gaskets.
5. Case walls and doors shall be insulated with 1 inch, 4 pound density, foil/scrim faced, high-density fiberglass board insulation, providing a cleanable surface and eliminating the possibility of exposing the fresh air to glass fibers.
6. The ERV cores shall be protected by a MERV-8 rated, 2” nominal, pleated, disposable filter in both airstreams.
7. Unit shall have single-point power connection and a single-point 24 VAC contactor control connection (except Inverter Ready units that have terminal connections for an independent inverter for each airstream).
8. Blower motors shall be EPACT compliant for energy efficiency and be thermally protected or supplied with external starters.
9. Blowers shall be quiet running, forward curve type and be either direct drive or belt drive. HE6X and HE8X units use backward incline, belt drive blower packages. Belt drive motors shall be provided with adjustable pulleys and motor mounts allowing for proper belt tensioning.
B. Options (Select options based on application requirements.)
1. Provide unit and duct connection orientation per project schedule.
2. Provide double wall construction with 24-gauge galvanized steel liner.
3. Units are available single or three phase at a full range of operating voltages. See project schedule.
4. Provide motor horsepower as specified in project schedule.
5. Provide “inverter-ready” units which include shielded power wiring and terminal connections for inverters (inverters provided and installed by others).
6. Provide factory installed fused disconnects.
7. Provide factory installed non-fused disconnects.
8. Provide factory installed transformer/relay package to supply a 24 VAC power source.
9. Provide factory installed filter monitors for each airstream.
Packaged Indoor Energy Recovery Ventilators: EV450IN, HE1XIN, HE2XIN, HE3XIN, HE4XIN, HE6XIN, HE8XIN
(800) 627-4499 • Fax: (608) 221-282412
EV450IN
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 200-500 CFM
AHRI 1060 Certified Core: One L85
Airflow Rating Points (for AHRI): 450 CFM and 338 CFM
Motors: One, 0.6 hp (Single Phase) One, 0.5hp (Three Phase)
V HZ Phase FLA
115 60 Single 7.0
208-230 60 Single 3.5
277 60 Single 2.4
208-230 60 Three 1.7-1.5
460 60 Three 0.8
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 14” x 20” nominal size
Weight: 141 lbs (unit), 160 lbs (in carton), up to 3 units on 50 lb pallet
Shipping Dimensions: 37 1/2” W x 48” L x 17” H
Options: 45EVHB - Hanging Bracket, Foot Kit 45EVDF - Rectangular 12” x 8” Flange Kit (2 in kit) 45EVT10 - 10” Round Transition Kit (2 in kit)
Airflow CFM
ESP in H20
Watts1P 3P
Temp EFF%
Total EFF%Winter/Summer*
225 1.25 335 181 81 76/66
338 1.00 420 278 77 71/61
380 0.90 470 340 75 69/59
450 0.65 550 430 73 66/56
540 0.25 640 540 70 62/52
575 0.00 690 610 69 61/51
600 -0.25 735 664 68 60/50
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Indoor Unit Specifications
G5 Performance
www.RenewAire.com13
EV
450
INU
nit
Dim
en
sio
ns
16 1/8"
5 3/8"
20 3/8"24 7/8"
11 5/8"
1"13 1
/4"
35 1/4"
33 7/8"
36 3/8"
4 1/4"16 1/8"
20 1/4"32"
10"
36 3/8"
2 1/
8"18
"44
1/8
"6
1/2"
1 1/4"
16"
34 1
/8"
Ser
vice
Are
a
8"2
1/8"
8"8"
8"8"
FRO
NT
VIE
W
TOP
VIE
W
Pow
er S
uppl
y E
ntry
7/8"
Dia
.
Filte
r Acc
ess:
Hin
ged
and
Latc
hed
Doo
r
All
othe
r Acc
ess:
Scr
ew-a
ttach
edpa
nel
1 1/
2" C
lear
ance
requ
ired
to re
mov
e do
ors
from
hin
ges.
6 3/
8"
26 1/4"10 1/8"
Opt
iona
l 45E
VT1
0-10
" Rou
nd
Tran
sitio
n K
it S
how
nO
ptio
nal 4
5EV
DF
Rec
tang
ular
12
" X 8
" Fla
nge
Kit
Sho
wn
EA FA
OA
RA
OA
RA
FAEA
FRO
NT
VIE
W (D
oors
rem
oved
)R
IGH
T V
IEW
SLE
FT V
IEW
S2
1/8"
10"
4 1/4"16 1/8"
20 1/4"32"
36 3/8"
O10" R
OUND
11 1/8"25 1/8"
1"8
3/4"
4 1/4"16 1/8"
20 1/4"32"
3 1/4"
5 1/
4"
2 1/
8"4
3/4"
13 1/4"
Alte
rnat
eP
ower
Sup
ply
Ent
ry7/
8" D
ia.
Opt
iona
l Tra
nsiti
ons
(45E
VT1
0) s
how
nCon
trol W
ire E
ntry
7/8"
Dia
.
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282414
HE1XINHIndoor Unit
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 250-925 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V HZ Phase FLA Min. Cir. Amps
Max. Fuse Size
115 60 Single 8.6 19.4 25
208-230 60 Single 4.3 9.7 15
277 60 Single 2.4 5.4 15
208-230 60 Three 2.1 5.2 15
460 60 Three 1.1 2.6 15
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 211 lbs (unit), 250 lbs (shipping weight)
Shipping Dimensions: 44” W x 56” L x 27” H
Specifications
Motor HPPhase
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
0.75 (Two DD)Single Phase
970 CFM1,490 Watts
925 CFM1,375 Watts
860 CFM1,270 Watts
795 CFM1,160 Watts
720 CFM1,030 Watts
635 CFM 950 Watts
350 CFM 750 Watts
0.75 (Two DD)Three Phase
1,030 CFM1,220 Watts
1,010 CFM1,210 Watts
975 CFM1,160 Watts
880 CFM1,050 Watts
800 CFM 990 Watts
700 CFM 850 Watts
530 CFM 720 Watts
G5 PerformanceCFM
250 500 750 1,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Airflow Performance
www.RenewAire.com15
HE1X
INH
Un
it D
imen
sio
ns
OA
FAR
A
EA
EA
FA
Con
trol W
iring
Inle
t 7/8
" Dia
.
40 5
/8"
Min
imum
Ser
vice
Are
a(D
oors
can
be
take
n of
f hin
ges.
)
49 1
/8" C
ase
34 7
/8" C
ase
Ø12
" TY
P
FRO
NT
VIE
WLE
FT V
IEW
TOP
VIE
W
Alte
rnat
e C
ontro
l Wiri
ng In
let
7/8"
Dia
.
Pow
er W
iring
Inle
t 7/ 8
" Dia
.
Alte
rnat
e P
ower
Wiri
ng In
let
7/8"
Dia
.
20 5
/8"
50 1
/8"
Max
imum
Doo
r Ext
ensi
on
54 3
/4" O
vera
ll
9 1/
2"
28 3
/8"8 5/
8"12
7/8
"
9 5/
8"28 1
/4"36
3/8
"O
vera
ll
RIG
HT
VIE
W10 3
/8"
21 3
/4" O
vera
ll
OA
RAEA
: E
xhau
st A
ir t
o ou
tdoo
rsO
A: O
utdo
or A
ir in
take
RA:
Roo
m A
ir t
o be
exh
aust
edFA
: F
resh
Air
to
insi
de
(800) 627-4499 • Fax: (608) 221-282416
HE1XINV
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 250-925 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V HZ Phase FLA Min. Cir. Amps
Max. Fuse Size
115 60 Single 8.6 19.4 25
208-230 60 Single 4.3 9.7 15
277 60 Single 2.4 5.4 15
208-230 60 Three 2.1 5.2 15
460 60 Three 1.1 2.6 15
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 211 lbs (unit), 250 lbs (shipping weight)
Shipping Dimensions: 44” W x 56” L x 27” H
Indoor Unit Specifications
Motor HPPhase
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
0.75 (Two DD)Single Phase
970 CFM1,490 Watts
925 CFM1,375 Watts
860 CFM1,270 Watts
795 CFM1,160 Watts
720 CFM1,030 Watts
635 CFM 950 Watts
350 CFM 750 Watts
0.75 (Two DD)Three Phase
1,030 CFM1,220 Watts
1,010 CFM1,210 Watts
975 CFM1,160 Watts
880 CFM1,050 Watts
800 CFM 990 Watts
700 CFM 850 Watts
530 CFM 720 Watts
Airflow Performance
G5 PerformanceCFM
250 500 750 1,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
www.RenewAire.com17
HE1X
INV
Un
it D
imen
sio
ns
OA
FARA
EA
RIG
HT
VIE
WFR
ON
T V
IEW
LEFT
VIE
WP
ower
Wiri
ng In
let
7/8"
Dia
.C
ontro
l Wiri
ng In
let
7/8"
Dia
.
20 5/8"
40 3
/8" O
vera
ll
21 3
/4" O
vera
ll10
3/8
"
17"41 1/2"
50 5/8"
17"41 5/8"
10 3
/8"
12 7
/8"
34 7
/8" C
ase
49 1/8" Case
51 3/8" Overall
40 5
/8"
Min
imum
Ser
vice
Are
a(D
oors
can
be
take
n of
f hin
ges.
)
50 1
/8"
Max
imum
Doo
r E
xten
sion
RA FA
OA EA
TOP
VIE
W
Ø12" TYP
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282418
HE2XINH
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-2,000 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two
Drive HP Volts HZ Phase FLA
Min. Cir.
Amps
Max. Fuse Size
DD 0.75
115208-230
277208-230
460
6060606060
SingleSingleSingleThreeThree
8.64.32.42.11.1
36.618.310.29.84.9
4520151515
BD 1.5
208-230208-230
460575
60606060
SingleThreeThreeThree
9.3-9.04.8-4.8
2.41.8
20.910.85.44.1
30151515
BD2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.12.3
25.414.07.05.2
35201515
Control Voltage: 24 VAC
Filters: Four total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 414 lbs (unit), 420 lbs (shipping weight)
Shipping Dimensions: 50” W x 62” L x 41” H
Motor HP Blower RPM Nominal
Turns Open
External Static Pressure (Inches Water Column)0.0 0.25 0.5 0.75 1.0 1.25 1.5
0.75 (Four DD)
Single PhaseN/AN/A
N/AN/A
1,950 CFM2,240 Watts
1,830 CFM2,155 Watts
1,670 CFM2,020 Watts
1,400 CFM1,795 Watts
1,150 CFM1,490 Watts
700 CFM1,190 Watts
- - - -
0.75 (Four DD)
Three PhaseN/AN/A
N/AN/A
1,960 CFM2,500 Watts
1,840 CFM2,300 Watts
1,700 CFM2,125 Watts
1,600 CFM1,900 Watts
1,380 CFM1,700 Watts
1,190 CFM1,500 Watts
800 CFM1,260 Watts
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.5 (BD)1,0001,2301,420
4.520
1,378 0.51,694 0.91,956 1.4
1,175 0.51,550 0.91,850 1.4
900 0.41,335 0.81,680 1.2
635 0.41,125 0.71,475 1.2
- -1,000 0.71,300 1.1
- - 500 0.61,200 1.1
- - - - 930 0.9
2 (BD)1,2201,4701,660
4.520
1,681 0.92,025 1.6 - -
1,530 0.91,925 1.5 - -
1,315 0.71,750 1.42,000 2.0
1,100 0.71,575 1.31,900 1.9
975 0.61,375 1.21,750 1.8
- -1,275 1.21,570 1.7
- -1,125 1.11,475 1.7
Indoor Unit
CFM500 1,000 1,500 2,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Specifications
G5 Performance
Airflow Performance
Note: Brake Horse Power (BHP) is for one blower motor package only.
www.RenewAire.com19
HE2X
INH
Un
it D
imen
sio
ns
EAFA
8"
OA
RA
2 7/8"21 5/8"
36 5/8"
41 1
/4"
54 7
/8" o
vera
ll
60" Service Area
33"59
" Ser
vice
Are
a
49 1
/4" c
ase
34 3/4"E
AFA
15 3/8"
LEFT
VIE
WB
elt D
riven
Ver
sion
LEFT
VIE
WD
irect
Driv
e Ve
rsio
n
FRO
NT
VIE
WR
IGH
T V
IEW
TOP
VIE
W
24" T
YP
14" typ
Filte
rs
35 1/4" Case
3 1/2"20 5/8"2 3/4"
19 5/8"
Wiri
ng E
ntry
7/8"
Dia
.
E-B
ox
RA OA
FA EA
Not
e: D
oor l
ifts
away
.
E-B
ox
Not
e: A
ll du
ct fl
ange
s ar
e 14
" x 2
4".
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282420
HE2XINVIndoor Unit Specifications
CFM500 1,000 1,500 2,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
G5 Performance
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-2,000 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two
Drive HP Volts HZ Phase FLA
Min. Cir.
Amps
Max. Fuse Size
DD 0.75
115208-230
277208-230
460
6060606060
SingleSingleSingleThreeThree
8.64.32.42.11.1
36.618.310.29.84.9
4520151515
BD 1.5
208-230208-230
460575
60606060
SingleThreeThreeThree
9.3-9.04.8-4.8
2.41.8
20.910.85.44.1
30151515
BD2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.12.3
25.414.07.05.2
35201515
Control Voltage: 24 VAC
Filters: Four total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 399 lbs (unit), 420 lbs (shipping weight)
Shipping Dimensions: 48” W x 62” L x 55” H
Motor HP Blower RPM Nominal
Turns Open
External Static Pressure (Inches Water Column)0.0 0.25 0.5 0.75 1.0 1.25 1.5
0.75 (Four DD)
Single PhaseN/AN/A
N/AN/A
1,870 CFM2,160 Watts
1,720 CFM2,070 Watts
1,520 CFM1,900 Watts
1,290 CFM1,715 Watts
1,080 CFM1,505 Watts
700 CFM1,210 Watts
- - - -
0.75 (Four DD)
Three PhaseN/AN/A
N/AN/A
1,870 CFM2,500 Watts
1,720 CFM2,300 Watts
1,540 CFM2,125 Watts
1,350 CFM1,950 Watts
1,240 CFM1,730 Watts
1,030 CFM1,490 Watts
800 CFM1,240 Watts
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.5 (BD)1,0001,2301,420
4.520
1,378 0.51,694 0.91,956 1.4
1,175 0.51,550 0.91,850 1.4
900 0.41,335 0.81,680 1.2
635 0.41,125 0.71,475 1.2
- -1,000 0.71,300 1.1
- - 500 0.61,200 1.1
- - - - 930 0.9
2 (BD)1,2201,4701,660
4.520
1,681 0.92,025 1.6 - -
1,530 0.91,925 1.5 - -
1,315 0.71,750 1.42,000 2.0
1,100 0.71,575 1.31,900 1.9
975 0.61,375 1.21,750 1.8
430 0.61,275 1.21,570 1.7
- -1,125 1.11,475 1.7
Airflow Performance
Note: Brake Horse Power (BHP) is for one blower motor package only.
www.RenewAire.com21
HE2X
INV
Un
it D
imen
sio
ns
TOP
VIE
W a
nd S
ervi
ce A
rea
OARA
FRO
NT
VIE
W
FARA
EAOA
FARA
OA EA
EAFA
RIG
HT
EN
D V
IEW
BE
LT D
RIV
ELE
FT E
ND
VIE
WB
ELT
DR
IVE
RIG
HT
EN
D V
IEW
DIR
EC
T D
RIV
ELE
FT E
ND
VIE
WD
IRE
CT
DR
IVE
8 1/
8"24
"
41 1
/2"
3 1/
2"14"
35 5
/8"
49 1
/8"
35 1
/4"
w/ s
crew
s
38 3
/4"
34 1
/8"
74 7
/8" C
lear
39 1
/4"
43 3
/4"
4 1/
4"
Not
e: A
ll du
ct fl
ange
s ar
e 14
" x 2
4".
E-b
ox p
ower
wire
7/8"
Dia
.5
7/8"
19 3
/8"
6 3/
8"
19 3
/8"
50 5
/8"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282422
HE3XINH
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 750-3,300 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.12.3
25.414.07.05.2
35201515
3
208-230208-230
460575
60606060
SingleThreeThreeThree
13.79.2-8.6
4.33.2
30.820.79.77.2
45301515
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Six total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 675 lbs (unit), 700 lbs (shipping weight)
Shipping Dimensions: 72” W x 84” L x 46” H
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
21,0951,2201,340
420
2,040 1.32,340 1.52,590 1.8
1,760 1.32,110 1.42,370 1.7
1,370 1.21,790 1.32,130 1.6
920 1.11,380 1.21,760 1.4
- - 940 1.21,310 1.3
- - - - 980 1.2
- - - - - -
31,3451,5351,685
4.520
2,420 2.32,850 2.8 - -
2,280 2.22,760 2.7 - -
2,090 2.12,570 2.6 - -
1,760 2.02,380 2.52,660 2.9
1,280 1.92,090 2.42,470 2.7
860 1.91,810 2.22,280 2.6
- -1,330 2.12,000 2.4
51,4951,6751,855
6.53.50
2,850 3.13,280 3.8 - -
2,710 3.03,140 3.7 - -
2.520 2.92,990 3.53,470 4.9
2,280 2.82,800 3.33,330 4.7
2,040 2.72,610 3.13,140 4.5
1,620 2.52,380 2.93,040 4.4
1,140 2.42,090 2.72,760 4.0
Indoor Unit
G5 Performance
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
CFM1,500 2,000 2,500 3,000
80
60
40Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
Specifications
Airflow Performance
www.RenewAire.com23
HE3X
INh
Un
it D
imen
sio
ns
Fron
t Vie
wLe
ft Vi
ew
EA
FA
Rig
ht V
iew
RA
Top
View
OA
EA
FA
5 1/8"
40 3/8"
62 1
/4"
62 1
/4"
22 3/8"40 3/8"
18 5/8"
57 1
/4"
64 1
/2" o
vera
ll
62 1/4"
97" Service Area
64 1
/2"
Ser
vice
Are
a
55 1
/8" C
ontro
l Wiri
ng In
let
E-b
ox
58 1
/8" P
ower
Wiri
ng In
let
39"12
"
5 1/2"12"
E-b
ox
26 1/8"
4 1/
4"
OA
12" X
34"
RA
12" X
34"
Not
e: T
here
are
two
12" x
12"
dis
char
ges.
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282424
HE3XINV
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
21,0951,2201,340
420
1,900 1.32,200 1.52,300 1.7
1,600 1.21,960 1.42,160 1.6
1,250 1.21,610 1.31,950 1.5
850 1.11,240 1.31,580 1.4
- - 860 1.21,150 1.3
- - - - 800 1.2
- - - - - -
31,3451,5351,685
4.520
2,400 2.22,720 2.7 - -
2,250 2.22,450 2.52,870 3.0
1,970 2.12,250 2.42,740 2.9
1,570 2.01,950 2.32,540 2.8
1,170 1.91,650 2.22,340 2.7
900 1.81,200 2.02,090 2.5
- - 875 1.91,800 2.4
51,4951,6751,855
6.53.50
2,850 2.73,230 3.73.520 4.5
2,610 2.63,090 3.53,370 4.3
2.380 2.52,850 3.33,230 4.1
2,090 2.42,610 3.13,090 3.9
1,710 2.22,380 2.92,850 3.6
1,330 2.12,090 2.72,610 3.4
950 2.01,810 2.52,380 3.2
Indoor Unit
G5 Performance
Specifications
Airflow Performance
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
CFM1,500 2,000 2,500 3,000
80
60
40Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 750-3,300 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.12.3
25.414.07.05.2
35201515
3
208-230208-230
460575
60606060
SingleThreeThreeThree
13.79.2-8.6
4.33.2
30.820.79.77.2
45301515
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Six total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 640 lbs (unit), 675 lbs (shipping weight)
Shipping Dimensions: 45” W x 70” L x 70” H
www.RenewAire.com25
HE3X
INV
Un
it D
imen
sio
ns
Fron
t Vie
w
35 1
/4"
62"
3 7/8"
Left
View
EA
61 3
/4"
OA
62"
Rig
ht V
iew
FA
37 1/2"
55 7
/8"
RA
39 3/8" overall
Top
View
61 3
/4" U
nit
95 7
/8" S
ervi
ce A
rea
OA
EA
RA
FA
43 1/4"Service Area
58 1
/8"
61 3
/4"
7/8"
Dia
.W
iring
Ent
ries
E-b
ox
47"
1"1"
47"RA
14" X
28"
FA 1
2" x
12"
OA
14" X
28"
EA
12" x
12"
8 3/4"12"
38 7
/8"
12"
8 3/4"12"
38 7
/8"
12"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282426
HE4XINH
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-4,400 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.52.3
25.414.07.95.2
35201515
3
208-230208-230
460575
60606060
SinlgeThreeThreeThree
13.79.2-8.6
4.33.2
30.820.79.77.2
45301515
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Eight total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 846 lbs (unit), 900 lbs (shipping weight)
Shipping Dimensions: 84” W x 92” L x 46” H
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
21,0101,2101,370
4.520
2,489 0.92,995 1.6 - -
2,200 0.92,290 1.5 - -
1,715 0.82,430 1.4 - -
1,100 0.72,005 1.32,600 2.0
- -1,540 1.22,215 1.9
- - - -1,800 1.7
- - - -1,100 1.5
31,3451,5351,685
4.520
3,295 2.13,832 2.9 - -
3,145 2.13,682 2.9 - -
2,840 2.03,480 2.8 - -
2,509 1.93,170 2.6 - -
2,116 1.82,839 2.43,409 3.0
1,747 1.62,449 2.33,003 2.8
1,135 1.51,878 2.02,465 2.4
51,4951,6751,855
630
3,718 2.74,223 3.8 - -
3,568 2.64,083 3.7 - -
3,345 2.63,943 3.6 - -
3,030 2.43,659 3.44,287 4.9
2,686 2.23,364 3.24,011 4.6
2,301 2.12,994 2.93,760 4.3
1,722 1.92,490 2.73,434 4.0
Indoor Unit
G5 PerformanceCFM
1,000 2,000 3,000 4,000
80
60
40
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Effe
ctiv
enes
s (%
)
Specifications
Airflow Performance
www.RenewAire.com27
HE4X
INh
Un
it D
imen
sio
ns
RA
12" X
40"
25 1/2"
5 1/2"
77 7
/8" P
ower
Wiri
ng In
let
22 3/8"
5 1/8"
Left
View
Fron
t Vie
wR
ight
Vie
w
74 7
/8" C
ontro
l Wiri
ng In
let
82"
40 3/8"
18 5/8"
FAEA
E-b
ox
E-b
ox
116 3/4" Service Area
40 3/8"
OA
12" X
40"
EA
OA
FAR
A
57 1
/4"
82"
4 1/
4"
64 1
/2"
Ser
vice
Are
aTo
p Vi
ew
64 1
/2" o
vera
ll
82"
39"
12" x
32"
typ
OA
RA
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282428
HE4XINV
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
21,0101,2101,370
4.520
2,300 0.92,800 1.53,068 2.2
1,810 0.82,350 1.42,754 2.0
1,300 0.71,950 1.32,430 1.9
- -1,500 1.32,082 1.8
- -1,050 1.21,725 1.7
- - - -1,342 1.6
- - - - - -
31,3451,5351,685
4.520
3,042 2.03,452 2.7 - -
2,705 1.93,226 2.6 - -
2,341 1.82,955 2.5 - -
1,983 1.72,696 2.33,148 2.9
1,611 1.62,422 2.22,884 2.8
1,211 1.52,093 2.02,595 2.6
- -1,722 1.92,269 2.4
51,4951,6751,855
630
3,348 2.73,896 3.9 - -
3,114 2.63,688 3.7 - -
2,820 2.43,466 3.64,229 4.9
2,549 2.33,232 3.43,979 4.6
2,268 2.22,972 3.23,700 4.3
1,917 2.12,694 3.03,430 4.0
1,523 1.92,392 2.83,178 3.8
Indoor Unit
G5 Performance
Specifications
Airflow Performance
CFM1,000 2,000 3,000 4,000
80
60
40
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Effe
ctiv
enes
s (%
)
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-4,400 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.52.3
25.414.07.95.2
35201515
3
208-230208-230
460575
60606060
SinlgeThreeThreeThree
13.79.2-8.6
4.33.2
30.820.79.77.2
45301515
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Eight total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 815 lbs (unit), 875 lbs (shipping weight)
Shipping Dimensions: 45” W x 90” L x 70” H
www.RenewAire.com29
HE4X
INV
Un
it D
imen
sio
ns
OA
FA EA
RA
EA
OA
FA
RA
OA
FAE
A
RA
81 3
/8"
3 7/8"
62"
35 1
/4"
62 1/4"
81 3
/8"
115
1/2"
Ser
vice
Are
a39 3/8"
with flanges
81 1
/2" U
nit
75 1
/2"
37 1/2"Le
ft Vi
ewFr
ont V
iew
Rig
ht V
iew
Top
View
7/8"
Dia
.W
iring
Ent
ries
E-b
ox
1"38 7
/8"
8 1/2"47"
1"38
3/4
"
8 1/2"
12" X
32"
14" X
34"
12" X
32"
14" X
34"
47"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282430
HE6XIN
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,500-6,500 CFM
AHRI 1060 Certified Core: Six L125-00
Airflow Rating Points (for AHRI): 4,500 CFM and 3,375 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
5208-230
460575
606060
ThreeThreeThree
14.2-13.06.55.0
32.614.911.3
452015
7.5208-230
460575
606060
ThreeThreeThree
20.9-19.29.67.6
47.021.617.1
703025
Control Voltage: 24 VAC
Filters: Twelve total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 2,340 lbs (unit), 2,640 lbs (shipping weight)
Shipping Dimensions: 85” W x 114” L x 85” H
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
51,4601,6101,725
4.520
5,005 3.25,550 4.2 - -
4,800 3.25,375 4.2 - -
4,650 3.15,250 4.1 - -
4,475 3.05,100 4.15,525 5.0
4,200 2.94,900 4.05,475 5.0
4,000 2.84,650 3.95,200 4.9
3,750 2.84,500 3.85,050 4.8
7.51,5601,7401,865
4.520
5,275 3.75,950 5.06,500 6.5
5,200 3.65,825 5.06,350 6.5
4,900 3.55,625 4.96,225 6.4
4,775 3.55,490 4.96,125 6.4
4,550 3.45,325 4.85,910 6.3
4,350 3.35,125 4.75,825 6.2
4,125 3.34,950 4.75,625 6.1
Indoor Unit
G5 PerformanceCFM
3,000 4,000 5,000 6,000
80
60
40
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Effe
ctiv
enes
s (%
)
Specifications
Airflow Performance
www.RenewAire.com31
HE6X
INU
nit
Dim
en
sio
ns
62"
112
3/4"
Uni
t Roo
f
108
1/2"
Bas
e
108
1/2"
Bas
e
EA
18"
39 1
/2" M
in.
Cle
aran
ce
85 1
/2" U
nit R
oof
148
1/4"
Ser
vice
Are
a
34"Service Area
FRO
NT
VIE
W
LEFT
VIE
WB
AC
K V
IEW
RIG
HT
VIE
W
4"9"
24"77"
9 1/
2"49
"
24"
typ
22"36"
TOP
VIE
W
OARA
FA
Pow
er a
ndC
ontro
lW
iring
Ent
ries
7/8"
Dia
.
Pow
er a
nd C
ontro
l Wiri
ngE
ntrie
s
EA
Cor
eA
cces
s
FA B
LOW
ER
Out
let i
s 18
" x 2
4".
24" x
36"
Duc
t Fla
nge
is a
lso
supp
lied.
Fiel
d in
stal
l onl
y in
loca
tion
show
n.
62"
IND
OO
R U
NIT
S: E
A B
LOW
ER
Out
let i
s 18
" x 2
4".
24" x
36"
Duc
t Fla
nge
is a
lso
supp
lied.
Fie
ld in
stal
l onl
y in
loca
tion
show
n.
Fron
t Vie
ws
at 0
.5X
:B
LOW
ER
RO
TATI
ON
55"
78 1/4" Overall
151 1/2" Service Area
36"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282432
HE8XIN
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 2,000-8,000 CFM
AHRI 1060 Certified Core: Eight L125-00
Airflow Rating Points (for AHRI): 6,000 CFM and 4,500 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
5208-230
460575
606060
ThreeThreeThree
14.2-13.06.55.0
32.614.911.3
452015
7.5208-230
460575
606060
ThreeThreeThree
20.9-19.29.67.6
47.021.617.1
703025
10208-230
460575
606060
ThreeThreeThree
29.0-26.813.410.0
65.330.222.5
904535
Control Voltage: 24 VAC
Filters: Sixteen total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 2,525 lbs (unit), 2,825 lbs (shipping weight)
Shipping Dimensions: 85” W x 114” L x 85” H
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
51,4601,6101,725
4.52
0.5
5,575 3.26,200 4.36,550 5.0
5,425 3.26,010 4.36,380 5.0
5,200 3.25,875 4.26,210 5.0
5,000 3.25,700 4.26,100 5.0
4,775 3.15,500 4.25,880 4.9
4,550 3.05,325 4.15,730 4.8
4,270 2.95,125 4.15,510 4.8
7.51,5601,7401,865
4.520
6,000 3.96,700 5.3 - -
5,850 3.96,575 5.3 - -
5,650 3.86,400 5.3 - -
5,475 3.86,300 5.36,800 7.5
5,275 3.86,125 5.36,675 7.5
5,100 3.75,950 5.26,500 7.5
4,875 3.75,750 5.26,375 7.4
101,8102,0202,105
4.521
7,000 6.17,850 8.5 - -
6,875 6.17,745 8.5 - -
6,750 6.17,625 8.57,950 9.6
6,600 6.07,450 8.47,800 9.6
6,425 6.07,350 8.47,725 9.6
6,275 6.07,200 8.37,600 9.5
6,100 5.97,050 8.37,450 9.5
CFM2,000 4,000 6,000 8,000
80
60
40
SensibleWinter Total
Summer Total
Indoor Unit
G5 Performance
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Effe
ctiv
enes
s (%
)
Specifications
Airflow Performance
www.RenewAire.com33
HE8X
INU
nit
Dim
en
sio
ns
62"
112
3/4"
Uni
t Roo
f
108
1/2"
Bas
e
108
1/2"
Bas
e
EA
18"
39 1
/2" M
in.
Cle
aran
ce
85 1
/2" U
nit R
oof
148
1/4"
Ser
vice
Are
a
34"Service Area
FRO
NT
VIE
W
LEFT
VIE
WB
AC
K V
IEW
RIG
HT
VIE
W
4"9"
24"77"
9 1/
2"49
"
24"
typ
22"36"
TOP
VIE
W
OARA
FA
Pow
er a
ndC
ontro
lW
iring
Ent
ries
7/8"
Dia
.
Pow
er a
nd C
ontro
l Wiri
ngE
ntrie
s
EA
Cor
eA
cces
s
FA B
LOW
ER
Out
let i
s 18
" x 2
4".
24" x
36"
Duc
t Fla
nge
is a
lso
supp
lied.
Fiel
d in
stal
l onl
y in
loca
tion
show
n.
62"
IND
OO
R U
NIT
S: E
A B
LOW
ER
Out
let i
s 18
" x 2
4".
24" x
36"
Duc
t Fla
nge
is a
lso
supp
lied.
Fie
ld in
stal
l onl
y in
loca
tion
show
n.
Fron
t Vie
ws
at 0
.5X
:B
LOW
ER
RO
TATI
ON
55"
78 1/4" Overall
151 1/2" Service Area
36"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282434
Commercial
OutDOOR Products
Many airflow orientation options.•
Weatherized cabinets with hoods for • outdoor applications.
Wide range of airflow and static capacities.•
Easy installation and service.•
AHRI certified performance data for • efficiency and cross leakage.
UL tested flammability and • smoke generation that meets NFPA 90A and 90B test standards for commercial applications.
Ten year core warranty.•
RenewAire means Trouble-Free ERV.
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
Contact RenewAire for other application schematics.
www.RenewAire.com35
Part I - General
A. Product Specification
1.Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured by RenewAire and shall transfer both heat and humidity using static plate core technology. B. Quality Assurance
1.The energy recovery cores used in these products shall be third party Certified by AHRI under its Standard 1060 for Energy Recovery Ventilators. AHRI published certifications shall confirm manufacture’s published performance for airflow, static pressure, temperature and total effectiveness, purge air (OACF) and exhaust air leakage (EATR). Products that are not currently AHRI Certified will not be accepted.
2. Manufacturer shall be able to provide evidence of independent testing of the core by Underwriters Laboratory (UL), verifying a maximum flame spread index (FSI) of 25 and a maximum smoke developed index (SDI) of 50 thereby meeting NFPA 90A and NFPA 90B requirements for materials in a compartment handling air intended for circulation through a duct system. The method of test shall be UL Standard 723.
3. Unit shall be Listed under UL 1812 Standard for Ducted Air to Air Heat Exchangers (Note that a few low volume product or product configurations are not UL Listed). Units intended for “Outdoor Use” shall be listed using the specific UL requirements for rain penetration, corrosion protection and seal durability and shall be so labeled.
4. The ERV core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. The balance-of-unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase.
Part II – Performance
A. Energy TransferThe ERV shall be capable of transferring both sensible and latent energy between airstreams. Latent energy transfer shall be accomplished by direct water vapor transfer from one airstream to the other, without exposing transfer media in succeeding cycles directly to the exhaust air and then to the fresh air.
B. Passive Frost ControlThe ERV core shall perform without condensing or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional more extreme conditions shall not affect the usual function, performance or durability of the core. No condensate drains will be allowed.
C. Continuous VentilationUnit shall have the capacity to operate continuously without the need for bypass, recirculation, pre-heaters or defrost cycles under normal operating conditions.
D. Positive Airstream SeparationWater vapor transfer shall be through molecular transport by hydroscopic resin and shall not be accomplished by “porous plate” mechanisms. Exhaust and fresh airstreams shall travel at all times in separate passages, and airstreams shall not mix.
E. Laminar FlowAirflow through the ERV core shall be laminar over the products entire operating airflow range, avoiding deposition of particulates on the interior of the energy exchange plate material.
Part III – Product
A. Construction
1. The energy recovery component shall be of fixed-plate cross-flow construction, with no moving parts.
2. No condensate drain pans or drains shall be allowed and unit shall be capable of operating in both winter and summer conditions without generating condensate.
3. The unit case shall be constructed of G90 galvanized, 20-gauge steel, with lapped corners and zinc plated screw fasteners. The unit roof shall be one piece or have watertight standing seam joints and shall overlap wall panels and doors in order to positively shed water.
4. Access doors shall provide easy access to blowers, ERV cores and filters. Doors shall have an airtight compression seal using closed cell foam gaskets rated for outdoor exposure.
5. Weatherhoods shall be screened to exclude birds and animals. Inlet weatherhoods shall be sized to maintain inlet velocities below 500 fpm, and equipped with rain excluder baffles.
6. Case walls and doors shall be insulated with 1 inch, 4 pound density, foil/scrim faced, high-density fiberglass board insulation, providing a cleanable surface and eliminating the possibility of exposing the fresh air to glass fibers.
7. The ERV cores shall be protected by a MERV-8 rated, 2” nominal, pleated, disposable filter in both airstreams.
8. Unit shall have single-point power connection and a single-point 24 VAC contactor control connection (Except Inverter Ready units that have terminal connections for an independent inverter for each airstream).
9. Blower motors shall be EPACT compliant for energy efficiency and be thermally protected or supplied with external starters.
10. Blowers shall be quiet running, forward curve type and be either direct drive or belt drive. HE6X and HE8X units use backward incline, belt drive blower packages. Belt drive motors shall be provided with adjustable pulleys and motor mounts allowing for proper belt tensioning. B. Options (Select options based on application requirements)
1. Provide unit and duct connection orientation per project schedule.
2. Provide double wall construction with 24-gauge galvanized steel liner.
3. Units are available single or three phase at a full range of operating voltages. See project schedule.
4. Provide motor horsepower as specified in project schedule.
5. Provide “inverter-ready” units which include shielded power wiring and terminal connections for inverters (inverters provided and installed by others).
6. Provide factory installed fused disconnects.
7. Provide factory installed non-fused disconnects.
8. Provide factory installed transformer/relay package to supply a 24VAC power source.
9. Provide factory installed filter monitors for each airstream.
10. Provide 14 inch high, non-pitched roof curbs as available from the factory. Pitched curbs, vibration curbs, seismic curbs and other custom curbs are available directly from curb manufacturer.
11. RTC (RoofTop Connect) units shall have return air and fresh air ducts configured to permit direct tie-in to rooftop air handlers using factory offered transition piece. (See separate specification for factory transition availability.)
12. Provide high wind tie-down kit.
Packaged Rooftop Energy Recovery Ventilators: EV450RT, HE1XRT, HE2XRT, HE3XRT, HE4XRT, HE6XRT & HE8XRT
(800) 627-4499 • Fax: (608) 221-282436
EV450RT
Dimensions
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 240-550 CFM
AHRI 1060 Certified Core: One L85
Airflow Rating Points (for AHRI): 450 CFM and 338 CFM
Motors: One, 0.6 hp (Single Phase) One, 0.5 hp (Three Phase)
V HZ Phase FLA
115 60 Single 7.0
208-230 60 Single 3.5
277 60 Single 2.4
208-230 60 Three 1.7-1.5
460 60 Three 0.8
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 14” x 20” nominal size
Weight: 185 lbs (unit), 235 lbs (shipping weight)
Shipping Dimensions: 48” W x 90” L x 25” H (on pallet)
Airflow CFM
ESP in H20
Watts1P 3P
Temp EFF%
Total EFF%Winter/Summer*
240 1.00 425 243 80 75/66
338 0.85 474 313 77 71/61
380 0.75 496 345 75 69/59
450 0.50 534 412 73 66/56
500 0.25 563 461 71 64/54
550 0.00 593 516 70 62/52
600 -0.25 623 572 68 60/50
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Outdoor Unit Specifications
G5 Performance
74 7/8
19 1/4OA
EA
OAEA
RAFA
RIGHT VIEW
47 7/8
1
4 3/4
4 3/81
33 7/8 12 3/8
PWR ANDCONTROL WIRING
DRILL HEREOR THRU BOTTOM
2 7/83 1/8
LEFT VIEW 3 1/8
EBOX
RAFRONTVIEWFA
37 1/2
TOP VIEW WITH DOOR OFF
FILTERS
2 5/813 1/82 3/4
11 3/4
8 3/45 1/2
10 1/4
4 1/2
www.RenewAire.com37
The RTH/RTC Adapter allows horizontal connection of both the Fresh Air and the Return Air ducts. It is also possible to connect the adapter directly to the return plenum of most Rooftop Units (openings must be cut into RTU). Duct openings to be field cut into adapter. Opening location and size is flexible.
For horizontal connection of either the Fresh Air duct or the Return Air duct, stack the optional RTF/RTR Adapter on the Standard Roof Curb. Duct openings to be field cut into adapter. Opening location and size is flexible.
Standard Roof Curb Shown (available option). Curbs for sloped roofs or metal roofing are available on a custom basis from RenewAire or from local curb fabricators.
EV450RTApplication options
EA: Exhaust Air to outdoorsOA: Outdoor Air intakeRA: Room Air to be exhaustedFA: Fresh Air to inside
(800) 627-4499 • Fax: (608) 221-282438
HE1XRT
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 250-870 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V HZ Phase FLA Min. Cir. Amps
Max. Fuse Size
115 60 Single 8.6 19.4 25
208-230 60 Single 4.3 9.7 15
277 60 Single 2.4 5.4 15
208-230 60 Three 2.1 5.2 15
460 60 Three 1.1 2.6 15
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 250 lbs (unit), 330 lbs (shipping weight)
Shipping Dimensions: 31” W x 76” L x 45” H
Options: Controls (see pages 64 & 65) Roof curb Alternate duct connections
Outdoor Unit Specifications
OA
RAFA
EA
RTV
OA
RA
FA
EA
RTF
Base Type/Airflow Orientations
OA
RA
EA
FA
RTR
OA
RA
EA
FA
RTH
Motor HPPhase
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
0.75 (Two DD)Single Phase
950 CFM1,630 Watts
880 CFM1,550 Watts
820 CFM1,475 Watts
775 CFM1,430 Watts
730 CFM1,385 Watts
650 CFM 1,300 Watts
540 CFM 1,200 Watts
0.75 (Two DD)Three Phase
950 CFM1,200 Watts
880 CFM1,100 Watts
820 CFM1,020 Watts
760 CFM 980 Watts
660 CFM 890 Watts
560 CFM 800 Watts
450 CFM 700 Watts
G5 PerformanceCFM
250 500 750 1,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
*At AHRI 1060 standard conditions(See certified data on page 67 for core components.)
Airflow Performance
www.RenewAire.com39
CURB
1X
HE1X
RT
Un
it D
imen
sio
ns
ON
LYR
TH, R
TFR
AOA
FAR
TV, R
TFO
NLY
RTV
, RTR
ON
LY
RA
RTH
, RTR
EA
FAO
NLY
RA
(RTH
,RTF
)12
" x 1
2"
OA
FA (R
TH,R
TR)
12" x
12"
Con
trol W
iring
Inle
t7/
8" D
ia.
Pow
er W
iring
Inle
t7/
8" D
ia.
Ser
vice
Are
a
RA
(RTV
,RTR
)12
" x 1
2"
FA (R
TV,R
TF)
12" x
12"
RIG
HT
VIE
WFR
ON
TV
IEW
LEFT
VIE
W
TOP
VIE
W
10 3/8"17 3/8" Control
19 1/4" Power
22 1/2"56 1/8"
4"14
3/4
"29
1/2
"44 1
/4"55
"63 7
/8"
4 7/8"
40 1/4"
3"4
3/8" 4 7/8"
9"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282440
HE1XRTC
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-1,000 CFM
AHRI 1060 Certified Core: One L125-00
Airflow Rating Points (for AHRI): 750 CFM and 560 CFM
Number Motors: Two
V HZ Phase FLA Min. Cir. Amps
Max. Fuse Size
115 60 Single 8.6 19.4 25
208-230 60 Single 4.3 9.7 15
277 60 Single 2.4 5.4 15
208-230 60 Three 2.1 5.2 15
460 60 Three 1.1 2.6 15
Control Voltage: 24 VAC
Filters: Two total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 300 lbs (unit), 375 lbs (shipping weight)
Shipping Dimensions: 40” W x 87” L x 45” H
Damper Position
Total Watts Static Pressure in Adjacent Air Handler (Inches Water Column)
-0.5 -0.25 0.0 +0.25 +0.51 Phase 3 Phase
EA FA EA FA EA FA EA FA EA FA
100% Open 1,295 1,155 855 1,035 900 985 950 940 985 885 1,045 835
65% Open 1,285 1,140 785 980 820 945 855 900 890 855 935 810
55% Open 1,275 1,130 775 965 805 920 840 875 865 835 900 790
45% Open 1,265 1,120 750 920 775 875 805 935 830 790 860 750
35% Open 1,265 1,110 695 860 730 820 760 775 790 740 820 700
25% Open 1,265 1,100 625 780 660 750 685 715 715 680 750 650
15% Open 1,260 1,085 575 585 615 630 650 665 685 705 730 745
CFM300 500 700 900
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter Total
Summer Total
Outdoor Unit
G5 Performance
Specifications
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
Airflow Performance
www.RenewAire.com41
HE1X
RTC
Un
it D
imen
sio
ns
RA
EA
Ser
vice
Are
a
RIG
HT
VIE
W
FRO
NT
VIE
WS
how
n w
ith L
evel
ing
Legs
(shi
pped
loos
e)LE
FT V
IEW
TOP
VIE
W
22 1/2"
56 1/8"
21 1
/8"
72"
40 1/4"
FA RA
FA
OA
EA
RA
FA
OA
OA
9"
14 1
/2" t
o 17
1/2
"he
ight
adj
ustm
ent
19 7
/8"
Lifti
ng L
ugs
46 3
/8"
Lifti
ng L
ugs
Pow
er W
ire In
7/8"
Dia
.
Con
trol W
ire In
7/8"
Dia
.
51"
Acc
ess
to b
low
ers
Acc
ess
to
Ele
ctric
al
Com
pone
nts,
OA
filte
r
6 5/
8"
11"
3 1/
2"
11"
9"
16"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282442
HE2XRTOutdoor Unit
G5 Performance
Specifications
CFM500 1,000 1,500 2,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 500-2,000 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Direct Drive (DD) Four, Belt Drive (BD) Two
Drive HP Volts HZ Phase FLA
Min. Cir.
Amps
Max. Fuse Size
DD 0.75
115208-230
277208-230
460
6060606060
SingleSingleSingleThreeThree
8.64.32.42.11.1
36.618.310.29.84.9
4520151515
BD 1.5
208-230208-230
460575
60606060
SingleThreeThreeThree
9.3-9.04.8-4.8
2.41.8
20.910.85.44.1
30151515
BD2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.12.3
25.414.07.05.2
35201515
Control Voltage: 24 VAC
Filters: Four total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 488 lbs (unit), 525 lbs (shipping weight)
Shipping Dimensions: 51” W x 76” L x 45” H
OA
RAFA
EA
RTV
OA
RA
FA
EA
RTF
Base Type/Airflow Orientations
OA
RA
EA
FA
RTR
OA
RA
EA
FA
RTH
Motor HP Blower RPM Nominal
Turns Open
External Static Pressure (Inches Water Column)0.0 0.25 0.5 0.75 1.0 1.25 1.5
0.75 (Four DD)
Single PhaseN/AN/A
N/AN/A
1,770 CFM2,220 Watts
1,680 CFM2,145 Watts
1,555 CFM2,015 Watts
1,375 CFM1,825 Watts
1,110 CFM1,560 Watts
760 CFM1,195 Watts
- - - -
0.75 (Four DD)
Three PhaseN/AN/A
N/AN/A
1,760 CFM2,300 Watts
1,670 CFM2,200 Watts
1,550 CFM2,050 Watts
1,375 CFM1,825 Watts
1,120 CFM1,530 Watts
850 CFM1,375 Watts
500 CFM 950 Watts
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.5 (BD)1,0001,2301,420
4.520
1,378 0.51,694 0.91,956 1.4
1,175 0.51,550 0.91,850 1.4
900 0.41,335 0.81,680 1.2
635 0.41,125 0.71,475 1.2
- -1,000 0.71,300 1.1
- - 500 0.61,200 1.1
- - - - 930 0.9
2 (BD)1,2201,4701,660
4.520
1,681 0.92,025 1.6 - -
1,530 0.91,925 1.5 - -
1,315 0.71,750 1.42,000 2.0
1,100 0.71,575 1.31,900 1.9
975 0.61,375 1.21,750 1.8
430 0.61,275 1.21,570 1.7
- -1,125 1.11,475 1.7
Airflow Performance
Note: Brake Horse Power (BHP) is for one blower motor package only.
www.RenewAire.com43
HE2X
RT
Un
it D
imen
sio
ns
20 1/8"Curb
Center
34 7/8"control
37 3/8"power
42 1/4"
76 1/8"
10 5
/8"
25 1
/2"
Cur
bC
ente
r
51 1
/8"
72 3
/8"
15 3
/4"
15 3
/4"
3 3/
4"
4 5/8"
7 1/
4"
40 1
/4"
39 3/8"
3"Top ofCurb
43 1
/4"
FRO
NT
VIE
WLE
FT V
IEW
RIG
HT
VIE
W
TOP
VIE
W
Ser
vice
Are
a
RA
(RTV
RTR
)10
" X 2
4"FA
(RTV
, RTF
)10
" X 2
4"
FA (R
TH, R
TR)
14" X
24"
RA
(RTH
, RTF
)14
" X 2
4"O
A
EA
OA
EA
RA
FA
RTV
, RTF
O
NLY
RTV
, RTR
O
NLY
FAR
TH, R
TR
ON
LYR
TH, R
TFO
NLY
RA
4" Wiring Inlet Pow
er W
iring
Inle
t7/
8" D
ia.
Con
trol W
iring
Inle
t7/
8" D
ia.
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
CURB
2X
(800) 627-4499 • Fax: (608) 221-282444
HE2XRTC
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-1,700 CFM
AHRI 1060 Certified Core: Two L125-00
Airflow Rating Points (for AHRI): 1,500 CFM and 1,120 CFM
Number Motors: Two, Belt Drive
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
BD2 208-230 60 Single 11.3-10.5 25.4 35
BD2
208-230460575
606060
ThreeThreeThree
6.2-6.23.12.3
14.07.05.2
201515
Control Voltage: 24 VAC
Filters: Four total, MERV 8, 2” pleated, two 20” x 20” nominal size, and two 14” x 20” nominal size
Weight: 538 lbs (unit), 575 lbs (shipping weight)
Shipping Dimensions: 51” W x 76” L x 45” H
Blower RPM Nominal Turns Open
Static Pressure in Adjacent Air Handler (Inches Water Column)-0.5 -0.25 0.0 +0.25 +0.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Exhaust Air
1,420 0 1,700 1.8 1,850 1.9 - - - - - -
1,360 1 1,540 1.7 1,720 1.8 1,860 1.9 1,920 2.0 1,980 2.0
1,300 2 1,375 1.5 1,600 1.7 1,740 1.8 1,800 1.8 1,860 1.9
1,240 3 1,240 1.4 1,440 1.6 1,625 1.7 1,690 1.7 1,740 1.7
1,180 4 1,080 1.3 1,300 1.4 1,500 1.5 1,575 1.6 1,640 1.6
Fresh Air
1,675 0 - - - - 1,630 2.0 1,575 2.0 1,465 1.9
1,595 1 1,720 2.0 1,620 2.0 1,530 1.9 1,440 1.8 1,355 1.7
1,515 2 1,630 1.9 1,520 1.8 1,430 1.8 1,355 1.7 1,230 1.6
1,435 3 1,530 1.8 1,430 1.7 1,320 1.7 1,250 1.6 1,135 1.5
1,355 4 1,415 1.6 1,310 1.6 1,225 1.5 1,150 1.5 1,035 1.4
Outdoor Unit
G5 Performance
Specifications
Airflow Performance
CFM500 1,000 1,500 2,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
www.RenewAire.com45
HE2X
RTC
Un
it D
imen
sio
ns
RIG
HT
VIE
W
57 3
/4"
RAFA
EA
FA RA
EA
OA
EA
FA RA
42 1
/4"
4 1/
2"29
"
1 7/8"
7 3/
4" to
10
1/2"
he
ight
adj
ustm
ent
7 1/8"
21 3/4"11 1/8" typ
39 1/4"
39 1/4"
32"37 1/4"39 1/4"
39 1/4"
57 3
/4"
75 1
/8"
42 3
/8"
40 1
/8"
60 3
/8"
75 1
/8"
37 1/4"LiftingLugs
101" Service Area76
"52 3
/4"
Lifti
ng L
ugs
each
cor
ner
OA
FA RA
EA
FRO
NT
VIE
Wsh
own
with
leve
ling
legs
(shi
pped
loos
e)
LEFT
VIE
WB
AC
K V
IEW
TOP
VIE
W a
nd
serv
ice
area
Con
trol W
iring
In7/
8" D
ia.
Pow
er W
iring
In7/
8" D
ia.
Filte
r Acc
ess
OA
59"
C-C
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282446
HE3XRT
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
21,0951,2201,340
420
2,040 1.32,340 1.52,590 1.8
1,760 1.32,110 1.42,370 1.7
1,370 1.21,790 1.32,130 1.6
920 1.11,380 1.21,760 1.4
- - 940 1.21,310 1.3
- - - - 980 1.2
- - - - - -
31,3451,5351,685
4.520
2,420 2.32,850 2.8 - -
2,280 2.22,760 2.7 - -
2,090 2.12,570 2.6 - -
1,760 2.02,380 2.52,660 2.9
1,280 1.92,090 2.42,470 2.7
860 1.91,810 2.22,280 2.6
- -1,330 2.12,000 2.4
51,4951,6751,855
6.53.50
2,850 3.13,280 3.8 - -
2,710 3.03,140 3.7 - -
2.520 2.92,990 3.53,470 4.9
2,280 2.82,800 3.33,330 4.7
2,040 2.72,610 3.13,140 4.5
1,620 2.52,380 2.93,040 4.4
1,140 2.42,090 2.72,760 4.0
Outdoor Unit
G5 Performance
Specifications
Airflow Performance
CFM1,500 2,000 2,500 3,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 750-3,000 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.12.3
25.414.07.05.2
35201515
3
208-230208-230
460575
60606060
SingleThreeThreeThree
13.79.2-8.6
4.33.2
30.820.79.77.2
45301515
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Six total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 726 lbs (unit), 755 lbs (shipping weight)
Shipping Dimensions: 72” W x 84” L x 49” H
OA
RAFA
EA
RTV
OA
RA
FA
EA
RTF
Base Type/Airflow Orientations
OA
RA
EA
FA
RTR
OA
RA
EA
FA
RTH
www.RenewAire.com47
CURB
3X
HE3X
RT
Un
it D
imen
sio
ns
Left
View
FA
Fron
t Vie
w
Rig
ht V
iew
Top
View
RA
OA
RA
FA
FA
97"
Ser
vice
Are
a
RA
(RTV
, RTR
Onl
y)11
" x 3
4"
8 1/8"14 3/4"
RA
17 1
/2"
18 3
/8"
28 3
/4"
Cur
b C
ente
r
30 1
/8"
Cur
b C
ente
r
EA
FA(R
TV, R
TF O
nly)
12" x
12"
64 1
/2" S
ervi
ce A
rea
40 3
/8"
4 1/
8"
5 1/8"
34" X
12"
RA
Inle
t(R
TH, R
TF)
62 1
/4"
Ove
rall
4"Top of Curb
OA
Inle
t
60 1
/4"
89 3
/4" O
vera
ll
9"
57"
2"
21 3
/4"
12" X
12"
FA O
utle
t(R
TH, R
TR)
EA
Out
let
40 3
/8"
5 1/2"
58 1
/8" P
ower
Wire
Inle
t55
1/8
" Con
trol W
ire In
let
12"
38 3
/4"
18 5/8"
Wiri
ng In
7/8"
Dia
.
E-b
ox
EA
55 1
/4" l
ift lu
gs60
1/4
" lift
lugs
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282448
HE3XRTC
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,700-2,500 CFM
AHRI 1060 Certified Core: Three L125-00
Airflow Rating Points (for AHRI): 2,250 CFM and 1,690 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
3 208-230 60 Single 13.7-13.7 30.8 45
3208-230
460575
606060
ThreeThreeThree
9.2-8.64.43.2
20.79.97.2
301515
Control Voltage: 24 VAC
Filters: Five total, MERV 8, 2” pleated, three 20” x 20”and two 16” x 25” nominal size
Weight: 775 lbs (unit), 830 lbs (shipping weight)
Shipping Dimensions: 72” W x 84” L x 50” H
Blower RPM Nominal Turns Open
Static Pressure in Adjacent Air Handler (Inches Water Column)-0.5 -0.25 0.0 +0.25 +0.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Exhaust Air
1,520 0 - - - - - - - - - -
1,465 1 2,130 2.9 - - - - - - - -
1,405 2 2,000 2.5 2,245 2.8 2,455 3.0 - - - -
1,345 3 1,915 2.3 2,135 2.6 2,345 2.7 2,475 2.8 2,575 2.9
1,285 4 1,725 1.8 1,950 2.1 2,180 2.3 2,345 2.4 2,455 2.5
Fresh Air
1,800 0 2,565 3.0 2,385 2.9 2,225 2.8 2,065 2.7 1,830 2.4
1,740 1 2,480 2.8 2,290 2.7 2,150 2.6 1,975 2.5 1,740 2.2
1,680 2 2,375 2.6 2,210 2.5 2,070 2.4 1,910 2.3 1,645 2.0
1,620 3 2,290 2.4 2,125 2.4 1,990 2.3 1,825 2.1 1,555 1.8
1,560 4 2,200 2.1 2,040 2.1 1,910 2.0 1,725 1.9 1,450 1.5
SpecificationsOutdoor Unit
G5 Performance
Airflow Performance
CFM1,500 2,000 2,500 3,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
www.RenewAire.com49
HE3X
RTC
Un
it D
imen
sio
ns
Fron
t Vie
wLe
ft Vi
ew
RAFA
Bac
k Vi
ew
EA
OA
EA
FA
OA
EARA RAFA
RAFA
OA
EA
120"
Ser
vice
Are
a
83 7
/8"
Ser
vice
Are
a
6 1/
2" 25 1
/2"
45"
57 1
/2"
81 1
/4"
Rig
ht V
iew
Cor
e an
d E
A B
low
er A
cces
s
OA
Blo
wer
and
Fi
lter A
cces
s
33 1
/8"57
"74
1/2
"
40"
42"
45"
28 1
/4"
Wiri
ng In
7/8"
Dia
.
E-b
ox A
cces
s
OA
Blo
wer
and
Filte
r Acc
ess
RA
Filte
r Acc
ess
EA
Blo
wer
Acc
ess
29"
Top
View
OA
36 3
/8"
Ser
vice
Are
a
61 3
/4"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282450
HE4XRT
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
21,0101,2101,370
4.520
2,489 0.92,995 1.6 - -
2,200 0.92,290 1.5 - -
1,715 0.82,430 1.4 - -
1,100 0.72,005 1.32,600 2.0
- -1,540 1.22,215 1.9
- - - -1,800 1.7
- - - -1,100 1.5
31,3451,5351,685
4.520
3,295 2.13,832 2.9 - -
3,145 2.13,682 2.9 - -
2,840 2.03,480 2.8 - -
2,509 1.93,170 2.6 - -
2,116 1.82,839 2.43,409 3.0
1,747 1.62,449 2.33.003 2.8
1,135 1.51,878 2.02,465 2.4
51,4951,6751,855
630
3,718 2.74,223 3.8 - -
3,568 2.64,083 3.7 - -
3,345 2.63,943 3.6 - -
3,030 2.43,659 3.44,287 4.9
2,686 2.23,364 3.24,011 4.6
2,301 2.12,994 2.93,760 4.3
1,722 1.92,490 2.73,434 4.0
Outdoor Unit
G5 Performance
Airflow Performance
CFM1,000 2,000 3,000 4,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
SpecificationsVentilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,000-4,400 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
2
208-230208-230
460575
60606060
SingleThreeThreeThree
11.3-10.56.2-6.2
3.52.3
25.414.07.95.2
35201515
3
208-230208-230
460575
60606060
SinlgeThreeThreeThree
13.79.2-8.6
4.33.2
30.820.79.77.2
45301515
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Eight total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 915 lbs (unit), 1,000 lbs (shipping weight)
Shipping Dimensions: 84” W x 92” L x 49” H
OA
RAFA
EA
RTV
OA
RA
FA
EA
RTF
Base Type/Airflow Orientations
OA
RA
EA
FA
RTR
OA
RA
EA
FA
RTH
www.RenewAire.com51
CURB
4X
HE4X
RT
Un
it D
imen
sio
ns
Left
View
Fron
t Vie
w
Rig
ht V
iew
Top
View
RA
OA
RA
FA
FA
117
1/4"
Ser
vice
Are
a
RA
(RTV
, RTR
Onl
y)11
" x 4
6"
12 1/4" 14 3/4"
17 3
/4"
18 5
/8"
28 3
/4" C
urb
Cen
ter
40 1
/8"
Cur
b C
ente
r
64 1
/2" S
ervi
ce A
rea
40 3
/8"
4"
5 1/8"
12" X
40"
RA
Inle
t(R
TH, R
TF)
82" O
vera
ll
4"Top of Curb
OA
Inle
t
80"
89 3
/4" O
vera
ll
9"
57"
2"
21 3
/4"
12" X
32"
FA O
utle
t(R
TH, R
TR)
EA
Out
let
40 3
/8" 5 1/2"
77 3
/4" P
ower
Wire
Inle
t74
3/4
" Con
trol W
ire In
let
38 3
/4"
18 5/8"
Wiri
ng In
7/8"
Dia
.
E-b
ox
EA
12" X
32"
FA (R
TV, R
TF)
55 1
/4" l
ift lu
gs79
3/4
" lift
ing
lugs
82 1
/4"
Uni
t
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282452
HE4XRTC
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 2,500-3,700 CFM
AHRI 1060 Certified Core: Four L125-00
Airflow Rating Points (for AHRI): 3,000 CFM and 2,250 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
5208-230
460575
606060
ThreeThreeThree
14.0-13.06.55.0
31.514.611.3
452015
Control Voltage: 24 VAC
Filters: Six total, MERV 8, 2” pleated, four 20” x 20”, and two 16” x 25” nominal size
Weight: 965 lbs (unit), 1,050 lbs (shipping weight)
Shipping Dimensions: 84” W x 92” L x 50” H
SpecificationsOutdoor Unit
Blower RPM
Nominal
Turns Open
Static Pressure in Adjacent Air Handler (Inches Water Column)-0.5 -0.25 0.0 +0.25 +0.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Exhaust Air
1,600 0 3,700 3.6 4,000 3.8 4,250 4.3 - - - -
1,555 1 3.575 3.5 3.900 3.6 4,220 3.9 4,325 4.3 4,380 4.6
1,515 2 3,415 3.2 3,740 3.5 4,135 3.8 4,275 4.2 4,340 4.5
1,470 3 3,235 2.9 3,600 3.2 4,000 3.6 4,215 4.0 4,300 4.3
1,430 4 3,085 2.7 3,455 3.0 3,820 3.2 4,140 3.6 4,260 3.8
1,385 5 2,980 2.5 3,280 2.7 3,640 2.9 3,985 3.2 4,170 3.4
1,340 6 2,880 2.3 3,135 2.5 3,475 2.7 3,840 2.9 4,080 3.0
Fresh Air
1,805 1 - - - - - - - - 3,210 4.9
1,755 2 - - - - 3,410 4.9 3,190 4.6 3,110 4.3
1,705 3 3,710 5.0 3,585 4.9 3,310 4.5 3,130 4.2 3,010 3.9
1,655 4 3,600 4.8 3,470 4.6 3,210 4.2 3,030 3.8 2,910 3.6
1,605 5 3,510 4.3 3,335 4.1 3,110 3.7 2,920 3.4 2,800 3.2
1,555 6 3,400 3.9 3,220 3.8 3,010 3.4 2,810 3.2 2,710 3.0
G5 Performance
Airflow Performance
CFM1,000 2,000 3,000 4,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
www.RenewAire.com53
HE4X
RTC
Un
it D
imen
sio
ns
80 3
/4"
82 1
/4" S
ervi
ce A
rea
OA
Blo
wer
and
Fi
lter A
cces
s
Cor
e an
d E
AB
low
er A
cces
s
RAFA
OAOA
EA
139
1/2"
Ser
vice
Are
a EAOA
57 1
/2"
81 3
/4"
5 1/
2"
Rig
ht V
iew
25 1
/2"
6 1/
2"
RAFA
RAFA45
"
RAFA
40"
42"
33 1
/8"
57"
74 1
/2"
11 1
/4" t
yp
37"
E-b
ox A
cces
s
OA
Blo
wer
and
Filte
r Acc
ess
Wiri
ng In
7/8"
Dia
.
EA
Blo
wer
Acc
ess
RA
Filte
rA
cces
s
Fron
t Vie
wLe
ft Vi
ewB
ack
View
Top
View
46 1
/2"
OA
36 3
/8"
Ser
vice
Are
a
EAEA
82 1
/4"
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282454
HE6XRT
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
51,4601,6101,725
4.520
5,005 3.25,550 4.2 - -
4,800 3.25,375 4.2 - -
4,650 3.15,250 4.1 - -
4,475 3.05,100 4.15,525 5.0
4,200 2.94,900 4.05,475 5.0
4,000 2.84,650 3.95,200 4.9
3,750 2.84,500 3.85,050 4.8
7.51,5601,7401,865
4.520
5,275 3.75,950 5.06,500 6.5
5,200 3.65,825 5.06,350 6.5
4,900 3.55,625 4.96,225 6.4
4,775 3.55,490 4.96,125 6.4
4,550 3.45,325 4.85,910 6.3
4,350 3.35,125 4.75,825 6.2
4,125 3.34,950 4.75,625 6.1
SpecificationsOutdoor Unit
G5 Performance
Airflow Performance
CFM3,000 4,000 5,000 6,000
80
60
40
SensibleWinter Total
Summer Total
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 1,500-6,500 CFM
AHRI 1060 Certified Core: Six L125-00
Airflow Rating Points (for AHRI): 4,500 CFM and 3,375 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
5208-230
460575
606060
ThreeThreeThree
14.2-13.06.55.0
32.614.911.3
452015
7.5208-230
460575
606060
ThreeThreeThree
20.9-19.29.67.6
47.021.617.1
703025
Control Voltage: 24 VAC
Filters: Twelve total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 2,340 lbs (unit), 2,640 lbs (shipping weight)
Shipping Dimensions: 85” W x 114” L x 85” H
OA
RAFA
EA
RTV
OA
RA
FA
EA
RTF
Base Type/Airflow Orientations
OA
RA
EA
FA
RTR
OA
RA
EA
FA
RTH
www.RenewAire.com55
CURB
6X
HE6X
RT
Un
it D
imen
sio
ns
62"
34" Min.Clearance
112
3/4"
Uni
t Roo
f
108
1/2"
Bas
e
78 1/4" Overall
49"
81 1
/2" B
ase
24"
108
1/2"
Bas
e
EA
18"
39 1
/2" M
in.
Cle
aran
ce
85 1
/2" U
nit R
oof
160
1/4"
Ser
vice
Are
a
165" Service Area
12"41 3/4"
FRO
NT
VIE
WB
low
er A
cces
sB
AC
K V
IEW
LEFT
VIE
W
RIG
HT
VIE
W
4"9"
24"77"
4"22"
36"
TOP
VIE
W
(RTF
,RTH
Onl
y)
(RTV
,RTR
)
RA
RA
FA
FA
Pow
er a
ndC
ontro
lW
iring
Ent
ries
7/8"
Dia
.
Pow
er a
nd C
ontro
l Wiri
ng E
ntrie
s
OA
EA
Cor
eA
cces
s
RTH
, RTR
UN
ITS
ON
LY:
FA B
LOW
ER
Out
let i
s 18
" x 2
4".
24" x
36"
Duc
t Fla
nge
is a
lso
supp
lied .
Fiel
d in
stal
l onl
y in
loca
tion
show
n.
RTV
, RTF
UN
ITS
ON
LY:
FA B
low
er O
utle
t is
16" x
22"
.C
urb
acce
pts
up to
24"
x 3
6" d
uct;
see
sepa
rate
Cur
b dr
awin
g.
63 1
/2"
39 3/4"
Fron
t Vie
ws
at 0
.5X
:B
LOW
ER
RO
TATI
ON
21 7
/8"
EAEA
59 3
/8"
60 7/8"
Not
e:A
ll un
its h
ave
an in
tegr
alex
haus
t air
back
draf
t dam
per.
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282456
HE8XRT
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airflow Range: 2,000-8,000 CFM
AHRI 1060 Certified Core: Eight L125-00
Airflow Rating Points (for AHRI): 6,000 CFM and 4,500 CFM
Number Motors: Two
HP Volts HZ Phase FLAMin. Cir.
Amps
Max. Fuse Size
5208-230
460575
606060
ThreeThreeThree
14.2-13.06.55.0
32.614.911.3
452015
7.5208-230
460575
606060
ThreeThreeThree
20.9-19.29.67.6
47.021.617.1
703025
10208-230
460575
606060
ThreeThreeThree
29.0-26.813.410.0
65.330.222.5
904535
Control Voltage: 24 VAC
Filters: Sixteen total, MERV 8, 2” pleated, 20” x 20” nominal size
Weight: 2,730 lbs (unit), 3,080 lbs (shipping weight)
Shipping Dimensions: 85” W x 114” L x 85” H
CFM2,000 4,000 6,000 8,000
80
60
40
SensibleWinter Total
Summer Total
SpecificationsOutdoor Unit
G5 Performance
Motor HP Blower RPM Nominal Turns Open
External Static Pressure (Inches Water Column)
0.0 0.25 0.5 0.75 1.0 1.25 1.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
51,4601,6101,725
4.52
0.5
5,575 3.26,200 4.36,550 5.0
5,425 3.26,010 4.36,380 5.0
5,200 3.25,875 4.26,210 5.0
5,000 3.25,700 4.26,100 5.0
4,775 3.15,500 4.25,880 4.9
4,550 3.05,325 4.15,730 4.8
4,270 2.95,125 4.15,510 4.8
7.51,5601,7401,865
4.520
6,000 3.96,700 5.3 - -
5,850 3.96,575 5.3 - -
5,650 3.86,400 5.3 - -
5,475 3.86,300 5.36,800 7.5
5,275 3.86,125 5.36,675 7.5
5,100 3.75,950 5.26,500 7.5
4,875 3.75,750 5.26,375 7.4
101,8102,0202,105
4.521
7,000 6.17,850 8.5 - -
6,875 6.17,745 8.5 - -
6,750 6.17,625 8.57,950 9.6
6,600 6.07,450 8.47,800 9.6
6,425 6.07,350 8.47,725 9.6
6,275 6.07,200 8.37,600 9.5
6,100 5.97,050 8.37,450 9.5
Airflow Performance
Effe
ctiv
enes
s (%
)
*At AHRI 1060 standard conditions(See certified data on page 67 for core components).
OA
RAFA
EA
RTV
OA
RA
FA
EA
RTF
Base Type/Airflow Orientations
OA
RA
EA
FA
RTR
OA
RA
EA
FA
RTH
www.RenewAire.com57
62"
34" Min.Clearance
112
3/4"
Uni
t Roo
f
108
1/2"
Bas
e
78 1/4" Overall
27 1
/4"
49"
81 1
/2" B
ase
24"
29"
OA
108
1/2"
Bas
e
OA
39 1
/2" M
in.
Cle
aran
ce
85 1
/2" U
nit R
oof
183
1/4"
Ser
vice
Are
a
165" Service Area
35"
41 3/4"
FRO
NT
VIE
WB
low
er A
cces
sB
AC
K V
IEW
LEFT
VIE
W
RIG
HT
VIE
W
4"
77"
4"22"36"
TOP
VIE
W
(RTF
,RTH
Onl
y)
(RTV
,RTR
)
RA
RA
Pow
er a
ndC
ontro
lW
iring
Ent
ries
7/8"
Dia
.
OA
Cor
e A
cces
s
RTH
, RTR
UN
ITS
ON
LY:
FA B
LOW
ER
Out
let i
s 18
" x 2
4".
24" x
36"
Duc
t Fla
nge
is a
lso
supp
lied .
Fiel
d in
stal
l onl
y in
loca
tion
show
n.
24"
FA
Fron
t Vie
ws
@ 0
.5X
:B
LOW
ER
RO
TATI
ON
RTV
, RTF
UN
ITS
ON
LY:
FA B
low
er O
utle
t is
16" x
22"
.C
urb
acce
pts
up to
24"
x 3
6" d
uct;
see
sepa
rate
Cur
b dr
awin
g.
18"
9"
39 3/4"
63 1
/2"
FA
OA
Hoo
ds o
nR
oofto
p U
nits
on
ly.
EA
21 7
/8"
EA
EA
Pow
er a
nd C
ontro
l Wiri
ng E
ntrie
s
EA59
3/8
"
60 7/8"
Not
e:A
ll un
its h
ave
an in
tegr
alex
haus
t air
back
draf
t dam
per.
CURB
8X
HE8X
RT
Un
it D
imen
sio
ns
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
(800) 627-4499 • Fax: (608) 221-282458
CA4X
Applied Products
Cost effective energy recovery for virtually • any air handling system.
Field assembled into air handling systems • or integrated in custom packaged air handlers.
Unlimited airflow capacity.•
Flexible installation and easy servicing.•
AHRI certified performance data for • efficiency and cross leakage.
UL tested flammability and • smoke generation that meets NFPA 90A and 90B test standards for commercial applications.
Ten year core warranty.•
RenewAire means Trouble-Free ERV.
Similar designs can use PA-Series arrays. (PA-Series provide top service access and an “over-under” airflow arrangement.)
Central Air Handler using CA4X and exhaust and make-up air blowers. (CA-Series provide side service access and a “side-by-side” airflow arrangement.)
Installation Example
www.RenewAire.com59
Part I - General
A. Product Specification
1. Energy Recovery Ventilator (ERV) shall be a packaged unit as manufactured by RenewAire and shall transfer both heat and humidity using static plate core technology. B. Quality Assurance
1. The energy recovery cores used in these products shall be third party Certified by AHRI under its Standard 1060 for Energy Recovery Ventilators. AHRI published certifications shall confirm manufacture’s published performance for airflow, static pressure, temperature and total effectiveness, purge air (OACF) and exhaust air leakage (EATR). Products that are not currently AHRI Certified will not be accepted.
2. The energy recovery core shall be a UL Listed Component complying to UL Standard 723. Manufacturer shall be able to provide evidence of independent testing of the core by Underwriters Laboratory (UL), verifying a maximum flame spread index (FSI) of 25 and a maximum smoke developed index (SDI) of 50 thereby meeting NFPA 90A and NFPA 90B requirements for materials in a compartment handling air intended for circulation through a duct system.
3. The ERV core shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of ten years from the date of purchase. The balance-of-unit shall be warranted to be free of manufacturing defects and to retain its functional characteristics, under circumstances of normal use, for a period of two years from the date of purchase.
Part II – Performance
A. Energy TransferThe ERV shall be capable of transferring both sensible and latent energy between airstreams. Latent energy transfer shall be accomplished by direct water vapor transfer from one airstream to the other, without exposing transfer media in succeeding cycles directly to the exhaust air and then to the fresh air.
B. Passive Frost ControlThe ERV core shall perform without condensing or frosting under normal operating conditions (defined as outside temperatures above -10°F and inside relative humidity below 40%). Occasional more extreme conditions shall not affect the usual function, performance or durability of the core. No condensate drains will be allowed.
C. Continuous VentilationUnit shall have the capacity to operate continuously without the need for bypass, recirculation, pre-heaters or defrost cycles under normal operating conditions.
D. Positive Airstream SeparationWater vapor transfer shall be through molecular transport by hydroscopic resin and shall not be accomplished by “porous plate” mechanisms. Exhaust and fresh airstreams shall travel at all times in separate passages, and airstreams shall not mix.
E. Laminar FlowAirflow through the ERV core shall be laminar over the products entire operating airflow range, avoiding deposition of particulates on the interior of the energy exchange plate material.
Part III – Product
A. Construction
1. The energy recovery component shall be of fixed-plate cross-flow construction, with no moving parts.
2. No condensate drain pans or drains shall be allowed and unit shall be capable of operating in both winter and summer conditions without generating condensate.
3. The unit case shall be constructed of G90 galvanized, 20-gauge steel, with lapped corners and zinc plated screw fasteners.
4. Access doors shall provide easy access to ERV cores and filters. Doors shall have an airtight compression seal using closed cell foam gaskets.
5. Case walls and doors shall be insulated with 1 inch, 4 pound density, foil/scrim faced, high-density fiberglass board insulation, providing a cleanable surface and eliminating the possibility of exposing the fresh air to glass fibers. PA-Series bottom panels shall be insulated with ¼ inch sheet rubber insulation.
6. The ERV cores shall be protected by a MERV-8 rated, 2” nominal, pleated, disposable filter in both airstreams.
7. CA-Series cabinet construction shall allow stacking of units up to three cabinets high for larger airflow applications. Hinged and latched access doors will be provided on each end of the unit.
8. PA-Series shall use RenewAire patented modular vertical stack of cores (US Patent 5,660,228) allowing assembly of unlimited sizes of ERV systems. Latched access doors are provided on the top of each unit. B. Options (Select options based on application requirements)
1. Provide unit and duct connection orientation per project schedule.
2. Provide double wall construction with 24-gauge galvanized steel liner (CA-Series only).
3. CA and PA-Series units are available pre-assembled on a structural steel base.
Part IV – Installation
A. Unit Location
1. Locate and orient unit to provide the shortest and most straight duct connections. Provide service clearances as indicated on the plans. Locate system blowers (provided by others) distant from sound critical occupancies.
2. Provide a poured concrete equipment pad for all floor mounted units. The pad thickness, and floor plan dimensions to be determined based on the unit selected, and site structural considerations.
3. Provide a structurally suitable support for the base of any wall mounted or hung units.
B. Vibration Isolation
1. No moving parts are allowed in the ERV modular assemblies.
C. Duct Design
1. All ductwork shall be designed, constructed, supported and sealed in accordance with SMACNA HVAC Duct Construction Standards and pressure classifications.
2. At a minimum all duct runs to the outdoors shall be thermally insulated at levels appropriate to the local climate. A continuous vapor barrier shall also be provided on warm surface of the insulation.
D. Sound Control
1. The ERV cores shall act as flow straighteners and sound attenuators. This attribute can be used to isolate mechanical noise from blowers and other mechanical equipment from sound critical occupancies.
E. Test and Balancing
1. Test and Balancing may not begin until 100% of the installation is complete and fully functional.
2. Follow National Comfort Institute (NCI) air test and balance procedures specific to Heat Recovery Ventilator Balancing Procedure including standard reports to the owner’s representative.
CA & PA Series Applied Energy Recovery Ventilators: CA2X, CA3X, CA4X, PA6X, PA9X, PA8X & PA12X
(800) 627-4499 • Fax: (608) 221-282460
CA-Series
Ventilation Type: Static Plate, Heat and Humidity Transfer
Insulated sheet metal cabinets with energy exchange cores and filters.
Individual CA-Series units or stacks of units can be built into larger air handling systems.
Blower not included and must be specified to meet job requirements.
Description CA2X CA3X CA4X
Typical Airflow Range CFM 500-2,200 750-3,300 1,000-4,400
AHRI 1060 Certified Core Two L125-00 Three L125-00 Four L125-00
Airflow Rating Points (for AHRI)
1,500 and1,120 CFM
2,250 and 1,690 CFM
3,000 and 2,250 CFM
Unit Weight 225 lbs 325 lbs 400 lbs
Shipping Weight 275 lbs 375 lbs 475 lbs
Filters: MERV 8, 2” pleated 20” x 20” nominal size Four Total Six Total Eight Total
Shipping Dimensions: CA2X - 40” W x 48” L x 41” H CA3X - 40” W x 67” L x 41” H CA4X - 40” W x 87” L x 41” H
Insulation: One inch, high density, FSK faced, fiberglass
CFM
500 1,000 1,500 2,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter TotalSummer Total
CA2X
CFM
1,000 2,000 3,000 4,000
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter TotalSummer Total
CA4X
CFM
1,250 1,750 2,250 2.750
80
60
40
Effe
ctiv
enes
s (%
)
SensibleWinter TotalSummer Total
CA3X
CA3X
2.0
1.5
1.0
0.5
1,000 2,000 3,000 4,000
Airflow (CFM)
Inte
rnal
Sta
tic
Pres
sure
(in.
H2O
)
CA2X
CA3X
CA4X
SpecificationsIndoor Unit - Up to 20,000 CFM in Stacked Arrays
G5 Performance
Airflow Performance
*At AHRI 1060 standard conditions(See certified data on page 66 for core components).
www.RenewAire.com61
CA
-SERIE
SU
nit
Dim
en
sio
ns Le
ft Vi
ew
B
F
A
34 3
/4"
BF
E
34 3/4"
End
Vie
w15"
1"R
ight
Vie
w
E
34 3/4"
15"1"
D (
Min
imum
Ser
vice
Are
a)
2.50
00
39 3/4"
C (M
axim
um S
ervi
ce A
rea)
2.50
00
Not
e: F
ilter
s ar
e pr
ovid
ed fo
r ins
talla
tion
in
any
two
of th
e lo
catio
ns s
how
n, d
epen
ding
on
whi
ch d
uct c
onne
ctio
ns a
re s
elec
ted
for
inle
ts.
Filte
rs a
re 2
" x 2
0" x
20"
ple
ated
di
spos
able
.
Top
View
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
CA2X
CA3X
CA4X
A42
”62
”81
-5/8
”B
14”
24”
32”
C11
1”13
0”14
9”D
77”
96”
116”
E5-
5/8”
5-5/
8”7-
5/8”
F19
-3/4
”29
-5/8
”39
-3/4
”
Avai
labl
e O
ptio
ns:
Dou
ble
Wal
l Con
stru
ctio
n
(800) 627-4499 • Fax: (608) 221-282462
Ventilation Type: Static Plate, Heat and Humidity Transfer
Insulated sheet metal panels easily slide into receivers to enclose stacks of energy exchange cores using unique patented design, US Patent 5,660,228
Individual PA-Series units can be joined together to provide unlimited airflow capacities for larger air handling systems.
Blower not included and must be specified to meet job requirements.
Description PA6X PA8X PA9X PA12X
Typical Airflow Range CFM 1,500-6,600 2,000-8,800 2,250-9,900 3,000-13,200
AHRI 1060 Certified Core Six L125-00 Eight L125-00 Nine L125-00 Twelve L125-00
Airflow Rating Points (for AHRI)
4,500 and 3,375 CFM
6,000 and 4,500 CFM
6,750 and 5,062 CFM
9,000 and 6,750 CFM
Unit Weight 565 lbs 695 lbs 800 lbs 980 lbs
Shipping Weight 650 lbs 900 lbs 990 lbs 1,180 lbs
Filters: MERV 8, 2” pleated, 20” x 20” nominal size PA6X - 12 Total PA9X - 18 Total PA8X - 16 Total PA12X - 24 Total
Insulation: One inch, high density, FSK faced, fiberglass
3,500 5,000 6,500 8,000
80
60
40
Effe
ctiv
enes
s (%
)
Sensible
Summer TotalPA8X
3,000 4,000 5,000 6,000
80
60
40
Effe
ctiv
enes
s (%
)
Sensible
Winter TotalSummer Total
PA6X
5,000 7,000 9,000 11,000
80
60
40
Effe
ctiv
enes
s (%
)
Sensible
Summer TotalPA12X
3,500 5,000 6,500 8,000
80
60
40
Effe
ctiv
enes
s (%
)
Sensible
Winter TotalSummer Total
PA9X
Winter Total
CA3X
2.0
1.5
1.0
0.5
3,000 6,000 9,000 12,000
Airflow (CFM)
Inte
rnal
Sta
tic
Pres
sure
(in.
H2O
)
PA6X
PA12
XPA9XPA8X
Winter Total
CFM
CFM
CFM
CFM
PA-SeriesSpecificationsIndoor Unit - Unlimited Airflow in Multiple Arrays
G5 Performance
Airflow Performance
*At AHRI 1060 standard conditions(See certified data on page 66 for core components).
www.RenewAire.com63
PA
-SERIE
SU
nit
Dim
en
sio
ns
PA-9
X/1
2X
35 1
/2"
A =
109
1/2
Top
View
35 1
/2"
2
1 2
1
Arr
ange
men
t 4S
ame-
side
Ent
ries
Par
alle
l-pat
h A
irflo
ws
35 1
/2"
1 2
1 2
Arr
ange
men
t 3O
ppos
ite-s
ide
Ent
ries
Par
alle
l-pat
h A
irflo
ws
35 1
/2"
21 2
1
Arr
ange
men
t 2S
ame-
side
Ent
ries
Cro
ss-p
ath
Airf
low
s
35 1
/2"
1 212
Opp
osite
-sid
e E
ntrie
sC
ross
-pat
h A
irflo
ws
Arr
ange
men
t 1
PA-6
X/8
X
35 1
/2"
A =
73 1
/4
Avai
labl
e A
irflow
Arr
ange
men
ts(S
ide
View
s)
Perf
orm
ance
Der
atin
g:A
irflow
arr
ange
men
ts 3
& 4
resu
lt in
low
er e
nerg
y tr
ansf
er.
Redu
ce s
ensi
ble
effec
tiven
ess
by 2
per
cent
age
poin
ts.
Redu
ce to
tal e
ffect
iven
ess
by 1
per
cent
age
poin
t.S
ide
View
Ser
vice
A
rea
35 1
/2"
22 1
/2”
A (O
vera
ll)
Fron
t Vie
w
Ser
vice
Are
a
G
EE
D (D
uct F
lang
e)
F 5”
EA:
Exh
aust
Air
to
outd
oors
OA:
Out
door
Air
inta
keRA
: R
oom
Air
to
be e
xhau
sted
FA:
Fre
sh A
ir t
o in
side
PA6X
PA9X
PA8X
PA12
XA
73-1
/4”
109-
1/2”
73-1
/4”
109-
1/2”
D72
-3/4
”10
9”72
-3/4
”10
9”E
28”
28”
37”
37”
F1-
1/2”
1-1/
2”3-
1/8”
3-1/
8”G
66-1
/4”
66-1
/4”
86”
86”
APPR
OX.
WEI
GH
T56
581
070
010
00
Avai
labl
e O
ptio
ns:
Knoc
kdow
n
Asse
mbl
ed o
n st
ruct
ural
fo
rklif
t ba
se
(800) 627-4499 • Fax: (608) 221-282464
These controls are intended to turn RenewAire commercial energy recovery ventilation systems on and off at appropriate times. Specification, installation and set-up is an easy process. RenewAire units should be ordered with the 24 volt contactor option for all controls.
It is not necessary that RenewAire controls be used to operate RenewAire units. A wide range of controls or building automation systems may be used. Make sure units are ordered with compatible contactor control voltage.
RenewAire residential units have their own line of compatible controls that are not intended to operate RenewAire commercial units.
TC7D-WWall Mount
TC7D-E ControlIn NEMA 3R Enclosures
MC-CCeiling Mount
MC-WWall Mount
CO2-WWall Mount
CO2-DDuct Mount
Commercial Controls & Interconnection Options
TC7D
MC
CO2
Digital Time Clock
Motion (occupancy) Control
Carbon Dioxide Control
up to 8 on/off cycles per day or 56 per week• 24 VAC power requirement• battery back-up• wall mount or outdoor enclosure options• wall mount fits any 4” x 4” electrical box• optional RenewAire transformer relay • package (TR40) may be used
passive infared sensor• adjustable time-off delay to 30 minutes• 24 VAC power requirement• ceiling mount or directable wall mount• covers up to 1500 sq. ft. floor space • ceiling mount - walking motion coverage up to 22 foot radius wall mount - various coverage patterns up to 90 linear feet of sensitivity
requires the use of RenewAire transformer relay package • (TR40) (ordered separately)
adjustable control from 600-2000 PPM• digital display• 24 VAC power requirement• computer/BAS interface for information and control• self calibrates during periods of low occupancy• wall mount or add duct mount accessory• requires the use of RenewAire transformer relay package • (TR40) (ordered separately)
www.RenewAire.com65
DH24Wall Mount
DS
TR40
IBC
DH24
Disconnect Switch
Transformer Relay Package
Independent Blower Control
Dehumidistat Control
provides a 24 VAC, 40 VA class II power supply for unit control• includes isolation relay with low voltage circuit breaker• handles any RenewAire unit with one contactor• installation voltage must be specified 115, 208-230, 460• installed in unit electric box• TR40 is configured as part of the model numbering for a unit (see page 67)•
adds a second contactor to allow independent control of exhaust fan and • supply fanmay be used to provide economizer (no heat recovery operation) function• can provide relief fan or make-up air function to benefit building pressurization• IBC is configured as part of the model numbering guide for a unit (see page 67)•
fused or non-fused• indoor or NEMA 3R exterior enclosures - I or E• installation voltage must be specified 115, 208-230, 460• installed on unit and wired to unit contactor• disconnects are configured as part of the model numbering for a unit (see page 67)•
secondary control to time clock or other primary control• mechanical switching of 24 VAC (or 120 VAC)• adjustable from 0 - 100% relative humidity• wall mount to single gang box• Note: RenewAire ERVs are not to be used for applications • where indoor relative humidity exceeds 50% RH for extended periods of time
(800) 627-4499 • Fax: (608) 221-282466
HVI Tested/CertifiedPer CSA C439
Electrical Requirements Volts 120 Amps 3.3Exhaust Air Transfer Ra�o = 4% @ 0.4 in. wg (100 PA)
Electrical Requirements Volts 120 Amps 1.5Exhaust Air Transfer Ra�o = 3% @ 0.2 in. wg (50 PA) and 3% @ 0.4 in. wg (100 PA)
Electrical Requirements Volts 120 Amps 1.3Exhaust Air Transfer Ra�o = 2% @ 0.2 in. wg (50 PA) and 2% @ 0.4 in. wg (100 PA)
Electrical Requirements Volts 120 Amps 1.0Exhaust Air Transfer Ra�o = 4% @ 0.2 in. wg (50 PA) and 4% @ 0.4 in. wg (100 PA)
EV300 - Ventilation Performance
Ext. Static Pressure Net Supply AirflowGross Airflow
Supply ExhaustPa in. wg L/S CFM L/S CFM L/S CFM100 0.4 145 310 150 320 143 305125 0.5 141 300 145 310 138 295150 0.6 136 289 140 299 127 270175 0.7 126 268 130 276 114 242200 0.8 117 249 121 251 92 195225 0.9 94 199 97 206 79 169250 1.0 73 155 75 160 65 138
EV300 - Energy PerformanceSupply
Temperature Net Airflow Average Power Watts
Sensible Recovery Efficiency %
Apparent Sensible Effectiveness %
Net Moisture Transfer %
C° F° L/S CFM Heating
0° 32° 138 293 310 68 76 45 Cooling Total Recovery Efficiency %
35° 95° 120 272 299 38
EV200 - Energy PerformanceSupply
Temperature Net Airflow Average Power Watts
Sensible Recovery Efficiency %
Apparent Sensible Effectiveness %
Net Moisture Transfer %
C° F° L/S CFM Heating
0° 32° 85 181 157 78 85 62 Cooling Total Recovery Efficiency %
35° 95° 85 180 155 52
EV200 - Ventilation Performance
Ext. Static Pressure Net Supply AirflowGross Airflow
Supply ExhaustPa in. wg L/S CFM L/S CFM L/S CFM25 0.1 97 207 100 213 109 23250 0.2 90 192 93 199 104 22175 0.3 88 186 90 192 101 216100 0.4 83 176 85 181 96 204125 0.5 79 168 81 173 88 187150 0.6 70 149 72 154 76 162175 0.7 57 122 59 126 68 145
BR130/EV130 - Energy PerformanceSupply
Temperature Net Airflow Average Power Watts
Sensible Recovery Efficiency %
Apparent Sensible Effectiveness %
Net Moisture Transfer %
C° F° L/S CFM Heating
0° 32° 58 124 121 72 80 55 Cooling Total Recovery Efficiency %
35° 95° 59 126 121 46
BR130/EV130 - Ventilation Performance
Ext. Static Pressure Net Supply AirflowGross Airflow
Supply ExhaustPa in. wg L/S CFM L/S CFM L/S CFM25 0.1 70 148 71 151 75 15950 0.2 66 141 67 143 69 14775 0.3 62 132 63 134 64 135100 0.4 53 113 54 115 56 119125 0.5 44 94 45 96 47 99150 0.6 32 69 33 70 29 62175 0.7 24 52 25 53 21 45
BR70/EV70 - Energy PerformanceSupply
Temperature Net Airflow Average Power Watts
Sensible Recovery Efficiency %
Apparent Sensible Effectiveness %
Net Moisture Transfer %
C° F° L/S CFM Heating
0° 32° 32 69 94 66 77 53 Cooling Total Recovery Efficiency %
35° 95° 30 64 94 42
BR70/EV70 - Ventilation Performance
Ext. Static Pressure Net Supply AirflowGross Airflow
Supply ExhaustPa in. wg L/S CFM L/S CFM L/S CFM25 0.1 41 86 42 89 46 9750 0.2 34 73 35 75 39 8475 0.3 28 59 29 61 32 69100 0.4 21 46 22 47 25 53
0 50 100 150 200 250 300 350
in.
wg.
(PA
= n
x 2
48.8
)
1.11.00.90.80.70.60.50.40.30.20.10.0
CFM (L/S = n x 0.4719)
Gross Supply Gross Exhaust
0 25 50 75 100 125 150 175 200 225 250
in.
wg.
(PA
= n
x 2
48.8
)
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
CFM (L/S = n x 0.4719)
Gross Supply Gross Exhaust
0 25 50 75 100 125 150 175
in.
wg.
(PA
= n
x 2
48.8
)
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
CFM (L/S = n x 0.4719)
Gross Supply Gross Exhaust
0 25 50 75 100 125 150 175
in.
wg.
(PA
= n
x 2
48.8
)
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
CFM (L/S = n x 0.4719)
Gross Supply Gross Exhaust
www.RenewAire.com67
AHRI 1060-2005Certified Performance
Leakage Ratings
Pressure Differential EATR OACF Purge Angle
or Setting
Test 1 -1 in. H20 1.0% 1.00 N/A
Test 2 0 in. H20 0.0% 1.02 N/A
Test 3 1 in. H20 0.0% 1.05 N/A
AHRI-1060 Certified Performance - Model Number L85-G5
Type Tilt Angle Nominal Airflow Pressure Drop
Plate N/A 100% - 450 SCFM 75% - 338 SCFM
0.6 in. H200.5 in. H20
Thermal Effectiveness Ratings at 0” Pressure Differential
Nominal Airflow Sensible Latent Total Net
AirflowNet
SensibleNet
LatentNet
Total
450 HeatingCFM Cooling
73%73%
53%46%
66%56%
450 CFM
73%73%
53%46%
66%56%
338 HeatingCFM Cooling
77%77%
60%52%
71%61%
338CFM
77%77%
60%52%
71%61%
Leakage Ratings
Pressure Differential EATR OACF Purge Angle
or Setting
Test 1 -1 in. H20 1.0% 1.00 N/A
Test 2 0 in. H20 0.0% 1.02 N/A
Test 3 1 in. H20 0.0% 1.05 N/A
AHRI-1060 Certified Performance - Model Number L125-G5
Type Tilt Angle Nominal Airflow Pressure Drop
Plate N/A 100% - 750 SCFM 75% - 563 SCFM
0.65 in. H200.45 in. H20
Thermal Effectiveness Ratings at 0” Pressure Differential
Nominal Airflow Sensible Latent Total Net
AirflowNet
SensibleNet
LatentNet
Total
750 HeatingCFM Cooling
71%71%
52%43%
64%53%
750 CFM
71%71%
52%43%
64%53%
563 HeatingCFM Cooling
75%75%
59%50%
69%59%
563CFM
75%75%
59%50%
69%59%
NOTE: SCFM = Standard Cubic Feet per Minute OACF = Outdoor Air Correction Factor EATR = Exhaust Air Transfer Ratio N/A = Not Applicable
Energy recovery component certified in accordance with AHRI Standard 1060-2005.Actual performance in packaged equipment may vary.
7-8 "IN" = INDOOR
11 WALL TYPE (UNUSED IN PA MODELS):
1-2 MODEL:
21 OPTION 1 (RESERVED): "-" = NONE
22 OPTION 2 (RESERVED): "-" = NONE
24 OPTION 4: PRE-ASSEMBLY
25 UL: "N" = NON-LISTED
MODEL NUMBER
MU
LTIP
LE-C
HO
ICE
OR
O
PTI
ON
AL
FEAT
UR
ES
STANDARDFEATURES
9BASE TYPE (SEE DIAGRAM)(CA) "-" (NONE)(PA) "9" = FORKLIFT BASE 10
3-5QTY OF CORES:
"CA" = CABINET APPLIED"PA" = PANELIZED APPLIED
12-20 UNUSED IN PA, CA MODELS
6 CORE: "J" = G5
23 OPTION 3 (RESERVED): "-" = NONE
"K" = KNOCKDOWN (PA MODELS)"A" = ASSEMBLED (PA MODELS)"-" = NOT APPLICABLE (CA MODELS)
AIRFLOW ORIENTATION (UNUSED IN CA MODELS)
"S" = SINGLE (CA MODELS ONLY)"D" = DOUBLE (CA MODELS ONLY)
"nX" = (n) CORESn = 2, 3, 4 (CA MODELS)n = 6, 8, 9, 12 (PA MODELS)
"1" = OPPOSITE-SIDE ENTRY, CROSS-FLOW"2" = SAME-SIDE ENTRY, CROSS FLOW"3" = OPPOSITE-SIDE ENTRY, PARALLEL-FLOW"4" = SAME-SIDE ENTRY, PARALLEL-FLOW"-" = DEFAULT IN CA MODELS AND IN PA MODELS WITH PRE-ASSEMBLY OPTION "K" (KNOCK-DOWN).
J I N N- - - - - - - --- - -1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
CA & PA MODELS
Model Numbering Guide Not all options are available on every model.
Mo
del N
um
berin
g G
uid
e
Not
e: N
ot a
ll o
ptio
ns a
re a
vail
able
on
ever
y m
odel
.
J-
--
-
6C
OR
E: "
J" =
G5
11W
ALL
TY
PE
: "S
" = S
ING
LE, "
D" =
DO
UB
LE
12PH
ASE:
"1" =
SIN
GLE
-PH
ASE,
"3" =
TH
REE
-PH
ASE
192122
OP
TIO
N 1
: 24V
TR
AN
S. (
RE
STR
ICTI
ON
S 1
1 &
12)
:
25U
L LI
STI
NG
(S
EE
RE
STR
ICTI
ON
15)
:M
OD
EL
NU
MB
ER
MULTIPLE-CHOICE OR OPTIONAL FEATURESSTANDARD
FEATURES
9B
AS
E T
YP
E (S
EE
RE
STR
ICTI
ON
1)
"V",
"H",
"T" (
IND
OO
R U
NIT
S)
"V",
"H",
"R",
"F",
"C" (
RO
OFT
OP
UN
ITS
)"-
" - D
EFA
ULT
IN H
E45
0
10U
NU
SE
D IN
HE
MO
DE
L
13V
OLT
AG
E: (
SE
E R
ES
TRIC
TIO
NS
2, 3
, 4 &
5)
7-8
IND
OO
R/O
UTD
OO
R
1-5
MO
DE
L
20
16-1
8U
NU
SE
D IN
TH
ES
E M
OD
ELS
15E
A H
OR
SE
PO
WE
R14
FA H
OR
SE
PO
WE
R"H
" = 0
.75
HP
EPA
CT
DIR
EC
T-D
RIV
E (
HE
-1X
ON
LY)
"J" =
1.5
HP
EPA
CT
(HE
-2X
ON
LY)
"K" =
2H
P E
PAC
T (H
E-2
X, H
E-3
X, H
E-4
X O
NLY
)"L
" = 3
HP
EPA
CT
(HE
-3X
, HE
-4X
ON
LY)
"M" =
5H
P E
PAC
T (H
E-3
X, H
E-4
X, H
E-6
X, H
E-8
X O
NLY
)"N
" 7.5
HP
EPA
CT
(HE
-6X
, HE
-8X
ON
LY)
"P" 1
0HP
EPA
CT
(HE
-8X
ON
LY)
"Q" =
(2) 0
.75H
P E
PAC
T D
IRE
CT-
DR
IVE
(H
E-2
X O
NLY
)"-
" = D
EFA
ULT
IN E
V45
0
"IN" =
IND
OO
R, "
RT"
= R
OO
FTO
P
"1" =
115
V, "4
" = 4
60V,
"5" =
208
-230
V,
"6" =
115
/208
-230
V, "7
" = 2
08-2
30/4
60V,
"8
" = 5
75V,
"9" =
277
V
RESTRICTIONS:
1: B
AS
E T
YP
E "C
" NO
T AV
AIL
AB
LE W
ITH
MO
DE
LS
EV
450,
HE
-6X
, HE
-8X
.B
AS
E T
YP
E "T
" AVA
ILA
BLE
ON
LY IN
HE
-6X
, HE
-8X
.
2: V
OLT
AG
E C
OD
ES
"1",
"6" &
"9" A
VAIL
AB
LE W
ITH
P
HA
SE
CO
DE
"1" (
SIN
GLE
-PH
AS
E) O
NLY
.
3: V
OLT
AG
E C
OD
ES
"4",
"7" &
"8" A
VAIL
AB
LE W
ITH
P
HA
SE
CO
DE
"3" (
THR
EE
-PH
AS
E) O
NLY
.
4. V
OLT
AG
E C
OD
E "9
" (27
7V) A
VAIL
AB
LE O
NLY
WIT
H
HO
RS
EP
OW
ER
CO
DE
S "H
", "Q
" OR
EV
450
MO
DE
L.
5: V
OLT
AG
E C
OD
E "8
" (57
5V) N
OT
AVA
ILA
BLE
WIT
H
HO
RS
EP
OW
ER
CO
DE
S "H
", "Q
" OR
WIT
H M
OD
EL
EV
450.
V
OLT
AG
E C
OD
ES
"1" (
115V
), "6
" (11
5/20
8-23
0V),
"7"
(208
-230
/460
V),
"9" (
277V
) NO
T AV
AIL
AB
LE IN
HE
-6X
, H
E-8
X.
VO
LTA
GE
CO
DE
"5" (
208-
230V
) NO
T AV
AIL
AB
LE W
ITH
P
HA
SE
CO
DE
"1" (
SIN
GLE
-PH
AS
E) I
N M
OD
ELS
HE
-6X
&
HE
-8X
.
6: V
OLT
AG
E C
OD
ES
"1" &
"6" A
VAIL
AB
LE O
NLY
WIT
H
FA/E
A H
OR
SE
PO
WE
R C
OD
ES
"H",
'Q" &
"-".
7: U
NIT
CO
NTR
OL
CO
DE
"R" (
INV
ER
TER
RE
AD
Y) N
OT
AVA
ILA
BLE
WIT
H P
HA
SE
CO
DE
"1" (
SIN
GLE
PH
AS
E),
OR
IN M
OD
EL
EV
450.
8: U
NIT
CO
NTR
OL
CO
DE
"D" (
2 C
ON
TAC
TOR
S) N
OT
AVA
ILA
BLE
IN M
OD
EL
EV
450.
9: D
ISC
ON
NE
CT
CO
DE
S "N
" & "F
" AVA
ILA
BLE
ON
LY
WIT
H V
OLT
AG
E C
OD
ES
1, 4
, 5, 8
& 9
.
10: D
ISC
ON
NE
CT
CO
DE
S "N
" & "F
" NO
T AV
AIL
AB
LE
WIT
H U
NIT
CO
NTR
OL
CO
DE
"R" (
INV
ER
TER
RE
AD
Y).
11: T
RA
NS
FOR
ME
R C
OD
E "T
" (TR
40) A
VAIL
AB
LE O
NLY
W
ITH
VO
LTA
GE
CO
DE
S 1
, 4, 5
& 9
.
12: T
RA
NS
FOR
ME
R C
OD
E "T
" (TR
40) N
OT
AVA
ILA
BLE
W
ITH
UN
IT C
ON
TRO
L C
OD
ES
"D" (
2 C
ON
TAC
TOR
S) O
R
"R" (
INV
ER
TER
RE
AD
Y),
EX
CE
PT
IN M
OD
ELS
HE
-6X
&
HE
-8X
.
13: F
ILTE
R M
ON
ITO
RS
NO
T AV
AIL
AB
LE IN
EV
450.
14: S
OM
E U
NIT
S W
ITH
CU
STO
M "X
" CO
DE
NO
T U
L-LI
STE
D.
23O
THE
R O
PTI
ON
S (R
ES
ER
VE
D)
24
UL:
"L" =
LIS
TED
"N
" = N
ON
-LIS
TED
OP
TIO
N 4
: OTH
ER
S
"-" =
NO
NE
"T" =
TR
40 (T
RA
NS
FOR
ME
R W
ITH
ISO
LATI
ON
RE
LAY
)
"-" =
NO
NE
,"W
" = W
HIT
E P
AIN
T, "C
" = C
US
TOM
PA
INT
"X" =
CU
STO
M U
NIT
RE
STR
ICTI
ON
6
12
34
56
78
910
1112
1314
1516
1718
1920
2122
2324
25 UN
IT C
ON
TRO
L (R
ES
TRIC
TIO
NS
7 &
8)
DIS
CO
NN
EC
T (R
ES
TRIC
TIO
NS
9 &
10)
:"N
" = N
ON
-FU
SE
D"F
" = F
US
ED
"-" =
NO
NE
"A" =
(1) 2
4V C
ON
TAC
TOR
"D" =
(2) 2
4V C
ON
TAC
TOR
S"R
" = IN
VE
RTE
R R
EA
DY
(NO
CO
NTA
CTO
R)
OP
TIO
N 2
: FIL
TER
MO
NIT
OR
(RE
STR
ICTI
ON
13)
"-" =
NO
NE
,"F
" = F
ILTE
R M
ON
ITO
R B
OTH
AIR
STR
EA
MS
"EV
450"
, "H
E-1
X",
"HE
-2X
""H
E-3
X",
"HE
-4X
", "H
E-6
X, "
HE
-8X
"
EV/H
E M
OD
ELS
For
Tech
nica
l Sup
port
E-m
ail:
Sup
port
@Re
new
Air
e.co
mTo
Pla
ce a
n O
rder
E-m
ail:
Ren
ewA
ireO
rder
s@Re
new
Air
e.co
m
Save Energy
Reduce Pollution
Material Efficient
People Friendly
Green
Ample Airflow
Pressure Balanced
Quiet Operation
Energy Efficient
Automatic Control
Ve
n t il a tio n
RenewAire ventilation products will give you cleaner air to breathe - letting you and your family feel better and healthier AND will do so in the most consistent, controlled, safe and energy-efficient manner possible.
For over 30 years, RenewAire has been a pioneer in the use of plate exchangers that simultaneously tranfer heat and humidity between ventilation airstreams in extreme climates. From cool-dry (Point Barrow, Alaska) to hot-humid
(Puerto Rico) climates, RenewAire exceeds customer expectations for effective, reliable ventilation solutions.
ERV manufacturing begins using Mitsubishi “Lossnay” core. 1983
HVI residential unit certification confirms superior heat and humidity transfer. 1996
ARI-1060 commercial product certification of only ERV with 0% cross contamination. 2001
G4 - 4th generation core introduced with enhanced humidity transfer. 2004
Energy Star Qualified with energy use in the lowest 20% of comparable buildings. 2006
Introduction of RD Series dedicated outdoor air system. 2008
First HRV and ERV installations using a variety of plate and wheel technologies.1980
RenewAire model is the first listed by UL-1812 standard for ERV safety.1987
Introduction of first roof-top connected unit (RTC).1998
Introduction of BREEZE® easy to install residential unit.2005
Over 100 school projects shipped in one year.2003
New factory achieves LEED-Silver rating. 120,000th North American unit sold. 2007 sales result in 30,000 tons of CO2 emission reductions!2007
RenewAire Product & Ventilation Commitment
G5 - 5th generation core introduced with enhanced humidity transfer. 2010
Introduction of V-Series Ventilation Exhaust Fans.2009
Residential & Small Commercial5 Models• 50 - 300 CFM• built-in 24 V transformer/relay package•
Commercial Products23 Models• 250 - 7,950 CFM• 1 or 3 phase multi-voltage• 24 volt control•
Applied ProductsCA-Series (cabinet) - 500 - 20,000 CFM• PA-Series (panelized) - 1,500 - Unlimited CFM• (requires blowers & manifolds by others)•
Dedicated Outdoor Air Systems4 Models• 500 - 4400 CFM• integrated VFD for each airstream• coil options including DX, chilled • water, hot water and combinations
Ventilation Exhaust Fans4 Models• 50 - 150 CFM• robust steel housing and duct collar• the most efficient line of exhaust fans • available in North America
This piece was printed using earth-friendly soy ink on 100% post-consumer recycled paper. RenewAire ERVs are proudly manufactured in our LEED-Silver Certified facility using 100% wind generated electricity.
Part # LIT029© RenewAire LLC, 2010
Full Line of Ventilation Products