PowerFlex 400 Adjustable Frequency AC Drive for Fan & Pump ApplicationsCatalog Numbers 22C, Series B
User ManualOriginal Instructions
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Table of ContentsImportant User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Who Should Use This Manual? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Manual Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Drive Frame Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Catalog Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1Installation/Wiring Opening the Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Frame C Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Frame D Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Frame E Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Frame F Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Frame G Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Frame H Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mounting Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Maximum Surrounding Air Temperature. . . . . . . . . . . . . . . . . . . . 15Minimum Mounting Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Debris Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
AC Supply Source Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Ungrounded Distribution Systems . . . . . . . . . . . . . . . . . . . . . . . . . . 18Input Power Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General Grounding Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Ground Fault Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Safety Ground - (PE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Motor Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Shield Termination - SHLD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20RFI Filter Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fuses and Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Bulletin 140M (Self-Protected Combination Controller)/UL489 Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Motor Cable Types Acceptable for 200...600 Volt Installations 23Reflected Wave Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Output Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Power Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
I/O Wiring Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Motor Start/Stop Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 1
Table of Contents
Control Wire Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28I/O Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Maximum Control Wire Recommendations . . . . . . . . . . . . . . . . . 29I/O Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32Typical Multiple Drive Connection Examples . . . . . . . . . . . . . . . 36
Start and Speed Reference Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Accel/Decel Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
RS485 Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38On Drive Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
EMC Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39Low Voltage Directive (2014/35/EU). . . . . . . . . . . . . . . . . . . . . . . 39EMC Directive (2014/30/EU) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39General Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40Essential Requirements for CE Compliance. . . . . . . . . . . . . . . . . . 40
FCC Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42FCC Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42Essential Requirements for FCC Compliance . . . . . . . . . . . . . . . . 42
Chapter 2Start Up Prepare For Drive Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Before Applying Power to the Drive. . . . . . . . . . . . . . . . . . . . . . . . . 45Applying Power to the Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Start, Stop, Direction and Speed Control . . . . . . . . . . . . . . . . . . . . 46
Integral Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47Operator Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47LED Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48LCD Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Viewing and Editing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Keypad Hand-Off-Auto Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Hand-Off-Auto Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Local/Remote Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Auto/Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52No Function Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Chapter 3Programming and Parameters About Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Parameter Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Basic Display Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58Basic Program Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61Terminal Block Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Communications Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79Advanced Program Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83Aux Relay Card Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98Advanced Display Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102Parameter Cross Reference by Name . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
2 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Table of Contents
Chapter 4Troubleshooting Drive Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
LED Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Manually Clearing Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114Auto Restart (Reset/Run) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Fault Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115Common Symptoms and Corrective Actions . . . . . . . . . . . . . . . . . . . 117
Motor does not Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117Drive does not Start from Start or Run Inputs wired to the terminal block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118Drive does not Start from Integral Keypad. . . . . . . . . . . . . . . . . . 118Motor and/or drive will not accelerate to commanded speed. . 119Motor operation is unstable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119Drive will not reverse motor direction. . . . . . . . . . . . . . . . . . . . . . 119Drive does not power up. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Appendix ASupplemental Drive Information Drive, Fuse & Circuit Breaker Ratings . . . . . . . . . . . . . . . . . . . . . . . . . 121
Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122PowerFlex 400 Watts Loss (Rated Load, Speed & PWM) . . . . 127
Input Power Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Appendix BAccessories and Dimensions Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Product Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Appendix CRJ45 DSI Splitter Cable Connectivity Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
DSI Cable Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153Connectivity Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Appendix DApplication Notes Damper Control Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
PID Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157PID Control Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157Exclusive Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158Trim Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159PID Reference and Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159Analog PID Reference Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161PID Deadband . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162PID Preload. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162PID Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 3
Table of Contents
PID Gains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162Guidelines for Adjusting the PID Gains . . . . . . . . . . . . . . . . . . . . 163
Auxiliary Motor Control Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Appendix EModbus RTU Protocol Network Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170Supported Modbus Function Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . 170Writing (06) Logic Command Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 170Writing (06) Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171Reading (03) Logic Status Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172Reading (03) Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172Reading (03) Drive Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172Reading (03) and Writing (06) Drive Parameters . . . . . . . . . . . . . . . 173Additional Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Appendix FMetasys N2 Understanding Metasys N2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Metasys N2 Virtual Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175Metasys N2 Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Network Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177Using Percent (%) for the Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . 180Using Metasys Configurable Objects to Access Parameters. . . . . . . 181
Reading Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181Writing Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Appendix GP1 – Floor Level Network (FLN) Understanding P1-FLN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
P1-FLN Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183Network Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184Using Percent (%) for the Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . 188Using P1 Configurable Points to Access Parameters . . . . . . . . . . . . . 188
Reading Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188Writing Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
4 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Summary of Changes
This manual contains new and updated information as indicated in the following table.
New Parameters
No new parameters have been added with the release of Firmware Release Number (FRN) 8.xx.
Topic Page
CE Conformity updated 39
Programming options updated 55
UL and CE certification updated 123
Internal DC Bus Choke specification for 380-480V AC Input updated from "18.5-160 kW (25-250 HP)" to "11-160 kW (15-250 HP)".
124
Connected Components Workbench and DriveExecutive software compatibility updated
134
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 5
Summary of Changes
Notes:
6 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Preface
Overview The purpose of this manual is to provide you with the basic information needed to install, start-up and troubleshoot the PowerFlex 400 Adjustable Frequency AC Drive.
Who Should Use This Manual?
This manual is intended for qualified personnel. You must be able to program and operate Adjustable Frequency AC Drive devices. In addition, you must have an understanding of the parameter settings and functions.
Additional Resources These documents contain additional information concerning related products from Rockwell Automation.
You can view or download publications athttp://www.rockwellautomation.com/global/literature-library/overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Resource Description
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001
Provides basic information to install, protect, wire, and ground pulse width modulated (PWM) AC drives.
Preventive Maintenance of Industrial Control and Drive System Equipment, publication DRIVES-TD001
Provides a checklist as a guide in performing preventive maintenance.
Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control, publication SGI-1.1
Provide general guidelines for the application, installation, and maintenance of solid-state control in the form of individual devices or packaged assemblies incorporating solid-state components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.rockwellautomation.com/global/certification/overview.page
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 7
Preface
Manual Conventions • In this manual we refer to the PowerFlex 400 Adjustable Frequency AC Drive as; drive, PowerFlex 400 or PowerFlex 400 Drive.
• Parameter numbers and names are shown in this format:
• The following words are used throughout the manual to describe an action:
Drive Frame Sizes Similar PowerFlex 400 drive sizes are grouped into frame sizes to simplify spare parts ordering, dimensioning, etc. A cross reference of drive catalog numbers and their respective frame sizes is provided in Appendix B.
P031 [Motor NP Volts]
Name
Number
Groupb = Basic Display GroupP = Basic Program GroupT = Terminal Block GroupC = Communications GroupA = Advanced Program GroupR = Aux Relay Card Groupd = Advanced Display Group
Word Meaning
Can Possible, able to do something
Cannot Not possible, not able to do something
May Permitted, allowed
Must Unavoidable, you must do this
Shall Required and necessary
Should Recommended
Should Not Not Recommended
8 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Preface
General Precautions
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before performing any work on the drive. Measure the DC bus voltage at the –DC and +DC terminals or at the –DC and P2 terminals on the Power Terminal Block (refer to Chapter 1 Power Terminal descriptions). The voltage must be zero.A darkened LCD display and LEDs is not an indication that capacitors have discharged to safe voltage levels.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system.
ATTENTION: The bus regulator function is extremely useful for preventing nuisance overvoltage faults resulting from aggressive decelerations, overhauling loads, and eccentric loads. However, it can also cause either of the following two conditions to occur.1. Fast positive changes in input voltage or imbalanced input voltages can cause uncommanded positive speed changes;2. Actual deceleration times can be longer than commanded deceleration timesHowever, a “Stall Fault” is generated if the drive remains in this state for 1 minute. If this condition is unacceptable, the bus regulator must be disabled (see parameter A187).
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 9
Preface
Catalog Number Explanation
1-3 4 5 6-8 9 10 11 12
22C – D 038 A 1 0 3Drive Dash Voltage Rating Rating Enclosure HIM Emission Class Comm Slot
Code Drive
22C PowerFlex 400
Code Voltage Ph.
B 240V AC 3
D 480V AC 3
Output Current @ 200...240V 60Hz Input Output Current @ 380...480V Input
Code Amps kW HP Frame Code Amps kW HP Frame
012 12 2.2 3.0 C 6P0 6.0 2.2 3.0 C
017 17.5 3.7 5.0 C 010 10.5 4.0 5.0 C
024 24 5.5 7.5 C 012 12 5.5 7.5 C
033 33 7.5 10 C 017 17 7.5 10 C
049 49 11 15 D 022 22 11 15 C
065 65 15 20 D 030 30 15 20 C
075 75 18.5 25 D 038 38 18.5 25 D
090 90 22 30 D 045 45.5 22 30 D
120 120 30 40 E 060 60 30 40 D
145 145 37 50 E 072 72 37 50 E
088 88 45 60 E
105 105 55 75 E
142 142 75 100 E
170 170 90 125 F
208 208 110 150 F
260 260 132 200 G
310 310 160 250 G
370 370 200 300 H
460 460 250 350 H
Code Enclosure
N Panel Mount - IP20/UL Open-Type(1)
A Panel Mount - IP30/NEMA 1/UL Type 1(2)
F Flange Mount - IP20/UL Open Type(3)
Code Interface Module
1 Fixed Keypad
Code Rating
0 Not Filtered
Code Version
3 RS485
(1) Frame C drives only available with IP20/UL Open-Type enclosure. Field installed conversion kit available to achieve IP30/NEMA 1/UL Type 1 rating.(2) Frame D, E, F, G and H drives only available with IP30/NEMA 1/UL Type 1 enclosure.(3) Frame C drives only.
Additional accessories, options and adapters are available. See Appendix B for details.
10 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 1
Installation/Wiring
This chapter provides information on mounting and wiring the PowerFlex 400 Drive.
Most start-up difficulties are the result of incorrect wiring. Every precaution must be taken to assure that the wiring is done as instructed. All items must be read and understood before the actual installation begins.
For information on... See page
Opening the Cover 12
Mounting Considerations 15
AC Supply Source Considerations 18
General Grounding Requirements 19
Fuses and Circuit Breakers 21
Power Wiring 22
I/O Wiring Recommendations 28
Start and Speed Reference Control 37
RS485 Network Wiring 38
EMC Instructions 39
FCC Instructions 42
ATTENTION: The following information is merely a guide for proper installation. Rockwell Automation, Inc. cannot assume responsibility for the compliance or the noncompliance to any code, national, local or otherwise for the proper installation of this drive or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 11
Chapter 1 Installation/Wiring
Opening the Cover Frame C Drives
1. Press and hold in the tabs on each side of the cover.
2. Pull the cover out and up to release.
Frame D Drives
1. Loosen the two captive cover screws.
2. Pull the bottom of the cover out and up to release.
12 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Frame E Drives
1. Loosen the four captive cover screws.
2. Pull the bottom of the cover out and up to release.
Frame F Drives
1. Turn the latch counterclockwise.
2. Pull on the latch to swing the door open.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 13
Chapter 1 Installation/Wiring
Frame G Drives
1. 1. Loosen the four captive cover screws.
2. Pull the bottom of the cover out and up to release.
Frame H Drives
1. Loosen the four captive cover screws.
2. Pull the bottom of the cover out and up to release.
14 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Mounting Considerations • Mount the drive upright on a flat, vertical and level surface.
• Protect the cooling fan by avoiding dust or metallic particles.• Do not expose to a corrosive atmosphere.• Protect from moisture and direct sunlight.
Maximum Surrounding Air Temperature
Frame Screw Size Screw Torque
C M5 (#10-24) 2.45-2.94 N-m (22-26 lb.-in.)
D M8 (5/16 in.) 6.0-7.4 N-m (53.2-65.0 lb.-in.)
E M8 (5/16 in.) 8.8-10.8 N-m (78.0-95.3 lb.-in.)
F M10 (3/8 in.) 19.6-23.5 N-m (173.6-208.3 lb.-in.)
G M12 (1/2 in.) 33.5-41.0 N-m (296.5-362.9 lb.-in.)
H M12 (1/2 in.) 33.5-41.0 N-m (296.5-362.9 lb.-in.)
Frame Enclosure Rating Temperature Range Minimum Mounting Clearances
C IP 20/UL Open-Type -10° to 45°C(14° to 113°F)
See Figure 1, Mounting Option A
IP 30/NEMA 1/UL Type 1(1)
(1) Frame C drives require installation of the PowerFlex 400 IP 30/NEMA 1/UL Type 1 option kit to achieve this rating.
-10° to 45°C(14° to 113°F)
See Figure 1, Mounting Option B
IP 20/UL Open-Type -10° to 50°C(14° to 122°F)
See Figure 1, Mounting Option B
D IP 30/NEMA 1/UL Type 1 -10° to 45°C(14° to 113°F)
See Figure 2
E
F See Figure 3
G See Figure 4
H
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 15
Chapter 1 Installation/Wiring
Minimum Mounting Clearances
Refer to Appendix B for mounting dimensions.
Figure 1 - Frame C Mounting Clearances
Figure 2 - Frames D & E Mounting Clearances
120 mm(4.7 in.)
120 mm(4.7 in.)
25 mm(1.0 in.)
120 mm(4.7 in.)
120 mm(4.7 in.)
120 mm(4.7 in.)
120 mm(4.7 in.)
120 mm(4.7 in.)
120 mm(4.7 in.)
Closest object that may restrict air flow
through the drive heat sink and chassis.
Mounting Option ANo clearance required
between drives.
Mounting Option B
150 mm(6.0 in.)
150 mm(6.0 in.)
50 mm(2.0 in.)
50 mm(2.0 in.)
16 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Figure 3 - Frame F Mounting Clearances
Figure 4 - Frames G & H Mounting Clearances
Debris Protection
Frame C Drives – A plastic top panel is included with the drive. Install the panel to prevent debris from falling through the vents of the drive housing during installation. Remove the panel for IP 20/Open Type applications.
Frame D, E, F, G and H Drives – These drives have built-in debris protection. Installation of a protective panel is not required.
250 mm(9.8 in.)
150 mm(6.0 in.)
50 mm(2.0 in.)
50 mm(2.0 in.)
300 mm(11.8 in.)
300 mm(11.8 in.)
200 mm(1)
(7.9 in.)200 mm(1)
(7.9 in.)
(1)
(1) If the drive is installed with a side gap of 200 mm, it has to be removed from the shelf to change the fan. If the drive is installed with a side gap of 300 mm, it does not need to be removed from the shelf to change the fan.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 17
Chapter 1 Installation/Wiring
Storage• Store within an ambient temperature range of -40° to +85°C.• Store within a relative humidity range of 0% to 95%,non-condensing.• Do not expose to a corrosive atmosphere.
AC Supply Source Considerations
Ungrounded Distribution Systems
Disconnecting MOVs (Drive Frames C, E and F only.)
To prevent drive damage, the MOVs connected to ground shall be disconnected if the drive is installed on an ungrounded distribution system where the line-to-ground voltages on any phase could exceed 125% of the nominal line-to-line voltage. To disconnect these devices, remove the jumper shown in Figure 6.
Figure 5 - Phase to Ground MOV Removal
Figure 6 - MOV Jumper Location
ATTENTION: PowerFlex 400 drive frames contain protective MOVs that are referenced to ground. These devices must be disconnected if the drive is installed on an ungrounded or resistive grounded distribution system.
R/L1S/L2T/L3
1 2 3 4
Three-PhaseAC Input
Jumper
Frame C Frame E and F (Typical)
Important:Tighten screw after jumper removal.
18 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Note: Frame D, G and H drives do not contain a MOV to ground connection and are suitable for operation in both grounded and ungrounded distribution systems without modification.
Input Power Conditioning
The drive is suitable for direct connection to input power within the rated voltage of the drive (see Appendix A). Listed in Table 1 are certain input power conditions which may cause component damage or reduction in product life. If any of the conditions exist, as described in Table 1, install one of the devices listed under the heading Corrective Action on the line side of the drive.
General Grounding Requirements
The drive Safety Ground - (PE) must be connected to system ground. Ground impedance must conform to the requirements of national and local industrial safety regulations and/or electrical codes. The integrity of all ground connections should be periodically checked.
Figure 7 - Typical Grounding
IMPORTANT Only one device per branch circuit is required. The device should be mounted closest to the branch and sized to handle the total current of the branch circuit.
Table 1 - Input Power Conditions
Input Power Condition Corrective Action
Low Line Impedance (less than 1% line reactance) • Install Line Reactor(1)
• or Isolation Transformer
(1) Refer to Appendix B for accessory ordering information.
Line has power factor correction capacitors • Install Line Reactor(1)
• or Isolation TransformerLine has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V (lightning)
Phase to ground voltage exceeds 125% of normal line to line voltage
• Remove MOV jumper to ground (Frame C, E and F drives only)
• or Install Isolation Transformer with grounded secondary if necessaryUngrounded distribution system
SHLD
U/T1V/T2W/T3
R/L1S/L2T/L3
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 19
Chapter 1 Installation/Wiring
Ground Fault Monitoring
If a system ground fault monitor (RCD) is to be used, only Type B (adjustable) devices should be used to avoid nuisance tripping.
Safety Ground - (PE)
This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a floor ground rod or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the drive.
Shield Termination - SHLD
Either of the safety ground terminals located on the power terminal block provides a grounding point for the motor cable shield. The motor cable shield connected to one of these terminals (drive end) should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to the safety ground terminal. The conduit box may be used with a cable clamp for a grounding point for the cable shield.
When shielded cable is used for control and signal wiring, the shield should be grounded at the source end only, not at the drive end.
RFI Filter Grounding
Using an external filter with any drive rating, may result in relatively high ground leakage currents. Therefore, the filter must only be used in installations with grounded AC supply systems and be permanently installed and solidly grounded (bonded) to the building power distribution ground. Ensure that the incoming supply neutral is solidly connected (bonded) to the same building power distribution ground. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. Some local codes may require redundant ground connections. The integrity of all connections should be periodically checked.
20 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Fuses and Circuit Breakers The PowerFlex 400 does not provide branch short circuit protection. This product should be installed with either input fuses or an input circuit breaker. National and local industrial safety regulations and/or electrical codes may determine additional requirements for these installations.
Fusing
The ratings in the table that follows are the recommended values for use with each drive rating. The devices listed in this table are provided to serve as a guide.
Bulletin 140M (Self-Protected Combination Controller)/UL489 Circuit Breakers
When using Bulletin 140M or UL489 rated circuit breakers, the guidelines listed below must be followed in order to meet the NEC requirements for branch circuit protection.
• Bulletin 140M can be used in single and group motor applications.• Bulletin 140M can be used up stream from the drive without the need
for fuses.
Table 2 - Recommended Branch Circuit Protective Devices
Voltage Rating
Drive RatingkW (HP)
Fuse Rating(1)
Amps140M MotorProtectors(2)(3)
Catalog No.
Recommended MCS ContactorsCatalog No.
Min. EnclosureVolume(4)
Inches3
200-240V AC – 3-Phase
2.2 (3.0) 20 140M-F8E-C16 100-C23 5098
3.7 (5.0) 30 140M-F8E-C25 100-C37 5098
5.5 (7.5) 35 140M-F8E-C32 100-C37 5098
7.5 (10) 45 140M-F8E-C45 100-C45 5098
11 (15) 70 — 100-C60 —
15 (20) 90 — 100-C85 —
18.5 (25) 100 — 100-D95 —
22 (30) 125 — 100-D110 —
30 (40) 175 — 100-D180 —
37 (50) 200 — 100-D180 —
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 21
Chapter 1 Installation/Wiring
Power Wiring
380-480V AC –3-Phase
2.2 (3.0) 10 140M-D8E-C10 100-C09 5098
4.0 (5.0) 20 140M-D8E-C16 100-C16 5098
5.5 (7.5) 20 140M-D8E-C16 100-C23 5098
7.5 (10) 25 140M-D8E-C20 100-C23 5098
11 (15) 30 140M-F8E-C32 100-C30 5098
15 (20) 40 140M-F8E-C32 100-C37 5098
18.5 (25) 50 140M-F8E-C45 100-C60 9086
22 (30) 60 — 100-C60 —
30 (40) 80 — 100-C85 —
37 (50) 100 — 100-C85 —
45 (60) 125 — 100-D110 —
55 (75) 150 — 100-D140 —
75 (100) 200 — 100-D180 —
90 (125) 250 — 100-D210 —
110 (150) 250 — 100-D250 —
132 (200) 300 — 100-D300 —
160 (250) 400 — 100-D420 —
200 (300) 500 — 100-D420 —
250 (350) 600 — 100-D630 —
(1) Recommended Fuse Class: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
(2) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(3) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(4) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure.
Table 2 - Recommended Branch Circuit Protective Devices
Voltage Rating
Drive RatingkW (HP)
Fuse Rating(1)
Amps140M MotorProtectors(2)(3)
Catalog No.
Recommended MCS ContactorsCatalog No.
Min. EnclosureVolume(4)
Inches3
ATTENTION: National Codes and standards (NEC, VDE, BSI, etc.) and local codes outline provisions for safely installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection and disconnect devices. Failure to do so may result in personal injury and/or equipment damage.
ATTENTION: To avoid a possible shock hazard caused by induced voltages, unused wires in the conduit must be grounded at both ends. For the same reason, if a drive sharing a conduit is being serviced or installed, all drives using this conduit should be disabled. This will help minimize the possible shock hazard from “cross coupled” power leads.
22 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Motor Cable Types Acceptable for 200...600 Volt Installations
A variety of cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 0.3 meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases, long parallel runs must be avoided. Do not use cable with an insulation thickness less than 15 mils (0.4 mm/0.015 in.). Do not route more than three sets of motor leads in a single conduit to minimize “cross talk”. If more than three drive/motor connections per conduit are required, shielded cable must be used. UL installations must use 600V, 75°C or 90°C wire.Use copper wire only.
Unshielded
THHN, THWN or similar wire is acceptable for drive installation in dry environments provided adequate free air space and/or conduit fill rates limits are provided. Do not use THHN or similarly coated wire in wet areas. Any wire chosen must have a minimum insulation thickness of 15 mils and should not have large variations in insulation concentricity.
Shielded/Armored Cable
Shielded cable contains all of the general benefits of multi-conductor cable with the added benefit of a copper braided shield that can contain much of the noise generated by a typical AC Drive. Strong consideration for shielded cable should be given in installations with sensitive equipment such as weigh scales, capacitive proximity switches and other devices that may be affected by electrical noise in the distribution system. Applications with large numbers of drives in a similar location, imposed EMC regulations or a high degree of communications /networking are also good candidates for shielded cable.
Shielded cable may also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance of shielded cable may help extend the distance that the motor can be located from the drive without the addition of motor protective devices such as terminator networks. Refer to Reflected Wave in “Wiring and Grounding Guidelines for PWM AC Drives,” publication DRIVES-IN001A-EN-P.
Consideration should be given to all of the general specifications dictated by the environment of the installation, including temperature, flexibility, moisture characteristics and chemical resistance. In addition, a braided shield should be included and be specified by the cable manufacturer as having coverage of at least 75%. An additional foil shield can greatly improve noise containment.
A good example of recommended cable is Belden® 295xx (xx determines gauge). This cable has four (4) XLPE insulated conductors with a 100% coverage foil and an 85% coverage copper braided shield (with drain wire) surrounded by a PVC jacket.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 23
Chapter 1 Installation/Wiring
Other types of shielded cable are available, but the selection of these types may limit the allowable cable length. Particularly, some of the newer cables twist 4 conductors of THHN wire and wrap them tightly with a foil shield. This construction can greatly increase the cable charging current required and reduce the overall drive performance. Unless specified in the individual distance tables as tested with the drive, these cables are not recommended and their performance against the lead length limits supplied is not known.
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations with long motor cables may require the addition of external devices to limit voltage reflections at the motor (reflected wave phenomena). See Table 4 for recommendations.
The reflected wave data applies to all frequencies 2 to 10 kHz. For 240V ratings, reflected wave effects do not need to be considered.
Output Disconnect
The drive is intended to be commanded by control input signals that will start and stop the motor. A device that routinely disconnects then reapplies output power to the motor for the purpose of starting and stopping the motor should
Table 3 - Recommended Shielded Wire
Location Rating/Type Description
Standard(Option 1)
600V, 90°C (194°F)XHHW2/RHW-2Anixter B209500-B209507,Belden 29501-29507,or equivalent
• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and tinned copper drain wire.
• PVC jacket.
Standard(Option 2)
Tray rated 600V, 90°C(194°F) RHH/RHW-2Anixter OLF-7xxxxx or equivalent
• Three tinned copper conductors with XLPE insulation.
• 5 mil single helical copper tape (25% overlap min.) with three bare copper grounds in contact with shield.
• PVC jacket.
Class I & II;Division I & II
Tray rated 600V, 90°C(194°F) RHH/RHW-2Anixter 7V-7xxxx-3Gor equivalent
• Three bare copper conductors with XLPE insulation and impervious corrugated continuously welded aluminum armor.
• Black sunlight resistant PVC jacket overall.• Three copper grounds on #10 AWG and smaller.
Table 4 - Maximum Cable Length Recommendations
Reflected Wave
380...480V Ratings Motor Insulation Rating Motor Cable Only(1)
(1) Longer cable lengths can be achieved by installing devices on the output of the drive. Consult factory for recommendations.
1000 Vp-p 7.6 meters (25 feet)
1200 Vp-p 22.9 meters (75 feet)
1600 Vp-p 152.4 meters (500 feet)
24 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
not be used. If it is necessary to disconnect power to the motor with the drive outputting power, an auxiliary contact should be used to simultaneously disable drive control run commands.
Power Terminal Block
Frame C, D, F, G and H drives utilize a finger guard over the power wiring terminals. Replace the finger guard when wiring is complete.
Figure 8 - Power Terminal Blocks (Frames C through D)
Frame D
R/L1 S/L2 T/L3 P1 P2 DC– U/T1 V/T2 W/T3
Frame CR/L1 S/L2 T/L3 U/T1 V/T2 W/T3 P2 P1
BR–BR+DC+DC–
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 25
Chapter 1 Installation/Wiring
Figure 9 - Power Terminal Blocks (Frames E through H)
IMPORTANT For Frame E, 240V 30...37 kW (40...50 HP) and 480V 55...75 kW (75...100 HP) drives, take care to place the wire beneath the jumper and not above it when connecting to terminals P1 and P2.
R/L1 S/L2 T/L3 P1 P2 DC– U/T1 V/T2 W/T3
Frame E:240V 480V30-37 kW 55-75 kW(40-50 HP) (75-100 HP)
Frame F
R/L1S/L2 T/L3 P1 P2 DC– U/T1 V/T2 W/T3
Frame G
R/L1 S/L2 T/L3 P1 P2 DC– U/T1 V/T2 W/T3
Frame H
R/L1 S/L2 T/L3 DC–DC+ U/T1 V/T2 W/T3
Frame E:480V37-45 kW(50-60 HP)R/L1S/L2T/L3 P1 P2 DC– U/T1V/T2W/T3
See note at the bottom of this page.
P1 P2 DC- P1 P2 DC-
Bottom view of terminal block and wire
Jumper
Wire
Wire
Jumper
Correct Incorrect
26 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Table 5 - Power Terminal Descriptions
Terminal(1)
(1) Important: Terminal screws may become loose during shipment. Ensure that all terminal screws are tightened to the recommended torque before applying power to the drive.
Description
R/L1, S/L2, T/L3 3-Phase Input
U/T1 To Motor U/T1Switch any twomotor leads to change forward direction.
V/T2 To Motor V/T2 =
W/T3 To Motor W/T3
P2, P1 DC Bus Inductor Connection Drives are shipped with a jumper between Terminals P2 and P1. Remove this jumper only when a DC Bus Inductor will be connected. Drive will not power up without a jumper or inductor connected.
DC–, DC+ DC Bus Connection (Frame C and H Drives)
P2, DC– DC Bus Connection (Frame D, E, F and G Drives)
BR+, BR– Not Used
Safety Ground - PE
Table 6 - Power Terminal Block Specifications
Frame Maximum Wire Size(1)
(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations. If national or local codes require sizes outside this range, lugs may be used. Some ratings will require a pair of wires.
Minimum Wire Size(1) Recommended Torque
C 8.4 mm2 (8 AWG) 1.3 mm2 (16 AWG) 2.9 N-m (26 lb-in)
D 33.6 mm2 (2 AWG) 8.4 mm2 (8 AWG) 5.1 N-m (45 lb-in)
E 480V37...45 kW(50...60 HP)
33.6 mm2 (2 AWG) 3.5 mm2 (12 AWG) 5.6 N-m (49.5 lb-in)
E 240V30-37 kW(40...50 HP)480V55...75 kW(75...100 HP)
107.2 mm2 (4/0 AWG) 53.5 mm2 (1/0 AWG) 19.5 N-m (173 lb-in)
F 152.0 mm2 (300 MCM) 85.0 mm2 (3/0 AWG) 19.5 N-m (173 lb-in)
G 152.0 mm2 (300 MCM) 107.2 mm2 (4/0 AWG) 29.4 N-m (260 lb-in)
H 253.0 mm2 (500 MCM) 152.0 mm2 (300 MCM) 40.0 N-m (354 lb-in)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 27
Chapter 1 Installation/Wiring
I/O Wiring Recommendations Motor Start/Stop Precautions
Important points to remember about I/O wiring:• Always use copper wire.• Wire with an insulation rating of 600V or greater is recommended.• Control and signal wires should be separated from power wires by at
least 0.3 meters (1 foot).•
Control Wire Types
I/O Terminal Block
ATTENTION: A contactor or other device that routinely disconnects and reapplies the AC line to the drive to start and stop the motor can cause drive hardware damage. The drive is designed to use control input signals that will start and stop the motor. If used, the input device must not exceed one operation per minute or drive damage can occur.
ATTENTION: The drive start/stop control circuitry includes solid-state components. If hazards due to accidental contact with moving machinery or unintentional flow of liquid, gas or solids exist, an additional hardwired stop circuit may be required to remove the AC line to the drive. When the AC line is removed, there will be a loss of any inherent regenerative braking effect that might be present - the motor will coast to a stop. An auxiliary braking method may be required.
ATTENTION: Driving the 4-20 mA analog input from a voltage source could cause component damage. Verify proper configuration prior to applying input signals.
Table 7 - Recommended Control and Signal Wire(1)
(1) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.
Wire Type(s) Description Minimum Insulation Rating
Belden 8760/9460or equivalent
0.8 mm2 (18 AWG), twisted pair,100% shield with drain
300V60 °C(140 °F)
Belden 8770or equivalent
0.8 mm2 (18 AWG), 3 conductor,shielded for remote pot only.
Table 8 - I/O Terminal Block Specifications
Frame Maximum Wire Size(1)
(1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Minimum Wire Size(1) Torque
All 1.3 mm2 (16 AWG) 0.13 mm2 (26 AWG) 0.5...0.8 N-m (4.4...7 lb-in)
28 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Maximum Control Wire Recommendations
Do not exceed control wiring length of 30 meters (100 feet). Control signal cable length is highly dependent on electrical environment and installation practices. To improve noise immunity, the I/O terminal block Common must be connected to ground terminal/protective earth. If using the RS485 (DSI) port, I/O Terminal 20 should also be connected to ground terminal/protective earth.
Figure 10 - Control Wiring Block Diagram
(1) Important: I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set to option 1 “3-Wire” or 6 “2-W Lvl/Enbl”. In three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode]. All other stop sources are controlled by P037 [Stop Mode]. Important: The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove this jumper when using I/O Terminal 01 as a stop or enable input.
(2) Two wire control shown. For three wire control use a momentary input on I/O Terminal 02 to command a start. If reverse is enabled by A166, use a maintained input for I/O Terminal 03 to change direction.
(3) When using an opto output with an inductive load such as a relay, install a recovery diode parallel to the relay as shown, to prevent damage to the output.
(4) When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a hardware enable, causing a coast to stop without software interpretation.
(5) Most I/O terminals labeled “Common” are not referenced to the safety ground (PE) terminal and are designed to greatly reduce common mode interference. Frame D...H drives have Analog Common 1 referenced to ground.
04
05
06
07
01
02
03
08
09
10
12
13
14
15
16
17
18
19
20
11
Digital Common
Digital Common
Digital Input 1
Digital Input 2
Digital Input 3
Stop/Function Loss
(1)(4)
Start/Run FWD (2)
Direction/Run REV
Digital Input 4
Opto Common
R1
R2
R3
#1 Relay N.O.
#1 Relay Common
#1 Relay N.C.
+24V DC Source
+10V DC Source
Analog Input 1 (AI1)
Analog Common 1
Analog Output 2 (AO2)
Analog Output 1 (AO1)
Analog Input 2 (AI2)
Analog Common 2 (6)
Opto Output
RS485 Shield
+24V
+10V
R4
R5
R6
#2 Relay N.O.
#2 Relay Common
#2 Relay N.C.
TypicalSNK Wiring
TypicalSRC Wiring
RS485(DSI)
Enable (4)
Jumper
30V DC50mANon-inductive
Common24V
ENBL
(3)
Pot must be1-10k ohm2 Watt Min.
SRCSNK
SNK
SRC
Earth Referenced Frames D & E
(5)
0-10V
0-20mA
0-10V
0-20mA
0-10V0-20mA
1 of 7 Digital Input Circuits
10V 20MAAO1
10V 20MAAO2
10V 20MAAI1
10V 20MAAI2
Isolated
P036 [Start Source] Stop I/O Terminal 01 Stop
Keypad Per P037 Coast
3-Wire Per P037 Per P037(4)
2-Wire Per P037 Coast
RS485 Port Per P037 Coast
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 29
Chapter 1 Installation/Wiring
(6) Common for Analog Input 2 (AI2). Electronically isolated from digital I/O and opto output. Not to be used with Analog Input 1 (AI1), Analog Output 1 (AO1) or Analog Output 2 (AO2). With Analog Input 2, provides one fully isolated analog input channel.
Table 9 - Control I/O Terminal Designations
No. Signal Default Description Param.
01 Stop(1) /Function Loss
Coast Factory installed jumper or a normally closed input must be present for the drive to start. Program with P036 [Start Source].
P036 (1)
02 Start/Run FWD – HAND Mode: Command comes from Integral Keypad. AUTO Mode: I/O Terminal 02 is active.Program with P036 [Start Source].
P036, P037
03 Direction/Run REV Rev Disabled To enable reverse operation, program with A166 [Reverse Disable].Program with P036 [Start Source].
P036, P037, A166
04 Digital Common – For digital inputs. Tied to I/O Terminal 09.Electronically isolated with digital inputs from analog I/O and opto output.
05 Digital Input 1 Purge(2) Program with T051 [Digital In1 Sel]. T051
06 Digital Input 2 Local Program with T052 [Digital In2 Sel]. T052
07 Digital Input 3 Clear Fault Program with T053 [Digital In3 Sel]. T053
08 Digital Input 4 Comm Port Program with T054 [Digital In4 Sel]. T054
09 Digital Common – For digital inputs. Tied to I/O Terminal 04.Electronically isolated with digital inputs from analog I/O and opto output.
10 Opto Common – For opto-coupled outputs. Electronically isolated with opto output from analog I/O and digital inputs.
11 +24V DC – Drive supplied power for digital inputs.Referenced to Digital Common. Max. Output: 100mA.
12 +10V DC – Drive supplied power for 0-10V external potentiometer.Referenced to Analog Common. Max. Output: 15mA.
P038
13 Analog Input 1 0-10V External 0-10V (unipolar), 0-20mA or 4-20mA input supply or potentiometer wiper. Default input is 0-10V.For current (mA) input, set AI1 DIP Switch to 20mA. Program with T069 [Analog In 1 Sel].Input Impedance: 100k ohm (Voltage Mode)
250 ohm (Current Mode)
T069, T070, T071, T072
14 Analog Common 1 – Common for Analog Input 1 and Analog Output 1 and 2. Electrically isolated from digital I/O and opto output.
15 Analog Output 1 OutFreq 0-10 Default analog output is 0-10V.For current (mA) value, set AO1 DIP Switch to 20mA. Program with T082 [Analog Out1 Sel].Maximum Load: 4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
P038, T051...T054, A152
16 Analog Output 2 OutCurr 0-10 Default analog output is 0-10V.For a current (mA) value, set AO2 DIP Switch to 20mA. Program with T085 [Analog Out2 Sel].Maximum Load: 4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
T082, T084, T085, T086, T087
17 Analog Input 2 0-10V Optically isolated external 0-10V (unipolar), ±10V (bipolar), 0-20mA or 4-20mA input supply or potentiometer wiper. Default input is 0-10V.For current (mA) input, set AI2 DIP Switch to 20mA. Program with T073 [Analog In 2 Sel].Input Impedance: 100k ohm (Voltage Mode)
250 ohm (Current Mode)
T073, T074, T075, T076
30 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Figure 11 - User Installed Auxiliary Relay Card (Frames D, E, F, G and H Only)
18 Analog Common 2 – For Analog Input 2. Electronically isolated from digital I/O and opto output. With Analog Input 2, provides one fully isolated analog input channel.
19 Opto Output At Frequency Program with T065 [Opto Out Sel]. T065, T066, T068
20 RS485 (DSI) Shield – Terminal connected to Safety Ground - PE when using the RS485 (DSI) Communication Port.
(1) See Footnotes (1) and (4) on page 29.
(2) Important information regarding Stop commands and the [Digital Inx Sel] Purge option is provided on page 66.
Table 10 - Relay Terminal Designations and DIP Switches
No. Signal Default Description Param.
R1 #1 Relay N.O. Ready/Fault Normally open contact for No. 1 output relay. T055
R2 #1 Relay Common – Common for output relay.
R3 #1 Relay N.C. Ready/Fault Normally closed contact for No. 1 output relay. T055
R4 #2 Relay N.O. Motor Running Normally open contact for No. 2 output relay. T060
R5 #2 Relay Common – Common for output relay.
R6 #2 Relay N.C. Motor Running Normally closed contact for No. 2 output relay. T060
Selection DIP Switches:Analog Input (AI1 & AI2)Analog Output (AO1 & AO2)
0-10V Sets analog output to either voltage or current.Settings must match: AI1 & T069 [Analog In 1 Sel]
AI2 & T073 [Analog In 2 Sel]AO1 & T082 [Analog Out1 Sel]AO2 & T085 [Analog Out2 Sel]
Sink/Source DIP Switch Source (SRC) Inputs can be wired as Sink (SNK) or Source (SRC)via DIP Switch setting.
Table 9 - Control I/O Terminal Designations
No. Signal Default Description Param.
3A 3B 4A 4B 5A 5B
6A 6B 7A 7B 8A 8B
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 31
Chapter 1 Installation/Wiring
I/O Wiring Examples
IMPORTANT If using auxiliary motor control, ensure that wiring and parameter configuration are correct before wiring contactor outputs. All relays on the Auxiliary Relay Card will energize on power-up by default. Failure to verify proper wiring and parameter configuration can result in improper motor operation or drive damage. Refer to Appendix D for more details.
Table 11 - User Installed Relay Board Terminal Designations
No. Signal Default Description Param.
3A #3 Relay N.O. Ready/Fault Normally open contact for Number 3 Output Relay R221
3B #3 Relay Common – Common for Number 3 Output Relay
4A #4 Relay N.O. Ready/Fault Normally open contact for Number 4 Output Relay R224
4B #4 Relay Common – Common for Number 4 Output Relay
5A #5 Relay N.O. Ready/Fault Normally open contact for Number 5 Output Relay R227
5B #5 Relay Common – Common for Number 5 Output Relay
6A #6 Relay N.O. Ready/Fault Normally open contact for Number 6 Output Relay R230
6B #6 Relay Common – Common for Number 6 Output Relay
7A #7 Relay N.O. Ready/Fault Normally open contact for Number 7 Output Relay R233
7B #7 Relay Common – Common for Number 7 Output Relay
8A #8 Relay N.O. Ready/Fault Normally open contact for Number 8 Output Relay R236
8B #8 Relay Common – Common for Number 8 Output Relay
Input/Output Connection Example Required Settings
Potentiometer1-10k Ohm PotentiometerRecommended(2 Watt Minimum)
DIP SwitchAI1 = 10V
ParametersP038 [Speed Reference] = 2 “Analog In1”T069 [Analog In 1 Sel] = 2 “0-10V”
ScalingT070 [Analog In 1 Lo]T071 [Analog In 1 Hi]
Check Resultsd305 [Analog In 1]
Analog InputBipolar Speed Reference,±10V Input
DIP SwitchAI2 = 10V
ParametersP038 [Speed Reference] = 3 “Analog In2”T073 [Analog In 2 Sel] = 3 “-10 to +10V”
ScalingT074 [Analog In 2 Lo]T075 [Analog In 2 Hi]
Check Resultsd306 [Analog In 2]
121314
1718
-/+ 10V
Common
32 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Analog InputUnipolar Speed Reference,0 to +10V Input
DIP SwitchAI1 = 10V
ParametersP038 [Speed Reference] = 2 “Analog In1”T069 [Analog In 1 Sel] = 2 “0-10V”
ScalingT070 [Analog In 1 Lo]T071 [Analog In 1 Hi]
Check Resultsd305 [Analog In 1]
Analog InputUnipolar Speed Reference,4-20 mA Input
DIP SwitchAI1 = 20MA
ParametersP038 [Speed Reference] = 2 “Analog In1”T069 [Analog In 1 Sel] = 1 “4-20 mA”
ScalingT070 [Analog In 1 Lo]T071 [Analog In 1 Hi]
Check Resultsd305 [Analog In 1]
Analog OutputUnipolar, 0 to +10V Output• 1k Ohm Minimum
DIP SwitchAO1 = 10V
ParametersT082 [Analog Out1 Sel] = 0 through 6
ScalingT083 [Analog Out1 High]T084 [Analog Out1 Setpt]
Analog OutputUnipolar, 4-20 mA Output• 525 Ohm Maximum
DIP SwitchAO2 = 20MA
ParametersT082 [Analog Out1 Sel] = 14 through 20
ScalingT083 [Analog Out1 High]T084 [Analog Out1 Setpt]
2 Wire ControlSourcing (SRC),Internal Supply,Non-Reversing• Input must be active for
the drive to run.• When input is opened, the
drive will stop as specified by P037 [Stop Mode].
• Drive will not run if I/O Terminal 01 is open. Drive will coast to stop if opened while running
DIP SwitchSNK/SRC = SRCParametersP036 [Start Source] = 2, 3, 4P037 [Stop Mode] = 0 through 7
Input/Output Connection Example Required Settings
1314
+
Common
1314
+
Common
1415
Common
+
14
16
Common
+
11 0102
Stop-Run
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 33
Chapter 1 Installation/Wiring
2 Wire ControlSourcing (SRC),External Supply,Non-Reversing• Input must be active for
the drive to run.• When input is opened, the
drive will stop as specified by P037 [Stop Mode].
• User supplied 24V DC power source must be used.
• Each digital input draws 6 mA.
• Drive will not run if I/O Terminal 01 is open. Drive will coast to stop if opened while running.
DIP SwitchSNK/SRC = SRC
ParametersP036 [Start Source] = 2, 3, 4P037 [Stop Mode] = 0 through 7
2 Wire ControlSinking (SNK),Internal Supply,Non-Reversing• Input must be active for
the drive to run.• When input is opened, the
drive will stop as specified by P037 [Stop Mode].
• Drive will not run if I/O Terminal 01 is open. Drive will coast to stop if opened while running.
DIP SwitchSNK/SRC = SNK
ParametersP036 [Start Source] = 2, 3, 4P037 [Stop Mode] = 0 through 7
2 Wire ControlSourcing (SRC),Internal Supply,Run FWD/Run REV• Input must be active for
the drive to run.• When input is opened, the
drive will stop as specified by P037 [Stop Mode].
• If both Run FWD and Run REV inputs are closed at the same time, an undetermined state could occur.
• Drive will not run if I/O Terminal 01 is open. Drive will coast to stop if opened while running.
DIP SwitchSNK/SRC = SRC
ParametersP036 [Start Source] = 2, 3, 4P037 [Stop Mode] = 0 through 7A166 [Reverse Disable] = 0 “Enabled”
Input/Output Connection Example Required Settings
+24V Common
0102
04
Stop-Run
0102
04
Stop-Run
11 010203
Stop-RunForward
Stop-RunReverse
34 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
2 Wire Control with Function Loss and SW EnableSourcing (SRC),Internal Supply,Non-Reversing• Input must be active for
the drive to run.• When input is opened, the
drive will stop as specified by P037 [Stop Mode].
• Drive will not run if I/O Terminal 03 is open. Drive will coast to stop if opened while running.
• Drive will fault if I/O Terminal 01 is open. Drive will coast to stop if opened while running. Requires drive reset once terminal is closed.
DIP SwitchSNK/SRC = SRC
ParametersP036 [Start Source] = 6 “2-W Lvl/Enbl”P037 [Stop Mode] = 0 through 7
3 Wire ControlSourcing (SRC),Internal Supply,Non-Reversing• A momentary input will
start the drive.• A stop input to I/O
Terminal 01 will stop the drive as specified by P037 [Stop Mode].
DIP SwitchSNK/SRC = SRC
ParametersP036 [Start Source] = 1 “3-Wire”P037 [Stop Mode] = 0 through 7
3 Wire ControlSourcing (SRC),Internal Supply,Reversing• A momentary input will
start the drive.• A stop input to I/O
Terminal 01 will stop the drive as specified by P037 [Stop Mode].
• I/O Terminal 03 determines direction.
DIP SwitchSNK/SRC = SRC
ParametersP036 [Start Source] = 1 “3-Wire”P037 [Stop Mode] = 0 through 7A166 [Reverse Disable] = 0 “Rev Enabled”
Opto Output• When using Opto Output
with an inductive load such as a relay, install a recovery diode parallel to the relay as shown to prevent damage to the output.
• Opto Output is rated 30V DC, 50 mA (non-inductive).
ParametersT065 [Opto Out Sel] = 0 through 15T066 [Opto Out Level]T068 [Opto Out Logic]
Input/Output Connection Example Required Settings
Function Loss
Run FWD
SW Enable
11 010203
11 0102
Stop
Start
11 010203
Stop
Start
Direction
Common+24V
CR0919
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 35
Chapter 1 Installation/Wiring
Typical Multiple Drive Connection Examples
Input/Output Connection Example
Multiple DigitalInput ConnectionsCustomer Inputs can be wired per the External Supply (SRC) example on page 34.
When connecting a single input such as Run, Stop, Reverse or Preset Speeds to multiple drives, it is important to connect I/O Terminal 04 common together for all drives. If they are to be tied into another common (such as earth ground or separate apparatus ground) only one point of the daisy chain of I/O Terminal 04 should be connected.
Multiple Analog Connections
When connecting a single potentiometer to multiple drives it is important to connect I/O Terminal 14 common together for all drives. I/O Terminal 14 common and I/O Terminal 13 (potentiometer wiper) should be daisy-chained to each drive. All drives must be powered up for the analog signal to be read correctly.
Customer Inputs Optional Ground Connection
04020402 0402
ATTENTION: Digital inputs on multiple drives should not be tied together when using SNK (Internal Supply) mode. In SNK mode, if power is removed from one drive, inadvertent operation of other drives that share the same I/O Common connection may occur.
Remote Potentiometer Optional Ground Connection
12 13 1413 14 13 14
36 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Start and Speed Reference Control
The drive speed command can be obtained from a number of different sources. The source is normally determined by P038 [Speed Reference]. The drive Start command is normally determined by P036 [Start Source]. However, the settings for these parameters can be overridden by a variety of methods. See the chart below for the override priority.
Purge InputEnabled and Active:[Digital Inx Sel] = 1
Local InputEnabled and Active[Digital Inx Sel] = 3
No
YesStart, Speed and Direction commands
come from Integral Keypad.
Direction is Forward unless an input isprogrammed for "Keypad/Jog Direction"
Auto InputEnabled and Active[Digital Inx Sel] = 2
No
Yes
Run as specified byP038 [Speed Reference].
Start and Direction commandscome from P036 [Start Source].
Comm Select InputEnabled and Active:[Digital Inx Sel] = 4
No
Yes Start, Speed and Direction commandscome from RS485 (DSI) port.
Drive is inHand/Local Mode
selected by AUTO key(1)
No
Yes
Start and Speed commandscome from Integral Keypad.
Direction is Forward unless an input isprogrammed for "Cmd Reverse"
Analog Input 1Override Enabled & Active:
[Digital Inx Sel] = 14
Analog Input 2Override Enabled & Active:
[Digital Inx Sel] = 15
No
Yes
Speed commands come fromAnalog Input 1 (I/O Terminal 13).
Start and Directionfollows P036 [Start Source].
Speed commands come fromAnalog Input 2 (I/O Terminal 17).
Start and Directionfollows P036 [Start Source].
No
Yes
P038 [Speed Reference]= 4 or 5
No
Yes
Run as specified byP038 [Speed Reference].
Start and Direction commands come from P036 [Start Source].
Run as specified byA144-A146 [Preset Freq 1-3].
Start follows P036 [Start Source],Direction follows
Preset Frequency settings.
Preset Inputs ActiveT051/T052/T053 = 8
No
Yes
Run as specified byA152 [PID Ref Sel].
Start and Direction commands come from P036 [Start Source].
PID Enabled:A152 [PID Ref Sel] ¹ 0
No
Yes
Run as specified by P038 [Speed Reference].
Start and Direction commands come from P036 [Start Source].
No
YesDrive will Start and Run as
specified by A141 [Purge Frequency].
Direction is always Forward.
(1) Refer to page 50 for additional information on the operation of the Hand/Auto Mode.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 37
Chapter 1 Installation/Wiring
Accel/Decel Selection
The Accel/Decel rate can be obtained by a variety of methods. The default rate is determined by P039 [Accel Time 1] and P040 [Decel Time 1]. Alternative Accel/Decel rates can be made through digital inputs, RS485 (DSI) communications and/or parameters. See the chart below for the override priority.
RS485 Network Wiring Network wiring consists of a shielded 2-conductor cable that is daisy-chained from node to node.
Figure 12 - Network Wiring Diagram
Only pins 4 and 5 on the RJ45 plug should be wired. The other pins on the PowerFlex 400 RJ45 socket contain power, etc. for other Rockwell Automation peripheral devices and must not be connected.
RS485 (DSI) PortControls Speed
No
Yes
EitherP039 [Accel Time 1]/P040 [Decel Time 1]
orA147 [Accel Time 2]/A148 [Decel Time 2]
can be selected whenRS485 (DSI) port is active.
Input is programmedas "Acc & Dec 2"
[Digital Inx Sel] = 18
No
Yes A147 [Accel Time 2]/A148 [Decel Time 2]is active when input is active.
Speed is controlledby [Preset Freq x]
No
Yes
P039 [Accel Time 1]/P040 [Decel Time 1];A147 [Accel Time 2]/A148 [Decel Time 2]
determined by the activePreset Frequency.
See A143-A146 [Preset Freq 0-3]
Drive is performing anAuxiliary Motor AutoSwap
No
Yes A147 [Accel Time 2]/A148 [Decel Time 2]are used.
P039 [Accel Time 1]/P040 [Decel Time 1]are used.
MasterPowerFlex 400
Node 1
4
5
PowerFlex 400Node 2
4
5
PowerFlex 400Node "n"
4
5
TxRxD+
TxRxD-
TxRxD+
TxRxD-
TxRxD+
TxRxD-
NOTE: The shield should be grounded at ONLY ONE location.
Shield Shield Shield
120 ohm resistor
120 ohm resistor
FRONT
PIN 8PIN 1
38 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Wiring terminations on the master controller will vary depending on the master controller used and “TxRxD+” and “TxRxD-” are shown for illustration purposes only. Refer to the master controller’s user manual for network terminations. Note that there is no standard for the “+” and “-” wires, and consequently Modbus device manufacturers interpret them differently. If you have problems with initially establishing communications, try swapping the two network wires at the master controller.
On Drive Connections
PowerFlex 400 Frame D, E, F, G and H drives are equipped with two RS485 (DSI) ports. One is accessible via an access door when the cover is on and one is only accessible with the cover off. When one of these ports has a Rockwell DSI device connected, the second port cannot be used.
Figure 13 - Frame D, E, F, G and H RS485 Ports
EMC Instructions CE Conformity
Conformity with the Low Voltage (LV) Directive and Electromagnetic Compatibility (EMC) Directive has been demonstrated using harmonized European Norm (EN) standards published in the Official Journal of the European Communities. PowerFlex Drives comply with the EN standards listed below when installed according to the User Manual.
CE Declarations of Conformity are available online at:http://www.rockwellautomation.com/certification/overview.page.
Low Voltage Directive (2014/35/EU)• EN 61800-5-1 Electronic equipment for use in power installations.
EMC Directive (2014/30/EU)• EN61800-3 Adjustable speed electrical power drive systems Part 3:
EMC product standard including specific test methods.
RS485 (DSI) Network Connection
Second RS485 (DSI) Connection
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 39
Chapter 1 Installation/Wiring
General Notes
All Drive Frames• The motor cable should be kept as short as possible in order to avoid
electromagnetic emission as well as capacitive currents.• Use of line filters in ungrounded systems is not recommended.• Conformity of the drive with CE EMC requirements does not
guarantee an entire machine installation complies with CE EMC requirements. Many factors can influence total machine/installation compliance.
Frame C Drives Only• If the plastic top panel is removed or the optional conduit box is not
installed, the drive must be installed in an enclosure with side openings less than 12.5 mm (0.5 in.) and top openings less than 1.0 mm (0.04 in.) to maintain compliance with the LV Directive.
Essential Requirements for CE Compliance
Conditions 1...4 listed below must be satisfied for PowerFlex drives to meet the requirements of EN61800-3.
1. Grounding as described in Figure 14. Refer to page 20 for additional grounding recommendations.
2. Output power, control (I/O) and signal wiring must be braided, shielded cable with a coverage of 75% or better, metal conduit or equivalent attenuation.
3. All shielded cables should terminate with the proper shield connector.
4. Conditions in Table 12.
Table 12 - PowerFlex 400 – EN61800-3 Compliance
PowerFlex 400 Drive First Environment Restricted First Environment Unrestricted
kW(HP)
Cat No.22C-...
Required Filter(Allen-Bradley)
RestrictMotorCable to(Meters)
InstallDrive andFilter inShieldedEnclosure
Required Filter RestrictMotorCable to(Meters)
InstallDrive andFilter inShieldedEnclosure
200...240 Volts
2.2 (3.0) B012N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
3.7 (5.0) B017N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
5.5 (7.5) B024N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
7.5 (10) B033N103 22-RF034-CS 10 No 22-RF034-CS 1 Required
11 (15) B049A103 22-RFD070 150 Required Deltron MIF Series 50 Required
15 (20) B065A103 22-RFD100 150 Required Deltron MIF Series 50 Required
18.5 (25) B075A103 22-RFD100 150 Required Deltron MIF Series 50 Required
22 (30) B090A103 22-RFD150 150 Required Deltron MIF Series 50 Required
40 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Figure 14 - Connections and Grounding
(1) Shielded Enclosure required to meet EN61800-3 First Environment Restricted for 200-240V AC 11-22 kW (15-30 HP) PowerFlex 400 drives and to meet EN61800-3 First Environment Unrestricted for all PowerFlex 400 ratings.
30 (40) B120A103 22-RFD150 150 No Deltron MIF Series 50 Required
37 (50) B145A103 22-RFD180 150 No Deltron MIF Series 75 Required
380...480 Volts
2.2 (3.0) D6P0N103 22-RF018-CS 10 No 22-RF018-CS 1 Required
4.0 (5.0) D010N103 22-RF018-CS 10 No 22-RF018-CS 1 Required
5.5 (7.5) D012N103 22-RF018-CS 10 No 22-RF018-CS 1 Required
7.5 (10) D017N103 22-RF018-CS 10 No 22-RF018-CS 1 Required
11 (15) D022N103 22-RF026-CS 10 No 22-RF026-CS 1 Required
15 (20) D030N103 22-RFD036 100 No Deltron MIF Series 5 Required
18.5 (25) D038A103 22-RFD050 150 No Deltron MIF Series 5 Required
22 (30) D045A103 22-RFD050 150 No Deltron MIF Series 5 Required
30 (40) D060A103 22-RFD070 50 No Deltron MIF Series 5 Required
37 (50) D072A103 22-RFD100 50 No Deltron MIF Series 5 Required
45 (60) D088A103 22-RFD100 50 No Deltron MIF Series 5 Required
55 (75) D105A103 22-RFD150 150 No Deltron MIF Series 5 Required
75 (100) D142A103 22-RFD180 50 No Deltron MIF Series 5 Required
90 (125) D170A103 22-RFD208 50 No 22-RFD208 5 Required
110 (150) D208A103 22-RFD208 50 No 22-RFD208 5 Required
132 (200) D260A103 22-RFD323 50 Required 22-RFD323 5 Required
160 (250) D310A103 22-RFD480 50 Required 22-RFD480 5 Required
200 (300) D370A103 22-RFD480 50 Required 22-RFD480 5 Required
250 (350) D460A103 22-RFD480 50 Required 22-RFD480 5 Required
Table 12 - PowerFlex 400 – EN61800-3 Compliance
PowerFlex 400 Drive First Environment Restricted First Environment Unrestricted
kW(HP)
Cat No.22C-...
Required Filter(Allen-Bradley)
RestrictMotorCable to(Meters)
InstallDrive andFilter inShieldedEnclosure
Required Filter RestrictMotorCable to(Meters)
InstallDrive andFilter inShieldedEnclosure
R/L1S/L2T/L3
U/T1V/T2W/T3
EMI Fittings and Metal Conduit
IP 30/NEMA 1/UL Type 1Option Kit (Frame C Drives Only)
Shielded Enclosure (1)
Building Structure Steel
Enclosure Ground Connection
EMI Filter
L1'L2'L3'
L1L2L3
Shielded Motor Cable
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 41
Chapter 1 Installation/Wiring
FCC Instructions FCC Compliance
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules when installed according to the User Manual. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the User Manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense.
Essential Requirements for FCC Compliance
Conditions 1...4 listed below must be satisfied for PowerFlex 400 drives to meet the requirements of FCC Part 15 Subpart B.
1. Grounding as described in Figure 15. Refer to page 20 for additional grounding recommendations.
2. Output power, control (I/O) and signal wiring must be braided, shielded cable with a coverage of 75% or better, metal conduit or equivalent attenuation.
3. All shielded cables should terminate with the proper shield connector.
4. Conditions in Table 13.
Table 13 - PowerFlex 400 – FCC Part 15 Subpart B Compliance
PowerFlex 400 Drive Required Filter Restrict MotorCable to (Meters)
Install Drive andFilter in Enclosure
kW (HP) Cat No.
200...240 Volts
2.2 (3.0) 22C-B012N103 22-RF034-CS 10 No
3.7 (5.0) 22C-B017N103 22-RF034-CS 10 No
5.5 (7.5) 22C-B024N103 22-RF034-CS 10 No
7.5 (10) 22C-B033N103 22-RF034-CS 10 No
11 (15) 22C-B049A103 22-RFD070 150 Required
15 (20) 22C-B065A103 22-RFD100 150 Required
18.5 (25) 22C-B075A103 22-RFD100 150 Required
22 (30) 22C-B090A103 22-RFD150 150 Required
30 (40) 22C-B120A103 22-RFD150 150 No
37 (50) 22C-B145A103 22-RFD180 150 No
380...480 Volts
2.2 (3.0) 22C-D6P0N103 22-RF018-CS 10 No
4.0 (5.0) 22C-D010N103 22-RF018-CS 10 No
5.5 (7.5) 22C-D012N103 22-RF018-CS 10 No
42 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Installation/Wiring Chapter 1
Figure 15 - Connections and Grounding
(1) Shielded Enclosure required for 200-240V AC 11-22 kW (15-30 HP) PowerFlex 400 drives.
7.5 (10) 22C-D017N103 22-RF018-CS 10 No
11 (15) 22C-D022N103 22-RF026-CS 10 No
15 (20) 22C-D030N103 22-RFD036 100 No
18.5 (25) 22C-D038A103 22-RFD050 150 No
22 (30) 22C-D045A103 22-RFD050 150 No
30 (40) 22C-D060A103 22-RFD070 50 No
37 (50) 22C-D072A103 22-RFD100 50 No
45 (60) 22C-D088A103 22-RFD100 50 No
55 (75) 22C-D105A103 22-RFD150 150 No
75 (100) 22C-D142A103 22-RFD180 50 No
90 (125) 22C-D170A103 22-RFD208 50 No
110 (150) 22C-D208A103 22-RFD208 50 No
132 (200) 22C-D260A103 22-RFD323 50 Required
160 (250) 22C-D310A103 22-RFD480 50 Required
200 (300) 22C-D370A103 22-RFD480 50 Required
250 (350) 22C-D460A103 22-RFD480 50 Required
Table 13 - PowerFlex 400 – FCC Part 15 Subpart B Compliance
PowerFlex 400 Drive Required Filter Restrict MotorCable to (Meters)
Install Drive andFilter in Enclosure
kW (HP) Cat No.
R/L1S/L2T/L3
U/T1V/T2W/T3
EMI Fittings and Metal Conduit
IP 30/NEMA 1/UL Type 1Option Kit (Frame C Drives Only)
Shielded Enclosure (1)
Building Structure Steel
Enclosure Ground Connection
EMI Filter
L1'L2'L3'
L1L2L3
Shielded Motor Cable
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 43
Chapter 1 Installation/Wiring
Notes:
44 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 2
Start Up
This chapter describes how to start up the PowerFlex 400 Drive. To simplify drive setup, the most commonly programmed parameters are organized in a single Basic Program Group.
Prepare For Drive Start-Up Before Applying Power to the Drive
1. Confirm that all inputs are connected to the correct terminals and are secure.
2. Verify that AC line power at the disconnect device is within the rated value of the drive.
3. Verify that any digital control power is 24 volts.
4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to match your control wiring scheme. See Table 9 on page 30 for location.
For information on... See page
Prepare For Drive Start-Up 45
Integral Keypad 47
Viewing and Editing Parameters 49
IMPORTANT Read the General Precautions section before proceeding.
ATTENTION: Power must be applied to the drive to perform the following start-up procedures. Some of the voltages present are at incoming line potential. To avoid electric shock hazard or damage to equipment, only qualified service personnel should perform the following procedure. Thoroughly read and understand the procedure before beginning. If an event does not occur while performing this procedure, Do Not Proceed. Remove All Power including user supplied control voltages. User supplied voltages may exist even when main AC power is not applied to the drive. Correct the malfunction before continuing.
IMPORTANT The default control scheme is Source (SRC). The Stop terminal is jumpered (I/O Terminals 01 and 11) to allow starting from the keypad. If the control scheme is changed to Sink (SNK), the jumper must be removed from I/O Terminals 01 and 11 and installed between I/O Terminals 01 and 04.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 45
Chapter 2 Start Up
5. Verify that the Stop input is present or the drive will not start.
6. Verify that the Analog I/O DIP Switches are set to 10 volts.
Applying Power to the Drive7. Apply AC power and control voltages to the drive.
8. . 8. Familiarize yourself with the integral keypad features (see page 47) before setting any Program Group parameters.
Start, Stop, Direction and Speed Control
Factory default parameter values allow the drive to be controlled from the integral keypad. No programming is required to start, stop, and control speed directly from the integral keypad.
If a fault appears on power up, refer to Fault Descriptions on page 115 for an explanation of the fault code.
IMPORTANT If I/O Terminal 01 is used as a stop input, the jumper between I/O Terminals 01 and 11 must be removed.
46 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Start Up Chapter 2
Integral Keypad
Operator Keys
Key Name Description
Escape Back one step in programming menu.Cancel a change to a parameter value and exit Program Mode.
Select Advance one step in programming menu.Select a digit when viewing parameter value.
Up ArrowDown Arrow
Scroll through groups and parameters.Increase/decrease the value of a flashing digit.
Enter Advance one step in programming menu.Save a change to a parameter value.
Digital Speed Increment and Decrement Arrows
Used to control speed of drive. Default is active.Control is activated by parameter P038 [Speed Reference] or P042 [Auto Mode].
Run/Start & Hand(1)
(1) Important: Certain digital input settings can override drive operation. Refer to Start and Speed Reference Control on page 37 for details.
Used to start the drive. Default is Hand mode as controlled by parameter P042 [Auto Mode].Control is activated by parameter P036 [Start Source] or P042 [Auto Mode].
Auto(1) Used to select Auto control mode.Controlled by parameter P042 [Auto Mode].
Stop/Off Used to stop the drive or clear a fault.This key is always active.Controlled by parameter P037 [Stop Mode].
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 47
Chapter 2 Start Up
LED Status Indicators
LCD Display
LED LED State Description
Program Status Steady Red Indicates parameter value can be changed.Selected digit will flash.
Fault Status Flashing Red Indicates that the drive is faulted.
Speed Status Steady Green Indicates that the digital speed control keys are enabled.
Hand Status Steady Green Indicates that the Run/Start key is enabled.
Auto Status Steady Yellow Indicates that the drive is in Auto mode.
No. Description
1 Parameter Name
2 Run/Stop Status: = Stopped / = Running flashes to indicate that the drive is stopping, but is still decelerating. flashes when DC Injection is commanded.
Direction Indication: The Direction Arrow indicates the commanded direction of rotation. If the Arrow is flashing, the drive has been commanded to change direction, but is still decelerating.Sleep Mode Indication: flashes to indicate that the drive is in sleep mode.
3 Parameter Group and Number: = Basic Display = Basic Program = Terminal Block = Communications = Advanced Program = Aux Relay Card = Advanced Display
4 Fault Indication and Fault Number
5 Fault Name
21
3
45
48 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Start Up Chapter 2
Viewing and Editing Parameters
The last user-selected Basic Display Group parameter is saved when power is removed and is displayed by default when power is reapplied. The following is an example of basic integral keypad and display functions. This example provides basic navigation instructions and illustrates how to program the first Basic Program Group parameter.
Step Key(s) Example Displays
1. When power is applied, the last user-selected Basic Display Group parameter number is displayed with flashing characters. The display then defaults to that parameter’s current value. (Example shows the value of b001 [Output Freq] with the drive stopped.)
2. Press the Up Arrow or Down Arrow to scroll through the Basic Display Group parameters. (Only in Display Groups)
or
3. Press Esc once to display the Basic Display Group parameter number shown on power-up. The parameter number will flash.
4. Press Esc again to enter the group menu. The group menu letter will flash.
5. Press the Up Arrow or Down Arrow to scroll through the group menu (b, P, T, C, A and d).
or
6. Press Enter or Sel to enter a group. The right digit of the last viewed parameter in that group will flash.
or
7. Press the Up Arrow or Down Arrow to scroll through the parameters that are in the group.
or
8. Press Enter or Sel to view the value of a parameter. If you do not want to edit the value, press Esc to return to the parameter number.
or
9. Press Enter or Sel to enter program mode to edit the parameter value. The right digit will flash and the Program LED will illuminate if the parameter can be edited.
or
10.If desired, press Sel to move from digit to digit or bit to bit. The digit or bit that you can change will flash.
11.Press the Up Arrow or Down Arrow to change the parameter value.
or
12.Press Esc to cancel a change. The digit will stop flashing, the previous value is restored and the Program LED will turn off. Or Press Enter to save a change. The digit will stop flashing and the Program LED will turn off.
13.Press Esc to return to the parameter list. Continue to press Esc to back out of the programming menu. If pressing Esc does not change the display, then b001 [Output Freq] is displayed. Press Enter or Sel to enter the last group menu viewed.
The Basic Program Group (page 61) contains the most commonly changed parameters.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 49
Chapter 2 Start Up
Keypad Hand-Off-Auto Functions
Parameter P042 [Auto Mode] defines the operation mode of the control keys on the integral keypad.
Hand-Off-Auto Mode
In HAND mode:• Control keys operate as Hand-Off-Auto. • Start command and speed reference come from the integral keypad
Start/Hand and Digital Speed Increment and Decrement keys. • Auto key switches control from HAND mode to AUTO mode in a
bumpless transfer as long as there is an active Run command.
In AUTO mode:• Auto key LED is illuminated. • Start command is defined by P036 [Start Source]. • Speed Reference command is defined by P038 [Speed Reference]. • Start/Hand key switches control to the integral keypad in a bumpless
transfer and switches the speed reference to the integral keypad. • Stop key stops the drive and the drive switches to HAND mode.
Table 14 - P042 [Auto Mode] = 1 “Hnd-Off-Auto” (Default) T051-T054 [Digital Inx Sel] ≠ 2 “Auto Mode” or 3 “Local”
HAND Mode AUTO Mode
Key LED Key Function LED Key Function
On Starts drive.Runs according to Speed Increment/ Decrement keys.
On Changes to HAND Mode and Starts drive.Runs according to Speed Increment/ Decrement keys.
On Changes speed. Off Not active.Keys are only active if P038 [Speed Source] = 0 “Drive Pot”.
Off Changes to AUTO Mode. On Not active.
N/A Stops drive. N/A Changes to HAND Mode and Stops drive.
IMPORTANT Certain digital input settings can override drive operation. Refer to Start and Speed Reference Control on page 37 for details.
50 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Start Up Chapter 2
Local/Remote Mode
In Local mode:• Start command and speed reference come from the integral keypad
Start/Hand and Digital Speed Increment and Decrement keys.• Auto key stops the drive and the drive switches to Remote mode.
In Remote mode:• Auto key LED is illuminated. • Start command is defined by P036 [Start Source]. • Speed Reference command is defined by P038 [Speed Reference]. • Auto key stops the drive and the drive switches to Local mode.
IMPORTANT If the drive is running and P036 [Start Source] = 3 or 6 (2-Wire Control), the drive will continue to run at reference defined by P038 [Speed Reference] if a valid start command is present
Table 15 - P042 [Auto Mode] = 2 “Local/Remote” T051-T054 [Digital Inx Sel] ≠ 2 “Auto Mode” or 3 “Local”
Local Mode Remote Mode
Key LED Key Function LED Key Function
On Starts drive.Runs according to Speed Increment/ Decrement keys.
Off Not active.Only active if P036 [Start Source] = 0 “Keypad”. Starts drive.
On Changes speed. Off Not active.Keys are only active if P038 [Speed Source] = 0 “Drive Pot”.
Off Stops drive and changes to Remote Mode.
On Stops drive and changes to Local Mode.
N/A Stops drive. N/A Changes to HAND Mode and Stops drive.
IMPORTANT Certain digital input settings can override drive operation. Refer to Start and Speed Reference Control on page 37 for details.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 51
Chapter 2 Start Up
Auto/Manual Mode
In Manual mode:• Start command is defined by P036 [Start Source].• Speed Reference command is defined by the Digital Speed Increment
and Decrement keys.• Auto key toggles frequency control to AUTO in a bumpless transfer.
In AUTO mode:• Auto key LED is illuminated. • Start command is defined by P036 [Start Source]. • Speed Reference command is defined by P038 [Speed Reference]. • Auto key switches frequency control to the integral keypad in a
bumpless transfer.
Table 16 - P042 [Auto Mode] = 2 “Auto/Manual” T051-T054 [Digital Inx Sel] ≠ 2 “Auto Mode” or 3 “Local”
Manual Mode AUTO Mode
Key LED Key Function LED Key Function
Off Not active.Only active if P036 [Start Source] = 0 “Keypad”. Starts drive.Runs according to Speed Increment/ Decrement keys.
Off Not active.Only active if P036 [Start Source] = 0 “Keypad”. Starts drive.
On Changes speed. Off Not active.Keys are only active if P038 [Speed Source] = 0 “Drive Pot”.
Off Changes to AUTO Mode.If running, drive will continue to run at reference defined by P038 [Speed Reference].
On Changes to Manual Mode.If running, drive will continue to run according to Digital Speed Increment and Decrement keys.
N/A Stops drive. N/A Stops drive.
IMPORTANT Certain digital input settings can override drive operation. Refer to Start and Speed Reference Control on page 37 for details.
52 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Start Up Chapter 2
No Function Mode
In No Function mode:• Auto key LED has no function. • Start command is defined by P036 [Start Source]. • Speed Reference command is defined by P038 [Speed Reference].
Table 17 - P042 [Auto Mode] = 0 “No Function” T051-T054 [Digital Inx Sel] ≠ 2 “Auto Mode” or 3 “Local”
Key LED Key Function
Off Not active.Only active if P036 [Start Source] = 0 “Keypad”. Starts drive.
On Not active.Only active if P038 [Speed Reference] = 0 “Drive Pot”. Changes drive speed.
Off Not active.
N/A Stops drive.
IMPORTANT Certain digital input settings can override drive operation. Refer to Start and Speed Reference Control on page 37 for details.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 53
Chapter 2 Start Up
Notes:
54 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3
Programming and Parameters
This chapter provides a complete listing and description of the PowerFlex 400 parameters. Parameters are programmed (viewed/edited) using the integral keypad. As an alternative, programming can also be performed using DriveExecutive™ software or Connected Components WorkBench™ version 1.0 or greater software, a personal computer and a serial converter module. Refer to Appendix B for catalog numbers.
In addition programming can also be performed using design software RS Logix 5000 version 16.0 or greater or Studio 5000 version 21.0 or greater with appropriate communication option kits and accessories listed in Appendix B.
About Parameters To configure a drive to operate in a specific way, drive parameters may have to be set. Three types of parameters exist:
• ENUMENUM parameters allow a selection from 2 or more items. Each item is represented by a number.
• Numeric ParametersThese parameters have a single numerical value (0.1V).
• Bit ParametersBit parameters have four or more individual bits associated with features or conditions. If the bit is 0, the feature is off or the condition is false. If the bit is 1, the feature is on or the condition is true.
For information on... See page
About Parameters 55
Parameter Organization 56
Basic Display Group 58
Basic Program Group 61
Terminal Block Group 66
Communications Group 79
Advanced Program Group 83
Aux Relay Card Group 98
Advanced Display Group 83
Parameter Cross Reference by Name 110
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 55
Chapter 3 Programming and Parameters
Some parameters are marked as follows.
Parameter Organization Refer to page 110 for an alphabetical listing of parameters.
= Stop drive before changing this parameter.
= 32 bit parameter. Parameters marked 32 bit will have two parameter numbers when using RS485 communications and programming software.
32
Basic Display Output Freq b001Commanded Freq b002Output Current b003Output Voltage b004
DC Bus Voltage b005Drive Status b006Fault 1 Code b007Process Display b008
Output Power b010Elapsed MWh b011Elapsed RunTime b012
Torque Current b013Drive Temp b014Elapsed kWh b015
Basic Program Motor NP Volts P031Motor NP Hertz P032Motor OL Current P033Minimum Freq P034
Maximum Freq P035Start Source P036Stop Mode P037
Speed Reference P038Accel Time 1 P039Decel Time 1 P040
Reset To Defalts P041Auto Mode P042Motor OL Ret P043
Terminal Block Digital In1 Sel T051Digital In2 Sel T052Digital In3 Sel T053Digital In4 Sel T054Relay Out1 Sel T055Relay Out1 Level T056Relay 1 On Time T058Relay 1 Off Time T059Relay Out2 Sel T060Relay Out2 Level T061
Relay 2 On Time T063Relay 2 Off Time T064Opto Out Sel T065Opto Out Level T066Opto Out Logic T068Analog In 1 Sel T069Analog In 1 Lo T070Analog In 1 Hi T071Analog In 1 Loss T072Analog In 2 Sel T073
Analog In 2 Lo T074Analog In 2 Hi T075Analog In 2 Loss T076Sleep-Wake Sel T077Sleep Level T078Sleep Time T079Wake Level T080Wake Time T081Analog Out1 Sel T082
Analog Out1 High T083Analog Out1 Setpt T084Analog Out2 Sel T085Analog Out2 High T086Analog Out2 Setpt T087Anlg Loss Delay T088Analog In Filter T089Sleep Sel T090Wake Sel T091
Communication Language C101Comm Format C102Comm Data Rate C103
Comm Node Addr C104Comm Loss Action C105
Comm Loss Time C106Comm Write Mode C107
Start Source 2 C108Speed Ref 2 C109
BasicDisplay Group
BasicProgram Group
TerminalBlock Group
CommunicationsGroup
56 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
Advanced Program Purge Frequency A141Internal Freq A142Preset Freq 0 A143Preset Freq 1 A144Preset Freq 2 A145Preset Freq 3 A146Accel Time 2 A147Decel Time 2 A148S Curve % A149PID Trim Hi A150PID Trim Lo A151PID Ref Sel A152PID Feedback Sel A153PID Prop Gain A154PID Integ Time A155PID Diff Rate A156PID Setpoint A157
PID Deadband A158PID Preload A159Process Factor A160Auto Rstrt Tries A163Auto Rstrt Delay A164Start At PowerUp A165Reverse Disable A166Flying Start En A167PWM Frequency A168PWM Mode A169Boost Select A170Start Boost A171Break Voltage A172Break Frequency A173Maximum Voltage A174Slip Hertz @ FLA A175DC Brake Time A176
DC Brake Level A177DC Brk Time@Strt A178Current Limit 1 A179Current Limit 2 A180Motor OL Select A181Drive OL Mode A182SW Current Trip A183Load Loss Level A184Load Loss Time A185Stall Fault Time A186Bus Reg Mode A187Skip Frequency 1 A188Skip Freq Band 1 A189Skip Frequency 2 A190Skip Freq Band 2 A191Skip Frequency 3 A192Skip Freq Band 3 A193
Compensation A194Reset Meters A195Testpoint Sel A196Fault Clear A197Program Lock A198Motor NP Poles A199Motor NP FLA A200PID Invert Error A201MOP Reset Sel A202Wake Deviation A203ACT1 Input A204ACT2 Input A205ACT1 Minimum A206ACT1 Maximum A207ACT2 Minimum A208ACT2 Maximum A209Wake PID Preload A210
Aux Relay Card Relay Out3 Sel R221Relay Out3 Level R222Relay Out4 Sel R224Relay Out4 Level R225Relay Out5 Sel R227Relay Out5 Level R228Relay Out6 Sel R230
Relay Out6 Level R231Relay Out7 Sel R233Relay Out7 Level R234Relay Out8 Sel R236Relay Out8 Level R237Aux Motor Mode R239Aux Motor Qty R240
Aux 1 Start Freq R241Aux 1 Stop Freq R242Aux 1 Ref Add R243Aux 2 Start Freq R244Aux 2 Stop Freq R245Aux 2 Ref Add R246Aux 3 Start Freq R247
Aux 3 Stop Freq R248Aux 3 Ref Add R249Aux Start Delay R250Aux Stop Delay R251Aux Prog Delay R252Aux AutoSwap Tme R253Aux AutoSwap Lvl R254
Advanced Display Control Source d301Contrl In Status d302Comm Status d303PID Setpnt Displ d304Analog In 1 d305Analog In 2 d306Fault 1 Code d307Fault 2 Code d308Fault 3 Code d309Fault 1 Time-hr d310Fault 1 Time-min d311Fault 2 Time-hr d312Fault 2 Time-min d313
Fault 3 Time-hr d314Fault 3 Time-min d315Elapsed Time-hr d316Elapsed Time-min d317Output Powr Fctr d318Testpoint Data d319Control SW Ver d320Drive Type d321Output Speed d322Output RPM d323Fault Frequency d324Fault Current d325Fault Bus Volts d326
Status @ Fault d327PID Fdbk Display d328DC Bus Ripple V d329Fault 4 Code d330Fault 5 Code d331Fault 6 Code d332Fault 7 Code d333Fault 8 Code d334Fault 9 Code d335Fault 10 Code d336Fault 4 Time-hr d337Fault 4 Time-min d338
Fault 5 Time-hr d339Fault 5 Time-min d340Fault 6 Time-hr d341Fault 6 Time-min d342Fault 7 Time-hr d343Fault 7 Time-min d344Fault 8 Time-hr d345Fault 8 Time-min d346Fault 9 Time-hr d347Fault 9 Time-min d348Fault10 Time-hr d349Fault10 Time-min d350
AdvancedProgram Group
Aux RelayCard Group
AdvancedDisplay Group
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 57
Chapter 3 Programming and Parameters
Basic Display Groupb001 [Output Freq] Related Parameter(s): b002, b008, P034, P035, P038
Output frequency present at T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0.00/P035 [Maximum Freq]
Display: 0.01 Hz
b002 [Commanded Freq] Related Parameter(s): b001, P034, P035, P038, d302
Value of the active frequency command. Displays the commanded frequency even if the drive is not running.
Values Default: Read Only
Min/Max: 0.00/P035 [Maximum Freq]
Display: 0.01 Hz
IMPORTANT The frequency command can come from a number of sources. See Start and Speed Reference Control on page 37 for more information.
b003 [Output Current]
The output current present at T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
b004 [Output Voltage] Related Parameter(s): P031, A170, A174
Output voltage present at terminals T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0/510
Display: 1 VAC
b005 [DC BusVoltage]
Present DC bus voltage level.
Values Default: Read Only
Min/Max: 0/820
Display: 1 VDC
b006 [Drive Status] Related Parameter(s): A166
Present operating condition of the drive.
Values Default: Read Only
Min/Max: 0/1
Display: 1
1 = Condition True, 0 = Condition FalseRunning Bit 1Forward Bit 2Accelerating Bit 3Decelerating Bit 4
58 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
b007 [Fault 1 Code] Related Parameter(s): A186, A197, d307...d315
A code that represents a drive fault. [Fault 1 Code] is the most recent fault. Repetitive faults will only be recorded once.Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
b008 [Process Display] Related Parameter(s): b001, A16032 bit parameter.
Output frequency scaled by A160 [Process Factor]
Values Default: Read Only
Min/Max: 0.00/9999
Display: 0.01 – 1
32
Output Freq
Process Display
Process Factor
x =
b010 [Output Power]
Output power present at T1, T2 & T3 (U, V & W).
Values Default: Read Only
Min/Max: 0.0/999.9 kW
Display: 0.1 kW
b011 [Elapsed MWh] Related Parameter(s): b015, A195
Accumulated output energy of the drive.
Values Default: Read Only
Min/Max: 0/3276.7 MWh
Display: 0.1 MWh
b012 [Elapsed Run Time] Related Parameter(s): A195
Displays the accumulated time that the drive has output power since the last A195 [Reset Meter].Time is displayed in 10 hour increments.
Values Default: Read Only
Min/Max: 0/9999 Hrs
Display: 1 = 10 Hrs
b013 [Torque Current]
Displays the torque portion of the output current.
Values Default: Read Only
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
b014 [Drive Temp]
Present operating temperature of the drive power section.
Values Default: Read Only
Min/Max: 0/120 degC
Display: 1 degC
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 59
Chapter 3 Programming and Parameters
b015 [Elapsed kWh] Related Parameter(s): b011, A195
Accumulated output energy of the drive. This parameter works in conjunction with [Elapsed MWh]. When the maximum value of this parameter is reached, this parameter resets to zero and [Elapsed MWh] is incremented.
Values Default: Read Only
Min/Max: 0.0/100.0 kWh
Display: 0.1 kWh
60 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
Basic Program GroupP031 [Motor NP Volts] Related Parameter(s): b004, A170, A171, A172, A173
Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values Default: Based on Drive Rating
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
P032 [Motor NP Hertz] Related Parameter(s): A170, A171, A172, A173, A181, A182Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values Default: 60 Hz
Min/Max: 15/320 Hz
Display: 1 Hz
P033 [Motor OL Current] Related Parameter(s): P042, T055, T060, T065, A175, A179, A180, A181, A183
Set to the maximum allowable motor current. The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60 seconds.
Values Default: Drive Rated Amps
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
P034 [Minimum Freq] Related Parameter(s): b001, b002, P035, T070, T074, A171, A172, A173, d302
Set to the maximum allowable motor current. The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60 seconds.
Values Default: Drive Rated Amps
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
P035 [Maximum Freq] Related Parameter(s): b001, b002, P034, T071, T075, T082, T083, T085, T086, A171, A172, A173, d302Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values Default: 60.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 61
Chapter 3 Programming and Parameters
P036 [Start Source] Related Parameter(s): P037, P042, A166, d301Stop drive before changing this parameter.
Sets the control scheme used to start the drive when in Auto/Remote mode. Refer to Start and Speed Reference Control on page 37 for details about how other drive settings can override the setting of this parameter.
Options 0 “Keypad” Integral keypad controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Not Used• I/O Terminal 03 = Not Used
1 “3-Wire” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Per P037 [Stop Mode] • I/O Terminal 02 = Start • I/O Terminal 03 = Direction
2 “2-Wire” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = Run REV
3 “2-W Lvl Sens” (Default) I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = Run REVDrive will restart after a “Stop” command when:• Stop is removed and Run FWD is held active
4 “2-W Hi Speed” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = Run REVOutputs are kept in a ready-to-run state. The drive will respond to a “Start” command within 10 ms.
5 “Comm Port” Remote communications controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Not Used• I/O Terminal 03 = Not Used
6 “2-W Lvl/Enbl” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Function Loss: Fault and Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = SW EnableDrive will restart after a “Stop” command when:• Stop is removed and Run FWD is held active
IMPORTANT For all settings except options 3 and 6, the drive must receive a leading edge from the start input for the drive to start after a stop input, loss of power or fault condition.
ATTENTION: Hazard of injury exists due to unintended operation. When P036 [Start Source] is set to option 3 or option 6, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input or a fault clear for the drive to run again. The drive will stop only when the stop command is maintained or the drive is faulted.
ATTENTION: When operating in 2-Wire Level Sense (Run Level), the drive should only be controlled from the Digital Input Terminal Blocks. This should NOT be used with any other DSI or Network device.
IMPORTANT There is greater potential voltage on the output terminals when using this option.
ATTENTION: Hazard of injury exists due to unintended operation. When P036 [Start Source] is set to option 3 or option 6, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input or a fault clear for the drive to run again. The drive will stop only when the stop command is maintained or the drive is faulted.
62 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
P037 [Stop Mode] Related Parameter(s): P036, C105, A176, A177, A178
Active stop mode for all stop sources [e.g. keypad, run forward (I/O Terminal 02), run reverse (I/O Terminal 03), RS485 port] except as noted below.
Hardware Enable CircuitryBy default, I/O Terminal 01 is a coast to stop input. The status of the input is interpreted by drive software. If the application requires the drive to be disabled without software interpretation, a “dedicated” hardware enable configuration can be utilized. This is accomplished by removing the ENBL enable jumper on the control board. See page 29 for details. In this case, the drive will always coast to a stop regardless of the settings of P036 [Start Source] and P037 [Stop Mode].
Options 0 “Ramp, CF”(1) Ramp to Stop. “Stop” command clears active fault.
1 “Coast, CF”(1) (Default) Coast to Stop. “Stop” command clears active fault.
2 “DC Brake, CF”(1) DC Injection Braking Stop. “Stop” command clears active fault.
3 “DCBrkAuto,CF”(1) DC Injection Braking Stop with Auto Shutoff.• Standard DC Injection Braking for value set in A176 [DC Brake Time].
OR• Drive shuts off if the drive detects that the motor is stopped.“Stop” command clears active fault.
4 “Ramp” Ramp to stop.
5 “Coast” Coast to stop.
6 “DC Brake” DC Injection Braking Stop.
7 “DC BrakeAuto” DC Injection Braking Stop with Auto Shutoff.• Standard DC Injection Braking for value set in A176 [DC Brake Time]
OR• Drive shuts off if the drive detects that the motor is stopped.
(1) Stop input also clears active fault.
IMPORTANT I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set for “3-Wire” control. When in three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode].
P038 [Speed Reference] Related Parameter(s): b001, b002, P038, P040, P042, T051...T054, T070, T071, T073, T074, T075, C102, A141, A142, A143...A146, A152, d301
Sets the source of the speed reference to the drive.The drive speed command can be obtained from a number of different sources. The source is normally determined by P038 [Speed Reference]. However, when T051...T054 [Digital Inx Sel] is set to option 1, 2, 3, 4, 5, 8, 14, 15, 16, 17 and the digital input is active, or if A152 [PID Ref Sel] is not set to option 0, the speed reference commanded by P038 [Speed Reference] will be overridden. Refer to the flowchart on page 37 for more information on speed reference control priority.
Options 0 “Drive Keypad” Internal frequency command from the digital speed keys on the integral keypad.
1 “InternalFreq” Internal frequency command from A142 [Internal Freq]. Must be set when using MOP function.
2 “Analog In 1” (Default) External frequency command from an analog source as determined by T069 [Analog In 1 Sel] and DIP Switch AI1 on the control board. Default Dip Switch setting is 10V.
3 “Analog In 2” External frequency command from an analog source as determined by T073 [Analog In 2 Sel] and DIP Switch AI2 on the control board. Default Dip Switch setting is 10V.
4 “Preset Freq” External frequency command as defined by A141...A146 [Preset Freq x] when T051...T054 [Digital Inx Sel] are programmed as “Preset Frequencies” and the digital inputs are active.
5 “Comm Port” External frequency command from the communications port. Refer to Appendix E and Appendix G for details. Parameter C102 [Comm Format] is used to select a communications protocol.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 63
Chapter 3 Programming and Parameters
P039 [Accel Time 1] Related Parameter(s): P038, P040, T051...T054, A141, A143...A146, A147
Sets the rate of acceleration for all speed increases.
Values Default: 20.00 Secs 2.2-110 kW (3.0-150 HP)60.00 Secs 132-250 kW (200-350 HP)
Min/Max: 0.00/600.00 Secs
Display: 0.01 Secs
Maximum FreqAccel Rate
Accel Time=
Speed
0Time
P035 [Maximum Freq]
P039 or A147[Accel Time x]
P040 or A148[Decel Time x]0
Acce
lerat
ion
Deceleration
P040 [Decel Time 1] Related Parameter(s): P038, P039, T051...T054, A141, A143...A146, A148
Sets the rate of deceleration for all speed decreases.
Values Default: 20.00 Secs 2.2-110 kW (3.0-150 HP)60.00 Secs 132-250 kW (200-350 HP)
Min/Max: 0.00/600.00 Secs
Display: 0.01 Secs
Maximum FreqDecel Rate
Decel Time=
Speed
0Time
P035 [Maximum Freq]
P039 or A147[Accel Time x]
P040 or A148[Decel Time x]0
Acce
lerat
ion
Deceleration
P041 [Reset to Defalts] Stop drive before changing this parameter.
Resets all parameter values to factory defaults.
Options 0 “Ready/Idle” (Default)
1 “Factory Rset” • After the reset function is complete, this parameter will set itself back to “0”.• Causes an F48 Params Defaulted fault.
IMPORTANT Drives packaged for fan and pump applications ship with custom default settings that differ from Factory Defaults. Setting this parameter to option 1 will require reprogramming of select parameters. Refer to publication 22C-IN002 for packaged drive default settings.
P042 [Auto Mode] Related Parameter(s): P036, P038Stop drive before changing this parameter.
Determines the operation of the “Auto” key on the integral keypad. Refer to page 50 for details.
Options 0 “No function” LED above “Auto” key is always dark.
1 “Hnd-Off-Auto” (Default) Toggles control start and frequency to and from keypad; starts drive.
2 “Local/Remote” Toggles control start and frequency to and from keypad.
3 “Auto/Manual” Toggles only the frequency control to and from keypad.
64 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
P043 [Motor OL Ret] Related Parameter(s): P033, A181
Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor overload counter is saved at power-down and restored at power-up.
Options 0 “Disabled” (Default)
1 “Enabled”
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 65
Chapter 3 Programming and Parameters
Terminal Block GroupT051 [Digital In1 Sel] (I/O Terminal 05) Related Parameter(s):P036, P038, P039, P040 A141, A142, A143...A146, A147, A148, A166, A177, A180, d301, d302 T052 [Digital In2 Sel] (I/O Terminal 06)T053 [Digital In3 Sel] (I/O Terminal 07)T054 [Digital In4 Sel] (I/O Terminal 08)
Stop drive before changing this parameter.
Selects the function for the digital inputs. Refer to the flowchart on page 37 for more information on speed reference control priority.
Options 0 “Not Used” Terminal has no function but can be read over network communications via d302 [Contrl In Status].
1 “Purge”(1) (T051 Default) Starts the drive at Purge speed regardless of the selected start source. Purge can occur, and is operational, at any time whether the drive is running or stopped. If a valid stop condition is present, other than from the Comm Port or SW Enable input (I/O Terminal 03), the drive will not start on the Purge Input Transition.
2 “Auto Mode” (1) When active, forces drive into “Auto” control mode. Start source determined by P036 [Start Source] and speed reference determined by P038 [Speed Reference].
3 “Local” (1) (T052 Default) When active, sets integral keypad as start source and digital speed keys on the integral keypad as speed source.
4 “Comm Port” (1) (T054 Default) When active, sets communication device as default start/ speed command source.
5 “PID Disable” Disables PID function. Drive uses the next valid non-PID speed reference.
6 “PID Hold” Drive output remains at current value.The integrator for Process PID loop is also clamped at current value.
7 “PID Reset” The integrator for the Process PID loop is reset to zero and drive output is set to Preload value.
8 “Preset Freq” Preset speed inputs that enable the use of preset speeds.
9 “Aux Fault” If input is enable but not active, the drive will immediately fault.
10 “Clear Fault” (T053 Default) Clears an active fault.
11 “RampStop,CF” The drive immediately ramps to stop. Can also be used to clear a fault.
12 “CoastStop,CF” The drive immediately coasts to stop. Can also be used to clear a fault.
13 “DCInjStop,CF” The drive immediately begins a DC Injection stop. Can also be used to clear a fault.
14 “Anlg1 InCtrl” (1) Selects Analog Input 1 control for the frequency reference.
15 “Anlg2 InCtrl” (1) Selects Analog Input 2 control for the frequency reference
16 “MOP Up” Increases the value of A142 [Internal Freq] at the current Accel rate if P038 [Speed Reference] is set to 1 “InternalFreq”. Default for A142 is 60 Hz.
17 “MOP Down” Decreases the value of A142 [Internal Freq] at the current Decel rate if P038 [Speed Reference] is set to 1 “InternalFreq”. Default for A142 is 60 Hz.
18 “Acc & Dec 2” (1) • When active, A147 [Accel Time 2] and A148 [Decel Time 2] are used for all ramp rates.• Can only be tied to one input.Refer to the flowchart on page 38 for more information on Accel/Decel selection.
19 “Current Lmt2” When active, A180 [Current Limit 2] determines the drive current limit level.
20 “Force DC” If the drive is not running, applying this input causes the drive to apply a DC Holding current (use A177 [DC Brake Level], ignoring A176 [DC Brake Time] while the input is applied.
21 “Mtr I-Lock 1” Can be used as a protective motor interlock in Auxiliary Motor Control mode. When programmed but not active, input will prevent corresponding motor from operating. Refer to Appendix C for details.22 “Mtr I-Lock 2”
23 “Mtr I-Lock 3”
24 “Mtr I-Lock 4”
25 “Cmd Reverse” When programmed and active the drive will run in the reverse direction when started from the integral keypad.
31 “Logic In 1” Input 1 used by digital output settings.
32 “Logic In 2” Input 2 used by digital output settings.
36 “Damper Input” • When active, drive is allowed to run normally.• When inactive, drive is forced into sleep mode and is prevented from accelerating to commanded speed.
(1) This function may be tied to one input only.
ATTENTION: A Purge command will take precedence over a stop command from the Comm Port/Network and over a SW Enable command from the terminal block. Insure that another stop method is available, such as I/O Terminal 01 of the control terminal block, if stopping is necessary during a purge.
66 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
T055 [Relay Out1 Sel] Related Parameter(s): P033, T056, T058, T059, T069, T072, T073, T076, A163, d318
Sets the condition that changes the state of the output relay contacts.
Options 0 “Ready/Fault” (Default) Relay changes state when power is applied. This indicates that the drive is ready for operation. Relay returns drive to shelf state when power is removed or a fault occurs.
1 “At Frequency” Drive reaches commanded frequency
2 “MotorRunning” Motor is receiving power from the drive.
3 “Hand Active” Active when drive is in local control.
4 “Motor Overld” Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq” • Drive exceeds the frequency (Hz) value set in T056 [Relay Out1 Level].• Use T056 to set threshold.
7 “Above Cur” • Drive exceeds the current (% Amps) value set in T056 [Relay Out1 Level].• Use T056 to set threshold.
8 “Above DCVolt” • Drive exceeds the DC bus voltage value set in T056 [Relay Out1 Level].• • Use T056 to set threshold.
9 “Above Anlg 2” • Analog input voltage (I/O Terminal 17) exceeds the value set in T056 [Relay Out1 Level].• Do not use if T073 [Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.• Use T056 to set threshold.
10 “Above PF Ang” • Power Factor angle has exceeded the value set in T056 [Relay Out1 Level].• Use T056 to set threshold.
11 “Anlg In Loss” Analog input loss has occurred. Program T072 [Analog In 1 Loss] and/or T076 [Analog In 2 Loss] for desired action when input loss occurs.
12 “ParamControl” Enables the output to be controlled over network communications by writing to T056 [Relay Out1 Level]. (0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163 [Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” • Number of retries for A163 [Auto Rstrt Tries] is exceeded, or• Non-resettable fault occurs, or• A163 [Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
23 “Aux Motor” Auxiliary Motor is commanded to run. Refer to Appendix C for details.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option 0, “Ready/Fault”.
IMPORTANT Value for T056 [Relay Out1 Level] must be entered in percent of drive rated output current.
T056 [Relay Out1 Level] Related Parameter(s): T055, T058, T059, d31832 bit parameter.
Sets the trip point for the digital output relay if the value of T055 [Relay Out1 Sel] is 6, 7, 8, 9, 10 or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T055 Setting T056 Min/Max6 0/320 Hz7 0/180%8 0/815 Volts9 0/100%10 1/180 degs12 0/1
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 67
Chapter 3 Programming and Parameters
T058 [Relay 1 On Time] Related Parameter(s): T055, T056, T059
Sets delay time before Relay energizes after required condition testing.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
T059 [Relay 1 Off Time] Related Parameter(s): T055, T058, T058
Sets delay time before Relay de-energizes after required condition testing ceases.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
IMPORTANT Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.
T060 [Relay Out2 Sel] Related Parameter(s): P033, T061, T063, T064, T076, A163, d318
Sets the condition that changes the state of the output relay contacts.
Options 0 “Ready/Fault” (Default) Relay changes state when power is applied. This indicates that the drive is ready for operation. Relay returns drive to shelf state when power is removed or a fault occurs.
1 “At Frequency” Drive reaches commanded frequency.
2 “MotorRunning” (Default) Motor is receiving power from the drive.
3 “Hand Active” Active when drive is in local control.
4 “Motor Overld” Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq” • Drive exceeds the frequency (Hz) value set in T061 [Relay Out2 Level].• Use T061 to set threshold.
7 “Above Cur” • Drive exceeds the current (% Amps) value set in T061 [Relay Out2 Level].• Use T061 to set threshold.
8 “Above DCVolt” • Drive exceeds the DC bus voltage value set in T061 [Relay Out2 Level].• Use T061 to set threshold.
9 “Above Anlg 2” • Analog input voltage (I/O Terminal 17) exceeds the value set in T061 [Relay Out2 Level].• Do not use if T073 [Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.• Use T061 to set threshold.
10 “Above PF Ang” • Power Factor angle has exceeded the value set in T061 [Relay Out2 Level].• Use T061 to set threshold.
11 “Anlg In Loss” Analog input loss has occurred. Program T072 [Analog In 1 Loss] and/or T076 [Analog In 2 Loss] for desired action when input loss occurs.
12 “ParamControl” Enables the output to be controlled over network communications by writing to T061 [Relay Out2 Level]. (0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163 [Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” • Number of retries for A163 [Auto Rstrt Tries] is exceeded OR• Non-resettable fault occurs OR• A163 [Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
23 “Aux Motor” Auxiliary Motor is commanded to run. Refer to Appendix C for details.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option 0, “Ready/Fault”.
IMPORTANT Value for T061 [Relay Out2 Level] must be entered in percent of drive rated output current.
68 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
T061 [Relay Out2 Level] Related Parameter(s): T060, T063, T064, d31832 bit parameter.
Sets the trip point for the digital output relay if the value of T060 [Relay Out2 Sel] is 6, 7, 8, 9, 10 or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T060 Setting T061 Min/Max6 0/320 Hz7 0/180%8 0/815 Volts9 0/100%10 1/180 degs12 0/1
T063 [Relay 2 On Time] Related Parameter(s): T060, T061, T064
Sets delay time before Relay energizes after required condition testing.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
T064 [Relay 2 Off Time] Related Parameter(s): T060, T061, T063
Sets delay time before Relay de-energizes after required condition testing ceases.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
IMPORTANT Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 69
Chapter 3 Programming and Parameters
T065 [Opto Out Sel] Related Parameter(s): P033, T066, T068, T072, T076, A163, d318
Determines the operation of the programmable opto output.
Options 0 “Ready/Fault” Opto output is active when power is applied. This indicates that the drive is ready for operation. Opto output is inactive when power is removed or a fault occurs.
1 “At Frequency” (Default) Drive reaches commanded frequency
2 “MotorRunning” Motor is receiving power from the drive.
3 “Hand Active” Active when drive is in local control.
4 “Motor Overld” Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq” • Drive exceeds the frequency (Hz) value set in T066 [Opto Out Level].• Use T066 to set threshold.
7 “Above Cur” • Drive exceeds the current (% Amps) value set in T066 [Opto Out Level].• Use T066 to set threshold.
8 “Above DCVolt” • Drive exceeds the DC bus voltage value set in T066 [Opto Out Level].• • Use T066 to set threshold.
9 “Above Anlg 2” • Analog input voltage (I/O Terminal 17) exceeds the value set in T066 [Opto Out Level].• Do not use if T073 [Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.• Use T066 to set threshold.
10 “Above PF Ang” • Power Factor angle has exceeded the value set in T066 [Opto Out Level].• Use T066 to set threshold.
11 “Anlg In Loss” Analog input loss has occurred. Program T072 [Analog In 1 Loss] and/or T076 [Analog In 2 Loss] for desired action when input loss occurs.
12 “ParamControl” Enables the output to be controlled over network communications by writing to T066 [Opto Out Level]. (0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163 [Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” • Number of retries for A163 [Auto Rstrt Tries] is exceeded, or• Non-resettable fault occurs, or• A163 [Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option 0, “Ready/Fault”.
IMPORTANT Value for T066 [Opto Out Level] must be entered in percent of drive rated output current.
T066 [Opto Out Level] Related Parameter(s): T065, T068, A163, d31832 bit parameter.
Determines the on/off point for the opto output when T065 [Opto Out Sel] is set to option 6, 7, 8, 9, 10,or 12..
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T065 Setting T066 Min/Max6 0/320 Hz7 0/180%8 0/815 Volts9 0/100%10 1/180 degs12 0/1
70 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
T068 [Opto Out Logic] Related Parameter(s): T065, T066
Determines the logic (Normally Open/NO or Normally Closed/NC) of the opto output..
Note: Setting output to NC may cause output to “glitch” on power-up. The off/reset state of all outputs is open.
Values Default: 0
Min/Max: 0/1
Display: 1
T058 Option Opto Out Logic0 NO (Normally Open)1 NC (Normally Closed)
T069 [Analog In 1 Sel] Related Parameter(s): T055, T070, T071, T072
Sets the analog input signal mode (0-20mA, 4-20mA, or 0-10V). This parameter must match DIP Switch AI1 setting on the control board..
Values Default: 2
Min/Max: 0/6
Display: 1
T069 Option Setting Input Range DIP Switch AI1 Setting0 Current Mode 0-20 mA 20 mA1 Current Mode 4-20 mA 20 mA2 Voltage Mode - Unipolar 0-10V 10V4 Current Mode (Square Root) 0-20 mA 20 mA5 Current Mode (Square Root) 4-20 mA 20 mA6 Voltage Mode - Unipolar (Square Root) 0-10V 10V
T070 [Analog In 1 Lo] Related Parameter(s): P034, P038, T069, T071, T072, A152, A153Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034 [Minimum Freq].Analog inversion can be accomplished by setting this value larger than T071 [Analog In 1 Hi].
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
IMPORTANT If analog inversion is implemented the drive will go to maximum frequency in the event the analog input is lost. It is strongly recommended to activate T072 [Analog In 1 Loss] to protect from this potential occurrence.
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]0
Speed
Referen
ce
T071 [Analog In 1 Hi] Related Parameter(s): P035, P038, T069, T070, T072, A152, A153Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].Analog inversion can be accomplished by setting this value smaller than T070 [Analog In 1 Lo].
Values Default: 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 71
Chapter 3 Programming and Parameters
T072 [Analog In 1 Loss] Related Parameter(s): T055, T060, T065, T069, T070, T071, A152Stop drive before changing this parameter.
Selects drive action when an input signal loss is detected. Signal loss is defined as an analog signal less than 1V or 2mA. The signal loss event ends and normal operation resumes when the input signal level is greater than or equal to 1.5V or 3mA. If using a 0-10V analog input, set T070 [Analog In 1 Lo] to a minimum of 20% (i.e. 2 volts).The drive will fault on an F29 Analog Input Loss when the analog signal is lost if this parameter is used for the PID feedback, and this parameter and A152 [PID Ref Sel] are both set to an option other than 0 “Disabled”.
Options 0 “Disabled” (Default)
1 “Fault (F29)” F29 Analog Input Loss
2 “Stop” Uses P037 [Stop Mode]
3 “Zero Ref” Drive runs at zero speed reference.
4 “Min Freq Ref” Drive runs at minimum frequency.
5 “Max Freq Ref” Drive runs at maximum frequency.
6 “Preset Freq0” Drive runs at A143 [Preset Freq 0].
7 “Hold Last” (with FRN 6.xx and later)
Drive uses last frequency command from analog input prior to signal loss, or last PID reference prior to signal loss when used as a PID reference.
T073 [Analog In 2 Sel] Related Parameter(s): P038, T055, T065, T074, T075, T076, A152
Sets the analog input signal mode (0-20mA, 4-20mA, 0-10V, -10 to +10V). This parameter must match DIP Switch AI2 setting on the control board..
Values Default: 2
Min/Max: 0/7
Display: 1
T073 Option Setting Input Range DIP Switch AI1 Setting0 Current Mode 0-20 mA 20 mA1 Current Mode 4-20 mA 20 mA2 Voltage Mode - Unipolar 0-10V 10V3(1)
(1) Setting 3 is only available on [Analog In 2 Sel]. Input 2 is isolated and supports a bi-polar input, so that setting 3 determines if the voltage input is enabled for bipolar control. If bipolar is selected, P034 [Minimum Freq] and T074 [Analog In 2 Lo] are ignored. If input 2 is set up for current control, Bipolar mode is not possible. If the analog input is inverted ([Analog In 2 Lo] > [Analog In 2 Hi]), Bipolar mode is disabled and this input uses unipolar control only (negative values are treated like zero).
Voltage Mode - Bipolar -10 to +10V 10V4 Current Mode (Square Root) 0-20 mA 20 mA5 Current Mode (Square Root) 4-20 mA 20 mA6 Voltage Mode - Unipolar (Square Root) 0-10V 10V7 Voltage Mode - Bipolar (Square Root) -10 to +10V 10V
T074 [Analog In 2 Lo] Related Parameter(s): P034, P038, T072, T073, T075, T076, A152, A153Stop drive before changing this parameter.
Sets the analog input level that corresponds to P034 [Minimum Freq].Analog inversion can be accomplished by setting this value larger than T075 [Analog In 2 Hi].
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
IMPORTANT If analog inversion is implemented the drive will go to maximum frequency in the event the analog input is lost. It is strongly recommended to activate T072 [Analog In 1 Loss] to protect from this potential occurrence.
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T074 [Analog In 2 Lo] T075 [Analog In 2 Hi]0
Speed
Referen
ce
72 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
T075 [Analog In 2 Hi] Related Parameter(s): P035, P038, T073, T074, T076, A152, A153Stop drive before changing this parameter.
Sets the analog input level that corresponds to P035 [Maximum Freq].Analog inversion can be accomplished by setting this value smaller than T074 [Analog In 2 Lo].
Values Default: 100.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T076 [Analog In 2 Loss] Related Parameter(s): T055, T060, T065, T073, T074, T075Stop drive before changing this parameter.
Selects drive action when an input signal loss is detected. Signal loss is defined as an analog signal less than 1V or 2mA. The signal loss event ends and normal operation resumes when the input signal level is greater than or equal to 1.5V or 3mA. If using a 0-10V analog input, set T074 [Analog In 2 Lo] to a minimum of 20% (i.e. 2 volts).The drive will fault on an F29 Analog Input Loss when the analog signal is lost if this parameter is used for the PID feedback, and this parameter and A152 [PID Ref Sel] are both set to an option other than 0 “Disabled”
Options 0 “Disabled” (Default)
1 “Fault (F29)” F29 Analog Input Loss
2 “Stop” Uses P037 [Stop Mode]
3 “Zero Ref” Drive runs at zero speed reference.
4 “Min Freq Ref” Drive runs at minimum frequency.
5 “Max Freq Ref” Drive runs at maximum frequency.
6 “Preset Freq0” Drive runs at A143 [Preset Freq 0].
7 “Hold Last” (with FRN 6.xx and later)
Drive uses last frequency command from analog input prior to signal loss, or last PID reference prior to signal loss when used as a PID reference.
T077 [Sleep-Wake Sel] Related Parameter(s): T078, T079, T080, T081, T090, T091
The drive “sleeps” if the appropriate analog input drops below the set [Sleep Level] for the time set in [Sleep Time] and the drive is running. When entering sleep mode the drive will ramp to zero and the run indicator ( ) on the keypad display will flash indicating the drive is in “sleep” mode. When the appropriate analog input rises above the set [Wake Level] the drive will “wake” and ramp to the commanded frequency.Inversion can be accomplished by setting T078 [Sleep Level] to a higher setting than T080 [Wake Level].
Options 0 “Disabled” (Default)
1 “Analog In 1” Sleep and Wake enabled from Analog Input 1.
2 “Analog In 2” Sleep and Wake enabled from Analog Input 2.
3 “Command Freq” Sleep and Wake enabled based on drive commanded frequency.
4 “Ind Slp Wake” (with FRN 7.xx and later)
Sleep and Wake enabled independently using parameters T090 [Sleep Sel] and T091 [Wake Sel].
ATTENTION: Enabling the Sleep-Wake function can cause unexpected machine operation during the Wake mode. Equipment damage and/or personal injury can result if this parameter is used in an inappropriate application. In addition, all applicable local, national & international codes, standards, regulations or industry guidelines must be considered.
T078 [Sleep Level] Related Parameter(s): T077, T079, T080, T081
Sets the analog input level the drive must reach to enter sleep mode.
Values Default: 10.0%
Min/Max: 0.0/100.0%
Display: 0.1%
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 73
Chapter 3 Programming and Parameters
T079 [Sleep Time] Related Parameter(s): T077, T078, T080, T081
Sets the analog input time the drive must stay below to enter sleep mode.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
T080 [Wake Level] Related Parameter(s): T077, T078, T079, T081
Sets the analog input level the drive must reach to wake from sleep mode.
Values Default: 15.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T081 [Wake Time] Related Parameter(s): T077, T078, T079, T080
Sets the analog input time the drive must stay above to wake from sleep mode.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
74 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
T082 [Analog Out1 Sel] Related Parameter(s): P035, T083, T084
Sets the analog output signal mode (0-20 mA, 4-20 mA, or 0-10V). The output is used to provide a signal that is proportional to several drive conditions. This parameter must match DIP Switch AO1 setting.
Values Default: 0
Min/Max: 0/29
Display: 1
Setting Output Range Minimum Output Value Maximum Output Value =[Analog Output High]
Filter(1)
(1) For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in 500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.
DIP Switch AO1 Setting
RelatedParameter
0 OutFreq 0-10 0-10V 0V = 0 Hz [Maximum Freq] None 10V b0011 OutCurr 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b0032 OutTorq 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b0133 OutVolt 0-10 0-10V 0V = 0 Volts 120% Drive Rated Output V None 10V b0044 OutPowr 0-10 0-10V 0V = 0 kW 200% Drive Rated Power Filter A 10V b0105 Setpnt 0-10 0-10V 0V = 0.0% 100.0% Setting None 10V T0846 TstData 0-10 0-10V 0V = 0000 65535 (Hex FFFF) None 10V A1967 OutFreq 0-20 0-20 mA 0 mA = 0 Hz [Maximum Freq] None 20 mA b0018 OutCurr 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b0039 OutTorq 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b01310 OutVolt 0-20 0-20 mA 0 mA = 0 Volts 120% Drive Rated Output V None 20 mA b00411 OutPowr 0-20 0-20 mA 0 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b01012 Setpnt 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting None 20 mA T08413 TstData 0-20 0-20 mA 0 mA = 0000 65535 (Hex FFFF) None 20 mA A19614 OutFreq 4-20 4-20 mA 4 mA = 0 Hz [Maximum Freq] None 20 mA b00115 OutCurr 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b00316 OutTorq 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b01317 OutVolt 4-20 4-20 mA 4 mA = 0 Volts 120% Drive Rated Output V None 20 mA b00418 OutPowr 4-20 4-20 mA 4 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b01019 Setpnt 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting None 20 mA T08420 TstData 4-20 4-20 mA 4 mA = 0000 65535 (Hex FFFF) None 20 mA A19621 MinFreq 0-10 0-10V 0V = Min. Freq [Maximum Freq] None 10V b00122 MinFreq 0-20 0-20 mA 0 mA = Min. Freq [Maximum Freq] None 20 mA b00123 MinFreq 4-20 4-20 mA 4 mA = Min. Freq [Maximum Freq] None 20 mA b00124 AnlgIn1 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d30525 AnlgIn1 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d30526 AnlgIn1 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d30527 AnlgIn2 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d30628 AnlgIn2 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d30629 AnlgIn2 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d306
T083 [Analog Out1 High] Related Parameter(s): P035, T082, T084
Scales the Maximum Output Value for the T082 [Analog Out1 Sel] source setting.Examples:.
Values Default: 100%
Min/Max: 0/800%
Display: 1%
T083 Setting T082 Setting T082 Max. Output Value50% 1 “OutCurr 0-10” 5V for 200% Drive Rated Output Current90% 11 “OutPowr 0-20” 18mA for 200% Drive Rated Power
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 75
Chapter 3 Programming and Parameters
T084 [Anlg Out1 Setpt] Related Parameter(s): T082, T083
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog output.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T085 [Analog Out2 Sel] Related Parameter(s): P035, T086, T087
Sets the analog output signal mode (0-20 mA, 4-20 mA, or 0-10V). The output is used to provide a signal that is proportional to several drive conditions. This parameter must match DIP Switch AO2 setting.
Values Default: 1
Min/Max: 0/29
Display: 1
Setting Output Range Minimum Output Value Maximum Output Value =[Analog Output High]
Filter(1)
(1) For settings with the filter enabled, if a 0-100% step change occurs, the output will reach 95% in 500 milliseconds, 99% in 810 milliseconds and 100% in 910 milliseconds.
DIP Switch AO2 Setting
RelatedParameter
0 OutFreq 0-10 0-10V 0V = 0 Hz [Maximum Freq] None 10V b0011 OutCurr 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b0032 OutTorq 0-10 0-10V 0V = 0 Amps 200% Drive Rated FLA Filter A 10V b0133 OutVolt 0-10 0-10V 0V = 0 Volts 120% Drive Rated Output V None 10V b0044 OutPowr 0-10 0-10V 0V = 0 kW 200% Drive Rated Power Filter A 10V b0105 Setpnt 0-10 0-10V 0V = 0.0% 100.0% Setting None 10V T0846 TstData 0-10 0-10V 0V = 0000 65535 (Hex FFFF) None 10V A1967 OutFreq 0-20 0-20 mA 0 mA = 0 Hz [Maximum Freq] None 20 mA b0018 OutCurr 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b0039 OutTorq 0-20 0-20 mA 0 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b01310 OutVolt 0-20 0-20 mA 0 mA = 0 Volts 120% Drive Rated Output V None 20 mA b00411 OutPowr 0-20 0-20 mA 0 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b01012 Setpnt 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting None 20 mA T08413 TstData 0-20 0-20 mA 0 mA = 0000 65535 (Hex FFFF) None 20 mA A19614 OutFreq 4-20 4-20 mA 4 mA = 0 Hz [Maximum Freq] None 20 mA b00115 OutCurr 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b00316 OutTorq 4-20 4-20 mA 4 mA = 0 Amps 200% Drive Rated FLA Filter A 20 mA b01317 OutVolt 4-20 4-20 mA 4 mA = 0 Volts 120% Drive Rated Output V None 20 mA b00418 OutPowr 4-20 4-20 mA 4 mA = 0 kW 200% Drive Rated Power Filter A 20 mA b01019 Setpnt 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting None 20 mA T08420 TstData 4-20 4-20 mA 4 mA = 0000 65535 (Hex FFFF) None 20 mA A19621 MinFreq 0-10 0-10V 0V = Min. Freq [Maximum Freq] None 10V b00122 MinFreq 0-20 0-20 mA 0 mA = Min. Freq [Maximum Freq] None 20 mA b00123 MinFreq 4-20 4-20 mA 4 mA = Min. Freq [Maximum Freq] None 20 mA b00124 AnlgIn1 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d30525 AnlgIn1 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d30526 AnlgIn1 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d30527 AnlgIn2 0-10 0-10V 0V = 0.0% 100.0% Setting Filter A 10V d30628 AnlgIn2 0-20 0-20 mA 0 mA = 0.0% 100.0% Setting Filter A 20 mA d30629 AnlgIn2 4-20 4-20 mA 4 mA = 0.0% 100.0% Setting Filter A 20 mA d306
76 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
T086 [Analog Out2 High] Related Parameter(s): P035, T085, T087
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.Examples:.
Values Default: 100%
Min/Max: 0/800%
Display: 1%
T086 Setting T085 Setting T085 Max. Output Value50% 1 “OutCurr 0-10” 5V for 200% Drive Rated Output Current90% 11 “OutPowr 0-20” 18mA for 200% Drive Rated Power
T087 [Anlg Out2 Setpt] Related Parameter(s): T085, T086
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog output.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
T088 [Anlg Loss Delay] Related Parameter(s): T069, T070...T076
Sets the length of time after power-up during which the drive will not detect an analog signal loss. The drive response to an analog signal loss is set in T072 or T076 [Analog In x Loss].
Values Default: 0.0 Secs
Min/Max: 0.0/20.0 Secs
Display: 0.1 Secs
T089 [Analog In Filter]
Sets level of additional filtering of the analog input signals. A higher number increases filtering and decreases bandwidth. Each setting doubles the applied filtering (1 = 2x filter, 2 = 4x filter, etc.). No additional filtering is applied when set to “0”.
Values Default: 0
Min/Max: 0/14
Display: 1
T090 [Sleep Sel] Related Parameter(s): b001, b002, T077, T078, d305, d306
(with FRN 7.xx and later.)Selects the operation of the sleep function.
Options 0 “AI1 > SlpLvl” (Default) Sleep enabled from Analog Input 1 (d305 [Analog In 1]) above sleep level.
1 “AI1 < SlpLvl” Sleep enabled from Analog Input 1 (d305 [Analog In 1]) below sleep level.
2 “AI2 > SlpLvl” Sleep enabled from Analog Input 2 (d306 [Analog In 2]) above sleep level.
3 “AI2 < SlpLvl” Sleep enabled from Analog Input 2 (d306 [Analog In 2]) below sleep level.
4 “OFrq>SlpLvl” Sleep enabled based on drive output frequency (b001 [Output Freq]) above sleep level.
5 “OFrq>SlpLvl” Sleep enabled based on drive output frequency (b001 [Output Freq]) below sleep level.
6 “CFrq>SlpLvl” Sleep enabled based on drive command frequency (b002 [Commanded Freq]) above sleep level.
7 “CFrq>SlpLvl” Sleep enabled based on drive command frequency (b002 [Commanded Freq]) below sleep level.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 77
Chapter 3 Programming and Parameters
T091 [Wake Sel] Related Parameter(s): T077, T080, A203, d304, d305, d306, d328
(with FRN 7.xx and later.)Selects the operation of the wake function.
Options 0 “AI1 > WakLvl” (Default) Wake enabled from Analog Input 1 (d305 [Analog In 1]) above wake-up level.
1 “AI1 < WakLvl” Wake enabled from Analog Input 1 (d305 [Analog In 1]) below wake-up level.
2 “AI2 > WakLvl” Wake enabled from Analog Input 2 (d306 [Analog In 2]) above wake-up level.
3 “AI2 > WakLvl” Wake enabled from Analog Input 2 (d306 [Analog In 2]) below wake-up level.
4 “CFrq>WakLvl” Wake enabled based on drive command frequency (b002 [Commanded Freq]) above wake-up level.
5 “CFrq>WakLvl” Wake enabled based on drive command frequency (b002 [Commanded Freq]) below wake-up level.
6 “FB-SP>WakLvl” PID Feedback Display minus PID Setpoint Display above wake-up level. If (d328 [PID Fdbk Display] - d304 [PID Setpnt Displ]) > T080 [Wake Level], then wake is enabled.
7 “SP-FB>WakLvl” PID Setpoint Display minus PID Feedback Display above wake-up level. If (d304 [PID Setpnt Displ] - d328 [PID Fdbk Display]) > T080 [Wake Level], then wake is enabled.
8 “AI1 > WakDev” Wake enabled from Analog Input 1 above PID Setpoint Display plus wake deviation.If d305 [Analog In 1] > (d304 [PID Setpnt Displ] + A203 [Wake Deviation]), then wake is enabled.
9 “AI1 < WakDev” Wake enabled from Analog Input 1 below PID Setpoint Display minus wake deviation.If d305 [Analog In 1] < (d304 [PID Setpnt Displ] - A203 [Wake Deviation]), then wake is enabled.
10 “AI2 > WakDev” Wake enabled from Analog Input 2 above PID Setpoint Display plus wake deviation.If d306 [Analog In 2] > (d304 [PID Setpnt Displ] + A203 [Wake Deviation]), then wake is enabled.
11 “AI2 < WakDev” Wake enabled from Analog Input 2 below PID Setpoint Display minus wake deviation.If d306 [Analog In 2] < (d304 [PID Setpnt Displ] - A203 [Wake Deviation]), then wake is enabled.
12 “CFrq>WakDev” Wake enabled based on drive command frequency above PID Setpoint Display plus wake deviation.If b002 [Commanded Freq] > (d304 [PID Setpnt Displ] - A203 [Wake Deviation]), then wake is enabled.
13 “CFrq<WakDev” Wake enabled based on drive command frequency below PID Setpoint Display minus wake deviation.If b002 [Commanded Freq] < (d304 [PID Setpnt Displ] - A203 [Wake Deviation]), then wake is enabled.
T080 [Wake Level]
T080 [Wake Level]
T091 [Wake Sel] = 6 “FB-SP>WakLvl”
PID Feedback
PID Setpoint
T091 [Wake Sel] = 7 “SP-FB>WakLvl”
78 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
Communications GroupC101 [Language]
Selects the language displayed by the integral LCD display and remote communications option.
Options 1 “English” (Default)
2 “Français”
3 “Español”
4 “Italiano”
5 “Deutsch”
6 “Reserved”
7 “Português”
8 “Reserved”
9 “Reserved”
10 “Nederlands”
C102 [Comm Format] Related Parameter(s): d303...d306
Selects the protocol data bits (8 data bits only), parity (None, Even, Odd), and stop bits (1 or 2) used by the RS485 port on the drive.Refer to Appendix D and Appendix E for details on using the drive communication features.
Options 0 “RTU 8-N-1” (Default)
1 “RTU 8-E-1”
2 “RTU 8-O-1”
3 “RTU 8-N-2”
4 “RTU 8-E-2”
5 “RTU 8-O-2”
6 “MetaSys N2”
7 “P1 8-N-1” Floor Level Network (FLN)
8 “P1 8-E-1” Floor Level Network (FLN)
9 “P1 8-O-1” Floor Level Network (FLN)
IMPORTANT Power to drive must be cycled before any changes will affect drive operation.
C103 [Comm Data Rate] Related Parameter(s): d303
Sets the serial port rate for the RS485 (DSI) port.
Options 0 “1200”
1 “2400”
2 “4800”
3 “9600” (Default)
4 “19.2K”
5 “38.4K”
IMPORTANT Power to drive must be cycled before any changes will affect drive operation.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 79
Chapter 3 Programming and Parameters
C104 [Comm Node Addr] Related Parameter(s): d303
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Values Default: 100
Min/Max: 1/247
Display: 1
IMPORTANT Power to drive must be cycled before any changes will affect drive operation.
C105 [Comm Loss Action] Related Parameter(s): d303, P037, C106
Selects the drive’s response to a loss of the communication connection or excessive communication errors.
Options 0 “Fault” (Default) Drive will fault on an F81 Comm Loss and coast to stop.
1 “Coast Stop” Stops drive via coast to stop.
2 “Stop” Stops drive via P037 [Stop Mode] setting.
3 “Continu Last” Drive continues operating at communication commanded speed saved in RAM.
4 “Run Preset 0” Drive will run at preset speed.
5 “Kypd Inc/Dec” Drive will run at keypad (digital pot) speed.
C106 [Comm Loss Time] Related Parameter(s): d303, C105
Sets the time that the drive will remain in communication loss before implementing the option selected in C105 [Comm Loss Action].
Values Default: 5.0 Secs
Min/Max: 0.1/60.0 Secs
Display: 0.1 Secs
C107 [Comm Write Mode]
Determines whether parameter changes made over communication port are saved and stored in Non-Volatile Storage (NVS) or RAM only. If they are stored in RAM, the values will be lost at power-down.
Options 0 “Save” (Default)
1 “RAM Only”
ATTENTION: Risk of equipment damage exists. If a controller is programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS unless C107 [Comm Write Mode] is set to option 1.
80 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
C108 [Start Source 2] Related Parameter(s): P037, P042, A166, d301Stop drive before changing this parameter.
Sets the control scheme used to start the drive when in Comm Control and the communication network commands the drive to run from Local Control. This function is normally used by Point 79 of a P1-FLN. Refer to Start and Speed Reference Control on page 37 for details about how other drive settings can override the setting of this parameter.
Options 0 “Keypad” Integral keypad controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Not Used• I/O Terminal 03 = Not Used
1 “3-Wire” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Per P037 [Stop Mode] • I/O Terminal 02 = Start • I/O Terminal 03 = Direction
2 “2-Wire” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = Run REV
3 “2-W Lvl Sens” (Default) I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = Run REVDrive will restart after a “Stop” command when:• Stop is removed and Run FWD is held active
4 “2-W Hi Speed” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = Run REVOutputs are kept in a ready-to-run state. The drive will respond to a “Start” command within 10 ms.
5 “Comm Port” Remote communications controls drive operation.• I/O Terminal 01 = Stop: Coast to Stop• I/O Terminal 02 = Not Used• I/O Terminal 03 = Not Used
6 “2-W Lvl/Enbl” I/O Terminal Block controls drive operation.• I/O Terminal 01 = Function Loss: Fault and Coast to Stop• I/O Terminal 02 = Run FWD• I/O Terminal 03 = SW EnableDrive will restart after a “Stop” command when:• Stop is removed and Run FWD is held active
IMPORTANT For all settings except options 3 and 6, the drive must receive a leading edge from the start input for the drive to start after a stop input, loss of power or fault condition.
ATTENTION: Hazard of injury exists due to unintended operation. When P036 [Start Source] is set to option 3 or option 6, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input or a fault clear for the drive to run again. The drive will stop only when the stop command is maintained or the drive is faulted.
IMPORTANT There is greater potential voltage on the output terminals when using this option.
ATTENTION: Hazard of injury exists due to unintended operation. When P036 [Start Source] is set to option 3 or option 6, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input or a fault clear for the drive to run again. The drive will stop only when the stop command is maintained or the drive is faulted.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 81
Chapter 3 Programming and Parameters
C109 [Speed Ref 2] Related Parameter(s): b001, b002, P038, P040, P042, T051...T054, T070, T071, T073, T074, T075, C102, A141, A142, A143...A146, A152, d301
Sets the source of the speed reference to the drive when in Comm Control and the communication network commands the drive to run from Local Control.Refer to the flowchart on page 37 for more information on speed reference control priority.
Options 0 “Drive Keypad” Internal frequency command from the digital speed keys on the integral keypad.
1 “InternalFreq” Internal frequency command from A142 [Internal Freq]. Must be set when using MOP function.
2 “Analog In 1” (Default) External frequency command from an analog source as determined by T069 [Analog In 1 Sel] and DIP Switch AI1 on the control board. Default Dip Switch setting is 10V.
3 “Analog In 2” External frequency command from an analog source as determined by T073 [Analog In 2 Sel] and DIP Switch AI2 on the control board. Default Dip Switch setting is 10V.
4 “Preset Freq” External frequency command as defined by A143-A146 [Preset Freq x] when T051-T054 [Digital Inx Sel] are programmed as “Preset Frequencies” and the digital inputs are active.
5 “Comm Port” External frequency command from the communications port. Refer to Appendix E and Appendix G for details. ParameterC102 [Comm Format] is used to select a communications protocol.
82 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
Advanced Program GroupA141 [Purge Frequency] Related Parameter(s): P038, P039, P040, T051...T054
Provides a fixed frequency command value when T051...T054 [Digital Inx Sel] is set to 1 “Purge”. An active purge input will override speed command as shown in the flowchart on page 37.
Values Default: 5.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
A142 [Internal Freq] Related Parameter(s): P038, T051...T054
Provides the frequency command to the drive when P038 [Speed Reference] is set to 1 “Internal Freq”. When enabled, this parameter will change the frequency command in “real time” using the digital speed keys when in program mode.
If T051...T054 [Digital Inx Sel] is set to 16 “MOP Up” or 17 “MOP Down” this parameter acts as the MOP frequency reference if P038 [Speed Reference] is set to 1 “InternalFreq”.
Values Default: 60.00 Hz
Min/Max: 0.00/320.00 Hz
Display: 0.01 Hz
IMPORTANT Once the desired command frequency is reached, the Enter key must be pressed to store this value to EEPROM memory. If the ESC key is used before the Enter key, the frequency will return to the original value following the normal accel/decel curve.
A143 [Preset Freq 0](1) Related Parameter(s): P038, P039, P040, T051...T052, A147, A148A144 [Preset Freq 1]A145 [Preset Freq 2]A146 [Preset Freq 3]
Provides a fixed frequency command value when T051...T052 [Digital Inx Sel] is set to 8 “Preset Freq”.An active preset input will override speed command as shown in the flowchart on page page 37.
Values A143 Default:(1) A144 Default:A145 Default:A146 Default::
0.0 Hz5.0 Hz10.0 Hz20.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.01 Hz
(1) To activate A143 [Preset Freq 0] set P038 [Speed Reference] to option 4 “Preset Freq”
(2) When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.
Input State of Digital In 1 (I/O Terminal 05 when T051 = 8)
Input State of Digital In 2 (I/O Terminal 06 when T052 = 8)
Frequency Source Accel / Decel Parameter Used (2)
0 0 A143 [Preset Freq 0] [Accel Time 1] / [Decel Time 1]
1 0 A144 [Preset Freq 1] [Accel Time 1] / [Decel Time 1]
0 1 A145 [Preset Freq 2] [Accel Time 2] / [Decel Time 2]
1 1 A146 [Preset Freq 3] [Accel Time 2] / [Decel Time 2]
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 83
Chapter 3 Programming and Parameters
A147 [Accel Time 2] Related Parameter(s): P039, T051...T054, A143...A146
When active, sets the rate of acceleration for all speed increases. Refer to the flowchart on page 38 for details.Accel Rate = [Maximum Freq]/[Accel Time]
Values Default: 30.00 Secs
Min/Max: 0.00/600.00 Secs
Display: 0.01 Secs
Speed
0Time
P035 [Maximum Freq]
P039 or A147[Accel Time x]
P040 or A148[Decel Time x]0
Acce
lerat
ion
Deceleration
A148 [Decel Time 2] Related Parameter(s): P040, T051...T054, A143...A146
When active, sets the rate of deceleration for all speed decreases. Refer to the flowchart on page 38 for details.Maximum Freq/Decel Time = Decel Rate
Values Default: 30.00 Secs
Min/Max: 0.01/600.00 Secs
Display: 0.01 Secs
A149 [S Curve %]
Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve. Time is added, 1/2 at the beginning and 1/2 at the end of the ramp.
Values Default: 20%
Min/Max: 0/100% (A setting of 0% disables this parameter.)
Display: 1%
Example:Accel Time = 10 sS-Curve Setting = 50%S-Curve Time = 10 x 0.5 = 5 sTotal Time = 10 + 5 = 15 S
1/2 S Curve Time2.5 Seconds
Total Time to Accelerate = Accel Time + S Curve Time
50% S Curve
Target
Target/2
Accel Time10 Seconds
1/2 S Curve Time2.5 Seconds
Total Time to Accelerate = Accel Time + S Curve Time
100% S Curve
Target
S-Curve Time = Accel Time
A150 [PID Trim Hi]
Sets the maximum positive value that is added to a PID reference when PID trim is used.
Values Default: 60.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
84 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A151 [PID Trim Lo]
Sets the minimum positive value that is added to a PID reference when PID trim is used.
Values Default: 0.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
A152 [PID Ref Sel] Related Parameter(s): P038, T070, T071, T072, T074, T075Stop drive before changing this parameter.
Enables/disables PID mode and selects the source of the PID reference. Refer to Appendix D for details.Note: PID analog reference is scaled through the [Analog In x Hi/Lo] parameters. The invert operation is obtained through programming these two parameters. If A152 [PID Ref Sel] is not set to zero, PID can be disabled by programming a digital input.
Options 0 “PID Disabled” (Default)
1 “PID Setpoint
2 “Analog In 1”
3 “Analog In 2”
4 “Comm Port”
5 “Setpnt, Trim” Use PID output as Trim on [Frequency Select]
6 “A-In 1, Trim” Use PID output as Trim on [Frequency Select]
7 “A-In 2, Trim”(1) Use PID output as Trim on [Frequency Select]
8 “Comm, Trim” Use PID output as Trim on [Frequency Select]
(1) The PID will not function with bipolar input. It will ignore any negative voltages and treat them like zero.
A153 [PID Feedback Sel] Related Parameter(s): T070, T071, T072, T074, T075, A204, A205
Select the source of the PID feedback. Refer to Appendix D for details.Note: PID analog reference is scaled through the [Analog In x Hi/Lo] parameters. The invert operation is obtained through programming these two parameters.
Options 0 “Analog In 1” (Default)
1 “Analog In 2”
2 “Comm Port”(1)
3 “ACT1 - ACT2” (with FRN 7.xx and later)
ACT1 minus ACT2
4 “ACT1 + ACT2” (with FRN 7.xx and later)
ACT1 plus ACT2
5 “ACT1 * ACT2” (with FRN 7.xx and later)
ACT1 multiplied by ACT2
6 “ACT1 / ACT2” (with FRN 7.xx and later)
ACT1 divided by ACT2
7 “Min A1, A2” (with FRN 7.xx and later)
The smaller of ACT1 or ACT2 is used as the feedback signal.
8 “Max A1, A2” (with FRN 7.xx and later)
The larger of ACT1 or ACT2 is used as the feedback signal.
(1) The PID will not function with bipolar input. It will ignore any negative voltages and treat them like zero.
A154 [PID Prop Gain]
Sets the value for the PID proportional component when the PID mode is enabled by A152 [PID Ref Sel].
Values Default: 1.00
Min/Max: 0.00/99.99
Display: 0.01
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 85
Chapter 3 Programming and Parameters
A155 [PID Integ Time]
Sets the value for the PID integral component when the PID mode is enabled by A152 [PID Ref Sel].
Values Default: 2.0 Secs
Min/Max: 0.0/999.9 Secs
Display: 0.1 Secs
A156 [PID Diff Rate]
Sets the value for the PID differential component when the PID mode is enabled by A152 [PID Ref Sel].
Values Default: 0.00 (1/Secs)
Min/Max: 0.00/99.99 (1/Secs)
Display: 0.01 (1/Secs)
A157 [PID Setpoint]
Provides an internal fixed value for process setpoint when the PID mode is enabled by A152 [PID Ref Sel].
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
A158 [PID Deadband]
Sets the lower limit of the PID output.
Values Default: 0.0%
Min/Max: 0.0/10.0%
Display: 0.1%
A159 [PID Preload]
Sets the value used to preload the integral component on start or enable.
Values Default: 0.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
A160 [Process Factor] Related Parameter(s): b008
Scales the output frequency value displayed by b008 [Process Display].Process Display = [Output Freq] x [Process Factor]
Values Default: 30.0
Min/Max: 0.1/999.9
Display: 0.1
86 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A163 [Auto Rstrt Tries] Related Parameter(s): T055, T060, T065, T066, A164
Sets the maximum number of times the drive attempts to reset a fault and restart.Clear a Type 1 fault and restart the drive.1. Set A163 [Auto Rstrt Tries] to a value other than “0”.2. Set A164 [Auto Rstrt Delay] to a value other than “0”.Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.1. Set A163 [Auto Rstrt Tries] to a value other than “0”.2. Set A164 [Auto Rstrt Delay] to “0”.Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled. This feature automatically clears faults, but does not restart the drive.
Values Default: 0
Min/Max: 0/9
Display: 1
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate application. Do not use this function without considering applicable local, national and international codes, standards, regulations or industry guidelines.
A164 [Auto Rstrt Delay] Related Parameter(s): A163
Sets the time between restart attempts when A163 [Auto Rstrt Tries] is set to a value other than zero.Note: If the parameter is not set to zero and [Auto Rstrt Time] is set to zero, auto fault clear is enabled. This feature automatically clears faults, but does not restart the drive.
Values Default: 1.0 Secs
Min/Max: 0.0/160.0 Secs
Display: 0.1 Secs
A165 [Start At PowerUp] Related Parameter(s): P036Stop drive before changing this parameter.
Enables/disables a feature that allows a Start or Run command to automatically cause the drive to resume running at commanded speed after drive input power is restored. Requires a digital input configured for Run or Start and a valid start contact.This parameter will not function if parameter P036 [Start Source] is set to 4 “2-W Hi Speed”.
Options 0 “Disabled” (Default)
1 “Enabled”
ATTENTION: Equipment damage and/or personal injury may result if this parameter is used in an inappropriate application. Do not use this function without considering applicable local, national and international codes, standards, regulations or industry guidelines.
A166 [Reverse Disable] Related Parameter(s): b006, P036, T051-T054Stop drive before changing this parameter.
Enables/disables the function that allows the direction of motor rotation to be changed. The reverse command may come from a digital or a serial command. All reverse inputs including two-wire Run Reverse will be ignored with reverse disabled.
Options 0 “Rev Enabled”
1 “Rev Disabled” (Default
A167 [Flying Start En] Related Parameter(s): A200
Sets the condition that allows the drive to reconnect to a spinning motor at actual RPM.
Options 0 “Disabled” (Default)
1 “Enabled”
IMPORTANT When this parameter is enabled, verify that A200 [Motor NP FLA] is set to the motor’s actual full load amp value.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 87
Chapter 3 Programming and Parameters
A168 [PWM Frequency] Related Parameter(s): A169
Sets the carrier frequency for the PWM output waveform. The chart below provides derating guidelines based on the PWM frequency setting.
Values Default: 4.0 kHz
Min/Max: 2.0/10.0 kHz (Frame C and D drives)2.0/8.0 kHz (Frame E, F, G and H drives)
Display: 0.1 kHz
IMPORTANT Ignoring derating guidelines can cause reduced drive performance.
% O
utpu
t Cur
ent (
A)
68
8488
8076
96100
92
72
646056525048
Carrier Frequency (kHz)87654321 109
A169 [PWM Mode] Related Parameter(s): A168
Selects the PWM algorithm used.
Options 0 “Space Vector” 3-Phase Modulation: Provides quiet operation and produces less motor losses.
1 “2-Phase” (Default) 2-Phase Modulation: Provides less drive losses and best performance with long motor cable runs.
88 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A170 [Boost Select] Related Parameter(s): b004, P031, P032, A171, A172, A173
Sets the boost voltage (% of P031 [Motor NP Volts]) and redefines the Volts per Hz curve.Drive may add additional voltage unless Option 5 is selected.
Frames C-F Frames G-H
Options 0 “Custom V/Hz” 0 “Custom V/Hz”
1 “30.0, VT” 1 “30.0, VT” Typical Fan/Pump Curves
2 “35.0, VT” 2 “35.0, VT”
3 “40.0, VT” 3 “40.0, VT”
4 “45.0, VT” (Default) 4 “45.0, VT” (Default)
5 “0.0 no IR” 5 “0.0 no IR”
6 “0.0” 6 “0.0” Boost Curves
7 “2.5” 7 “0.2”
8 “5.0” 8 “0.5”
9 “7.5” 9 “0.8”
10 “10.0” 10 “1.0”
11 “12.5” 11 “2.0”
12 “15.0” 12 “3.0”
13 “17.5” 13 “4.0”
14 “20.0” 14 “5.0”
15 “Kepco” Curve(1) 15 “Kepco” Curve(1)
(1) Kepco Curve is used in specific systems to meet requirements of the Korean Electric Power Company.
% P032 [Motor NP Hertz]
% P
031
[Mot
or N
P Vo
lts]
100
501/2 [Motor NP Volts]
1/2
[Mot
or N
P H
ertz
]
4321
0 50 100
Settings5-14
A174 [Maximum Voltage] can be set anywhere.Settings greater than P031 [Motor NP Volts] define a point on the V/Hz curve.Settings less than P031 [Motor NP Volts] function as limits only and do not change the V/Hz curve.
P034 [Minimum Freq] can be set anywhere.Functions as a limit only and does not change the V/Hz curve.
P035 [Maximum Freq] can be set anywhere.Settings greater than P032 [Motor NP Hertz]define a point on the V/Hz curve.
P035 [Maximum Freq] can be set anywhere.Settings less than P032 [Motor NP Hertz] functionas limits only and do not change the V/Hz curve.
Setting Boost Voltage (% of Base)5 0.0 (no IR Comp. added)6 0.07 2.58 5.09 7.510 10.011 12.512 15.013 17.514 20.015 "Kepco" Curve (1)
Setting Fan/Pump Curves1 30.02 35.03 40.04 45.0
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 89
Chapter 3 Programming and Parameters
A171 [Start Boost] Related Parameter(s): P031, P032, P034, P035, A170, A172, A173, A174
Sets the boost voltage (% of P031 [Motor NP Volts]) and redefines the Volts per Hz curve when A170 [Boost Select] = 0 “Custom V/Hz”.
Values Default: 2.5%
Min/Max: 0.0/25.0%
Display: 1.1%
Frequency
Volta
ge
A173 [Break Frequency] P032 [Motor NP Hertz]
P035 [Maximum Freq]
A171
[Sta
rt Bo
ost]
P031 [Motor NP Volts]
A174 [Maximum Voltage]
A17
2 [B
reak
Vol
tage
]
A034 [Minimum Freq]
A172 [Break Voltage] Related Parameter(s): P031, P032, P034, P035, A170, A171, A173, A174
Sets the break voltage applied at the break frequency when A170 [Boost Select] = 0 “Custom V/Hz”.
Values Default: 25%
Min/Max: 0.0/100.0%
Display: 0.1%
A173 [Break Frequency] Related Parameter(s): P031, P032, P034, P035, A170, A171, A172, A174
Sets the frequency where break frequency is applied when A170 [Boost Select] = 0 “Custom V/Hz”.
Values Default: 15.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
A174 [Maximum Voltage] Related Parameter(s): b004, A171, A172, A173
Sets the highest voltage the drive will output.
Values Default: Drive Rated Volts
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
A175 [Slip Hertz @ FLA]] Related Parameter(s): P033
Compensates for the inherent slip in an induction motor. This frequency is added to the commandedoutput frequency based on motor current.
Values Default: 2.0 Hz
Min/Max: 0.0/10.0 Hz
Display: 0.1 Hz
90 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A176 [DC Brake Time] Related Parameter(s): P037, A177
Sets the length of time that DC brake current is “injected” into the motor when P037 [Stop Mode] is set to either 4 “Ramp” or 6 “DC Brake”. Refer to parameter A177 [DC Brake Level].
Values Default: 0.0 Secs
Min/Max: 0.0/99.9 Secs (A setting of 99.9 = Continuous)
Display: 0.1 Secs
A177 [DC Brake Level] Related Parameter(s): P037, T051...T054, A176, A178
Defines the maximum DC brake current, in amps, applied to the motor.
Values Default: Drive Rated Amps × 0.05
Min/Max: 0.0/(Drive Rated Amps × 1.5)
Display: 0.1 Amps
DC Injection Braking ModeVo
lts/S
peed
Voltage
TimeStop Command
Speed
[DC Brake Level]
[DC Brake Time]
Volts
/Spe
ed
Ramp-to-Stop Mode
TimeStop Command
[DC Brake Level]
[DC Brake Time]
VoltageSpeed
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliary mechanical braking device must be used.ATTENTION: This feature should not be used with synchronous or permanent magnet motors. Motors may be demagnetized during braking.
A178 [DC Brk Time@Strt] Related Parameter(s): P037, A177
Sets the length of time that DC brake current is “injected” into the motor after a valid start command is received. Parameter A177 [DC Brake Level] controls the level of braking current used.
Values Default: 0.0 Secs
Min/Max: 0.0/99.9 Secs (A setting of 99.9 = Continuous)
Display: 0.1 Secs
Volts
/Spe
ed
TimeStart Command
[DC Brake Level]
[DC Brk Time@Strt]Voltage
Speed
A179 [Current Limit 1] Related Parameter(s): P033
Maximum output current allowed before current limiting occurs.
Values Default: Drive Rated Amps × 1.1
Min/Max: 0.0/(Drive Rated Amps × 1.5)
Display: 0.1 Amps
A180 [Current Limit 2] Related Parameter(s): P033
Maximum output current allowed before current limiting occurs.
Values Default: Drive Rated Amps × 1.1
Min/Max: 0.0/(Drive Rated Amps × 1.5)
Display: 0.1 Amps
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 91
Chapter 3 Programming and Parameters
A181 [Motor OL Select] Related Parameter(s): P032, P033, P043
Drive provides Class 10 motor overload protection. Settings 0-2 select the derating factor for the I2t overload function.
Options 0 “No Derate” (Default)
1 “Min Derate”
2 “Max Derate”
Min Derate
0
80
100
60
40
20
No Derate
0
80
100
60
40
20
% o
f P03
3 [M
otor
OL
Cure
nt] Max Derate
0
80
100
60
40
20
0 2001751501251007550250 200175150125100755025 0 200175150125100755025
A182 [Drive OL Mode] Related Parameter(s): P032, P033
Determines how the drive handles overload conditions that would otherwise cause the drive to fault.
Options 0 “DIsabled”
1 “Reduce CLim”
2 “Reduce PWM”
3 “Both-PWM 1st” (Default)
A183 [SW Current Trip] Related Parameter(s): P033
Enables/disables a software instantaneous (within 100 ms) current trip.
Values Default: 0.0 (Disabled)
Min/Max: 0.0/(Drive Rated Amps × 1.8)
Display: 0.1 Amps
A184 [Load Loss Level] Related Parameter(s): P033
Provides a software trip (Load Loss fault) when the current drops below this level for the time specified in [Load Loss Time].
Values Default: 0.0 (Disabled)
Min/Max: 0.0/Drive Rated Amps
Display: 0.1 Amps
A185 [Load Loss Time] Related Parameter(s): P033
Sets the required time for the current to be below [Load Loss Level] before a Load Loss fault occurs.
Values Default: 0 Secs (Disabled)
Min/Max: 0/9999 Secs
Display: 1 Secs
A186 [Stall Fault Time]
Sets the time that the drive will remain in stall mode before a fault is issued.
Options 0 “60 Seconds” (Default)
1 “120 Seconds”
2 “240 Seconds”
3 “360 Seconds”
4 “480 Seconds”
5 “Flt Disabled
92 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A187 [Bus Reg Mode]
Controls the operation of the drive voltage regulation, which is normally operational at decel or when the bus voltage rises.Refer to the Attention statement on page 9 for important information on bus regulation.
Options 0 “Disabled”
1 “Enabled” (Default)
A188 [Skip Frequency 1] Related Parameter(s): A189
Sets the frequency at which the drive will not operate.A setting of 0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0/320 Hz
Display: 1 Hz
A189 [Skip Freq Band 1] Related Parameter(s): A188
Determines the bandwidth around A188 [Skip Frequency 1]. A189 [Skip Freq Band 1] is split applying 1/2 above and 1/2 below the actual skip frequency.A setting of 0.0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0.0/30.0 Hz
Display: 0.1 Hz
Frequency
Time
Skip Frequency
CommandFrequency
Drive OutputFrequency
Skip Frequency Band
A190 [Skip Frequency 2] Related Parameter(s): A191
Sets the frequency at which the drive will not operate.A setting of 0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0/320 Hz
Display: 1 Hz
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 93
Chapter 3 Programming and Parameters
A191 [Skip Freq Band 2] Related Parameter(s): A190
Determines the bandwidth around A190 [Skip Frequency 2]. A191 [Skip Freq Band 2] is split applying 1/2 above and 1/2 below the actual skip frequency.A setting of 0.0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0.0/30.0 Hz
Display: 0.1 Hz
Frequency
Time
Skip Frequency
CommandFrequency
Drive OutputFrequency
Skip Frequency Band
A192 [Skip Frequency 3] Related Parameter(s): A193
Sets the frequency at which the drive will not operate.A setting of 0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0/320 Hz
Display: 1 Hz
A193 [Skip Freq Band 3] Related Parameter(s): A192
Determines the bandwidth around A192 [Skip Frequency 3]. A193 [Skip Freq Band 3] is split applying 1/2 above and 1/2 below the actual skip frequency.A setting of 0.0 disables this parameter.
Values Default: 0 Hz
Min/Max: 0.0/30.0 Hz
Display: 0.1 Hz
Frequency
Time
Skip Frequency
CommandFrequency
Drive OutputFrequency
Skip Frequency Band
A194 [Compensation]
Enables/disables correction options that may improve problems with motor instability.
Options 0 “Disabled”
1 “Electrical” (Default)(1) Some drive/motor combinations have inherent instabilities which are exhibited as non-sinusodial motor currents. This setting attempts to correct this condition.
2 “Mechanical” Some motor/load combinations have mechanical resonances which can be excited by the drive current regulator. Thissetting slows down the current regulator response and attempts to correct this condition.
3 “Both”(1)
(1) Use “Dead Time Compensation” algorithm to minimize flat spots in motor current waveforms. Use this solution also to achieve motor stability.
94 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A195 [Reset Meters] Related Parameter(s): d310...d317
Resets the marker that indicates Fault Times and Energy usage.
Options 0 “Ready/Idle” (Default)
1 “Reset MWh” Also resets kWh marker.
2 “Reset Time” min, hr, and x10hr
A196 [Testpoint Sel] Related Parameter(s): d319
Used by Rockwell Automation field service personnel.
Values Default: 1024
Min/Max: 1024/65535
Display: 1
A197 [Fault Clear] Related Parameter(s): b007, d307, d308, d309Stop drive before changing this parameter.
Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.
Options 0 “Ready/Idle” (Default)
1 “Reset Fault”
2 “Clear Buffer” Clears all fault buffers.
A198 [Program Lock]
Protects parameters against change by unauthorized personnel. Enter a user-selected password to lock the parameters via Option 1. Enter the same password to unlock the parameters.
Options 0 “Unlocked” (Default)
1 “Locked” Locks all parameters.
2 “Locked” Parameter edits allowed over communications network.
3 “Locked” Locks P035 [Maximum Freq] and A170 [Boost Select].
A199 [Motor NP Poles] Related Parameter(s): d323
Sets the motor poles. This is used to calculate d323 [Output RPM].
Values Default: 4
Min/Max: 2/40
Display: 1
A200 [Motor NP FLA] Related Parameter(s): A167
Set to the motor nameplate rated full load amps.
Values Default: Drive Rated Amps
Min/Max: 0.1/(Drive Rated Amps × 2)
Display: 0.1 Amps
A201 [PID Invert Error]
(With FRN 6.xx and later.)When set to “Inverted”, changes the sign of the PID error. This causes an increase in the drive output frequency with PID Feedback greater than PID Setpoint, and a decrease in drive output frequency with PID Feedback less than PID Setpoint.
Options 0 “Not Inverted” (Default)
1 “Inverted” Locks all parameters.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 95
Chapter 3 Programming and Parameters
A202 [MOP Reset Sel] Related Parameter(s): A142
(With FRN 6.xx and later.)Set the drive to save the current MOP reference command.
Options 0 “Zero MOP Ref” This option clamps A142 [Internal Freq] at 0.0 Hz when the drive is not running.
1 “Save MOP Ref” (Default) Reference is saved in A142 [Internal Freq].
A203 [Wake Deviation] Related Parameter(s): T091
(with FRN 7.xx and later.)Sets the deviation from PID setpoint the drive must reach to wake from sleep mode.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
A204 [ACT1 Input] Related Parameter(s): A153
(with FRN 7.xx and later.)Defines the source of the data used as the actual (ACT) 1 input.
Options 0 “Analog In 1” (Default) Use Analog Input 1
1 “Analog In 2” Use Analog Input 2
2 “Current” Use b003 [Output Current]
A205 [ACT2 Input] Related Parameter(s): A153
(with FRN 7.xx and later.)Defines the source of the data used as the actual (ACT) 2 input.
Options 0 “Analog In 1” (Default) Use Analog Input 1
1 “Analog In 2” Use Analog Input 2
2 “Current” Use b003 [Output Current]
A206 [ACT1 Minimum] Related Parameter(s): A204
(with FRN 7.xx and later.)Sets the minimum value of the actual (ACT) 1 input. Used with the analog input min/max settings to scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.
Values Default: 0.0%
Min/Max: 0.0/200.0%
Display: 0.1%
A207 [ACT1 Maximum]
ACT1 % Normal
A206 [ACT1 Minimum]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]
A206 [ACT1 Minimum]
ACT1 % Inverted
A207 [ACT1 Maximum]
T070 [Analog In 1 Lo] T071 [Analog In 1 Hi]
A207 [ACT1 Maximum] Related Parameter(s): A204
(with FRN 7.xx and later.)Sets the maximum value of the actual (ACT) 1 input.
Values Default: 100.0%
Min/Max: 0.0/200.0%
Display: 0.1%
96 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
A208 [ACT2 Minimum] Related Parameter(s): A205
(with FRN 7.xx and later.)Sets the minimum value of the actual (ACT) 2 input. Used with the analog input min/max settings to scale the analog input for use as the PID feedback. Can be used in a normal and inverted mode.
Values Default: 0.0%
Min/Max: 0.0/200.0%
Display: 0.1%
A209 [ACT2 Maximum]
ACT2 % Normal
A208 [ACT2 Minimum]
T074 [Analog In 2 Lo] T075 [Analog In 2 Hi]
A208 [ACT2 Minimum]
ACT2 % Inverted
A209 [ACT2 Maximum]
T074 [Analog In 2 Lo] T075 [Analog In 2 Hi]
A209 [ACT2 Maximum] Related Parameter(s): A205
(with FRN 7.xx and later.)Sets the maximum value of the actual (ACT) 2 input.
Values Default: 100.0%
Min/Max: 0.0/200.0%
Display: 0.1%
A210 [Wake PID Preload] Related Parameter(s): T078
(with FRN 7.xx and later.)Sets the value used to preload the PID integral component on wake. This value must be greater than T078 [Sleep Level] or drive will not wake up.
Values Default: 0.0 Hz (No preload)
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
A210 [Wake PID Preload]
A210 = 0.0 Hz (no preload)PID Output
TimeWake
A157 [PID Setpoint]
A210 = 0.1 to 320.0 Hz
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 97
Chapter 3 Programming and Parameters
Aux Relay Card GroupR221 [Relay Out3 Sel] Related Parameters for the Aux Relay Card Group:R224 [Relay Out4 Sel] Aux ParametersR227 [Relay Out5 Sel] PID ParametersR230 [Relay Out6 Sel] Digital InputsR233 [Relay Out7 Sel] Relays 1 and 2R236 [Relay Out8 Sel]
Note: Auxiliary Relay Card option is not available for Frame C drives.Sets the condition that changes the state of the output relay contacts.
Options 0 “Ready/Fault” Relay changes state when power is applied. This indicates that the drive is ready for operation. Relay returns drive to shelf state when power is removed or a fault occurs.
1 “At Frequency” Drive reaches commanded frequency.
2 “MotorRunning” Motor is receiving power from the drive.
3 “Hand Active” Active when drive is in local control.
4 “Motor Overld” Motor overload condition exists.
5 “Ramp Reg” Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq” • Drive exceeds the frequency (Hz) value set in [Relay OutX Level].• Use T056 to set threshold.
7 “Above Cur” • Drive exceeds the current (% Amps) value set in [Relay OutX Level].• Use T056 to set threshold.
8 “Above DCVolt” • Drive exceeds the DC bus voltage value set in [Relay OutX Level].• Use T056 to set threshold.
9 “Above Anlg 2” • Analog input voltage (I/O Terminal 17) exceeds the value set in [Relay OutX Level].• Do not use if T073 [Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.• Use T056 to set threshold.
10 “Above PF Ang” • Power Factor angle has exceeded the value set in [Relay OutX Level].• Use T056 to set threshold.
11 “Anlg In Loss” Analog input loss has occurred. Program T072 [Analog In 1 Loss] and/or T076 [Analog In 2 Loss] for desired action when input loss occurs.
12 “ParamControl” Enables the output to be controlled over network communications by writing to [Relay OutX Level]. (0 = Off, 1 = On.)
13 “Retries Exst” Value set in A163 [Auto Rstrt Tries] is exceeded.
14 “NonRec Fault” • Number of retries for A163 [Auto Rstrt Tries] is exceeded OR• Non-resettable fault occurs OR• A163 [Auto Rstrt Tries] is not enabled.
15 “Reverse” Drive is commanded to run in reverse direction.
16 “Logic In 1” An input is programmed as “Logic In 1” and is active.
17 “Logic In 2” An input is programmed as “Logic In 2” and is active.
23 “Aux Motor” (Default) Auxiliary Motor is commanded to run. Refer to Appendix D
24 “Fault” (with FRN 7.xx and later) Relay output is inactive when power is applied to the drive and is active when a fault occurs. This is inverted from Option 0, “Ready/Fault”.
IMPORTANT Value for [Relay OutX Level] must be entered in percent of drive rated output current.
98 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
Refer to Appendix D for details on the application of parameters R239 through R254.
R222 [Relay Out3 Level] R225 [Relay Out4 Level] R228 [Relay Out5 Level] R231 [Relay Out6 Level] R234 [Relay Out7 Level] R237 [Relay Out8 Level]
Sets the trip point for the digital output relay if the value of [Relay OutX Sel] is 6, 7, 8, 9, 10 or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
[Relay OutX Select] Setting Relay OutX Level] Min/Max
67891012
0/320 Hz0/180%0/815 Volts0/100%1/180 degs0/1
R239 [Aux Motor Mode]
Enables operation of the auxiliary motor control modes when in PID mode.
Options 0 “Disabled” (Default)
1 “Enabled”
R240 [Aux Motor Qty]
Sets the number of auxiliary motors used while in Auxiliary Motor Control mode.
Options 1 “1 Aux Mtr” (Default) 1 Auxiliary Motor
2 “2 Aux Mtr” 2 Auxiliary Motors
3 “3 Aux Mtr” 3 Auxiliary Motors
4 “1 Mtr + Swap”(1) 1 Auxiliary Motor and AutoSwap Active
5 “2 Mtr + Swap”(1) 2 Auxiliary Motors and AutoSwap Active
6 “3 Mtr + Swap”(1) 3 Auxiliary Motors and AutoSwap Active
(1) Important: Proper wiring and parameter configuration of Aux Motor Control functions are especially important when using AutoSwap. Improper wiring or configuration could result in line power being applied to the drive outputs. Verify system operation before connecting auxiliary motor contact or outputs.
R240Option
Drive Relays Auxiliary Relay Card Relays
#1 Relay #2 Relay #3 Relay #4 Relay #5 Relay #6 Relay #7 Relay #8 Relay
1 Motor #2 AC Line
— — — — — — —
2 Motor #2 AC Line
Motor #3 AC Line
— — — — — —
3 Motor #2 AC Line
Motor #3 AC Line
Motor #4 AC Line
— — — — —
4 Motor #1 Drive
Motor #1 AC Line
Motor #2 Drive
Motor #2 AC Line
— — — —
5 Motor #1 Drive
Motor #1 AC Line
Motor #2 Drive
Motor #2 AC Line
Motor #3 Drive
Motor #3 AC Line
— —
6 Motor #1 Drive
Motor #1 AC Line
Motor #2 Drive
Motor #2 AC Line
Motor #3 Drive
Motor #3 AC Line
Motor #4 Drive
Motor #4 AC Line
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 99
Chapter 3 Programming and Parameters
R241 [Aux 1 Start Freq] R244 [Aux 2 Start Freq] R247 [Aux 3 Start Freq]
Sets the frequency that causes the next available auxiliary motor to turn on.
Values Default: 50.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
R242 [Aux 1 Stop Freq] R245 [Aux 2 Stop Freq] R248 [Aux 3 Stop Freq]
Sets the frequency that causes the next running auxiliary motor to turn off.
Values Default: 25.0 Hz
Min/Max: 0.0/320.0 Hz
Display: 0.1 Hz
R243 [Aux 1 Ref Add] R246 [Aux 2 Ref Add] R249 [Aux 3 Ref Add]
Sets the amount to add to the PID reference once the next auxiliary motor is turned on to compensate for a drop in the pipe due to the increased flow in a typical pump system.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
R250 [Aux Start Delay]
Sets the delay time before turning on the next auxiliary motor once the output frequency has risen above the value set in [Aux X Start Freq].
Values Default: 5.0 Secs
Min/Max: 0.0/999.9 Secs
Display: 0.1 Secs
R251 [Aux Stop Delay]
Sets the delay time before turning off the next running auxiliary motor once the output frequency has dropped below the value set in [Aux X Stop Freq].
Values Default: 3.0 Secs
Min/Max: 0.0/999.9 Secs
Display: 0.1 Secs
R252 [Aux Prog Delay]
Sets the time delay between connecting the drive controlled motor contactor and running the drive controlled motor and starting the auxiliary motor control.
Values Default: 0.50 Secs
Min/Max: 0.00/60.00 Secs
Display: 0.01 Secs
100 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
R253 [Aux AutoSwap Tme]
Sets the total running time between automatic motor changes.
Values Default: 0.0 Hr
Min/Max: 0.0/999.9 Hr
Display: 0.1 Hr
IMPORTANT Proper wiring and parameter configuration of Aux Motor Control functions are especially important when using AutoSwap. Improper wiring or configuration could result in line power being applied to the drive outputs. Verify system operation before connecting auxiliary motor contactor outputs.
R254 [Aux AutoSwap Lvl]
Sets the maximum level allowable for an AutoSwap to occur. If the PID output is above this level, AutoSwap will be delayed until the PID output drops below this parameter setting.
Values Default: 50.0%
Min/Max: 0.0/100.0%
Display: 0.1%
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 101
Chapter 3 Programming and Parameters
Advanced Display Groupd301 [Control Source] Related Parameter(s): P036, P038, T051...T054
Displays the active source of the Start Command and Speed Command which are normally defined by the settings of P036 [Start Source] and P038 [Speed Reference] but may be overridden by digital inputs. Refer to the flowcharts on page 37 and page 38 for details.
Values Default: Read Only
Min/Max: 0/99
Display: 1
Start Command Digit 00 = Keypad1 = Terminal Block2 = CommunicationsSpeed Command Digit 10 = Local Keypad Potentiometer1 = A142 [Internal Freq]2 = Analog Input 13 = Analog Input 24 = A143-A146 [Preset Freq x]
(T051 - T053 [Digital Inx Sel] must be set to 4)5 = CommunicationsReserved Digit 2Reserved Digit 3
d302 [Contrl In Status] Related Parameter(s): b002, P036, T051...T054
Status of the control terminal block control inputs.
Values Default: Read Only
Min/Max: 0/1
Display: 1
IMPORTANT Actual control commands may come from a source other than the control terminal block.
1 = Condition True, 0 = Condition FalseStart/FWD In I/O Terminal 02Dir/REV In I/O Terminal 03Stop Input I/O Terminal 01Digital In 1 I/O Terminal 05Digital In 2 I/O Terminal 06Digital In 3 I/O Terminal 07Digital In 4 I/O Terminal 08Not Used
d303 [Comm Status] Related Parameter(s): C102...C103
Status of the communications ports.
Values Default: Read Only
Min/Max: 0/1111
Display: 1
1 = Condition True, 0 = Condition FalseReceived Good Message Packet Digit 0Transmitting Message Digit 1DSI Peripheral Connected Digit 2Received Bad Message Packet Digit 3
102 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
d304 [PID Setpnt Displ] Related Parameter(s): A152
Displays the active PID Setpoint value.
Values Default: 0.0%
Min/Max: 0.0/100.0%
Display: 0.1%
d305 [Analog In 1] Related Parameter(s): T069-T071
Displays the status of Analog Input 1.
Values Default: 0.0%
Min/Max: 0.0/120.0%
Display: 0.1%
d306 [Analog In 2] Related Parameter(s): T073...T075
Displays the status of Analog Input 2.
Values Default: 0.0%
Min/Max: 0.0/120.0%
Display: 0.1%
d307 [Fault 1 Code] Related Parameter(s): A197
A code that represents a drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d308 [Fault 2 Code] Related Parameter(s): A197
A code that represents the second most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 1 Code]. The value of this parameter is then moved to [Fault 3 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d309 [Fault 3 Code] Related Parameter(s): A197
A code that represents the third most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 2 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d310 [Fault 1 Time-hr] Related Parameter(s): A195, d316
Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 103
Chapter 3 Programming and Parameters
d311 [Fault 1 Time-min] Related Parameter(s): A195, d317
Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1 Min
d312 [Fault 2 Time-hr] Related Parameter(s): A195, d316
Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d313 [Fault 2 Time-min] Related Parameter(s): A195, d317
Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1 Min
d314 [Fault 3 Time-hr] Related Parameter(s): A195, d316
Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d315 [Fault 3 Time-min] Related Parameter(s): A195, d317
Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1 Min
d316 [Elapsed Time-hr] Related Parameter(s): A195, d310, d312, d314
Displays the total elapsed powered-up time (in hours) since timer reset. The timer stops when it reaches maximum.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d317 [Elapsed Time-min] Related Parameter(s): A195, d311, d313, d315
Displays the total elapsed powered-up time (in minutes) since timer reset. The timer will increment the hour parameter when appropriate.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1 Min
d318 [Output Powr Fctr] Related Parameter(s): T055, T056, T060, T061, T065, T066
The angle in electrical degrees between motor voltage and motor current.
Values Default: Read Only
Min/Max: 0.0/180.0 deg
Display: 0.1 deg
104 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
d319 [Testpoint Data] Related Parameter(s): A196
The present value of the function selected in A196 [Testpoint Sel].
Values Default: Read Only
Min/Max: 0/FFFF
Display: 1 Hex
d320 [Control SW Ver]
Main Control Board software version.
Values Default: Read Only
Min/Max: 1.00/99.99
Display: 0.01
d321 [Drive Type]
Used by Rockwell Automation field service personnel.
d322 [Output Speed] Related Parameter(s): P034
Displays current output frequency in percent (%). The scale is 0% at 0.00 Hz to 100.0% at P034 [Maximum Freq].
Values Default: Read Only
Min/Max: 0.0/100.0%
Display: 0.1%
d323 [Output RPM] Related Parameter(s): A199
Displays current output frequency in RPM. The scale is based on A199 [Motor NP Poles].
Values Default: Read Only
Min/Max: 0/24000 RPM
Display: 1 RPM
d324 [Fault Frequency] Related Parameter(s): b001
Displays the value of b001 [Output Freq] when the last fault occurred.
Values Default: Read Only
Min/Max: 0.00/320.00 Hz
Display: 0.01 Hz
d325 [Fault Current] Related Parameter(s): b003
Displays the value of b003 [Output Current] when the last fault occurred.
Values Default: Read Only
Min/Max: 0.0/(Drive Rated Amps × 2)
Display: 0.1 Amps
d326 [Fault Bus Volts] Related Parameter(s): b005
Displays the value of b005 [DC Bus Voltage] when the last fault occurred.
Values Default: Read Only
Min/Max: 0/820 VDC
Display: 1 VDC
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 105
Chapter 3 Programming and Parameters
d327 [Status @ Fault] Related Parameter(s): b006
Displays the value of b006 [Drive Status] when the last fault occurred.
Values Default: Read Only
Min/Max: 0/1
Display: 1
d328 [PID Fdbk Display] Related Parameter(s): b006
(With FRN 7.xx and later.)Displays the active PID Feedback value.
Values Default: 0.0%
Min/Max: -200.0/200.0%
Display: 0.1%
d329 [DC Bus Ripple V] Related Parameter(s): b006
(With FRN 6.xx and later.)Displays the real-time value of DC bus ripple voltage.Excessive voltage ripple will eventually result in F017 Input Phase Loss fault.Fault ripple levels are: 30V for 230V rated drives, and 60V for 460V rated drives.
Values Default: Read Only
Min/Max: 0/(410 for 230 VAC drives, 820 for 460 VAC drives) VDC
Display: 1 VDC
d330 [Fault 4 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the fourth most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 3 Code]. The value of this parameter is then moved to [Fault 3 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d331 [Fault 5 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the fifth most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 4 Code]. The value of this parameter is then moved to [Fault 3 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d332 [Fault 6 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the sixth most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 5 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
106 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
d333 [Fault 7 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the seventh most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 6 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d333 [Fault 7 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the seventh most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 6 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d334 [Fault 8 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the seventh most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 7 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d335 [Fault 9 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the seventh most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 8 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d336 [Fault 10 Code] Related Parameter(s): A197
(With FRN 6.xx and later.)A code that represents the seventh most recent drive fault. The codes will appear in these parameters in the order they occur (d307 [Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once. As faults occur, this parameter will be overwritten by [Fault 9 Code].Refer to Chapter 4 for fault code descriptions.
Values Default: Read Only
Min/Max: 0/122
Display: 1
d337 [Fault 4 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 107
Chapter 3 Programming and Parameters
d338 [Fault 4 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
d339 [Fault 5 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d340 [Fault 5 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
d341 [Fault 6 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d342 [Fault 6 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
d343 [Fault 7 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d344 [Fault 7 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
108 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
d345 [Fault 8 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d346 [Fault 8 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
d347 [Fault 9 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d348 [Fault 9 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
d349 [Fault10 Time-hr] Related Parameter(s): A195, d316
(With FRN 6.xx and later.)Displays the value of the d316 [Elapsed Time-hr] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0/32767 Hr
Display: 1 Hr
d350 [Fault10 Time-min] Related Parameter(s): A195, d317
(With FRN 6.xx and later.)Displays the value of the d317 [Elapsed Time-min] parameter when the fault occurred.
Values Default: Read Only
Min/Max: 0.0/60.0 Min
Display: 0.1Min
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 109
Chapter 3 Programming and Parameters
Parameter Cross Reference by Name
Parameter Name Number Group Page Parameter Name Number Group Page
Accel Time 1 P039 Basic Program 64 Aux Stop Delay R251 Relay Card 100
Accel Time 2 A147 Advanced Program 84 Boost Select A170 Advanced Program 89
ACT1 Input A204 Advanced Program 96 Break Frequency A173 Advanced Program 90
ACT1 Maximum A207 Advanced Program 96 Break Voltage A172 Advanced Program 90
ACT1 Minimum A206 Advanced Program 96 Bus Reg Mode A187 Advanced Program 93
ACT2 Input A205 Advanced Program 96 Comm Data Rate C103 Communications 79
ACT2 Maximum A209 Advanced Program 97 Comm Format C102 Communications 79
ACT2 Minimum A208 Advanced Program 97 Comm Loss Action C105 Communications 80
Analog In 1 d305 Advanced Display 103 Comm Loss Time C106 Communications 80
Analog In 1 Hi T071 Terminal Block 71 Comm Node Addr C104 Communications 80
Analog In 1 Lo T070 Terminal Block 71 Comm Status d303 Advanced Display 102
Analog In 1 Loss T072 Terminal Block 72 Comm Write Mode C107 Communications 80
Analog In 1 Sel T069 Terminal Block 71 Commanded Freq b002 Basic Display 58
Analog In 2 d306 Advanced Display 103 Compensation A194 Advanced Program 94
Analog In 2 Hi T075 Terminal Block 73 Contrl In Status d302 Advanced Display 102
Analog In 2 Lo T074 Terminal Block 72 Control Source d301 Advanced Display 102
Analog In 2 Loss T076 Terminal Block 73 Control SW Ver d320 Advanced Display 105
Analog In 2 Sel T073 Terminal Block 72 Current Limit 1 A179 Advanced Program 91
Analog In Filter T089 Terminal Block 77 Current Limit 2 A180 Advanced Program 91
Analog Out1 High T083 Terminal Block 75 DC Brake Level A177 Advanced Program 91
Analog Out1 Sel T082 Terminal Block 75 DC Brake Time A176 Advanced Program 91
Analog Out2 High T086 Terminal Block 77 DC Bus Voltage b005 Basic Display 58
Analog Out2 Sel T085 Terminal Block 76 DC Bus Ripple V d329 Advanced Display 106
Anlg Loss Delay T088 Terminal Block 77 DC Brk Time@Strt A178 Advanced Program 91
Anlg Out1 Setpt T084 Terminal Block 76 Decel Time 1 P040 Basic Program 64
Anlg Out2 Setpt T087 Terminal Block 77 Decel Time 2 A148 Advanced Program 84
Auto Mode P042 Basic Program 64 Digital In1 Sel T051 Terminal Block 66
Auto Rstrt Delay A164 Advanced Program 87 Digital In2 Sel T052 Terminal Block 66
Auto Rstrt Tries A163 Logic 87 Digital In3 Sel T053 Terminal Block 66
Aux 1 Ref Add R243 Relay Card 100 Digital In4 Sel T054 Terminal Block 66
Aux 2 Ref Add R246 Relay Card 100 Drive OL Mode A182 Advanced Program 92
Aux 3 Ref Add R249 Relay Card 100 Drive Status b006 Basic Display 58
Aux 1 Start Freq R241 Relay Card 100 Drive Temp b014 Basic Display 59
Aux 2 Start Freq R244 Relay Card 100 Drive Type d321 Advanced Display 105
Aux 3 Start Freq R247 Relay Card 100 Elapsed MWh b011 Basic Display 59
Aux 1 Stop Freq R242 Relay Card 100 Elapsed Run Time b012 Basic Display 59
Aux 2 Stop Freq R245 Relay Card 100 Elapsed Time-hr d316 Advanced Display 104
Aux 3 Stop Freq R248 Relay Card 100 Elapsed Time-min d317 Advanced Display 104
Aux AutoSwap Lvl R254 Relay Card 101 Fault 1 Code b007 Basic Display 59
Aux AutoSwap Tme R253 Relay Card 101 Fault 1 Code d307 Advanced Display 103
Aux Motor Mode R239 Relay Card 99 Fault 1 Time-hr d310 Advanced Display 103
Aux Motor Qty R240 Relay Card 99 Fault 1 Time-min d311 Advanced Display 104
Aux Prog Delay R252 Relay Card 100 Fault 2 Code d308 Advanced Display 103
Aux Start Delay R250 Relay Card 100 Fault 2 Time-hr d312 Advanced Display 104
110 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Programming and Parameters Chapter 3
Fault 2 Time-min d313 Advanced Display 104 Opto Out Logic T068 Terminal Block 71
Fault 3 Code d309 Advanced Display 103 Opto Out Sel T065 Terminal Block 70
Fault 3 Time-hr d314 Advanced Display 104 Output Current b003 Basic Display 58
Fault 3 Time-min d315 Advanced Display 104 Output Freq b001 Basic Display 58
Fault 4 Code d330 Advanced Display 106 Output Power b010 Basic Display 59
Fault 4 Time-hr d337 Advanced Display 107 Output Powr Fctr d318 Advanced Display 104
Fault 4 Time-min d338 Advanced Display 108 Output RPM d323 Advanced Display 105
Fault 5 Code d331 Advanced Display 106 Output Speed d322 Advanced Display 105
Fault 5 Time-hr d339 Advanced Display 108 Output Voltage b004 Basic Display 58
Fault 5 Time-min d340 Advanced Display 108 PID Deadband A158 Advanced Program 86
Fault 6 Code d332 Advanced Display 106 PID Diff Rate A156 Advanced Program 86
Fault 6 Time-hr d341 Advanced Display 108 PID Fdbk Display d328 Advanced Display 106
Fault 6 Time-min d342 Advanced Display 108 PID Feedback Sel A153 Advanced Program 85
Fault 7 Code d333 Advanced Display 107 PID Integ Time A155 Advanced Program 86
Fault 7 Time-hr d343 Advanced Display 108 PID Invert Error A201 Advanced Program 95
Fault 7 Time-min d344 Advanced Display 108 PID Preload A159 Advanced Program 86
Fault 8 Code d334 Advanced Display 107 PID Prop Gain A154 Advanced Program 85
Fault 8 Time-hr d345 Advanced Display 109 PID Ref Sel A152 Advanced Program 85
Fault 8 Time-min d346 Advanced Display 109 PID Setpnt Displ d304 Advanced Display 103
Fault 9 Code d335 Advanced Display 107 PID Setpoint A157 Advanced Program 86
Fault 9 Time-hr d347 Advanced Display 109 PID Trim Hi A150 Advanced Program 84
Fault 9 Time-min d348 Advanced Display 109 PID Trim Lo A151 Advanced Program 85
Fault10 Code d336 Advanced Display 107 Preset Freq 0 A143 Advanced Program 83
Fault10 Time-hr d349 Advanced Display 109 Preset Freq 1 A144 Advanced Program 83
Fault10 Time-min d350 Advanced Display 109 Preset Freq 2 A145 Advanced Program 83
Fault Bus Volts d326 Advanced Display 105 Preset Freq 3 A146 Advanced Program 83
Fault Clear A197 Advanced Program 95 Process Display b008 Basic Display 59
Fault Current d325 Advanced Display 105 Process Factor A160 Advanced Program 86
Fault Frequency d324 Advanced Display 105 Program Lock A198 Advanced Program 95
Flying Start En A167 Advanced Program 87 Purge Frequency A141 Advanced Program 83
Internal Freq A142 Advanced Program 83 PWM Frequency A168 Advanced Program 88
Language C101 Communications 79 PWM Mode A169 Advanced Program 88
Load Loss Level A184 Advanced Program 92 Relay 1 Off Time T059 Terminal Block 68
Load Loss Time A185 Advanced Program 92 Relay 1 On Time T058 Terminal Block 68
Maximum Freq P035 Basic Program 61 Relay 2 Off Time T064 Terminal Block 69
Maximum Voltage A174 Advanced Program 90 Relay 2 On Time T063 Terminal Block 69
Minimum Freq P034 Basic Program 61 Relay Out1 Level T056 Terminal Block 67
MOP Reset Sel A202 Advanced Program 96 Relay Out1 Sel T055 Terminal Block 67
Motor NP FLA A200 Advanced Program 95 Relay Out2 Level T061 Terminal Block 69
Motor NP Hertz P032 Basic Program 61 Relay Out2 Sel T060 Terminal Block 68
Motor NP Poles A199 Advanced Program 95 Relay Out3 Level R222 Relay Card 99
Motor NP Volts P031 Basic Program 61 Relay Out3 Sel R221 Relay Card 98
Motor OL Current P033 Basic Program 61 Relay Out4 Level R225 Relay Card 99
Motor OL Ret P043 Basic Program 65 Relay Out4 Sel R224 Relay Card 98
Motor OL Select A181 Advanced Program 92 Relay Out5 Level R228 Relay Card 99
Opto Out Level T066 Terminal Block 70 Relay Out5 Sel R227 Relay Card 98
Parameter Name Number Group Page Parameter Name Number Group Page
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 111
Chapter 3 Programming and Parameters
Relay Out6 Level R231 Relay Card 99 Slip Hertz @ FLA A175 Advanced Program 90
Relay Out6 Sel R230 Relay Card 98 Speed Ref 2 C109 Communications 82
Relay Out7 Level R233 Relay Card 98 Speed Reference P038 Basic Program 63
Relay Out7 Sel R234 Relay Card 99 Stall Fault Time A186 Advanced Program 92
Relay Out8 Level R237 Relay Card 99 Start At PowerUp A165 Advanced Program 87
Relay Out8 Sel R236 Relay Card 98 Start Boost A171 Advanced Program 90
Reset Meters A195 Advanced Program 95 Start Source P036 Basic Program 62
Reset To Defalts P041 Basic Program 64 Start Source 2 C108 Communications 81
Reverse Disable A166 Advanced Program 87 Status @ Fault d327 Advanced Display 106
S Curve % A149 Advanced Program 84 Stop Mode P037 Basic Program 63
Skip Freq Band 1 A189 Advanced Program 93 SW Current Trip A183 Advanced Program 92
Skip Freq Band 2 A191 Advanced Program 94 Testpoint Data d319 Advanced Display 105
Skip Freq Band 3 A193 Advanced Program 94 Testpoint Sel A196 Advanced Program 95
Skip Frequency 1 A188 Advanced Program 93 Torque Current b013 Basic Display 59
Skip Frequency 2 A190 Advanced Program 93 Wake Deviation A203 Advanced Program 96
Skip Frequency 3 A192 Advanced Program 94 Wake Level T080 Terminal Block 74
Sleep Level T078 Terminal Block 73 Wake PID Preload A210 Advanced Program 97
Sleep Sel T090 Terminal Block 77 Wake Sel T091 Terminal Block 78
Sleep Time T079 Terminal Block 74 Wake Time T081 Terminal Block 74
Sleep-Wake Sel T077 Terminal Block 73
Parameter Name Number Group Page Parameter Name Number Group Page
112 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 4
Troubleshooting
This chapter provides information to guide you in troubleshooting the PowerFlex 400 drive. Included is a listing and description of drive faults (with possible solutions, when applicable).
Drive Status The condition or state of your drive is constantly monitored. Any changes will be indicated through the integral keypad.
LED Indications
See page 47 for information on drive status indicators and controls.
Faults A fault is a condition that stops the drive. There are two fault types.
For information on... See page
Drive Status 113
Faults 113
Fault Descriptions 115
Common Symptoms and Corrective Actions 117
Type Fault Description
1 Auto-Reset/Run When this type of fault occurs, and A163 [Auto Rstrt Tries] is set to a value greater than “0,” a user-configurable timer, A164 [Auto Rstrt Delay], begins. When the timer reaches zero, the drive attempts to automatically reset the fault. If the condition that caused the fault is no longer present, the fault will be reset and the drive will be restarted.
2 Non-Resettable This type of fault may require drive or motor repair, or is caused by wiring or programming errors. The cause of the fault must be corrected before the fault can be cleared.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 113
Chapter 4 Troubleshooting
Fault Indication
Manually Clearing Faults
Automatically Clearing Faults
Condition Display
Drive is indicating a fault.The integral LCD display provides visual notification of a fault condition by displaying the following.• Flashing fault number• Flashing fault indicator Press the Escape key to regain control of the integral keypad.
Step Key(s)
1. Press Esc to acknowledge the fault. The fault information will be removed so that you can use the integral keypad. Access b007 [Fault 1 Code] to view the most recent fault information.
2. Address the condition that caused the fault. The cause must be corrected before the fault can be cleared. See Table 18.
3. After corrective action has been taken, clear the fault by one of these methods.– Press Stop if P037 [Stop Mode] is set to a value between “0” and “3”. – Cycle drive power.– Set A197 [Fault Clear] to “1” or “2”.– Cycle digital input if T051...T054[DigIn TermBlk xx] is set to option 10 “Clear Fault”.
Option/Step
Clear a Type 1 fault and restart the drive.1. Set A163 [Auto Rstrt Tries] to a value other than “0”.2. Set A164 [Auto Rstrt Delay] to a value other than “0”.
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.1. Set A163 [Auto Rstrt Tries] to a value other than “0”.2. Set A164 [Auto Rstrt Delay] to “0”.
114 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Troubleshooting Chapter 4
Auto Restart (Reset/Run)
The Auto Restart feature allows the drive to automatically perform a fault reset followed by a start attempt without user or application intervention. This allows remote or “unattended” operation. Only certain faults are allowed to be reset. Certain faults (Type 2) that indicate possible drive component malfunction are not resettable.
Use caution when enabling this feature, since the drive will attempt to issue its own start command based on user selected programming.
Fault Descriptions Table 18 - Fault Types, Descriptions and Actions
No. Fault Type(1)
Description Action
F2 Auxiliary Input 1 Auxiliary input interlock is open. 1. Check remote wiring.2. Verify communications
programming for intentional fault.
F3 Power Loss 2 FRN 5.03 and earlier only: The DC bus voltage fell below undervoltage level within 200 ms of a start command, DC bus ripple voltage is excessive, or an input phase loss has been detected.
1. Monitor the incoming AC line for low voltage or line power interruption.
2. Check input fuses.
F4 UnderVoltage 1 DC bus voltage fell below the minimum value.
1. Monitor the incoming AC line for low voltage or line power interruption.
2. Check input fuses.
F5 OverVoltage 1 DC bus voltage exceeded maximum value.
Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake chopper.
F6 Motor Stalled 1 Drive is unable to accelerate or decelerate motor.
Increase P039...A147 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A179 [Current Limit 1].
F7 Motor Overload 1 Internal electronic overload trip. 1. An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current].
2. Verify A170 [Boost Select] setting.
F8 Heatsink OvrTmp 1 Heatsink temperature exceeds a predefined value.
1. Check for blocked or dirty heat sink fins. Verify that ambient temperature has not exceeded 45°C (113°F) for IP 30/NEMA 1/UL Type 1 installations or 50°C (122°F) for IP20/Open type installations.
2. Check fan.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 115
Chapter 4 Troubleshooting
F12 HW OverCurrent 2 The drive output current has exceeded the hardware current limit.
Check programming. Check for excess load, improper A170 [Boost Select] setting, DC brake volts set too high or other causes of excess current.
F13 Ground Fault 2 A current path to earth ground has been detected at one or more of the drive output terminals.
Check the motor and external wiring to the drive output terminals for a grounded condition.
F15 Load Loss 1 Output current has dropped below the level set in A184 [Load Loss Level].
Check for load loss (i.e., a broken belt).
F17 Input Phase Loss (FRN 6.xx and later)
2 Excessive DC bus ripple voltage detected. See d329 [DC Bus Ripple V].
Check incoming power for a missing phase or blown fuse. If drive is used intentionally with single phase input, apply output derating to 35% actual drive rating.
F29 Analog Input Loss
1 An analog input is configured to fault on signal loss. A signal loss has occurred.Configure with T072 [Anlalog In Loss].
1. Check parameters.2. Check for broken/loose
connections at inputs.
F32 Fan Fdbck Loss (FRN 6.xx and later)
2 A loss of cooling fan feedback has been detected. (Frames E and F only
Make sure cooling fans are clear of debris and spinning freely. Replace fan if necessary.
F33 Auto Rstrt Tries 2 Drive unsuccessfully attempted to reset a fault and resume running for the programmed number of A163 [Auto Rstrt Tries].
Correct the cause of the fault and manually clear.
F38 Phase U to Gnd 2 A phase to ground fault has been detected between the drive and motor in this phase.
1. Check the wiring between the drive and motor.
2. Check motor for grounded phase.3. Replace drive if fault cannot be
cleared.
F39 Phase V to Gnd
F40 Phase W to Gnd
F41 Phase UV Short 2 Excessive current has been detected between these two output terminals.
1. Check the motor and drive output terminal wiring for a shorted condition.
2. Replace drive if fault cannot be cleared.
F42 Phase UW Short
F43 Phase VW Short
F48 Params Defaulted
The drive was commanded to write default values to EEPROM.
1. Clear the fault or cycle power to the drive.
2. Program the drive parameters as needed.
F63 SW OverCurrent 1 Programmed A183 [SW Current Trip] has been exceeded.
Check load requirements and A183 [SW Current Trip] setting.
F64 Drive Overload 2 Drive rating of 110% for 1 minute or 150% for 3 seconds has been exceeded.
Reduce load or extend Accel Time.
F70 Power Unit 2 Failure has been detected in the drive power section.
1. Cycle power.2. Replace drive if fault cannot be
cleared.
F71 Net Loss The communication network has faulted.
1. Cycle power.2. Check communications cabling.3. Check network adapter setting.4. Check external network status.
Table 18 - Fault Types, Descriptions and Actions
No. Fault Type(1)
Description Action
116 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Troubleshooting Chapter 4
Common Symptoms and Corrective Actions
Motor does not Start.
F81 Comm Loss 2 RS485 (DSI) port stopped communicating.
1. Check RS485 wiring connection.2. Check if a communications
adapter or HIM was disconnected.
3. Increase C106 [Comm Loss Time] to an appropriate time for application.
4. Change C105 [Comm Loss Action] to a value other than “0” (fault), if appropriate for the application.
F94 Function Loss 2 P036 [Start Source] is set to setting 6. The input to terminal 01 has been opened.
Close input to terminal 01 and re-start the drive
F100 Parameter Checksum
2 The checksum read from the board does not match the checksum calculated.
Set P041 [Reset To Defalts] to option 1 “Reset Defaults”.
F122 I/O Board Fail 2 Failure has been detected in the drive control and I/O section.
1. Cycle power.2. Replace drive if fault cannot be
cleared.
(1) See page 113 for a description of fault types
Table 18 - Fault Types, Descriptions and Actions
No. Fault Type(1)
Description Action
Cause(s) Indication Corrective Action
No output voltage to the motor. None Check the power circuit.• Check the supply voltage.• Check all fuses and disconnects.Check the motor.• Verify that the motor is connected properly.Check the control input signals.• Verify that a Start signal is present. If 2-Wire control is used, verify that either the
Run Forward or Run Reverse signal is active, but not both.• Verify that I/O Terminal 01 is active.• Verify that P036 [Start Source] matches your configuration.• Verify that A166 [Reverse Disable] is not prohibiting movement.
Drive is Faulted Flashing red status light Clear fault.• Press Stop.• Cycle power.• Set A197 [Fault Clear] to option 1 “Clear Faults”.• Cycle digital input if T051...T054 [Digital Inx Sel] is set to option 7 “Clear Fault”.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 117
Chapter 4 Troubleshooting
Drive does not Start from Start or Run Inputs wired to the terminal block.
Drive does not Start from Integral Keypad.
Cause(s) Indication Corrective Action
Drive is Faulted Flashing red status light Clear fault.• Press Stop.• Cycle power.• Set A197 [Fault Clear] to option 1 “Clear Faults”.• Cycle digital input if T051...T054 [Digital Inx Sel] is set to option 7 “Clear Fault”.
Incorrect programming.• P036 [Start Source] is set to option 0 “Keypad” or option 5
“RS485 (DSI) Port”.• T051...T054 [Digital Inx Sel] is set to option 5 “Local” and
the input is active.
None Check parameter settings.
Incorrect input wiring.See page 32 for wiring examples.• 2 wire control requires Run Forward, Run Reverse or Jog
input. • 3 wire control requires Start and Stop inputs• Stop input is always required.
None Wire inputs correctly and/or install jumper.
Incorrect Sink/Source DIP switch setting. None Set switch to match wiring scheme.
Cause(s) Indication Corrective Action
Integral keypad is not enabled. Green LED above Start key is not illuminated.
• Set P036 [Start Source] to option 0 “Keypad”.• Set parameter T051...T054 [Digital Inx Sel] to option 5 “Local” and activate
the input.
I/O Terminal 01 “Stop” input is not present. None Wire inputs correctly and/or install jumper.
118 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Troubleshooting Chapter 4
Drive does not respond to changes in speed command.
Motor and/or drive will not accelerate to commanded speed.
Motor operation is unstable.
Drive will not reverse motor direction.
Cause(s) Indication Corrective Action
No value is coming from the source of the command. The drive “Run” indicator is lit and output is 0 Hz.
• Check d301 [Control Source] for correct source.• If the source is an analog input, check wiring and use a meter to check for
presence of signal.• Check b002 [Commanded Freq] to verify correct command.
Incorrect reference source is being selected by remote device or digital inputs.
None • Check d301 [Control Source] for correct source.• Check d302 [Contrl In Status] to see if inputs are selecting an alternate source.
Verify settings for T051...T054 [Digital Inx Sel].• Check P038 [Speed Reference] for the source of the speed reference. Reprogram
as necessary.• Review the Speed Reference Control chart on page 37.
Cause(s) Indication Corrective Action
Acceleration time is excessive. None Reprogram P039[Accel Time 1] or A147 [Accel Time 2].
Excess load or short acceleration times force the drive into current limit, slowing or stopping acceleration.
None • Compare b003 [Output Current] with A179 [Current Limit 1].• Remove excess load or reprogram P039 [Accel Time 1] or A147 [Accel Time 2].• Check for improper A170 [Boost Select] setting.
Speed command source or value is not as expected. None • Verify b002 [Commanded Freq].• Check A170 [Control Source] for the proper Speed Command.
Programming is preventing the drive output from exceeding limiting values.
None Check P035 [Maximum Freq] to ensure that speed is not limited by programming.
Cause(s) Indication Corrective Action
Motor data was incorrectly entered. None 1. Correctly enter motor nameplate data into P031, P032 and P033.2. Enable A194 [Compensation].3. Use A170 [Boost Select] to reduce boost level.
Cause(s) Indication Corrective Action
Digital input is not selected for reversing control. None Check T051...T054 [Digital Inx Sel] and P036 [Start Source]. Choose correct input and program for reversing mode.
Digital input is incorrectly wired. None Check input wiring (See page 30).
Motor wiring is improperly phased for reverse. None Switch two motor leads.
Reverse is disabled. None Check A166 [Reverse Disable].
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 119
Chapter 4 Troubleshooting
Drive does not power up.
Cause(s) Indication Corrective Action
No input power to drive. None • Check the power circuit.• Check the supply voltage.• Check all fuses and disconnects.
Jumper between Power Terminals P2 and P1 not installed and/or DC Bus Inductor not connected.
None Install jumper or connect DC Bus Inductor.
120 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix A
Supplemental Drive Information
Drive, Fuse & Circuit Breaker Ratings
The tables on the following pages provide recommended AC line input fuse and circuit breaker information. See Fusing and Circuit Breakers below for UL and IEC requirements. Sizes listed are the recommended sizes based on 40 °C (104 °F) and the U.S. N.E.C. Other country, state or local codes may require different ratings.
Fusing
The recommended fuse types are listed below. If available current ratings do not match those listed in the tables provided, choose the next higher fuse rating.
• IEC – BS88 (British Standard) Parts 1 & 2(1), EN60269-1, Parts 1 & 2, type gG or equivalent should be used.
• UL – UL Class CC, T or J must be used.(2)
Circuit Breakers
The “non-fuse” listings in the following tables include inverse time circuit breakers, instantaneous trip circuit breakers (motor circuit protectors) and 140M self-protected combination motor controllers. If one of these is chosen as the desired protection method, the following requirements apply:
• IEC – Both types of circuit breakers and 140M self-protected combination motor controllers are acceptable for IEC installations.
• UL – Only inverse time circuit breakers and the specified 140M self-protected combination motor controllers are acceptable for UL installations.
For information on... See page
Drive, Fuse & Circuit Breaker Ratings 121
Specifications 122
Input Power Connections 128
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.
(2) Typical designations include; Type CC - KTK-R, FNQ-RType J - JKS, LPJType T - JJS, JJN
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 121
Appendix A Supplemental Drive Information
SpecificationsDrive Ratings
Catalog Number Output Ratings Input Ratings Branch Circuit Protection
kW (HP) Amps VoltageRange
kVA Amps Fuses 140M MotorProtectors(1)(2)
Contactors Min. Enclosure Volumes(3) (in.3)
45 °C 50 °C
200...240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22C-B012N103 2.2 (3.0) 12 12 180-265 6.5 15.5 20 140M-F8E-C16 100-C23 5098
22C-B017N103 3.7 (5.0) 17.5 17.5 180-265 8.8 21 30 140M-F8E-C25 100-C37 5098
22C-B024N103 5.5 (7.5) 24 24 180-265 10.9 26.1 35 140M-F8E-C32 100-C37 5098
22C-B033N103 7.5 (10) 33 33 180-265 14.4 34.6 45 140M-F8E-C45 100-C45 5098
22C-B049A103 11 (15) 49 49 180-265 21.3 51 70 – 100-C60 –
22C-B065A103 15 (20) 65 65 180-265 28.3 68 90 – 100-C85 –
22C-B075A103 18.5 (25) 75 75 180-265 32.5 78 100 – 100-D95 –
22C-B090A103 22 (30) 90 81 180-265 38.3 92 125 – 100-D110 –
22C-B120A103 30 (40) 120 120 180-265 51.6 124 175 – 100-D180 –
22C-B145A103 37 (50) 145 130 180-265 62.4 150 200 – 100-D180 –
380...480V AC – 3-Phase Input, 0...460V 3-Phase Output
22C-D6P0N103 2.2 (3.0) 6 6 340-528 6.3 7.5 10 140M-D8E-C10 100-C09 5098
22C-D010N103 4.0 (5.0) 10.5 10.5 340-528 10.9 13 20 140M-D8E-C16 100-C16 5098
22C-D012N103 5.5 (7.5) 12 12 340-528 11.9 14.2 20 140M-D8E-C16 100-C23 5098
22C-D017N103 7.5 (10) 17 17 340-528 15.3 18.4 25 140M-D8E-C20 100-C23 5098
22C-D022N103 11 (15) 22 22 340-528 19.2 23 30 140M-F8E-C32 100-C30 5098
22C-D030N103 15 (20) 30 27 340-528 25.8 31 40 140M-F8E-C32 100-C37 5098
22C-D038A103 18.5 (25) 38 38 340-528 33.3 40 50 140M-F8E-C45 100-C60 9086
22C-D045A103 22 (30) 45.5 45.5 340-528 39.1 47 60 – 100-C60 –
22C-D060A103 30 (40) 60 54 340-528 53.3 64 80 – 100-C85 –
22C-D072A103 37 (50) 72 72 340-528 60.7 73 100 – 100-C85 –
22C-D088A103 45 (60) 88 88 340-528 74.9 90 125 – 100-D110 –
22C-D105A103 55 (75) 105 105 340-528 89 107 150 – 100-D140 –
22C-D142A103 75 (100) 142 128 340-528 124.8 150 200 – 100-D180 –
22C-D170A103 90 (125) 170 170 340-528 142 170 250 – 100-D250 –
22C-D208A103 110 (150) 208 208 340-528 167 200 250 – 100-D250 –
22C-D260A103 132 (200) 260 260 340-528 196 235 300 – 100-D300 –
22C-D310A103 160 (250) 310 290 340-528 242 290 400 – 100-D420 –
22C-D370A103 200 (300) 370 370 340-528 304 365 500 – 100-D420 –
22C-D460A103 250 (350) 460 410 340-528 387 465 600 – 100-D630 –
(1) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings.
(2) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(3) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure.
122 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Supplemental Drive Information Appendix A
Agency Certification
Protection
Environment
Specification
Listed to UL508C and CAN/CSA-22.2
Certified to AS/NZS, 1997 Group 1, Class A
Marked for all applicable European DirectivesEMC Directive (2014/30/EU)
EN 61800-3Low Voltage Directive (2014/35/EU)
EN 61800-5-1
The drive is also designed to meet the appropriate portions of the following specifications:NFPA 70 - US National Electrical CodeNEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
Specification
Bus Overvoltage Trip: 200...240V AC Input: 405V DC bus voltage (equivalent to 290V AC incoming line)380...460V AC Input: 810V DC bus voltage(equivalent to 575V AC incoming line)
Bus Undervoltage Trip: 200...240V AC Input: 210V DC bus voltage (equivalent to 150V AC incoming line)380...480V AC Input: 390V DC bus voltage (equivalent to 275V AC incoming line)
Power Ride-Thru: 100 milliseconds
Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
Electronic Motor Overload Protection: Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A) (2). UL 508C File 29572.
Overcurrent: 180% hardware limit, 220% instantaneous fault
Ground Fault Trip: Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output
Specification
Altitude: 1000 m (3300 ft) max. without derating.Above 1000 m (3300 ft), derate 1% for every 100 m(328 ft) up to a maximum altitude of 2000 m (6600 ft).
Maximum Surrounding Air Temperature without derating:
IP20, Open Type:IP30, NEMA Type 1, UL Type 1:
–10...50 °C (14...122 °F)–10...45 °C (14...113 °F)
Cooling Method: Fan: All drive ratings
Storage Temperature:2.2 kW (3.0 HP) to 7.5 kW (10 HP):11 kW (15 HP) to 250 kW (350 (HP):
–40...85 °C (–40...185 °F)–40...70 °C (–40...158 °F)
UL®C US
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 123
Appendix A Supplemental Drive Information
Electrical
Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity: 0...95% non-condensing
Shock (operating): 15G peak for 11 ms duration (±1.0 ms)
Vibration (operating): 1G peak, 5...2000 Hz
Seismic Rating: Meets the seismic requirements of the 2003 International Building Code as specified by AC156.(1)
(1) Drives 75 kW (100 HP) and greater have not been tested.
Specification
Voltage Tolerance: 200...240V ±10%380...480V ±10%
Frequency Tolerance: 48...63 Hz
Input Phases: Three-phase input provides full rating.Single-phase operation provides 35% rated current.
Displacement Power Factor: 0.98 across entire speed range
Efficiency: 97.5% at rated amps, nominal line voltage
Maximum Short Circuit Rating: 100,000 Amps Symmetrical (Frame C Drives)200,000 Amps Symmetrical (Frame D–H Drives)
Actual Short Circuit Rating: Determined by AIC Rating of installed fuse/circuit breaker
Transistor Type: Isolated Gate Bipolar (IGBT)
Internal DC Bus Choke200-480V AC Input:380-480V AC Input:
11-37 kW (15-50 HP) Panel Mount Drives11-160 kW (15-250 HP) Panel Mount Drives
Internal AC Line Reactor380-480V AC Input: 200...250 kW (300...350 HP) Panel Mount Drives.
Specification
124 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Supplemental Drive Information Appendix A
Control
Control Inputs
Specification
Method: Sinusoidal PWM, Volts/Hertz
Carrier FrequencyFrames C and D:Frames E – H:
2...10 kHz, Drive rating based on 4 kHz2...8 kHz, Drive rating based on 4 kHz
Frequency AccuracyDigital Input:Analog Input:Analog Output:
Within ±0.05% of set output frequencyWithin 0.5% of maximum output frequency, 10-Bit resolution±2% of full scale, 10-Bit resolution
Speed Regulation –Open Loop with Slip Compensation: ±1% of base speed across a 60:1 speed range
Output Frequency: 0...320 Hz (programmable)
Stop Modes: Multiple programmable stop modes including –Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve.
Accel/Decel: Two independently programmable accel and decel times.Each time may be programmed from 0...600 seconds in 0.1 second increments.
Drive Overload: 110% Overload capability for up to 1 minute
Electronic Motor Overload Protection: Provides class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A) (2). UL 508C File 29572.
Specification
Digital Quantity: (3) Semi-programmable(4) Programmable
TypeSource Mode (SRC):Sink Mode (SNK):
18...24V = ON, 0...6V = OFF0...6V = ON, 18...24V = OFF
Analog Quantity: (1) Isolated, –10 to 10V or 4-20mA(1) Non-isolated, 0 to 10V or 4-20mA
SpecificationResolution:0 to 10V DC Analog:4-20mA Analog:External Pot:
10-bit100k ohm input impedance250 ohm input impedance1...10k ohm, 2 Watt minimum
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 125
Appendix A Supplemental Drive Information
Control Outputs
Keypad
Communication
Specification
Relay Quantity: (2) Programmable Form C
SpecificationResistive Rating:Inductive Rating:
3.0 A @ 30V DC, 3.0 A @ 125V, 3.0 A @ 240V AC0.5 A @ 30V DC, 0.5 A @ 125V, 0.5 A @ 240V AC
Optional Relay Card
Quantity: (6) Optional Programmable Form A(Not available for Frame C drives)
SpecificationResistive Rating:Inductive Rating:
0.1 A @ 30V DC Class II circuits, 3.0 A @ 125V, 3.0 A @ 240V AC0.1 A @ 30V DC Class II circuits, 3.0 A @ 125V 3.0 A @ 240V AC
Opto Quantity: (1) Programmable
Specification: 30V DC, 50 mA Non-inductive
Analog Quantity: (2) Non-Isolated, 0-10V or 4-20mA
SpecificationResolution:0 to 10V DC Analog:4-20mA Analog:
10-bit1k ohm minimum525 ohm maximum
Specification
Display: Integral 2 line by 16 character LCD with (5) LED Indicators
Language: English, Français, Español, Italiano, Deutsch, Português, Nederlands
Specification
Type: Serial (RS485)
Supported Protocols (Standard):
Drive Serial Interface (DSI)Modbus RTUMetasys N2P1 - Floor Level Network (FLN)
Supported Protocols (Optional):
BACnetDeviceNetEtherNet/IPPROFIBUS DPControlNetLonWorks
Software (Optional): Windows Based Pocket PC/Windows Mobile 2003
126 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Supplemental Drive Information Appendix A
PowerFlex 400 Watts Loss (Rated Load, Speed & PWM)
Voltage kW (HP) Panel Mount Watts Flange Mount Watts
Total External Internal Total
200-240V AC 2.2 (3.0) 146 119 28 146
3.7 (5.0) 207 174 33 207
5.5 (7.5) 266 228 39 266
7.5 (10) 359 315 44 359
11 (15) 488 – – –
15 (20) 650 – – –
18.5 (25) 734 – – –
22 (30) 778 – – –
30 (40) 1055 – – –
37 (50) 1200 – – –
380-480V AC 2.2 (3.0) 105 77 28 105
4.0 (5.0) 171 143 28 171
5.5 (7.5) 200 161 39 200
7.5 (10) 267 229 39 267
11 (15) 329 285 44 329
15 (20) 435 380 55 435
18.5 (25) 606 – – –
22 (30) 738 – – –
30 (40) 764 – – –
37 (50) 1019 – – –
45 (60) 1245 – – –
55 (75) 1487 – – –
75 (100) 2043 – – –
90 (125) 2617 – – –
110 (150) 3601 – – –
132 (200) 3711 – – –
160 (250) 4208 – – –
200 (300) 4916 – – –
250 (350) 6167 – – –
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 127
Appendix A Supplemental Drive Information
Input Power Connections Figure 16 - Frame C, D, and E Connections
Figure 17 - Frame F Connections
Note: Frames G and H do not support single-phase operation.
Input Protection
Three Phase Input
T
S
R
Input Protection
Single Phase Input
T
S
R
Input Protection
Three Phase Input
T
S
R
Input Protection
Single Phase Input
T
S
R
128 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix B
Accessories and Dimensions
Product Selection Table 19 - Catalog Number Description
22C – B 024 N 1 0 3Drive Dash Voltage Rating Rating Enclosure HIM Emission Class Comm Slot
Table 20 - PowerFlex 400 Drives
Drive Ratings Catalog Number FrameSize
Input Voltage Normal Duty Output Current (Amps)
kW HP 45°C 50°C
240V 50/60 Hz3-Phase
2.2 3.0 12 12 22C-B012N103 C
3.7 5.0 17.5 17.5 22C-B017N103 C
5.5 7.5 24 24 22C-B024N103 C
7.5 10 33 33 22C-B033N103 C
11 15 49 49 22C-B049A103 D
15 20 65 65 22C-B065A103 D
18.5 25 75 75 22C-B075A103 D
22 30 90 81 22C-B090A103 D
30 40 120 120 22C-B120A103 E
37 50 145 130 22C-B145A103 E
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 129
Appendix B Accessories and Dimensions
480V 50/60 Hz3-Phase
2.2 3.0 6 6 22C-D6P0N103 C
4.0 5.0 10.5 10.5 22C-D010N103 C
5.5 7.5 12 12 22C-D012N103 C
7.5 10 17 17 22C-D017N103 C
11 15 22 22 22C-D022N103 C
15 20 30 27 22C-D030N103 C
18.5 25 38 38 22C-D038A103 D
22 30 45.5 45.5 22C-D045A103 D
30 40 60 54 22C-D060A103 D
37 50 72 72 22C-D072A103 E
45 60 88 88 22C-D088A103 E
55 75 105 105 22C-D105A103 E
75 100 142 128 22C-D142A103 E
90 125 170 170 22C-D170A103 F
110 150 208 208 22C-D208A103 F
132 200 260 260 22C-D260A103 G
160 250 310 290 22C-D310A103 G
200 300 370 370 22C-D370A103 H
250 350 460 410 22C-D460A103 H
Table 21 - PowerFlex 400 Flange Mount Drives
Drive Ratings Catalog Number FrameSize
Input Voltage kW HP Output Current (Amps)
45°C 50°C
240V 50/60 Hz3-Phase
2.2 3 12A 12A 22C-B012F103 C
3.7 5 17.5A 17.5A 22C-B017F103 C
5.5 7.5 24A 24A 22C-B024F103 C
7.5 10 33A 33A 22C-B033F103 C
480V 50/60 Hz3-Phase
2.2 3 6.0A 6.0A 22C-D6P0F103 C
4.0 5 10A 10A 22C-D010F103 C
5.5 7.5 12A 12A 22C-D012F103 C
7.5 10 17A 17A 22C-D017F103 C
11 15 22A 22A 22C-D022F103(1)
(1) A DC bus inductor is required. See Table 25 for ordering information.
C
15 20 30A 27A 22C-D030F103(1) C
Table 20 - PowerFlex 400 Drives
Drive Ratings Catalog Number FrameSize
Input Voltage Normal Duty Output Current (Amps)
kW HP 45°C 50°C
130 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Table 22 - Bulletin 1321-3R Series Line Reactors – 200...240V, 60 Hz, 3-Phase
kW HP FundamentalAmps
MaximumContinuousAmps
Inductancemh
Watts Loss Catalog Number
IP00(Open Style)
IP11(NEMA Type 1)
3% Impedance
2.2 3.0 12 18 1.25 26 1321-3R12-A 1321-3RA12-A
3.7 5.0 18 27 0.8 36 1321-3R18-A 1321-3RA18-A
5.5 7.5 25 37.5 0.5 48 1321-3R25-A 1321-3RA25-A
7.5 10 35 52.5 0.4 49 1321-3R35-A 1321-3RA35-A
11 15 45 67.5 0.3 54 1321-3R45-A 1321-3RA45-A
15 20 55 82.5 0.25 64 1321-3R55-A 1321-3RA55-A
18.5 25 80 120 0.2 82 1321-3R80-A 1321-3RA80-A
22 30 80 120 0.2 82 1321-3R80-A 1321-3RA80-A
30 40 100 150 0.15 94 1321-3R100-A 1321-3RA100-A
37 50 130 195 0.1 108 1321-3R130-A 1321-3RA130-A
5% Impedance
2.2 3.0 12 18 2.5 31 1321-3R12-B 1321-3RA12-B
3.7 5.0 18 27 1.5 43 1321-3R18-B 1321-3RA18-B
5.5 7.5 25 37.5 1.2 52 1321-3R25-B 1321-3RA25-B
7.5 10 35 52.5 0.8 54 1321-3R35-B 1321-3RA35-B
11 15 45 67.5 0.7 62 1321-3R45-B 1321-3RA45-B
15 20 55 82.5 0.5 67 1321-3R55-B 1321-3RA55-B
18.5 25 80 120 0.4 86 1321-3R80-B 1321-3RA80-B
22 30 80 120 0.4 86 1321-3R80-B 1321-3RA80-B
30 40 100 150 0.3 84 1321-3R100-B 1321-3RA100-B
37 50 130 195 0.2 180 1321-3R130-B 1321-3RA130-B
Table 23 - Bulletin 1321-3R Series Line Reactors – 380...480V, 60 Hz, 3-Phase
kW HP FundamentalAmps
MaximumContinuousAmps
Inductance Watts Loss Catalog Number
IP00(Open Style)
IP11
3% Impedance
2.2 3.0 8 12 5 25.3 1321-3R8-C 1321-3RA8-C
4.0 5.0 12 18 2.5 31 1321-3R12-B 1321-3RA12-B
5.5 7.5 12 18 2.5 31 1321-3R12-B 1321-3RA12-B
7.5 10 18 27 1.5 43 1321-3R18-B 1321-3RA18-B
11 15 25 37.5 1.2 52 1321-3R25-B 1321-3RA25-B
15 20 35 52.5 0.8 54 1321-3R35-B 1321-3RA35-B
18.5 25 35 52.5 0.8 54 1321-3R35-B 1321-3RA35-B
22 30 45 67.5 0.7 62 1321-3R45-B 1321-3RA45-B
30 40 55 82.5 0.5 67 1321-3R55-B 1321-3RA55-B
37 50 80 120 0.4 86 1321-3R80-B 1321-3RA80-B
45 60 80 120 0.4 86 1321-3R80-B 1321-3RA80-B
55 75 100 150 0.3 84 1321-3R100-B 1321-3RA100-B
75 100 130 195 0.2 180 1321-3R130-B 1321-3RA130-B
90 125 160 240 0.15 149 1321-3R160-B 1321-3RA160-B
110 150 200 300 0.11 168 1321-3R200-B 1321-3RA200-B
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 131
Appendix B Accessories and Dimensions
132 200 250 375 0.09 231 1321-3R250-B 1321-3RA250-B
160 250 320 480 0.075 264 1321-3R320-B 1321-3RA320-B
200 300 400 560 0.06 333 1321-3R400-B 1321-3RA400-B
250 350 500 700 0.05 340 1321-3R500-B 1321-3RA500-B
5% Impedance
2.2 3.0 8 12 7.5 28 1321-3R8-D 1321-3RA8-D
4.0 5.0 12 18 4.2 41 1321-3R12-C 1321-3RA12-C
5.5 7.5 12 18 4.2 41 1321-3R12-C 1321-3RA12-C
7.5 10 18 27 2.5 43 1321-3R18-C 1321-3RA18-C
11 15 25 37.5 2.0 61 1321-3R25-C 1321-3RA25-C
15 20 35 52.5 1.2 54 1321-3R35-C 1321-3RA35-C
18.5 25 35 52.5 1.2 54 1321-3R35-C 1321-3RA35-C
22 30 45 67.5 1.2 65 1321-3R45-C 1321-3RA45-C
30 40 55 82.5 0.85 71 1321-3R55-C 1321-3RA55-C
37 50 80 120 0.7 96 1321-3R80-C 1321-3RA80-C
45 60 80 120 0.7 96 1321-3R80-C 1321-3RA80-C
55 75 100 150 0.45 108 1321-3R100-C 1321-3RA100-C
75 100 130 195 0.3 128 1321-3R130-C 1321-3RA130-C
90 125 160 240 0.23 138 1321-3R160-C 1321-3RA160-C
110 150 200 300 0.185 146 1321-3R200-C 1321-3RA200-C
132 200 250 375 0.15 219 1321-3R250-C 1321-3RA250-C
160 250 320 480 0.125 351 1321-3R320-C 1321-3RA320-C
200 300 400 560 0.105 293 1321-3R400-C 1321-3RA400-C
250 350 500 700 0.085 422 1321-3R500-C 1321-3RA500-C
Table 24 - Bulletin 1321 - DC Series Bus Inductors - 200...240V, 60 Hz, 3-Phase
kW HP DC Amps Inductancemh
Watts Loss Catalog NumberIP00 (Open Style)
2.2 3 12 0.92 5 1321-DC12-1
3.7 5 18 0.63 5 1321-DC18-1
5.5 7.5 32 0.85 11 1321-DC32-1
7.5 10 40 0.75 15 1321-DC40-2
Table 25 - Bulletin 1321 - DC Series Bus Inductors – 380...480V, 60 Hz, 3-Phase
kW HP DC Amps Inductancemh
Watts Loss Catalog NumberIP00 (Open Style)
2.2 3 9 3.68 7 1321-DC9-2
4.0 5 12 2.1 7 1321-DC12-2
5.5 7.5 18 3.75 17 1321-DC18-4
Table 23 - Bulletin 1321-3R Series Line Reactors – 380...480V, 60 Hz, 3-Phase
kW HP FundamentalAmps
MaximumContinuousAmps
Inductance Watts Loss Catalog Number
IP00(Open Style)
IP11
132 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
7.5 10 25 1.75 13 1321-DC25-4
11 15 32 2.68 21 1321-DC32-2(1)
15 20 40 2.0 29 1321-DC40-4(1)
(1) Required on 11 and 15 kW (15 and 20 HP) Frame C Flange Mount drive ratings.
Table 26 - EMC Line Filters
Drive Ratings Catalog Number
Input Voltage kW HP
240V 50/60 Hz 3-Phase 2.2 3.0 22-RF034-CS
4.0 5.0 22-RF034-CS
5.5 7.5 22-RF034-CS
7.5 10 22-RF034-CS
11 15 22-RFD070
15 20 22-RFD100
18.5 25 22-RFD100
22 30 22-RFD150
30 40 22-RFD150
37 50 22-RFD180
480V 50/60 Hz 3-Phase 2.2 3.0 22-RF018-CS
4.0 5.0 22-RF018-CS
5.5 7.5 22-RF018-CS
7.5 10 22-RF018-CS
11 15 22-RF026-CS
15 20 22-RFD036
18.5 25 22-RFD050
22 30 22-RFD050
30 40 22-RFD070
37 50 22-RFD100
45 60 22-RFD100
55 75 22-RFD150
75 100 22-RFD180
90 125 22-RFD208
110 150 22-RFD208
132 200 22-RFD323
160 250 22-RFD480
200 300 22-RFD480
250 350 22-RFD480
Table 25 - Bulletin 1321 - DC Series Bus Inductors – 380...480V, 60 Hz, 3-Phase
kW HP DC Amps Inductancemh
Watts Loss Catalog NumberIP00 (Open Style)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 133
Appendix B Accessories and Dimensions
Table 27 - Communication Option Kits and Accessories
Item Description Catalog Number
BACnet® MS/TP RS-485 Communication Adapter
Embedded communication options for use with the PowerFlex family of drives.Requires a Communication Adapter Cover when used with Frame C PowerFlex 400 drives (Ordered Separately).
22-COMM-B
ControlNet™ Communication Adapter
22-COMM-C
DeviceNet™ Communication Adapter
22-COMM-D
EtherNet/IP™ Communication Adapter
22-COMM-E
LonWorks™ Communication Adapter
22-COMM-L
PROFIBUS™ DP Communication Adapter
22-COMM-P
External DSI™ Communications Kit
External mounting kit for 22-COMM communication adapter options.
22-XCOMMDC-BASE
External Comms Power Supply
Optional 100-240V AC Power Supply for External DSI Communications Kit.
20-XCOMMAC-PS1
Compact I/O Module 3 Channel. 1769-SM2
Communication Adapter Cover
Cover that houses the communication adapter.Frame C Drive
22C-CCC
DSI Cable 2.0 meter RJ45 to RJ45 cable, male to male connectors. 22-RJ45CBL-C20
Serial Cable 2.0 meter serial cable with a locking low profile connector to connect to the serial converter and a 9-pin sub-miniature D female connector to connect to a computer.
1203-SFC
Serial Null Cable Converter For use when connecting the serial converter to DriveExplorer on a handheld PC.
1203-SNM
Universal Serial Bus™ (USB) Converter
Includes 2m USB, 20-HIM-H10 & 22-HIM-H10 cables. 1203-USB
Splitter Cable RJ45 one to two port splitter cable AK-U0-RJ45-SC1
Terminating Resistors RJ45 120 Ohm resistors (2 pieces) AK-U0-RJ45-TR1
Terminal Block RJ45 Two position terminal block (5 pieces) AK-U0-RJ45-TB2P
Connected Components Workbench Software (Download or DVD-ROM)
Windows based software packages for programming and configuring Allen-Bradley drives and other Rockwell Automation products.Compatibility:
Windows XP, 7 Professional (Service Pack 1, 32-bit) and Vista (Service Pack 1 and 2, 32-bit).
http://www.rockwellautomation.com/global/support/connected-components/workbench.page?
DriveExecutive software (CD-ROM) Version 1.01 or later
Windows based software package that provides an intuitive means for monitoring or configuring Allen-Bradley drives and communication adapters online and offline.Compatibility:
Windows 98, ME, NT 4.0 (Service Pack 3 or later), 2000, XP, 7 Professional (Service Pack 1, 32-bit), and Vista (Service Pack 1 and 2, 32-bit).
9303-4DTE01ENE
Serial Flash Firmware Kit Use a PC to update drive firmware. AK-U9-FLSH1
134 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Table 28 - Human Interface Module (HIM) Option Kits and Accessories
Item Description Catalog Number
LCD Display,Remote Panel Mount
LCD DisplayDigital Speed ControlCopyCat CapableIP66 indoor use onlyIncludes 2.0 meter cable
22-HIM-C2S
LCD Display,Remote Handheld
LCD DisplayDigital Speed ControlFull Numeric KeypadCopyCat CapableIP30Includes 1.0 meter cablePanel Mount with optional Bezel Kit
22-HIM-A3
Bezel Kit Panel mount for LCD Display, Remote Handheld unit, IP30 22-HIM-B1
DSI HIM Cable(DSI HIM to RJ45 cable)
1.0 Meter (3.3 Feet)2.9 Meter (9.51 Feet)
22-HIM-H1022-HIM-H30
Table 29 - Frame C IP30 Kit
Item Description DriveFrame
CatalogNumber
IP30/NEMA 1/UL Type 1 Kit
Field installed kit. Converts drive to IP30/ NEMA 1/UL Type 1 enclosure. Includes conduit box with mounting screws and plastic top panel.
C 22-JBAC
IP30/NEMA 1/UL Type 1 Kit for Communication Option
Field installed kit. Converts drive to IP30/ NEMA 1/UL Type 1 enclosure. Includes communication option conduit box with mounting screws and plastic top panel.
C 22-JBCC
Table 30 - Field Installed Option
Item Description Catalog Number
Auxiliary Relay Board Field installed kit. Expands drive output capabilities. AK-U9-RLB1
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 135
Appendix B Accessories and Dimensions
Product Dimensions Table 31 - PowerFlex 400 Frames and Weights
Frame kW (HP) Drive Weightkg (lbs.)
Packaged Weightkg (lbs.)
240V AC – 3-Phase
C 2.2 (3.0) 2.89 (6.4) 3.41 (7.5)
C 4.0 (5.0) 2.97 (6.5) 3.49 (7.7)
C 5.5 (7.5) 3.72 (8.2) 4.27 (9.4)
C 7.5 (10) 3.78 (8.3) 4.33 (9.5)
D 11 (15) 12.1 (26.7) 13.4 (29.5)
D 15 (20) 12.7 (28.0) 14 (30.9)
D 18.5 (25) 12.7 (28.0) 14 (30.9)
D 22 (30) 12.7 (28.0) 14 (30.9)
E 30 (40) 38 (83.8) 48.2 (106.3)
E 37 (50) 38 (83.8) 48.2 (106.3)
480V AC – 3-Phase
C 2.2 (3.0) 2.87 (6.3) 3.39 (7.5)
C 4.0 (5.0) 3.03 (6.7) 3.55 (7.8)
C 5.5 (7.5) 3.65 (8.0) 4.2 (9.3)
C 7.5 (10) 3.75 (8.3) 4.3 (9.5)
C 11 (15) 6.41 (14.1) 7.41 (16.3)
C 15 (20) 6.47 (14.3) 7.49 (16.5)
D 18.5 (25) 12.7 (28.0) 14 (30.9)
D 22 (30) 12.7 (28.0) 14 (30.9)
D 30 (40) 14.3 (31.5) 15.6 (34.4)
E 37 (50) 36 (79.4) 46.2 (101.9)
E 45 (60) 36 (79.4) 46.2 (101.9)
E 55 (75) 41 (90.4) 51.2 (112.9)
E 75 (100) 41 (90.4) 51.2 (112.9)
F 90 (125) 78 (172.0) 88 (194.0)
F 110 (150) 78 (172.0) 88 (194.0)
G 132 (200) 89 (196.2) 106 (233.7)
G 160 (250) 89 (196.2) 106 (233.7)
H 200 (300) 157 (346.1) 177 (390.2)
H 250 (350) 157 (346.1) 177 (390.2)
240V AC – 3-Phase, Plate Drive
C 2.2 (3.0) 2.66 (5.9) 3.26 (7.2)
C 4.0 (5.0) 2.74 (6.0) 3.34 (7.4)
C 5.5 (7.5) 3.15 (6.9) 3.75 (8.3)
C 7.5 (10) 3.21 (7.1) 3.81 (8.4)
480V AC – 3-Phase, Plate Drive
C 2.2 (3.0) 2.63 (5.8) 3.23 (7.1)
136 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
C 4.0 (5.0) 2.77 (6.1) 3.37 (7.4)
C 5.5 (7.5) 3.04 (6.7) 3.64 (8.0)
C 7.5 (10) 3.13 (6.9) 3.73 (8.2)
C 11 (15) 3.19 (7.0) 3.79 (8.4)
Table 31 - PowerFlex 400 Frames and Weights
Frame kW (HP) Drive Weightkg (lbs.)
Packaged Weightkg (lbs.)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 137
Appendix B Accessories and Dimensions
Figure 18 - PowerFlex 400 Frame C Drive
260(10.2)
320(12.6)
246(9.7)
130.0 (5.1)
116.0 (4.57)
111.2(4.38)
152.2(5.99)
∅ 22.2 (0.87)
∅ 28.5 (1.12)
107.0 (4.21)66.0 (2.60)
24.0 (0.94)
180.0 (7.1)
Dimensions are in millimeters and (inches)
138 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Figure 19 - PowerFlex 400 Frame D Drive
Dimensions are in millimeters and (inches)
226.0 (8.90)250.0 (9.84)
206.1 (8.11)
383.4(15.09)
436.2(17.17)
71.6 (2.82)
132.0 (5.20)
175.5 (6.91)
192.0 (7.56)
156.3(6.15)
132.7(5.22)
167.4(6.59)
∅ 22.2 (0.87)
∅ 42.0 (1.65)
∅ 9.0 (0.35)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 139
Appendix B Accessories and Dimensions
Figure 20 - PowerFlex 400 Frame E Drive
Dimensions are in millimeters and (inches)
130.2 (5.13)
240.2 (9.46)
315.2 (12.41)
55.2 (2.17)
174.9(6.89)
234.9(9.25)
204.9(8.07)
∅ 22.2 (0.87)
∅ 62.7 (2.47)
567.4(22.34)
605.5(23.84)
335.0 (13.19)
370.0 (14.57) 259.2 (10.21)∅ 8.5 (0.33)
140 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Figure 21 - PowerFlex 400 Frame F Drive
Dimensions are in millimeters and (inches)
137.5 (5.41)
287.5 (11.32)
370.0 (14.57)
55.0 (2.17)
169.0(6.65)
228.5(9.00)
199.0(7.83)
∅ 74.8 (2.94)
∅ 22.0 (0.87)
381.0 (15.00)
381.0 (15.00)
425.0 (16.73)
∅ 13.0 (0.51)
850.0(33.46)
678.0(26.69)
647.5(25.49)
264.0 (10.39)
165.8 (6.53)
280.0 (11.02)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 141
Appendix B Accessories and Dimensions
Figure 22 - PowerFlex 400 Frame G Drive
Dimensions are in millimeters and (inches)
425.0 (16.73)
381.0 (15.00)264.0 (10.39)
892.0(35.12)
819.5(32.26)
57.5 (2.26)
122.5 (4.82)
302.5 (11.91)
367.5 (14.47)
199.6(7.85)
244.6(9.62)
22.0 (0.87)
92.0 (3.62)
142 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Figure 23 - PowerFlex 400 Frame H Drive
Dimensions are in millimeters and (inches)
529.2 (20.83)
1363.8(53.69)
480.0 (18.90)
1119.0(44.06)
358.6 (14.12)
115.5 (4.55)
39.6 (1.56)
413.7 (16.29)
489.6 (19.28)
255.2(10.05)
310.2(12.21)
22.3 (0.88)
117.5 (4.63)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 143
Appendix B Accessories and Dimensions
Figure 24 - PowerFlex 400 Frame C Flange Mount Drive
Dimensions are in millimeters and (inches)
138.2(5.44)
105.8(4.17)
325(12.8)
300(11.81)
130.3(5.13)
22B-CCC
291.5(11.48)
164(6.46)
180(7.09)
90(3.54)
307.5(12.11)
230.6(9.08)
153.8(6.06)
76.9(3.03)
8(0.31)
8(0.31)
5.3(0.21)
Cutout Dimensions
144 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Figure 25 - Bulletin 1321-3R Series Line Reactors
Catalog Number A B C D E Weight
1321-3R8-C 152 (6.00) 122 (4.80) 86 (3.40) 67 (2.62) 51 (2.00) 5.0 (11)
1321-3R8-D 152 (6.00) 122 (4.80) 86 (3.40) 63 (2.48) 51 (2.00) 5.9 (13)
1321-3R12-A 152 (6.00) 127 (5.00) 84 (3.30) 53 (2.10) 51 (2.00) 4.1 (9)
1321-3R12-B 152 (6.00) 127 (5.00) 76 (3.00) 53 (2.10) 51 (2.00) 4.5 (10)
1321-3R12-C 152 (6.00) 127 (5.00) 91 (3.60) 69 (2.73) 51 (2.00) 8.2 (18)
1321-3R18-B 152 (6.00) 135 (5.30) 89 (3.50) 63 (2.48) 51 (2.00) 5.5 (12)
1321-3R18-C 183 (7.20) 146 (5.76) 92 (3.63) 66 (2.60) 76 (3.00) 7.3 (16)
1321-3R25-A 183 (7.20) 146 (5.76) 85 (3.35) 60 (2.35) 76 (3.00) 4.9 (11)
1321-3R25-B 183 (7.20) 146 (5.76) 85 (3.35) 60 (2.35) 76 (3.00) 6.3 (14)
1321-3R25-C 183 (7.20) 146 (5.76) 105 (4.10) 79 (3.10) 76 (3.00) 8.1 (18)
1321-3R35-A 193 (7.60) 146 (5.76) 91 (3.60) 66 (2.60) 76 (3.00) 6.3 (14)
1321-3R35-B 183 (7.20) 147 (5.80) 95 (3.75) 79 (3.10) 76 (3.00) 7.3 (16)
1321-3R35-C 229 (9.00) 187 (7.35) 118 (4.66) 80 (3.16) 76 (3.00) 13.6 (30)
1321-3R45-A 229 (9.00) 187 (7.35) 118 (4.66) 80 (3.16) 76 (3.00) 10.4 (23)
1321-3R45-B 229 (9.00) 184 (7.25) 118 (4.66) 80 (3.16) 76 (3.00) 12.7 (28)
1321-3R45-C 229 (9.00) 187 (7.35) 135 (5.30) 93 (3.66) 76 (3.00) 17.7 (39)
1321-3R55-A 229 (9.00) 187 (7.35) 118 (4.66) 80 (3.16) 76 (3.00) 10.9 (24)
1321-3R55-B 229 (9.00) 187 (7.35) 118 (4.66) 80 (3.16) 76 (3.00) 12.3 (27)
1321-3R55-C 229 (9.00) 184 (7.25) 142 (5.60) 99 (3.90) 76 (3.00) 18.6 (41)
1321-3R80-A 274 (10.80) 216 (8.50) 139 (5.47) 88 (3.47) 92 (3.63) 19.5 (43)
1321-3R80-B 274 (10.80) 216 (8.50) 139 (5.47) 88 (3.47) 92 (3.63) 23.1 (51)
1321-3R80-C 274 (10.80) 210 (8.26) 156 (6.16) 106 (4.16) 92 (3.63) 25.0 (55)
1321-3R100-A 274 (10.80) 217 (8.55) 139 (5.48) 84 (3.30) 92 (3.63) 21.3 (47)
1321-3R100-B 274 (10.80) 210 (8.26) 144 (5.66) 93 (3.66) 92 (3.63) 23.1 (51)
1321-3R100-C 274 (10.80) 210 (8.26) 156 (6.16) 106 (4.16) 92 (3.63) 33.6 (74)
1321-3R130-A 229 (9.00) 179 (7.04) 118 (4.66) 80 (3.16) 76 (3.00) 13.2 (29)
1321-3R130-B 274 (10.80) 213 (8.40) 144 (5.66) 93 (3.66) 92 (3.63) 25.9 (57)
1321-3R130-C 279 (11.00) 216 (8.50) 156 (6.16) 106 (4.16) 92 (3.63) 29.0 (64)
DC
BA
E
A1 A2B1 B2
C1 C2
BA
E DC
IP00 (Open) –45 Amps (fundamental) and Below
IP00 (Open) –55 Amps (fundamental) and Above
Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 145
Appendix B Accessories and Dimensions
Figure 26 - Bulletin 1321-DC Series Bus Inductors
1321-3R160-A 274 (10.80) 216 (8.50) 172 (6.80) 80 (3.16) 92 (3.63) 19.0 (42)
1321-3R160-B 279 (11.00) 216 (8.50) 178 (7.00) 88 (3.47) 92 (3.63) 23.0 (51)
1321-3R160-C 287 (11.30) 216 (8.50) 229 (9.00) 118 (4.66) 92 (3.63) 33.0 (72)
1321-3R200-B 274 (10.80) 216 (8.50) 210 (8.30) 112 (4.41) 92 (3.63) 31.0 (67)
1321-3R200-C 274 (10.80) 216 (8.50) 254 (10.00) 150 (5.91) 92 (3.63) 46.0 (100)
1321-3R250-B 366 (14.40) 292 (11.50) 292 (11.50) 192 (7.56) 117 (4.60) 53.5 (118)
1321-3R250-C 366 (14.40) 286 (11.25) 260 (10.25) 167 (6.56) 117 (4.60) 57.0 (125)
1321-3R320-B 274 (10.80) 229 (9.00) 254 (10.00) 165 (6.50) 92 (3.63) 46.3 (102)
1321-3R320-C 366 (14.40) 286 (11.25) 267 (10.50) 192 (7.56) 117 (4.60) 72.6 (160)
1321-3R400-B 381 (15.00) 286 (11.25) 292 (11.50) 179 (7.06) 117 (4.60) 53.5 (118)
1321-3R400-C 366 (14.40) 286 (11.25) 318 (12.50) 192 (7.56) 117 (4.60) 67.6 (149)
1321-3R500-B 366 (14.40) 292 (11.50) 292 (11.50) 192 (7.56) 117 (4.60) 53.5 (118)
1321-3R500-C 366 (14.40) 286 (11.25) 254 (10.00) 141 (5.56) 117 (4.60) 54.4 (120)
CatalogNumber
Model A B C D E F Weight
1321-DC9-2 A 95 (3.75) 83 (3.25) 51 (2.00) – 80 (3.13) 4.7 (0.19)
1321-DC12-1 A 95 (3.75) 83 (3.25) 44 (1.75) – 80 (3.13) 4.7 (0.19)
1321-DC12-2 B 97 (3.81) 114 (4.50) 72 (2.82) 51 (2.00) 80 (3.13) 5x8 (.20x.33) 5.9 (13.0)
1321-DC18-1 A 95 (3.75) 83 (3.25) 51 (2.00) – 80 (3.13) 4.7 (0.19)
1321-DC18-4 B 118 (4.63) 133 (5.25) 102 (4.00) 64 (2.50) 95 (3.75) 5x8 (.20x.33) 3.6 (8.0)
1321-DC25-4 B 97 (3.81) 114 (4.50) 76 (3.00) 64 (2.50) 80 (3.13) 5x8 (.20x.33) 5.9 (13.0)
1321-DC32-1 B 97 (3.81) 114 (4.50) 84 (3.32) 64 (2.50) 80 (3.13) 5x8 (.20x.33) 2.3 (5.0)
1321-DC32-2 B 118 (4.63) 133 (5.25) 108 (4.25) 76 (3.00) 95 (3.75) 5x8 (.20x.33) 4.5 (10.0)
1321-DC40-2 B 97 (3.81) 114 (4.50) 95 (3.75) 76 (3.00) 80 (3.13) 5x8 (.20x.33) 3.2 (7.0)
1321-DC40-4 B 165 (6.50) 166 (6.55) 152 (6.00) 86 (3.38) 135 (5.31) 7x13 (.28x.52) 9.5 (21.0)
Catalog Number A B C D E Weight
A C
E D
B
FA CE
B
F
Model A Model B
Dimensions are in millimeters and (inches). Weights are in kilograms and (pounds).
146 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Figure 27 - EMC Line Filters
CatalogNumber
A B C D E F G
22-RFD036 74 (2.91) 272 (10.71) 161 (6.34) 60 (2.36) 258 (10.16) 7.5 (0.30) 7 (0.28)
22-RFD050 93 (3.66) 312 (12.28) 190 (7.48) 79 (3.11) 298 (11.73) 13.5 (0.53) 7 (0.28)
22-RFD070 93 (3.66) 312 (12.28) 190 (7.48) 79 (3.11) 298 (11.73) 13.5 (0.53) 7 (0.28)
22-RFD100 93 (3.66) 312 (12.28) 190 (7.48) 79 (3.11) 298 (11.73) 13.5 (0.53) 7 (0.28)
22-RFD150 126 (4.96) 312 (12.28) 224 (8.82) 112 (4.41) 298 (11.73) 19.5 (0.77) 7 (0.28)
22-RFD180 126 (4.96) 312 (12.28) 224 (8.82) 112 (4.41) 298 (11.73) 27 (1.06) 7 (0.28)
5.5 (0.22)17(0.67) 30
(1.18)
90(3.54)
130(5.12)
60(2.36)
32(1.26)
309(12.17)
297(11.69)
297(11.69)
B
E
AD C
F
G
Dimensions are in millimeters and (inches)
Catalog Numbers: 22-RF018-CS, 22-RF018-CL, 22-RF026-CS, 22-RF026-CL, 22-RF034-CS
Catalog Numbers: 22-RFD036, 22-RFD050, 22-RFD070, 22-RFD100, 22-RFD150, 22-RFD180
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 147
Appendix B Accessories and Dimensions
Catalog Number: 22-RFD208
938(36.93)
900(35.43) 913
(35.94)
1000(39.37)
110(4.33)
300(11.81)
80(3.15)
6.5(0.26)
M10
M10
148 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
CatalogNumber
A B C D E F G
22-RFD323 300 (11.81) 735 (28.94) 145 (5.71) 275 (10.83) 689 (27.13) 64 (2.52) 180 (7.09)
22-RFD480 300 (11.81) 882 (34.72) 145 (5.71) 275 (10.83) 836 (32.91) 64 (2.52) 240 (9.45)
aa
aaM11
Ø 10.8(0.43)
45°
A
D
C
F
250(11.81)
25(0.98)
60(2.36)
60(2.36)
10(0.39)
50(1.97)
12.5(0.49)
6(0.24)
G
G
G
EB
M12
ø 9(0.35)
x 8
3(0.12)
64(2.52)
18(0.71)
Catalog Numbers: 22-RFD323 and 22-RFD480
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 149
Appendix B Accessories and Dimensions
Figure 28 - Remote (Panel Mount) Small HIM
Dimensions are in millimeters and (inches)
Catalog Number: 22-HIM-C2S
93(3.66)
25(0.98)
2m
180(7.09)
154(6.06)
77(3.03)
23.5(0.93)
67(2.64)
60(2.36)
19.1(0.75)
4.8(0.19)
150 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Accessories and Dimensions Appendix B
Figure 29 - NEMA Type 1 Bezel
Dimensions are in millimeters and (inches)
Catalog Number: 22-HIM-B1
93(3.66)25.2
(0.99)
2m
180(7.09)
11.1(0.44)
19.1(0.75)
4.8(0.19)
154(6.06)
77(3.03)
23.5(0.93)
67(2.64)
60(2.36)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 151
Appendix B Accessories and Dimensions
Notes:
152 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix C
RJ45 DSI Splitter Cable
The PowerFlex 400 drive provides a RJ45 port to allow the connection of a single peripheral device. The RJ45 DSI Splitter Cable can be used to connect a second DSI peripheral device to the drive.
Connectivity Guidelines
• Two peripherals maximum can be attached to a drive.• If a single peripheral is used, it must be connected to the Master port
(M) on the splitter and configured for “Auto” (default) or “Master.” Parameter 9 [Device Type] on the DSI keypads and Parameter 1 [Adapter Cfg] on the Serial Converter are used to select the type(Auto / Master / Slave).
• Do not use the RJ45 Splitter Cable with a drive that has an internal network communication adapter installed. Since only one additional peripheral can be added, the second peripheral can be connected directly to the RJ45 port on the drive. The internal Comm is always the Master, therefore the external peripheral must be configured as “Auto” (for temporary connections) or “Slave” (for permanent connections).
• If two peripherals will be powered up at the same time, one must be configured as the “Master” and connected to the Master port (M) and the other must be connected as the “Slave” and connected to the Slave port (S).
DSI Cable Accessories Figure 30 - RJ45 Splitter Cable
ATTENTION: Risk of injury or equipment damage exists. The peripherals may not perform as intended if these Connectivity Guidelines are not followed. Precautions should be taken to follow these Connectivity Guidelines.
Slave Port
Master Port
PIN 8PIN 1
MS
Catalog Number: AK-U0-RJ45-SC1
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 153
Appendix C RJ45 DSI Splitter Cable
Figure 31 - RJ45 Two-Position Terminal Block Adapter
Figure 32 - RJ45 Adapter with Integrated Termination Resistor
Connectivity Examples Figure 33 - Connecting One Temporary Peripheral
Catalog Number: AK-U0-RJ45-TB2P
TB2(PIN 5)
TB1(PIN 4)
PIN 8
PIN 1
Catalog Number: AK-U0-RJ45-TR1
PIN 8
PIN 1
M
S
Serial Converter
Parameter 1 [Adapter Cfg] set to "Auto" (default) or "Master" and connected to Master port (M) on RJ45 Splitter Cable
DSI
DSI Hand Held
or
Parameter 9 [Device Type] set to "Auto" (default) or "Master" and connected to Master port (M) on RJ45 Splitter Cable
DSI Drive
154 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
RJ45 DSI Splitter Cable Appendix C
Figure 34 - Connecting One Temporary Peripheral and One Permanent Peripheral
Figure 35 - Connecting Two Permanent Peripherals
Serial Converter
NEMA 4 Panel Mount Unit
or
NEMA 1 Bezel with DSI Hand Held
Parameter 9 [Device Type] set to "Master" and
connected to Master port (M)on RJ45 Splitter Cable
Parameter 1 [Adapter Cfg] set to "Auto" (default) or
"Slave" and connected to Slave port (S)
on RJ45 Splitter Cable
DSI
M
S
DSI Drive
or
NEMA 1 Bezel with DSI Hand Held
NEMA 4Panel Mount Unit
Parameter 9 [Device Type] set to "Master" and connected to Master
port (M) on RJ45 Splitter Cable
Parameter 9 [Device Type] set to "Slave" and
connected to Slave port (S) on RJ45 Splitter Cable
M
S
DSI Drive
or
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 155
Appendix C RJ45 DSI Splitter Cable
Figure 36 - Connecting an RS-485 Network
AK-U0-RJ45-TR1 Terminating Resistor
(end of network)
AK-U0-RJ45-TB2P Two-position
Terminal Block
DSI Drives
or or
Customer supplied RJ45 male-to-RJ45 male cables with wires connected at pins 4 and 5 only.
Both the Master (M) and Slave (S) ports on the RJ45 Splitter Cable operate as standard RS-485 ports in this configuration.
156 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix D
Application Notes
Damper Control Setup The PowerFlex 400 allows damper control logic to be imbedded within the drive reducing cost associated with external control hardware and software. A system Run command can be wired directly into one of the drive inputs. Relay outputs can be used to energize the damper to either open or close. A damper limit switch can be wired back to the drive providing indication that the damper is in the proper position and that it is safe for the drive to run at commanded speed.
Example• The System Run Command can come from a terminal block, integral
keypad, or communication port. Configure parameter P036 [Start Source] per application requirements.
• Set one of the available digital inputs, parameter T051...T054 [Digital Inx Sel] to option 36 “Damper Input”. The damper end switch or limit switch should be wired into this input.
• Set one of the available relay outputs, parameter T055/T060 [Relay Outx Sel] to option 2 “Motor Running”. This output should be used to energize the damper to either open or close.
PID Setup PID Control Loop
The PowerFlex 400 has a built-in PID (proportional, integral, differential) control loop. The PID loop is used to maintain a process feedback (such as pressure, flow or tension) at a desired set point. The PID loop works by subtracting the PID feedback from a reference and generating an error value. The PID loop reacts to the error, based on the PID Gains, and outputs a frequency to try to reduce the error value to 0. To enable the PID loop, parameter A152 [PID Ref Sel] must be set to an option other than 0 “PID Disabled”.
Supply Fan
Air Flow
Damper Limit Switch
Damper Position CommandSystem Run Command
Outside AirDamper
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 157
Appendix D Application Notes
Exclusive Control and Trim Control are two basic configurations where the PID loop may be used.
Exclusive Control
In Exclusive Control, the Speed Reference becomes 0, and the PID Output becomes the entire Freq Command. Exclusive Control is used when A152 [PID Ref Sel] is set to option 1, 2, 3 or 4. This configuration does not require a master reference, only a desired set point, such as a flow rate for a pump.
Example• In a pumping application, the PID Reference equals the Desired System
Pressure set point.• The Pressure Transducer signal provides PID Feedback to the drive.
Fluctuations in actual system pressure, due to changes in flow, result in a PID Error value.
• The drive output frequency increases or decreases to vary motor shaft speed to correct for the PID Error value.
• The Desired System Pressure set point is maintained as valves in the system are opened and closed causing changes in flow.
• When the PID Control Loop is disabled, the Commanded Speed is the Ramped Speed Reference.
–+
PID Prop Gain
PID Loop
PID Integ Time
PID Diff RatePID Enabled
PID Fdbk
PID RefPIDError +
+
+
PIDOutput Accel/Decel
RampFreq
Command
Pump
PID Feedback =Pressure Transducer Signal
PID Reference =Desired System Pressure
158 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Application Notes Appendix D
Trim Control
In Trim Control, the PID Output is added to the Speed Reference. In Trim mode, the output of the PID loop bypasses the accel/decel ramp as shown. Trim Control is used when A152 [PID Ref Sel] is set to option 5, 6, 7 or 8.
Example• In a winder application, the PID Reference equals the Equilibrium
set point.• The Dancer Pot signal provides PID Feedback to the drive.
Fluctuations in tension result in a PID Error value.• The Master Speed Reference sets the wind/unwind speed.• As tension increases or decreases during winding, the Speed Reference is
trimmed to compensate. Tension is maintained near the Equilibriumset point.
PID Reference and Feedback
Parameter A152 [PID Ref Sel] is used to enable the PID mode (A152 = 0 “PID Disabled”) and to select the source of the PID Reference. If A152 [PID Ref Sel] is not set to 0 “PID Disabled”, PID can still be disabled by select programmable digital input options (parameters T051...T054) such as “Local” or “PID Disable”.
–+
PID Prop Gain
PID Loop
PID Integ Time
PID Diff RatePID Enabled
Speed Ref
PID Fdbk
PID RefPIDError +
+
+
+
PIDOutput Output
Freq
+
Accel/DecelRamp
Speed Reference
0 Volts
PID Feedback =Dancer Pot Signal
10 Volts
PID Reference =Equilibrium Set Point
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 159
Appendix D Application Notes
A153 [PID Feedback Sel] is used to select the source of the PID feedback.
Table 32 - A152 [PID Ref Sel] Options
Option Description
0 “PID Disabled” Disables the PID loop (default setting)
1 “PID Setpoint“ Selects Exclusive Control. <A157> [PID Setpoint] will be used to set the value of the PID Reference.
2 “Analog In 1” Selects Exclusive Control. Selects the Analog In 1 Input.
3 “Analog In 2” Selects Exclusive Control. Selects the Analog In 2 Input. Note that the PID will not function with a bipolar analog input. It will ignore any negative voltages and treat them like a zero.
4 “Comm Port” Selects Exclusive Control. The reference word from a communication network (see Appendix C for details on the reference word) such as Modbus RTU or DeviceNet becomes the PID Reference. The value sent over the network is scaled so that P035 [Maximum Freq] x 10 = 100% reference. For example, with [Maximum Freq] = 60 Hz, a value of 600 sent over the network would represent 100% reference.
5 “Setpnt, Trim” Selects Trim Control. A157 [PID Setpoint] will be used to set the value of the PID Reference.
6 “0-10V, Trim” Selects Trim Control. Selects the 0-10V Input. Note that the PID will not function with a bipolar analog input. It will ignore any negative voltages and treat them like a zero.
7 “4-20mA, Trim” Selects Trim Control. Selects the 4-20mA Input.
8 “Comm, Trim” Selects Trim Control. The reference word from a communication network (see Appendix C for details on the reference word) such as Modbus RTU or DeviceNet becomes the PID Reference. The value sent over the network is scaled so that P035 [Maximum Freq] x 10 = 100% reference. For example, with [Maximum Freq] = 60 Hz, a value of 600 sent over the network would represent 100% reference.
Table 33 - A153 [PID Feedback Sel] Options
Option Description
0 “Analog In 1” Selects the Analog In 1 Input (default setting).
1 “Analog In 2“ Selects the Analog In 2 Input. Note that the PID will not function with a bipolar analog input. It will ignore any negative voltages and treat them like a zero.
2 “Comm Port” The reference word from a communication network (see Appendix E for details on the reference word) such as Modbus RTU or DeviceNet becomes the PID Feedback. The value sent over the network is scaled so that P035 [Maximum Freq] x 10 = 100% Feedback. For example, with [Maximum Freq] = 60 Hz, a value of 600 sent over the network would represent 100% Feedback.
3 “ACT1 - ACT2” Selects actual inputs A204 [ACT1 Input] minus A205 [ACT2 Input] to be used as the feedback signal.
4 “ACT1 + ACT2” Selects actual inputs A204 [ACT1 Input] plus A205 [ACT2 Input] to be used as the feedback signal.
5 “ACT1 * ACT2” Selects actual inputs A204 [ACT1 Input] multiplied by A205 [ACT2 Input] to be used as the feedback signal.
6 “ACT1 / ACT2” Selects actual inputs A204 [ACT1 Input] divided by A205 [ACT2 Input] to be used as the feedback signal.
7 “Min A1, A2” Selects the smaller of actual inputs A204 [ACT1 Input] or A205 [ACT2 Input] to be used as the feedback signal.
8 “Max A1, A2” Selects the larger of actual inputs A204 [ACT1 Input] or A205 [ACT2 Input] to be used as the feedback signal.
160 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Application Notes Appendix D
Analog PID Reference Signals
Parameters T070 [Analog In 1 Lo], T071 [Analog In 1 Hi], T074 [Analog In 2 Lo], and T075 [Analog In 2 Hi] are used to scale or invert an analog PID Reference.
Examples
Scale Function
For a 0...5 volt signal, the following parameter settings are used so that a 0 volt signal = 0% PID Reference and a 5 volt signal = 100% PID Reference.
• T069 [Analog In 1 Sel] or T073 [Analog In 2 Sel] = 2 “Voltage Mode - Unipolar”
• T070 [Analog In 1 Lo] or T074 [Analog In 2 Lo] = 0.0%• T071 [Analog In 1 Hi] or T075 [Analog In 2 Hi] = 50.0%• A152 [PID Ref Sel] = 0 “0-10V Input”
Invert Function
For a 4...20 mA signal, the following parameter settings are used so that a 20 mA signal = 0% PID Reference and a 4 mA signal = 100% PID Reference.
• T069 [Analog In 1 Sel] or T073 [Analog In 2 Sel] = 1 “Current Mode 4-20 mA”
• T070 [Analog In 1 Lo] or T074 [Analog In 2 Lo] = 100.0%• T071 [Analog In 1 Hi] or T075 [Analog In 2 Hi] = 0.0%• A152 [PID Ref Sel] = 2 “Analog In 1” or 3 “Analog In 2”
0 10 20 30 40 50 60 70 80 90 100
PID Reference (%)
Inpu
t Vol
ts
2
4
6
8
10
12
0 10 20 30 40 50 60 70 80 90 100
PID Reference (%)
4-20
mA
Inpu
t
4
8
12
16
20
24
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 161
Appendix D Application Notes
PID Deadband
Parameter A158 [PID Deadband] is used to set a range, in percent, of the PID Reference that the drive will ignore.
Example• [PID Deadband] is set to 5.0• The PID Reference is 25.0%• The PID Regulator will not act on a PID Error that falls between 20.0
and 30.0%
PID Preload
The value set in A159 [PID Preload], in Hertz, will be pre-loaded into the integral component of the PID at any start or enable. This will cause the drive’s frequency command to initially jump to that preload frequency, and the PID loop starts regulating from there.
PID Limits
A150 [PID Trim Hi] and A151 [PID Trim Lo] are used to limit the PID output and are only used in trim mode. [PID Trim Hi] sets the maximum frequency for the PID output in trim mode. [PID Trim Lo] sets the reverse frequency limit for the PID output in trim mode. Note that when the PID reaches the Hi or Lo limit, the PID regulator stops integrating so that windup does not occur.
PID Gains
The proportional, integral, and differential gains make up the PID regulator.
PID Enabled
Freq Cmd
PID OutputPID Pre-load Value
PID Pre-load Value > 0
162 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Application Notes Appendix D
• A154 [PID Prop Gain]The proportional gain (unitless) affects how the regulator reacts to the magnitude of the error. The proportional component of the PID regulator outputs a speed command proportional to the PID error. For example, a proportional gain of 1 would output 100% of max frequency when the PID error is 100% of the analog input range. A larger value for [PID Prop Gain] makes the proportional component more responsive, and a smaller value makes it less responsive. Setting [PID Prop Gain] to 0.00 disables the proportional component of the PID loop.
• A155 [PID Integ Time]The integral gain (units of seconds) affects how the regulator reacts to error over time and is used to get rid of steady state error. For example, with an integral gain of 2 seconds, the output of the integral gain component would integrate up to 100% of max frequency when the PID error is 100% for 2 seconds. A larger value for [PID Integ Time] makes the integral component less responsive, and a smaller value makes it more responsive. Setting [PID Integ Time] to 0 disables the integral component of the PID loop.
• A156 [PID Diff Rate]The Differential gain (units of 1/seconds) affects the rate of change of the PID output. The differential gain is multiplied by the difference between the previous error and current error. Thus, with a large error the D has a large effect and with a small error the D has less of an effect. This parameter is scaled so that when it is set to 1.00, the process response is 0.1% of [Maximum Freq] when the process error is changing at 1% / second. A larger value for [PID Diff Rate] makes the differential term have more of an effect and a small value makes it have less of an effect. In many applications, the D gain is not needed. Setting [PID Diff Rate] to 0.00 (factory default) disables the differential component of the PID loop.
Guidelines for Adjusting the PID Gains
1. Adjust the proportional gain. During this step it may be desirable to disable the integral gain and differential gain by setting them to 0.After a step change in the PID Feedback:– If the response is too slow increase A154 [PID Prop Gain].– If the response is too quick and/or unstable (see Figure 37), decrease
A154 [PID Prop Gain].– Typically, A154 [PID Prop Gain] is set to some value below the point
where the PID begins to go unstable.
2. Adjust the integral gain (leave the proportional gain set as in Step 1).After a step change in the PID Feedback:– If the response is too slow (see Figure 38), or the PID Feedback does
not become equal to the PID Reference, decrease A155 [PID Integ Time].
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 163
Appendix D Application Notes
– If there is a lot of oscillation in the PID Feedback before settling out (see Figure 39), increase A155 [PID Integ Time].
3. At this point, the differential gain may not be needed. However, if after determining the values for A154 [PID Prop Gain] and A155 [PID Integ Time]:– Response is still slow after a step change, increase A156 [PID Diff
Rate].– Response is still unstable, decrease A156 [PID Diff Rate].
The following figures show some typical responses of the PID loop at different points during adjustment of the PID Gains.
Figure 37 - Unstable
Figure 38 - Slow Response – Over Damped
Figure 39 - Oscillation – Under Damped
PID Feedback
PID Reference
Time
PID Feedback
PID Reference
Time
PID Feedback
PID Reference
Time
164 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Application Notes Appendix D
Figure 40 - Good Response – Critically Damped
Auxiliary Motor Control Setup
The PowerFlex 400 has a built in Auxiliary Motor Control feature. This feature allows operation of up to three (3) line-started motors in addition to the motor controlled directly by the PowerFlex 400 drive. System output can vary from 0% (auxiliary motors off and drive-controlled motor at zero speed) to 400% (3 auxiliary motors and drive-controlled motor at full speed). To enable the Auxiliary Motor Control, parameter R239 [Aux Motor Mode] must be set to an option 1 “Enabled.” When enabled, the internal PID controller in the PowerFlex 400 uses a reference and feedback signal to adjust the speed of the drive controlled motor such that the feedback signal follows the reference signal. When demand exceeds the first motors capacity, the PowerFlex 400 Auxiliary Motor Control automatically starts an auxiliary motor. The speed of the drive controlled motor is reduced to account for the auxiliary motors additional output to the system. If demand continues to increase, the PowerFlex Auxiliary Motor Control starts additional motors using the same process. When demand decreases, an auxiliary motor is stopped and the PowerFlex Auxiliary Motor Control increases the speed of the drive controlled motor to account for lost system output. A Motor Interlock input identifies motors that are out of service and causes them to skipped over to the next available motor.
An AutoSwap function also can be used which allows equal wear to be placed on each motor by periodically swapping the drive controlled and auxiliary motors. Each motor in the system will over time be connected to the PowerFlex 400 drive and also directly to the AC line. During an AutoSwap, the motor directly connected to the PowerFlex 400 drive is stopped and the contactor is opened. The contactor of the next motor that will be controlled by the PowerFlex 400 drive is opened if running across the AC line. A contactor is closed connecting this motor directly to the PowerFlex 400 drive and is started. An additional motor is line started if required.
PID Feedback
PID Reference
Time
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 165
Appendix D Application Notes
Example 1
Figure 41 - One External Motor without AutoSwap
• Auxiliary Motor Control is enabled via Parameter R239 [Aux Motor Mode].
• Number of auxiliary motors is set via Parameter R240 [Aux Motor Qty].• Relays are configured for Auxiliary Motor Control via parameters T055,
T060, R222, and R225.• The frequency of Motor #1 that Motor #2 turns on at is set via
Parameter R241 [Aux 1 Start Freq].• The time that Motor #1 is above the value set by R241 [Aux 1 Start
Freq] before turning on Motor #2 is set via Parameter R250 [Aux Start Delay].
• The frequency of Motor #1 that Motor #2 turns off at is set via Parameter R242 [Aux 1 Stop Freq].
• The time that Motor #1 is below the value set by R242 [Aux 1 Stop Freq] before turning off Motor #2 is set via Parameter R251 [Aux Stop Delay].
• PID setup is done via Parameters A150 through A159. See Appendix D for additional information.
PIDReferenceFeedback
Drive Relays
Auxiliary Relay Card
M2L
PowerFlex 400
Three-Phase Power
M2L
M1 M2
Frequency
R241 [Aux 1 Start Freq]
R251 [Aux Stop Delay]
R250 [Aux Start Delay]
R242 [Aux 1 Stop Freq]
Time
166 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Application Notes Appendix D
Example 2
Figure 42 - One External Motor with AutoSwap
(1) Mechanically interlocked contactors are recommended to ensure that the drive contactor and the line contactor do not close at the same time. If the drive and line contactor close at the same time, drive damage may result.
• Auxiliary Motor Control is enabled via Parameter R239 [Aux Motor Mode].
• Number of auxiliary motors is set via Parameter R240 [Aux Motor Qty].• Relays are configured for Auxiliary Motor Control via parameters T055,
T060, R222, R225, R228, R231, R234, and R237.• The frequency of Motor #1 that Motor #2 turns on at is set via
Parameter R241 [Aux 1 Start Freq].• The time that Motor #1 is above the value set by R241 [Aux 1 Start
Freq] before turning on Motor #2 is set via Parameter R250 [Aux Start Delay].
• The frequency of Motor #1 that Motor #2 turns off at is set via Parameter R242 [Aux 1 Stop Freq].
• The time that Motor #1 is below the value set by R242 [Aux 1 Stop Freq] before turning off Motor #2 is set via Parameter R251 [Aux Stop Delay].
• PID setup is done via Parameters A150 through A159. • The maximum PID output level that an AutoSwap can occur is set via
Parameter R254 [Aux AutoSwap Lvl]. AutoSwap will be delayed until the PID output drops below this parameter setting.
IMPORTANT If using auxiliary motor control, ensure that wiring and parameter configuration are correct before wiring contactor outputs. All relays on the Auxiliary Relay Card will energize on power-up by default. Failure to verify proper wiring and parameter configuration can result in improper motor operation or drive damage.
PIDReferenceFeedback
Drive Relays
Auxiliary Relay Card
M1D M1L M2D M2L
PowerFlex 400
Three-Phase Power
M1DM1L
M2DM2L
M1 M2
(1) (1)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 167
Appendix D Application Notes
IMPORTANT If using auxiliary motor control, ensure that wiring and parameter configuration are correct before wiring contactor outputs. All relays on the Auxiliary Relay Card will energize on power-up by default. Failure to verify proper wiring and parameter configuration can result in improper motor operation or drive damage.
168 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix E
Modbus RTU Protocol
PowerFlex 400 drives support the RS485 (DSI) protocol to allow efficient operation with Rockwell Automation peripherals. In addition, some Modbus functions are supported to allow simple networking. PowerFlex 400 drives can be multi-dropped on an RS485 network using Modbus protocol in RTU mode.
For information regarding DeviceNet or other communication protocols, refer to the appropriate user manual.
Network Wiring Network wiring consists of a shielded 2-conductor cable that is daisy-chained from node to node.
Figure 43 - Network Wiring Diagram
Only pins 4 and 5 on the RJ45 plug should be wired. The other pins on the PowerFlex 400 RJ45 socket contain power, etc. for other Rockwell Automation peripheral devices and must not be connected.
Wiring terminations on the master controller will vary depending on the master controller used and “TxRxD+” and “TxRxD-” are shown for illustration purposes only. Refer to the master controller’s user manual for network terminations. Note that there is no standard for the “+” and “-” wires, and consequently Modbus device manufacturers interpret them differently. If you have problems with initially establishing communications, try swapping the two network wires at the master controller.
Controller
MasterPowerFlex 400
Node 1
4
5
PowerFlex 400Node 2
4
5
PowerFlex 400Node "n"
4
5
TxRxD+
TxRxD-
TxRxD+
TxRxD-
TxRxD+
TxRxD-
NOTE: The shield should be grounded at ONLY ONE location.
Shield Shield Shield
120 ohm resistor
120 ohm resistor
FRONT
PIN 8PIN 1
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 169
Appendix E Modbus RTU Protocol
Standard RS485 wiring practices apply. Termination resistors need to be applied at each end of the network cable. RS485 repeaters may need to be used for long cable runs, or if greater than 32 nodes are needed on the network.
Parameter Configuration The following PowerFlex 400 parameters are used to configure the drive to operate on a network.
Supported Modbus Function Codes
The peripheral interface (DSI) used on PowerFlex 400 drives supports some of the Modbus function codes.
Writing (06) Logic Command Data
The PowerFlex 400 drive can be controlled via the network by sending Function Code 06 writes to register address 8192 (Logic Command). P036 [Start Source] must be set to 5 “Comm Port” in order to accept the commands.
Parameter Details Reference
P036 [Start Source] Set to 5 “RS485 (DSI) Port” if Start is controlled from the network. page 62
P038 [Speed Reference] Set to 5 “RS485 (DSI) Port” if the Speed Reference is controlled from the network.
page 63
C102 [Comm Format] Sets the transmission mode, data bits, parity and stop bits for the RS485 (DSI) Port. All nodes on the network must be set to the same setting.
page 79
C103 [Comm Data Rate] Sets the data rate for the RS485 (DSI) Port. All nodes on the network must be set to the same data rate.
page 79
C104 [Comm Node Addr] Sets the node address for the drive on the network. Each device on the network requires a unique node address.
page 80
C105 [Comm Loss Action] Selects the drive’s response to communication problems. page 80
C106 [Comm Loss Time] Sets the time that the drive will remain in communication loss before the drive implements C105 [Comm Loss Action].
page 80
C107 [Comm Write Mode] Determines whether parameter changes made over communication port are saved or stored in RAM only. If they are stored in RAM, the values will be lost at power-down.
page 80
Modbus Function Code Command
03 Read Holding Registers
06 Preset (Write) Single Register
16 (10 Hexadecimal) Preset (Write) Multiple Registers
IMPORTANT Modbus devices can be 0-based (registers are numbered starting at 0) or 1-based (registers are numbered starting at 1). Depending on the Modbus Master used, the register addresses listed on the following pages may need to be offset by +1. For example, Logic Command may be register address 8192 for some master devices (e.g. ProSoft 3150-MCM SLC Modbus scanner) and 8193 for others (e.g. PanelViews).
170 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Modbus RTU Protocol Appendix E
In addition to being written, register address 8192 can be read using Function Code 03.
Writing (06) Reference The Speed Reference to a PowerFlex 400 drive can be controlled via the network by sending Function Code 06 writes to register address 8193 (Reference). P038 [Speed Reference] must be set to 5 “Comm Port” in order to accept the Speed Reference. In addition to being written, register address 8193 can be read using Function Code 03.
Logic Command
Address (Decimal) Bit(s) Description
8192 0 1 = Stop, 0 = Not Stop
1 1 = Start, 0 = Not Start
2 1 = Jog, 0 = No Jog
3 1 = Clear Faults, 0 = Not Clear Faults
5, 4 00 = No Command
01 = Forward Command
10 = Reverse Command
11 = No Command
6 1 = Local Control(1), 0 = Comm Control
(1) Local Control causes the drive to use C108 [Start Source 2] and C109 [Speed Ref 2] for start and speed reference control.
7 1 = MOP Increment, 0 = Not Increment
9, 8 00 = No Command
01 = Accel Rate 1 Enable
10 = Accel Rate 2 Enable
11 = Hold Accel Rate Selected
11, 10 00 = No Command
01 = Decel Rate 1 Enable
10 = Decel Rate 2 Enable
11 = Hold Decel Rate Selected
14, 13, 12 000 = No Command
001 = Freq. Source = P038 [Speed Reference]
010 = Freq. Source = A142 [Internal Freq]
011 = Freq. Source = Comms (Addr 8193)
100 = A143 [Preset Freq 0]
101 = A144 [Preset Freq 1]
110 = A145 [Preset Freq 2]
111 = A146 [Preset Freq 3]
15 1 = MOP Decrement, 0 = Not Decrement
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 171
Appendix E Modbus RTU Protocol
Reading (03) Logic Status Data
The PowerFlex 400 Logic Status data can be read via the network by sending Function Code 03 reads to register address 8448 (Logic Status).
Reading (03) Feedback The Feedback (Output Frequency) from the PowerFlex 400 drive can be read via the network by sending Function Code 03 reads to register address 8451 (Feedback).
Reading (03) Drive Error Codes
The PowerFlex 400 Error Code data can be read via the network by sending Function Code 03 reads to register address 8449 (Drive Error Codes).
Reference
Address (Decimal) Description
8193 A decimal value entered as xxx.xx where the decimal point is fixed.For example, a decimal “1000” equals 10.00 Hz and “543” equals 5.43 Hz.
Logic Status
Address (Decimal) Bit(s) Description
8448 0 1 = Ready, 0 = Not Ready
1 1 = Active (Running), 0 = Not Active
2 1 = Cmd Forward, 0 = Cmd Reverse
3 1 = Rotating Forward, 0 = Rotating Reverse
4 1 = Accelerating, 0 = Not Accelerating
5 1 = Decelerating, 0 = Not Decelerating
6 1 = Alarm, 0 = No Alarm
7 1 = Faulted, 0 = Not Faulted
8 1 = At Reference, 0 = Not At Reference
9 1 = Reference Controlled by Comm
10 1 = Operation Cmd Controlled by Comm
11 1 = Parameters have been locked
12 Digital Input 1 Status
13 Digital Input 2 Status
14 Digital Input 3 Status
15 Digital Input 4 Status
Feedback(1)
(1) Returns the same data as Reading (03) Parameter b001 [Output Freq].
Address (Decimal) Description
8451 A xxx.xx decimal value where the decimal point is fixed.For example, a decimal “1234” equals 12.34 Hz and “300” equals 3.00 Hz.
172 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Modbus RTU Protocol Appendix E
Reading (03) and Writing (06) Drive Parameters
To access drive parameters, the Modbus register address equals the parameter number. For example, a decimal “1” is used to address Parameter b001 [Output Freq] and decimal “39” is used to address Parameter P039 [Accel Time 1].
Additional Information Refer to http://www.ab.com/drives/ for additional information.
Error Code
Address (Decimal) Value (Decimal) Description
8449 0 No Fault
2 Auxiliary Input
3 Power Loss
4 Undervoltage
5 Overvoltage
6 Motor Stalled
7 Motor Overload
8 Heatsink Overtemperature
12 HW Overcurrent (300%)
13 Ground Fault
15 Load Loss
29 Analog Input Loss
33 Auto Restart Tries
38 Phase U to Ground Short
39 Phase V to Ground Short
40 Phase W to Ground Short
41 Phase UV Short
42 Phase UW Short
43 Phase VW Short
48 Params Defaulted
63 Software Overcurrent
64 Drive Overload
70 Power Unit Fail
71 Net Loss
81 Communication Loss
94 Function Loss
100 Parameter Checksum Error
122 I/O Board Fail
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 173
Appendix E Modbus RTU Protocol
Notes:
174 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix F
Metasys N2
This appendix provides information about controlling a PowerFlex 400 drive, setting its Reference, and accessing its parameters through configurable objects when the Metasys N2 network protocol is selected.
Understanding Metasys N2 Metasys nodes are built up by the use of several virtual objects. The Metasys N2 master performs read and write commands to these virtual objects, and the internal Metasys protocol firmware transfers/translates the data between these virtual objects and the drive.
When a read or write command occurs to a certain dedicated virtual object, data in the virtual objects is refreshed from or transferred to the drive.
The Metasys N2 master performs read and write commands to the virtual objects one at a time. The data types that are used in the virtual objects are binary input (BI), binary output (BO), analog input (AI), analog output (AO), and internal integer (ADI).
The Metasys N2 master also performs cyclic polling of all the virtual objects.
Metasys N2 Virtual Objects
A Metasys N2 node may contain up to 256 virtual objects in each of its seven different data types, called regions (Table 34).
For information on... See page
Understanding Metasys N2 175
Network Points 177
Using Percent (%) for the Reference 180
Using Metasys Configurable Objects to Access Parameters 181
ATTENTION: Risk of equipment damage exists. If a controller is programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS unless C107 [Comm Write Mode] is set to option 1.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 175
Appendix F Metasys N2
Metasys N2 Data Types
Table 34 - Description of the Regions of a Virtual Object
Region Type Short Description
Region 1 Analog Input AI 32-bit, IEEE-standard floats
Region 2 Binary Input BI 1-bit
Region 3 Analog Output AO 32-bit, IEEE-standard floats
Region 4 Binary Output BO 1-bit
Region 5 Internal Float ADF 32-bit, IEEE-standard floats (Analog Data Float)
Region 6 Internal Integer ADI 16-bit (Analog Data Integer)
Region 7 Internal Byte DB 8-bit (Analog Data Byte)
Table 35 - Internal Structure of Metasys N2 Analog Input (AI)
Attribute Type Description
1 Byte Object Configuration
2 Byte Object Status
3 Float Analog Input Value
8 Float Low Alarm Limit
9 Float Low Warning Limit
10 Float High Warning Limit
11 Float High Alarm Limit
12 Float Differential
Table 36 - Internal Structure of Metasys N2 Binary Input (BI)
Attribute Type Description
1 Byte Object Configuration
2 Byte Object Status
Table 37 - Internal Structure of Metasys N2 Analog Output (AO)
Attribute Type Description
1 Byte Object Configuration
2 Byte Object Status
3 Float Current Value
Table 38 - Internal Structure of Metasys N2 Binary Output (BO)
Attribute Type Description
1 Byte Object Configuration
2 Byte Object Status
176 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Metasys N2 Appendix F
Network Points
3 Integer Minimum On-Time
4 Integer Minimum Off-Time
5 Integer Maximum Cycle/Hour
Table 39 - Internal Structure of Metasys N2 Internal Integer (ADI)
Attribute Type Description
1 Byte Object Configuration
2 Integer Current Value. Signed 16-bit.
Table 38 - Internal Structure of Metasys N2 Binary Output (BO)
Attribute Type Description
Table 40 - Binary Inputs
Network Point Name Description ON (“1”) OFF (“0”)
Type(NPT)
Address(NPA)
BI 1 Ready Logic Status bit 00 Ready Not Ready
BI 2 Active Logic Status bit 01 Active Not Active
BI 3 Cmd Dir Logic Status bit 02 Forward Reverse
BI 4 Act Dir Logic Status bit 03 Forward Reverse
BI 5 Accel Logic Status bit 04 Accelerating Not Accelerating
BI 6 Decel Logic Status bit 05 Decelerating Not Decelerating
BI 7 Alarm Logic Status bit 06 Alarm No Alarm
BI 8 Fault Logic Status bit 07 Fault No Fault
BI 9 At Speed Logic Status bit 08 At Reference Not at Reference
BI 10 Main Freq Logic Status bit 09 Comm Controlled Not Comm Controlled
BI 11 Oper Cmd Logic Status bit 10 Comm Controlled Not Comm Controlled
BI 12 Param Lock Logic Status bit 11 Locked Not Locked
BI 13 Digital In 1 Logic Status bit 12(Drive Terminal #2)
On Off
BI 14 Digital In 2 Logic Status bit 13(Drive Terminal #3)
On Off
BI 15 Digital In 3 Logic Status bit 14(Drive Terminal #4)
On Off
BI 16 Digital In 4 Logic Status bit 15(Drive Terminal #5)
On Off
BI 17 Digital In 5 Drive Terminal #6 On Off
BI 18 Digital In 6 Drive Terminal #7 On Off
BI 19 Digital In 7 Drive Terminal #8 On Off
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 177
Appendix F Metasys N2
Table 41 - Analog Inputs
Network Point Name Description Units Min/Max
Type(NPT)
Address(NPA)
AI 1 Feedback Feedback % 0/100
AI 2 Speed d323 [Output RPM] RPM 0/24000
AI 3 Current b003 [Output Current] A 0.00/Rated × 2
AI 4 DC Bus Volts b005 [DC Bus Voltage] V 0/820
AI 5 Last Fault d307 [Fault 1 Code] 1 1/100
AI 6 2nd Fault d308 [Fault 2 Code] 1 1/100
AI 7 Analog In 1 Drive Analog Input #1(Drive Terminal #13)
% –
AI 8 Analog In 2 Drive Analog Input #2(Drive Terminal #17)
% –
AI 9 Read Value Read value of Param.selected by AO 10
Varies by the parameter selected.
AI 10 User In 1 User-defined Input 1(Param. selected via ADI 1)
AI 11 User In 2 User-defined Input 2(Param. selected via ADI 2)
AI 12 User In 3 User-defined Input 3(Param. selected via ADI 3)
AI 13 User In 4 User-defined Input 4(Param. selected via ADI 4)
Table 42 - Binary Outputs
Network Point Name Description ON (“1”) OFF (“0”)
Type(NPT)
Address(NPA)
BO 1 Run Enable Logic Command bit 00 Enable Stop (Coast)
BO 2 Start/Stop Logic Command bit 00 & 01 Start Stop (Normal)
BO 3 Jog Logic Command bit 02 Jog Not Jog
BO 4 Clear Faults Logic Command bit 03 Clear Flts Not Clear Flts
BO 5 Fwd/Rev Logic Command bit 04 & 05 Forward Reverse
BO 6 Not Used Logic Command bit 06 – –
BO 7 MOP Inc Logic Command bit 07 Increment Not Increment
BO 8 Accel 1 Logic Command bit 08 Accel Rate 1 Not Accel 1
BO 9 Accel 2 Logic Command bit 09 Accel Rate 2 Not Accel 2
BO 10 Decel 1 Logic Command bit 10 Decel Rate 1 Not Decel 1
BO 11 Decel 2 Logic Command bit 11 Decel Rate 2 Not Decel 2
178 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Metasys N2 Appendix F
BO 12 Ref Sel 1 Logic Command bit 12 BO14 13 120 0 0 = No Command0 0 1 = P038 [Speed Reference]0 1 0 = A142 [Internal Freq]0 1 1 = Comm - Address 8193(1)
1 0 0 = A143 [Preset Freq 0]1 0 1 = A144 [Preset Freq 1]1 1 0 = A145 [Preset Freq 2]1 1 1 = A146 [Preset Freq 3]
BO 13 Ref Sel 2 Logic Command bit 13
BO 14 Ref Sel 3 Logic Command bit 14
BO 15 MOP Dec Logic Command bit 15 Decrement Not Decrement
BO 16 Pnl Lock Lock-out Drive Front Panel Lock Unlock
BO 17 Digital Out 1 Relay #1 on Drive(Drive Terminal R1, R2, R3)
On Off
BO 18 Digital Out 2 Relay #2 on Drive(Drive Terminal R4, R5, R6)
On Off
BO 19 Opto Out Terminal #19 On Off
(1) See Writing (06) Reference on page 170.
Table 43 - Analog Outputs
Network Point Name Description Units Min/Max
Type(NPT)
Address(NPA)
AO 1 Reference Reference % 0/100
AO 2 Accel 1 P039 [Accel Time 1] Secs 0.0/600.0
AO 3 Decel 1 P040 [Decel Time 1] Secs 0.0/600.0
AO 4 Mtr OL Current P033 [Motor OL Current] A 0.0/Rated x 2
AO 5 PID Setpoint A157 [PID Setpoint] % 0/100
AO 6 Analog Out 1 Drive Analog Output #1 (T084) % –
AO 7 Analog Out 2 Drive Analog Output #2 (T087) % –
AO 8 Write Param # Param. number to write in AO 9 – 0...Max Param.
AO 9 Write Value Write value of param. selected by AO 8 Based on AO 8 selected param.
AO 10 Read Param # Param. number to read in AI 9 – 0...Max Param.
AO 11 User Out 1 User-defined Output 1(Param. selected via ADI 5)
Varies by the parameter selected.
AO 12 User Out 2 User-defined Output 2(Param. selected via ADI 6)
AO 13 User Out 3 User-defined Output 3(Param. selected via ADI 7)
AO 14 User Out 4 User-defined Output 4(Param. selected via ADI 8)
Table 42 - Binary Outputs
Network Point Name Description ON (“1”) OFF (“0”)
Type(NPT)
Address(NPA)
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 179
Appendix F Metasys N2
Using Percent (%) for the Reference
The Reference (AO 1) for Metasys N2 is set as a percentage from 0% to +100%.
Table 44 - Internal Integer
Network Point Name Description Min/Max Default
Type(NPT)
Address(NPA)
ADI 1 Param# IN1 User IN 1 (AI 10)Data Source (Param#)
0/Max Drive Params. b001 [Output Freq] (Hz)
ADI 2 Param# IN2 User IN 2 (AI 11)Data Source (Param#)
0/Max Drive Params. b011 [Elapsed MWh]
ADI 3 Param# IN3 User IN 3 (AI 12)Data Source (Param#)
0/Max Drive Params. b012 [Elapsed Run Time]
ADI 4 Param# IN4 User IN 4 (AI 13)Data Source (Param#)
0/Max Drive Params. b014 [Drive Temperature]
ADI 5 Param# OUT1 User OUT 1 (AO 11)Data Source (Param#)
0/Max Drive Params. A154 [PID Gain]
ADI 6 Param# OUT2 User OUT 2 (AO 12)Data Source (Param#)
0/Max Drive Params. A155 [PID Integral Time]
ADI 7 Param# OUT3 User OUT 3 (AO 13)Data Source (Param#)
0/Max Drive Params. A156 [PID Diff Rate]
ADI 8 Param# OUT4 User OUT 4 (AO 14)Data Source (Param#)
0/Max Drive Params. A158 [PID Deadband]
Table 45 - Example Speed Reference and Feedback for a PowerFlex 400 (P035 = 60 Hz)
Reference (A0 1) Feedback (AI 1)
Percent Speed Speed Percent
100% 60 Hz 60 Hz 100%
50% 30 Hz 30 Hz 50%
25% 15 Hz 15 Hz 25%
0% 0 Hz 0 Hz 0%
100%
0%Pr. P035 [Maximum Freq] Value0
180 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Metasys N2 Appendix F
Using Metasys Configurable Objects to Access Parameters
Configurable objects are inputs and outputs that let you read and write parameter values. These objects handle only 16-bit parameter values.
Reading Parameter Values
The configurable points may show any parameter in the drive by configuring the Param# for INx point. The drive reads the value of the parameter configured in the Param# for INx point and shows the result in the User INx point. The Param# for INx’s default to commonly accessed parameters and can be changed if desired. A “0” disables the fetching of data and a “0” is returned in the respective User INx. See Figure 44 and Table 46.
Figure 44 - Configurable Input Point Operation Objects Inputs
Table 46 - Configurable Objects: Inputs
Network Point Name Description Default
Type(NPT)
Address(NPA)
AI 10 User IN1 User-defined Input 1 0
AI 11 User IN2 User-defined Input 2 0
AI 12 User IN3 User-defined Input 3 0
AI 13 User IN4 User-defined Input 4 0
ADI 1 Param# for IN1 User IN1 (AI 10)Data Source (Param#)
b001 [Output Freq] (Hz)
ADI 2 Param# for IN2 User IN2 (AI 11)Data Source (Param#)
b011 [Elapsed MWh]
ADI 3 Param# for IN3 User IN3 (AI 12)Data Source (Param#)
b012 [Elapsed Run Time]
ADI 4 Param# for IN4 User IN4 (AI 13)Data Source (Param#)
b014 [Drive Temp]
Controller Drive
Param# for INx
User INx
ADI
AI
Request
Response Data
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 181
Appendix F Metasys N2
Writing Parameter Values
These outputs are written each time the User OUTx point is written from the network.
The Param# for OUTx’s default to commonly accessed parameters and can be changed if desired. A value of “0” in the Param# for OUTx field disables the writing of data for that specific point.
Figure 45 - Configurable Objects: Outputs
ATTENTION: Risk of equipment damage exists. If configurable outputs are programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS.
Table 47 - Configurable Objects: Outputs
Network Point Description Range Default
Type(NPT)
Address(NPA)
AO 6 User OUT1 Varies by the parameter selected by Param# for OUTx.
0
AO 7 User OUT2 0
AO 8 User OUT3 0
AO 9 User OUT4 0
ADI 5 User OUT1 (A06)Destination (Param#)
0 (not in use), 1 to maximum # of drive parameters
A154 [PID Prop Gain]
ADI 6 User OUT2 (A07)Destination (Param#)
0 (not in use), 1 to maximum # of drive parameters
A155 [PID Integ Time]
ADI 7 User OUT3 (A08)Destination (Param#)
0 (not in use), 1 to maximum # of drive parameters
A156 [PID Diff Rate]
ADI 8 User OUT4 (A09)Destination (Param#)
0 (not in use), 1 to maximum # of drive parameters
A158 [PID Deadband]
Controller Drive
Param# for OUTx
ADI
A0User OUTx
182 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix G
P1 – Floor Level Network (FLN)
This appendix provides information about controlling a PowerFlex 400 drive, setting its Reference, and accessing its parameters through configurable points when the P1-FLN protocol is selected. The P1-FLN protocol is a serial communication protocol used by the Siemens APOGEE® system.
Understanding P1-FLN The P1-FLN master performs read and write commands to certain points, and the internal P1-FLN protocol firmware transfers/translates the data between these points and the drive.
When a read or write command occurs to a certain point, data in the point is refreshed from or transferred to the drive.
The P1-FLN master also performs cyclic polling of all the virtual objects.
P1-FLN Points
A P1-FLN node may contain up to 99 points.
For information on... See page
Understanding P1-FLN 183
Network Points 184
Using Percent (%) for the Reference 188
Using P1 Configurable Points to Access Parameters 188
ATTENTION: Risk of equipment damage exists. If a controller is programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to NVS unless C107 [Comm Write Mode] is set to option 1.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 183
Appendix G P1 – Floor Level Network (FLN)
Network Points Table 48 - Point Database for Application 2735
PointNumber(1) (2)
PointType
SubpointName
FactoryDefault(SI Units)(4)
EngineeringUnits(SI Units)(4)
Slope(SI Units)(4)
Intercept(SI Units)(4)
On Text Off Text
01 LAO CTLR ADDRESS 99 – 1 0 – –
02 LAO APPLICATION 2735 – 1 0 – –
{03} LAI FREQ OUTPUT 0 Hz 0.01 0 – –
{04} LAI PCT OUTPUT 0 PCT 001 0 – –
{05} LAI SPEED 0 RPM 1 0 – –
{06} LAI CURRENT 0 AMPS 0.1 0 – –
{07} LAI TORQUE 0 AMPS 0.1 0 – –
{08} LAI POWER 0 HP (kW) 0.1333 (0.1) 0 (0) – –
{09} LAI DRIVE TEMP 0 DEG F (DEG C) 1.8 (1) 32 (0) – –
{11} LAI DRIVE MWH 0 MWH 0.1 0 – –
{12} LAI RUN TIME 0 HRS 10 0 – –
{13} LAI DC BUS VOLT 0 VOLTS 1 0 – –
20 LAO OVRD TIME 1 HRS 1 0 – –
{21} LDI FWD.REV MON FWD – 1 0 REV FWD
{22} LDO CMD FWD.REV FWD – 1 0 REV FWD
{23} LDI RUN.STOP MON STOP – 1 0 RUN STOP
{24} LDO CMD RUN.STOP STOP – 1 0 RUN STOP
{25} LDI READY READY – 1 0 READY NOTRDY
{26} LDO RUN ENABLE STOP – 1 0 ENABLE STOP
{29} LDO DAY NGT DAY – 1 0 NIGHT DAY
30 LAO CURRENT LIMT (5) AMPS 0.1 0 – –
31 LAO ACCEL TIME 20 SEC 0.02 0 – –
32 LAO DECEL TIME 20 SEC 0.02 0 – –
33 LDO KEYPAD LOCK UNLOCK – 1 0 LOCK UNLOCK
{36} LAO READ PARAM 0 – 1 0 – –
{37} LAI READ VALUE 0 – 1 0 – –
{38} LAO WRITE PARAM 0 – 1 0 – –
{39} LAO WRITE VALUE 0 – 1 0 – –
{40} LDO DIGITAL OUT1 OFF – 1 0 ON OFF
{41} LDO DIGITAL OUT2 OFF – 1 0 ON OFF
{42} LDO DIGITAL OUT3 OFF – 1 0 ON OFF
{43} LDO OPT RELAY 1 OFF – 1 0 ON OFF
{44} LDO OPT RELAY 2 OFF – 1 0 ON OFF
{45} LDO OPT RELAY 3 OFF – 1 0 ON OFF
{46} LDO OPT RELAY 4 OFF – 1 0 ON OFF
{47} LDO OPT RELAY 5 OFF – 1 0 ON OFF
{48} LDO OPT RELAY 6 OFF – 1 0 ON OFF
{49} LDI DIGITAL IN 1 OFF – 1 0 ON OFF
184 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
P1 – Floor Level Network (FLN) Appendix G
{50} LDI DIGITAL IN 2 OFF – 1 0 ON OFF
{51} LDI DIGITAL IN 3 OFF – 1 0 ON OFF
{52} LDI DIGITAL IN 4 OFF – 1 0 ON OFF
{53} LDI DIGITAL IN 5 OFF – 1 0 ON OFF
{54} LDI DIGITAL IN 6 OFF – 1 0 ON OFF
{55} LDI DIGITAL IN 7 OFF – 1 0 ON OFF
{60} LAI INPUT REF 1 0 (6) 0.1 0 – –
{61} LAI INPUT REF 2 0 (6) 0.1 0 – –
{62} LAO ANALOG OUT 1 0 PCT 0.1 0 – –
{63} LAO ANALOG OUT 2 0 PCT 0.1 0 – –
{64} LAI LAST FAULT 0 – 1 0 – –
65 LAO PID GAIN 1 PTC 0.01 0 – –
66 LAO PID INT TIME 2 SEC 0.1 0 – –
67 LAO PID DIFF RATE 0 PERSEC(7) 0.01 0 – –
68 LAO PID SETPOINT 0 PTC 0.1 0 – –
{70} LDI CMD DIR MON FWD – 1 0 REV FWD
{71} LDI ACCELERATING OFF – 1 0 ON OFF
{72} LDI DECELERATING OFF – 1 0 ON OFF
{73} LDI ALARM NORMAL – 1 0 ALARM NORMAL
{74} LDI AT SPEED OFF – 1 0 ON OFF
{75} LDI MAIN FREQ OFF – 1 0 ON OFF
{76} LDI OPER CMD OFF – 1 0 ON OFF
{77} LDI PARAM LOCK UNLOCK – 1 0 LOCK UNLOCK
{78} LDO JOG OFF – 1 0 ON OFF
{79} LDO LOCAL CNTRL(3) OFF – 1 0 ON OFF
{80} LDO MOP INC OFF – 1 0 ON OFF
{81} LDO ACCEL RATE 1 OFF – 1 0 ON OFF
{82} LDO ACCEL RATE 2 OFF – 1 0 ON OFF
{83} LDO DECEL RATE 1 OFF – 1 0 ON OFF
{84} LDO DECEL RATE 2 OFF – 1 0 ON OFF
{85} LDO REF SELECT 1 OFF – 1 0 ON OFF
{86} LDO REF SELECT 2 OFF – 1 0 ON OFF
{87} LDO REF SELECT 3 OFF – 1 0 ON OFF
{88} LDO MOP DEC OFF – 1 0 ON OFF
{92} LAO REFERENCE 0 PCT 0.01 0 – –
{93} LDI OK.FAULT OK – 1 0 FAULT OK
{94} LDO RESET FAULT NORMAL – 1 0 RESET NORMAL
{99} LAO ERROR STATUS 0 – 1 0 – –
Table 48 - Point Database for Application 2735 (continued)
PointNumber(1) (2)
PointType
SubpointName
FactoryDefault(SI Units)(4)
EngineeringUnits(SI Units)(4)
Slope(SI Units)(4)
Intercept(SI Units)(4)
On Text Off Text
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 185
Appendix G P1 – Floor Level Network (FLN)
(1) Points not listed are not used in this application.(2) Point numbers that appear in brackets { } may be unbundled at the field panel.(3) Local Control causes the drive to use C108 [Start Source 2] and C109 [Speed Ref 2] for start and speed reference control.(4) A single value in a column means that the value is the same in English units and in SI units.(5) Depends on drive model.(6) Depending on configuration, units can be volts or milliamperes.(7) 1 / Secs
Table 49 - Point Database for Application 2735
Point Number Subpoint Name Parameter
01 CTLR ADDRESS C104
02 APPLICATION –
03 FREQ OUTPUT b001
04 PCT OUTPUT d322
05 SPEED d323
06 CURRENT b003
07 TORQUE b013
08 POWER b010
09 DRIVE TEMP b014
11 DRIVE MWH b011
12 RUN TIME b012
13 DC BUS VOLT b005
20 OVRD TIME –
21 FWD.REV MON –
22 CMD FWD.REV –
23 RUN.STOP MON b006, bit 1 (Running)
24 CMD RUN.STOP –
25 READY d302, bit 2 (I/O Terminal 01)
26 RUN ENABLE –
29 DAY NGT –
30 CURRENT LIMT P033
31 ACCEL TIME 1 P039
32 DECEL TIME 1 P040
33 KEYPAD LOCK A198
36 READ PARAM # –
37 READ VALUE –
38 WRITE PARAM # –
39 WRITE VALUE –
40 DIGITAL OUT1 T055, T056
41 DIGITAL OUT2 T060, T061
42 DIGITAL OUT3 T065, T066
43 OPT RELAY 1 R221, R222(1)
44 OPT RELAY 2 R224, R225(1)
186 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
P1 – Floor Level Network (FLN) Appendix G
45 OPT RELAY 3 R227, R228(1)
46 OPT RELAY 4 R230, R231(1)
47 OPT RELAY 5 R233, R234(1)
48 OPT RELAY 6 R236, R237(1)
49 DIGITAL IN 1 d302, bit 0 (I/O Terminal 02)
50 DIGITAL IN 2 d302, bit 1 (I/O Terminal 03)
51 DIGITAL IN 3 d302, bit 2 (I/O Terminal 04)
52 DIGITAL IN 4 d302, bit 3 (I/O Terminal 05)
53 DIGITAL IN 5 d302, bit 4 (I/O Terminal 06)
54 DIGITAL IN 6 d302, bit 5 (I/O Terminal 07)
55 DIGITAL IN 7 d302, bit 6 (I/O Terminal 08)
60 INPUT REF 1 d305
61 INPUT REF 2 d306
62 ANALOG OUT 1 T082
63 ANALOG OUT 2 T085
64 LAST FAULT b007
65 PID GAIN A154
66 PID INT TIME A155
67 PID DIFF RATE A156
68 PID SETPOINT A157
70 CMD DIR MON b006, bit 2 (Forward)
71 ACCELERATING b006, bit 3 (Accelerating)
72 DECELERATING b006, bit 4 (Decelerating)
73 ALARM –
74 AT SPEED –
75 MAIN FREQ d301 (Digit 0)
76 OPER CMD d301 (Digit 1)
77 PARAM LOCK –
78 JOG –
79 LOCAL CNTRL –
80 MOP INC –
81 ACCEL RATE 1 –
82 ACCEL RATE 2 –
83 DECEL RATE 1 –
84 DECEL RATE 2 –
85 REF SELECT 1 –
86 REF SELECT 2 –
87 REF SELECT 3 –
88 MOP DEC –
Table 49 - Point Database for Application 2735
Point Number Subpoint Name Parameter
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 187
Appendix G P1 – Floor Level Network (FLN)
Using Percent (%) for the Reference
The Reference (Point 92) for P1 is set as a percentage from 0% to +100%.
Using P1 Configurable Points to Access Parameters
Configurable points are inputs and outputs that let you read and write parameter values. These objects handle only 15-bit parameter values (0...32767).
Reading Parameter Values
The configurable points may show any parameter in the drive by configuring the Param# in the Read Param point. The drive reads the value of the parameter configured in the Param# for the Read Param point and shows the result in the Read Value point. The Param# for the Read Param point default to commonly accessed parameters and can be changed if desired. A “0” disables
92 REFERENCE b002
93 OK.FAULT –
94 RESET FAULT –
99 ERROR STATUS –
(1) These parameters affect the operation of an optional auxiliary relay board.
Table 49 - Point Database for Application 2735
Point Number Subpoint Name Parameter
Table 50 - Example Speed Reference and Feedback for a PowerFlex 400 (P035 = 60 Hz)
Reference (Point 92) PCT Output (Point 4)
Percent Speed Speed Percent
100% 60 Hz 60 Hz 100%
50% 30 Hz 30 Hz 50%
25% 15 Hz 15 Hz 25%
0% 0 Hz 0 Hz 0%
100%
0%Pr. P035 [Maximum Freq] Value0
IMPORTANT If a parameter has a decimal point, the value must be properly scaled by the user. For example, Accel Time has two decimal places. To use the value 60.00, the scaled value 6000 must be communicated to the drive. The scaled value 6000 will be returned.
188 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
P1 – Floor Level Network (FLN) Appendix G
the fetching of data and a “0” is returned in the Read Value point. See Figure 46 andTable 51.
Figure 46 - Configurable Input Point Operation
Writing Parameter Values
These outputs are written each time the Write Value point is written from the network.
The Param# for Write Param point’s default to commonly accessed parameters and can be changed if desired. A value of “0” in the Param# for Write Param point field disables the writing of data.
Figure 47 - Configurable Objects: Outputs
Table 51 - Configurable Objects: Inputs
Point Name Description Default
36 Read Param Param# to read value 0
37 Read Value Value of parameter specified by Point 36 0
Table 52 - Configurable Objects: Outputs
Point Name Description Default
38 Write Param Param# to write value 0
38 Write Value New value of parameter specified by Point 38 0
Controller Drive
Set Point 36 with Param# to Read Data From.
Set Point 37 to get Data of Param# in Point 36.
Controller DriveSet Point 38 with Param# to Read Data To.
Write Point 39 to Write Data to Param# inPoint 38.
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 189
Appendix G P1 – Floor Level Network (FLN)
Notes:
190 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Index
AAC Supply
Ground 19Source 18Ungrounded 18
Analog Input Loss Fault 116Armored Cable 23Auto Rstrt Tries Fault 116Auxiliary Input Fault 115
BBefore Applying Power 45, 46
CCable Length 28Cable, Power 23Catalog Number Explanation 10CE Conformity 39Checklist, Start-Up 45, 46Circuit Breakers
Input 21Comm Loss Fault 117Command Sources for Start and Speed 37Contactors, Input 28Control, 2 and 3 Wire 32, 36Conventions, Manual 8Cover, Opening 12
DDimensions
Drive 136Minimum Clearances 15
Display 45, 48, 49, 50, 51, 52, 53Display Group Parameters 58, 79Distribution Systems, Ungrounded 18Drive Frame Size 136Drive Grounding 19Drive Overload Fault 116Drive Ratings 10, 121DriveExecutive 55
EEarthing, see GroundingEMC/RFI
Grounding, Filter 20Interference 39
ESD, Static Discharge 9
FFan Fdbck Loss Fault 116
FaultsAnalog Input Loss 116Auto Rstrt Tries 116Auxiliary Input 115Comm Loss 117Drive Overload 116Fan Fdbck Loss 116Function Loss 117Ground Fault 116Heatsink OvrTmp 115HW OverCurrent 116I/O Board Fail 45, 117Input Phase Loss 116Load Loss 116Motor Overload 115Motor Stalled 115Net Loss 116OverVoltage 115Parameter Checksum 117Params Defaulted 116Phase Short 116Phase to Ground Short 116Power Loss 115Power Unit 116SW OverCurrent 116UnderVoltage 115
Filter, RFI 20Frame Designations 136Function Loss Fault 117Fuses
Input 21Ratings 121
GGeneral Precautions 9, 55Ground Fault 116Grounding
Filter 20General 19
HHeatsink OvrTmp Fault 115HW OverCurrent Fault 116
II/O
Wiring 28Wiring Examples 32, 36
I/O Board Fail Fault 45, 117Input Contactor 28Input Fusing 21Input Phase Loss Fault 116Input Power Conditioning 19Installation 11Integral Keypad 47Interference, EMC/RFI 39
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 191
Index
KKeypad 47
LLEDs 45, 48, 49, 50, 51, 52, 53Load Loss Fault 116
MMetasys N2
point map 177, 184Minimum Clearances 15Motor Cable Length 24Motor Overload Fault 115Motor Stalled Fault 115motor starter 21Mounting Options and Clearances 15MOVs 18
NNet Loss Fault 116
OOpening the Cover 12Operator Interface 47OverVoltage Fault 115
PParameter
Types 55Parameter Checksum Fault 117Parameters
Display Group 58, 79Program Group 61Terminal Block Group 66
Params Defaulted Fault 116PE Ground 20Phase Short Fault 116Phase to Ground Fault 116point map
Metasys N2 177, 184Power Cables/Wiring 22Power Conditioning, Input 19Power Connections, Single-Phase 128Power Loss Fault 115Power Unit Fault 116Powering Up the Drive 45, 46Precautions, General 9, 55Product Selection 129Program Group Parameters 61
RRatings 121Reflective Wave Protection 24Removing Cover 12Repeated Start/Stop 28Repeated Start/Stop Precautions 28RFI, see EMC/RFIRWR (Reflective Wave Reducer) 24
SSafety Ground 20Shielded Power Cables 23Short Circuit Protection 21Single-Phase Input Power Connections 128Start and Speed Reference Selection and
Control 37, 38Start/Stop, Repeated 28Start-Up Checklist 45, 46Static Discharge, ESD 9Status LEDs 45, 48, 49, 50, 51, 52, 53Supply Source, AC 18SW OverCurrent Fault 116System Grounding 19
TTerminal Block
I/O 28Power 27
Terminal Block Group Parameters 66Three Wire Control 32, 36Two Wire Control 32, 36
UUnderVoltage Fault 115Ungrounded Supply 18Unshielded Power Cables 23
WWiring 11
Block Diagram 29, 30, 31, 32I/O 28I/O Examples 32, 36Power 22
192 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Publication 22C-UM001J-EN-E - January 2017Supersedes Publication 22C-UM001I-EN-P - August 2014 Copyright © 2017 Rockwell Automation, Inc. All rights reserved.
Rockwell Automation SupportUse the following resources to access support information.
Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/pcdc.page
.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Software, PowerFlex, DriveExecutive, SCANport and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.