Item Clause/ Section
Comments (Reviewer) Reviewer
Initials Action Undertaken (Originator)
Close Out(Y/N)
1 Liquid Check Vapor Pressure CLJOC Noted and revise to KPa in next revision Y
2 Welding and Repair, material specification
Update CLJOC
This section is to specify the alternative method for welding and material inspection, it is not compulsory by API 610, but is optional only. This option is not necessary. This is applicable only if specified by Purchaser.
Y
3 Note
Coupling guard instead of Coupling CLJOC Noted and Incorporated in next revision Y
4 Motor Datasheet Temperature Rise : check CLJOC We have checked already. Temperature rise from -20 deg C to 40 deg C is correct. Y
5 Motor Datasheet Max sound pressure level : 79 instead of 85
CLJOC Noted and Incorporated in next revision Y
6 Motor Datasheet Max S.C.KVA@ Motor Bus : 30 kA instead of 20 kA
CLJOC 20 kA as latest motor datasheet. Y
7 Motor Datasheet Starting Method : Soft Starter CLJOC Noted and Incorporated in next revision Y
8 Motor Datasheet Update for Starting section CLJOC Vendor data is not available till now. Y
9 Motor Datasheet Mounting : Horizontal CLJOC Noted and Incorporated in next revision Y
10 Mechanical Seal Check for consistency CLJOC We have checked already. Seal arrangement is 1CW-FX. The seal faces is CS and Reaction Bonded Silicon Carbide. Seal chamber is Floating Throat Bushing.
Y
Equipment Title: COOLING WATER CIRCULATION PUMPS 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP
PBE-4915 A/B
2 C 20-07-15
3 D Approved for Purchase 28-07-15
Issued for Review ( Incorporated proposed vendor data )
REVISION RECORD SHEET
No. Rev. No Date of Revision
1 B 28-01-15Approved for Design
D
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Tag No.: Sheet: 2 of 16
Equipment Title:
Type:
Equipment Tag No.:
1
2 ROTATION: (VIEWED FROM COUPLING END) CW CCW MANUFACTURER'S STANDARD OTHER (SEE BELOW)
3 PUMP TYPE: (4.1) SPECIFICATION NO.
4 OH2 OH3 OH6 OTHER_____________ PUMP:
5 CASING MOUNTING: PRIMER
6 CENTERLINE IN-LINE OTHER_____________ FINISH COAT
7 BASEPLATE: (6.3.17)
8 CASING TYPE: PRIMER
9 SINGLE VOLUTE MULTIPLE VOLUTE DIFFUSER FINISH COAT
10 CASE PRESSURE RATING: DETAILS OF LIFTING DEVICES(6.3.20)
11 OH6 PUMP SUCTION REGION DESIGNED FOR MAWP (5.3.6) SHIPMENT: (7.4.1)
12 MAX. ALLOWABLE WORKING PRESSURE (bar) DOMESTIC EXPORT EXPORT BOXING REQUIRED
13 @ (°C) OUTDOOR STORAGE MORE THAN 12 MONTHS
14 HYDROTEST PRESSURE (bar) SPARE ROTOR ASSEMBLY PACKAGED FOR:
15 NOZZLE CONNECTIONS: (5.4.2) HORIZONTAL STORAGE VERTICAL STORAGE
16 TYPE OF SHIPPING PREPARATION
17
18 SUCTION HEATING AND COOLING
19 DISCHARGE HEATING JACKET REQ'D. (5.8.9)
20 COOLING REQ'D.
21 PRESSURE CASING AUX. CONNECTIONS: (5.4.3) COOLING WATER (C.W.) PIPING PLAN (6.5.3.1)
22 C.W. PIPING:
23 DRAIN 1 1" PIPE TUBING; FITTINGS
24 VENT C.W. PIPING MATERIALS:
25 PRESS. GAUGE S. STEEL C. STEEL GALVANIZED
26 TEMP. GAUGE COOLING WATER REQUIREMENTS:
27 WARM-UP BEARING HOUSING (m3/h)
28 BALANCE / LEAK-OFF HEAT EXCHANGER (m3/h)
29 CYLINDRICAL THREADS REQUIRED (5.4.3.3) TOTAL COOLING WATER (m3/h)
30 ROTOR: HEAT PIPING: STEAM OTHER
31 COMPONENT BALANCE TO ISO 1940 G1.0 (5.9.4.4) HEATING PIPING: TUBING PIPE
32 COUPLINGS: (6.2.2) ( Note 16 ) BEARINGS AND LUBRICATION ( Note 15 )
33MANUFACTURER MODEL BEARING (TYPE/NUMBER) (5.10.1): ( Note 15 )
34 RATING (kW per100 r/min) RADIAL /
35 SPACER LENGTH 178 (mm) SERVICE FACT. 2 THRUST /
36 COUPLING BALANCED TO ISO 1940-1 G6.3 (6.2.3) LUBRICATION (5.11.3, 5.11.4):
37 COUPLING WITH PROPRIETARY CLAMPING DEVICE (6.2.11) GREASE OIL FLINGER
38 COUPLING PER ISO 14691 (6.2.4) PURE OIL MIST PURGE OIL MIST
39 COUPLING PER ISO 10441 (6.2.4) CONSTANT LEVEL OILER PREFERENCE (5.10.2.2):
40 COUPLING PER API 671 (6.2.4) ASME B15.1 OIL VISC. ISO GRADE
41 NON-SPARK COUPLING GUARD (6.2.14c) INSTRUMENTATION
42 COUPLING GUARD STANDARD PER (6.2.14a) ACCELEROMETER(S) (6.4.2.1)
43 BASEPLATES: PROVISION FOR MOUNTING ONLY (5.10.2.11)
44 API BASEPLATE NUMBER VTA (ANNEX D) FLAT SURFACE REQ'D (5.10.2.12)
45 NON-GROUT CONSTRUCTION (6.3.13) TEMP. GAUGES (WITH THERMOWELLS) (8.1.3.6)
46 OTHER Common baseplate for pump and driver PRESSURE GAUGE TYPE
47 MECHANICAL SEAL: (5.8.1)
48 SEE ATTACHED ISO 21049/API 682 DATA SHEET
49 REMARKS:
50
51 MASSES (kg)
52 PUMP 771
53 BASEPLATE 771
54 DRIVER VTA
55 TOTAL VTA
56
Revis
ion
Jonh Crane
TYPE
FF
Ball Single
SIZE FLANGE RATING FACING
Ball Single
10" ( VTC ) ASME #300 RF SIDE
10" ( VTC ) ASME #300 RF TOP
POSITION
(IN)
36.75
55.16
D
PBE-4915 A/B Sheet: 4 of 16
NO. SIZE (DN)
CONSTRUCTION SURFACE PREPARATION AND PAINT
TSKS-0230-X077-1778
(VTC)
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION
PUMPS
COOLING WATER CIRCULATION PUMPS Document No.: 2014-4849-1M-1006
API CENTRIFUGAL PUMP Revision:
Equipment Title:
Type:
Equipment Tag No.:
1
2 ROTATION: (VIEWED FROM COUPLING END) CW CCW MANUFACTURER'S STANDARD OTHER (SEE BELOW)
3 PUMP TYPE: (4.1) SPECIFICATION NO.
4 OH2 OH3 OH6 OTHER_____________ PUMP:
5 CASING MOUNTING: PRIMER
6 CENTERLINE IN-LINE OTHER_____________ FINISH COAT
7 BASEPLATE: (6.3.17)
8 CASING TYPE: PRIMER
9 SINGLE VOLUTE MULTIPLE VOLUTE DIFFUSER FINISH COAT
10 CASE PRESSURE RATING: DETAILS OF LIFTING DEVICES(6.3.20)
11 OH6 PUMP SUCTION REGION DESIGNED FOR MAWP (5.3.6) SHIPMENT: (7.4.1)
12 MAX. ALLOWABLE WORKING PRESSURE (bar) DOMESTIC EXPORT EXPORT BOXING REQUIRED
13 @ (°C) OUTDOOR STORAGE MORE THAN 12 MONTHS
14 HYDROTEST PRESSURE (bar) SPARE ROTOR ASSEMBLY PACKAGED FOR:
15 NOZZLE CONNECTIONS: (5.4.2) HORIZONTAL STORAGE VERTICAL STORAGE
16 TYPE OF SHIPPING PREPARATION
17
18 SUCTION HEATING AND COOLING
19 DISCHARGE HEATING JACKET REQ'D. (5.8.9)
20 COOLING REQ'D.
21 PRESSURE CASING AUX. CONNECTIONS: (5.4.3) COOLING WATER (C.W.) PIPING PLAN (6.5.3.1)
22 C.W. PIPING:
23 DRAIN 1 1" PIPE TUBING; FITTINGS
24 VENT C.W. PIPING MATERIALS:
25 PRESS. GAUGE S. STEEL C. STEEL GALVANIZED
26 TEMP. GAUGE COOLING WATER REQUIREMENTS:
27 WARM-UP BEARING HOUSING (m3/h)
28 BALANCE / LEAK-OFF HEAT EXCHANGER (m3/h)
29 CYLINDRICAL THREADS REQUIRED (5.4.3.3) TOTAL COOLING WATER (m3/h)
30 ROTOR: HEAT PIPING: STEAM OTHER
31 COMPONENT BALANCE TO ISO 1940 G1.0 (5.9.4.4) HEATING PIPING: TUBING PIPE
32 COUPLINGS: (6.2.2) ( Note 16 ) BEARINGS AND LUBRICATION ( Note 15 )
33MANUFACTURER MODEL BEARING (TYPE/NUMBER) (5.10.1): ( Note 15 )
34 RATING (kW per100 r/min) RADIAL /
35 SPACER LENGTH 178 (mm) SERVICE FACT. 2 THRUST /
36 COUPLING BALANCED TO ISO 1940-1 G6.3 (6.2.3) LUBRICATION (5.11.3, 5.11.4):
37 COUPLING WITH PROPRIETARY CLAMPING DEVICE (6.2.11) GREASE OIL FLINGER
38 COUPLING PER ISO 14691 (6.2.4) PURE OIL MIST PURGE OIL MIST
39 COUPLING PER ISO 10441 (6.2.4) CONSTANT LEVEL OILER PREFERENCE (5.10.2.2):
40 COUPLING PER API 671 (6.2.4) ASME B15.1 OIL VISC. ISO GRADE
41 NON-SPARK COUPLING GUARD (6.2.14c) INSTRUMENTATION
42 COUPLING GUARD STANDARD PER (6.2.14a) ACCELEROMETER(S) (6.4.2.1)
43 BASEPLATES: PROVISION FOR MOUNTING ONLY (5.10.2.11)
44 API BASEPLATE NUMBER VTA (ANNEX D) FLAT SURFACE REQ'D (5.10.2.12)
45 NON-GROUT CONSTRUCTION (6.3.13) TEMP. GAUGES (WITH THERMOWELLS) (8.1.3.6)
46 OTHER Common baseplate for pump and driver PRESSURE GAUGE TYPE
47 MECHANICAL SEAL: (5.8.1)
48 SEE ATTACHED ISO 21049/API 682 DATA SHEET
49 REMARKS:
50
51 MASSES (kg)
52 PUMP 771
53 BASEPLATE 771
54 DRIVER VTA
55 TOTAL VTA
56
Revis
ion
Jonh Crane
TYPE
FF
Ball Single
SIZE FLANGE RATING FACING
Ball Single
10" ( VTC ) ASME #300 RF SIDE
10" ( VTC ) ASME #300 RF TOP
POSITION
(IN)
36.75
55.16
D
PBE-4915 A/B Sheet: 4 of 16
NO. SIZE (DN)
CONSTRUCTION SURFACE PREPARATION AND PAINT
TSKS-0230-X077-1778
(VTC)
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION
PUMPS
COOLING WATER CIRCULATION PUMPS Document No.: 2014-4849-1M-1006
API CENTRIFUGAL PUMP Revision:
Equipment Title:
Type:
Equipment Tag No.:
1 SPARE PARTS (TABLE 18) QA INSPECTION AND TESTING (CONT.)
2 START-UP NORMAL MAINTENANCE TEST NON-WIT WIT OBSERVE
3 SPECIFY OPERATION SPARE HYDROSTATIC (7.3.2)
4 PERFORMANCE (7.3.3)
5 OTHER PURCHASER REQUIREMENTS NPSH (7.3.4.2) (ONE PUMP ONLY)
6 COORDINATION MEETING REQUIRED (9.1.3) RETEST ON SEAL LEAKAGE (7.3.3.2d)
7 MAXIMUM DISCHARGE PRESSURE TO INCLUDE (5.3.2) RETEST REQUIRED AFTER FINAL
8 MAX RELATIVE DENSITY HEAD ADJUSTMENT (7.3.3.5b)
9 MAX DIA. IMPELLERS AND/OR NO OF STAGES COMPLETE UNIT TEST (7.3.4.3)
10 OPERATION TO TRIP SPEED SOUND LEVEL TEST (7.3.4.4)
11 CONNECTION DESIGN APPROVAL (5.12.3.4) CLEANLINESS PRIOR TO FINAL
12 INERT GAS INHIBITED STORAGE - SPARE CARTRIDGE (8.2.8.4) ASSEMBLY (7.2.2.2)
13 TORSIONAL ANALYSIS REQUIRED (5.9.2.1) NOZZLE LOAD TEST (6.3.6)
14 TORSIONAL ANALYSIS REPORT (5.9.2.6) CHECK FOR CO-PLANAR
15 PROGRESS REPORTS (9.3.3) MOUNTING PAD SURFACES (6.3.3)
16 OUTLINE OF PROCEDURES FOR OPTIONAL TESTS (9.2.5) MECHANICAL RUN UNTIL OIL
17 ADDITIONAL DATA REQUIRING 20 YEARS RETENTION (7.2.1.1f) TEMP. STABLE (7.3.4.7.1)
18 LATERAL ANALYSIS REQUIRED (8.2.4.1 / 8.2.4.1.3) 4 HR. MECHANICAL RUN AFTER
19 DYNAMIC BALANCE ROTOR (8.2.4.2) OIL TEMP. STABLE (7.3.4.7.3)
20 PIPING AND APPURTENANCES 4 HR. MECH. RUN TEST(7.3.4.7.2)
21 MANIFOLD PIPING TO SINGLE CONNECTION (6.5.1.6) TRUE PEAK VELOCITY DATA (7.3.3.4d)
22 VENT DRAIN COOLING WATER BRG HSG RESONANCE TEST (7.3.4.6)
23 MOUNT SEAL RESERVOIR OFF BASEPLATE (6.5.1.4) REMOVE / INSPECT HYDRODYNAMIC
24 FLANGES REQ'D IN PLACE OF SOCKET WELD UNIONS (6.5.2.8) BEARING AFTER TEST (8.2.7.5)
25 INSTALLATION LIST IN PROPOSAL (9.2.3L) AUXILIARY EQUIPMENT TEST (7.3.4.5)
26 CONNECTION BOLTING CHARPY TEST (EN 13445/ASME VIII))
27 PTFE COATING ASTM A153 GALVANIZED
28 PAINTED SS
29
30 SHOP INSPECTION (7.1.4) VENDOR KEEP REPAIR AND HT RECORDS (7.2.1.1c)
31 PERFORMANCE CURVE APPROVAL VENDOR SUBMIT TEST PROCEDURES (7.3.1.2 / 9.2.5)
32 TEST WITH SUBSTITUTE SEAL (7.3.3.2b) VENDOR SUBMIT TEST DATA WITHIN 24 HOURS (7.3.3.3e)
33 MATERIAL CERTIFICATION REQUIRED (5.12.1.8) INCLUDE PLOTTED VIBRATION SPECTRA (5.9.3.3)
34 CASING IMPELLER SHAFT RECORD FINAL ASSEMBLY RUNNING CLERANCES
35 OTHER Note 6 COMPLETION OF INSPECTION CHECK LIST (7.1.6)
36 CASTING REPAIR PROCEDURE APPROVAL REQ'D (5.12.2.5)
37 INSPECTION REQUIRED FOR CONNECTION WELDS (5.12.3.4e)
38 MAG PARTICLE LIQUID PENETRANT
39 RADIOGRAPHIC ULTRASONIC
40 INSPECTION REQUIRED FOR CASTINGS (7.2.1.3 / 5.12.1.5)
41 MAG PARTICLE LIQUID PENETRANT
42 RADIOGRAPHIC ULTRASONIC
43 HARDNESS TEST REQUIRED: (7.2.2.3)
44 ADDITIONAL SUBSURFACE EXAMINATION FOR 7.2.1.3
45 FOR
46 METHOD
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Re
vis
ion
Sheet:
2014-4849-1M-1006
D
5 of 16
QA INSPECTION AND TESTING
REMARKS
PBE-4915 A/B
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
COOLING WATER CIRCULATION PUMPS
API CENTRIFUGAL PUMP
Document No.:
Revision:
Equipment Title: COOLING WATER CIRCULATION PUMPS 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP D
PBE-4915 A/B
1 PRESSURE DESIGN CODES WELDING REQUIREMENTS PURCHASER DEFINED MATERIAL IN SECTIONS
2 APPLICABLE TO: PROPOSALS PURCHASE AS BUILT
3 UNIT 2 (TWO) x 100% COOLING WATER CIRCULATION PUMPS
4 SERVICE COOLING WATER
5 NOTES: INFORMATION BELOW TO BE COMPLETED: BY PURCHASER BY MANUFACTURER BY MANUFACTURER OR PURCHASER
6
7 THESE REFERENCES MUST BE LISTED BY THE MANUFACTURER
8 CASTING FACTORS USED IN DESIGN (5.3.4) (TABLE 3)
9 SOURCE OF MATERIAL PROPERTIES
10
11 THESE REFERENCES MUST BE LISTED BY THE PURCHASER. (DEFAULT TO TABLE 10 IF NO PURCHASER PREFERENCES STATED)
12 ALTERNATE WELDING CODES AND STANDARDS (5.12.3.1)
13 Welding Requirements (Applicable Code or Standard) Purchaser Defined Default per Table 10
14 Welder Operator Qualification
15 Welding Procedure Qualification
16 Non-pressure retaining structural welding such as base plate or supports
17 Magnetic particle or liquid penetrant examination of the plate edges
18 Postweld heat treatment
19 Post weld heat treatment of casing fabrication welds
20
21 THESE REFERENCES MUST BE LISTED BY THE PURCHASER. (DEFAULT TO TABLE 13 IF NO PURCHASER PREFERENCES STATED)
22 ALTERNATIVE MATERIAL INSPECTIONS AND ACCEPTANCE CRITERIA (SEE TABLE 13)
23 Type of Inspection Methods Fabrications Castings
24 Radiography
25 Ultrasonic Inspection
26 Magnetic Particle Inspection
27 Liquid Penetrant Inspection
28
29
30
31
32
33
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Tag No.: Sheet:
Re
vis
ion
6 of 16
REMARKS
PRESSURE VESSEL DESIGN CODE REFERENCES
WELDING AND REPAIRS (5.12.3)
MATERIAL INSPECTION (7.2.2.1) (7.2.1.3)
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
Equipment Title: COOLING WATER CIRCULATION PUMPS 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP D
PBE-4915 A/B
1 1) VENDOR to complete the pump data sheet. VTC : Vendor to confirm.
2 2) Motors shall be suitable for auto-start with discharge valve open and also for end of curve operation.
4 3) Deleted
5
6 4) Deleted
7
8 5) Nozzles connection to pump casing shall be subject to 100% MPI/DPI and 10% minimum Radiographic / Ultrasonic Inspection.
9 6) Certified Material Test Report (CMTR) shall be provided by VENDOR. Casing, impeller, shaft, seal wearing and base plate will be cert 3.1
10 7) Deleted
11 8) The pump shall be designed for the wind and transportation load as specified in COMPANY Datasheet 2014-4800-9M-0010,
12 "Environmental Conditions and Utility Available Datasheet".
13 9) * : VENDOR to advise.
14 10) Pump shall be in compliance with API 610 and COMPANY Specification : 2014-4800-1L-0006, "API Centrifugal Pump Specification".
15 11) Deleted
16 12) Deleted
17 13) Refer P&ID 2014-4849-01-0064 " Cooling Water Circulation Pump "
18 14) Material of other components as below :
19 - Motor casing : Cast iron
20 - Base plate : Fabricated Steel
21 - Casing stud & nuts : A 193 Gr B7 4140, A194 Gr 2H
22 - Coupling Guard: Brass
23 15) Pump bearing housing shall be rigid shell molded vast steel construction.
24 Bearing housing shall be sealed by INPRO seal type and seal parts material shall be non-sparking type.
25 16) Coupling hubs shall be supplied with zinc or manganese phosphate finish. Hub bolts shall be ISO Gr12.9 Alloy Steel.
26 Coupling hub shall be heated and fitted into shaft with key
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
Equipment Tag No.: Sheet:
Re
vis
ion
7 of 16
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Title: COOLING WATER CIRCULATION PUMP - MOTOR Document No.: 2014-4849-1M-1006
Type: MEDIUM VOLTAGE MOTOR Revision: D
Equipment Tag No.: ZDE - 4915 A/B Sheet: 8 of 16
By Supplier if not provided by Purchaser By Supplier Option- check mark indicates selection
1
2 Basic Data Starting Continued:
3 Type of Motor General Purpose Special Purpose No. of Cold/Hot starts per hour
4 Volts Phase Hertz P.F at starting
5 Rated Output Service Factor Starting current @ 100% Voltage
6 Fault Withstand Poles Starting current @ 80% Voltage
7 Insulation Class and Type Starting time @ 100% Voltage
8 Temperature Rise : ºC Above ºC Ambient Starting time @ 80% Voltage
9 @ SF BY: Resistance RTD Load, PU 0.50 0.75 1.0
10 Min % Overspeed Current, Amp
11 Bearing Type: Hydrodynamic Antifriction Percent Efficiency
12 Max Driven-Equipment Vertical Thrust : Percent Power Factor
13 Duty type (e.g S1 for "Continuous") : Speed, RPM
14 Differential Protection To Be Applied Mounting :
15 Manufacturer SO Frame size Horizontal Vertical Shaft Up Shaft Down
16 Site Data Foot Mounted Flange Mounted. Type of mounting
17 Area Classification Mounting Position
18 Zone 2 Group IIA Non-Classified Baseplate Furnished By
19 Ignition Temperature ºC Temp. Class Soleplate Furnished By
20 Elevation M Enclosure :
21 Ambient Temperature: Max ºC Min ºC Open-DripProof IP56 IP68
22 Relative Humidity: Max % Min % Weather Protected Type I Type II
23 Indoor Outdoor Heated Unheated TEFC TEWAC IC 411
24 Roof Over Motor No Roof Over Motor Explosion Proof ( Exd ) Other Type
25 Non-Massive Foundation Description TEAAC-Tubes Copper Copper Alloy
26 Aluminum Stainless Steel Aluminum Alloy
27 Max Sound Pressure Level dBA AISI 300 Series Hardware
28 Unusual Conditions: TEWAC Heat Exchanger:
29 Abrasive Dust Tube Material
30 External Forces & Moments Tube Construction Double Tube Single Tube
31 Seismic loading Air Temperature Sensor Yes No
32 Corrosive Agents RTD Type TC Type
33 Other Cooling Water Conditions Yes No
34 Electric System Conditions: If No, Specify Differences
35 Max S.C. KVA @ Motor Bus
36 I²t Let-Through Energy Flow Sensor Local Indicator
37 Min S.C. KVA @ Motor Bus Outer Tube on Double Tube Coolers Leak Detection
38 X/R Ratio Type
39 Type of System Earthing Resistance Reactance Drive System:
40 UnEarthed Solid Direct Connected Gear
41 Earth Fault Amperes Type of Coupling
42 Starting : Starting Method: Furnished By
43 Torques in Excess of IEC 60034-12 Rotation Required by Driven Equipment When Facing Motor
44 Full Voltage % Reduced Voltage & Type Opposite Drive End: Clockwise CounterClockwise
45 Loaded (100%) Partially Loaded % Driven Equip. Wk² kg-m² @ RPM
46 Other Load Re-Acceleration Rq'd. Yes No
47 Load Curve If Yes, Provide:
48 Voltage at Locked Rotor Min % of Rated: Max Voltage Interruption (Cycles)
49 Maximum Number of Full-Voltage Starts Per Hour Voltage @ Motor Terminals on Reclosure
50 Capability in Excess of IEC 60034-12 Load Speed-Torque Reference Curve No.
51 Specify Other
Revis
ion
4160±10%
SS
3 cold, 2 hot
N/A
N/A
Driven Equipment Manufacturer
10 A
Note 2 Note 2
80
N/A
None ( See below)
Salt Laden Moisture
20 kA for 0.25 sec.
TBA
79 @ 1 M
N/A
No
19.5
35 19
100 80
Offshore Platform
No
WEG
Equipment Mfgr.
T3
S1
N/A
F, VPI, Enduraseal (See Note 4)
40 -20
1.0 0.0 0.25
Note 11 1
4
MOTOR DESIGN DATA
3 60
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
Equipment Title: COOLING WATER CIRCULATION PUMP - MOTOR Document No.: 2014-4849-1M-1006
Type: MEDIUM VOLTAGE MOTOR Revision: D
Equipment Tag No.: ZDE - 4915 A/B Sheet: 9 of 16
1
2 Reciprocating Compressor Load: Miscellaneous (Continued):
3 Crank-Effort Diagram Curve No. List of Materials to be Identified with Applicable ANSI, ASTM, or
4 Miscellaneous: ASME Numbers :
5 Special Low-Temperature Material Requirements :
6
7 Evaluation factor (EF) $/KW Special Identification :
8 Federal, State, or Local Codes or Special Rules :
9
10
11
12 Winding Temperature Detectors : Vibration Detectors (Continued):
13 RTD Type: Pt 100 No. / Phase Bearing Housing Seismic Sensors N/A
14 Resistance Material Ohms Provisions Only Installed
15 3-Wire 2-Wire Earth 1 Lead Yes No Sensor Type Model
16 Other Output Transducer Model
17 Note 6 No. per Bearing Location (H,V,A)
18 Provision Only Per API 670 Pt 100 Vibration Switch Manual Reset Electric Reset
19 RTD Type: Material Ohms Switch Type Model
20 Other Space Heaters : Note 7
21 Terminal Head or Box Volts Phase Hertz
22 Bearing Housing Temp. Indicators Rq'd. : Max Sheath Temperature ºC
23 Lubrication System: Terminal Junction Box (Note 5)
24 Self Lube Forced Lube Box Location Oversized Box
25 Bearing Oil Rings for Coastdown Required Main Supply Leads: Conductor Size Type
26 Oil Mist Insulation No. Per Motor
27 Bearing Constant-Level Sight Feed Oilers Required : Enter From Above Below Side (R/L)
28 Type Gland Plate Drilled Undrilled
29 Special Seals for Gas Purge Current Transformers for Differential Protection ( N/A )
30 Lube System Common with Driven Equipment Accuracy Class
31 Supplied By Mounted By
32 Type of Oil Pressure PSIG Quantity Ratio
33 Pressure Lube System Surge Capacitors
34 Per API 614 Manufacturer's Standard Mounted By 0.25 m F/Phase 0.50 m F/Phase
35 Main Oil Pump Required Surge Arresters :
36 Standby Oil Pump Required Mounted By Rated KV
37 Filter Element : Phase Current Transformers for Local Ammeter N/A
38 Manufacturer Model No. Accuracy Class
39 Duplex Oil Filters Req'd. Oil Cooler Req'd. Quantity Ratio
40 Oil Heater Required Voltage Transformers for Local Voltmeter
41 Vibration Detectors : * See Note 3 Accuracy Class
42 Non-Contact Probes Mounted By
43 Provisions Only Installed Quantity Ratio
44 Probe Type Size Fuses Required
45 Transmitter Model Bushing Studs or Receptacles
46 No. per Bearing Two Four Space for Stress Cones
47 Thermal Insulation
Re
vis
ion
MECHANICAL DATA SHEET FOR COOLING WATER
CIRCULATION PUMPS
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
N/A
N/A
Yes
N/A
* Note 3 * Note 3
EPR * Note 3
N/A
Top TYPE II
* Note 3 3-C ARM'D
230 V 1 60
Bearing Temperature Detectors :
Platinum 100
ACCESSORY EQUIPMENT
3 / 3
Platinum 100
N/A
Per Specification 2014-4869-3L-0004
MOTOR DESIGN DATA (CONTINUED)
NONE
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Equipment Title: COOLING WATER CIRCULATION PUMP - MOTOR Document No.: 2014-4849-1M-1006
Type: MEDIUM VOLTAGE MOTOR Revision: D
Equipment Tag No.: ZDE - 4915 A/B Sheet: 10 of 16
1
2 Terminal Junction box (Continued): Coupling
3 Breathers Taper Fit Cylindrical Fit
4 Drains Coupling Supplied By
5 Provisions for Purging Vendor Model
6 Removable Links Coupling Data Sheet Numbers
7 Silver-Plated Bus Joints Silver-plated Cu bus bars Mounted By: Motor Mfr Driven-Equip Mfr Purchaser
8 Earth Bus Internal and External Idling Adapter/Mass Moment Simulator Supplied By
9 Fault Withstand Coupling to be Used for Test Contract Shop None
10 Other Terminal Box Requirements Insulated Standoffs Painting:
11 Oil Resistant Leads Vendor's Standard Extra Cost @ Shipment
12 Space Heaters : User's Special Paint
13 Volts Phase 1 Hertz 60 Shipment:
14 Max Sheath Temperature ºC Domestic Export
15 Air Filters : Export Boxing Required
16 Provisions Only - WP I Required - WP I or WP II Outdoor Storage for More Than 12 months
17 Filter Type Special Shipping Bearings
18 Differential Pressure Device Required Mounted on Skid
19 Type Other Requirements:
20 Bearing Heaters : Any External Forces on Motor Housing That May Affect Site
21 Type Performance
22 Volts Phase Hertz Data Required on Current Variation and Effeciency for Variable
23 Miscellaneous Torque Load
24 Epoxy Grout to be Used Type Vendor's Representative to be Present During Initial
25 Nameplate Material Stainless Steel Monel Equipment Alignment Check
26 Special Nameplate for Identification Motor Tag Number Special Weather Protection Requirements
27 Quantity of Special Tools Required Vendor's Review and Comments on the Purchaser's Foundation
28 Proof of Non-Sparking, Corrosion-Resistant Fan Drawings
29 Shaft Seals of Electrically Non-Conducting Materials Guaranteed Eff. & PF Req'd.
30 Location of Aux. Junction Boxes Erection Supervisor Costs
31 MOC of Aux. Junction Boxes Stainless Steel Assembly Photographs Required
32 Switches with Contacts Rated for DC Yes No Motor Thermal Time Constant (minutes)
33 Vendor Documents
34 This data sheet duly filled up Thermal Limit Curves (Hot & Cold)
35 Certificate of Compliance Motor and Accessory Connection Diagrams
36 Certified GA Drawing and Dimension Sheet Equivalent Circuit Data
37 Terminal Box and accessories Drawing RTD Settings
38 Speed vs. Torque and Current Curves Test Certificates
39 Torque vs. slip and current curves Instruction Manual
40
41
Re
vis
ion
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION
PUMPS
No
Yes
No
No
No
No
No
230V, Note 7
Yes
Yes
N/A
Zone 2, IIA, T3, IP56 min
ACCESSORY EQUIPMENT (CONTINUED)
Yes
Yes Equipment Mfgr
John Crane
20 Ka 0.25 sec
Equipment Title: COOLING WATER CIRCULATION PUMP - MOTOR Document No.: 2014-4849-1M-1006
Type: MEDIUM VOLTAGE MOTOR Revision: D
Equipment Tag No.: ZDE - 4915 A/B Sheet: 11 of 16
1
2 Required Witnessed Observed
3 Acceptance Criteria
4 Lateral Critical Speed Analysis By
5 Design Review Meeting
6 Torsional Analysis By
7 Shop Inspection
8 Data Preservation
9 Material Certifications (for shaft)
10 Assembly, Maintenance and Running Clearances
11 Painting Deferred
12 Surface & SubSurface Inspection of Parts
13 Radiographic Test Parts:
14 Ultrasonic Test Parts:
15 Magnetic Particle Test Parts:
16 Liquid Penetrant Test Parts:
17 Hardness Test Parts:
18 Optional ASTM Tests to be Proposed by Vendor
19 Balance in Minimum of Three Planes
20 Check Balance with Half Coupling
21 Inspection for Cleanliness per API 614
22 Review of Quality Control Program
23 Stator Inspection Prior to Vacuum-Pressure Impregnation
24 Residual UnBalance Test
25 Routine Test @
26 Polarization Index Voltage: 1,000V 2,500V 5,000V @
27 Vibration Recording @
28 Stator Core Test
29 Special Surge Test on Sample Coils
30 Power Factor Tip-Up Test Wound Stator Sacrificial Coils
31 Sealed Winding Conformance Test
32 DC High-Potential Test
33 Complete Test @
34 Rated Rotor Temperature Vibration Test When Complete Test Not Specified
35 Bearing Inspection at Completion of Test
36 UnBalance Response Test
37 Bearing Housing Natural Frequency Test
38 Certified Data Prior to Shipment
39 Test Equipment Supplied By Purchaser
40 Test Equipment / Data Acquisition Accuracy to be Demonstrated Prior to Test
41 Other
42
43
44
45
46
47
48
49
Re
vis
ion
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
@ Routine Tests, Polarization Index Test and Vibration checking are included
in Complete Test.
ANALYSIS, SHOP INSPECTION, AND TESTS
Driver Equipment Manufacturer
Driver Equipment Manufacturer
1
2 POWER SYSTEM STUDY DATA (TO BE COMPLETED BY VENDOR):
3
4 i) Description:
5 1 Rated output: kW
6 2 Rated Voltage: kV
7 3 Frame size:
8 4 Base kVA: kVA
9 5 Stator resistance (R1):
10 a) at oC p.u.
11 b) at oC p.u.
12 6 Stator leakage reactance (X1): p.u.
13 7 Magnetising reactance (Xm): p.u.
14 8 Rotor standstill:
15 a) Resistance (Rs): p.u.
16 b) Reactance (Xs): p.u.
17 9 Rotor running:
18 a) Resistance (Rr): p.u.
19 b) Reactance (Xr): p.u.
20 10 Synchronous reactance (Xd): p.u.
21 11 Transient reactance (X'd): p.u.
22 12 Sub-transient reactance (X"d): p.u.
23 13 Open circuit time constant (T'do): secs.
24 14 Transient short circuit time constant (T'd): secs.
25 15 Sub-transient short circuit time constant (T"d): secs.
26 16 D.C. short circuit time constant (Ta): secs.
27 17 Inertia constant (H):
28 a) Motor: kW secs / kVA
29 b) Driven equipment: kW secs / kVA
30 18 Synchronous speed: rpm
31 19 Slip at full load: %
32
33
34
35
36 ii) Characteristics: Curve Nos.
37 1 Speed/torque curve for motor and load at 80% and 100% volts:
38 2 Current/time curve at 80% and 100% volts:
39 3 Speed/time curve at 80% and 100% volts:
40 4 Current/speed curve at 80% and 100% volts:
41 5 Power factor/speed curve at 80% and 100% volts:
42
43 Notes:
44 1. Vendor to submit certified motor dimensional drawing.
45 2. Vendor to complete the required data when applicable.
46 3. TBA : To be advised later; N/A : Not Applicable;
47 4. The insulation system shall be capable of withstanding the lightning impulse voltage as per IEC 60034-15.
48 5. Separate Terminal Boxes shall be provided for Main Power, Space Heater and RTD connections. Terminal Box / Junction Box shall be IP56 as minimum.
49 6. MV motors rated at 1200kW or greater and using hydrodynamic radial bearings shall have 2 RTD elements per bearing.
50 Vertical mounted motors shall have RTD elements on the thrust bearing.
51 7. Space heaters shall be rated at 230 VAC and Operated at 110 VAC. For Submerged motor no Space Heater required.
52 8. For MV Submersible Motor Data Sheet refer to 2014-4872-3M-0004.
53 9. Test Requirements:
54 - Type Test: Certificate only required (certification by a recognized testing authority, the test documents shall include Winding temperature rise,
55 Locked rotor current and torque tests).
56 - Performance Test: IEC60034.
57 - Routine Test: IEC60034.
58 Other tests listed in IEC 60034 and Induction Motors Specification (Medium Voltage & Low Voltage) 2014-4869-3L-0004 shall be performed.
59 10. VENDOR to fill in one motor datasheet for each typical motor.
60 11. Minimum recommend motor rating is 176 kW.
Re
vis
ion
MEDIUM VOLTAGE MOTOR Revision: D
Equipment Tag No.: ZDE - 4915 A/B Sheet: 12 of 16
Value: Tolerence (%)
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Equipment Title: COOLING WATER CIRCULATION PUMP - MOTOR Document No.: 2014-4849-1M-1006
Type:
Equipment Title: COOLING WATER CIRCULATION PUMP - MECHANICAL SEAL 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP D
PBE-4915 A/B
1 DEFAULT SELECTION DATA SUPPLIED: CUSTOMARY UNIT SI UNIT
2 INDICATES DATA COMPLETED BY PURCHASER HARDWARE SUPPLIED: CUSTOMARY UNIT SI UNIT
3 BY SEAL VENDOR STANDARD APPLICABLE: PRIMARY REFERENCE (5.2)
4 BY SEAL VENDOR OR PURCHASER SECONDARY REFERENCE (5.2)
5
6 CATEGORY SEAL CATEGORY 1 (4.1.2) SEAL CATEGORY 2 (4.1.2) SEAL CODE (ANNEX D)
7 TYPE TYPE A (3.73) TYPE B (3.74) ALTERNATE STATIONARY (TYPE A & B)
8 (CODE-CW) TYPE C (3.75) ALTERNATE ROTATING (TYPE C) SINGLE SPRING (TYPE A)
9 ARR'GT
10 1(3.2) 1CW-FX 1CW-FL DIST. FLUSH 01 11 14 23 32 51 62
11 ALTERNATE BUSH 02 13 21 31 41 61
12 LIQUID 2CW-CW FX DIST. FLUSH 01 13 23 41 62 75
13 2 (3.3) TANGENTIAL LBO CONN. 02 14 31 52 71 76
14 GAS 2CW-CS 2NC-CS FX 11 21 32 61 72
15 LIQUID 3CW-FB 3CW-BB FX 01 13 53B 61
16 3(3.4) 3CW-FF TANG.LBO 02 32 53C 62
17 GAS 3NC-BB 3NC-FF 3NC-FB 11 53A 54 74
18 SLEEVE-SHAFT DRIVE SET SCREW ONTO SHAFT ALTERNATE (6.1.3.13) - SPECIFY :
19
20
21 FKM FFKM CARBON VS SIC UNS N10276 (TYPE B) UNS N10276 UNS S31600 / S31635
22 SPIRAL-W GASKET SIC VS SIC UNS N07718 (TYPE C) OR N06455 UNS N10276
23 NBR EPM/EPDM SS - SIC RB-SIC UNS N08020 UNS S31600 UNS N08020
24 OTHER : CS VS RB SIC OTHER : OR S31635 OTHER :
25
26 SEAL VENDOR John Crane ALTERNATE SEAL FOR PUMP PERFORMANCE TEST
27 DATA REQUIREMENTS FORM (ANNEX G) DYNAMIC SEALING PRESSURE RATING (3.19) bar(g)
28 SIZE / TYPE * / 1648 STATIC SEALING PRESSURE RATING (3.74) bar(g)
29 SEAL DRAWING NUMBER MAXIMUM ALLOWABLE TEMPERATURE (3.39)oC
30 VENDOR'S SEAL CODE C2A1A MINIMUM DESIGN METAL TEMPERATUREoC
31 MODIFIED FACES FOR PUMP PERFORMANCE TEST
32
33 ASME B73.1 & 2 CYLINDRICALHXN/DVT TAPERED ISO 13709 ISO 3069-C OTHER, SPECIFY
BOLT-ON CHAMBER (6.1.2.5) SEAL CHAMBER FLUSH PORT REQ'D SEAL CHAMBER VENT REQUIRED
35 FLOATING THROAT BUSH FIXED THROAT BUSH CHAMBER HEATING /COOLING H C
36
37 PUMP DESIGN MANUFACTURER CLYDE UNION PUMP MODEL 10 x 10 x 15A FRAME/SIZE CASE M'TL A743 Gr.CF3M
38 PUMP OPERATING PRESSURE SUCTION PRESS.(RATED) bar(g) DISCHARGE PRESS. bar(g)
39 SEAL CHAMBER NORMAL * bar(g) MIN/MAX (3.41) * / * bar(g) MSSP(3.43) * bar(g)
40 SHAFT DIA. VTC mm SHAFT SPEED 1780 r/min SHAFT DIRECT. (FROM DRIVER) CW CCW
41
42 PUMPED STREAM (REFER TO PAGE 3 OF 16 FOR PROCESS CONDITION) HAZARDOUS FLAMMABLE
43 TYPE OR NAME COOLING WATER CONC'N % FLUID SOLID @ AMBIENT
44 DISSOLVE CONTAMINANT H2S ml/m3
WET SOLIDIFIES@oC POUR POINT
oC
45 Cl2 ml/m3
OTHER @ ml/m3
PUMPED STREAM SOLIDIFIES UNDER SHEAR
46 SOLID CONTAMINANT PUMP STRAM CONTAINS AGENTS THAT POLYMERIZE
47 CONCENTRATION (MASS FRACTION) SPECIFY AGENTS @ TEMP oC
48 PUMPING TEMPERATURE PUMPED STREAM CAN PLATE OUT OR DECOMPOSE:
49 MIN.oC NORM.
oC MAX
oC SPECIFY CONDITION :
50 RELATIVE DENSITY (TO WATER @25 OC) AT REF. TEMP. PUMPED STREAM IS REGULATED FOR FUGITIVE OR
51 @ NORMAL TEMPERATURE @' MAX TEMP. OTHER EMISSIONS. REGULATION LEVEL ml/m3
52 ABSOLUTE VAPOR PRESSURE AT REFERENCE TEMP. SPECIAL PUMP CLEANING PROCEDURES
53 NORMAL TEMP. bar MAX. TEMP. bar SPECIFY:
54 ATMOSPHERIC BOILING POINToC ALTERNATE PROCESS FLUIDS & CONCENTRATION
55 VISCOSITY @ NORMAL PUMPING TEMP. cP (INCL. COMMISSIONING)
56 FLUSH FLUID If flush fluid is pumpage, then flush fluid data is not required
57 TYPE OR NAME CONC'N % ABSOLUTE VAPOR PRESSURE AT REFERENCE TEMPERATURE
58 SEAL VENDOR REVIEW REQUIRED NORMAL TEMP. bar MAX. TEMP. bar
59 FLUID TEMPERATURE ATMOSPHERIC BOILING POINT.oC
60 MINoC NORMAL
oC MAX
oC VISCOSITY @ NORMAL PUMPING TEMPERATURE Pa.s
61 RELATIVE DENSITY (TO WATER @ 25 OC AT REF. TEMP. FLOWRATE REQ'D MAX/MIN / l/min
62 @ NORMAL TEMP. @ MAX. TEMP. PRESSURE REQ'D MAX/MIN / bar(g)
Re
vis
ion
13 of 16
MATERIALS (REFERENCE 6.1.6 & ANNEX C)
SECONDARY SEALS SEAL FACES METAL BELLOWS
MECHANICAL SEAL DATA
SEAL CHAMBER DATA (REFERENCE 6.1.2.4)
PUMP DATA (REFER TO PUMP DATA SHEET FOR MORE DETAIL, PAGE 3 )
6.5 12.1
FLUID DATA (FOR QUENCH, BUFFER AND BARRIER FLUID DATA, SEE NEXT PAGE)
SPRINGS METAL PARTS
SEAL SPECIFICATION - (REF CLAUSE 1.2, FIGURES 1 TO 6)
DEFAULT CONFIGURATION ALTERNATE DESIGN FLUSH PLANS (SEE ANNEX D)
BU
FF
ER
BA
RR
IER
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Tag No.: Sheet:
Equipment Title: COOLING WATER CIRCULATION PUMP - MECHANICAL SEAL 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP D
PBE-4915 A/B
1 INDICATES DATA COMPLETED BY PURCHASER BY SEAL VENDOR BY SEAL VENDOR OR PURCHASER
2
3 QUENCH MEDIUM SUPPLY TEMPERATURE MAX/MIN /oC
4 TYPE OR NAME FLOWRATE REQ'D MAX / MIN / l/min
5 BUFFER / BARRIER MEDIUM
6 TYPE OR NAME RELATIVE DENSITY (TO WATER @ 25 oC) AT REF. TEMP.
7 PURCHASER SELECTION SEAL VENDOR SELECT'N @ NORMAL TEMP @ MAX TEMP
8 SEAL VENDOR REVIEW PURCHASER REVIEW ABSOLUTE VAPOR PRESSURE AT REFERENCE TEMPER.
9 FLOW RATE REQ'D MAX / MIN / l/min @ NORMAL TEMP bar @ MAX TEMP bar
10 COOLING / HEATING REQ'D (+ OR -) kW ATMOSPHERIC BOILING POINT (LIQUID)oC
11 SUPPLY PRESSURE MAX / MIN * / * bar(g) VISCOSITY @ NORMAL TEMP. (LIQUID) Pa.s
12 FLUID OPERATING TEMPERATURE SPECIFIC HEAT CAPACITY @ CONSTANT PRESSURE
13 MINoC NORMAL *
oC MAX
oC FOR LIQUID @ NORMAL TE,MPERATURE J/Kg.K
14
15 CONTROL VOLTAGE V PHASE HERTZ COOLING H2O SUPPLY TEMP.oC Cl2 ml/m
3
16 ELECTRICAL AREA CL. GR. DIV. TEM. CLASS COOLING H2O PRESS. NORM. / DES. / bar(g)
17 DESIGN AMBIENT MIN./MAX. 19 / 35oC EXPLOSIVE AREA CLASS (DIRECTIVE 94/9/EC)
18
19 GENERAL PLAN 52 AND 53 SYSTEM - CONTINUED
20 JOINT USER / VENDOR LAYOUT OF EQUIPMENT (8.1.4) EQUIPMENT SUPPORT VENDOR ` FILLING SYSTEM VENDOR
21 SPECIAL REQUIREMENTS FOR HAZARDOUS SERVICE ASME CODE STAMP REQUIRED
22 SPECIAL CLEANING AND DECONTAMINATION REQ'TS RESERVOAR CAPACITY (8.5.4.3.1) l
23 UTILITY MANIFOLD CONNECTION REQUIRED (8.4.4) NLL TO GLAND PLATE HEIGHT (8.5.4.2.3) m
24 TYPE AND SPEC. OF HEAT TRACING (8.6.5.8) PRESSURE CASING MAWP (3.40) bar(g) @oC
25 THERMAL RELIEF VALVES REQUIRED (9.8.3) SET PRESSURE RANGE, MAX / MIN. / bar(g)
26 COOLING SYSTEM SYSTEM HOLD-UP PERIOD (PLANS 53B & 53C) DAYS
27 HEAT EXCHANGER VENDOR PRESSURE SWITCH (8.5.4.2.7) TO ACTIVE ON:
28 WATER COOLED AIR COOLED ASME B31.3 RISING PRESSURE (ARR.,2) SET @
29 EQUIPMENT REFERENCE / CODE FALLING PRESSURE (ARR.,3) SET @
30 COOLING WATER LINES VENDOR HIGH LEVEL ALARM REQUIRED (8.5.4.2.8)
31 TUBING GALVANIZED PIPING (8.4.2) FLANGED SS 316L PIPING H/Q CURVE FOR INTERNAL CIRCULATING DEVICE (8.6.2.1)
32 COOLING WATER FLOWRATE l/min TEST BASED H/Q CURVE FOR INTERNAL CIRC. DEVICE
33 SIGHT FLOW INDICATORS (8.4.3) OPEN CLOSED EXTERNAL CIRCULATING PUMP (8.6.3.1)
PLAN 11, 12, 13, 31 AND 41 PLAN 72 & 74 SYSTEM
35 CONNECTING LINES VENDOR EQUIPMENT VENDOR HIGH FLOW ALARM SWITCH (8.6.6.5)
36 TUBING PIPING (8.5.2.1) ( Note b ) PLAN 75 & 76 SYSTEM
37 RESTRICTION ORIFICE NIPPLE IN FLUSH LINE (8.5.2.3) EQUIPMENT VENDOR
38 CYCLONE SEPARATOR VENDOR HIGH LEVEL ALARM SWITCH FOR PLAN 75 (8.6.5.3) TEST CONNECTION (8.6.5.4)
39 PLAN 52 AND 53 SYSTEMS INSTRUMENTATION
40 STANDARD (FIG. D.26) ALTERNATE (FIG. D27) USER SPECIFICATION REFERENCE FOR - INSTRUMENTATION / CONTROLS
41 DIMENSIONAL VARIATIONS TO STANDARD (FIG. D26) PRESSURE GAUGES (9.4) OIL FILLED PRESSURE GAUGES (9.4.3)
42 DIMENSIONAL VARIATIONS TO ALTERNATE (FIG. D27) PRESSURE SWITCHES (9.5.2) TRANSMITTER (9.5.2.3)
43 ALTERNATE FABRICATION STANDARD LEVEL SWITCHES (9.5.3)
44 PRIMARY EQUIPMENT VENDOR HYDROSTATIC CAPACITANCE ULTRASONIC
45 VENDOR REFERENCE / CODE LEVEL INDICATORS (9.6) TRANSMITTER (9.5.3.2)
46 CONNECTING LINES VENDOR WELD PAD EXTERNAL REMOVABLE (9.6.2)
47 TUBING FLANGED SS 316L PIPING (8.5.4.4.9) FLOW INDICATOR (9.7) TRANSMITTER (9.7.2)
48
49 PURCHASER PARTICIPATION IN INSPECTION & TEST SPECIFY : 100% INSPECTION OF ALL WELDS (6.1.6.10.5.1) USING:
50 INSPECTOR'S CHECK LIST (10.1.7 & ANNEX E) MAGNETIC PARTICLE LIQUID PENETRANT
51 OPTIONAL QUALIFICATION TESTING REQ'D (10.3.1.1.2) RADIOGRAPHIC ULTRASONIC
52 PURCHASER APPROVAL REQUIRED FOR WELDED MODIFIED FACES FOR PUMP TEST (10.3.5.2.1)
53 CONNECTION DESIGNS (6.1.6.10.5.4) ALTERNATE SEAL PUMP TEST (10.3.5.2.2)
54 HARDNESS TEST (10.2.14) REQUIRED FOR :
55 NOTES a) VENDOR to complete the data sheet and advise mechanical seal construction, materials selection and seal flushing plan.
56 b) Flush pipe material shall be 316L
57
58
59
60
61
62
Re
vis
ion
14 of 16
FLUID DATA - (QUENCH, BUFFER AND BARRIER FLUID DATA, LIQUID AND GAS)
SITE AND UTILITIES (REFER TO PUMP DATA SHEET, PAGE 3 OF 16)
ACCESSORIES (CLAUSES 8 AND 9)
INSPECTION AND TESTING
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Tag No.: Sheet:
Equipment Title: COOLING WATER CIRCULATION PUMP - NOISE 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP D
PBE-4915 A/B
1 APPLICABLE TO : PROPOSALS PURCHASE AS BUILT
2 CUULONG JOINT OPERATING COMPANY
3 SU TU TRANG PIP
4 COOLING WATER
5
6 THE OVERALL MAXIMUM PERMISSIBLE SOUND LEVEL FOR THE EQUIPMENT IS SPECIFIED IN THE TABLE BELOW.
7 VENDOR SHALL COMPLETE THE TABLE BELOW.
8 ALL SOUND DATA FOR THIS TABLE IS :
9 SOUND PRESSURE LEVELS IN dB dBA (RE 0.0002 MICROBAR)
10 AT METRE FROM MAJOR EQUIPMENT BOUNDING SURFACES.
11 SOUND POWER LEVELS IN dB dBA (RE 10^-12 WATT)
12
13
14
15
16
17
18
19 VENDOR SHALL COMPLETE THE TABLE BELOW.
20 ALL SOUND DATA FOR THIS TABLE IS :
21 SOUND PRESSURE LEVELS IN dB dBA (RE 0.0002 MICROBAR)
22 AT METRE FROM MAJOR EQUIPMENT BOUNDING SURFACES.
23 SOUND POWER LEVELS IN dB dBA (RE 10^-12 WATT)
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39 DESCRIPTION OF SPECIAL DESIGN
40
41
42 DESCRIPTION OF ACOUSTIC TREATMENT
43
44
45 REMARKS :
46 a) The maximum permissible sound levels apply to the equipment over it's entire operating range.
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
Re
vis
ion
8000
4000
2000
1000
500
250
125
SPECIAL DESIGNWITH ACOUSTIC
TREATMENTFREQUENCY
(Hz)
63
1.0
OCTAVE BAND MANUFACTURER'S ESTIMATED MAXIMUM MANUFACTURER'S GUARANTEED MAXIMUM
CENTER
NORMAL DESIGN SPECIAL DESIGN
NORMAL
WITH ACOUSTIC
TREATMENTNORMAL DESIGN
85 dBA
MANUFACTURER'S ESTIMATED MAXIMUM
WITH ACOUSTIC
SOUND LEVEL DESIGN DESIGN TREATMENT DESIGN DESIGN TREATMENT
PERMISSIBLE
FOR
SPECIAL WITH ACOUSTIC NORMAL SPECIAL
SERVICE
1.0
OVERALL SOUND LEVEL DATA
OVERALL MAX.
SITE
MANUFACTURER'S GUARANTEED MAXIMUM
OCTAVE BAND SOUND LEVEL DATA
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Tag No.: Sheet: 15 of 16
Equipment Title: COOLING WATER CIRCULATION PUMP - WEIGHT 2014-4849-1M-1006
Type: API CENTRIFUGAL PUMP D
PBE-4915 A/B
1 APPLICABLE TO : PROPOSAL 1ST ESTIMATE (AFTER P.O.) DETAILED ESTIMATES AS BUILT
2 UNIT
3 RFQ / P.O. NO.
4 VENDOR
5
6
7
8
9
10 kg
11 kg
12 kg
13 kg
14
15 kg
16 kg
17 kg
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33 HXN/DVT
34
35
36
37
38 MEASUREMENT STATUS
39
40
41
42
43
44
45
46 a) VENDOR TO SPECIFY MAXIMUM EQUIPMENT / SKID DIMENSIONS.
47 b) VENDOR TO SPECIFY MINIMUM MAINTENANCE ENVELOPE DIMENSIONS.
48 c) ALL DIMENSIONS SHALL BE IN mm AND REF. POINT BE CLEARLY INDENTIFIED ON DRAWINGS AND EQUIPMENT / SKID.
49 d) PURCHASER SHALL SPECIFY THE TARGET WEIGHT UNCERTAINTY FOR EACH EQUIPMENT / SKID.
50 e) VENDOR SHALL ADVISE THE REASONS AND PROPOSE RECTIFICATION ACTIONS, IF THE WEIGHT ESTIMATE IS OUTSIDE.
51
52
53
54
55
56
57
58
Re
vis
ion
EQUIPMENT / SKID DIMENSIONS AND C.O.G. DATA
DIMENSION 'Z'
DIMENSION 'W'
REMARKS
DIMENSION 'X'
DIMENSION 'Y'
DIMENSION 'H'
EQUIPMENT / SKID ENVELOPE C.O.G LOCATION
PROPOSAL PRELIMINARY EST. DETAILED EST. AS BUILT
DIMENSION 'L'
MAINTENANCE WEIGHT OF COMPONENTS :
TRANSPORT WEIGHT
HYDROTEST WEIGHT
DRY WEIGHT 2941 ( VTC )
OPERATING WEIGHT
TARGET WEIGHT UNCERTAINTY 15% 8% 6% 2%
VENDOR WEIGHT UNCERTAINTY
SERVICE COOLING WATER
WEIGHT DATA
WEIGHT STATUS PRELIMINARY & IFC AFC AS BUILT WEIGHED
FOR CUULONG JOINT OPERATING COMPANY PBE-4915 A/B
SITE SU TU TRANG PIP
16 of 16
SU TU TRANG FULL FIELD DEVELOPMENT – PHASE 1
DETAILED ENGINEERING AND PROCUREMENT ENGINEERING
SUPPORT SERVICES
MECHANICAL DATA SHEET FOR COOLING WATER CIRCULATION PUMPS
Document No.:
Revision:
Equipment Tag No.: Sheet:
C.O.G.
'L'
'X'
FRONT
'W'
'Y'
PLANREF. POINT (DATUM)
C.O.G.
'H'
'Z'
ELEVATIONREF. POINT (DATUM)
EQUIPMENT / SKID