LV Electrical Distribution
System
Schneider Electric 2- Marketing - Pakon – 22 July 2008
Topic
1.Basic Concept2.LV Components (Design and
Select)3.Schneider Offer in LV
Schneider Electric 3- Marketing - Pakon – 22 July 2008
Topic
1.Basic Concept2.LV Components (Design and
Select)3.Schneider Offer in LV
Schneider Electric 4- Marketing - Pakon – 22 July 2008
CB1 Isc 85 kA
415 V
In 600 A
Isc 40 kA50 m cable
Workshop
Desktop
In 800 A Isc 70 kA
CB2CB3
In 2500 A
Ics 100% Icu
Service continuity needed
CB5
CB4Isc 50 kA
Isc 36 kA
Service continuity neededIn 250 A
Component in LV system
Availability
Safety&
+
Energy Efficiency
Schneider Electric 5- Marketing - Pakon – 22 July 2008
CB1 Isc 85 kA
415 V
In 600 A
Isc 40 kA50 m cable
Workshop
Desktop
In 800 A Isc 70 kA
CB2CB3
In 2500 A
Ics 100% Icu
Service continuity needed
CB5
CB4Isc 50 kA
Isc 36 kA
Service continuity neededIn 250 A
Major Components in LV system
LV Circuit Braker
LV Distribution panel
Energy Management
System
Schneider Electric 6- Marketing - Pakon – 22 July 2008
Fault พนฐานทอาจเกดขนในระบบไฟฟาได
1.Overload2.Short Circuit3.Ground/Earth fault4.Earth Leakage
Schneider Electric 7- Marketing - Pakon – 22 July 2008
ภาวะปรกตNormal
Zแหลงจายไฟฟา
โหลด
Schneider Electric 8- Marketing - Pakon – 22 July 2008
Overload
ZZ
ภาวะโอเวอรโหลด
Z
โหลด
แหลงจายไฟฟา
Schneider Electric 9- Marketing - Pakon – 22 July 2008
Normal
ZZ
ภาวะปรกต
แหลงจายไฟฟา
โหลด
Schneider Electric 10- Marketing - Pakon – 22 July 2008
Short Circuit
Z
ภาวะกระแสลดวงจร
Zแหลงจายไฟฟา
โหลด
Schneider Electric 11- Marketing - Pakon – 22 July 2008
(c)L3L2L1
L2L1
L3L2L1
L3
(d) L2L1
L3
Short Circuit Current Branch Short - circuit Currents
I"k3 k2I"
I"k1k2EI"
a) Balance Three Phase Short Circuit.b) Line to Line Short Circuit Without Earth Connection.c) Line to Line Short Circuit With Earth Connection.d) Line to Earth Short Circuit.
in Conductors and Earth
(a) (b)
ชนดของการลดวงจรประเภทตางๆ
Schneider Electric 12- Marketing - Pakon – 22 July 2008
●ตวอกษรแสดงความหมายของการตอลงดน●อกษรตวแรก ตำาแหนงการตอลงดน ณ ตำาแหนง star ของ
หมอแปลงแหลงจาย ●อกษรตวหลง: ตำาแหนงการตอลงดนของสวนนำากระแสทเปดโลง เชน
โครงของอปกรณไฟฟา●TT: เปนระบบทหมอแปลง และโครงอปกรณมหลกดนทแยกจากกน●TN: เปนระบบทหมอแปลง และโครงอปกรณมหลกดนรวมกน
– TN-S: แยกสาย N (Neutral) และ PE (Earth) ออกจากกน
– TN-C: รวมสาย N (Neutral) และ PE (Earth) ดวยกน– TN-C-S: เรมตนดวยการรวมสาย N (Neutral) และ PE
(Earth) ดวยกน จากนนจงแยกออกจากกน●IT: โครงอปกรณตอหลกดน
2nd letter1st
letter
T(earth)
N(neutral)
T(earth)
I(isolated)
TT
IT
TN
ระบบตอลงดน
Schneider Electric 13- Marketing - Pakon – 22 July 2008
TT system
RB RA
PEN
Id
RdUd
123
TN system
Ud
RB
Id
1
2
3
N
PE
TN-C TN-S
RB
123
C3 C2 C1
R3 R2 R1
IT system
Schneider Electric 14- Marketing - Pakon – 22 July 2008
Topic
1.Basic Concept2.LV Components (Design and
Select)3.Schneider Offer in LV
Schneider Electric 15- Marketing - Pakon – 22 July 2008
LV Circuit Breaker
What are function of LV Circuit Breaker? Mechanical switching device, capable of making,
carrying and breaking currents under normal
circuit conditions and also making, carrying for a
specified time and breaking currents under
specified abnormal circuit conditions such as
those of short circuit. (IEC60947-1)
Schneider Electric 16- Marketing - Pakon – 22 July 2008
Type of LV Circuit Breakers
1. MCB - Miniature Circuit Breaker0.5-125A
2. MCCB - Molded Case Circuit Breaker15-3200A
3. ACB - Air Circuit Breaker800-6300A
Schneider Electric 17- Marketing - Pakon – 22 July 2008
หลกการท Circuit Breaker ใชใน การตรวจจบ และตดกระแสเกน
แบงไดเปน 2 หลกการคอ….
• Thermal-Magnetic trip unit
• Electronic trip unit
Schneider Electric 18- Marketing - Pakon – 22 July 2008
Thermal-Magnetic trip unitการตดวงจรโดยอาศยผลทางความรอน และสนามแมเหลก
ประกอบดวยอปกรณปลดวงจร 2 สวน 1. Thermal Unit. (ทำาหนาทปองกน
) 2. Magnetic Unit. (ทำาหนาทปองกน
C CCCCCCC)
Schneider Electric 19- Marketing - Pakon – 22 July 2008
หลกการทำางานของกลไกทใชผลทางความรอน (Thermal unit)
Thermal-Magnetic trip unit
ภาวะปรกต
ภาวะเกดกระแสเกน (Overload)
Schneider Electric 20- Marketing - Pakon – 22 July 2008
หลกการทำางานของกลไกทใชผลของสนามแมเหลกไฟฟา (Magnetic unit)
Thermal-Magnetic trip unit
ภาวะปรกต ภาวะเกดกระแสลดวงจร Short circuit
Schneider Electric 21- Marketing - Pakon – 22 July 2008
สวนปองกนโอเวอรโหลด
สวนปองกนกระแสลดวงจร
ของจรง...
เบรกเกอร MCB รน multi 9
Schneider Electric 22- Marketing - Pakon – 22 July 2008
How LV Circuit Breakers work
1- The current is measured by current sensors installed in the breaking unit or in the trip unit.
2- The current is analysed by an electronic circuit board in the trip unit. The electronic trip unit sends an electrical tripping command to the MITOP.
3- The MITOP (electromagnet) converts the electrical command into a mechanical command and activates the half wheel of the mechanism. The mechanism opens.sensorssensors
MITOPMITOP
trip unittrip unit
Schneider Electric 23- Marketing - Pakon – 22 July 2008
ของจรง...
Schneider Electric 24- Marketing - Pakon – 22 July 2008
สามารถปรบระดบกระแสทรปไดละเอยดกวา รวมทงสามารถปรบคาหนวงเวลาได (time delay)
ม Fault indicator แสดงสาเหตการปลดวงจร
ใชprotect fault ไดหลายประเภท รวมไปถง อาท Earth fault, Earth League
ม Pre-trip alarm เตอน เมอเบรคเกอรใกลจะเกดการทรป เนองจากปรมาณกระแสใชงาน ใกลเคยงกบพกดกระแสโอเวอรโหลด
มฟงกชนของแอมมเตอร เพาเวอรมเตอร บางรนสามารถวดฮารโมนคได สามารถเชอมตอเขาระบบ Energy Management or SCADA เพอบรหารจดการการใชพลงงานได
ขอดของ Electronic trip unit
Other Technology for LV CBElectronic trip unit
Schneider Electric 25- Marketing - Pakon – 22 July 2008
Tripping Curves
●เวลา ในการตดวงจรของเบรกเกอร (Tripping time) แสดงเวลาในการตดวงจร มหนวยเปนวนาท อยในแนวแกนตงของกราฟ
ปรมาณ กระแส ทไหลผานเบรกเกอร แสดงปรมาณกระแสทไหลผานเบรกเกอร โดยกราฟจะ แสดงเปนจำานวนเทาของคาแอมปทรปของเบรกเกอร มหนวยเปนแอมป อยในแนวแกนนอนของกราฟ
กราฟแสดงการทำางานของเบรกเกอร
Schneider Electric 26- Marketing - Pakon – 22 July 2008
●เสนกราฟจะอยชวงบนซายของกราฟ
Tim
e in
Sec
onds
Multiples of Amp Trip
Thermalunit
●ระดบกระแสทเบรกเกอรทำางานจะอยระหวาง 1-10 เทาของคาแอมปทรป
●แผน bimetal จะทำางาน (โกงงอ) เมอกระแสเกนไหลผาน แลวทำาใหเกดความรอน
●กระแสยงไหลผานมากเทาไร เบรกเกอรยงตดวงจรเรวมากขนเทานน
การตดวงจรโดยอาศยผลทางความรอน
(Thermal Tripping)
Schneider Electric 27- Marketing - Pakon – 22 July 2008
การตดวงจรโดยอาศยผลทางความรอน (Thermal Tripping)
1วนาท
5วนาท
Schneider Electric 28- Marketing - Pakon – 22 July 2008
การตดวงจรโดยอาศยผลทางความรอน (Thermal Tripping)
10วนาท
35วนาท
Schneider Electric 29- Marketing - Pakon – 22 July 2008
●เสนกราฟแสดงอยบรเวณทางขวาดานลาง
Tim
e in
Sec
onds
Multiples of Amp Trip
Magneticunit
●ระดบกระแสทเบรกเกอรตดวงจรจะอยตงแต10 เทาของคาแอมปทรปขนไป
●สนามแมเหลกไฟฟาจะทำางาน เมอมกระแสไหลผานตวเบรกเกอร
●การตดวงจรของเบรกเกอร จะทำางานทนท ไมมการหนวงเวลา
การตดวงจรโดยอาศยผลของสนามแมเหลกไฟฟา (Magnetic tripping)
Schneider Electric 30- Marketing - Pakon – 22 July 2008
0.02วนาท
การตดวงจรโดยอาศยผลของสนามแมเหลกไฟฟา (Magnetic tripping)
Schneider Electric 31- Marketing - Pakon – 22 July 2008
กราฟแสดงการทำางานของเบรกเกอรแบบ Electronic trip unit
Schneider Electric 32- Marketing - Pakon – 22 July 2008
● - Long time setting●เปนการจำาลองการทำางานของแผน Bimetal ในเบรกเกอรแบบ Thermal-Magnetic
●เบรกเกอรจะทำางานเมอเกด Overload●เปนตวกำาหนดขนาดแอมปทรปของเบรกเกอร
●ปองกนความเสยหายของฉนวนสายไฟฟา● - Long time delay
●ปรบตงเวลาในการตดวงจรของเบรกเกอร หลงจากตรวจจบกระแสโอเวอรโหลดแลว
Electronic trip unit
Schneider Electric 33- Marketing - Pakon – 22 July 2008
● - Short time pickup●ใชปรบตงปรมาณกระแสลดวงจร เพอประโยชนในการทำา Coordination
●ปองกนอนตรายทจะเกดขนในระบบ :●ปองกนกระแสสงๆ ทำาลายความเปนฉนวนของสายไฟฟา●ปองกนการหลอมละลายของสายไฟฟา
● - Short time delay●ปรบตงเวลาในการตดวงจรของเบรกเกอร หลงจากตรวจจบกระแสลดวงจรแลว เพอประโยชนในการทำา Coordination
Electronic trip unit
Schneider Electric 34- Marketing - Pakon – 22 July 2008
● Instantaneouspickup●เปนการจำาลองการทำางานของสนาม
แมเหลกไฟฟาในเบรกเกอรแบบ Thermal-Magnetic
●เบรกเกอรตดวงจรทนท ไมมการหนวงเวลา
●ปองกนอนตรายอนจะเกดจากการบดตว ของตวนำา (Electrodynamic) หลงจากเกดลดวงจรในระบบไฟฟา
Electronic trip unit
Schneider Electric 35- Marketing - Pakon – 22 July 2008
●Ground-fault pickup● จดทเบรกเกอร เรมตรวจจบปรมาณกระแสลดวงจรลงดน
●Ground-fault delay●ปรบตงเวลาในการตดวงจรของ
เบรกเกอร หลงจากตรวจจบกระแสลดวงจรลงดนแลว
Electronic trip unit
Schneider Electric 36- Marketing - Pakon – 22 July 2008
Application of Electronic Trip UnitThermal image
Schneider Electric 37- Marketing - Pakon – 22 July 2008
Application of Electronic Trip UnitI2t ON/OFF
Schneider Electric 38- Marketing - Pakon – 22 July 2008
Application of Electronic Trip Unit
Principles of the ZSI function
Schneider Electric 39- Marketing - Pakon – 22 July 2008
- Ground fault Protection Equipmentระบบตรวจจบกระแสลดวงจรลงดน (Ground Fault Sensing)
แบบ Residual• สายแตละเสนจะถกตรวจวดกระแสดวยหมอแปลงกระแส (CT) โดยเฟส A, B, C จะตดตงใน ตวเบรกเกอร สวนในสายนวทรล จะตดตงแยกตางหาก แลวเดนสายกลบมาทตวเบรกเกอร
Concept3 เฟส 4 สาย: I1+I2+I3+IN = 0
3 เฟส 3 สาย: I1+I2+I3 = 0
เฟสเดยว: I1+IN = 0
Schneider Electric 40- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breakerparameter display definition selection
Rating
Breaking capacity
In (A)Must be indicated on the front of the circuit breaker
Maximum current that the device can withstand under specific operating conditions
The rated current determines the rating (In)
In = rated current: to withstand the current absorbed by the loadsIn > rated current: if derating is required, according to the ambient T° and installation and operating conditions (connector cross-section, temperature, environment, etc.)
Icu in kAMust be indicated on the front of the circuit breakerN.B. magnifying glass effect on the front of a device
Maximum short-circuit current that the circuit breaker can interrupt
The assumed short-circuit current (Isc) determines the breaking capacity
Schneider Electric 41- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker
In = 400A
Icu = 70kA at 380/415 V
Schneider Electric 42- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit BreakerHow to select suitable Icu?
1. Must know what is the level of 3 phase short circuit fault at that location. (By
calculation or from drawing)
2. LV CB at that location must have Icu ≥ 3 phase fault level at that location.
DC component AC component
Iproot2 Ik
2 root2 Ik
Schneider Electric 43- Marketing - Pakon – 22 July 2008
High power test lab
"O" opening test
"CO” closing/opening test
enclosureA B
is closed
ON Opening, breaking OFF
is closed
OFF ON Opening, breaking OFFclosing
to t1
BA
to t1
BA
making switch
ground fuse
t
t
การทดสอบคา Icu“O” - รอ3 นาท - “CO”
Schneider Electric 44- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)
Ics
Discrimination: Icw
parameter selectiondefinitiondisplay
Icw (kA RMS)Category B
On the front of the device
Permissible short-time current.
Icw covers the TED and I²t performances of a circuit breaker
A selective circuit breaker has an Icw.To be selective, according to IEC 60947-2, a circuit breaker must have an Icw > 12 In (Category B). To be completely selective, it must have an Icw equivalent to the max Icu of the downstream circuit breaker(s).
It is expressed as a % of Icu.It is defined by IEC 947-1/-2. The higher the Ics the more effective the circuit breaker
Ics is the rated service breaking capacity given by the manufacturer. Ics indicates the ability of a circuit-breaker to provide normal operation after three short-circuit breaking operations.
Ics (kA RMS)
Schneider Electric 45- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)
Ics = 100%Icw = 6kA/ 0.25 s
Schneider Electric 46- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)
Breaker ทมคา Ics สงๆ ชวยเพมความตอเนองของระบบไฟฟาอยางไร ?
- Breaker ภายในตเมน (MDB) ซงอยใกลหมอแปลง มโอกาสทจะพบกบกระแสลดวงจรทมขนาดสงใกลเคยงกบคา Icu หรอ กระแสลดวงจร 3 เฟส มากกวา breaker ทอยภายในตยอย
Breaker ทตดในตเมน (MBD) หรออยใกลหมอแปลงควรจะเลอกใช แบบทมคา Ics = 100 % Icu
Schneider Electric 47- Marketing - Pakon – 22 July 2008
เทคโนโลย Current limiting ชวยใหคา Ics = 100 % Icu
DC component
AC component
Ip
Schneider Electric 48- Marketing - Pakon – 22 July 2008
ตดกระแสลดวงจรดวยเวลาเพยง 0.002 วนาท !Compact NS
Schneider Electric 49- Marketing - Pakon – 22 July 2008
aa
10 0005 000
2 0001 000
500
20010050
20105
21.5
.2
.1.05
.02
.01.005
.002
.001.5 .7 1 2 3 4 5 7 10 20 30 50 70100 200 300
t(s)
I / Ir
Im = 5 … 10 x In
déclenchement réflexe :t < 10 ms
t(ms)
5
20
10
87
6
4
3
2 3 4 6 10 20 30 40 60 100 200
STR22SE160
NS250
NS100-NS160
TM160D
TM16D...TM100D
kA eff
Trip curve ของเบรคเกอรทไมใช current limit •Isc < 25 In
Thermal magnetic ทำางาน
•Isc > 25 In“Reflex tripping” ทำางาน
Compact NS
Schneider Electric 50- Marketing - Pakon – 22 July 2008
a
Compact NS“roto-active”
Schneider Electric 51- Marketing - Pakon – 22 July 2008
fixedcontact
housingchamber
gasgenerating parts
arc chute
arcchute
gasgenerating parts
rotarycontact
magnetique U
fixedcontact
a
i
Fm
i
Fr
Compact NS“roto-active”
Schneider Electric 52- Marketing - Pakon – 22 July 2008
MCCB (molded case CB) ทวๆไป
a
i
Fm
i
Fr
Schneider Electric 53- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)ICE 947-2แบงอปกรณปองกนเซอรกตเบรคเกอรออกเปน 2 ประเภท
• Category A• Category B
เบรกเกอร category B :• เปนเบรคเกอรทม time delay ทำาใหสามารถทำา time discrimination กบเบรคเกอรตวลางได• คา Icw บอกระดบกระแส (kA)ทสามารถทนไดในชวง time delay (0.05 ,0.1 ,0.25 ,0.5 ,1 sec)• พกดกระแส 800-6300 A
เบรกเกอร category A :• ไมมการกำาหนดคา Icw• สามารถทำา discrimination แบบ current discrimination ได• พกดกระแส 1-630 A
Im
tm
mt
Schneider Electric 54- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)
Icu(D2)
CB1CB2
CB1
CB2
CB2 CB1
CB1
CB2
Icu(CB2)
Current discrimination Time discrimination
Schneider Electric 55- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)
ยงใชเบรคเกอร category B ทมคาIcw สงเทาใด discrimination กยงดเทานน …
(ใกลเคยง total discrimination)
Icw = Icu
ถา Icw = Icu จะได total discrimination !
Instantaneous OFFbreaking power:Icu= Ics = Icw
Category B
Icu
If Icw = Icu?
Schneider Electric 56- Marketing - Pakon – 22 July 2008
Key Parameter to Select LV Circuit Breaker (2)
Easy way to check Discrimination!
upstreamCompact circuit breaker NS100N/H/L NS160N/H/L NS250N/H/L NS400N/H/L NS630N/H/LTM-Dn trip unit 80 100 125 160 200 250 400 630
downstreamcircuit breaker TM-Dmulti 9 C60N 10 to 25
32 to 4063
Compact NS80H-MA 2.5 to 80NS100N 16 to 100NS160N 16 to 160NS250N 16 to 250
Discrimination table
Schneider Electric 57- Marketing - Pakon – 22 July 2008
…ความตอเนองของระบบไฟฟา ใครๆกตองการ
• ลดตนทนการผลต• เพมปรมาณการผลต• คณภาพของสนคา
Schneider Electric 58- Marketing - Pakon – 22 July 2008
LV co-ordination techniques● Optimising LV electrical distribution through 3 actions at the Protection
Plan Level
1) discrimination to guarantee continuity of supply 2) limitation to reduce constraints 3) cascading to optimise performances
Schneider Electric 59- Marketing - Pakon – 22 July 2008
Co-ordination of protection devices1) discrimination● Whatever the fault: overload short-circuit insulation fault
only the circuit-breaker located just upstream from the fault trips
● 4 types of discrimination current time energy logic
E41139
a
A
CB
Schneider Electric 60- Marketing - Pakon – 22 July 2008
Co-ordination of protection devices2) limitation● Technique that allow for the harmful effects of short-circuit currents
to be diminished
● Limitation reduces effects of the following type: electromagnetic: reduction in EMC disturbances mechanical: reduction of deformation and/or breaks thermal: rise in the life span of trunkings
E62650
E62651
Isc presumed transient peakIsc presumed steady peak
Isc limited peak
Isc
10 %
Â
tsc t
100 %
t
A2 I2sc
Presumedenergy 100 %
Limitedenergy< 1 %
1 %
100 %
Schneider Electric 61- Marketing - Pakon – 22 July 2008
Co-ordination of protection devices3) cascading● The limiting upstream circuit-breaker helps the downstream
circuit-breakers to open● Technique that allows for the cost of LV electrical distribution
to be optimisedE62667
Non priorityfeeder
Schneider Electric 62- Marketing - Pakon – 22 July 2008
a
1000 A
100 A
• โอเวอรโหลด : I < 10 In
• ลดวงจรแบบมความตานทาน :10 In > Icc 30 In
• ลดวงจร : In > 30 In
กระแสเกนในระบบไฟฟามหลายระดบเบรกเกอร CB1
เบรกเกอร CB2
Ic3 = 30 kA - ลดวงจร
breaking capacity
Ic2Ic1 Ic3 I(A)
t(s)
100A
เบรกเกอร CB2
เบรกเกอร CB1
Ic1 = 300 A - โอเวอรโหลด
Ic2 = 3000 A - ลดวงจรแบบมความตานทาน
Schneider Electric 63- Marketing - Pakon – 22 July 2008
หลกการ Current discrimination Discrimination limit Is = Im(CB1) หลกการ Current discrimination จะใชไดดมาก กบต Load center, Consumer unit (เพราะพกดกระแส CB1 กบ CB2 หางกนมาก และกระแสลดวงจรตำา)
Ir ของ CB1
Ir ของ CB2> 2
Ir(CB2) Ir(CB1)
Im(CB2)Im(CB1)
Im ของ CB1
Im ของ CB2> 2
Note : Merlin Gerin Im(CB1)/Im(CB2) >1.5
Icu(D2)
CB1CB2
CB1
CB2
Schneider Electric 64- Marketing - Pakon – 22 July 2008
การทำา Discrimination ในชวงกระแสลดวงจรตำาๆ
CB2 CB1
CB1
CB2
Icu(CB2)
•ใชหลกการ time discrimination
Schneider Electric 65- Marketing - Pakon – 22 July 2008
มาตรฐาน IEC947-2 แบงอปกรณปองกนเซอรกตเบรคเกอรออกเปน 2 ประเภท
• Category A• Category B
เบรกเกอร category B :• เปนเบรคเกอรทม time delay ทำาใหสามารถทำา time discrimination กบเบรคเกอรตวลางได• คา Icw บอกระดบกระแส (kA)ทสามารถทนไดในชวง time delay (0.05 ,0.1 ,0.25 ,0.5 ,1 sec)• พกดกระแส 800-6300 A
เบรกเกอร category A :• ไมมการกำาหนดคา Icw• สามารถทำา discrimination แบบ current discrimination ได• พกดกระแส 1-630 A
Im
tm
mt
Schneider Electric 66- Marketing - Pakon – 22 July 2008
ยงใชเบรคเกอร category B ทมคาIcw สงเทาใด discrimination กยงดเทานน …
(ใกลเคยง total discrimination)
การทำา Discrimination ในชวงกระแสลดวงจร
• ใชหลกการ time discrimination
Icw = Icu
ถา Icw = Icu จะได total discrimination !
Instantaneous OFFbreaking power:Icu= Ics = Icw
Category B
Icu
Schneider Electric 67- Marketing - Pakon – 22 July 2008
Other Technology for LV CB (2)Current Limiting and Cascading
A device is said to be limiting when the current passing through it during a short-circuit has an amplitude considerably lower than the prospective short-circuit current
t
Icc Prospective Isc peak
Limited Isc peak
What is Current Limiting?
Schneider Electric 68- Marketing - Pakon – 22 July 2008
Other Technology for LV CB (2)Current Limiting Technology
Limitation thermal, mechanical and electromagnetic stresses of cables, thanks to rapid opening preventing complete development of the short-circuit
Cost reduction:Smaller cables for high short-circuit currentsSmaller devicesSmaller switchboard enclosureUse of the cascading principle
Even our multi 9 circuit-breakers are equipped with limitation technology thanks to an extremely effective mechanism
Limitation curves are defined for each device.t
Icc Prospective Isc peak
Limited Isc peak
Schneider Electric 69- Marketing - Pakon – 22 July 2008
Other Technology for LV CB (2)What is Cascading?
Cascading is the use of the current limiting capability of circuit breakers at a given point to permit installation of lower- rated and therefore lower cost breakers downstream
1 1 3
Schneider Electric 70- Marketing - Pakon – 22 July 2008
Other Technology for LV CB (2)Cascading table
Upstream NS100N NS100H NS100LBreaking capacity kA eff 36 70 150Downstream (kA)C60a 15 20 20C60N 25 30 30C60H 25 40 40
Breaking capacity (kA eff)
Note : C60a 5kA @ 415VC60N 10kA @ 415VC60H 15kA @ 415VFault at 36kA
Schneider Electric 71- Marketing - Pakon – 22 July 2008
Other Technology for LV CB (2)Cascading with Enhanced Discrimination
Upstream NS160N/H/L 36kA trip unit TM-D
Downstream rating (A) 80 100/125/160
C60N <16 30/30 30/3020 30/30 30/3025 30/30 30/3032 15/30 30/3040 15/30 30/3050 15/30 30/3063 30/30
15/30Selectivity limit enhanced by cascading (in kA)
Downstream device breaking capacity enhanced by cascading (in kA)
Schneider Electric 72- Marketing - Pakon – 22 July 2008
Topic
1.Basic Concept2.LV Components (Design and
Select)3.Schneider Offer in LV
Schneider Electric 73- Marketing - Pakon – 22 July 2008
Ecodial Program for LV Electrical system design
B2
Tableau
D4
CEP
Q8
Circuit
C8
L8 L9
C9
Circuit
Q9
Q7
Circuit
C7
L7L6
C6
Circuit
Q6
Q5
Circuit
C5
L5
Q3
Circuit
C3
Q1
Circuit
C1
T1
Schneider Electric 74- Marketing - Pakon – 22 July 2008
Up to 125A MCB multi9
Up 10 100A MCB QOvs
Up to 400A MCCB Easypact
100 – 3200A MCCB Compact NS
800 – 1600A ACB Masterpact
NT
800 – 6300A ACB Masterpact
NW
Circuit breaker from 0.5 – 6300 A
Schneider Electric 75- Marketing - Pakon – 22 July 2008
Easypact: performances
25010015 60
7.5
10
36
30
25
18
15
EZD100B
EZD100FEZD100N
EZD100H
EZD250F
EZD250N
EZD250H
EasyPact 100 EasyPact 250
Breaking Capacity Icu kA at 415Vac
50
EZDV250N
EZDV250H EZD400N
EZD400H
Ratedcurrent In A
EasyPact 400
400
Schneider Electric 76- Marketing - Pakon – 22 July 2008
●Breaking capacities by standards
400/415V
100 AF 250 AF
IEC-JIS 550V
230/240V
240VNema 480V
B F N H
5 2.5 105
10 7.5 30 15
25 10 100 25
- - 18 10
-- 100 25
kA F N H
5 15 10
18 36 25
25 85 50
15 25 18
25 85 50
400 AF
N H
2015
5036
100 85
3525
8550
Easypact: performances
Schneider Electric 77- Marketing - Pakon – 22 July 2008
Compact NSX and Compact NS Range Overview●4 volumes only to cover...
●Ratings from 100 to 3200 A●Performances from 36 to 200 kA
Compact NSX 100 - 250 Compact NSX 400-630 Compact NS 630-1600 Compact NS 1600-3200
Schneider Electric 78- Marketing - Pakon – 22 July 2008
NPerformances (kA) H L LB
Types of poles NH unit L unit LB unit
Icu 220/240 V 50 70 150 200
380/415 V 50 70 150 200
440 V 50 65 130 200
500/535 V 40 50 100 100
660/690 V 30 42 - 75
Icw 0.5 s 25 25 10 7
1 s 19.2 19.2 7 5
Break. cap.NEMAAB1
240 V 50 65 125 200
480 V 35 50 100 200
600 V 25 50 - 100
Mechanical durability 10 000 10 000 10 000 10 000
Compact NS IEC60947-2 performances
Schneider Electric 79- Marketing - Pakon – 22 July 2008
Compact NS IEC60947-2 performances
630b
Performance N
Manual Compact NS
Ics 100% 75%
800 1000 1250 1600
Performance H Ics 75% 50%
Performance L Ics 100%
Performance LB Ics 100%
630b
Performance N
Electrical Compact NS
Ics 75% 75%
800 1000 1250 1600
Performance H Ics 50% 50%
Performance L Ics 100%
Schneider Electric 80- Marketing - Pakon – 22 July 2008
ACB ●2 families, 3 sizes
Masterpact NT
630 to 1600 A
Smallest circuit-breaker !
4000 to 6300 A
Masterpact NW
800 to 4000 A
Masterpact NW
Masterpact NT/NW Range Overview
Schneider Electric 81- Marketing - Pakon – 22 July 2008
Masterpact NT/NW IEC60947-2 performances
Schneider Electric 82- Marketing - Pakon – 22 July 2008
อปกรณประกอบสำาหรบเซอรกตเบรคเกอร●SHUNT TRIP●UNDERVOLT RELEASE (UVR)●UNDERVOLT RELEASE WITH TIME DELAY●AUXILIARY SWICH●ALARM SWITCH●HANDLE PADLOCK●KEY LOCKS●MOTER OPERATE
Schneider Electric 83- Marketing - Pakon – 22 July 2008
Shunt Trip
●จะปลดวงจรเซอรกตเบรคเกอร เมอ Coil shunt trip ไดรบVoltage
●สามารถนำาไปตอกบระบบอนเพอนำามาสงปลดวงจรได
For MCCB For ACB
Schneider Electric 84- Marketing - Pakon – 22 July 2008
Undervoltage Release (UVR)●ปลดวงจรเมอ voltage ตกตำากวาคาทกำาหนดไว●สวนใหญจะใชงานคกบ under/over voltage relay●มทงแบบทม และไมม Time delay
ไมม Time delay ม Time delay
การไฟฟาแนะนำาใหเลอกใชงานแบบทม Time delay
Schneider Electric 85- Marketing - Pakon – 22 July 2008
Under volt. แบบไมมtime delay
BAD !
Under volt. แบบมtime delay
Good !
Phase protection relay with under voltage release
L1L2L3N
Schneider Electric 86- Marketing - Pakon – 22 July 2008Under voltage release with time delay Control board ของตว Under voltage
Undervoltage Release With Time Delay
Schneider Electric 87- Marketing - Pakon – 22 July 2008
Undervoltage Release With Time Delay
แบบตดตงภายนอกตวเบรคเกอร
Schneider Electric 88- Marketing - Pakon – 22 July 2008
For MCCBFor ACB
Auxiliary Switch●เมอเซอรกตเบรคเกอรเปลยนสถานะ - (on off) จะทำาใหหนาสมผส
ชวยเปลยนสถานะดวย
Schneider Electric 89- Marketing - Pakon – 22 July 2008
Auxiliary Switch (ตอ)●เมอเซอรกตเบรคเกอรเปลยนสถานะ - (on off) จะทำาใหหนาสมผส
ชวยเปลยนสถานะดวย
Schneider Electric 90- Marketing - Pakon – 22 July 2008
Alarm Switch●หนาสมผสชวยจะเปลยนสถานะเมอเซอรกตเบรคเกอรทรป
เนองจากเกด Fault ขนในระบบ (Overload, Short circuit)
For MCCB
Schneider Electric 91- Marketing - Pakon – 22 July 2008
Motor Operate●ผใชสามารถสง ON-OFF เบรกเกอรไดจากหองคอนโทรล โดยไม
ตองไปทหนาตวเบรคเกอร
Schneider Electric 92- Marketing - Pakon – 22 July 2008
Handle Padlock●ตดตงเพอกนการ ON เซอรกตเบรคเกอร●ลอกไวในตำาแหนง OFF เทานน ไมสามารถลอกไวในตำาแหนง ON
For MCCB For ACB
Schneider Electric 93- Marketing - Pakon – 22 July 2008
Key Locks●ตดตงเพอกนการ ON เซอรกตเบรคเกอร●ลอกไวในตำาแหนง OFF เทานน ไมสามารถลอกไวในตำาแหนงON
Schneider Electric 94- Marketing - Pakon – 22 July 2008
●นยมใชกบเบรคเกอรทควบคมมอเตอร●สามารถลอคเบรคเกอรทตำาแหนง OFF ได โดยไมตองใช
อปกรณเพม
Rotary Handle
Extend Direct