paul o. abbe, inc

257
>>>> PAUL O. ABBE, INC. <<<< LITTLE FALLS, NEW JERSEY 07424 ***************** 201-256-4242 INSTALLATION AND OPERATING INSTRUCTIONS FOR ROTA-CONE BLENDER PURCHASER: DATE: SERIAL NO.: ORDER NO.: Fluor Daniel Inc. September 4,1997 A46665 619930-4-0708

Upload: khangminh22

Post on 26-Mar-2023

1 views

Category:

Documents


0 download

TRANSCRIPT

>>>> PAUL O. ABBE, INC. <<<<

LITTLE FALLS, NEW JERSEY 07424

*****************

201-256-4242

INSTALLATION

AND

OPERATING INSTRUCTIONS

FOR

ROTA-CONE BLENDER

PURCHASER:

DATE:

SERIAL NO.:

ORDER NO.:

Fluor Daniel Inc.

September 4,1997

A46665

619930-4-0708

PAUL O. ABBE INC.

ROTA-CONE BLENDER

BLENDER SIZE: 54 diameter

SERIAL NO.: A46665

TOTAL VOLUME: 53 cubic feet

MAXIMUM OPERATING CAPACITY: 35 cubic feet

BLENDER SPEED: 8 TO 25 RPM

The MAXIMUM operating capacity of this Blender is 35 Cubic Feet. Amounts less thanthis may be loaded into the machine. FOR BEST RESULTS THIS FIGURE SHOULDNOT BE EXCEEDED.

FOOTINGS

ERECTION

GEARING

INSTALLATION INSTRUCTIONS

It is important that the blender be mounted on a solid sub-stratumwith reinforced concrete footings as follows:

18" through 42" dia. Units: 12 inches thick

48" through 66" dia. Units: 18 inches thick72" dia. and larger: 30 inches thick

Note that the tops of the supporting steel stands are machined, andthe bottoms are not. When erecting, the tops of the stands must belevel and in the proper plane, as well as axially aligned. Anyshimming or grouting should be between the steel stand and theconcrete footing or pedestal.

On units with gears, back lash of 0.027 has been pre-set at thefactory. This should be checked.

PAUL O. ABBE INC.

DRIVE

LUBRICATION

BRAKES

START-UP

The standard drive for Blenders through 42" dia. is a gearmotorconnected to the Blender through a roller chain drive. Thesecomponents are installed and aligned at the factory. Since the

machine is broken down for shipment, it is necessary that it bereassembled properly in the field to assure that alignment ismaintained.

On units 48" dia. and larger, alignment is especially critical since

these units are furnished with a gear and pinion drive, instead ofroller chain. In this case, exact center distance between gear andpinion, as well as alignment, must be maintained. Again, this isdone at the factory and care must be exercised during erection tomaintain this alignment. Following the instructions under"ERECTION" will assure that the drive is properly aligned.

Information on lubricants for drive components and bearings isgiven on the following page.

Brakes are furnished as an optional item when required. Theirfunction is primarily to hold the unit during loading and unloadingoperations. A secondary function is to assist the operator in"spotting" the unit for loading and unloading. The braking effort isadjustable (model dependent, consult the brake specificationsheet), except on explosion proof units, and it is recommended thatit be set to allow the unit to "coast" approximately 30° on units thru

42" dia., and 45° on the larger units. This lessens the shock on alldrive components, thereby adding to their life.

Lubricate gear and pinion, fill gearhead to proper level, checkwiring to motor and brake (when furnished) before starting. Be

sure there is nothing in the path of the rotating Blender. Operatewith no load in the Blender to make sure all drive components arealigned. Allow to run for several minutes. Stop and check lubepattern on gear and pinion. This will give good indication ofalignment. Adjust alignment if necessary, re-lube and repeatprocedure before operating under load.

WARRANTY

Seller warrants to buyer that goods sold hereunder are free from defects in design,material or workmanship for a period of twenty-four (24) months from date of shipment.

The foregoing warranty is exclusive and in lieu of all other warranties, express, impliedor statutory, including but not limited to the warranty of merchantability, the warranty ofsuitability of fitness for use and the warranty of fitness for any particular purpose or useand excludes any claims for indirect or consequential losses or damages.

If within twenty four (24) months from the date of shipment any products sold hereundermeets with the warranty specified above, the buyer notifies seller promptly and inwriting, seller shall correct any such defect, at seller's option, by repairing or replacingany defective product or part.

Costs for shipping parts or equipment to and from the installation point of the equipmentshall be born entirely by the buyer.

Seller will make no allowance for repairs or alterations to the products by buyer, unlessmade with the advanced written consent of seller.

GUARDS

FENCE

SAFETY

EQUIPMENT

CAUTION

All power transmitting components of this machine have safetyguards. However, it is imperative that you inspect the installation tomake sure that there are no projections or moving components ofthe machine which might also require guards.

It is recommended that the entire machine be placed within a

fence-type enclosure to prevent anyone from contacting it while it isrunning. To this end, the enclosure should have a limit switch (withthe proper NEMA classification) installed on all gates, doors, etc.which provide access for the machinery. The limit switches shouldbe installed so that opening any of the access door will interruptpower to the machine.

Operating personnel should be provided with theproper equipment for the job being performed. (Examples:

suitable clothing, safety glasses, gloves, breathing device.)

FIRE Fire extinguishing apparatus and breathing devicesEXTINGUISHING should be determined and implemented, withEQUIPMENT consideration for the product being handled and the NEMA

classification of the environment.

ELECTRICAL

WORK

All electrical work should be done by a licensed electricianwho is familiar with local as well as NEMA electrical codes.

Your electrician should incorporate the following features in

the design of your electrical controls:

1. At least one (1) emergency stop switch within the reach ofthe operator.

2. Machine must be grounded. When flammable liquids of anykind, or combustible dust are being used, grounding isimperative.

3. When working with flammable liquids - fluid containers, fluidhandling equipment and pouring spouts should also begrounded.

Please consult the National Electrical Codes if you are

uncertain of the suitability of this equipment for yourenvironment.

Parts List

SP-A46665

Userl

Item Qty Pad

' 1 100 1200004

Spare Parts List

Fluor Daniel. RCB-54

Rev Status U

Wt. Mach Labor

2 1 237U1288*02

3 25 25OG0083100-50r-•---=- •-- ---- - --- *. --- - -/-

Legris,

Meto

Industrial Retaining Rings

4 1 339004300254

5 _ 2 33940MP-E-2 1/2

6 1 900031581

-7- 1 1 900031582

8 1 900031647

9 1 9OOR5321

Tri-Clover

Dodge

Dodge

Dodge

Duff Norton

Paul 0. Abbe Inc.

139 Center Avenue, Little Falls, NJ 07424

973-256-4242 Fax: 973-256-2699

TypeStat

PS

U

PS

U

Title

Detail

PS Tubing, Clear NylonU | 1/4", per ft.

1094P5600 $0.19 (ea)

Seat, Butterfly Valve, White EPDM

8" Meto Butterfly Valve

5185.00 (ea)Retaining Ring, External, SS

1/2" Shaft

Weld Labor

3100-50-SS $0.88 (ea)

PS Gasket, EPOMU Ring, 1/4x 157/81Dx 18 3/400

$47.85 (ea)

PS Gasket, EPDMU | 21/2" Tri-Clover

40MP-E-2 1/2 $2.48 (ea)

PS Pressure Plate U 15 Ib Dodge Brake031581 $31.08 (ea)

PS Friction DiscU 15 Ib Dodge Brake

$67.35 (ea)031582

PS Kit, Magnet & CoilU | 15 Ib Dodge Brake

031647 $119.23 (ea)

PS Spare Part, Repair CartridgeU 3/4" NPT, Duff Norton Rotary Union #R530OP

451265 $52.50 (ea)

Reference

Printed 9/22/97

Date 9/5/97

$18.70 (extended)

$185.00 (extended)

Hinged Cover

$22.00 (extended)

547.85 (extended)

$4.96 (extended)

$31.08 (extended)

$67.35 (extended)

$119.23 (extended)

$52.50 (extended)

SP-A46665

Page 1 of 1

PAUL O. ABBE, INC.

Manufacturers Redogniti o b _& .S pe_cific-at i 2{EES

PAUL O. ABBE, INC. - LITTLE FALLS, NEW JERSEY

Manufacturers of ball and pebble mills, ribbon blenders, ROTA-CONE® blenders &dryers, double shaft mixers and jar mills. This processing equipment serves the paint,pharmaceutical, synthetic fiber and chemical industries throughout the world.

This lubricant selection guide was prepared by Castrol to meet the applicationsdescribed by Paul O. Abbe, Inc. The Molub-Alloy® and Tribol® recommended productswere approved as meeting the performance characteristics required.

PAUL O. ABBE EQUIPMENT

Main Bearings and Countershaft Bearings:

Rigid Babbit Type (Grease Reservoir)

Ball or Roller Type

Open Gear and Pinion Drives

Roller Chains

Packing Glands

Motor Bearings, Grease

Gear Drives

Westinghouse (Requiring AGMA No.4)

Dorris Gear Drive (Requiring SAE 30)Falk Shaft Mounted GB (Requiring SAE 40)Worm Gear Boxes

Dodge (Requiring AGMA)SEW Eurodrive

NOTE:

MOLUB-ALLOY

RECOMMENDED PRODUCTS

Molub-Alloy 593 under 250°F/120°C

Molub-Alloy 659 over 250°F/120C

Molub-Alloy 882 Heavy or Molub-Alloy 936 SF Heavy

Molub-Alloy Spindle Oil Medium

Molub-Alloy BRB 572 or Molub-Alloy 777-2

Molub-Alloy BRB 572

Molub-Alloy 814/'Tribol 1100/150Molub-Alloy 80/Tribol 1100/100Molub-Alloy 814/Tribol 1100/150Molub-Alloy 17OW/Tribol 800/460Molub-Alloy 140/Tribol 1100/460Molub-Alloy 90/Tribol 1100/220

For variations, or adjustments or equipment, contact Representative ofPaul 0. Abbe, Inc.

Castrol Industrial North America Inc.

Performance Lubricants Division

1001 West 31 st Street. Downers Grove, Illinois 60515-1280

Telephone: (708) 241-4000 · Fax: (708) 663-0489

MRS 1583-2 8/97

Molub-Alloy®Optimole

Tribol®

TribolASIA

HONG KONGICI China Ltd.

14th Floor, One Pacific Place88 Queensway CentralG.P.O. Box 107

Hong KongPhone: (852) 843 4888Facsimile: (852) 868 5282

CHINA

Pan China Trade Company

Room 202, Bldg. 59254 Zhongshan Road NorthNanjing, 210003Peoples Republic of ChinaPhone: (86) (25) 334-3143

Facsimile: (86) (25) 334-3143

INDIACastrol India UmitedTribol Division

52, Rajall SalalMadras, 600 001 IndiaPhone: (91) (44) 522-9710Facsimile: (91) (44) 522-2323INDONESIA

P.T. Fadjar Klmia Pratama PrimaJalan Aipda K.S. Tubun 11/7Jakarta, IndonesiaPhone: (62)(21)5493070,

5486319,5485937,514599,5486876

Facsimile: (62) (21) 5485937

JAPANTribal Japanc/o ICI JapanPalace Building, ath. floor, Rm. 8011-1,1-Chome, Marunouchi

Chlyoda-ku, Tokyo 100JapanPhone: (81) (3) 3211-3096Facsimile: (Ill) (3) 3211-7806

REPUBLICOF

SOUTH KOREAKorea Luba-Tech Ltd.

238-16, Sinwol 1 -dongYanchung-kuSeoul 158091, KoreaPhone: 82) (2) 602-6907-8,

82) (2) 607-2491-2Facsimile: 82) (2 6907141,(82) (2) 693-2883

MALAYSIAUniwes Technology SDN. BHD.5 JLNSS 18/6

47500 Subang JayaSelangor, MalaysiaPhone: (60) (3) 7340439Facsimile: (60) (3) 7347875

Uniwes Technology SDN. BHD.4160 JLN Kampung Bengaii12200 Buttemorth

Penang, MalaysiaPhone: (60) (4) 322161/2Facsimile: (60) (4) 324996Uniwes Technology SDN. BHD.59 JLN Persisiran PerlingTaman Perling81200 Johor Bharu

Johor, MalaysiaPhone: (60) (7)368066Facsimile (60) (7) 368061

PHILIPPINESPhilippine Explosives Corp.7/h Floor, City Trust Bldg.Edsa, Mandaluyong, Metro ManilaPhilippinesPhone: (63)(2) 788031 to 34Facsimile: (63)(2) 531-0227

Mailing Address:P.O. Box 330 GreenhillsSan Juan, Metro Manila 1502Philippines

SINGAPOREUniversal Westech (S) Pte Ltd.10 Tanjong PenjuruSingapore 2260Republic of SingaporePhone: (65) 265-8444Facsimile: (65) 265-6409

TAIWAN

Taipel Office (Main Office)Tal-Luba International Corporation7-4, No. 49 Ho-Ping E. RoadSection 3Taipei, Taiwan 10660Phone: (886) (2)703-4795Facsimile: (886) (2)702-6158

Kaohsiung OfficeTai·Lube International Corporation9a Swallow Building A267-143, Lin Sheng 1 st RoadKaohsiung, TaiwanPhone: (886) (7) 251 1462Facsimile: (886) (7) 251 1462

THAILANDPeo Tech Co.. Ltd.

52/81-82 Ramkamhaeng Rd.Huamark BangkapiBangkok 10240Thailand

Phone: (66) (2) 377 67734Facsimile: (66) (2) 375 7753

AUSTRALIA

MELBOURNEMain Oflice

Applied Chemicals Pty. Ltd.121 Lewis Road

Wantlma South, VictoriaMelbourne, Auslralia 3152Phone: (61) 9) 800·1555Facsimile: (61) (3) 800-2876

Mailing Address:Applied Chemicals Pty. Ltd.Ptivate Bag 35Bayswater, Victoria, Australia 3153

PERTHApplied Chemicals Pty. Ltd.62 Collingwood StreetOsborne Park, PerthWestern Australia 6017

Phone: (61)(9)446·6144Facsimile: (61) (9) 4464781

SYDNEYApplied Chemicals Pty. Ltd.14 Hume Road

Smithlield, N.S.W. 2164, AustraliaPhone: (61) (2) 725-2000Telex: (790)21607 APPCHEMFacsimile: (61) (2) 725-2320

Mailing Address:P.O. Box 668

Smithfield, N.S.W. 2169, Auslralia

TAbol

Headquarters21031 Ventura Boulevard. Woodland Hills, California 91364-2297Phone: (818) 888-0808 Facsimile: (818) 884-1885

di,an,UlaaROLCO.*

international Sales Offices & Distributors

BRISBANEApplied Chemicals Pty. Ltd.16 Proprietary StreetTingalpa, QLD 4173, AustraliaPhone: (61) (7) 390-7522Facsimile: (61) (7) 390·8556

Mailing Address:Applied Chemicals Ply. Ltd.P.O. Box 6

Cannon Hill, OLD 4170,Australia

MACKAYApplied Chemicals Pty. Ud.11 McLennan StreetCity GatesMackay, QLD 4740,AustraliaPhone: (61) (79) 522333Facsimile: (61) (79) 523279

Mailing Address:P.O.Box 5452Mackay Mall Centre, QLD. 4741

YEPPOONApplied Chemicals Pl. Ltd.54 James StreetYeppoon, QLD 4703, AustraliaPhone: (61) (79) 395455Facsimile: (61) (79) 395515

NEW ZEALANDApplied Chemicals (NZ)4/390 Rosebank Road

Avondale, Auckland 7, New ZealandPhone: (64) (9) 8282155Facsimile: (64) (9) 8283319

Mailing Address:Applied Chemicals (NZ Ltd.)P.O. Box 71137Avondale, Auckland 7, New Zealand

PUERTO RICO &

CARIBBEANTribo-TecP.O. Box 11596

Caparra Heights StationSan Juan, Puerto Rico 00922-1596Phone: (809)788-6270/788·6200Facsimile: (809) 788-6325Cellular. (809) 385·5856

Horacio A. Montes GilorminiP.O. Box 166

Yauco, P.R. 00698Phone: (809) 821-1397Tel/Facsimile: (809) 821-0804

LATIN AMERICA

BRASILCastrot BrasitAv. Itaaca, 2440InhaOma

CEP 21061-020Rio de Janeiro, RJBrazil

Phone: (55) (21) 598-7222Facsimile: (55) (21) 598-7277CHILETribot, Chile S.A.Fidel Oleiza 1921,01.606Providencia, Santiago, ChilePhone: (56) (2) 2239212Facsimile: (56) (2) 2747431

COLOMBIAIngenieros Quimlcos Asociados (IQA)Calle 108A, No. 17-26Bogota, ColombiaPhone: (57) (1) 619-0968

(57)(1)214-2128(57) (1) 213-4862

Facsimile: (57) (1) 215-2104

Mailing Address:Ingenieros Quimicos AsocladosApartado Aereo 56222Bogota, Colombia

COSTA RICA/

NICARAGUATRITECH

Apartado Postal No. 78041000 San Jose, Costa RicaPhone: (506) 2326186Facsimile: (506) 2327258

EL SALVADORTRITECH

25 Calle Poniente #811San Salvador, El SalvadorCentro America

Phone: (503)226-0775Facsimile: (503) 225-1869

GUATEMALATRITECH

Sa Av. 6 39, Zona 14Guatemala City, GuatemalaPhone: (502) (2) 373013,

373031-36Facsimile: (502) (2) 373041

HONDURAS/BELIZETRITECH

2 Av. 1 y2 Calle N.0.Editicio Paseo del Sol

No. 4-8, San Pedro SulaHonduras, C.A. 2642Phone (504) (52) 1981/1982Facsimile: (504) (52) 1984MEXICOTribol Mexico/ALGC. S. A. de C. V.Norte 45 No. 812

Colonia Industrial VallejoC. P. 02300 Mexico D. F.Phone: (52) (5) 567-4409Facsimile: (52) (5) 567-2674

MEXICO (Southern)TRITECH de Mexico, S. A. de C.V.Calle 15, No. 317Cordoba, Veracruz, 945000Mexico

Phone: (52) (2) 7148879,7120093

Facsimile: (52) (2) 7148970

PANAMALubmetal Panama, S.A.P.O. Box 6-4107

El Dorado, Republic of PanamaPhone: (507) 364322; 364323Facsimile: (507) 361067PERUJ. F. Ingenieros S.R.L.Av. de Las Artes Sur No. 629San Boria SurUma 41, PeruPhone (51) (14) 476-8790Facsimile: (51) (14) 476-3872

OF 365-62 1/95

TribolEUROPE

HEADQUARTERSTdbol GmbH

Tribol EuropeErkelenzer Strasse 20

D-41179 Moenchengladbach

GermanyPhone: (49) (2161)909-30Facsimile'. (49) (2161) 909400

Mailing Address:P. O. Box 500210

0-41172 Moenchengladbach

MANUFACTURING

PLANT/

WAREHOUSE & SHIPPING

Tribol GmbH

Erkelenzer Strasse 20

D-41179 MoenchengladbachGermanyPhone: (49) (2161) 909-30Facsimile: (49) (2161) 909-500

Mailing Address:P. O. Box 500210

D-41172 Moenchengladbach

GERMANYTribol GmbHTribol Deutschland

Erkelenzer Strasse 20

D-41179MoenchengladbachGermanyPhone: (49) (2161) 909-30Facsimile:. (49) (2161) 909-400

Mailing Address:P. O. Box 500210

0-41172 Moenchengladbach

AUSTRIACastrol Austria Gesellschaft m.b.H.Industriezentrum N6-SOdStrasse 6

A-2355 Wr. NeudorfPhone: (43) (2236) 695-0Facsimile: (43) (2236) 695-2129

BELGIUMAgeml S.P.R.L. B.V.B.A.Bisschoppenhoflaan 2328·2100 Deurne, BelgiumPhone: (32) (3) 325-0420Facsimile: (32) (3) 326-0977

DENMARKSquare Oil A/SHattemagerve15DK-9000 Aalborg, DenmarkPhone: (45) 98130300Facsimile: (45) 9812 07 87

FINLANDKaukomarkkinat OY

Lubrication DepartmentP.O. Box 40

SF-02631 Espoo 63, FinlandPhone: (35) (80) 5211Facsimile: (35) (80) 521 -6641

FRANCETrbol SAR.L.

3, rue du TMatre

F-91884 MassyPhone: (33) (1) 69536190Facsimile: (33) (1) 69536199

GREECE

G. Beligiannis & Co. O.E.Praxitelous St. No. 1

Thessaloniki 54641, GreecePhone: (30) (31) 840883, 821795Facsimile: (30) (31)831023

IRELAND

Applied Chemicals (ireland) Ltd.Grand Canal Business CentreJamestown Road

Inchlcore,

Dublin 8, IrelandPhone: (353) (1) 549200 or 546333Facsimile: (353) (1) 549230

ITALYTribol

Divisione Di Castrol Italiana SpAVia Aosta 4a

20155 Milano. ItalyPhone: (39) (2) 33625800,801,802Facsimile: (39) (2) 33625803

NETHERLANDSContivema B.V.

Beuketsdijk 162NL-3022 Rotterdam, HollandPhone: (31) (10)477-4733Facsimile: (31) (10) 477-5726

NORWAY

Square Oil A/SHattemagervej 5DK-9000 Aalborg, DenmarkPhone: (45) 98130300

Facsimile: (45) 98 12 07 87

POLANDMETEX Poland Lid.

ul. Humanska 10

00-789 Warsaw, PolandPhone: (48) (22) 496633Facsimile: (48) (22) 497534

PORTUGALICI Portuguesa, Lda.Rua Filipe Foique, 2-5P-1000 Lisboa, PortugalPhone: (351)(1)3525191Facsimile: (351) (1) 562220

SPAINCastrol Espana, S. A.Tribol Divisione

Poligono Induslrial CongostAvda. San Julgn 260-A

08400 Granoliers, BarcelonaSpainPhone: (34) (3) 8464334

Facsimile: (34) (3) 8463652

Tribol

Headquarters21031 Ventura Boulevard, Woodland Hills, California 91364-2297

Phone: (818) 888-0808 Facsimile: (818) 884-1885diABLRMH<AgROLINAm

International Sales Offices & Distributors

SWEDENMolub-Alloy ABDalbogatan 15431 38 Moindal-Gothenburg, SwedenPhone: (46) (31)815990Facsimile: (46) (31) 208210

SWITZERLANDZier Anlagenbau AG

Haegelerstrasse 3CH-5453 Remelschwil, SwitzerlandPhone: (41) (56) 962217Facsimile: (41) (56) 962216

UNITED KINGDOMApplied Chemicals, Ltd.Applied HouseWilson's Lane

Coventry, England CVB BJAPhone: (44) (203) 368800Direct Ph.: (44) (203) 368926Facsimile: (44) (203) 366639

MIDDLE EAST

ABU DHABI/U.A.E.Boodai Trading CompanyOld Airport RoadP.O. Box 46027

Abu Dhabi, United Arab EmiratesPhone: (971) (2)431581Facsimile: (971) (2) 431671

DUBAl/U.A.E.

Boodal Trading Company Ltd.Salah-Al Din Road

P.O. Box 5108

Deim, Dubal, United Arab EmiratesPhone: (971) (4) 431581

Facsimile: (971) (4) 431671

ISRAELGAD RAM

Industrial Services

Moshav Sateri 73272

P.O. Box 751

Rehovot, Israel 76100Phone: (972) (8) 418788/418501Facsimile: (972) (8) 410486

JORDANAt-Tewfik Automobile &

Equipment Co.Station Road

(P.0. Box 253)Amman, JordanPhone: (962) (6) 656273/4,651591,

656247

Facsimile: (962) (6) 647814

SAUDI ARABIAArab Equipment EstablishmenlP.O. 1660

Damman, 31441 Saudi ArabiaPhone: (966)(3)857-4988,

857-3559

Facsimile: (966) (3) 8574463

AFRICA

ZAMBIA

Cemol Chemicals (Zambia) Ltd.Prescot Road

P.O. Box 22648

Kitwe, ZambiaPhone: (260)211722,211967,

(2) 216068

ZIMBABWECemol Chemicals

(Zimbabwe) (Pvt.) Ltd.

111 Dagenham RoadWillowvale. Zlmbabwe

Phone: (263) (4) 62681/5Facsimile: (263) (4) 63544

Mailing Address:Cemot Chemicals

(Zimbabwe) (Pvt.) LId.P.O. Box 344

Willow-valle, Harare,Zimbabwe

Cemol Chemicals

(Zimbabwe) (Pvt.) Lid.17 Falcon Street

Belmont, Bulawayo, ZimbabwePhone: 66296,66718

Mailing Address:

Cemol Chemicals(Zimbabwe) (Pvt.) Lld.P.O. Box 8129

Belmont, Bulawayo, Zimbabwe

SOUTH AFRICAChemserve Systems (Pty.) Ltd.200 Bergrivier DriveChloorkop, Ext. 24 Kempton ParkRepublic of South AfricaPhone: (27) (11) 976-2162Facsimile: (27) (11) 976-2338

Mailing Address:P.O. Box 12055

Chloorkop 1624South Africa

OF 365-62 1/95

Tribol

ALABAMATribol

4185 Billy Mitchell Road(P.O. Box 705)Addison, T)(75001-0705

Phone: (800)745-0125

ALASKATdbol

Meadow Creek Office Park

22516 SE 64[h Place, Suite 220Issaquah, Washington 98027Phone: (800)328-1902Facsimile: (206) 391-8206

ARIZONATdbol

21031 Ventura Boulevard

Suite 600

Woodland Hills, California 91364Phone: (818) 888-9345

(800) 622- 1258Facsimile: (818) 884-1885

ARKANSASTdbol

4185 Billy Mitchell Road(P.O. Box 705)Addison, Texas 750010705Phone: (214) 387-4606Facsimile: (214) 3864914

CALIFORNIANORTHERN CALIF.

Tribol

P.O. Box 5685

So. San Francisco, California 94083Phone: (800) 622-1258Facsimile: (415) 572-9421

SOUTHERNCALIF.

Tribol

21031 Ventura Boulevard,Suite 600

Woodland Hills, California 91364Phone: (818) 888-9345

(800) 622-1258Facsimile: (818) 884-1885

RESEARCH &DEVELOPMENTLABORATORYTdbol

4801 West 147th Street

Hawthorne, California 9025043791Phone: (310) 679-0271Facsimile: (310) 679-0862

COLORADOTribol

21031 Ventura Boulevard

Woodland Hills, California 91364Phone: (800) 622-1258

(818) 888-9345Facsimile: (818) 884-1885

CONNECTICUTTdbol

Hill Professional Park Office Bldg.115 Water Street

Milford, Massachusetts 01757-3001

Phone: (508) 478-7442Facsimile: (508) 478-7989

DELAWARETribol

101 Southpointe DriveBildgeville, Pennsylvania 16017-1297Phone: (412) 257-1140

(800) 347-1440Facsimile:. (412) 221-1280

DISTRICT OF COLUMBIATribol

101 Southpointe OliveBridgeville, Pennsylvania 15017-1297Phone: (412)257-1140Phone: (800) 347-1440Facsimile: (412)221-1280

FLORIDATAbol

4185 Billy Mitchell Road(P.O. Box 705)Addison, Texas 75001-0705Phone: (214) 387-4606

Facsimile: (214) 386-4914

GEORGIATribot

4185 Billy Mitchell Road(P.O. Box 705)Addison, TX 75001-0705Phone: (800) 745·0125

HAWAIITribol

95-095 Kawau Street

Mitilani, Hawaii 967894097

Phone: (808) 531-1466

IDAHOTribol

Meadow Creek Office Park22516 SE 64th Place, Suite 220Issaquah, Washington 98027Phone: (800) 328-1902Facsimile: (206) 391-8206

ILLINOISTribol

1001 West 31 :st.

Downers Grove, illinois 60515Phone: (708) 663-0482Facsimile: (708) 663-0489

INDIANATribol

1001 West 31 st.

Downers Grove, Illinois 60515Phone: (708) 663-0482Facsimile: (708)6634489

IOWATribol

1001 West 31 st.

Downers Grove, Illinois 60515Phone: (708) 663-0482Facsimile: (708) 663·0489

KANSASTribol

8600 West Shawnee Mission Pkwy.Suite 306

Merriam, Kansas 66202Phone: (913) 362-9590Facsimile: (913) 362-9693

Tribol

Headquarters

21031 Ventura Boulevard, Woodland Hills, California 91364-2297Phone: (818) 888-0808 Facsimile: (818) 884-1885

££1,&0Mt(CASmOLCOME'NE

Sales Offices: United States & Canada

KENTUCKYTnbol

110 S. Huntington StreetMedina, Ohio 44256Phone: (800) 347-1440Facsimile: (216) 723·0852

LOUISIANATribol

4185 Billy Mitchel Road(P.O. Box 705)Addison, TX 75001-0705Phone: (800) 745-0125

MAINETdbol

Hill Professional Park Oflice Bldg.115 WaterStreet

Milford, Massachusetts 01757-3001Phone: (508)478-7442Facsimile: (508) 478-7989MARYLANDTribol

101 Southpointe DriveBridgeville, Pennsylvania 15017-1297Phone: (412)267-1140

{800) 347-1440Facsimile: (412) 221-1280

MASSACHUSETTSTribol

Hill Professional Park Office Bldg.115 Water Street

Milford, Massachusetls 01757-3001Phone: (508) 478-7442

(800) 736-4662Facsimile: (508) 478-7989

MICHIGANTribol

888 West Big BeaverSuite 313

Troy, Michigan 48084Phone: (800) 8294746Phone: (810)362-0979Facsimile: (810) 362-1026

MINNESOTATribol

4815 Burning Tree Road,Suite 210Duluth, Minnesota 55811

Phone: (218)727-4440Phone: (800) 727-3434Facsimile: (218) 727-7051

MISSISSIPPITribol

4185 Billy Mitchell Road(P.O. Box 705)Addison, Texas 75001-0705Phone: (214) 3874606Facsimile: (214) 3864914

MISSOURITdbol

4185 Billy Mitchell Road

(P.O. Box 705)Addison, Texas75001-0705Phone: (214) 3874606Facsimile: (214)3864914

MONTANATribol

Meadow Creek Oftice Park

22516 SEE 64th Place, Suite 220Issaquah, Washington 98027Phone: (800) 328-1902

(206)391-7997Facsimile: (206) 391-8206

NEBRASKATdbol

4185 Billy Mitchell Road

(P.O. Box 705)Addison, Texas 75001-0705Phone: (214)387-4606Facsimile: (214)386-4914

NORTH CAROLINATribol

4185 Billy Mitchell Road(P.O.Box 705)Addison, TX 75001-0705Phone: (800) 745-0125

NEVADATribot

21031 Ventura Boulevard,Suite 600

Woodland Hills, California 91364Phone: (800)622-1258

(818) 888-9345Facsimile:. (818) 884-1885

NEW HAMPSHIRETAbol

Hill Professional Park Oifice Bldg.115 Water Street

Milford, Massachuse!1801757-3001Phone: (508) 478-7442Facsimile:. (508) 478-7989

NEW JERSEYTribol

101 Southpointe DriveBridgeville, Pennsylvania 15017-1297Phone: (412) 257-1140

(800) 347-1440Facsimile: (412)221-1280NEW MEXICOTribol

21031 Ventura Boulevard,Suite 600

Woodland Hills, California 91364Phone: (800) 622-1258

(818) 888-9345Facsimile: (818) 884-1885

OF 366·61 1/95

Tribol

NEW YORKTribol

Hill Professional Park Office Bldg.115Water Street

Millord, Massachusetts 01757-3001Phone: (508) 478-7442Facsimile: (508) 478-7989

NORTH DAKOTATribol

P.O. Box 636

Bismarck,North Dakota 58502-0636Phone: (701) 223-5523Facsimile: (701) 223·9632

OHIOTribol

110 S. Huntington StreetMedina, Ohio 44256Phone: (216) 723-0852Facsimile: (216) 723-0852

OKLAHOMATribal

4185 Billy Mitchell Road(P.O. Box 705)Addison, Texas 75001-0705Phone: (214)387-4606Facsimile: (214)3864914

OREGONTribol

Meadow Creek Office Park

22516 SE 641h Place, Suite 220

Issaquah, Washinglon 98027Phone: (206) 391-7997

(800)328-1902Facsimile: (206) 391-8206

PENNSYLVANIATribol

101 Southpointe Drive

Bridgeville, Pennsylvania 15017-1297Phone: (412)257-1140

(800) 347-1440Facsimile: (412) 221-1280

RHODEISLANDTAbol

Hill Professional Park Office Bldg.115 WaterStreet

Milford, Massachusetts 01757-3001Phone: (508) 478-7442Facsimile: (508) 478-7989

SOUTH CAROLINATribol

4185 Billy Mitchell Road(P.O.Box 705)Addison, TX 75001-0705Phone: (800) 745-0125

SOUTH DAKOTATribol

1001 West 31st.

Downers Grove, Illinois 60515Phone: (708) 663-0482Facsimile: (708) 6634489

TENNESSEETdbol

4185 Billy Mitchell Road(P.O. Box 705)Addison, Texas 75001-0705Phone: (214)387-4606Facsimile: (214) 386-4914

TEXASTribot

4185 Billy Mitchell Road(P.0. Box 705)Addison, Texas 75001 -0705Phone: (214) 387-4606Facsimile: (214) 3864914

UTAHTdbol

21031 Ventura Boulevard,Suite 600

Woodland Hills, California 91364Phone: (800)622-1258

(818) 888-9345Facsimile: (818) 884-1885

VERMONTTribol

Hill Prolessional Park Office Bldg.115Water Streat

Milford, Massachusetts 01757-3001Phone: (508)478-7442Facsimile: (508) 478-7989

Tribol

Headquarters21031 Ventura Boulevard, Woodland Hilis, California 91364-2297Phone: (818) 888-0808 Facsimile: (818) 884-1885

dl aRMVH BSTROLCOMFANY

Sales Offices: United States & Canada

VIRGINIATribol

101 Southpointe DriveBridgeville, Pennsylvania 15017-1297Phone: (412) 257-1140

(800)347-1440

Facsimile: (412) 221-1280

WASHINGTONTribol

Meadow Creek Olfice Park

22516 SE 64th Place, Suite 220

Issaquah, Washington 98027Phone: (206)391-7997

(800)328-1902Facsimile: (206) 391 -8206

WEST VIRGINIATribol

101 Southpointe DriveBridgeville,Pennsylvania 15017-1297Phone: (412)257-1140

(800)347-1440Facsimile: (412) 221-1280

WISCONSINTribol

1001 West 31 : t.

Downers Grove, Illinois 60515Phone: (708)663-0482Facsimile: (708) 663-0489

WYOMINGTdbol

Meadow Creek Office Park

22516 SE 64th Place, Suite 220Issaquah, Washington 98027Phone: (206) 391-7997

(800) 328-1902Facsimile: (206) 391-8206

CANADA

EASTERNTribol Inc.

150 Consumers Road, Suite 403North York, Ontario M2J 1 P9Phone: (416)498-4988Facsimile: <416)498-6660

WESTERNTribol Inc.14627-128111. Avenue

Edmonton, Alberta Canada TSL3H3Phone: (403)452-9908

Facsimile: (403) 451-3340

OF 366-61 1/95

JUL. 9.1997 11:48AM

Sl 8/DP 09 JUL. 1997

Parent

Part Numbar

464610

464619

465378

465379

466380

468381

469382

465383

465386

465390

465399

465632

465639

465661

469758

469765

48706n

SIB/OF

DUFF NORTON COMPANY NO.268 P.2/4

Sinole Leve= 1 Bill With Mfo Notes (DF) Pane 1

Part Number : 750089

Descrintion : R530OP

Descriotion

118917 0-RING. VITON

087BRI-H RET, RING S.S.

5306-0 BRG SPA 3/4"-56

5310 FACE RING 3/4"-50

5308 SEAL RG 3/4" 5000 SE

5311 SAL RG S.S. 3/4"-5

2145 PIPE PLUG 1/2" S.S.5302 HSG S.S. 3/44-50

5319 WAVE SPRING 3/4" 500

5305 26MM 88 62055

R5303 SHF RH.NPT 3/4"-50

5306-I BRG SPA INNER.3/45316 SUP DISC 3/4"-5000

1/4"-28 SET SCR S.S.

0988F1TP RET RG 3/4" 5080

206AFITP RET RG 3/4" 5000

115 0 GREASE FITTING

09 JUI- 1997

Um : FA

Orw Quantit v

A

A

B

B

B

A

A

B

A

A

B

A

A

A

A

A

1.000000

1.nnnAOO1.00n000

1.8800001.000000

1.000000

1.000000

1.000000

1.0000002.000000

1.000000

1.0000001.000000

1.000000

1.00nnoo

1.ooonoo

1.000000

EA

EA

EAEA

EA

EA

EA

EA

EA

EA

EA

EA

EA

EA

EA

EAEA

Sincle Level Bill With Mfrl Notes (OF)

Renair

LIM PArt

RP

RP

RP

RP

RP

RP

RPRP

Pace 1

.

0-

ru

2

Z

b

Ai

1*

3 'R

THREAD "A- ORDER NO ' MODEL NO SHAFT NO

314-14 IFT LH 75000/ LBOOP 465398

94 14 IfT 101 15008, R5300P 465399

1.-141*5 Mr Lit 150]51 L532*P , 465545

r-1406 MT Lai 750]52 R5324P 4655463/4--16 Br Lit 750153 l_530(r-20 465547

3/4£118/ RH 750154 RSIOOP-20 465548

U# 14 ES' Ul 750243 l.530©P-19 4GS67G

3/4 14 BEFF M I 750244 RSSOOP-19 465677

alia £EmE , 150155_ 053001' 465549

** COPPER BASKET PART #482173 FORMACHINE THREADED SHAFTS ANDPART #465828 FOR BSPP SHAFTS

USE LOCTITE PIPE SEALANT #567AND LOCTITE PRIMER #7649 FORSEALING. WIPE OFF EXCESS AFTERTIGHTENING PLUG

f 0.e[D

0-0-

1 -3| .89 |. 38

QUICK RELEASE DESIGN

QUICK RELEASE ASSEMBLYPART ORDER NUMBERS:

FLANGE

SPLITWEDGES

COPPERGASKET

SPRING

CLIP

465746

485618

485607

463334 83326

'Sn

00

CY N00

--

E

il,rv

lesne --1/2" NPT

3/4- NPT

REVISED&REDRAWN

Ham CHAGE

464610

465639

465386

488067

464619

092294nye

500069

465758

482060 AND465661 (PLUG)

465381 465378

465380 465390 (2 ROD)

X-6477-119 465383

465379 465765

-SHAFT No

0

465832

e Z

3-1/16"

TT

5-1/4 APPROXIMATELY

9H

;I

ill----Lar--

3/4

1-11/32"

Mi, Imiwu,8 Coll,NM ImiN e=I /mipiC in DI,40,mll ,HAle Alr 1, m I

010 mY Poly:,S IM,Ul N,I,JI M li,0/mlm. aN: /ullylil il,Au Nal me CIM=»u, INIX

I... MI C= .Rm-,Emuni n.=.0 *- al,NromoN =,AMT.

rmall/E .1 W=.m "//Innnrs; rm,r= s,E·n

DIEsion I =ImDEmMIL- =COO Z.OM 12=065

51[FE Room*[Es rE Eclo IMH %19

rlm= M 99=* st, r#2(L V

JnES** 111;IE COSh,CR 1110* 11

¤El* Ca- am.Min 2

ZOOI

7

l /J

:11--0!0

| DUFF·NORTONCHARLOTTE. NORTH CAROLINA

3/4" 5000 SERIES P-TYPE ROTARY UNION 1

MATERTAL SEE ABOVE

ORMA|| CH, 11 *-ZI

PAT'r. Na -9 102093 mul· 4- i

*£*T9RZAT

500069

11

IT

TYPICAL ASSEELY

6ADAM DRAWING-DO NCT REVISE MANUALLY

SEALM8SIER

SEALMASTER Ball Bearing zone hardened, extended inner races are ground for a sliding fit overthe shaft. Setscrew locking bearings are easily and securely locked to the shaft by means of twoself-locking, cup point, socket head setscrews. A positive race-to-shaft lock is attained when theground threads of the setscrews are securely tightened through the soft, extended ends of the innerrace. The hardened cup point penetrates the shaft surface trapping the shaft material. The cup hasflat faceted surfaces inside which prevent the setscrew from backing out during operation.

SETSCREW

DIAMETER

HEX SIZE

ACROSS FLATS

66

126

228

348

504

1104

SKWEZLOC locking units are locked by tightening a single socket head capscrew in the collar.Uniform clamping pressure in a concentric grip is attained which does not indent or mar the shaft.

Table 2

TORQUE FOR TIGHTENING SETSCREWS

1/4

5/16

3/8

7/16

1/2

5/8

1S

5/32

3/16

782

1/4

5/16

MINIMUM RECOMMENDED

TORQUE

INCH LBS. FOOT LBS.

AWARNING

5.5

10.5

19.0

29.0

42.0

920

INSTALLATION INSTRUCTIONS FORSETSCREW AND SKWEZLOC LOCKING

Mounting Instructions

AWARNINGFailure to observe

safely precautionscould cause

personal injuryor equipmentdamage

Setscrev Locking -

1. Use clean shafting free of nicks and burrs. If old shafting is used, locate SEALMASTER bearing on an unused section.

2. Make certain setscrews are clear of bore.

3. Slide SEALMASTER bearing into position on shaft. Never hammer the ends of the inner race, as they may be damaged.If necessary to apply force, use a brass bar or pipe againstlhe inner race only 10 drift bearing into place. Never strike thehousing as it may damage the bearing.

4. Bolt housing to support.

5. Rotate shaft to make certain it turns freely.

6. Tighten self-locking, cup point setscrews securely onto the shaft. If a torque wrench is used, see Table 2.

SKWEZLOC Locking

1. The optional SKWEZLOC locking unit is assembled on the shaft as per points 1 and 5 above. Then, slide the collar intoposition on the extended end of the inner race seating it squarely against the shoulder. Tighten the capscrew to thetorque indicated in Table 3 below. Do not exceed the indicated torque value.

Table 3

TORQUE FOR TIGHTENING SKWEZLOC COLLARS

CAPSCREW

SIZE

#8-32

UN03 A

#10-24

UNC-3 A

#1/4-20

UNC-3 A

#916-18

UNC-3 A

HEX

WRENCH

SIZE

1/8

9/64

3/16

1/4

MAXIMUM TORQUE

INCH LBS.

Disconnect all power while adjusting units

70

90

180

400

FOOT LBS.

5.8

7.5

15.0

33.3

{Sfilt] 446}ES> :s>zi.#.:;,3 6 ... f'.i ; :5·-5/5/33-6 ·< ::]··J . ··,4.8*;*}*33:226,ZI)*.-14UBRIdATION INTRUCTIONS ··:i " =' Zi.71-':4Yir/*4,%-,12.*,2-ir,4,5,·LAi_.·m..:F.'#,t'. t.fries.:, 9 r ., t

i:,6-..1,531'.***.r'-1**il'SE*EmASTER bearing uftits· ate pielubrical OV#6 greasechosen foritachemicaland mecfliniclistability.SEDdMASTER J ':311-83:C'efbt?. f?ff.b*iririgh*re'deSidnect for lubrication:witti'¥reak Units furnished with a grease fitting should be periodicaliyfelubricated.

1'''*; Z.'3 45.55,:JhdreliriEatid;;rintervhl depends orifberirk; ipinling conditions: speed. temperature, and environmelif. (Sed Conditionsi--· :): '-:n, '3 in Table 1 6elow for typical· relubri*on schedules.)

- - -1 . L . 2'1 Figure 1 shdws the annularpassage and pot< feature,of the SEALMASTER relubricable units. This feature provides positive-meanaforrellibrlcation while allowing seveal dogrees of misalignment. If the grea* fitting·supplfed with the unit is re-placed, mpke certain the same [ength.of.th[id engagement is maintained.

-1 -

. APPROX 1 1/2'

ALEMITE FITTING. -fl 4 MISALIGNMENT EACH

. SIDE OFCENTERORADAPTOR AE<trrn

LOCKING PIN

iDLE@9:1 NOTE V GROOVE

SEALMASTER - -1i BEARING

ZONESLOW SLIGHT BEAD FORMS HERE

=-Ri » GREASE WHILE RUNNINGWHEN POSSIBLE. PUMP

HARDENING

Fig. 1

Relubrication

1. Add grease slowly with shaft rotating until a slight bead forms at the seals.

2. Relubrication is generally accompanied by a temporary rise in operating temperature until the bearing chamber isstabilized with the proper amount ot grease. 9

1

3. If necessary to relubricate while bearing is stationary, refer to SEALMASTER catalog for maximum grease capacity forthe size bearing.

4. For abnormal operating conditions of high temperature or abnormal environments, consult SEALMASTER Engineers.

5. Rotate shaft to make certain it turns freely. '

6. Tighten self-locking, cup point setscrews securely onto the shaft. If a torque wrench is used, see Table 2

Tabl/1

SPEED)

100 RPM ,

500 RPM

. 1000.RPM

1500 FFM

Any Speed .

Any Speed

Any Speed

Any Speed

TEMPERATURE

UP b 120° F

Up b 150• E

--UP,t>2101.63=---*

Over 210° R

Up 10 150« F.

Over 150° F.

Any Temperatire

Any Tempgature ,

CLEANLINESS

Clean

Clean

daan

Dilly

Dirty

Very, Crty

Extome conditions

GREASING

INTERVAL

6 10 12 Months

2 to 6 Months

2 ek:1> 2 Monthe-- ·

Weeldy1 Week b 1 Month

L

Daily 9 2 WeeksDaily 6 2 V*ieks 1Daily b 2 Weeks

For normal operating conditions, relubricate with a grease conforming to NLGI No. 2 pei1etrati6n, free from chen*cal impu-rities, such as dust, rust, metal particles or abrasives.

d S

4 ;· AL

.r . i 1 ..i,,5.r-- 4

Form #86-164-A 1/30/97 U9 Eme;son PowerTransmission Corp.Printed in US.A. 1 SEALMASTERI- AURORA, IL 60507

E LINE AC

1·.

1

1

1

1

1

1

1

1

1

1

1

1

1

1

4

1

1

1

1

1

2

1

1

1

1

1

1

2

2

1

RELIANCESmELECTRIC IE]

CUST. PO. NO. DATE

727826 07/11/97

SOLD TO DODGE-NEWARK SUPPLY CO,INC

198 RTE 46

FAIRFIELD NJ 07004

1 SHIP TO DODGE-NEWARK SUPPLY CO., INC.

198 ROUTE 46

FAIRFIELD NJ ' 07004

PROD LINE

HERTZ HP

60 5

MOTOR ID

FRAME SIZE TYPE INSL

E 014TC P F

RPM

BRG, DRIVE END

1740

QUANTITY PART NUMBER

802327-1!A

33050-l A

403783-G

75450-Y

65774-11A

416821-2F

416821-2G

609898-2BA

603207-SJS

418424-33BE

801714-2L

400638-18

78546-1G

78565-3AM

602538-l A

602453-9008

404832-18A

49374-1OL

34180-14CA

1507-A

412043-12A

418150-3A

48977-298

33775-4EA

4824-12DP

415072-lA

34180-6DA

801715-4AA

404832-188

415045-2K

404080-8

34036-12AB

418150-3A

48977-298

STICKERS & TAGS

STICKERS & TAGS

STICKERS & TAGS

I J

VOLTAGE

0000 230/ 460

308C02JPP30A

46101-8

E01613-8 E 02

412031-IA

PARTS

B

SALES ORDER NUMBER

1 YA897941 01 PAGE : 1

SPECIAL MARKS: R2759

ENTIFICAT

DESIGN SERV FCTR

1.00

FT/MIN

ION

PHASE AMB.

3 040

FL AMP

12.8 / 6.40000

DUTY

CONT

BRG,OPP DRIVE END 258C02JPP30A

LIST

PART DESCRIPTION DISC. SYM LIST PRICE

FRAME

EYEBOLT Sl

RETAIN PINCOND BOX

TERM BOARD Sl

8 BRG,FE 51

8 BRG,BE 51

CAP.BE INNERSHAFT

ROTOR

BRKT,FE

'4 WAVE WSHR,FE BRKT Sl

FAN,FE OUTER Sl

CVR.FAN

GRILL,FAN CVRBRAKE

OIL SEAL,FE Sl

SPCL SCR,FE BRKT

KEY,BRAKE

WARN TAG,BRAKE

PLUG,FAN CVRGREASE FTG CAP,FE Sl

ALEM FTG FE

DR SCR,N/PLT Sl

N/P ADHESIVE

CLAMP,FAN St

KEY,OUTER FAN

BRKT.BE

OIL SEAL,BE Sl

SLINGER,BEORING WSHR BE CAP Sl

EXT.TOOTH LCKW

GREASE FTG CAP.BE Sl

ALEM FTG BE

3.00

3.00

14.00

27.00

2.00

61.00

16.00

1.00

1.00

3.00

12.00

1.00

1.00

ENCL

TEFC

CODE

3

,1

f.4

:. 4,,'t.,ttf. li..

...

Installation, 6 .1

Obaration And Maintenance OfReliance®-Standard

, . . |·1, 814; i,kir.1. i ..,-,ILm;

industrial.jAC 3; 1

- , .tri triq/: br V,A: H -1 :, ' 1 41 « ' 3Induction Motors• 180

• 112

449·Frames-(NEMA)280 Fr*6<(IEC)

, 1, Iii 23•': f .,

"

': 4

. - C ar'1boliitions

AC MOTORS *u CanTrust"

.-. I ' " ... .

Instruction Manual 8-3620-23

March, 1997.,:,r i

.,O, .%.6.1 4,2' 4.

3 9,<' L#S du :2

:"iel 1 1 (.1'. 3,• .

t..:d,:.r'k no n.1, be' ROCIONell Automauon

·· tr:p A444 ' jttf'FRenanbe'E/ecMe f' - .

Table of Contents

3.

RECEIVING AND HANDLING ...

ACCEPTANCE..,.. lt.'..

EXTENDED STORAGE - AC MOTORS, DC MOTORS,'' GENERATORS ANb SHIPBOARD MOTORS ...................

STORAGE CONDITIONS - SHORT TERM ............STORAGE PREPARATION ...................

FOR STORAGE OF EXTENDED PERIODS OF TIME(GREATER THAN i8 MONTHS)......................UNPACKING ...f?.'.

...............

INSTALLATION .

INSPECTION .....

LOCATION ...

LIFTING MEANS ...

MOUNTING ................................

MOUNTING OF 6&8 HOLE MOTOR FRAMES ..DRIVE

ROTATING PARTS .........................

SOME SATISFACTORY METHODS OF GUARDING ......

STARTING

DRAIN PLUGS ..... ...............................

ROTATION

TEST FOR GENERAL CONDITION .................

INITIAL LUBRICATION ........................

OPERATION

MAINTENANCE AND REPAIR ................................................. 8

DISASSEMBLY .8

REMOVING BRACKETS AND ROTOR

REMOVING AND REPLACING BALL BEARINGS ........... .................. 8

REASSEMBLY .......................................

LUBRICATION OF BEARINGS ................................................. 9

GREASE LUBRICATED BEARINGS ....................

RECOMMENDED LUBRICANT

, BALL' BEARING'MOTORS' ROLLER BEARING MOTORS . :r..:......:

,

LUBRICATIONROCEDURE t.... A- LUBRICATION INSTRUCTIONS.............

0

': SERVICE CONDITIONS

LUBRICATION FREQUENCY ........................ ......................10

LUBRICATION VOLUME"..j:.::....

/ 1REPLACEMENT BEARINGS:..........

GENERAL CROSS SECTION AND PARTS IDENTIFICATION DRAWING

TOTAL SERVICE PROGRAMS ................................................12

RENEWAL PARTS

ADDITIONAL LITERATURE................................................ 12

Rellance® Is a trademark of Reliance Electric industrial Company or its subsidiaries.©1997 Rockwell international Corporation

1 ' ·st;Ii.;A?·

3

3

4

4

4

4

4

5

5

5

6

6

6

6

6

1

1

2

2

1

1

1,

4

i

-

]*11$,as::M' 4. j.« .5

DANGER

ONLY QUALIFIED ELECTRICAL PERSONNEL FAMILIAR WITH THE CONSTRUCTI6N AND OPERATION'OFTHIS EQUIPMENT AND THE HAZARDS INVOLVED SHOULD INSTALLi ADJUSI OPERATE, AND/OR SER-VICE THIS EQUIPMENT. READ AND UNDERSTAND THIS MANUAL IN ITS ENTIRETY BEFORE PROCEED-

ING. FAILURE TOOBSERVETHIS PRECAUTIONCOULDRESULT IN SEVEREBODILY INJURY OR LOSS OFLIFE. ,

The products described in this manual are manufactured by or for Reliance Electric Industrial Company.

RECEIVING AND HANDLING

ACCEPTANCE

Thoroughly inspect the equipmeht before accepting ship-ment from thetransportationcompany. If anyof thegoodscalled for in the bill of lading or express receipt are dam-aged orthe quantity is short, do not acceptthem until thefreight or express agent makes an appropriate notationon your freiht bill or express receipt. If any concealedloss or damage is discovered later, notify your freight orexpress agent at once and rqquest him to make an in-

spection. We will be very happyto assist you in collecting

claims for loss or damage in shipment; however, this will-ingness on our part does not remove the transportationcompany's fesponsibility in relmbursing you for collectionof claims or replacement of material. Claims for loss ordamage in shipment must not be deducted from the

Reliance Electric invoice,nor should payment of theReliance Electric invoice be withheld awaiting adjustmentof such claims, as the carrier guarantees safe delivery.

If considerable damage has been incurred and the situa-tion is urgent, contact the nearest Reliance Electric Sales

Office for assistance: Please keep a written regord of allcommunications.

*.

EXTENDED STORAGE -

AC MOTORS

If considerable damage has been incurred and the situa-

tion is urgent, contact the nearest Reliance Electric SalesOffice for assistance. Please keep a writtpn record of allcommunications. .,

STORAGE CONDITIONS -

SHORT TERM

The following storage requirements must be followed:

1. Motors are to be kept in their original containers orprovided with equivalent protection and stored in a

warehouse free from extremes in temperature, hu-midity, and corrosive atmosphere.

2. If unusual vibrations exist at the storage location, themotor should be protected with isolation pads.

3. All breathers and drains are to be operable while instorage dnd/or the moisture drain plugs removed. Themotors must be stored so the drain is at the lowest

r point. ., -

STORAGE PREPARATION : h 1-''id 4, 5 I iImproper storage of electric machines will result in seri-ously reduced reliability of that equipment. For example,an electric motor that does not experience regular usagewhile being exposeEI to normally humid atmospheric con-ditions is likely to cause the bearings to rust or rust par-ticles from surrounding surfaces to contaminate the bear-ings. The electrical insulation may absorb an excessiveamountof moisture leadingto the motor winding failing toground. The following preparations should be followed:

1. Minimize condensaton in and around the motor byuse of desiccants or other humidity control methods.

2. Motor space heaters when specified are to be ener-

gized where there is a possibility that the,storage amibient conditions will reach the dew point. Space heat-

' ers are an option. ,

3. Coat all external machined surfaces with a material to

prevent corrosion. An acceptable product for this pur-i pose is Eicxon Rust Ban #392.

+

4. Measure and record the electrical resistancd of the

winding Insulation with a megger or an insulation re-,

, sistanpe meter. Minimum accepted Megohm level ist:ithe insulation ky rating +1 Megohm. If leyels fall below '

, the above, contact the nearest Reliance sales office.

The recorded data will be required when removingfrom storage.

.

-:·,1,·; 21.,

.:1

5.IL>me motors have a shipping bracqattached tp the .0 ' ' shaft to prevent damage during tran®ortation. The .

shipping brace, if.provided, must:be removed and· stored forfuture use. The bra9e must be reinstalled to.

· hold the shaft firmly in place against the bearing be-fore the motor is moved. ..' ., 4. ./ I

6. Upon placing the motor into extended storage (great-er than 3 months), the motors with regreasable bear-ings must be greased per Table 1 followed by the mo-tor shaft being rotated a minimum of 15 times aftergreasing. Non-regreasable motors with "Do Not Lubri-cate" nameplate should also be rotated 15 times to re-distribute grease within the bearing.

7. Remove the grease drain plug, if supplied, (oppositethe grease fitting) on the bottom of each end bracketprior to lubricating the motor. Replace the plug aftergreasing.

Table 1. Lubrication Volume (Storage)

NEMA . Vol. in

' ' ' Frame Size (IEC) Cubic in. (Cm3)182 thru 215 (112 - 132) 0.5 (8)

254 thru 286 (160- 180) 1.016)

324 thru 365 (200-225) : - r ' 1.5(24) 'r 404 thru 449 (250 - 280) 2.5 (40)

s' ,,•

./ . 01 -

8.''Regreasable bearings are tc; be greased per Tabld 1aillibtir6 of Being pla6ed into extendidstorage. Mo-

+ tdrshaftiareto be rotated at least 15 revolutions man-"' lialli> e06ry 3 rhonths and dditional grease added ev-

erynine months perTable 1 toeach bearing. Bearings41re to bi greased at the time of removal from storage.

Non-regreasable, motors should have their shaft ro-tated 15 revolutions every 5 months.

9. All breather drains should be fully operable while instorage:The motors mlist bd stored so the drain is atthe lowest point. i All breathers and automatic Tdrains must be operable to allow breathing at pointsother than through the bearing fits. ' 8

10.The space hehters when specified are to be con-' nected and operable while in storage. c11. Windings are to be meggered atthe time equipment is

' put in storage. Reference Para. 4 on page 1.'At thetime of removal from storage; the insulation resis-tance reading must not have dropped more than 50%from the initial reading. Any drop below this point ne-cessitates electrical or mechanical drying. Refer to"Motor Drying Procedure."

.

12.Where motors are not stored in the original contain-ers, but are removed and mounted on other pieces of

2

't ' machinery, the mounting must be such that the drains' and breathersand space heatersare fullyoperable. Inthis respect, the drains must be kept at the lowestpoint in the motor so that all condensation can auto-matically drain out.

FOR STORAGE OF EXTENDEDPERIODS OF TIME

(GREATER THAN 18 MONTHS)All requirements of general preparation and short termstorage apply with the following additional requirements.

1. Motoristo becratedinaboxsimilarto EXPORTBOX-

ING but that the "shell" (sides & top of box) will beLAG-BOLTED to the wooden base (not nailed as ex-port boxes are). This design will allow for the openingand reclosing the box many times without destroyingthe "shell".

2. The motor will be sealed in an air-tight vapor barrierbag with desiccant inside. This airtight bag will giveadded protection during shipment of motor to the per-manent storage area.

3. Afterthe first"Inspection" for megger reading, turning- the shaft, etc., the «por. bag should be re-sealed by

taping it closed with maskingior similar tape. Also addnew desiccknt inside bag before closing. The shellshould then 6e placed overthe motor and the lag boltsreplaced.

4. If a "zipper-closing" type bag is used instead of the"heat-sealed" type bag, then rezipper the bag closedinstead of taping it. .

5. Be sure to add new desiccant inside bag after eachperiodic inspection.

6. Minimizethe accumulation of condensed waterin andaround the machine.

UNPACKING

After unpacking and inspection to see that all parts are ingood condition, turn the shaftbyhandtobesurethereareno obstructions to free rotation. Equipment which hasbeen in storage for some time should be tested and relu-bricated (regreasabletype) priorto being put into service.Refer to "Test General Conditioh" and "Lubrication"for

procedure to be performed after extended storage.

Equipment with roller bearings is shipped with a shaftblock. After removing the shaft block, be sure to replaceany bolts usedto hold the shaft block in place during ship-ment that are required in service.

is S f.,:%''

r

3&709*AAFI?,·,1..4,39

, DANGER

ONLY QUALIFIED ELECTRICAL PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF,THIS EQUIPMENT AND THE HAZARDS INVOLVED SHOULD INSTALL, ADJUST, OPERATE, AND/OR SER-VICE THIS EQUIPMENT. READ AND UNDERSTAND THIS MANUAL IN ITS ENTIRETY BEFORE PROCEED-

ING. FAILURE TO OBSERVETHIS PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSS OF·

LIFE. '

INSTALLATION

INSPECTION

Afterthemotoris unpacked, examinethe nameplate data

to see that it agrees with the power circuit to which it is to

be connected. The motor will operate with frequency notmore than 5% and voltage not more than 10% above or

below the nameplate data, or combined variation of

Variation

Voltags Variation:

120%

VORage

110% voltage

Function of

Vokage

90%

Voltage

herease

44% .

Sta® 9 andmmnum

runningtorque

**

meass 21%

{,ollage)2

decrease

19%

Fiequency variation:

10516 decrease

frequency 10%

Function 01 1

frequency (fmquenq) 2

Synchro-nous

speed

nochanga

nochange

constant

no

change

Increase

5%

frequency

sEP %

decrease

30%

decrease

17%

#0694 2

Increase

23%

pracall,rodlange

voltage and frequency of not more than 10% above orbe-low nameplate data. Efficiency, power factor and current

may vary from nameplate data. Performance within thesevoltageand frequencyvariations will notnecessarilybe iAaccordance with the standards established for operationat rated voltage and frdquency. . , ...1. , f 1.' .

Typical Effect of Voltage and Frequency Variation oninduction Motor Characteristics

FuR-Load

# Speed

*crease

15%

ncrease

1%

(synchro-nous

speed

decreass

, 1.1/2%

(Vavo-nous

speedSUP)

decrease

5%

sightdmN

hCrBase

5%

decrease

2 p©08

aghtkrease

60%

decrease

(1·75 HP)B.3%

Increase

(100·300

HP)

Ssghtdecrease

FuU-load

3/4

Ellidenc,

decrease

1/2.2 ,poklts

practicallyno

change

INghtIncrease

praaicallyno

change ;

decease

7.20

points

slight61088/8

1/2

load

decrease

1·2 polnts

krease

1-2 points

Full load

slightIncrease

deczease

5-10

pobts

decraase

5-15

points

bcreas,5

90&1ts

powsr FactodCOSe

3/41oad

decraase

10-30

Pohlts

0 .

decrease

5 poh*

ir:c:ease

24 points

*9htIncrease

1/21oad

3

iI

dacriase

15-40

poirds • •

decrnse

5-6 poans,

Increase4-5 poklts

Ughtcrease

Increase

12%

Increase

2-4%

4.

increase

10-11% .

Fufload

current

decrease

slightly

95% increase 11% decrease practically sight SU'1 61101! /110't dght *t r Increasshequency .9 5% nochange decrgase , decrease decrease decrease decrease decrease Slightly

1%phase sight sught 2% 54% , 1.1/2% '

unbalanca decrease decreass decmaza dacraass hor,ase

2% phasa slight slight sOoN 8% 7% " . 3%

unbalance decteass decrease decrease decrease decrBass ' increase

..

NOTE: This table shows general effects, which will vary somewhat for specific ratings.

increase

20%

krease

56%

SigM ,d#Crease

52

voltage

decrease

10-12%

Uea I10-12% L

decr,2130

54%

frequency

anoht' - idecrease

.

Increase 5-6°C.

U-75116Decrease

34°C

(100-300

HP).

#craas 9

34® C.

Tomprise, luU

load

*Base

6-7°C

decrease

reaS"

2% kbcroa50

SM'hclease

Mardmurn

ovefload

cepacity

decrease

6*4

44%

2 4increass

21%,311

6$660.1

decrease

19%

decrease

sightly

.*5

Magneticnoise-

»loadin

par!ar

able .

Increass

-444

*cruse

s¥* 1.*b..

bxrnaSs :slightly

'PA..f :

1 Ii.·'h' f.

: Bl 64.i

decrease

heraase.

5tly

8.

-fl .

4

LOCATION d ' 31'j:,·';:li *.:'r. '.I . :'*3'1'.:' 5.'lipplications. After carefully aligning the motor with theThe 1116t6r should be installed'i a locati-compatibie' driven unit, bolt securely in place.with the motor enclosure and specific ambient. , . When motors, which are normally mounted with the shaft

To allow adequate air flow, the following clearances must . in a horizontal position, are mounted vertically, it may be

be maintained between the motor and any obstruction: · necessary to provide additional guards to prevent foreignobjects from falling into the motor openings and striking

TEFC (IC0141) rotating parts. Such guards may be obtained at the time ofEnclosures purchase or from a local service repair center.Fan Cover Air Intake

Exhaust

r , Ly

Protected Enclosures

Bracket Intake , -

Frame Exhaust

I ..1'91 1.4.. :

1 LIFTING MEANS.

- 180 - 21 OT Frame 1"

250 - 449T Frame 4"

IEC 112 - 132 2.5 cm

IEC 160 - 280 10 cm

- Envelope equal to the "P". dimension on the motordimension sheet

- Same as TEFC

Exhaust out the sides-envelopeaminimum Ofthe"P"dimension

plus 2" (5cm).Exhaust out the end-same asintake. . ,

I i,1 1

;A*£ass,w**imrss". , , ,*Tr· t V,j!11 1 11 = 1 1- ' Ill Alif.ARNING , *, .>_.., ,_ -j ,

WHEN A LIFTING MEANS IS PROVIDED FOR

HANDLING THE MOTOR, IT SHOULD NOT BEUSED TO LIFT THE MOTOR PLUS ADDITIONAL

EQUIPMENT SUCH AS GEARS, PUMPS, COM-PRESSORS, OR OTHER DRIVEN EQUIPMENT.FAILURE TO FOLLOWTHESE PRECAUTIONS

i

COULD RESULr [N BODILY INJURY.:2 - .. jt

'i Z : ':

In the case 6f assemblies on a common base, any liftind vmeans provided on the motor or generatoj should not beused to lift the assembly and base but, rather, the assem-bly should be lifted by a sling around the base or by otherlifting means provided on the base.' In all cases careshould be taken to assure lifting in the direction intendedin the design of the lifting means. Likewise, precautionsshould be taken to prevent hazardous overloads due todeceleration, acceleration or shock forces.

MOUNTING

Mount the motor on a foundation sufficiently rigid to pre-vent excessive vibration. Roller bearing and ball-bearingmotors may be mounted with the shaft at any angle. Roll-er bearing motors are not suitable for coupled duty

Explosion proof motors are shipped from the factorywith the condqik box mounted. If the conduit box is re-moved or rotatdd, a minimum of five (5) full threads of en-gagement on the motor.pipe nipple must be maintainedfor explosion proof integrity, of the conduit box.

, Some motors have standardized frames containing 6 or8 ·mounting holes. 6 hole frames are notsuitable for field re-versal of mounting from F-1 to F-2, etc. The following dia-gram indicates the proper mounting holes to use.

MOUNTING OF

6 & 8 HOLE MOTOR FRAMES

View From Above

??111111

Not present on "6-hole frame"Not· used on "8-hole frame"

(Allows F-1 to F-2 conversionon 8-hole frames)

11

Use these holes for

short frame designations182,213,254,284,324,364,404,444 (NEMA) .

DRIVE

SHAFT

END

Always use these holeswhich are closer to shaft.

112S, 1325,16OM, 18OM,2OOM, 2255,2505,2805(IEC)

Use these holes for long frame designations184, 215,256, 286, 326,365,405,445 (NEMA)

i (IEC) 112M, 132M, 1601., 20OL, 225M, 250M, 28OM

DRIVE

The pulley, sprocket, or gear used in the drive should belocated on the shaft as close tolbe shaft shoulder as pos-sible. Heat to install. Driving a unit on the shaft will dam-age the bearings.

Belt Drive: Align the pulleys so that the belt will run true;tighten the belt just enough to preventslippage, anytight-er will cause premature bearing failure. If possible, thelower side of the belt should be the driving side.

:. ;:'. i.'.:i...,12.31 :,1

-

Chain Drive: Mount the sprocket on the shaft as close tothe bracket as possible. Align the sprockets so that thechain will run true. Avoid excessive chain tension.

Gear Drive and Direct Connection: Accurate alignment isessential. Secure the motor and driven unit rigidly to thebase.

ROTATING PARTS

t-]-' - L.-- - I T'*i.WAKA':460*ARi>]fff,

ROTATING PARTS, SUCH AS COUPLINGS, PUL-LEYS, EXTERNAL FANS, AND UNUSED SHAFT

EXTENSIONS, SHOULD BE PERMANENTLYGUARDED AGAINST ACCIDENTAL CONTACT

WITH HANDS OR CLOTHING. THIS IS PARTICU-,LARLY IMPORTANT WHERE THE PARTS HAVE

SURFACE IRREGULARITIES SUCH AS KEYS,KEYWAYS OR SET SCREWS. FAILURE TO OB-

SERVE THIS PRECAUTION COULD RESULT IN

BODILY INJURY.

46SOME SATISFACTORY METHODS OF ·

GUARDINGARE:

1. Covering lila. machine and associated rotating partswith structuial or decorative parts of the driven equip-ment.

2. Providing covers for the rotating parts. Covers shouldbe sufficiently rigid to maintain adequate guarding innormal service.

DANGER

THE USER IS RESPONSIBLE FOR CONFORM-ING WITH THE NATIONAL ELECTRICAL cobE

AND ALL OTHER APPLICABLE LOCAL CODES. WIRING PRACTICES, GROUNDING DISCON- ,NECTS AND OVERCURRENT PROTECTION

ARE OF PARTICULAR IMPORTANCE. FAILURE''TO OBSERVE THESE PRECAUTIONS COULD

RESULT IN SEVERE BODILY INJURY bR LOSS.

OF LIFE.

'Lit-.;

5

DANGER

SUBSEQUENT :STEPS'r';REQUIRE i ROTATING'

PARTS AND/OR ELECTRICAL CIRCUITS.TO BE,

EXPOSED. STAY CLEAR IF UNIT MUST BE RUN€

NING OR DISCONNECT AND LOCKOUT OR TAG>

POWER SOURCE IF CONTACT MUST BE MADE.

, .. , I ' .

Connect the mbtor io the p6wer supply according to'thEliagram'on tho motor nameplate. For most 230/460 Ooltmotors, nine leads are brought out from the stator wind-ings sothatthe motor may be connected foreither 230 or460 volts.,. u, ·,·.A , , 0 :· en

,

GROUNDING ; ,„ 11. L: , i r#':1 /1 4:i

In the USA consult the Natiohal Electrical Code, Anic\e430 f6r information on grounding of motors; Article 445 forgrounding of generatorsi'and,Article'250 for general'inlformation on grounding. In mailing the ground bonnecllion, the installer should make certain that there is a solidand permanent metallic connection between ttie ground

-

point, the motor or generator terminal housing, and the

motor or generator frame. In non-USA locatiops consultthe appropriate natiohal or local code applicable. 1.. ,-1 .

i -6.1, 1 e· 3 :1111·:>:ti:sE; SMotors with resilient cushion rings usually-Must bd pro=vided With a bondirig conductor acr6ss the resilient m*miben Some motors are supplied *lth the bondinb conducl

1 1 *,r

torontheconcea16dsideof thecushion ring to protect thd* ie 1 *

bond from damage: Motors with bonded cushion, ripgsshould usually·be grounded at the time of installation inaccordance with the above r666mmendations formakihgground connections.,When motors with bonded cushionrings are used in multimotor -installations emploing

1 group fusin'ggroup protection, the bonding of thecushrion ring should be checked to determine.that -it'is' adelIluatefor the rating of the branch circuit overcurrent prol

.tective device being used. . -." ..!. ,i

*V

There are applicatiohswhere groundingtheexteriorpartsof a motor or generator may result in greater hazard byincreasing the possibility of a peroBiri the area,simulta-neously contacting ground and some oth,9r rle,arby,liveelectrical parti'of'other ungrddnded electrical equipment.In portable equipment it is difficult to be s\.Ird thai 6 dosi-tive ground connection is maintained as the equipment ismoved, and providing a grounding conductor may lead toa false sense of security. . ».1

,

The user must select a motor starter And overcurrent*3,

protection suitable for this motor and its application. Con-suit motor starter application data as well as the Nati6nalElectric Code an4/or other applicable local codes. '*

t''

h, DANGER2 1.14 ... . 4(-IU h'SUM· .'•C''..2.? ... I.- .., .4

WHENICAREFUC¢.CONSIDERATIONCOF .THEHAZARDS INVOLVED' iNFAiPARTICOLAR 'AP-PEICATION INDICATE THE: MACHINE FRAMES

SHOULD NOT, BE. GROUNDED OR.WHEN UNLUSUALLBOPERATING:<CONDITIONSMDICTATE

'THATA GROUNDED FRAME CANNOT BE USED,

,JHE INSTALLERSHOULD,MAKE SURE THE MA-, CHINE,IS PERMANENTLYAND, EFFECTIVELY .INSULATED FROM GROUND. IN THOSE

INSTALLATIONS WHERE , THE · MACHINE ,FRAME IS INSULATED FROM GROUND, IT IS'RECOMMENDED THAT APPROPRIATE WARN-

ING LABELS OR SIGNS BE PLACED ON,pR INTHE ABEA OF THE EQUIPMENT BY THE IN-STALLER. FAILURE TO OBSERVE THESE PRE-

. CAUTIONS COULD RESULT IN SEVEREBODILY, INJURY OR LOSS OF LIFE. ,,

STARTINGf- 1, 13'.1-t ' f

J -1

t----A

BEFORE STARTING MOTOR, REMOVE ALL UN-4 * 4 + •k

*|1SEf,SHAFI -KEYS AND LOOSE ROTATING-,PARTS,Tg PREVEN THEM FROM FLYING OFF.",FAILURE.,TO ' OBSERVE , THIS ' PRECAUTION,*COULD RESULT INBODILY INJURY. '·,, . ,. J.

71·.11*illitta }41 0- .i 6,41 1:. 1:Li·, 1,·'11' "ty Lif'·*04, t": · 'r

--- TAS -f-5 :1*>.EAUERAYFURN#F*frkmuCheck direction of motor rotation before coU-

pling motor to load. Failure to observe this pre-caution could result in damage to or destruction

' of the equipment.- * .....; i':.:'I'-'!=/ -·. 4. i.,

Before starting the motor, check the following items: ,-t·

1„ The rotor should tum freely when disconnected fromthe load.' ; { ¢

.

2. Driven machine should 6e unloaded when first start-ing the motor.

\

t

' .5/

h1

6

The motor should run smoothly with little noise. If the mo-

torshould fail to stat'tand produces a decided hum, it maybe that the load is too great for the motor or that it hasbeen connected improperly. Shutdown immediately andImestigate for tiouble.

DRAIN PLUGS

If motor is totally enclosed fan-cooled or non-venti-lated it is recommended that condensation drain

plugs, if present, be removed. These are located inthe lower portion of the end-shields. Totallyenclosedfan-cooled "XT" motors are normally equipped withautomatic drains which may be left In place as re-ceived.

ROTATION

To reverse the direction of rotation, disconnect from pow-er source and interchange any two of the three line'leadsfor the three-phase motors.

TEST FOR GENERAL CONDITION

If the motor has been in storage for an extensive period orhas been subjected to adverse moisture conditionsi it isbest to check the insulation resistance of the stator wind-

ing with a megohmeter.

I f the resistance is lower than one megohm the windingsshould be dried in one of the two following ways:

1. Bake in oven at temperatures not exceeding 90°C.until insulation resistance becomes constant.

2. With rotor locked, apply low voltage and gradually in-,:T crease current through windings until temperature

measured with thermometer reaches 194°F (90°C).Do not exceed this temperature.

INITIAL LUBRICATION

ir, 1 Reliance motors are shipped from the factory with thebearings properly packed with grease and ready to oper-ate. Where the unit has been subjected to extended stor-age (6 months or more) the bearings should be relubri-cated (regreasable type) prior to starting. When motorsare equipped for oil mist lubrication refer to InstructionManual 8-3654.

OPERATION

9*.*'**j'<4%15:,-I-fLitiv,-4.1SURFACE TEMPERATURES OF MOTOR EN-

CLOSURE MAY REACH TEMPERATURES

WHICH CAN CAUSE DISCOMFORT OR INJURY

TO PERSONNEL ACCIDENTALLY COMING INTO

CONTACT WITH HOT SURFACES. WHEN

INSTALLING, PROTECTION SHOULD BE PRO- ,VIDED BY USER TO PROTECT AGAINST ACCI-

DENTAL CONTACT WITH HOT SURFACE. FAIL-

URE TO OBSERVE THIS PRECAUTION COULD ,RESULT IN BODILY'INJURY.

i'.'*1%,0.·f:..LAIIA -WARNING- =- ,

ROTATING PARTS, SUCH AS COUPLINGS, PUL-LEYS, INTERNAL-EXTERNAL FANS AND UN-USED SHAFT EXTENSIONS SHOULD BE PER-

MANENTLY GUARDED AGAINST ACCIDENTALCONTACT WITH HANDS ORiCLOTHING. FAIL-URE TO OBSERVE THIS PRECAUTION COULD

RESULT IN:BODILY INJURY. ' - . U

Duetothe inherentcharacteristics of insulatingmaterials,abnormally high temperatures shorten the operating lifeof electrical apparatus. The total temprature,'not thetemperature rise, should be the measurZ of safe opera-lion. The class of insulation determines the maximum

safe operating temperature. Aging of insulation occurs atan accelerated rate at abnormally high temperatures. Ageneral rule for gauging the effect of excessive heat isthat for each 10°C. rise in temperature above the' maxi-mum limit for the insulation, the life of the insulation ishalved.

r

-7

V.. r 42f ,

Unbalanced voltage or single-phase operation of poly-fhase machines may cause , excessive heating andultimate failure. It requires onlya slight unbalance of volt-age applied to a polyphase motor to cause large unbal-ance currents and resultant overheating.

feriodic checks of phase voltage, frequency and powerconsumption«of a'moto'while in operationidre recomimended; such checks assure the gorrectness offfequ,encyandvoltage applied tothe motorand yield an indicationof the load offered,by the apparatus which the motodrives.· ' (11 ' InIt' "' r i. , f f'i:· :.:.- 4 FANComparisons of this data with previous no-load and full-load power demands will give an indication of the perfor-mance of the complete machine. Any serious deviationsshould be investigated and corrected.

Statortroubles can usually be traced to one of the followling causes:.r , ;

, Worn bearings ' ' Operating single-phase ' 2Moisture it:. 1 .! Poor insulation 4 5 ·- 11 2 1

Overloading ' Oil and dirt' M;46; tre, 1.,1, 'I.' . 4 '- . *-I / 1/ 4/,/ I '1./ki'' I

Dustand dirt are usually contributing factors. Some formsof dust are highly conductive and contribute materially toinsulation breakdown. ·The effect of dust oq the nlotortemperaturethrough restriction of ventilation isaprindpalreason for keeping the-windings clean. 2 1 "62:f .g,;: :. '

.' Ir//'. 6, .Sqilirrel-cage rotors are rugged and, ingeneral, give littletrouble. The first symptom of a defective rotor is lack oftorque. This may cause a slowing down in speed accom-panied by a growling noise or perhaps failure to start theload.

I ,

This is caused by an open or high resistance joint in therotor bar circuit. Such a condition'ban generally be de-tected by looking for evidence of localized heating. '

.

. ,

../f.

4

1 21"·

A,%. 0

. '5%,4:i - 4.: 1 4.,

4

MAINTENANCE AND REPAIR

-

2TO INSURE THAT THE' DRiVEN EQUIPMENT IS'' NOT UNEXPECTEDLY' STARTED, TURN OFF 1.AND LOCKOUT OR TAG POWER SOURCE BE-

. FORE PROCEEDING. FAILURE.TO OBSERVE

:THJS PRECAUTION COULD RESULT IN BODILYANJURYs,e.. ··· 'r . f

The fundamental principle of electrical maintenance isKEEP THE APPARATUS CLEAN AND DRY. This re-

quires periodic inspection of the motor, the frequency de-pending upon the type of motor and the service.

The following should be checked at regular intervals:

P*pgk,LiffAA-WARNIN-9..,

DO NOT USE GASOLINE OR OTHER FLAM-

MABLE SOLVENTS WHEN CLEANING THE MO-

TOR. FAILURE TO OBSERVE THIS' PRECAU-TION COULD RESULT IN BODILY INJURY. ,

'."

e Windings'should Be dry and free'of du51, grease;'oil,.'·' ?'and'dirt. Windings may be cleaned 64 suction clean-7- 4*rsBY by wiping. Nozzles 6n suctioh type cleanersi-ge;shoOId be n6n-metallic. Gummy deposits of dirt and

grease may be removed by using a commerciallyavailable low volatile solvent.

2. Terminal connections, assembly screws, bolts and' nuts should be tight. They may loosen if motor is notf' securely bolted and tend to vibrate. + 1 .

3. Insulation resistance of motors in service should be

:. 4 checked periodically at approximately the same tem-5 perature and humidity conditionsto determine pos-

sible deterioration of the insulation. When such mea-

surements at regular intervals indicate a wide varia-tion, the cause should be determined. Motor shouldbe reconditioned if the motor has been subjected toexcessive moisture by re-winding or re-insulating ifnecessary. Enclosed motors require very little atten-tion. Be sure that external air chamber of fan-cooled

motors does not become clogged with foreign materi-al which will restrict passage of air.

DISASSEMBLY

if it becomes necessary to disassemble the motor, careshould be taken not to damage the stator windings as theinsulation may be injured by improper or rough handling.

8

Frecautions to keep bearings clean should be exercised.Before removing either end shield:

4. DisconAect motor from power source. Tag the leads to[ 'indure proper reconnection.2., Remove motorfrom mounting base. Remove fan cov-

, ,er and fan if present.3. Mark end brackets relative to position on frame so' ·they can be easily replaced.

iREMOVING BRACKETS AND ROTOR

4. Remove bearing cartridge nuts or screws. (If used)

5. Remove opposite drive end bracket bolts.

6. Pull bracket.

7. Remove drive end bracket in same manner.1

8. ' Remove rotor.

.

REMOVING AND REPLACING BALL

BEARINGS,BEARINGS SHOULD NOT BE REMOVED UNLESS

THEY ARE TO BE REPLACED. WHEN REMOVAL IS

NECESSARY, USE A BEARING PULLER. A BEARING

PULLER MAY BE RIGGED BY USING A METALPLATE,WITH HOLES DRILLED TO MATCH THE TAPPED

HOLES IN THE INNER CAR USE CARE TO KEEP THE

PRESSURE EQUAL TO PREVENT BREAKING THE

CAR

TO INSTALL A BEARING, HEAT THE BEARING IN AN

OVEN AT 250°F (121 °C). THIS WILL EXPAND THE IN-NER RACE, ALLOWING IT TO SLIP OVER THE BEAR-ING SEAT. ALL BEARINGS MUST BE REPLACED

WITH THE IDENTICAL PART USED BY RELIANCE. IN" * MANY CASES SPECIAL BEARINGS ARE USED

WHICH CANNOT BE IDENTIFIED BY MARKINGS ON

BEARING. IN ALL CASES, WHEN REPLACING BEAR-: INGS, USE MARKINGS ON BEARINGS AND MOTOR

IDENTIFICATION NUMBER TO OBTAIN CORRECTREPLACEMENT BEARING.

THE MAJORITY OF BEARINGS USED NOW HAVE A

(3 INTERNAL FIT.

REASSEMBLY

Follow reverse procedure as outlined for Disassembly.Having marked the brackets in the original position, re-place as marked.

jiMi-,fj

LUBRICATION OF BEARINGS

Motors covered by this Instruction Manual are equippedwith several types of bearings. This description covers relgreasable anti-friction hearings only. Non-regreasableball bearings require no periodic maintenance. See 1/M8-3654 for oil mist lubricated anti-friction bearing prdce-dures. 1

GREASE LUBRICATED BEARINGS

This motor has been properly lubricated at the time ofmanufacture and it is not necessary to lubricate at time ofinstallation unless the motor has been in storage for a pe-riod of six months or mdre.

•4.1.I.

LUBRICATION PROCEDURE ; i 01.:,1'.' I. i

Reliance regreasea6le'anti-friction behrings may be luJbricated with the motor running or stationary. Stationary

with the niotor warm is 'preferred. .1 .1, 0 Di:, 1

6?t,il,Of ' ,;i.; 1. Locate thegrease inlet, clean the area and replace thR Pipe plug -with a grease.litting, if the motor is noti equipped with grease fittings. . ·': :¢.. I, ..> ..1

2. If motor is equipped with grease drain plug, removeplug and loosen any hardened grease that may blockdrain. '1, 'it. bj. i. -1 -. ".,/17.:4. .4

3. Add the Recommended' Volume of the Recom-

Lubrication of anti-friction bearings should be done as a i mended Lubricant u6ing a hand operated grease gunpart of a planned maintenance schedule. The Recom- 4. Run the motor 6 t,bo hoors.- 1 ,' ' ! 1mended Lubrication Interval should be used as a guide to .,/'...., . ': 1

establish this schedule. ' , 5. Replace the pipe plug in grease drain. ' 1 5 '' 1

Cleanliness is important in lubrication. Any grease used ,6. Grease may not relieve from drain. Use only volume

shown in Table 3. i . ,to lubricate anti-friction bearings should be fresh and free ! 1.,„1.21,4 i '

from contaminatipn. Similarly, care should be taken to i i ! , '.''ir; 8 it ' i 5, 1properly clean the grease inlet area of·the motor to pre- 'LUBRICATION INSTRUCTIONST i , r /1.1 ,

.,1 bAHvent grease contamination. 2 · 11. Select Servce Condition from Tabl'e 1. ';4 „#ue1;

,2. Select Lubrication Frequency Tfrom Table 2.RECOMMENDED LUBRICANT

3. Select Lubrication Volume from Table 3.-......--I....

For motors operating in ambienttemperatures shown be- !. : i 1 t'.n.. I.low, use the following lubricant or its equal: '4. Lubricatethe motor atthe re4uired frequency withthd

required lubricant volume irlacg,ordance with LUBRI-

BALL BEARING MOTORS ...., ...EN:. ,11. ...;:··.. t...ilit :.7113:60'1,0··1CATION PROCEDURE.:,

OPERATING TEMP. -25°C (-15°F) to 50°C (120°F) NOTE: Mixing lubricants is notrecommended dueto pos-

sibleincompatibility. If itisdesiredtochange lubricant, fol-CHEVRON OIL SRI NO. 2

low Instructions for lubrication and repeat lubrication aEXXON UNIREX N2

second time after 100 hours of service. Care mustbetak-SHELL OIL CO. DOLIUM R

TEXACO, INC. PREMIUM RB ·· 1 , *entolook. forsignsof lubricantincompatibility, such asex-treme souplness visible from the grease relief drain area,

MINIMUM STARTING TEMPERATURE -60°C (-76°5

SHELLOIL CO. AEROSHELL 7

ROLLER BEARING MOTORS

OPERATING TEMR-25°C el 5°F) to 50°C (120°F)

CHEVRON OIL BLACK PEARL EP NO. 2

TEXACO, INC. PREMIUM RB

t

9

or from the shaft opening.

t

4*C- ,»ff

i S"ty,

i

SERVICE CONDITIONS -

+ Table 1: >,Er*, i 4.':i ...0 1 5,·LUBRICATION VOLUME

Table3

Eight hours per day, normal or lightloading, clean @ 40°C,(l OON:) max-imum ambient. ,

Twenty-four hour per day operation,or shock loading, vibration, or in dirior dust @ 40-50°C (100-120°F) iambient ... c.-,·.· r ...

Standard

Conditions, .

Severe

Conditions

·1/'10„/9,·1!

Extreme

Conditions

LUBRICATION FREQUENCY

NEMA

(IEC)Speed Frame

1800

RPM

and

Slower

182 (112)- Thru '

215 (132)

254 (160)Thru '

365 (200).

404 (225)' 1" Thru'

449 (280)

Heavy shock or vibration, or dust.

i /Table2. . &BALL: BEARINGS . , .-

Standard

Condi-'T tions v r

3 YJars j

2 Years

*1 Year' ·

, SevereCondi-

Ltions f

'1 Year

6 to 12'.

Months1.

Months

3

' Months

Extrema

Condi-

tions .

6

Months

Months

i 1.to 3 -

Months,,

' NEMA (IEC),·«Frame Size

182 Thfu 215 (112 -132)

. 254 Thru 286 (160 - 180)

324 Thru 365 (200 - 225)

404 Thru 449 (250 - 280)

Volume in Cubic

inches (cm3)

0.5 (8)

1.0 (16)

1.5 (24)

2.5 (40)

3600

-'RPMY 'b' ALL :.. 6.Months 1 Month

-404. 1 1,1 i.. ROLLER BEARIVGS 'i" '' '

For Roller Bearings divide the time periods above by 2.•s + b"Obbi!· ··'Y ' r.(Mulk);1:'L·.1· ' ·4,3 F ... apic ··

2 ,·: i,,; 1'··i.1 'Ci - 2 48(t 1. 7*···-111(· lit · r- :-·1:2, I !'2115:.. :'1 :a·,tin ;,fs:.).. ih,foi,1,0 270611 :Ori.Hia·w,:E bt.:ir,aa'«2-- 1. f4 fH)Dn·,5:)'REPLACEMENT BEARINGS

, < 5 3 45'< 'tr; h.1 !> ! F, 1 " 98 °4) 111 :31 11 m C),7 ) : d iv f. 1, H} i i' 1" 3 ¢1 5 LATI, Y Itt 1 1 :#0 #E#in r Pit r y(,1 w A..le- . ·.·9/ -:.

Your maintenance program will not be complete without All hearings used In Reliance motors are subject to exactIncluding spare bearings. It must be remembered thatthe specifications and tests necessatytosatisfy performance

*..bearing is a wearable component and therefore must requirements. In this manner, it is possible to duplicateeventually be replaced. To insure that you are able to your present bearing. Markings on the bearing do not in-maintain original operation, we recommend the pur- dicate complete sp,ecifications.chase of spares directly from Reliance Electric.

10

4 ' - ··.1 & k

2

3

4

5

6

7

8

9

10

11

12

13

661 . ' .4. t . ;

15

- 43

1 I , .41, ;/

El/991* ' .1 , 177- MI

1 4 111 Z \1. . ': "1 .,'.,.i E E i'/ I

t-3

1 9 1 6-4& -Ilt ./

FIND NO.1

11 ®@

FRAME

1 fl

1.

PART DESCRIPTION

STATOR

ROTOR/INTERNAL COOLING FAN

BACKEND BRACKET ''4' ' '" "./

FRONTEND BRACKET '*- J.'1

SHAFT

BACKEND BALL BEARING a

BACKEND INNER CAP

FRONTEND BALL BEARING "- .,;,«...

FRONTEND INNER CAP

WAVE WASHER, FRONTEND

FAN COVER

OUTER COOLING FAN

NOTE: Bearings shown are regreasable type. Not all, itemsfshown may be present on motor. Not all items on

motor may be shown on drawing. Drawing is for general' reference purposes only.

3f;

4''B

'3 ' a

CROSS SECTIONAL AND i

PARTS IDENTIFICATION DRAWING

4 4.

.

7 19

..1 / '' I .H "

t ' 3 5 ./'Ui' Ed ..

2 , S)21.*·21 1,>.1 :1

23 F>

. 1,

1 ., 1,/. 1/.1

I # · -. ' ·*i #3.idit;

s .,I:, I L. 14&,17: Nr

,., ALTERNATE .VIE¥44' =' GREASE 'DRAIN'#r ,

, 4 ,· 4... 6 i., ;11,.Q .Ij,lilifilFIND NO. PART DESCRIPTION

-14 ' v * FRONT END BRACKET BOLTS

. . 15

"" $-16

'- ' 17

18

19

20

21

·23

24

i 44 '11

t

FAN COVER BOLTS

EYEBOLT 4

TERMINAL BOX '

FAN CLAMP].1 ·,GREASE ENTRYA.CONDENSATION DRAINKEY ':,· i

SLINGER

BACKEND CAP BOLTS f.:.5 .

i GREASEDRAIN -·v, :g··· '-

: %,t tfy:' · '/ It . I

6:.

1-

C ,

:*d 'rt:.-.__64-le

1

TOTAL SERVICE·PROGRAMSCAAft.W!,ir, 1.:f# 1. ir,ty:A

, Reliance Electric can provide a wide range of mainte-. nance programs to help you reduce downtime, improve

productivity and increase profits. Capabilities include:

• Motor Start-Up Service

• Motor Electrical and Mechanical Preventive Mainte-nance

• Vibration Analysis

• Mobile Van Repair Service

• Balancing and Alignment Service

• Maintenance Schools

• 24-Hour Technical Support

• Modernization Service

1 .For more information contact your local Reliance ElectricSales Office or write:

Reliance Electric '· 2 ,

Industrial Services ·

24701 Euclid Avenue . ,Cleveland, Ohio 44117

USA :150 1 V

1, 4f:.,; 15.RENEWAL; PARTSArt'SEIdqi&id ifbckof factory-made renewal parts isan in-tegrdl1;#rfSfii 6und maintenance program to protect,against costly. downtime. ... ,-'.„...." '101:ff:R: ·:30 7;"F'·N ; rt<.1 .....I ':

...

f/ IT' - ./ ,

4-*

r ·.41 I

r

Parts can bi obtained from your nearest RelianceElectric parts distributor, or directly from the RelianceElectric factory. When ordering parts for which a partnumber is not available, give complete description of partand purchase order number, serial number, model num-ber, etc., of the equipment on which the part is used.

A detailed parts list, which gives Reliance Electric recom-. mendations for spare parts that should be stocked foryour equipment, can be ordered from:

1. Nearest Reliance Electric Sales Office

2. Nearest Reliance Electric Keyparts Distributor

3. Reliance Electric Renewal Parts, Cleveland, Ohio

Be sure to include complete nameplate data-purchase' ordernumber, serial number, rating, etc. - foryourequip- '

ment when ordering the spare parts list.

For the telephone number (USA) of your local KeypartsStocking distribotor call 1-800-321-2795 or in Ohio call216-266-7222.

ADDITIONAL LITERATURE

Additional literature covering the maintenance of AC mo-tors can be obtained from the Reliance Electric Services

Division. Requests should be submitted through yournearest Reliance Electric Sales Office.

r

MOTOR PURCHASE RECORD

! 305 i,.1/ RELIANCE ELECTRIC r ,i,.3.TRI.2,] 3 DUTY MASTER MOTORS

' LOCAL ITEM# -1

...1 H P/ .- I.- ... ....,,. „,-5,WiE, 1 · SPEED VOLT

u , Purchase ContacUPhone #Daid POichEisd: t·:Comme,nts on maintenanci/maintenance log . ,' 1 3 u Date 2 F', · Item 1 1 Remarks ./ Initials ' '.

. -# '..1 r'/ '. :tri .../

Ill i.

12

..:PS:*CMJ:.:.94.AS'.d,1.

.4

9

0,1 1

. 2 r,*.,

2 -T -

't .

-

....-

*/7

'lf -17

-

r .,1'1

$4 :..... lf * 1 ' .3, ,,' a: i ... ' ; ' s. 1, ;:. ,,· ...1 ,£11;f 1-1 :, ', 51)1,r -s,(4 bt,-42·.·: , 0 5 61: i J liS!,*:N:3*IRIO . .:· ;' " ' #'1;'•f»:*ca,1•,:.4: 14; ,t:VX--Z. "-,r,2;,'whd.¢•hZhio);4;*.7 VH:44W4' rl·1,2-7**4#GAU,·akr'* t*1144

.r.

, It

.-*-·Sjt;:·i,·. 2 f*' ,-,•A. « , .Y'*Kilpha,t-*43;:

''(51S

ft»e·1

Reliance Electric / 24701 Euclid Avenue / Cleveland, Ohio 44117./ (216) 266-7000

Printed in U.S.A

f

8-3620-23

40 Rocbmel, Adomauon

Reliance Electric

397

DODGE®APG0 INSTALLATION, SERVICE AND REPAIR

MANUAL FOR GEARMOTORS-C-FACE REDUCERS-

SEPARATE REDUCERSManual Number

499972

I.

WARNING: Because of the possible danger to person(s) or property from accidents which may result from the improper use of products, it isimportant that correct procedures be followed. Products must be used in accordance with the engineering information specified in the catalog.Proper installation, maintenance and operation procedures must be observed. The instructions in the instruction manuals must be followed.Inspections should be made as necessary to assure safe operation under prevailing conditions. Proper guards and other suitable safety devices orprocedures as may be desirable or as may be specified in safety codes should be provided, and are neither provided by Reliance Electric IndustrialCompany nor are the responsibility of Reliance Electric Industrial Company. This unit and its associated equipment must be installed, adjusted andmaintained by qualified personnel who are familiar with the construction and operation of all equipment in the system and the potential hazardsinvolved. When risk to persons or property may be involved, a holding device must be an integral part of the driven equipment beyond the speedreducer output shaft.

ODGE / RO. Box 499 / 6040 Ponders Court / Greenville, S.C. 29602-0499 / 864-297-4800

© Reliance Electric Company, 1994 DODGE is a registeredtrademark of Reliance Electric Company or its affiliates.

Printed in U.S.A. Instruction Manual 499972

0. ROC#n¥eN AuknbonDodge

1/96 12MK

SUBJECT

GENERAL INFORMATION

The DODGE APG

Gearhead ConfigurationsTypes of MountingTypes of InputAccessories

Dataplates and Information PlatesAcceptance of ShipmentSafetyWarranty

Extended Warranty ConsiderationUnpackingStorage

Preparation for StorageTo Put the Stored APG into Service

DODGE APG SERVICE MANUAL

TABLE OF CONTENTS

PAGE NO.

INSTALLATION

Proper Application 5Mounting Motors to C-Face Reducers ...............................Lifting and Moving (including Weights) ....... ......................Approximate Weights of the DODGE APG ......................7Drive Location, Mounting Position and Safety Guards ..... 7Drive Supports and Foundations 8Leveling and Alignment ..8Hardware for Mounting the DODGE APG.. ........................Attachments to Shafts 9Motor Wiring 9Recommended Wire Sizes 9Motor Direction of Rotation 9

Grounding 9Start-Up

Pre-Start Checklist 10

Start-Up Checklist 10Lubrication of the DODGE APG

General Information 10

Operating Temperatures 11Gearcase Vent 11Recommended Gearcase Lubricant

Alternate Gearcase Lubricants 11

Special Instructions:for Separate Reducer Adapters ---„-------„-„-12

for Separate Reducers with Backstops........ ....„12

Grease for Use in Backstops 12NEMA C-Face Adapter Lubrication ---„-„--„-----13

Output Shaft Bearing Lubrication 13Motor Bearing Lubrication 13Mounting Position Diagrams:

for Separate Reducer - S/[)/T Reduction ..............14

for Gearmotor & C-Face - S/D/T Reduction -„„„-15

Interchange (See pages 14& 15)

TROUBLE SHOOTING CHART 16

3

3

..3

..3

3

3

3

4

4

4

4

4

5

2

SUBJECT PAGE NO.

REPAIRING THE DODGE APG

General 19

Replacement PartsBearings , 47Lubricant ....46

Oil Seals ....48

Parts 19

Workmanship and Safety 19Tools and Equipment Needed 19Threaded Fasteners and Pipe Plugs .............................20Cautions and Tips about Common Procedures

Parts Handling and Cleaning 20Inspection and Repair of Mating Flanges...................20Sealing Joints - Using RTV Sealant or LoctiteGasket Eliminator 515 20

Removing and Installing Bearings and Gears ------20

Working with Shaft Oil Seals 21Preparing the DODGE APG for Repair ..........................21

Removing and Installing the Input Device......................21Removing and Installing the First Stage Pinion....... .......22

Removing the Cross Pin 99

Repairing the Separate Reducer InputRemoving the Pinion 93Installing the Pinion PTeardown 94

Assembly . 94Parts Identification Drawing 95

Repairing the C-Face Adapter InputParts Identification Drawing 44/PTeardown

Assembly . 96Repairing the Gearmotor Input

Parts Identification Drawing, 56 & 140 frames... ----„27

Parts Identification Drawing, 180-400 frames.... ----„28

Teardown 99AssemblY 31

Repairing the Single Reduction GearcaseParts Identification DrawingTeardown.. 34Assembly .. 34

Repairing the Double Reduction GearcaseParts Identification DrawingTeardown..

Assembly 98Repairing the Triple Adapter

Parts Identification Drawing 42

Teardown 43

Assembly . 43Bearing End Play Shimming 44HARDWARE TORQUE TABLES .................................. .45

THE DODGE APG

GENERAL INFORMATION

The DODGE APG is a broad line of high power density,helical geared products adaptable to a wide variety ofapplications. The DODGE APG is designed in accordance

with the standards of the American Gear ManufacturersAssociation to give trouble-free performance when proper-ly selected, installed and maintained. This instruction man-ual contains precautions and procedures to observe wheninstalling, operating and maintaining your DODGE APG.Additional information may be obtained from your localDODGE Sales Office, Authorized Distributor or AuthorizedService Center.

GEARHEAD CONFIGURATIONS

The DODGE APG gearhead is produced in three basicconfigurations:

1. The Single Reduction has one pair or "stage" of gears.The Single Reduction unit is available in ratios of 1.2:1through 5:1.

2. The Double Reduction uses two pairs of gears in seriesto provide ratios from 4:1 through 25:1. The DoubleReduction gearcase is different from the Single Reduc-tion gearcase.

3. The Triple Reduction is the Double Reductiongearhead with yet another pair of gears housed in a"Triple Adaptef' added at the input. The Triple Reduc-tion provides ratios from 31:1 through 129:1

TYPES OF MOUNTING

Each of the three gearhead configurations is available intwo types of mounting:

1. Foot Mount is standard. The APG Gearmotor shown on

the cover of this manual is Foot Mounted. Some combi-

nations of motor and gearhead require riser blocksunder the mounting feet if the drive is to be mounted to alarge flat surface and the body of the motor extendsbelow the feet of the gearhead. Suitable riser blocks aresupplied as standard parts where needed.

2. Flange Mount units use the same gearcase as the FootMount units. The output bearing housing is changed toprovide a mounting flange concentric with the outputshaft.

TYPES OF INPUT

The three gearhead configurations in either of thetwo mounting types are each available in three inputconstructions:

1. The Gearmotor uses a special motor designed to pro-duce a compact package of prime mover and reducer.Couplings and exposed rotating parts at the input areeliminated.

2. The C-Face Reducer has a hollow, integral inputcoupling to accept the shaft of a standard NEMA

3

C-Face motor. A clamp collar is provided to lock themotor shaft and the input coupling together to preventfretting corrosion.

3. The Separate Reducer has an extended input shaft tobe coupled to a separately mounted prime mover. Theinput may be through a belt or chain if the input speedrequired is different from standard motor speeds.

ACCESSORIES

The DODGE APG may be equipped with brakes, dutches,backstops or other accessories. Backstops are availableonly in the Separate Reducer input construction and arecovered in detail in this manual. Other accessories are

described in their own manuals.

DATA PLATES AND INFORMATION PLATES

The primary plate is attached to the DODGE APGgearcase. This rectangular stainless steel plate containsvital information about your DODGE APG. Gearmotor andC-face reducer input constructions have an equally im-portant dataplate on the motor. Information plates may beattached to any component to provide operational instruc-tions or precautions. Bolt-on accessories will usually havetheir own data plates. All plates are to be consideredimportant. The information they contain will be of helpto youthroughout the life of the drive. Take care not to damage orpaint over any of the plates.

When ordering parts or service, or asking a question aboutyour DODGE APG, please provide all the informationstamped on both the motor and gearcase dataplates. If

your drive has an accessory, such as a brake, provide thatinformation also.

ACCEPTANCE OF SHIPMENT

Thoroughly inspect the equipment before accepting ship-ment from the transportation company. If any of the goodscalled for in the bill of lading or express receipt are dam-aged or missing, do not accept the shipment until thefreight or express agent makes an appropriate notation onyour freight bill or express receipt. If any concealed loss ordamage is discovered later, notify the agent at once andrequest an inspection. Though DODGE will be happy toassist you with claims for loss or damage in shipment, thetransportation company is responsible for reimbursing youfor such claims. Claims for loss or damage in shipmentmust not be deducted from the DODGE invoice, nor should

payment of the DODGE invoice be withheld awaitingadjustment for such claims. The carrier, not DODGE, guar-antees safe delivery.

If considerable damage or shortage has occurred and thesituation is urgent, contactthe nearest DODGE Sales Officefor assistance.

SAFETY

DANGER

HIGH VOLTAGE AND ROTATING PARTS CAN

CAUSE SERIOUS OR FATAL PERSONAL INJURYAND PROPERTY DAMAGE. THE USE OF ELECTRI-

CAL MACHINERY, LIKE ALL OTHER UTILIZATIONOF CONCENTRATED POWER AND ROTATING

EQUIPMENT, CAN BE HAZARDOUS. INSTALLA-TION, OPERATION AND MAINTENANCE OF ELEC-TRIC MACHINERY SHOULD BE PERFORMED ONLY

BY QUALIFIED ELECTRICAL AND MECHANICALMAINTENANCE PERSONNEL FAMILIAR WITH

NEMA SAFETY STANDARDS, THE NATIONALELECTRICAL CODE AND SOUND LOCAL PRAC-

TICES. THE MANUAL IS TO BE STUDIED THOR-OUGHLY BY PERSONNEL RESPONSIBLE FOR THEINSTALLATION AND MAINTENANCE OF THISEQUIPMENT BEFORE INSTALLATION IS BEGUN.PERSONNEL MUST BE FAMILIAR WITH THEPOTENTIAL HAZARDS INVOLVED. IF THIS WARN-

ING IS NOT OBSERVED, PERSONAL INJURY AND/OR PROPERTY DAMAGE MAY RESULT. KEEP THISMANUAL FOR FUTURE REFERENCE.

Many precautions are inserted in this manual to advisepersonnel of possible hazards. All should be read andunderstood before any work is begun. Adequate instal-lation, maintenance and safety instructions must be givenby the user to personnel responsible for the operation ofthe equipment. The user is also responsible for the instal-lation of proper guards, signs and safety equipmentneeded to protect the operating personnel.

WARRANTY

NOTE: SERVICE AND REPAIR UNDER WARRANTY

SHOULD BE PERFORMED ONLY BY A DODGE

AUTHORIZED SERVICE SHOP. CALL WARRANTYADMINISTRATION AT 812-376-1100 FOR THE

NEAREST LOCATION.

The DODGE APG is warranted under the DODGE

"Standard Terms and Conditions of Sale."

Warranty claims on any such apparatus must be submittedto the company within one year from date of installation orwithin three years from date of manufacture, whichevercomes first. The Seller's Warranty applies insofar as theequipment is operated within the rating and service condi-tions for which it was specifically sold. The warranty doesnot extend to failures induced by misuse, improper storageor handling, abuse or misapplication.For warranty service, contact the nearest DODGE SalesOffice or Authorized Distributor or call Warranty Administra-tion at 812-376-1100.

UNPACKING

After unpacking and inspecting for possible damage, turnthe shafts by hand to be sure there are no obstructions tofree rotation. C-Face input devices have a shipping straparound the input shaft which must be cut and removedbefore the shaft may be turned.

4

WARNING

KEYWAYS IN SHAFTS HAVE SHARP EDGES. USE

APPROPRIATE HAND PROTECTION WHEN

HANDING SHAFTS. FAILURE TO OBSERVE THISPRECAUTION COULD RESULT IN BODILY INJURY.

Check the packing materials. Save any instruction tags,wiring diagrams or accessory parts and hardware. Inspectthe dataplate(s) to verify that the drive matches the intend-ed load, application and power supply. If the drive is to gointo immediate service, see "INSTALLATION," below.If the DODGE APG is to be stored for some time before

going into service, see "STORAGE," below.

STORAGE

NOTE: Unless an extended warranty has been negotiatedprior to sale, time in storage is considered time in serviceforwarranty purposes. If a negotiated extended warranty isin effect, these storage procedures must be followed topermit the submission of a valid warranty claim.

Warranty considerations aside, the following storage pro-cedures should be taken to prevent problems when thedrive is eventually placed in service.

LONG-TERM STORAGE GUIDELINES FOR

GEAR REDUCERS:

Care must be taken to ensure that gear reducers areplaced in service in the best possible condition. Duringperiods of long storage (six months or longer) specialprocedures must be followed which will protect thereducer and make certain that it will be in good condition when ready to be put into service.

By taking special precautions, problems such as sealleakage and reducer failure due to lack of lubrication,improper lubrication quantity, or contamination can beavoided. The following precautions will protect reducersduring periods of long-term storage:

A. Preparation:

1. Select a clean, dry, protected storage area free ofvibration and temperature extremes. Set the drivelevel on its feet with no load on either the input oroutput shafts. Block as needed to keep weightoff the motor fan shroud and motor conduit box

(if unit has a motor).

2. Fill the gearbox to the highest designated oil levelwith a recommended lubricant blended with 2% byvolume of *Daubert Chemical Co. Nox-Rust VCI-

105 oil. Do not fill the gearbox completely full ofoil. Expansion space is needed to avoid pressur-izing the gearbox during temperature variations.Rotate the input shaft at least 60 revolutions toensure a full distribution of the lubricant.

3. All condensate drains and breathers (on motors

so equipped) are to be fully operable to allow breathing through points other than bearing fits.Remove the condensate drain plugs located inthe motor end shield. Position the motor so the

drain is at the lowest point. Totally enclosed fan-

cooled XT motors are equipped with automaticdrains which should be left in place.

4. All units equipped with heaters must have theheaters connected and operational if the storageconditions are in any way like the anticipated serv-ice conditions.

5. Motor windings are to be checked with a meg-ohmeter when the equipment is put into storage.The resistance must be recorded and saved for

future reference. See "to put the stored unit intoservice" for the megohmeter check required uponremoval from storage.

6. Apply a thick coating of chassis-type grease,Cosmoline or equivalent protective coating*(Daubert Chemical Co. Nox-Rust X-110 is a suit-able coating) on all unpainted surfaces includingthreads, bores, keyways and shafts.

7. Apply a thick coating of chassis-type grease to allexposed shaft seals.

8. If the unit must be stored outdoors or in damp orunheated areas indoors, cover the entire exteriorwith a rust preventative. Seal the unit in a moisture-proof containeror in an envelope of heavy polyeth-ylene film with a dessicant inside. Shade theenclosure from direct sunlight.

9. Rotate the input shaft at least 60 revolutions oncea month to redistribute the lubricant and to pre-vent brinelling of bearings and drying of seals.

10. Instruction manuals and tags are paper and mustbe kept dry. Remove these documents and storethem in a safe, dry place for future reference atstart up.

B. To put the stored unit into service:

1. Remove all protective coatings added for storage.

2. Drain and refill the gearbox with a recommendedtype and amount of lubricant. Regreasable assem-blies and bearings must be purged and filledwith new grease.

3. Install the oil level plug in the proper location forthe mounting position to be used. Check the motorcondensate drain locations to assure the motors

will drain properly when mounted in the proposedposition. Rotate the motor on the gearhead orrotate the motor end shields on the motor frame if

necessary to getthe drains in the proper positions.

4. Check all hardware for proper tightness.

5. If the gear unit has been stored for more thanthree years or in an area with high ambient tem-peratures, the oil seals must be replaced beforebeing put into service. See the instruction manualfor directions on oil seal replacement.

6. Check the motor stator insulation resistance with

a megohmeter Resistance less than one megohmor less than 50% of the resistance reading takenwhen the motor was put into storage (whicheveris the higher resistance), requires the motor wind-

5

ing to be dried in one of the two ways describedbelow. If drying does not restore the winding insu-lation resistance to the values listed above, the

motor must be repaired or rewound.

a. Remove the motor from the reducer (see in-struction manual), place the motor in a ven-tilated oven at not more than 90 degreesCelsius (194 degrees F.). Check the insula-tion resistance every 30 minutes. Bake, untilthe resistance becomes constant.

or

b. Lock the motor rotor. Insert a thermocouple inthe winding or set up to measure rise by resis-tance. Apply low voltage, gradually increase thecurrent through the winding until the windingtemperature reaches 90 degrees Celsius (194degrees F.). Do not exceed this temperature.Check the winding insulation resistance with amegohmeter. Repeat if necessary.

After drying, briefly run the motor not connectedto any load to further dry the motor and to checkthe bearings for noise and smooth operation.

7. When stored motors are found to be wet, a moredetailed inspection should be made by removingthe motor end shields and visually inspecting forwater in the grease or rust on the bearings. Ifeither is found, replace the bearings, clean the endshields thoroughly and relubricate.

*Note: Daubert Nox-Rust VCI-105 oil and Nox-Rust

X-110 protective coating can be procured inbulk quantity from:

Daubert Chemical Company, Inc.4700 S. Central Ave. '

Chicago, Illinois 60638Telephone (708) 496-7350

or in 5-gallon pails from their distributor:

Rock Island Lubricants and Chemicals

1320 First Street

Rock Island, Illinois 61204-5015Telephone (309) 788-5631

INSTALLATION

A good installation is essential to get the long life andsuperior performance designed into the DODGE APG.Careful planning and good workmanship at installation willgreatly reduce future maintenance problems.

PROPER APPLICATION

Review the dataplates on the DODGE APG gearcase anddrive motorto verifythatthedrive is correct forthe intendedloads, speeds and electric power supply. The DODGEAPG catalog has detailed rating charts and instructions forapplying proper service factors for various types of appli-cations. Verify that the DODGE APG has the correct enclo-sures for your application. Standard enclosures are notsuitable for explosion proof or washdown applications.

WARNING

THE USE OF ELECTRICAL EQUIPMENT IN HAZARDOUS

LOCATIONS IS RESTRICTED BY THE NATIONAL ELECTRI-

CAL CODE, ARTICLE 500. ORIGINAL EQUIPMENT MANU-FACTURERS AND USER CUSTOMERS MUST READ,UNDERSTAND AND APPLY ARTICLE 500 FOR INSTALLA-

TION AND USE OF ALL EQUIPMENT IN SUCH LOCATIONS

AND CONSULT LOCAL CODE INSPECTION AND

ENFORCEMENT AGENCIES AS NECESSARY TO ENSURE

COMPLIANCE. MOTORS LISTED BY UNDERWRITERS LAB-

ORATORIES, INC. FOR USE IN SPECIFIC LOCATIONSHAVE BEEN DESIGNED, TESTED AND APPROVED FORUSE IN SUCH LOCATIONS ONLY.

Review the application to determine the signs, guards andany special provisions or devices needed to make the instal-

lation safe, practical and legal.

WARNING

MOTORS WITH AUTOMATIC RESET THERMAL PROTEC-

TORS SHOULD BE USED ONLY IN APPLICATIONS WHERE

AN UNEXPECTED RESTART WOULD NOT BE HAZ-

ARDOUS. IF A MOTOR WITH AN AUTOMATIC RESET THER-

MAL PROTECTORS HAS TRIPPED TO "OFF", BE SURE TODISCONNECT AND LOCKOUT THE ELECTRICAL POWER

SUPPLY TO THE MOTOR BEFORE WORKING NEAR THE

MOTOR OR ANY EQUIPMENT DRIVEN BY THE MOTOR. AN

UNEXPECTED AUTOMATIC "RESET" AND MOTOR START

COULD CAUSE SERIOUS BODILY INJURY.

Review the application to assure that any accessories onthe DODGE APG are correct for the intended use and that

the accessories needed are provided. Installations involvingholding or overhauling loads such as hoists or conveyorsshould have a brake or other separate locking deviceinstalled.

WARNING

BACKSTOPS ARE NOT RECOMMENDED FOR APPLICA-

TIONS INVOLVING SHOCK AND/OR TORQUE LOADS IN

EXCESS OF THE GEARBOX RATINGS. BACKSTOPS ARE

NOT RECOMMENDED FOR APPLICATIONS REQUIRING

ENERGY ABSORPTION. BACKSTOPS ARE NOT RECOM-

MENDED ON APPLICATIONS SUCH AS CHAIR LIFTS OR

AMUSEMENT RIDES, NOR ON ANY APPLICATION WHERETHE SAFETY OF PERSONS OR PROPERTY IS DEPENDENT

ON THE BACKSTOP FUNCTION. OTHER SAFETY DEVICES

MUST BE PROVIDED BY THE USER ON SUCH APPLICA-

TIONS.

Review the application for any unusually high or low ambi-ent temperatures and for sources of radiant heat.

Abnormally high temperatures will seriously shorten theoperating life of any machine. For every 10 degrees C (18degrees F) rise in temperature above the maximum ratedthermal limit, the life of motor insulation, shaft seals and

lubricants is reduced by half. The total temperature, not justthe temperature rise, is the measure of safe operation.

The DODGE APG and its motor should be shielded from hot

surfaces, such as ovens or furnaces, and shaded from

direct sunlight to prevent overheating when operating athigh loads. The thermal horsepower rating of the gearcase

6

should be checked as described in the DODGE APG cata-

log. Each motor nameplate carries a maximum ambient

temperature rating. Motors should not be operated at ambi-ents in excess of this rating. Applications with frequent starts

should be reviewed to be sure the thermal rating of thmotor is not exceeded.

Extreme low temperatures require special attention to lubri-cants, as detailed in the "LUBRICATION" section of this

manual. Flexible components such as wiring and lip seals

must also be considered to assure they remain flexible inservice. The drive should be shielded from the direct dis-

charge of freezer air supply ducts.

Questions about DODGE APG applications should be

directed to Applications Engineering at 812-376-1100.

MOUNTING MOTORS TO C-FACE REDUCERS

1. Prepare the reducer by cutting the shipping strap from

the input hub and removing the shipping strap retaining

plug. Loosen the input shaft clamp collar. Check the inputhub bore for dirt or damage which may make assemblydifficult.

2. Prepare motor by checking the motor shaft extension fordirt or damage. Remove any anti-rust coating that maybe on the shaft. Motor frame sizes 56C through 320TChave keys which are pre-installed in the input shaft key-

way. Apply a thin, even coating of the anti-seize com-pound supplied to the entire motor shaft extension ankey. Leave no bare areas. Push the motor shaft into thereducer input shaft.

Motor frame sizes 360TC and larger have a loose key in

the input shaft. Install this key in the motorshaft keyway

flush with the end of the shaft. Lightly stake the shaft key-

way at the motor end of the key to prevent the key fromsliding back as the motor is pushed into the reducer inputshaft. Apply anti-seize compound as listed above.

3. The DODGE APG C-Face reducer should be firmlyanchored to prevent sliding as the motor is mounted. Themotor should be rotated on its axis so the motor flangeholes line up with the reducer input flange holes. Check

to be sure the motor conduit box, grease fittings and con-

densate drains (where fitted) will be oriented as neededby the reducer mounting position. Motor end shields mayhave to be removed and rotated in some installations to

permit proper positioning.

WARNING

KEEP FINGERS CLEAR OF THE MATING FLANGES ON THE

MOTOR AND REDUCER. WHEN ALL PARTS REACH ALIGN-

MENT, THE MOTOR CAN ENGAGE THE REDUCER VERYRAPIDLY AND WITH GREAT FORCE. ANYTHING BETWEEN

THE FLANGES WILL BE SERIOUSLY INJURED.

.

4. Hoist the motor level and in line with the reducer input

bore. Align the motor shaft key with the reducer input bore

keyway and push the motor into place. Motor shaft to

reducer input bore clearances are tight and good align-ment is essential. If the motor resists going into place, raise

or lower the motor slightly while maintaining a steady push

toward the reducer. Check the clamp collar to be sure it is

still loose on the input hub. Use care if pushing on the fanhousing or conduit box. These parts are easily damaged.

WARNING

KEEP FINGERS CLEAR OF THE MATING FLANGES ON THE

MOTOR AND REDUCER. WHEN ALL PARTS REACH ALIGN-

MENT, THE MOTOR CAN ENGAGE THE REDUCER VERYRAPIDLY AND WITH GREAT FORCE. ANYTHING BETWEEN

THE FLANGES WILL BE SERIOUSLY INJURED.

5. Insert and tighten the motor retaining bolts. Torque to thevalue shown below:

C-FACE MOTOR

FRAME SIZE

56-140

180-286

324-365

RETAINING

BOLT

SIZE

BOLT

TORQUE

LB-FT

23

55

110

6. Tighten the input hub clamp thru the access hole in the

adapter collar. Torque to the value shown below:

C-FACE MOTOR

FRAME SIZE

56-140

180-250

280-365

%-161/2-13

%-11

CLAMP

COLLAR

BOLT SIZE

1/4-28

5/16-24

%-24

BOLT

TORQUE

LB-FT

14

27

47

WARNING

REMOVE THE WRENCH AND INSTALL THE SOLID, SNAP-IN SAFETY PLUG PROVIDED AFTER TIGHTENING THE C-

FACE REDUCER INPUT HUB CLAMP COLLAR TO THE

SPECIFIED TORQUE. FAILURE TO REMOVE THE WRENCH

AND INSTALL THE SAFETY PLUG MAY CAUSE BODILY

INJURY.

LIFTING AND MOVING THE DODGE APG

WARNING

CARE MUST BE TAKEN WHEN LIFTING OR MOVING THE

DODGE APG TO AVOID BODILY INJURY, PROPERTY DAM-AGE AND/OR DAMAGE TO THE DODGE APG. DO NOT USE

LIGHT EYEBOLTS WHICH MAY BE PROVIDED ONLY FOR

HANDLING THE MOTOR TO LIFT THE MOTOR AND ANY

ATTACHED EQUIPMENT SUCH AS GEARHEAD. LIFTING

DEVICES MUST NOT BE ATTACHED TO NOR LIFTING

LOADS APPLIED TO LIGHT HOUSING COMPONENTS SUCH

AS CONDUIT BOXES OR FAN SHROUDS.

Suitable handling equipment of adequate capacity is necessaryfor the safe installation of the DODGE APG. The charts below

can be used as a guide for the lifting capacity needed. Be sureto add capacity for any attached accessories or structure.

7

3

4

5

6

7

8

202

325

476

895

1706

2066

APPROXIMATE WEIGHTS OF THE DODGE APG

S = Single Reduction D = Double Reduction

T = Triple Reduction

APG

SIZE

2

3

4

5

6

7

8

GEARMOTOR WITH MAXIMUM HORSEPOWER

MOTOR ATTACHED

APG FOOT MOUNTED FLANGE MOUNTED

SIZESDTSDT

N/A

208

333

489

937

1404

1484

3

4

5

6

7

8

221

349

524

969

1845

2370

182

227

356

538

1011

1543

1742

41

48

94

143

340

420

97

126

273

406

846

1497

C-FACE REDUCER WITH MAXIMUM

HORSEPOWER MOTOR

FOOT MOUNTED FLANGE MOUNTED

DTSDT

95

108

174

299

470

868

1561

SEPARATE REDUCER (NO MOTOR

OR ACCESSORIES ATTACHED)

APG FOOT MOUNTED

SIZE S D T

DRIVE LOCATION, MOUNTING POSI-TION AND SAFETY GUARDS

211

334

491

921

1746

2105

N/A

217

342

504

963

1444

1524

66

80

160

240

530

790

232

366

546

1016

1973

2491

108

143

295

453

974

1618

WARNING

THE DODGE APG AND ITS CONNECTED EQUIPMENT AND

ACCESSORIES MUST BE GUARDED. ROTATING PARTS

SUCH AS COUPLINGS, PULLEYS, FANS AND UNUSEDSHAFT EXTENSIONS MUST BE PERMANENTLY GUARDED

BY THE USER AGAINST ACCIDENTAL CONTACT WITH

PERSONNEL AND THEIR CLOTHING. THE SURFACE TEM-

PERATURE OF THE DODGEAPG ENCLOSURE MAY REACH

TEMPERATURES WHICH CAN CAUSE DISCOMFORT OR

INJURY TO PERSONNEL ACCIDENTLY COMING INTO CON-

TACT WITH HOT SURFACES. THE USER SHOULD PROVIDE

GUARDS TO PREVENT ACCIDENTAL CONTACT WITH HOT

SURFACES. GUARDS MUST BE SUFFICIENTLY RIGID TO

MAINTAIN ADEQUATE GUARDING IN NORMAL SERVICE.

59

72

142

218

479

724

190

238

373

560

1058

1671

1863

108

119

191

321

517

996

1689

Review the installation for interferences with adjacent

structures and access for maintenance. Lubrication fittingsand plugs should be easy to reach. It may be necessary toextend lubrication lines with properly supported pipe nip-ples and fittings. Fill, drain and vent plugs must be locatedat the levels shown in the "LUBRICATION" section of this

manual. Consult the factory for proper lubricant level andvent locations for mounting positions not shown.

CAUTION

MOTORS INSTALLED VERTICALLY MUST BE

PROPERLY GUARDED BY THE USER TO PREVENT

FALLING OBJECTS FROM STRIKING ROTATING

PARTS. FAILURE TO OBSERVE THIS PRECAUTION

MAY RESULT IN DAMAGE TO THE EQUIPMENT.

Electric motors are normally designed for mounting in ahorizontal position. If the motor is mounted vertically, addi-tional guards may be needed to prevent foreign objectsfrom falling into the motor openings and striking rotatingparts. Suitable guards to shield openings in Reliance mo-tors are available through your local Reliance Sales Office.

Some totally enclosed motors are equipped with conden-sate drain plugs located in the motor end shields. Themotor should be positioned so these plugs are down fordrainage and the plugs removed. Automatic drain plugsfound on some motors should be left in place.

DRIVE SUPPORTS AND FOUNDATIONS

Foundations or fabricated supports to which the DODGEAPG is mounted must be carefully designed to providesufficient rigidity to maintain alignment with the drivenequipment and to withstand the intended operating condi-tions. The mounting surface in contact with the gearcasefeet or mounting flange must be flat to assure uniformloading.

A rigid base plate is recommended for mounting to struc-turalsteel. Boltthegearcase and base plate securelytothe

steel supports, using riser blocks as needed between thebaseplate and the gearcase. Shim as needed to assure aflat surface. If the DODGE APG is to be mounted to a

concrete foundation, grout steel mounting pads into theconcrete base. Mount the gearcase to the steel pads. Donot grout the reducer directly into a concrete foundation.

LEVELING AND ALIGNMENT

The foot mounted DODGE APG must be supported evenlyon all four feet or riser blocks* to prevent distortion orfracture of the gearcase. Use a feeler gauge to determinethe correct thickness of steel shims required. All feet mustbe solidly supported before tightening the mounting bolts.

The flange mounted DODGE APG must also have evensupport at the flange face. Use a feeler gauge to verifythat the flange has solid contact with the mounting surfaceat all attachment points and is not being "broken" acrosshigh spots between bolts. Where practical, flange mountunits will benefit from additional support under the gear-case feet.

8

*16-18%-16

1/2-13%-11%-101 8-7

CAUTION

WHERE BOTH THE FLANGE AND THE FEET ARE

SUPPORTED, EXTRA CARE MUST BE USED INSHIMMING TO ASSURE THAT NO LOADS ARE IM-

POSED ON THE ASSEMBLY AS THE MOUNTING

BOLTS ARE TIGHTENED. FAILURE TO OBSERVE

THIS PRECAUTION MAY RESULT IN DAMAGE TO

THE EQUIPMENT.

Good alignment of attached input and output devices isimportant to avoid excessive overhung and thrust loads onthe DODGE APG shafts. Couplings must be well alignedand have adequate clearance along the axis of the con-nected shafts. Carefully follow the installation instructionsprovided with the coupling used.

HARDWARE FOR MOUNTING THE DODGE APG

WARNING

THREADED HARDWARE USED TO MOUNT THE

DODGE APG MUST BE SAE GRADE 5 OR METRIC

CLASS 8.8 OR BETTER. DO NOT USE HARDWARE

OF A LOWER GRADE. FAILURE TO OBSERVE THIS

PRECAUTION MAY RESULT IN BODILY INJURY.

Bolts, nuts and washers used to mount the DODGE APG

must be of first quality and of the material grades specifiedin the warning above. The use of self-locking hardwareand/orproven locking devices is recommended. Hardwareshould be evenly tightened to 10% of the torque shown inthe following charts. Make another check with a feelergauge to assure level shimming. The hardware is thenevenly tightened to the full torque specified. The torquesshown are for "lubricated" threads which are defined as

any plated thread or a thread containing any amount of oilor wax. Most threaded hardware is lubricated. If in doubt,

wipe the threads with a lightly oiled rag.

FOOT BOLT SIZES FOR THE

FOOT MOUNTED DODGE APG

SINGLE, DOUBLE AND TRIPLE REDUCTION

METRIC

CASE SAE BOLT TORQUE BOLT TORQUE

SIZE SIZE LB-FT SIZE LB-FT

2

3

4

56

7&8

132355

110200

600

* Riser Blocks are shipped with unit where needed.Reference page 32 and 35.

M8

M10M12

M16M20M30

19

3867

158

3081067

.

FLANGE BOLT SIZES FOR THE

FLANGE MOUNTED DODGE APG

SINGLE (S) AND DOUBLE/TRIPLE (D/T) REDUCTION

CASE

SIZE

53,54,55D/1-2

D/T3, D/T4S6,57,58D/T5, D/T6,D/17,[)/T8

%-13lk-131/2-13%-11

3/1-10

SAE BOLT TORQUESIZE LB-FT

ATrACHMENTS TO SHAFTS

55

5555

110

200

METRIC

BOLT

SIZE

M12M12M12

M20

TORQUE

LB-FT

308

Use care when installing couplings, sprockets and pulleyson the DODGE APG input or output shafts. Such compo-nents should not be hammered into place. Damage toshafts and bearings may result. If parts do not slip ontoshafts easily, check fordirt or burrsthat may be binding theassembly. Very tightly fitted parts may need to be heated toget them onto the shafts. Keys should be located for maxi-mum engagement between the shaft and the attachedpart. Sprockets and pulleys should be mounted as close aspossible to the gearcase to minimize overhung loads. Re-taining hardware for sprockets, pulleys and couplingsshould be tightened as recommended by the componentmanufacturer. Chain and belt drives must be aligned to runtrue. Tighten chains and belts according to the chain or beltmanufacturer's instructions. Excessive tension producesrapid chain and belt wear and reduces the bearing life ofthe DODGE APG.

MOTOR WIRING

DANGER

THE USER IS RESPONSIBLE FOR CONFORMING TO

THE NATIONAL ELECTRICAL CODE IN THE INSTAL-

LATION OF WIRING FOR THE DODGE APG. THE

USER IS ALSO RESPONSIBLE FOR UNDERSTAND-ING AND APPLYING ALL OTHER APPLICABLE LO-

CAL CODES WHICH GOVERN SUCH PRACTICES

AS WIRING PROCEDURES, WIRING PROTECTION,GROUNDING, DISCONNECTS AND OVER-CUR-RENT PROTECTION. BE CERTAIN THE ELECTRICAL

POWER IS DISCONNECTED AND LOCKED OUT BE-

FORE ATTEMPTING CONNECTION TO THE POWER

SUPPLY, CHANGING CONNECTIONS OR DOINGANY OTHER WORK NEAR THE DRIVE OR ITS CON-

NECTED EQUIPMENT. IF THIS PRECAUTION IS

NOT OBSERVED, SERIOUS INJURY, FATALITY ORPROPERTY DAMAGE MAY RESULT.

These motor wiring instructions apply to all gearmotorversions of the DODGE APG. However, these instructions

apply to the NEMA C-face and separate reducer versionsonly if a Reliance motor is used. If a motor manufacturedby other than Reliance is used, refer to the motor manu-facturer for wiring instructions.

All motors should be installed, protected and used in ac-cordance with the National Electric Code and NEMA

67

6767

9

VOLTS

230

460

575

12

14

14

Standard publication MG-2. Connect the. motor to thepower supply according to the diagram in the conduit boxor on the motor dataplate. Fuses, thermal cutouts andother protective devices should be of the correct size tosafelycarrythe load while reliably interruptinglhe circuitonoverloads. Built-in motor thermals, when installed, are of

the proper size to provide the required protection.

RECOMMENDED WIRE SIZES BYMOTOR HORSEPOWER AND VOLTAGE

1-3

VOLTS

230

460

575

14

14

14

5 71/2

10

14

14

000

2

4

8

12

14

HORSEPOWER

10 15 20

6

10

10

4

8

10

HORSEPOWER

50 60

MOTOR DIRECTION OF ROTATION

25

2

6

8

30

300

0

1

1

6

8

75

DANGER

POWER SHOULD BE DISCONNECTED AND

LOCKED OUT BEFORE ATTEMPTING TO CHANGE

MOTOR ROTATION. BEFORE CHANGING MOTOR

ROTATION, CHECK THE DODGE APG, THE CON-NECTED EQUIPMENT AND ALL ACCESSORIES

FOR THE ONE-WAY MECHANICAL DEVICES, SUCHAS BACKSTOPS. THE DIRECTION OF ROTATIONOF ANY SUCH DEVICE MUST MATCH MOTOR

ROTATION OR PERSONAL INJURY OR PROPER-

TY DAMAGE MAY RESULT.

40

Refer to the notation on the motor wiring diagram for theproper method of changing the direction of rotation of themotor.

GROUNDING

DANGER

THE METAL EXTERIORS OF MOTORS, GEAR-HEADS GUARDS AND DRIVE ACCESSORIES ARE USU-ALLY GROUNDED TO LIMIT THEIR POTEN-TIAL TO GROUND IN THE EVENT OF ACCIDENTAL

CONNECTION OR THE CONTACT BETWEEN LIVEELECTRICAL PARTS AND THE METAL EXTERIORS.

HOWEVER, WHEN CAREFUL CONSIDERATIONS OFTHE HAZARDS INVOLVED IN A PARTICULAR

APPLICATION INDICATE THE MACHINE FRAMES

SHOULD NOT BE GROUNDED, OR WHEN UN-USUAL OPERATING CONDITIONS DICTATE THATA GROUNDED FRAME CANNOT BE USED, THE

USER SHOULD MAKE SURE THE MACHINE IS PERMA-NENTLY AND EFFECTIVELY INSULATED FROMTHE GROUND. APPROPRIATE PERMANENT

WARNING LABELS OR SIGNS SHOULD BE INSTALLED

BY THE USER OR IN THE AREA OF THE EQUIPMENT.

0000

1

3

00

4

6

Frames and accessories on motors should be groundedin accordance with the National Electrical Code. Where no

other specific grounding point is provided, the motor con-duit box mounting screw is recommended.

PRE-START CHECKLIST - Before making the finalconnectiontothe driven load, use the following checklisttobe sure that:

1. Oil level, air vent and oil drain plugs are in the properlocations for the mounting position used.

2. Lubricants have been checked for the proper type,

viscosity and amount for the temperatures and condi-tions.

3. Hardware has been checked for proper tightness.

DANGER

BE CERTAIN ALL WIRING CONFORMS TO THE

WIRING DIAGRAMS AND TO APPLICABLE SAFETY

CODES. RECHECK FOR CORRECT COLORS AND

NUMBER IDENTIFICATIONS.

4. Electrical connections have been checked and

insulated.

5. Alignment of the drive with all couplings, shafts,pulleys, sprockets and connected equipment hasbeen checked. Connection to the driven load is dis-

connected.

WARNING

MAKE SURE ALL GUARDS ARE IN PLACE, CLEAROF ALL MOVING PARTS AND SECURELY FAS-

TENED BEFORE START UP.

6. Required guards and signs are in place and secure.

7. Support structure is in place and secure.

WARNING

BEFORE STARTING THE DODGE APG, OBSERVEALL LOCAL SAFETY CODES. MAKE SURE ALL

PERSONNEL AND ALL OBSTRUCTIONS ARE

CLEAR OF MOVING PARTS.

8. Personnel are clear.

9. Tools, trash and loose keys, setscrews or other un-used rotating parts have been removed from the area.Check C-Face drives to be sure the clamp collarwrench has been removed and that the snap-in safetyplug has been installed.

10. Backstop rotation has been checked.

CAUTION

TO AVOID DAMAGE TO THE MOTOR USED WITH A

DODGE APG WITH A BUILT-IN BACKSTOP, SEPARATETHE CONNECTION BETWEEN THE MOTOR AND THE

REDUCER. TURN THE REDUCER INPUT SHAFT TO

VERIFY THE DIRECTION OF BACKSTOP ROTATION.

REMOVE ALL KEYS OR OTHER UNSECURED ROTAT-

ING PARTS FROM THE MOTOR SHAFT. OPERATE THE

MOTOR TO ASSURE IT IS CONNECTED FOR THE

ROTATION DESIRED. IF BOTH THE MOTOR AND THE

BACKSTOPOPERATE IN THE PROPER DIRECTION,RECONNECT THE MOTOR TO THE REDUCER.

10

11. With all of the above accomplished, energize themotor to verify proper rotation.

12. SEE THE STARTUP CHECKLIST BEFORE MAK-

ING THE FINAL CONNECTION TO THE DRIVEN

EQUIPMENT.

STARTUP CHECKLIST- Before making the final con-nection to the driven equipment, review the Pre-startChecklist to be sure all work has been completed and allprecautions observed, then proceed with this checklist:

1. Be sure the driven equipment is ready to run with all

brakes released, blocking removed and loose partssecured.

2. Make the final connection between the DODGE APG

and the driven equipment. Check alignment of the con-necting coupling or sprocket and secure any shieldsand guards.

3. If possible, arrange to start the motor slowly to avoidshock loads on the gearing and the connected equip-ment. Across the line starting of motors should be

used with care to prevent overloading gears and drivenequipment, especially on applications where the con-nected load has considerable inertia.

4. Make a last check to be sure personnel are clear, thenstart the drive.

5. Bring the drive to normal operating speed.. Check forexcessive vibration, unusual noises or oil leakage.Overheating may take two hours or more to becomeapparent. If any problems develop, the drive should be

shut down. Determine the cause and correct the prob-

lem before restarting the DODGE APG. The TROUBLE SHOOTING CHART on page 15 is useful as an aid to

diagnosing problems.

LUBRICATION OF THE DODGE APG

WARNING

HOT OIL CAN CAUSE SERVE BURNS. USE EX-

TREMECAREWHENREMOVINGLUBRICATIONPLUGS

AND VENTS. DO NOT GET IN LINE WITH

THE PLUG. HOT OIL CAN BE BLOWN A CONSIDER-

ABLE DISTANCE SHOULD THE GEARCASE BE

PRESSURIZED BY A CLOGGED VENT. WEAR SUIT-

ABLE PROTECTIVE CLOTHING AND EYE SHIELDS.

Proper lubrication is essential to the performance and lifeof the DODGE APG. Proper lubrication consists of:

1. Use of the proper type and viscosity of lubricants.

2. Maintenance of the correct oil level for the mountingposition used.

3. Drain, flush and refill at the required intervals.

Cleanliness is also critical to proper lubrication and mainte-nance. All lubricants used should be clean and fresh. Con-

tainers used to handle lubricants should be clean. The

area around a lube. or vent plug should be wiped down .before removing the plug to prevent dirt from getting intothe gearbox. Grease fittings should be wiped clean beforeuse.

The DODGE APG is filled at the factory with Mobil SHC634 oil to the correct oil level for the specified mountingposition. The correct oil level is indicated by the red oil levelplug. Changes in the mounting position will require reloca-

AIIA tion of the oil level and vent plugs. Oil may have to be, added or drained to get the correct oil level in the new

mounting position. See the Mounting Position (pages 11 &15) diagrams in this section of the manual for the correctplug locations for various mounting positions.

The oil level should be checked before start-up and fre-quently thereafter, preferably with the gearbox warm.Check the oil level by removing the red plug. The oil levelshould be at the bottom edge of the threaded hole. If thelevel is low, add oil slowly through one of the upper plugholes until the oil starts out the level hole. Replace all plugssecurely.

WARNING

HOT OIL CAN CAUSE SERVE BURNS. USE EX-

TREMECAREWHENREMOVINGLUBRICATIONPLUGS

AND VENTS. DO NOT GET IN LINE WITH

THE PLUG. HOT OIL CAN BE BLOWN A CONSIDER-

ABLE DISTANCE SHOULD THE GEARCASE BE

PRESSURIZED BY A CLOGGED VENT. WEAR SUIT-

ABLE PROTECTIVE CLOTHING AND EYE SHIELDS.

OPERATING TEMPERATURES

WARNING

THE SURFACEOFTHE DODGE APG ENCLOSURE MAY

REACH TEMPERATURES WHICH CAN CAUSE DIS-

COMFORT OR INJURY TO PERSONNEL ACCIDENTLY

COMING INTO CONTACT WITH HOT SURFACES. THE

USERSHOULDPROVIDEGUARDS TOPREVENTACCI-

DENTAL CONTACT WITH HOT SURFACES.

Heat generation is a natural characteristic of gear opera-tion. A maximum gearcase temperature approaching 200degrees F is not uncommon for units operating at ratedload in normal ambient temperatures. Applications shouldbe reviewed for thermal limitations as defined in the

DODGE APG catalog.

GEARCASE VENT

The gearcase vent plug is provided to balance the airpressure inside the gearcase with the atmospheric pres-sure outside the gearcase. The vent plug must be clear atall times. Do not paint over.

RECOMMENDED GEARCASE LUBRICANT and

OIL CHANGE INTERVALS

Mobil SHC634 is factory supplied in the DODGE APG andis suitable for use at all output speeds and in ambienttemperatures from -10 degrees F to +110 degrees F. Noinitial oil change after break in is needed. The initial factory

oil fill is good for up to one year in normal industrial environ-ments. Extremely hot, wet or dirty conditions may requiremore frequent changes. Consult Application Engineeringat 812-376-1100 for advice about unusual applications.

11

ALTERNATE GEARCASE LUBRICANTS andOIL CHANGE INTERVAL

Though Mobil SHC 634 is highly recommended, it is recog-nized that some users may prefer other lubricants. If achange to another type of oil is made, the Mobil SHC 634should be drained and the gearcase flushed with cleanmineral spirits to avoid any possible compatibility problemsbetween the SHC 634 and the new oil. Flushing is notrequired if changing to Mobil SHC 629 for low temperatureapplications, nor is the oil change interval affected. Oilchanges every 1500 hours under normal conditions andevery 1000 hours under severe conditions are required forall lubricants other than the Mobil SHC series. To order fac-

tory approved lubricants see page 46.

Use only AGMA R&0 oils as alternate lubricants. Theproper grades of oil for various temperature ranges arelisted below:

NOTE: See Backstop Warning (page 6)

AMBIENT TEMPERATURE

(degrees F)

60-110

35 - 60

10 - 35

-30 - 10

AGMA

GRADE

7

6

5

Mobil SHC 629

The following chart lists lubricants which are suitable foruse under these conditions:

AGMA 7 +60°F. To +110°F. #

(ISO 460)

Mobil SHC-634 (Factory Fill)Mobil 600W Cylinder OilMobil 600W Super Cylinder OilMobilgear 634Amoco 460 Cylinder OilAmoco EP460

Arco Mineral Gear Oil SAE 140

Fiske Bros. Lubriplate APG 140Gulf Transgear Lube EP140Keystone WG-APhillips Philube 140Texaco Vanguard 460Chevron FM Lubricating Oil 460X (USDA H-1)Chevron Borate 460

Tribol 800/460 *

AGMAG +35°F. To +60°F. #

(ISO 320)

Mobil SHC-632

Mobilgear 632Mobil DTE Oil AA

Amoco Industrial Oil 320

Arco Pennant Oil 320

Chevron Borate 320

Tribol 800/320*

AGMA 5 +10°F To + 35°F. #

(ISO 220)

Mobil SHC-630

Mobilgear 630Mobil DTE Oil BB

Arco Mineral Gear Oil SAE 90

Fiske Bros. Lubriplate APG 90Phillips Philube 90Tribol 800/220*

AGMA 4 -30°F. To +10°F. # @

(ISO 150)

'Mobil SHC-629

Tribol 800/150*

# Be careful of the pour point of all lubricants used in theambient temperatures listed. The pour point must be atleast 10°F. belowthetemperatureatwhich itistobe used.

* Tribol lubricants are polyglycol-based synthetic lubri-cants. They are not petroleum-based oils. Consequently,when switching from petroleum-based lubricants topolyglycol-based (and vice versa) the gearcase must bethoroughly flushed with mineral spirits before installingthe desired lubricant.

@ Lubricants listed in the -30°F. to +10°F. ambient rangeare synthetics. Synthetics are the only lubricants whichwill have the desired viscosity along with the required lowpour point.

This list must not be construed as the only lubricantssuitable for use in APG gear units. These are lubricantswith which DODGE/MASTER is familiar. For other lubri-

cant vendors, select a reputable manufacturer, payingclose attention to the viscosity and pour point of the lubricantto be used.

NOTE: For ambient temperatures below -45°F. special oilseals are required. Consult the factory.

SPECIAL INSTRUCTIONS FOR

SEPARATE REDUCER ADAPTERS

The input shaft bearings of the size 3 through 6 separate

reducer adapters are double shielded ball bearings pre-packed at the factory with a lithium based, mineral oilgrease. Size 7 and 8 separate reducer adapter bearingsare of the tapered roller type and are oil lubricated.

GREASES FOR USE IN

SEPARATE REDUCER INPUT SHAFT BEARINGS:

FOR 10 TO 110 degrees F AMBIENT:Chevron "SRI-2"

Exxon "Unirex N-2"

FOR -30 TO +10 degrees F AMBIENT:Shell "Aeroshell 7"

Shell "Aeroshell No. 16"

Exxon "Beacon 325

12

FREQUENCY: Separate reducer input shaft bearingsmust be lubricated every 1000 hours of operation or every6 months, whichever occurs first. Only size 3 thru 6 unitsmounted in position 1 need regreasing. On all othermounting positions these bearings are oil. Lubricated.Input bearings on size 7 and 8 reducers do not needto be lubricated with grease. The input bearings onthese sizes are always oil lubricated. Lubricating withgrease may cause bearing failure on these sizes.

PROCEDURE: Remove the purging plug(s) before re-greasing so old grease will not be forced into the gearboxor through the seals. Add new grease of the type recom-mended until fresh, clean grease exits the purgehole. Afterlubricating, run the drive for 15 minutes before replacingthe purging plugs.

SPECIAL INSTRUCTIONS FOR

SEPARATE REDUCER ADAPTERS

EQUIPPED WITH BACKSTOPS

The input shaft bearings in separate reducer adapters areto be lubricated the same whether a backstop is fitted ornot. However, extra care should be taken with backstop

equipped units to be sure the bearings are not over

greased while the backstop is greased per the recom-mended schedule.

Backstops are very sensitive to proper lubrication.

WARNING

SUBSEQUENT STEPS REQUIRE ROTATING PARTS

TO BE EXPOSED. DISCONNECT AND LOCKOUT

OR TAG POWER SOURCE BEFORE LUBRICATING

UNIT. FAILURETO OBSERVETHESE PRECAUTIONS

COULD RESULT IN BODILY INJURY.

Greases with extreme pressure (EP) additives must not beused. EP greases will prevent the backstop from lockingproperly. Select a grease from the list below, or consultApplication Engineering at 812-376-1100 for othergreases.

NOTE: The backstop must be removed from the separate

reducer adapter if any grease other than Alvania No.1 is tobe used. Both the backstop and the separate reducer must

be thoroughly cleaned before regreasing with an alternategrease.

GREASES FOR USE IN BACKSTOPS

FOR 10 TO 110 degrees F AMBIENT:*Shell "Alvania No.1"

Fiske Bros. "Lubriplate Low-Temp"Fiske Bros. "Aero Lubriplate"

FOR - 30 TO + 10 degrees F AMBIENTShell "Aeroshell No.7"

Shell "Aeroshell No. 16"

Exxon "Beacon 325"

* = Factory supplied grease.

CAUTION

GREASE LUBRICATED BACKSTOPS MUST HAVE

THE PROPER GREASE FOR THE AMBIENT TEM-

PERATURE OF THE INSTALLATION. FAILURE TO

OBSERVE THIS PRECAUTION COULD RESULT IN

DAMAGE TO THE EQUIPMENT.

FREQUENCY: Backstops must be lubricated every 1000hours of operation or every 6 months, whichever comesfirst.

PROCEDURE: Remove the purging plugs before regreas-ing so old grease will not be forced into the gearbox orbearings. Add new grease of the type recommended untilfresh, clean greaseexitsthe purging plug. Afterlubricating,run the drive for 15 minutes before replacing the purgingplugs to allow excess grease to be forced out.NEMA C-FACE ADAPTER LUBRICATION

The NEMA C-Face adapter is equipped with a single ballbearing which is packed at assembly with Chevron SRI-2grease. Units mounted in position 1 * must have this bear-ing regreased with Chevron SRI-2 grease every 1000hours or every six months, whichever occurs first.

Note:

1. Units mounted in position 5 (output shaft down) mustbe regreased per tables 1 and 2 on page 16.

2. Only units mounted in positions 1 * and 5 need re-greasing. On all other mounting positions thesebearings are oil lubricated.

* Size 2 C-Face units mounted in position 1 need not beregreased.

CAUTION

ZERK FITTINGS ARE USED ONLY IN POSITIONS 1

AND 5. ON ALL OTHER MOUNTING POSITIONSTHIS PIPE-TAPPED HOLE MUST HAVE A SOLID

PLUG INSTALLED OR OIL LEAKAGE CAN OCCURTHROUGH THE ZERK. FAILURE TO OBSERVE THIS

PRECAUTION WOULD RESULT IN DAMAGE TO THE

EQUIPMENT.

OUTPUT SHAFT BEARING LUBRICATION

Units equipped with regreasable output shaft bearingsshould be regreased with Chevron SRI-2 every 2006 hoursor once per year, whichever comes first.

13

MOTOR BEARING LUBRICATION - GENERAL

Follow the motor manufacturer's instructions for lubrica-

tion of motors used with separate reducer and NEMAC-Face style DODGE APG drives. Motors used on gear-motor style DODGE APG drives are to'be lubricated asfollows.

SMALL MOTORS may have no provision for regreasing

the bearings. These motors are equipped with doubleshielded, deep groove ball bearings, factory packed withsufficient lubricant for the life of the bearing under normalconditions. No periodic servibe is needed.MOTORS WITH PROVISION FOR REGREASING maybe equipped with grease fittings or with plugs which are tobe replaced with grease fittings in service. Motors areproperly lubricated at assembly. If the motor has been instorage for six months or more, relubricate the bearingsbefore starting the motor.

MOTOR BEARING LUBRICATION -

FREQUENCY AND PROCEDURE

Use the following tables to:

Select the application service conditions from Table 1,page 16.

Select the lubrication frequency from Table 2, page 16.

Select a recommended lubricant from Table 3, page 16.

Lubricate the motor at the required frequency with therequired lubricant volume in accordance with the follow-ing procedure.

WARNING

SUBSEQUENT STEPS REQUIRE ROTATING PARTS

TO BE EXPOSED. DISCONNECT AND LOCKOUT

OR TAG POWER SOURCE BEFORE LUBRICATING

UNIT. FAILURETO OBSERVE THESE PRECAUTIONSCOULD RESULT IN BODILY INJURY.

Motors may be lubricated with the motor running or

stopped. Stopped with the motor still warm is preferred.

1. Locatethe grease inlet for each bearing. Clean the areaand replace the pipe plug with a grease fitting if themotor is not equipped with grease fittings.

2. Regrease the bearing using a hand operated greasegun loaded with the recommended lubricant.

3. Run the motor for two hours before replacing thegrease fitting with the pipe plug. If desired, the greasefitting may also be left in place.

L

Z•

DB

M

L

MOUNTING POSITION AND LUBRICATION CHART

* GEARMOTOR - C-FACE INPUT SINGLE/DOUBLE/TRIPLE

Cl,CF1

C4,CF4

rvZ. In

-4 -4,%%

-_-t' 1 Y#£-Da L-L

Al,AFl

V--\

-EI-4 B

0-

* Applies to sizes 3 thru 8 only

There is no size 2 gearmotor.

V

Fl

3U

L

Iii

1iIIi

V

f --r«-i!.19=-- t_

-D

C2,CF2

L

9-

1

CS,CFS

...re

-V

L k L

-4-1U - \

L-D

D

L-V

A2,AF2NOTE: L a REOUIRES STREET

ELL FOR TRIPLES

%-2

lit. 1 -Va -,rr

L

Uj

A4,AF4 A5,AF5

L = OIL LEVEL PLUG

D = DRAIN PLUG

V

Z

SIZES 3-8

0

L

C3,CF3

La

NOT

AVAILABLE

C6,CF6

va

A6,AF6

va 7

L«1=5 8»-L-

u Lo

A3,AF3NOTE: L 6 REOUIRES STREET

ELL FOR TRIPLES

4

a

AS,AF5 SIZE 2

VENT. PLUG

ZERK FITTING

Size 2 has no zerk in this location.

14

4

J

1

Z

a

D

C1

L

MOUNTING POSITION AND LUBRICATION CHART

* SEPARATE REDUCER - INPUT SINGLE/DOUBLE/TRIPLE

Z-7 -V

1 LL

SIZES 3 THRU 6

C3

a

A1

A3

D

Fv

r 1 -_1=

LaD

SIZES 3 THRU 6

L

-b

V

8 D LLae

SIZES 7 AND 8

C1

r-V

L-7 -

IL-

LD

C4

A1

A4

* There is no size 2 separate reducer.

V

Da

SIZES 7 AND 8

V

-rU D

L

L*

C2

-V

L/'- L

-D

NOT

AVAILABLE

C5

NOT

AVAILABLE

C6

FV

L L---

LD

A2

NOT

AVAILABLE

A5

NOT

AVAILABLE

A6

PLUG ON OPPOSITE SIDE

SIZE 7&8 HAVE STREET ELL FOR OIL LEVEL

15

TABLE 1 - APPLICATION SERVICE CONDITIONS

STANDARD CONDITIONS = 8 hours or less perday at normal load in a clean area at less than 100degrees F.

SEVERE CONDITIONS = More than 8 hours perday or shock loading or vibration or dirt or dust orambient temperature above 100 degrees F.

EXTREME CONDITIONS = Heavy shock or severevibration or extremely dirty or wet conditions.

TABLE 2 - MOTOR BEARING LUBRICATION

FREQUENCY

MOTOR HP

STANDARD

CONDITIONS

SEVERE

CONDITIONS

1800 RPM or less

Up to 75 HP 6 months 3 months

100 HP and up 1 year 6 months

Over 1800 RPM

All HP ratings | 6 months 3 months1 Includes output shaft down position.

EXTREMEl

CONDITIONS

1 month

1 month

1 month

TROUBL

PROBLEM INSPECT FOR. . .

Overheating 1. Overload

2. Oil level too high or too low

3. Type or viscosity of oil

4. Vent plug stopped up

5. Bearing adjustment

6. Coupling binding

7. Excessive Overhung Load(OHL)

8. Excessive ambient temperatureor radiant heat sources or

blocked air flow

9. Line voltage too high or toolow or a phase problem

Bearing Failure 1. Overload

2. Excessive Overhung Load

3. Bearing Adjustment(OHL)

4. Improper lubrication

TABLE 3 - RECOMMENDED MOTOR BEARING

LUBRICANTS

Motors applied in ambient temperatures from - 15degrees F to +120 degrees F may use any of thelubricants listed below. Consult the factory for theproper lubricants for extremely cold or hot environ-ments.

*CHEVRON OIL CO. SRI Number 2

EXXON UNIREX N2

SHELL OIL CO. DOLIUM R

TEXACO INC. PREMIUM RB

*The factory supplied bearing lubricant is ChevronSRI Number 2. See the warning below if changinglubricant brand at any time.

CAUTION

MIXING LUBRICANTS IS NOT RECOMMENDED

DUE TO POSSIBLE LUBRICANT INCOMPATIBILITY.TO CHANGE LUBRICANT FOLLOW THE INSTRUC-

TIONS FOR LUBRICATION AND REPEAT LUBRICA-TION AFTER 100 HOURS OF SERVICE. INSPECT

FOR SIGNS OF LUBRICANT INCOMPATIBILITY,SUCH AS EXTREME SOUPINESS VISIBLE FROMTHE GREASE RELIEF AREA.

ESHOOTING CHART

ACTION Reduce the load or replace the drive with one of adequaterating.

Correct the oil level.

Oil must be the type and viscosity specified in the lubricationinstructions. Drain and refill with the proper lubricant.

The vent plug must be open and clean. Clean the vent plug insolvent when servicing the drive.

Shafts should turn freely when disconnected from the load.Check end play per this manual. If a shaft has too little or toomuch end play, the shaft bearings must be reshimmed.Adjust couplings to eliminate thrust load on shafts.Reduce the OHL by moving the pulley or sprocket closer to thegearcase, by using a larger diameter pulley or sprocket or byadding an outboard support bearing.

Check thermal rating per procedure in the catalog.Shield from hot surfaces and direct sunlight. Clean thoroughlywith special attention to the motor fan and fan shroud.

Check for rated voltage at all phases at the motor terminals.

See Overheating, Item 1 above. Abnormal loading producesflaking cracks and fractures of the bearing.

See Overheating, Item 7 above.

See Overheating, Item 5. If a bearing is too loose or not square *„

with the shaft axis an erratic wear pattern may show in thebearing race.

Verify correct oil level, oil type and viscosity. Note that somebearings require periodic greasing depending on mountingposition and construction as detailed in this manual.

16

.

PROBLEM

Excessive

Noise

Oil Leakage

Gear Wear

INSPECT FOR. . .

5. Rust, water and dirt

6. Damage from improperstorage or prolongedshutdown

1. Unusual or increasing noise

1. Oil level too high

2. Vent plug stopped up

3. Shaft seal wear or damage

5. Pipe plugs leaking

6. Gearcase joints leaking

1. Gear tooth wear or failure

2. Excessive backlash

3. Gear misalignment

4. Overload

5. Improper lubrication

6. Bearing adjustment

7. Coupling Binding

Shaft Failure 1. Type of coupling used

2. Coupling binding

ACTION

Make provisions to prevent the entrance of dirt or water. Coverthe vent plug before washing down the drive. Lubricatebearings and gears by rotating the input shaft often during longshutdown. Check that condensate drains in the motor are openand in the proper position to drain.

Long periods of storage in damp or unheated areas will rustbearings and gears. The drive must be disassembled forinspection. Rusted parts must be replaced. See "Storage" forproper storage procedures to prevent such damage.

Check all parts and accessories for tightness, includingcouplings and guards.

Drain to correct oil level for mounting position used.

See Overheating, Item 4

Replace shaft seals. Inspect seal journal under seal for wear or

scratches. Replace shaft or wear sleeve. Slight leakage is

normal and is required to minimize wear, friction and heat.

Drain oil.

WARNING

HOT OIL CAN CAUSE SEVERE BURNS. IF VENT

IS STOPPED UP, HOT OIL CAN BE BLOWN ACONSIDERABLE DISTANCE WHEN A PLUG IS

REMOVED.

Remove leaking plug and clean all threads well with solvent.Apply anti-seize type thread sealant (Loctite thread sealant withTeflon is recommended.) Install plug. Refill with the proper oilto the correct level.

Tighten bolts to torques shown in Hardware Torque Tables. Ifnot effective, remove the leaking part. Clean mating surfaces.Apply new sealant and reassemble. Give sealant adequate timeto cure before refilling the gearbox with oil and returning toservice.

Refer to the factory.

Gearset must be replaced.

Check contact pattern of gear teeth. Teeth should contact overat least 75% of the gear width. The pattern should be near thecenter of the tooth. Check bearing condition and shaft end play.Adjust bearings as needed.

See Overheating, Item 1

See Bearing Failure, Item 4

See Bearing Failure, Item 3

See Shaft Failure, Items 1 and 2

Rigid couplings between rigidly supported shafts can imposesevere shaft loads. Use couplings with the necessary flexibilityand axial float.

Realign the equipment and adjust coupling as needed.

17

PROBLEM INSPECT FOR...

3. Excessive Overhung Load(OHL)

4. High energy loads or extreme,frequent shocks.

Does Not Start 1. Overload

The Load

2. Proper power supply

3. Power supply disconnected orconnected wrong

4. Backstop installed backwardsor brake locked.

18

ACTION

See Overheating, Item 7.

Install shock absorbing couplings or replace the drive with oneof adequate rating for the shock loads.

Reduce the load or replace the drive with one of adequaterating. Check for locked load by running drive disconnectedfrom load.

Voltage at the motor terminals at each phase must be within10% and frequency within 5% of the values stamped on thedataplate.

Check fuses, disconnects and wiring for continuity and proper size.Check wiring connections against wiring diagram supplied.Check motor direction of rotation.

Check backstop direction of rotation. Check brake wiringconnections.

Check fuses, disconnects and wiring for continuity andproper size.Check wiring connections against wiring diagram supplied.Check motor direction of rotation.

.

REPAIRING THE DODGE APG

REPAIRING THE DODGE APG

Unlikesomehighpowerdensitygearedproducts,the DODGEAPG is designed to be repaired. Lifting, pressing and pullingequipment and tools found in the average maintenance

department aresufficientto repairmostsizes ofthe DODGEAPG. However, many users wisely take advantage of themaintenance and repair assistance available from theirlocal DODGE Authorized Service Shop. The user shouldalso consider whether the drive should be overhauled or

replaced with a new drive. Small drives are often moreeconomically replaced than repaired. Repairs to drives stillunder warranty should be done only by an authorizedrepresentative of DODGE. See "WARRANTY," page 4.

REPLACEMENT PARTS

An adequate stock of renewal parts is an integral part of asound maintenance program to protect against costlydowntime. All parts in the DODGE APG are subject toexact specifications and tests necessary to assure properand safe performance, including many parts usually con-sidered "hardware." We recommend that the parts on thefollowing list be purchased only from Reliance Electric.To assure the continued reliable operation of yourDODGE APG:

1. Bearings 5. Shaft Seals

2. Threaded Fasteners 6. Lockrings3. Dowel Pins 7. Pinion Cross Pins

4. Shaft Keys 8. Clamp Collars

Replacement parts for your DODGE APG may be ob-tained from the nearest DODGE Parts Distributor or

through DODGE Renewal Parts at 803 297-4800. Nev-er attempt to duplicate or rework a part at a local machineshop. To help DODGE get you the parts you need, pleaseput the following information on your order:

1. All data from all nameplates on the drive, including thegearcase, motor and any accessories.

2. The reference numbers and descriptions of the partsbeing ordered as shown on the Parts List and the spe-cific illustration for your drive in this manual. Referenceto this manual number and to page numbers will help.

When selecting parts to replace, keep these suggestionsin mind:

1. If a gear has failed, the mating gear is very likely to bedamaged, though the damage may not be visible.Gears must be replaced in mating pairs. Keys, pins and/or threaded fasteners locking the gears to the shaftsmust be replaced with new parts.

2. Shaft seals should always be replaced with new sealswheneverthe gearbox is torn down for service. The sealjournal or sleeve should be inspected for wear ordamage and replaced if needed.

3. Should a gear or bearing fail, abrasive steel particlesareoftenthrownthroughoutthegearcase. Tremendousseparating forces may be generated, su fficient to bendshafts or fracture the gearcase. All bearings, gears,shafts and housing components should be carefullyinspected for damage.

19

4. Reliance Renewal Parts Department can preparekits including all of the parts likely to be needed toperform basic types of repairs. Inquire when placingyour parts order.

REPAIR PRACTICES

The DODGE APG is a precision device and must be treat-ed as such during repair. The work area should be cleanand free of clutter. Use the proper tools for the job at hand.Adequate lifting and pressing equipment must be availa-ble. Parts as removed should be placed where they will notbe nicked or otherwise damaged. Parts should be carefullyinspected as they are removed and before washing. Sometypes of damage and wear are more easily seen beforewashing. Parts should only be washed in clean solvent.Parts should again be inspected after washing.

WARNING

WHEN USING SOLVENTS, THE USER IS RESPON-SIBLE FOR UNDERSTANDING AND APPLYING ALLAPPLICABLE LOCAL CODES GOVERNING THEIR

USE. DO NOT USE GASOLINE OR OTHER HIGHLY

FLAMMABLE AND/OR TOXIC SOLVENTS. PRE-

CAUTIONS FOR HANDLING CHEMICALS OF THIS

TYPE SHOULD BE OBSERVED. THESE PRECAU-

TIONS INCLUDE: FOLLOW THE MANUFACTURER'SRECOMMENDATIONS.

Gear teeth, keyways in shafts, edges on gearcase parts,etc. can all be very sharp and capable of inflicting seriouscuts. Pressing and hammering operations can produceflying chips. Hot oil can be splashed when the gearcase isdrained. Suitable protective clothing and proper eye andface protection should be worn when working on theDODGE APG or any other machinery.

TOOLS AND EQUIPMENT NEEDED

Tools, equipment and materials needed for repair of theDODGE APG will vary depending on the unitsize andtype,but may include:

1. Magnetic base dial indicator2. Metric and inch size wrenches and sockets

3. Torque wrenches4. Pin punches5. Lockring pliers6. Heavy duty grease gun7. Bearing and gear pullers8. Hydraulic press (10 ton minimum)9. Lifting equipment

10. Pry bars11. Soft faced and hard faced hammers

12. Plastic electrical tape13. Proper Lubricants (See "LUBRICATION,"

page 9)14. Metric and inch hex keys for hex socket bolts.15. RTV Silicone Rubber Sealant or Loctite Gasket

Eliminator 515

16. Wood or plastic blocks or wedges17. 0-1" micrometer and 0-1" depth gauge18. Set of feeler gauges

--

THREADED FASTENERS AND PIPE PLUGS

WARNING

THREADED FASTENERS USED ON THE DODGE

APG ARE CAREFULLY SELECTED FOR TYPE,GRADE AND FEATURES. DO NOT SUBSTITUTE

OTHER THREADED FASTENERS. REPLACE DAM-

AGED THREADED FASTENERS ONLY WITH PARTSOBTAINED FROM DODGE. FAILURE TO OBSERVE

THIS PRECAUTION MAY RESULT IN BODILY

INJURY.

Unless otherwise specifically noted, all threaded fastenersare to be tightened to the torques shown in the HardwareTorque Tables in the back of this manual. Tighten boltsevenly in a crisscross pattern until all are snug, then tightento 50% of the torque shown. Finally, tighten to 100% torque,still using the crisscross pattern. This procedure reducesthe possibility of warping flanges or misaligning parts.

WARNING

THE DODGE APG HAS A MIXTURE OF INCH SIZE

AND METRIC SIZE THREADED HARDWARE. IN

GENERAL, THREADED FASTENERS ON AND IN-SIDE THE GEARCASE ARE METRIC. OTHER

THREADED HARDWARE IS USUALLY INCH SIZE.

TAKE CARE TO SELECT THE PROPER TOOL FOR

THE HARDWARE TO BE LOOSENED OR TIGHT-

ENED. TAKE CARE TO REPLACE HARDWARE IN

THE HOLES FROM WHICH THEY CAME. SERIOUS

PROPERTY DAMAGE AND/OR PERSONAL INJURY

COULD RESULT FROM MISMATCHING THREADED

HARDWARE WITH TAPPED HOLES OR USING THE

WRONG SIZE TOOL.

PRECAUTIONS AND TIPS ABOUT

COMMON REPAIR PROCEDURES

PARTS HANDLING AND CLEANING: Gear teeth and

seal journals are especially prone to damage during repairoperations. Parts must be handled with care, not allowedto bang together or to hit other hard surfaces. Parts fromthe largersizes ofthe DODGE APG are very heavy. Properlifting equipment and practices are necessary to preventpart damage.

With the exception of shielded ball bearings and oil seals,all gearcase, input device and non-electrical motor partscan be washed in a circulating wash tank. Do not washshielded ball bearings in such a tank or flood them in anyother fashion. Such washing removes the grease lubricantin the bearing and leaves behind any dirt or chips whichmay be suspended in the wash solvent. Shielded ballbearings should only be wiped off, taking care to not forcedirt and old grease through the shields. If the bearing issuspected of being contaminated, it should be replaced.Oil seals should be replaced whenever the drive is torndown for any reason.

Inspection and Repair of Mating Flanges and Tenons:After teardown, clean all mating flanges and tenons toremove sealant. The sealant used at the factory is Loctite

20

Gasket Eliminator 515. Also suitable is room temperaturevulcanizing (RTV) silicone rubber. Both can be removedeasily with a sharp scraper or rubbed off with a coarse clothafter softening by soaking with mineral spirits.

Inspect all mating surfaces for any damage resulting from .the teardown procedure. Use a large flat file to smooth anynicks or raised areas back down to the original surface.Check with a good steel straightedge. Failure to properlyprepare mating surfaces for reassembly will cause gearmisalignment and/or oil leakage in the repaired unit.

Sealing Joints - Using RTV Silicone Rubber Sealantor Loctite Gasket Eliminator 515: Loctite Gasket Elimi-nator 515 is available from the Loctite Corporation, an in-dustrial supply house, or an automotive supply store. RTVis available under many brand names, types, and colors.Any such material sold for high temperature automotiveuse is suitable for use on the DODGE APG. Sufficient RTV

is supplied with many DODGE APG parts kits to reseal allthe joints involved in a major overhaul.

RTV or Loctite Gasket Eliminator 515 is best used

sparingly. A W bead issufficienttosealthelargest flangeonthe largest DODGE APG. Flat mating flanges,such as the triple adapter to gearcase joint, are best sealedby applying the bead evenly all around one flange facein the space between the bolt holes and the inside (oilside) edge of the flange. Tenon joints, such as the outputbearing housing joint on the single stage gearcases, aresealed by applying the bead all around the male tenon.Some joints may require a combination of both tech- AI*niques, depending on the specific shape of the flange.

Loctite Gasket Eliminator 515 which squeezes out of ajoint can be wiped off immediately because it will not cureoutside the joint. Joints sealed with Loctite Gasket Elim-inator 515 should be allowed to cure for at least one hour

before being exposed to oil.

RTV which squeezes out of a joint is best left to thorough-ly cure. It can be peeled off or cut away if the appearanceis objectionable. RTV sealed joints should be allowed tocure for at least a half hour before being exposed to oil.This is sufficient time for a skin to form, preventing oil frompenetrating the joint. RTV may also be used as a threadsealant for pipe plugs. A small amount applied to thethreads of the plug before installing will reduce the torquerequired to produce a good seal and will make the plugeasier to remove later.

REMOVING AND INSTALLING BEARINGS AND

GEARS requires the proper tools to prevent damage. Forexample, large sizes of the DODGE APG require over 30tons of press capacity to change the output gear. The usermay wish to contact his local DODGE Service Center forassistance.

Bearings must be removed and installed by pressing only onthe inner race with a pressing tool of the proper size. Bearings removed by pulling on the outer race are to be

. considered scrap. Screw type gear pullers should be usedwith care to avoid damaging the gear teeth. Bearings and

.

.

gears are best mounted by heating the part to not over 300degrees F and dr6pping into place on the shaft.

WORKING WITH SHAFT OIL SEALS: Shaft oil seals are

easily damaged by dirl, exposure to solvents and roughhandling. The steel parts of the seal are nearly as subjectto damage asthe rubberseal lip. The steel cases are easilybent. Seals should be kept wrapped and out of the immedi-ate work area until just before installation.

Seals should be installed with bullet type seal sleeves andslide hammers. However, seals can be worked into placeon the seal journal or sleeve without special tools if care istaken to be sure the seal garter spring is not popped out ofplace. Shaft extensions with sharp keyways, gears or anyother surfaces which might damage the seal lip duringinstallation should be taped. The seal lip and seal journalshould be prelubricated with the same oil to be used in thegearcase. The seal can be driven home with a soft malletand a smooth faced cylinder with an outside diameter aslarge or larger than the seal diameter. The seal must beinstalled square to the shaft. A thin coat of RTV on the sealoutside diameter will help assure a leak free installation.

PREPARING THE DODGE APG FOR REPAIR

WARNING

TO ENSURE THAT DRIVE IS NOT UNEXPECTEDLY

STARTED, TURN OFF AND LOCK OUT OR TAGPOWER SOURCE BEFORE PROCEEDING. FAIL-

URE TO OBSERVE THESE PRECAUTIONS COULDRESULT IN BODILY INJURY.

Remove the DODGE APG from the driven equipment.Remove any attached couplings, sprockets or pulleys andtheir keys from the input and output shaft extensions.C-Face motors may be removed or kept with the drive asdesired. Clean the entire drive thoroughly and move it tothe work area.

gearbox. Such oil is likely to be contaminated with metalparticles and damaged by severe overheating.REMOVING AND INSTALLING THE INPUT DEVICE

The DODGE APG may have a motor, a C-face adapteroraseparate reducer adapteras the inputto the gearcase. Theprocedureto remove or replace the input is the same forallinput devices. Take care when working with the input de-vice to avoid gear damage. Pull the input device straightback until the tenon is disengaged and the gears can beseen, then swing the input device to bring the gears outof mesh.

WARNING

EQUIPMENT BEING REMOVED MAY BE TOOHEAVY TO CONTROL MANUALLY. SUPPORT IT

BY EXTERNALMEANS. FAILURE TOOBSERVE THESEPRECAUTIONS COULD RESULT IN BODILY INJURY.

1. Support the input device so it will not fall when it isremoved. Secure slinging is recommended.

2. Remove the bolts holding the input device to the gear-case. Note that Sizes 7 and 8 have one stud in the bolt

- pattern on the same side_.as _the gearcase feet.

3. Insert a sharp cold chisel into the pryoff slot cast into the

gearcase. Strike the chisel sharply with a heavy ham-mer to break the seal. As soon as one side separates,move to the other side of the gearcase. Use the chisel

--7TF

Inspect the input and output shafts for nicks, set screwmarks or other damage. Smooth the shaft extensions asneeded with a fine toothed file. Wrap the shaft extensionswith one or two smooth layers of plastic electrical tape,covering the shaft from the end to past the end of thekeyway. The tape will help protect hands as well as theshaft. .- \7 «-'.

WARNING

HOT OIL CAN CAUSE SEVERE BURNS. USE EX-

TREME CARE WHEN REMOVING LUBRICATIONPLUGS AND VENTS. DO NOT GET IN LINE WITH THE

PLUG. HOT OIL CAN BE BLOWN A CONSIDERABLEDISTANCE SHOULD THE GEARCASE BE PRES-

SURIZED BY A CLOGGED VENT. WEAR SUITABLE

PROTECTIVE CLOTHING AND EYE SHIELDS.

Drain the oil from the gearcase. Use extreme care if thedrive is still warm. Hot oil will cause severe burns. Remove

the highest plug first to relieve any possible pressure in thegearcase and to speed draining. Drain the oil from thelowest plug. Do not save or reuse oil from a damaged

21

4. Use slender pry bars to complete the separation of theinput device from the gearcase. Single and double re-duction units (upthrough 25.6:1 ratio) have atenon fittothe gearcase. Triple reduction units (ratios from 31 :1and higher) have two dowel pins aligning the tripleadaptertothe gearcase. Thetriple adapter will comeoffwith the input device. Be prepared to catch the "Y"

stage pinion assembly as the input on a triple reductionunit is withdrawn. See "Triple Adapter Repair" forremoval of the triple adapter from the input device.

INSTALLING THE INPUT DEVICE

The input device is installed after all other repair work isdone and is the last major step before relubricating thedrive and placing it back into service.

1. Supportthe inputdevice securely, butso itcan easilybemoved into alignment.

2. Apply a W bead of Loctite Gasket Eliminator 515 orRTV silicone sealent around the mating flange on thegearcase or triple adapter. Run the bead inside the boltholes and dowel pins.

3. On Sizes 7 and 8, be sure the mounting stud is in placein the gearcase input flange on the side near the feet.Refer to the Parts Identification Drawings on page 35.

4. Guide the input device into place, keeping the inputpinion clear of its mating gear as long as possible. Atleast one of the gears (preferably both) must be free torotate so the gear teeth can align and mesh withoutforcing. The gearcase output shaft should be free torotate. If the input device is a brakemotor, use themanual release to free the brake. If the input device is aseparate reducer adapter, be sure the input shaft is freeto rotate. C-face adapters should have the shippingstrap removed from the input shaft before assembly.

5. Secure the input device retaining hardware and tightento the torque shown in the Hardware Torque Table.

1

b, 1

6. The DODGE APG is now completely assembled.Check all hardware for the proper torque according tothe Hardware Torque Tables. Grease all bearings ascalled for in the "Lubrication" section. If practical, refillwith oil to the proper level for the mounting positionused. See "Lubrication." Where the mounting positionmakes proper filling in the shop difficult, tag the unit witha "DO NOT RUN BEFORE LUBRICATING" sign anddelay final oil fill until after installation. A rebuilt DODGEAPG should be treated as a new drive. See -Installa-

tion" for prestart and startup checklists.

REMOVING AND INSTALLING THE

FIRST STAGE PINION

A shank type first stage pinion is a common feature of all

22

'1

T

models of the DODGE APG, regardless of the style of inputdevice. The first stage pinion is interference fit into an axialbore in the shaft of the input device. The pinion is furthersecured by a cross pin driven through the shaft and thepinion shank.

7- CROSS PIN

/ It( 11\ 11\LLr

rSHANK

PINION1,I

TYPE

n----f1 1

1 1 - ill-L_-4 lp----=6:EKES-L INPUT DEVICE SHAFT

TYPICAL FIRST STAGE PINION ASSEMBLY

For ease of handling, the shaft assembly containing thepinion should be removed from the input device beforeattemptingto removethe pinion. Whilethe pinion isout, theaxial bore and the cross pin hole in the shaft should becleaned well and examined for wear, damage orcorrosion.Do not reuse an input device shaft unless both the axialbore and the cross pin hole are in good condition.

Once removed, the cross pin must always be discardedand replaced with a new pin.

A variety of methods may be used to remove the pinion

from the shaft bore. The following procedures are suggest- ed. Contact the factory if difficulty is encountered. ./-

REMOVING THE CROSS PIN

1. Protect the pinion teeth by wrapping with several layersof plastic tape.

2. Support the shaft below the pin with a wooden block toreduce the risk of damaging the shaft or bearings. Thissupport is especially important on the smaller sizes.

3. Use a pin drift of the proper size to drive the crosspin out. Discard the used pin.

AL Vi t..t

REMOVING THE PINION

Pinions are removed from 1/4 HP through 10 HP gear-motors and the smaller sizes of the separate reduceradapters by means of a pinion puller. On ratios where thepinion diameter is smaller than the input shaft a washerhas to be welded to the end of the pinion. See examplesbelow:

,-=F,2-F-e- ip

*1

i-EXfli

f P»CON PULLER &ARM ASSEMBLY

PINION PULLER &CAP ASSEMBLY

:11

Pinion removal kits may be obtained from your DodgeParts Distributor. To help you get the kit you need, pleaseprovide data from all name-plates on the drive, includingthe gearcase, motor and accessories.

14 H.P. THRU 5 H.R KIT NUMBER IS 79130-02-J

5 H.R AND 10 H.R KIT NUMBER IS 79130-02-M

Grease Gun Method of Pinion Removal:

The shafts of 15 HPthrough 200 HP gearmotors are drilledand tapped forgreaselittings, as are the larger sizes of theseparate reducer adapters. A 1/4-28 grease fitting isthreaded into the tapped hole. In gearmotors, the tappedhole may be located ahead of or behind the motor bearing.The tapped hole in separate reducer shafts may be foundon either side of or under the bearing closest to the pinion.

116"k .»·. .

..

Pi Ii"le'

WELD

23

A heavy duty grease gun is used to remove the pinion withhydraulic pressure.

After the pinion is removed, the grease fitting should beremoved.

INSTALLING THE PINION

T

A

1. Lubricate the pinion shank with a thin coat of highquality antiseize compound.

2. Center the input device shaft assembly in a press.

Positionthe shaftassembly sothecross pin hole can besighted through while operating the press.

If- tl3. Set the pinion in the shaft bore. Rotate the pinion to

align the cross pin hole in the pinion with the crosspinhole in the shaft.

t

4. Press slowly while sighting through the crosspin hole inthe shaft. Press until the pinion bottoms or until thecross pin holes line up. Avoid overpressing.

REPLACING THE CROSS PIN

1. Protect the pinion teeth from a missed hammer blow.

2. Support the shaft opposite the pin.

3. Drive a new pin in place.

REPAIRING THE SEPARATE REDUCER INPUT

NOTE: See "Removing and Installing the Input Device"and "Removing and Installing the First Stage Pinion" be-fore proceeding.

SEPARATE REDUCER ADAPTER TEARDOWN

1. Remove the shaft key (1) and wrap the shaft extensionwith plastic tape. Wrap the pinion (9) teeth with plastictape.

2. Remove the bearing clamp (12) retaining hardware(11). Remove the bearing clamp (12). Use a soft malleton the keyed extension end of the shaft (2) to drive allthe internal parts out the flange end of the housing (16).Work carefully. Remove the backstop key (6 or 18) as itbecomes accessible on units equipped with backstops.On Sizes 7 and 8, remove the bearing cup (21) as soonas it clears the bore.

3. If the bearings or backstop must be replaced, removethe bearing (3 or 27) at the keyed end of the shaft first.Remove the retaining rings (7 and/or 15). Remove thebackstop (5). Remove the pinion (9) end bearing (13 or20) last. If the pinion outside diameter is larger than thebearing inside diameter, the pinion will have to beremoved before the bearing can be removed. See"Removing and Installing the First Stage Pinion"in this manual.

4. Remove the input oil seal (17) from the housing (16).The oil seal should be replaced with a new seal when-ever the unit is torn down for any reason. On Sizes 7and 8, remove the bearing cup (26). Remove all pipeplugs (4, 14, 23).

24

5. Clean and inspect all parts. Be sure the housing iscleaned of all old grease. The backstop should be thor-oughly cleaned& then rinsed in clean solvent. Inspectthe shaft for wear at the seal journal and in the areaunder the backstop.

SEPARATE REDUCER ADAETER ASSEMBLY1. Study the Parts Identification Drawing for the size of

separate reducer adapter you have.

2. Assemble all components on the shaft. Start by press-ing the bearing on the pinion end. Add the other compo-nents and complete the shaft assembly by pressing thebearing on the shaft extension end. Be sure to installthe retaining rings (7 and/or 15) and grease shields(24). Check the direction of rotation of the backstop tobe sure it is installed in the proper direction for yourapplication. If the backstop is not installed properlybefore installing the bearing (3 or 27), the whole unitwill have to be torn down to correct the backstop.

3. Put some stiff grease in the backstop keyway to hold thebackstop key (6 or 18) in place in the backstop keyway.On Sizes 7 and 8, install the bearing cup (26) in thehousing and seat solidly.

4. Slide the shaft assemblyintothe housing, taking caretoalign the backstop key with the keyway in the housing.On Sizes 7 and 8, the grease shield (24) must berotated to aligned with the pipe plug holes (23).

5 . Sizes 3 through 6: Install the bearing clamp (12) andhardware (10 or 11). Tighten the screws to the torquespecified in the Hardware Torque Tables. Spin the shaftto check for smooth rotation with little drag.

Sizes 7 and 8: Install the bearing cup (21), seal (19),bearing clamp (12), and hardware (11). Tighten thescrews to the torque specified in the Hardware TorqueTables. Use a soft mallet to drive the shaft both ways toseatthe bearings. Spin the shaftto be sure the bearingsare seated and square. Use a dial indicator to measurethetotal shaftendplay. Selectashim pack toprovidetheendplay shown in the table below:

SHAFT ENDPLAY CHART FOR

SIZE 7 AND 8 SEPARATE REDUCER ADAPTERS

INPUT RPM

100 - 750

750 - 1800

1800 - 2500

NORMAL

DUTY

(2OF - 11 OF)

.000 - .002

.002 - .004

.003 - .005

LOW TEMP

DUTY'

( - 3OF to + 2OF)

.000 - .002

.001 - .003

.002 - .004

'Also includes operation less than 4 hours per day.

Remove the bearing clamp (12), insert the shims (22)and retorque the bearing clamp screws. Check theendplay. Reshim if needed. Spin the shaft to check forsmooth rotation with little drag.

1

.

36

37

31

32

33

34

35

28

29

30

RER

NO.

24

26

27

22

23

20

21

16

17

18

13

14

15

7

8

9

4

5

6

10

11

12

1

2

3

SEPARATE REDUCER ADAPTER PARTS IDENTIFICATION DRAWING

PART DESCRIPTION

INPUT SHAFT KEYINPUT SHAFT

BALL BEARING

PIPE PLUG

BACKSTOPBACKSTOP KEY

RETAINING RINGCROSS PIN

PINION

HEX SOCKET HEAD

HEX HEAD SCREW

CLAMP

BALL BEARING

PIPE PLUGRETAINING RING

SEPARATE ADAPTER

INPUT OIL SEAL

BACKSTOP KEY

BEARING CONE

BEARING CUP

BEARING SHIMS

PIPE PLUG

GREASE SHIELD*BEARING CUP

BEARING CONE

COOLING FAN

FAN COVER

SCREW

WASHER

SPACER

SET SCREW

VENT PLUGREDUCER BUSHING

DRIVE SCREW

VENT BAFFLE

1

1

0/1

1

1

1

1

1

*USED ONLY ON SIZE 7&8 UNITS WITH BACKSTOPS

2131 35

28 30 32 16 4 5 18 24 20 34

33

29

17 26 27 23

FIGURE 4 - FOR DODGE APG SIZES S7-D7-S8-08

1

1

1

4

1

FIG. 1

SIZES

5,6

QTY.

1

1

1

1

1

1

1

FIG. 2

SIZES

3,4

QTY.

1

0/1

1

1

1

4

1

4I

36

37

12

11

FIG. 3

SIZES

T7-T8

QTY.

1

1

1

1

0/1

1

1

1

1

1

1

4

1

0/2

0/1

1

1

AS REQ.

2

2

1

1

1

1

1

25

0/1

1

1

2

1

4

4

2

1

1

4

1

1

0/20/1

FIG. 4

SIZES

57-D7

58-D8QTY.

1

1

4

1

AS REQ.2

1

1

17

34 5 6

789

--

-

11

- - 11-

16 14 13

rj12

11

FIGURE 1 - FOR DODGE APG SIZES 5 AND 6

17

3 4 5 6

-- 31- - - .1;1 --1- .1

---+J112

11

16 15 14 13

FIGURE 2 - FOR DODGE APG SIZES 3 AND 4

16

17

7

21 33

4 5 18 24 20 32

26 27 23

r

4I

22

FIGURE 3 - FOR DODGE APG SIZES T7-T8

36

37

12

11

7 9

2.

1.

7. Install a new input oil seal (17). Use a smooth facedcylinder slightly larger than the outside diameter of theseal to press or drive the new seal flush with the end ofthe housing.

8. See the "Special Instructions" in the "Lubrication" sec-tion of this manual for proper lubrication for the separatereducer adapter with and without backstop. Check the

1 2

torque on all hardware before installing the separatereducer adapter on the gearcase.

WARNING

CHECK THE DIRECTION OF ROTATION ON BACK-STOP EQUIPPED UNITS AGAIN BEFORE RETURN-ING TO SERVICE. FOLLOW THE PRESTART ANDSTARTUP CHECKLISTS IN THIS MANUAL.

C-FACE ADPATER PARTS IDENTIFICATION DRAWINGSFOR DODGE APG SIZES 2-8

3 4 5

BEARING SHIELD

BEARING SHIELD

9

8 9

15 14 13 12

ASSEMBLY OF MOTOR TO C-FACE REDUCER

See yellow instruction tag no. DMR070 which is attachedto the C-face adaptor casting and accompanies eachreducer from the factory.

Removal of motors from C-face reducers or rotation of

motor conduit box location with relation to 12:00-3:00-

6:00-9:00 o'clock positions

Removal of motor from C-face reducer:

A. Remove plastic caplug from hold in size ofC-face adaptor.

B. Loosen clamp collar clamp screw.C. Remove four bolts which attach motor to C-face

adaptor.

D. Using two pry bars, carefully insert tips of pry barsinto motodC-face adaptor joint and pry off usingequal pressure on each side.

Rotation of motor conduit box position:A. Remove plastic caplug from hole in side of

C-face adaptor.

B. Loosen clamp collar clamp screw.C. Remove four bolts which attach motor to

C-face adaptor.

D. Using two pry bars, carefully insert tips of pry barsinto motor/C-face adaptor joint and move motorjust enough to allow it to be rotated.

26

REF.

NO.

10

11

12

13

14

15

1

2

3

4

5

6

7

8

9

PART DESCRIPTION

CLAMP COLLAR

OIL SEAL

BALL BEARING

INPUT SHAFT

CROSS PIN

PINION

RETAINING RING

HEX HEAD SCREW

HEX SOCKET

CAP SCREW

CLAMP

C-FACE

ADAPTER HOUSING

PIPE PLUG

GREASE FITTING

SNAP-IN HOLE PLUG

HEX HEAD SCREW

QTY.

1

1

1

1

1

1

1

0 OR 4

0 OR 4

1

1

1

1

4 OR 8

E. Rotate motor to give desired conduit boxposition.

F. Reattach motor mounting bolts and tightento recommended torque listed on page 45 of thismanual.

G. Retighten clamp collar clamp screw to rec-ommended torque listed below:

H. Reinstall caplug into hole in side of C-face adaptor.

MOTOR

FRAME

56/140

180/250

280/365

COLLAR

SCREW

1/4-20

5/16-24

3/8-24

REC.

TORQUE

LB-FT

14

27

47

REC.

TORQUE

LB-IN

REPAIRING THE C-FACE ADAPTER

NOTE: See "Removing and Installing the Input Device"before proceeding.

C-FACE ADAPTER TEARDOWN

1. Remove the clamp collar (1). Remove the bearingclamp (10). Slide the input shaft (4) assembly out of thehousing (11).

2. Remove the oil seal (2). The oil seal should always be replaced with a new seal. .....

3. Use a pin drift to drive out the cross pin (5). Use a closefitting rod through the input shaft to press the pinion (6)out.

168

324

564

.

4. Remove the retaining ring (7). Press the bearing (3) offthe input shaft (4).

5. Remove the grease fitting (13). Clean and inspect allparts to determine what needs to be replaced. Useextra care when cleaning the single shielded bearing.Dirt and old grease are difficult to remove from the areabetween the ball retainer and the shield. Flush the

grease channel from the grease fitting to the bearingbore thoroughly.

ASSEMBLY OF THE C-FACE ADAPTER

1. Press bearing (3) on the input shaft (4) with the bearingshield facing the pinion end of the shaft. Be sure thebearing is solid against the shaft shoulder. Install theretaining ring (7).

2. Press the pinion (6) into the shaft. Before pressing,take care to line up the cross hole in the pinion with thecross hole in the input shaft so the cross pin can bedriven through.

3. Protect the pinion by wrapping with several layers ofplastic tape. Rest the input shaft extension on a woodblock while driving the cross pin through.

4. Press a new oil seal (2) into the housing (11) from themotor side. The seal garter spring must face the gear-case. The seal isto be flush to 1/16"below flush with the

REF.

NO,

motor side of the housing and square with the inputshaft.

5. Smoothly wrap the clamp collar end of the input shaftwith a layer of plastic tape to prevent cutting the oil seallip as the input shaft assembly is installed.

6. Pack the ball bearing about half full of grease. Wipegrease over the motor end of the shaft, over the tapeapplied in Step 5. See "Lubrication" for propergreases.

7. Insert the input shaft assembly into the bearing bore inthe housing, taking care to work the seal over the shaftwithout dislodging the seal garter spring. Use a softmallet to be sure the bearing is fully seated.

8. Install the bearing clamp (10) and screws (8 or9). Tightenthe screws to the torque specified in the HardwareTorque Table, page 45.

9. Install the grease fitting (13). Remove all protectivetape from the input shaft. Put the clamp collar in placeon the shaft, but do not tighten the clamp screw.

10. See "Input Device Removal and Replacement" forassembly of the C-Face adapter to the gearcase. See"Mounting Motors to C-Face Reducers" in the "Instal-lation" section for motor mounting.

GEARMOTOR INPUT - PARTS IDENTIFICATION DRAWING56 AND 140 FRAME MOTORS

56 FRAME MOTORS H

(E<

0-11- 11= 61-111- 119 1111Ill

140 FRAME MOTORS

1

2

3

4

5

6

7

8

9

10

11

12

13

PART DESCRIPTION

BALL BEARING (B.E.)WAVE SPRING

PIN

PINION

DEFLECTOR

SEAL SLEEVE

OIL SEAL

BACK END (B.E.) SHIELDPLUG

SHAFT AND ROTOR

ASSEMBLY

STATOR AND WINDING

MOTOR FRAME

FAN SHROUD BRACKET

1

1

1

1

0091

1

1

1

1

56 FR.

MOTOR

Qly.

1

1

1

25

140 FR.

MOTOR

QTY.

1

1

1

1

0OR1

1

1

1

1

1

1

1

4

I111111

27

REF.

NO.

14

15

16

17

18

19

20

21

22

23

24

25

26

® (!!) i

*1

26 1

-1

75 ,

PART DESCRIPTION

FAN SHROUD SCREW

THROUGH BOLT

FAN SHROUD

FRONT END (F.E.)SHIELD

FAN

LOCKWASHER

BEARING CLAMP

SCREW

FAN CLAMP

BALL BEARING (F E.)

LOCKRING (F.E.)

.025 SHIMBEARING CLAMP

LOCKRING (B.E)

1 1

56 FR.

MOTOR

QTY.

2

4

1

1

1

2

2

1

1

2

1

1

140 FR.

MOTOR

QTY.

4

4

1

1

2

2

1

1

1

1

0

71

Ill E

1

2

·3

4

5

6

7

8

9

10

REF.

NO.

18

22

19

23

(jir

GEARMOTOR INPUT - PARTS IDENTIFICATION DRAWING

180 THROUGH 360 FRAME MOTORS

24

17 16 15

PART DESCRIPTION

BALL BEARING (B.E.)PLUG

PIN

PINION

DEFLECTOR

SEAL SLEEVE

OIL SEAL

BACK END (B.E.) SHIELDGREASE FITTING

HEX HEAD BOLT (B.E.)

QTY.

1

1

1

1

0OR1

1

1

1

4

REPAIRING THE GEARMOTOR INPUT

11

12

13

14

15

16

17

18

REF.

NO.

T.

11

PART DESCRIPTION

SHAFT AND ROTOR

ASSEMBLY

STATOR AND WINDING

MOTOR FRAME

FAN SHROUD BOLT

HEX HEAD BOLT (F.E.)GREASE FITTING

GREASE TUBE

FAN SHROUD

NOTE: See"INPUT DEVICE REMOVAL AND REPLACE-

MENT" for instructions for removing the motor from agearmotor.

GENERAL INFORMATION

The motor used for the gearmotor version of the DODGEAPG is designed to provide a compact, high power densitypackage when mated to the DODGE APG gearcase.

All DODGE APG gearmotors share common designfeatures:

1. The fan end motor bearing is clamped to take all thrustfrom the gearing.

28

1

1

1

4

4

1

1

1

QTY.

REF.

NO.

19

20

21

22

23

24

25

CD CD

10 9 8

71

PART DESCRIPTION

FRONT END (F.E.)SHIELD

FAN

FAN CLAMP

FAN KEY

BEARING CLAMP

SCREW

BALL BEARING (F.E.)BEARING CLAMP

5

1

1

1

1

QTY.

3

1

1

2. All motors are "TEFC" (Totally Enclosed, Fan Cooled)construttion suitable for a wide variety of applications.

3. The motor shaft is also the input shaft to the gearcaseand carries the first stage pinion.

4. The motor end shield opposite the fan is called the"back end" or "B.E." shield, and will be referred to as

the B.E. shield in this manual. On the DODGE APG, theB.E. shield forms the input face of the gearcase and

carries the input shaft oil seal. The motor end shield onthe fan end of the motor is called the "fan end" or "F. E."

shield and will be so called in this manual.

.

--

.

MOTOR TEARDOWN

NOTE: The photos show a 256 frame motor, but are typi-cal of all 180 frame and larger motors. 56 and 140 seriesframe motors have structural differences, but the se-

.quence of repair operations is the same as shown. The PartReference Numbers in ( ) in the following instructionsrefer to the Parts Identification Drawing for 180 through400 series frame motors.

1. Wrap several layers of plastic tape around the pinion(4) and applygrease overthetapeto protectthe pinionand oil seal (7) during repairs.

Remove the fan shroud (18), the fan clamp (21), thefan (20) and key (22). On small motor fans, the key ismolded integral with the fan and the fan clamp is alockring. Take care to not crack the fan. Wood blockingand wide faced pry bars will help.

2. Remove grease fittings (9 and 16) and extensiontubes (17), if so equipped, at both ends of the motor.

r

*%?

29

3.

4.

7 15.7.

f

Removethe bolts (10) holding the B.E. shield (8) tothemotor frame (13).

Remove the bolts (15) holding the F.E. shield to themotor frame (13).

5. Use a soft mallet to loosen the B.E. shield to motor 8.

frame tenon. Slide the B. E. shield off. Take care to pullstraight back to avoid bumping the oil seal on thepinion or shaft.

4 454,--*-JL-' 9

6. Checkthecondition of the oilseal sleeve (6). Itmustbereplaced if grooved orotherwise damaged. Inspectthe

B.E. bearing (1).

t

9

7. Loosen, but do not remove, the F.E. bearing clampbolts (23).

9. Use a soft mallet to loosen the F.E. shield to motor

frame tenon. Slide the F.E. shield back. The motor

shaft and rotor assembly will come along.

a=£47-*Ii

i!*r-,'/p...il-

4444£Q-

10. Remove the F.E. bearing clamp bolts (23), and slidethe F.E. shield (19) off the bearing. inspect the F.IE.bearing (24). Slide the motor shaft and rotor assem-bly out of the stator. Take care to not hit the motorwindings.

I I

L ,

'4*, 1 1,

30

t

.

.

11.

12.

13.

Replace the bearings and seal sleeve if needed. If thepinion (4) is bigger in diameter than the motor shaftextension diameter, the pinion will have to be removed

before the B.E. bearing and seal sleeve can bechanged. See "Removing and Installing the First

Stage Pinion" in this manual. The rubber oil deflector

(5) is only used with large diameter pinions. It shouldbe removed by stretching over the pinion before pinionor bearing removal is begun. Take care to not damagethe pinion bore in the motor shaft. Use a protective

plate, as shown, across the pinion bore if using abearing puller.

Dr

Remove and discard the oil seal (7). The seal shouldalways be replaced at teardown.

1

Clean and inspect all parts. Blow the stator and wind-ing out with compressed air. Do not clean the windingwith solvents unless the solvents are specifically ap-

proved for such use. End shields should be cleanedwell in a wash tank. Use a small brush or pipe cleaner

to be sure all old grease is removed from greasepassages. Bearings should not be immersed in sol-vent. If the bearing is to be reused, wipe old grease offthe outside of the bearing and clean no further.

31

ASSEMBLY OF THE MOTOR

1. Replace the oil seal in the B.E. shield. Use a smoothfaced, heavy walled cylinder larger than the outsidediameter of the seal but smaller than the outside

diameter of the bearing. Insert the seal with the garter

spring toward the gearcase side of the B.E. shield.Press or drive the seal in from the motor side of the

B.E. shield. Seat the seal flush with the bearing shoul-der in the B.E. shield.

2. If the pinion has been removed from the motor shaft,see"Removing and Replacing the First Stage Pinion."

3. Slip the F.E. shield into place on the bearing. Align thebearing clamp and start the bearing clamp screws.

f

5.

4. Tighten the bearing clamp screws to the torque speci- 7.fied in the Hardware Torque Tables, page 43.

k

4

Insert the rotor and shaft assembly with the F.E. shieldattached into the motor stator and frame assembly. 8.Take care not to hit the end turns of the winding.Rotate the F.E. shield so the grease fittings will beaccessible in the installation and so any condensatedrains fitted will be down.

Install the fan key, fan and fan clamp. Locate the screw

on the hose type clamp opposite the fan key to main-tain balance.

1

Install the fanshroud andgrease fittings on the fan endof the motor.

1

.

4

6. Tighten the F.E. shield retaining bolts to the torque

specified in the Hardware Torque Tables.

0

32

9. Be sure the pinion is taped and greased the same aswas done in Step 1 of "Motor Teardown." Coat the oilseal lip in the B.E. shield and the seal sleeve on themotor shaft with the same grease that will be used toregrease the motor bearings. Carefully slide the B.E.shield into place. Do not let the new oil seal bump thepinion. The bearing provides a good guide to smoothlyengage the oil seal with the seal sleeve. Install thedeflector (5).

j

r

.

REF.

NO.

1

2

3

4

5

6

7

8

9

10

11

12

22

21

20

19

10. Rotate the B.E. shield so the grease fittings will beaccessible in the installation and so any condensatedrains will be down. Note the position of the gearcaseflange holes. Install the B.E. shield retaining bolts andtorque to the value specified in the Hardware TorqueTable. Recheck all accessible hardware for tightness.The motor is now assembled and ready to belubricated. See "Motor Bearing Lubrication" in the"Lubrication" section of this manual.

3

SINGLE REDUCTION GEARCASE PARTS IDENTIFICATION DRAWINGFOR DODGE APG SIZES 3-8

REF.

NO.

2 1111

(D--

4

5

1 1

4-1..../ko-41 111 1 '1 /1 111 1L-1413 46 'lilli

®®® Ill)

PART DESCRIPTION

GEARCASE

HEX HEAD SCREW

NAMEPLATE

NAMEPLATE PIN

VENT PLUG ASSEMBLY

STANDARD BEARING HOUSING

HEX HEAD SCREW

OUTPUT SHAFT SEAL

OUTPUT SHAFT KEY

OUTPUT SHAFT

BEARING SHIMS

OUTBOARD BEARING CUP

QTY.

1

6

1

2

1

0OR1

4

1

1

1

AS REQ.

1

33

13

14

15

16

17

18

19

20

21

22

23

RISER BLOCK

OUTBOARD BEARING CONE

INBOARD BEARING CONE

INBOARD BEARING CUP

"Y" GEAR

LUBRICANT PLUG

OIL LEVEL PLUG (RED)"Y" GEAR RETAINER WASHER

SOCKET HEAD CAP SCREW

"Y" GEAR KEY

FLANGED BEARING HOUSING

23

6

1

8 (D®1 1

1--

PART DESCRIPTION QTY.

0OR4

1

1

1

1

4

1

1

1

1

0OR1

REPAIRING THE SINGLE REDUCTION GEARCASE

NOTE: The output bearing housing on the DODGE APGmay be eitherstandard or flanged. Teardown and assemblyis the same for both.

TEARDOWN

1. Place the gearcase foot down on the workbench. Use awood or plastic wedge between the inside bottom of thegearcase and the "Y" gear (17) to prevent the outputshaft from turning.

Z

NOTE: A Double Reduction gearcase is shown.

*2. Remove the socket head cap screw (21) and gear re-taining washer (20). The "Y" gear (17) should slide offthe output shaft (10). Remove the "Y" gear key (22).

4/3/>4

0

f

NOTE: A Double Reduction gearcase is shown.

3. Place the gearcase on the workbench with the outputshaft (10) extension up. Wrap the output shaft extensionwith plastic tape. Remove the hex head screws (7) hold-ing the output bearing housing (6 or 23).

4. The output bearing housing is sealed to the gearcasewith Loctite Gasket Eliminator 515 or RTV silicone

sealant. Use a chisel and hammer to break the seal, as

was done to remove the input device.

5. With the output bearing housing removed, the outputshaft can be lifted out. The output shaft bearing cones(14 and 15)arepress fitontheoutputshaft. Properpresstools and press capacity will be needed to replace them.The output bearing cups (12 and 16) are slip fit into the

34

f

gearcase and bearing housing. The cups should beremoved for proper cleaning and inspection.

6. Inspect all parts for wear or damage, replacing parts asneeded. The output shaft oil seal (8) should always be.replaced with a new seal.

ASSEMBLY OF SINGLE REDUCTION GEARCASE

1. Insert the inboard bearing cup (16) into the gearcase.Tap with a soft mallet to be sure it is fully seated.

2. Place the output shaft, complete with bearing cones (14and 15) installed, into the gearcase.

3. Insert the outboard bearing cup (12) into the outputbearing housing. Tap with a soft mallet to be sure it isfully seated.

4. Install the bearing housing with just two diametricallyopposite bolts. Pull the bolts snug. Tap both ends of theoutput shaft with a soft mallet while rotating the shaft toseat the bearings.

5. Measure the end play of the output shaft. This is mosteasily done by mounting a dial indicator against oneend of the shaft, then pushing the shaft both ways torecord the limits of shaft travel. Select shims to make a

shim pack.001 to.003 inches less in thickness than theshaft endplay measured.

NOTE: If pry bars are used to move the shaft, asshown, be sure the bars are notagainstthe gear teeth.

1 ir»

NOTE: A Double Reduction gearcase is shown.

6. Remove the bearing housing. Remove the outboardbearing cup (12) from the bearing housing. Place thebearing shims (11) in the bearing housing and replacethe bearing cup, seating it firmly on the shims.

7. Replace the bearing housing and check for.001 to.003inches of end play in the output shaft, using the sameprocedure as used in Step 5. Spin the output shaft tocheck for any binding or roughness. Adjust shimmingas needed.

8. Once the end play is correct, remove the bearinghousing and apply a %" bead of Loctite Gasket Elimiinator 515 or RTV silicone rubber around the tenon.

Replace the bearing housing and tighten the bolts to thetorque shown in the Hardware Torque Tables, page 44.

1

.

*9. Put the gear key (22) in the output shaft. Slip the gearover the shaft and key. Note that the extended hub ofthe gear goes toward the bearing. Install the gear re-tainer washer (20) and socket head cap screw (21).Tighten the screw to the torque specified in the Hard-ware Torque Tables. Turn the shaft slowly through sev-eral revolutions to check for binding or roughness.

10. The output shaft extension should be taped, clean andlubricated with the oil to be used in the gearcase. Lubri-cate the shaft seal (8) lip with more of the same type of

*NOTE: Some reducers with special features may in-clude an interference fit gear (17), ratherthan a slip fit.Inthose cases it will be necessaryto use abearing pullertoremove the gear. Exercise care not to damage gear teethin this process.

35

oil and slide the seal over the shaft. The seal garterspring goes toward the shaft bearing. Gently work theseal lip over the seal journal, taking care to not unseatthe seal garter spring. Drive or press the seal flush to1/ 6 below flush with the output bearing housing, usinga smooth, cylindrical driver against the outside edge ofthe seal. The seal must be installed square with theshaft. The gearcase assembly is complete. See theappropriate sections of this manual for assembly of theinput device and lubrication instructions.

Reinstallation of the gear will require the use of a press.Care must be taken to support the shaft to prevent thepressing load being transmitted thru the bearings.

If you are unsure if your reducer has an interferencefit, contact the factory with the Identification Number ofyour reduce.

1

2

3

4

5

6

7

8

17

18

19

30NUT ANDSTUD ON

SIZES 7 AND 8 29ONLY

10

11

12

13

14

15

REF.

NO.

16

9

33

32

1

SIZE

2-6

QTY.

1

1

1

1

2

DOUBLE REDUCTION GEARCASE PARTS IDENTIFICATION DRAWINGSFOR DODGE APG SIZES 2-8

31

1 1Ll

37 38 Q * (f * (j)(D 0 -,37/ 1 1 40

1 Jff)clov117-

- --Ula/d

d V1 152*5/I -

16i P1 992::Mir ITL-L.6.---

r-7

C--N\35

PART DESCRIPTION

GEARCASE

"Z" OUTPUT GEAR

"Z" GEAR KEY

VENT PLUG ASSEMBLY

NAMEPLATE

NAMEPLATE PIN

HEX HEAD SCREW

FLANGED BEARING

HOUSING

STANDARD BEARING

HOUSING

OUTPUT BEARING CUP

1

J

1 X\\\

1 3 28 27 26 25 (8) 23 ®

OUTPUT BEARING CONE

OUTPUT SHAFT

OUTPUT SHAFT KEY

DOWEL PIN

OUTPUT SHAFT

OIL SEAL

OUTPUT BEARING

SHIMS

OUTPUT BALL BEARING

OIL LEVEL PLUG (RED).025 THICK

BEARING SHIM

1

1

1

1

1

2

6

0OR1

0OR1

1

1

2

AS REQ.

1

1

1

1

1

1

1

1

2

6

SIZE

7

QTY.

OOR 1

0 OR 1

AS REQ.

1

1

SIZE

8

QTY.

1

1

1

OOR 1

1

1

1

1

1

2

6

0OR1

1

1

1

1

2

AS REQ

36

33

34

35

36

37

38

24

25

REF.

NO.

20

21

22

23

26

27

28

29

30

31

32

Lt4l «5

PART DESCRIPTION

"YZ" BEARING SHIMS

RISER BLOCK

"YZ" SHAFT

BEARING CUP

"YZ" SHAFT

BEARING CONE

"YZ" PINION SHAFT

"YZ" SHAFT

BEARING CONE

"YZ" SHAFT

BEARING CUP

"Y" GEAR SPACER

LUBRICANT PLUG

INPUT STUD

HEX NUT

"Y" GEAR

SOCKET HEAD

CAP SCREW

"Y" GEAR RETAINER

"Y" GEAR KEY

OUTPUT BALL BEARING

HEX HEAD SCREW

OUTPUT BEARING CUP

OUTPUT BEARING CONE

LJ

14

11

SIZE

2-6

QTY.

1

1

1

1

1

1

1

1

6

1

18

AS REQ.

OOR#

1

1

2

SIZE

7

QTY.

TAPERED

ROLLER

BEARINGS

SIZE 8 ONLY

BALL BEARINGS

SIZES 2 THRU 7

AS REQ.

OOR 4

1

1

1

1

1

1

1

1

5

1

1

2

1

1

1

1

1

1

1

1

AS REQ.

0 OR 4

5

1

1

1

1

1

1

2

1

1

1

SIZE

8

QTY.

.j

REPAIRING THE DOUBLE REDUCTION GEARCASE

NOTE: The output bearing housing on the DODGE APGmay be either standard or flanged. Teardown and assem-bly is the same for both.

TEARDOWN

1. Place the gearcase foot down on the workbench. Use awood or plastic wedge between the inside of the gear-case and the "Y" gear (31) to prevent the "Y" gear fromturning.

4

.e 9

4. Wrap the output shaft (12) extension with plastic tape.Remove the bolts (7) holding the output bearing hous-ing (8 or 9).

f

hi

2. Remove the socket head cap screw (32) and the gearretaining washer (33).

f

5. Theoutputbearing housing issealedtothegearcase withLoctite Gasket Eliminator 515 or RTV silicone sealant.Use a chisel and hammer at the cast-in pry off slots tobreak the seal, as was done to remove the input device.Larger sizes may be easier to work on if placed on theinput end of the gearcase.

*3. The "Y" gear (31) should slide off the "YZ" pinion shaft '(24). Remove the gear key (34) and the gear spacer(27). The "Y" gear in some ratios will not come all theway off the shaft until the "YZ" pinion is free to move ' JUI 4* -forward. In these cases, leave the "Y" gear in place until .-.13 MStep 6.

37

See note on page 40 regarding special features.

6. With the output bearing housing removed, the outputshaft (12) assembly can be lifted out. The assembly isheavy and must be cocked so the gear will clear otherinternal parts.

DODGE APG Sizes 3 through 7 have shielded ballbearings on the output shaft. DODGE APG Size 8 hastapered roller bearings. The output shaft bearings are aheavy press fit on the output shaft. Proper press toolsand press capacity will be needed to replace them. Theoutput bearings are slip fit into the gearcase and bear-ing housing. The bearing cups in the Size 8 should beremoved for proper cleaning and inspection.

NOTE: Shielded ball bearings are not to be washed orflushed with solvent. If the bearing is contaminated,replace it.

'.

I +

7. Remove the "YZ" pinion shaft (24) by pushing on theextension on the input end. If the "Y" gear would notcome out in Step 3, it can now be removed as the "YZ"pinion is withdrawn. The shims (19 and 20) and out-board bearing cup (22) will come out with the shaft.Note that the outermost shim (19) is .025 inches thick.This shim will have to be replaced in this outermostposition at assembly.

f

1

38

8. Clean and inspect all parts for wear or damage. Theoutput shaft oil seal (15) should always be replaced.

ASSEMBLY OF THE

DOUBLE REDUCTION GEARCASE

1. Insert the "YZ" pinion shaft bearing cup (26) into thegearcase. Tap with a soft mallet or hammer handle tobe sure it is fully seated.

2. Place the "YZ" pinion shaft (24), complete with bear-ing cones installed, into the gearcase. The "Y" gear ofsome ratios will have to be installed at the same time.

See Step 13.

3. Install the outboard "YZ" pinion shaft bearing cup (22).Tap the cup and the shaft with a soft mallet as the shaftis spun to be sure the bearings are seated. Use adepth micrometer as shown to measure from the gear-case face to the bearing cup.

15 +

.

.

4. Select a shim pack equal to the depth dimension 7. Putthe outboard bearing cup (10) in place on the Sizemeasured minus .001 to .003 inches. Check the shim 8. Tap the shaft and bearings to be sure they are fullypack thickness with a micrometer. One of the shims seated. Use a metal straightedge and a depth microm-(19) must be .025 thick. eter or vernier caliper as shown to get the dimension

from the outeredge of the outboard bearing tothe face

, of the gearcase.

.kt,r

5. Place the shim pack over the bearing cup with the.025shim outboard. The shim pack may be held in placewith a small amount of stiff grease or RTV sealant. 8. Use the same method to get the dimension from the

bearing housing face to the shoulder of the bearingbore.

1 --1

16

6. Only the Size 8 requires the bearing cup (37) to beplaced in the gearcase bore before installing the out-put shaft (12) assembly. All other sizes have ball bear-ings on the output shaft. Install the output shaftassembly, carefully engaging the output gear (2) withthe "YZ" pinion shaft (24) teeth.

39

9. Subtract the dimension obtained in Step 7 from thedimension of Step 8. For Sizes 1 through 7, assemblea shim pack with a thickness.005 to.010 less than theresult. For Size 8, select a shim pack.001 to .003 lessthan the result. Check the shim pack thickness with amicrometer. Insert the shim pack (16) into the bearinghousing bore. Retain with a small amount of stiffgrease or RTV sealant.

E

10. Carefully set the output bearing housing (7 or 8) intoplace, checking to be sure the bearing shims remain inplace. Tap the bearing housing over the aligning pins.

NOTE: Though the output shaft oil seal (15) is shownin place in the photo, it is recommended that it be leftout until all other components are assembled. SeeStep 17.

Im 1

13. Install the gear retainer washer (33) and the sockethead cap screw (32). Wedge the gear to preventrotation and tighten the screwto the torque specified inthe Hardware Torque Tables, page 43.

2

0

14.

11. Tighten the bearing housing bolts (7) to the torquespecified in the Hardware Torque Tables, page 43.

* 12. Place the gearcase back on its feet or with the inputface up. Larger sizes are more easily worked on withthe input face up. Install the "Y" gear spacer, key andgear. Note that the extended hub on the "Y" gear isinstalled toward the bearing.

Use a dial indicator to check the end play of both the"YZ" pinion shaft (24) and the output shaft (12). Bothshafts must indicate end play within the limits speci-fied. If the shafts show end play outside the tolerance,record the actual end play for reference, remove theoutput bearing housing and add or remove shims asneeded. Right angle pry bars, as shown, can be usedto move the intermediate shaft if care is taken not to

pry on the gear teeth. The output shaft is best movedby pushing and pulling on the output extension.

F

t

& 0

-

15. With the end play of the shafts correct, turn the shaftsslowly through several revolutions to check forbindingor roughness.

r

40

.

.t

.

16. Remove the output bearing housing. Apply RTVsealant or Locfite Gasket Eliminator 515 to the gear-case face. Run a W' bead around inside the bolt

holes and dowel pins. Carefully set the output bear-ing housing (7 or 8) into place, checking to be surethe bearing shims remain in place. Tap the bearinghousing over the aligning pins. Tighten the bear-ing housing bolts (7) to the torque specified in theHardware Torque Tables, page 45.

1

1

*NOTE:-Some reducers with special features mayinclude an interference fit of the "Y" gear (31) on the

41

"YZ" pinion shaft (24). In those cases, it will be neces-sary to use a bearing puller to remove the gear. Exercisecare not to damage gear teeth in this process.

Reinstallation of the gear will require the use of a press.

17. The output shaft extension should be taped, clean andlubricated with the oil to be used in the gearcase.Lubricate the lip of the oil seal (15) with more of thesame type of oil and slide itoverthe shaft. Gently workthe seal lip over the seal journal, taking care to notunseat the seal garter spring. Drive or press the sealflush to 1/16" below flush with the output bearing hous-ing (8 or 9), using a smooth, cylindrical driver againsttheoutside edgeof theseal. Theseal mustbe installedsquare with the output shaft. The gearcase assemblyis complete. See the appropriate sections of this man-ual for assembly of the input device and triple adapter,and for lubrication instructions.

Care should be taken to support the "YZ" pinion shaft to

prevent the pressing load being transmitted to YZ shaftbearing (23).

If you are unsure if your reducer has an interference fit,

contact the factory with the identification number of yourreducer.

Stud Used On

Size 7 Only

14

13 ll '1\1 1k. 11.1

12

11

10 1

1 2893

FIGURE 1 - DODGE APG SIZE 2-7

REF.

NO.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

A

PART DESCRIPTION

TRIPLE ADAPTER

BALL BEARING

BALL BEARING

BEARING CUP

BEARING CONE

BEARING CUP

BEARING CONE

"X" GEAR

"XY" PINION SHAFT

"X" GEAR KEY

BEARING SHIMS

RETAINING RING

HEX HEAD SCREW

INPUT STUD

HEX NUT

19

TRIPLE ADAPTER PARTS IDENTIFICATION DRAWING

42

14

SIZE

2-6

QTY.

1

1

1

15

ff]811 9 1k. 11 1

5 19

148

FIGURE 2 - FOR DODGE APG SIZE 8

FIGURE 1

SIZE

7

QTY.

9 6

1 1

1 1

1 1

AS REQUIRED

1 1

6 5

- 1

- 1

1

1

1

1

FIG. 2

SIZE

8

QTY.

1

1

1

1

1

1

1

1

5

1

1

1

.

.

.

REPAIRING THE TRIPLE ADAPTER

NOTE: The triple adapter is used only with overall ratios of31.4:1 and higher.

The triple adapter will usually come off with the input de-vice, since they are sealed together with RTV siliconerubber sealant. The "XY" pinion shaft (9) assembly willusually stay in the gearcase, though it may pull free duringremoval of the input device. See "Removing the InputDevice."

Triple adapters for DODGE APG Sizes 2 through 7 areequipped with ball bearings on the "XY" pinion shaft asshown in Figure 1 of the Triple Adapter Parts IdentificationDrawing. The Size 8 triple adapter has tapered rollerbearings as shown in Figure 2.

TRIPLE ADAPTER TEARDOWN

Sizes 2 thru 7 (Ball Bearings):Remove the "XY" pinion shaft assembly.

Size 8 (Roller Bearings):Remove the "XY" pinion shaft assembly.Remove the bearing cup (4), bearing shims (11), and theretaining ring (12) from the bearing bore in thetriple adaptor.Remove the bearing cup (6) from the bore in the gearcase.

Sizes 2 thru 8:

Remove the triple adaptor from the input device by insertingpry bars and blocks between the triple adaptor spokes andthe gearcase side of the input device. Pry carefully toseparate. Use proper gear and bearing removal tools toseparate the "XY" pinion assembly into its component partsif necessary. Clean and inspect all parts to determine whatne6ds to be replaced.

TRIPLE ADAPTER ASSEMBLY

NOTE: All work on the gearcase and the input deviceshould be completed before assembly of the triple adapteris started.

NOTE: A number of flat washers of the correct size to fit the

input device attaching bolts will prove handy while settingthe "XY" pinion shaft end play. Place several on each boltused to temporarily hold the triple adapter to the gearcasesothetriple adaptercan be snugged down without bottom-ing out the bolts.

1. Begin assembly by pressing all parts in the "XY" pinionshaft assembly into place on the "XY" pinion shaft (9).Be sure the gear (8) and bearing (2 or 5) are solidagainst each other and the shaft shoulder and that thekey (10) is in place. Press the bearing (3 or 7) solidagainst the other shaft shoulder.

43

2. Install the bearing cup (6) in the gearcase bore (Size 8only). Tap with a softhammerto besurethe bearing cupisseated. Install the "XY" pinion shaftassembly into thegearcase bore. In some cases, the "Y" gear will have tobe loosened on the "YZ" pinion and pulled back toprovide clearance to install the "XY" pinion assembly.See"REPAIRING THE DOUBLE REDUCTION GEAR-

CASE," page 36.

3. Install the retaining ring (12) into the triple adapter (1).Be sure the ring snaps all the way into the groove.

4. Temporarily install the triple adapter on the gearcase.Make sure the two dowel pins which align the tripleadapter with the gearcase are in place. Three of the sixbolts are sufficient.

5. Measurethe shaft end play byeitherof thetwo methodsshown:

Preferred Method: Mount a dial indicator and move the

"XY" shaft end to end. Rotate the shaft to be sure the

bearings are seating at both ends of the stroke. Recordthe total end play indicated.

Optional Method: Use feeler gauges to measure theclearance between the outside race of the bearing andthe retaining ring. Be sure the bearings are fully seatedtoward the gearcase by tapping with a soft mallet whilerotating the shaft. Record the clearance measured.

/r=

6. Remove the triple adapter. For Sizes 2 through 7, selecta shim pack .005 to .010 inches less than the end playmeasured in Step 5. For the Size 8, select a shim pack.001 to .003 inches less than the measured end play.Insert the shims in the triple adapter bore so they aresolid against the retaining ring. Again, temporarily as-semble the triple adapter. Spin the shaft to be sure thebearings are seated and turning smoothly. Recheckthe end play. Reshim as needed.

4

1 -

7. With the end play of the "XY" pinion shaft assemblyproperly set, remove the triple adapter for final assem-bly. Be sure the input stud (14) is in place in Sizes 7and 8 gearcases. Be sure the aligning dowel pins arein place on all sizes. Apply a W bead of RTV sealantor Loctite Gasket Eliminator 515 around the gearcaseflange face which mates with the triple adapter. Applythe bead just inside the bolt and 61owel pin holes on thegearcase.

44

GEAR

CASE

SIZE

4

8. Assemble the triple adapter to the gearcase. Use a softmallet to seat the adapter over the dowel pins. Replacethe input device (See "Replacing the Input Device")immediately. Tighten the attaching hardware (13 and15) tothetorque shown inthe Hardware Torque Tables.The DODGE APG is now complete and ready for relu-brication. See the "Lubrication" section of this manual.

HARDWARE TORQUE TABLES

The torques shown are for "lubricated" threads. Lubri-cated threads are defined as any plated thread or anythread coated with any amount of oil or wax. By this defini-tion, most threaded hardware is lubricated. If in doubt, wipethe threads with a lightly oiled rag.

Specifications and torques for hardware for mounting thegearcase and for C-Face motor attachment are detailed inthe "Installation" section of this manual.

TABLE OF BEARING SHIMMING CLEARANCES

IN INCHES FOR ALL

CONFIGURATIONS OF APG UNITS

2 to 3

6

5

7

100/750

RPM

750/1800

RPM

1800/2500

RPM

8

100/750RPM

750/1800

RPM

1800/2500

RPM

SEPARATE

REDUCER

INPUT SHAFT

.000 TO

.002

.002 TO

.004

.003 TO.005

.000 TO

.002

.002 TO

.004

.003 TO

.005

XY

PINION

SHAFT

.005 TO

.010

.005 TO.010

.005 TO.010

.005 TO.010

.005 TO.010

.001 TO.003

YZ

PINION

SHAFT

.001 TO

.003

.001 TO.003

.001 TO

.003

.001 TO.003

.001 TO.003

.001 TO

.003

OUTPUT

SHAFT

.005 TO.010

.005 TO.010

.005 TO

.010

.005 TO.010

.005 TO.010

.001 TO.003

' Sizes 2 thru 6 separate reducers have clamped ball bearings on the inputshaft. No shimming is necessary.

•Sizes 7&8 clearances are for normal ambient duty (20°F to 110°F). Seepage 22 of this manual for low ambient duty ( -30°F to +20°F).

All Single Parallel units have roller bearings on the outputshaft-shim to .001/.003.

.

.

CASE

SIZE

2

3&4

5

6

7&8

TORQUES FOR GEARCASE BOLTS

(Metric Grade 8.8, Hex Head Screws)

INPUT DEVICE

TO GEARCASE

BOLT

SIZE

TORQUE

LB-IN

M12

M16

M16

M20

OUTPUT BEARING

HOUSING TO GEARCASE

SINGLE

REDUCTION

BOLT TORQUE

SIZE LB-IN

D/T

REDUCTION

BOLT TORQUE

SIZE LB-IN

CASE SIZE

CASE

SIZE

3&4

5,6,7,8

CASE

SIZE

2,3,4

5,6,7,8

M8

M10

M12

M12

M20

3

4&5

6&7

8

230

460

800

800

3700

TORQUES 'FOR "Y" GEAR RETAINING SCREWS

(Metric Grade 12.9, Hex Socket Head Screws)

CASE BOLT TORQUE

SIZE SIZE LB-IN

M8

M10

M12

M16

TORQUES FOR PIPE PLUGS

ALL CASE SIZES

TORQUE

PLUG SIZE LB-IN

1/8-27 NPT

1/4-18 NPT

3/8 - 18 NPT

1/2-14 NPT

TORQUES FOR SEPARATE REDUCER

ADAPTER BEARING CLAMP SCREWS

BOLT SIZE & DESCRIPTION

M5 HEX SOCKET HEAD, Grade 12.9

M6 HEX HEAD, Grade 8.8

TORQUES FOR C-FACE ADAPTER

BEARING CLAMP SCREWS

BOLT SIZE & DESCRIPTION

M5 HEX SOCKET HEAD, Grade 12.9

M5 HEX SOCKET HEAD, Grade 12.9

for 56/1400 motors

800

1900

1900

3700

410

815

1415

3425

100

200

400

700

TORQUE

LB-IN

100

96

TORQUE

LB-IN

100

100

5,6,7,8 M6 HEX HEAD, Grade 8.8 96for 1800 motors and larger

MISCELLANEOUS HARDWARE: The following tablesare for general application where threaded hardware is notincluded in previous torque tables.

M8

M10

M10

M12

M20

230

460

460

800

3700

45

THREAD

SIZE

6-32

6-40

8-32

8-36

10-24

10-32

1/4-20

1/4-28946-18

SA 6-24

%-16

3/8-24

746-147/16-20

1/243

1/2-20

%-11

%-18

3/4-10

3/4-16

778-9

7/8-14

1-8

1-12

8

9

14

M12

M14

M16

M20

M24

M30

M36

M3

M4

M5

M6

M8

M10

480

900

1020

1560

1800

1500

1680

2280

2520

800

1260

1900

3700

6400

12800

22500

288

324

420

15

21

23

THREAD

SIZE

108

180

204

50

56

96

12

28

56

96

230

460

TORQUES FOR ENGLISH SYSTEM

THREADED HARDWARE

HEX HEAD OR HEX SOCKET SCREWS

TORQUE (LB-IN) FORGRADE GRADE GRADE

258

420

480

660

TORQUES FOR METRIC SYSTEM

THREADED HARDWARE

HEX HEAD OR HEX SOCKET SCREWS

(Coarse Thread Series per ISO 261262)

TORQUE (LB-IN)FOR

GRADE GRADE

8.8 12.9

780

1320

1560

2400

2640

3840

4320

5760

6360

75

86

156

168

276

300

12

13

22

23

32

36

170

410

815

22

50

100

HEX

BOLT

SOCKET

WRENCH

SIZE (mm)

5.5

7

8

10

13

17

19

22

24

840

900

1300

1370

2530

2660

4400

4800

7000

7600

10400

11000

1415

2250

3425

6640

11400

22900

40000

150

170

305

325

545

570

30

36

46

55

28

30

49

50

64

76

T3

S4

D4

T2

S3

D3

S7

D7

6.75

15.00

16.50

RENEWAL PARTS

CONTACT YOUR NEAREST RELIANCE PARTS DISTRIBUTOR IN THE YELLOW PAGES UNDER THE HEADINGS

SPEED REDUCERS, POWER TRANSMISSION EQUIPMENT, OR VARIABLE SPEED DRIVES.

OR

CONTACT DODGE-MASTER-REEVES RENEWAL PARTS QUOTATIONS FOR ASSISTANCE AT PHONE NUMBER

1-803-297-4160 OR FAX NO. 1-803-281-2364. IDENTIFICATION NUMBER FROM UNIT NAMEPLATE WILL BE

REQUIRED FOR PARTS ASSISTANCE.

SERVICE ENGINEERS

FOR RATES AND AVAILABILITY OF SERVICES CALL 1-812-378-2416.

LUBRICANTFOR YOUR CONVENIENCE WE MAKE AVAILABLE FACTORY APPROVED LUBRICANT IN SMALL VOLUME CON-

TAINERS. ORDER BY PART NUMBER FROM YOUR LOCAL DODGE DISTRIBUTOR.

VOLUME

12 OZ

1 QT

1 GAL

VOLUME

1 QT

1 GAL

PART NUMBER (SHC-634)41170966AB

41170966AE

41170966AF

PART NUMBER SHC-629)

41170966AG

41170966AH

DODGE APG REDUCERS RECOMMENDED LUBRICANT SHC-634

Size

D2

T4

S5

D5

T5

S6

D6

T6

T7

S8

D8

T8

QuaMs

.70

1.63

1.63

2.00

3.38

3.50

2.75

5.25

.75

1.00

.88

1.25

1.25

5.25

4.75

16.00

17.75

CapacityGallons

.188

.250

.219

.312

.312

.172

.406

.406

.500

.844

.875

.688

1.313

1.313

1.688

3.750

4.125

1.188

4.000

4.438

46

Part No.

41170966AE

41170966AE

41170966AE

41170966AE

41170966AE

41170966AE

41170966AE

41170966AE

41170966AE

41170966AF

41170966AF

41170966AE

41170966AF

41170966AE

41170966AF

41170966AE

41170966AF

41170966AF

41170966AF

41170966AE

41170966AF

41170966AE

41170966AF

41170966AF

41170966AE

Quantity

1 Quad

1 Quart

1 Quan

2 Quarts

2 Quarts

1 Quad

2 Quarls

2 Quarts

2 Quarts

1 Gallon

1 Gallon

3 Quarts

1 Gallon

2 Quarts

1 Gallon

2 Quarts

2 Gallons

4 Gallons

4 Gallons

1 Quart

1 Gallon

1 Quart

4 Gallons

4 Gallons

2 Quarts

.

.

7

Size

4

5

6

8

2

3

SG/SM

DG/DM

TG/TM

SG/SM

DG/DM

TGHM

SG/SM

DG/DM

TG/TM

SG/SM

DG/DM

TG/TM

SG/SM

DG/DM

TG/rM

SG/SM

DG/DM

TGHM

Type

SM2

DM

TM

4

Size

2

Inner

0714701 BJ

079147038P

07914703D

07914703E

07914704L

07914704M

41162601 FT

SIZE

S2

S3

S4

S5

S6

S7

S8

X-Stacie

Outer

07914701 BJ

079147038P

07914703D

07914703E

07914704L

07914704M

41162601 GA

APG BEARING SELECTIONFor Sizes 2-8

REDUCER BEARINGS

Inner

41162601 FR

41162601D

41162601D

41162601 BC

41162601 FR

41162601 FR

41162601AC

41162601 BC

411626018C

41162601 GC

41162601 FS

41162601 FS

41162601 GD

4116201 FT

41162601 FT

41162601 FW

41162601 FV

41162601 FV

41162601 GE

41162601 FW

41162601 FW

Y-S'age

6

Outer

411626018C

41162601D

41162601D

41162601 GB

41162601 FR

41162601 FR

41162601 GB

41162601 BC

411626018C

41162601 FT

41162601 FS

41162601 FS

41162601 FV

41162601 FT

41162601 FT

41162601 FW

41162601 FV

41162601 FV

41162601 GE

41162601 FW

41162601 FW

SIZE

T2

T2F

T3

T4

T4F

T5

T6

17

T8

Z-Stage (Foot MTD)Inner Outer

07914703E

07914703E

07914703K

07914703K

07914703N

07914703N

07914703AA

07914703AA

07914703AG

07914703AG

07914703AP

07914703AP

41162601 FX

41162601 FX

07914703CS

07914703CS

07914703CT

07914703CT

07914703CU

07914703CU

07914703CV

07914703CV

07914703CW

07914703CW

07914703CM

07914703CM

41162601 FY

41162601 FY

Z-Stage (Flanqe)Outer

07914702CX

07914702CS

07914703CT

07914703CT

07914703CX

07914703CX

07914703CV

07914703CV

07914703CW

07914703CW

07914703CM

07914703CM

41162601 FY

41162601 FY

BEARING KIT

INCLUDES ALL REDUCER BEARINGS FOR GEARMOTOR STYLE UNITS. REDUCERS WITH

"C" FACE AND SEPARATE INPUT DEVICES HAVE ADDITIONAL BEARING(S) WHICH MUST BESELECTED FROM FOLLOWING CHARTS.

3

5

PART NO.

41164245AW

41164245Y

411642452

41164245AA

41164245AB

41164245AC

41164245AD

SIZE

D2

D2F

D3

D4

D4F

D5

D6

D7

D8

PART NO.

41164245AE

41164245AX

41164245AF

41164245AG

41164245AZ

41164245AH

41164245AJ

41164245AK

41164245AL

C-FACE ADAPTOR BEARING CHART

Motor

Frame

All

56C/140TC

182TC/184TC

210TC

56C/140TC

182TC/184TC

210TC/250TC

56TC/140TC

182TC/184TC

210TC

250TC

280TC

Size

3&4

5

6

7&8

C-Face AdaptorBearing

07914702AC

07914702CR

07914702CS

07914702CS

07914702CR

07914702CS

07914702CS

07914702CR

07914702CS

07914702CS

07914702CT

07914702CM

Size

7&8

Motor

Frame

140TC

182TC/184TC

210TC

250TC

280TC

320TC/360TC

182TC/184TC

210TC

250TC

280TC

320TC/360TC

400TC

SEPARATE ADAPTOR BEARING CHART

Type Inner

07914703CU

07914703DB

07914703DC

41162601GG

47

Input BearingOuter

07914703DA07914703CU

07914703CV

41162601 GH

PART NO.

41164245AM

41164245AY

41164245AN

41164245AP

41164245BA

41164245AR

41164245AS

41164245AT

41164245AV

C-Face Adaptor

Bearing07914702CR

07914702CS

07914702CS

07914702CT

07914702CM

07914702CN

07914702CS

07914702CS

07914702CT

07914702C

07914702CP

07914702CN

SIZE &

TYPE

SM2•

DM-TM2A

DM-TM2F

SG3

SM3

DG-TG3

DM-TM3

SG4

SM4

DG-TG4A

DG-TG4F

DM-TM4A

DM-TM4F

SG5

SMS

DG-TGS

DM-TMS

SGG

SM6

MOTOR

FRAME

56C/14OTC

180TC

56C/140TC

180TC

56C/14OTC

180TC

56/143/145

146/147

180

210

56C/140TC

180TC/210TC

56/143/145

146/147

180

210

56C/140TC

180TC/210TC

56/143/145

146/147

180

210

256

56C/140TC

180TC/210TC/250TC

56/143/145

146/147

180

210

256

56/143/145

146/147

180

210

256

56C/140TC

180TC/210TC/250TC

560/14OTC

180TC/210TC/250TC

56/143/145

146/147

180

210

256

56C/140TC

180TC/210TC/250TC

280TC

56/143/145

146/147

180

210

256

56C/14OTC

180TC/210TC/250TC

280TC

56/143/145

146/147

180

210

256

286

326

365

140TC

180TC/210TC/250TC

280TC

APG OIL SEAL CHART

OIL SEAL

411627-01 CR

411627-01 CS

411627-01 CR

411627-01 CS

411627-01 CR

411627-01 CS

411627-01 CY

411627-01 DA

411627-02DB

411627-01 DC

411627-01 CE

411627-01 CF

411267-01 CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 CE

411627-01CF

411627-01 CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 CE

411627-01 CF

411627-01 CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 CE

411627-01 CF

411627-01 CE

411627-01 CF

411627-01 CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 CE

411627-01 CF

411627-01CG

411267-01 CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 CE

411627-01 CF

411627-01 CG

411627-01CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 DD

411627-01 DJ

411 627-01 DL

411627-01 CE

411627-01 CF

411627-01 CG

INPUT

SLEEVE

48

79142-05C

79142-050

79142-058

79142-05E

79142-05C

79142-05D

79142-058

79142-05E

79142-05C

79142-05D

79142-058

79142-05E

79142-05A

79142-OSC

79142-05D

79142-058

79142-05E

79142-05A

79142-05C

79142-05D

79142-058

79142-OSE

79142-05A

79142-05C

79142-05D

79142-058

79142-05E

79142-05A

79142-060

79142-05D

79142-058

79142-OSE

79142-05A

79142-05C

79142-05D

79142-058

79142-05E

79142-05A

79142-05F

79142-05G

79142-05H

OUTPUT SEAL

STANDARD

411627-01 DE

411627-01 DE

411627-01 CN

411627-01 CN

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 CP

411627-01 CP

411627-01 CP

411672-01 CP

411627-01 CP

411627-01 CP

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 DF

411627-01 CR

411627-01 CR

411627-01 CR

411627-01 CR

411627-01 CR

411627-01 CX

411627-01 CX

411627-01 CX

411627-01 CX

411627-01 CX

411627-01 CR

411627-01 CR

411627-01 CX

411627-01 CX

411627-01 DG

411627-01 DG

411627-01 DG

411627-01 DG

411627-01 DG

411627-01 DG

411627-01 DG

411627-01 DG

411627-01 CS

411627-01 CS

411627-01 CS

411672-01 CS

411672-01 CS

411627-01 CS

411627-01 CS

411627-01 CS

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

411627-01 DH

OUTPUT SEAL

EASY CLEAN-XT

411627-02FE

411627-02FE

411627-02EW

411627-02FG

411627-02FG

411627-02EX

411627-02FG

411627-02EY

411627-02FD

411627-02EY

411627-02FD

411627-02FH

411627-02EZ

411627-02FJ

.

.

.SIZE

SM6

DG-TGG

DM-TMG

SG7

SM7

DG-TG7

DM-TM7

SG8

SM8

DG-TGB

DM-1-M8

MOTOR

FRAME

320TC/360TC

56/143/145

146/147

180

210

256

286

326

365

140TC

18OT(21016/25OTC

280TC

320TC/360TC

180

210

256

286

326

365

405/445

180TC/210TC/250TC

280TC

320TC/360TC

400TC

180

210

256

286

326

365

405/445

1 BOTC/21OTC/250TC

280TC

320TC/360TC

400TC

180

210

256

286

326

365

405/445

18OTC/21 OTC/250TC

280TC

320TC/360TC

400TC

180

210

256

286

326

365

405/445

180TC/210TC/250TC

280TC

320TC/360TC

400

OILSEAL

411627-01-CH

411627-01CY

411627-01 DA

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 DD

411627-01 DJ

411627-01DL

411627-01 CE

411627-01CF

411627-01CG

411627-01CH

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 DD

411627-01 DJ

411627-01DL

411627-01DL

411627-01CF

411627-01CG

411627-01CH

411627-01CJ

411627-01 DB

411627-01 DC

411627-01 DD

411627-01 DD

411627-01 DJ

411627-01 DL

411627-01 DL

411627-01(F

411627-01 CG

411627-01CH

411627-01CJ

411627·01DB

411627-01[C

411627·01 DD

411627-01 DD

411627-01 DJ

411627-01 DL

411627-01 DL

41162701CF

411627-01 CG

411267-01CH

411627-01 CJ

411627-0108

411627-01 DC

411627-0100

411627-0100

411627-01 DJ

411627-01 DL

411627-01 DL

411627-01 CF

411627-01CG

411627-01 CH

411627-0101

Continued

INPUT

SLEEVE

79142-056

79142-050

79142-058

79142-05E

79142-05A

79142-05F

79142·05G

79142-05H

79142-058

79142-05E

79142-05A

79142-05F

79142-05G

79142-05H

79142-05J

79142-058

79142-05E

79142-05A

79142-05F

79142-05G

79142-05H

79142-053

79142-058

79142-OSE

79142-05A

79142-05F

79142-05G

79142-05H

79142-05J

79142-058

79142-05E

79142-05A

79142-05F

79142-05G

79142-05H

79142-05J

OUTPUT SEAL

STANDARD

411627-01 DH

411627-01CT

411627-01CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411 627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01 CT

411627-01CT

411627-01 CT

411627-01 CT

411627-01CV

411627-01CV

411628-01CV

411627-01CV

411627-01CV

411627-01CV

411627-01CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01 CV

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

411627-01CW

49

OUTPUT SEAL

EASY CLEAN-XT

411627-02FJ

411627-02FA

411627-02FA

411627-02FB

411627-02FB

411627-02FB

411627-02FC

Size

SR3

SEPARATE REDUCER OIL SEAL CHART

DR-TR3

SR4

DR-TR4

SR5

DR-TRS

SR6

DR-TRG

SR7

DR-TR7

SRB

DR-TR8

Enclosure

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZ Clean

Standard

XT-EZCIean

Standard

XT-EZCIean

Standard

XT-EZ Clean

Standard

XT·EZ Clean

Input41162701 DK

41162702FK

41162701 DK

41162702FK

41162701 DK

41162702FK

41162701 DK

41162702FK

41162701CP

41162702EX

41162701CP

41162702EX

41162701CR

41162702EY

41162701CR

41162702EY

41162701 DN

41162701DN

41162701 DN

41162701 DN

41162701 DN

41162701 DN

41162701 DN

41162701 DN

Output41162701DF

41162702FG

41162701 CP

41162702EX

41162701 DF

41162702FG

41162701CR

41162702EY

41162701 DG

41162702FH

41162701 CS

41162702EZ

41162701 DH

41162702FJ

41162701 CT

41162702FA

41162701CT

41162702FA

41162701CV

41162702FB

41162701CV

41162702FB

41162701 CW

41162702FC

'

D-SERIES MOTOR BRAKE WARRANTY

DODGE will cover all defects due to material and work-

manship (if properly installed, operated and maintainedin accordance with DODGE specifications) for a periodof one year in service or 18 months from date code,whichever occurs first.

If within the warranty timeframe a customer has arectifier failure only, DODGE will supply a rectifierreplacement kit to the customer at no charge which canbe installed in the motor conduit box. If the unit fails for

reasons other than the rectifier, a returned goods autho-rization should be obtained from DODGE CustomerService at (803) 297-4800, and the unit should bereturned to DODGE at the address below for inspectionto determine the actual cause of failure.

If the failure was due· to defects in material or workman-

ship DODGE, at its· discretion, will either repair, replace6r issue credit for the failed unit. This warranty shall notapply where equipment is operated above rated load

' capacity or is subjected to accident, alteration, misuse orabuse. In either case, inbound and outbound transporta-

tion chargesre.the buyer's responsibility. *Ex6ept· as directly modified herein, this product is subjectto the. Reliance,Electric Standard Terms and Conditionsof Sale. 4*1 2Return to: REtIANCE ELECTRIC CO.

DODGE CLUTCH BRAKE

146 POWDER MIELROAD· - .,COLLINSVILLE, CT 06022 -ATTN: WARRANTY INSPECTION -

DODGE / P.O. Box 499 / 6040 Ponders Court / Greenville, S.C. 29602-0499 / (864) 297-4800t Reliance Electric Company, 1995

DODGE and E-Z KLEEN are registered trademarksof Reliance Electric Company or its affiliates.

Printed in US.A. Instruction Manual 499776

'A

Y

14

34

..2 Ii:.fr:

'I ?

I.

./. ft?41.

. . -L

.f 109515M-K

,,

h

1

*

ti

.iy

f.

f

t'

1,

':1 4. 5./.

INSTRUCTION MANUAL FOR DODGEiD-SERIES SPRING-SET MOTOR BRAKES

(STANDARD, WASHDOWN AND E-Z KLEEN ENCLOSURES)

DBSC Model ,

DBSS Model

NOMENCLATURE

56 DBSS - 3NEMA C-Face -- -Designation

56 = 56 (5/8" Shaft)140= 143TC/145TC

(7/8" Shaft)180 = 180TC/210TC*

.(11/8" Shaft)

DODGE Brakes

Housing EnclosureS = Standard Enclosure/

Drip-ProofW = Washdown (NEMA 4)E = E-Z KLEEN/BISSC

(Food Duty/NEMA 4)0XP = Explosion Proof

Mounting ConfigurationC = C-Face (Single)/

Fan End MountingS = Shaft Out (Double

C-Face) Coupler

Static Torque Rating (Ft.-Lbs.)

p Wear Adjustment MethodMA = Manually Adjusted

Coll Voltagc115/230 VAC230/460 VAC

1 Other as Noted on Brake Label

- MA -115/230 VAC 60 Hz

Frequency60 Hz50 Hz

Blank if DC voltage only

'Note: 180 frame motor brakes available with single C-face mounting only

PRE-INSTALLATION INSTRUCTIONS:

The DODGE D-Series motor brakes are manufactured toNEMA standards for mounting to C-face and double shaftedmotors. They operate as spring-set, electrically-releasedpower-off brakes to provide a holding or parking action.These DODGE motor brakes are factory assembled,adjusted and pre-bumished allowing for immediate oper-ation after attachment to the motor. Chart 1 should beconsulted to verify compatibility.

WARNING

When failure of brake or connecting equipment (gear-box, coupling, etc.) may allow unexpected machinemovement an additional holding device is required atthe load. Failure to observe this precaution couldresult in bodily injury.

CHART 1 (Important: See Note 1)

NEMA Motor E haft Dia.

Motor Non-Drive

Frame Drive End (Fan) End

56C

143TC/

145TC

182TCY184TC

213TC/215TC

7/8'

11/8"

13/8"

5/8"

7/8"

11/8"

DBSC

Model (2)56DBSC-3

56DBSC-656DBSC-1056DBSC-1556DBSC-2056DBSC-25

56DBSC-356DBSC-656DBSC-10

56DBSC-1556DBSC-2056DBSC-25

140DBSC-3140DBSC-6

140DBSC-10140DBSC-15140DBSC-20

140DBSC-25

180DBSC-6180DBSC-10180DBSC-15180DBSC-20180DBSC-25180DBSC-35180DBSC-50

DBSS

Model (2)56DBSS-356DBSS-656DBSS-10

56DBSS-15

56DBSS-2056DBSS-25

140DBSS-3

140DBSS-6140DBSS-10140DBSS-15140DBSS-20140DBSS-25

N/A

N/A

Notes:

(1) Chart 1 is based on dimensions of Reliance Electric standard ACmotors. As seen in the chart, the shaft at the non-drive end of 140,180 and 210 frame motors is smaller than the drive end enablingthe use of the smaller frame size brake. THIS MAY VARY WITHOTHER MOTOR MANUFACTURERS. For use ol these brakes with

other makes of motors, brake mounting dimensions should be veri-fied with motor manufacturer.

(2) These selectionsare also applicable for DBWC/DBWS &DBEC/DBES styles.

WARNING: Because qf the possible danger to persons(s) or property from accidents which may result from the improper use of products, it isimportant thatcorrect procedures be followed. Products must be used in accordance with the engineering information specified in the catalog.Proper installation, maintenance and operation procedures must.·bq observed. The instructions in the instruction manuals must be followed.Inspections should be made as necessary to assure safe operati6n under prevailing conditions. Proper guards and other suitable safety devicesor procedures as may be desirable or as may be specified in safety codes should be provided, and are neither provided by Reliance ElectricIndustrial Company nor are the responsibility of Reliance Electric Industrial Company. This unit and its associated equipment must be installed,adjusted and maintained by qualified personnel who bre familiar with the construction and operation of all equipment in the system and the poten-tial hazards involved.- When risk to persons or property may be involved, a holding device must be an integral part of the driven equipmentbeyond the speed reducer output shaft.

.

.

.

Longer LifeQuieter OperationEasy Installation -<:301Interchangeable

• Easy-to-use, reliable manualrelease levers reset automatically.

• Industry standard NEMAC-face mounting. Interchangeseasily with competitive units.

• Wear adjustments are made externalto brake - no disassembly required!Adjustments can be made in less thana minute.

sa"i

l

• Single C-face (fan end mounting) & Double C-face(coupler) configurations.

• Covers 56, 140 dind 180 NEMA C-face mountingdimensions.

• Static torque ratings: 3-50 lb.-ft.• 115/230/460/575 units available from stock.

-'.8812,01/11--

G*r'

Reliance TENV Brakemotor

2

• Rugged, die-cast aluminumhousing mounts at any anglewithout modification.

• Internally rectified DC voltage coiloperates on either AC or DC voltage.Class B insulation is standard.

• Splined hub permits uniform loaddistribution. Integral key designsimplifies installation - no loose parts.

• Non-asbestos friction disc designextends life, reduces replacementparts and allows quiet operation.Single disc unit shown.

- •Standard enclosure is a

drip-proof design.

• Brakes are available in washdown models completelysealed on the shaft per Underwriters Laboratories (U/L)Environmental Type 4 rating.

Additionally these models with a food industryapproved coating are available as an E-Z KLEENModel for 'BISSC' Service.

-t

22.2/*-:" <.

I .

14. .'4

Reliance TEFC Brakemotor

811"44#A

Double C-Face Brake On

C-Face Motor

*

4

1

.06 i'

Description

DBEC COMPLETE UNITS

56 Frame, 5/8" Bore

115/230 VAC 60 Hz (1 )230/460 VAC 60 Hz (2)

287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)

190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC12 VDC

DBEC COMPLETE UNITS

140 Frame, 5/8" Bore

115/230 VAC 60 Hz (1)

230/460 yAC 60 Hz (2)

287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)

250/500 VAC 50 Hz

48 VDC

24 VDC

12 VDC

DBES COMPLETE UNITS

56 Frame, %" Bore

115/230 VAC 60 Hz (1)

230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC12 VDC

DBES COMPLETE UNITS

140 Frame, 5/8 Bore

115/230 VAC 60 Hz (1 )

230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)

190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC

12 VDC

COMPLETE UNIT PART NUMBERS-DBEC/DBES Models

3 Ft-Lb

031910

031716

031911

030753

030754

030755

030861

030860

030859

029436

029437

029438

029454

029455

029456

029492

029491

029490

030381

030382

030383

030735

030736

030737

030843

030842

030841

029400

029401

029402

029418

029419

029420

029474

029473

029472

6 Ft-Lb

031913

031718

031914

030756

030757

030758

030864

030863

030862

029439

029440

029441

029457

029458

029459

029495

029494

029493

030384

030385

030386

030738

030739

030740

030846

030845

030844

029403

029404

029405

029421

029422

029423

029477

029476

029475

Unit Size

10 Ft-Lb

031915

031916

031917

030759

030760

030761

030867

030866

030865

029442

029443

029444

029460

029461

029462

029498

029497

029496

030387

030388

030389

030741

030742

030743

030849

030848

030847

029406

029407

029408

029424

029425

029426

029480

029479

029478

Notes:

Other voltages covered

(1) 115/208-230 VAC 50 or 60 Hz, 133/265 VAC 60 Hz, 110-125 VDC.

(2) 208-230/460 VAC 50 or 60 Hz, 240/480 VAC 60 Hz, 220/440 VAC 50 Hz, 230 VDC.

(3) 287/575 VAC 60 Hz, 275/550 VAC 60 Hz, 300/600 VAC 60 Hz.

(4) 104/208 VAC 50 or 60 Hz, 100/200 VAC 60 Hz, 90-95 VDC.

(5) 190/380 VAC 50 or 60 Hz, 200/400 VAC 60 Hz, 208/416 VAC 50 Hz.

15

Static Torque

15 Ft-Lb

031918

031919

031920

030762

030763

030764

030870

030869

030868

029445

029446

029447

029463

029464

029465

029501

029500

029499

030390

030391

030392

030744

030745

030746

030852

030851

030850

029409

029410

029411

029427

029428

029429

029483

029482

029481

20 Ft-Lb

031921

031922

031923

030765

030766

030767

030873

030872

030871

029448

029449

029450

029466

029467

029468

029504

029503

029502

030393

030394

030395

030747

030748

030749

030855

030854

030853

029412

029413

029414

029430

029431

029432

029486

029485

029484

25 Ft-Lb

031924

031925

031926

030768

030769

030770

030876

030875

030874

029451

029452

029453

029469

029470

029471

029507

029506

029505

030396

030397

030398

030750

030751

030752

030858

030857

030856

029415

029416

029417

029433

029434

029435

029489

029488

029487

F.I

Description

DBWC COMPLETE UNITS

56 Frame, 5/8 Bore

115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)

287/575 VAC 60 Hz (3)

104/208 VAC 60 Hz (4)

190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC12 VDC

DBWC COMPLETE UNITS

140 Frame, 5/8" Bore

115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)

104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC

12 VDC

DBWS COMPLETE UNITS

56 Frame, %" Bore

115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)

287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)

190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC12 VDC

DBWS COMPLETE UNITS

140 Frame, 5/8" Bore

115/230 VAC 60 Hz (1)

230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)

104/208 VAC 60 Hz (4)

190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC

24 VDC

12 VDC

COMPLETE UNIT PART NUMBERS-DBWC/DBWS Models

3 Ft-Lb

031331

031674

031194

029051

029052

029053

029074

029073

029072

029508

029509

029510

029526

029527

029528

029092

029091

029090

031720

031615

031721

029144

029145

029146

029164

029163

029162

029180

029181

029182

029199

029200

029201

029218

029219

029220

6 Ft-Lb

031189

031677

031195

029054

029055

029056

029077

029076

029075

029511

029512

029513

029529

029530

029531

029095

029094

029093

030351

030352

030353

029147

029148

029149

029167

029166

029165

029183

029184

029185

029202

029203

029204

029221

029222

029223

Unit Size

10 Ft-Lb

031190

031327

031196

029057

029058

029059

029080

029079

029078

029514

029515

029516

029532

029533

029534

029098

029097

029096

030354

030355

030356

029150

029151

029152

029170

029169

029168

029186

029187

029188

029205

029206

029207

029224

029225

029226

Notes:

Other voltages covered

(1) 115/208-230 VAC 50 or 60 Hz, 133/265 VAC 60 Hz, 110-125 VDC.

(2) 208-230/460 VAC 50 or 60 Hz, 240/480 VAC 60 Hz, 220/440 VAC 50 Hz, 230 VDC.

(3) 287/575 VAC 60 Hz, 275/550 VAC 60 Hz, 300/600 VAC 60 Hz.

(4) 104/208 VAC 50 or 60 Hz, 100/200 VAC 60 Hz, 90-95 VDC.

(5) 190/380 VAC 50 or 60 Hz, 200/400 VAC 60 Hz, 208/416 VAC 50 Hz.

14

Static Torque

15 Ft-Lb

031191

031328

031197

029060

029061

029062

029083

029082

029081

029517

029518

029519

029535

029536

029537

029101

029100

029099

030357

030358

030359

029153

029154

029155

029173

029172

029171

029189

029190

029191

029208

029209

029210

029227

029228

029229

20 Ft-Lb

031192

031329

031198

029063

029064

029065

029086

029085

029084

029520

029521

029522

029538

029539

029540

029104

029103

029102

030360

030361

030362

029156

029157

029158

029176

029175

029174

029192

029193

029194

029211

029212

029213

029230

029231

029232

25 Ft-Lb

031193

031330

031199

029066

029067

029068

029089

029088

029687

029523

029524

029525

029541

029542

029543

029107

029106

029105

030363

030364

030365

029159

029160

029161

029179

029178

029177

029196

029197

029198

029214

029215

029216

029233

029234

029235

All parts should be examined for any damage during theshipping and handling process. Measurements shouldbe taken to ensure parts meet mounting requirements,

' such as hub and shaft fits, etc. All parts must be cleanand free of any foreign material before attemptingassembly. Care should be taken to ensure that contami-nants (such as grease from the motor, oil from a gear-box, etc.) do not contact the friction faces as this willcause the brake to operate improperly.

Prior to shipment, the friction disc/discs has been cen-trally located in the brake. As a result, it is not recom-mended to engage the manual release mechanism tomount the brake. However, should the manual release

mechanism be engaged prior to mounting the brake, the

j * friction disc/discs may have to be centrally located andaligned during mounting.

It is recommended that the entire INSTALLATION

and ELECTRICAL CONNECTIONS sections be read

prior to starting installation in order to plan ade-quately for electrical connections.

DANGER

This equipment is at line voltage when AC power isconnected. Disconnect and lock out all ungroundedconductors of the AC power line. Failure to observethese precautions could result in severe bodily injuryor loss of life.

INSTALLATION: 56/140 DBSC/DBWC/DBEC

MODELS (Single C-face)

STEP 1. Remove any burrs from the motor shaft beforeattempting to mount the hub. Mount.the splined hub ontothe motor shaft. The hub'utilizes an integral key s<? thatno installation or securing of a key is necessary. SeeDiagram A below for proper positioning of the brake hubon the motor shaft. The chamfered end of the splinedhub should be positioned away from the motor to providea lead-in guide when mounting the brake. Secure thetwo hub setscrews to 75-80 lb.-in. of torque. The use ofanaerobic adhesives either on the shaft/hub connection

DIAGRAM A: Hub Positioning

CHAMFERED END

(Hold location withinlimits shown)

Standard non-vent (TENV) andfan-cooled (TEFC) motors

CHAMFERED END

(Hold location withinlimits shown)

Dust-tighVwater-tight andE-Z KLEEN/washdown motors

1/s" to 34"

3/is" * 1/16"--• 1-

3

or the hub set screws is not recommended because of

the possibility of uncured material contaminating the fric-tion surfaces when the motor is started up.

Note: Prior to mounting the brake onto the hub, deter-mine how electrical connections will be made. For exam-

pie, external through the conduit egress in the brakehousing or internal from the motor to the brake.

For these models wiring may be made easier by bringingthe brake leads from the motor out through the lead wireaccess cover on the label side of the brake before mak-

ng connections.

STEP 2. Mount the brake to the motor taking care toproperly engage the splined hub with the splined bore ofthe friction disc in the brake. If force seems to be needed

for proper mounting, look for other problem areas suchas foreign matter in the spline or cocking of the brake.DO NOT HAMMER BRAKE INTO PLACE. Once the

brake contacts the motor face, rotate the brake to alignthe mounting holes. If the motor shaft is not free to rotatedue to an external load, it may be necessary to manuallyrelease the brake at this time in order to rotate it so as to

align the mounting holes. Secure the (4) mounting bolts(3/8-16 UNC) provided to the motor with 300 lb.-in. oftorque. The brake can be mounted in any orientation:horizontal, vertical (either end up) or on an incline with-out any adjustments.

INSTALLATION: MODEL 180 DBSC

STEP 1: Remove new brake from flange by loosening(4) mounting bolts (3/8-16 UNC).

STEP 2: Mount adapter flange to 180 motor flange with(4) mounting bolts (1/2-13 UNC). Tighten mounting boltsto 75 lb.-ft. of torque.

STEP 3: Remove any burrs from shaft before attemptingto mount hub. Mount the splined hub onto the motorshaft. The hub utilizes an integral key so that no installa-tion or securing of the key is necessary. Space hub fromthe flange face·per diagram A. The chamfered end of thesplined hub should be positioned away from the motor toprovide a lead-in guide when mounting the brake.Secure the two setscrews to 20-25 in.-lbs. of torque. Theuse of anaerobic adhesives either on the shafUhub con-

nection or the hub set screws is not recommended

because of the possibility of uncured material contami-nating the friction surfaces when the motor is started up.

STEP 4: See Step 2 of 56/140 DBSC installation.

Note: Prior to mounting the brake onto the hub, deter-mine how electrical connections will be made. For exam-

pie, external through the conduit egress in the brakehousing or internal from the motor to the brake.

For these models wiring may be made easier by bringingthe brake leads from the motor out through the lead wireaccess cover on the label side of the brake before mak-

ing connections.

INSTALLATION: DBSS/DBWS/DBES MODELS

(Double C-Face)

These models are intended to be concentrically locatedbetween two pieces of equipment such as a motor andreducer. It is not intended to have a sheave, pulley,sprocket or any overhung load placed on the outputshaft.

Note: There are two access holes in the brake housingfor tightening the hub set screws. Positioning the hubsetscrews in-line with these access holes by releasingthe manual release levers and rotating the shaft willmake location easier after the brake is positioned ontothe motor shaft.

STEP 1. Slide brake onto motor shaft taking care first toremove any burrs on the motor shaft. If force seems tobe needed for proper mounting, check for other problemareas. DO NOT HAMMER BRAKE INTO PLACE. Once

the brake contacts the motor face, rotate the entire brake

to align the mounting holes. Finger tighten the mountingbolts to secure the brake to the motor.

STEP 2. Tighten the (4) mounting thru bolts (3/8-16 UNC)to the motor with 300 lb.-in. of torque.

STEP 3. Using the access holes in the housing, tightenthe two setscrews in the splined hub to 75-80 lb.-in. Thesetscrews should be already aligned with the accessholes so that no adjustments or movement of the motorshaft or hub are necessary to enable tightening of thesetscrews. Note: Both (2) setscrews must be tightenedto the recommended torque levels to ensure properoperation. Realignment of the hub setscrews with thehousing access holes, if necessary, requires the use ofboth manual release levers to release the brake (seeManual Release Operation) and allow brake output shaftto rotate freely.

ELECTRICAL CONNECTIONS:

DANGER

The user is responsible for conforming with theNational Electrical Code and all other applicable localcodes. Wiring practices, grounding, disconnects andovercurrent protection are of particular importance.Failure to observe these precautions could result insevere bodily injury or loss of life.

CAUTION

If the brake is to be internally wired to the motor, besure that the lead wires are not pinched when themating faces are brought together. Failure to observethis precaution could result in damage to or destruc-tion of the equipment.

CAUTION

If electrical soft-start or inverter is used in the systemcare must be taken to ensure that the brake is sup-plied with full voltage. Brake must have the full inputvoltage to ensure proper release and operation.

CAUTION

REPLACEMENT/RETROFIT APPLICATIONS: In

order to ensure proper wiring connections when plac-ing this brake in place of another, be sure to tracemotor leads back to the motor conduit box. Brake lead

markings may differ among brake manufacturers. If indoubt, voltages should be measured.

1) WIRING FOR T.HE FOLLOWING VOLTAGE UNITS:

* 115/208-230 VAC 50 or 60 Hz, 133/265 VAC 60 Hz,110-125 VDC

4

* 208-230/460 VAC 50 or 60 Hz, 240/480 VAC 60 Hz,220/440 VAC 50 Hz, 230 VDC

* 287/575 VAC 60 Hz, 275/550 VAC 60 Hz, 300/600VAC 60 Hz

* 104/208 VAC 50 or 60 Hz, 100/200 VAC 60 Hz,

90-95 VDC

* 190/380 VAC 50 or 60 Hz, 200/400 VAC 60 Hz,208/416 VAC 50 Hz

* 250/500 VAC 50 or 60 Hz

The above group of DODGE D-Series Motor Brakesoperates on single phase, dual voltage AC and containsan internal rectifier to convert AC voltages to DC (Note:the brake coil is DC). The same brake will also run onsingle voltage DC.

There are 5 lead wires coming out of the brake. Eachwire is clearly marked every 11/2: Lead wires are graywith the exception of B-5 (used for Hi-pot testing-seeMaintenance Guide for procedure) which is red. Wiringconnections should be made per Chart 2 (a similar chartis also included in a label on the brake). To change theoperating voltage, simply change the wiring connectionsper Chart 2. Note that for DC operation, the connectionsare the same as for the low voltage AC input. Whenchanging brake wiring connections for operation atanother voltage, be sure to verify the brake's compatibili-ty with the voltage desired.

CHART 2: WIRING CONNECTIONS

(see also Wiring Schematic below)

Voltage

AC Voltage-Low

AC Voltage-High

DC Voltage-Low

WIRING SCHEMATIC

Power

Line A

B1

Bl & 85

B1

Power

Line B

B2

B2

B2

Insulate

Together83 & 85

83 & 85

AC Voltage-Low and DC Voltage

81 0 Power Line A

82 0 Power Line B

B3

85 Insulate Together

84 • Insulate Alone

AC Voltage-HighB1

85 82 •

83 •

84 •

Power Line A

Power Line B

Insulate Alone

Insulate Alone

Insulate

Alone

B4

B3

B4

B4

2) WIRING FOR THE FOLLOWING VOLTAGE UNITS:

* 48 VDC

*24 VDC

* 12 VDC

This group of DODGE D-Series Motor Brakes operateson single voltage DC only. There are two white leadwires coming out of the brake. These leads should be

Description

DBSC COMPLETE UNITS56 Frame, 5/8" Bore, 41/2" Pilot Diameter115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz48 VDC

24 VDC

12 VDC

DBSC COMPLETE UNITS

140 Frame, 7/8" Bore, 41/2" Pilot Diameter115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48 VDC24 VDC

12 VDC

DBSC COMPLETE UNITS

140 Frame, 11/8" Bore, 41/2" Pilot Diameter115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz12 VDC

24 VDC

48 VDC

DBSC COMPLETE UNITS

180 Frame, 11/8" Bore, 81/2" Pilot Diameter115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

12 VDC

24 VDC48 VDC

DBSS COMPLETE UNITS56 Frame, 5/8" Bore/Shaft, 41/2" Pilot Diameter115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48VDC

24VDC

12VDC

DBSS COMPLETE UNITS

140 Frame, 7/8" Bore/Shaft, 41/2" Pilot Diameter115/230 VAC 60 Hz (1)230/460 VAC 60 Hz (2)287/575 VAC 60 Hz (3)104/208 VAC 60 Hz (4)190/380 VAC 50 Hz (5)250/500 VAC 50 Hz

48VDC

24VDC12VDC

REPLACEMENT PARTS LIST

3 Ft-Lb

031351

031353

031355

031000

031001

031002031003

031004

031005

031007

031009

031011031006

031008

031010

031012

031013

031014

031369

031371

031373031088

031089

031090

031091

031092

031093

031375

031377

031379

031094

031095031096

031097

031098

031099

6 Ft-Lb

031393

031395

031397

031015

031016031017

031018

031019

031020

031022031024031026

031021031023

031025031027

031028031029

029820

029821

029822

029823

029824

029825

029826

029827

029828

027023

027024

027025

027026

027027

027028

027029

027030

027031

031411

031413

031415

031100

031101

031102

031103

031104

031105

031417

031419

031421031106

031107

031108

031109

031110

031111

Unit Size-Static Torque10 Ft-Lb 15 Ft-Lb 20 Ft-Lb

031435

031437

031439

031030

031031

031032

031033

031034

031035

031037031039

031041031036

031038

031040

031042031060

031061

029829

029830

029831

029832

029833

029834

029835

029836

029837

027032

027033

027034

027035

027036

027037

027038

027039

027040

031453

031455

031457

031112

031113

031114

031115

031116

031117

031459

031461

031463

031118

031119

031120

031121

031122

031123

031477

031479

031481

031043

031044

031045

031046031047

031048

031050

031052

031054

031049

031051

031053

031055

031056

031057

029838

029839

029840

029841

029842

029843

029844

029845

029846

027041

027042

027043

027044

027045

027046

027047

027048

027049

031342031343

031344031124

031125

031126

031127

031128

031129

031495

031497

031499

031130

031131

031132

031133

031134

031135

Notes:

(1) 115/208-230 VAC 50 or 60 Hz, 113/265 VAC 60 Hz, 110-125 VDC.(2) 208-230/460 VAC 50 or 60 Hz, 240/480 VAC 60 Hz, 220/440 VAC 50 Hz, 230 VDC.(3) 287/575 VAC 60 Hz, 300/600 VAC 60 Hz.(4) 104/208 VAC 50 or 60 Hz, 100/200 VAC 60 Hz, 90-95 VDC.(5) 190/380 VAC 50 Hz, 200/400 VAC 60 Hz, 208/416 vAC 50 Hz.

13

031507

031509

031511

031058

031059

031060

031061

031062

031063

031065031067

031069

031064031066

031068031070

031071

031072

029847

029848

029849

029850

029851

029852

029853

029854029855

027050

027051

027052

027053

027054

027055

027056

027057

027058

031345

031346031347

031136

031137

031138

031139031140

031141

031525031527

031529

031142

031143031144

031145

031146

031147

25 Ft-Lb

031537

031539031541

031073

031074

031075

031076

031077031078

031080

031082

031084

031079

031081

031083

031085

031086

031087

029856

029857

029858

029859

029860

029861

029862

029863

029864

027059

027060

027061

027062

027063

027064

027065

027066

027067

031348

031349

031350

031148031149

031150

031151

031152

031153

031555

031557

031559

031154

031155

031156

031157

031158

031159

35 Ft-Lb

032432

032433

032434032435

032436

032437

032438

032439

032440

027068

027069

027070

027071

027072

027073

027074

027075

027076

50 Ft-Lb

032410

032424

032425

032426

032427

032428

032429032430

032431

027077

027078

027079

027080027081

027082

027083

027084

027085

Description

DBSC Housing/Field CupAssemblyDBWC Housing/Field Cup AssemblyDBEC Housing/Field CupAssembly56DBSS Hsg & ShaWHub Assembly (1)

140DBSS Hsg & ShaNHub Assembly (1)56DBWS Hsg & Shaft/Hub Assembly (1)140DBWS Hsg & Shaft/Hub Assembly (1)56DBES Hsg & ShaWHub Assembly (1)140DBES Hsg & Shaft/Hub Assembly (1)Coil/Rectifier Assy (2)

115/230 VAC 60 HZ (3)230/460 VAC 60 Hz (4)287/575 VAC 60 HZ (5)

104/208 VAC 60 HZ (6)190/380 VAC 50 HZ (7)250/500 VAC 50 HZ

48 VDC

24 VDC12 VDC

Clapper Plate

Floating Plate

Pressure Plate (DBSC/DBSS/DBWC/DBEC)Pressure Plate (DBWS/DBES)

Friction Disc (thick)Friction Disc 2 (thin)Wave Spring

DBSC Splined Hub w/ 2 S.S.5/8' bore, Integral Key (Std.)7/8 bore, Integral Key (Std.)5/8- bore, Keyway7/8" bore, Keyway

3/4" bore, Keyway11/8" bore, Integral Key (Std.)

56DBWS/DBES Hub End Plate & Seal

140DBWS/DBES Hub End Plate & Seal

REPLACEMENT PARTS LIST

DBSC/DBSS Pilot Plate w/4 Screws

DBWC/DBWS/DBEC/DBWS Pilot Plate & 0-RingDBSC/DBSS Mounting Bolts & WashersDBWC/DBWS Mounting Bolts & WashersDBEC/DBES Mounting Bolts & WashersDBSC/DBSS Manual Adjust Screw AssemblyDBWC/DBWS Manual Adjust Screw AssemblyDBEC/DBES Manual Adjust Screw AssemblyDBSC/DBSS Man. Release Mech. less levers (8)DBWC/DBWS Man. Release Mech. less levers (8)DBEC/DBES Man. Release Mech. less levers (8)Manual Release Levers

DBSC/DBSS/DBWC/DBWS Lever Mounting ScrewDBEC/DBES Lever Mounting ScrewAdapter Flange (180/140)

3 Ft-Lb

031569

031675

031715

031570

031571

031789

031799

030347

030346

031574

031576

031578

031625

031627

031629

031631

031633

031635

031580

031581

031787

031582

031583

(orange)

031589

031590

031186

031187

031599

032416

031930

031931

031591

031949

031592

031803

031804

031593

031819

031822

031594

031790

031790

031595

031239

031960

024450

6 Ft-Lb

031569

031675

031715

031570

031571

031789

031799

030347

030346

031574

031576

031578

031625

031627

031629

031631

031633

031635

031580

031581

031787

031582

031584

(green)

031589

031590

031186

031187

031599

032416

031930

031931

031591

031949

031592

031803

031804

031593

031819

031822

031795

031665

031665

031595

031239

031960

024450

Unit Size-Static Torque10 Ft-Lb 15 Ft-Lb 20 Ft-Lb 25 Ft-Lb

031569

031675

031715

031570

031571

031789

031799

030347

030346

031575

031577

031579

031626

031628

031630

031632

031634

031636

031580

031581

031787

031582

031585

(blue)

031589

031590

031186

031187

031599

032416

031930

031931

031591

031949

031592

031803

031804

031593

031819

031822

031796

031791

031791

031595

031239

031960

024450

Notes:

(1) Consists of: Housing, Field Cup, Shaft, Hub, Bearing & Retaining Ring.(2) Consists of: Coil, Rectifier, Spring Plate, Flux Busters (if required) & Wire Protector.(3) 115/208-230 VAC 50 or 60 Hz, 113/265 VAC 60 Hz, 110-125 VDC.(4) 208-230/460 VAC 50 or 60 Hz, 240/480 VAC 60 Hz, 220/440 VAC 50 Hz, 230 VDC.(5) 287/575 VAC 60 Hz, 275/556 VAC 60 Hz, 300/600 VAC 60 Hz.(6) 104/208 VAC 50 or 60 Hz, 100/200 VAC 60 Hz, 90-95 VDC.(7) 190/380 VAC 50 Hz, 200/400 VAC 60 Hz, 208/416 vAC 50 Hz.(8) Consists of: Manual Release Shaft, Retaining Ring & Spring.

12

031569

031675

031715

031570

031571

031789

031799

030347

030346

031643

031647

031651

031641

031645

031649

031653

031655

031657

031580

031581

031787

031582

031586

(red)

031589

031590

031186

031187

031599

032416

031930

031931

031591

031949

031592

031803

031804

031593

031819

031822

031796

031791

031791

031595

031239

031960

024450

031258

031699

031927

031259

031260

030343

030342

030345

030344

031644

031648

031652

031642

031646

031650

031654

031656

031658

031580

031581

031787

031582

031587

(yellow)

031589

031590

031186

031187

031599

032416

031930

031931

031591

031949

031592

031803

031804

031593

031819

031822

031796

031791

031791

031595

031239

031960

024450

031258

031699

031927

031259

031260

030343

030342

030345

030344

031644

031648

031652

031642

031646

031650

031654

031656

031658

031580

031581

031787

031582

031588

(white)

031589

031590

031186'

031187

031599

032416

031930

031931

031591

031949

031592

031803

031804

031593

031819

031822

031796

031791

031791

031595

031239

031960

024450

35 R-Lb

032398

031643

031647

031651

031641

031645

031649

031653

031655

031657

032412

032419

032415

031582

032418

031586

(red)

032416

031591

031796

031595

031239

024450

50 Ft-Lb

032411

031644

031648

031652

031642

031646

031650

031654

031656

031658

032412

032419

032415

031582

032418

031588

(white)

032416

031591

031796

031595

031239

024450

i.

j

wired to the incoming DC power source. Note that theseconnections are not polarity sensitive. The two leadwires may also be used to check the coil resistance.

3) GENERAL INSTRUCTIONS:

Each brake has a standard 3/4" threaded conduit connec-tion for use with a conduit box or flexible conduit. Care

should be taken to not screw the conduit connection too 'far into the housing as this may pinch the lead wires.Use jam nut to secure the conduit, without pinching the 'wires.

An opening is provided in the brake housing to makewiring connections if a conduit box or flexible conduit is not used. Remove the (2) cover plate screws as well asthe plate. Route brake and motor leads through thebrake housing. Cut off excess wire lengths and makeproper wiring connections. Coil and route wires back intothe brake housing. Replace cover plate.

4) SPECIAL WIRING INSTRUCTIONS:

Consult the chart below when making brake connectionsto standard Reliance Electric motors.

Motor

3-Phase

Dual

Voltage

2-Phase

Dual

Voltage

1-Phase

Dual

Voltage

SeparatelyConnected

Brake

STANDARD BRAKE CONNECTIONS

FOR RELIANCE ELECTRIC MOTORS

Volts

Low

High

Low

High

Low

High

Low

High

Connect

81 - Tl &T7

82-T2&TB

83 & 85 - Insulate

84 - Insulate

Bl & 85 - Tl

83 -1- Insulate

84 - Insulate ,82-T2

81 - Tl &T7

82-T3&TS

83 & 85 - Insulate

84 - Insulate

81 & 85 - Tl

83 - Insulate

84 - Insulate

82 - T3

81 - Tl & T3

82-T2&*4

83 & 85 - insulale

84 - Insulate

Bl & 85 - Tl

83 - Insulate

84 - Insulate

82-T4

Bl - Ll

82-1-2

83 & 85 - Insulate

84 - Insulate

Bl & 85 - Ll83 - Insulate

84 - Insulate

82 - L.2 '

Notes:

1) Check compatability of motor and brake voltages withpower supply.

2) Insulate means: tie together (or alone) and cap off.For example: 83 & 85 insulate means 83

EE> Cap off & insulate84 insulate means M-Capoff & insulate

5

Consult the chart below when making brake connectionsto Reliance Electric thermally protected motors.

BRAKE CONNECTIONS FOR RELIANCE ELECTRICSINGLE PHASE THERMALLY PROTECTED MOTORS

USING 115/230 VAC BRAKE COIL

Volts

(Motor)Motor Connect

'81 -P2

1 -Phase High 82-T2-T)-TBDual (230) 83 -1 85 Insulate TogetherVoltage 84 - Insulate Alone

81 - T3 - T8 - P2

1 -Phase Low 82-T2-T4-TS-1-2

Dual (115) 83 - 85 Insulate TogetherVoltage 84 - Insulate Alone

81-85 -Tl-TB

1 -Phase High 82 -T4 -TS- l-2

Single (230) 83 - Insulate Alone

Voltage 84 - Insulate Alone

81 - Tl - T8

1-Phase Low 82-T4-TS-L2

Single (115) 83 - 85 Insulate Together

Voltage 84 - Insulate.Alone

Note:

1) Use existing motor connection decal and connectbrake per above.

.

BRAKE CONNECTIONS FOR RELIANCE ELECTRIC .THREE PHASE THERMALLY PROTECTED MOTORS

USING 133/266 VAC BRAKE COIL .

Motor Volts (Motor) Connection

81 - Tl - Ll

3-Phase High 82-T4-T7

Dual (460) 83 - 85 Insulate TogetherVoltage 84 - Insulate Alone

Bl-Tl-T7-Ll

3-Phase Low 82-T4-P4

Dual (230) 83 - 85 Insulate TogetherVoltage 84 - Insulate Alone

Notes:

1) Use existing motor connection decal and connectbrake per above using special 133/266 volt brakecoil.

2) Three-phase thermally protected single voltage - nostandard connection available.

5) ALTERNATE SWITCHING METHODS

To obtain faster stop times, alternate switchingmethods can be used. Consult DODGE.

Coil VoltageLow/High

115/230 VAC (1)230/460 VAC (2)287/575 VAC (3)104/208 VAC (4)190/380 VAC (5)250/500 VAC (6)

48 VDC24 VDC12 VDC

BRAKE COIL DATA: CURRENT/RESISTANCE

RATINGS (see notes below)

Current

Draw (A)

0.19

0.10

0.09

0.24

0.13

0.10

0.48

0.97

1.95

3 & 6 Ft.-Lb.

Resistance (8)(Ohms)

562

2078

2987

384

1341

2336

100

24.7

6.2

Current

Draw (A)

0.28

0.14

0.12

0.31

0.19

0.13

0.58

1.14

2.24

10 - 50 Ft.-Lb.

Resistance (8)(Ohms)

387

1550

2245

290

923

1793

82

21.7

5.4

Notes:

Other nameplate voltage capabilities:1) 115/208-230 VAC 50 or 60 Hz, 133/265 VAC 60 Hz, 110-125 VDC2) 208-230/460 VAC 50 or 60 Hz, 240/480 VAC 60 Hz, 220/440 VAC 50 Hz, 230 VDC3) 237/575 VAC 60 Hz, 275/550 VAC 60 Hz, 300/600 VAC 60 Hz4) 104/208 VAC 50 or 60 Hz, 100/200 VAC 60 Hz, 90-95 VDC5) 190/380 VAC 50 or 60 Hz, 200/400 VAC 60 Hz, 208/41 6 VAC 50 Hz6) 250/500 VAC 50 or 60 Hz7) Values for other nameplate voltages will vary. Consult DODGE Engineering for actual values.8) Coil resistance is measured between leads 84 and 85. Measured resistance may vary *7112% from nominal values.

MANUAL RELEASE OPERATION:

WARNING

Do not manually release brake before blocking over-hauling loads to prevent unexpected machine move-ment. Failure to observe this precaution could resultin bodily injury.

The manual release levers are located on the back of

the brake opposite the input hub for the single C-facemodels (see Diagram B). On the double C-face modelsthey are located on the output shaft side.

If it is necessary to manually release the brake, simulta-neously turn the (2) levers counterclockwise (CCW),approximately 90 degrees to their stop positions. Themanual release levers will reset automatically the nexttime the brake is energized. Note: They may also bemoved into the reset position manually.

DIAGRAM B

Single C-Face

MANUAL

RELEASE

LEVERS

Double C-Face

6

MAINTENANCE GUIDE

(See Reference Sheet Drawings - pages 9-11)

DANGER -

This equipment is at line voltage when AC power isconnected. Disconnect and lock out all ungroundedconductors of the AC power line. Failure to observethese precautions could result in severe bodily injuryor loss of life.

WARNING

Do not manually release brake before blocking over-hauling loads to prevent unexpected machine move-ment. Failure to observe this precaution could resultin bodily injury.

1. TASK: Wear Adjustment.

PROCEDURE:

Note: New brakes DO NOT require wear adjustment.If new brake appears to coast more than desired, seetroubleshooting guide, Step 1.

Adjustment of the air gap is necessary if either or bothof the following conditions are observed:

1) A decrease in braking torque. Adjustment is recom-mended when braking torque drops to approxi-mately 80% of its static rating.

2) Complete lack of disengagement (dragging), ormotor stalled.

STEP 1. Before attempting any adjustment to the brake,be sure the power is turned off and there is no possibilityof motor start-up. The brake must be de-energizedbefore attempting wear adjustment.

STEP 2. Turn the 3 smaller hex head bolts clockwise

(CW) progressively to 50 lb.-in. For 35 and 50 lb.-ft.

5-

A

•cZET# A 1*[,FORMUTIC»4

CAD4894

A

0

*]RE EGRESS PLATE

55rr': BOLTS

(43 WASHERS

Sjo£,sr

BRAKE HOUSWG®/ -

REFERENCE SHEET DRAWINGS

(Also Use for Replacement Parts)

Wro-

SPLINE HUB WITHUGECRAL KEY

DBWC/DBEC Model

SPR:NG PLATE

WAVE SPRING

,-*CUFFERFmCTION DISC

PRESSURE PLATE

B

0

0

--* KEY

0

li 102 UNC

LOCK NUT

Am (6) LEK WIRCS (#PPROX. WV LOING)

- LEAD WIRE RETAINER

21#/a//sn/o"1/4-28 x 2-3/4

(3) FLUX BUSTER

SECTION A-A

El , Lo=° -© 12) M,NUAL ROIASE SH•n

(2) SOCKEr HGO NP SCREW ®JSECTION C-C

DBWS/DBES Model

US-16 X 4

(4) *ASHERS

Coll/RECTIFIER ASSEMBLY

RETNING raINGRETAINING RING

62 i-*:,O \2 - -4

CAD4895

0

1/4-28 X 2-3/4

SHuff/SPUNC ASSEMBLY {IH

MU BUJUNG ®- (2) RELEASE KNOBS

BRAKE HOUSING

(2) SOCKET HEAD CAP SCREW

C SPRING PLATE

#VE SPRING

CUPPER

FRICT)ON DISC

B

SECTION B-B

- 0 Wic

RAU'rER LOCK NUT

SECTION A-A

0' ---© (:;,45:D nREONG,--

LED IRC RET/NER

/ 1 1 \ \>© RETAINING RIC\ L© SPR;NG

SECTION C-C

11

SECTION B-B

1

F -2.57--

SEC-nON B-B

A

- 4.30 MAX |

WITH MANUAL RELEASELEVERS ENGAGED

0

(5) LEAD WIRES

REFERENCE SHEET DRAWINGS

(Also Use for Replacement Parts)

35-50 lb-ft DBSC

3/4· NPT THREADED HOLEFOR CONDUIT FITTING.

.50 DIA LEAD HOLDLOCATED AS SHOWN

ON A 5.62 DIA 3.C- 3.71 HA-

LEAD VIRE ACCESS COVER -3.36-

- CLAPPER PLATE

' /- FLOATING PLATEBOLT CIRCLE. ' - STATIONARY PLATE

SPL I NE HUB- 1*6%ME

INTEGIRAL KEY 6.92rs/8 MAX

DIA

--- --1 -2 - ; PILOT DIA4.5014.509

BRAKE HOUS ING --/ YBil"BTIZIM ADJUSTING-0'BOLT HEADLOCKS -X-mAKE DISCS

\ SECTION A-A4.30 MA- \

L- PART NUMBER LABEL AND]CONNECTION INFORMATION

LOCATED AS SHOWN

L <3) AIRGAP ADJUSTMENT SCREWS1/2 HEX HEAD 120· APART

848 BOUS

DBSS Model

0, (41 ·,445}ERS

ACOIL/RECTFIER ASEISLY

RETANING RING

RETAB#40 RING

SE X - rrIFrV-' :..

SA#Fr/SPUNE ASSEMBLY d>' BALL BEARING ®J |

(2) RELEASE KNODS0

BRAKE HOUSING

x 2-3/4

CAD4656

SPRING PLATE

AVE SPEM#G

Ct/PPERFRICION DISC

0B

0

0

OPT[ONAL

180/210 ADAPTER

20·- CONDUIT HOLELOCATION

<2) 1/4-20 UNCSET SCREWS

67.5- APART

0

0

N LEAD WIRES (APPROX, 10' LING)

KEY

C

0

m 7<142 UNC

8YUF LOCK NUT

SECT ON A-A

3/r WT n·REACED HOLE -1 7

04 OpnON*L CONDUF FrTT,He

\>-(p RETANIB RI,G

(2) SOCKET HOO CAP - \ HS) SPRNG\-© (z) IwiuAL RaBSE SMFT CIZESSECTION C-C SECTION B-B

10

C

models, first loosen bolt head locks. (Caution: Theselocks must be reinstalled after adjustment.) DO NOTOVERTIGHTEN. Then turn each of the bolts back

counter clockwise (CCW) 1/2 of a full turn (180 degrees).If more than one full tum is required, see troubleshootingguide, Step 2. This resets the air gap to the properamount. Tum power back on and check for normal operation.

If adjustment intervals become more frequent, brake fric-tion disc may be nearing the end of its normal life; seereplacement procedure.

2. TASK: Friction Disc Replacement.PROCEDURE:

Note: The new friction disc/discs must be clean and

free of any grease, oil or other contaminants whichmight result in a loss of torque. Block load, if required.

1) Disconnectand lock out all electrical power to themotor and brake.

2) Remove brake from motor.

3) a. For standard models, remove pilot plate onbrake input by removing the four (4) #6-32 panhead screws.

b. For sealed models (Washdown & E-Z KLEEN),remove pilot plate by gently and uniformly pullingthru bore of lip seal. Pilot plate is held in position byan O.D. '0-ring' seal and,the '0-ring' seals on themounting bolts.

4) Alternately turn counterclockwise (CCW) but do notcompletely remove the (3) manual adjustment boltsuntil the pressure plate is free and can be removedfrom the brake assembly. It is important to alter-nately tum these bolts so as not to cock the pres-sure plate. No more than 1-2 revolutions per bolt,then move to the next bolt. Continue until the plateis free.

5) After pressure plate is out, remove the old frictiondisc. For double disc units, remove disc 1, floatingplate and disc 2. Replace both discs and inspectfloating plate. At this time use dry, filtered com-pressed air to blow out any loose wear particles

i and visually inspect the steel wear surfaces of boththe clapper and pressure plates.

6) Place the new friction disc onto the clapper platewith the 3" diameter boss facing up, away from theclapper. For double disc units, install thinner disconto clapper plate, followed by floating plate andthicker disc. Friction discs on double disc unit

should be installed with 3" diameter boss facing up,away from clapper.

7) Reassemble brake following the BRAKEREASSEMBLY PROCEDURE beginning at step 8.

3. TASK: Manual Release Adjustment.

PROCEDURE:

The manual release levers need adjusting if:

1) Levers will not stay in the brake released position(i.e., 90 degrees from housing).

2) Levers will not rotate back to the full engage posi-tion when the brake is energized.

7

For Condition (1): With power to the brake off, manu-ally hold the lever out (90 degrees from the housing)and insert a 7/64 hex key into the hex-head cap screwin the release lever. Slowly turn clockwise (CW) untilthe lever will maintain this position by itself. Repeatthis procedure for the other lever. Rotate both leverssimultaneously to the brake released position; theyshould maintain this position. If not, repeat the proce-dure. Next, supply power to the brake. The leversshould snap back to their original position.

For Condition (2): Start with the levers in the brakereleased position. With power supplied to the brakeinsert a 7/64 hex key into the hex-head cap screw inthe release lever. Slowly turn counterclockwise(CCW) until the lever snaps back to the housing.Repeat this procedure with the other lever. To test,with power off to the brake, use the manual releaselevers to release the brake. Supply power to the brakeand both levers should snap back to the housing. Ifnot, repeat procedure.

4. TASK: Coil Replacement.

PROCEDURE:

1) Follow steps 1 through 5 outlined under FRICTIONDISC REPLACEMENT.

2) Place tile unit open end up and press down contin-ually on the clapper plate in order to release thespring force from the manual release mechanism.This pressure should be maintained until step 5.

3) Unscrew the (2) socket head cap screws which arerecessed in the manual release knobs. Lift out the

manual release shaft/return spring/retaining ringassembly.

4) Remove clapper plate and wave spring.

5) Remove the aluminum spring plate and (3) brass"flux busters." The flux busters should be secured

to the aluminum spring plate using RTV sealant(flux busters are used on 3, 6 and 10 ft-lb unitsonly). It may be necessary to turn the brake overwith the open end down and gently tap the brakehousing on a clean flat surface to remove thespring plate. -

6) Remove the old coil from the brake housing. It maybe necessary to apply a prying force in order toremove the old coil as it was installed using severaldrops of RTV sealant to keep the coil positioned.Care should be taken not to scratch the machined

surface of the field cup.

7) Using dry, filtered compressed air blow out housingto remove loose wear particles.

8) Reassemble brake following the BRAKEREASSEMBLY PROCEDURE beginning at step 1.

5. TASK: Brake Reassembly.PROCEDURE:

This procedure begins with an empty housing to com-pletely rebuild the brake. Care should be taken toensure that work is started with the proper stepdepending on the procedures being performed.

1 ) Place (3) small drops of RTV silicon in the bottomof the field cup to secure the coil in the housing.

./

2) After first feeding the (5) lead wires through theegress hole in the field cup, insert the coil into thehousing. The side with the notch in the flange ofthe coil bobbin goes down inside the housing. Donot force coil into the housing as this may causedamage. The top flange of the coil must sit belowthe counterbore in the field cup.

3) Place the aluminum spring plate on top of the coilaligning the (3) brass "flux busters" in the smallnotches in the O.D. The "flux busters" should be

attached to the spring plate with RTV approximate-ly 120 degrees apart. "Flux busters" are notrequired for use in 15 thru 50 ft.-lbs. units.

4) Place wave spring on top of aluminum spring plate.Wave springs are painted on the edge with differ-ent colors corresponding to different torque ratingsas follows:

Orange = 3 ft-lb Red = 15 ft-lb & 35 ft-lb

Green = 6 ft-lb Yellow = 20 ft-lb

Blue = 10 ft-lb White = 25 ft-lb & 50 ft-lb

5) Place clapper plate on top of wave spring.

6) Place the new friction disc onto the clapper platewith the 3" diameter boss facing up, away from theclapper. For double disc units, install thinner disconto clapper plate, followed by floating plate andthicker disc. Friction discs on double disc unit

should be installed with 3" diameter boss facing up,away from clapper.

7) Place the pressure plate back into the housingmaking sure the pressure plate ears do not coverthe manual release mechanism access holes.

Alternately tighten the (3) manual adjustment boltsmaking sure the 3" diameter boss on the frictiondisc pilots into the bore of the pressure plate. It isimportant to tighten the bolts no more than 1-2 rev-olutions per bolt before moving to the next bolt toavoid cocking the pressure plate. Continue to tight-en until the pressure plate is pulled all the waydown. Do not attempt to over tighten as this maydamage the plate.

8) Replace the manual release shaft assembly intothe brake housing through the open end of thehousing. Ensure that the flange on the manual

8

release shaft seats against the clapper plate. Thetang end of the torsional spring should rest on top

of the cast boss inside the housing. Insert ascrewdriver into the slot in the manual release

shaft next to the torsional spring. Rotate the shaftclockwise (CW) approximately 20 degrees andinsert the manual release lever into the slot in the

other end (protruding through the brake housing)of the manual release shaft. Install the #6 socket

head cap screw to attach the lever to the shaft.Snug, but do not overtighten, the cap screw witha 7/64 hex key.

Back off the (3) manual adjustment bolts 1/2 turn(180 degrees).

9) Follow instructions in MANUAL RELEASEADJUSTMENT PROCEDURE to set the manual

release.

10) Follow instructions in WEAR ADJUSTMENTPROCEDURE to reset air gaps.

6. TASK: Hi-pot Coil Testing.

CAUTION

If Hi-pot testing the brake coil, take care to increasethe voltage slowly (see Troubleshooting Guide forprocedure details). Instantaneous exposure to highvoltages may damage the internal rectifier.

PROCEDURE:

All coils are 100% Hi-pot tested at the factory, afteradsembly in the brake.

Hi-pot test between the red (85) lead and the brakehousing. AC voltage must be raised slowly (a mini-mum of 1 second) from 0 volts to 1500 volts. Holdvoltage at 1500 volts for a maximum of one secondthen slowly decrease to 0 volts. Make sure all otherleads are capped off or otherwise isolated from con-tact with personnel or equipment. Note: The Hi-pottester used must have a variable rheostat control in

order to raise and lower the voltage as slowly as pos-sible (over a minimum of 1 second). Slowly turningthe rheostat will help prevent damaging the diode orrectifier in the circuit.

TROUBLESHOOTING GUIDE

(See Reference Sheet Drawings-pages 9-11)

DANGER

Subsequent steps require rotating parts and/or electrical circuits to be exposed. Stay clear if unit must be running ordisconnect and lock out or tag power source if contact must be made. Failure to observe these precautions couldresult in severe bodily injury or loss of life.

SYMPTOM

1) Loss of Torque

(Coasting)

2) Brake Not Releasing

3) Motor. Stalled

4) High Housing Temperature

80°C (176'F) Maximum

.Er

A

e

Mal# -1

CAD4655

POSSIBLE CAUSE(S)

Improper Switching Method

Brake Disc Worn

Brake Too Small

Excessive Cycle Rate(Disc Too Hot/Torque Fade)Friction Surfaces Contaminated

Brake Worn Out (Frequent Adjustment)

Open Circuit(Brake Wires Pinched or Broken)(Open Coil)

Improper or No Voltage to Brake

Requires Adjustment

Manual Release Out of Adjustment

Brake Not Releasing

Excessive Cycle Rate

'High Ambient Temperature

Excessive Load Inertia

Brake Not Releasing

ERE EGRESS PUTE

ses

(4) ¥SHERS

SOLUTION

If new brake appears to coast farther then desired,an alternate switching method may be required,such as fast response circuit. Consult DODGE.

See Wear Adjustment Procedure -Maintenance Guide

Check Application

Reduce Cycle Rate & CheckApplication

Replace Friction Disc - Maintenance Guide

Replace Friction Disc - Maintenance GuideCheck Resistance Between Brake

Leads (84 & E35) for Continuity

Establish Proper Voltage. If input voltage is okay,check for DC voltage across leads 84 & 85. H novoltage exists, rectifier may be blown. Replace coilor use rectifier replacement kit.

See Wear Adjustment Procedure -Maintenance Guide

See Manual Release Adjustment ProcedureMaintenance Guide

(See Symptom 2)

Reduce Cycle Rate

Reduce Cycle Rate and/or Load Inertia (AddExternal Cooling Fan)Reduce Load Inertia

See symptom 2

REFERENCE SHEET DRAWINGS

(Also Use for Replacement Parts)

#SS[kaly

-rz,wm,

MAKE HOJS,B

A -1/4-28 X 2-3/4

3-25 lb-ft DBSC

1

4

LOCK PUT

9

SPRING PLATZ

WA'•t SP*540

CPPER 2FRICTION DiSC

MASSURC PLATE

0

95

(5) LEAD W'RES BPPROX 1(r LONG)

(4) PILOT PLATE SCRCIS

0 0 5 '41*C

B

(I)-®KEY

CNC

0

(3) FLUX BUSIER

SECTION A-A

- "/0 #6fc;:;:T'-94

\-© LEAOW, RETA,NER

(21 SOCKET le[ CV SCREW 04SECTION C-C SECTION BrB

U

HP.

5MttAbY CLEANil Sfi

CLASS 1.00 It&*,T• 4· TYPE IMTR

IFR

086912-08-A-602437=04=A-0791-5-6-0-6-ZN-

0791-58=12=D---08691-4--1-0-A-

r-1--r--4-

1

RENEWAL PARTS SECURITY LIST

CUSTOMER

DODGE NEWARK

[691602UU-03-ASSY. Al

SIZE

ASSY.MTO Al

8888 SIZERS· PAe,vul -06-AFINISH

RED'GEAH PRESS /. 33MOTOR

ASRUCTION63125

PARTNUMBER

*****r 11\[AL

EZ=CASE- ·'-DES

0791-09*05-F-0791-47=03=K-4-1-1-623-02-E-421-623=02=W -4-1-1-623-03-CA-41-1-623=03=CC-4-1-1-625-16-G-41-1-626-06-G -41-1-627=02-EX-41-1-637-02-BH-4-1-1-6-42-40--B-41-1'647-05-H -41-1-688-*12-8-4-1-1-693-80-AF-4-1-1-709-89-A-41-1-720-02-D -4-1-1723-06-8 -41-51-04-37-F -521-55 -53292-58101

602452--02-C--

4-1-1-642*4-1-A»r

-MI-!m./..P,0

-r-r-1-

-r-1-

-2

-r-r

-1-

-2-2

-1-

-1--1--4

-1

88

.-i

-

IMPORTANT - DO NOT DESTROY

1

,ENT. GOODSNO33664700011 FINISHEDorr, ,RIALpur MX.

REAS 9.3 1 1Y; 1750 S/F CLASS Iwit. 15 QUE 2594

IHPTORQUE

1 ?80'ROL |TROLTORQUE PHASEPA001-OV-A

CONTROLIGEAR

MtN,

4749991Fiall SIZE

VOLTS

PHASE HERTZ

HERTZLUBE63125

1 MY

CONTROL ASSYCASDAEOUCER

DESCRIPTION

ir I lu[\is*****I

PICKED PARTS

-3-GEARCASE

-3-OUTPUT-SHAFT- 62- _- · 2-DGV-1-7-GEAR-570-66-X-SY-DGVT-1-7-P-IN-5:06-YZ-SHAFZ4 C FACE -ADPTR-1-80721-072

-PAINT-MASK-1807210725OT--APG-3-BALL-BRG -6306--r-SHIM.006-

-3-BEAR-ING-SHIM

-3-BEAR INGZSHIM -BRG-CLAMP

-CUP-REF41-1-626=01==WEADrA--DBC-CPSEAL-HARWAE38XGOX-

-5-RET-RING--5100=255---Z-APG-BOLT-PACK-1-BOTC728OT-SQ-HD-PEG-

-HDKEY:25-SQ-X:81-0-EG--5-SPIROL-PIN-311-6-IXT--51---NP. ADHESIVE-MOB-IC-SHC-634-OIC ..-TIETCABCE-APG-"C-"FACE--SOFT-KEY-1-/4-X-2

-PLUG - 172"SOCKHD--BRASS-RED-BUS-3/8-=-178--ZERK-FITTING-1-6-1-0-BE-

-2TMETRICISOC-HD-SCREW-*-*-*-L-INE-P

-KITT-INST-MANUAL-AP G----

24E7079163-63-

1=TEASY CLEAN

ImHZ PH. IMPMVOLTS

I mr |MENT VOLTS

42. 01 1 gEss,

HF

1 =1:

5.55 1 PALNT

CONST DISC ASSY./GAOUP

1

ORDER NO.

Igesr

EL

3566470001 RE184DM3A

**, BORE

ENCL

IENCL

lag 30657

CARTON

TEST

2NCL

1 EAZE EZ

TACH*IT

602297-71-BPART NUMBER · DESCRIPTION

./Ill./...Il,Ir

-079201-01-D--0791-56=04-ADZZ-0791-57=-0-4-A-F

-08691-1-065*--079-1-47-62-CS

-0791-47t03-CT--41-1-622-09-D-.-4-1-1-623-02=R-41-1-623-02-X--74-1-1-623-03-CB

-41-1-623-03-CD--4-1-1-626-05-AY-41-1-627--01-n-CFZZ-41-1-632-0-1--AD-41-1-642-37-AD--4-1-1-647=-05=B-411-649-06-A---41-1-688-12-V

-4-1-1-709-6-5=H.-411715-05-B-41-172306-A--4-15-1-0-1-=1-6-M-4-4P01.- L_ --' 1-531-1-4

-55025-Z-Z-Z-=-602452-01-A-602452=02=F-ARTS-***DMR070-

IDODGE-MASTER-REEVES

RENEWAL PARTS|$HEETNO, 1 OF 11 1 UMiGiNAL

-1-=1*

1

If

-5-INPOT-SAAFT 184-TC-IRMCI21=GEARIC-864.3.F-RMC 21 PIN 1.84 .78SH

33-0-OTPUTICONER---APG BALL BRG 6213Z

-AP-G-BACLB-R-G-6-368ZZ-/5-C-3-SPACERT -SHIR .OOB

ISBIMI002* 1 --12.__L__L_-_3 BEARING SHIM

-3IBEARING-SAIM-3 BEAR-ING CORE 09081-2-A5ZSGLE-LIP-SEAL-CR-2617-

-3 PC-A-IN-WA-SFIER-FIARDENED-RISER-BLOCK--KIT-SIZE-32OCPLUG 53114

178=27-HEX=HDZPCOG--ADKEY .1-88 SQ *-7630

ROCE-PL-WWEI;31 ---665=N--4-DOWEL P-IN 3/8 X . 882TIET-CABLE-APG C-"FACEZZ-5-CL-COLLAR-C[328-FNAMEPCATET-P-IN-_SQHDPEUG

LSOFT-KE_Y-174-SQ-X-717-374-5-METRIC HD-SCREW3IMETR-I-CISOCIRD-I-SCREWZZ

-1-

Lf--

-r-1-2-r-1-

1-r2-r-r2

-r

--

2

-r12r

r

r

-APG-ZINSTRUCTIONITAG--..

SAVEIMPORTANT INFORMATION

The information on this form provides a record of part numbersfor the component parts of this product. Retain this information forfuture reference and parts ordering.For 'downtime protection' and routine servicing, call your nearestReliance Electric Parts Distributor and secure the spare parts thathe recommends you have on hand.

1 1 |DATE 06/01/97 14:23: 05

=n

/6

RENEWAL PARTS

CONTACT YOUR NEAREST RELIANCE PARTS DISTRIBUTOR IN THE YELLOW PAGES UNDER THE

HEADINGS SPEED REDUCERS, POWER TRANSMISSION EQUIPMENT, OR VARIABLE SPEED DRIVES.

r„ OR

CONTACT DODGE-MASTER-REEVES RENEWAL PARTS QUOTATIONS, FOR ASSISTANCEAT PHONE NUMBER 1-803-297-4160. IDENTIFICATION NUMBER FROM UNIT i·NAMEPLATE WILL BE REQUIRED FOR PARTS ASSISTANCE.r' ,

SERVICE ENGINEERS5 0 -L

FOR RATES AND AVAILABILITY OF SERVICES CALL 1-812-378-2416.

AFTER HOURS EMERGENCY SERVICE

- Parts in stock are available.for shipment 24 hours a day, 365 days a year for your' BREAKDOWN requiremsnts(A specim handling charge is Made to assure sameday shipment on EgEOSENCY BREAKDOWN : orders for*arts in stock not

c jequiring assembly. ·-,_:f;1 Gr

-3.7 1 -T U 3.3 r , J , : ,

CONTACT<-YppyNEAREST PARTS DIS¥RIBUTOR FIRST

c 0-6"-E - -.

*, . :,, , Dodge/MasteiP*Is (If Part No. Is Known) ..... 502-839-7233

- (Workdays:,only uAtil 12:00'P.M. - - Weekends-and Halidays,'f. call 606-281 -5996.. E ·; 1 '

Dgdge/Master) Parts (H ,PArt Ng. UnknoWn) 7.-..9?803-297-4800r , Y.-A. : 4

Reeves Parts...·..6.'.:f):*.r, ':0,...., fl :f,: ..8036297-4800 '''-4 6:'i '13

DODGE = MASTER . REEVESRENEWAL PARTS' "1

J ., t.,

A

[RE) [Ed][E@Ell)8(REIFTE[lig

@1-El0= A 0

L

10 3/8\

-

4 1/2 1

0

9 5/8 -- 4 4

1/8 N.PA. TYP.

Krl_

ds==5

RETAINER WITH 1TRICLOVER NECK

16

10.550 0

80

BV-02-8

8 0

Ih

11,550 0

4

5 1/8

i

LANGE NECK

1.500

t - QUICK DISCONNECT TLAMP

- QUICK DISASSEMBLE CLAMP

1 2

THIS DOCUMENT AND THE INFORMATION CONTAINEDTHEREIN IS THE EXCLUSIVE PROPERTY OF METOCORP. AND IS NOT TO BE REPRODUCED OR USEDBY OTHERS WITHOUT WRITTEN CONSENT BY METOCORP. AND IS NOT TO BE USED IN ANY WAYDETRIMENTAL TO METO CORP.

MEE--I

.CORP.

PROJECT

CAPACITY

N/A

MATERIAL

304 S.S.

Q 9 Q% . /1-«\5/1)iPM

ALLENDALE, NEW JERSEY, U,S.A. 07401

DRAWN r nPAUL 0 ABBE INC.

Appi, H.H,T[TLE

BV-02-FN-RT(4875)-P-8'BUTTERFLY VALVE

ANISH DATE SCALE DRAWING NUMBERPHARMA.GRADE 5/22/97 3'=1' A-6586-1

MET

L_

F

TU.S.A.

REV.

.

.

.

TECHNICAL

REFERENCE

MANUAL

Reference No. - 424306

PRODUCED FOR

PAUL O. ABBE INC.JOB NO.: A46665

August 15, 1997

2 00

4

::r'

8CO

0U

EC000370

11k

.

I..

EY' i

l21 lilITEM

2

3

4

5

6

7

8

,0

12

13

14

15

;;M

t9

20

21

22

r

/IT@

DES*PDON

30' X 24 X 8- N£MA 41 0405URE

30 WP FUSED DISCONNECT

ENGI PRESEr RUER

ALLUUU SUR; RS<TRN-GWI

EX}40EO STOP FOSHeurro, - RED

Tpm =-*- *EMERGENCY STOP PUSHBUTIONSP-500 5 HP DRIE

' SFArl. FUSOfem%'trn:17'£011Rl IM

S;; SRZr3¢0 yA CONTROL mANS*miER

il{RU TERWINAL

&611*'icCUBJ BASE 110UNMNG *07

Cue M INIATURE TUER 1/ BATERY

PART NUIBIR

141459<8

19 IR- N,mOPJ,IRI

LIET-10-N

JSUIC]05

*530*520

FLO-l

FLO-2 1/2FL>10

CS*-40£-120

P m fl-E

MY#N- 115

T.2-81200

%'LU-4

19.11&221-02

LP--30

BNKS<00'0

OUgT110

60*Tlryl

1

1

1

2

2

1

3

3

15

2

\6

r- TE .

7,-

EE

ZOO YA mANSFID/[R40/ V0RIB.. 5[Z....

-t-'.74%0,1.7 '1..:RUN mECOUNTER

RMI CONTROL ZAY

@

L_5.14%-"-91- -Ar - --fl'-,BLE (XM= OW„TETS.

2,1£/T me

.

i.i.-i----.i- ,

m,IL, IA2 W,

urn 'fm *m

S..2P 'rt,5 H0 -

0 -:

: 93 DE

-UT

EE#

]

NXI ILIAN,r Sl/,Lr CO. rK Gle 4,4306

PAUL O. ABBE INC.

.r.."'..*-554:"."St'n.,4,-,1 nUOR CANIC INC

EESSRAN | --- |03/.ul/07|NONe| AICIoa

rl E- CK:.076 1 4 „,#-- 1 1 OF 2

1

OFF ON

30 A,F

460V «-[EE LJ3 PHASE .-4-17611 L2

30 AMP .1.-<20 LlLl L2

Fl R

1 WF 1 AMP

300 VA TRANSFORM

r-'immL-1 460V PRIMARY/115V_3!_1 N21/2 AMP

<Gl N

£-STOP STOP SIART

12IT 03 A tecilf ® N

1CR-2 TIMER-1

1-11-5-1 A L RED UON -N

CUBJT110

C 1 opNr-L.[sc 6 N

<2CR 0

1 .7 N(BR 1 0

1 ICR-lA C 11

1 1(R-,8 9 2(R-1 12 Nf J.f Fifk- \Ir- - -

1

11 *CR-3 10

788-1

TBA-3

104-4

RED UON

LIBT1000

6-1

180-2

TBB-3

ma-4

Taa--5

TO CA-, LA,CH CRCT

---=eD To CRl-, LATOf (RCT

N

ER

SECONDARY

RUN UGHT

RUN CONTROL RELAY

RUN 1-IME COUNTER

VALVE CONTROL RELAY

BRAKE CONTROL RELAY

10 NAP

Erp

L32

L22

Ll 2

2 VALVE CONTROL CONTACTS

PRESET TIMER

n

L12 L22

n

O /

L32

R/Ll S/L2 T/L3

S

P

5

0

0

STOPe

START 7

COMM ii

U/Tl V/T2 W/T3

UVW

BRAKE

18

8

1C

8

4

3

2

12

13

14

9

10

LiET liT IT

f MOTOR \< BRAKE 1

1 TURN

P3\ 1 POTENT.

20

1CR-4

O IHIJnG

21

PROGRAM PARAMETERS

MODIFIED FROM FACTORY

DEFAULT

F-00 -> "1"F-01 -> "15.0"

F-03 -> "0.5"

RE

U

EDCCO375

5 a

TD

2

4

5

.

\1 u 1 11-WN£

Il W.

- 100'

C€5¢MMPnCN

tr K 10, / 8. 1/'MA 4* D/"Fl

BUU¢MEAD UMKIN

rt-/RORATCR

UJOQUAR

0-160 P....

SCLENCO ¥,4

3 Pli COP#!ECTOR

1,1*PHa,K

3180,6&06

1.&BIlli

1$30¢>do

C31HS¢561*P5293Zss

OIJAMmt.

/

FH-1

E

0

0

V

.

1*

9 Ll J11

L__3

3

5

4

3

1-

0

0

6,7

EXMAUST 0.11PUT

WLE NlPUT

.

1-1.-i --- 1 -. 1

noxi NETARK =p,tr 00, n=. Z= 44*OU

PAUL O. ABBE INC.

PNCWZ: 1-100-61'41;* n.t ?MO *0-N[f

.--,1 FLOOR DANEl INC

.AINCEN BOX, PNEUIJATIC CONTROLS

INEMA 4 480//3PH/66HZ54' ROTI-CONE BLENDER

RAN | --- |03/WN|NONC|I4686I

*-1-"' E-00-0676 ' 1.-T I.fo- -

.

.

CO

En

Enclosure

Disconnect

Start Switch

Stop Switch

Jog Switch

Speed Potentiometer

Discharge switch

ELECTICAL UNIT SPECIFICATIONS

The AC Drive, control transformer, relays, fuses and internaltimer are housed in a NEMA 4X Stainless Steel Enclosure.

Terminals are provided for field termination's.

07/02/97

A NEMA 4X, through the door, fused disconnect is providedfor main input power cut-ofF. The unit utilizes Class J fuses andhas lockout capability.

A NEMA 4X rated illuminated push-button is used for the "Start"switch. Pressing this button energizes the coils on the run controlrelays. This starts the timers and the drive.

The light inside the switch illuminates while the relays areengaged.

A NEMA 4X rated push-button is used for the «Stop" switch.Pressing this button de-energizes the coils on the run control

relays and initiates a stop on the drive.

The light in the 'Start" switch also goes offwhen this button isdepressed.

A momentary pushbutton used to engage the drive and release thebrake. The drive will continue to accelerate to full speed whilethe button is being pressed. The jog button does not activate thetimers.

A Single turn trim potentiometer is provided for setting themaximum speed ofthe main drive.

Opens or closes the main discharge valve by energizing the valverelay.

Page 1

Emergency Switch

.

Fuses

Transformer

Control Relays

Brake Relay

Internal Timer

Panel Mounted Timer

A NEMA 4X rated Emergency Stop operator is used fordisconnecting control power in the enclosure and stopping thennotor.

07/02/97

Pressing this operator opens the coils on the run relays and stopsthe timers and drive. It also extinguishes the *Start" switch light.

Twisting and pulling this operator reactivates the control powerand enables the system.

Fusing is provided for protection ofthe primary feed into thecontrol transformer and the secondary feed from the transformer.

A 300 VA control transformer is provided to produce the115VAC control voltage from the 230V/3Ph/60Hz main input

power.

Three 4PDT 115v Coil relays are used for the control in thissystem. Two are main run relays, the third controls the solenoidvalve in the pneumatic enclosure.

Used to control the switching on and off of the 460V/3Ph/60Hzpower to the main motor brake. The relay is activated bysupplying 115V AC across its coil which in turn releases thebrake.

An integral non-resetable timer is provided inside the mainenclosure to allow accurate monitoring ofprocess run time.

A single preset timer is used for engaging the drive for apredetermined period oftime and automatically stopping upontiming out. To re-engage the drive, the timer must be manuallyreset.

Page 2

Enclosure

Regulator

Pressure Gauge

Lubricator

Solenoid

PNEUMATIC UNIT SPECIFICATIONS

The regulator, pressure gauge, lubricator, and air solenoid arehoused in a NEMA 4X Stainless Steel Enclosure.

07/02/97

Controls the maximum output pressure to the discharge valve.

Displays the current set output pressure to the discharge valve.

Dispenses the required amount of lubricant to the air as it flows tothe discharge valve.

Controls the flow of air to the discharge valve. When energized bythe valve control relay, the solenoid allows the air to pass throughand opens the discharge valve.

Page 3

EC/D

.

Fuses

3 pcs

3 pcs

2 pc

1 pc

LPJ-30SP

FLQ-10

FLQ-1

FLQ-2.5

Miscellaneous

1 pc D5-N130

1 pc MY4N-115

RECOMMENDED SPARE PARTS

30 AMP Class J fuse

10 AMP, 600V

1 AMP, 600V

2.5 AMP, 600V

120V Incandescent Bulb for Push-button

115V 4PDT Relay

Page 4

07/02/97

EErl

.

.

.4. 2- < 1

'·1 ,- - ·': '.1 -..BULLET/NNO.-.LBT-F

7 497:-»;r:4_·--er---,-:=Llt»SREV/SED696 - 'f-%*4*iw.; 1-'.. ..:7': I:.':1*4.---.SI..DRAWING NO. LP0104

REDYIZION*6*!TRdES{Ff b ,/ . •i

INTERNATIONAL HEADQUARTERS--:IT---p·: -- -**EUROPEAN HEADQUARTERS"- 0-r '-1·-' --:--

.20 Willow Springs Cirde, York, Pa. 17402, (717)-767-651·f FAX: (717) 764-0839*892 Plymauth Road, Slough, Berkshire. SL1 4LPWebsite- htlp://www.redlion-controls.com E-mail- [email protected] r ENGLAND +44 1753 696888 FAX: +44 1753 696339

1 15: .

MODEL LIST - LIBRA SERIES TIMERS.(LCD_& LED)

.ONE OR TWO PRESET VERSIONS .e ..4 t- ...-. 11 SELECTABLE TIME RANGES - - -

. 0.5* (12.7 mm) HIGH LIQUID CRYSTAL DISPLAY OR0.4" (102 mm) HIGH LED DISPLAYI

. SOLID-STATE C6RRENT SINK OUTPUT(S). FORM C RELAY OUTPUT(S).

s PROGRAMMABLE TIMED OUTPUT (0.01 sec to 99.99 sec.)

. SIMPLE FRONT PANEL FOR PROGRAMMING EASE

. MEETS DIN PANEL MOUNT SPECIFICATIONS

. REMOTE RESET CAPABILITY

. INSTANTANEOUS & DELAYED CONTACTS u

. NON-VOLATILE MEMORY (ISPROM)

. SEALED FRONT PANEL CONSTRUCTION (NEMA 4/IP65)

LJ La tr

CAUnON: Read complete instructions prior CAUTION: Risk d electric shock. to insttlaton and operation of the unit.**4

DESCRIPTIONThe Libra Series of presettable timers is an economical and reliable sohftion

to onc or two preset timing requirements. The LIETl and LIBTIEre thesinglepreset timerversions andthe LIBT2 and LIBTZE are the dual presettimerversions. All four units have a solid-state output and a form C relay output for ,each preset. These units feature a full complement of control inpUtB.programmable timed output values, non-volatile memory and many otherfearures which will satisfy most any single or dual preset timer requirement.

The Libra Timers have two main timing actions, Reset to Zero (7?7Z) £7imeupl and Reset to Preset 0?77) mme Downl. With RTZ, the timer resets to zero, times up, and activates the outputs when the preset value(*) are reached.When RTP is used,Ihe unit starts at the preset value. times down, and activatesthe output when zero is reached (singleprzset unit). For the dual preset version,the time starts at preset 2 and times toward zero. Output 1 fires when the preset1 value is reached and outpvt 2 fires when the time reaches zero. There are tenmodes of operation for the s.ngle presetunit and sixteenmodes ofoperation forthe dual preset unit.

The Libra Timers also have eleven different selectable time range values.These include: hours, minutes, orseconds; tenths of hours, minutes, or seconds;hundredths of hours, minutes, or seconds; and two chronometer time functionsof minutes and *conds; and hours and minutes.

DIMENSIONS "In inches (mrn)

OJOCU _L_1 LJ

0000Pt K

EOAOR

r· MIT .· 89.- -ry

2.83'(721-

2.83

(72)

TL

$

L 0-1 0 n -1

0, 0@@Pl P 2

g8 R

T

L

4jst

. ABILITY TO LOCK OUT FRONT PANEL FUNCTIONS

. FRONT PANEL RESET ENABLBDISABLE/

C€

The timed output is programmed through the front panel buttons and can be kprogrammed from 0.01 sec. to 99.99 sec. Bbe unitk timed output is ser at thefactory to be 0.1 sec) The Libra timers have an internal non-volatile memorydevice which eliminates the need for battery back-up. When input power is lost.this device will maintain all data necessary for system operation. A ProgramDisable terminal is present which is used to prevent accidental Ehanges ortampering by unauthorized personnel to the preset<) or timed output valuets):The front panel reset button can also be enabled or disabled by a rear panel DIPswitch. These timers also have an on-line self-test, which checks all displaydriver and micro-processor hardware. The self-test can be nm at any timewithout losing time or missing preset value(s).

Power, input, and output connections are made via removable terminal blockslocated at the rear ofthe unit. These blocks can accept one #14 AWG strippedwire. DIP switches at the rear ofthe unit are used to set the time ranges and toset the desired operating modes.

The Libra Series timershave a metal die-cast front bezel, which is seated, andmeets NEMA 4/IP65 specifications for wash-down and/or dust when properlyinstalldit Mounting clips are provided for easy panel installation

Note: Recommended minimum clearance (behind the panel) formounting dip installation is 2.7-(69)H x 4.9(114)W.

1 -- I- 1

.11.131 V6.60(142.21

2.60|661

2.GB.(681

PANEL CUT-OUT

2.687681 .

.

.

+12*Crm_rL

COMM. Il47UH

DIS. 1-47uH98#:mirmn

4©.0

- BLOCK:DIAGRAMI I .2,328*1, -1 I.- ...... ,<-„.':%

-511//rbkilt-AASHORea,-xe/.1 -

1Qi 11K .8'23

10K

1- A.ass- POLOIS

110

m 6 H*p vRST ».

WASE laRESET 9 .'-BM * : PROCESSING

' -72:12 CIRCUITRY

U 11--R ! .-- 11ME

- - 0U1PUT 2

/ 0nlpt

TIME RANGES

+12V - 0 ' -h "n -v 1. .44.1 POWER . +--J-1.A k POWER

4- 19·}PPLYI -48*.Attt:150/60 HZ ·«

+ m

11(

NON VOLATILE

MEMORY

*ISPLAYI

--Kr

1*:2r--4

1

oy .91 1 1 1.0-Iffftff.f P RST.

SPECIFICATIONS1. DISPLAY:

4-digit, 0.5" (12.7 mm) high LCD display.4-digit, 0.4 (10.2 mm) high LED display.

2. POWER REQUIREMENTS: - .-AC Operation: 1 15/230 VAC (tl0%), 50/60 Hz, 6 VA (LCD) or 9 VA

(LED).DC Operation: 11 to 14 VDC @ 0.2A max (LCD) or 0.3 A max (LED).

3. SENSOR POWER: 10 to 16 VDC @ 150 mA.4. RUN INPUTS Can accept switch contact closure and NPN Open Collector

outputs and similar types of current sinking inputs. · VIL = 1 V max..internally pulled up to 5 VDC through a 10 KA resistor (ISNK = 0.5 mA).Response time = 5 msec to 15 msec. micze units operate with FCM fE„mmodulm.)

5. TIME ACCURACY: *081%6. CONTROL INPUTS:

Remote Reset: Active low (VIL =lV max.), internally pulled up to 5 VDCthrough a 10 Kn resistor (ISNK = 0.5 mA). Response time = 10 nisec. Alow will reset the unit and deactivate the outputs.

Program Disable: Active low (VIL = 0.5 V max·), internally pulled up to 5V[)C through a 10 Kn resistor (ISNK = 0.5 mA). A low will inhibit thechanging of presets and timed outputs, as well as the testing of outputs inself-test

7. OUTPUTS:

Solid-State: Current sinking NPN open collector transistors. ISNK = 100 mAmax. VOH = 30 VDC max. (Internal Zener diodeprotection). Onesolid-state output for each preset level. Vol = 1 VDC max. @ 100 niA.

Relay(s): Form C contacts max. rating 5 amps @ 120/240 VAC, 28 VDC(resistiveload), 1/8 H.P. @ 120 VAC (inductive laad). The operate timeis 5 msec nominal and the release time is 3 msec nominal.

Relay Life Expectancy: 100,000 cycles at max. rating. Ms load leveldecreases, life expectancy increases.)

Programmable Timed Output: The timed output canbc programmed from0.01 sec to 99.99 sec, *0.01% - 10 nisec. The timed output is set for 0.1sec at the factory.

8. MEMORY RETENTION: The Libra Timers have a "no power IFPROM"which maintains all information when the input power is removed. The lifeexpectancyof this device is at least 10,000 power down cycles and length ofmemory retention for a single power down can be as long as 10 years.

9. INPUT, POWER, AND OUTPUT CONNECTIONS: There are two plug- in, compressiontype, banierstrips located attherGof thc 6nit. Thesestrips

can be removed from the rear of the unit for ease of 4iling.' After wring iscomplete, the connector can be plugged back into the-,nit. ·:--

- 41' d ILC

«1--[El N.0.

al &M.

i -[] COL{M.r=mil-[Z] 01-SNK

02-SNK

A V IBN.c, -

1 -HHfN.o031&YJ

FOR TWO PRESET --VERSION ONLY

0

2

0

10. CERTIFICATIONS AND COMPLIANCES:EMC EMISSIONS:

Meets EN 500814: Industrial EnvironmentCISPR 11 Radiated and conducted emissions

EMC IMMUNITY:Meets EN 50082-2: Industrial Environment.

, ENV 50140 -Radio-frequency radiated electromagnetic fieldENV 50141 - Radio-frequency conducted electromagnetic field 1

. \ EN 61000-4-2 - Electrostatic discharge (ESD)EN 61000-4-4 - Electrical fast transient/burst (EFT) 1EN 61000-4-8 - Power frequency magnetic field

I.;, Noter 1. Unit required a tine Jilter (RLC #LFIL0000) when DC powered. Aly DC·,pi .. Power through the line jilter to TBA terminals 5 (Comm) and 6 (+12

3*S VDC). Connect all other VO Common returns to TBB terminal 6 (Comm.).a*y Tesc EN 61 000-4-4 EFT and ENV 50141 RF Conducted Immunity.62£3 Refer to the EMC Installation Guidelines for additional information.rbll. OPERATING TEMPERATURE RANGE: 0°C to 50°C2·:12. STORAGE TEMPERATURE RANGE:-40°C to 70°C·@'13. CONSTRUCTION: Metal die·cast bezel with black. high impact plastic112! insert. Front panel meets NEMA 4/IP65 requirements for wash-down and8..tdusty environments when properly installed. (Panel gasket and mounting

clipsincluded with unit)96.14. WEIGHT. 13 lbs. (0.68 kg) /LCD;, 1.75 lbs. (0.79 kg) /LEDJ

--n

=El

:Tyf

'5

SELECTION OF MODES OF OPERATION, TIME_RANGE VALUE, POWER-UP RESET, & FRONT© PANEL RESET

12'·The selection of Modes of Operation. Time Range, Power-Up Reset, and2- Front Panel Reset is accomplished by a ten-position DIP switch, located at the

rar of the unit, in the upper right-hand corner. DIP switches 14 are used to set the desired modcof operation,while DIP switches 5-8 are used to determine the' time range setting. DIP switch 9 is used to determine whether the unit, on

p6wer.up, is to restore or reset the time value. When this switch is up, the timevalue, displayed before power loss. will be restored and will be operated on asbefore power loss. When the switch is down, the unit will reset the time valueto either zero (R74 or to the preset value FIP) when input power is restored.DIP switch 10 is used to enable or disable the front panel reset button. When

' S-&'autch is up the front panel reset button is Babled When the switch is - ..4¢1EG;ir¢*sot,ffi reset button is enabled. The selection of Mode of.61*be-discuss#d f followedby the selection pfTime Range Value. 14*:jEEZEE{Ze- ·- ·:*ir.TTE%. r.:i.-/ /.../. . Y

. :,-"'-4¢,;"9,...'..bg>:91 :4:.,

MODES OF OPERATIONZ23>**hUbi@SP'Mode settings of the switches'2S*i*Lk_-9£1kENbelow:,-The

mode number correspcUs to I BIP,switchpositions. When the switch is 3Jrl,'it-6-equivalnt to a &2mhA iheswitch

.*,» *'·54*As.Famj=-m*;zm:2&. :4

1 -

.

*50*0 ,9:42:9*ASk'--'*Aifi,21*..d-< LLE?.'*-1* ·;··-34 -, *is"DOK:', itis equivaic-ntto.a one©nodjswitch·settings can,be easily--,the stateJof these mode*,itches are displayUi*1SE.1*YYOF.ZI bbserved frpm the-;ai21, fr6it by kising-thd Self-tcEifNA:rihe end of self-test;'1 '

-

MODES OF OPERATION FOR SINGLE PRESET LIBRATIMER '-11.7 * t

MODE 0 LATCH OUTPUT AT PRESET,MANUAL RESEr,TO ZERO, TIME MODE 8 LATCH OUTPUT AT ZERO, MANUAL RESET TO PRESET TIMESTOPS AT PRESET (ACCUMULATING DELAY ON MAKE, TIME ' .GS·STOPS AT ZERO (ACCUMULATING DELAY ON MAKES, TIME

" S-{*DOWN) 4 5*.5 4,112*3:3·, er .- · ··up) *. «.4,·-2.*f...2+64**bi: ..In this mode, as the unit times up from zero, thd-butput will Inthis le, s'thounit dm42&wn frompreset.the output.will

when preset is reached. When amanual reset*,ocgurs, the,uniC.will Reset to Zero and the outpiit if latallad 6ey*6tatc£36' - 28*-Assa'and the'ou*it iflatched 64 will untatch. · . .,

To use as a DELAY ON MAKE timer, sEfihB¥mid-WuE to the desired :-* Touse as a DELAY ON MAKE timer, set the preset value to the desireddelay value. When "RUN" is ht a low le,;el, t6*€#nlincreient. The output t. delaikalud.,When "RUN" is ath low level, time will decrcment The outputwill activate when the preset is QachJ> m¢*Ift;se, 11 reset or 2) set the 4 willa*Nate when the zero is reached. To recycle use 1) reset, or 2) set the-power-up resct switch to enable. then rem6ve and reapply input power.power-up reset switch to enable, th€rcniovedApply input power.

-

,.. MODE 1 LATCH OUTPUT AT PRESET, MANUAL RESET TO ZERO, TIME MODE 9 LATCH OUTPUT AT ZERO, MANUAL RESET TO PRESET, TIME

CONTINUES AT PRESET (ACCUMULATING DELAY ON MAKE - - Cit¢ CONTINUES AT ZERO (ACCUMULATING DELAY ON _2.-Iri'thts:nddd,astheunittimesdown frompreset.th66utatwill'-i.1-AA ,; 1./ E'KI .' I. .

In this mode, as the unit times up from ·zsro. the output will ..latchonivhenzero is reached. Timd,kill contini@'tpaccumu!,te 111!illilmilatch on when the preset is reached. Time'will continue to .* after 570 is mached. When a manual reset* occurs. the unit willaccumulate after the preset is reached. When Inanual reset* . 5 ResZi to Preset,'and the output, if latched on, will unlatch. , ,occurs, the unit will Reset to Zero, and the output, if latched on, will unlatch. 5-· Touse asa DELAY ON MAKE timer, follow the description under Mode

To use as a DELAY ON MAKE timer, follow the description under Mode .*8 I.... 3--' ..-. . I

MODE 10 & 11 -**MODE 2& 3 - ** ., - . _ *MODE 12 TIMED OUfPUT ATZERO, MANUAL RESETTO PRESET, TIME

MODE 4 11MED OUTPUT AT PRESET, MANUAL RESET TO ZERO, TIME Zf:'' ' STOPS AT ZEROSTOPS AT PRESET Zi. In this mode, as the unit times down from preset, the output willIn this mode, as the unit times up fromzero, the output will tum t, 2 3 4, urn on when zero isreached. The output will rum off after its dl[;]dldllon when the preset is reached. The output will turn off after its @| 0-programmed time value has occurred. Also, the unit will stop

programmed time value has occurred. Also, the unit will stop Btiming when zero is reached. When a manual reset* occurs, the unit willtiming whenthe preset is reached. When a manual reset occurs, the unit will ]Reset to Preset Manual reset* will terminate the timed output, if the outputReset to Zero. Manual reset* will terminate the timed output, if the output is -MODE 13 TIMED OUTPUT ATZERO, AUTOMATIC RESETTO PRESET

5.is still turned on.

still turned on.

MODE 5. TIMED OUTPUT AT PRESET, AUTOMATIC RESET TO ZERO F AFTER TIMED OUTPUT (OFF/ON RECYCUNG, T[ME DOWN)

AFTER TIMED OUTPUT (OFF/ON RECYCLING, TIME UP) / Inthis mode, as the unittimes down from preset, the output will ,In this mode, as tile unit times up fromzero, the output will turn turn on when zero is reached. The output will turn off after the Illl|

on when the preset is·reached. The output will turn off after iB 'IhilifiJ - programmed tinie value has occwred. Also. attheend of thetimed 1programmed time value has occurred. Also, at the end of the *. output, the unit will automatically Reset to Preset and start the cyclc over.

S. ,

timed output, the unit will automatically Reset to Zero and start the cycle ofer.r: Manual reset* will turn offthe output, if turned on, and reset the time to theManual reset* will turn off the output, if turned on, and reset the time to z6;S.,lff · preset value. ' · --

When used as an OFF/ON RECYCLING timer, the total cycle time is th#' When usedasan OFF/ON RECYCLING timer, thetotal cycle time is equalsum of the preset value plus the programmed timed output value. The ON?K to the sum of the preset value plus the programmed timed output value. Thedelay value is equal to the programmed timed output value.tt When "R. ON delay value is equal to the programmed timedoutput value.tt Whenis at a low level, time will increment. The output (ON delay) will activate@ "RUN" is at a low level, time will decrement The output (ON delay) will

when the preset is reached. The unit will recycle at the end ofthe timed oytp *rwhen zero is reached. The unit will recycle at tile end 6f the timedMODE 6 TIMED OUTPUT AT PRESEr, AUTOMATIC RESET TO ZERO AT*

PRESET t (OFF/ON RECYCLING, TIME UP) ; ,!Aif MODE 14 TIMED OUTPUT AT ZERO, AUTOMATIC RESET TO PRESET ATZERO t (OFF/ON RECYCUNG, TIME DOWN) .In this mode, as the unit times up from zero, the output will turn

on when the preset is reached. '.he output will turn off after A 1*51% In this mode, as the unittimes down frompreset, the output will''I ,programmed time value has occurred. Also, when the preset is L----4;f. turn on when zero is reached. The output will tim off after its []reached, the unit will automatically Reset to Zero and start the cycle over. c.' programmed time value has occurred. Also, when zero is reached,(The output will remain on until its time value has occurred.) Manual reset* 94 the unit automatically resets the time to the preset vilue and startS the 6yplewill tum off the output, if turned on, and reset the time to zero. . «*3, over. Manual reset* will aim off the output, if turned on, and reset. thetif°$

When used as an OFF/ON RECYCLING timer, the total cycle time is the:re to the preset value.

preset value. The ON delay value is equal to the programmed timed output,$4*When used as an OFF/ON RECYCLING timer, the total cycle time,is the

value.tt When"RUN" is at a low level, time will increment. The output (ON ir r: Preset value. The ON delay value is equal to the programmed timed 6utputdelay) will activate when the presct is reached. The unit will recycle at the - value.tt When "RUN" is atalow level, time will decrement The output (ONbeginning o f the timed output. :.,.pr.f7- delay) will activate when zero is reached. Tile unit will recycle at the_L--./ beginning ofthetimedoutput. -

c - £:S.ViMODE 7-** -PA% 00E15-ita* -Manual reset. either by.front panet reset (fenabled) or remotereseL is ::-. -always active andwilloverride any conditionorstateof the timU5*99 1 -netimed output vaitte must be less thanthevalue required totimefrom** - nese modes are not applicable to ihe single preset Ilibra time,1[u0 t: =ron to the preset point. Otherwise. the output willappear to

are used only for the two presd timer unit). . -,,"131212:» _-2=5*A tt - The maximum ON delay is 99.99 seconds.

POWER-UP DIAGNOSTICSThe Libra timers have internal diagnostics which.will che«th18ii:12. thesff!3¢Fesults.then a "P" will appearon theright side ofthe display. Normalduring power.up. When the data is saved 0,ower.down),computatio*SE; 1 OPention.oftheunitwill continue while this "P"displayed. To remove the "P"with these values, The result of these computations is stored in * I¥mE!*5jd#51.- fkom the display, press the "E" button. Then check programmed values to beserve as a check against possible error. Then on '86weSkib1¢F«K*IlE'*n *ZE·(9rrect.computations are repeated on the stofed da If tliase reilikdhot agreti*¤f·· --

4 .f·42*·.-**ES.7*,

a.

-

'1 .. ..e.*

MODES OFOPERA¥ION*bUAL PRESET LIBRA TIMER '.L..# -- *FE &*HIC64*33*S»*• ,

•46 '0) ./!.B .1*" 'Al'*Ae.* ''- 73 -' '' - .':-

MODE 0 LATCH OUTPUTS ATPRESETS;MANUAL RESETTO ZER611AEj* MODE 5 TIMED OUTPUTSAT PRESErS, AUTOMATICRESET TO ZEROSTOPS AT PRESET- 2 (INSTANTANEOUS & TIME H)ELAY.11:BE AFTER TIMED OUTPUT 2 t (TWO LOSE' OFF/ON RECYCLING,9. ..

CONTACT, TIME UP) TIME UP) In this mode, as the unit times up from zero, output 1 will latch 1 - i *92 In this mode, as the unit times up fronp zero, output 1 will turnon when preset 1 is reached and output 2 willtatchon when preset [ f-, on when preset lis reached and output 2 wili turn on when preset |IblhAIDI2 is reached. The unit will stop timing when preset 2 is reached. 11+ 2 is reached. The' outputs will turn off after their respectiveThis mode also has an input tracking feature (INSTANTANEOUS-g-;:. programmed time values have occurred. Also at the end oftimed output 2, theCONTACT) where if preset 1 is set to zero, output 1 will turn on when the -, + unit will automatically Reset to Zero and start the cycle over. Manual reset*input is activated, and it will turn off when the input is deactivated. (Ou®t 23>E -" will turn offboth outputs, if' turned on, and reset tile time to zero.is the TIME DELAY CONTACT.) Whena manual reset* occurs, the unitwill'*i . When used as an OFF/ON RECYCLING timer, the total cycle time is equalReset to Zero and the outputs, if latched on, will unlatch. -- 214%f to the sum of the preset 2 value andthe progammed timed output 2 value. The

To use as an INSTANTANEOUS AND TIME DELAY CONTACT tinicri'-Sys, first lobe of the cycle will use output 1. The first ON delay value is equal toset preset 1 value to zero and set preset 2 value to the desired delay value::' /1 4 the programmed timed output 1 value.tt The second lobe of the cycle willWhen "RUN" is at a low level, time will increment and output 1 will be If £ use output 2. The second ON delay is equal to the programmed timed outputactivated. Output 2 (TIME DELAY CONTACI) will activate vien preset 2 84.4.. 2 value.tt When"RUN" is at a low level, time will increment. Output 1 (first

-js reached. To recycle use 1) reset. or 2) set the power-up reset switch to.j: ON delay) will activate when preset 1 is reached, and output 2 (second ON. . 2.inable, then remove and reapply input power. ·U, 1. delay) will activate when preset 2 is reached The unit will recycle at the end

oftimed output 2." · MODE 1 LATCH OUTPUTS AT PRESETS, MANUAL RESET TO ZERO, TIME,·'.:CONnNUES AT PRESET 2 (INSTANTANEOUS & TIME DELAY, < - MODE 6 TIMED OUTPUTS AT PRESETS, AUTOMATIC RESET TO ZERO ATCONTACT, TIME UP) PRESET 2 t (T'WO LOBE OFF/ON RECYCLING, TIME UP)

fe

In this mode, as the unit times up from zero, output 1 will tatch In this mode, as the unit times up from zero, output 1 will turnon when preset 1 is reached, and output 2 will latch on when preset *1 81 on when preset lis reached and output 2 will turn on when preset 1[hd#*ib2 is reached. Time will continue to accumulate after preset 2 is ' ' · -7 2 is reached. The outputs will turn off after their respectivereached. This mode also has a input tracking feature (INSTANTANEOUS ,li€ programmed time values have occurred. Also when preset 2 is reached, theCONTACT) where if preset 1 is set to zero, output 1 will mm on when the -.mt- unit witl automatically reset the time to zero and start the cycle over. (Outputinput is activated, and it will turn off when the input is deactivated. (Outpuil*Z- 2 will remain on until its time value has occurred.) Manual reset* will turnis the TIME DELAY CONTACT.) When manual reset* occurs, the unit will *: off both outputs, if still turned on, and reset the time to zero.Reset to Zero, and the outputs, if latched on, will unlatch. 5 When used as an OFF/ON RECYCLING timer, the total cycle time is equal

To use as an INSTANTANEOUS AND TIME DELAY CONTACT timer. - 11 to the preset 2 value. The first lobe of the cycle will use output 1. The first ONfollow the description under Mode 0. ..'.·< delay is equal to the programmed timed output 1 value.tt The second lobe ofMODE 2 OUTPUT 1 TURN OFF AT PRESET 2. LATCH OUTPUT 2 AT ''1 the cycle will use output 2. The second ON delay is equal to the programmedPRESET 2, MANUAL RESET TO ZERO, TIME STOPS AT PRESET .1· timed output 2 value.tt When "RUN" is at a low level, time vvill increment

2 (INTERVAL, TIME UP)Z Output 1 (first ON delay) will activate when preset l is reached, and output 2.it (second ON delay) will activate when preset 2 is reached. The unit will

In this mode, as the unit times up from zero, output 1 will turnwhen preset 1 is reached. When preset 2 is reached, output 2 Idithli#1 - recycle at the beginning oftimed output 2.11 turn on and output 1 will turn off. Output 2 will remain MODE 7 OUTPUTl TURN OFF AT PRESET 2, TIMED OUTPUT2 AT PRESET

latched on until a manual reset occurs, and the unit will stop timing when \. 2, AUTOMATIC RESET TO ZERO AFTER TIMED OUTPUT 2 tpreset 2 is reached. This mode also has an input tracking feature where if '4 (INSTANTANEOUS & TWO LOBE OFF/ON RECYCLING, TIME UP)preset 1 is set to zero, output 1 will turn on when the input is activated, and it In this mode, as the unit times up from zero, output 1 will min Iwill turn off when the input is deactivated. (After preset 2 is reached, output on when preset 1 is reached. When preset 2 is reached, output 2 1%/thaild1 will tum offend stay off, regardlesi of the input condition, until a manual will turn on and output 1 will turn off. Output 2 will nirn off afterreset* occurs.) When amanual reset* occurs, the unit will Reset to Zero and its programmed time value has occurred. At the end of timed output 2, the unitthe outputs, if latched on, will unlatch. will automatically Reset to Zero and start the cycle over. This mode also has·'" To use as an INTERVAL timer, set preset lyalue.td zero and set preset 2 an«jpput tmcking feature (INSTANTANEOUS CONTACT) where if preset 1value to the desired delay value. When "RUN" is at a low level, time will is Sel to zero, output 1 will turn on when the input is activated, and off whenincrement and output 1 will be activated. Output 1 will deactivate (regardless the input is deactivated. (After preset 2 is reached, output 1 will turn off and

- of the input condition) when preset 2 (TIME DELAY VALUE) is reached. To stai' off, regardless ofthe input condition until a reset occurs.) Manual resetlkrecycle use 1) reset, or 2) set the power-up reset switch to enable, then remove will Rim off both outputs, if turned on, and reset the time to zero.

and reapply input power. · .Whenused as an OFF/ON RECYCLING timer, the total cycletime is equalto'thersum oftic preset 2 value and the programmed timed output 2 value.

MODE 3 - OUTPUT 1 TURN OFF AT PRESET 2, LATCH OUTPUT 2 AT Thetst lobe of the cycle will use ouJut 1. The first ON delay is equal to thePRESET 2, MANUAL RESET TO ZERO, TIME CONTINUES AT difference between preset l and preset 2 values (this is because output 1 willPRESEr 2 (INTERVAL TIME UP) turn off' at preset 2). The second lobe of the cycle will use output 2. The

In this mode, as the unit times up from zero, output 1 will mm Ion when preset 1 is reached. When preset 2 is reached. output.2 i AltlI second ON delay is equal to the programmed timed output 2 value.tt When

"RUN" is at a low level, time will increment. Output 1 (first ON delay) willwill turn on and output 1 will nim off. Output 2 Will remain activate when preset 1 is reached, and output 2 (second ON delay) willlatched on until a manual reset occurs, and the unit will continue toaccumulate time after preset 2 is reached. Thismode also has an input tracking

activate when preset 2 is reached (output 1 will deactivate when preset 2 isreached). The unit will-recycle at the end of timed output 2.

feature where if preset 1 is set to zero, output 1 will turn on when the mput isactivated, and it will turn off when the input is deactivated. (After prext 2 isreached, output 1 will tum off and stay off, regardless.6fthe input condition, *. Manual resel. either by front panel reset (ifenabled) or remote reset, is

until a manual reset occurs.) When manual reset* occurs, the unit will Reset ' always active,andwilt overrideany conditionorstateof the timer.

to Zero, and the outputs, if latched on, will unlatch.t .netimed output value must be less thanthevalue requind totime from

To use as an INTERVAL timer, follow the description under Mode 2 . thereptcondition to thepresetpoint Otherwise.the outputwillappear toDe latched ok

MODE 4 TIMED OUTPUTS AT PRESETS, MANUAL RESETTO ZERO, TIME tt -The maximum ON delay is 99.99 seconds.STOPS AT PRESET 2

.-I

- In this mode, as the unit times up from zero, output 1 will turnn when preset 1 is reached, and output 2 will tum on when preset IhIAL*1*1

L.,(Modes Conrd)

2 is reached. The outputs will turn off after their respectiveprogrammed time values have 0*urred. Also, the unityill stop timing when

. preset 2 is reached. When a manual reset* odaurs, theunit will Reset to Zero.fil»*P:*-4:9 f#:**A'1.=:# . ,en,65.*t.<f,44:0·,s: u.'9..6:Y-5.·=.i 1

Manual reset* will terminate the timed outpilt, if the 6ittpUtS are still turned.

on. *ful:*Y:1158:'•Ctz.'trocr· MI, r.· - -

.

11

3/ELF

=

=Z

a '.*i

4 4

Si

i.

·fY?CriSS.iE..

1. '3'-trN··*Kl4J<<TEUP _.---__Y'*El F.".3·31 · - --f Ir #. 1 --teor-k

g ->«49*MODES<Or*)PERATION FOR DUAL RRESET LIBRA TIMER (Corit'd) *au: ie„ L.108#Er,,#755.*Grtwk.,7,- · - 1-4:6. rir.&62&: -'..n#r.·F--

MODES LATCH'OUTPUTAT'PRESErr»AND ZERO,'MANUAL RESET TOT--NMODE 13 TIMED OUTPUTS AT PRESET 1 AND ZERO, AUTOMATIC RESETPRESET 2, TIME STOPS*iZER*(INSTANTANEOUS & TIME 2 fig'659.rro PRESET 2 AFTER TIMED OUTPUT 2 + (TWO LOBE OFF/ONIntllis11,et,1ttwill - - -- thisnxide astheumttlmesdownfromprese£2, outputlwillr-'75.4-RECYCUNG,TIME DOWN) -t - ': U..1.--

latchon when prdset lis reache€28>i$§),2j*,h-on when 11 , non»en prfser 1 is reached and output 2 will tum on when |LD®|zero is reached. The unit witt stop timing wheq,zTds reached. 1---I · zero is reached. The outputs will turn ofF after their respectiveThis mode also harlm"inpdf'i82kii*'feabe'-(INSTANTANEOUS programmed time values have occurred. Also, at the end oftimed output 2, theCONTACT) where if preset-lis«inRiN*R"1*ill tum on when the . ';:" unit willlRitomatically Reset to Preset 2 and start the cycle over. Manualinput is activated, and it will@ri;9ff'*,*iput is deactivated. (Output 2 -.-4-. res* will him off both outputs, if turned on, and reset the time to preset 2.is the TIME DELAY 9355·) Ebsill&»Ad.lms.d* ckcurs, the unit will ZES&*das an OFF/ON RECYCLING timer. the total cycle time is equalReset to Preset aiid iite outplfstijf18kh-4.993©Alick, - .Aito.¢le sum oftlic preset 2 value and the propmmed timed output 2 value. The

To useas an INSTANTANEOUSAND TIMEDELAY CONTACT timer, 1- 5*firk lobd-of the cycle will use output 1. The first ON delay is equal to theset preset 1 *alue to zeni*-**ji2>R11 to the desired delay value.. -,fprogrammed timed output 1 value.tt The second iobe ofthe cycle will useWhen "RUN'Us at a low level;Vmeyill decNinciit'd output 1 will bel. ZE@4yut 2. The second ON delay is equal to the programmed timed output 2activated. Output 2 mME-DELAYfCONTACI) ill activate when zero is < .vallie.tt When "RUN" is ata low level, time will decrement. Output 1 (first

·V=•.le -' FL r r.,1 .0

reached To recycle use 1)resetior 2) setthe power-up reset switch to enable. · 3ZPN-delay) will activate when preset 1 is reached, and output 2 (second ONthenmmove and m?ppl,¥j,P,tE*illS--„-., , . -

-2 timed output 2.-Efidelay) will activate when zero is reached. The unit will recycle at the end of

MODE 9 LATCH OUTPUT AT PRESET.1 AND ZERO, MANUAL RESET TO .7:PRESET 2, TIME CONTINUES AT ZERO (INSTANTANEOUS & ' -f- MODE 14 TIMED OUTPUTS AT PRESET 1 AND ZERO, AUTOMATIC RESETTIME DELAY CONTACT, TIME DOWN) -·: - ' -- TO PRESET 2 AT ZERO t (TWO LOSE OFF/ON RECYCLING,In this mode, as tile unit times dod frpm preset 2, outputlwill , 2 3 4 i ., --SAG . TIME DOWN)

latch on when preset 1 is reached, and output 2 will latch on when 1[illfill[Ill,j 3Inthismode, asthe Unittimes down from preset 2, output i will Izero is reached. Time will continue to accumulate after zero is L----1 --2=, turn on when preset 1 is reached and output 2 will turn on when F]reached. This mode also has an input tracking feature (INSTANTANEOUS * Et<ze:p is reached. The outputs will turn off after their respectiveCONTACT) which if preset 1 is set to zero, output 1 will turn on when the * .2- programmed time values have occurred. Also when zero is reached, the unitinput is activated. and it will tum off when the input is deactivated. (Output 2* 7.f will automatically reset the time to preset 2 and start the cycle over. (Outputis the TIME DELAY CONTACT.) When manual reset* occurs, the unit will Z Z- 2 will remain on until its time value has occurred.) Manual reset* will tumReset to Preset 2 and the outputs, if latched on, will unlatch. lir j.:-off both outputs, if still turned on, and reset the time to Preset 2.

To use as an INSTANTANEOUS AND TIME DELAY CONTACT timer,_. When used as an OFF/ON RECYCLING timer, the total cycle time is equalfollow the description under Mode 8. . to the preset 2 value. The first lobe ofthe cycle will use output 1. The first ON

delay is equal to the programmed timed output 1 value.tt The second lobc ofMODE 10 OUTPUT 1 TURN OFF AT ZERO, LATCH OUTPUT 2 AT ZERO,

MANUAL RESET TO PRESET 2, TIME STOPS AT PRESET 2the cycle will use output 2. The second ON delay is equal to the programmed

(INTERVAL, TIME DOWN) timed output 2 value. tt When "RUN" is at a low level, time will decrement.

In this mode, as the unit tis down from preset 2, output l will i, . Output 1 (first ON delay) will activate when preset 1 is reached. and output 2turn on when preset 1 is reached. When zero is reached, output,2 @[ the beginning of timed outpu 2.(second ON delay) will activate when zero is reached. The unit will recycle at

will tum on and output 1 will tum off. Output 2 will remamlatched on until amanual reset occurs, and the unit will stop timing when zero MODE 15 OUTPUT 1 TURN OFF AT ZERO, TIMED OUTPUT 2 AT ZERO,is reached. This mode also has an input tracking feature where ifpriset 1 is - _ AUTOMATIC RESET TO PRESET 2 AFTER TIMED OUTPUT 2 t

set to zero, output 1 will turn on when the input is activated, and it will turn (INSTANTANEOUS & TWO LOSE OFF/ON RECYCLING, TIME

offwhen the input is deactivated (After zero is reached ourput 1 will'Etrn off DOWN)

and stay off, regardless of the input condition, until a manual reset* 6ccurs.) In this mode; aithe unit times down frompreset 2, output 1 will i1,1

When a manual reset* occurs, the unit will Reset to Preset 2 and the outputs, turn on when preset 1 is reached. When zero is reached output 2 |maiiin|if latched on, will unlatch. ' - witt turn on and output 1 will turn off. Output 2 will tum offafter

r 1,» its programmed time value has occurred. At the end of Timed output 2, theMODE 11 OUTPUT 1 TURN OFF AT ZERO, LATCH OUTPUT 2 AT ZERO, unit will automatically Reset to Preset 2 and start the cycle over. This mode

MANUAL RESET TO PRESET 2, TIME CONTINUES AT PRESET 2(INTERVAL, TIME DOWN) .'. 4*

also has an input tracking feature (INSTANTANEOUS CONTACT) where if. preset 1 is set to zero, output 1 will turn on when the input is activated, and

In this mode, as the unit times down from preset 2, output 1 will- offwhenthe input is dcactivated (After zero is reached, Output 1 will turn off'turn on when preset 1 is reached. When zero is reached, output 2 and stay off, regardleS of the input condition, until a reset occurs.) Manualwill turn on and output 1 will tum ofK Output 2 will remain reset* will turn off both outputs, if turned on, and reset the time to preset 2.latched on until a manual reset occurs, and the unit will continue to When used as an OFF/ON RECYCLING timer. the total cycle time is equalaccumulate time after zero is reached. This mode also has a input tmcking to the sum of thepreset 2 value andtheprogrammed timed output 2 value. Thefeature where if preset 1 is set to zero, output 1 will turn on when the input is first lobe ofthe cycle will use output 1. The first ON delay value is equal toactivated. and it will tim off when the input is deactivated. (After zero is the difference between preset 1 and zero (this is because output 1 will turn offreached, output 1 will turn offand stay off, regardless of the input condition at zero). The second lobc of the cycle will use output 2. The second ON delayuntil a manual reset* occurs.) When manual resetfr occurs, the unit Will value is equal to the progranm:d timed output 2 value.tt When "RUN" is atReset to Preset 2, and the outputs, if latched on, will unlatch. a low level, time will decrcment. Output I (first ON delay) will activate when

MODE 12 TIMED OUTPUT AT PRESET 1 AND ZERO, MANUAL RESET TO preset 1 is reached. and output 2 (second ON delay) will activate when zero is

PRESET 2, TIME STOPS AT ZERO reached (output 1 will deactivate when zero is reached). The unit will recycle. In this mode, as the unit times down from preset 2, output 1 Will at the end oftimed output 1turn on when preset 1 is reached, and output 2 will tum on wherl 1 - Ilie timed oupur vulue must be len than the vatue nquired zo time»m

zero is reachdd. The outputs will tum off after theirrespective - *. thereset condition to thepreset point Otherwise, the outputwill appear toproglmnmed time values have occurred. Also, the unit will stop timing when be /ctched on.zero is reached. When a manual reset* occurs, the unit will Reset to Preset 1 tt - The maximum ON delay is 99.99 seconds.Manuai reset* will terminate the timed outputs, if the outputs are still turned

Note: Many other modes of operation, roo numerous to mention here, areOn. ' 1 -- possible with the Libra Timer. These "extra" modes of operation are

*-Manual reset. either by front pane! reset (ifenabled) or remote reset. ix accomplished by tying inputs to outputs, by using powerup resetfunctions,

always active, and will override any piesent condirionor xmas ofiketimu: erc.

- . :..'.4 ..:di 411

i

.

'.CMY

TIME RANGE VALUE-»„ -·.- . -***ntt·

Time Range switch settings are sh@Sn'tY&2 rightof the chart belot:.-The/f*time range number corresponds to a binaifcode represented by the DIP switch _334positions. When the switch is up, itis equi*atent to a zero. When the switch is *

--down, it is-equivalent to a one. Th»e time range switch settings can be«eksilyS*served from the front panel by using self-test. At the end of self-test (the thinter of switches shown), the state of these time range switches are displayed.

These time range values must not be changed during normal course of operationbecause of the possibility of erratic operation. A reset must be made after the:.desired range has been selected to lock it into the internal memory.

5678 '

TIME RANGE ZERO 99.99 Seconds .MIlam -/. 'TIME RANGE ONE 99.99 Minutes MliER..

TIME RANGE TWO 99.99 Hours EM'm- I

TIME RANGE FOUR 999.9 Seconds .1891/r

TIME RANGE FIVE 999.9 Minutes IlgliBil

TIME RANGE SIX 999.9 Hours 'MWIWII' .

TIME RANGE EIGHT 9999 Seconds wim m le

TIME RANGE NINE 9999 Minutes :18"12

TIME RANGE TEN 9999 Hours limwm .I

TIME RANGE TWELVE 99 Minutes and 59 Seconds @Rmin 4

TIME RANGE THIRTEEN 99 Hours and 59 Minutes Wgimm *

Note: TIME RANGES 3.7, and ll are not valid ranges.

CONNECTIONS 5 *:

As depicted in the drawing showing *# 2

tile rear view of the Libra Timer, there TBA

..Iare two terminal blocks where all wir- L1 connections are made. The blocks gliti _-_AL_lee f

56 1

,=ican be removed for easy access to theterminal screws. To remove the block, /pull from the back of the block until itslides clear of the terminal block QEIRIAE] ..EHEHHshroud. CAUTION: The tenninal 5,£21

blocks should NOT be removed with · ·· Tee

power applied to the unit. 1 r *:All the DC power and input HY RELAY I | Z 91 RELAY 2

connections are made to the top 1 ff-1 9 49 ff-1terminal block labeled TBA. The AC ECIZ;ISjZEZ;Il,Tn,2--30power and output connections are rvrr'rrint'.:'fr_11made to the bottom tenninal block

labeled TBB. The input connections 7- rwill be discussed first, using the DASHED LINES ARE FOR 2 PRESET UNIT ONLY

drawing as a guide.(The input connections am the samefor l or 2 preset timers.) f

EMC INSTALLATION GUIDELINESAlthough this unit is designed with a high degree of -immunity to

ElectroMagnetic Interference (EMD, proper installation and widng methodsmust be followed to ensure compatibility in each application. The type of theelectrical noise, source or coupling method into the unit may be different forvarious installations. It should be noted that the methods listed below may notbe necessary for every unit installation. In extremely high EMI environments,additional measures may be needed. The unit becomes more immune to EM 1with fewer 1/0 connections. Cable length, routing and shield termination arevery important and can mean the difference between a succeisful installation ora troublesome installation. Listed below are sbme EMC guidelines forsuccessful installation in an industrial environment.

1. Use shielded (screened) cables for all Signal and Control inputs. The shield(screen) pigtail connection should be mide as short as possible. Theconnection point for the shield depends somewhat upon the application.- Listed below are the recommended methods of connecting the shield, in orderof their effectiveness.

a. Connect the shield only at the panel where the unit is mounted to earth . ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually. whenthe noise source frequency is above 1 MHz.

2*

c. Connect the shield to common of the unit and leave the other end of the, shield unconnoted and flsulaied tomearth ground.

2. Never run Signal pr Control cables in the same conduit or raceway with ACpower lines, conductors feedin motors, solenoids, SCR controls, andheaters, etc. The cables should beirun in metal conduit that is properlygrounded. This is especially useful in applications where cable runs are longand portable two-way radios are used in close proximity or if the installationis near a commercial radio transmitter.

3. Signal or Control cables within an enclosure should be routed as far away aspossible from contactors, control relays, transformers, and other noisycomponents.

4. In extremely high EMI environments, the use of external EMI suppressiondevices, such as ferrite suppression cores, is effective. Install them on Signaland Control cables as close to theunitas possible. Loop the cable through thecore several times or use multiple cores on each cable for additionalprotection. Install line filters on the power input cable to the unit to suppresspower line interference. Install them near the power entry point of theenclosure. The following EMI suppression devices (or equivalent) arerecommended:

Ferrite Suppression Cores for signal and control cables:Fair-Rite # 0443167251 (RLC #FCOR0000)TDK # ZCAT3035-1330ASteward #2882029-OAO

Line Filters for input power cables:Schaffner # FN610-1/07 (RLC #LFILO{)00)Schaffner # FN670-1.8/07Corcom #1VB3

Corcom #1VR3

Note: Reference manufacturer's instructions when installing a line filter.5. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.6. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI.Snubbers:

RLC #SNUB0000

DC POWER AND INPUT CONNECTIONSTenninal number 5 on TBA (thefirst renninatpum the k/V, is the +12 VDC

,*ut/output terminal. As an output, this terminal is for sensor supply and canprovide up to 150 mA of' current As an input, an external 11 to 14 VDC supplycan be appplied to this terminal to power the unit in the absence of AC power.Terminal 4 is the common terminal which the common line from the sensor and

-other inputs are coonected. (Do NOT connect relay common or solid-state,:output common to this point) Terminal 3 is the run terminal. When the signal at-this terminal is pulled low (ze,0 vole), time will accumulate on the display.

Terminal 2 is the Program Disable (PGM. DAS.) terminal. When this terminal is. at high level (+5 F), the Preset value (s) and timed output value(s) can be

C changed using the front panel buttons. (Outputs can alio be tested during se(A' test. See "Sef-Tat" secrionforfu,·ther detai'Le When terminal 2 is at a low

level (connected to COMMOM, changing these values and' testing of the- outputs is no longer possible. Terminal 1 is the Remote Reset terminal. When

this terminal is at a low level (connected to COMMOAO, the unit will reset, theoutputs will tum off (f activated). As long as reset is low, the unit is held at

., reset.

AC POWER & OUTPUT CONNECTIONSAs mentioned before, AC power and output connections are made to the

bottom tenninal block, labeled TBB. Primary A.C. power is connected toternina 1 andl (marked A.C. Power, located on the left-hand side of terminalblock TRB). For best results, the A.C. Power should be relatively "clean"andwithinthe specified *10% variation limits. Drawing power from heavily loadedcircuits or from circuits that also power loads that cycle on and off, should beavoided.

Terminals 3,4, and 5 are used to connect to tile output relay 1. Terminal 3 isthe normally closed contact. Terminal 4 is the normally open contact. andTerminal 5 is the output relay common. Terminal 6 is an output common usedfor the solid-state outpugs). This terminal should NOT be used as the commonfor the input or control terminals. Terminal 7 is the current sinking output 1Babeled OMNK.). Thid internally connects to an NPN Open Collectoruansistor. The remaining terminals are for the dual preset version of tile Libratimer and serve the same functions as those for the single preset unit. Terminal8 is current sinking output 2 (labeled 02-SNK.). Terminal 9 is the normallyclosed contact of relay 2. Terminal 10 is the normally open contact. Tenninal 11is thc output relay common.

4

FRONT PANEL-FUNCTION'DESCRIPTIONiThese units employ six frontpaAl bilit for 6onti61 andkaiA enteringS'Ihe

button Amotions amdescribdbdi63!SS',EIE5,E,24,4W.4.RESET "R" -This buttonresets thecounter to>ither zero or preset, depending

on the mode of Qperation selebted»foi'this.b6£on:to operate, the

enable/disable reset button switch, at the raarAfahnirmusi be set to tileenable BM position. This button is also used in conjunction with the twopreset buttons (one button on the sing/epreset unit) to view and change thetimed output value. (lphen reset if activated, a// pivcsa an stopped orinfenipted. LE. outputs mni €g tbne stops,Y«plaq 29 *364 etc.) Iltis isthe case under any mode of operation,.or any data entry mode.

PRESET Upl" ("P27 - The preset buttons are labeled and are the two left-hand buttons of the top row, located on the front of the unit. for the singlepreset unit. theteft-mostbuttonisthepreset button.) Wligathe "Pl"buttonis pressed, preset 1 is displayed. When the "22" Ofavailable) button ispressed, preset 2 is displayed. These- values will remain displayed forapproximately 10 sec. after release ofthe button. Also, the preset buttons areused in conjunction with the reset button, to view and change the timedoutput values. (See "To Enter.4 New 7Tmed Output Value"section.)

ENTER UE" - This button is used in the "Preset Enter" mode and in the

"7Dned Output Enter" mode. After the desired value is obtained on thedisplay, this burton is pressed which then enters the value into the internalprocessor. This new value, at that instant, is used in the processing of presetor timed output values. "E"isalsousedatthe end ofsclf-test to exit self-test.

TO ENTER A NEW PRESET VALUEFIRST: Press "Pl" (or "P2", ff a two praget unit). This will displaythe

respectivepreset value and it will remain displayed for approximately 10 sec.after release of the last button pushed. (At this n'me, preser displaymodecanbe exited without change. by pressing the "E" button.)

SECOND: Once the preset value is displayed, changing the digit value can bedone by pressing the button directly beneath the digit position to be changed.(This value cannotbechanged when "PGM. DIS."is activated.) Each timethe button is pressed, the digit will increment by one. Also, pressing andholding the button will continuously scroll the digit from 0 through 9, thenback to 0 again. When the desired value for that digit is reached, release thebutton. Do this for all the digits to be changed.

THIRD: Press the "E" IEnred button to enter the value into the unit's memory.As soon asthe "E " button is pressed, this new value is used as the operating

data. This means, if the preset value is entered, and the old or new valuc hall.not been reached, the new value will be used without process disruptiod(Preset on thely). If the "E" button is not pressed within 10 sec. after thelast digit has been changed, the value will disappear (go back to normaldispiq mode) and the unit will continue to operate on the previous value.During the displaying, changing, and entering of a new preset value, allfunctions of the unit are operational, such as, timing, resetting, outputs firing,etc. Note: For RIP modes of operation, "Pl " ("P2" for dual preset units)witt determine the "Start Count" value of each cycle.

TO ENTER A NEW TIMED OUTPUT VAI,UEFIRST: Press andhold the "Pl" (or '72':fortwopresetuMits) button and then

press the "R" (Reset) button. At this time, the respective timed output valuewill be displayed and will kmain displayed for a#proximately 10sec. afterrelease of the last buttonpushed. (Arthistime, the,imedoutput displaymodecan be exited without change, by pressing the "E" button.)

SECOND: Once the timed output is displayed, changing the digit value can bedone by pressing the button directly beneath the digit position to be changed.frhis value cannot be changedwhen "PGM. DIS." is activated.) Each timsthe button is pressed, the digit will increment by one. Also, pressing andholding the button will continuously scroll the digit from 0 through 9, thenback to 0 again. When the desired value for that digit is reached, release thebutton. Do this far all the digits to be changed. (mis value can be setberween .Olsec and 99.99 sec.)

THIRD: Press the "E" (Enter) button to enter the value into the unit's memory.As soon as the "E" button is pressed, this new value is used as the operatingdata. If the "E" button is not pressed within 10 sec. after the last digit hasbeen changed, the value will disappear (goback tononnal dirplay mode) and the unit will continue to operate on the previous value. During thedisplaying, changing, and entering ofa new timed output value, atl functionsofthe unit are active, such as timing, resetting, output firing, etc. without anyinterruption.

-I.- . --*4,+rd.

a..:"12819- L23:551

*SEEF,1 tul£6>,This unit has a built-in, self-:st,8**'whi*h-,42=*%*hout .,

1 ':tfjesi#tinic, preset values, missing preset.points;-timEd,StEYBiwatigns, or:'interf4%;ith Zontrol Ainctions. Witi;1NN8, all diits are cycled thr6ugh,ZiNSAh;mode select, the power up reset, and'tlle.time range switch settings arc

displayed Un thar orded, During the displayofthCinode selectswitcllsettings,the outputs can also be tested.

To enter self-test, press the two upperright-hand digitbuttons (located on thefont pond), simultaneously. At this time, whatever time value was displayedwill disappear and be replaced by a string of four zeros. This will be shown forabout halfa second, then a string of ones will appear for the same time'duration.Following these, a string oftwos and so on, up to nine will be displayed. Afterthe nines are shown, three decimal points will appear. After this portion, anihterlace pattern 6f the same numbers will be shown. First a combination of 1,0,·.1,0 tien 1,2,1,2 and so on, until all digits from zero to nine have been

, di*lai,eci. ,The next portion of self-test will display a group of ones and zeros. These

ones and zeros are the settings of the mode select switches (thefour le#-handDIP switches only). This pattern directly corresponds to the numberrepresenting the mode of operation. If the switches are changed while at thispoint in the self-test, the settings can be seen to change. These changes will notaffect counter operation immediately, but any changes will take effect whenself-test is exited. When the switch is "DOWN", the display will show a one.When the switch is "UP", tile display will show a zero. If no testing of the

- outputs is required, press the "E" button until the unit advances to the nextdisplay Ohe unitwill nextshow the power-up reset DIP switch setting). Also.

:if no activity occurs on the switches or the front panel buttons within 18 sec.* after the unit pauses at the mode switch display, the unit will automaticallyT advance to the next display.3* During the time the mode switch settings are displayed, the outputs can bef 'tested. To activate the outputs, press the "Pl" button gor dual preset version,*4 "Pl" or "PZ"is pressed).

, Note: The "PGM. DIS." terminal must beata highlevelfor the outputs tobe

acrivated Atio, caution should be used when testing the outputs. so as not tocauseany undesirable orhazardousconditionsinthesystem. go turn ofthe: outputs, release the button.) If the outputs are not tested. the state of the

outputs wUZ nmain the same as it was p,Yor to sel/:test If the ouiputs aretested in self-test the outputs will be turned oll-after witingself-tenAfter the display of the mode switch settings. the state of the power-up reset i

DIP switch is shown. If the display shows a zero, then power-up reset is"DISABLED". Ifthe display shows aone, then power-up reset is "ENABLED"which means the unit will reset itself when input power is restored. As with theprevious DIP switch settings, the unit will go on to the next display if no activityoccurs on the switches or the front panel buttons within 18 seconds afterentering the power-up reset display section. (Pressing "E" will also cause rheunit to advance to the next display)

The time range DIP switch settings are displayed next This pattern directlycorresponds to the number representing the time range value. If the switches arechanged while at this point in self-test, the settings can be seen to change. Thesechanges will not affect timer operation immediately, but any changes will takeaffect when self-test is exited. When the switch is "DOFFN", the display will

show a one. When the switch is "UP", the display will show a zero. Press the"E" button until the unit exits self-test (71ie unit wiN go back ro displaying thetime). Also, if no activity occurs on the switches or the front panel buttons;,within 18 seconds after the unit pauses at the time range switch display, the uidtwill automatically exit self-test.

Rapid advance of the self-test routine can be done by pressing and releasingany of the front panel buttons except f6r the "R" button. (Pressing '72" aranytime. except when entering the timed output mode, will reset the unit.) ,

INITIAL POWER-UP & FACTORY SETTINGSWhen the unit is shipped from the factory, the values and following modes

are set as shown.

Preset 1

Preset 2

Time value

Timed output values

05.00

10.00 (if a dual preset version)0.00

00.10 second

DIP SWITCH SETTINGSAll switches are moved up to the "UP" position except for the front panel

reset enable switch, which is moved "DOWN". With the switches set in thesepositions, tile unit is operating in mode zero (larch prese:(s), manual reset rozero. ame stops at preset 2). The th range value is 99.99 seconds and thepower-up reset is disabled.

- Ill.-

d GASKET -. '· · -5:E-Msy£*:-. . .·-te :c.'y:f< 22i@INSTALLAT/ONlijoi.1 /- ExisT,Na pL;4 -i.-52ER The Libra counters and timers are designed to be panel-mounted with a·- THICK ,. 1 (3.10 - 6.4MMOTHICK .22-:*r.125*-0.25' . *' W?'2*gasket to provide a water-tight seal. Two mounting clips and screws are

· -«: ·· 9- :01'.,.5provided foreasy installation. Consideration shouldbe given to the thicknessr:,,4. i. . ofthe panel. Toothinofa panel may distort and notprovide a water-tight seal...r,Bi,: .· (Recommended minimum panel thickness is 1/8".)

LMJFL -- After the panel cut-out has been completed and deburred, carefully apply

-2 c **11.·'.: *p**#4645-94/jji,- depicted in the drawing (at right), install the screws into the narrow end ofthe:%* 25: .18@i. "'4TA*3*617-/" *,10-3 2.-mounting clips. Thread the screws into the clips until the pointed end justMCS;% = 4 protrudes through the other side. Install each of the two mounting clips byPLACES -,»' f33'*'-='- 4 F

EXISmNG PANEL®,1' inserting the wide lip of the

2 f ts,I 442· tiS·555£6'zie,Hih*=47 1 ., .0' Cclips into the front end of the .125' - 0.25-

r - :* Y«;.**KS?Zt . ,• .« ihole, located on either side of GASKET3.18 - 6.4mm) THICK. .6 the case. Then snap the clip 3:?4 - -CUT-AWAY-,m -' onto the case. Tighten the /'-ZZ-><' WEW OF

' ..Inu screws evenly to apply uni:forrn / \CASE_. ··-* compression, thus providing a- 28 E11

., water-tight seal. Caunon: Only -

419- MinGCUP MOUNTING /

e. minimum pressure is required

2·PLACES - to seal panel. Do NOT over- MOUNTING - /- . tighten mounting scravs.

SCREW

APPLICATION FOR DUAL LEVEL PRESET LIBRA TIMER

CURING/DRYING PROCESS CONTROL rIn a typical manufacturing curing/drying process, it is required to control +

the duration of time heat is applied to the items within an oven. These items ,are to be heated at a high temperamre for a long period of time (30 minutes).At the end of the curing/drying process, the heat is turned ofrand an indicator *light is turned on, signaling rhe unloading attendant. The dual preset Libra t.timer will satisfy all these requirements.

The Libra timer is first set to minutes time range, which is time range 9./4 the mode switches are set to Mode 0 (Latch Outputs at Presets, Manual ,ct to Zero, Time Stops at Preset 2). Mode 0 is used because the outputs

must latch on when the presets are reached (When the outputs latch on, theheaters de<nergize). Also, the time increments will stop at preset 2. Thepower-up reset switch is set to "Enable", which causes the unit to start thecycle over in the event of an input power loss (when enabled, the unit will

reset itself when input power is restored). The front panel reset button"EN./DIS." switch is "Disabled" to prevent accidental resetting (restarting) ofthe cycle. The "REM. RST." terminal is connected to a remote reset buttonlocated at the. loading end of the oven. The "PGM. IMS." and the *'RUN"terminals are tied to the *'COMMON' terminal. With "PGM. DIS." tied low

(this is done after preset 1 is set to 3 minuies and preset 2 is set to 33 minutes),the heating time periods cannot be changed. "RUN" is permanently tied low,which causes the unit to increment time (when Preset 2 is reached, Mode 0will cause time accumulation to stop). The nonnally closed contact of Relay1 is connected to the high temperature heater and the normally closed contactof Rclay 2 is connected to the low temperature heater. The operation sequence -is as follows:

The operator/attendant wheels a rack of items into the heating area (oven).Once the oven doors are closed, the operator/attendant presses the remotereset switch which starts the heating cycle (both high and low temperatureheaters are aimed on at this time). After three minutes have elapsed, output 1

fires, which opens the ndrmally closed contact of Relay 1. (This turns off thehigh temperature heater.) After 30 minutes have elapsed, output 2 fires, whichstops tile time accumulation and opens the nomnally closed contact of Relay2. (This turns offthe low temperature heater.) Also, the normally open contactof Relay 2 closes, which then turns on the Indicator light. Chis signals theunloading attendant that the process is complete.)

.ef

·»:

'P

Gu:.54

ART#7 i b

LOAOING END

[NOICATOR

LIGHT

4-ir- ENDUNLOADING

ime :wy

5

TIIdE - tai-5-255#

S6

*1*ly .MUU,il'vit'!!i;LIBRA 95 i 5 Ei tiTIMER *B 5 x o xREAR *20 VIEW

---"= 4:*

3K Mi H i *49A444#444477

,

TO HIGH

TEMPERATUREHEATER

r

TEMPERREHEATER

ORDERING INFORMATION

PART NUMBERS FOR

. MODELN DESCRIPTION AVAILABLE SUPPLY VOLTAGES23DVAC 115VAC

LIBT1 Single Preset LCD Ubra.Timer -5-E- '· LIST1O1O LIST 1000UBT2010 LIBT2000LIBT2 - - , Dual Preset LCD Ubra Timer , .

LIBTl E Single Preset LED Ubra Timer UBTl E10 LIBTl EOO- r¥631'1.2LIST2E Dual Preset LED Ubra Timer UBT2610 LIBT2EOO

For more information on Pricing, Enclosures & Panel Mount 15rio the RLC Catalog or contact your local RLCdistributor.

i.

NS

DDITIONS TO LIST - LIBRA SERIES T'EMC Installation Guidelines

Although this unit is designed with a high degree of immunity toElectroMagnetic Interference (EMI), proper installation and wiring methodsmust be followed to ensure compatibility in each application, The type of theelectrical noise, source or coupling method into the unit may be different forvarious installations. It should be noted that the methods listed below may notbe necessary for every unit installation. In extremely high EMI environments,additional measures may be needed. The unit becomes more immune to EMIwith fewer 1/0 connections. Cable length, routing and shield termination arevery important and can mean the difference between a successfuLinstallation ora troublesome installation. Listed below are some EMC guidelines forsuccessful installation in an industrial environment.

.- 1. Use shielded (screened) cables for all Signal and Control inputs. The shield(screen) pigtail connection should bc made as short as possible. Theconnection point for the shield depends somewhat UpOn the application.Listed below are the recommended methods of connecting the shield, in ordero f their c ffectiveness.

a. Connect the shield only at the panel where the unit is mounted to earthground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually whenthe noise source frequency is above I MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.2. Never run Signal or Control cables in the same conduit or raceway with AC

power lines, conductors feeding motors, solenoids, SCR controls, andheaters. etc. The cables should be run in metal conduit that is properlygrounded. This is especially useful in applications where cable runs are longand portable two-way radios are used in close proximity or if the installationis near a commercial radio transmitter.

3. Signal or Control cables within an enclosure should be routed as far away aspossible from contactors, control relays, tensformers. and other noisy

omponents.n extremely high EMI environments. the use of external EMI suppression

devices, such as ferrite suppression cores, is effective. Install them on Signaland Control cables as close to the unit as possible. Loop the cable through thecore several times or use multiple cores on each cable for additionalprotection. Install line filters on the power input cable to the unit to suppresspower line interference. Install them near the power entry point of theenclosure. The following EMI suppression devices (or equivalent) arerecommended:

ADEN104X

EFFECTIVE 7/96

IMERS (LCD & LED)

Ferritc Suppression Cores for signal and control cables:Fair-Rite # 0443167251 (RLC #FCOR0000)TDK # ZCAT3035-1330A

Steward #28B2029-OAO

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC #LFIL0000)Schaffner # FN670-1.8/07

Corcom #IVB3

Corcom #IVR3

Note: Reference manufacturer s instructions when installing a line.Biter.5. Long cable runs are more susceptible to EM! pickup than short cable runs.

Therefore. keep cable runs as short as possible.6. Switching of inductive loads produces high EMI. Use of snubbers across

inductive loads suppresses EMI.Snubbers:

RLC #SNUB0000

Specifications15. AGENCY APPROVALS:

EMC EMISSIONS:

Meets EN 50081-2: Industrial Environment.

CISPR 11 Radiated and conducted emissionsEMC IMMUNITY:

Meets EN 50082-2: Industrial Environment.

ENV 50140 - Radio-frequency radiated electromagnetic fieldENV 50141 - Radio-frequency conducted electromagnetic field 1EN 61000-44 - Electrostatic discharge (ESD) 2EN 610004-4 - Electrical fast transient/burst (EFT) 1EN 610004-8 - Power frequency magnetic field

Notes:

1. Unit required a line-filter (RLC #LFILOOO[)) when DC powered. Apply DC .Power through the line Jilter to TBA terminals 5 (comm.) and 6 (+ 12 YDC).Connect alt other UO Common returns to TBB terminal 6 (comm.).

Test: EN 61000-4-4 EFTand ENV 50141 RFConducted immunity.

Refer to the EMC Installation Guidelines for additional information.

.

r,-

RED LION CONTROLS

. fBULLETIN NO. CU83T/R-FDRAWING NO. LP0122

REVISED 10/96

INTERNATIONAL HEADQUARTERS . EUROPEAN HEADQUARTERS

Willow Springs Circle. York. Pa. 17402, (717) 767·6511 FAX: (717) 764·0839 892 Plymouth Road. Slough, Berkshire SL1 4LPIieb site- http:i/www.redlion-controls.com E.mail· [email protected] ENGLAND *44 1753 696888 FAX: +44 1753 696339

MODEL CU83T & CU83TR - GENERAL PURPOSE MINIATURE ELECTRONIC TIMERS

. 5!/2-DIGIT TIMER ACCUMULATES TIME IN HOURS. 1/10 HOURS.1/100 HOURS, OR 1/10 MINUTES

. OPERATES FROM EITHER SWITCH CONTACT. 10 to 130 V OR 60

to 260 V (AC 50/60 Hz or DC) INPUTS

.

1.1-

DESCRIPTION

The CUBJT's :,re si:,te-of-m·l products of Micro-Electronie tedinologyThey open up a #,·ide wiriety of new timing applica,lion possibilities that, untilnow, were economically impractical

The CUB3T is designed lo be used as an hour. tenth hour. hundredih hour ortenth minute meier for continuous time measurement applications and is not·.resenable. The CUB3TR is a standard CU83T which is user resettable. Both

models accumulate time and display it on the 57-digit LCD. The CUB3T'sdisplay will wrap :tround from a filll display of 199999 to 00000 when an over-

-,Dow occurs. An indicator. resenibling u colon (located to the leR ofthe display),

11 blink (along with fhe decimal point except the hours meted whenever the•-nmer is actuated. All timers are factory reser to indicate zero. The reset feature

of the CUB3-1'R allows the user to periodically measure elapsed time. TheCUB]T, on the olher hand. is ideally suited for measuring total run time.

Application of the CUBJT is simplicity itself. Its rugged rcinfurced nyloncase snap·fits into a standard rectangular opening without screws or ocherhardware. Hook-up is simply :1 matter ofeo,Inecting two wires (four wires for

CAUTION: Read complete instructions prior toinstallation and operation of me Ii,ill.

ORDERING INFORMATION

MODEL NO.

CUB3T

CU83TR

CAUTION: Risk of electric shock.

DESCRIPTION

CUB3 Timer Conlact. 1 hr.CUB3 Timer Conlact, .1 hr.

CUB33 Timer Contact. 01 hr.

CUB3 Timer Contact, .1 min.

CUB3 Timer 10-130V, 1 hr.CUB3 Timer 10-130V, .1 hr.CUB33 Timer 10-130V, .01 hr.

CUB3 Timer 10·130V, .1 min.

CU83 Timer 60-260V. 1 hr.

CUB3 Timer 60-26OV, .1 hr.

CUB3 Timer 60·260V, .01 hr.

CUBS Timer 60-260V, .1 min.

. CU83T Resetlable Contact, 1 hr.

CU83T Resettable Contact, .1 hr.GU83T Resettable Contact, .01 hr.

CU83T Resettable Contact. .1 min.

CUBST Resettable 10 to 130 V. 1 hr.CUB3T Resettable 10 10130 V, .1 hr.

CU83T Resettable 10 10130 V. .01 hr.

CU83T Resettable 10 10130 V, .1 min.CU83T Reseltable 60 to 260 V, 1 hr.CU83T Resettable 60 to 260 V. .1 hr.

CU83T Resettable 60 to 260 V. .01 hr.

CU83T Resellable 60 to 260 V, .1 min.

PART NUMBER

CU83TOOO

CUBGT010

CUBGT020

CUMT030

CU83T1 OO

CU83T110

CU83T120

CUB3T130CU83T200

CU83T210

CU83T220

CU83T230

CU83TROO

CU83TRO1

CU83TR02

CU83TR03

CU83TR 10

CUETR11

CU83TR 12

CU83TR13

CU83TR20

CUBBTR21CU83TR22

CU83TR23

. SELF-POWERED WITH INTERNAL UTHIUM BATTERY FOR UPTO 10 YEARS OF CONTINUOUS OPERATION

. AVAILABLE IN RESETTABLE AND NON-RESETTABLE MODELS

. EASY SNAP-IN MOUNTING IN 1" X 2" (25 mm x 50 mm) PANELOPENING

. IDEAL FOR PORTABLE, MOBILE, OR STATIONARY INDUSTRIAL EQUIPMENT

0 WIDE TEMPERATURE RANGE (-30 to +75°C) C€ 6

lite CUB3TR). No external power source is required since the internal lithium

battery provides up 10 10 years of uninterrupted service. in addition [0 these

advantages, the CUInT oiltrs Ihe integrtiled circuiliy, embedded in a singlemonolithic, silicon micro-chip.

DIMENSIONS "In inches (mm)" & INSTALLATION

:/5:i...3..9;0-13 SIBEZEL

4-t. PROTRUSION FROU

I. f tp/&/- PANEL FRONT

«/5(24.21

110- 8009

PANEL

BEZEL 1 /

CLASP

PA=RE:PANEL TH,CKNE35:

05'TO.,25

STRAIH

RELIEF

SPECIFICATIONS1. DISPLAY: 514-Digit, LCD, 0.2" (5. imm) Hih.2. POWER: 3 Volts supplied by a non-replabable lithium battery. Nominal

battery life is 10 years.3. RESET: h · , f

CUB JT: This version is a non-resettable timer.

CUB 3TR: A contact closure between the bl4ck and blue wires,cgnnects the 9 ·internal limium battery to the CUB3TRWircuitry. To resel<Ille'CUBJTR,

motnentarily break this connection. K,pfef up reset willcur. * :,4. S[GNAL INPUT:

Contact Versions: Switch Contact or SolidrS[ate Transisior Switch.«Contact

bur(led 6 pamps max. A closed switch will actuate the timer.

10 to 130 V Versions: 10 V min. to 130 V max. AC (50/60 Hz) or DC. Inpul

current 150 ;tamps max. Voltage applied to the inputs will actuate thetimer.

60 to 260 V Versions: 60 V min. to 260 V max. AC (50/60 liz) or DC. Inputcmrent 150 pamps max. Voltage applied to the inputs will actuale thetimer.

5. OPERATING TEMPERATURE RANGE: -30° to +75°C

6. ACCURACY: 0.025%

..,

SPECIFICATIONS

7. CERTIFICATIONS AND COMPLIANCES:

EMC EMISSIONS

Meets EN 50081-1: Residential, Commercial, and Light IndustryCISPR 11 Radiated and conducted emissions

ERIC IMMUNITY:

Meets EN 50082: industrial Environment.

ENV 50140 - Radio-frequency radialed electromagnetic fieldENV 50141 - Radio-frequency conducted electromagnetic fieldEN 61000-4-2 - Electrostatic discharge (ESD)'EN 61000-4-4 - Electrical fast transient/burst (EFT)

EN 61000-4-8 - Power frequency magnetic fieldNofe:

j. This unit hcix cin exposed LCD display. Therefore m avoid eleclms:aticdischalze in smtie environments ubove 4 KK zinti-static precautionsshould be obsen·ed befoi·e touching the display.

Relt· to [he EMC Installalion Guidelines qf thir bulletin ®r additionalinformation.

8. WEIGHT: 2 oz (56.7 g)

EMC INSTALLATION GUIDELINES

Although this unit is designed with a high degree of immunity toElectroMagnetic Interference (EMI). proper installation and wiring methodsmust be followed to ensure compatibility in each aliplication. The type of theeleclrical noise, source or coupling method into the unit may be different forvarious installations. Cable length. routing and shield termination are vcry

important and can mean the difference between a successful or a troublesomeinstallation. Listed below are sonie EMC guidelines for successful installationin an industrial environment.

1. Use shielded (screened) cables for all Signal and Control inputs. The shield(screen) pigtail connection should be made as short as possible. Theconnection point for the shield depends somewhat upon the application.Listed below are the recommended methods of connecting the shield, inorder of their e frectiveness.

a. Connect the shield only at the panel where the unit is mounted to earthground (prolective earlh).

b. Connect the shield to earth ground at both ends of ihe cable, usually whenthe noise source frequency is above I MHz.

c. Connect the shield to common of the unit and leave the other end of the

shield unconnected and insulated from earth ground.2. Never run Signal or Control cables in tlic fame condilit or raceway with AC

power lines, conducturx fucding motors. solenoids. SCR controls. andheaters. etc. The cables should be run in metal conduit that[ is properlygrounded. Tlils is especially useful in applications where cable runs are longand portable two-way radios are used in close proximity or if the installationis tiear a commercial radio transmitter.

3. Signal or Control cables within an enclosure should be routed as far away aspossible from contactors, control relays, transformers, and other noisy

components.

4. In extremely high EMI enviromnents, the use of extemal EMI suppressiondevices. such as fcrrite suppression cores, is effective. Install them on Signaland Control cables as close to the unit as possible. Loop the cahle throughthe core several times or use multiple cores on each cable for additionalprotection. Install line filters on the power input cable to the unit to suppresspower line interference. Install them near tlic power cn(ry point of theenclosure. Tile following EM 1 suppression devices (or equivalent) arerecommended:

Ferrite Suppression Cores for signal and control cables:Fair-Rite # 0443 167251 (RLC #FCOR0000)TDK # ZCAT3035-1330A

Steward #2882029-OAO

Line Filters for input power cables:Schaffncr # FN610-1/07(RLC #LFIL0000)Schaffner # FN670- 1.8/07

Corcom # 1 VR3

Nofe.: Reference mant,factwer's insinictions when insmiling a line jllter.

5. Long cable runs are more susceptible to EMI pickup than short cable runs.Therefore. keep cable runs as short as possible.

WARNING: Lithium battery may explode ifincinerated. Input voltagemust not exceed 3.0 VDC on contact versions or maximum rated

voltage versions to prevent damage to the battery.

CAUTION: The black and blue leads to the CUB3TR1's and

CU83TR2's will be at Ihe same line potential as the input leads.

-

-

ELECTRICAL CONNECTIONS & INPUTS

The CUB3T's can be supplied with input signals from mechanical switchcontacts L solid-state switches (NPN or PNP fransiwors) as shown in the

diagrams below. Reed switches. mercury-wetted contacts. snap-action limitswitches, and silver alloy contacts with wiping action are usuallysatisfactory choices for mechanical switch input. Heavy "clapper-O,pecontacts such as used in contactors or large machine tool relays. tungsten contacts, or brush typc contacts are not recommended as count inputdevices.

Signal input leads can be almost any type of electrical wiring for thc"CONTACT" version. "VOLTAGE' version input wires must have the

proper insulation as required by electrical codes. All conductors shouldmeet voltage and current ratings for erich terminal Also cabling shouldconform to appropriate standards of good installation. local codes mid

regulations. It is recommended that power supplied to the unit (AC or DC)be protected by a fuse or circuit breaker.

- Volfage Connections VOLTAGE

· „ WORN r irc OR DC; 1cue,r:· 9(-l ORN/WHT

I .OR YEL

Confac# Conneclions

CUBBT

Reset Connections

CUeSTR

WIRED

(-I WHT

(t) BLUE

2-1 BLK

C*1[W, r*sMOR

c8Wf& ,=NiON4 ,

SWITCH CLOSED-POWER ON

TYPICAL APPLICATIONS

An equipment rental company chnrges customers by the hour tiir Ilicrental of forktrucks or other heavy equipment. To help determine theamount to actual run time. a CUB3TR000 is connected to a spare set ofcontacts on the ignition switch of Ihe forkinick. When the switch is in the"RUN" position. the "Red" and "ff'hife" leads of the CU83TR areconnected, which cause it to accumulate tiine iii hours on the display. Therental company simply resets the CUB)TR by momentarily opening theconnection between the "Black " and "Bhle " leads before each rental

period. The normally closed "RESET" button should be protected toprevent Inml,ering by tlic clistoilier.

'+

CUBSTMOO

2 .ty'

r

1 OFFO +OSTART

RED

WHT

1--RESETBLUE KOLK

A machine shop manager charges customers for machine lime by tlichour. He is also interested in tracking ninchitic rim time vs. down time. ACUB3TI 10 connected across the 115 VAC spindle motor of a drill presswill serve both purposes. A reading taken before and after each job willindicate the actual machine run time in tenth hour increments. A reading atthe beginning and end of each shift will indicate total run time. allowing themanager to evaluate production efficiency and down time.

CU83 T·110

ORN MOTOA *» MACHINEORN/WHT

RED LION CONTROLSINTERNATIONAL HEADQUARTERS20 Willow Springs Circle, York. Pa. 17402. (717) 767-6511 FAX: (717) 764-0839Web site- htip://www.redlion-controls.com E-mail- [email protected]

INSTALLATION FOR BASE MOUNT KITS

BMK 1 BMK IA

11 \ /<11

Four Base Mount Kits used in conjunclion with Lic Cub Counter Scrics arcavailable Lo replace almost a existing miniature and general purpose electro·mechanical counters on the market today. Two Base Mount Kits are designedfor the CUBI (BMKt and BMKIA), one for the CUB2 (BMK2), and one forthc CUB3(BMKS). Thekits arecoated with adurable flat black polyurethancfinish.

'llic counters are easily installed by sliding the unit into the base mount

0

EUROPEAN HEADQUARTERS892 Plymouth Road, Slough. Berkshire SL1 4LPENGLAND +44 1753 696888 FAX: +44 1753 696339

BULLETIN NO. BMK-A

REVISED 183

BMK 2 BMK 5

l«///7enclosure until the spring clips engage in the slots on the side of Ihc case.

The connecting wires can either be brought through [he panel on which Ihcunit is mounted, or through a hole in the enclosure itself. A grommct isprovided to insertin the hole on thebase mount (where applicable) when wiresarc routed through it. A plug is provided to close the hole when this option isnot used. The plug and grommci arc provided in the accessory bag with eachbase mount unit along with four nuts and bolts for mounting.

INSTALLATION

For installation, acc Figurc 1 and follow the procedures below.a NOTE. InsmU.nion for all basl mounts and coumers are basically die same.

..

7 1. Slide the panel gasket (Provided in me accessog bag wit/: the CURcolmier) over the back of the counter (CUBl mid CUB2 ONLYO.

2. Attach two mounting clips to the side of Ihc counter with two scrcws.(Clips and screws are provided in {he accessoly bag of the CUBI andCUBZ counlers ONLY. The CUB3 does not requirectips and screws.)

3. Mount thc base mount enclosure to the panel or frame as applicationrequires. l'our bolts and nuts are provided with the Base Mount Kil.

4. If the hole in the base mount is uscd, install the grommct into the holeand pull the external signal wires from the count switch or sensor (andremofe resi·/ (fused) into the enclosure through the grommct.

If wires enter through the existing panel or frame and back of the basemount unit, close the hole in the base mount with the plug.Both grommet and plug arc provided in the accessory bag with ihc BaseMount Kit.

5. Cut the wires from the CUB to a length of aboOt 5" and make wirc nulconnections to the incoming wires. (Wire nuu are provided with the CUBI

and CUBC ONLY.)

6. Fold excess wire into the rear of thc base mount while sliding thecounter body into the enclosure until the spring tabs snap out to engagein the slots in ihe side of the case.

COUNTER /i(CUB 2 shown) \

BASE MOUNT

fl liSPRING TAB , 1 ..659(021 -.

/0

{53\<4441PANEL GASKET 4 + 4.EXISTING

SLOT m. ff.: PAN E L'

/

WIRE HOLES --FIGURE 1

BMK 1

BMKlA

-F1 .69' (1753'm)

L

t.13"

1 (3.31rm)

BMK 2

1.360'

(34.54.m)

BMK 6

rne

C

.27"

{606-)

09'

/2 2-9-m]

-rr -y l)148:.1 (245)

1=1-Ijjj 11'84'(461Ii %1

14.-1 -1.74- 144.2--1-|4-1.12(28.45..1-4|

*S--1,9"(48.25.-I-

1.0"

(254.nm)

1 1(44.45 -4

/11.BIO"

(33.27mm)

8-

.

.89-

(22.6mm]

*---I. 84"{46.74mm)---2-1.9"(48.26-m)-

2.25'(51:15mn)

2.56"(65.0211

182-30mi

(9s:Rl,m)

/01://mi

2700"[70.(Irnm)

2.I mi 01.34#m)

1.75"[4445,m)

-/125.120.58..1-4

.3:29 -CnIM

--1+1

2.0. (50 amm)

(2413.4

1 /#

1 I c:.'.Mli

CUM*

-8-

S-

.

6.

33- (830mnd

150 (3.61mmt

+

\Q

+

C

DIMENSIONS

. 115,75.4/-- 7£.41

119.05mr)

19 65mm).38

2.63*(66. Bmml

*6(671*-42;1*1

7.880/

[22.35 mm)

-

(2.5•mm)

19.65mm).38'

2.61(66.Bmm)

175

(44.-Smrn)

-m=-1

-r.,0-(els-

19.r-C

-,s21:m#Fit.75'

[44.45mmi

2.2£ (SZmml

3

REPLACES

Duralit Miniature

Electric Counters

4Y & 6Y Series

REPLACES

Veeder Root Series

1205,1981,7443,7995 & 7997Durant Electric Counters Series

Y-RMF, Y-MF, YB, 6-CS & 54000

MS

REPLACES

Veeder Root Series

7437 & 7438

REPLACESDurant Miniature

Electric Counters

4Y & 6Y Series

1..

.

.

1

Operating HandlePoignee d'actionnementBedienungshebel

Mando operativoManipulo de accionfimento

Maniglia di azionamentoCat 194R-HS1, -HSlE (TYPE 1-IP42)Cat 194R-H54, -HS4E (TYPE 3-3R/4/4X/12 - IP66)

5

ATI'ENTION: To prevent electrical shock, disconnect from power source before installing or servicing. Installin suitable enclosure. Keep freefrom conuminants.ATTENTION: Prdalablement a l'installation et aux opdrations de service. couper l'alimentation secteur pourempecher louts chocs dlectriques. Installerdans uneboire appropride. Protegerle relaiscontreles conmminants.ACHTUNG: Vor Installations oder Servicearbeiten Stromversorgung zur Vermcidung von elektrischen Unflillentrennen. Die Gerate mussen in einem passenden Gebause eingebaut und gegen Verschmulming geschutzt wer{len.ATENCION: Descondctese de la corriente el,Ectrica. antes de la instalacion o del servicio. a fin de impedirsacudidas eldcuicas. Instatelo en una caja apropinds Mantdngato libre de con[aminantes.ATENCAO: Para evitar choques, desconectar da corrente elktrica antes de fazer a insual*o ou a manutengao.Instalarem cain apropriada. Manter livre de contaminantes.ATIENZIONE: Per prevenire informni, togliere tensione prima dell'installazione o manutenzione. Installare incustodia idonea. Tenere lontano da contaminand.

Mount Handle On a Flat Surface For Type 3, 3R, 4, 4X and 12 EnclosuresPour les coffrets de types 3,3R, 4,4X et 12, monter la polgnee sur une surface platteFur gehause typ 3, SR, 4,4X und 12 hebel auf ebener flache montierenMonte el mando en una superficie plana para las cajas del tlpo 3, 3R, 4, 4X y 12Montar o marnipulo numa superficie lisa para recintos tipo 3, 3R, 4, 4X e 12Montare la maniglia su una superficie piatta per le custodie nema tipo 3, 3R, 4, 4X, e 12

11@ndle Features

1 acteristiques de la poigneeMebelmerkmale

N Caracteristicas del mando

Caracterfsticas do manipuloCaratteristiche della maniglia

mm

in.

5.9

(3/16 - 5/16)

Handle Off - Open or Close EnclosurePoignee positionnee sur off - cotfret ouvert ou fermeHebel auf aus - gehause offen oder geschlossenMando de bloqueo desactivado - caja abierta o cerradaManipulo en "Off" . recinto aberto ou cerradoManlglia in "Off" - custodia aperta o chiusa

Pf-

Lock Handle Off With Enclosure Door Interlock

Poignee de verrouillage positionnee surr "Off" - avec interverrouillage de la porte du coffretVerriegelungshebel "aus"(Off) mit'gehauseturverriegelungMando de bloqueo desactivado (Off) con enclavamiento de la puerta de la cajaManipulo da fechadura em "Off" com travamento da porta do compartimentoBlocco maniglia in "Off" con interblocco della porto della custodia

0

U

1

,-r-i

Handle On - Open or Close EnclosurePoignee positionnee sur on - coffret ouvert ou fermeHebel auf ein - gehause offen oder geschlossenMando de bloqueo activado - caja abierta o cerradaManipulo en "On" - recinto aberto ou cerradoManiglia in "On" - custodia aperta o chiusa

P

Lock Handle On With Enclosure Door Interlock

Poignee de verrouillage positionnee sur "on" avec interverrouillage de la porte du coffretVerriegelungshebel "Ein" (on) mit gehauseturverriegelungMando de bloqueo activado (on) con enclavamiento de la puerta de la cajaManipulo da fechadura em "on" com travamento da porta do compartimentoBlocco maniglia in "on" con interblocco della porlo della custodia

r -% 1 0 0

1 .

F

F

1/ ;

/ I

Handle Installation

Installation de la poigneeHebelmontageInstalacion del mando

Instalaao do manfpuloInstallazione della maniglia

Supplied with Cat 194R-HS4 and -HS#E

Fourni avec references 194R-HS4 et -HS*E

Lieferung mit kat-nr 194R-HS4 und -HS#ESe suministra con el cat. 194R-HS4 y el -HS4EFornecido com cat 194R-HS# e -HS#E

Fornito con num. cat. 194R-HS#e-HS#E

2.8 N.m(25 Ib - in)

0

n

0

F

.

40053-127-01(IDPrinted in U.S.A.

9

mm

(in.)

035

(01 - 3/8)

25

(63/64)

(1 - 31/32)

2-05.5

(2 - 0 7/32)

19.9 ,(25/32)

76.21 .wh

(3)

76.2

(3)

A

8.8

(11/32)

25

(63/64)

Cover Thickness

Epaisseur du panneauDeckelstarke

Grosor de la tapaEspessura da tampa

Spessore def panello

50

(1 - 31/32)

Front of Cover

Partle frontale du panneauVorderseite des deckels

Frente de la tapaFrente da tampaParte frontale del panello

4»E\

\

\

\

\

\

18.4

(23/32)

1,- 40.3 -1,-(1 - 19/32)

- _ 65.1 -(2 - 9/16)

1.2 - 4.8 mm(3/64 - 3/16)

01. ROCIONell Automation-

Allen-Bradley

.

Modification

AnderungModificaci6n

ModifiaoModifica

Operating ShaftSectionneur

BetatigungswelleVarilla de operaci6nVeio de accionamento

Albero

(Cat 194R-Rl, -R2)

ATTENTION: To prevent electrical shock, disconnect from power before installing or servicing. Install in .suitableenclosure. Keep free from contaminants.

ATTENTION: Avant le montage et la misc en service, couper i alimentation secteur pour dviter mute ddcharge. Pr6voirune misc en coffret ou armoire appropride. Proldger le produit contre les environnements agressifs.ACHTUNG: Vor Installations-oder Servicearbeiten Stromversorgung zur Vermeidung von elektrischen Unfillentrennen. Die Geriite mussen in einem passenden Gehiluse eingebaut und gegen Verschmutzung geschutzt werden.ATENCION: Desconictese de la cordente e!6ctrica, antes de la instalacidn o defservicio. a fin de impedir sacudidaseldctricas. Insthlelo en una caja apropiada. Mant6ngalo libre de containinantes.ATENCAO: Para evitar choques, desconectar da corrente e16trica antes de fazer a instalaqao ou a manutengao. Installarem caixa apropriada. Manter livm de contaminantes.ATI'ENZIONE: Per prevenire infortuni, togliere tensione prima dell'installazione o manutenzione. Installare in cus-todia idonea. Tenere lontano da contaminanti.

194R-HS1

194A-HS#

194R-HSlE

194R-HS#E

194R-HS1

194R-HS4

194R-HSl E

194R-HS4E

194R-NAl OOP3

194R-NA200P3

194R-NA300P3

194R-NC030PS

194R-NJ030P3

194R-NJOGOP3

194R-NN030P3

194R-NN060P3

A

194R-Rl

194R-R2

194R-Rl

194R-R2

* Cut to proper lengthSectionner h la longueur requiseAuf richtlge Lange zuschnelden

Corte a la longitud adocuadaCortar para o comprimentoTagliare alla lunghezza approprlata

0 + Ei3*FORI190-HS1

190-HS4

190-HSl E

190-HS#E

198-Hl

+A

194R-Rl

194R-R2

Cutto proper lengthSectionner A la tonguourrequise Auf richtlge Lange zuschneldenCorte a In longllud adecuadaCortar para o comprimentoTagliare alla lunghezza approprlata

263

(10-11/32)

263

(10-11/32)

457

(18)

457

(18)

A

MIN

147.6

(5-13/16}

147.6

(5-13/16)

111

(4-3/8)

111

(4--3/8)

Drill hole

Percer un trou

Loch bohren

Aguiero taladradoFazerum oriffcioEffettuare la foratura

A

263

(10-11/32)

457

(18)

MIN

153

(6-1/32)

153

(6-1/32)

Drill hole

Porcer un trou

Loch bohren

Agujero taladradoFazerum oriffclo

Effettuare la foratura

C

C

MAX

260

(10-15/64)

454

(17-7/8)

260

(10-15/64)

454

(17-7/8)

MAX

369

(14-17/32)

563

(22-5/32)

[i

-4---- C

r-711

kr

r

C+3

4CU

0255- ta®(.101 0)

Ko 1 { 1/8)

C -It

E rtlf1r·rif

El* /1 i11-_I L

C-106

|--- C-(4-3/16) --1 (f)IC I \·4

U7.2

(9/32)_1 4 @5go

02.55 - t.3®(.101 0)

(1/8)

n

L

/ a 1 7 or

92:9 + ode, OU + *1 +

19041S1

190-HS4

190-HSl E

190-HS#E

190-MN

+

190-A40_+

190-P___

190-MN

+

190-P 190-SE2

= A

A

194R-Rl

194R-A2

263

(10-11/32)

Cut to proper length Drill holeSectionner a la longueur requise Percer un trouAuf richtige Lange zuschnelden Loch bohren

Corte a la longitud adecuada Aguiero taladradoCortar pari o comprimento Fazerum oriflclo

Tagllam alla lunghozza appropriata Effettuare la foratura

1904151

190-HS4

190-HSl E

190-HS4E

4 0% 4 1.+ oder +43+

0

,

190-CPS40_+

190-P___

I ,

190-MN

+

190-A40_+

190-P__-+

190-Nl

190-SE2

4-F

A

194R-Rl

194R-A2

A

263

(10-11/32)

457

(18)

* Cut to proper length Drill hole

Sectionner a la longueur requise Percer un trouAuf richtige Lange zuschnelden Loch bohren

Corle a la longitud adecuada Aguiero taladradoCortar para o comprimonlo Fazorum oriffcio

Tagliare alia lunghena appropriata Effettuare la foratura

40053-315-01 (C)Printed in U.S.A.

457

(18)

A

MIN

167

(6-5/16)

167

(6-5/16)

MIN

176

(6-59/64)

176

(6-59/64)

C 1--

MAX

391

(15-25/64)

585

(23-1/32)

C Mt--

MAX

400

(15-3/4)

594

(23-3/8)

[t[

1=--C-128

C - (5-1/32) -'146 1 U

02.55 J * ®(.101 0) LJ

(1/8)to ,

V

1=---C- 137

C - (5-1/8) -+1< 1 /U

4

(5/32)_r-1 4*CU 32.55 34 ' t 3

(.1010)(1/8)

4C. 1

010 RockWell Automa#on

Allen-Bradley

T1

r

-4-=i

L

r

--LiL

mm

(in )

-1

-1

.

1

//4 BULLETIN

9 194RFUSED DISCONNECT SWITCH

SECTIONNEUR PROTEGE PAR FUSIBLE

TRENNSCHALTER MIT SICHERUNG

INTERRUPTOR DE DESCONEXION CON FUSIBLE

INTERRUPTOR DE DESCONEXAO COM FUSIVEL

SEZIONATORE PORTA - FUSIBILI

-NCOSOPS

-NJOSOP3

-NN030P3

-NAl OOP3

-NA200P3

-NJ060P3

-NNOGOP)

-NA300P3

U.L LISTED SWITCHES

SECTIONNEURS AGREES ULSCHALTER MIT UL-ZULASSUNG

LISTADO DE INTERRUPTORES U.L

CHAVES DA U.L

SEZIONATORE ELENCATI U.L.

CAT.

194R-NC030P3

194R-NJ030P3

194R-NJOGOP3

194R-NN030P3

194R-NNOBOP3

OTHER SWITCHES

AUTRES SECTIONNEURS

WEITERE SCHALTER

OTROSINTERRUPTORES

OUTRAS CHAVES

ALTRI SEZIONATORI

CAT.

194R·NA1OOP3

194R-NA200P3

194R-NA300P3

U.L. RECOGNIZED ACCESSORIES

ACCESSOIRES HOMOLOGUES UL

U.L. ZUGELASSENES ZUBEHOR

CAT.

194R-H51

-HS4

-HSl E

4154E

194A-Rl

·R2

194R·AA

OPERATING HANDLE

POIGNEE D'ACTIONNEMENT

BEDIENONGSHEBEL

MANDO OPERATIVO

MAN[PULO DEACCIONAMENTOMANIGUA 01 ABONAMENTO

OPERATING SHAFT

TIGE D'ACTIONNEMENT

BETRIEBSWELLE

EJE OPERATIVO

VEIO DE ACCIONAMENTO

ALBERO DI AZIONAMENTO

AUXILIARY CONTACT ADAPTER

ADAPTATEUR DE CONTACT AUXILLIAIRE

HILFSKONTAKT·ADAPTER

ADAPTADOR DE CONTACTO AUXIUAR

ADAPTADOR 00 CONTATO AUXILIAA

AOATTATORE CONTATTO AUSIUARIO

A1

A1

B1

WARNING: To prevent electrical shock, disconnect from power source beforeinstalling or Servicing. Install in suitable enclosure. Keep free from contaminants.AVERTISSEMENT: Praalablement a rinstallation et aux oparations de service,couper ralimentation secteur pour empacher touts chocs dlectriques. Installer dansune boite appropride. Protdger le relais contre les contaminants.WARNUNG: Vor Installations oder Servicearbeiten Stromversorgling zurVermeidung von elektrischen Unfallen trennen. Die Gerate mussen in einempassenden Gehause eingebaut und gegen Verschmutzung geschOtzt werden.ADVERTENCIA: Descondctese de la corriente e16ctrica, antes de la instalaci6n odel servicio, a fin de impedir sacudidas eldctricas. insthlelo en una caja apropiada.Mantangalo libre de contaminantes.ADVERTENCIA: Para evitar choques, desconectar da corrente elactrica antesde fazer a instalagao ou a manutenao. Instalar em caixa apropriada. Manter livrede contaminantes.

AVVERTENZA: Togliere tensione prima dell installazione. Installare in custodiaidonea. Tenere lontano da contaminanti.

. DIMENSION REFERENCE

REFERENCE DE DIMENSIONSKENNUNG FOR ABMESSUNGSANGABEN

REFERENCIA DE DIMENSIONSREFERENCIA DA DIMENSAOREFERENZE DIMENSIONALI

A2

82

DIMENSION REFERENCEREFERENCE DE DIMENSIONS

KENNUNG FOR ABMESSUNGSANGABENREFERENCIA DE DIMENSIONS

REFERENCIA DA DIMENSAOREFERENZE DIMENSIONAL!

A1

A1

81

ACCESORDS RECONOCIDOS FOR U.L.

ACESSORIOS RECONHECIDOS PELA UL

ACCESSORI RICONOSCIUTI U.L.

CAT.

194R·FCA2

194R-FCJ60

194R-LNCl

-UNC2

195·GA01

-GA10

-GAll

-GAO 2

-GA20

FUSE COVERCACHE-FUSIBLES

SICHERUNGSDECKELTAPA DE FUSIBLE

TAMPA DO FUSIVELCOPRI·FUSIBILI

TERMINAL SHIELD

BUNDAGE DE BORNE

KLEMMENABSCHIRMUNG

APANTALLAMIENTO OE BORNAS

RESGUARDO DO TERMINAL

PROTEBONE DE! TERMINALI

AUXILIARY CONTACT

CONTACT AUXILIAIREHILFSKONTAKT

CONTACTO AUXILIAR

CONTATO AUXILIAA

CONTATTO AUSIUARIO

CIRCUIT

SCHALTUNG

CIRCUITO

Li CZ L.0

SP-Zirs,- ,00©-I] 1 1 i al5&-4--6-- 01·-01-- F -21,67*/TS

LtuU

St-%-1-=f..

2==

CIRCUIT

SCHALTUNG

CIRCUITO

U 12 U

$.A-;i-_

Ef-4 in _0]OTHER ACCESORIES OTROS ACCESORIOS

AUTRES ACCESSOIRES OUTRQS ACESSORIOSWEITERE ZUBEHORTEILE ALTRI ACCESSORI

CAT.

194R-SLA1

·SLA3

SHORTING LINKS

CONTACTS OE PONTAGE DE MISE

EN COURT-CIRCUIT

KARZSCHLUSSBROCKEN

PUENTES DE CORTOCIRCUITO

BARRAS OE CURTO-CIRCUITO

COLLEGAMENTI 01 CORTOCIRCUITO

.

.

OPERATING SHAFT INSTALLATION

INSTALLATION DE LA TIGE D'ACTIONNEMENTMONTAGE DER BETRIESSWELLE

INSTALACION DEL EJE OPERATIVOINSTALAGAo DO VEIO DE ACCIONAMENTOINSTALLAZIONE DELL'ALBERO DI AZIONAMENTO

u

04

UE

SI

U lu1

1

POWER WIRE INSTALLATION

INSTALLATION DU FIL DE PUISSANCE

INSTALLATION DES NETZKABELS

INSTALACION DEL HILO DE AUMENTACION

INSTALAGAo DO CABO DE CORRENTEINSTALLAZIONE DEI CAVI DI UNEA

CAT.

194R-NAl OOP3194 R-NA 200P3

194 R-NJ030P3

194 R-NC 030 P3

1944-NN 030 P3

194R-NA300P3194R-NJOSOPS194R-NN 0605'3

E

DIM.

REF.

Al, A2

81.82

mm

2.5-10

2.5-25

2

A

#AWG

14-8

144

N•m

1.4

4.0

B

lb-in

12

35

2,3.

B

u

ol [51311-83-1 id*111[t

-=*-11.-ZF:-C3Bluu ..-11

4[--1*1-af-]Is

3

.

195-GA

195-GA

195GA

195-GA

195-GA

195-GA

L.1 W -U

IfioF=%, 2 MAXIMUM

, 2 MAX, MAX 2. MAXIMO 2

, 2 MAXIMO

, MASSIMO 2

1 1

MIQY2-05.5

2-219 dia.

0351.38 dia.

mm

in.

The switch is capableof accepting #8 x 1-3/8'screws for mounting

11 1

4IL -

1-»111 1

tt1; 1

rLJ 1

A

G =

H-I'-

.t.

9 0

70

91»%3-93-

50

14102

25

63/64

IR

s

4T ,

A 2MINIMUM

MINK

MINMD

-·4- U

1

1 ,

1tl/1 '11 1It 1

1

40.3 -lb

11' 1.19,3225

63/64 L J

SO J, 11-31/32

EVCLOSURE INSTALLATION DIMENSIONSEMCOMBREMENT DU BOITIER

INSTALLATIONSABMESSUNGEN FOR DIESCHALTSCHRANKMONTAGEDIMENSIONS PARA INSTALACION EMPOTRADADIMENSOES PARA INSTALAGAO DO GABINETEDIMENSIONI PER INSTALLAZIONE IN CUSTODIA

CAT.

194R-NAloOP3

194R-NA200P3194R-NC030P3194R-NJOLB

194:A-NN030P3

194R-NA300P3

194R-NJOGOPJ

194R-NN060P3

A 1

A2

81

82

DIM.

REF.

mm

in.

mm

in.

mm

in.

mm

in.

A1MNULIM

M N MD

AANMO

171

6-3/4

171

6-34

197

7-34

197

7-3/4

203

7-63/64

203

7-63/64

228

8-63/64

228

8-63/64

*L

45

45

149/64

45

149/64

149/64

45 *

149/64

81MNMUM

MINMO

MINMO

3

3

76

3

B2MINMU,1

MINMO

MINMO

76

76

76

3

2-M42.0 N·m

18 lb-in

G -7-+1

Ir-- -11----------&-1-,41--7-1,1

-/

'' i,---------- -1 L-1 lili1 11 1/ 1

$-r' 1, 1 11 1/1 11 1 1

1 111 /1 , 1

:1 1 1

: Ill1,

11 1 1

1 1, 1 1

+ 821+A2

MINMLM

MirJUO

MINIMO

147.6

5-13/16

111

44/8

147.6

111

4-3/8

MAX]MUM

MAXMO

MAXI.'40

MASSIMO

1 t H-7 A.fl

Q,

1 94R -NC 03OP 3

194R-NJ030P3

194R-NN030P 3

5- 13/16

C

454

177/8

454

17-7/8

454

17-7/8

454

17- 7/8

248

9-3/4

248

94/4

248

D

MNMUM

MINMO

MINA)

248

9-3/4

9-3/4

E

-f]

105

E

-FC-4-

-----------

T

1 1

,

4-# 4

1-T1 1

1 1

L

U

1 1It

1 17 1

1 1

1 1

1 1

1 1

4-M#2.ON•m -718 lb-in

- G-0:44H-+114-1 L

6 + S)01 e

194R-NA300P3

194R-NJOGOP3194R-NN060P3

MIMMU.4

MINMO '

MIMMO

89

3-112

89

3-1/2

4-9/64

105

4-9/64

MINMLM

MINMO

MiNMO

1.4

1/16

1.4

1/16

1.4

1/16

1.4

1/16

MAXMUM

MAXMO

1.,Axi.,0

MASSIMO

4.78

3/16

4.78

3/16

4.78

3/16

4.78

3/16

.

.

2- 05.5

2-219 dia.

62564b

50

1-31/32

0 35

1.38 dia.

mm

in.

The switch is capableof accepting #8 x 1-3/8"

screws for mounting

1

*----Z--------7

1 1, E,

1

1 1

1 1! 1

1 /1 -1-1

/,Iii

1 11 , 1

1 7----

1 111 -1

lili ,it I

lia1-13 ' £47

f - A -', 811 2 1

195-GA

195-GA

195-GAG---p 19FGA

195GA

195·GA

1/ N

V/ /i kOf :102 T

IftS ' 4L-JI1 1

1,

0' '

U-*

50

1-31 r32

25

63/64

R

S

T

.5

, 2 MAXIMUM

, 2 MAX., MAX 2, MAXIMO 2

, 2 MAXIMO

, MASSIMO 2

M

A

40.3 _I-1-19/32

2-M4i 2.ON•m

18 lb-in

G D-1

i »H* 11 L@-1 Q

01 94R-NAl OOP 3

1 94R- NA 200P 3

194R-NC030P 3194R-NJ030P31 94R-NN 030P 3

E

Al

-4AFCA

--------------

---

4/-

0-1

1 ,

1 1

1 1 ;4Z*==4=i===/1 1

/, 1/1 1/1 ;

4-M4

2.0 N•m 718 tb-in

11 G --,Pr•--H 4*1

L. 1

0 6 -t -4194R-NA300P3

194R-NJOGOP3

194R-NN 060!'3

DISCONNECT SWITCH AND OPERATING HANDLE INSTALLATION DIMEN SIONSENCOMBREMENT DU SECTIONNEUR ET DE LA POIGNEE D'ACTIONNEMENTINSTALLATIONSABMESSUNGEN FOR TRENNSCHALTER UND BEDIENUNGSHEBELDIMENSIONES DEL INTERRUPTOR DE DESCONEXION E INSTALACION NO EMPOTRADADIMENSOESPARA INSTALAGAO DA CHAVE SECCIONADORA E DA ALAVANCA DE ACIONAMENTODIMENSIONI PER L'INSTALLA ZIONE DEL SEZIONATORE E MANIGLIA DI AZIONAMENTO

D M. KLMNPQRSCAT. REF. GHJ

194R-NA:OOP3

194R-NA200P3

194R-NC030P3194R-NJOGOP3

194R+INOSOPS

194R-NASOOP3

194R-NJOBOP3

1944-NNOGOP3

A A2

81 82

nm

n.

mn

85

3 1/32

120

4-23/32

19/64

0

25/64

24.2

61/64

28.5

1- /8

64.8

53

76.5

3-1/64

139'6

50

4 1296

5- /64

153

-31/32 6 1/32

11.8

5/32

1.5

11/16

06

4- 1/64

118

4-21/32

82

3-15/64

100

3- 5/16

D

102

4-1/64

134

5 9/32

1 .1

4- 12

146.1

5/4

126.2

4-31/32

158.2

T

615/61

12

U

1 5/32

16

58

LINE TERMINAL SHIELD INSTALLATIONINSTALLATION DU BUNDAGE DE LA BORNE D'ALIMENTATION

MONTAGE DER LEITUNGSKLEMMEN-ABSCHIRMUNGINSTALACION DEL APANTALLAMIENTO DE LAS BORNAS DE UNEA

INSTALACAO DO RESGUARDO DO TERMINAL DO CABOINSTALLAZIONE DELLA PROTEZIONE DEI TERMINAU DI LINEA

0

0

CLICK

CLICK

194R-LNCl

(Ser. B)

lillf'r-

,

194R-NC030P3

194R-NJ030P3

194R-NN030P3

r-194R-LNC2

(Ser. B)

, .i> -A

C\.AC K-.

%-

194R-NJOGOP3

194R-NNOGOP3

/1,0.CLICK v4

FUSE INSTALLATION

INSTALLATION DES FUSIBLES

EINSETZEN DER SICHERUNGINSTALACION DE FUSIBLE

INSTALACAo DOS FUsfvEISINSTALLAZIONE DEI FUSIBILI

-1[

6,1 194R-NC030p3

+ Y-1 ,-J-1.-51-

a F

-If

1-R

0

, A- ; OPTIONAL; / ' Eli OPTION--- OPTION

.8 Bm HOPCIONAL 7 lb·In 110OPZIONALE 1

L.1 L / L--U

(Q=0

i OPTIONAL

' EN OPTION

OprIONOPCIONAL Al

OPZIONALE.8 N,11 I r 4 1

TLl 1 44.112 A L'

8 : u f

((20

- b

.Uf?-_r --1__i -1_5=-1111 la=11®11' totallis

194R-NJ030P3

194R-NJ060P3

LJ 1__1 1-j

Frd fo]-FEIt

-1

0

.

FUSE INSTALLATION

INSTALLATION DES FUSIBLES

EINSETZEN DER SICHERUNG

INSTALACION DE FUSIBLE

INSTALAGAO DOS FUSIVEIS .-INSTALLAZIONE DEI FUSIBILI

MAXIMUM FUSING RECOMMENDATIONS0 FUSES MUST BE SELECTED WITH REGARD TO THE MAXIMUM PROSPECTIVE FAULT CURRENT OFTHE SYSTEM AND THE MAXIMUM CUTOFF CURRENT OFTHE FUSE.WHEN SUBJECTED TO THAT MAXIMUM FAULT CURRENT, THE MAXIMUM FUSE CUTOFF cURRENT AS SPECIFIED FOR EACH DISCONNECT MUST NOTRE EXCEEDED.

INTENSITE MAXIMUM DE FUSIBLE RECOMMANDEE

rih LES FUSIBLES DOIVENT £TRE CHOISIS EN TENANTCOMPTE DU COURANT DE FUITE EvENTUEL MAXIMUM DU SYS*ME ET DU COURANT DEE COUPURE MAXIMUM\-/ DU FUSIBLE LORS D'UNE APPUCATION DE CE COURANT DE FUITE MAXIMUM, LE COURANT DE COUPURE MAXIMUM DU FUSIBLE, COMME IL EST PRECISE POUR

CHAQUE SECTIONNEUR, NE DOIT PAS 6TRE DPASSE.

EMPFOHLENE MAX. ABSICHERUNG

0 DIE AUSWAHL DER SICHERUNGEN NUSS AUF GRUNDLAGE DES MAXIMALZU EAWARTENDEN FEHLERSmOMS DES SYSTEMS UND DES MAX AUSSCHALTSPinEN-STROMS ER SICHERUNG ERFOLGEN. BEI AUFTRETEN DIESES MAX. FEHLERSTROMS DARF DER FOR JEDE TRENNUNG ANGEGEBENE MAX. AUSSCHALTSPITZEN-STROM DER SICHERUNG NICHT OBERSCHRITTEN WEADEN.

RECOMENDACIONES MAXIMAS SOBAE FUSIBLES

LOS FUSIBLES DEBEN SELECCIONARSE CON RESPECTO A LA COARIENTE DE FALLA MAXIMUM ANTICIPADA DEL SISTEMA Y A LA CORRIENTE DE FUNDICION MAX-1 IMUM DEL FUSIBLE At SOMETIRSE A ESTA CORRIENTE DE FALLA MAXIMUM, LA CORRIENTE DE FUNDICION MAXIMUM DEL FUSIBLE. COMMO ESPECIFICADO PARA

CADA DESCONEXION, NO OEBE EXCEDERSE.

RECOMENDAC6ES DOS VALORES MAXIMOS DOS FUSIVEISOS FUSIVElS OEVEM SER SELECCIONADOS EM RELAQAO A CORRENTE MAXIMA PROVAVELEM CASO DE AVARIA 00 SISTEMA E EM RELAfAO A CORRENTE MAXIMA

1 DE ROTURA DO FUSfVEL QUAN[JO O SISTEMA E SUBJEITO A ESSA CORRENTE MAXIMA DE AVARIA, A COARENTE MAXIMA DE AOTURA DO FUSIVEL CONFORMEESPECIFICAOA PARA CADA CORTE DO CIRCUITO NAo DEVE SER EXCED[DA.

CORRENTE MASSIMA DEL FUSIBILE RACCOMANDATA

1 1 FUSIBIU DEVONO ESSERE SELEZIONAll IN BASE ALLA CORRENTE MASSIMA DI GUASTO PREVISTA DEL SISTEMA E DELLA CORRENTE MASSIMA 01 INTERVENTODELFUSIBLE. IN PRESENZA DI QUESTA MASSIMA CORRENTE 01 GUASTO. NON DEVE ESSERE SUPERATA LA COARENTE MASSIMA 01 INTERVENTO DEL FUSIBILECOME SPECIRCATO PER OGNI SeONATORE.

CAT.

194*AlOOK

19481\IA200P3

1948·NA30083

1UUIMUM SHORT CIRCUIT PROTECTIVE CURRENT

COURANT MAXIMUM DE COURT - CIRCUITPRESUME

UAX. KURZSCHLUBSTROM

CORRENTE MAXIMA DE CORTOCIRCUITO

CORRENTE MAIGMA DE CURTOIRCUITO

CORRENTE MASSIMA DI PROTEZIONE DACORTOCIRCUITO

80 KA

80 KA

80 KA

MAXIMUM MOTOR CIRCUFT FUSE LINK

PUISSANCE NOMINALE mil DE LA CONNEXON OU FUSIBLE

Dll CIRCUIT MC]TEUR

MAX. BEMESSUNG DES SICHERUNGSELEMENTS FORDIEMOTORSCHALTUNG

REGIMEN MA)L DE LA CONE]06N DELFUSIBLE DEL CRCU[TO MOTOR

POTENCIA MAXIMA DO Flo 00 FUSIVEL DOCIACUITO 00 MOTORPOTENZA MASSIMA DEL FUSIBLE DEL CIACUrrO DEL MOTORE

my

- Tr 1-0 3

=111[,Er LE.-1 -EE'fir40053-313-01 (D)Printed h U.S.A

32M63

32M63

63MloO

..

U

4A

CAT

194R-NAl OOP3

194R-NA200P3

194R-NA300F)3

A

N•m

20

37

17

LB-IN

18

33

33

MAXIMUU FUSE CUTOFF CURRENT

COURANT MA)0 DE COUPURE DU FUSIBLE

MAX. AUSSCHALTSPITZENSTROM DEB

SICHERUNG

COARIENTE MAX. DE FUNDICBN DEL FUSIBLE

CORRENTEMAJOMADECORTEDOFUSiVEL

CORRENTE MASSIMA DI INTERVENTO DELFUSIBLE

7.5 KA

7.5 KA

10 KA

- 00 Rockwell Automation

Allen-Bradley

0

Sdk mlerBellows® RO. Box 631

Akron, Ohio 44309-0631

WARNINGTo avoid unprodletable system behavlorthal can cmuse personallnjuryand property damegr• Disconnact alt supply and depressurize 811 alr lines connected to

this priduct beforo Installation, sorvicing, or conversion.• Operiti wi:hin mi marturacturoh specified pressure, temperature

and other condmons listed In trisse instructions· Medium must bo molsluio-froe [l Imblent temperature is below

Mezing.

• Service according [o proceaures listed In thesalnstructions.• Inst,!lation, service. and con¥enlon of these products must be

performed by knowledgeable personnel who uncentand howpneumallc products ire to bo applied.

• After installation, servicing, or conversion, alr supply should boconnected and thi product tesled for proper function and Isakage. Ifal,dible leakage 1% presant or thi product docs not oper,lo pmperly,do not put Intouse. 1

• Warnings and speclncations on the product should not bi covered

by.paint. etcia masking li not possible. conpet your localrepresantallys.for replacement isbell

Introduction

Fouow these hslructions when *slaning. operaung. m spking fe f,owELApplication Limits "These pIcts are intended tor usein general purpose comfessed ax systemsonly. Compaance with the rated pressure and temperature is necessary.

Maximum Operallng (Inlel) Presim: kh psig bar

14E with Potycarbonate 80.4 1030 150 10.3

14E with kletal Bowl 1720 250 172

14R&15R 1720 250 172

AmblentTemperature Range: Ot to 522 132'F:0 125'7

Symbols ·

-FE -BJE -4- 414E 14E 14R & 15ft 148&15R

ManuaiD,ain · Manual Drain Rele,Ing N/,Aeic. ngRobevrg Non-Re"M

Installation

1. Thislnishouldbeiristalled¥Athreasonabla accesslyjorserv¥:ewheneverpossble - lepair Ben,ice kim ale Evailat8. Keep pipe and liking lengths to amanizim with Inside clean ard Iree of dirt and ch©s. Pipe jotm compoundsshould ba used sparingly and applied only to the male pipe - ne,er imo thelemae port Do not uss Tenont tape 10 88% pipe joints - pieces have atendency S break oM and looge inside the unil. p)33*lycausng mal[Incoon.

2. Instal unit 10 43! air flew is in the Erection of mrow. Installation must beupstream 01 and close lo devices It is to service (valve, cylinder, tool et).MMIg & regulatofs may ba m any position; mounling 01 lillemegulalmmust be„16cal as shown n igure.

3. Gal,90 ports are located on both sides 01 the regulator body lor yowconvarianca. It is n,r#,-7 to install a gauge or Fpe plug tntc each portduring bstanabon.

L To Prolod iegulamr (14R· & 191 units) against lust pA, scale. ancl otherIoreign mailer, Istaa filter on the,stream (high pressure) side as close to01* regdator 03 possible

Trac-"'i E L 4 7," 1 N.mcln 8 Ca

Installation & Service InstructionsForm 1R402858

145 Mini Filter/Regulator, 145,14R & 15RMini Regulators14R & 15R Mini Regulators1/8" & 1/4" Ports

ISSUED: August, 1996 1Supersecles: August.1995ECN, P25 519

Operation of Filter/Regulator1. Botn tree mots,ure anosoles are removed autornatcallybytne Finermeguator.2. Idanial arn finers must De cra:ned regularly Delore the seoarated moisture

and oil reaches the bottom of me element holaer. Automatg [Iran mooels

(ouse drsn) ¥,i collect enci ammp liquids aulomaicaly. They are actuatedwnen a pressure crop occufs witkn tne filter.

3. The IMer elemernt sholld be removed ar* replaced when the pressurediterential across me fine, 8 excessive.

Service

Caution: SHUT OFF AIR SUPPLY and exhaust the primary andseconcary pressure beloodisassembling unIL (Units may be servicedwithout remo¥Ingthern Irom the air lina)

Servicing Filter Element:Note: See Foure 1 to aidwitht* Focedure.1. Unscrew threaded bd and element holder. Then remove Imer element,

deneclor, and gaskets.

1 Clean al htemal parts. bo*i. md body before re-assembling uniL SeePolycarbonate bowl dearking section.

3. install delleclor, rtterelement and gaskets.4. Attach element hok er.Torque 0.9 to 1.4 N·m B to 12 in-lbs).

5. To assist wim retab*ig beak o·ring v/hile instaning bowl. hbricate the 0-ring(wilk a mberal baseo oa orgaase).Then plaze n on the bod.

6. Scrm, bowlinto body unB il is slipped by body: then back 011 bowl 1/8 turn-7. Apply pressure to Ule sys,em and chedc lor leaks. N leaks occur, Shut Off tile

air supply CO-pressurize me systern and make necessary adjustments :oelmunm leakage.

Servicing Regulator:Note: See Figwg 1,2&3 toad with this procedure.

1, Unkxit tne adjustng knob by puOing upward (with the unit in an uprightPositionj Then turn 06FWID *ob counte,cloawlse imm compression ofthe comrot spring has been removed.

2. Remove the bonnet from body. Then remove 047 0. pistor, lip seal (91,and control sping to serve une bonnel subassembly. Unswew seal (8) toservice the poppel (17], iehm sing (5). aneor poppet seal (61 onngs(25 & 27). and wwher (261

Note: On merkegdatoi ur:4 tie poppet assembly & poppet return spfingmay be accessed by removng liner element

1 Clean 09 grease tiom unn and inspect seals lor sign of wear (nicks, arts.4 scraches). Repair los ate available rdlich conlan me pans which arety», replaced

4. Apply a Bght rtlrn ©1 Feag lo all sea and sld•,g surlaces using me greasepacket supplied with repal k

Note: Reler to Figures lo determne the correa posit,on and orientabon of thevanous parts g assembly.

5, On relimng 15R uni, gently and frmly press vent seal into piston using ablunlmsuument

WARNING |FAILURE OA IMPROPER SELECHON OR IMPROPER USE OF THE PRODUCTSANDOR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE

DEATH, PERSONAL iNJURY AND PAOPERTY DAMAGE.

111,3 6xurnent Bno otner #*<mation trom The Ccnpaily. as wtzioanes andauthonreo ostrattors gronce :Nockc: anc*©r system collors lor turlner rr.estgaknry users na·.Ing tecnnal c.pertse. R 15 ,Mc.tant #al yc analy- an Ispec:$ Ofyoct Acci ation, r.1,.ng c¢nicouences of any ta..e ano ree* the Iumm,ortCC**39,g 010 FOCJC: u :752/m i the 0Jnlent procia cilalog. Duo 10 :na vanet,Gr©pe,mr,9 cont®ons Sno Gf/x:crn t r Hlesel,oducs CY sy=ems. 128 use5, treJgnEs 0*n aufria and :251:ng 6 5010'yi sconttle lor mak ng me Inal 361#coon 01 meprocum and sys:ems and *33:rng thai 0 perlormance, sality and warningrecurimints el mi applicxicn ar, miL

Tne Or©Oucts oescr/Fo hormt Eau*ng muou! 6"81/n, Fooua ks,tures.xed=j„4 0594.,ILD#y *Corcrlg, sre $.60(10 anarge 0, Tra Conx=tyanc :3 51.©searles al my trns w,$re,1 not,ce.

EXTRA COMES OF THESE :NSTRUCT)ONS ARE AVAILABLE FOM INCLUSIONINEOUIPMENT/MAINTEHANCE,LANUALS THATUTTUZE THESE PRODUCTS.DONTACT YOUR LOCAL REPRESENTATIVE

6. Install lip seal onto piston with me fps ol the seal faang away from thesupport Ilange. Then insert control spring and piston assembly into bonneL

7. On 15R units. place balancing 0·ring (27 and washer (26] into bodnbore. Then insert poppet return spring and poppel assembly, lollowed byseat o·ring (25) and seal On 14E & 14R units. place poppet return springand poppet assembly into Dore. lonowed by poppet Beal and seaL

8. On 14E & 14R units. tignten seal to body trom 0.9 to 1.1 N·m (8 to 10 18lbs) of torque.On 15R units, tightenseat from 0.6 10 0.8 *m (5 to 7 ints).Tighlen bonnet onto body from 5.6 to 7.3 N·m (50 to 65 in·lbs) ol torque.

9. Make sure tnat me cor,lro! spring is s#11 uncompressed betore turning onthe aw supply. Turn on air supply. then slowly aoiust the knob clockwise toincrease downstream pressure unlit the desired pressure has been reached.

10. To decrease regula:or pressure setting. always reset from a pressurelower than the final serting des,red. For example. lowering me secondarypressure irom 550 10 410 kPa (8010 60 psig) is best accomplished by

1 dropping tile secondary pressure to 350 kPa (50 psig). then acliuslhguped 10 410 k Pa (60 osig).

, 11. When the desired secondary pressure Setting has been reached, push meh adjusung knobdown tolodiL: ; 12. Check tor leaks. 11 leaks occur, Shut oft the air supply, exhaust system air

V pressure, and maks necessary adjuslments to enminale leakage.11 you have questions concerning how to service this unit, contact jur localauthorized dealer or your customer service representative.

Parts identification ListItem# Description

1 Boattl#El; 2 Filter Bement (14E); 3 Denector (14 E)

4 Bring (14E1 - bo·,110 body5 Poppet Return Spring6 Puppet Seal

7 0,ing-body to bonnel

9 Up Seal - piston to bonnet10 0-ring (14E & 14Rrelieving units) - piston to poppet11 Piston (reteving shovm)

2rl SPFing14 Hex Nut

m *4-17 Poppel (14E & 1411) & Poppet Assembly (15FI)18 80*19 Gasket (140 - denector to body20 Gaskel (14E} -element holderto finer element21 Element Holder (14E)22 0·ring (14E)·body to drain23 Tmst Drain (148

24 Vent Seat (15R. reaeving units) - poppet assemblyto piston25 0ring (15R) - seat to body26 Washer (balanced units)27 0-ring (balanced units) - popPet assembly to body

FIGURE 1: 14ERegulator-Un-balanced, Relleving

Unit Shown withMotal Bowl and Twist Drain

13

1

11

1

9

8

7

6 7,

5

5-

1

Torque:

Finger Tght

1 R402BSB

Service Kits Available

The lollowing service kitscontain theapproptiate seals and parts necessary tofordmary field service.

Description 14E 14R 15R

Foppet Kit - Balanced WA NIA PS455BSBPiston Kil - Non-Relieving N/A N/A PS42258Piston KA - Relie,ing WA N/A PS423SB

Piston & Poppel Kit - Unbal. Rel. PS426SB PS42658 N/A

Pislon & poppet Kit - Bal. Rel. PS#2758 PS427SB NIA

Piston & Poppet Kit . Unbal. Non·Rel PS42858 PS·:28SB WA

Piston & Poppet Et - BaL NomAel. PS429SB PS,12968 NIA

Bonnet Asembly [01369 L01369 L01369Mounting Brackel Kit (plastic ring) PS417858 PS417[3SS PS#178SBMounting Bracke: 151 (aluminum ring) PSBESSB PS4166SB PS466SBKnobTamperfooClip P01265 P01265 - P01265

5 Micron Element Kit PS40358 NIA N'A40 M·cron Element Kit PS40158 WA N/A

Polycalbonale BOM w/Manual Dmin PS40458 WA NIA '

Folycarbonate Bowl w/Automatic Drain PS408SB WA N/AMetal Bowl w/Manual Drain P5447858 mA WAMetal Bowl w/Automatic Drain PS451 SB N,/A MA

SAFETY: Transparent Bowls

6 CAlmON:

Zit:Z52;C2UTZ:Sfij':1Zt5:-2:: 'shculd not be kocated in areai where they couk, be subject lo djrect sunlight. animpact blo,/. nor lemperatums outside of the rated fang. As wim mos, piastics.sorna chemas can cause damaga Por).Zr>onate tents Bhoukj not be exposeto cni/:nated hyerucarbons, ketores. esters and cermin alconols. They shouldnot be usal in air symems ¥,te,8 /Inliessors afe lubricated with fire resistantnuics sual as phosphate cs:er and *€ster typesMetal Hits are recommended v,here ambient and/or meda concitions afe nol#249*.:te#T:7Ut#&#Ort,#AW<*&505: isan laden atmospheres. Consult the factory lor specific recommenalaboris ¥dnen,

TO CLEAN POLYCARBONATE BOWLS USE MILD SOAPAND WATER ONLYIDO NOT usi diansing agents such aa acitone, benzene. Cart)on tettachionce,gasogne. toluene. es. whwal AM dan*,glothls planc.

BcM guark are imnmmended for adood protection or Polycarbonate thils wherecherncal anack may O¢:casionaNy occur.

0 !11#1 irl

Q.14 -*aM/l

(7)-=9*51 |gL-@

1@Ye@fa(5>-11#m[3311£111 /,UL-@

11=21-=®FIGURE 2: 14R Regulator FIGURE 3: 15R Regulator-

Un-balanced, Relleving Unit Shown Balanced, Relleving Unit Shown

8 - 1

6

f

FIGURE 4: Dotall of Poppet Seal .for 14E & 14R Units

'I

,#,:i. ' ,-0-»·?2,1 :..,->.:..6,1.. 'i.,..

rf

APPROVAL ABENCIES LABORATORY DATA ON ELECTRICALLY OPERATED VALVES

LISTED UNDER

U. L. FILE NUMBER MH7261, GUIDE CARD YIOZ

CCESA FILE NUIBER LR50392, GUIDE CARD 440-A-0

THE INFORMATION CONTAINED HEREIN IS IN ACCORDANCE WITH THE

APPLICABLE APPROVAL AGENCIES REQUIREMENTS GOVERNING THE FINAL

FORM OF LISTING MARK (UL, CSA, OR UL/CSA SYMBOL).

GENERAL PURPOSE VALVES

THE TYPES OF FLUID FOR WHICH THEE VALVE IS LISTED.

THE TYPES OF FLUID FOR WHICH THIS VALVE IS LISTED IS INDICATED IN

THE SYMBOLS HAVING THE FOLLOWING SIGNIFICANCE:

A - AIR OR NONTOXIC, NONFLAMMABLE GASES-

F - COMMON REFRIGERANTS EXCEPT AMMONIA.

G - CITY GAS SUPPLIED BY PUBLIC UTILITIES.

LP - LIQUEFIED PETROLEUM GASES.

02 - NOS. 1 AND 2 FUEL OILS, OILS HAVING VISCOSITIES NOT MORE

THAN 40 SSU AT 100- F.

W - WATER OR OTHER AQUEOUS NONFLAMMABLE LIQUIDS.

THE MAX I MUM FLU I D AND AMB Ie,IT TEMPERATURE RATING FOR DIHICH THE

VALVE IS LISTED 18 77- F.

SchraderBellows®[Ilt)mIESE

Plo 6=631Aron. Oho 443]9-0631

74000-7011

Printed in USAREV July 1991

(

e.,-vcr.·>-S*7-51&10'fa.te>:A-,3-26©:.71*·:···,·; 357'.-9

./, ••4 r, -4?117,WARN I NG--iituse 81'tht<)rbdWL,noibduse e.xp/mon andpersonal'uvury.£ Do not use wi'4outfirse reading and'r understanding these instructions and the apparatus initallation and 6pdfai:Ag uisiructions4 drir'1,1,2..9, 011'Imu,::B --3'el• 8 Bis},IM,1 0% ly,lr•tith :1,1,!N A 9)8,. -c·,}rhiA 1 rLE f 7

' Ad! co'!,4 1/.1 ''% mm&=1 Mi; 11·'fl "r,3 3 , MMIETEK 2 06*ObE,biVibidi. LIA#45 r r,• .' HUNTER SPRING PRODUCTS

F L '"11 ' 117,51 a·ligra:44,Ubli· i r i#," , .,1£ A -wrar} Bus*,ri,i#A f.11 n SELLERSVILLEnPENNSYLVANIA, 18960 . „, ,., .. i.,, .m 2,; :,·,- -,*,¥ , 0 9&4)#fittin4-' , ' 4/444 8•r „*Dr, i=19*be "

" USE'AND INSTALEATIONOF PRESSURE GAUGES ' 1.,

The following formation oninstallation anduse hasbeeixce,pted fr* ASME B40 1-1991 The complek ASME B40 1-1991 standard which confaim 'additional informalioii may be,obmincdfrom the Amencan Society of Mdchanwat Eng,neers, 22 11,w Dni:e, BJ'2300, Fatdield, NJ 07007-2300 ,1,Y14 ]i4re2&0 ctnnectioo•1 3 1:a, ···-u che:ncal (dkraY;4'idir resemble 6*losive'flttlird' 11'; " 116,•4 3'chAnge n

"'14,'*11196(w. •- 1 k rili.dampers or snubbers, syp A restrictorplacedinthegaugepres-. 1 3,14.1{Location of Connection |f 'i•· 2NE other sundar items; am avallab|e for sure mletwil[ reduce.pressure 4.17.6 Vibration-Induced Fatigue(a) stem mounted -bottom orback usem these potentially hazardous sys. and restrtck fluid [low.9,11<cp,' e1,3 Failure. Inaddihon loits effect on tile(b) surface mounted - bottom or teens. Ibellazardpotent,almcicasesal open Bourdon tuberc" back ·r,q.r' '- *50 8,1,11 ., 71' ' , 'i, g:!FRemovemeitand linkage (seepara.(c) flush mounted - back ; I ' ·,1. „·«· .- ht,#.r.J'm#?f pl;TU;r; '* „ 1 4.2 7.2 4 overpreshurel,'Failure: "" UZi reti;mhjlikaor:it:1•.u. 1 ,•' 4.2.4 Ihe,foljowing systems are con --Overp[es:Prd fallurg m cjuse4by the,»ops parts of thetirssure element as',3342 Type or Connection Taper mderedpotentiallynazardousandiousl ' appl,callon ormtcmal firtssuregreater sembly 'nlis admg could'causef?:pe connections for pressures up be carefully evaluated than tberated imits of the elast,c cle-,- cracksintheelementieself, ormjomis20 0)00 VW,000 kpa),95 d Ca)compressed gas systems ment and can occur when a low pms- Case pressure bulldup may be slow8. or !/2-14Nri,..1 (bloxygen systemsAmencan Standard extemal or mter- (c)systeniscootatnulghydrogenorfrec s pZJ*t liC etiZf , , Mde*Zieoft¥,ULgh ratcofholemay

nallfperpipethreadsperANSUASME hydrogen atoms 4/1 It.81 1 required. Abow thispres overpressurefallure. usuallymorecrita-' · case pressure ns£ which could resultsum,/4 Mgh ressure tubmft connec- i i' Mw:;,nu,d sy:=,(,6,;:mid A]yfidj,84-,b ' " EAYW7 'imkr 0 an explosivelions, or eaua maybe 11563 Other (e}pressuresystemscontaining any ex- and may cause parts to be propelled m l

appropriately sized connections, cm-, plosive or flammable mixture,or me- any dinction, Cases with pressure , 4.18 Premure Connection See rtcploying scating means other than,la- dium , .rf, 1, 1 .·, 4 1,-« , ,3pered Utreads, are acceptable. (0 steam systems

re[ief ovenings will not always retainexpelleapatts ' ' '"' .,1 ommendations m para. 3.34 F

In applwauons of stem mounted Woonsteady pressumbystcms .Placing a restnctor m-GpressuA ' ' 43 Safety Recommendationsi4

gauge*•especially with litwd filled (6)systems where high ove:pressure - gauge mid will notreduceticimmed,cases andiwherxvibrationts sbvere,,A .,- could be accidentally applied. 4.3 1 Operating Pressu re. The prest ate cffect or failure. but willhelpcon" - suregaugeselecled shouldhave a full

possibitconsideration should be

IN.of fulure of Illgiven to the (

e stempori·.,r,i o tZ:%:fl:NZIMI:5 4 · scale pressure such that the ODeratinpassoc:atedpipmg¢aused bythc vibrat- & 1, mternal contaminabon or where lower ary effects. . pressure occurs m themiddial:alf (25mgmassol Lhegauge Alargeconnec pressure gauges could be installed in to 75%) of Ihe scale. 1he full scalehon(eg, 1/2NPT Instead of 1/4NFT) higher pressure systems It ts gene,ally accepted tbat solid pressure of the gauge,;elected should

front cases with pressure rellcf back be approxrmately two tunes the inorastroogerstent matenal (e g .stain- - 0) systems contaming radjoacllve or - wd! reduce thepossibility of parts be- (ended operating pressure.less steer mstcad.of brass),or both, . , toxic fluids (hquids or.gases) 1 -should be considered. (k) systems mstalled m a hai#dous Log projected forward mthp event of „ , Should it be necessaiy for Ihe oper-failurel .

environment ating pressure to exceed 75% of fullThe windowalonewill notprovide scale contact thesuppller forrecom-3.4 110 Moununpapressuregaugem adequate protection against mlernal mendationsa position other 15an that 'at whtch lt, 16:Ni.4.15,When gaues are Lo bc used m case ressure bulldup, and can be the Inus doesnotapply totest, retarded, or- -- was calibrated can affect lid·accuracl 7 Si'(4*.contactwith merna havmg known or mostmrdous component

Noribd calibratmgposition,supright uncertamcorrosiveeffcctsorknown to , flippressed scald gauges- - Short duration pressure impulses inandvertical Forapplications requir- bc radloactive, mndomor unique de (pressurespikes)mayoccurmhydrau * 432 UseorGaugesNearZeroPres-Ing mounting Li other than this post- SU'uctive phenomena can occur In llc or pneumauc systems, gecially sure1104 notify the supplier suchcases theusershoutdalways fur when valves oren orclose Jile mag- Thcuscofgaugesnearzero pressure Lsnish thesupplier or manuructurerwith mtudcofthespikesmaybemanytimes not recommended because the accu-3.4.1112 Caytion to Users. 1 3 r , mfonoation relative to the applicatton thenormaloperattI; pressure,andmay racy tolerance may bea large percent-Pressure gaukes can be rendered inac- andsolicithis advicepnortomstalla not De tndicated b the gauge. The '"' age of the appited Dr(Wate, dunng sh,pment despite care tion of tlic gauge. · 31.'' , essure If forresuitcould be immediate failure. ora i example, aO/100 :Orade B gauge staken 10 packagmg ' To ensure con- 4.2.6Fireand explosionswilimapres- larpeupscaleerror A restnctor (mub- used fo measure Sm. the accuracy offormancelothestandardgradetowhich ', sure system calo cause pressum ele. ber)mayreducelliemag,litudeofthe 2, measurement wiliL+/-3psl, or-/the pressure Rauze was manufactured, ment failure,with very violent effects, pressure transmitted to the elaslic ele- ' 50% of the appited pressure, It] addl11 shoulclpe EheEked before use .,j, : r„ evento thepdmtofcoinpletelydismic- ment

r-, -_ i w 1 _ - 1 ' .nt gratmg ormelti[10 thepressitr:,uge . . 1,2 - 't u tion, thescareof a gaugels oftoi kid4 SAFETY-,' - " :1:. 4+11 4*101,441197 :41 "out with takeup; whwn can result m4.1 Scope ,

f, , Violenteffccisitrealsoprodulc4 fallum occursdleto whcn --4 17·3Currosion Falliir*torrosidS ruslher maccuracies when mcasunng-failumoccurs when the elashcclcmentYhtS SectiOn of the Standard pre-,' (!)hydrogenembnulement; pressures (hatareasmall percentageothas bcco weakened through attack by ' ihe Raule spansents vertam mformationto guide us. 4:(b)contammationofacompressed gas, corrosive chemicals present meliherera. SUFpliers, and manufactumrs to- (c)formattonofacetylides, Rirthesamereasons, gaugesshouldthe media ms, de or Uic environment not be used for the purpose of indicat-wardmmimmingthehazardsthatcould , ·(d)weakenmgofsonsolder joints by outside it. Failuremayoccuraspin-: I mg that chcpressure m a tank, auto-result from misuse or mtsapplication stam or other heal sources, holeleakagethroghtheelementwals , z clave. or olher similar untt has beenof pressure gauR.es with elit:c etc (e)weakeningofsoftsolderedorsilvcr or early fatigue tallure due to stress completely exhausted to atmosphericments. Theuserniould becomefamil- brazed Jomls caused by heat sources cracking brought about by chemical pressure.Depending on & accuracytarwithallsectionsofthis Standard,as t.i.,suchasfires,'

at] aspects ofsafety cannotbecovered..i,•,

Fcorrosion, deterloration or embnulcment of the and the span of the gauge and thematerial

in this Section. Consult the manufac- possibility that Ukeup is mcorporatedturer or supplier for advice whenever tncalstiock,' 1 ' '4: Actiemicai(diaphragm)sealshould , , atthebeginningofthescale,hazardous_tlimps uncertamty about 00 safe ap 1) excessive vibration. , be considered for use with pressure 1 1, pressure may remain m the tank even

media liatmay have acorrosiveeffect , ihough the gauge m indicating zeroicayof a pressure gaugetr •1':,Off*1001'57Faiturcm acompressedgassystem on theelastic element.imzr rjuoRnur.*Ii*pressureA venting device must belt. 4,..m¥-20*.... itr" ' *in lean be expected to produce violent4 2 G46721 DiscusAIon effects. ' QU., i le 1 · 1(19! .TE,¥i-tr-,Ds. lf , ,rk ,r" , ·usedtocomoletelyreducelliepressurete safetv results from in-, 4 2.7.4 Explosiye Failure. Explosive 4 - beforeunlockingcovers, removu}gfit-fatlureiscausedbytherelease of ex- tings, orperforming other similar ac-; igt ,ingandcareful selection " A 4 2.7Modesof Pressure,Ga6ze Fall- Plosive enugy genented by a chemi ' tivittesand mstdktion of gauges into a ores- cal reaction such as can result whensure system The user should dorm 17 1 Fatu;ue Fallure. Fatisue fail. admbatic compresslon of oxygen oc- 11 4-13 Compatibility With the Pressurethesupplierofall conditionsperllnent , um caused by pressure induced struss curs inthe presence of hydrocarbons, ' Mediumtotheapplication andenvtronmentso generally o©curs from the =Ide tolhe Itas geneelly accepted thatthercis no , Ille elast:celement ls generaity a thlnthat 11:e mmpller can recommend the 9 outside along a highly stressed edge knownmeansoforedicting themagnt- . „walled member, which of necessity

,, most suitabre gauge rpr the apphcag•,, radius,appearing asasmall crackthat tlideor effects of thistype of fatium., *operates undcrhigh stress condiuonstion.·

-I pagatesatongtheedgeradius. Such Forthismodeoffatiure, asoltdwallor and must, therefore be carefully se4 12Thehistory orsafety with respect ilures am usually moreentlcal w,lh partillon between the elast}celement lected for compatibility with thepres-i . #.6 ¢,(0 the use orpressure gdoges has 6®ell. #,p,i. liquid_

excettent. Injuiytope:sonnelanddam- I.Q.-in *1 Fabgua cracks 1&&hill, release the =#As'*r: nlne-ss,anli 4 suremedlumbeingmeasured. Noneofg projected forward. ' the common elcment materials is iin-4 .. , pervlous to every tyoe of chemicalagotopropertyhavebecommimal 'In 4, gnedia nuld slowly so casa pressure 4 1715 Vibration Faildre Themost-*, attack The Lotenttaffor CONOSIVe at-mostinstances,thecauseoffallurchas 48 bulldupcan beaverted by Droviding common mode of v:bration fallum ts T,i r lack Ls esta6lished bv many factors,been masuse ormisapplication. pressure relief openings m tic that where the movement parts wear mcludin& tbe concenfallon, tempera-|- becauscof high cyclm loadmgcaused. ·ture. andcontammationofthemedium|4 23?Ihe presmrAZing elemmt in - ;1%Z'te Rishngh ap- by vibration, resulung m gradualloss Theusershould inEonnthegaugesupimostgauges ts subjected tohigh tnter- + proaches the ultimale strength of the: 2 r oT accuracy. and. ultimatcly fallure of ,. plier of the installation conditions so'nal stresses. and applicabons exist element matenal, fatigue fallure may,' r thr; pomler to Indicate any pressure 8.lat the appropnate element matertals'where the possibility of catastrophicfailumispresent Prdsureregulators,

IMPORT ANT · Red other s,de Jor odditional inunce:ons and *arfungs Q..7. b.m ASMB B4(11 1991 conbmi on b:ck)

.

canbe selecki _ Laboratories, Inc-Someof thescspecificscrvicegaugesarellstedbelow.jIbelist

/ 0.3.4 116 addition to the factors discussed above, the capabltity of a pressure , 4,„g tsnot mlendedtoincludealltypes. and thouserhould always advf thoupplier, of all'ap hcatioh details., *:enced by lie dcsign. materials, an,*cabo,9 ,(,f, ti'F »P„N :,01,13, 31·,8%,Pimi,11 4,r' 3,\* r,,·, '1' I J, 4 1L .Commoo methods of Joining aresoftsoldenng, silverbrazing, and weldmg 4 3.8.2 Acet,lene Gau» A gaugedcsigned to mdicate acetylene pressure„ It|Joints can be affected by temperature, stras and corrosive media Where ----· shall be consttucted ustng matertals that are compatible with commercially

application questions anse, these factors should be considered and discussed by66 user and manufacturer i :'1,,1 1 mila fetylene.i,The gauge may bear the mscnpoon ACETYLIENE on the4 3 5 Somespecial appkcations reclutrethatth6 presureblementassembly have 1 ' F 4.3 83 Ammonin Gauga Agauge des,gned tomdicalc ammonta pressure andahighdegreeofleakage mtcar:ty omanuracturer and user to assure Ula t*5¤&h·'6·t, ·;!15%12T11n»::: .

. + scalemarkmgsonthediali lai .R„4,

4.3.6 .1- 4,4 nniZ,fBit,9-4.4 6 0; :j#, ii*1?3„1*i Jo,-1 ' yfil f At , 438.4Chemical(316iDA*ge*dto mdicatethepressureorclrA,si;436 Solid FronL k isgenerally acceptedthotasolia trontcaseperpara3 3 1 will red,ke the possibility of parts bemg Projected for,vard m the event of 3 4 M,1, or hjgh miscosity fluKS. or both. €rhe prunan, matenal(sj in contact with theelastic elementassembly fallure. An exception ts explosive failure O£0pplafticm pressuremediummaybeldentlfiedonthedial Rmaxbecquippedwithachemical

,. element assembly r, [diapbragm) seal LIsation dam or pressure rettef dev,ce, ora combination1 :nesedencestleiJ'toin,nimlietialdamagetopersonnel and propertx Inthe

4!3 dil'r*2<'1)fqlild'FiliSci 'It ha been general practice td use glvcenne or'.. 1, event of gauge failure.*Dey may, however. also reduceaccuracy or Sensitivtty.sillcone- fillmg-liquids However these [hulda may not be suitaole for ar 'orboth. 1. .Ji to-/4 1 "' u i /5 1,„. i 1

applications. They shouldbeavoided where strong oxidizmg agents mcludmg,IO ' ;,h"n'n-,1.,901LudiV' •l, ·11 : t.,

43 8.5 Oxygen Gauge.AgauR) desinned toind,cate oxy-en Dressure Cleanbul not imtted to, oxygen, chlorine, nitric acti. and hydroaen peroxide Bre A 1,nessshalrcomplywithievelIV(seeSactionS) Thed,alsffaLISeclearlymarkedinvolvedAIn the presence of oxidaing agents, potcolial hazaa can result from

0.,v'*,1. ,*Cmue,e,7}14&.,;9,9,1 M,,,1,4,v, 16*,5=%=;for.U,SPNO=11*5515;*1 11?". '3,7,Da user shall fumish deta!led mforniation relative',to the'ypplicatiuniof,j 4.4 Reuse of Pressure eluges · 4 74 .Raugeshavingliquld filledcasesandsollcittlieadyce,of*,8 gaugesuppperp«, . Itis not recommended that pressure gauges be moved from one appllcallon JTo installation another Shouldit be necessary,'however. the followmg must be considered. r„.Comideralion shoitld also bd gn,en to thJ insta1;0461J h];drkulic kffilhli, 4

may becreatedby oneofthemodesoffallureoullinddmpara417 Thehydraultc 4 4 1 Chem ical Compalibilit.hne consequence* of incompatibility canrangeeffEct due to pressure element failure could cause the,window,Ip t projected, b tom contammutzon to explosrve failure For example. mo¥Ing an 0,1 servaceforwardeven when a case having a solid froBt.ls employed.& ,.,6 ,, JL. re, 1,, gapge to oxygen service can result m explosrve failure

4.11011;14or.' Placing a reAItA bctwed Ilw ir&urcionJectiqQ and thr' 44 2 Partial Fatigua The fin:installation may involve pressurepulsabon thatelasticelementwilinotrcducetheimmediateeffecto fallure,butwillbelpcontrot, has expended most of the gaugelde. resulting m early faugue ul the secondflow of escapmg fluid following rupture and reduce*,potent:al olksecondaty mstallation

,1 1 #,2: 4,/.,Hi< 9<CTEk'Le,1,» 9;1: ,&,4.,t __ .Ltic,4,164,1;illrwau_ f. 4413'I 'lluM'I,

Corrosion Corrosion'of the pressure clement assembly m the first4 3 8 Specific Service Conditions ' mstallation may be sufficientto cause early folure m the second mstallatton.4 18.1 Specific applications forpressure gauges exist whe hazardsareknown 1In many,nstances. requirements for design, construction, and use of gauges for, 4.4 4OtherConsiderations. WhenrcustnR.auve,aliguidelmescoveredmtillsthese applications are specified by state or federal agencies or Underwnters Standard relative to application or gauges shofild Se rollowed m (bc same manner

1: as whena new gauge is selected. ,f -1 941 "4.B.p.on, 1 ., L, ,

j .<, 'In add,tion:o [heASME 840 1-1991 standord, the following addmonul instrud,onsandfvorm,ng:should be readand undentood befom using th:$ produr¢2A*e,9 import t ofs'blcctuig and installmgpregure diuges isthe considerationof the hazards resultln the event the gauge faik The primary causes oriallure 5 5 Freauency or Accuracy Evalgationuc misapplicationand(brabuse of the gauge "Illose people wr,o are reponmble forthe , i Where tte pressuremeasureinent 13 cntical and gauze rallureor gross Inaccuracy willselection and unstallabon or pressure gauges must recoingc conditiou wh.ch will 1 resull m flazard to personnel orproperly, the gauge Aliould be chedked for accuracy and

--- -adversetraffect theabilityoftforaur,elorcitorm:116 funclionor wincliwilliead loearly 9, properoperation on a perlodic bans ,falluro. These conditions mayllienbe discussed with tlie manufacturer to obtain Ihcir i

'11 "

recommendations ../ /4# ai#u 8 't.' 92 1 , 4 R 41 ,• 6 Use &18 Oxygen _ A

talijai@'coAM,6,9 i i Gauges used for measurement ofoxygen pressurb must bc [rce of contannration wlitun

1· Loss ofaccuncy 1 1 Ir„"141 itthe Dressure contalmn on. Various levels of clcanliness are 5Decifted in ANSI

840 1 The zauxe iMFd the equipment to which the gauge m akached (pressurej<rl' Clog&4 or,ho pressuro o,a, or damage to the mterml mpchsmsm so that ' • 11 regulaim, glindus, ac.) must bekepiclean zo aa not to contammate the £auze. Fillcrs1 I 4 there la either '· f ; on thoequipment must boaamlned periodically and clcancdor mplacodI lic sudden'1*izaa:noindicatiditwienprdsuroisapplicdor ' '11 m-rush 01 a hlgh presmire gas will momentari ly create a very high t©inperat uto which in10, :b' theroisanind:cation orpicssurccven thoughnono 15 applied. 1 1 ·4/n' e the presence of oxygen may iEntte the contaminant caustng a violent explosion f 3 A leak m tile pressure conia,ning parts or Joints.. i . 4 i i e ,, Thercrore, when the valvemn the oxygen supply tank Is opened, to admit oxygen lo1114 'Acrackorfatiguefatlureorthebourdon. . , f: r,Il 4 I 1, , ,r r,1 ., the regulator, the valve shoold be opened verialowly so alto alIow the pressure to

1,105. Bumtmg of the bourdon duo to severe overpressure. bulld up slowly in order lo accompltsh thisitis recommended that the tank valve be, 14, An explosion wiann thesysterndue toadierincal rraction orthepressure opened momentarily and then closed mugly but not excessively before attachtngale

,* r[edjum with contarmnafs (55ng the 4Durdon,tglode. . - regulator Tins wilrnot only blow,outaccunaliated dirt inthe valve, butwill alsogiare4* ? 1 ' dic Falve m a cond,tton thai will Qumt It to be opened alowly rather than mdaenly

Whert:pecithng:us:*fliMillmgaprasuregiuge,the follUinli t'mustbegive¢; brcakinzloosens arrsull orbngrlod Inn nolly Whenblecdmzthcoxygentankpnorattention. ' . 1' .1 1, i alwu,111 the regulator be certain the Valve opening ts directea away trom any open Ji Iil,420.b.,* :),Q!41 .Joy lim 1,1 01'1 :Irl' u'IbOK '44) 1 . nameandultopentor *henopeninglheoxygen lankvalve,theoperatormus[ not1 OpeFatin:Pressured h 10, -11 1,4 . 8.5 T'lili itandinfronl ororbehindthegaugeand mustive,reyeand raceproteclion. int.jusDonot coonnuously operate thegaugeatmorethan75% of thespan. Bourdan [ubesare , 3 9, ei tti in 11 there le an exolomon due 10 containinated equipment any particles projectednecessartly highly stressed, especially in ranges ovcr 1000 Im md contimous operation ' Irom the gallge will notbe propelled directly K the operatorat full scale wtll remill m pty fattgue failureand sub=lucn[ rupture „a,11 1 1 49. F 1 -, *HVH

2."Madri111.:94 & ,1 4 n' '*i It '11 11'J , 1,; .16 9 J -1 9 'i ' ,7 Uill,Ith Hydrogen ,9'f. Steel bourdonsmcluding400sen65 stainless steclat'csublectto ll,drogen embnttlementBe ce,tain Lhe mate;,aifor d@ pUu:o con,mmng'pditloils 6rtho gauge aro comoattble, whenstressed- Measummemtof.gamor liquidscontainingliydrogen(such asnat,tral gas,

with tho Ixessurlzed mtinm ·Gauges are cormnonly made o[ coo alloys'lbrass, sour oil) require the use of gccial materials for the bourdon-bronze;e[G) and may be subject lomes corromonorchernical attaLE',Bouraons have '1relallvely tfun'walls, and UN'accuric¥ or the mdicationgis directly affeced by any 8 Venting or Case i in 4rm' ln/OB-f, 7 '" 1.

-f«- reductionin:ha wdl lildneu,I Uw ul Ule salne rnatqial for tho bourdon aa l,sc4 fbriliqu _ _ -yentsprovidedln Ihopressum biaugecase (cleafancoaroundpremroconnectlon,rubbertank or associalcd plpin 19 nr,1 necezii,nly good piactice A matcrial having a conosion EZomnicts, presum rellefbact dc) must not be closed or restncted acm opualmi.rate of 001'16'ear may ve alibble for thc piping. but mli be entlrely unsuitable for a , ·Inere ls always l!10_pogibility tltal the pressuze medium will be adnutted to the casebourdon having a wait tjuckness of for example, 008 inclics la ts unpcrative that the 1 intenor as aresult ora lenknip, JoLic or bourdon tube faitura Ifihis occurs, the pressureproper bourdon inatenal boselestedfor lim service on which the gaugets used,.Gauges, mediummust bevented from ule caso 50 8 nolto build up trficicnt pressuretoruvturespectallyconstructed [orcolrosionier v,wc arcivallable ,i ,-J:·7, 1; nrn< or: 1 , Ilic casc or mndow, However, venting mil not prevent case rupture m the even[ of a

m Ii '1 JE:i,,A i 1 , «, j *D; 15 ' violent explogon·I or3 Cyclk Pressureand Vibration r'

Conianuous.raptdpomtcrmotion will result inexcessive wear6rthemronal mochansm 9 Liquid Filled Gugesand cause gross crrom m thopress:remdicated andpossibly carly fatigue failure or tile' Performance or Dressure gauges used in severe vibration or pu Isanng pressirescrvlce,bourdon. Ifthepotnte:rmotiontaductomechanicalv,bration,Ute gaugenuslberemotely , canbeunprovedby mlingthe gauge case wltha viscous fluid. Gauzes constnictcdm thlsmountcdonanon vibratlng suiraccandconncted tothcapparatus by flcolible mbing If ' mnner noccsson y requlm scoled cascs to prevet the escape of Ilic I:quid..[loweverthopointermotionmduc topressum pulsattons, a mittableaampermust beuscd between switei,imns ur v,mtin£ Ilie ca·:emuslbe provtded. In some insiances this vent ts scaled

· the pressuresourcaand the gauge. 1, fir" 11 1,",151|41.-_ I ./4 i' >4i in prevenl loei or nuiddunrm shipment, and must be released after thegaugcts mstalled.rl lIt ilir 5 4 72Lb hil UDIJ t. '1'4 , Be certain to follow the Mislallallon instructions for properly ventmi tic gauge aner

lit*P@IE litk 1*urdon millail aner eSM&!'612 #r&656 th i45511;zr * installut:on, 7bs liquid filling moslcommonly us,s a mixture or glycen and.Zatermed:urn. inc larger the number of applied pressure cycles and the greater tne extent or Glycerin can combine withstrong oxidtzing agents hicluding (but not limited to)the pressurecycle, lite earher ranummiloccur Ilw faugue fa,lurc may be explosive., , chiorine, nitric acid and hydrogen peroilde. and mult In an explosion which canSmce such a failurewill be hazafdouslo personnel or property, precautions must Be takal· ' ' causeproperlydamapeand personallnjury Irgaugesare (obeusedlrigchier¥ke,

0 ©ontan or direct 11,rcle ze or * ptessurized mediw in sat manneL p,do nof,V glycerindYges, consulliheractory rorpropr niling medium,

|i--WARNING:--Misuse orthts'product m;@Tifie'«plosionand Fli, ,

injury Donotuse withoutflrstreading and understanding " these instructidnsandtheapparatus installationandoperating instructions " ' H'h•.

„ Important- Read other side fur additional instructions and warnings. , „ ·· rein#1421

.

mumTUBE EfELEET

RESTRJCTORHOLDER

RESTRECTOR

GASKET

LOCATWG .

EYELET --0ATOMIZER

-1

6

6

6

6

Sch der RO. Box 631

Akron, Ohio 44309-0631

Bellows®ISSUED: OCTOBER, 1995Supersedes: February, 1994

DEFLECTOR

80"/

P.4 -

f -. 1

OUTERSIGHT DO'/5

OUTER

SIGHT COME

LUBRICATOR

METERING SCREW

- SEAL

METER#JGSCREW

-,r * f SEALDER.ECTOR

SEAL

BODY'BOWL

CHECKBALL

--N PJCKUP TURE

INSTALLATION

1. Install WBRICATOR so Air Flow is in direction ofarrow cast in body.

2. Installation should be upstream from the deviceitisto lubricate (valve, cylinders, tool, etc.).

f OPERATION AND SERVICE- 1. FILLING--Inlet pressure must be eliminated before

fill plug or bowl is removed. Fill to fill line on thebowl (DO NOT OVER FILL) with oil of 100 to 200SSU viscosity at 100°F and an aniline point greaterthan 200°F-same as SAE No. 10 (petroleum basehydraulic oils or spindle oils are good examples).DO NOT USE OILS WITH ADHESIVES OR TACKYADDITIVES COMPOUNDED OILS CONTAININGSOLVENTS, GRAPHITE, SOAPS OR DETER-GENTS (automotive oils generally contain deter-genls) ARE NOT RECOMMENDED.

2. Replace the fill plug and/or bowl assembly firmly-excessive torque is not necessary.The lubricator isnow ready for setting. Repressurize the lubricator.

3. OIL DELIVERY ADJUSTMENT-To adjust oildelivery, use a small blade slotted screwdriver toturn the adjusting screw in the top of the lubricator.Leaner-Clockwise

Richer-Counterclockwise

By counting the number 01 drops per minute in thesight dome, you can adjust to your requirements.Approximately 3% of the drops seen in sight domego downstream. Adjust drip rate accordingly. Con-suit oil delivery conversion chart above.

25 drops per minute equal is one ounce per hour- -volume of oil passing through sight dome.

NOTE: This is a constant density type lubricator whichdelivers a constant ratio of oil to air flow. Therefore, ilair flow increases or decreases, oil delivery will beadjusted propoMionately. ONLY IF A DIFFERENTRATIO IS DESIRED SHOULDYOUR NEEDLE VALMESETTING BE CHANGED AFTER YOUR INITIALSETTING.

installation & ServiceInstructions 1 M103 DSB MINIATURE SERIESMICROMIST LUBRICATOR 14LFILIER 14F

Oil Delivery Conversion3% of Drip Rate To Downstream

6* 7

¤6

:5 - -

4 +

S 3Ez

-

67 100 133 67 200 233

Dome Drip Rate DPM

SAFETY: TRANSPARENT BOWLSCAUTION:

Polycarbonate bowls, being transparent and tough,are ideal for use with Filters and Lubricators. They aresuitable for use in normal industrial environments, butshould not be located in areas where they could besubjected to direct sunlight, an impact blow, nortemperatures outside of the rated range. As with mostplastics, some chemicals can cause damage. Polycar-bonate bowls should not be exposed to chlorinatedhydro carbons, ketones, esters and certain alcohols.They should not be used in air systems where com-pressors are lubricated with fire-resistant fluids suchas phosphate ester and di-ester types.Metal bowls are recommended where ambient and/ormedia conditions are not compatible with polycarbon-ate bowls. Metal bowls resist the action of most suchsolvents, but should not be used when strong acids orbases are present or in salt laden atmospheres. Con-suit the factory for specific recommendations wherethese conditions exist.

TO CLEAN POLYCARBONATE BOWLS USE MILDSOAP AND WATER ONLY! DO NOT use cleaningagents such as acetone, benzene, carbon tetrachlo=ride, gasoline, toluene, etc., which are damaging tothis plastic.

Bowl guards are recommended for added protectionof polycarbonate bowls where chemical altack mayoccasionally occur.

14L REPLACEMENT BOWL

KFT NO. DESCRIPTIONPS420SB Poly Bowl With DrainPS421SB Poly Bowl Without DrainPS447BSB Metal Bowl With Drain

NOTE: All bowl kits consist of (1) bowl assembly and(1) body to bowl seal (o-ring).

MAXIMUM PRESSUAE AND TEMPERATURE

150 PSIG @ 125°F (10 bar 0 52'C) with Polycarbonate Bowl250 PSIG @ 175°F (17 bar 0 80'C) with Metal Bowl ,

*. Conversion: 1 bar = 14.5 PSI; °C 4/9 (°F - 32)

1

MINIATURE SERIES iMICRO-MIST LUBRICATOR 144 FILTER 14F'.1

1FILTER

4

BODY

GRING

GASKET

8001

MYST

DRAN

DEFLECTOR

EUMENT

HOLDER

(ELEMENT)

GASKET

(ELE. END

MAINTENANCE SERVICE KITS

5 MICROMETER ELEMENT KrT

(2) Gasket

(1) Bowl Seal

(1) Filler Bement

40 MICROMETER ELEMENT

(2) Gasket

(1) Bowl Seal

(1) Filter Elemem

POLYCARBONATE BOWLMANUALDRAIN

POLYCARBONATE BOWLAUTOMATIC DRAIN

METAL BOWL MANUAL DRAIN

METALBOWLWITHAUTOMATIC DRAIN

5 MICROMETER ELEMENTCARTRIDGE KfT

.1M103 DSB

5. Install filter vertically with bowl drain mechanism atthe bottom. Free moisture will thus drain into the

sump (*quiet-zone') at the bottom of the bowl(automatic drain models are recommended asstandard equipment).

/., OPERATION & SERVICE

'

PS408SB

14F

PS403SB

PS401SB

MAXIMUM PRESSURE AND TEMPERATURE

PS404SB

PS4OBSB

P5447BSB

PS451SB

PS407SB

150 PSIG O 125°F (10 bar 0 52'C) with Polycarbonate Bowl

250 PSIG O 1757 (17 bar O 80°C) with Metal Bowl

Conversion: 1 bar- 14.5 PSI; °C =5/9 (*F - 32)

INSTALLATION

1. The equipment to which the filter is attached shouldbe internally cleaned to remove all traces of accu-mulated oil and dirt. Also, new pipe or hose shouldbe Installed between the filter and equipment beingprotected.

2. Blow all upstream pipe work dear of accumulateddirt and liquids.

3. Select a filler location as close as possible to theequipment being protected and upstream 01 anypressure regulator.

4. Install filter so that air flows in the direction of arrowon body.

1. Both free moisture and solids are removed auto-

matically by the mter. There are no moving parts.

2. Manual drain filters must be dralned regularlybefore the separated moisture and oil reaches thebottom of the lower baffle. Automatic drain models

will collect and dump liquids automatically.

3. The filter element should be removed and replacedwhen the pressure fferentjal across the filter Is 1ten (10) PSIG.

4. To service the filter element: SHUT OFF AIR

SUPPLY and de-pressurize the unita. Unscrew threaded bowl.

b. Unscrew element holder and remove filterelement & gaskets.

c. Clean bowl and internal parts before reassembling. See polycarbonate bowl deaning section.

d. Replace element and gaskets (2)e.Attach element post assembly and tighten firmly. i -f. Replace bowl seal; lubricate seal to assist In

retaining it in position. Use only mineral baseoils or grease. DO NOT use synthetic oils such .as esters, and DO NOT use silicones.

g.Screw bowl into body.

SAFETY: TRANSPARENT BOWLS

CAUTION

Polycarbonate bowls, being transparent and tough,are ideal for use with Filters and Lubricators. They aresuitable for use in normal industrial environments, butshould not be located in areas where they could besubjected to an impact blow, nortemperatures outsideof the rated range. As with most plastics, somechemicals can cause damage. Polycarbonate bowlsshould not be exposed to chlorinated hydro-carbons,ketones, esters, and certain alcohols.They should notbe used in air systems where compressors are lubri-cated with fire resistant nuids such as phosphate es-ters and di-esters types. In areas where polycarbon-

--ate bowls are exposed to high temperatures or atmo-spheres containing vapors or fluids, which are damag-ing to plastic, use metal bowls.

Metal bowls resist the action of most such solvents but

should not be used where strong acids or bases arepresent or in salt laden atmospheres. Consult the tac-tory for specific recommendations where these con-ditions exist.

TO CLEAN POLYCARBONATE BOWLS USE MILD

SOAP AND WATER ONLYI DO NOT use cleaningagents such as acatone, benzene, carbon letrachlo-ride, gasoline, toluene, etc.. which are damaging tothis plastic.

9

*44%1 01/Bc/MBellows®BEDHm]IEI][IE

.

P.O. Box 631

Akron, Ohio 44309-0631

i

1

i i A WARNING ,|To avoid unpredictable system behavior that can'cause personalinjury and property damage:

• Disconnect supply and depressurize all lines connected tothis product before Installation, servicing, or conversion.

• Disconnect electrical supply before installation, servicing, orconversion. . 'r.

' *·+ ;4•3,4<00364• Operate within the manufacturehs specified pressure,

temperature, voltage and other conditions listed in theseinstructions.

• Medium must be moisture-tree 11 ambient temperature isbelow freezing.

• Setwice according to procedures listed on these instructions.• Installation, service, and conversion of these products must

be performed by knowledgeable personnel who understandhow pneumatic products are to be applied.

• Arter installation, servicing, or conversion, pressure andelectrical supplies should be connected and the producttested for proper function and leakage. If audible or visual

' leakage Is present, ortheproductdoes nol operate properly,do not put into use.

• Warnings and specifications on the product should not becovered by paint, etc. If masking is not possible, contact yourlocal representative for replacement labels.

Function

Application I imitqOperating Pressure Range - Vacuum to the maximum operatingpressure differential (M.O.P.D.) assigned to the orifice structurechosen from chart below. M.O.P.D. is the maximum allowabledifference between pressures recorded at any two working ports of thevalve. If the M.O.P.D. is notknown, regard the M.O. P.D. as tho supplypressure.

1 Body Otifte (Cv)

|1/32-| 3/64| 3'64| 1/16*|1/16-| 302·| 1/8'| 1/8" 932 34167/37(.02) (.06) (.06) (.10) (.10) (.20) (.32) 1.32) (.42) (.52) (.73)

.

Stop0,01ce

[Cv)

1/32·

(.02)

3/64.

006)

1/16·

(.12)

·arxt

(.21}

. 2-way. Normally Closed ·

2-way. Normally Open " 3-way, Normally Closed3-way, Nornath' Open

3-way. Mulli Purpose

3-way. Directional Control

500250300 1 200250 -200 -250 150

300 200

M.O.P.O.

200 -

150 -

2 125

150 -

A

100 75

150 125

* On 2-way Normally Closed Valves the stop orilice is blank." On 2-way Normally Open Valves the body olifice 13 blank.

'175

eDC

125

125

90

(PSI 3)

--

- 65

100 75

50

!100

75/50

40

50

30

75

20

25

10

50

.

50/25

Operating Temperature Range (Ambient):Continuous Duty

'Class '8" Coils 20F (-7*C) to 125'F (52°C)Class 'H" Coils, Viton Seals 20F (-700) to 1800F (8200)

intermillent DutyClass 'B Coils 20F (-7°C) to 1800F (82°C)f*e. Class "H" Coils, Viton Seals 20F (-70C) to 270'F (1320C)

2 Voltage Range: +10% to -15% of rating.

25/1C

10

10

10

1

Wiring InstructionsConned the two wires to suitable supply voltage. Either may be"Hot-.

NOTE: In addition to above instructions, follow all requirements forlocal and national electrical codes.

installation/Operating instructions

Valve should be insialled wilheap*lable accessibility for servicewhenever possible - repair sen/16*kits are available. Keep pipe ortubing lengthstoaminimum with insideclean and free oldirtandchips.Pipe joint compound should be Used sparinglyand applied only to themale pipe- never into the female port. Do not use Teflon tape to sealpipe joints - pieces have a tendency to break oll and lodge inside theunit, possibly causing malfunction. .

Airappliedtothevalvemustbelilteredtorealizemaximum component

U fe Expeclancy - Normal multi-million cycle lite expeclancy of these: valves is based on theuse of properly filteredand lubricatedairatroom

temperature. These valves are also designed to operate undernon-lubricated conditions and will yield millions of maintenance treecycles.

Protect the valve from exposure to extreme temperatures, dirt andmoisture (except units with JIC housings) to maximize life.

Factory Pre-Lubrication -All valves are pre-lubricated atassemblywith Sunaplex 781 or equivalent (Petroleum Base-Lithium Content)grease.

, in Service Lubrication - In-Service lubrication is not required:! however, il lubrication is to,be.used, Schrader Bellows F442 oil is

15=miended. -This oil Ii"specially formulated to provide peakperformance and maximum service life from all air operatedequipment. Otherwise, use a straight paraffin base mineral oil ofviscosity 100-200 SSU @ 100©F and an anatine point greater than200F.

Port Identifications/Connections

A

NT

P

2-way N.C.

M

--, N.]\\ 1 - M3-way N.C.

2

- -263 13-way

Directional Control

3 M

P - Inlet

A - CylinderE - Exhaust

P

A

Installation/Service Instructions

740007013

Direct Acting Solenold Valve

June, 1992

2-way N.O.

E P

3-way N.0.

-T T1 3

3-wayMultl-Purpose

T

1

Service Procedures

mNOTE: All cleaning of parts to be done with mineal spiritsr equivalent cleaning solution. Grease should be aineral based lubricant (Sunaplex 781).General Service - Remove exhaust adapter (A> - whereapplicable and hex nut (B) on top of valve or operator.Separate the housing and coil assembly from the plungerguide(D). Remove the fluxwasher(C)-whereapplicable.Remove the plunger guide (D), spnng (E), 0-ring (F) andplunger (G). Use spanner wrench no. 740007100. Cleanall paris taking special care to remove all foreign malterfrom seal areas.

Coil Replacement (Conduit or Grommet) - Remove coil(H) through bottom of housing and replace with new coil: ·· n ·' 1Coil Replacement (Hazardous Duty) - Remove cap (J)and spacer (K). Remove coil (H) through top of housingand replace with new mil. Assemble in reverse order otdisassembly. .

r.

Coil Replacement (J.I.C.) - Loosen cover sorews (L) and Bremovecoverassembly. Remove flux washer (C),coil (H)andwave washers (M) Replace with new one. Assemble in reverse order 01 disassembly.Replace plunger and guide (See Kit Selection), or entireoperator. Assemble parts in reverse order of disassembly.Tighten hex nut to 20-25 in-lbs. Assemble exhaustadaptor and tighten ta 20-25 in-lbs. for Hazardous DutyEnclosures (hand tight is sufficientwith other endosures). CIndiqator Light ReglacementIndicator Lights120V 60Hz / 110V 50Hz . . H1910924V DC ............... H19110

1. Remove dome nut (8), loosen cover screws (L) and E'

remove cover assembly (N).. .,/1.4,;1 ....:''*Ilnjig will, Avir,Al eads -Snap open splicecorinect68*"" 'd pry clip out ol splice. Slide wires out of splice.-mnits with 3-Pin or 5-Pin Connectors - Twist off two Awire nuts (P) connected to lamp leads.

3. Crush lens of indicator light (0), pull out of cover andretain 0-ring (R).

4. Strip insulation of 1 01 indicator light lead wires 1/2-.Slide 0-ringontonew lampand slide thru hole in cover.

---

Repair KitsFUNCTION

3 WAY N.C.

3 WAY N.O.

3 WAY MULTI-PURPOSE2 WAY N.O. AND

3 WAY DIRECTIONAL CONTROL2 WAY N.C.

H

M

H

*-

STOP ORIF CE1132 3/64' 1/le 3132"

744008031 744008046 744008062 744008093742008031742008046 742008062 742008093745008031745008046 745008062 745008093

746008031746008046 746008062 746008093

NOTE: For viion seals Change the 7th digit in part nurrber Imm f to •6·.EXAMPLE: 744008031 would ba 744008631 for viton seals.

EXHAUST ADAPTER(INCLUQEFV?'ING)**e

\CONDUIT G

F

1/8· PPE 1/4· PIPE

744008000 744108000BUNA) BUNA)

744008600 744108600(VITON) (VITON)

M

J.I.C.

4

.., 44*dqu#

COILS ....4,

B VOLTAGE/ CLASS 'B· CLASS ·H· GLASS 'BKJ · 6\/60HZ 740007141 740007291 760007141

HERTZSPADE

12V/60HZ 740007142 740007292 780007142 '1H.\ 24V/60HZ 740007143 740007293 7800071435. Units With Flvina Leads,- Slide one indicator light wire BVDCinto each splice. Connect red cdt lead with red lamp »/leadand white coilleadwith white lamplead. Placectip '

120V/60HZ 740007145 740007295 7800071454BV/60HZ 740007152 740007202 780007152into spliceand pressuntil flush with topof splice (viceor

liIESESSGU 12VDC 740007152 740007202 780007152

shut.

4801//60HZ 740007147 740007297 780007147assembly.

24OV/eOHZ 740007148 740007296 780007146

24VDC 740007153 740007203 780007153120VDC 740007155 740007205 7800071556. Reassemble junction box cover and tighten screws to E F 120V/502

740007165

230VDC 740007156 740007206 78000715620-25 in-lbs. Screw on dome nut.

240W50HZ 740007166G 4401//50HZ 740007167

- HAZARDOUS.DUTY,*r 4 : 4, ". - -1·'n't*21 , , t.,e

'EXTRA COPIES OF THESE INSTRUCTIONSARE AVAILABLE FOR INBLUSION IN EQUIPMENT/MAITEd-ANCSfMANUALS THAT UTILIZE THESE PRODUCTS. CONTACT YOUR LOCAL REPRESENTATIVE .I.- I

A WARNINGFAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS AND/OR SYSTEMS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE "DEATH, PERSONAL INJURY AND PROPERTY DAMAGES. . ··i

0 users having technical expertise. Il la Important that you analyze att aspects 01 your application, Induding consequences ol any lailure and ieview :he Information 1This document and other Intormailon fromThe Corr©any, Its subsWIalles and aulhollzed distilbutors provideproduciand'ors¥stemoptions for fulther Inveslgation by 1concerning the product or system In the cunent product catalog. Due to the variety 01 operating conditions and applications lor these products or systems. the user.through ils own analysis and testing. 18 solely responsble for maKIng the ,inal arlmion ol the products and systems and assuring thai all performance. salely andwarning mquirements of the application ara met.

Theproducts describedhemin. including without timitation.product features, spedtications,6,19ns, availatmy and pticing, ara subjecttochange by TheCorr¥,any and ..1*4. I !its subsidlifles atany lima without notice.

0

B

CP

74009:9AL

741008000

.rhinH:*Nat 9 1 ·--

5

NQL

R

NONE

.

,

f

SP500 AC Drive

Installation and Operation ManualVersion 3.1

Instruction Manual D2-3356-2

00 ROCIONell Automation

Reliance Electric

The information in this manual is subject to change without notice.

ATTENTION: Only qualified electrical personnel familiar with the construction and operation ofthis equipment and the hazards involved should install, adjust, operate, and/or service thisequipment. Read and understand this manual in its entirety before proceeding.

Throughout this manual, the following advisories are used to point out safety considerations:

.

ATTENTION: Identifies information about practices or circumstances that can lead to personalinjury or death, property damage, or economic loss.

Important: Identifies information that is critical for successful application and understanding of the product.

Note: Identifies additional information that is helpful for successful application and understanding of theproduct.

Reliance, ReSource, and AutoMax are trademarks of Rockwell Automation.

© 1997 Rockwell International Corporation

f

Y

.

1.0 Introduction...

Table of Contents

1.1 Who Should Use This Manual ...............

1.2 Installation Overview ......................

1.3 Requesting Assistance from Reliance Electric

2.0 Learning About the SP500 Drive

2.1 Standard Features ................................

2.2 Drive Description..................................

2.3 Identifying the Drive by Model Number ..............

2.3.1 Power Ratings and NEMA Enclosure Ratings . .

2.3.2 Enclosure Ratings and Sizes ................

2.4 Component Locations ..........................2.5 Option Kits .........................................

3.0 SP500 System Planning 3-1

3.1 Installation Site Requirements .................................... 3-1

3.1.1 Determining the Total Area Required for Installation . . . . . . . . . . . 3-1

3.1.2 Providing Proper Air Flow Clearances ........................ 3-4

3.1.3 Verifyingthe Drive's Power Loss Rating ................................ 3-4

3.2 Wiring Requirements ..................................... 3-4

3.2.1 Verifying Conduit Sizes ................................................. 3-4

3.2.2 Recommended Power Wire Sizes .......................... 3-4

3.2.3 Recommended Control and Signal Wire Sizes................. 3-5

3.2.4 Recommended Motor Lead Lengths ......................... 3-5

3.3 Selecting Input AC Line Branch Circuit Fuses....................... 3-6

3.4 Installing an Emergency Stop .................................... 3-7

3.4.1 Complying with Machinery Safety Standard EN 60204-1 :1992 .. . 3-7

3.5 Motor Considerations ............................................ 3-8

3.5.1 Single-Motor Applications ................................... 3-8

3.5.2 Multiple-Motor Applications ................................ 3-8

4.0 installing the Drive 4-1

4.1 Mounting the Drive................................... 4-1

4.2 Routing Wires ....................................... 4-1

4.3 Installing External Components ........................ 4-6

4.3.1 Disconnects .................................... 4-6

4.3.2 Input AC Une Branch Protection ................... 4-6

4.3.3 Transformers ................................. 4-6

4.3.4 Output Contactors ............................ 4-7

4.3.5 Mechanical Motor Overload Protection .............. 4-7

4.4 Setting the Analog Input Jumper on the Regulator Board 4-7

4.5 Preparing the Motor .......... ........................ 4-8

5.0 Wiring the Drive

5.1 Input Power Wiring ..................

5.2 Signal and Control Wiring ............

5.2.1 Analog Speed Reference Wiring

5.2.2 Analog Output Wiring ..........

Table of Contents

1-1

1-1

1-1

1-1

2-1

5-1

5-1

5-3

5-3

5-4

2-1

2-2

2-6

2-7

2-8

2-8

2-13

5.2.3 Digital Input Wiring .........

5.2.4 Snubber Resistor Wiring ...5.2.5 Output Status Relay Wiring

5.3 Output Power Wiring ...........5.4 Grounding ...... ..............

6.0 Completing the Installation .................

6.1 Checking the Installation With the Power Off .....

6.2 Checking Drive Operation............

7.0 Keypad and Display Operation ...............

7.1 Display Description .....................................7.2 Key Descriptions ..........................................

7.3 LED Descriptions .................................

7.4 Program Mode ........................................... 7.5 Monitor Mode

7.5.1 Displaying the Percent Selected Speed Reference ......

7.5.2 Scaling the RPM Display and Reference Using F-08 .....7.6 Drive Control .................................,..........

7.6.1 Changing the Reference Using the Keypad ..............

8.0 Programming Reference ............

8.1 Displaying or Changing Parameter Values....

8.2 Ensuring Program Security..............8.3 Parameter Descriptions ..................

9.0 Troubleshooting Reference .................

9.1 Verifying DC Bus Voltage ...................................

9.2 Troubleshooting the Drive Using Fault Codes..................

9.3 Accessing and Clearing the Error Log ........................9.4 Checking the Drive's Power Module Circuitry with the Power Off

6-1

6-1

6-2

7-1

8-1

8-1

8-2

8-4

9-1

9-1

9-3

9-6

9-8

SPSOO AC Drive Installation and Operation Manual, Version 3.1

7-1

7-1

7-2

7-4

7-5

7-6

7-6

7-7

7-7

54

5-8

5-9

5-10

5-10

f

4.

Appendix ATechnical Specifications .

Appendix B

Record of User Settings .

Appendix C

Alphabetical Listing of Parameters

Appendices

Appendix DCompliance with Machinery Safety Standard EN-60204-1:1992

Appendix E

Compliance with Electromagnetic Compatibility Standards

Appendix F

Replacement Parts

Glossary...

Index.

Table of Contents

A-1

B-1

C-1

D-1

E-1

F-1

. Glossary-1

. Index-1

m

IV

List of Figures

Figure 2.1 - SP500 System Diagram .............

Figure 2.2 - SP500 System Diagram (Continued) ....

Figure 2.3 - Regulator Board Component Locations

Figure 2.4 - Identifying the Drive Model Number.....

Figure 2.5 - Enclosure A Component Locations ...

Figure 2.6 - Enclosure B Component Locations ....

Figure 2.7 - Enclosure C Component Locations

Figure 2.8 - Enclosure D Component Locations ....

Figure 3.1 - Enclosure A Dimensions ....

Figure 3.2 - Enclosure B Dimensions .............

Figure 3.3 - Enclosure C Dimensions .............

Figure 3.4 - Enclosure D Dimensions .............

Figure 3.5 - How to Measure Motor Lead Lengths

Figure 4.1 - Enclosure A Wire Routing Locations ......................

Figure 4.2 - Enclosure B Wire Routing Locations ......................

Figure 4.3 - Enclosure C Wire Routing Locations .....................

Figure 4.4 - Enclosure D Wire Routing Locations .....................

Figure 4.5 - Jumper J6 Settings for the Analog Input Speed Reference

. 2-3

.. 2-4

.. 2-5

... 2-6

... 2-9

...2-10

... 2-11

.. 2-12

. 3-2

.. 3-2

.. 3-3

3-3

.. 3-6

4-2

.. 4-3

.. 4-4

. 4-5

..4-7

Figure 5.1 - Typical Electrical Connections ............................... 5-2

Figure 5.2 - Typical Control Terminal Strip Connections ................................ ... 5-3

Figure 5.3 - Analog Speed Reference Wiring Connections ..:......................... . 5-4

Figure 5.4 - Analog Output Wiring Connections .......................................... .. 5-4

Figure 5.5 - Two-Wire StarVStop Sample Control Wiring .......................................... 5-5

Figure 5.6 - Three-Wire StarUStop Sample Control Wiring ................................ .. 5-5

Figure 5.7 - Multi-Speed Preset Sample Control Wiring ................................... ... 5-6

Figure 5.8 - Terminal Usage During Multi-Speed Preset Operation ............................ ... 5-7

Figure 5.9 - Snubber Resistor Wiring Connections for M/N 1 SU2>000< Drives ... . 5-8

Figure 5.10 - Snubber Resistor Wiring Connections for M/N 1 SU4)0(xx and 1 SU5>00<x Drives . 5-9

Figure 5.11 - Output Status Relay Wiring Connections . . . . . . . . . . . . . . . . . . . . . . 5-9

Figure 7.1 - SP500 Keypad and Display .....

Figure 7.2 - SP500 Menu Structure .......

Figure 7.3 - Example of a Program Mode Display.

Figure 7.4 - Example of a Monitor Mode Display

Figure 8.1 - Manual Torque Boost Adjustment Range

. 7-1

. 7-4

. 7-5

.. 7-6

. 8-6

SP500 AC Drive installation and Operation Manual, Version 3.1

Figure 8.2 - Volts/Hertz Curve. . 8-7

Figure 9.1 - DC Bus Terminals on Model 1 SU1xxxx and 1 SU2xxxx Drives ........................... 9-2

Figure 9.2 - DC Bus Terminals on Model 1 SU4)000( and 1 SU5¤xx Drives (except 1 SU4x015, 1 SU4)(020) . . 9-2'.

Figure 9.3 -DC Bus Terminals on Model 1 SU4x015 and 1 SU4x020 Drives .......................... 9-3

Figure E.1 - AC Mains Filter Dimensions ............

Figure E.2 - Typical SP500 Single-Phase Connections

Figure E.3 - Typical SP500 Three-Phase Connections .

Figure E.4- 1/0 Signal Cable.............................

Table of Contents

. E-3

.. E-5

.. E-5

.. E-7

V

V1

Table 2.1

Table 2.2

Table 2.2

Table 2.3

Table 3.1

Table 3.2

Table 3.3

Table 3.4

Table 3.5

Table 3.6

Table 3.7

Table 3.8

Table 7.1

Table 7.2

Table 7.3

Table 8.1

Table 8.2

Table 9.1

Table 9.2

Table 9.3

List of Tables

- SP500 Model Number Notation .................

- Power and NEMA Enclosure Ratings.................

- Power and NEMA Enclosure Ratings (Continued)

-SP500 Option Kits .............................

- Air Flow Clearances .................................................

- Recommended Power Wire Sizes for M/N 1 SU1 xx= and 1 SU2)000( Drives ....

- Recommended Power Wire Sizes for M/N 1 SU4xxxx and 1 SU5xxxx Drives .....

- Recommended Power Wire Sizes for M/N 1 SU4x015 and 1 SU4x020 Drives............

- Recommended Power Terminal Tightening Torque ...................

- Recommended Control and Signal Wire Sizes and Tightening Torque

- Motor Lead Length Guidelines .....................................

- AC Input Line Fuse Selection Values . . ...................

- Key Descriptions ..............

- Drive Status LED Descriptions

- Monitor Mode LED Descriptions .

- Multi-Speed Presets Digital Inputs ...

- Auto-Restartable Faults ............

- Drive Faults and Corrective Actions

- Resistance Checks for Input Diodes

- Resistance Checks for IGBTs ......

Table A.1 - Service Conditions .......

Table A.2 - Dimensions ...............

Table A.3 - Environmental Conditions

Table A.4 - Drive Inputs .............

Table A.5-Drive Outputs ....................

Table E.1

Table E.2

Table F.1

Table F.2

Table F.3

- AC Mains Filters ......................................

-AC Mains Filter Mounting Dimensions and Weights ....

- Replacement Parts List for Model 1 SU2xxx)( Drives

- Replacement Parts Ust for Model 1 SU4)000( Drives

- Replacement Parts Ust for Model 1 SU5)000< Drives

. 2-6

..2-7

. 2-8

.. 2-13

. 3-4

3-4

... 3-5

... 3-5

... 3-5

. 3-5

. 3-6

. 3-7

. 9-3

..9-8

.. 9-9

. A-1

.. A-1

... A-1

...A-2

... A-2

. E-2

... E-4

. F-1

.. F-1

.. F-2

7-2

. 7-3

7-3

8-16

. 8-17

SP500 AC Drive Installation and Operation Manual, Version 3.1

W

1.0 Introduction

The products described in this manual are manufactured by Reliance Electric Industrial Company.

1.1 Who Should Use This Manual

This manual is intended for qualified electrical personnel responsible for installing, programming,starting up, and maintaining the SP500 drive.

1.2 Installation Overview

This manual describes how to install and troubleshoot the SP500 drive. Drive installation consists of

the following basic tasks:

• Plan your installation using the guidelines presented in chapter 3. If your installation must be incompliance with Electromagnetic Compatibility Standards, read Appendix E also.

• Mount the drive and install external components according to the guidelines presented inchapter 4.

• Wire the drive's input power, output power, and control signal terminal strip using the instructionsin chapter 5.

• Adjust parameter values, if required. The parameters are described in chapter 8. For quickreference, the factory-set values are listed in Appendix B.

• Perform the power-off and power-on checks described in chapter 6 to complete the installation.

If problems occur during drive operation, refer to chapter 9. Appendix F lists the parts of the drive thatcan be replaced.

Before you begin the installation procedure, become familiar with the drive by reading chapter 2,which provides an overview of the drive and its features, chapter 7, which describes the operation ofthe keypad and the display, and Appendix A, which lists the drive's technical specifications.

1.3 Requesting Assistance from Reliance Electric

Introduction

If you have any questions or problems with the products described in this instruction manual, contactyour local Reliance Electric sales office. For technical assistance, calll-800-726-8112, Mondaythrough Friday, 8:00 AM to 5:00 PM (EST).

1-1

1-2 SP500 AC Drive Installation and Operation Manual, Version 3.1

1

2.0 Learning About the SP500 DriveThis chapter describes the SP500 drive and how to identify it based on its model number. Thischapter also provides power and enclosure rating information. ,

2.1 Standard Features

The SP500 drive has the following features:

• On-board keypad and display providing:

Start/Stop/Reset control

FonNard/Reverse (reverse-disable selectable)

Setpoint adjustment

Motor RPM, %load, or output voltage display

Drive diagnostics

• 500 millisecond power dip ride4hrough

• 150% overload for one minute

• 0.5 to 240 Hz three-phase voltage output

• NEMA 1 and NEMA 4/12 enclosures

• A snubber resistor braking signal and a scaled voltage analog output (0 to 10 VDCD which isproportional to:

Output frequency

Output amps

Output voltage

Selected reference

• Quiet motor operation with high carrier frequency selection

• Drive protection

C)vercurrent

Short circuit

Ground fault

Overvoltage

Undervoltage

Overtemperature

• UL/CSA electronic overload that meets NEC/CEC requirements

• User-selectable relay contact for indications of drive running, drive faulted, or drive at selectedspeed

• User-selectable power-up start, auto-restart, and coast-to-rest or ramp-to-rest stop functions

• User-selectable local or remote operation

• 29 user-adjustable software parameters

2.2 Drive Description

The SP500 drive is an AC PWM (pulse-width-modulated) inverter that operates on single- orthree-phase power. See figures 2.1 and 2.2. AC input power is applied to the drive's input terminals.

Learning About the SP500 Drive 2-1

2-2

Voltage transients are suppressed by three metal-oxide-varistor (MOV) suppressors. Thesesuppressors keep any input voltage transients within the maximum voltage rating of the input diodemodule.

The input diode module rectifies the incoming AC voltage into a constant DC bus voltage which isfiltered by the DC bus capacitor bank. An internal DC-to-DC power supply uses power from the DCbus and provides the necessary voltages required by the drive. Under regulator software control, the

*

IGBT (insulated-gate bipolaMransistor) inverter bridge converts the constant DC voltage into an ACPWM waveform. The regulator switches the IGBT inverter bridge using a 4,6, or 8 kHz carrierfrequency (user-selectable). A low carrier frequency maximizes the power rating of the drive but alsoincreases acoustic noise. A high carrier frequency selection reduces acoustic noise but results in aderating of the drive's efficiency.

The volts per hertz (V/Hz) regulator governs the open-loop operation of the drive for adjustable-speed performance of AC induction and synchronous motors. The regulator maintains a ratio ofvoltage to output frequency that provides constant or variable torque across a wide speed range.Drive operation can be adjusted by the parameters entered through the keypad. A microprocessoron the Regulator board controls drive regulation. See figure 2.3. The Regulator board acceptsinternal power feedback signals and an external speed reference signal. The Regulator boardprovides display data for a four-character display, which is used to indicate drive parameters,parameter values, and fault codes.

The drive can be controlled either locally through the keyboard and display (see section 7) orremotely through the terminal strip (see section 5).

The drive is intended to operate trip-free under any condition. The drive uses selected signals toextend the acceleration (starting) and deceleration (stopping) rates of the motor when an overcurrentcondition occurs. When a fault does occur, however, the regulator generates an instantaneouselectronic trip (IET) signal to turn the drive off (coast40-rest). The drive stores an indication or recordof the IET fault, which can be viewed on the four-character display. After a fault, the STOP/RESET key

or a user-supplied IET RESET pushbutton must be pressed to reset the IET signal and clear the fault from the drive.

SP500 AC Drive installation and Operation Manual, Version 3.1

.

W

88

U

g8=E

E

-%.2 000.-0

X90D

S5

LO

*--0-0

4

D > 9

.K

Learning About the SP500 Drive

BiB

2b

S

W55&

,-0

M

S *o

Z=>Ii

CK Ul +

III

999

N

1 050

Z0

5D

n n:

Z2

0

0

50<C

1 05*Or-

62558O0Ir

0

80

5

0-«>

+ 1

Figure 2.1 - SP500 System Diagram

589

n

&7

8 821 >m

1 m-

C\1

0,1

eE

0

a-

3U)

6g0-

E

SuUS

S:

0

:

5 485351c

0* U

We W

L

Wr

5g

0

4

2-3

2-4

SCO

Cn

0

-599

U

N

g

g+

LAI

LUCKLuLlLL;

EL.Cl.

M

9--

N

D

LL

01-

X

W

E9

E

-J

Z

8

5

0BOW0

"1

ro

8

LO

+

00

f(Z

U)

0

5

0

SZ

5

u)

lo

3Ul

I

0

9E('0

B

8

0

d

5C

0

:

S

5

[1

5

m

5

m

-1

* Ir OnQU,2

5@m

# 10 M

22

el

Z

8

E

Cz

00

* tO (0'---

4

_5

0

CD

Z

CE

CKLLI

0

f f

0660

Ld

5

L- {'1')

0- c> co A W

[1

m

a

=f-0 Figure 2.2 - SP500 System Diagram (Continued)

LU

CL

0

B

LJ

EOfLLl

Bil

Eng00

00911]0

SP500 AC Drive installation and Operation Manual, Version 3.1

&2KB

0000

EP:

i&2&

0000

.

2

0

000000002_0000@00

1 2 3 4 5 6 7 8 910111213141516

.0U5er 1/0 Terminal Strip

1Q1

88

Learning About the SPSOO Drive

Display

88

7-Pin J5

Figure 2.3 - Regulator Board Component Locations

0

8210

Sg0

0

2-5

2-6

2.3 Identifying the Drive by Model Number

A model number identifies each SP500 AC drive. See figure 2.4. This number appears on theshipping label and on the drive's nameplate located on the right side of the drive housing. The drive's model number contains codes that indicate: input voltage range, enclosure rating, and horsepowerrating. See section 2.3.1 for more information on the drive power ratings. See section 2.3.2 for moreinformation on the drive enclosure ratings.

Basic Catalog Number

Horse

001

002

003

005

007

010

015

020

LabelingU = UL Listed, IEC Certified

Voltage1 = 115 VAC2 = 200 - 230 VAC4 = 380 - 460 VAC5 = 575 VAC

Standard Model Number

1SU21001

Endosure

1 = NEMA 1 or Chassis

2 = NEMA 12 Only4 = NEMA 4X (Indoor Only)/NEMA 12

power Rating= 0.25 to 1.0 HP

= 2.0 HP

= 3.0 HP

= 5.0 HP

= 7.5 HP

= 10.0 HP

= 15.0 HP

= 20.0 HP

Figure 2.4 - Identifying the Drive Model Number

All SP500 drives described in this instruction manual function in the same manner. To identify themechanical differences between certain models, the manual uses the notation in table 2.1.

Model Notation

1 SU 1 >000<

1 SU2xxxx

1 SU4xxxx

1 SU5)000<

Table 2.1 - SP500 Model Number Notation

Input Voltage

115 VAC

208 - 230 VAC

380 - 460 VAC

575 VAC

Horsepower

1/4 -1 HP

1,2,3,5,7.5,10 HP

1,2,3,5,7.5,10,15,20 HP

1,2,3,5,7.5,10 HP

SP500 AC Drive Installation and Operation Manual, Version 3.1

2.3.1

Model

Number

Power Ratings and NEMA Enclosure Ratings

Table 2.2 provides SP500 drive power and NEMA enclosure ratings.

1 SU11001

1 SU14001

1 SU21001

1 SU24001

1 SU21002

1 SU21001

1 SU24001

1 SU21002

1 SU24002

1 SU21003

1 SU24003

1 SU21005

1 SU24005

1 SU41001

1 SU44001

1 SU41002

1 SU44002

1 SU41003

1 SU44003

1 SU41005

1 SU44005

1 SU41007

1 SU44007

1 SU41010

1 SU44010

1 SU41015

1 SU42015

1 SU41020

Input Powerand Horsepower

Rating*

Single-Phase - 1 HP

Single-Phase - Demo

Single-Phase -1 HP

Single-Phase - 1 HP

Single-Phase - 2 HP4 kHz Carrier

6 kHz Carrier

8 kHz Carrier

Three-Phase - 1 HP

Three-Phase - 1 HP

4 kHz Carrier

6 kHz Carrier

8 kHz Carrier

Three-Phase - 2 HP

4 kHz Carrier

6 kHz Carrier

8 kHz Carrier

Three-Phase - 2 HP

Three-Phase - 3 HP

Three-Phase - 3 HP

Three-Phase - 5 HP

Three-Phase - 5 HP

Three-Phase - 1 HP

Three-Phase - 1 HP

Three-Phase - 2 HP

Three-Phase - 2 HP

Three-Phase - 3 HP

Three-Phase - 3 HP

Three-Phase - 5 HP

Three-Phase - 5 HP

Three-Phase - 7.5 HP

Three-Phase - 7.5 HP

Three-Phase - 10 HP

Three-Phase - 10 HP

Three-Phase - 15 HP

Three-Phase - 15 HP

Three-Phase - 20 HP

Learning About the SPSOO Drive

NEMA

Rating

1

1

1

4X/12

1

1

4X/12

4X/12

1

4X/12

1

4X/12

1

4X/12

1

4X/12

1

4X/12

1

4X/12

1

4X/12

1

4X/12

1

12

1

Enclosure

Size **

A

A

A

A

A

A

A

C

C

C

C

C

B

B

B

B

B

B

B

B

C

C

C

C

D

D

D

Table 2.2 - Power and NEMA Enclosure Ratings

AC InputVolts

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

200-230

380-460

380-460

380-460

380460

380-460

380-460

380-460

380-460

380-460

380-460

380-460

380460

380-460

380-460

380-460

115

115

InputAmps

13.1

7.0

6.4

5.2

5.2

5.2

9.9

5.0

5.0

9.9

9.3

8.7

19.1

17.2

15.3

12.5

12.5

17.2

17.2

2.5

2.5

4.2

4.2

6.4

6.4

9.9

9.9

13.4

13.4

17.2

17.2

25.4

25.4

32.7

InputKVA

1.5

0.6

1.3

1.3

4.4

4.0

3.5

2.8

2.6

2.0

2.0

4.0

3.8

3.5

4.0

5.0

5.0

6.9

6.9

8.0

8.0

10.7

10.7

13.7

13.7

20.2

20.2

26.1

2.0

2.0

3.3

3.3

5.1

5.1

OutputAmps*

6.8

2.0

5.0

4.5

3.6

3.6

7.5

7.0

6.5

1.7

1.7

7.5

7.0

6.5

7.5

10.6

10.6

14.2

14.2

11.1

11.1

14.2

14.2

21.0

21.0

27.0

2.1

2.1

3.4

3.4

5.3

5.3

8.2

8.2

Power

Loss

Watts ***

80

80

70

70

120

210

210

250

250

70

70

70

70

70

70

120

120

120

70

60

60

100

100

140

140

180

180

210

210

250

250

375

375

600

2-7

2-8

Model

Number

1 SU42020

1 SU51001

1 SU54001

1 SU51002

1 SU54002

1 SU51003

1 SU54003

1 SU51005

1 SU54005

1 SU51007

1 SU54007

1 SU51010

1 SU54010

Table 2.2 - Power and NEMA Enclosure Ratings (Continued)

Input Powerand Horsepower

Rating*

Three-Phase - 20 HP

Three-Phase - 1 HP

Three-Phase - 1 HP

Three-Phase - 2 HP

Three-Phase - 2 HP

Three-Phase - 3 HP

Three-Phase - 3 HP

Three-Phase - 5 HP

Three-Phase - 5 HP

Three-Phase - 7.5 HP

Three-Phase - 7.5 HP

Three-Phase - 10 HP

Three-Phase - 10 HP

NEMA

Rating

12

1

4X/12

1

4X/12

1

4X/12

1

4X/12

1

4)</12

1

4X/12

Enclosure

Size **

D

B

B

B

B

B

B

B

B

C

C

C

C

AC InputVolts

380-460

575

575

575

575

575

575

575

575

575

575

575

575

InputAmps

32.7

2.0

2.0

3.4

3.4

5.2

5.2

7.5

7.5

10.9

10.9

14.5

14.5

InputKVA

26.1

5.1

5.1

2.0

2.0

3.3

3.3

7.5

7.5

10.9

10.9

14.4

14.4

OutputAmps*

27.0

1.6

1.6

2.7

27

4.3

4.3

6.2

6.2

9.0

9.0

12.0

12.0

600

50

50

90

90

120

120

150

150

Power

Loss

Watts ***

* To properly size the drive for motor nameplate horsepower and amps, refer to section 3.5 for more information. Derating for 4,6,8 kHz carrier frequencies is not required except for the units indicated.

** Refer to section 2.3.2 for more information on enclosure sizes.

*** Full-load at all carrier frequencies. Refer to section 3.1.3 for more information.

2.3.2

2.4

Enclosure Ratings and Sizes

Each of the SP500 drives have one of the following NEMA ratings:

NEMA

Rating

1

4X/12

Description

Vented. For general-purpose indoor applications.Not vented. Supplied with base and keypad gaskets. For use in indoorenvironments that require a water-tight and dust4ight enclosure. Anenclosure with this NEMA rating encompasses both ratings (4X and 12).

12 Intended for use in indoor environments that require a dust-tight anddrip4ight enclosure.

See table 2.2 for a listing of drive model numbers and their individual NEMA ratings.

For clarity in this manual, SP500 drive enclosures are identified by size as enclosures A through D.Refer to table 2.2 for a listing of the drive model numbers and their individual enclosure sizes. Referto section 3.1.1 for the dimensions of enclosures A through D.

Component Locations

Figures 2.5 through 2.8 show the main components of the SP500 drives (enclosures A through D).Appendix F lists replacement parts.

SP500 AC Drive installation and Operation Manual, Version 3.1

180

180

250

250

/

V 7 U le olf w

39El

0

0000000000000000

1011

8.8.8.8. 4]1']Mode 1 FO'A,Cm RJU m RUN .211 dfEE. .'

O [Z] % LOGo [I] Program C[III Voks 0 Forward | S. I-EQE. 1gl Remote Reverse l RESET

r

e ©

L. 0110 0

nfl

0

11 - 1

Learning About the SP500 Drive

0

CO-#

0Io J

0

/

0

0

-

[rf)

1 3

1 29 '*1 -

0 0

/

CONTROL TERMINALSTRIP

REGULATOR PCB

MEMBRANE SWITCH/BRACKET ASSEMBLY

INTERNAL FAN

ASSEMBLY

POWER TERMINAL

STRIP

POWER PCB

GND CONNECTION

Figure 2.5 - Enclosure A Component Locations

2-9

2-10

CONTROL TERMINALE-- STRIP

REGULATOR PCB

F BRACKET ASSEMBLYMEMBRANE SWITCH/

INTERNAL FAN

ASSEMBLY --7

------urIf

40

\ 1('11

RAR v

Es«d RUN

ProgramForward

Remote Reverse

e /--,4Ir =

11 */ 111

(

\ 0.

1 u..1. 1 lili.lili

LE_11 1START 1 -STOP

1 RESEr Yi j

1 - -1-1- - 11 1-%s 24 4L

11

1

/1, 1 @ :=52==5 (h" 1«,S k

CAPACITOR PCB TI L(3&5 HP ONLY)

L-- POWER TERMINALSTRIP

+

0

+1*1+ 1 //-11

111 f@7 FL

POWER PCB

GND CONNECTION

Figure 2.6 - Enclosure B Component Locations

SP500 AC Drive Installation and Operation Manual, Version 3.1

f

O/

CONTROLTERMINALSTRIP

--- REGULATOR PCB-- MEMBRANE SWITCH/

1 BRACKET ASSEMBLY_ INTERNAL FAN

ASSEMBLY@ 1 1* " --1-{11-' I f--6-7 11 ]-2011 4, J *-4 "1 i \,R i id 1111

7. tfa 1-€- fi

lU

1 1 d .i @ 1!.1 /f, 1 [-111 01 1

8.8.8.8. ZI I '1 jE RDM RUN ®Volts /2/ Fo,•aid 5'AR-

SIOP

Remole Cl Reverse RESET

--

0,----

\\

1 \\ 1

\

-1 /

\\ \44 1

¢

t

r

/ 11..

1 1 61.

//.

@

11

B

@ 0

1 1 1 ..dll

O - Lit O- fe e@

il ,

-LIJ 42 + + 1+1*14 *' 4 1+It & /\

It/1 Ll It \

CAPACITOR PCB POLR PCB_ 1 STRIPGND CONNECTIONS

POWER TERMINAL->

Learning About the SP500 Drive

Figure 2.7 - Enclosure C Component Locations

2-11

1

2-12

S

CONTROLTERMINAL7 STRIP

f\0 15 k \ 3

1 »0010.000 1

RARR-Z--33

MEMBs *1* 14ZZ}si---1-- 1

157-3

k:

6

(3«46'

CAPACITOR PCB

POWER PCB -

POWER TERMINAL STRIP

REGULATOR PCB

- MEMBRANE SWITCH/BRACKET ASSEMBLY

INTERNAL FAN

ASSEMBLY

E -

000.01 1 /

1__-2__-r-'

.% 4.

n-

' ,i///

\ 1/'11 0

i :fig.k ed--{71*::ss

@

A DANGER

t

/.

.-h

4." 11

0

lilli IN i-Ll i

0

r.--

e

1-.k.

%\

0*k

0

./ W A \

04/\\ 1-'r/1»JS

'-4 I lin_1j / THERMAL SWITCH

GND CONNECTIONS

Figure 2.8 - Enclosure D Component Locations

03

SP500 AC Drive Installation and Operation Manual, Version 3.1

.

2.5 Option Kits

Table 2.3 provides a listing of the available SP500 option kits.

Table 2.3 - SP500 Option Kits

Option Kit Description

Low Energy Snubber Resistor Braking Kit forM/N 1 SU2xxxx Drives

Low Energy Snubber Resistor Braking Kit forM/N 1 SU4xxxx Drives*

Low Energy Snubber Resistor Braking Kit forM/N 1 SU4x015 and 1 SU4x020 Drives

Low Energy Snubber Resistor Braking Kit forM/N 1 SU5)000( Drives*

Option KitModel Number

2082005

2084010

2SR40700

2SR41800

2D85010

Instruction

Manual

D2-3178

D2-3179

D2-3291

D2-3180

* Snubber resistor braking kits for M/N 1 SU4)000 and 1 SU51000 drives require connection to the snubberresistor braking l OV power supply. See section 5.2.4 for more information.

Learning About the SP500 Drive 2-13

2-14 SP500 AC Drive installation and Operation Manual, Version 3.1

4

.

3.0 SP500 System Planning

. This chapter provides information that you must consider when planning an SP500 drive installation.Installation site, wiring, and motor application requirements are included.

A ATTENTION: Only qualified electrical personnel familiar with the construction andoperation of this equipment and the hazards involved should install, adjust, operate, orservice this equipment. Read and understand this manual and other applicablemanuals in their entirety before proceeding.

ATTENTION: Use of power correction capacitors on the output of the drive can result inerratic operation of the motor, nuisance tripping, and/or permanent damage to thedrive. Remove power correction capacitors before proceeding.

ATTENTION: The user is responsible for conforming with all applicable local, national,and international codes.

3.1 Installation Site Requirements

3.1.1

It is important to properly plan before installing an SP500 drive to ensure that the drive's environmentand operating conditions are satisfactory. Note that no devices are to be mounted behind the drive.This area must be kept clear of all control and power wiring. Read the following recommendationsbefore continuing with the drive installation.

Before deciding on an installation site, consider the following guidelines:

• The area chosen should allow the space required for proper airflow as specified in sections 3.1.1and 3.1.2.

• Do not install the drive above 1000 meters (3300 feet) without derating output power. For every91.4 meters (300 feet) above 1000 meters (3300 feet), derate the output current by 1 %.

• Verify that the drive location will meet the following environmental conditions:

Operating temperature (ambient): 0 to +40'C (32 to 104'F)

Storage temperature (ambient): - 40 to +65'C (-40 to +149'ID

Humidity: 5 to 95% (non-condensing)

• Verify that NEMA 1 drives can be kept clean, cool, and dry.

• Be sure NEMA 1 drives are located away from oil, coolants, or other airborne contaminants.

• Verify that the AC power distribution system meets the service conditions specified in table A.1.

Determining the Total Area Required for Installation

Figures 3.1 to 3.4 provide drive dimensions for enclosures A through D as an aid in calculating thetotal area required by the SP500 drives. Appendix A lists drive weights.

SP500 System Planning 3-1

3-2

r

6

E

ii

%'ELEE

CO

CO

EEElo

0'1

:0

EE

146.Omm [5.751

'pe.90-251 1%='1 SP 5003/c 1*

,- I.ill

V/ SP 500 -

8.8.8.88 76 8,4-EZLEZ=

AV [

Rgil

1 f'df .,2-26:e.at"lijC j

222.3mm [8.751-198.1 mm [7.801

12.1 mm [0.481

73.Omm [2.88"]

P

EE

8N

Figure 3.1 - Enclosure A Dimensions

/

Il

088,8, GIE]

UU' Ull 11111

F07.Omm [0.281

Figure 3.2 - Enclosure B Dimensions

r

0

EE

C4

r

E

EE

A

0-'1

f \

121.9mm [4.80"1

,

,

,

11

1 "1'.1:Bili i i

d

U

160.1 mm [6.307

"31"lia

52-.

l'Ir

SP500 AC Drive Installation and Operation Manual, Version 3.1

-J

Am,=fil:i

i

.

.

a

CN

EE-

1

EE00

0

K

278.1 mm [10.97248.Omm [9.81

- -12.4mm [0.5-1-7lzY'

SP 500

.

1 89.98 [El[El

J Mt@li = rf

=j roy'-W W 11111-11JU

E

F08.Bmm [.351

Figure 3.3 - Enclosure C Dimensions

286.5mm [11.287

223.Ornm [8.78731.7mm [1.251

61-r " .

1 1

SP500 System Planning

SP 500

Mit@,8.

// Ji

1 /41Lrl u' 11181 1111. , 1.11 n_1

F- 010.Omm [0.391

r.

CMi

EE/9

S

r

S

EE

/9

Figure 3.4 - Enclosure D Dimensions

158.2mm [6.27---11

a/54

-%/r

198.9mm [7.837 1

0

0

0

\uul -

i

-

3-3

1

3-4

3.1.2 Providing Proper Air Flow Clearances

Be sure there is adequate clearance for air ventilation around the drive. For best air movement, donot mount SP500 drives directly above each other. Note that no devices are to be mounted behindthe drive. This area must be kept clear of all control and power wiring. See table 3.1 for a listing of therecommended air flow clearances.

Table 3.1 - Air Flow Clearances

Minimum distance from the sides of the drive if

adjacent to non-heat producing equipment

Minimum distance from the top and bottom of thedrive if adjacent to non-heat producing equipmentMinimum distance from the sides of the drive if

adjacent to other drives

Minimum distance from the top and bottom of thedrive if adjacent to other drives

3.1.3 Verifying the Drive's Power Loss Rating

A

51 mm

(27102 mm

51 mm

(2")254 mm

(10")

B

Enclosure

102 mm

(4'3

102 mm

(4")

102 mm

(4")

254 mm,

C

102 mm

(4')

102 mm

(4")102 mm

(4")254 mm

(10")

D

102 mm

(4")

102 mm

(4")

102 mm

(4")

102 mm

(47

When installing an SP500 drive inside of another enclosure, you should consider the drive's wattsloss rating shown in table 2.2. This table lists the typical full load power loss watts value under alloperating carrier frequencies. Ensure adequate ventilation is provided based on the drive's watts lossrating.

3.2 Wiring Requirements

3.2.1

Evaluate the following areas of drive wiring before you do the installation: size of available conduit, size of power and control wiring, and motor lead lengths.

Verifying Conduit Sizes

It is important to determine the size of the conduit openings accurately so that the wire planned for aspecific entry point will fit through the opening. Figures 4.1 through 4.4 show conduit opening sizes.

3.2.2 Recommended Power Wire Sizes

Size input power wiring according to applicable codes to handle the drive's continuous-rated inputcurrent. Size output wiring according to applicable codes to handle the drive's continuous-ratedoutput current. Tables 3.2,3.3, and 3.4 provide recommended power wiring sizes. Use only copperwire with a minimum temperature rating of 60/75'C. Table 3.5 contains the recommended tighteningtorque values for all power wiring terminals.

Table 3.2 - Recommended Power Wire Sizes for M/N 1 SUl )000 and 1 SU2xxxx Drives

Type of Wiring

AC Input Power

Output Power

DC Bus

Terminals

R, S, T

U, V, W

GND

Size of Wire

(maximum)*

14 AWG, 2 (mm2)

14 AWG, 2 (mm2)14 AWG, 2 (mm2)

Ground 14 AWG, 2 (mm2)

* Except for M/N 1 SU21002 (single-phase input), 1 SU21005, and 1 SU24005, for which 12 AWG, 3 (mm2) wire isrecommended.

SP500 AC Drive Installation and Operation Manual, Version 3.1

Table 3.3 - Recommended Power Wire Sizes for M/N 1 SU4)000( and 1 SU5xxxx Drives

Type of Wiring

AC Input Power

Output Power

DC Bus

Snubber Resistor

Ground

Terminals

R(Ll),S(1-2),T(L3)

l.151),V(12),Wrr3)

+10 VDC, 10 COM

GND

Size of Wire

(maximum)*

14 AWG, 2 (mm2)

14 AWG, 2 (mm2)14 AWG, 2 (mm2)14 AWG, 2 (mm2)

14 AWG, 2 (mm2)

* Except for M/N 1 SU41010 and 1 SU44010, for which 12 AWG, 3 (mm5 wire is recommended.

Table 3.4 - Recommended Power Wire Sizes for M/N 1 SU4x015 and 1 SU4x020 Drives

Drives

All

Type of Wiring

AC Input Power

Output PowerDC Bus

Snubber Resistor

Ground

Terminals

R/Ll, S/L.2, T/L3

U/Tl, V/T2, WF3

GND

Size of Wire

(maximum)

12 AWG, 3 (mm2)

12 AWG, 3 (min2)

12 AWG, 3 (mr,12)12 AWG, 3 (mm2)

12 AWG, 3 (mm2)

Table 3.5 - Recommended Power Terminal Tightening Torque

Terminals

All power wires

Maximum Tightening Torque

1.08 Newton-meters (9.5 in-lb)

3.2.3 Recommended Control and Signal Wire Sizes

Table 3.6 shows the recommended wire sizes to connect 1/0 signals to the terminal strip on theRegulator board. The minimum wire insulation rating is 600V. Operator controls can be up to 303meters (1000 feet) from the SP500 drive. All signal wires should be twisted-pair.

Table 3.6 - Recommended Control and Signal Wire Sizes and Tightening Torque

Drives

All

Terminals

1-16

Minimum

Wire Size

20 AWG, 0.5 (mm2)

3.2.4 Recommended Motor Lead Lengths

Maximum

Wire Size

14 AWG, 2 (mm2)

Maximum

Tightening Torque

0.5 Newton-meters

(4.5 in-lb)

The following motor lead lengths are recommended to reduce line disturbances and noise. Seefigure 3.5.

• For applications using one motor, motor lead length should not exceed 76 meters (250 feet).

• For applications with multiple motors, total motor lead length should not exceed 76 meters(250 feet).

When total lead length exceeds 76 meters (250 feet), nuisance trips can occur, caused by capacitivecurrent flow to ground. Note that these capacitively-coupled currents should be taken intoconsideration when working in areas where drives are running. If the motor lead length must exceedthese limits, the addition of output line reactors or other steps must be taken to correct the problem.See table 3.7. Note that the motor lead lengths shown in table 3.7 are only guidelines. Yourapplication may be restricted to a shorter motor lead length due to:

• the type of wire

• the placement of the wire (for example, in conduit or a cable tray)

• the type of line reactor

• the type of motor.

SP500 System Planning 3-5

3-6

38m (125')

SP500 Drive

Motor Motor

38m (125115m (50')

SP500 Drive

Motor

SP500 Drive

61 m (200')

107m

(350')

(1)

(2)

\

Motor

61 m (200')

All examples represent 76m (250') of motor lead length.

1 HP at 4 kHz

76 m

(250')Yes

91 m

(300')

(1)

(2)

Bm (25') Bm (251( Motor ) ( Motor )

Figure 3.5 - How to Measure Motor Lead Lengths

Table 3.7 - Motor Lead Length Guidelines

122 m

(400')(1)

137 m

(450')

(1)

Distance to Motor

152 m

(500')

(1)

183 m

(600')

NO

213 m

(700')No

SP500 Drive

Motor

244 m

(800')

No

76m (250')

274 m

(900')

NO

1 HP at 6/8 kHz Yes (2) (2) (2) No No No No

2 HP at 4 kHz Yes Yes Yes (1) (1) (1) No No No No

2 HP at 6/8 kHz Yes Yes Yes (1) (1) (1) ' (1) (1) No No

3 HP at 4 kHz Yes Yes Yes Yes (1) (1) (1) (1) No No

3 HP at 6/8 kHz Yes Yes Yes Yes (1) (1) (1) (1) (1) (1)5 HP Yes Yes Yes Yes Yes Yes (1) (1) (1) (1)

7.5-10 HP Yes Yes Yes Yes Yes Yes (3) (3) (3) (3)15-20 H P Yes Yes Yes Yes Yes Yes (4) (4) (4) (4)

(1) Requires the use of the following MTE 5% reactor*. Reactor with LC filters P/N RL-00803(3 or reactor without LC filters P/N RL-00803.

(2) Requires the use of the following MTE 5% reactor*. Reactor with LC filters P/N R!:00202C or reactor without LC filters P/N RL-00202.

(3) Requires the use of the following MTE 5% reactor*. Reactor with LC filters P/N R601803C or reactor without LC filters P/N AL-01803.

(4) Requires the use of the following MTE 5% reactor*. Reactor with EC filters P/N Rl-03513C or reactor without LC filters P/N RL-03503.*Note that reactors may reach temperatures exceeding 100'C (212'F).

3.3 Selecting Input AC Line Branch Circuit Fuses

ATTENTION: Most codes require that upstream branch circuit protection be provided

0 the fuse ratings.to protect input power wiring. Install the fuses recommended in table 3.8. Do not exceed

Input line branch circuit protection fuses must be used to protect the input power lines. See figure5.1. Table 3.8 shows recommended fuse values. These fuse ratings are applicable for one drive perbranch circuit. No other load may be applied to that fused circuit. Note that contactors and circuitbreakers are not recommended for AC input line branch protection.

SP500 AC Drive Installation and Operation Manual, Version 3.1

305 m

(1000')No

(1)

(1)

(3)

(4)

No

No

No

No

Model

Number

1 SU11001

1 SU14001

1 SU21001

1 SU24001

1 SU21002

1 SU21001

1 SU24001

1 SU21002

1 SU24002

1 SU21003

1 SU24003

1 SU21005

1 SU24005

Fuse

Rating*

20A

12A

1 SU41001

1 SU41007

3.4 Installing an Emergency Stop

10A

10A

30A

12A

12A

20A

20A

25A

25A

35A

35A

Table 3.8 - AC Input Line Fuse Selection Values

Model

Number

1 SU44001

1 SU41002

1 SU44002

1 SU41003

1 SU44003

1 SU41005

1 SU44005

1 SU44007

1 SU41010

1 SU44010

1 SU41015

1 SU42015

1 SU41020

1 SU42020

* Recommended fuse type: UL Class J, 600V, time-delay, or equivalent.

3.4.1

Fuse

Rating*

6A

6A

8A

8A

1 SU54001

1 SU54010

ATTENTION: The user must provide an external, hardwired emergency stop circuitoutside of the drive circuitry. This circuit must disable the system in case of improper

-operation. Uncontrolled machine operation may result if this procedure is not followed..

12A

12A

25A

25A

25A

25A

35A

35A

45A

45A

55A

55A

Model

Number

1 SU51001

1 SU51002

1 SU54002

1 SU51003

1 SU54003

1 SU51005

1 SU54005

1 SU51007

1 SU54007

1 SU51010

Fuse

Rating*

4A

4A

7A

7A

10A

10A

15A

15A

20A

20A

25A

25A

Depending upon the requirements of the application, the SP500 drive can be programmed to provideeither a coast-to-rest (default) or a ramp-to-rest (user-option) operational stop without physicalseparation of the power source from the motor. Refer to sections 5.2 and 8.3 (parameter F-16) formore information on how to program an operational stop.

In addition to the operational stop, users must provide a hardwired emergency stop external to thedrive. The emergency stop circuit must contain only hardwired electromechanical componants.Operation of the emergency stop must not depend on electronic logic (hardware or software) or onthe communication of commands over an electronic network or link.

Complying with Machinery Safety Standard EN 60204-1:1992

This section applies to users who must comply with machinery safety standard EN 60204-1:1992,part 9.2.5.4, Emergency Stop.

The SP500 drive coast-to-rest stop is a category 0 operational stop.The ramp-to-rest stop is acategory 1 operational stop.

The required external hardwired emergency stop must be either a category 0 or 1 stop, dependingon the user's risk assessment of the associated machinery. In order to fully comply with machinerysafety standard EN 60204-1:1992, part 9.2.5.4, at least one of the two stop methods must be acategory 0 stop. Refer to Appendix D for more information.

SP500 System Planning 3-7

3-8

3.5 Motor Considerations

To obtain motor nameplate horsepower, the drive's output current rating at the selected carrier ,frequency should be equal to or greater than motor nameplate current. If the motor nameplate 'current rating is higher than the drive's output current rating, derate motor horsepower by the ratio ofthe drive's output ampere rating (at the selected carrier frequency) to the motor nameplate current.Note that this approximation is only accurate if the drive and the motor have nearly the same rating.

3.5.1 Single-Motor Applications

Size the drive and motor for the load and speed requirements of the specific application.

The motor's operating current must not exceed the drive's rated output current (at the selectedcarrier frequency). In addition, the motor's horsepower rating (for example, 1,2,3,5,7,10,15, and20 HP) must not be more than one horsepower range larger than the drive's horsepower rating.

If the motor will be operated below one-half of its rated speed, the motor overload relay may notprotect the motor because of reduced cooling action due to the reduced speed. A motor thermostat,internal to the motor, should be installed to monitor the actual temperature of the windings.

3.5.2 Multiple-Motor Applications -

One drive can run two or more motors. Adhere to the following requirements to assure correct driveoperation in this case:

• When starting and stopping all the motors at the same time (using the drive for starting andstopping), the sum of the full-load sine wave currents of all the motors must be equal to or lessthan the maximum sine wave output current at the selected carrier frequency for the drive.

For example: |FLA + |FLA + |FLA

(Motor 1) (Motor 2) (Motor 3)

Where: ITLA 5100% rated drive output at the selected carrier frequency

|TLA

(Total Load)

• When one or more of the motors connected to the output of the drive are to start independently(using a secondary switching device to add or remove the motor from the circuit):

Any motor that starts or stops while the drive is running must have a current rating less than 10%of the maximum sine wave current rating of the drive at the selected carrier frequency.

The sum of the maximum full-load sine wave currents of all the motors connected continuously tothe drive must be less than the maximum output current rating under all conditions.

Note that each motor requires separate thermal overload protection (for example, a motor relay or amotor thermostat).

4

SP500 AC Drive installation and Operation Manual, Version 3.1

4.0 installing the Drive

. This chapter shows how to mount the SP500 drive and its external components. Also shown are theentry areas for routing wiring in and out of the drive.

4.1 Mounting the Drive

Attach the drive to the selected flat, vertical surface using the mounting holes provided. Enclosure Adrives have two mounting holes, which are accessible after the cover is removed. Enclosure B, C,and D drives have four mounting holes. In order to maintain a flat mounting surface and to ensurethat bolt tightness is maintained, use washers under the bolt heads. Refer to figures 3.1 through 3.4for drive mounting dimensions. Use the following user-supplied mounting bolts and washers:

• Enclosure A drives: two M6 (1/4")

• Enclosure B drives: four MB (5/16")

• Enclosure C drives: four M8 (5/16")

• Enclosure D drives: four M8 or M10 (5/16" or 3/8")

4.2 Routing Wires

All wiring should be installed in conformance with the applicable local, national, and internationalcodes (e.g., NEC/CEEC). Signal wiring, control wiring, and power wiring must be routed in separateconduits to prevent interference with drive operation. Do not route wires behind the drive. Usegrommets when hubs are not provided to guard against wire chafing. Figures 4.1 through 4.4 showthe wire routing, grounding terminal, and power terminal strips of the SP500 drives.

ATTENTION: Do not route signal and control wiring in the same conduit with powerwiring. This can cause interference with drive operation.

Do not route more than three sets of motor leads through a single conduit. This will minimizecross-talk that could reduce the effectiveness of noise reduction methods. If more than three

drive/motor connections per conduit are required, you must use shielded cable. If possible, eachconduit should contain only one set of motor leads.

ATTENTION: Unused wires in conduit must be grounded at both ends to avoid apossible shock hazard caused by induced voltages. Also, if a drive sharing a conduit is

, 0 being serviced or installed, all drives using this conduit should be disabled to eliminate= the possible shock hazard from cross-coupled motor leads.

installing the Drive 4-1

4-2

GROUND TERMINAL

SIGNAL OR CONTROL WIRING

- I Wel W ieL0 15%1 0 Ful

°BUr EB.0 Remote 0 Rm,ne

tE ' 1

Coo)

@e

A V

IE =1

4 00 0000

*-f---5D f RN 9 1 A-4

AC INPUT POWEROR

SNUBBER RESISTOR

WIRING

USER WIRE ROUTING

C )

)

( 1

,

* 3

n

100=1=00*0*04- -fir

1 Ef?

*=t4 4

0000

0

Figure 4.1 - Enclosure A Wire Routing Locations

0

CONTROL

TERMINAL

STRIP

REGULATOR

PCB

FRONT VIEW

POWER

TERMINAL

STRIP

MOTOR LEADS

OR

AC INPUT POWER

COVER

BOTTOM VIEW

BASE

OPENINGS FOR WIRE ENTRY

1 /2 - 14NPT PIPE THREAD4 PLACES; 2 TOP, 2 BOTTOM

SP500 AC Drive installation and Operation Manual, Version 3.1

.

Installing the Drive

0@ 4

6 (-3 #

+ +1 ,

CONTROL

TERMINALSTRIP

REGULATOR

PCB

411 @LJ

tnAr

1119'r

V

1- O- 1 5 1121

PF==a===[3=41 '1,1-23]LE) r7 - '=7, 50 1 1)1-=» / -hzz _[32__LC9]

n@

# @ 11

++ + +

0 - 'Imi

+ +

r--'

++

.e

@El

SIGNAL WIRING CONTROL WIRING AC INPUT POWER

OR OR AND

SIGNAL & CONTROL SNUBBER RESISTOR MOTOR LEADS

WIRING WIRING

USER WIRE ROUTING

1 lilli 1rj Q U u M,4& 1 D V.fu

FRONT VIEW

POWER

TERMINAL

STRIP

GROUND

TERMINAL

COVER

BOTTOM VIEW

BASE

(3) 1/2 CONDUIT HUBS (NEMA 4X/12)OR

1/2"-14NPT PIPE THREAD (NEMA 1)(3) PLACES

Figure 4.2 - Enclosure B Wire Routing Locations

4-3

4-4

L.

E-

, -9- *63 c, ''*-*&3:T IM/6.2£im*'*EM

1011

E-1 _01

8.8.88 A],1

=El= - 11 =

-1 0-7¥UZZZ--.

- 7 ; .1-

e

-Ir *----3 -1(fE011 *->tr

L__J J

B

® 0

„ „ IEZEzl,,

% 7

--- - ---f®®s/ @®r '@1 --=h'11 1-==4- , 1-lili /.-r=:;1'«

»f/»'p *\SIGNAL

WIRING

0

CONTROL

TERMINAL

STRIP

REGULATORPCB

FRONT VIEW

-,, POWERTERMINAL

STRIP

GROUNDTERMINALS

CONTROL AC INPUT POWER MOTOR LEADS

WIRING OR OR

SNUBBER RESISTOR AC INPUT POWER

WIRING AND MOTOR LEADS

USER WIRE ROUTING -

.-COVER

1 1

000*BOTTOM VIEW

BASE

(4) 1/2" CONDUIT HUBS (NEMA 4X/12)OR

1/2"-14NPT PIPE THREAD (NEMA 1)(4) PLACES

Figure 4.3 - Enclosure C Wire Routing Locations

SP500 AC Drive installation and Operation Manual, Version 3.1

.

Installing the Drive

f

0

SL

.E{El cIR:':-{

-

mr

L -11-----

YE>*

- *%:0 *111.1 ..0».-9.noo#*01 1 /

0, , -lo '- oIF I n

IllI 8.88.8 'A li! 1 --= r i--ti

MIME{Z][*] 1 b 1-oR_1-I- 1 111-1 j E- 1 0

1

81 I-7

.r

6 .C===E * 3 1 1/--- O- ISi*k_-:L_ 200F*-Trlb f-=--7 -7

1»»' »lj' 1*1-1SIGNAL CONTROL AC INPUT POWER MOTOR LEADS

WIRING WIRING OR OR

SNUBBER RESISTOR AC INPUT POWER

WIRING AND MOTORLEADS

USER WIRE ROUTING

UUuUUULJL L

Figure 4.4 - Enclosure D Wire Routing Locations

0

0

il

CONTROL

TERMINALSTRIP

- REGULATOR

PCB

FRONT VIEW

POWER

TERMINALSTRIP

GROUND

TERMINALS

COVER

OTTOM VIEW

- BASE

- NEMA 4)(/12 UNITS SUPPUEDWITH <3) 3/4" CONDUIT HUBSAND (1) 1/2" CONDUIT HUBAS SHOWN HERE

ORNEMA 1 UNITS SUPPLIED WITH

(1) 3/4" NEOPRENE PLUG AND(1) 1/2" NEOPRENE PLUG

4-5

4-6

4.3

4.3.1

Installing External Components

Install the input power and output power components that are located outside of the SP500enclosure. See figure 5.1. The following sections describe disconnect, transformer, and AC line branch protection installation.

Disconnects

An input disconnect (for example, a switch or circuit breaker) must be installed in the line before thedrive input terminals in accordance with local, national, and international codes (e.g., NEC/CEC).Size the disconnect according to the inrush current as well as any additional loads the disconnectmight supply. Coordinate the trip rating for the current (10 to 12 times the full load current) with thatof the input isolation transformer, if used. Refer to section 4.3.3 for additional information.

4.3.2 Input AC Line Branch Protection

A ATTENTION: Most codes require that upstream branch protection be provided to protect input

power wiring.

User-supplied branch circuit protection fuses must be installed according to the applicable local,national, and international codes (for example, NEC/CEEC). The fuses must be installed in the linebefore the drive's AC input terminals. Table 3.8 provides fuse values.

4.3.3 Transformers

aATTENTION: Distribution capacity above the maximum recommended system KVA rating(100 KVA for 115/230 VAC, 1000 KVA for 460/575 VAC) requires the use of an isolationtransformer, a line reactor, or other means of adding similar impedance to the drive's inputpower wiring.

ATTENTION: When the AC line is shared directly with other SCR-rectified drives, an optionalsnubber resistor braking kit might be required to alleviate excess DC bus voltage.

Input isolation transformers may be needed to help eliminate the following:

• Damaging line voltage transients.

• Line noise from the drive back to the incoming power source.

• Damaging currents that could develop if a point inside the drive becomes grounded.

Observe the following guidelines when installing an isolation transformer:

• A power disconnecting device must be installed between the power line and the primary of thetransformer. If the power disconnecting device is a circuit breaker, the circuit breaker trip ratingmust be coordinated with the inrush current (10 to 12 times the full load current) of thetransformer.

Do NOT use an input isolation transformer rated more than 100 KVA for 230 VAC (or 1000 KVA for460 VAC) with less than 5% impedance directly ahead of the drive without additional impedancebetween the drive and the transformer.

If your SP500 application requires the use of an output transformer, contact Reliance Electric forassistance.

SP500 AC Drive Installation and Operation Manual, Version 3.1

r

4.3.4 Output Contactors

ATTENTION: Any disconnecting means wired to drive output terminals U, V, and WA, must be capable of disabling the drive if opened during drive operation. If openedduring drive operation, the drive will continue to produce output voltage between U, V,

I W. An auxiliary contact must be used to simultaneously disable the drive or outputcomponent damage may occur.

Output contactors provide a positive means of disconnecting the motor from the drive. If your SP500application requires the use of output contactors, contact Reliance Electric for assistance.

4.3.5 Mechanical Motor Overload Protection

To provide the motor with overload protection, local, national, and international codes (for example,NEC/CEC) require that a motor thermostat, internal to the motor, be installed or an electronic thermalmotor overload relay, sized to protect the motor, be installed between the motor and the drive'soutput terminals.

The Electronic Thermal Overload parameter (F-14) may be used in place of the electronic thermalmotor overload relays in single motor applications. Note, however, that temperature-sensing devicesintegral to the motor are the best way of thermally-protecting AC motors under all conditions.Parameter F-14 must be enabled to provide overload protection. Refer to section 8.3 for theparameter description.

In multiple motor applications, each motor must have its own user-supplied overload protection.

4.4 Setting the Analog Input Jumper on the Regulator Board

SP500 drives have an analog speed reference input. This is a jumper-selectable 0 to 10 VDC or 0 to20 mA input with programmable gain and offset adjustments (parameters F-11 and F-12). Jumper J6on the Regulator board is set to match the type of incoming analog signal, either voltage or current.See figures 2.2,4.5, and 5.3. Refer to section 5.2.1 for more information.

installing the Drive

0

0000000*000*e000

1 2 3 4 5 6 7 8 91011 121314 1516

0-0.20 mAn tO-10 VDC

Figure 4.5 - Jumper J6 Settings for the Analog input Speed Reference

0

4-7

4-8

4.5

Use the following procedure to set jumper J6:

A ATTENTION: DC bus capacitors retain hazardous voltages after input power has been disconnected. After disconnecting input power, wait five (5) minutes for the DC bus

/ 0 capacitors to discharge and then check the voltage with a voltmeter to ensure the DCI--Il bus capacitors are discharged before touching any internal components.

Step 1. Turn off and lock out input power. Wait five minutes.

Step 2. Remove the cover from the drive by unscrewing the four cover screws.

Step 3. Verify that the DC bus voltage is zero by following the procedure in section 9.1.

Step 4. Locate jumper J6 on the Regulator board. Refer to figure 2.3.

Step 5. Move the jumper to the desired setting as shown in figure 4.5.

Step 6. Reattach the cover.

Step 7. Reapply input power.

Step 8. Verify that parameters F-11 and F-12 are correctly set.

Note that if the setting of jumper J6 is changed, the regulator software will not automatically detect it.Verify that parameters F-11 (gain) and F-12 (offset) are set correctly before starting the drive.

Preparing the Motor

Follow these guidelines when preparing to install the motor:

• Verify that the motor is the appropriate size to use with the drive.

• Verify that the total motor lead length does not exceed the values given in section 3.2.4.

• Follow the instructions in the motor instruction manual when installing the motor.

• Verify that the motor is properly aligned with the application's machine to minimize unnecessarymotor loading due to shaft misalignment.

• If the motor is accessible when it is running, install a protective guard around all exposed rotatingparts.

SP500 AC Drive installation and Operation Manual, Version 3.1

5.0 Wiring the Drive

. This chapter describes how to wire the SP500 drive including: input wiring, control and signal wiring,output wiring, and grounding.

5.1 Input Power Wiring

Use the following steps to connect AC input power to the drive:

Step 1. Verify that the AC input power to the drive corresponds to the drive's nameplate voltage andfrequency

Step 2. Wire the AC input power leads by routing them according to the type of enclosure. Seefigures 4.1 through 4.4. See tables 3.2 through 3.4 for recommended wire sizes.

A ATTENTION: Do not route signal and control wiring with power wiring in the same

conduit.This can cause interference with drive operation.

Step 3.

Step 4.

Wiring the Drive

Connect the AC input power leads to terminals R,S,T on the power terminal strip. Seefigure 5.1.

Tighten terminals R and S (single-phase input) or terminals R,S,T (three-phase input) to theproper torque as shown in table 3.5.

5-1

5-2

User-

Supplied

User-

Supplied

AC InputVoltage

GND

TITyManual

Disconnect SffFuse

Motor Overload

Relay (Optional ifElectronic

Overload is Used)

R/Ll S/l-2 T/1-3

4

Ugl V/2 W/3

M

SP500Drive

GND

n

GND

U-L

Figure 5.1 - Typical Electrical Connections

SP500 AC Drive installation and Operation Manual, Version 3.1

.

5.2 Signal and Control Wiring

&

2

8

The terminal strip on the Regulator board provides terminals for connecting signal (for example,external speed reference and analog output) and control (for example, stop, start, and function loss)wiring. See figure 5.2. Terminals for the following wire connections are provided:

• Terminals 1-3: analog speed reference connections

• Terminals 4-5: analog output connections

• Terminals 6-11: digital input connections

• Terminals 12-13: snubber resistor connections

• Terminals 14-16: output status connections

8

2 e

- C

5 25 10 m

5 2R O

5 E

SCL

3E E

80

9 n v E0

&522

CD

2

gw E

5 01 9

H

i15

E)

1/

0000000000000000678910 14 15 16123

1 1

Analog

SpeedReference

4 5

LJ I

AnalogOutput

Digital

Inputs

11 12 13

Snubber

Resistor

BrakingSignal

T E

S E5 82 0n

gEE0

0

S5

g0

0

i

OutputStatus

Relay

Figure 5.2 - Typical Control Terminal Strip Connections

5.2.1 Analog Speed Reference Wiring

g0

CE

0

Z

Analog speed reference input wiring connects to terminals 1 through 3 on the Regulator board'steminal strip. See figure 5.3. This reference signal is jumper-selectable for either a 0 to 10 VDC or 0 to20 mA input. The setting of jumper J6 on the Regulator board determines whether the input referenceis a voltage or current signal. This reference signal can be provided by either a user-supplied SK ohmpotentiometer or an external 0-10 VDC/0-20 mA supply. See section 4.4 for more information.

Wiring the Drive 5-3

5-4

+10VD

User-SuppliedSpeed Reference

Potentiometer

51<Q

0000012345

or

User-SuppliedSpeed Reference

Input Signal

0-10VDC

or

0-20mA

L

0000012345

Figure 5.3 - Analog Speed Reference Wiring Connections

5.2.2 Analog Output Wiring

\

Analog output wiring connects to terminals 4 and 5 on the Regulator board's terminal strip. Seefigure 5.4. This is a scaled 0 to 10 VDC output signal that is proportional to either current speed,percent of load, calculated output voltage, or percent of the selected reference value, whichever isselected through parameter F-29. This output signal is available during both local and remoteoperation.

5.2.3 Digital Input Wiring

Load

(User-SuppliedAnalog Meter)

+ 0-

000000@\1234 567

+lov OV

Figure 5.4 - Analog Output Wiring Connections

Digital input wiring connects to terminals 6 through 11 on the Regulator board's terminal strip. Thedrive has a 24 VDC power supply that provides the required voltage for control signals. Enabling ordisabling a control signal requires that a contact (switch) be opened or closed.

Start and Stop Control Wiring

Start and stop control wiring connects to terminals 6,7, and 11. See figures 5.5 and 5.6. Note thatthese starUstop wiring connections are not to be used in multi-speed preset applications which arediscussed in the following section.

SP500 AC Drive Installation and Operation Manual, Version 3.1

Wiring the Drive

Start/Stop IET

_L Reset-00

Fwd3 Rev

-0 0

Function Customer

-alo Loss ir Interlock

000000000000000012345 6789 10 11 12 13 14 15 16

0 t

2 1CO CO

[r

m

U>

E

LL

C

.9S

5LL

Figure 5.5 - Two-Wire Start/Stop Sample Control Wiring

Stop--aLD

Start1

,-0 0

iE0

0

8Z

IET

_L Reset-00

- Fwd/'-' Rev

-60

Function Customer

-ato LOSS Jr Interlock

60000011 12 13 14 15 16

000000000012345678910

/ 19 0

I 0 2

mE

(0

E2

Figure 5.6 - Three-Wire Start/Stop Sample Control Wiring

C

LL

E0

0

0

9

@

5

5-5

5-6

Multi-Speed Preset Wiring

Multi-speed preset wiring connects to terminals 6 through 8, and 11. See figure 5.7. When controltype 3 is selected through parameter F-00, remote terminal strip control is enabled with multi-speedpresets. This mode of operation changes the functionality of terminals 6 through 8 and may be usedin place of 2- and 3-wire start/stop wiring. See figure 5.8.

When you enable multi-speed preset operation, the state of terminals 7 and 8 determine the sourceof the speed reference:

Terminal 7

1

1

0

0

Terminal 8

0

1

0

1

Speed Reference Source

Terminal Strip Analog Input

Multi-Speed Preset 1 (Parameter F-23)

Multi-Speed Preset 2 (Parameter F-24)

Multi-Speed Preset 3 (Parameter F-25)

Start/Stop/IET Reset

LHI

-11Multi-Speed Preset 1

Multi-Speed Preset 211

„ FwdA' Rev

-ioFunction Customer

-ato Loss Ar Interlock

60000011 12 13 14 15 46

0000000000r2345678910

S .I N

B 65 @

65%0

S 2.(5

a S i

5 3>

0

E Ir0

Figure 5.7 - Multi-Speed Preset Sample Control Wiring

gEE

80

52RI

S

0

SP500 AC Drive installation and Operation Manual, Version 3.1

.

n

S0

g)La

30

9

m

S

F-00 = 0,1,2

30000000\456789101112

3&%BEE M 0 50-9$ 1 E 50

5 0 ES *85/5 0 8 immr 5 g Lir r .SM16 N Z U CO

F-00 = 3 (Multi-Speed Presets)

000000045 678910

r N

2 20- 0-

0 9+

--

2

-1

C

5IL

E

80

9

0611 12

Figure 5.8 - Terminal Usage During Multi-Speed Preset Operation

IET Reset Control Wiring

IET reset control wiring connects to terminals 8 and 11. See figures 5.5 and 5.6. Note that these resetwiring connections are not to be used in multi-speed preset applications. See figures 5.7 and 5.8.

Forward/Reverse Control Wiring

Forward/reverse control wiring connects to terminals 9 and 11. See figures 5.5 through 5.7. Note thatthe setting of the forward/reverse switch is ignored when parameter F-17 is equal to 1 (disablereverse operation).

Function Loss Control Wiring

Function loss control wiring connects to terminals 10 and 11. See figures 5.5 through 5.7. Typically, afunction loss input is a maintained, normally-closed pushbutton.

A signal must be present at terminal 10 for the drive to run. A factory-installed jumper connectsterminals 10 and 11 which provides that signal. Remove this jumper if a function loss input, acoast-stop pushbutton, or another external interlock (for example, a motor thermostat) is used.Removing the jumper allows the drive to stop when the contact is open.

Wiring the Drive

ATTENTION: The user must provide an external, hardwired emergency stop circuitoutside of the drive circuitry. This circuit must disable the system in case of improperoperation. Uncontrolled machine operation may result if this procedure is not followed.

gaCO

5-7

5-8

5.2.4 Snubber Resistor Wiring

Snubber resistor wiring connects to terminals 12 and 13 on the Regulator board's terminal strip. Seefigures 5.9 and 5.10.

Drive Model Number

1 SU2>000<

1 SU4)000< and 1 SU5xxxx

1 SU4x015 and 1 SU4x020

REGULATORBOARD

CONTROL fTERMINALZ |||

STRIP 1*121-11

50 6

0

POWER fTERMINAL=< 10101

STRIP i '+'-'- DC BUS

VOLIS

SP500 DRIVE

Snubber

Resistor

Terminals

1 (+)2 (-)

147 (+)

45 (-)

1 (+)

2 (-)

147 (+)

45 (-)

13 (+)

14 (-)

Control Terminal

Strip Connections12

13

N/A

N/A

12

13

Power Terminal

Strip Connections

N/A

(+) DC Bus

(-) DC Bus

N/A

(+) DC Bus

(-) DC Bus

N/A (+) 10V

(-) 10 COMRefer to instruction manual D2-3291.

+1 SNUBBER RESISTOR-2 BRAKiNG SIGNAL

+147DC BUS VOLTS

-45

SNUBBER RESISTOR

Figure 5.9 - Snubber Resistor Wiring Connections for M/N 1 SU21000 Drives

SPSOO AC Drive Installation and Operation Manual, Version 3.1

.

.

REGULATOR

BOARD

sTRIP

2 5

50 AZE R

)m &

111STRIP 1 + - + -

4 DC BUS 1 OV lOV

VOLIS COM

SP500 DRIVE

+1 SNUBBER RESISTOR-2 BRAKING SIGNAL

+147 DC BUS VOLTS-45

+13

-1410VSUPPLY

SNUBBER RESISTOR

Figure 5.10 - Snubber Resistor Wiring Connections for M/N 1 SU4xxxx and 1 SU5>000< Drives

5.2.5 Output Status Relay Wiring

Output status wiring connects to terminals 14 through 16 on the Regulator board's terminal strip. Seefigure 5.11. Parameter F-09 specifies the type of status indication provided by the output relay. Seethe F-09 parameter description in section 8.3 for more information.

Wiring the Drive

USER-SUPPLIEDLAMP

U USER-SUPPLIEDN.O. 115 VAC/24 VDC

(10 mA Min.)

5014 15 16

Figure 5.11 - Output Status Relay Wiring Connections

5-9

Flo

5.3 Output Power Wiring

Use the following steps to connect AC output power wiring from the drive to the motor:

Step 1. Wire the AC output power leads by routing them according to the type of enclosure. Seefigures 4.1 through 4.4. See tables 3.2 through 3.4 for recommended wire sizes.

.

ATTENTION: Do not route signal and control wiring with power wiring in the sameconduit.This can cause interference with drive operation.

Do not route more than three sets of motor leads through a single conduit. This willminimize cross4alk which could reduce the effectiveness of noise reduction methods. If

more than three drive/motor connections per conduit are required, you must use shieldedcable. If possible, each conduit should contain only one set of motor leads.

ATTENTION: Unused wires in conduit must be grounded at both ends to avoid apossible shock hazard caused by induced voltages. Also, if a drive sharing aconduit is being serviced or installed, all drives using this conduit should bedisabled to eliminate the possible shock hazard from cross-coupled motor leads.

Step 2. Connect the AC output power motor leads to terminals U, V, and W on the power terminalstrip. See figure 5.1.

Step 3. Tighten terminals U, V, and W to the proper torque as shown in table 3.5.

5.4 Grounding

A ATTENTION: The user is responsible for conforming with all applicable local,

national, and international codes.

Use the following steps to ground the drive:

Step 1. Remove the drive's cover.

Step 2.

Step 3.

Step 4.

Run a suitable equipment grounding conductor unbroken from the drive's ground terminalto the motor's ground terminal and then to earth ground. See figures 4.1 through 4.4 and5.1.

Connect a suitable grounding connector to the motor frame and transformer (if used). Runeach conductor unbroken to earth ground.

When adding more than one grounding conductor wire to a single chassis ground, twist theconductors together.

Re-attach the drive's cover.

SP500 AC Drive Installation and Operation Manual, Version 3.1

6.0 Completing the Installation

6.1

This chapter provides procedures to check the installation.

A ATTENTION: only qualified electrical personnel familiar with the construction and

operation of this equipment and the hazards involved should install, adjust, operate,/ 0 and/or service this equipment. Read and understand this manual in its entirety beforeI proceeding.

Checking the Installation With the Power Off

ATTENTION: DC bus capacitors retain hazardous voltages after input power has beendisconnected. After disconnecting input power, wait five (5) minutes for the DC buscapacitors to discharge and then the check the voltage with a voltmeter to ensure the

I DC bus capacitors are discharged before touching any internal components.

Perform the following checks of the drive installation with the power off:

Step 1. Turn off, lock out, and tag the input power to the drive. Wait five minutes.

Step 2. Check the DC bus potential with a voltmeter as described in section 9.1 to ensure that theDC bus capacitors are discharged.

Step 3. If an input disconnect is installed, make sure it is in the off position.

Step 4. Make sure the drive interlocks installed around the driven machine are operational.

ATTENTION: The user must provide an external, hardwired emergency stop circuitoutside of the drive circuitry. This circuit must disable the system in case of improper

, . operation. Uncontrolled machine operation may result if this procedure is not followed.

Step 5. Verify that the user-installed stop pushbutton is wired correctly. Be sure the factory-installedjumper at terminals 10 and 11 has been removed so that the coast-stop pushbutton willwork. (Refer to section 5.2.3.)

,.

Step 6.

Step 7.

Step 8.

Step 9.

ATTENTION: Make sure electrical commons are not intermixed in the drive.

Remove any debris from around the drive.

Check that there is adequate clearance around the drive.

Verify that the wiring to the control terminal strip and power terminals is correct. Refer tochapter 5.

Check that the wire sizes are within terminal specifications and that the terminals aretightened to the appropriate torque specifications. Refer to tables 3.2 through 3.6.

Step 10. Check that the user-supplied branch circuit protection is installed and correctly rated.

Step 11. Check that the incoming AC power is rated correctly.

Step 12. Check the motor installation and length of motor leads.

Step 13. Disconnect any power correction capacitors connected between the drive and the motor.

Completing the Installation 6-1

6-2

6.2

Step 14. Check that any motor thermal switch and the drive's electronic thermal overload areenabled (parameter F-15 = ON).

Step 15. Check that the rating of the transformer (if used) matches the drive requirements and isconnected for the proper voltage.

Step 16. Verify that a properly-sized ground wire is installed and that a suitable earth ground is used.Check for and eliminate any grounds between the motor frame and the motor power leads.Verify that all ground leads are unbroken.

Step 17. Uncouple the motor from any driven machinery to initially start the drive.

Checking Drive Operation

ATTENTION: DC bus capacitors retain hazardous voltages after input power has beendisconnected. After disconnecting input power, wait five (5) minutes for the DC bus

, 0 capacitors to discharge and then check the voltage with a voltmeter to ensure the DCI bus capacitorsare dis®arged before touching any internal components.

Use the following procedure to check the operation of the drive:

Step 1. Turn off, lock out, and tag power to the drive. Wait five minutes.

Step 2. Remove the cover and check the DC bus potential with a voltmeter as described in section9.1. Verify that the DC bus capacitors are discharged. Replace the cover.

Step 3. Uncouple the driven equipment from the motor, if possible.

Step 4. Apply power to the drive. SELF should be displayed for approximately 1 to 2 seconds toindicate internal diagnostics are being performed. After 1 to 2 seconds, 0 should bedisplayed and the LEDs should indicate drive status. If any fault codes are displayed, referto chapter 9, Troubleshooting Reference.

Step 5. Check all parameter settings and verify that they are set correctly based on the application.In most cases, the factory default values are adequate for this no-load start-up test.Parameters are described in chapter 8.

Step 6.

Step 7.

Step 8.

Press the L__J key. The drive should ramp at the acceleration rate (F-01) until it reachesthe preset minimum speed (F-03).

Verify the direction of the motor shaft rotation. If it is incorrect for your application, use thefollowing procedure to change the direction of rotation. If it is correct, go to step 8.

SIRE

RESET

Step a. Press the key to stop the drive.

Step b. Wait until the motor has completely stopped.

Step c. Turn off, lock out, and tag power to the drive. Wait five minutes.

Step d. Remove the cover and check the DC bus potential with a voltmeter as described insection 9.1. Verify that the DC bus capacitors are discharged. Replace the cover.

Step e. Reverse any two of the three motor power leads (U, V, or W).

Step f. Turn the power on.

1 STARTStep g. Press the L_J key and verify the direction of rotation.Using the A and V' keys, run the motor without any load across the speed range. Ifthe motor does not operate satisfactorily, check the parameter settings. Refer to chapter 8.

1 RESET 1

Step 9. Press the L__J key to stop the drive.

SP500 AC Drive Installation and Operation Manual, Version 3.1

Step 10. Turn off, lock out, and tag power to the drive. Wait five minutes. Remove the cover andcheck the DC bus potential with a voltmeter as described in section 9.1. Verify that the DCbus capacitors are discharged. Replace the cover.

Step 11. Couple the driven equipment to the motor.

Step 12. Turn power on.

START Step 13. Press the l key.

Step 14. Run the drive across the required speed range under load. If the motor does not rotate atminimum speed, increase the manual torque boost (F-06).

Step 15. If the drive operates the motor properly, go to step 16.

If the drive does not operate the motor properly, follow the steps below:

Step a. Refer to chapter 9, Troubleshooting Reference, if any fault codes were displayedduring start up.

Step b. Verify the parameter settings again.

Step 16. If the drive operates the motor properly:

1=1Step a. Press the CD key to stop the drive.

Step b. Record the parameter settings in Appendix B.

Completing the Installation 6-3

G4 SP500 AC Drive Installation and Operation Manual, Version 3.1

.

7.0 Keypad and Display Operation

The front-panel keypad and display, shown in figure 7.1, are used to program, monitor, and controlthe drive. They operate in two modes: monitor mode and program mode.

In monitor mode (the default mode), you can monitor specific drive outputs and the drive's speedreference.

In program mode, you can view and adjust drive parameter values and examine the error log.

In addition to the functions above, if the control source is local (F-00 = 0), you use the keypad to startand stop the drive, select motor direction, and adjust speed.

Regardless of the control source selected, you can use the keypad to stop the drive and reset drivefaults.

The following sections describe the keypad, the display, and the LEDs. Monitor mode and programmode are described in more detail later in this chapter.

1 RPM

E-1 %Load

0 Volts

0 Remote

7.1 Display Description

0 RUN .

F-1 Program

E Forward

0 Reverse

Mode

Enter

START«

Figure 7.1 - SP500 Keypad and Display

Forward

Reverse

STOP

RESET

The display is a four-character, seven-segment LED. At drive power up, SELF is displayed while thedrive performs power-up diagnostics. During drive operation, the display indicates parameternumbers, parameter values, fault codes, and drive output values. Figures 7.3 and 7.4 show sampledisplays.

7.2 Key Descriptions

The keypad's six membrane keys are used to monitor, program, and control the drive. Table 7.1describes the keys.

Keypad and Display Operation 7-1

7-2

Mode

Enter

Forward

Reverse

START

STOP

RESET

Table 7.1 - Key Descriptions

Use the UP and DOWN arrow keys to:

• Step through the drive parameters and error log when the drive is in programmode. ,

• Increase or decrease a parameter's numeric value or status in program mode.

• Increase or decrease the internal speed reference when F-00 (Control SourceSelect) = 0 or 2.

Hold down these keys to increase the scroll speed.

Use the MODE/ENTER key to:

• Advance through each monitor display item in monitor mode.

• Select program mode when the drive is stopped.

• Display a parameter value in program mode.

• Save a parameter value in program mode.

The MODE/ENTER key provides these functions regardless of the control sourceselected (local or remote).

Use the FORWARD/REVERSE key to select the direction of motor shaft rotationwhen the control source is local (F-00 = 0).

Use the START key to apply power to the motor when the control source is local(F-00 = 0).

When this key is pressed, and there are no active faults, the drive will accelerate tothe last programmed frequency setpoint (speed).

Use the STOP/RESET key to:

• Turn off the drive output to the motor if the drive is running.

• Clear drive faults when the drive is in program mode.

• Exit program mode.

When this key is pressed, the drive will ramp to rest at a user-defined rate (useroption) or coast to rest (default). This key stops the drive regardless of the selectedcontrol source (remote or local).

7.3 LED Descriptions

The keypad area contains eight LEDs that indicate either drive status or which drive output value isdisplayed in monitor mode. Tables 7.2 and 7.3 describe the drive status LEDs and monitor modeLEDs, respectively.

SPSOO AC Drive installation and Operation Manual, Version 3.1

LED

I Run

State

On

Off

Table 7.2 - Drive Status LED Descriptions

Description

.The drive is generating an output voltage and frequency.

The drive is not generating an output voltage and frequency.

aATTENTION: The RUN LED must not be used as an indication that there is no line voltagepresent in the drive. Verify there is no voltage present at the DC bus terminals (+) and (-)before servicing the drive. Failure to observe this precaution could result in severe bodily injuryor loss of life.

.. Program

I Forward

Il Reverse

i Remote

LED

I RPM/Engineering Unit

I %Load

i Volts

All LEDs (RPM, %Load, Volts)

Keypad and Display Operation

On

Off

On

Off

On

Off

On

Off

The keypad and display are in program mode.

The keypad and display are in monitor mode.

The requested motor rotation direction is forward.

The requested motor rotation direction is not forward.

The requested motor rotation direction is reverse.

The requested motor rotation direction is not reverse.

The drive is being controlled from the terminal strip.

The drive is being controlled from the keypad.

Table 7.3 - Monitor Mode LED Descriptions

Corresponding Display When LED is On (Actual Value)

Motor speed in RPM or in a user-specified engineering unit. (Refer to theF-08 parameter description for more information.)

Percentage of drive full load amps rating.

Drive output voltage to the motor.

Value of the active speed reference signal as 0 to 100% of the total scaledreference range. F-13 must be set to ON to display this value. (Refer to theF-13 parameter description for more information.)

7-3

7-4

F.02

7.4 Program Mode

Program mode allows you to display and modify drive parameter values when the drive is stopped. The following can be displayed in program mode:

• Parameter numbers

• Parameter values

• Error log information

To enter program mode:

I srop

Step 1. Stop the drive (if it is running) by pressing the lm key1 Mode

Step 2. Press the lYL key until the PROGRAM LED turns on.

Parameter F-00 will be displayed. Use the A key or '7 key to scroll through the parameter list.The error log follows parameter F-49 and precedes parameter F-00 as shown in figure 7.2.

.L I

F-(to

I

F-01

:

F-49

Err

It

Figure 7.2 - SP500 Menu Structure

To exit program mode:

IMEL

Step 1. Press the l Emor , key until a parameter number or ERR is displayed.

STOP 1

Step 2. Press the l RESET J key until the PROGRAM LED turns off.

filImportant: Pressing the LRESET J key while you are examining the error log clears the log.

A sample program mode display is shown in figure 7.3.

SP500 AC Drive Installation and Operation Manual, Version 3.1

.

7.5

r _ ri nUU

6 RPM

%Load

0 Volts

EZ] Remote

Q RUN

I Program

E Forward

0 Reverse

U( Mode ] Forward Enter I IReverseJ

ru*21 1621 l»ESE

Figure 7.3 - Example of a Program Mode Display

For information about:

Displaying or changing parameter values

Ensuring program security

Individual parameters

Accessing the error log

Monitor Mode

Refer to section:

8.1

8.2

8.3

9.4

Monitor mode is the keypad and display's default mode of operation (in other words, the keypad anddisplay will return to monitor mode when you exit program mode). The keypad and display must bein monitor mode before the drive can be put into run (RUN LED is on) and will remain in monitormode while the drive is running.

The following output data can be displayed in monitor mode:

• RPM

• %Load

• Volts

• Percent Selected Speed Reference (if F-13 = ON)

Mode

To select a value to monitor, press the key until the LED turns on next to the desired display' Midiitem. Pressing the £ E'to' key will advance you through each of the displays. (Note that all the LEDs

will turn on to indicate the percent selected speed reference display if parameter F-13 is set to ON.Refer to section 7.5.2.)

A sample monitor mode display is shown in figure 7.4.

Keypad and Display Operation 7-5

7-6

7.5.1

C JU6 RPM

Z %Load

- Volts

I Remote

El RUN

1 Program

U Forward

0 Reverse

U*

| -Mosle 1 Enter Reverse

Figure 7.4 - Example of a Monitor Mode Display

Displaying the Percent Selected Speed Reference

To display the percent selected speed reference, parameter F-13 must be set to ON. Use thefollowing procedure to display the percent selected speed reference:

L srop 1Step 1. Stop the drive (if it is running) by pressing the fRESET J key.

1 E!9!5 1Step 2. Enter program mode by pressing the l E- j key until the PROGRAM LED turns on.

Step 3. Press the AA or vlv key until F-13 is displayed.

Mode

Step 4. Press the key to access the parameter.

Step 5. Press the AA key until ON is displayed.

Step 6.

Step 7.

Step 8.

Press the

Press the

Mode

ERierkey to save the value. (F-13 will be displayed.)

6% ' key to exit program mode.START

Start the drive by pressing the key.

I ModeStep 9. Press the. E= , key until all three monitor mode LEDs are on.

The display will show the active speed reference as 1 to 100% of maximum speed (F-04).

7.5.2 Scaling the RPM Display and Reference Using F-08

The RPM display and reference can be scaled to an engineering unit to match your application. Referto the F-08 description in chapter 8 for this procedure.

SP500 AC Drive Installation and Operation Manual, Version 3.1

7.6 Drive Control

When the control source is the local keypad (F-00 = 0), the keypad is used to control the drive. Thismeans that the drive will respond to START, STOP/RESET, and FORWARD/REVERSE commandsonly from the keypad.

The functions of the keypad keys are described in section 7.2. Refer to the F-00 Control SourceSelect parameter description in chapter 8 for more information on selecting a drive control source.

7.6.1 Changing the Reference Using the Keypad

The speed reference can be increased or decreased using the A or 77 key when F-00 = 0 or 2.The display will show the internal speed reference in hertz (Hz) while the keys are pressed. There willbe a slight delay before the display returns to the active monitor mode.

Note that changing the drive's internal speed reference using the A or 77 key when the drive isunder remote control will have no operational effect on the drive (unless F-00 = 2).

Keypad and Display Operation 7-7

7-8 SP500 AC Drive Installation and Operation Manual, Version 3.1

8.0 Programming Reference

To program the SP500 drive for a specific application, you display the appropriate parameter andadjust it as required. The parameters specify characteristics of the drive. This chapter describes howto access, display, and modify parameters. Section 8.3 describes each parameter in detail. AppendixC lists the parameters in alphabetical order.

8.1 Displaying or Changing Parameter Values

Use the following procedure to display or change parameter values:

r-*1IRESET

Step 1. Stop the drive (if it is running) by pressing the L----, key.

[ MOE 1

Step 2. Enter program mode by pressing the LZL; key until the PROGRAM LED turns on.

F - O d F. {*16.w J nir 21

lEZZI0- - -- -

1 El =.= 22 IlThe first parameter number (F-00) will be displayed.

Step 3. Press the A or vlv key until the desired parameter number is displayed.

F-0 1Cl- C]=

0 tl- --

m- C.-•.

*E *

Each parameter number will be displayed as you scroll through the parameter list.

Model1 Enter 1

Step 4. Press the - key to display the parameter value.

Programming Reference

c n3.U

= RM' (-

Cl- --

m- [22 4-,

0- (-ir i

8-1

8-2

Step 5. Press the A or V key to change the value.

5.10 - m„

CJ UW - PI+,-=-

m- C- El *

Note that if programming has been disabled in parameter F-20 (Password Lockout Enable),the value will not change. Refer to section 8.2, Ensuring Program Security, for moreinformation.

Step 6. Press the L___ key to save the changed value.

F-0121*C - m MUN L.EL' eZZI0.... --

=- B *

The parameter number is displayed again.

To display or change additional parameters, repeat steps 3 through 6.

| Mode 1

To exit program mode, press thel-5; J key until a parameter number or ERR is displayed; thenr=-1

press the LZJ key.

Important: Parameter values and the keypad status (local or remote) are retained through a line dipor power loss.

8.2 Ensuring Program Security

ATTENTION: It is the user's responsibility to determine how to distribute the password.Reliance Electric is not responsible for unauthorized access violations within the user's

organization.

Parameter values can be password-protected using parameter F-20 (Password Lockout Enable).When F-20 is set to ON, parameter values can be displayed but cannot be modified from the keypadunless the correct password is entered in F-20.

Note: The password is factory set to 257 and cannot be modified by the user.

SP500 AC Drive Installation and Operation Manual, Version 3.1

.

Use the following procedure to disable or enable parameter programming:

Step 1. In program mode, press the A or 'V key until F-20 is displayed.

Step 2.

F -2 01 6 (*=- m- J {*El//m-

0 - s= {E]

IMs* 11 Enter I

Press the L__j key to access the parameter. ON or OFF is displayed to indicate whetherthe password lockout feature is currently enabled or disabled.

OFFC- 0 FN

En-

m- m-

[-3 - C) -

lue- 1 9---

Programming Enabled

nun

= PM,

m lili - .-I-[=1 - C] r--

0-

Programming Disabled

Step 3. Press the A key until the password number, 257, is displayed. (Holding down the Akey increases the scroll speed.)

251C Rn, = -C- --

0- 0-

0- ¤ P"m.,

Step 4. Press the

nun0-

0-

0- m -

Ell

key to save the password number.

l-ELI tmI

ON or OFF is displayed to indicate the current state of the password lockout.

Programming Reference 8-3

8-4

ModelEnter IStep 5. Press the ,-__J key to exit the parameter.

F-201* *m I... -./.-

=-

m- B E-D

The parameter number is displayed again.

Important: There is no visual indication of the status of this feature. You must access F-20 to verifyits current value (ON or OFF).

8.3 Parameter Descriptions

F-00 Control Source Select

This parameter selects the drive [ Parameter Range:control source and speed :reference source. 1

j

Default Setting:

' Step Size:

0 = Local control; control signals andspeed reference from the keypad

I »

1 = Remote control; control signals from 1the terminal strip; speed reference :-from the analog input

2 = Remote control; control signals from 1the terminal strip; speed reference 4from the keypad

:

3 == Remote control; control signals from jthe terminal strip; multi-speed presets,from the terminal strip

0 = Local control

N/A

When F-00 = 0, the drive responds to sequencing commands (start, stop, forward, reverse) from onlythe keypad.

When F-00 = 1, 2, or 3, the drive responds to sequencing commands from the terminal strip. Note thatthe drive will respond to the stop command from the keypad regardless of the value in this parameter.

Refer to the F-23 to F-25 Multi-Speed Presets parameter description for more information aboutmulti-speed presets.

SPSOO AC Drive Installation and Operation Manual, Version 3.1

F-01 Acceleration Time

This parameter specifies the Parameter Range:amount of time it takes the motor, Default Setting:to ramp from stop to the ' Step Size:maximum speed setting in F-04. '

0.5 to 90 seconds

5.0 seconds

0.10 seconds

If the setpoint frequency requested from the keypad (using theA and vlvkeys) is less than themaximum speed setting, the time to ramp to that frequency will be proportionally less than the actualrate setting. For example, if F-04 = 60 Hz and F-01 = 4 seconds, it will take 2 seconds to ramp to afrequency reference of 30 Hz.

Note that if the acceleration rate is set too fast, an overcurrent fault may occur (OC will be displayed).

F-02 Deceleration Time

This parameter specifies the Parameter Range:amount of time it takes the motor s Default Setting:to ramp from the maximum Step Size:speed setting in F-04 to a stop.

0.5 to 90 seconds

5.0 seconds

0.10 seconds

If the frequency requested from the keypad (using the A and Vv keys) is less than the maximumspeed setting, the time to ramp to that frequency will be proportionally less than the actual rate setting.For example, if F-04 = 60 Hz and F-02 = 4 seconds, it will take 2 seconds to ramp to a frequencyreference of 0 Hz from 30 Hz.

Note that if the deceleration rate is set too fast, a high bus fault may occur (HU will be displayed).

F-03 Minimum Speed

This parameter limits the speedreference to the drive.

Regardless of what speedreference is supplied, theregulator will not command aspeed less than the value inF-03.

Parameter Range:Default Setting:Step Size:

0.5 to 30 Hz

5.0 Hz

0.10 Hz if F-04 < 100 Hz

0.25 Hz if F-04 2 100 Hz

ATTENTION: The SP500 drive is intended to operate the motor at a predeterminedminimum speed unless disconnected from the power source. The user is responsible forassuring safe conditions for operating personnel by providing suitable guards, audible or

I visual alarms, or otherdevices to indicate that the drive is operating at minimum speed,(possibly zero speed), or the user must verify that the motor output shaft will rotate at allcombinations of load and output speed required by the application.

Programming Reference 8-5

8-6

F-04 Maximum Speed

This parameter limits the speedreference to the drive.

Regardless of what speedreference is supplied, theregulator will not command aspeed greater than the value inF-04.

Parameter Range:Default Setting:Step Size:

30 to 240 Hz

60 Hz

0.10 Hz if F-04 < 100 Hz

0.25 Hz if F-04 2 100 Hz

ATTENTION: The user is responsible for ensuring that driven machinery, all drive-trainmechanisms, and process line material are capable of safe operation at maximum speed

, 0 (F-04). Failure to observe this precaution could result in bodily injury.

F-05 Current Limit

This parameter limits motor Parameter Range:output torque while it is running i Default Setting:or accelerating. Step Size:

vue»

10% to 150% of rated drive current

150%

1.0%

When output current attempts to exceed the preset current limit, motor current will be maintained orreduced, or the acceleration / deceleration time will be extended. If current limit is set too low or too highrelative to the required load, an overcurrent fault may occur (OC will be displayed).

F-06 Manual Torque Boost

This parameter sets thepercentage of output voltageboost at zero frequency.

1 Parameter Range:,1 Default Setting:5 Step Size:

0 to 10%

2%

1%

Torque boost offsets the Voltage drop of the AC motor at low speeds. For high friction loads or highinertia loads, a high starting torque level may be needed. Manual torque boost is only effective at speedslower than one-half of the motor's base frequency. See figure 8.1.

When adjusting this parameter, start with the default setting of 2% and gradually increase the value untilmotor operation is satisfactory. If torque boost is set too high relative to the load and acceleration rate,an overcurrent fault may occur (OC will be displayed).

ELU 100

5 50

5 10Manual Torque Boost E

--

1 11

Base Speed Base Speed2

FREQUENCY (Hz)

Figure 8.1 - Manual Torque Boost Adjustment Range

SP500 AC Drive Installation and Operation Manual, Version 3.1

F-07 V/Hz (Base Speed)

This parameter specifies thebase speed at maximum outputvoltage and is used to establishthe volts/hertz (V/Hz) curve.

&

5

30

Parameter Range:Default Setting:Step Size:

30 to 240 Hz60 Hz

1.0 Hz

The WHz curve allows the drive to maintain a constant V/Hz ratio, providing constant torque at anyfrequency. See figure 8.2.

Programming Reference

100

0

El

Base

Frequency

Minimum

FREQUENCY (Hz)

Figure 8.2 - Volts/Hertz Curve

240

8-7

8-8

F-08 RPM at Base Speed

This parameter scales the RPM Parameter Range: - 10 to 9999display and the setpoint to a Default Setting: 1750

user-specified engineering unit. Step Size: 1.0 unit

This parameter defines the scaling value applied to the current speed before it is displayed. It is alsoused to scale the local reference when F-18 is set to ON.

The value to enter into F-08 is the maximum value (in RPM, hertz, or any other engineering unit) to bedisplayed when the drive is running at base speed (F-07).

Display Scaling Examples

Example 1: Assume that an application requires the display show 1750 RPM when the drive is runningat a base speed of 60 Hz. The RPM display is scaled according to the following equation:

Present Operating Speed (Hz) x 2 = Displayed Value

At 30 Hz, the RPM display will show 875:

30 Hz x 1750 = 87560

Example 2: Assume the application requires the display show 20 feet per minute for a conveyor (or 20gallons per minute for a pump) when the motor is running at base speed (F-07= 60 Hz). Enter 20 inparameter F-08 to scale the display.

At 30 Hz, the display will show 10 feet (or gallons) per minute:

30 Hz x 20 = 1060

F-09 Configurable Output Relay Select

This parameter specifies the type Parameter Range: 0 = Output relay is energized to showof status indication the output state of drive running.relay contacts provide (terminals 14,15, and 16 on the drive ; 1 = Output relay is energized to showterminal strip). state of active fault (IET).

· Default Setting:Step Size:

--

If F-09 = 0, the output is energized only when the RUN LED is on.

0

N/A

2 = Output relay is energized to showstate of drive running at speed.

STOP

If F-09 = 1, the output remains energized until the fault is cleared by pressing the key (in local operation) or by using the remote IET reset signal (for remote operation).

If F-09 = 2, the output is energized when the drive is running and at speed.

SP500 AC Drive Installation and Operation Manual, Version 3.1

F-10 Carrier Frequency

This parameter selects thedrive's carrier frequency.

:»Parameter Range:

Default Setting:Step Size:

4 = 4 kHz Carrier frequency6 = 6 kHz Carrier frequency8 = 8 kHz Carrier frequency4

N/A

.

The carrier frequency controls the width of the pulse and keeps the current smooth to the motor. Thisparameter can compensate for acoustic noise, heating, and other current problems by adjusting theswitching frequency of the transistors in the inverter section.

Keeping the carrier frequency at 4kHz maximizes the continuous power rating of the drive with,generally, an acceptable acoustic noise level from the motor. Increasing the carrier frequency reducesthe acoustic noise, but in some applications this can result in derating of the drive output amps. (Refer totable 2.2 for the derated ratings at the various carrier frequencies.)

F-11 Remote Reference Gain

This parameter scales themaximum remote speedreference to match external

equipment.

Parameter Range:

Default Setting:Step Size:

60% to 100% offull scale maximum

reference

100%

0.10%

Normally, the maximum speed reference (the amount of reference at maximum speed, F-04) is either 10VDC or 20 mA. The reference gain is used to scale the speed reference to another value (for example,9.5 VDC or 19 mA). Enter the parameter value in percent of full scale reference.

To calculate the scaled reference if you are using a 0 to 20 mA remote reference, use the followingequation:

Desired Maximum Reference (mA) x 100 = 56 gain (mA reference)Reference Range (20)

Example

If the remote speed reference is 0 to 20 mA and the maximum reference required is 19.2 mA, scale asfollows:

19.2- x 100 = 96% gain20

To calculate the scaled reference if you are using a 0 to 10 VDC remote reference, use the followingequation:

Desired Maximum Reference (VDC) x 100 = % gain (VDC reference)Reference Range (10)

Example

If the remote speed reference is 0 to 10VDC and the maximum reference required is 9.5 VDC, scale asfollows:

Programming Reference

9.5

-1-6 x 100 = 95% gain

8-9

8-10

F-12 Remote Reference Offset

This parameter scales theremote speed reference (0 to10VDC or 0 to 20 mA) to aminimum value.

r

Parameter Range:Default Setting:

1 Step Size:

0% to 40% of full scale minimum reference

0%

0.10%

Typically, the value of the minimum speed reference (the amount of reference at minimum speed, F-03) iseither 0 VDC or 0 mA. Enter the parameter value as a percentage of the full scale reference to be offset fromminimum speed.

To calculate the scaled minimum reference, use the following equation:

Desired Minimum Speed Offsetx 100

Reference Range

Scaling Examples

%offset

Example 1: If the remote analog input speed reference is 0 to 20 mA (J6 set on terminals 2 and 3), andthe available analog reference signal is 4 to 20 mA, use F-12 to obtain minimum speed with minimumanalog input as follows: -4 x 100 = 20% offset

20

Example 2: If the remote analog input speed reference is 0 to 10 VDC (J6 set on terminals 1 and 2), andthe available signal is offset 0.4 VDC, use F-12 to obtain minimum speed with minimum analog input asfollows: 114 X 100 = 4% offset

10

F-13 Percent Selected Speed Reference Display Enable

This parameter enables ordisables the fourth monitor

mode display.

Parameter Range: ON = Fourth monitor mode display isenabled.

Default Setting:

Step Size:

OFF = Fourth monitor mode display isdisabled.

OFF

N/A

If F-13 = ON, the current value of the active speed reference can be displayed by pressing the key(while the drive is running) until all three monitor mode LEDs are on. The active speed reference is displayedas 1 to 100% of maximum speed (F-04).I.

If F-13 = OFF, the active speed reference will not be displayed.

Refer to chapter 3 for more information on the monitor mode displays.

SP500 AC Drive installation and Operation Manual, Version 3.1

F-14 Electronic Thermal Overload

This parameter sets the trip level ' Parameter Range:for the electronic thermal Default Setting:overload fault (01_) when ' Step Size:F-15 = ON.

20% to 100% rated current

100%

1%

This parameter should be adjusted if the motor current rating is less than the drive current rating.

Use the formula below to calculate the setting level as a percentage of maximum continuous current:

F-14 = -Motor Full Load Current

x 100Drive Output Rated Current

The motor full load current value can be found on the motor nameplate. See table 2.2 or the drive nameplatefor the drive rated output value.

F-15 Electronic Thermal Overload Enable

This parameter enables or Parameter Range:disables the electronic motorthermal overload function. This

function operates like a motorthermal switch to protect themotor from overheating. Default Setting:

Step Size:

OFF = No electronic thermal overload

protection.

ON = Electronic thermal overload

protection is active.ON

N/A

A ATTENTION: Parameter F-15 should be set to ON to prevent damage to the motor and the

When F-15 = ON, the drive faults if it exceeds the thermal overload time (60 seconds at 150% of F-14).When an external thermal switch or other overtemperature monitoring device is connected to the functionloss circuit (terminals 10 and 11), this parameter may be set ON or OFF.

For multi-motor applications, set this parameter to OFF. The individual motors must have thermal switchprotection.

Programming Reference 8-11

8-12

F-16 Coast Stop Enable·

This parameter selects how the Parameter Range: ON = Enable coast stop (motor will motor will stop when given a coast to rest)stop command.

Default Setting:Step Size:

OFF = Disable coast stop (motor willramp to rest)

OFF

1%

A ATTENTION: The user must provide an external, hardwired emergency stop circuit outside of

the drive circuitry. This circuit must disable the system in case of improper operation., 0 Uncontrolled machine operation may result if this procedure is not followed.

A coast-to-rest stop turns off the transistor power device drivers. A ramplo-rest stop fires the transistorpower device drivers until the motor comes to a stop and then turns off the power device drivers. -

Note that the function loss input opening or a drive fault will always cause a coast-to-rest stop.

F-17 Reverse Disable

This parameter enables ordisables reverse rotation of the

motor.

i Parameter Range:

Default Setting:Step Size:

ON = Disable reverse

OFF = Enable reverse

OFF

N/A '

If F-17 = OFF, the forward/reverse input allows forward or reverse rotation of the motor.

i Forward i

If F-17 = ON, reverse rotation of the motor is prohibited. When F-17 = ON, pressing the »- j key on thekeypad in local control, or wiring to terminal 9 on the terminal strip in remote control, does not affect driveoperation.

SP500 AC Drive Installation and Operation Manual, Version 3.1

F-18 RPM Setpoint Enable

-

The parameter enables the , Parameter Range:setpoint to be displayed in F-08 iunits.

! Default Setting:i »Step Size:

OFF = Setpoint is displayed in hertz.

ON =

ONN/A

Setpoint is displayed in the unitsspecified in F-08.

If F-18 = ON, pressing the A and YV keys will change the setpoint in units of 1 between minimumspeed in F-08 units and maximum speed in F-08 units. Note that this parameter only affects the setpoint, notthe display.

Example

Assume a drive is currently running at 60 Hz = 1750 RPM, F-08 = 1750, and F-10 = ON. When the VYkey is pressed, 1750 is displayed. When the V key is pressed three more times, the display will changefrom 1750 to 1749 to 1748 to 1747. The reference is then rescaled based on this input:

Reference (1747)Input reference =

F-08 (1750)x F-04 (60Hz) = 59.89 Hz

F-19 Power-Up Start Enable

This parameter determineswhether the motor starts

automatically when the drive ispowered up.

Parameter Range: OFF = Motor does not start at drive

powerup.

Default Setting:Step Size:

ON = Motor starts at drive power up.OFF ·

N/A

A ATTENTION: Setting F-19 = ON causes output power to be applied to the motor automaticallyat drive power up. When this function is enabled, the user must ensure that automatic start upof the driven equipment will not cause injury to operating personnel or damage to the driven

I equipment.In addition, the user is responsible for providing suitable audible or visual alarms orother devices to indicate that this function is enabled and the drive may start at any moment.

When F-19 = ON, output power is applied to the motor at drive power up if the following conditions are met:

• The drive power-up diagnostics must be passed (SELF will be displayed at power up).

• No faults can be active.

• The terminal strip function loss input must be closed.

• The front-panel keypad l J key must not be pressed.

If the drive is under local control, it will effectively simulate a start signal to start the drive.

If the drive is under remote control, the drive will start only if the terminal strip START input is asserted.

Programming Reference 8-13

8-14

F-20 Password Lockout Enable

This parameter enables ordisables parameter passwordprotection.

j Parameter Range: OFF = Password lockout disabled

(parameters can be modified)

Default Setting:Step Size:

ON = Password lockout enabled

(parameters cannot be modified)OFF

N/A

L.JATTENTION: It is the user's responsibility to determine how to distribute the password.

Reliance Electric is not responsible for unauthorized access violations within the user'sorganization.

.

When F-20 = ON, parameter values can be displayed but cannot be modified (except F-20). Entering thefactory-set password number (257) toggles the state of the lockout. Refer to section 8.2, Ensuring ProgramSecurity for this procedure.

Important: There is no visual indication of the status of this feature. You must access F-20 to verify itscurrent value (ON or OFF).

F-21 Avoidance Frequency

This parameter specifies the Parameter Range:midpoint of the avoidance band ; Default Setting:selected in F-22. ' Step Size:

Minimum speed to maximum speed (Hz)5.0

0.10 Hz

The avoidance band can help alleviate problems with vibrations/harmonics at a specific operatingfrequency of the driven motor or machinery. Refer to the F-22 parameter description for moreinformation.

SP500 AC Drive Installation and Operation Manual, Version 3.1

.

F-22 Avoidance Bandwidth

This parameter sets the - Parameter Range:avoidance bandwidth. Anyfrequency that falls within the , Default Setting:avoidance band results in a ' Step Size:generated frequency below thebandwidth.

0 to 30 Hz (0disabled)0

0.10 Hz

avoidance frequency

This parameter is used with parameter F-21 (Avoidance Frequency). The drive can accelerate anddecelerate through the avoidance band. However, it cannot operate at a steady state at any of theavoidance band frequencies. Setting F-22 to 0 disables the avoidance frequency.

Assume:

Minimum Speed (F-03) = 3 HzMaximum Speed (F-04) = 60.0 HzAvoidance Frequency (F-21) = 32.2 HzAvoidance Bandwidth (F-22) = 4 HzAvoidance band = 30.2 to 34.2 Hz

Programming Reference

Requested OutputFrequency

25.0 Hz

30.0 Hz

31.0 Hz

32.0 Hz

34.0 Hz

34.2 Hz

34.3 Hz

35.0 Hz

Example

Output Frequency AfterAvoidance Band Correction

25.0 Hz

30.0 Hz

30.2 Hz

30.2 Hz

30.2 Hz

30.2 Hz

34.3 Hz

35.0 Hz

8-15

8-16

F-23, F-24, and F-25 Multi-Speed Presets 1,2, and 3

These parameters allow thesetting of up to three differentpresetspeeds.

Parameter Range:Default Setting:Step Size:

Minimum speed to maximum speed20 Hz

0.10 Hz

Setting F-00 = 3 (multi-speed configuration) reconfigures the terminal strip control inputs as follows:

Terminal 6 = START/STOP/IET RESET (open = STOP; closed = IET RESET/START)Terminal 7 = MSPD 1

Terminal 8 = MSPD 0

Refer to section 5.2.

Terminals 7 and 8 are used to select the reference source as shown in table 8.1.

' Table 8.1 - Multi-Speed Presets Digital Inputs

MSPD 1

Open (0)

Open (0)Closed (1)

Closed (1)

MSPD 0

Open (0)

Closed (1)

Open (0)

Closed (1)

Reference Source

Terminal strip analog input (variable speed)

Multi-Speed #1 (F-23)

Multi-Speed #2 (F-24)Multi-Speed #3 (F-25)

SP500 AC Drive installation and Operation Manual, Version 3.1

.

F-26 Auto-Restart Number of Attempts

This parameter selects thenumber of times the drive will

attempt to restart after certainfaults have shut down the drive.

Parameter Range:Default 'Setting:Step Size:

Oto 10

0

N/A

ATTENTION: if parameter F-26 4 0, the drive will attempt to restart automatically afterauto-restartable drive faults (see table 8.2) have shut down the drive. When this feature is

, 0 enabled, the user must ensure that automatic restart of the driven equipment will not causeI injury to operating personnel or damage to the driven equipment.

If F-26 + 0, the drive logs and resets certain faults (called auto-restartable faults and listed in table 8.2) itdetects while running. The drive then waits the amount of time specified in F-27 (Auto-Restart Retry WaitTime) and restarts the drive automatically.

While the drive counts down the auto-restart time period, the display flashes the countdown period (inseconds) in the following format:

"Ar30.. Ar29.. Ar28 ...... Ar01 .- ArOO"

This shows the amount of time remaining before the auto-restart takes effect.

Once the drive restarts, it must run for 5 minutes in order to reset the number of fault reset attempts to thevalue in F-26.

If the fault occurs again, the drive decrements the number of auto-restart attempts, counts down theauto-restart time again, and continues the auto-restart process. If the drive faults on all of these attempts, itremains in the faulted state and displays the fault code for the fault it is trying to clear.

If the Stop/Reset input is asserted during the countdown, the auto-restart procedure is cancelled and thefault is latched.

If a fault occurs that is auto-restartable and other faults are active that are not auto-restartable, theauto-restart function will be disabled until all faults are cleared.

When F-26 # 0, the drive logs the first occurrence of a fault in the fault log. Any subsequent occurrence ofthat fault while attempting to restart the drive will not be logged.

Table 8.2 lists the auto-restartable faults.

Programming Reference

Table 8.2 - Auto-Restartable Faults

Fault Code

HU

LU

0C

0H

0L

Description

High bus voltage

Low bus voltage

Overcurrent

Thermostat/drive overload

Electronic thermal overload

8-17

8-18

F-27 Auto-Restart Retry Wait Time

This parameter specifies theamount of time the drive will wait

between auto-restart attempts.

Parameter Range:Default'Setting:Step Size:

1 to 30 seconds

1

1.0 second

This parameter is used with parameter F-26 (Auto-Restart Number of Attempts). Refer to the F-26parameter description for information regarding this feature.

F-28 Drive Voltage Selection

This parameter displays thedrive's voltage rating.

.

Parameter Range:Default Setting:Step Size:

ATTENTION: This parameter is set at the factory and must not be changed by the user.

F-29 Analog Output Select

This parameter selects whichmonitor mode value is directed

to the analog output (regardlessof which monitor mode value is

displayed).

Parameter Range:

Default Setting:Step Size:

SPd

N/A

N/A

N/AN/A

SPd =

LOAd

UOL=

rEF =

Refer to table A.5 in Appendix A for more detail about the analog output.

F-49 Version Information

This parameter displays thesoftware version.

' Parameter Range:; Default Setting:' Step Size:

N/AN/AN/A

Current RPM/speed output

Current percent load output

Current calculated output voltage

Current percent of selected kreference

SP500 AC Drive Installation and Operation Manual, Version 3.1

9.0 Troubleshooting Reference

aATTENTION: Only qualified electrical personnel familiar with the construction andoperation of this equipment and the hazards involved should install, adjust, operate,and/or service this equipment. Read and understand this manual in its entirety beforeproceeding.

The SP500 drive is monitored by internal diagnostics. If a fault occurs, the drive displays a two-digitfault code to identify the problem. A fault causes the drive to coast to rest if it is running or preventsthe drive from starting if it is stopped. The fault code is also entered into the error log.

This chapter defines the fault codes and suggests actions to correct problems. It also describes how

to access and clear the error log.

Note: Refer also to the F-26 (Auto-Restart Number of Attempts) parameter description in chapter 8.This describes the drive's reaction to drive faults if the auto-restart feature is enabled

(F-26 + 0)..

Important: Before servicing the drive, verify that the DC bus capacitors have discharged asdescribed in section 9.1. Use an isolated multimeter to measure the DC bus voltage andto make resistance checks. Note that dedicated troubleshooting test points are notprovided.

9.1 Verifying DC Bus Voltage

ATTENTION: DC bus capacitors retain hazardous voltages after input power has beendisconnected. After disconnecting input power, wait five minutes for the DC buscapacitors to discharge and then check the voltage with a voltmeter to ensure the DC

I bus capacitors are discharged before touching any internal components.

The SP500 drive's DC bus capacitors retain hazardous voltages after input power has been

disconnected. Perform the following steps before touching any internal components:

Step 1. Turn off, lock out, and tag input power to the drive. Wait five minutes.

Step 2. Remove the drive's cover. .

Step 3. Verify that there is no voltage at the drive's input power terminals.

Step 4. Measure the DC bus voltage at the DC bus power terminals with a multimeter whilestanding on a non-conductive surface and wearing insulated gloves (600\9. See figures 9.1to 9.3.

Once the drive has been serviced, reattach the drive's cover and reapply input power.

Troubleshooting Reference 9-1

9-2

0

R0 0

ST

AC POWER

INPUT LEADS*

0000

+ 11 V

51) 52)

11-1-11DC BUS

VOLTS

(SNUBBERRESISTOR

BRAKING)

. *For single-phase units, connect AC input power to terminals R and S.

MOTOR LEADS

0

W

53)

Figure 9.1- DC Bus Terminals on Model 1 SU1;000< and 1 SU2)000< Drives

+R S

(Ll) (12) (U)

AC POWER

INPUT LEADS

+T

++

DC BUS

VOLIS

(SNUBBERRESISTOR

BRAKING)

+ U

+V

+W

10V 10 COM (Tl) (T2) (T3)

(SNUBBERRESISTOR

BRAKING

1 OV SUPPLO

MOTOR LEADS

Figure 9.2 - DC Bus Terminals on Model 1 SU4woo and 1 SU5xxxx Drives (except 1 SU4x015, 1 SU4x020)

SP500 AC Drive Installation and Operation Manual, Version 3.1

U/Tl V/T2 W/T3 + - R/Ll S/L2 T/L3

MOTOR LEADS DC BUS VOLIS

(SNUBBERRESISTOR

BRAKING)

AC POWER

INPUT LEADS

Figure 9.3 - DC Bus Terminals on Model 1 SU4x015 and 1 SU4x020 Drives

9.2 Troubleshooting the Drive Using Fault Codes

Table 9.1 defines the fault codes for user-correctable faults, lists possible causes, and suggestsactions to take to correct the problem. All other faults require replacement of the drive.

If a fault occurs, do the following:

Step 1. Try to clear the fault first by pressing the l,EE- key or asserting the IET reset input (remoteoperation). If the fault reoccurs, continue with step 2.

Step 2. Refer to table 9.1 to identify the fault code and the possible causes.

Step 3. Perform the suggested corrective action(s).

F.moplStep 4. Clear the fault by pressing the l RESEr J key or asserting the IET reset input.

FL = FUNCTION LOSS

Table 9.1 - Drive Faults and Corrective Actions

The function loss input signal has been asserted (terminals 10 and 11).

Possible Cause

The external equipment connection to the functionloss terminals has failed or is giving repeated stoprequests.

Troubleshooting Reference

Corrective Action

Check the external equipment wired to the remotefunction loss terminals (10 and 11). Refer tochapter 5.

Check the function loss input connections.

9-3

9-4

HU = HIGH BUS VOLTAGE

The DC bus is charged above the electronic trip threshold. Note that the fault will not clear until the bus fallsbelow the high bus level.

Possible Cause

The deceleration rate setting in F-02 is too fast.

The drive was started into a forward-running loadthat has a high inertia.

High input line.

LU = LOW BUS VOLTAGE

Corrective Action

Decrease the deceleration rate in F-02. Refer to

chapter 8 for the F-02 parameter description.

Install the optional snubber resistor braking kit.

Install the optional snubber resistor braking kit.

Verify that the AC input is within specification. Installan isolation transformer if required.

The DC bus voltage has fallen below the electronic trip low threshold level. Note that the fault will not clearuntil the linput line voltage is within the proper range. This may take a few seconds.

Important: If a line dip or momentary power loss occurs and the DC bus is able to rise back to the properlevel within 500 ms, the drive will automatically restart (if the drive was running when the faultoccurred).

Loss of input power.

Low line voltage.

Possible Cause Corrective Action

Check incoming power.

Check incoming power. Install an isolationtransformer if required.

SP500 AC Drive Installation and Operation Manual, Version 3.1

.

.

.

06= OVERCURRENT

The drive's 200% current rating has been exceeded.

Possible Cause

Short in the drive outputs.

Ground fault condition.

Instantaneous overcurrent resulting in 200% rateddrive current.

OH = THERMOSTAT / DRIVE OVERLOAD

Corrective Action

Verify that the drive's input and output wiring areproperly connected. Refer to chapter 5.

Verify that the drive's input and output wiring areproperly connected. Refer to chapter 5.

Verify that the output wiring to the motor is notconnected to ground or any other voltage source.Refer to chapter 5.

increase the acceleration time in F-01 or the

deceleration time in F-02. Refer to chapter 8 forparameter descriptions.

Adjust the current limit level in F-05 if it is too low ortoo high relative to the load. Make the adjustments in5% increments.

The internal thermostat detected excessive temperatures in the drive. Note that the fault will not clear untilthe internal drive temperature is back within range. This may take a few seconds.

Possible Cause

The drive's operating specifications have beenexceeded.

The ambient operating temperature of the drive hasbeen exceeded. See Appendix A.

Troubleshooting Reference

Corrective Action

Check the application and change the carrierfrequency in F-10. Refer to chapter 8 for theparameter description.

Check the temperature at the installation site. Movethe driveto a cooler location.

9-5

9-6

OL= ELECTRONIC THERMAL OVERLOAD

The electronic thermal overload trip level has been exceeded. This fault protects the drive motor fromoverheating due to excessive current within a specified period. Note that the fault will not clear until the inputline voltage is within the proper range. This may take a few seconds.

Possible Cause

The current limit setting in F-05 is incorrect.

The electronic thermal overload setting in F-14 doesnot match the motor and drive combination.

r/,r 2 = POWER SUPPLY OUT OF RANGE

The power supply is out of range.

Possible Cause

Possible regulator failure.

SELU = INVALID DRIVE VOLTAGE

The value in F-28 is incorrect for the drive.

Possible Cause

An invalid drive voltage was selected in F-28.

9.3

Corrective Action

If the current limit level is too low relative to load,

increase the current level in F-05. Refer to chapter 8for the parameter description.

Verify the value of F-14. Refer to chapter 8 for theparameter description.

Corrective Action

Contact Reliance Electric for assistance if the fault

reoccurs after pressing the*key for asserting theNET reset input) or cycling power.

Corrective Action

Select the voltage to match the input line voltage.

Accessing and Clearing the Error Log

If a fault occurs, the drive displays a fault code and logs the fault code into the error log. If more thanone fault occurs, the first fault flashes on the display and the subsequent faults (up to two) are loggedin the error log. After three faults, no subsequent faults are logged.

The faults in the error log are numbered sequentially. For example, if an overcurrent fault occurredfirst followed by a thermal overload fault, the error log would read 1 -OC, 2-OL.

The last fault to occur appears first when the error log is accessed. For example, if the last fault tooccur was a low bus fault, and the error log contained three entries, the error log would display 3-LUwhen the error log is accessed.

SP500 AC Drive Installation and Operation Manual, Version 3.1

Use the following procedure to access the error log:

Step 1. Enter program mode by pressing the J key until the PROGRAM LED turns on.

F-00E Z. = -0- CZ] P-•f,

C- m-

(-2 ;*.14L__1 L__j

IE®

Step 2. Press the V' key until ERR is displayed. The error log precedes parameter F-00 andfollows F-49.

Erre - m-

0./.----

C --

1_ModilStep 3. Press the l-EZY key to access the error log.

Step 4.

2-OL**rz;7 m1

m- m- 1 Elli + A.... 1

0 - 0-

0 - e - Ell

(Sample Display)

Press the AA key to move through the error codes.

1 B- o i11%5 ==-

Troubleshooting Reference

CL l*J

(Sample Display)

9-7

9-8

1 STOP 1

Step 5. Press the lZZLI key to clear the log.

7 1 MClu

C] "61 e-

EZ=m- m-

The display will return to the active monitor display.

9.4 Checking the Drive's Power Module Circuitry with the Power Off

InputDiode No.

1

2

3

4

5

6

aATTENTION: DC bus capacitors retain hazardous voltages after input power has beendisconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitorsto discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors aredischarged before touching any internal components.

Use the following procedure to check the drive's Power Module circuitry. Note that this test isperformed with the power off.

Step 1. Turn off and lock out input power. Wait five minutes.

Step 2. Remove the drive's cover.

Step 3. Verify that there is no voltage at the drive's input power terminals.

Step 4. Check the DC bus voltage with a voltmeter as described in section 9.1 to ensure that theDC bus capacitors are discharged.

Step 5. Disconnect the motor from the drive.

Step 6. Check all AC line and DC bus fuses.

Step 7. If a fuse is open, use a multimeter to check the input diodes and output IGBTs. See tables9.2 and 9.3.

Step 8. Reconnect the motor to the drive.

Step 9. Reattach the drive's cover.

Step 10. Reapply input power.

*

*

R/Ll

S/L2

T7L3

Table 9.2 - Resistance Checks for Input Diodes

Meter Connection

H*

*(+)DC bus volts power terminal

** (-) DC bus volts power terminal

R/Ll

S/L2

17L3**

**

**

Component is OK ifresistance (R) is:

50 <R<10 Megohm

Component isdefective if:

Continuity (short circuit) oropen when the meter isconnected with reversed

polarity.

SP500 AC Drive Installation and Operation Manual, Version 3.1

IGBT No.

1

2

3

4

5

6

*

W/T3

VF2

U/Tl

Table 9.3 - Resistance Checks for IGBTs

Meter Connection

* W/T3

V/T2U/Tl**

**

*(+)DC bus volts power terminal

** (-) DC bus volts power terminal

4

Troubleshooting Reference

**

Component is OK ifresistance (R) ls:

50 <R<10 Megohm

Component isdefective if:

Continuity (short circuit) oropen when the meter isconnected with reversed

polarity.

9-9

9-10 SP500 AC Drive Installation and Operation Manual, Version 3.1

AC Une Distribution Capacity(Maximum)

Control Method

Carrier Frequency

Displacement Power Factor

Line Frequency

Line Voltage Variation

Line Dip RideThrough

Linearity

Long4erm Frequency Stability

Minimum Frequency Range

Maximum Frequency Range

Maximum Load

Motor Lead Lengths

Overcurrent Trip IET

Enclosure

A

B

C

D

Height

304.8 mm (12.00")

301.7 mm (11.88")

357.8 mm (14.10")

465.2 mm (18.31")

Operating Temperature

Storage Temperature

Humidity

Altitude

Technical Specifications

Appendix A

Technical Specifications

Table A.1 - Service Conditions

100KVA, single-phase 115 VAC and three-phase230 VAC, with 5,000 amps symmetrical fault currentcapacity for M/N 1 SU l=xx and 1 SU21000< drives

1000KVA, three-phase 460 and 575 VAC, with30,000 amps symmetrical fault current capacity forM/N 1 SUzboox and 1 SU5xox drives

All-digital, pulse-width-modulated (PWM)4 kHz, 6 kHz, or 8 kHz, software selectable

0.96

50/60 Hz (+5 Hz)

-10% to +10%

500 milliseconds

0.05 (Speed reference to output frequency)0.01%

0.5 - 30 Hz

30 - 240 Hz

150% for 1 minute (based on drive nameplate rating)76 meters (250 feet) total (See table 3.7 for moreinformation)

200% rated drive current

Table A.2 - Dimensions

Depth

121.9 mm (4.80")

160.1 mm (6.30")

158.2 mm (6.20")

198.9 mm (7.83")

Width

146.0 mm (5.75")

222.3 mm (8.75")278.1 mm (10.9")

286.5 mm (11.28")

Table A.3 - Environmental Conditions

Weight

2.7 kg (6 lb)

5.4 kg (12 lb)

8.1 kg (18 lb)

15.3 kg (34 lb)

00 to +40®C (32' to 104®F) -enclosed drives

0® to +55 C (32' to 131 'F) -open chassis (cover removed)-40' to +65'C (-40' to +149'F)

5 to 95% (non-condensing)

Do not install the drive above 1000 meters (3300 feet) withoutderating output power. For every 91.4 meters (300 feet) above1000 meters (3300 feet) up to 3033 meters (10,000 feet),derate the output current by 1%. Above 3033 meters(10,000 feet), contact your local Reliance Electric sales officefor assistance.

A-1

A-2

Analog Speed Reference

Start

Stop

IET Reset

Forward/Reverse

Function Loss

Analog Output

(0-10 VDC scaled signal)

Snubber Resistor Braking

Output Status Relay

Appendix A

(Continued)

Table A.4 - Drive Inputs

0 to 10 VDC or 0 to 20 mA

Edge-sensitive signal that must see an open-to-closed contacttransition. This transition may be a momentary or fixed closure.

An open contact that must be closed when the drive is running.The drive will remain off as long as the contact is open.

Edge-sensitive signal that must see an open-to-closed contacttransition. This transition may be a momentary or fixed closure.

An open contact to assert the forward direction and a closedcontact to assert the reverse direction.

An open contact that must be closed when the drive is running.When the contact is open, the drive turns off. The drive will remainoff as long as the contact is open.

Table A.5 - Drive Outputs

The scaled signal is selected through parameter F-29 and can beone of the following:

• Output Voltage: 0 to 115 VAC (M/N. 1 SU1 )000 drives)0 to 253 VAC (M/N 1 SU2)000< drives)0 to 506 VAC (M/N 1 SU4)000< drives)0 to 632 VAC (M/N 1 SU5)000 drives)

• % Load (Amps): 0 to 200% (Percentage of output ampsbased on the drive nameplate.)

• RPM/Engineering Unit: Minimum to maximum RPM orminimum to maximum of anyengineering unit (See parameterF-08)

• % Selected Speed Reference: 0 to 100% (Percentage ofthe selected reference

signal range.)

Snubber resistor control signal used by an optional snubberresistor. -

115 VAC/24 VDC, 0.5 Amp, relay output (One Form A and oneForm B contact wired with a single common.)

SP500 AC Drive Installation and Operation Manual, Version 3.1

Parameter

No.

F-00

F-01

F-02

F-03

F-04

F-05

F-06

F-07

F-08

F-09

F-10

F-11

F-12

F-13

F-14

F-15

F-16

F-17

F-18

F-19

F-20

F-21

F-22

F-23

F-24

F-25

F-26

F-27

F-28

Parameter Name

Control Source Select

Accel Time (seconds)

Decel Time (seconds)

Minimum Speed (Hz)

Maximum Speed (Hz)

Current Limit (96)

Manual Torque Boost (%)

V/Hz Base Speed (Hz)

RPM at Base Speed

Configurable Output RelaySelect

Carrier Frequency (kHz)

Remote Reference Gain (%)

Appendix B

Record of User Settings

Remote Reference Offset (%)

Percent Selected SpeedReference Display EnableElectronic Thermal Overload

(%)

Electronic Thermal Overload

Enable

Coast Stop Enable

Reverse Disable

RPM Setpoint Enable

Power-Up Start EnablePassword Lookout Enable

Avoidance Frequency (Hz)

Avoidance Bandwidth (Hz)

Multi-Speed Preset 1 (Hz)

Multi-Speed Preset 2 (Hz)

Multi-Speed Preset 3 (Hz)

Auto-Restart Number of

Attempts

Auto-Restart Retry Wait Time(seconds)

Drive Voltage Selection

Record of User Settings

Range

0,1,2,3

0.5 - 90.0

0.5 - 90.0

0.5 - 30.0

30.0 - 240.0

10-150

2-10

3 - 240

10 -9999

0,1,2

4,6,8

60-100

0-40

ON, OFF

20-100

ON, OFF

ON, OFF

ON, OFF

ON, OFF

ON, OFF

ON, OFF

Min speed -Max speed

0.0 - 30.0

Min speed -Max speed

Min speed -Max speed

Min speed -Max speed

0-10

0 = disabled

1 - 30

Step Size

N/A

0.10

0.10

0.10/0.25

0.10/0.25

1.0

1.0

1.0

1.0

N/A

N/A

0.10

0.10

N/A

1.0

0.10

0.10

0.10

N/A

N/A

N/A

N/A

N/A

N/A

0.10

0.10

N/A

1.0

Default

Setting

0

5.0

5.0

5.0

60.0

150

2

60

1750

0

100

0

OFF

4

100

ON

0

20

20

20

1

0

Setting

This parameter is set at the factory. Do not change thesetting.

ON

OFF

OFF

OFF

OFF

5

Date

B-1

8-2

Parameter

No.

F-29

F-49

Parameter Name

Analog Output Select

Version Information

Appendix B

(Continued)

Range

SPd

LOAd

UOL

rEF

X.XX

Step Size

N/A

N/A

Default

SettingSPd

Read

Only

Setting Date

SP500 AC Drive installation and Operation Manual, Version 3.1

Appendix C

Alphabetical Listing of Parameters

Acceleration Time .............................. . F-01

Analog Output Select ............................. . F-29

Auto-Restart Number of Attempts .................... . F-26

Auto-Restart Retry Wait Time . . . . . . . . . . . . . . . . . . . . . , , .F-27

Avoidance Bandwidth ............................... . F-22

Avoidance Frequency ........................ .. F-21

Carrier Frequency ............................. F-10

Coast Stop Enable ................................ ... F-16

Configurable Output Relay Select.... ............. . F-09

Control Source Select............ ............... F-00

Current Limit ..................................... .... F-05

Deceleration Rate .........................,.'..... .. F-02

Drive Voltage Selection ............................... .. F-28

Electronic Thermal Overload ..................... .. F-14

Electronic Thermal Overload Enable ......... .. F-15

Manual Torque Boost ................ .............. ... F-06

Maximum Speed ................. ............. .. F-04

Minimum Speed .................................. .. F-03

Multi-Speed Preset 1 ................................ .. F-23

Multi-Speed Preset 2 ................................ ... F-24

Multi-Speed Preset 3 ................................. .. F-25

Password Lockout Enable ...................... .. F-20

Percent Selected Speed Reference Display Enable ... F-13

Power-Up Start Enable ............................. . F-19

Remote Reference Gain ......................... F-11

Remote Reference Offset ................ .......... ... F-12

Reverse Disable ................................... F-17

RPM at Base Speed ................................. . F-08

RPM Setpoint Enable ............... .............. ...F-18

V/Hz (Base Speed) ......................................... F-07

Version Information ............................ .. F-49

Alphabetical Listing of Parameters C-1

C-2 SP500 AC Drive installation and Operation Manual, Version 3.1

Appendix D

Compliance with Machinery Safety Standard EN-60204-1:1992

The SP500 AC Speed Controller for Electric Motors complies with the following sections of Machinery SafetyStandard EN-60204-1:1992.

EN-60204-1

Section

6

6.2.1

6.2.3

6.3.1

6.4

7

7.2

7.2.3

7.2.6

7.5

8

8.2.1

8.2.2

8.2.3

8.2.7

8.3

8.4

8.5

8.6

9

9.1.1

9.1.3

9.1.4

9.2

9.2.1

9.2.2

9.2.3

9.2.5

9.2.5.3

9.2.5.6

9.2.6

Title

Protection against electrical shock

- Protection by enclosure

- Protection against residual voltages

- Protection by automatic disconnect of supply

- Protection by the use of PELY (Protective Extra Low Voltage)

Protection of equipment

- Overcurrent protection

- Control circuits

- Transformers

- Protection against supply interruption or voltage reduction and subsequent restoration

Equipotential bonding

- General (the PE terminal)

- Protective conductors (connection points)

- Continuity of the protective bonding circuit

- Protective conductor connecting points

- Bonding of the protective bonding circuit for operational purposes

- Insulation failures

- Bonding to a common reference potential

- Electrical interferences

Control circuit and control functions

- Control circuit supply

- Protection

- Connection of control devices

- Control functions

- Start function

- Stop function

- Operating modes

- Operation

- Stop

- Hold-to-run controls

- Combined start and stop controls

Compliance with Machinery Safety Standard EN-60204-1:1992 D-1

D-2

19.1

18

18.2

18.4

19

10

10.8

9.3

9.3.5

9.4

9.4.2.1

9.4.3

9.4.3.1

9.4.3.2

11

11.2

11.2.1

11.2.2

11.3

11.3.1

11.5

12

12.2.2

12.2.3

12.3

12.3.1

12.3.2

12.3.3

12.3.4

12.3.5

13

13.2.3

13.4

15

15.1.1

15.1.3

15.2.2

Appendix D

(Continued)

- Protective interlocks

- Reverse current braking

- Control functions in case of failure

- Use of proven circuit techniques and components

- Provisions for redundancy

- Earth faults

- Voltage interruption

Operator interface and machine mounted control devices

- Display

Control interfaces

- Digital input/output interfaces

- Inputs

- Outputs

- Drive interfaces with analog inputs

- Separation between control and electric drives

- Communications

Electronic equipment

- Electronic control equipment

- Equipotential bonding

- Programmable equipment

- Programmable controllers

- Memory retention and protection

- Programming equipment

- Software verification

- Use in safety-related functions

Controlgear: Location, mounting and enclosures

- Heating effects

- Enclosures, doors and openings

Wiring practices

- General requirements

- Conductors of different circuits

- Identification of the protective conductor

Warning signs and item identification

- Warning signs

- Marking of control equipment

Technical documentation

- General

SP500 AC Drive Installation and Operation Manual, Version 3.1

Appendix E

Compliance with Electromagnetic Compatibility Standards

E.0 Introduction

This appendix provides information on the SP500 drive's compliance with European communityelectromagnetic compatibility standards and covers the following:

• Requirements for standards compliance

• Guidelines on installing the AC Mains Filter

• Instructions on how the drive must be wired

The SP500 drives listed on the Declaration of Conformity (DOC) have been tested and are incompliance with the following standards when installed with the appropriate AC Mains Filter:

• EN50081-1 (1992)Electromagnetic compatibility - Generic emission standardPart 1: Residential, commercial, and light industrial

• EN50081-2 (1992)Electromagnetic compatibility - Generic emission standardPart 2: Industrial

• EN50082-1 (1992)Electromagnetic compatibility - Generic immunity standardPart 1: Residential, commercial, and light industrial

• EN50082-2 (1995)Electromagnetic compatibility - Generic immunity standardPart 2: Industrial

Note that the conformity of the SP500 drive to the above standards does not guarantee that the entireinstallation will be in conformance.

Contact the Rockwell AutoFax service at 216-646-7777 for copies of the Declaration of Conformity(DOC).

E.1 Compliance Requirements

In order for the SP500 drive to conform to the standards listed in section E.0, the drive must:

• be specified by model number on the DOC.

• have a CE mark. This mark is found on the drive's certification label.

• include an AC Mains Filter. See section E.2 for information on installing the filter.

• be installed according to the instructions in this appendix.

Note that when using 15-20 HP SP500 drives, a special cover is required. The model number of theSP500 cover kit is M/N 2CK4120. Follow the instructions provided with the kit when replacing thecover. The instructions in this appendix assume that the drive has the correct cover on it.

E.2 Installing the AC Mains Filter

. This section describes how to identify and install the AC Mains Filters. These filters have beendesigned to limit the conducted electromagnetic emissions to the AC power mains from the SP500drives.

Compliance with Electromagnetic Compatibility Standards E-1

E-2

2

2

3

3

5

5

7.5

Appendix E

(Continued)

Table E.1 identifies the SP500 drives that are in conformance with the standards listed in section E.0

and their corresponding AC Mains Filters. Verify that you have the correct AC Mains Filter for yourapplication.

10

15

20

HP

1

1

Table E.1 - AC Mains Filters

SP500 Model Number

1 SU21001

1 SU41001

1 SU21002

1 SU41002

1 SU21003

1 SU41003

1 SU21005

1 SU41005

1 SU41007

1 SU41010

1 SU41015

1 SU41020

AC Mains Filter .Model Number

2DF2282

2DF4283

2DF2282

2DF4283

2DF4283

2DF4283

2DF4283

2DF4283

2DF4284

2DF4284

2DF4285

2DF4285

Use the following guidelines to mount the SP500 drive to the AC Mains Filter and then mount thedrive/filter assembly to a panel:

Attach the SP500 drive to the AC Mains Filter. See figure E.1. No other type of mounting ispermitted. The required mounting hardware is supplied with the filter.

Attach the SP500 drive/AC Mains Filter assembly to a panel or wall. See figure E.1 and table E.2for mounting dimensions. The panel/wall surface does not have to be conductive, although it ispreferable. The user must supply the hardware for mounting the drive/filter assembly to thepanel/wall.

SP500 AC Drive Installation and Operation Manual, Version 3.1

0

IlL

0

0

Appendix E

(Continued)

Top View(Filter Only, Cover Removed)

Il

t-- MS Nuts

101.A A A 1&414-K, Conduit Entry

0

E

D E-»111.-0000-Ll l-2 L.3 E(GND)-

AC MainsFilter

1.F & 2Front View

(Filter Only)

See table E.2 for dimensions.

7G

CB

A

ACMains

Filter

SP500

DriveMounts on Topof Mains Filter

(ScrewsProvided)

Side View

(Filter and Drive)

Figure E.1 - AC Mains Filter Dimensions

Compliance with Electromagnetic Compatibility Standards

Flexible

,/ Conduit(Provided)

E-3

E-4

Dimension

C

J

A

D

H

G

K

E

F

B

Filter Weight

Appendix E

(Continued)

Table E.2 - AC Mains Filter Mounting Dimensions and Weights

AC Mains Filter

M/N 2DF2282

146 mm

5.7"

407 mm

16"

382 mm

15'

104 mm

4.1"

9 mm

0.35"

21 mm

0.83"

63 mm

2.5"

118 mm

4.6"

25 mm

1"

22 mm

0.87"

2.5 kg

5.5 Ib

E.3 Wiring Practices

AC Mains Filter

M/N 2DF4283

217 mm

8.5"

387mm

15.25.

362 mm

14.25"

174 mm

6.9"

9 mm

0.35"

21.5 mm

0.85"

53 mm

2.1"

180 mm

7.1 "

18 mm

0.71 "

22 mm

0.87"

3.2 kg7 Ib

AC Mains Filter

M/N 2DF4284

272 mm

10.7"

441 mm

17.4"

415 mm

16.3" -

230 mm

9.1 "

9 mm

0.35"

21 mm

0.83"

53 mm

2.1.

231 mm

9.1 '

18 mm

0.71"

22 mm

0.87"

3.2 kg7 Ib

AC Mains Filter

M/N 2DF4285

272 mm

10.7

575 mm

22.6"

550 mm

21.7"

232 mm

9.1"

9 mm

0.35"

20 mm

0.79"

93 mm

3.7"

235 mm

9.1 "

43 mm

1.7"

28 mm

1.1"

5 kg11 Ib

This section describes how the SP500 drive must be wired to conform to the standards listed in

section E.0. See figures E.2 and E.3 for typical SP500 connection diagrams.

E.3.1 Connecting the AC Malns Filter Output to the SP500 Drive Input

The power leads that connect the output terminals of the AC Mains Filter to the drive's AC inputterminals are included with the filter. The flexible conduit to be used with these power leads is alsoprovided. See figures E.2 and E.3.

• Place the flexible conduit's hub in the drive's wire entry hole that is in-line with the filter's outputwiring opening. Route the leads through the conduit. Secure both ends of the flexible conduit.

Trim the power leads to the proper length and connect them to the drive's AC input powerterminals (R,S,T). Connect the green/yellow ground lead to the drive's ground terminal.

Note that the filter's output leads are red, yellow, and blue. This color coding is stenciled on theprinted circuit board at the filter's input power terminals to help identify the filter's output wiringrelative to the filter's input wiring.

SP500 AC Drive installation and Operation Manual, Version 3.1

Appendix E

(Continued)

• When the drive is connected to single-phase AC input power, follow the color coding shown infigure E.2 and connect all three filter output leads to the drive's AC input power terminals.

• When the drive is connected to three-phase AC input power, the three output leads from the filtershould be connected to the drive's AC input power terminals as shown in figure E.3.

• Connect the filter ground wire (green/yellow) to the drive ground.

FILTER'S AC INPUT POWER---+-

DRIVE'S AC INPUT POWER-

A 8

&606=Ll L2 L3 E(GND)AC MAINS FILIER

GREEN/

REDYEUOW BLUE YELLOW

SP500

u 6#

MOTOR

GND

0

Figure E.2 - Typical SP500 Single-Phase Connections

FILTERS AG INPUT POWER-

DRIVE'SAC INPUT POWER-

C

--1 5 6 r-*Ll L2 L3 E(GND)

AC MAINS FILTERGREEN/

REDYELLOW BLUE YEUOW

fs,1SP500

Udd

MOTOR

Figure E.3 - Typical SP500 Three-Phase Connections

Compliance with Electromagnetic Compatibility Standards

GND

0

E-5

E-6

E.3.2 Motor Leads

Appendix E

(Continued)

The motor leads must be run in continuous, rigid, conductive conduit, continuously-screenedarmored cable, or equivalent. Note that the use of flexible metal conduit, open wire, or wire in trays isnot acceptable. Many flexible metal conduit products have not been designed for RF containmentand are not adequate to maintain compliance.

All motor leads should have the same cross-sectional area.The maximum allowable motor lead

length from the drive to the motor is 76 m (250 feet).

A ground (earth) lead, equivalent in size to the motor leads, must be run with the motor leads fromthe motor to the drive. Terminate this lead in the drive at the ground terminal.

Proper glands must be used to terminate the motor conduit/cable. The gland must secure the cablescreen to the conductive surfaces of the drive and motor. A full 360' screen termination is preferred.

Follow all instructions supplied with the motor.

E.3.3 Connecting AC Input Power to the AC Mains Filter

Connect AC input power to the filter by first removing the filter's cover and then connecting the ACinput power leads to the terminals at the top of the filter. See figure E.1.The AC input power leadsshould have lugs attached. The filter has a conduit opening to secure the AC input power conduit.

E.3.4 Grounding the Drive/Filter Assembly

Connect the drive/filter assembly to earth ground at the terminal provided next to the filter's AC inputpower terminals. Size the ground wire per EN-60204-1, Part 5.21 , for copper conductors andEN-60204-1, Part 8.2.2.2 2, for non-copper conductors. European Union standards require that theground wire must be green/yellow according to EN-60204-1, Part 15.2.2.3

1EN-60204-1, Part 5.2: Minimum Cross-Sectional Area of the External Protective Copper Conductor

Cross-Sectional Area of

Phase Conductors Supplyingthe Equipment (S) (mm2)

S<16

16<S<35

S > 35

Minimum Cross-Sectional Area of

the External Protective

Conductor (mm2)

S

2EN-60204-1, Part 8.2.2.2: Protective Conductors

16

S12

Copper conductor should be used. If a material other than copper is used, its electrical resistanceper unit length should not exceed that of copper. Non-copper conductors should not be less than 16mm2 in cross-sectional area.

3EN-60204-1, Part 15.2.2: Identification of the Protective Conductor

For insulated conductors, the two-color combination of green and yellow should meet the followingcriteria for any given 15 mm length: one of the colors should cover at least 30% and no more than70% of the surface, with the other color covering the remainder of the surface.

SP500 AC Drive Installation and Operation Manual, Version 3.1

E.3.5 Operator Control Stations

Appendix E

(Continued)

The enclosure of an operator's control station must be constructed of a conductive metal. The coverof the enclosure should be bonded to the case and not rely on the hinge for bonding. Standardindustrial operator devices, e.g., pushbuttons, switches, and meters, may be used.

The wiring connecting the operator's devices to the drive must be run in continuous, rigid,conductive conduit, continuously-screened armored cable, or equivalent. Note that the use of flexiblemetal conduit, open wire, or wire in trays is not acceptable. Many flexible metal conduit productshave not been designed for RF containment and are not adequate to maintain compliance.

Proper glands must be used to terminate the operator's control station conduit/cable at the stationand the drive. The gland must secure the cable screen to the conductive surfaces of the drive andstation enclosure. A full 360. screen termination is preferred. Screen pigtails are not permitted.

E.3.6 1/0 Signals

Il_

t

Control (1/0) and signal Wiring must be run in continuous, rigid, conductive conduit orcontinuously-screened cable as shown in figure E.4. Note that the use of flexible metal conduit, openwire, or wire in trays is not acceptable. Many flexible metal products have not been designed for RFcontainment and are not adequate to maintain compliance.

Stranded copper wire

Plastic insulation

Inner plastic sheath

Compact screen of galvanized (tinned) copper or steel braid

Outer plastic jacket

Figure E.4 - 1/0 Signal Cable

Compliance with Electromagnetic Compatibility Standards E-7

E-8 SP500 AC Drive Installation and Operation Manual, Version 3.1

.

Appendix F

Replacement Parts

The following tables list the replacement parts available from Reliance Electric. Replacement parts are notavailable for 1 and 2 HP drives (M/N 1 SU1 000( and 1 SU2xx00. For M/N 1 SU24002, use the replacementparts listed for the 3 HP drive.

Description

Fan Assembly

NEMA 4X

Cover/Gasket

NEMA 1 Cover

NEMA 12 Cover

Membrane Switch

(Keypad)/Bracket

Regulator PCB

Capacitor PCB

Fan Assembly(Internal)

Replacement Parts

Table F.1 Replacement Parts List for Model 1 SU2xxxx Drives

Description

Fan Assembly

NEMA 4X Cover/Gasket

NEMA 1 Cover

Membrane Switch

(Keypad)/Bracket

Regulator PCB

Capacitor PCB

Fan Assembly (Internal)

Part Number

615161-S

805522-1 R

805508-2R

709511-1 R

56952-300

56931-050

615159-1 R

2

Quantity perHorsepower

3 HP 5 HP

1

1

1

2

Table F.2 - Replacement Parts List for Model 1 SU4xxxx Drives

Part Number

615161-S

805512-1 R

805522-1 R

805504-7R

805508-9R

805522-2OR

805512-2OR

709507-1 R

709511 -1 R

709516-1 R

56953-3xx

56954-3xx

56928-030

56928-050

56919-070

56919-100

56961

56962

615159-1 R

1

1

1 HP

1

1

1

1

2 HP

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

Quantity per Horsepower

3 HP 5 HP 7.5 HP 10 HP

2

1

1

1

1

1

1

1

1

1

1

1

2

1

1

1

1

15 HP

1

1

2

1

1

1

1

1

20 HP

1

1

2

1

1

1

1

1

F-1

F-2

Description

Power Supply(Signal) PCB

Power PCB

Gate Driver PCB

IGBT Module

Diode Bridge

Appendix F

(Continued)

Part Number

56957

56963

56960

602909-813AW

Description

Fan AssemblyNEMA 4X

Cover/Gasket

701819-112BA

701819-111 BA

NEMA 1 Cover

1 HP 2 HP

Membrane Switch

(Keypad)/Bracket

Regulator PCB

Capacitor PCB

Fan Assembly(Internal)

Part Number

615161-S

805512-1 R

805522-1 R

805504-7R

805508-9R

709507-1 R

709511 -1 R

56953-3xx

56954-3xx

56922-055

56939-105

615159-1 R

1

1

1

1

Table F.2 - Replacement Parts List for Model 1 SU4xxxx Drives (continued)

1

1

Quantity per Horsepower

3 HP 5 HP 7.5 HP 10 HP

Table F.3 - Replacement Parts List for Model 1 SU5xxxx Drives

1 HP

1

1

Quantity per Horsepower2 HP 3 HP 5 HP 7.5 HP

1

1

1

1

1

1 1

1

1

1

1

1

1

1

1

1

1

1

1

2

15 HP

1

1

1

3

1

1

1

1

1

1

1

10 HP

2

1

1

20 HP

SP500 AC Drive Installation and Operation Manual, Version 3.1

1

1

3

.

£:

Glossary

accelerating torque - an increase in torque (force) generated by a motor in order to achieverunning speed.

base speed - the manufacturer's nameplate rating at which point the motor will develop ratedhorsepower at rated load and voltage.

base frequency - the motor nameplate frequency rating.

carrier frequency - the switching frequency at which an IGBT inverter bridge converts a DCvoltage into a pulse-width modulated (PWM) voltage.

constant torque - a torque (force) characteristic independent of motor speed.

current feedback - a current signal used by the regulator to control the operating current of thedrive.

decelerating torque - the torque (force) generated by the decrease in motor and load kineticenergy which the motor and load requires to reach its final (slower) speed condition.

drive - an electronic device that can control the speed, torque horsepower, and direction of anAC or DC motor.

dynamic braking - a braking technique in which the kinetic energy is converted into electricalenergy and dissipated as heat energy via a resistor or other means.

r frequency setpoint - the frequency value stored in memory (either by local or remote means)within a given frequency range of the drive's output voltage. This sets the speed of the motor.

Hz - the abbreviation for hertz. The number of cycles per second.

IET - the abbreviation for instantaneous electronic trip. A fault condition that occurs while thedrive is running resulting in a motor coast-to-rest stop. The drive senses a condition that couldresult in equipment damage and turns itself off.

input power factor - the ratio of the input inverter AC effective power to the input AC apparentpower.

inverter - a static power converter that changes DC power to AC power.

line dip - a short duration, low input voltage condition.

load torque - the motor torque required to keep the load rotating at nearly constant speed.

NEMA - the abbreviation of the National Electrical Manufacturer's Association.

NEMA 1 - the Type 1 enclosure defined in NEMA standards that provides protection againstdust, light indirect splashing, and accidental human contact with the electrical circuit.

NEMA 4x - the Type 4x enclosure defined in NEMA standards that provides a degree ofprotection from falling rain, splashing water, hose-directed water, and corrosion. The Type 4xenclosure described here is for indoor use only.

NEMA 12 - the Type 12 enclosure defined in NEMA standards intended for use in applicationswhere it is desirable to exclude such materials as cooling oil, seepage, dust, lim, fibers, andfilings.

G/ossary Glossary-1

Glossary-2

overcurrent - a current greater than a specified maximum current value.

overload capacity - the ability of the drive to withstand currents beyond the system'scontinuous rating. It is normally specified as a percentage of full load current for a specified time period.

overtemperature - a temperature greater than the specified (rated) temperature limit.

power factor - a measurement of the time phase difference between the voltage and current inan AC circuit. Power factor is the ratio of Real Power (kW) to total KVA or the ratio of actualpower (W) to apparent power (volt-amperes).

pulse-width modulation (PWM) - a method whereby a DC voltage is converted to produce anAC voltage whose magnitude and frequency can be varied.

rated input voltage - the specified AC line voltage connected to the drive.

rated output current - the total maximum current delivered from a drive or to a motor under fullload conditions. .

rated output voltage - the drive's total maximum output voltage while delivering rated currentunder full load conditions.

rated output frequency - the fundamental output wave frequency.

rectifier - a static power converter that changes AC power to DC power.

speed range - the speed minimum and maximum at which a motor must operate underconstant or variable torque load conditions.

stall - a motor state in which the motor remains motionless although the motor is generatingtorque.

surge suppressor - circuit protection that suppresses the peak value of any unusual inputvoltage to the drive. It is sometimes used to lighten the leading edge of voltage.

torque - a turning force applied to a shaft, tending to cause rotation.

torque compensation - the increase of the volts/frequency ratio of the drive in the low frequencyarea to compensate for the reduced torque of the motor at low speeds. Reduced torque at lowspeeds is due to the resistance of the motor stator windings.

voltage feedback - a voltage signal which the regulator uses to control the operation of thedrive.

volts per hertz (V/Hz) - the ratio of output voltage (in volts) to output frequency (in hertz) in theoutput frequency range of the drive to achieve constant torque in the motor.

SP500 AC Drive Installation and Operation Manual, Version 3.1

. AAcceleration Time (F-01), 8-5

AC input

· diodes, checking, 9-8

line branch circuit fuses, 3-6 to 3-7,4-6,5-1

ratings, 2-7 to 2-8wire sizes, 3-4 to 3-5

wiring, 3-4 to 3-7,4-1 to 4-6,5-1 to 5-2

AC line distribution capacity, A-1AC mains filter, E-1 to E-6

AC output wiring, 3-4 to 3-6,4-1 to 4-5,4-7 to 4-8,5-2,5-10

Air flow, 3-1 to 3-4

Altitude requirements, 3-1, A-1

Analog input jumper (J6), 4-7 to 4-8Analog Output Select (F-29), 8-18

Analog output wiring, 5-4

» Analog speed reference wiring, 5-3 to 5-4

Area required, 3-1 to 3-4

Auto-Restart Number of Attempts (F-26), 8-17

z Auto-Restart Retry Wait Time (F-27), 8-18

Avoidance Bandwidth (F-22), 8-15

Avoidance Frequency (F-21), 8-14

B

Board

Capacitor, 2-10 to 2-12, F-1 to F-2Power, 2-9 to 2-12, F-2

Regulator, 2-9 to 2-12, F-1 to F-2

Braking, snubber resistor, 2-13, A-2

wiring, 4-2 to 4-5,5-8 to 5-9

C

Carrier frequency, 2-7 to 2-8, A-1

Carrier Frequency, 8-9

Coast Stop Enable (F-16), 8-12

Conduit size, 4-2 to 4-5

Configurable Output Relay Select (F-09), 8-8

Control Source Select (F-00), 8-4

Control terminal strip, 2-9 to 2-12,5-3

Control wiring, 5-3 to 5-9

Current Limit (F-05), 8-6

D DC bus

terminals, 9-2 to 9-3

Index

Index

verifying capacitor voltage, 9-1 to 9-3Deceleration Time (F-02), 8-5

Digital input wiring

Forward/reverse, 5-7, A-2

Function loss, 5-7, A-2

IET reset, 5-7, A-2

Multi-speed reset, 5-6 to 5-7, A-2

StarUstop, 5-4 to 5-5, A-2

Dimensions, 3-2 to 3-3, A-1

Display

description, 7-1

scaling, see RPM at Base Speed (F-08)Drive faults, see Faults

Drive Voltage Selection (F-28), 8-18

E

Electromagnetic compatibility standards

AC mains filter, E-1 to E-6

Compliance requirements, E-1

Declaration of conformity, E-1

Electronic Thermal Overload (F-14), 8-11

Electronic Thermal Overload Enable (F-15), 8-11

Emergency stop, 3-7

Enclosures, NEMA, 2-7 to 2-8

Environmental conditions, 3-1, A-1

Error log, 9-3

F

Fault codes, 9-3 to 9-6

Faults

drive reaction to, 9-1

possible causes and correctiveactions, 9-3 to 9-6

resetting, 9-3

Forward, digital input, 5-3 to 5-7

Frequency, carrier, 2r7 to 2-8, A-1

Function loss, digital input, 5-3,5-7

G

Grounding, 2-9 to 2-12,5-10

H

Humidity, 3-1, A-1

1

IET reset, digital input, 5-3,5-7

IGBT power devices, 2-2

Index-1

checking, 9-8 to 9-9

Input, AC, see AC input

Input, digital, see Digital Input WiringInstallation

checking with power off, 6-1 to 6-2checking with power on, 6-2 to 6-3

completing, 6-1 to 6-3disconnects, +6

output contactors, 4-7

planning, 3-1 to 3-8

requirements, 3-1transformers, 4-6

J

Jumper (J6)

location of, 4-7 to 4-8

K

Key descriptions, 7-1 to 7-2

Keypad and display operation, 7-1 to 7-7Kits

Option, 2-13

Snubber resistor braking, 2-13

L

Lead lengths, motor, 3-5 to 3-6, A-1

LED descriptions, 7-2 to 7-3

Une frequency, A-1

Une noise, avoiding, 4-6

N

M

Manual Torque Boost (F-06), 8-6

Maximum Speed (F-04), 8-6

Mechanical motor overload protection, 4-7

Membrane switch/bracket assembly, 2-9 to 2-12,F-1 to F-2

Minimum Speed (F-03), 8-5

Model numbers, 2-7 to 2-8

Monitor mode, 7-5 to 7-6

Motor

motor lead lengths, 3-5 to 3-6, A-1

multiple motor applications, 3-8

overload protection, mechanical, 4-7single motor applications, 3-8

Mounting dimensions, 3-2 to 3-3, A-1

Multi-Speed Presets 1, 2, 3 (F-23, F-24, F-25), 8-16

Multi-Speed presets, digital inputs, 5-6 to 5-8

NEMA enclosures

Index-2

0

Option kits, see Kits

Output

current, 2-7 to 2-8

power wiring, 34 to 3-6, 4-1 to 4-5, 4-7 to 4-8

status relay wiring, 5-9

PParameters

displaying or changing values, 8-1 to 8-2

factory settings and defaults, 8-1 to 8-2listed alphabetically, C-1menu structure, 7-4

password protection, 8-2

record of user settings, 8-1 to 8-2Parts, replacement, F-1 to F-2 '

Password Lockout Enable (F-20), 8-14

. Password protection, 8-2 to 8-4

Percent Selected Speed Reference Display Enable(F-13), 8-10

Planning

drive clearance, 3-4

location, 3-1

Power

loss, 2-7 to 2-8

ratings, 2-7 to 2-8

wire sizes, 3-4 to 3-5

Power Module

checking circuitry with power off, 6-1 to 6-2

verifying DC voltage, 9-1 to 9-3

Power-Up Start Enable (F-19), 8-13

Program mode, 7-4 to 7-5

R

Ratings

AC input, 2-7 to 2-8NEMA, 2-7 to 2-8

power, 2-7 to 2-8power loss, 2-7 to 2-8

Regulator board, 2-9 to 2-12, F-1 to F-2

Remote Reference Gain (F-11), 8-9

Remote Reference Offset (F-12), 8-10

Replacement parts, F-1 to F-2

Reset, digital input, 5-3,5-7

Resistor, snubber braking, 2-13,4-2 to 4-5,5-8 to 5-9, A-2

Reverse, digital input, 5-3,5-7

Reverse Disable (F-17), 8-12

Routing, wire, 4-1 to 4-5

RPM at Base Speed (F-08), 8-8

RPM Setpoint Enable (F-18), 8-13

SASOO AC Drive installation and Operation Manual, Version 3.1

0

S

Scaling the RPM display and reference, 7-6

Signal wiring, 5-3 to 5-9

Site requirements, 3-1

Snubber resistor braking, 2-13, 4-2 to 4-5, 5-8 to5-9, A-2

Specifications

conduit opening sizes, 4-2 to 4-5

environmental, 3-1, A-1

dimensions, 3-2 to 3-3, A-1

drive inputs, A-2

drive outputs, A-2

service conditions, A-1

terminal torque ratings, 3-5

wire sizes, 3-4 to 3-5

Start, digital input, 5-3 to 5-5

Stop, digital input, 5-3 to 5-5

Stopping the drive, 3-7

Index

T

Terminal strip

torque specifications, 3-5wire sizes, 3-4 to 3-5

wiring, 5-3 to 5-9

Testing, IGBI 9-8 to 9-9

Torque specifications, 3-5

Transformer, isolation, 4-6

V

Ventilation, see Air Flow

Version Information (F-49), 8-18

WHz (Base Speed) (F-07), 8-7

W

Watts loss rating, 2-7 to 2-8Weights, A-1

Wire routing, 4-1 to 4-5

Index-3

Index-4 SA500 AC Drive Installation and Operation Manual, Version 3.1

6 6

2C-

LLI

CE

Publication Name:

Publication Number:

Reliance Electric

Documentation improvement Form

Publication Date:

Use this form to give us your comments concerning this publication or to report an error that youhave found. For convenience, you may attach copies of the pages with your comments. Afteryou have completed this form, please return it to:

Comments:

Your Name:

Company Name:

Address:

Thank you for your comments.

Date:

Follow-Up Action:

Reliance Electric

RGA (Technical Publications)25001 Tungsten RoadCleveland, Ohio 44117

Fax: 216-266-7120

Technical Writing Internal Use

Date:

Phone: ( )

DIF Number.

03 ROCIONell Aummation

Reliance Electric

Reliance Electric / 24703 Euclid Avenue / Cleveland, Ohio 44117 / (216) 266-7000

Printed in U.S.A. 02-3356-2

* ROCIon,ell Automation

Reliance Electric

July 1997

J

0

3 gC

00

0

Z0

C

0

mmmr

o m

N00

$N

fi

0'

Eg

E

eN

00

.,6

=

TI K

K 0m :u

000050 r

m5

-1r OWPO4108-1 C ·

·m

-1

r 0

1. ObZC·'m

33 Eg

MEgme 59E= a@

SS @@Sm 58

m 8E

=10&,ezmEgo5EimES:SO

<-1MtgE05

Z0

Zam»i

E :3 zimas88g0 0 -1

Z0

iEr,

M 22

MSQ 0

il s, Ef 5 El

Eimal9-4Okr-

INFBBE'i

muggE=*EgmEMEZE8 F#1. STOe.&451AMSm@EE5m

- E Eqi@: sEEF= sial= EE EM mr·:0Om

1255151 3-1, 5 8 2 m M 8 8 5 S E

859@S

EHilMgo-:cm

=*5%12=

0 717

m

7 8:

E.r8 *9ipsr ROMed

3BiME

mm:Emtlte-it00400

0

M

)!rj

MM

U

AQ

e

. 09

0

U

E

2152um %5 , 0 , r,; J H J < 4 4

EZ< BE m=*4535552,25 ,5m==Em =====83=ms= 8899 104 w 82 Amumfgazedl >i:i <>r;, si 3$

Cons»ly.=i MOM MN

5 3#Mild REBERMIOEME' 29= 61#MmE =Em-Mmg:Z ='55 2,E 8zOE6 JUREBE Mas:=85=:sENE= em=

F NIN"95 +EBE: 24/amigi Wel152<SE: 5<529euM <El,Acg 6

4"WPKFDUEmE=m= FAMEW#ldsm=EE@mm EMB

3*ME<dE# ME%5S@gE:El ZE<%2920%9%„SAJ#MR ZAOFOE=med < L=J

EE=Esm* SZO Quin

119 0-'020 *za@MagEm,# 4%e> 9

*2@Z@=ReE Ew2§5582*5* EDAlSiREB 2§tifaim@292 SEQi

&0-30 91WlmE22220;Jo %222

MJ

085

Z Z E-005%

25FU] O Dffugt,05

mom

Zoa

2-,8dE#

f (4a

1d

Ea

ms

0

Z

5

8

M

A

mi

0

A

B

a

C

.

h, 1!!i E4332r

B d! O a: 60 1111

25& 22

iB5S St

15·8

Beammx

%159*9. 0 -n

m,3000mgs-¤/

iMESS0=90-1/Cloa

:*EjaEES5EME%

§8»»Elowgm

.SEE=2,dag

mES¥5

m

00 = ZZi S·sK5 22

zee zimIN<*a -8 ae=mils 555*BE9*01Nz o isigfW fif 8.8BM63586zBM@ 1 Teeles 129 592•

Lz<028<F zza 5 11:§811 589Z03 =oz-O OU n *{03®5- <71 R

92,6/PS"p PMS s =sa/566 3/gr0.0 m 2. 1/ 102/iiaE 245/*= m I 10===..BRESISE

2 3 iE piftilis jigE

A * 385S4 ra.W6%10.BrEne §*Mimiq H Hifi: i N i*0„ *4% Bi' 12. fiSBN m 30

v 4 ,« Bia Irn On

8 6 P [m =-"K Ta il2 ES* i

5 1/. 5 m

2 45

*W5522

E5

m6

gg

=m

. -L

E5SS

im

g0

5n

{D

R

5

i5

i:

0

E

g

i

e

F

15i6am

l@8m

g

Z

6) *

3 3

iZ

ii0

-·S3 3mgI 5

0

S

8

i

ro I

8 a

N -

2 1

§§

ZK

> 20

ii

.

g=0

a

B

I

i

E

Fm

E

E

ECD

E

@

Q

9

8

3

2S

g0

- -1

*RmUB f

SS 2%3%5SF/n

9Z

0285

0 sl6

H0@

52

82

3 8

S5

SS0

5·580 525

ES:=o as Rm -9 9

02.:

OP.2

1 512. c

5 a isaii

0 g

3SF7

3802#EKEQQ8:162503'E

§34'3§3Efi§52 §85;52

=z ifi:fi-- 51 1 11 i

.a *5.

. i; AggE-. SS = S.

55 trE E55 SS]* *

- 25 63

iNc.

E a5m

&a

8*./

0

Z502

0.

>Irr-1

5&23mEamz55/ZSWizdooOZO.m

MOK,=a

mEOzo42#ES=E/=m·25zo

Z-loc

62=5miEZEgs5

690Esm=z4/ZO

E29

0&>0

713 m z

5

m

mBE

5=00==

mwZ

o3emp

032

5eS

Q:

9 ¤

Sm

0

0Z

I LuI0

0Z

m Ok

. mui 41) 0.1

A<z

Eig

0_1a <C

Z

iiiE :263&ME'o

==M

i 14REY

111 E u 2O EeZ :Se

ElftiYint

5231

2 &·* 2

Mi:iZIEY

0000.= 8-4-2. B.8 Ef 6.62 :B ala 6 * SSoowAE-6 &%. 50 8 BB€ 5 5 852 Za

fifii! 880& SE 525.EB= %81 14m:55 9 XEDXDES66£,R 31,1 21 Giflii.Ef Iii*li5:fs: f 2%11 ti 11:511*i *11":1.30-el

2:=:27 M[DE€ 0. oES ne e o,r-ailifff im 1: i gil: 0.3 RE#/.81.SIES 186 t.i538 li83 2 185:lfi f!.iff 5 /3 :EY :1 11 /{ ap fyiti lilli:;559*&2 :2 .2:Bil*235"(4 905-0 N:g:52%=5 [email protected] :w 1915-#58z skr:-80 59-=25% 2=8 S°20450 20 Er€--E

f] 1 41 ij i; 1: Pul i·i liialfill ij i121*fll 52€* 1511,#Zi**11{19,2,2.=.A®. e.ol 169:d:MEfE:RiE22fENs11 E2ia i#€a=8365=:52:®1811/fili Vilit ilillilliffiltilit .

-z - F 1% 5·ijil *if :83,1 "affe f <Bul m FA B :ul 0 @0 E I E£28 w 5 2·D

&8

5 14

5 11RE 11

'Re EE

em §1

!{. iiiiz ly:0= -2

29 822

ZEE 62Eg

iii lill i

iii.

Zlia=

SIES

W=ZOi / 11/25E€*2:8:'SE=c --ac

.2 EE o

1 iii

Oj#:SEEEI5S2%52951#*EBE

2 E2

528 8 9 8291* § i }1

15 3 * EEDie .0 3 EO025 1 E EME=all 1 1 :5lili w /{Hi i iii1**5 0 LE

3262/ 1 }1&1&22 5 omS:ESQ -. SBBRF kE i if:5250 E -ag

liESSS §1 -306-2&2:1* 0" fERS§121112 21 851

it lit; f 11 Fi f#f56=8 - CV

BEE:

2.5 6 0

952,

EE:9 5

8 5

fY

9:

05 5

BmE2

23 52;%li/1 4 1 1 i1 E -B *3 i5* E*38

00: 6

il /{31EE E- Cv

M56 <e35MONS W#ES,5

¤2

Zt

R*0- Eli*8

88- 812800 . . orn0

REN* s I kk-0 10 I.

98*- 2 ' 28-/ .

g... 9 1§§)LOCY(OCO El ggo'141 -

8188*M . 0

89©02

.©00P --

2m8Z

2233 81 §§1 =o 1

'°833 R '88' 380 0

9333 8880 1 '&- -<0 052

12%11 figg R*,;5> C.'1 Mu S N * 10: 7:

Ng:M@600<og<SE

' #E/§3MS

M*gE@5805£:<555SEEd*Sa0-:Zz=Ul-1

a·51555/. 244=5-2

=Sid==SME=me=mgaliEWOAZBjafas=