n62470-21-c-0003 drawings volume 4 of 4 - aws

59
L CP 2 3 4 1 C B A FIRE DEPARTMENT ACCESS FOOTPRINT OF CANOPY SEE CIVIL DRAWINGS FOR ANTITERRORISM SECURE ACCESS NO FIRE SPRINKLER SYSTEM IS PRESENT. NO FREE STANDING FIRE DEPARTMENT CONNECTION OR PIV IS PRESENT IMAGINARY PROPERTY LINE. FOR PURPOSES OF APPLYING THE BUILDING CODE, ALL 3 BUILDINGS ARE CONSIDERED AS ONE BUILDING FIRE DEPARTMENT ACCESS FIRE HYDRANT FUTURE GUARD SHACKS - NOT IN SCOPE OF WORK FOR THIS PROJECT AND ARE SHOWN FOR REFERENCE ONLY 6 ,1 0 9 D VEDERE I DISEGNI CIVILI PER L'ACCESSO PROTETTO ANTITERRORISMO FUTURE GUARDIANIE - NON RIENTRANO NELL' AMBITO DI LAVORO DI QUESTO PROGETTO E SONO MOSTRATE SOLO COME RIFERIMENTO LINEA DI PROPRIETÀ IMMAGINARIA. AI FINI DELL'APPLICAZIONE DEL REGOLAMENTO EDILIZIO, TUTTI E 3 GLI EDIFICI SONO CONSIDERATI COME UN UNICO EDIFICIO NON È PRESENTE UN SISTEMA ANTINCENDIO A SPRINKLER. NESSUNA CONNESSIONE DEI VIGILI DEL FUOCO O VALVOLA A SARACINESCA CON INDICATORE AD ASTA È PRESENTE. IDRANTE ANTINCENDIO PROIEZIONE DELLA TETTOIA ACCESSO DEI VIGILI DEL FUOCO ACCESSO DEI VIGILI DEL FUOCO PLANIMETRIA DEL SITO DI CONFORMITÀ AL CODICE SCALA 1:400 EXISTING FIRE HYDRANT ESISTENTE IDRANTE ANTINCENDIO SATISFACTORY TO DATE APPROVED ACTIVITY FOR COMMANDER NAVFAC A/E INFO A B C D 1 2 3 4 5 1 2 3 4 5 A B C D SCALE: CONSTR. CONTR. NO. SHEET NAVFAC DRAWING NO. DES DRW CHK OF EPROJECT NO.: DEPARTMENT OF THE NAVY NAVAL FACILITY ENGINEERING SYSTEM COMMAND NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018 PM/DM BRANCH MANAGER DESIGN DIRECTOR FIRE PROTECTION NAVAL FACILITY ENGINEERING SYSTEM COMMAND ~ ATLANTIC NORFOLK, VIRGINIA AS NOTED UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED AVIANO AIR BASE AVIANO, ITALY AREA A1 ENTRY CONTROL POINT LET/JSL DPS 1917 SOUTH 67TH STREET OMAHA, NE 68106 4/7/2021 8:36:13 AM BIM 360://10224522_NAVFAC_A1_Design_Aviano_Italy_2018/10224522-A-Canopy_v2018.rvt F-101 CODE COMPLIANCE SITE PLAN - PLANIMETRIA DEL SITO DI CONFORMITÀ AL CODICE Checker 150 14090153 Designer Author 208 22 MARCH, 2021 APPROVED BY SCOTT KIBLER VIA E-MAIL 1631931 N62470-21-C-0003 ATLANTIC DESIGN AND CONSTRUCTION RICHARD STEPHENS, PE DER SCALE: 1 : 400 A1 CODE COMPLIANCE SITE PLAN OVERWATCH GATEHOUSE SEARCH ID CHECK PLAN NORTH KEY PLAN / PIANTA CHIAVE GENERAL NOTES/ NOTE GENERALE GRAPHIC SCALE: 1:400 0 8 4 16 12 20 40 S Y M D E S C R I P T I O N D A T E A P P R

Upload: khangminh22

Post on 21-Nov-2023

1 views

Category:

Documents


0 download

TRANSCRIPT

LC

P

2 3 41

C

B

A

FIRE DEPARTMENT ACCESS

FOOTPRINT OF CANOPY

SEE CIVIL DRAWINGS FOR ANTITERRORISM SECURE ACCESS

NO FIRE SPRINKLER SYSTEM IS PRESENT. NO FREE STANDING FIRE DEPARTMENT CONNECTION OR PIV IS PRESENT

IMAGINARY PROPERTY LINE. FOR PURPOSES OF APPLYING THE BUILDING CODE, ALL 3 BUILDINGS ARE CONSIDERED AS ONE BUILDING

FIRE DEPARTMENT ACCESS

FIRE HYDRANT

FUTURE GUARD SHACKS - NOT IN SCOPE OF WORK FOR THIS PROJECT AND ARE SHOWN FOR REFERENCE ONLY

6,109

D

VEDERE I DISEGNI CIVILI PER L'ACCESSO PROTETTO ANTITERRORISMO

FUTURE GUARDIANIE - NON RIENTRANO NELL' AMBITO DI LAVORO DI QUESTO PROGETTO E SONO MOSTRATE SOLO COME RIFERIMENTO

LINEA DI PROPRIETÀ IMMAGINARIA. AI FINI DELL'APPLICAZIONE DEL REGOLAMENTO EDILIZIO, TUTTI E 3 GLI EDIFICI SONO CONSIDERATI COME UN UNICO EDIFICIO

NON È PRESENTE UN SISTEMA ANTINCENDIO A SPRINKLER. NESSUNA CONNESSIONE DEI VIGILI DEL FUOCO O VALVOLA A SARACINESCA CON INDICATORE AD ASTA È PRESENTE.

IDRANTE ANTINCENDIO

PROIEZIONE DELLA TETTOIA

ACCESSO DEI VIGILI DEL FUOCO

ACCESSO DEI VIGILI DEL FUOCO

PLANIMETRIA DEL SITO DI CONFORMITÀ AL CODICE

SCALA 1:400

EXISTING FIRE HYDRANT

ESISTENTE IDRANTE ANTINCENDIO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VAL

FAC

ILIT

Y E

NG

INE

ER

ING

SYS

TEM

CO

MM

AN

D ~

ATL

AN

TIC

NO

RF

OL

K,

VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/7

/20

21 8

:36

:13

AM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

F-101

CO

DE C

OM

PLIA

NC

E SI

TE P

LAN

-PL

ANIM

ETRI

A DE

L SIT

O DI

CON

FORM

ITÀ

AL C

ODIC

E

Checker

150

14090153

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 400A1

CODE COMPLIANCE SITE PLAN

OVERWATCH

GATEHOUSESEARCH

ID CHECK

PLANNORTH

KEY PLAN / PIANTA CHIAVE

GENERAL NOTES/ NOTE GENERALE

GRAPHIC SCALE: 1:400

0 84 1612 20 40

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/7

/20

21 8

:43

:39

AM

BIM

360

://1

02

245

22

_N

AV

FA

C_A

1_

De

sig

n_

Avia

no

_Italy

_20

18

/10

22

45

22

-A-G

ate

ho

use_v20

18

.rvt

FB100

CO

DE

AN

ALY

SIS

-G

AT

EH

OU

SE

-ST

UDIO

DEL

REG

OLAM

ENTO

EDI

LIZI

O -C

ORPO

DI

GUAR

DIA

Checker

151

14090154

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

CONNECTING TO COLUMNS, BEARING WALLS & DIAGONALS , GRAVITY LOADS)

(COLUMNS, BEAMS & GIRDERS

STRUCTURAL FRAME 0-HOUR (IBC TABLE 601)

IDENTIFY FIRE RATED WALLSIBC SECTION 703.7 REQUIRES FIRE RESISTIVE WALLS TO BE IDENTIFIED WITH SIGNSOR STENCILING.

ACTUAL TOTAL BUILDING AREA: 862 FT2 (80.1 M2)

(3,740 M2) X 1 = (3,740 M2)

MAXIMUM TOTAL BUILDING AREA: 40,259 FT2 X 1 = 40,259 FT2 (SECTION 506)

TOTAL 40,259 FT2 (3,740 M2)

NO INCREASE FOR FULLY SPRINKLER ONE-STORY BUILDING 0

INCREASE FOR OPEN YARD AROUND BUILDING 23,000 * (.75) FT2 ((2136 M2) * 0.75))

BASIC ALLOWABLE BUILDING AREA (PER STORY) 23,000 FT2 (2136 M2)

MIXED OCCUPANCY (BUINESS MOST RESTRICTIVE)

ACTUAL HEIGHT/STORIES: 11 FT - 6 INCHES (3.5M) / 1 STORY

ALLOWABLE HEIGHT/STORIES: 55 FT (16M) / 3 STORIES (TABLE 504.3 AND SECTION 504.4)

TYPE OF CONSTRUCTION: TYPE (IIB) ANY NON COMBUSTIBLE MATERIAL ALLOWED BY IBC- NON FIRE RATED.

MIXED USE APPROACH: UNSEPERATED MIXED OCCUPANCY: BUSINESS AND STORAGE

OCCUPANCY CLASSIFICATION: BUSINESS (GATE HOUSE AND GUARD SHACKS)

FIRE DEPARTMENT ACCESS ROADS (NFPA 1 - SECTION 18.2.3) SHALL BE PROVIDED SUCH THAT ANY PORTION OF THE FACILITY OR ANY PORTIONOF AN EXTERIOR WALL OF THE FIRST STORY OF THE BUILDING IS LOCATED NOT MORE THAN 150 FT FROM FIRE DEPARTMENT ACCESS ROADS ASMEASURED BY AN APPROVED ROUTE AROUND THE EXTERIOR OF THE BUILDING OR FACILITY.

THE BUILDING WILL BE CLASSIFIED AS 1 STORY OF TYPE IIB CONSTRUCTION IN ACCORDANCE WITH IBC TABLE 503 AND SECTIONS 504.2. THECANOPY IS NOT CONSIDERED PART OF THE BUILDING AND DOES NOT CONTRIBUTE TO THE BUILDING AREA.

ITALIAN CODES AS NOTED

2018 NFPA 101 – LIFE SAFETY CODE

2018 INTERNATIONAL BUILDING CODE

UFC 3-600-01_FIRE PROTECTION ENGINEERING FOR FACILITIES_CHANGE 4 FEBRUARY 7 2020

UFC 1-200-01_GENERAL BUILDING REQUIREMENTS, CHANGE_2019-10/08

CODE AND STANDARD:

PER THE IBC, BUILDING AREA IS DEFINED "AREA, BUILDING: THE AREA INCLUDED WITHIN SURROUNDING EXTERIOR WALLS (OR EXTERIOR WALLS AND FIRE WALLS) EXCLUSIVE OF VENT SHAFTS ANDCOURTS. AREAS OF THE BUILDING NOT PROVIDED WITH SURROUNDING WALLS SHALL BE INCLUDED IN THE BUILDING AREA IF SUCH AREAS ARE INCLUDED WITHIN THE HORIZONTAL PROJECTION OFTHE ROOF OR FLOOR ABOVE."

THE CANOPY IS NOT CONSIDERED PART OF THE BUILDING AND DOES NOT CONTRIBUTE TO THE BUILDING AREA.

CANOPIES ARE REQUIRED TO BE DESIGNED AND CONSTRUCTED TO WITHSTAND WIND OR OTHER LATERAL LOADS AND LIVE LOADS AS REQUIRED BY IBC CHAPTER 16 WITH DUE ALLOWANCE FORSHAPE, OPEN CONSTRUCTION AND SIMILAR FEATURES THAT RELIEVE THE PRESSURES OR LOADS. STRUCTURAL MEMBERS ARE TO BE PROTECTED TO PREVENT DETERIORATION.

CANOPIES ARE REQUIRED (IBC -SECTION 3105.3) TO BE PROVIDED WITH AN APPROVED COVERING THAT MEETS THE FIRE PROPAGATION PERFORMANCE CRITERIA OF TEST METHOD 1 OR TEST METHOD2, AS APPROPRIATE, OF NFPA 701 OR HAS A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.

CANOPY

COMBINED PLUMBING FIXTURE COUNT ONE WATER CLOSET AND SINK HAS BEEN PROVIDED. SEPARATE FACILITIES ARE NOT REQUIRED (UFC 3-600-1 AND IBC -2902.2) IN STRUCTURES WITH A TOTAL OCCUPANT LOAD OF 15 OR FEWER.

EMERGENCY LIGHTING NOT REQUIRED (NFPA 101 SECTION 38.2.9 AND 42.2.9).

EGRESS ILLUMINATION 1 FOOT-CANDLE ON NORMAL POWER THROUGHOUT (NFPA 101 SECTION 7.8.1.3 (2) AND 38.2.8 AND 42.2.8)

EXIT SIGNS NOT REQUIRED IN SPACES WHERE ONE EXIT PATH IS ALLOWED (NFPA 101 SECTION 7.10.1.2.1)

LIGHTS:

NUMBER OF EXITS 1 EXIT PERMITTED (NFPA 101 SECTION 38.2.4.1 AND 42.2.4.1 )

NUMBER OF EXITS FROM SPACES:

MINIMUM WIDTH DOOR: 32 IN (812 MM) CLEAR (NFPA 101 SECTION 7.2.1.2.3 (1))

DOORS 0.47 IN (12 MM) PER PERSON (D.M. 10 MARZO 1998)

EXIT WIDTHS:

COMMON PATH OF TRAVEL 50 FEET (15M) IN ORDINARY HAZARD STORAGE OCCUPANCY (NFPA 101 SECTION 42.2.5)

TRAVEL DISTANCE 200 FEET (60M)IN ORDINARY HAZARD STORAGE OCCUPANCY (NFPA 101 SECTION 42.2.6)

DEAD ENDS 50 FEET (15M) IN ORDINARY HAZARD STORAGE OCCUPANCY (NFPA 101 SECTION 42.2.5)

COMMON PATH OF TRAVEL 100 FEET (22M) IN BUSINESS OCCUPANCY (NFPA 101 SECTION 38.2.5.3.2)

TRAVEL DISTANCE 200 FEET (60M) IN BUSINESS OCCUPANCY (NFPA 101 SECTION 38.2.6.2)

DEAD ENDS 20 FEET (6M) IN BUSINESS OCCUPANCY (NFPA 101 SECTION 38.2.5.2.2)

TRAVEL DISTANCES: (NON-SPRINKLERED OCCUPANCY)

IN THE DIRECTION OF EGRESS NOT REQUIRED - NOT SERVING 50 OR MORE (NFPA 101 SECTION 7.2.1.4.2)

DOOR SWING:

PERMITTED EXIT DOOR HARDWARE LEVER HANDLES

DOOR HARDWARE:

MECHANICAL/STORAGE ROOMS 500 (46.5) (GROSS)

OFFICE AREAS 150 (14) (GROSS)

OCCUPANT LOAD FACTORS (NFPA 101 TABLE 7.3.1.2) FT2 PER PERSON (M2 PER PERSON)

EXITING:

DOOR 80 IN. (2032 MM) (NFPA 101 SECTION 7.2.1.2.1.1(6))

ROOMS: 90 IN. (2286 MM) (NFPA 101 SECTION 7.1.5.1)

MINIMUM CLEAR HEIGHT:

FIRE EXTINGUISHERS REQUIRED (NFPA 101 SECTION 38.3.5)

FIRE ALARM SYSTEM NOT REQUIRED. UFC 3-600-01 CH 9

COMM ROOM IS NOT INFORMATION TECHNOLOGY ROOM - NO SPRINKLERS REQUIRED (2020 NFPA 75 - CHAPTER 8).

AUTOMATIC SPRINKLER SYSTEM NOT REQUIRED FOR BUILDING OF TYPE IIB CONSTRUCTION UNDER 15,000 FT2 (1393 M2). (UFC 3-600-01 CH9)

ACTIVE FIRE PROTECTION:

FLOOR FINISH: DOC FF 1-70 "PILL TEST" (FEDERALLY MANDATED)

WALL AND CEILING FINISH (NFPA 101 CHAPTER 10): - CLASS A, B OR C:

INTERIOR FINISH

WALL PENETRATIONS F RATING EQUAL TO THE RATING IF THE WALL PENETRATED (IBC SECTION 714.4)

MECHANICAL ROOM: 1 HR FIRE BARRIER (NFPA 101 SECTION 38.3.2.1 AND 8.7)

FLOOR CONSTRUCTION 0-HOUR (IBC TABLE 601)

ROOF COVERING CLASS C (IBC TABLE 1505.4)

ROOF CONSTRUCTION 0-HOUR (IBC TABLE 601)

EXTERIOR NONBEARING WALLS 0-HOUR CONSTRUCTION (IBC TABLE 602)

EXTERIOR WALL 0-HOUR ;FIRE SEPARATION DISTANCE GREATER THAN 10 FEET (3048 MM). (IBC TABLE 602)

INTERIOR AND EXTERIOR BEARING WALLS 0-HOUR (IBC TABLE 601)

( PILASTRI, TRAVI E TRAVETTI CHE SI COLLEGANO AI PILASTRI, MURIPORTANTI E RINFORZI DIAGONALI, CARICHI PERMANENTI)

TELAIO STRUTTURALE 0 ORE (TABELLA 601 DELL'IBC)

AL FUOCO SIANO IDENTIFICATE CON SEGNALETICA O ADESIVI.IDENTIFICAZIONE DELLE PARETI ANTINCENDIO IL PARAGRAFO 703.7 DELL'IBC PRESCRIVE CHE LE PARETI RESISTENTI

AREA TOTALE EFFETTIVA DELL'EDIFICIO: 862 FT2 (80,1 M2) (3.740 M2) X 1 = (3.740 M2)

AREA TOTALE MASSIMA DELL'EDIFICIO: 40.259 FT2 X 1 = 40.259 FT2 (PARAGRAFO 506)

TOTALE 40,259 FT2 (3,740 M2)

NESSUN AUMENTO PER SPRINKLER COMPLETO PER EDIFICI A UN PIANO 0 AUMENTO PER IL CORTILE APERTO INTORNO ALL'EDIFICIO 23.000 * (.75) FT2 ((2136 M2) * 0.75)) SUPERFICIE DI BASE CONSENTITA (PER PIANO) 23,000 FT2 (2136 M2)OCCUPAZIONE MISTA ( UFFICIO - NORMATIVA PIÙ RESTRITTIVA)

ALTEZZA ATTUALE / PIANI: 11 FT - 6 INCHES (3.5M) / 1 PIANOALTEZZA CONSENTITA / PIANI: 55 FT (16M) / 3 PIANI (TABELLA 503 E PARAGRAFO 504.2)

TIPO DI STRUTTURA: TIPO (IIB) MATERIALE NON COMBUSTIBILE CONSENTITO DALL'IBC - NON CLASSIFICATO AL FUOCO.

UTILIZZO MISTO: OCCUPAZIONE MISTA NON SEPARATA: UFFICIO E MAGAZZINO

CATEGORIA D'OCCUPAZIONE: LAVORATIVA (CORPO DI GUARDIA E GUARDIOLA)

LE STRADE DI ACCESSO PER I VIGILI DEL FUOCO (NFPA 1 - PARAGRAFO 18.2.3) DEVONO ESSERE PROGETTATE INMODO TALE CHE QUALSIASI PARTE DELLA STRUTTURA O QUALSIASIPORZIONE DI UNA PARETE ESTERNA DELPRIMO PIANO DELL'EDIFICIO SI TROVI A NON PIÙ DI 150 PIEDI DALLE STRADE DI ACCESSO DEI VIGILI DEL FUOCO,MISURATO DA UN PERCORSO APPROVATO INTORNO ALL'ESTERNO DELL'EDIFICIO O DELLA STRUTTURA.

L'EDIFICIO SARÀ CLASSIFICATO COME UNA COSTRUZIONE DI 1 PIANO DI TIPO IIB IN CONFORMITÀ CON LA TABELLAIBC 503 ED I PARAGRAFI 504.2. LA TETTOIA NON È CONSIDERATA PARTE DELL'EDIFICIO E NON CONTRIBUISCE ALLASUPERFICIE DELL'EDIFICIO.

REGOLAMENTI ITALIANI COME INDICATO2018 NFPA 101 - REGOLAMENTO SICUREZZA ANTINCENDIOREGOLAMENTO EDILIZIO INTERNAZIONALE 2018UFC 3-600-01_PROTEZIONE ANTINCENDIO PER LE STRUTTURE_MODIFICA 4 7 FEBBRAIO 2020UFC 1-200-01_REQUISITI GENERALI DI COSTRUZIONE, MODIFICA_2019-10/08REGOLAMENTI E NORMATIVE:

SECONDO L'IBC, L'AREA DELL'EDIFICIO È DEFINITA COME " AREA, EDIFICIO: L'AREA INCLUSA ALL'INTERNO DEI MURI ESTERNI CIRCOSTANTI (O DEI MURI ESTERNI E DEIMURI ANTINCENDIO) ESCLUSI I CAVEDI DI VENTILAZIONE E LE CORTI. LE AREE DELL'EDIFICIO NON DOTATE DI MURI DI CINTA DEVONO ESSERE INCLUSE NELL'AREADELL'EDIFICIO SE TALI AREE SONO INCLUSE NELLA PROIEZIONE ORIZZONTALE DEL TETTO O DEL PIANO SOVRASTANTE".

LA TETTOIA NON È CONSIDERATA PARTE DELL'EDIFICIO E NON CONCORRE ALLA SUPERFICIE DELL'EDIFICIO.

LE TETTOIE DEVONO ESSERE PROGETTATE E COSTRUITE PER RESISTERE AL VENTO O AD ALTRI CARICHI LATERALI E AI CARICHI DINAMICI COME RICHIESTO DALCAPITOLO 16 DELL'IBC CON LA DOVUTA ATTENZIONE ALLA FORMA , LE APERTURE E CARATTERISTICHE SIMILI CHE RIDUCONO LE PRESSIONI O I CARICHI. ICOMPONENTI STRUTTURALI DEVONO ESSERE PROTETTI PER PREVENIRE IL DETERIORAMENTO.

LE TETTOIE DEVONO ESSERE DOTATE (IBC - PARAGRAFO 3105.4) DI UNA COPERTURA APPROVATA CHE SODDISFI I CRITERI DI PROPAGAZIONE DEL FUOCO SECONDOIL METODO DI PROVA 1 O IL METODO DI PROVA 2, A SECONDA DEI CASI, DELL'NFPA 701 O CHE ABBIA UN INDICE DI PROPAGAZIONE DELLA FIAMMA NON SUPERIOREA 25 QUANDO TESTATO IN CONFORMITÀ CON ASTM E84 O UL 723.

TETTOIA

CALCOLO DEGLI APPARECCHI SANITARI È STATO PREVISTO UN WC E UN LAVANDINO. IN STRUTTURE CON UNA DENSITA' DIAFFOLLAMENTO TOTALE DI 15 PERSONE O MENO NON SONO RICHIESTI SERVIZI SEPARATI(UFC 3-600-1 E IBC - 2902.2).

ILLUMINAZIONE DELL'USCITA 10 LUMEN/MQ PER TUTTO L'AMBIENTE SU POTENZA NORMALE (NFPA 101 PARAGRAFO7.8.1.3 (2) E 38.2.8 E 42.2.8)

SEGNALETICA DI USCITA NON RICHIESTO NEGLI SPAZI IN CUI È CONSENTITO UN SOLO PERCORSO DI USCITA (NFPA 101PARAGRAFO 7.10.1.2.1)

ILLUMINAZIONE:

NUMERO DI USCITE E' CONSENTITA UNA SOLA USCITA (NFPA 101 PARAGRAFO 38.2.4.2 E 42.2.4.2 )NUMERO DI USCITE DAI LOCALI:

LARGHEZZA MINIMA PORTA: 32 IN (812 MM) SPAZIO LIBERO (NFPA 101 SEZIONE 7.2.1.3.2 (1))PORTE 0,47 IN (12 MM) A PERSONA (D.M. 10 MARZO 1998)LARGHEZZA DELLE USCITE:

PERCORSO COMUNE 50 PIEDI (15M) NEI MAGAZZINI DI STOCCAGGIO A RISCHIO ORDINARIO (NFPA 101 PARAGRAFO 42.2.5)DISTANZA DI PERCORRENZA 200 PIEDI (60M) NEI MAGAZZINI DI STOCCAGGIO A RISCHIO ORDINARIO (NFPA 101 PARAGRAFO 42.2.6)CORRIDOIO CIECO 50 PIEDI (15M) NEI MAGAZZINI DI STOCCAGGIO A RISCHIO ORDINARIO (NFPA 101 PARAGRAFO 42.2.5)PERCORSO COMUNE 75 PIEDI (22M) NEGLI UFFICI (NFPA 101 PARAGRAFO 38.2.5.2.2)DISTANZA DI PERCORRENZA 200 PIEDI (60M) NEGLI UFFICI (NFPA 101 PARAGRAFO 38.2.6.2CORRIDOIO CIECO 20 PIEDI (6M) NEGLI UFFICI (NFPA 101 PARAGRAFO 38.2.5.2.2)DISTANZE DI PERCORRENZA: (AREE SENZA SPRINKLER)

NELLA DIREZIONE DI USCITA NON RICHIESTO - GLI OCCUPANTI NON SONO PIU' DI 50(NFPA 101 PARAGRAFO 7.2.1.4.2)VERSO DI APERTURA DELLE PORTE:

FERRAMENTA PER PORTE D'USCITA CONSENTITE MANIGLIE A LEVAFERAMENTA PER LE PORTE:

CENTRALI TERMICHE/MAGAZZINI 500 (46.5) LORDE

UFFICI 150 (14) LORDEINDICI DI DENSITA' AFFOLLAMENTO (NFPA 101 TABELLA 7.3.1.2) FT2 PER PERSONA (M2 PER PERSONA)USCITE:PORTE 80 IN. (2032 MM) (NFPA 101 PARAGRAFO 7.2.1.2.1.1(6)STANZE: 90 IN. (2286 MM) (NFPA 101 PARAGRAFO 7.1.5.1)ALTEZZA LIBERA MINIMA:

ESTINTORI RICHIESTI (NFPA 101 SEZIONE 38.3.5)

IMPIANTO DI ALLARME ANTINCENDIO NON RICHIESTO. UFC 3-600-01 CH 9

LA SALA DI COMUNICAZIONE NON È UNA SALA INFORMATICA - NON SONO RICHIESTI SPRINKLER (2020 NFPA 75 - CAPITOLO 8).

IMPIANTO SPRINKLER AUTOMATICO NON RICHIESTO PER EDIFICI DI TIPO IIB AL DI SOTTO DEI 15.000 FT2 (1393 M2). (UFC 3-600-01 CH9)PROTEZIONE ANTINCENDIO ATTIVA:

FINITURA DEL PAVIMENTO: DOC FF 1-70 "PILL TEST" (SECONDO IL REGOLAMENTO FEDERALE)FINITURA DI PARETI E SOFFITTI (NFPA 101 CAPITOLO 10): - CLASSE A, B O C:FINITURA INTERNA

ATTRAVERSAMENTI DI PARETI RESISTENZA AL FUOCO UGUALE ALLA RESISTENZA DEL MURO ATTRAVERSATO ( IBC PARAGRAFO 714.3).

CENTRALE TERMICA BARRIERA ANTINCENDIO 1 HR (NFPA 101 PARAGRAFO 38.3.2.1 E 8.7)

STRUTTURA DEL PAVIMENTO 0 ORE (TABELLA 601 DELL'IBC)

COPERTURA DEL TETTO CLASSE C (TABELLA IBC 1505.4)

STRUTTURA DELLA COPERTURA 0 ORE (TABELLA 601 DELL'IBC)

MURI ESTERNI NON PORTANTI RESISTENZA AL FUOCO DELLA STRUTTURA - 0 ORE (TABELLA 602 DELL'IBC)

MURO ESTERNO 0 ORE ;DISTANZA DI SEPARAZIONE AL FUOCO MAGGIORE DI 10 PIEDI (3048 MM). (TABELLA IBC 602)

MURI PORTANTI INTERNI ED ESTERNI 0 ORE (TABELLA 601 DELL'IBC)

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

FD

FD

COMMAND & CONTROL101

PASSAGE103

BREAK106

MECH/ELEC107

JANITOR104

COMM105

TOILET102

DOORPORTA

81367

101A

DOORPORTA

81367

101B

TD

-1

TD

-1

DOORPORTA

81367

106

1 2

A

COMANDO E

CONTROLLO

TOILETTE

RIPOSTIGLIO

DI SERVIZIO

DISIMPEGNO

COMUNICAZIONE

STANZA DEL PERSONALE

CENTRALE TERMICA/ELETTRICA

A CLEAR DOOR WIDTH [mm]

B OCCUPANT LOAD CAPACITY [NO.OF PEOPLE] /

EXIT DOOR TAG

LIFE SAFETY NOTES:1.FOR EXIT LIGHTS AND EMERGENCY LIGHTING, SEE ELECTRICAL LIGHTING

DRAWINGS (E SERIES).

LINE TYPES FOR MEANS OF EGRESS:

TRAVEL DISTANCE

SYMBOL COMPONENT

LIFE SAFETY SYMBOLS:

TD

EXIT DISCHARGE ARROW

EXIT DISCHARGE

OTHER

FIRE EXTINGUISHER

WALL RATING LEGEND

1 HOUR FIRE BARRIER

A LARGHEZZA LIBERA DELLA PORTA (mm)

B DENSITA'' DI AFFOLLAMENTO (N° DI PERSONE)

TARGHETTA DELLA PORTA D'USCITA

1. PER LE LUCI DI USCITA E L'ILLUMINAZIONE DI EMERGENZA, VEDERE I DISEGNI DELL'ILLUMINAZIONE ELETTRICA (SERIE E).

USCITA

NOTE SULLA SICUREZZA ANTINCENDIO:

SIMBOLOGIA SICUREZZA ANTINCENDIO:

FRECCIA DI USCITA

LEGENDA CLASSIFICAZIONE ANTINCENDIO DELLE PARETI

DBARRIERA ANTINCENDIO DI 1 ORA

TIPI DI LINEE PER I PERCORSI DI USCITA:

DISTANZA DI VIAGGIO

SIMBOLOELEMENTO

TD

ALTRO

FUOCO ESTINTORE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/7

/20

21 8

:43

:39

AM

BIM

360

://1

02

245

22

_N

AV

FA

C_A

1_

De

sig

n_

Avia

no

_Italy

_20

18

/10

22

45

22

-A-G

ate

ho

use_v20

18

.rvt

FB101

LIF

E S

AF

ET

Y P

LAN

-G

AT

EH

OU

SE

-PL

ANIM

ETRI

A SI

CURE

ZZA

ANTI

NCEN

DIO

-COR

PODI

GUA

RDIA

Checker

152

14090155

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 50A3

GROUND FLOOR LIFE SAFETY PLAN/ PIANTAPIANO TERRA SICUREZZA ANTINCENDIO

MEANS OF EGRESS ARRANGEMENT DISTANCESCHEDULE - BUILDING SUMMARY

EGRESSPATH ID

EGRESS DISTANCE

PROVIDED (mm)MAXIMUM

PERMITTED (mm)TD-1 7,055 609,600

MEANS OF EGRESS WIDTH CAPACITY

EXIT ID

PROVIDED EGRESS CAPACITY - LEVELCOMPONENTS & RAMPS

EGRESSCAPACITY

FACTOR (mm)CLEAR

WIDTH (mm)

OCCUPANTLOAD

CAPACITY

101A 12 813 67

101B 12 813 67

106 12 813 67

GENERAL NOTES

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

KEY PLAN / PIANTA CHIAVE

GATEHOUSE

LARGHEZZA DELLE VIE D'USCITA

SIGLAD'USCITA

CAPACITÀ DI USCITA PREVISTA - ELEMENTI DILIVELLO E RAMPE

CAPACITA' DIDEFLUSSO

LARGHEZZALIBERA (mm)

DENSITA' DIAFFOLLAMENTO

101A 12 813 67101B 12 813 67106 12 813 67

NOTE GENERALE

TABELLA DELLE DISTANZE DELLE VIE DI USCITA -PER TUTTO L'EDIFICIO

SIGLA DELPERCORSOD'USCITA

DISTANZA DELL'USCITADI PROGETTO

(mm)MASSIMA PERMESSA

(mm)TD-1 7,055 609,600

SCALA: 1:50

SCALA GRAFICA

PIANO NORD

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/7

/20

21 8

:53

:32

AM

BIM

360

://1

02

24

522

_N

AV

FA

C_

A1_

De

sig

n_A

via

no

_Ita

ly_20

18

/102

24

522

-A-S

ea

rch_v20

18

.rvt

FC100

CO

DE

AN

ALY

SIS

-S

EA

RC

H O

FF

ICE

-ST

UDIO

DEL

REG

OLAM

ENTO

EDI

LIZI

O -U

FFIC

IOCO

NTRO

LLI

Checker

153

14090156

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

CONNECTING TO COLUMNS, BEARING WALLS & DIAGONALS , GRAVITY LOADS)

(COLUMNS, BEAMS & GIRDERS

STRUCTURAL FRAME 0-HOUR (IBC TABLE 601)

IDENTIFY FIRE RATED WALLSIBC SECTION 703.7 REQUIRES FIRE RESISTIVE WALLS TO BE IDENTIFIED WITHSIGNS OR STENCILING.

ACTUAL TOTAL BUILDING AREA: 862 FT2 (80.1 M2)

(3,740 M2) X 1 = (3,740 M2)

MAXIMUM TOTAL BUILDING AREA: 40,259 FT2 X 1 = 40,259 FT2 (SECTION 506)

TOTAL 40,259 FT2 (3,740 M2)

NO INCREASE FOR FULLY SPRINKLER ONE-STORY BUILDING 0

INCREASE FOR OPEN YARD AROUND BUILDING 23,000 * (.75) FT2 ((2136 M2) * 0.75))

BASIC ALLOWABLE BUILDING AREA (PER STORY) 23,000 FT2 (2136 M2)

MIXED OCCUPANCY (BUINESS MOST RESTRICTIVE)

ACTUAL HEIGHT/STORIES: 11 FT - 6 INCHES (3.5 M) / 1 STORY

ALLOWABLE HEIGHT/STORIES: 55 FT (16 M) / 3 STORIES (TABLE 503 AND SECTION 504.2)

TYPE OF CONSTRUCTION: TYPE (IIB) ANY NON COMBUSTIBLE MATERIAL ALLOWED BY IBC- NON FIRE RATED.

MIXED USE APPROACH: UNSEPERATED MIXED OCCUPANCY: BUSINESS AND STORAGE

OCCUPANCY CLASSIFICATION: BUSINESS (SEARCH OFFICE)

FIRE DEPARTMENT ACCESS ROADS (NFPA 1 - SECTION 18.2.3) SHALL BE PROVIDED SUCH THAT ANY PORTION OF THE FACILITY OR ANYPORTION OF AN EXTERIOR WALL OF THE FIRST STORY OF THE BUILDING IS LOCATED NOT MORE THAN 150 FT FROM FIREDEPARTMENT ACCESS ROADS AS MEASURED BY AN APPROVED ROUTE AROUND THE EXTERIOR OF THE BUILDING OR FACILITY.

THE BUILDING WILL BE CLASSIFIED AS 1 STORY OF TYPE IIB CONSTRUCTION IN ACCORDANCE WITH IBC TABLE 503 AND SECTIONS504.2.

ITALIAN CODES AS NOTED

2018 NFPA 101 – LIFE SAFETY CODE

2018 INTERNATIONAL BUILDING CODE

UFC 3-600-01_FIRE PROTECTION ENGINEERING FOR FACILITIES_CHANGE 4 FEBRUARY 7 2020

UFC 1-200-01_GENERAL BUILDING REQUIREMENTS, CHANGE_2019-10/08

CODE AND STANDARD:

PLUMBING FIXTURE COUNT THE WATER CLOSET IN THE GATE HOUSE ARE AVAILBE FOR USE.

EMERGENCY LIGHTING NOT REQUIRED (NFPA 101 SECTION 38.2.9 AND 42.2.9).

EGRESS ILLUMINATION 1 FOOT-CANDLE ON NORMAL POWER THROUGHOUT (NFPA 101 SECTION 7.8.1.3 (2) AND 38.2.8 AND 42.2.8)

EXIT SIGNS NOT REQUIRED IN SPACES WHERE ONE EXIT PATH IS ALLOWED (NFPA 101 SECTION 7.10.1.2.1)

LIGHTS:

NUMBER OF EXITS 1 EXIT PERMITTED (NFPA 101 SECTION 38.2.4.2 AND 42.2.4.2 )

NUMBER OF EXITS FROM SPACES:

MINIMUM WIDTH DOOR: 32 IN (812 MM) CLEAR (NFPA 101 SECTION 7.2.1.3.2 (1))

DOORS 0.47 IN (12 MM) PER PERSON (D.M. 10 MARZO 1998)

EXIT WIDTHS:

COMMON PATH OF TRAVEL 50 FEET (15 M) IN ORDINARY HAZARD STORAGE OCCUPANCY (NFPA 101 SECTION 42.2.5)

TRAVEL DISTANCE 200 FEET (60 M) IN ORDINARY HAZARD STORAGE OCCUPANCY (NFPA 101 SECTION 42.2.6)

DEAD ENDS 50 FEET (15 M) IN ORDINARY HAZARD STORAGE OCCUPANCY (NFPA 101 SECTION 42.2.5)

COMMON PATH OF TRAVEL 75 FEET (22 M) IN BUSINESS OCCUPANCY (NFPA 101 SECTION 38.2.5.3.2)

TRAVEL DISTANCE 200 FEET (60 M) IN BUSINESS OCCUPANCY (NFPA 101 SECTION 38.2.6.2)

DEAD ENDS 20 FEET (6 M) IN BUSINESS OCCUPANCY (NFPA 101 SECTION 38.2.5.2.2)

TRAVEL DISTANCES: (NON-SPRINKLERED OCCUPANCY)

IN THE DIRECTION OF EGRESS NOT REQUIRED - NOT SERVING 50 OR MORE (NFPA 101 SECTION 7.2.1.4.2)

DOOR SWING:

PERMITTED EXIT DOOR HARDWARE LEVER HANDLES

DOOR HARDWARE:

MECHANICAL/STORAGE ROOMS 500 (46.5) (GROSS)

OFFICE AREAS 150 (14) (GROSS)

OCCUPANT LOAD FACTORS (NFPA 101 TABLE 7.3.1.2) FT2 PER PERSON (M2 PER PERSON)

EXITING:

DOOR 80 IN. (2032 MM) (NFPA 101 SECTION 7.2.1.2.1.1(6))

ROOMS: 90 IN. (2286 MM) (NFPA 101 SECTION 7.1.5.1)

MINIMUM CLEAR HEIGHT:

FIRE EXTINGUISHERS REQUIRED (NFPA 101 SECTION 38.3.5)

FIRE ALARM SYSTEM NOT REQUIRED. UFC 3-600-01 CH 9

COMM ROOM IS NOT INFORMATION TECHNOLOGY ROOM - NO SPRINKLERS REQUIRED (2020 NFPA 75 - CHAPTER 8).

AUTOMATIC SPRINKLER SYSTEM NOT REQUIRED FOR BUILDING OF TYPE IIB CONSTRUCTION UNDER 15,000 FT2 (1393 M2). (UFC 3-600-01 CH9)

ACTIVE FIRE PROTECTION:

FLOOR FINISH: DOC FF 1-70 "PILL TEST" (FEDERALLY MANDATED)

WALL AND CEILING FINISH (NFPA 101 CHAPTER 10): - CLASS A, B OR C:

INTERIOR FINISH

WALL PENETRATIONS F RATING EQUAL TO THE RATING IF THE WALL PENETRATED (IBC SECTION 714.3)

MECHANICAL ROOM: 1 HR FIRE BARRIER (NFPA 101 SECTION 38.3.2.1 AND 8.7)

FLOOR CONSTRUCTION 0-HOUR (IBC TABLE 601)

ROOF COVERING CLASS C (IBC TABLE 1505.4)

ROOF CONSTRUCTION 0-HOUR (IBC TABLE 601)

EXTERIOR NONBEARING WALLS 0-HOUR CONSTRUCTION (IBC TABLE 602)

EXTERIOR WALL 0-HOUR ;FIRE SEPARATION DISTANCE GREATER THAN 10 FEET (3048 MM). (IBC TABLE 602)

INTERIOR AND EXTERIOR BEARING WALLS 0-HOUR (IBC TABLE 601)

( PILASTRI, TRAVI E TRAVETTI CHE SI COLLEGANO AI PILASTRI, MURI PORTANTI E RINFORZIDIAGONALI, CARICHI PERMANENTI)

TELAIO STRUTTURALE 0 ORE (TABELLA 601 DELL'IBC)

FUOCO SIANO IDENTIFICATE CON SEGNALETICA O ADESIVI.IDENTIFICAZIONE DELLE PARETI ANTINCENDIO IL PARAGRAFO 703.7 DELL'IBC PRESCRIVE CHE LE PARETI RESISTENTI AL

AREA TOTALE EFFETTIVA DELL'EDIFICIO: 862 FT2 (80,1 M2) (3.740 M2) X 1 = (3.740 M2)

AREA TOTALE MASSIMA DELL'EDIFICIO: 40.259 FT2 X 1 = 40.259 FT

TOTALE 40,259 FT2 (3,740M2)

NESSUN AUMENTO PER SPRINKLER COMPLETO PER EDIFICI A UN PIANO 0

AUMENTO PER IL CORTILE APERTO INTORNO ALL'EDIFICIO 23,000 * (.75) FT2 ((2136 M2) * 0.75)) SUPERFICIE DI BASE CONSENTITA (PER PIANO) 23,000 FT2 (2136 M2)OCCUPAZIONE MISTA ( UFFICIO - NORMATIVA PIÙ RESTRITTIVA)

ALTEZZA ATTUALE / PIANI: 11 FT - 6 INCHES (3.5M) / 1 PIANOALTEZZA CONSENTITA / PIANI: 55 FT (16M) / 3 PIANI (TABELLA 503 E PARAGRAFO 504.2)

DALL'IBC - NON CLASSIFICATO AL FUOCO.TIPO DI STRUTTURA: TIPO (IIB) QUALUNQUE MATERIALE NON COMBUSTIBILE CONSENTITO DALL'IBC - NON...

UTILIZZO MISTO: OCCUPAZIONE MISTA NON SEPARATA: UFFICIO E MAGAZZINO

CATEGORIA D'OCCUPAZIONE: LAVORATIVA (CORPO DI GUARDIA E GUARDIOLA

LE STRADE DI ACCESSO PER I VIGILI DEL FUOCO (NFPA 1 - PARAGRAFO 18.2.3) DEVONO ESSERE PROGETTATE IN MODO TALE CHE QUALSIASI PARTE DELLA STRUTTURA O QUALSIASIPORZIONE DI UNA PARETE ESTERNA DEL PRIMO PIANO DELL'EDIFICIO SI TROVI A NON PIÙ DI 150 PIEDI DALLE STRADE DI ACCESSO DEI VIGILI DEL FUOCO, MISURATO DA UN PERCORSO APPROVATOINTORNO ALL'ESTERNO DELL'EDIFICIO O DELLA STRUTTURA.

L'EDIFICIO SARÀ CLASSIFICATO COME UNA COSTRUZIONE DI 1 PIANO DI TIPO IIB IN CONFORMITÀ CON LA TABELLA IBC 503 ED I PARAGRAFI 504.2.

REGOLAMENTI ITALIANI COME INDICATO2018 NFPA 101 - REGOLAMENTO SICUREZZA ANTINCENDIOREGOLAMENTO EDILIZIO INTERNAZIONALE 2018UFC 3-600-01_PROTEZIONE ANTINCENDIO PER LE STRUTTURE_MODIFICA 4 7 FEBBRAIO 2020UFC 1-200-01_REQUISITI GENERALI DI COSTRUZIONE, MODIFICA_2019-10/08REGOLAMENTI E NORMATIVE:

CALCOLO DEGLI APPARECCHI SANITARI I WC NEL CORPO DI GUARDIA SONO DISPONIBILI ALL' USO.

LUCE D'EMERGENZA NON RICHIESTO (NFPA 101 PARAGRAFO 38.2.9 E 42.2.9).

ILLUMINAZIONE DELL'USCITA 10 LUMEN/MQ PER TUTTO L'AMBIENTE SU POTENZA NORMALE (NFPA 101 PARAGRAFO7.8.1.3 (2) E 38.2.8 E 42.2.8)

SEGNALETICA DI USCITA NON RICHIESTO NEGLI SPAZI IN CUI È CONSENTITO UN SOLO PERCORSO DI USCITA (NFPA101 PARAGRAFO 7.10.1.2.1)

ILLUMINAZIONE:

NUMERO DI USCITE E' CONSENTITA UNA SOLA USCITA (NFPA 101 PARAGRAFO 38.2.4.2 E 42.2.4.2 )

NUMERO DI USCITE DAI LOCALI:

LARGHEZZA MINIMA PORTA: 32 IN (812 MM) SPAZIO LIBERO (NFPA 101 SEZIONE 7.2.1.3.2 (1))PORTE 0,47 IN (12 MM) A PERSONA (D.M. 10 MARZO 1998)

LARGHEZZA DELLE USCITE:

PERCORSO COMUNE 50 PIEDI (15M) NEI MAGAZZINI DI STOCCAGGIO A RISCHIO ORDINARIO (NFPA 101...DISTANZA DI PERCORRENZA 200 PIEDI (60M) NEI MAGAZZINI DI STOCCAGGIO A RISCHIO ORDINARIO (NFPA 101...CORRIDOIO CIECO 50 PIEDI (15M) NEI MAGAZZINI DI STOCCAGGIO A RISCHIO ORDINARIO (NFPA 101...PERCORSO COMUNE 75 PIEDI (22M) NEGLI UFFICI (NFPA 101 SECTION 38.2.5.3.2)DISTANZA DI PERCORRENZA 200 PIEDI (60M) NEGLI UFFICI (NFPA 101 PARAGRAFO 38.2.6.2)CORRIDOIO CIECO 20 PIEDI (6M) NEGLI UFFICI (NFPA 101 PARAGRAFO 38.2.5.2.2)DISTANZE DI PERCORRENZA: (AREE SENZA SPRINKLER)

NELLA DIREZIONE DI USCITA NON RICHIESTO - GLI OCCUPANTI NON SONO PIU' DI 50(NFPA 101 PARAGRAFO 7.2.1.4.2)VERSO DI APERTURA DELLE PORTE:

NELLA DIREZIONE DI USCITA MANIGLIE A LEVAFERAMENTA PER LE PORTE:

CENTRALI TERMICHE/MAGAZZINI 500 (46.5) LORDE

UFFICI 150 (14) LORDEINDICI DI DENSITA' AFFOLLAMENTO (NFPA 101 TABELLA 7.3.1.2) FT2 PER PERSONA (M2 PER PERSONA)

USCITE:

80 IN. (2032 MM) (NFPA 101 PARAGRAFO 7.2.1.2.1.1(6)PORTE 90 IN. (2286 MM) (NFPA 101 PARAGRAFO 7.1.5.1)STANZE:ALTEZZA LIBERA MINIMA:

ESTINTORI RICHIESTI (NFPA 101 SEZIONE 38.3.5)

IMPIANTO DI ALLARME ANTINCENDIO NON RICHIESTO. UFC 3-600-01 CH 9

LA SALA DI COMUNICAZIONE NON È UNA SALA INFORMATICA - NON SONO RICHIESTI SPRINKLER (2020 NFPA 75 - CAPITOLO 8).

IMPIANTO SPRINKLER AUTOMATICO NON RICHIESTO PER EDIFICI DI TIPO IIB AL DI SOTTO DEI 15.000 FT2 (1393 M2). (UFC3-600-01 CH9)

PROTEZIONE ANTINCENDIO ATTIVA:

FINITURA DEL PAVIMENTO: DOC FF 1-70 "PILL TEST" (SECONDO ILREGOLAMENTO FEDERALE)

FINITURA DI PARETI E SOFFITTI (NFPA 101 CAPITOLO 10): - CLASSE A, B O C:FINITURA INTERNA

ATTRAVERSAMENTI DI PARETI RESISTENZA AL FUOCO UGUALE ALLA RESISTENZA DEL MURO ATTRAVERSATO ( IBCPARAGRAFO 714.3).

CENTRALE TERMICA BARRIERA ANTINCENDIO 1 HR (NFPA 101 PARAGRAFO 38.3.2.1 E 8.7)

STRUTTURA DEL PAVIMENTO 0 ORE (TABELLA 601 DELL'IBC

COPERTURA DEL TETTO CLASSE C (TABELLA IBC 1505.4

STRUTTURA DELLA COPERTURA 0 ORE (TABELLA 601 DELL'IBC

MURI ESTERNI NON PORTANTI RESISTENZA AL FUOCO DELLA STRUTTURA - 0 ORE (TABELLA 602 DELL'IBC)

MURO ESTERNO 0 ORE ;DISTANZA DI SEPARAZIONE ANTINCENDIO MAGGIORE DI 10 PIEDI (3048 MM).(TABELLA IBC 602)

MURI PORTANTI INTERNI ED ESTERNI 0 ORE (TABELLA 601 DELL'IBC)

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

SEARCH OFFICE101

COMM ROOM102

MECH/ELEC103

DOORPORTA

81367

101A

UFFICIO CONTROLLI

COMUNICAZIONE

CENTRALE TERMICA/ELETTRICA

A CLEAR DOOR WIDTH [mm]

B OCCUPANT LOAD CAPACITY [NO.OF PEOPLE]

EXIT DOOR TAG

LIFE SAFETY NOTES:

1. FOR EXIT LIGHTS AND EMERGENCY LIGHTING, SEE ELECTRICAL LIGHTING DRAWINGS (E SERIES).

LIFE SAFETY SYMBOLS:

EXIT DISCHARGE ARROW

EXIT DISCHARGE

WALL RATING LEGEND

1 HOUR FIRE BARRIER

A LARGHEZZA LIBERA DELLA PORTA (mm)

B DENSITA'' DI AFFOLLAMENTO (N° DI PERSONE)

TARGHETTA DELLA PORTA D'USCITA

1. PER LE LUCI DI USCITA E L'ILLUMINAZIONE DI EMERGENZA, VEDERE I DISEGNI DELL'ILLUMINAZIONE ELETTRICA (SERIE E).

USCITA

NOTE SULLA SICUREZZA ANTINCENDIO:

SIMBOLOGIA SICUREZZA ANTINCENDIO:

FRECCIA DI USCITA

LEGENDA CLASSIFICAZIONE ANTINCENDIO DELLE PARETI

DBARRIERA ANTINCENDIO DI 1 ORA

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/7

/20

21 8

:53

:33

AM

BIM

360

://1

02

24

522

_N

AV

FA

C_

A1_

De

sig

n_A

via

no

_Ita

ly_20

18

/102

24

522

-A-S

ea

rch_v20

18

.rvt

FC101

LIF

E S

AF

ET

Y P

LAN

-S

EA

RC

H O

FF

ICE

-PL

ANIM

ETRI

A SI

CURE

ZZA

ANTI

NCEN

DIO

-UF

FICI

O CO

NTRO

LLI

Checker

154

14090157

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 50B3

GROUND FLOOR LIFE SAFETY PLAN/ PIANODI SICUREZZA DI VITA DEL PIANO TERRA

GENERAL NOTES

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

KEY PLAN / PIANTA CHIAVE

SEARCH

SCALA: 1:50

PIANO NORD

SCALA GRAFICA

NOTE GENERALE

MEANS OF EGRESS WIDTH CAPACITY

EXIT ID

PROVIDED EGRESS CAPACITY - LEVELCOMPONENTS & RAMPS

EGRESSCAPACITY

FACTOR (mm)CLEAR

WIDTH (mm)

OCCUPANTLOAD

CAPACITY

101A 12 813 67

LARGHEZZA DELLE VIE D'USCITA

SIGLAD'USCITA

CAPACITÀ DI USCITA PREVISTA - ELEMENTI DILIVELLO E RAMPE

CAPACITA' DIDEFLUSSO

LARGHEZZALIBERA (mm)

DENSITA' DIAFFOLLAMENTO

101A 12 813 67

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

REF

FD

FD

REF

FD

FD

FD-01

FD-02

FD-02

L-01

WC-01MS-01

1 2

A

MECH/ELEC

107

BREAK

106

COMM

105

JANITOR

104

TOILET

102PASSAGE

103

COMMAND & CONTROL

101

EWH-01

50ø

S-1

50ø

I.E. = (-1.002 METERS) BELOW FINISHED FLOOR

QUOTA DI FONDO= (-1.002 METRI) AL DI SOTTO DEL PAVIMENTO FINITO

DOUBLE GRADE CLEANOUT

DOPPIO POZZETTO D'ISPEZIONE

SEE CIVIL FOR COORDINATION CONNECTION POINT: 1.5 METERS OUTSIDE OF BUILDING

VEDERE IL CIVILE PER IL COORDINAMENTO DEL PUNTO DI CONNESSIONE: A 1,5 METRI FUORI DALL'EDIFICIO

100mm VTR

100mm VTR SFIATO DAL TETTO

1 2

A

FD-01

FD-02

FD-02

L-01 WC-01

MS-01

BFP-01MECH/ELEC

107

BREAK

106

COMM

105

JANITOR

104

TOILET

102PASSAGE

103

COMMAND & CONTROL

101

54ø

54ø

14ø

28ø

EWH-01

SEE CIVIL FOR CONTINUATIONCONNECTION POINT: 1.5 METERS OUTSIDEOF BUILDING.

C.L. = -2.000 METERSBELOW FINISHED FLOOR.

WH-01

MS-01

VEDERE IL CIVILE PER LA CONTINUAZIONEPUNTO DI CONNESSIONE: 1,5 METRI FUORI DALL'EDIFICIO.

QUOTA DI FONDO= (-2.000 METRI) AL DI SOTTO DEL PAVIMENTO FINITO

S-01

14ø

WATER METERCONTATORE DELL'ACQUA

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK,

VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SSIF

IED

AVIA

NO

AIR

BAS

EAV

IAN

O, I

TALY

AREA

A1

ENTR

Y C

ON

TRO

L PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

21-

Apr

-21

BIM

360

://1

022

4522

_NA

VF

AC

_A1_

Des

ign_

Avi

ano_

Italy

_201

8/1

0224

522-

ME

P-G

ate

hous

e_v2

018

.rvt

PB101

PLU

MB

ING

FLO

OR

PLA

N -

PIAN

TE IM

PIAN

TO ID

RAUL

ICO

JAL

155

14090158

CER CER

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LAN

TIC

DE

SIG

N A

ND

CO

NS

TR

UC

TIO

N

RICHARD STEPHENS, PESEK

1 : 50

PLUMBING PLAN (SANITARY)1 : 50

PLUMBING PLAN (WATER)

GATEHOUSE

PLANNORTH

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

PIANTA IMPIANTO IDRAULICO (SCARICO) PIANTA IMPIANTO IDRAULICO (IDRICO)

SYM

DES

CR

IPTI

ON

DAT

EAP

PR

KEY PLAN - PIANTA CHIAVE

ALLA FONGNATURA.

CAST IRON PIPE (TYP)TUBO IN GHISA (TIPO)

CONCRETE PAD.PIASTRA DI CLS.

GRADE.TERRENO.

DOUBLE CLEANOUT FITTING.RACCORDO PER ISPEZIONE DOPPIO.

EXTEND CLEANOUT TO FINISH GRADE.ESTENDERE IL POZZETTO FINO AL TERRENO FINITO.

45° TO

60°

45°

TO

60°

DALLO SCARICO DELL'EDIFICIO.

TO SANITARY SEWER. FROM BUILDING DRAIN.

NOTES:

1. CLEANOUTS SHALL BE RECESSED 15 mm BELOW FINISHED SURFACE. COVER SHALL BE ACCESSIBLE FOR GENERAL MAINTENANCE.

1. I POZZETTI D'ISPEZIONE DEVONO ESSERE INCASSATI 15 mm AL DI SOTTO SUPERFICIE FINITA. IL COPERCHIO DEVE ESSERE ACCESSIBILE PER MANUTENZIONE GENERALE.

CLEANOUT, SEE SPECIFICATIONPOZZETTO D'ISPEZIONE - VEDERE SPECIFICA

FINISHED FLOORPAVIMENTO FINITO

CLEANOUT BRANCHTUBAZIONE DEL POZZETTO D'ISPEZIONE

SERVICE 'Y' (LATERAL)RACCORDO A "Y"(LATERALE)

SOIL OR WASTE PIPETUBO DI SCARICO45

°

DE

PT

H V

AR

IES

MIN. 100 mm DEEP SEAL P-TRAPSIFONE A TENUTA DA MIN. 100mm

FLOOR DRAINSCARICO A PAVIMENTO

PR

OF

ON

DIT

A'

VA

RIA

BIL

E

FLOOR.PAVIMENTO.

MOP SINK.GETTATOIO.

TEMPERATURE AND PRESSURERELIEF VALVE.VALVOLA DI SISFIATO PER TEMPERATURA E PRESSIONE.

THERMOMETER.TERMOMETRO.

HW.ACQUA CALDA.

EXPANSION TANKVASO D'ESPANSIONE.

FLEXIBLE UNION (TYP.)SEE SPECIFICATION 23 05 48.19COLLEGAMENTO FLESSIBILE (TIPO)VEDERE LA SPECIFICA 23 05 48.19

HEAT TRAP.SIFONE TERMICO.

CW.ACQUA FREDDA.

HW. ACQUA CALDA.

ELEC WATER HEATER.SCALDA ACQUA ELETTRICO.

MOUNT ON SHELF W/ SUPPORT BRACKETS. SEE SPECIFICATION 23 05 48.19 FOR BRACING DESIGN INFORMATION.MONTAGGIO SU SCAFFALE CON STAFFE DI SUPPORTO. VEDERE LA SPECIFICA 23 05 48.19 PER INFORMAZIONI SULLA PROGETTAZIONE DEI DISPOSITIVI DI SOSTEGNO.

EXPANSION TANK: SHELL: STEEL, DIAPHRAGM: HEAVY DUTY BUTYL NSF/ANSI 61, LINER: ANTIMICROBIAL POLYPROPYLENETANK VOLUME: 7.57 L., MAX. ACCEPTANCE FACTOR: .45, TANK DIAMETER: 203 mm, TANK HEIGHT: 330 mm, SYSTEM CONNECTION: 20 mm.

VASO DI ESPANSIONE: GUSCIO: ACCIAIO, DIAFRAMMA: BUTILE ROBUSTO NSF/ANSI 61,FODERA: POLIPROPILENE ANTIMICROBICOVOLUME DEL SERBATOIO: 7,57 L., MAX. FATTORE DI ACCETTAZIONE: .45, DIAMETRO DEL SERBATOIO: 203 mm, ALTEZZA DEL SERBATOIO: 330 mm, COLLEGAMENTO DELL'IMPIANTO: 20 mm

BALL VALVE NORMALLY (CLOSED) INSTALL LOCK ON VALVE OPERATORVALVOLA A SFERA NORMALMENTE (CHIUSA) INSTALLARE BLOCCO SULLA MANOPOLA DELLA VALVOLA

PRESSURE GAGEMANOMETRO

PRESSURE REDUCING VALVE (SET @ 448 kPa)VALVOLA DI RIDUZIONE DELLA PRESSIONE (IMPOSTATA A 448 kPa)

REDUCED PRESSURE BACKFLOW PREVENTERDISPOSITIVO ANTIRIFLUSSO A PRESSIONE RIDOTTA

M

GAUGE COCKRUBINETTO DEL MANOMETRO

FLOWFLUSSO

SHUT-OFF VALVE (TYP.)VALVOLA DI ARRESTO (TIPO)

NOTES: 1. BY-PASS SIZE SHALL BE ONE PIPE SIZE SMALLER THAN SERVICE SIZE.2. BY-PASS MUST BE INSTALLED TO ALLOW MIN. 457.2 mm CLEAR SPACING AROUND METER.

1. LA DIMENSIONE DEL BY-PASS SARÀ DI UNA DIMENSIONE DI TUBO PIÙ PICCOLA DELLA DIMENSIONE DELL'IMPIANTO.2. IL BY-PASS DEVE ESSERE INSTALLATO IN MODO DA CONSENTIRE UNO SPAZIO MINIMO DI 457,2 MM INTORNO AL CONTATORE.

INSTALL METER PER MANUFACTURERS RECOMMENDATIONSINSTALLARE IL CONTATORE SECONDO LE ISTRUZIONI DEL FABBRICANTE

3.18

mm

3.18

mm

A. THIS DETAIL IS FOR NONFIRE-RATED CONSTRUCTION. PIPE PENETRATIONS IN FIRE-RATED CONSTRUCTION SHALL BE FIRESTOPPED WITH A UL-CLASSIFIED SYSTEM. QUESTO DETTAGLIO È PER COSTRUZIONI NON CLASSIFICATE ANTINCENDIO. LE PENETRAZIONI DI TUBI IN COSTRUZIONI CLASSIFICATE ANTINCENDIO DEVONO ESSERE PROTETTE DAL FUOCO CON UN SISTEMA CLASSIFICATO UL.

B. AT INSULATED WALLS PROVIDE PACKING AND SEALANT AT ANNULAR SPACE. NELLE PARETI COIBENTATE FORNIRE GUARNIZIONI E SIGILLANTI NELLO SPAZIO ANULARE.

NOTES:

ESCUTCHEON (WHERE EXPOSED)ROSETTA (DOVE ESPOSTA)

PIPETUBO

NOTE B (TYP)NOTA B (TIPO)

SLEEVEMANICOTTO

WALL OR FLOORPARETE O PAVIMENTO

INSULATION (WHERE REQUIRED)ISOLANTE (DOVE RICHIESTO)

SEALANT WITH JOINT BACKINGSIGILLANTE PER GIUNTO CON SUPPORTO

PACKINGRIEMPIMENTO

ALUMINUM JACKETSCOCCA IN ALLUMINIO

NON-SHRINK GROUT ORMORTAR, OR SEALANTSTUCCO, MALTA O SIGILLANTE ANTIRITIRO

PIPE SLEEVEMANICOTTO PER IL PASSAGGIO DEL TUBO

LC

PERFORATED OR SOLID PIPETUBO PERFORATO O PIENO

CAST IN PLACE CONCRETECALCESTRUZZO GETTATO IN OPERA

PROVIDE NON-SWELLING GROUT TO FILL ANNULAR SPACEFORNIRE UNA MALTA ANTI RIGONFIAMENTO PER RIEMPIRE LO SPAZIO ANULARE

75 mm OR 100 mm SLEEVEMANICOTTO DA 75 mm O 100 mm

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK,

VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SSIF

IED

AVIA

NO

AIR

BAS

EAV

IAN

O, I

TALY

AREA

A1

ENTR

Y C

ON

TRO

L PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

21-

Apr

-21

BIM

360

://1

022

4522

_NA

VF

AC

_A1_

Des

ign_

Avi

ano_

Italy

_201

8/1

0224

522-

ME

P-G

ate

hous

e_v2

018

.rvt

PB501

PLU

MB

ING

DE

TA

ILS

-DE

TTAG

LI ID

RAUL

ICI

JAL

156

14090159

CER CER

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LAN

TIC

DE

SIG

N A

ND

CO

NS

TR

UC

TIO

N

RICHARD STEPHENS, PESEK

NOT TO SCALENON IN SCALA

1DOUBLE GRADE CLEANOUT DETAIL

NOT TO SCALENON IN SCALA

2FLOOR CLEANOUT DETAIL

NOT TO SCALENON IN SCALA

3TRAPPED FLOOR DRAIN DETAIL

NOT TO SCALENON IN SCALA

4WATER HEATER PIPING CONNECTION DETAIL.

NOT TO SCALENON IN SCALA

7WATER SERVICE ENTRANCE DETAIL

NOT TO SCALENON IN SCALA

5PIPE PENETRATION DETAIL

NOT TO SCALENON IN SCALA

6PIPE SLEEVE THROUGH FLOOR

NOT TO SCALENON IN SCALA

8TYPICAL PIPE SLEEVE THRU PRECAST PANEL

DETTAGLIO SCARICO A PAVIMENTO SIFONATO DETTAGLIO POZZETTO D'ISPEZIONE DETTAGLIO POZZETTO

D'ISPEZIONE DOPPIO IN TERRA

DETTAGLIO DEL COLLEGAMENTO DELLE

TUBAZIONI ALLO SCALDA ACQUA ELETTRICO.

MANICOTTO PER TUBO

ATTRAVERSO IL PAVIMENTO

DETTAGLIO DELL'ATTRAVERSAMENTO DEI TUBI

MANICOTTO TIPO PER TUBO ATTRAVERSO

PENNELLO PREFABBRICATODETTAGLIO INGRESSO IMPIANTO IDRICO

SYM

DES

CR

IPTI

ON

DAT

EAP

PR

HW & CW TO SINK, S-1ACQUA CALDA E ACQUA FREDDA AL LAVANDINO.

EWH-01

22mm HW & 22mm CW TO MOP SINK15mm HW & 15mm CW TO LAVATORY22 mm ACQUA CALDA e 22 mm ACQUA FREDDA VERSO IL GETTATOIO15mm ACQUA CALDA & 15mm ACQUA FREDDA AL LAVABO

MS-01

L-01

WC-01

28ø

14ø54ø

BFP-01MOUNT AT +915 MM A.F.F.MONTARE A +915 MM DAL PAVIMENTO FINITO

54ø

SEE CIVIL FOR CONTINUATION.VEDERE I DISEGNI CIVILI PER LA CONTINUAZIONE.

NOTE:1. MOUNT WATER HEATER EWH-01 ON A SHELF AS HIGH

AS POSSIBLE BELOW THE CEILING.

NOTA:1. MONTARE LO SCALDABAGNO EWH-01 SU UNA

MENSOLA, IL PIÙ IN ALTO POSSIBILE SOTTO IL SOFFITTO.

22ø

WH-01MOUNT AT +610 MM ABOVE GRADEMONTARE A +610 MM DAL PAVIMENTO

14ø

22ø22ø

54ø

28ø

22ø22ø

100mmVTRSFIATO DAL TETTO

50ø

50ø

DOUBLE GRADECLEANOUT

50mm FD-02

50ø

50ø

50ø

50mm FD-02

50mm FD-01

WC-01

L-01

MS-01

50ø

50ø

50ø

50ø

50ø

50ø

50ø

S-01

SEE CIVIL FOR CONTINUATIONVEDERE I DISEGNI CIVILI PER LA CONTINUAZIONE

50ø

50ø

50ø

50ø

100mmVTRSFIATO DAL TETTO

100ø

100ø

50ø

50ø

50ø75

PLUMBING FIXTURES SHALL BE OF ONE OF THE MANUFACTURERS INDICATED AND IN ACCORDANCE WITH THE INFORMATION AND MANUFACTURERS CATALOG NUMBERS INDICATED. IF MANUFACTURES CATALOG NUMBERS HAVE BEEN UPDATED OR DELETED, FIXTURES SHALL BE ONE OF SIMILAR CONFIGURATION AND OF SIMILAR OR BETTER QUALITY THAN WHAT IS SPECIFIED.

VERIFY THE MOUNTING HEIGHT OF THE PLUMBING FIXTURES PRIOR TO ORDERING THE FIXTURES. MOUNTING HEIGHTS SHALL BE AS INDICATED ON ARCHITECTURAL DRAWINGS/PLUMBING FIXTURE SCHEDULES AND COMPLY WITH ADA REQUIREMENTS.

VERIFY COLOR OF FIXTURES WITH ARCHITECT PRIOR TO ORDERING.

COUNTER TOP SINKS: CONTRACTOR SHALL COORDINATE SIZE OF CABINET(S) AND SINK(S) PRIOR TO ODERING FIXTURE(S).

ALL FIXTURE STOPS SHALL BE LOOSE KEY.

ADA WATER CLOSETS: FLUSH CONTROLS SHALL BE MOUNTED ON THE WIDE SIDE OF THE WATER CLOSET STALL AND AT A HEIGHT THAT COMPLIES WITH ADA GUIDELINES.

I DISPOSITIVI IDRAULICI DEVONO ESSERE DI UNO DEI PRODUTTORI INDICATI E IN CONFORMITÀ CON LE INFORMAZIONIED I NUMERI DI CATALOGO DEI PRODUTTORI INDICATI. SE I NUMERI DI CATALOGO DEI PRODUTTORI SONO STATI AGGIORNATI O CANCELLATI, GLI IMPIANTI DEVONO ESSERE SIMILI E DI QUALITÀ SIMILI O MIGLIORI DI QUELLO CHE È SPECIFICATO.

VERIFICARE L'ALTEZZA DI MONTAGGIO DEGLI APPARECCHI IDRAULICI PRIMA DI ORDINARE GLI APPARECCHI. LE ALTEZZE DI MONTAGGIO DEVONO ESSERE COME INDICATO SUI DISEGNI ARCHITETTONICI/TABELLE DELLE ATTREZZATURE IDRAULICHE E RISPETTARE I REQUISITI DELL'ADA.

VERIFICARE IL COLORE DEGLI APPARECCHI SANITARI INSIEME ALL'ARCHITETTO PRIMA DI EFFETTUARE L'ORDINE.

LAVABI DA TOP: L'APPALTATORE COORDINERÀ LE DIMENSIONI DEL/I MOBILE/I E DEL/I LAVABO/I PRIMA DI ORDINARE L'/GLI APPARECCHIO/I.

TUTTE LE CHIUSURE DEI RUBINETTI DEVONO ESSERE A CHIAVE ESTRAIBILE.

WC ADA: I COMANDI DELLO SCIACQUONE DEVONO ESSERE MONTATI SUL LATO LARGO DELLA CABINA DEL WATER CLOSET E AD UN'ALTEZZA CONFORME ALLE LINEE GUIDA DELL'ADA.

GENERAL NOTES FOR PLUMBING FIXTURE SCHEDULESNOTE GENERALI PER GLI SCHEMI IMPIANTO IDRAULICO

FD-01FLOORDRAIN

SCARICO A PAVIMENTO

DRAIN: CAST IRON FLOOR DRAIN BODY WITH ANCHOR FLANGE, REVERSIBLE CLAMPING COLLAR, SEEPAGE OPENINGS, 14mm PRIMER TAP WITH PLUG, AND ADJUSTABLE 125 ROUND SATIN FINISH NICKEL BRONZE TOP. INCLUDE INTERNAL TRAP SEAL DEVICE.

SCARICO: CORPO DI SCARICO A PAVIMENTO IN GHISA CON FLANGIA DI ANCORAGGIO, COLLARE DI SERRAGGIO REVERSIBILE, APERTURE DI DRENAGGIO, SIFONE da 14 mm CON TAPPO, E COPERCHIOREGOLABILE DA 125 ROTONDO IN BRONZO NICHELATO SATINATO. INCLUDERE IL SIFONE A TENUTA STAGNA. INCLUDERE IL SIFONE A TENUTA STAGNA.

----

REMARKS/ OSSERVAZIONI:

HW/ACQUACALDA

CW/ACQUA FREDDA

VENT/VENT

WASTE/SCARICO

DRAIN: CAST IRON FLOOR DRAIN BODY WITH ANCHORFLANGE, INTEGRAL CLAMPING COLLAR, SEEPAGEOPENINGS, 14mm PRIMER TAP WITH PLUG, GRATESUPPORTED BUCKET, AND 305 ROUND DUCTILE IRONHEAVY DUTY GRATE. INCLUDE INTERNAL TRAP SEAL DEVICE.

SCARICO: CORPO DI SCARICO A PAVIMENTO IN GHISA CON FLANGIA DI ANCORAGGIO, COLLARE DI SERRAGGIO REVERSIBILE, APERTURE DI DRENAGGIO, SIFONE da 14 mm CON TAPPO, GRATA SUPPORTATA DA CESTELLO, E GRATA ROBUSTA DA 305 ROTONDA IN GHISA SFEROIDALE

FD-02FLOORDRAIN

SCARICO A PAVIMENTO

----

REMARKS/ OSSERVAZIONI:

HW/ACQUACALDA

CW/ACQUA FREDDA

VENT/VENT

WASTE/SCARICO

MS-01MOP SINK

GETTATOIO

INCLUDE MOP HANGER BRACKET, HOSE BRACKET COMBO, AND WALL GUARDS.

INCLUDERE LA STAFFA COMBINATA PER IL MOCIO E PER IL TUBO E LE PROTEZIONI PER IL MURO.

ONE PIECE PRECAST TERRAZZO MOP SERVICE BASIN WITH FACTORY INSTALLED DRAIN WITH COMBINATION DOME STRAINER AND LINT BASKET FOR 75mm CAULK JOINT. STAINLESS STEEL CAPS ON CURBS. CAULK ALL EDGES WHERE BASIN MEETS WALL WITH COLOR MATCHED SILICONE SEALANT. SIZE: 609mm X 609mm X 304mm

FAUCET: EXPOSED WALL MOUNT-MOUNT UTILITY FAUCET WITH CAST BRASS BODY AND INTEGRAL SUPPLY STOPS. CAST BRASS SPOUT WITH BUCKET HOOK, TOP BRACE, VANDAL RESISTANT METAL LEVER HANDLES, VACUUM BREAKER, AND 1/4 TURN WASHERLESS CERAMIC DISC VALVE CARTRIDGES. CHROME PLATED FINISH

VASCA GETTATOIO IN GRANIGLIA, PREFABBRICATO IN UN UNICO PEZZO, CON SCARICO INSTALLATO IN FABBRICA CON FILTRO A CUPOLA E FILTRO ANTI LANUGGINE DA 75mm CON RACCORDO SILICONATO. PROTEZIONI IN ACCIAIO INOX SU BORDI. SILICONARE TUTTI I BORDI DOVE LA VASCA INCONTRA IL MURO CON SIGILLANTE SILICONICO DI COLORE ABBINATO.DIMENSIONI: 609mm X 609mm X 304mm

RUBINETTO: RUBINETTO DI SERVIZIO A PARETE A VISTA.RUBINETTO CON CORPO IN OTTONE FUSO E MANOPOLE D'ARRESTO INTEGRATE. EROGATORE IN OTTONE FUSO CON GANCIO PER SECCHIO, BRACCIO DI SOSTEGNO SUPERIORE, MANIGLIE A LEVA IN METALLO RESISTENTE AGLI ATTI VANDALICI, VALVOLA ROMPIVUOTO E CARTUCCE PER VALVOLE A DISCO IN CERAMICA SENZA RONDELLA 1/4 GIRO.FINITURA CROMATA

22mm22mm50 mm75 mm

REMARKS/ OSSERVAZIONI:

HW/ACQUACALDA

CW/ACQUA FREDDA

VENT/VENT

WASTE/SCARICO

FIXTURE: SINGLE BOWL, SELF-RIMMING, COUNTER MOUNTED, 18 GAUGE TYPE 304 (18-8) STAINLESSSTEEL WITH FAUCET LEDGE, SOUND DEADENINGUNDERCOATING, PUNCHED TO MATCH FAUCET.DRAIN: CRUMB CUP STRAINER.OVERALL DIMENSIONS 559mm x 495mm x 195mm DEEP.

FAUCET: BELOW DECK MOUNTED SINK FAUCET WITH 200mm FIXED CENTERS, CHROME PLATED FINISH. RESTRICTED SWING GOOSENECK SPOUT, 200mm CENTER-TO-CENTER. 100mm BLADE HANDLES WITH COLORINDEX BUTTONS. CERAMIC 1/4 TURN CARTRIDGE, 14mmSUPPLY INLETS AND COUPLING NUT. 5.6 L/M AERATOR.

APPARECCHIO: VASCA SINGOLA, AUTOLIVELLANTE, DA INCASSO NEL TOP, IN ACCIAIO INOSSIDABILE 18 GAUGE TIPO 304 (18-8)CON BORDO PER IL RUBINETTO, RIVESTIMENTO ANTIRUMORE,CON FORO PER IL RUBINETTO.SCARICO: CON FILTRODIMENSIONI COMPLESSIVE: 559 mm x 495 mm x 195 mm DI PROFONDITA'

RUBINETTO: RUBINETTO PER LAVELLO SOTTOPIANO CONFORI FISSI da 200mm, FINITURA CROMATA.EROGATORE GIREVOLE A COLLO D'OCA, INTERASSE 200mmMANIGLIE A LEVA da 100mm CON COLORE INDICATORE ACQUA CALDA E FREDDA. CARTUCCIA CERAMICA 1/4 di giro, INGRESSI DI ALIMENTAZIONE E DADO DI ACCOPPIAMENTO DA 14mm. AERATORE DA 5,6 L/M.

S-01SINK

LAVANDINO

REMARKS/ OSSERVAZIONI:

HW/ACQUACALDA

CW/ACQUA FREDDA

VENT/VENT

WASTE/SCARICO

14mm14mm50mm50mm

15 mm15 mm50 mm50 mm

REMARKS/ OSSERVAZIONI:

L-01LAVATORY

LAVABO

FIXTURE: WALL HUNG VITREOUS CHINA LAVATORY WITH FRONT OVERFLOW, SELF-DRAINING DECK AREA WITH BACK AND SIDE SPLASH SHIELDS AND FAUCET LEDGE. MOUNT AT ADA HEIGHT.OVERALL DIMENSIONS: 514mm x 464mm x 158mm

FAUCET: SINGLE LEVER, DECK MOUNTED WITH 100mm FIXED CENTERS, RIGID CAST BRASS SPOUT, 118mm CENTER-TO-CENTER, CHROME PLATED.1.9 L/M NON-AERATING SPRAY.

APPARECCHIO: LAVABO SOSPESO IN PORCELLANA VETROSA CON TROPPOPIENO ANTERIORE, BORDO AUTODRENANTE CON PARASPRUZZI POSTERIORI E LATERALI E BORDO DIETRO AL RUBINETTO.MONTARE AD ALTEZZA CONFORME ALLA NORMATIVA ADA.DIMENSIONI COMPLESSIVE: 514mm x 464mm x 158mm

RUBINETTO: MONOBLOCCO, MONTATO SUL BORDO CON FORI FISSI DA 100mm, EROGATORE FISSO IN OTTONE FUSO, INTERASSE 118mm, CROMATO.GETTO NON AERATO DA 1,9 L/M.

HW/ACQUACALDA

CW/ACQUA FREDDA

VENT/VENT

WASTE/SCARICO

HW/ACQUACALDA

-28mm

CW/ACQUA FREDDA

VENT/VENT

50mm

WASTE/SCARICO

100mm

REMARKS/ OSSERVAZIONI:

WC-01WATERCLOSET

FIXTURE: ADA COMPLIANT, FLOOR SET, VITREOUS CHINA, SIPHON JET WATER CLOSET WITH ELONGATED BOWL, 38mm TOP SPUD, 54mm TRAPWAY, AND BOLT CAPS. COLOR: WHITE. 6 LITERS PER FLUSH.

FLUSH VALVE: EXPOSED, DIAPHRAGM TYPE, CHROME PLATED WITH DUAL FILTERED BY-PASS, SPUD COUPLING AND FLANGE FOR 38mm TOP SPUD, ADA COMPLIANT METAL OSCILLATING HANDLE, ADJUSTABLE TAILPIECE, VACUUM BREAKER FLUSH CONNECTION, AND 25mm IPS SCREWDRIVER BAK-CHEK ANGLE STOP. 6 LITERS PER FLUSH.

SEAT: MOLDED PLASTIC, ELONGATED, SELF SUSTAINING CHECK HINGES, OPEN FRONT WITHOUT COVER. COLOR: WHITE.

APPARECCHIO: CONFORME NORMATIVA ADA, MONTAGGIO A PAVIMENTO, PORCELLANA VETROSA, RISCIACQUO A GETTO POTENTE CON VASO ALLUNGATO, MANICOTTO ACQUA DI SCARICO DA 38 mm, SIFONE DA 54 mm E TAPPI COPRI-BULLONE.COLORE: BIANCO. 6 LITRI A SCARICO.

VALVOLA DI RISCIACQUO: A VISTA, A MEMBRANA, CROMATA CON DOPPIO BY-PASS FILTRATO, RECCORDO E FLANGIA PER SCARICO 38 mm, MANIGLIA OSCILLANTE IN METALLO CONFORME ALLA NORMATIVA ADA, MANICOTTO REGOLABILE,CONNESSIONE DELLO SCIACQUONE CON VALVOLA ROMPIVUOTO, E VALVOLA D'ANGOLO DA 25mm TIPO: IPS SCREWDRIVER BAK-CHEK. 6 LITRI A SCARICO.

SEDILE COPRIVASO: PLASTICA MODELLATA, ALLUNGATO, CON CHIUSURA AMMORTIZZATA, FRONTE APERTO SENZA COPERCHIO. COLORE: BIANCO.

WH-01WALL HYDRANT

IDRANTE A PARETE

AUTOMATIC DRAINING, FREEZELESS WALL HYDRANT WITH HOSE CONNECTION BACKFLOW PROTECTION.HYDRANT WILL DRAIN AS HANDLE IS SHUT-OFF, EVEN IF HOSE IS ATTACHED.20 mm MALE HOSE THREAD, TWO INDEPENDENT CHECK VALVES.HARDENED STAINLESS STEEL OPERATING STEM AND ONE-PIECE VALVE PLUNGER TO CONTROL BOTH FLOW AND DRAIN FUNCTIONS.FINISH: CHROME PLATED.PROVIDE LOOSE TEE KEY.

IDRANTE A MURO ANTIGELO, A SVUOTAMENTO AUTOMATICO, CON PROTEZIONE ANTIRIFLUSSO PER IL COLLEGAMENTO DEL TUBO.L'IDRANTE SI SVUOTA QUANDO LA MANIGLIA VIENE CHIUSA, ANCHE SE ANCHE SE IL TUBO È ATTACCATO.FILETTATURA MASCHIO 20 mm, DUE VALVOLE DI CONTROLLO INDIPENDENTI. STELO OPERATIVO IN ACCIAIO INOSSIDABILE TEMPRATO E PISTONE DELLA VALVOLA IN UN UNICO PEZZO PER CONTROLLARE SIA IL FLUSSO SIA LA FUNZIONE DI SCARICO.FINITURA: CROMATO.FORNIRE UNA CHIAVE A T SCIOLTA.

----

REMARKS/ OSSERVAZIONI:

HW/ACQUACALDA

CW/ACQUA FREDDA

VENT/VENT

WASTE/SCARICO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK,

VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SSIF

IED

AVIA

NO

AIR

BAS

EAV

IAN

O, I

TALY

AREA

A1

ENTR

Y C

ON

TRO

L PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

21-

Apr

-21

BIM

360

://1

022

4522

_NA

VF

AC

_A1_

Des

ign_

Avi

ano_

Italy

_201

8/1

0224

522-

ME

P-G

ate

hous

e_v2

018

.rvt

PB601

PLU

MB

ING

SC

HE

DU

LES

/ SC

HEM

I IMPI

ANTO

IDRA

ULIC

O

JAL

157

14090160

CER CER

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LAN

TIC

DE

SIG

N A

ND

CO

NS

TR

UC

TIO

N

RICHARD STEPHENS, PESEK

NOT TO SCALENON IN SCALA

1WATER RISER

NOT TO SCALENON IN SCALA

2SAN RISER

WATER METERCONTATORE DELL'ACQUA

MONTANTI DELL'ACQUA

MONTANTI DI SCARICO

SYM

DES

CR

IPTI

ON

DAT

EAP

PR

2. ENERGY EFFICIENCIES MUST BE MET. DEVONO ESSERE RISPETTATE LE NORME DI EFFICIENZA ENERGETICA.

1. ENSURE WATER TEMPERATURE DELIVERED TO FIXTURE IS SET AT 44°C. ASSICURARSI CHE LA TEMPERATURA DELL'ACQUA EROGATAALL'APPARECCHIO SIA IMPOSTATA A 44°C.

NOTES:

EWH-01TANK /

SERBATOIO 115 2 46 2.84 3 1 230 1 1, 2

(°C) (°C) (L/M)KW STAGES VOLT PH

MARK /SIGLA

TYPESTORAGECAP. (L)

E.W.T. L.W.T. RECOVERY ELECTRICAL DATA / DATI ELETTRICI

NOTES

ELECTRIC WATER HEATER / RISCALDATORE D'ACQUA ELETTRICO

4. PROVIDE UNITS WITH SUPPLY AND DISCHARGE SHUTOFF VALVES. FORNIRE UNITÀ CON VALVOLE DI INTERCETTAZIONE DI ALIMENTAZIONE E DI SCARICO.3. PROVIDE WITH INTEGRAL STRAINER. FORNIRE UN FILTRO INCORPORATO.

2. UNIT SHALL COMPLY WITH LEAD-FREE INSTALLATION REQUIREMENTS. 'UNITÀ DEVE ESSERE CONFORME AI REQUISITI DI INSTALLAZIONE SENZA PIOMBO.

1. UNIT SHALL HAVE A FACTORY FURNISHED AND UNIT MOUNTED AIR GAP FITTING FOR DRAIN/BLOWOFF. L'UNITÀ AVRÀ UN RACCORDO PER IL DRENAGGIO/SPURGODELL'ARIA FORNITO DAL FABBRICANTE E MONTATO SULL'UNITÀ.

NOTES:

BFP-01 54 RPZWALL BRACKET /

STAFFA A PARETE

POTABLEWATER / ACQUA

POTABILE144 82.74

HORIZONTAL /ORIZZONTALE 1, 2, 3, 4

MARK /SIGLA

SERIES SIZE /DIMENSIONI

(MM)TYPE / TIPOLOGIA

MOUNTING /MONTAGGIO

SERVICE /UTENZA

DESIGN FLOW /FLUSSO DI

PROGETTO...

MAX PRESSURELOSS / PERDITA DI

PRESSIONE MAX.(kPA)

ORIENTATION /ORIENTAMENTO

NOTES

BACKFLOW PREVENTER SCHEDULE / TABELLA VALVOLA ANTIRIFLUSSO

SIMBOLOGIA HVAC

24x18

18

18x24

CANALE DI MANDATA ARIA O ARIA ESTERNA VERSO L'ALTO (SEZIONE , PRIMA DIMENSIONE LARGHEZZA DEL CANALE)

CANALE DI RITORNO ARIA VERSO L'ALTO (SEZIONE)

CANALE DI MANDATA ARIA O ARIA ESTERNA VERSO IL BASSO (NON SEZIONATO)

CANALE DI RITORNO ARIA VERSO IL BASSO (NON SEZIONATO)

TRANSIZIONE - CANALE RETTANGOLARE A CIRCOLARE

DIRAMAZIONE STANDARD

CANALE RETTANGOLARE O APERTURA, LA DIMENSIONE DEL PRIMO NUMERO INDICA LA DIMENSIONE DEL LATO MOSTRATO

INCLINAZIONE DEL CANALE RETTANGOLARE -ASCESA O CADUTA RISPETTO AL FLUSSO D'ARIA

DIMENSIONE CANALE CIRCOLARE

INCLINAZIONE DEL CANALE CIRCOLARE -ASCESA O CADUTA RISPETTO AL FLUSSO D'ARIA

SERRANDA DI TARATURA

GOMITO CURVO - (RETTANGOLARE)

GOMITO AD ANGOLO RETTO - CON DIRETTRICI (RETTANGOLARE)

CANALE DI ESPULSIONE ARIA VERSO L'ALTO (NON SEZIONATO)

CANALE DI ESPULSIONE ARIA VERSO IL BASSO (NON SEZIONATO)

GOMITO CIRCOLARE VERSO L'ALTO

GOMITO CIRCOLARE VERSO IL BASSO

SERRANDA TAGLIAFUOCO

SERRANDA TAGLIAFUMO

SERRANDA TAGLIAFUOCO E TAGLIAFUMO

SERRANDA MOTORIZZATA

M

ETICHETTA DI ELEVAZIONE DEL CANALE/TUBO SOPRA IL PAVIMENTO FINITO

18x10

CANALE NASCOSTO18x24

T 9'-10"B 9'-0"

GIUNTO FLESSIBILE

CANALE FLESSIBILE - DUE LINEE

UC

TAG-SIZECFM

TAGLIO SOTTO LA PORTA

BOCCHETTA ARIA DI MANDATA

GRIGLIA ARIA DI RITORNO O DI ESPULSIONE

GRIGLIA ARIA DI RITORNO O DI ESPULSIONE

GRUPPO ARIA DI MANDATA-DIFFUSORE QUADRATO

GRUPPO ARIA DI MANDATA-DIFFUSORE CIRCOLARE

ISOLAMENTO ACUSTICO - DIMENSIONI DEL CANALE PER L'AREA LIBERA NETTA

CANALE FLESSIBILE - UNA LINEA

GIUNTO

RIDUTTORE CONCENTRICO

RIDUTTORE ECCENTRICO, PARTE INFERIORE DRITTA

GOMITO A 90°, GIRATO IN GIU'

GOMITO A 90°, GIRATO IN SURACCORDO A T, USCITA IN ALTORACCORDO A T, USCITA IN BASSORACCORDO A T, USCITA IN ALTO CON GOMITO A 90°RACCORDO A T, USCITA IN BASSO CON GOMITO A 90°

INTERRUZIONE TUBO

LINEA CON TAPPO

FLANGIA CIECA

DIREZIONE DI FLUSSO

VALVOLA DI SCARICO

VALVOLA DI RITEGNO

VALVOLA DI EQUILIBRATURA MANUALE CALIBRATA

VALVOLA RIDUTTRICE DI PRESSIONE

VALVOLA DI REGOLAZIONE AUTOMATICA A DUE VIE

VALVOLA DI REGOLAZIONE AUTOMATICA A TRE VIE

VALVOLA DI CONTROLLO DEL FLUSSO AUTOMATICA

VALVOLA DI NON RITORNO

VALVOLA DI SFOGO DELLA PRESSIONE

PT

T

A

SIMBOLOGIA DI TUBAZIONI

ANCORAGGIO PER TUBO

GUIDA PER TUBO

GIUNTO DI ESPANSIONE

TEST PORT PRESSIONE/ TEMPERATURA

TERMOMETRO

MANOMETRO

INDICATORE DELLA TEMPERATURA

COLLEGAMENTO FLESSIBILE TUBAZIONI

RACCORDO A Y

VALVOLA DI SFIATO MANUALE

POZZETTO TERMOMETRICO

VALVOLA DI SFIATO AUTOMATICA

VALVOLA D'ARRESTO (NORMALMENTE APERTA)

CONTATORE (ACQUA,GAS,ALTRO)

POZZETTO D'ISPEZIONE A PAVIMENTO

POZZETTO D'ISPEZIONE DOPPIO IN TERRA

M

FCO

GCO

IMPIANTI DI TUBAZIONI

ACQUA FREDDA, POTABILE

ACQUA CALDA, POTABILE

ACQUA CALDA, POTABILE DI RICIRCOLO

ACQUA FREDDA, NON POTABILE

FOGNATURA SOTTO IL LIVELLO DEL TERRENO

FOGNATURA SOPRA IL LIVELLO DEL TERRENO

SFIATO FOGNATURA

SCARICO DELLE ACQUE PIOVANE SOPRA IL LIVELLO DEL TERRENO

SCARICO DELLE ACQUE PIOVANE SOTTO IL LIVELLO DEL TERRENO

SFIORO DELLE ACQUE PIOVANE

DRENAGGIO A PRESSIONE

ARIA COMPRESSA

GAS NATURALE

MANDATA ACQUA REFRIGERATA

RITORNO ACQUA REFRIGERATA

MANDATA ACQUA CALDA RISCALDAMENTO

RITORNO ACQUA CALDA RISCALDAMENTO

MANDATA DELL'ACQUA DEL CONDENSATORE

RITORNO DELL'ACQUA DEL CONDENSATORE

SCARICA DI CONDENSA

MANDATA VAPORE

SCARICO POMPA DI CONDENSA

SCARICO DELLA CALDAIA

ACQUA ALIMENTAZIONE CALDAIA

SFIATO DEL VAPORE

ACQUA CALDA, POTABILE TEMPERATURA

RIFIUTI ACIDI

VENTILAZIONE ACIDI

SCARICO E SFIATO COMBINATI

GAS PETROLIO LIQUEFATTO

RITORNO DI ACQUA CALDA RISCALDAMENTO A GLICOLE

MANDATA DI ACQUA CALDA RISCALDAMENTO A GLICOLE

LIQUIDO REFRIGERANTE

ASPIRAZIONE REFRIGERANTE

ACQUA DI REINTEGRO

SFIATO ROMPIVUOTOVB

AMMORTIZZATORE DEL COLPO DI ARIETE

VALVOLA SISMICAE

TAG-SIZECFM

TAGCFM

TAGCFM

TAGCFM

HWS

HWR

GHWS

GHWR

CHWS

CHWR

CWS

CWR

RL

RS

CD

STM -15

CPD

BBD

BF

SV

MU

CA

LP

NG

OD

SD

SD

PD

CWV

AV

AW

V

SAN

SAN

POZZETTO D'ISPEZIONE

POZZETTO D'ISPEZIONE A PARETE

BFP

ACQUA TIEPIDA, POTABILE

RITORNO ACQUA TIEPIDA, POTABILE

TWR

TW

CO

WCO

RIDUTTORE ECCENTRICO, PARTE SUPERIORE DRITTA

CONNESSIONE NUOVA A QUELLA ESISTENTE

RIMUOVERE L'ESISTENTE FINO A QUESTO PUNTO

INTERRUTTORE ARRESTO DI EMERGENZA HVAC

140

NPW

APPARECCHIO IDRAULICO

XX-1

S

SRITORNO DI ACQUA REFRIGERATA CON GLICOLE

MANDATA DI ACQUA REFRIGERATA CON GLICOLE

GCWS

GCWR

VALVOLA D'ARRESTO (NORMALMENTE CHIUSA)

R OR D

R OR D

OR

HVAC SYMBOLOGY

24x18

18

18x24

SUPPLY AIR OR OUTSIDE AIRDUCT UP (SECTION CUT,FIRST DIMENSION DUCT WIDTH)

RETURN AIR DUCT UP(SECTION CUT)

SUPPLY AIR OR OUTSIDE AIRDUCT DOWN (NO SECTION CUT)

RETURN AIR DUCT DOWN (NOSECTION CUT)

TRANSITION -RECTANGULAR TO ROUND DUCT

STANDARD BRANCH

RECTANGULAR DUCT OR OPENING SIZE FIRST NUMBER INDICATES SIZE OFSIDE SHOWN

RECTANGULAR DUCT INCLINE - RISE OR DROP IN RESPECT TO THE AIR FLOW

ROUND DUCT SIZE

ROUND DUCT INCLINE - RISE OR DROP IN RESPECT TO THE AIR FLOW

VOLUME DAMPER

ELBOW - (RECTANGULAR), SMOOTH RADIUS

ELBOW - W/TURNING VANE(RECTANGULAR)

EXHAUST AIR DUCT UP (NOSECTION CUT)

EXHAUST AIR DUCT DOWN(NO SECTION CUT)

ROUND ELBOW UP

ROUND ELBOW DOWN

FIRE DAMPER

SMOKE DAMPER

SMOKE AND FIRE DAMPER

MOTOR OPERATED DAMPER

M

DUCT/PIPE ELEVATION TAG ABOVE FINISH FLOOR

18x10

HIDDEN DUCT18x24

T 9'-10"B 9'-0"

FLEXIBLE CONNECTION

FLEXIBLE DUCT - TWO LINE

UC

TAG-SIZECFM

UNDERCUT DOOR

SUPPLY AIR REGISTER

EXHAUST AIR OR RETURN AIR GRILLE

EXHAUST AIR OR RETURN AIR GRILLE

SUPPLY AIR ASSEMBLYSQUARE DIFFUSER

SUPPLY AIR ASSEMBLYROUND DIFFUSER

ACOUSTICAL LINING - DUCT DIMENSIONS FOR NET FREE AREA

FLEXIBLE DUCT - ONE LINE

UNION

CONCENTRIC REDUCER

ECCENTRIC REDUCER, FLAT ON BOTTOM

ELBOW, 90° TURN DOWN

ELBOW, 90° TURN UP

TEE, OUTLET UP

TEE, OUTLET DOWN

TEE, OUTLET UP W/ 90° TURNTEE, OUTLET DOWN W/ 90° TURN

PIPE BREAK

PIPE CAP

BLIND FLANGE

FLOW ARROW

DRAIN VALVE

CHECK VALVE

CALIBRATED MANUAL BALANCING VALVE

PRESSURE-REDUCING VALVE (PRV)

AUTOMATIC CONTROL VALVE, 2-WAY

AUTOMATIC CONTROL VALVE, 3-WAY

AUTOMATIC FLOW CONTROL VALVE

BACKFLOW PREVENTER

PRESSURE-RELIEF VALVE

PT

T

A

PIPING SYMBOLOGY

PIPE ANCHOR

PIPE GUIDE

EXPANSION JOINT

PRESSURE/TEMPERATURE PORT

THERMOMETER

PRESSURE GAUGE

TEMPERATURE GAUGE

FLEXIBLE PIPING CONNECTION

WYE STRAINER

MANUAL AIR VENT

THERMOWELL

AUTOMATIC AIR VENT

SHUTOFF VALVE(NORMALLY OPEN)

METER (WATER, GAS, OTHER)

FLOOR CLEANOUT

DOUBLE GRADE CLEANOUT

M

FCO

GCO

PIPING SYSTEMS

COLD WATER, POTABLE (CW)

HOT WATER, POTABLE (HW)

HOT WATER RECIRCULATING,POTABLE (HWC)

NON POTABLE COLD WATER

SANITARY SEWER BELOW GRADE

SANITARY SEWER ABOVE GRADE

SANITARY VENT

STORM DRAIN ABOVE GRADE

STORM DRAIN BELOW GRADE

STORM DRAIN OVERFLOW

PRESSURE DRAINAGE

COMPRESSED AIR

NATURAL GAS

CHILLED WATER SUPPLY

CHILLED WATER RETURN

HEATING HOT WATER SUPPLY

HEATING HOT WATER RETURN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

CONDENSATE DRAIN

STEAM SUPPLY - PSI

CONDENSATE PUMPDISCHARGE

BOILER BLOW DOWN

BOILER FEED

STEAM VENT

HOT WATER -TEMPERATURE, POTABLE

ACID WASTE

ACID VENT

COMBINATION WASTE AND VENT

LIQUEFIED PROPANE

GLYCOL HEATING HOTWATER RETURN

GLYCOL HEATING HOTWATER SUPPLY

REFRIGERANT LIQUID

REFRIGERANT SUCTION

MAKE-UP WATER

VACUUM BREAKERVB

WATER HAMMER ARRESTOR

EARTHQUAKE VALVEE

TAG-SIZECFM

TAGCFM

TAGCFM

TAGCFM

HWS

HWR

GHWS

GHWR

CHWS

CHWR

CWS

CWR

RL

RS

CD

STM -15

CPD

BBD

BF

SV

MU

CA

LP

NG

OD

SD

SD

PD

CWV

AV

AW

V

SAN

SAN

CLEANOUT

WALL CLEANOUT

BFP

TEPID WATER, POTABLE

TEPID WATER RETURN, POTABLE

TWR

TW

CO

WCO

ECCENTRIC REDUCER, FLAT ON TOP

NEW TO EXISTING CONNECTION

REMOVE EXISTING UP TO THIS POINT

HVAC EMERGENCY SHUTDOWN SWITCH

140

NPW

PLUMBING FIXTUREXX-1

S

S

GLYCOL CHILLEDWATER RETURN

GLYCOL CHILLEDWATER SUPPLY

GCWS

GCWR

SHUTOFF VALVE(NORMALLY CLOSED)

R OR D

R OR D

OR

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 6

:34

:17

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

M-001

ME

CH

AN

ICA

L LE

GE

ND

-LE

GEND

A M

ECCA

NICO

JAL

158

14090161

GTH GTH

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

TEMPERATURE CONTROL DIAGRAM SYMBOLOGY ABBREVIATIONS

T

M

X

X

XX

XX

COIL IDENTIFIERSCC CHILLED WATER COOLING COILDG DIRECT FIRED GAS BURNERDX DIRECT EXPANSION COOLING COILEH ELECTRIC HEATING COILER DIRECT EVAPORATIVE COILFC FACE AND BYPASS COOLING COILFH FACE AND BYPASS HEATING COILHC HEATING HOT WATER HEATING COILIG INDIRECT FIRED GAS BURNERST STEAM HEATING COIL

FILTER

BACKDRAFT DAMPER

FAN

MOTOR OPERATED DAMPER

DUCT MOUNTED SMOKE DETECTOR

TEMPERATUREAVERAGING SENSOR

INTAKE/EXHAUST LOUVER

PUMPM MOTOR OPERATED

SINGLE BLADE DAMPER

HUMIDIFIER

AFS

AIRFLOW MEASURING STATION

PUMP WITH EC MOTOREC

M

CONTROL DEVICE IDENTIFIERAFS AIRFLOW MEASURING STATIONAM AIRFLOW MEASURING SENSORCO CARBON MONOXIDE SENSORCO2 CARBON DIOXIDE SENSORF FLOW SWITCHFRZ FREEZE STATH HUMIDITY SENSORHS HIGH STATIC SWITCHLS LOW STATIC SWITCHNO2 NITROGEN DIOXIDE SENSORP PRESSURE SENSORS SPACE TEMPERATURE SENSORSD SMOKE DETECTORT TEMPERATURE SENSORTS TEMPERATURE SWITCHΔP DIFFERENTIAL PRESSURE SENSOR

CONTROL ABBREVIATIONSBTU BTU METERCOMM COMMUNICATIONCT CURRENT TRANSMITTEREC ELECTRONICALLY COMMUTATEDEF EXHAUST FANFM FLOW METERM MOTOR ACTUATORMA MIXED AIRNC NORMALLY CLOSEDNO NORMALLY OPENOA OUTDOOR AIRRA RETURN AIRRL RELIEF FANRF RETURN FANSA SUPPLY AIRSF SUPPLY FANTCC TEMPERATURE CONTROL CONTRACTORVFC VARIABLE FREQUENCY CONTROLLER

XXFAN WITH EC MOTOREC

FRZ

FREEZE STAT

MISCELLANEOUS DEVICE IDENTIFIERCO SPACE CARBON MONOXIDE SENSORCO2 SPACE CARBON DIOXIDE SENSORH SPACE HUMIDITY SENSORNO2 SPACE NITROGEN DIOXIDE SENSORS SPACE TEMPERATURE SENSORT THERMOSTAT

X

X

SEE CONTROL ABBREVIATIONS (TYP)

CONTROL INPUT/OUTPUT IDENTIFIERAI ANALOG INPUTAO ANALOG OUTPUTDI DIGITAL INPUTDO DIGITAL OUTPUT

XX

GENERAL NOTES

S

SIMBOLOGIA DEL DIAGRAMMA DI CONTROLLO DELLA TEMPERATURA

ABBREVIAZIONI

T

M

X

X

XX

XX

DENTIFICATORI DI BATTERIECC BATTERIA DI RAFFREDDAMENTO AD

ACQUA REFRIGERATADG BRUCIATORE A GAS A FUOCO DIRETTODX BATTERIA DI RAFFREDDAMENTO AD

ESPANSIONE DIRETTAEH BATTERIA DI RISCALDAMENTO

ELETTRICAER BATTERIA EVAPORATIVA DIRETTAFC BATTERIA DI RAFFREDDAMENTO

FRONTALE E DI BYPASSFH BATTERIA DI RISCALDAMENTO

FRONTALE E DI BYPASSHC BATTERIA DI RISCALDAMENTO AD

ACQUA CALDAIG BRUCIATORE A GAS INDIRETTOST BATTERIA DI RISCALDAMENTO A

VAPORE

FILTRO

SERRANDA DI SOVRAPRESSIONE

VENTILATORE

SERRANDA MOTORIZZATA

RILEVATORE DI FUMO MONTATO NEL CONDOTTO

SENSORE DI TEMPERATURA MEDIA

GRIGLIA DI ASPIRAZIONE E DI ESPULSIONE

POMPAM

SERRANDA MOTORIZZATA A LAMA SINGOLA

UMIDIFICATORE

AFS

STAZIONE DI MISURAZIONE DEL FLUSSO D'ARIA

POMPA CON MOTORE ECEC

M

IDENTIFICATORE DEI DISPOSITIVI DI CONTROLLOAFS STAZIONE DI MISURAZIONE DEL FLUSSO D'ARIAAM SENSORE DI MISURAZIONE DEL FLUSSO D'ARIACO SENSORE DI MONOSSIDO DI CARBONIOCO2 SENSORE DI ANIDRIDE CARBONICAF INTERRUTTORE DI FLUSSOFRZ FREEZE STATH SENSORE DI UMIDITÀHS INTERRUTTORE STATICO ALTOLS INTERRUTTORE STATICO BASSONO2 SENSORE DI BIOSSIDO DI AZOTOP SENSORE DI PRESSIONES SENSORE DI TEMPERATURA DELL'AMBIENTESD RILEVATORE DI FUMOT SENSORE DI TEMPERATURATS INTERRUTTORE DI TEMPERATURAΔP SENSORE DI PRESSIONE DIFFERENZIALE

SIGLE DI CONTROLLOBTU MISURATORE DI BTUCOMM COMUNICAZIONECT TRASMETTITORE DI CORRENTEEC COMMUTATA ELETTRONICAMENTEEF VENTILATORE DI ESPULSIONEFM MISURATORE DI PORTATAM ATTUATORE MOTOREMA ARIA MISCELATANC NORMALMENTE CHIUSONO NORMALMENTE APERTOOA ARIA ESTERNARA ARIA DI RITORNORL VENTILATORE DI SCARICORF VENTILATORE DI RITORNOSA ARIA DI MANDATASF VENTILATORE DI MANDATATCC SENSORE DELLA TEMPERATURAVFC CONTROLLORE DI FREQUENZA

VARIABILE

XX VENTILATORE CON MOTORE EC

EC

FRZ

FREEZE STAT

MISCELLANEOUS DEVICE IDENTIFIERCO SENSORE DI MONOSSIDO DI CARBONIO

NELL'AMBIENTECO2 SENSORE DI ANIDRIDE CARBONICA

NELL'AMBIENTEH SENSORE DI UMIDITÀ DELL'AMBIENTENO2 SENSORE DI BIOSSIDO DI AZOTO

NELL'AMBIENTES SENSORE DI TEMPERATURA DELL'AMBIENTET TERMOSTATO

X

X

VEDI SIGLE DI CONTROLLO (TIPO)

IDENTIFICATORE DI INGRESSO/USCITA DI CONTROLLOAI INGRESSO ANALOGICOAO USCITA ANALOGICADI INGRESSO DIGITALEDO USCITA DIGITALE

XX

NOTE GENERALI

S

AD PORTA DI ACCESSOAFR SOPRA IL TETTO FINITOAHU UNITÀ DI TRATTAMENTO ARIAAPD PERDITA DI PRESSIONE DELL'ARIAARF SOPRA IL PAVIMENTO SOPRAELEVATOAV SOPRA IL PAVIMENTO SOPRAELEVATOBAS SISTEMA DI AUTOMAZIONE

DELL'EDIFICIOBDD SERRANDA DI SOVRAPRESSIONEBHP POTENZA AL FRENOBOE FONDO DELL'ATTREZZATURABTUH UNITÀ TERMICHE BRITANNICHE PER

ORACAV VOLUME D'ARIA COSTANTECOP COEFFICIENTE DI PRESTAZIONECOR RAPPRESENTANTE DELL'UFFICIALE

CONTRAENTECRAC CONDIZIONATORE D'ARIA PER SALA

COMPUTERCU UNITÀ DI CONDENSAZIONEDB BULBO SECCODDC CONTROLLO DIGITALE DIRETTODH DEUMIDIFICATOREDX ESPANSIONE DIRETTAEAT TEMPERATURA DELL'ARIA IN ENTRATAEDH RISCALDATORE ELETTRICO DEL

CONDOTTOEER RAPPORTO DI EFFICIENZA ENERGETICAEMCS IMPIANTO DI CONTROLLO DELLA

GESTIONE DELL'ENERGIAERU UNITÀ DI RECUPERO DI ENERGIAESP PRESSIONE STATICA ESTERNAESS INTERRUTTORE DI EMERGENZAEWT TEMPERATURA DELL'ACQUA IN ENTRATAF FUTUROFA AREA LIBERAFCP PANNELLO DI CONTROLLO DEL

VENTILATOREFCU UNITÀ VENTILCONVETTOREFDBK FEEDBACKFLA AMPERE A PIENO CARICOFLT FILTROFPB UNITA' ALIMENTATA DA VENTOLAGC APPALTATORE GENERALEGE ESPULSIONE A GRAVITÀGI ASPIRAZIONE A GRAVITÀI/O INGRESSO/USCITAI/P DA CORRENTE A PNEUMATICOIAQ QUALITÀ DELL'ARIA INTERNAIPLV VALORE DI CARICO PARZIALE

INTEGRATOL/h LITRI PER ORA

L/M LITRI AL MINUTOL/s LITRI PER SECONDOLAT TEMPERATURA DELL'ARIA IN USCITALVR LOUVERLWT TEMPERATURA DELL'ACQUA IN

USCITAm/s METRI AL SECONDOMBH MIGLIAIA DI BTUHMCC CENTRO DI CONTROLLO DEL

MOTORENC CRITERI DI RUMOROSITÀNO NUMERONRC COEFFICIENTE DI RIDUZIONE DEL

RUMOREOS&Y VITE ESTERNA PD CADUTA DI PRESSIONERH UMIDITÀ RELATIVARTU UNITÀ SUL TETTOS PORTA DEL SEGNALESCFM PIEDI CUBICI STANDARD AL MINUTOSEER RAPPORTO DI EFFICIENZA

ENERGETICA STAGIONALESP PRESSIONE STATICATC ASSISTENZA TECNICA

SPECIALIZZATATCP PANNELLO DI CONTROLLO DELLA

TEMPERATURATD DIFFERENZIALE DI TEMPERATURATES ACCUMULO DI ENERGIA TERMICATSP PRESSIONE STATICA TOTALEUH UNITÀ DI RISCALDAMENTOV&C VALVOLA E TAPPOVAV VOLUME D'ARIA VARIABILEVRF FLUSSO DI REFRIGERANTE

VARIABILEVTR SFIATO ATTRAVERSO IL TETTOWB BULBO BAGNATOWC COLONNA D'ACQUAWPD CADUTA DI PRESSIONE DELL'ACQUA

NOTE GENERALI MECCANICO

1. QUESTE NOTE NON SONO ESAUSTIVE. FARE RIFERIMENTO AI DISEGNI E ALLE SPECIFICHE PER ULTERIORI PRESCRIZIONI.

2. QUESTO E' UN FOGLIO STANDARD DI SIMBOLOGIA E ABBREVIAZIONI MECCANICHE (HVAC E IDRAULICA). L'ELENCO DEI SIMBOLI E DELLE ABBREVIAZIONI NON IMPLICA CHE TUTTI I SIMBOLI E LE ABBREVIAZIONI SIANO STATI UTILIZZATI IN QUESTO PROGETTO.

3. I SIMBOLI DELLE VALVOLE QUI RIPORTATI SONO RIFERITI SOLO ALLE TAVOLE MECCANICHE.4. FORNIRE TUTTI I MATERIALI, LA MANODOPERA E LE ATTREZZATURE PER IMPIANTI COMPLETI E

FUNZIONANTI COME INDICATO NEI DISEGNI, COME SPECIFICATO, O COME RICHIESTO DALLA NORMATIVA.

5. GLI IMPIANTI MECCANICI DEVONO ESSERE CONFORMI ALLE LINEE GUIDA DI ACCESSIBILITÀ DELL'ADA/ABA.

6. I DETTAGLI SI RIFERISCONO ALL'INTERO PROGETTO E SONO RIPORTATI SOLO PER FORNIRE CHIAREZZA SE CI SONO PIÙ DETTAGLI CHE POTREBBERO INTERESSARE UNA PARTICOLARE CARATTERISTICA DEL PROGETTO.

7. COORDINARE LA POSIZIONE DI TUTTE LE ATTREZZATURE MECCANICHE, LE CONDUTTURE E LE TUBAZIONI CON GLI ALTRI FORNITORI PRIMA DI PROCEDERE CON IL LAVORO. NON INSTALLARE LE APPARECCHIATURE MECCANICHE, LE CONDUTTURE O LE TUBAZIONI SOPRA LE APPARECCHIATURE ELETTRICHE DOVE È PROIBITO DALLA NORMATIVA ELETTRICA (QUADRI ELETTRICI, PANNELLI, ECC.).

8. LA LINEA LEGGERA INDICA LE TUBAZIONI, LE CONDUTTURE E/O LE ATTREZZATURE ESISTENTI CHE DEVONO RIMANERE. LA LINEA IN GRASSETTO INDICA UN NUOVO LAVORO DA INSTALLARE COME PARTE DI QUESTO CONTRATTO.

9. COORDINARE L'INSTALLAZIONE DELLE PRESE D'ARIA ESTERNA CON L'INSTALLAZIONE DEGLI SFIATI IDRAULICI, DELLE CANNE FUMARIE E DELLE USCITE DI ESPULSIONE/SFIATO IN MODO DA MANTENERE UNA DISTANZA DI 10'.

10. TUTTI I LAVORI NEGLI SPAZI FINITI DEVONO ESSERE COLLOCATI SOPRA I SOFFITTI, IN VANI O IN ALTRI LUOGHI ACCESSIBILI NASCOSTI, A MENO CHE NON SIA INDICATO DIVERSAMENTE. LOCALIZZARE E DISPORRE LE VALVOLE, I RACCORDI DI SCARICO, ECC. IN MODO DA ESSERE ACCESSIBILI ATTRAVERSO CONTROSOFFITTI, PANNELLI DI ACCESSO O PORTE DI ACCESSO. FORNIRE UN PANNELLO O UNA PORTA DI ACCESSO PER TUTTE LE INSTALLAZIONI NON ACCESSIBILI. COORDINARE LA POSIZIONE DEI PANNELLI O DELLE PORTE DI ACCESSO CON L'ARCHITETTO/INGEGNERE E GLI ALTRI OPERATORI.

11. TUTTI I MATERIALI COLLOCATI NEI PLENUM DEVONO ESSERE CLASSIFICATI PER L'INSTALLAZIONE NEI PLENUM.

12. TUTTE LE CONDUTTURE, LE TUBATURE E LE ATTREZZATURE SOSTENUTE DALL'ACCIAIO STRUTTURALE DEVONO ESSERE COORDINATE CON TUTTI I FORNITORI. TUTTI GLI ATTACCHI ALLE TRAVI A TRALICCIO IN ACCIAIO, ALLE CAPRIATE O ALLE TRAVI DI SOSTEGNO SARANNO EFFETTUATI NEI PUNTI DEI PANNELLI O COME INDICATO NEI DISEGNI MECCANICI O STRUTTURALI. NON È CONSENTITA LA SALDATURA AI COMPONENTI STRUTTURALI.

13. TUTTI I METALLI E I MATERIALI VARI NECESSARI PER GARANTIRE UNA CORRETTA INSTALLAZIONE E COME INDICATO NEI DETTAGLI PER LE TUBAZIONI, LE CONDUTTURE E LE ATTREZZATURE (SE NON DIVERSAMENTE INDICATO) DEVONO ESSERE FORNITI DAL FORNITORE DELL'INSTALLAZIONE.

14. PREVEDERE GIUNZIONI DIELETTRICHE IN TUTTE LE CONNESSIONI DI METALLI DIVERSI (COME IL RAME CON L'ACCIAIO ZINCATO).

15. FORNIRE VALVOLE DI ARRESTO IN CORRISPONDENZA DI OGNI APPARECCHIATURA. FORNIRE ANCHE VALVOLE DI ARRESTO SU OGNI DIRAMAZIONE E/O COLONNA MONTANTE CHE SERVE PIÙ APPARECCHIATURE O IMPIANTI E IN OGNI ALTRO PUNTO COME INDICATO. INSTALLARE LE VALVOLE IL PIÙ VICINO POSSIBILE ALLA LINEA PRINCIPALE.

NOTE GENERALI HVAC

1. DIMENSIONI DEI CANALI: IL PRIMO NUMERO INDICA IL LATO DELLA CONDUTTURA MOSTRATO. TUTTE LE DIMENSIONI SONO IN POLLICI E SONO DIMENSIONI INTERNE LIBERE.

2. LE SERRANDE DI TARATURA SOPRA I SOFFITTI IN GESSO O IN CARTONGESSO DEVONO AVERE ASTE DI PROLUNGA E PLACCHETTE CROMATE.

3. COORDINARE TUTTE LE POSIZIONI DI GRIGLIE, BOCCHETTE E DIFFUSORI CON LA PIANTA RIFLESSA DEL SOFFITTO, L'ILLUMINAZIONE E TUTTI GLI ALTRI DISPOSITIVI MONTATI SUL SOFFITTO.

4. FORNIRE COLLEGAMENTI FLESSIBILI IN TUTTE LE CANALIZZAZIONI E I SISTEMI DI TUBAZIONI COLLEGATI A VENTILATORI, POMPE E ALTRE APPARECCHIATURE CHE RICHIEDONO UN ISOLAMENTO DALLE VIBRAZIONI.

5. FORNIRE SERRANDE DI TARATURA ACCESSIBILI O ALTRI MEZZI DI REGOLAZIONE DEL FLUSSO D'ARIA IN TUTTE LE USCITE DEI CANALI VERSO I DIFFUSORI E LE GRIGLIE.

6. FORNIRE PORTE DI ACCESSO AI CANALI IN CORRISPONDENZA DEI PLENUM DI ASPIRAZIONE DELL'ARIA ESTERNA.

7. TUTTE LE USCITE DEI CANALI VERSO I DIFFUSORI E LE GRIGLIE DEVONO ESSERE UGUALI ALLE DIMENSIONI DEL COLLARE DEL DIFFUSORE O DELLA GRIGLIA, SALVO DIVERSA INDICAZIONE.

8. TUTTE LE USCITE DEI TUBI DEVONO ESSERE DI 20 mm, A MENO CHE NON SIA INDICATO DIVERSAMENTE.

NOTE GENERALI IDRAULICO1. LE TUBAZIONI DELLE RETI FOGNARIE INFERIORI A 75 mm DEVONO ESSERE INCLINATE A 6,35

mm OGNI 304,8 mm, 75 mm E PIÙ GRANDI DEVONO ESSERE INCLINATE A 3,18 mm OGNI 304,8 mm.

2. GLI IDRANTI A PARETE DEVONO ESSERE INSTALLATI TRA 457,2 mm MIN E 610 mm MAX SOPRA IL LIVELLO DI PAVIMENTO FINITO. COORDINARE LE QUOTE DEL PAVIMENTO FINITO O DELLA QUOTA ESTERNA FINITA. FORNIRE UNA VALVOLA DI CHIUSURA INTERNA ACCESSIBILE PER OGNI IDRANTE A PARETE.

3. INSTALLARE TAPPI D'ISPEZIONE A PARETE (WCO) SU TUTTE LE MONTANTI FOGNARIE E ACQUE METEORICHE A 762 mm SOPRA IL PAVIMENTO FINITO A MENO CHE NON SIA INDICATO DIVERSAMENTE. COORDINARE L'ALTEZZA ESATTA CON GLI ALTRI OPERATORI PER GARANTIRE L'ACCESSIBILITÀ.

4. DIRIGERE TUTTE LE TUBAZIONI DELLE ACQUE METEORICHE IL PIÙ IN ALTO POSSIBILE CON PENDENZA DI 3,18 mm OGNI 304,8 mm A MENO CHE NON SIA INDICATO DIVERSAMENTE. I BECCHUCCI DI SFIORO DEVONO ESSERE ISTALLATI A 304.8mm SOPRA LA QUOTA FINITA ESTERNA, SALVO DIVERSAMENTE INDICATO.

5. FORNIRE GLI ANTIRIFLUSSO IN CONFORMITÀ CON LE NORMATIVE LOCALI. FORNIRE VALVOLE DI SFIATO PER TUTTI GLI ANTIRIFLUSSO RPZ E INDIRIZZARE LE TUBAZIONI DI SCARICO AL PIÙ VICINO SCARICO A PAVIMENTO O AL LAVANDINO A PAVIMENTO O COME MOSTRATO SUI DISEGNI.

6. FORNIRE REGOLATORI DI GAS, TUBAZIONI DI SFIATO DEL REGOLATORE, VALVOLE DI INTERCETTAZIONE, SIFONI PER SEDIMENTI E RACCORDI SU TUTTE LE APPARECCHIATURE ALIMENTATE A GAS. REGOLARE LA PRESSIONE DEL GAS COME RICHIESTO PER OGNI SPECIFICA ATTREZZATURA ALIMENTATA A GAS.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 6

:34

:19

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

M-002

ME

CH

AN

ICA

L LE

GE

ND

-LE

GEND

A M

ECCA

NICO

JAL

159

14090162

GTH GTH

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

GENERAL HVAC NOTES

GENERAL PLUMBING NOTES

GENERAL MECHANICAL NOTES

1. DUCTWORK DIMENSIONS: FIRST NUMBER INDICATES SIDE OF DUCTWORK SHOWN.ALL DIMENSIONS ARE IN INCHES AND ARE INSIDE CLEAR DIMENSIONS.

2. VOLUME DAMPERS ABOVE PLASTER OR GYPBOARD CEILINGS SHALL HAVEEXTENSION RODS AND CHROME-PLATED ESCUTCHEON PLATES.

3. COORDINATE ALL GRILLE, REGISTER AND DIFFUSER LOCATIONS WITH REFLECTEDCEILING PLAN, LIGHTING, AND ALL OTHER CEILING MOUNTED DEVICES.

4. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK AND PIPING SYSTEMSCONNECTED TO FANS, PUMPS AND OTHER EQUIPMENT WHICH REQUIREVIBRATION ISOLATION.

5. PROVIDE ACCESSIBLE VOLUME DAMPERS OR OTHER MEANS OF AIRFLOWADJUSTMENT AT ALL DUCT RUN-OUTS TO DIFFUSERS AND GRILLES.

6. PROVIDE DUCT ACCESS DOORS AT OUTSIDE AIR INTAKE PLENUMS.

7. ALL DUCT RUN-OUTS TO DIFFUSERS AND GRILLES SHALL BE THE SAME AS THEDIFFUSER OR GRILLE NECK SIZE UNLESS NOTED OTHERWISE.

8. ALL PIPING RUNOUTS SHALL BE 20 mm UNLESS NOTED OTHERWISE.

1. SANITARY SEWER PIPING SMALLER THAN 75 mm SHALL BE SLOPED AT 6.35 mm PER304.8 mm, 75 mm AND LARGER SHALL BE SLOPED AT 3.18 mm PER 304.8 mm.

2. WALL HYDRANTS SHALL BE INSTALLED BETWEEN 457.2 mm MIN AND 610 mm MAXABOVE FINISH GRADE. COORDINATE ELEVATIONS OF FINISH FLOOR OR FINISHEXTERIOR GRADE. PROVIDE ACCESSIBLE INSIDE SHUTOFF VALVE FOR EACH WALLHYDRANT.

3. INSTALL WALL CLEANOUTS (WCO) ON ALL SANITARY AND STORM RISERS AT 762mm ABOVE FINISH FLOOR UNLESS NOTED OTHERWISE. COORDINATE EXACTHEIGHT WITH OTHER TRADES TO ENSURE ACCESSIBILITY.

4. ROUTE ALL STORM PIPING AS HIGH AS POSSIBLE AND SLOPE AT 3.18 mm PER 304.8mm UNLESS NOTED OTHERWISE. OVERFLOW DOWN SPOUT NOZZLES SHALL BEINSTALLED AT 304.8 mm ABOVE FINISH EXTERIOR GRADE UNLESS NOTEDOTHERWISE.

5. PROVIDE BACKFLOW PREVENTERS IN ACCORDANCE WITH THE LOCAL CODES.PROVIDE AIR GAP FITTINGS FOR ALL RPZ BACKFLOW PREVENTERS AND ROUTEDISCHARGE PIPING TO NEAREST FLOOR DRAIN OR FLOOR SINK OR AS SHOWN ONDRAWINGS.

6. PROVIDE GAS REGULATORS, REGULATOR VENT PIPING, SHUTOFF VALVES, DIRTLEGS, AND UNIONS ON ALL GAS FIRED EQUIPMENT. REGULATE GAS PRESSURE ASREQUIRED FOR EACH SPECIFIC PIECE OF GAS FIRED EQUIPMENT.

1. THESE NOTES ARE NOT ALL INCLUSIVE. REFER TO DRAWINGS AND SPECIFICATION FORADDITIONAL REQUIREMENTS.

2. THIS IS A STANDARD MECHANICAL (HVAC AND PLUMBING) SYMBOLOGY ANDABBREVIATIONS SHEET. LISTING OF SYMBOLS AND ABBREVIATIONS DOES NOT IMPLYALL SYMBOLS AND ABBREVIATIONS HAVE BEEN USED ON THIS PROJECT.

3. VALVE SYMBOLS SHOWN HERE ARE APPLICABLE ONLY TO MECHANICAL SHEETS.

4. PROVIDE ALL MATERIALS, LABOR, AND EQUIPMENT FOR COMPLETE AND OPERABLESYSTEMS AS INDICATED ON THE DRAWINGS AS SPECIFIED, OR AS REQUIRED BY CODE.

5. MECHANICAL INSTALLATION SHALL COMPLY WITH THE ADA/ABA ACCESSIBILITYGUIDELINES.

6. DETAILS APPLY TO THE ENTIRE PROJECT AND ARE ONLY REFERENCED TO PROVIDECLARITY IF THERE ARE MULTIPLE DETAILS THAT COULD APPLY TO A PARTICULARPROJECT CONDITION.

7. COORDINATE LOCATION OF ALL MECHANICAL EQUIPMENT, DUCTWORK, AND PIPINGWITH OTHER TRADES BEFORE PROCEEDING WITH WORK. DO NOT INSTALLMECHANICAL EQUIPMENT, DUCTWORK, OR PIPING ABOVE ELECTRICAL EQUIPMENTWHERE PROHIBITED BY ELECTRICAL CODES (SWITCHBOARDS, PANELS, ETC.).

8. LIGHT LINE WEIGHT INDICATES EXISTING PIPING, DUCTWORK, AND/OR EQUIPMENT TOREMAIN. BOLD LINE WEIGHT INDICATES NEW WORK TO BE INSTALLED AS WORK OFTHIS CONTRACT.

9. COORDINATE INSTALLATION OF OUTSIDE AIR INTAKE WITH INSTALLATION OF PLUMBINGVENTS, FLUES AND EXHAUST/RELIEF OUTLETS TO MAINTAIN 10’ SEPARATION.

10. ALL WORK IN FINISHED SPACES SHALL BE LOCATED ABOVE CEILINGS, IN CHASES OROTHER CONCEALED ACCESSIBLE LOCATIONS UNLESS NOTED OTHERWISE. LOCATEAND ARRANGE VALVES, DRAIN FITTINGS, ETC. TO BE ACCESSIBLE THROUGH LAY-INCEILINGS, ACCESS PANELS OR ACCESS DOORS. PROVIDE AN ACCESS PANEL OR DOORFOR ALL NON-ACCESSIBLE INSTALLATIONS. COORDINATE LOCATION OF ACCESSPANELS OR DOORS WITH THE ARCHITECT/ENGINEER AND OTHER TRADES.

11. ALL MATERIALS LOCATED IN PLENUM SHALL BE RATED FOR PLENUM INSTALLATION.

12. ALL DUCTWORK, PIPING, AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEELSHALL BE COORDINATED WITH ALL TRADES. ALL ATTACHMENTS TO STEEL BAR JOISTS,TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS OR AS SHOWN ON THEMECHANICAL OR STRUCTURAL DRAWINGS. WELDING TO STRUCTURAL MEMBERS SHALLNOT BE PERMITTED.

13. ALL MISCELLANEOUS METALS AND MATERIALS REQUIRED TO ENSURE PROPERINSTALLATION AND AS SHOWN IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT(UNLESS OTHERWISE NOTED) SHALL BE PROVIDED BY THE INSTALLING CONTRACTOR.

14. PROVIDE DIELECTRIC UNIONS AT ALL CONNECTIONS OF DISSIMILAR METALS (SUCH ASCOPPER TO GALVANIZED STEEL).

15. PROVIDE ISOLATION VALVES AT EACH PIECE OF EQUIPMENT. ALSO PROVIDEISOLATION VALVES ON EACH BRANCH AND/OR RISER SERVING MULTIPLE PIECES OFEQUIPMENT OR FIXTURES AND ELSEWHERE AS INDICATED. INSTALL VALVES AS CLOSETO MAIN AS POSSIBLE.

GE GRAVITY EXHAUST

GI GRAVITY INTAKE

I/O INPUT/OUTPUT

I/P CURRENT TO PNEUMATIC

IAQ INDOOR AIR QUALITY

IPLV INTEGRATED PART LOADVALUE

L/h LITERS PER HOUR

L/M LITERS PER MINUTE

L/s LITERS PER SECOND

LAT LEAVING AIRTEMPERATURE

LVR LOUVER

LWT LEAVING WATERTEMPERATURE

m/s METERS PER SECOND

MBH THOUSAND BTUH

MCC MOTOR CONTROL CENTER

NC NOISE CRITERIA

NO NUMBER

NRC NOISE REDUCTIONCOEFFICIENT

OS&Y OUTSIDE SCREW ANDYOKE

PD PRESSURE DROP

RH RELATIVE HUMIDITY

RTU ROOFTOP UNIT

S SIGNAL PORT

SCFM STANDARD CUBIC FEETPER MINUTE

SEER SEASONAL ENERGYEFFICIENCY RATIO

SP STATIC PRESSURE

TC TECHNOLOGYCONTRACTOR

TCP TEMPERATURE CONTROLPANEL

TD TEMPERATUREDIFFERENTIAL

TES THERMAL ENERGYSTORAGE

TSP TOTAL STATIC PRESSURE

UH UNIT HEATER

V&C VALVE AND CAP

VAV VARIABLE AIR VOLUME

VRF VARIABLE REFRIGERANTFLOW

VTR VENT THROUGH ROOF

WB WET BULB

WC WATER COLUMN

WPD WATER PRESSURE DROP

AD ACCESS DOOR

AFR ABOVE FINISHED ROOF

AHU AIR HANDLING UNIT

APD AIR PRESSURE DROP

ARF ABOVE RAISED FLOOR

AV ABOVE RAISED FLOOR

BAS BUILDING AUTOMATIONSYSTEM

BDD BACK DRAFT DAMPER

BHP BRAKE HORSE POWER

BOE BOTTOM OF EQUIPMENT

BTUH BRITISH THERMAL UNITSPER HOUR

CAV CONSTANT AIR VOLUME

COP COEFFICIENT OFPERFORMANCE

COR CONTRACTING OFFICER'SREPRESENTATIVE

CRAC COMPUTER ROOM AIRCONDITIONER

CU CONDENSING UNIT

DB DRY BULB

DDC DIRECT DIGITAL CONTROL

DH DEHUMIDIFIER

DX DIRECT EXPANSION

EAT ENTERING AIRTEMPERATURE

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCYRATIO

EMCS ENERGY MANAGEMENTCONTROL SYSTEM

ERU ENERGY RECOVERY UNIT

ESP EXTERNAL STATICPRESSURE

ESS EMERGENCY SHUTOFFSWITCH

EWT ENTERING WATERTEMPERATURE

F FUTURE

FA FREE AREA

FCP FAN CONTROL PANEL

FCU FAN COIL UNIT

FDBK FEEDBACK

FLA FULL LOAD AMPS

FLT FILTER

FPB FAN POWERED BOX

GC GENERAL CONTRACTOR

FD

FD

T

T

M

T

F-01

HP-01 HP-02

FC-01

EF-01

EF-02

140

L/s

D-1

250

ø

140

L/s

G-1

30

0x3

00

120

L/s

G-1

30

0x3

00

120

L/s

D-1

250

ø

180 L/sG-1 300x300

180 L/s

D-1 250ø

18 L/sD-2 150x150

200x360

360x360

380x380

300x300

VD

VD

VD

VD

VD

BREAK

106

MECH/ELEC

107

COMM

105

JANITOR

104

TOILET

102

PASSAGE

103

COMMAND & CONTROL

101

EUH-01

1

2

2

VD

VD

250ø

150x150

250ø

3

4

5

5

200x200

6

F-01

EUH-01

VD

VD

FC-01

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK,

VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SSIF

IED

AVIA

NO

AIR

BAS

EAV

IAN

O, I

TALY

AREA

A1

ENTR

Y C

ON

TRO

L PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21

6:34

:21

PM

BIM

360

://1

022

4522

_NA

VF

AC

_A1_

Des

ign_

Avi

ano_

Italy

_201

8/1

0224

522-

ME

P-G

ate

hous

e_v2

018

.rvt

MB101

ME

CH

AN

ICA

L F

LOO

R P

LAN

-PI

ANTA

IMPI

ANTO

MEC

CANI

CO

JAL

160

14090163

GTH GTH

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LAN

TIC

DE

SIG

N A

ND

CO

NS

TR

UC

TIO

N

RICHARD STEPHENS, PESEK

1 : 50

HVAC PLAN

1 ROUTE 100MM PVC PIPE BELOW SLAB FOR RADON MITIGATIONVENTILATION. TERMINATE PIPING WITH AN ELBOW 150MM ABOVEFINISHED ROOF. PORTARE UN TUBO IN PVC DA 100MM SOTTO LASOLETTA PER LA VENTILAZIONE DI CONTENIMENTO DEL RADON.TERMINARE LE TUBAZIONI 150 MM AL DI SOPRA DEL TETTO FINITO.

2 SIZE AND ROUTE REFRIGERANT PIPING PER MANUFACTURERSRECOMMENDATIONS. CONTRACTOR TO FIELD VERIFY THAT PIPING IS NOTROUTED ABOVE ELECTRICAL EQUIPMENT. DIMENSIONARE E DIRIGERE LETUBAZIONI DEL REFRIGERANTE SECONDO LE RACCOMANDAZIONI DEIPRODUTTORI.

3 ROUTE CONDENSATATE PIPING TO THE NEAREST FLOOR DRAIN.PORTARE LE TUBATURE DELLA CONDENSA ALLO SCARICO A PAVIMENTOPIÙ VICINO.

4 ROUTE CONDENSATE PIPING TO SERVICE SINK. PORTARE LE TUBAZIONIDELLA CONDENSA AL GETTATOIO.

5 TERMINATE EXHAUST FAN DUCT AT WALL WITH A HOODED WALL VENTWITH A SPRING LOADED DAMPER. TERMINARE IL CONDOTTO DELVENTILATORE DI ESPULSIONE SULLA PARETE CON UNO SFIATO A PARETECON CAPPUCCIO E UNA SERRANDA A MOLLA.

6 TERMINATE OUTDOOR AIR INTAKE WITH A HOODED WALL VENT.TERMINARE LA PRESA D'ARIA ESTERNA CON UNO SFIATO A PARETE CONCAPPUCCIO.

GATEHOUSE

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

PIANTA HVAC

SYM

DES

CR

IPTI

ON

DAT

EAP

PR

KEY PLAN - PIANTA CHIAVE

KEYNOTES - NOTE CHIAVE

T

MEF

CT

T

FAN COIL UNIT/ FURNACE

VENTILCONVETTORE/CALDAIA

NOTES:

1. ON DRAW-THRU UNITS, THE (A) DIMENSION (IN MM) SHALL BE 1.5 TIMES THE AIR HANDLING UNIT'S SUCTION PRESSURE AT OPERATING CONDITIONS, BUT IN NO CASE LESS THAN 50 MM.

1. SULLE UNITÀ DI TIRAGGIO, LA DIMENSIONE (A) (IN MM) DEVE ESSERE PARI A 1,5 VOLTE LA PRESSIONE DI ASPIRAZIONE DELL'UNITÀ DI TRATTAMENTO DELL'ARIA IN CONDIZIONI OPERATIVE, MA IN NESSUN CASO INFERIORE A 50 MM.

SLOPE CD TO FLOOR DRAIN OR FUNNEL DRAIN. SEE PLANS FOR CONTINUATIONS.INCLINARE IL CANALE VERSO LO SCARICO A PAVIMENTO O LO SCARICO A IMBUTO. VEDERELE PIANTE PER LA CONTINUAZIONE.

CLEANOUT PLUGTAPPO D'ISPEZIONE 5

0M

M M

IN A

NON IN SCALA

SUPPLY AIRARIA DI MANDATA RETURN AIR

ARIA DI RIPRESA

REFRIGERANT PIPING TO HEAT PUMP.TUBAZIONI DEL REFRIGERANTE ALLA POMPA DI CALORE.

CONDENSATE DRAIN. SCARICO DELLA CONDENSA.

FILTER RACKPORTAFILTRO

FLEX CONECTIONCONNESSIONE FLESSIBILE

NEOPRENE ISOLATOR PADSCUSCINETTI ISOLANTI IN NEOPRENE

CONCRETE EQUIPMENT PADBASAMENTO IN CLS PER LE APPARECCHIATURE

FURNACECALDAIA

HEAT PUMP / FURNACE CONTROL SEQUENCE• HEATING: THE HEAT PUMP / FURNACE SHALL RUN IN OCCUPIED MODE TO MAINTAIN 20 (ADJ.) DEGREE C. IN NON-OCCUPIED MODE, HEAT PUMP / FURNACE SHALL MAINTAIN A SPACE TEMPERATURE OF 12 (ADJ.) DEGREE C. THE FIRST STAGE OF HEATING

SHALL BE THE HEAT PUMP OPERATION. THE SECOND STAGE OF HEATING SHALL BE THE ELECTRIC FURNACE HEATING COIL.• COOLING: THE HEAT PUMP / FURNACE SHALL RUN IN OCCUPIED MODE TO MAINTAIN 25.6 (ADJ.) DEGREE C. IN NON-OCCUPIED MODE, HEAT PUMP / FURNACE SHALL MAINTAIN A SPACE TEMPERATURE OF 26.7 (ADJ.) DEGREE F.

SEQUENZA DI CONTROLLO POMPA DI CALORE/ CALDAIA• RISCALDAMENTO: LA POMPA DI CALORE/CALDAIA DEVE FUNZIONARE IN MODALITÀ OCCUPATA PER MANTENERE 20 °C ( REGOLABILI) . IN MODALITÀ NON OCCUPATA, LA POMPA DI CALORE/CALDAIA DEVE MANTENERE UNA TEMPERATURA AMBIENTE DI 12

°C IL PRIMO STADIO DI RISCALDAMENTO SARÀ IL FUNZIONAMENTO DELLA POMPA DI CALORE. IL SECONDO STADIO DI RISCALDAMENTO SARÀ LA BATTERIA DI RISCALDAMENTO ELETTRICA DELLA CALDAIA.• RAFFREDDAMENTO: LA POMPA DI CALORE/CALDAIA DEVE FUNZIONARE IN MODALITÀ OCCUPATA PER MANTENERE 25,6 °C ( REGOLABILE) IN MODALITÀ NON OCCUPATA, LA POMPA DI CALORE/CALDAIA DEVE MANTENERE UNA TEMPERATURA AMBIENTE

DI 26,7 GRADI F. (REGOLABILI)

• INTERRUTTORE ON-AUTO DEL VENTILATORE1. ON

A. CON L'INTERRUTTORE AUTOMATICO DEL VENTILATORE DEL TERMOSTATO IN POSIZIONE ON, IL TERMOSTATO PROGRAMMABILE 24/7 DEVE AVVIARE E FAR FUNZIONARE CONTINUAMENTE IL VENTILATORE.

2. AUTOA. CON L'INTERRUTTORE ON-AUTO DEL VENTILATORE DEL TERMOSTATO IN POSIZIONE AUTO, IL TERMOSTATO

PROGRAMMABILE 24/7 AZIONA IL VENTILATORE IN BASE ALL'INTERRUTTORE CALDO-SPENTO-FREDDO.

• INTERRUTTORE CALDO-SPENTO-FREDDO1. HEAT-COOL-EMERG HEAT

A. CON L'INTERRUTTORE DEL TERMOSTATO NELLE POSIZIONI DI RISCALDAMENTO O RAFFREDDAMENTO, UTILIZZARE IL TERMOSTATO PROGRAMMABILE 24/7 PER FAR FUNZIONARE L'UNITÀ IN BASE ALLA MODALITÀ DI OCCUPAZIONE.

2. OFFA. CON L'INTERRUTTORE DEL TERMOSTATO IN POSIZIONE OFF, SPEGNERE L'UNITÀ DI RISCALDAMENTO E L'UNITÀ DI

RAFFREDDAMENTO CON IL TERMOSTATO PROGRAMMABILE 24/7.

• MODALITA' DI OCCUPAZIONE1. IL FUNZIONAMENTO OCCUPATO / NON OCCUPATO DEVE ESSERE IMPOSTATO TRAMITE IL TERMOSTATO PROGRAMMABILE.

A. OCCUPATO - LA SERRANDA MOTORIZZATA CHE SERVE IL CONDOTTO DELL'ARIA ESTERNA DEVE ESSERE IN POSIZIONE APERTA QUANDO IN MODALITÀ OCCUPATA.

B. NON OCCUPATO - LA SERRANDA MOTORIZZATA CHE SERVE IL CONDOTTO DELL'ARIA ESTERNA DEVE ESSERE IN POSIZIONE CHIUSA QUANDO È IN MODALITÀ NON OCCUPATA.

• SICUREZZA1. FAR FUNZIONARE L'UNITÀ NEL RISPETTO DELLE NORME DI SICUREZZA DEL PRODUTTORE DELL'UNITÀ.

NON IN SCALA

M

• FAN ON-AUTO SWITCH1. ON

A. WITH THE THERMOSTAT FAN ON-AUTO SWITCH IN THE ON POSITION, THE 24/7 PROGRAMMABLE THERMOSTAT MUST START AND CONTINUOUSLY RUN THE FAN.

2. AUTOA. WITH THE THERMOSTAT FAN ON-AUTO SWITCH IN THE AUTO POSITION, THE 24/7 PROGRAMMABLE THERMOSTAT

OPERATES THE FAN ACCORDING TO HEAT-OFF-COOL SWITCH.

• HEAT-OFF-COOL SWITCH1. HEAT-COOL-EMERG HEAT

A. WITH THE THERMOSTAT SWITCH IN THE HEAT OR COOL POSITIONS, USE THE 24/7 PROGRAMMABLE THERMOSTAT TO OPERATE THE PACKAGE UNIT ACCORDING TO THE OCCUPANCY MODE.

2. OFFA. WITH THE THERMOSTAT SWITCH IN THE OFF POSITION, DE-ENERGIZE THE HEATING UNIT AND COOLING UNIT

WITH THE 24/7 PROGRAMMABLE THERMOSTAT.

• OCCUPANCY MODES1. OCCUPIED / UNOCCUPIED OPERATION SHALL BE SET VIA THE PROGRAMABLE THERMOSTAT.

A. OCCUPIED - THE MOTORIZED DAMPER THAT SERVES THE OUTDOOR AIR DUCT SHALL BE IN THE OPEN POSITION WHEN IN OCCUPIED MODE.

B. UNOCCUPIED - THE MOTORIZED DAMPER THAT SERVES THE OUTDOOR AIR DUCT SHALL BE IN THE CLOSED POSITION WHEN IN UNOCCUPIED MODE.

• SAFETIES1. RUN THE UNIT SUBJECT TO THE UNIT MANUFACTURER'S SAFETIES.

SPLIT SYSTEM CONTROL SEQUENCE

THE SPLIT SYSTEM MANUFACTURER SHALL PROVIDE A FACTORY INSTALLED CONTROL SYSTEM AND REMOTELY MOUNTED THERMOSTAT CAPABLE OF SCHEDULING 24 HOURS, SEVEN DAYS A WEEK.

THE SPLIT SYSTEM SHALL MAINTAIN SPACE SETPOINT AT A MAXIMUM OF 25 DEGREES C (ADJ.). FACTORY INSTALLED CONTROL SYSTEM SHALL RESTART ON A POWER FAILURE.

SEQUENZA DI CONTROLLO DELL'IMPIANTO SPLIT

IL PRODUTTORE DELL'IMPIANTO SPLIT DEVE FORNIRE UNSISTEMA DI CONTROLLO INSTALLATO IN FABBRICA E UN TERMOSTATO MONTATO A DISTANZA IN GRADO DI PROGRAMMARE 24 ORE, SETTE GIORNI ALLA SETTIMANA.

L'IMPIANTO SPLIT DEVE MANTENERE IL SETPOINT DELL'AMBIENTE AD UN MASSIMO DI 25 GRADI C ( REGOLABILI). IL SISTEMA DI CONTROLLO INSTALLATO IN FABBRICA DEVE RIAVVIARSI IN CASO DIMANCANZA DI CORRENTE.

HP-##

FC-##

(INDOORS)(INTERNO)

(OUTSIDE)(ESTERNO)

24/7 PROGRAMMABLE THERMOSTAT

TERMOSTATO PROGRAMMABILE 24/7

NON IN SCALA

VENTILCONVETTORE

POMPA DI CALORE

EXHAUST FAN CONTROL SEQUENCE

THE EXHAUST FAN WILL RUN CONTINOUSLY IN CONJUNCTION WITH THE LIGHT SWITCH FORTHE SERVED AREA.

FAN SHALL RUN AN ADDITIONAL 10 (ADJ.) MINUTES AFTER IT IS TURNED OFF.

SEQUENZA DI CONTROLLO DEL VENTILATORE DI ESPULSIONE

IL VENTILATORE DI ESPULSIONE FUNZIONERÀ CONTINUAMENTE IN COMBINAZIONE CON L'INTERRUTTORE DELLA LUCE PER LA ZONA SERVITA.

IL VENTILATORE FUNZIONERÀ PER ALTRI 10 ( REGOLABILI) MINUTI DOPO LO SPEGNIMENTO.

NON IN SCALA

ELECTRIC UNIT HEATER CONTROL SEQUENCE

THE ELECTRIC UNIT HEATER WILL RUN CONTINOUSLY WHEN THE THERMOSTAT SENSES A SPACE TEMPERATURE OF 5 DEGREES C (ADJ.) OR BELOW.

ROOM TEMPERATURE WILL BE MAINTAINED AT 7 DEGREES C (ADJ,).

ELECTRIC UNIT HEATER SHALL AUTOMATICALLY RESTART AFTER LOSS OF POWER.

SEQUENZA DI CONTROLLO DEL RISCALDATORE ELETTRICO

IL RISCALDATORE ELETTRIC FUNZIONA CONTINUAMENTE QUANDO IL TERMOSTATO RILEVA UNA TEMPERATURA AMBIENTE DI 5 GRADI °C ( REGOLABILE) O INFERIORE.

LA TEMPERATURA DELL'AMBIENTE SARÀ MANTENUTA A 7 GRADI °C ( REGOLABILE).

L'UNITÀ DI RISCALDAMENTO ELETTRICA SI RIAVVIA AUTOMATICAMENTE DOPO UNA PERDITA DI POTENZA.

EUH-## WALL MOUNTED THERMOSTATTERMOSTATO MONTATO A PARETE

NON IN SCALA

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 6

:34

:22

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

MB501

ME

CH

AN

ICA

L D

ETA

ILS

-DE

TTAG

LI M

ECCA

NICO

JAL

161

14090164

GTH GTH

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

1CONDENSATE DRAIN TRAP DETAIL

NOT TO SCALENON IN SCALA

3FURNACE DETAIL

NOT TO SCALENON IN SCALA

2SPLIT SYSTEM CONTROLS

NOT TO SCALENON IN SCALA

4EXHAUST FAN CONTROLS

NOT TO SCALENON IN SCALA

5ELECTRIC UNIT HEATER CONTROLS

DETTAGLIO DEL SIFONE DI

SCARICO DELLA CONDENSA

DETTAGLIO CALDAIA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

CONTROLLI IMPIANTO

SPLIT

CONTROLLI DEL VENTILATORE

DI ESPULSIONE

CONTROLLI DEL

RISCALDATORE ELETTRICO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK,

VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SSIF

IED

AVIA

NO

AIR

BAS

EAV

IAN

O, I

TALY

AREA

A1

ENTR

Y C

ON

TRO

L PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21

6:34

:23

PM

BIM

360

://1

022

4522

_NA

VF

AC

_A1_

Des

ign_

Avi

ano_

Italy

_201

8/1

0224

522-

ME

P-G

ate

hous

e_v2

018

.rvt

MB601

ME

CH

AN

ICA

L S

CH

ED

ULE

S -

TABE

LLE

IMPI

ANTO

MEC

CANI

CO

JAL

162

14090165

GTH GTH

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LAN

TIC

DE

SIG

N A

ND

CO

NS

TR

UC

TIO

N

RICHARD STEPHENS, PESEK

3. PROVIDE EXTENED COOLING OPERATING RANGE OF -20°C TO 46°C. PREVEDERE UN INTERVALLO OPERATIVO DI RAFFREDDAMENTO ESTESO DA -20°C A 46°C.2. PROVIDE CEILING MOUNTED INDOOR UNIT. FORNIRE UN'UNITÀ INTERNA MONTATA A SOFFITTO.1. PROVIDE WALL MOUNTED INDOOR UNIT. FORNIRE UN'UNITÀ INTERNA MONTATA A PARETE.

NOTES:

FC-04SEARCH OFFICE / UFFICIO

CONTROLLI RM 103 204 26.7 19.4 3.0 21.0 15.5 3.0 0.3 38 230 50 1 HP-05 SEARCH OFFICE / UFFICIOCONTROLLI

35.0R-410A 7 230 50 1 1,3

FC-03SEARCH OFFICE / UFFICIO

CONTROLLI RM 102 204 26.7 19.4 3.0 21.0 15.5 3.0 0.3 38 230 50 1 HP-04SEARCH OFFICE / UFFICIO

CONTROLLI35.0

R-410A 7 230 50 1 1,3

FC-02SEARCH OFFICE / UFFICIO

CONTROLLI RM 101 189 26.7 19.4 3.3 21.1 15.6 4.1 0.28 50 230 50 1 HP-03SEARCH OFFICE / UFFICIO

CONTROLLI35.0

R-410A 9 230 50 1 2,3

FC-01GATEHOUSE / CORPO DI

GUARDIA RM 105 204 26.7 19.4 3.0 21.0 15.5 3.0 0.3 38 230 50 1 HP-02GATEHOUSE / CORPO DI

GUARDIA 35.0R-410A 7 230 50 1 1,3

DB WB DB WB

E.A.T. (°C) (KW) E.A.T. (°C) (KW) (°C)

AIRSIDE DATA MIN. CAP. AIRSIDE DATA MIN. CAP.

FLA W VOLT HZ PH

TEMP

AMPS VOLT HZ PH

MARK /SIGLA

LOCATION / EDIFICIOSERVES /

AMBIENTE

AIRFLOW /PORTATA

(L/S)

COOLING COIL DATA / DATISERPENTINA DI

RAFFREDDAMENTO

HEATING COIL DATA / DATISERPENTINA RISCALDANTE

FAN MOTOR DATA / DATI DEL VENTILATORE

MARK /SIGLA

LOCATION / EDIFICIO AMB.

REFRIGERANT TYPE /TIPO DI

REFRIGERANTE

ELECTRICAL DATA / DATI ELETTRICI

NOTES

INDOOR DATA / DATI ESTERNO OUTDOOR DATA / DATI ESTERNO

DUCTLESS SPLIT SYSTEM AIR CONDITIONING SCHEDULE / TABELLA DEL SISTEMA DI CONDIZIONAMENTO D'ARIA CON SPLIT SENZA CONDOTTI

3. INCLUDE UNIT MOUNTED DISCONNECT. INCLUDERE IL DISPOSITIVO DI DISCONNESSIONE MONTATO SULL'UNITÀ.2. HANG PER MANUFACTURER'S INSTRUCTIONS AS SHOWN ON PLANS. APPENDERE SECONDO LE ISTRUZIONI DEL PRODUTTORE COME INDICATO NEI DISEGNI.1. INCLUDE WALL MOUNTED THERMOSTAT AS SHOWN. INCLUDERE IL TERMOSTATO MONTATO A PARETE COME MOSTRATO

NOTES:

EUH-01GATEHOUSE / CORPO DI

GUARDIA RM 107 5.0 230 1 50 1 165 4.0 -19.9 5.1 245 1,2,3

VEL. (M/S) (°C) (°C)KW VOLT PH HZ STEPS L/S

OUTLET E.A.T. L.A.T.

MARK /SIGLA

LOCATION / EDIFICIOSERVES /

AMBIENTE

ELECTRICAL DATA / DATI ELETTRICIAIR DELIVERY DATA / DATI MANDATA

DELL'ARIA RECOM'D MOUNTING HEIGHT /ALTEZZA DI MONTAGGIORACCOMANDATA (mm)

NOTES

ELECTRIC UNIT HEATER SCHEDULE / TABELLA UNITA' RISCALDAMENTO ELETTRICO

2. EXHAUST FAN SHALL BE INTERLOCKED WITH LIGHT SWITCH AND PROVIDED WITH 10 MINUTE (ADJ.) DELAY OFF. LA VENTOLA DI ESPULSIONE SARÀ INTERBLOCCATA CON L'INTERRUTTORE DELLA LUCE E DOTATA DI UN RITARDATORE DI SPEGNIMENTO DI 10MINUTI (REGOLABILE).

1. PROVIDE WITH GRAVITY BACKDRAFT DAMPER AND FACTORY WALL TERMINATION KIT. PREVEDERE CON SERRANDA A GRAVITÀ E KIT DI TERMINALE A PARETE DI FABBRICA.NOTES:

EF-02GATEHOUSE /

CORPO DI GUARDIA RM 104 35 124CENTRIFUGAL/ FORWARD CURVED

CENTRIFUGO, CON GIRANTE A PALE CURVE INAVANTI

950 54 0.04 230/1 DIRECT 1,2

EF-01GATEHOUSE /

CORPO DI GUARDIA RM 102 35 124CENTRIFUGAL/ FORWARD CURVED

CENTRIFUGO, CON GIRANTE A PALE CURVE INAVANTI

950 54 0.04 230/1 DIRECT 1,2

HP V/PH TYPE

DRIVE

MARK /SIGLA

LOCATION / EDIFICIOSERVES /

AMBIENTEOPERATING AIRFLOW /

PORTATA DI ESERCIZIO (L/S)S.P. / PRESSIONE

STATICA (Pa.)FAN TYPE / TIPO DI VENTILATORE

FAN RPM / VELOCITA' DELVENTILATORE

S.P.L. 250 HZMAX (dB)

MOTOR DATA DATI / DELMOTORE

NOTES

FAN SCHEDULE / TABELLA VENTILATORE

NOTES:

HP-01GATEHOUSE / CORPO

DI GUARDIA F-01 R-410A 35.0 2.11 -18.0 2.19 230 1 -

(°C) (KW) (°C) (KW)

TEMP. CAP. TEMP. CAP.

AMB. TOTAL AMB. TOTAL

VOLT PH

MARK / SIGLA LOCATION / EDIFICIOSERVES /

AMBIENTE

REFRIGERANT TYPE /TIPO DI

REFRIGERANTE

COOLING DATA / DATIRAFFRESCAMENTO

HEATING DATA / DATIRISCALDAMENTO

ELECTRICAL DATA /DATI ELETTRICI

NOTES

AIR TO AIR HEAT PUMP UNIT SCHEDULE / TABELLA DELLA POMPA DI CALORE ARIA-ARIA

1. PROVIDE WITH EC MOTOR. PREVEDERE MOTORE CON COMMUTAZIONE ELETTRONICA.NOTES:

F-01 RM 107 GATEHOUSE 458 70 124.42 26.6 19.4 14.6 14.4 7.2 5.9 DIRECT ECM 375 230 1 50 1DB WB DB WB (KW) (KW)

E.A.T. (°C) L.A.T. (°C) TOTAL SENS.

(Pa.) AIRSIDE DATA MIN CAP.

DRIVE MOTOR TYPE W V PH HZ

MARK /SIGLA

LOCATION /EDIFICIO

SERVES /AMBIENTE

AIRFLOW(L/S)

OA AIRFLOW(L/S)

EXT. S.P.COOLING COIL DATA / DATI SERPENTINA DI

RAFFREDDAMENTOFAN DATA DATI / DEL

VENTILATORE

ELECTRICAL DATA / DATIELETTRICI

NOTES

ELECTRIC FURNACE SCHEDULE / TABELLA CALDAIA ELETTRICA

NOTES:

G-1 RETURN / AIR RIPRESALAY IN / ATEGOLA 610 X 610 SEE PLANS / VEDI PIANTE 25 30 WHITE / BIANCO -

D-2 SUPPLY / AIR MANDATASURFACEMOUNT / 150 X 150 SEE PLANS / VEDI PIANTE 25 30 WHITE / BIANCO -

D-1 SUPPLY / AIR MANDATALAY IN / ATEGOLA 610 X 610 SEE PLANS / VEDI PIANTE 25 30 WHITE / BIANCO -

MARK /SIGLA

SERVES / AMBIENTE TYPE / TIPO

FACE SIZE /DIMENSIONE

FRONTALE W x H(mm)

CONNECTION SIZE / DIMENSIONEDEL RACCORDO (W x H OR DIA)

(MM)

MAX AIR P.D. /PERDITA DI CARICO

(PA)

MAX N.C. /VALUTAZIONE

RUMOREAMBIENTE

FINISH / FINITURA NOTES

DIFFUSER, REGISTER, AND GRILLE SCHEDULE / TABELLA DI DIFFUSORI, BOCCHETTE E GRIGLIE

NOTES:1. TEST IN ACCORDANCE WITH SECTION 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC AND THE PROCEDURES IN SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. TEST IN CONFORMITÀ CON UFGS 23 05 93,PROVE, REGOLAZIONI E BILANCIAMENTO PER HVAC E LE PROCEDURE NEL MANUALE SMACNA HVAC TEST DI TENUTA DEI CANALI DELL'ARIA.

EXHAUST FANS /VENTILATORI DIESPULSIONE

- - -497.7 - A 4 A 8 497.7 1

ELECTRIC FURNACE /CALDAIA ELETTRICA 248.8 -248.8 -497.7 497.7 A 4 A 8 497.7 1

SUPPLY DUCT /CANALE DIMANDATA

RETURN DUCT /CANALE DIRITORNO

EXHAUST DUCT /CANALE DI

ESPULSIONE

OUTSIDE AIR DUCT /CANALE ARIA

ESTERNA

DUCT SEALCLASS / CLASSEDI TENUTA DEL

CANALE

DUCT LEAKCLASS / CLASSEDI PERDITA DEL

CANALE

DUCT SEALCLASS / CLASSEDI TENUTA DEL

CANALE

DUCT LEAKCLASS / CLASSEDI PERDITA DEL

CANALE

PASCALS ROUND/OVAL / CIRCOLARE/OVALE RECTANGULAR / RETTANGOLARE

SYSTEM / IMPIANTO

DUCT PRESSURE CLASS / CLASSE DI PRESSIONE DEL CANALESUPPLY / RETURN / EXHAUST / OUTSIDE AIR /

MANDATA/RITORNO/ESPULSIONE/ARIA ESTERNA

DUCT TEST PRESSURE:PASCALS / PRESSIONE DI

PROVA DEL CANALE:PASCALS

NOTES

DUCTWORK CONSTRUCTION AND LEAKAGE TESTING SCHEDULE / COSTRUZIONE DI CANALIZZAZIONI E TEST DI TENUTA

1. GENERAL DESIGN CRITERIA: ELEVATION - 125 M, LATITUDE - 46.033°N, LONGITUDE - 12.617°E. CRITERI GENERALIDI PROGETTAZIONE: ALTITUDINE - 125 M, LATITUDINE - 46.033°N, LONGITUDINE - 12.617°E.

NOTES:

MECH/ELEC / LOCALEMECCANICO/ELETTRICO 4.4 -6 - 33 1

SUPPORT / SERVIZIO 4.4 -6 25.6 / 50 33 1

OFFICE / UFFICIO 20 -6 25.6 / 50 33 1

INDOOR /INTERNO

(°C)

OUTDOOR /ESTERNO

(°C)

INDOOR /INTERNO(°C / %RH)

OUTDOOR /ESTERNO

(°C)

ROOM TYPE / TIPOLOGIAAMBIENTE

WINTER / INVERNO SUMMER / ESTATE

NOTES

DESIGN CONDITIONS SCHEDULE

SYM

DES

CR

IPTI

ON

DAT

EAP

PR

T

T

T

HP-03

HP-04

HP-05

FC-03

FC-04

FC-02

1

1

1

2

2

2

MECH/ELEC

103

COMM ROOM

102

SEARCH OFFICE

101

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:50

:45

PM

BIM

360

://1

02

24

522

_N

AV

FA

C_

A1_

De

sig

n_A

via

no

_Ita

ly_20

18

/102

24

522

-ME

P-S

ea

rch

_v20

18

.rvt

MC101

ME

CH

AN

ICA

L F

LOO

R P

LAN

/ PI

ANTA

IMPI

ANTO

MEC

CANI

CO -

SE

AR

CH

OF

FIC

E /

UFFI

CIO

CONT

ROLL

I

JAL

163

14090166

GTH GTH

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50

FIRST FLOOR

PLANNORTH

1. SIZE AND ROUTE REFRIGERANT PIPING PER MANUFACTURERS RECOMMENDATIONS. CONTRACTOR TO FIELD VERIFY THAT PIPING IS NOT ROUTED ABOVE ELECTRICAL EQUIPMENT. DIMENSIONARE E

DIRIGERE LE TUBAZIONI DEL REFRIGERANTE SECONDO LE

RACCOMANDAZIONI DEI PRODUTTORI. RACCOMANDAZIONI.

L'APPALTATORE DEVE VERIFICARE CHE LE TUBAZIONI NON SIANO

POSATE SOPRA L'APPARECCHIATURA ELETTRICA.

2. ROUTE CONDENSATE PIPING OUTDOORS TO DRIP BLOCK. PORTARE

LE TUBAZIONI DELLA CONDENSA ALL'ESTERNO VERSO LA VASCHETTA

DI RACCOLTA.

SEARCH

GRAPHIC SCALE: 1:50

0 421 3 5

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

PRIMO PIANO KEY PLAN - PIANTA CHIAVE

KEYNOTES - NOTE CHIAVE

ONE-LINE, POWER, AND LIGHTING SYMBOLOGY

J

ATS

7 1/2 HP

G

CB

CONTROL PANEL WITH DISCONNECT SWITCH INTEGRALOR PROVIDED WITH ASSOCIATED EQUIPMENT

SEPARATELY MOUNTED COMBINATION MOTOR STARTER OR CONTROLLER; SEE ELECTRICAL ONE - LINE DIAGRAM OR SCHEDULE FOR DESCRIPTION

PANELBOARD (LESS THAN 250V)

PANELBOARD (250V TO 600V)

JUNCTION OR PULL BOX

CONTROL PANEL INTEGRAL OR PROVIDED WITHASSOCIATED EQUIPMENT

OR

3-PHASE, 4-WIRE GROUNDED WYE CONNECTION

3-PHASE, 3-WIRE DELTA CONNECTION

TRANSFORMER

TRANSFER SWITCH, CURRENT RATING, ANDNUMBER OF POLES AS NOTED

GENERATOR

MOTOR WITH DESIGN HORSEPOWER(WHEN INDICATED)

NON-FUSED DISCONNECT OR SAFETY SWITCH, 3P, X INDICATES AMP RATING GREATER THAN 30A.

OR

SEPARATELY MOUNTED CIRCUIT BREAKER; SEEELECTRICAL ONE - LINE DIAGRAM OR SCHEDULEFOR DESCRIPTION

ATS - AUTOMATICMTS - MANUAL

X

ELECTRICAL EQUIPMENT ENCLOSURE: SWITCHBOARD, MOTORCONTROL CENTER, CONTROL PANEL, TRANSFORMER OR OTHEREQUIPMENT AS INDICATED. ESTIMATED SIZE AS INDICATED.WHEN USED, X INDICATES EQUIPMENT TYPE.

FUSED DISCONNECT OR SAFETY SWITCH, 3P, XINDICATES AMP RATING GREATER THAN 30A, YINDICATES FUSE SIZE, 'MR' INDICATES MANUFACTURER'S RECOMMENDATION FOR FUSE SIZE

SEPARATELY MOUNTED MOTOR STARTER OR CONTROLLER;SEE ELECTRICAL ONE-LINE DIAGRAM OR SCHEDULE FORDESCRIPTION.

Y

X

X20A3P

X100AF80AT3P

EQUIPMENT TYPES:

ATSCPMTSMCCUPSVFDSBSGT

---------

AUTOMATIC TRANSFER SWITCHCONTROL PANELMANUAL TRANSFER SWITCHMOTOR CONTROL CENTERUNINTERRUPTIBLE POWER SUPPLYVARIABLE FREQUENCY DRIVESWITCHBOARDSWITCHGEARTRANSFORMER

TIPI:MCCB - SCATOLATIICCB - IN SCATOLA ISOLANTELVP - DI BASSA TENSIONEMCP - SALVAMOTORE

INTERRUTTORE DI LINEA BASSA TENSIONE (CB). PORTATA E NUMERO DI POLI COME INDICAO. QUANDO SONO RICHIESTI TIPI SPECIFICI, OLTRE CHE MCCB, X NE INDICA IL TIPO.

SGANCIATOREL - SOVRACCARICOS - CORTO CIRCUITO RITARDATOI - CORTO CIRCUITO ISTANTANEOG - GUASTO A TERRAA - ARCO MANUTENZINE

X

COMMUNICATION SYMBOLOGY

PRESA DATI A PARETE. IL NUMERO VICINO AL SIMBOLO INDICA IL NUMERO DI PRESE.

PRESA DATI INCASSATA A PAVIMENTO

(1)

SITE SYMBOLOGY

POLE - MOUNTED TRANSFORMER

EXTERIOR PAD MOUNTED TRANSFORMER

ELECTRICAL HANDHOLE OR MANHOLEHH - INDICATES HAND HOLEMH - INDICATES MAN HOLEC - INDICATES TELECOMMUNICATION UTILITYP - INDICATES ELECTRICAL POWER UTILITY(9) - INDICATES TYPE OR SIZE OF HANDHOLE PER DETAIL

X

Y

POLE MOUNTED AREA OR ROADWAY LUMINAIRE, LAMP TYPE AS SPECIFIED

POLE/STANCHION MOUNTED FLOOD LUMINAIRE, LAMP TYPE AS SPECIFIED

X

YHIGH MAST LIGHTING, NUMBER OF LUMINAIRES AS SPECIFIED

X

Y

X - INDICATES LUMINAIRE TYPE PER LUMINAIRE SCHEDULE

Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD

LIGHTING FIXTURE SUBSCRIPTS:

POWER POLE

DOWNGUY

E UNDERGROUND (UNO) ELECTRICAL SYSTEMS PATHWAY

OHE OVERHEAD ELECTRICAL PATHWAY

UNDERGROUND DUCT BANKC - INDICATES TELECOMMUNICATION UTILITYP - INDICATES ELECTRICAL POWER UTILITY

2C - 50mm

3P - 50mm

SIZEUTILITYQUANTITY OF CONDUITS

HHC1 - (9)

SIZESEQUENCEUTILITY

LIGHTNING PROTECTION SYMBOLOGY

AIR TERMINAL 300mm MINIMUM

ROOF CONDUCTOR

DOWN CONDUCTOR

RC

DC

COMM UNDERGROUND COMMUNICATION SYSTEMS PATHWAY

OHC OVERHEAD COMMUNICATION SYSTEMS PATHWAY

SOLAR PANEL

INVERTER-

~

SIMBOLOGIA DI TELECOMUNICAZIONI

WALL MOUNTED DATA OUTLET. NUMBER BY SYMBOL INDICATES QUANTITY OF JACKS.

RECESSED FLOOR MOUNTED DATA OUTLET

(1)

SIMBOLOGIA DEL SITO

TRASFORMATORE SU PALO

TRASFORMATORE INSTALLATO SU BASAMENTO ESTERNO

POZZETTO O CAMERETTA ELETTRICAHH - INDICA POZZETTOMH - INDICA CAMERETTAC - INDICA LINEA TELECOMUNICAZIONIP - INDICA LINEA ENERGIA ELETTRICA(9) INDICA TIPO O DIDMENSIONE POZZETTO COME DA DETTAGLIOTAGLIASEQUENZASERVIZIO

X

Y

ARMATURA PER AREA O STRADALE DA PALO, LAMPADA COME SPECIFICATO

FARO MONTATO SU PALO/SUPPORTO, TIPO LAMPADA COME SPECIFICATO

X

Y

TORRE FARO, NUMERO DI LAMPADE COME INDICATO.

INDICE CORPI ILLUMINANTI:X - INDICA CORPI ILLUMINANTI COME DA TABELLLA CORPI ILLUMINANTIY - INDICA NUMERO CIRCUITO DAL QUADRP

X

Y

PALO ELETTRICO

CALATA

E PERCORSO CIRCUITI ELETTRICI INTERRATI (UNO)

OHE PERCORSO LINEA ELETTRICA AEREA

CAVIDOTTO INTERRATOC - INDICA LINEA TELECOMUNICAZIONOP - INDICA LINEA ENERGIA ELETTRICA

DIMENSIONESERVIZIONUMERO DI CONDUTTORI

2C - 50mm

3P - 50mm

HHC1 - (9)

SIMBOLOGIA DI PROTEZIONE DA FULMINI

ASTA TERMINALE 300mm MINIMICONDUTTTORE SU TETTO CALATA

CONDUTTTORE SU TETTO

CALATA

RC

DC

COMM PERCORSO CIRCUITI TELECOMUNICAZIONI INTERRATI

OHC PERCORSO CIRCUITI TELECOMUNICAZIONI AEREA

J

ATS

7 1/2 HP

G

CB

QUADRO DI CONTROLLO CON SEZIONATORE INTEGRATO O FORNITO INSIEME ALLA RELATIVA APPARECCHIATURA

COMBINAZIONE DI AVVIATORE O CONTROLLORE MOTORE MONTATO A PARTE; VEDI SCHEMA ELETTRICO UNIFILARE O TABELLE PER DESCRIZIONE.

QUADRO ELETTRICO (TENSIONE MINORE DI 250V)

QUADRO ELETTRICO (250-600V)

CASSETTA DI GIUNZIONE O DI PASSAGGIO

QUADRO DI CONTROLLO INTEGRATO O FORNITO INSIEME ALLA RELATIVA APPARECCHIATURA

OR

TRIFASE, 4 FILI COLLEGATO A STELLA CON NEUTRO A TERRA

TRIFASE, 3 FILI COLLEGATI A TRIANGOLO

TRASFORMATORE

COMMUTATORE, PORTATA DI CORRENTE E NUMERO DI POLI COME INDICATO

ATS - AUTOMATICOMTS - MANUALE

GENERATORE

MOTORE CON INDICAZIONE DELLA POTENZA (QUANDO INDICATA)

SEZIONATORE O INTERRUTTORE DI SICUREZZA, 3P, X NE INDICA LA PORTATA SE MAGGIORE DI 30A.

OR

INTERRUTTORE MONTATO SEPRATAMENTE: VEDI SCHEMA ELETTRICO UNIFILARE O TABELLA PER DESCRIZIONE.

X

CASSETTA EQUIPAGGIAMENTO ELETTRICO: DISTRIBUZIONE, MOTOR CONTROL CENTER, QUADRO DI CONTROLLO, TRASFORMATORE O ALTRO EQUIPAGGIAMENTO COME INDICATO. QUANDO UTILIZZATO, X INDICA IL TIPO DI APPARECCHIATURA.

TYPO DI APPARECCHIATURA:ATS - COMMUTATORE AUTOMATICOCP- QUADRO DI CONTROLLOMTS - COMMUTATORE AUTOMATICOUPS - GRUPPO DI CONTINUITA'VFD - VARIATORE DI FREQUENZASB - QUADRO DI DISTRIBUZIONESG - QUADRO DI MANOVRAT - TRASFORMATORE

SEZIONATORE O INTERRUTTORE DI SICUREZZA CON FUSIBILI, 3P, X NE INDICA LA PORTATA SE MAGGIORE DI 30A, Y INDICA LA TAGLIA DEL FUSIBILE, 'MR' INDICA I SIGGERIMENTI DEL COSTRUTTORE PER LA TAGLIA DEI FUSIBILI

AVVIATORE O CONTROLLORE MOTORE MONTATO A PARTE; VEDI SCHEMA ELETTRICO UNIFILARE O TABELLE PER DESCRIZIONE.

Y

X

X20A3P

X100AF80AT3P

MCCBICCBLVPMCP

TYPES:

----

MOLDED CASEINSULATED CASELOW VOLTAGE POWERMOTOR CIRCUITPROTECTOR(RATING PER CONNECTEDLOAD)

LOW - VOLTAGE CIRCUIT BREAKER (CB). RATINGAND NO. OF POLES AS SHOWN. WHEN SPECIFICTYPE, OTHER THAN MCCB, IS REQUIRED, XINDICATES TYPE.

LSIGA

TRIP UNIT:

-----

LONG TIME PICKUPSHORT TIME PICKUPINSTANTANEOUS PICKUPGROUND FAULT PICKUPARC FLASHMAINTENANCE

X

PANNELLO SOLARE

INVERTER-

~

(TARATURA A SECONDA DEL MOTORE COLLEGATO)

SIMBOLOGIA UNIFILARE, POTENZA E ILLUMINAZIONE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:23

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-001

ELE

CTR

ICA

L LE

GE

ND

1 -

LEGE

NDA

ELET

TRIC

A 1

KVK

164

14090167

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

SIMBOLOGIA UNIFILARE, POTENZA E ILLUMINAZIONE

S

XXX

CONDUIT RUN BETWEEN DEVICES CONCEALED INNON-ARCHITECTURALLY FINISHED AREAS OR UNDERFLOOR SLAB. CONDUIT AND CONDUCTOR SIZES SHALLBE THE SAME AS THE HOMERUN FOR THE CIRCUIT.

TWO RECEPTACLES IN 2-GANG BOX UNDER COMMON COVER PLATE

X

Y

PLUG-IN RECEPTACLE STRIP, QUANTITY AND SPACINGOF RECEPTACLES AS NOTED OR SPECIFIED

Z

CONDUIT TAG OR CIRCUIT NUMBER - WIREAND CONDUIT SIZE AS SPECIFIED IN CIRCUITSCHEDULE ON THE SHEETS

CONDUIT STUBBED OUT AND CAPPED

CIRCUIT CONTINUATION

WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, ALL OR PARTIAL EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

X

YZ

SIMPLEX RECEPTACLEX

Y

Z YX

GROUND ROD

GROUND CABLE

Y

X

SPECIAL-PURPOSE RECEPTACLE AS DEFINED ON PLANS

DUPLEX RECEPTACLE

WALL SWITCH

Y

X

Y

X

Y

X

SINGLE-FACED CEILING OR WALL MOUNTED EXIT LIGHT;DIRECTIONAL ARROWS (IF REQUIRED) AS INDICATED ON PLANS

DOUBLE-FACED CEILING OR WALL MOUNTED EXIT LIGHT;DIRECTIONAL ARROWS (IF REQUIRED) AS INDICATED ON PLANS

X

Y

X

YEMERGENCY LIGHT, REMOTE MOUNTED HEAD

X

YEMERGENCY LIGHT, 2 ATTACHED HEADS AS SHOWN

CEILING/PENDANT MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, ALL OR PARTIAL EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

YXZ WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED

CEILING/PENDANT MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIEDY

X

Z

WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIEDX

YZ

CEILING/PENDANT/BOLLARD MOUNTED LUMINAIRE, LAMP TYPE ASSPECIFIED

X

YZ

CIRCUIT HASH MARKS (WHEN INDICATED); LONG,SHORT, SINGLE DOT, AND DOUBLE DOT REPRESENTPHASE, NEUTRAL, EQUIPMENT GROUND, AND ISOLATEDEQUIPMENT GROUND, RESPECTIVELY. #12 IN 3/4"CONDUIT UNLESS OTHERWISE INDICATED.

CIRCUIT RUN BETWEEN DEVICES EXPOSED INNON-ARCHITECTURALLY FINISHED AREAS; CONCEALEDIN ARCHITECTURALLY FINISHED AREAS. CONDUIT ANDCONDUCTOR SIZES SHALL BE THE SAME AS THEHOMERUN FOR THE CIRCUIT.

HOMERUN TO PANELSINGLE PHASE: 2-4.0mm2, 1-4.0mm2 G IN 20mm CTHREE PHASE: 2-4.0mm2, 1-4.0mm2 G IN 20mm CUNLESS OTHERWISE NOTED

CONDUIT TURNING DOWN

CONDUIT TURNING UP

X

Y

SUBSCRIPTS:

X - INDICATES TYPE GFI - GROUND FAULT CIRCUIT INTERRUPTER

IG - ISOLATED GROUNDTR - TAMPER RESISTANTPLH - PLUG LOAD HALF CONTROLLEDPLD - PLUG LOAD DUAL CONTROLLEDUSB - USB CHARGING STATIONSPD - SURGE PROTECTIVE DEVICE

Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD

XXXOR

X

YZ

X

YZ

CEILING/PENDANT/BOLLARD MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

CORD AND PLUG CONNECTION

WALL MOUNTED FLOOD LUMINAIRE, LAMP TYPE AS SPECIFIED

POLE/STANCHION MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED

POLE/STANCHION MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)

POLE/STANCHION MOUNTED FLOOD LUMINAIRE, LAMP TYPE AS SPECIFIED

X

YZ

X

YZ

X

YZ

X

YZ

PHOTOCELLPC

X - INDICATES TYPE

NONE

234KPL

DMMC

T

----------

SINGLE POLEDOUBLE POLETHREE-WAYFOUR-WAYKEY SWITCHPILOT LIGHTLIGHTED HANDLEDIMMINGMOMENTARY CONTACTTIMER

Y - INDICATES CONTROLLING SWITCH (IF REQUIRED)

X - INDICATES LUMINAIRE TYPE PER LUMINAIRE SCHEDULE

Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD

Z - INDICATES CONTROLLING SWITCH (IF REQUIRED)NL - NIGHT LIGHT UNSWITCHED

SUBSCRIPTS:

LIGHTING FIXTURE SUBSCRIPTS:

GENERAL NOTES:

S MANUAL MOTOR STARTERX

Y

X - INDICATES TYPE

MTEFT

---

HORSEPOWER RATEDHORSEPOWER RATED WITH THERMAL ELEMENTHORSEPOWER RATED WITH FUSETRON FUSE

Y - INDICATES SWITCH TYPE

SUBSCRIPTS:

NONER

--

TOGGLE SWITCH TYPEROTARY SWITCH TYPE

X

Y

X

YOR

X

Y

CONDUIT CONNECTION TO EQUIPMENT

1. THIS IS A STANDARD ELECTRICAL SYMBOLOGY SHEET. NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT.

LIGHTING CONTROL STRATEGY. SEE CORRESPONDING SCHEDULEX

LOW VOLTAGE WALL MOUNTED LIGHTING CONTROL STATION. NUMBER INDICATES QUANTITY OF PUSHBUTTONS PER SINGLE GANG PLATE. LETTER INDICATES CONTROL ZONE WHEN SHOWN

2a

S

Z

CORPO ILLUMINNTE A PARETE, LAMPADA COME INDICATO, TUTTO O IN PARTE DI EMERGENZA (GRUPPO DI ALIMENTAZIONE INTERNO O ESTERNO COME INDICATO)

X

YZ

Z YX

INTERRUTTORE A PARETE

INDICIX INDICA IL TIPONONE - UNIPOLARE2 - 2 POLI3 - 3 VIE4 - QUATTRO VIEK - INTERRUTTORE A CHIAVEP - LAMPADA PILOTAL - MANIGLIA LUMINOSADM - DIMMINGMC - CONTATTO MOMENTANEOT - TEMPORIZZATOY - INDICA IL CONTROLLO DELL'INTERRUTTORE (SE RICHIESTO)

Y

X

Y

X

Y

X

LAMPADA VIA D'USCITA UNA FACCIA , MONTAGGIO A SOFFITTO O PARETE CON FRECCE DIREZZIONALI (SE RICHIESTE) COME INDICATO IN PIANTA.INDICE CORPI ILLUMINANTI:X - INDICA IL TIPO COME DA TABELLA CORPI ILLUMINANTIY - INDICA IL NUMERO DEL CIRCUITO SU QUADROZ - INDICA L'INTERRUTTORE DI COMENDO (SE RICHIESTO)NL - LUCE NOTTURNA NON INTERROTTA

LAMPADA VIA D'USCITA DOPPIA FACCIA , MONTAGGIO A SOFFITTO O PARETE CON FRECCE DIREZZIONALI (SE RICHIESTE) COME INDICATO IN PIANTA.

X

Y

X

YLAMPADA DI EMERGENZA, CON SORGENTE DI LUCE REMOTA

X

YLAMPADA DI EMERGENZA, CON DOPPIA SORGENTE DI LUCE COME INDICATO

CORPO ILLUMINANTE TUTTO O IN PARTE DI EMERGENZA MONTATO A PLAFONEO/SOSPESO, TIPO DI LAMPADA COME INDICATO (SORGENTE DI ENERGIA INTERNA O ESTERNA COME INDICATO)

YXZ CORPO ILLUMINANTE DA PARETE, LAMPADA COME INDICATO

CORPO ILLUMINANTE A PLAFONE/SOSPENSIONE, LAMPADA COME INDICATOY

X

Z

LAMPADA A PARETE, TIPO DI LAMPADA COME INDICATOX

YZ

CORPO ILLUMINANTE MONTATO A PLAFONEO/SOSPESO/PALETTO, TIPO DI LAMPADA COME INDICATO

X

YZ

X

Y

X

YZ

X

YZ

CORPO ILLUMINANTE DI EMERGENZA MONTATO A PLAFONEO/SOSPESO/PALETTO, TIPO DI LAMPADA COME INDICATO (SORGENTE DI ENERGIA INTERNA O ESTERNA COME INDICATO)

CORPO ILLUMINANTE DI EMERGENZA A PARETE, TIPO DI LAMPADA COME INDICATO (SORGENTE DI ENERGIA INTERNA O ESTERNA COME INDICATO)

PROIETTORE MONTATO A PARETE, LAMPADA COME SPECIFICATO

CORPO ILLUMINANTE SU PALO/BRACCIO, LAMPADA COMEI NDICATO

CORPO ILLUMINANTE DI EMERGENZA SU PALO/BRACCIO, LAMPADA COMEI NDICATO (SORGENTE DI ENERGIA INTERNA O ESTERNA COME INDICATO)

PROIETTORE SU PALO/BRACCIO, LAMPADA COMEI NDICATO

X

YZ

X

YZ

X

YZ

X

YZ

FOTOCELLULAPC

S AVVIATORE MANUALE

INDICIX - INDICA IL TIPO

M - TAGLIA DI POTENZATE - TAGLIA DI POTENZA CON ELEMENTO TERMICOFT - TAGLIA DI POTENZA CON FUSIBILE FUSETRON

Y - INDICA IL TIPO DI INTERRUTTORENONE - INTERRUTTORE DEL TIPO A LEVAR - INTERRUTTORE ROTATIVO

X

Y

TIPOLOGIA DI CONTROLLO DELLA LUCE. VEDI TABELLA DI CORRISPONDENZA

X

PUNTO DI CONTROLLO IN BASSA TENSIONE, A PARETE, DELL'ILLUMINAZIONE. IL NUMERO INDICA LA QUANTITA' DEI PULSANTI PER CIASCUNA PLACCA. LA LETTERA INDICA LA ZONA DI CONTROLLO QUALORA MOSTRATA.

2a

XXX

TRATTA DI CIRCUITO TRA COMPONENTI A VISTA IN AREE ARCHITETTONICAMENTE NON RIFINITE, O SOTTO LA SOLETTA DEL PAVIMENTO. TUBI E SEZIONI DEI CAVI DEVONO ESSERE GLI STESSI DI QUELLI DEL CIRCUITO AL QUADRO

DOPPIA PRESA IN SCATOLA A DUE POSTI CON MOSTRINA UNICA

X

Y

STRISCIA DI PRESE, QUANTITA' E PSAZIATURA DELLE PRESE COME ANNOTATO O SPECIFICATO

TARGHETTA TUBO O NUMERO CIRCUITO -CONDUTTORI E DIMENSIONE TUBO COME SPECIFICATO SU TABELLA DEI CIRCUITI SULLE TAVOLE

TUBO TRONCATO E TAPPATO.

CONTINUAZIONE CIRCUITO

PRESA SEMPLICE

PEDICEX - INDICA IL TIPOGFI - INTERRUTTORE DIFFERENZIALEIG - TERRA ISOLATATR - RESISTENTE ALLA MANOMISSIONEPLH - SPINA DEL CARICO SEMICONTROLLATAPLD - SPINA FEL CARICO A DOPPIO CONTROLLOUSB - STAZIONE CARICA USBSPD - PROTEZIONE CONTRO LE SOVRATENSIONIY - INDICA IL NUMERO DEL CIRCUITO DEL QUADRO

X

Y

SPANDENTE DI TERRA

CAVO DI TERRA

Y

X

PRESA SPECIALE COME DEFINITO IN PIANTA

PRESA DOPPIA

MARCATURA CON TRATTI DEL CIRCUITO (QUANDO INDICATA): LUNGA, CORTA, PUNTO SINGOLO E DOPPIO PUNTO INDICANO FASE, NEUTRO, TERRA E TERRA ISOLATA. RISPETTIVAMENTE. 4 mm2 IN TUBI CONDUIT DA 20 mm SE NON DIVERSAMENTE INDICATO.

TRATTA DI CIRCUITO TRA COMPONENTI A VISTA IN AREE ARCHITETTONICAMENTE NON RIFINITE, INCASSATO IN AREE ARCHITETTONICAMENTE RIFINITE. TUBI E SEZIONI DEI CAVI DEVONO ESSERE GLI STESSI DI QUELLI DEL CIRCUITO AL QUADRO

COLLEGAMENTO AL QUADROMONOFASE 2-4mm2, Pe 1-4mm2, IN TUBO DA 20mmTRIFASE 3-4mm2, Pe 1-4 mm2 IN TUBO DA 20 mmSE NON DIVERSAMENTE INDICATO

TUBAZIONE VERSO IL BASSO

TUBAZIONE VERSO L'ALTO

XXXOR

CAVO E SPINA DI COLLEGAMENTO

NOTE GENERALI:

1. QUESTO E' UN FOGLIO DI SIMBOLI ELETTRICI STANDARD. NON TUTTI I SIMBOLI POTREBBEREO RISULTARE USATI IN QUESTO PROGETTO

X

Y

X

YOR

X

Y

TUBAZIONE DI COLLEGAMENTO ALLA APPARECCHIATURA

ONE-LINE, POWER, AND LIGHTING SYMBOLOGY

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:24

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-002

ELE

CTR

ICA

L LE

GE

ND

2 -

LEGE

NDA

ELET

TRIC

A 2

KVK

165

14090168

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

1. CONDUIT SIZES INDICATED ON DRAWINGS ARE MINIMUM ACCEPTABLE. ALL NEW CONDUITS SHALL BE SIZED TO PROVIDE SPARE CAPACITY IN ACCORDANCE WITH THE NEC.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING EXISTING CONDITIONS PRIOR TO BIDDING AND INSTALLATION.

3. THESE DRAWINGS ARE DIAGRAMMATIC AND REFLECT DESIGN INTENT ONLY. ALL UNDERGROUND CONDUITS, SLEEVES, FEEDS TO EQUIPMENT INSTALLATION AND PLACEMENT OF THAT EQUIPMENT SHALL BE VERIFIED IN FIELD AND WITH OTHER TRADES PRIOR TO INSTALLATION. SECURITY CONTRACTOR SHALL VISIT SITE PRIOR TO SUBMITTING BID AND NOTE ALL APPARENT FEATURES WHICH MAY AFFECT THE WORK OF THIS CONTRACT. NO SUBSEQUENT ALLOWANCES WILL BE MADE FOR FAILURE TO VISIT SITE PRIOR TO BID OR FOR LACK OF FIELD COORDINATION WITH THE WORK OF THE OTHER TRADES.

4. COORDINATE ELECTRICAL ROUGH-IN REQUIREMENTS WITH THE ELECTRICAL CONTRACTOR/TRADES AT ALL LOCATIONS OF ALL ELECTRICAL POWERED EQUIPMENT.

5. WHERE ROUTING OF RACEWAY/CONDUIT IS SHOWN ON PLANS TO PASS THROUGH WALLS AND PARTITIONS, CORE DRILL PENETRATIONS UNLESS SPECIFICALLY NOTED OTHERWISE. SIMILAR CUTTING AND PATCHING TO MATCH EXISTING SURFACES MAY BE UTILIZED WHERE CONDITIONS PERMIT.

6. ALL FLOOR AND WALL CONDUIT PENETRATIONS SHALL BE SLEEVED AND SEALED WITH AN INTUMESCENT FIRE RESISTIVE SYSTEM IN ACCORDANCE WITH N.E.C., N.F.P.A. AND DIVISION 07 OF THE SPECIFICATIONS.

7. ALL INTERIOR CONDUITS SHALL BE A MINIMUM OF 25 MM AND EXTERIOR CONDUIT SHALL BE A MINIMUM OF 25 MM UNLESS OTHERWISE NOTED. CONDUIT SIZES INDICATED SHALL BE THE MINIMUM SIZES UTILIZED.

8. ALL CONDUIT AND WIRING SHALL BE CONCEALED UNLESS OTHERWISE NOTED ON THE DRAWINGS AND/OR LOCATED IN ELECTRICAL, MECHANICAL OR STORAGE ROOMS OR SIMILAR UNFINISHED SPACES.

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATIONS OF PARTITIONS AND AVOIDING CONFLICTS WITH LIGHTS, DIFFUSERS, GRILLES, DUCTWORK, AND OTHER OBSTRUCTIONS.

10. CONDUIT RUNS INDICATED REFLECT DESIGN INTENT ONLY. ALL PULL BOXES AND JUNCTION BOXES SHALL BE SIZED IN ACCORDANCE WITH THE N.E.C. CONTRACTOR SHALL VERIFY QUANTITY AND LOCATION OF PULL BOXES AND JUNCTION BOXES IN ACCORDANCE WITH CABLE MANUFACTURERS RECOMMENDATIONS.

11. CONTRACTOR SHALL HAVE THE OPTION TO COMBINE HOMERUN CONDUCTORS OF REMOTE DEVICES OF SAME TYPE AND VOLTAGE CLASS AS PER THE N.E.C. SIZE CONDUIT AND INSTALL CONDUCTORS IN ACCORDANCE WITH THE N.E.C., N.F.P.A. AND DIVISION 26 OF THE SPECIFICATIONS.

12. COORDINATE EXACT LOCATION(S) OF CEILING MOUNTED EQUIPMENT/DEVICES WITH ARCHITECTURAL PLANS, REFLECTED CEILING PLANS, STRUCTURAL PLANS, AND ALL AFFECTED TRADES PRIOR TO CONSTRUCTION AND INSTALLATION.

13. ROUTE ALL HOMERUNS FROM ALL SECURITY DEVICES TO SECURITY EQUIPMENT CABINETS AS INDICATED ON PLANS.

14. COORDINATE EXACT LOCATIONS OF ALL DESKTOP/COUNTER MOUNTED SECURITY EQUIPMENT WITH MILLWORK/ CASEWORK AND FURNITURE PLANS PRIOR TO INSTALLATION.

15. WHERE DEVICES ARE INSTALLED IN FIRE RATED PARTITIONS, REVIEW SURFACE AND RECESS MOUNTING OPTIONS WITH THE ARCHITECT TO PRESERVE THE FIRE RATING.

16. ALL SECURITY EQUIPMENT AT EXTERIOR LOCATIONS ARE TO BE WEATHERPROOF RATED.

17. ALL CONDUIT BENDS SHALL BE LONG AND SWEEPING WITH A MINIMUM RADIUS OF 6 TIMES THE DIAMETER FOR CONDUITS UP TO 50 MM OR 10 TIMES FOR LARGER CONDUITS.

18. ALL SECURITY DEVICE WIRING AND INTERCONNECTIONS BETWEEN BUILDINGS MUST BE IN CONDUIT AND INACCESSIBLE TO PHYSICAL TAMPERING. AT LOCATIONS WHERE JUNCTION BOXES OR ELECTRICAL FITTINGS WOULD PROVIDE ACCESS, COVERS MUST BE SECURED WITH TORX W/ PEG TAMPER RESISTIVE HARDWARE TIGHTENED TO MANUFACTURER'S SPECIFICATIONS.

19. UNLESS OTHERWISE INDICATED ON THE DRAWINGS, ALL SECURITY DEVICES ARE TO BE MONITORED AND CONTROLLED FROM THE SECURITY CONTROL ROOM.

SECURITY GENERAL NOTES

RI

R

D

GOC

VIDEO SURVEILLANCE WORK STATION

DOOR POSITION SWITCH

CONNECTION TO ELECTRIC OR PNEUMATIC DOOR LOCK, DOOR POSITION SWITCH AND REQUEST TO EXIT SWITCH.

WALL MOUNTED CARD READER AT 1168 MM AFF.

CEILING MOUNTED MOTION SENSOR

CONNECTION TO ELECTRIC LOCK AND DOOR POSTION SWITCH

DESK/CASEMENT MOUNTED PUSH BUTTON DURESS ALARM WITHPATCH CORD TO WALL JACK.

STANCHION W/ CARD READER & CAMERA/ INTERCOM STATION

GATE OPERATOR CONTROL

SECURITY SYMBOLS LEGEND

AWG AMERICAN WIRE GAUGEC CONDUIT

CCTV CLOSED CIRCUIT TELEVISIONCKT ,CCT CIRCUIT

GFCI GROUND FAULT CIRCUIT INTERRUPTERGOVERNMENT FURNISHED CONTRACTOR INSTALL

GRD,GND,G GROUNDJB JUNCTION BOXMH MANHOLE, METAL HALIDE OR MOUNTING HEIGHTMLO MAIN LUGS ONLYN.C. NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENIC NOT IN CONTRACTN.O. NORMALLY OPENNTS NOT TO SCALE

PB PULLBOXPNL PANELPOE POWER OVER ETHERNETPP PATCH PANEL

PVC POLYVINYL CHLORIDEPWR POWERREC RECEPTACLERGS RIGID GALVANIZED STEELRX REQUEST TO EXIT, RECEIVER

TEL TELEPHONETGB TELECOMMUNICATIONS GROUNDING BUSBAR

TTB TELEPHONE TERMINAL BACKBOARDTV TELEVISIONTYP TYPICALUG UNDERGROUNDUON UNLESS OTHERWISE NOTED

VACVDC VOLTAGE DIRECT CURRENTVLAN VIRTUAL LOCAL AREA NETWORKWAN WIDE AREA NETWORK

ABBREVIATIONS

MS

PENDANT MOUNTED VIDEO CAMERA

CAMERA MOUNTED ON ELECTRICAL LIGHT POLE

RI CARD READER & CAMERA/ INTERCOM STATION

EMERGENCY FAST OPERATION BUTTON WITH PROTECTIVE COVER AT 1168 MM AFF.

MCP MASTER GRAPHIC CONTROL PANEL - COMMAND AND CONTROL

SEC SECURITY EQUIPMENT CABINET, NEMA 4X

IC WALL MOUNT INTERCOM STATION WITH INTEGRAL DOOR RELEASE PUSH BUTTON AT 1168 MM AFF.INTERCOM SUBSCRIPT

MV MASTER VIDEO INTERCOM STATIONC CAMERA INTERCOM STATION

J SECURITY FLOOR MOUNT JUNCTION BOX WITH MINIMUM (1) 38MM CONDUIT TURN UP TO ACCESSIBLE CEILING AS SHOWN ON FLOOR PLAN UNLESS OTHERWISE NOTED.

SECURITY SYMBOLS LEGEND

L

GFI,GF GROUND FAULT INTERRUPTER

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

PS POWER SUPPLY

TX TRANSCEIVER

UPS UNINTERRUPTIBLE POWER SUPPLYUTP UNSHIELD TWISTED PAIR

W WATTS OR WIREW/ WITHW/O WITHOUTWP WEATHERPROOF

VOLTAGE ALTERNATING CURRENT

WS WORK STATION

ACPACCESS CONTROL SYSTEMACSACCESS CONTROL PANEL

A AMPERE

SEC SECURITY EQUIPMENT CABINETSRV SERVER

D WALL MOUNTED WIRELESS DURESS RECEIVER.

CAM CAMERA

DSD DOOR SECURITY DEVICES

CEILING MOUNTED VIDEO CAMERA

TRAFFIC SIGNALTS

J LANE CONTROL SIGNALLCS

TCU TRAFFIC CONTROL UNIT

OS OVERWATCH SWITCH CONNECTION

HH HANDHOLE

J SIGNAL/HORN FOR WRONGWAY DETECTIONSH

LCP LOCAL CONTROL PANEL - GATE AND BARRIER MAINTENANCE

RCP REMOTE CONTROL PANEL - PORTABLE PLUG IN AT OVERWATCH

2 DUAL HEIGHTSUBSCRIPT

CAMERA MOUNTED ON SECURITY POLE

DIPOLE VEHICLE DETECTION LOOP

GATE OPERATION SIGNALS - STROB SIGNAL BEACONS

EFO

IC DESK MOUNT INTERCOM STATION WITH INTEGRAL DOOR RELEASE PUSH BUTTON.INTERCOM SUBSCRIPT

M MASTER VIDEO INTERCOM STATION

MOTOR

WALL MOUNTED VIDEO CAMERA P

W

O.D.D.S. OVER-SPEED AND DIRECTIONAL DETECTION SYSTEM

GOC

POSTAZIONE CONTROLLO VIDEOSORVEGLIANZA

CONTROLLO OPERATORE VARCO

TELECAMERA A SOSPENSIONE

TELECAMERA SU PALO ELETTRICO

MCP MASTER GRAPHIC CONTROL PANEL - COMMAND AND CONTROL

SEC CABINET APPARATI SICUREZZA , NEMA 4X

IC POSTAZIONE INTERCOM A PARETE CON PULSANTE APRIPRTA INTEGRATO 1168 MM DAL PAVIMENTO FINITO

PEDICE INTERCOM

MV - STAZIONE MASTER VIDEO INTERCOM

C - STAZIONE TELECAMERA INTERCOM

J CASSETTA SICUREZZA DI GIUNZIONE A PAVIMENTO CON MINIMO (1) TUBO 38 MM DI RISALITA FINO AL CONTROSOFFITTO ACCESSIBILE. COME INDICATO IN PIANTA SE NON DIVERSAMENTE INDICATO

LEGENDA SIMBOLI SICUREZZA

TELECAMERA A SOFFITTO

SEGNALE TRAFFICOTS

J CONTROLLO DI CORSIA

LCS

TCU UNITA' CONTROLLO TRAFFICO

OS INTERRUTTORE CONNESSIONE POSTO CONTROLLO

HH POZZETTO

J SEGNALE DIREZIONE ERRRATA

SH

LCP PANNELLO LOCALE DI CONTROLLO - MANUTENZIONE VARCO E BARRIERA

RCP PANNELLO REMOTO DI CONTROLLO - CONNESSIONE PORTATILE IN UNA GARITTA

TELECAMERA SU PALO SICUREZZA

IC POSTAZIONE INTERCOM DA TAVOLOCON PULSANTE APRIPRTA INTEGRATO 1168 MM DAL PAVIMENTO FINITO

PEDICE INTERCOM

M - STAZIONE MASTER VIDEO INTERCOM

TELECAMERA A PARETE

P

W

RI

R

D

INTERRUTTORE POSIZIONE PORTA

COLLEGAMENTO SERRATURA ELETTRICA O PNEUMATICA, INTERRUTTORE DI POSIZIONE PORTA E INTERRUTTORE RICHIESTA DI USCITA.

LETTORE DI SCHEDA MONTATO A PARETE A 1168MM DAL PAVIMENTO FINITO

SENSORE DI MOVIMENTO MONTATO A SOFFITTO

CONNESSIONE SERRATURA ELETTRICA E INYERRUTTORE DI POSIZIONE PORTA

PULSANTE ANTIRAPINA DA TAVOLO/BATTENTE CON CAVO DI COLLEGAMENTO A PRESA A PARETE

PIANTANA CON LETTORE DI SCHEDA E POSTAZIONE TELECAMERA/INTERCOM

MS

RI LETTORE DI SCHEDA E POSTAZIONE CAMERA/INTERCOM

PULSANTE RAPIDO DI EMERGENZA CON COPERCHIO PROTETTIVO A 1165 MM DAL PAVIMENTO FINITO

L

D RICEVITORE ANTIRAPINA SENZA FILI MONTATO A PARETE

2 - DOPPIA ALTEZZA

PEDICE

SPIRA DIPOLO PER RILEVAZIONE VEICOLO

SEGNALI ATTIVITA' VARCO - FARI DI SEGNALE STROBO

EFO

MOTORE

LEGENDA SIMBOLI SICUREZZA

1. LE DIMENSIONI DEI TUBI INDICATI SUI DISEGNI INDICANO LA DIMENSIONE MINIMA ACCETTABILE. TUTTI I NUOVO TUBI DEVONO ESSERE DIMENSIONATI PER GARANTIRE UNA CPACITA’ DI RISERVA SECONDO NEC.

2. L’APPALTATORE E’ RESPONSABILE DELLA VERIFICA DELLE CONDIZIONI ESISTENTI PRIMA DELLA OFFERTA E DELLA INSTALLAZIONE.

3. QUESTI DISEGNI SONO SCHEMATICI E RIFLETTONO L’INTENTO DEL PROGETTO. TUTTI I TUBI INTERRATI, I MNICOTTI, LE ALIMENTAZIONI ALLE INSTALLAZIONI APPARECCHIATURE E IL POSIZIONAMENTO DI DETTE APPARECCHIATURE DEVE ESSERE VERIFICATO IN CAMPO E CON LE ALTRE FORNITURE RPIMA DELLA INSTALLAZIONE. L’APPALTATORE DELLA SICUREZZA DEVE VISITARE IL SITO PRIMA DI SOTTOMETTERE OFFERTA E NOTARE TUTTI GLI ASPETTI CHE POSSANAO INFLUENZARE IL LAVORO DI QUESTO CONTRATTO. NON VERRANNO EFFETTUATE CONCESSIONI SUCCESSIVE PER MANCATA VISITA DEL SITO PRIMA DELL'OFFERTA O PER MANCANZA DI COORDINAMENTO IN CAMPO CON I LAVORI DELLE ALTRE DISCIPLINE.

4. COORDINARE I REQUISITI ELETTRICI DI MASSIMA CON L’APPALTATORE ELETTRICO/ALTRI FORNITORI IN TUTTE LE POSIZIONI DI APPARECCHIATURE CON ALIMENTAZIONE ELETTRICA.

5. OVE IL PERCORSO DEI CAVIDOTTI/TUBI E’ MOSTRATO IN PIANTA ATTRAVERSARE PARETI O SEPARAZIONI, EFFETTUARE LE PENETRAZIONI CON TRAPANO SE NON DIVERSAMENTE INDICATO. SIMILMENTE TAGLI E RATTOPPI PER RIPRISTINO CON LE SUPERFICI ESISTENTI POSSONO ESSERE IMPIEGATI DOVE LE CONDIZIONI LO PERMETTANO.

6. TUTTI GLI ATTRAVERSAMENTI DI PAVIMENTI E PARETI DI TUBAZIONI DEVONO ESSERE DOTATI DI MANICOTTI E SIGILLATI CON SISTEMI INTUMESCENTI RESISTENTI AL FUOCO IN CONFORMITA’ A N.E.V., NFPA E DIVISIONE 7 DELLE SPECIFICHE.

7. TUTTEL LE TUBAZIONI INTERNE ED ESTERNE DEVONO ESSERE DI DIAMETRO NON MINORE DI 25MM SE NON DIVERSAMENTE INDICATO. I DIAMETRI DEI TUBI INDICATI SONO I DIAMETRI MINIMI DA UTILIZZARE.

8. TUTTI I TUBI E LE CANALIZZAZIONI DEVONO ESSERE SOTTO TRACCIA TRANNE CHE DIVERSAMENTE INDICATO SUI DISEGNI E/O UBICATI NEI LOCALI ELETTRICI, MECCANICI O DEPOSITI O LOCALI SIMIL CON PARETI A GREZZO.

9. L’APPALTATORE E’ RESPONSABILE DELLA VERIFICA DELLE POSIZIONI DELLE PARETI E DI EVITARE CONFLITTI CON LAMPADE, DIFFUSORI, GRIGLIE, CANALI ARIA ED ALTRE OSTRUZIONI.

10. IL PERCORSO DEI TUBI INDICATO RIFLETTE SOLO L’INTENTO DI PROGETTO. TUTTE LE SCATOLE DI INFILAGGIO E DI GIUNZIONE DEVONO ESSERE DIMENSIONATE IN ACCORDO CON N.E.C.. L’APPALTATORE DEVE VERIFICARNE LA QUANTITA’ E LA POSIZIONE IN ACCORDO CON LE PRESCRIZIONI DEL PRODUTTORE DEI CAVI.

11. L’APPALTATORE HA LA POSSIBILITA’ DI RAGGRUPPARE PIU’ CIRCUITI DI COMPONENTI REMOTI DELLO STESSO TIPO E CLASSE DI TENSIONE SECONDO DIMENSIONAMENTO N.E.C. DELLE TUBAZIONI E INSTALLARE I CONDUTTORI IN CONFORMITA’ DI N.E.C., NFPA E DIVISIONE 26 DELLE SPECIFICHE.

12. COORDINARE L’ESATTA POSIZIONE(I) DELLE APPARECCHIATURE/COMPONENTI MONTATI A SOFFITTO CON LE PIANTE ARCHITETTONICHE, PIANTE RIFLESSE DEI SOFFITTI, PIANTE STRUTTURALI, E TUTTE LE OOPERAZIONI INTERESSSATE E PRIMA DELLA COSTRUZIONE E DELLA INSTALLAZIONE.

13. INDIRIZZARE TUTTE LE LINEE DAI COMPONENTI DELLA SICUREZZA AGLI ARMADI DELLA SICUREZZA COME INDICATO SULLE PIANTE.

14. COORDINARE L’ESATTA POSIZIONE DI TUTTI GLI APPARATI DI SICUREZZA MONTATI SU SCRIVANIE/RIPIANI CON LE LAVORAZIONI DI FORATURE E SCAFFALATURE E PIANTE DEGLI ARREDI PRIMA DELL’INSTALLAZIONE.

15. QUANDO I COMPONENTO SONO INSTALLATI IN SEPARAZIONI RESISTENTI AL FUOCO, RIVEDERE LE SUPERFICI E LE OPZIONI DI MONTAGGIO INCASSATO CON L’ARCHITETTO PER PRESERVARE LA PROTEZIONE AL FUOCO.

16. TUTTI I COMPONENTI DELL’IMPIANTO DI SICUREZZA MONTATI ALL’ESTERNO DEVONO AVERE CARATTERISTICHE DI RESISTENZA ALLE INTEMPERIE.

17. TUTTE LE CURVE DEI TUBI DEVONO ESSERE LUNGHI E CON CURVATURA DI RAGGIO MINIMO DI 6 VOLTE IL DIAMETRO PER TUBI FINO A 50MM DI DIAMETRO, E 10 VOLTE PER DIAMETRI SUOERIORI.

18. TUTTI I COLLEGAMENTI E INTERCONNESSIONI DEI DISPOSITIVI DI SICUREZZA TRA GLI EDIFICI DEVONO ESSERE IN TUBAZIONI ED INACCESSIBILI ALL’EFFRAZIONE FISICA. IN TUTTE LE POSIZIONI DEOVE LE SCATOLE DI GIUNZIONE O I RACCORDI ELETTRICI POTREBBERO FORNIRE ACCESSO, I COPERCHI DEVONO ESSERE ASSICURATI CON HARDWARE ANTIEFFRAZZIONE SERRATO SECONDO LE SPECIFICHE DEL PRODUTTORE.

19. SE NON DIVERSAMENTE INDICATO SUI DISEGNI , TUTTI I COMPONENTI DI SICUREZZA DEVONO ESSERE MONITORATI E CONTROLLA

NOTE GENERALI SICUREZZA

ABBREVIAZIONI

AMPEREPANNELLO CONTROLLO ACCESSISISTEMA CONTROLLO ACCESSIAMERICAN WIRE GAUGE NOT TO BE USED , USE S.I. METRICTUBOTELECAMERACIRCUITOTV CIRCUITO CHIUSOCOMPONENTI SICUREZZA PORTAINTERRUTTORE PROTEZIONE GUASTO CIRCUITO A TERRAFORNITURA DEL GOVERNO MONTATA DALL’APPALTATOREINTERRUTTORE GUASTO A TERRATERRACASSETTA DI GIUNZIONEPOZZETTO, ALOGENURI METALLICI O ALTEZZA DI MONTAGGIOSOLO CONNESSIONI PRINCIPALINORMALMENTE CHIUSONATIONAL ELECTRICAL CODENON IN CONTRATTONORMALMENTE APERTOFUORI SCALASISTEMA RILEVAMENTO ECCESSO DI VELOCITA’ E DIREZIONESCATOLA DI INFILAGGIOQUADROPOWER OVER ETHERNETPANNELLO CONNESSIONEALIMENTAZIONE DI POTENZAPOLIVINILCLORUROPOTENZAPRESARIGICO ACCIAIO ZINCATORICHIESTA DI USCITA RICEVITORE.CABINET APPARATI DI SICUREZZASERVERTELEFONOSBARRA MESSA A TERRA TELECOMUNICAZIONISBARRA PRINCIPALE DI MESSA A TERRA TELECOMUNICAZIONITRANSCEIVERPANNELLO TERMINALE TELEFONICOTELEVISIONETIPICOSOTTERRANEOSE NON DIVERSAMENTE INDICATOGRUPPO DI CONTINUITA’COPPIA TWISTATA NON SCHERMATATENSIONE CORRETE ALTERNATA TENSIONE CORRENTE CONTINUAAREA VIRTUALE COMUNICAZIONE LOCALERETE GEOGRAFICA COMUNICAZIONEWATT O FILOCONSENZAPROTETTO DALLE INTEMPERIESTAZIONE DI LAVORO

AACPACSAWGCCAMCKT, CCTCCTVDSDGFCI.GFI,FGGRD,GND,GJBMHMLON.C.NECNICN.O.NTSO.D.D.S.PBPNLPOEPPPSPVCPWRRECRGSRXSECSRVTELTGBTMGBTXTTBTVTYPUGUONUPSUTPVACVDCVLANWANWW/W/OWPWS

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:10

:32

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-003

SE

CU

RIT

Y S

YM

BO

LS, L

EG

EN

DS

, AB

BR

EV

IAT

ION

S A

ND

NO

TE

S -

SIM

BOLI

DEI

TIT

OLI,

LEGE

NDE,

ABB

REVI

AZIO

NI E

NOT

E

IBF

166

14090169

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

F

C x

Cx

Cx

x

Cx

Cx

Cx

Cx C x

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

C x

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

CxC

x

C x

C x

C x

C x

C x

C x

C x

x

Cx Cx

Cx Cx

Cx

Cx

Cx

Cx

W

W

W

WW

W

W

WW

WW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W WW

W W W W W W W W W W W W W W W W W W

W

WW

WW

WW

WW

WW

W

W

W

W

W W W

W

W

W

WW

WW

W

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx SDx SDx

F

F

FF

FF

F

F F

F

F

F

F

F

F

FF F

F F

FF

F

Ex

Ex

Ex

E x

E x

E x

E x

E x

E x

Ex

Ex

Ex

Ex

Ex

E x

E x

E x

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

ExExExEx

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

SS x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SS x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

C x

F

X

X

X

X

X

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

XX

XX

XX

XX

XX

X

XX

XX

XX

XX

XX

X

X

X

X

X

X

S3

S2

S1

S4

S5

S6

S7

MH A8.1

HH A9

MH A12.1

HH A9A

MH A9

7

5

4

6

3

5

2

MH A9C

CxCx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

CO

MM

CO

MM

COM

MC

OM

MC

OM

M

Cx

HH A229

1

1

9

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

CO

MM

MH A9D

MH A9B8

AR

EA

A1

EN

TRY

CO

NTR

OL

PO

INT

NA

VA

L FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TEM

CO

MM

AN

D ~

ATL

AN

TIC

1917 S. 67TH STOMAHA, NE 68106-2973

(402) 399-1000

GENERAL NOTES

3010 40m201:400

0

1. ADJUST TO GRADE

2. REMOVE FIBER OPTIC AND COPPER CABLES INSIDE THE TELECOMMUNICATIONROOM IN BLDG 103. PULL COPPER BACK TO HAND HOLE HH A9. SEAL END OF CABLE,NEATLY COIL CABLE AND PROVIDE LABEL. PULL FIBER OPTIC CABLE FO 110-103, 1-12BACK TO MANHOLE MH A9 AND RE-ROUTE TO THE EXISTING GUARD SHACK BLDG1001 TO PROVIDE TEMPORARY TELECOMMUNICATION SERVICE. ROUTE CABLE FROMMH A9 TO MH A8.1 THROUGH EXISTING DUCT. FROM MH A8.1 ROUTE CABLETHROUGH NEW DUCT BANK TO THE TELECOMMUNICATION ROOM IN THE GUARDSHACK. COORDINATE THE TERMINATION OF THE CABLE AND SERVICE CUTOVERWITH THE 31 COMM SQUADRON.

3. REMOVE FO CABLE AND DUCT BANK TO GUARD SHACK BLDG 1001 AFTER THEREROUTED FO CABLE FROM BLDG 103 IS TERMINATED IN THE GUARD SHACK ANDSERVICE IS REINSTATED.

4. REMOVE FIBER OPTIC AND COPPER CABLES INSIDE THE TELECOMMUNICATIONROOM. PULL CABLES BACK TO THE NEAREST MANHOLE MH A9A. SEAL ENDS OFCABLE NEATLY COIL AND LABEL.

5. REMOVE DUCT BANK FROM DEMOLISHED BUILDING BACK TO NEARESTMANHOLE/HAND HOLE. CAP AND SEAL THE DUCT PENETRATIONS IN THEMANHOLE/HAND HOLE.

6. PROVIDE ONE 2-INCH CONDUIT DIRECTIONALLY BORED UNDER ROAD FORREROUTED FO CABLE FOR TEMPORARY SERVICE TO THE GUARD SHACK. REMOVECONDUIT CAP AND SEAL THE DUCT PENETRATION IN MANHOLE WHEN GUARDSHACK IS DEMOLISHED.

7. REMOVE THE 12 STRAND OSP FIBER OPTIC CABLE LABELED 186-186_2 AND THE TWO100 PAIR COPPER CABLES LABELED CA0201 2401-2500 AND CA0201 2501-2600 INDUCT BANK FROM MH A9 TO BUILDING 186. IN MH A9 THE TWO 100 PAIR CABLES ARESPLICED TO ONE 200 PAIR CABLE WHICH IS THEN SPLICED TO A 3000 PAIR COPPERTRUNK. REMOVE THE TWO 100 PAIR COPPER CABLES, THE 200 PAIR SPLICEENCLOSURE AND THE 200 PAIR CABLE FROM THE 3000 PAIR SPLICE ENCLOSURE.

8. FOR INFORMATION ONLY: BUILDING 186 IS LOCATED APPROXIMATELY 65 METERSSOUTH OF THIS POINT. FIELD VERIFY EXACT LOCATION AND DISTANCE.

9. AFTER OSP CABLES ARE REMOVED FROM DUCTS REMOVE DUCT BANK AS REQUIREDTO ACCOMMODATE THE INSTALLATION OF THE SITE RETENTION POND. REMAINDEROF DUCT BANK MAY BE ABANDONED IN PLACE. PLUG ALL OPEN ENDS OF REMAININGDUCTS. THE BRACKETS SHOWN INDICATE THE APPROXIMATE AREAS OF DUCTBANK CONFLICTING WITH THE RETENTION PONDS. COORDINATE WORK WITHGRADING PLAN.

LEGEND LEGENDA

E-101SCALE:

TELECOMMUNICATIONS UTILITY DEMOLITION PLAN1:400

KEYNOTES

PLANNORTH

COMMUNICATION DUCTCAVIDOTTO TELECOMUNICAZIONI

COMMUNICATION DUCT DEMOLITIONDEMOLIZIONE CAVIDOTTO TELECOMUNICAZIONI

COMMUNICATION DUCT NOT IDENTIFIED ON SURVEY.ROUTING SHOWN WAS OBTAINED FROM UTILITY RECORDSPROVIDED BY 31 CS. FIELD VERIFY LOCATIONCAVIDOTTO TELECOMUNICAZIONI NON IDENTIFICATONELL'INDAGINE. IL PERCORSO MOSTRATO E' STATO RICAVATODA DOCUMENTAZIONE DEI SERVIZI FORNITO DA 31 CSVERIFICA DI PODIZIONAMENTO IN CAMPO

COMMUNICATION MANHOLEPOZZETTO TELECOMUNICAZIONI

Cx

COMM

1. THE EXISTENCE, SIZE AND/OR LOCATION OF UTILITIES ARE NOT GUARANTEED BYTHE SURVEY. FIELD VERIFY THE LOCATION OF ALL UTILITIES PRIOR TOCONSTRUCTION. A DIG PERMIT SHALL BE OBTAINED PRIOR TO CONSTRUCTION. ANYUTILITY DAMAGED SHALL BE REPAIRED AT NO ADDITIONAL COST TO THEGOVERNMENT. PROVIDE REPAIRS THAT ARE EQUAL TO OR EXCEED THE QUALITY OFTHE CONSTRUCTION PRIOR TO DAMAGE. UTILITIES NOT SHOWN ON DRAWINGS WILLBE COVERED UNDER SOLICITATION CLAUSE DIFFERING SITE CONDITIONS.

2. SCHEDULE AND COORDINATE ALL DEMOLITION WORK WITH THE CONTRACTINGOFFICER AND THE 31ST COMMUNICATIONS SQUADRON.

3. MAINTAIN EXISTING UTILITY SERVICES AT ALL TIMES EXCEPT WHEN SCHEDULEDWITH THE CONTRACTING OFFICER.

1. ADEGUARE AL LIVELLO

2. RIMUOVERE CAVI IN FIBRA OTTICA E RAME NEL LOCALE TELECOMUNICAZIONINELL’EDIFICIO 103. RIPIEGARE IL RAME AL POZZETTO HH A9. SIGILLARE LATERMINAZIONE DEL CAVO, PULIRE LA MATASSA DI CAVO ED ETICHETTARLA.RIPIEGARE IL CAVO IN F.O. 110-103, 1-12 AL POZZETTO MH A9 E REINDIRIZZARLOALL’ESISTENTE POSTO DI GUARDIA EDIFICIO 1001 PER FORNIRE UN SERVIZIOTEMPORANEO DI TELECOMUNICAZIONE. POSARE ILCAVO TRA MH19 E MH A8.1ATTRAVERSO CAVIDOTTO ESISTENTE . DA MH A8.1 POSARE IL CAVO IN NUOVOCAVIDOTTO AL LOCALE TELECOMUNICAZIONI NEL POSTO DI GUARDIA. COORDINARELA TERINAZIONE DEL CAVO E LA ATTIVITA’ DI TRASFERIMENTO CON IL 31°SQUADRONE TELECOMUNICAZIONI.

3. RIMUOVERE IL CAVO IN F.O. ED IL CAVIDOTTO AL POSTO DI GUARDIA EDIFICIO 1001DOPO LA TERMINAZIONE E LA MESSA IN SERVIZIO DEL CAVO REINDIRIZZATO IN F.O.DALL'EDIFICIO 103.

4. RIMUOVERE I CAVI IN F.O. ED IN RAME NEL LOCALE TELECOMUNICAZIONI. RIPIEGAREI CAVI AL VICINO POZZETTO MH 9A.. SIGILLARE LE TERMINAZIONI DEL CAVO, PULIRELA MATASSA DI CAVO ED ETICHETTARLA.

5. RIMUOVERE IL CAVIDOTTO DALL’EDIFICIO DEMOLITO FINO AL PIU’ VICNOPOZZETTO/CAMERETTA, E SIGILLARNE GLI ATTACCHI.

6. FORNIRE UN TUBO DA 2” INTERRATO SOTTO LA STRADA PER REINDIRIZZAMENTODEL CAVO IN FO DI SERVIZIO TEMPORANEO AL CORPO DI GUARDIA RIMUOVERE ILTAPPO TERMINALE DEL TUBO E SIGILLARE LA PENETRAZIONE NELLA CAMERETTAQUANDO IL CORPO DI GUARDIA VIENE DEMOLITO.

7. RIMUOVERE IL CAVO FO 12 FIBRE OSP ETICHETTATO 186-186_2BED I 2DUE CAVI INRAME A 100 COPPIE ETICHETTATI CA0201 2401-2500 E CA2501-2600 NEL CAVIDOTTODAL MH A9 ALL’EDIFICIO 186. NEL MH A9 I DUE CAVI A 100 COPPIE SONO GIUNTATI INUN CAVO A 200 COPPIE CHE E’ SUCCESSIVAENTE GIUNTATO AD UNA DORSALE DI3000 COPPIE. RIMUOVERE I DUE CAVI A 100 COPPIE, LA GIUNZIONE 200 COPPIE ED ILCAVO DA 200 COPPIE DALLA GIUNZIONE AL 3000 COPPIE.

8. SOLO PER INFORMAZIONE: L’EDIFICIO 186 E’ POSIZIONATO APPROSSIMATIVAMENTEA 65 METRI A SUD DI QUESTO PUNTO. VERIFICARE IN CAMPO L’ESATTA POSIZIONE ELA DISTANZA DAI CAVIDOTTI

9. UNA VOLTA RIMOSSI I CAVI OSP DALLE TUBZIONI RIMUOVERE I CAVIDOTTI COMERICHIESTO PER CONSENTIRE LA INSTALLAZIONE DELLA VASCA DI RITENUTADELL’AREA. LA RESTANTE PARTE DI CAVIDOTTO PUO’ ESSERE ABBANDONATA SULPOSTO. CHIUDERE TUTTE LE APERTURE DEI RIMANENTI CONDOTTI. LE PARENTESIMOSTRATE INDICANO L’APPROSSIMATIVA AREA DEL CAVIDOTTO IN CONFLITTO CONLA VASCA DI RITEGNO. COORDINARE IL LAVORO CON LA PIANTA DEL TERRENO.

NOTE CHIAVE

1. LA PRESENZA, DIMENSIONE E/O POSIIZIONE DI SERVIZI NON E’ GARANTITA DALSOPRALLUOGO. VERIFICARE IN CAMPO LA POSIZIONE DI TUTTI I SERVIZI PRIMA DELLACOSTRUZIONE. UN PERMESSO DI SCAVO DEVE ESSERE OTTENUTO PRIMA DELLACOSTRUZIONE. QUALSIASI DANNEGGIAMENTO DEI SERVIZI DEVE ESSERERIRPISTINATO SENZA ALCUNA SPESA AGGIUNTIVA PER IL GOVERNO. FORNIRERIPARZIONI CHE SIANO DI QUALITA’ UGUALE O SUPERIORE A QUELLE DEL SERVIZIOIPRIMA DEL DANNEGGIAMENTO. I SERVIZI NON MOSTRATI SUI DISEGNI SARANNOREGOLATI DA CLAUSOLA DI SOLLECITAZIONE PER DIFFERENTI CONDIZIONI DEL SITO.

2. PROGRAMMARE E COORDINARE TUTTI I LAVORI DI DEMOLIZIONE CON L’UFFICIALECONTRAENTE E IL 31° SQUADRONE TELECOMUNICAIONI.

3. 3. MANTENERE I SERVIZI ESISTENTI SEMPRE OPERATIVI, ECCETTUATO QUANDOPROGRAMMATO CON L’UFFICIALE CONTRAENTE.

NOTE GENERALI

PIANTA DEMILIZIONI SERVIZI DI TELECOMUNICAZIONE

C:\p

ww

orki

ng\c

entra

l01\

d182

7302

\P-2

3005

-163

1931

-E-1

01.D

WG

.dw

g, 9

, 4/6

/202

1 5:

39:3

2 P

M, L

TRA

VIS

C x

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx C x

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

C x

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

CxC

x

C x

C x

C x

C x

C x

C x

C x

x

Cx Cx

Cx Cx

Cx

Cx

Cx

Cx

W

W

W

WW

W

W

WW

WW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W

W WW

W W W W W W W W W W W W W W W W W W

W

WW

WW

WW

WW

WW

W

W

W

W

W W W

W

W

W

WW

WW

W

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx SDx SDx

Ex

Ex

Ex

E x

E x

E x

E x

E x

E x

Ex

Ex

Ex

Ex

Ex

E x

E x

E x

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

ExExExEx

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

Ex

ExSS x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SS x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

C x

1

11

1

1

1

1

1

S3

S2

S1

S4

S5

S6

S7

G103 B TOM

B04

TOM

B 98

TOM

B 96

TOM

B E 03

TOM

B 143

TOM

B 83

TOM

B 132

TOM

B 72

TOM

B 033

TOM

B 123

TOM

B 114

TOM

B 131

TOM

B 145

TOM

B 68

PLAV T2 01TOM

B01

TOM

B 019

TOM

B 013

GIA108 T14 TOM

TOM

B 055

TOM

B 82TO

MB 053

GLAV2 TG12 T01

TOM

B 86

TOM

B 92

TOM

B 61

TOM

B01

TOM

B 134

TOM

B E 01

TOM

B 116

TOM

B 95

TOM

B 80

TOM

B 020

TOM

B 125

TOM

B 037

TOM

B 71

TOM

B 99

TOM

B 024

TOM

B 117

TOM

B 81

G103 B TOM

B05

TOM

B 008

TOM

B 60

TOM

B 022

TOM

B 136

GIA108 TE TOM

B03

TOM

B 100

TOM

B 66

TOM

B 027

TOM

B 009

TOM

B 141

TOM

B 108

TOM

B 89

TOM

B 034

TOM

B 63

TOM

B 035

TOM

B 046

TUB VC4 TOB E 03

TOM

B 124

TOM

B 109

TUB VC4 TOB E 01

GIA108 T10 1 TOB

TOM

B 97

TOM

B 054

TOM

B 140

G103 B TOM

B06

TOM

B 044

TOM

B 77

TOM

B 137

TOM

B 111

G103 B TOM

B03

TOM

B 014

TUB VS4 E1 05 TB

AIULA1 TC O4TO

MB

TOM

B 012

TOM

B 76

TOM

B 005

TOM

B 144

TOM

B 90

TOM

B 120

TOM

B 67

TOM

B 93

GIA108 TOM

B F 03

GIA108 TE TOM

B02

TOM

B 023

AIULA1 TE 03 TOB

TOM

B 048

TOM

B 028

G103 B TOM

B01

TOM

B 050

TOM

B 010

TOM

B 047

TOM

B 79

TOM

B 139

TOM

B 004

TOM

B 007

TOM

B 130

TOM

B 043

TOM

B 103

G103 1 T6 06

TOM

B 64

TOM

B 056

TOM

B 041

TOM

B 017

TOM

B 127

GIA108 T13 TOM

B

TOM

B 003

TOM

B 045

TOM

B 039

TOM

B 104

TOM

B 040

TOM

B 026

TOM

B 121

TOM

B 74

TOM

B 110

TOM

B 051

TOM

B 052

TOM

B 84

IDRA 01

TOM

B 94

TOM

B 036

TOM

B 62

TOM

B 021

TOM

B 142

TOM

B 69

TOM

B 106TO

MB 65

TOM

B 57

TOM

B 018

TOM

B 118

TOM

B 87

TOM

B 58

TOM

B 101

TOM

B 138

TOM

B 113

TOM

B 59

TOM

B 91

TOM

B 006

TOM

B 135

TOM

B 011

TOM

B 78

TOM

B 85

TOM

B 030

GLAV2 T1 TOM

BTOT

TOM

B 129

G103 1 T6 TOM

B01

G103 B TOM

B02

TOM

B 105

TOM

B 049

TOM

B 112

TOM

B 016

TOM

B 038

TOM

B 73

TOM

B 75

TOM

B 015

TOM

B 029

TOM

B 126

TOM

B 133

TOM

B 042

TOM

B 128

TOM

B 156

TOM

B 155

TOM

B 154

TOM

B 153

TOM

B 152

TOM

B 151

TOM

B 149

TOM

B 150

TOM

B 157

TOM

B 159

TOM

B E 04

TOM

B E 05

TOM

B 146

TOM

B 163

TOM

B 147

TOM

B 161

TOM

B 160

TOM

B 158

GLAV2 TG12 T02

TOM

B 162

IDRA 02

1 3

5

4

2

6

AR

EA

A1

EN

TRY

CO

NTR

OL

PO

INT

NA

VA

L FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TEM

CO

MM

AN

D ~

ATL

AN

TIC

1917 S. 67TH STOMAHA, NE 68106-2973

(402) 399-1000

I HEREBY CERTIFY THAT THIS PLAN,SPECIFICATION, OR REPORT WAS PREPARED BY MEOR UNDER MY DIRECT SUPERVISION AND THAT I AM

A DULY LICENSED PROFESSIONAL ENGINEERUNDER THE LAWS OF THE STATE OF MINNESOTA.

PRINT NAME:

SIGNATURE:

DATE: LICENSE NO.

Andrew Kaner

52685

GENERAL NOTES

3010 40m201:400

0

LEGEND

E-102SCALE:

ELECTRICAL UTILITY DEMOLITION PLAN1:400

KEYNOTES

PLANNORTH

1. THE EXISTENCE, SIZE AND/OR LOCATION OF UTILITIES ARE NOT GUARANTEED BYTHE SURVEY. FIELD VERIFY THE LOCATION OF ALL UTILITIES PRIOR TOCONSTRUCTION. A DIG PERMIT SHALL BE OBTAINED PRIOR TO CONSTRUCTION. ANYUTILITY DAMAGED SHALL BE REPAIRED AT NO ADDITIONAL COST TO THEGOVERNMENT. PROVIDE REPAIRS THAT ARE EQUAL TO OR EXCEED THE QUALITY OFTHE CONSTRUCTION PRIOR TO DAMAGE. UTILITIES NOT SHOWN ON DRAWINGS WILLBE COVERED UNDER SOLICITATION CLAUSE DIFFERING SITE CONDITIONS.

2. SCHEDULE AND COORDINATE ALL DEMOLITION WORK WITH THE CONTRACTINGOFFICER AND THE 31ST COMMUNICATIONS SQUADRON.

3. MAINTAIN EXISTING UTILITY SERVICES AT ALL TIMES EXCEPT WHEN SCHEDULEDWITH THE CONTRACTING OFFICER.

1. LA PRESENZA, DIMENSIONE E/O POSIIZIONE DI SERVIZI NON E’ GARANTITA DALSOPRALLUOGO. VERIFICARE IN CAMPO LA POSIZIONE DI TUTTI I SERVIZI PRIMA DELLACOSTRUZIONE. UN PERMESSO DI SCAVO DEVE ESSERE OTTENUTO PRIMA DELLACOSTRUZIONE. QUALSIASI DANNEGGIAMENTO DEI SERVIZI DEVE ESSERERIRPISTINATO SENZA ALCUNA SPESA AGGIUNTIVA PER IL GOVERNO. FORNIRERIPARZIONI CHE SIANO DI QUALITA’ UGUALE O SUPERIORE A QUELLE DEL SERVIZIOIPRIMA DEL DANNEGGIAMENTO. I SERVIZI NON MOSTRATI SUI DISEGNI SARANNOREGOLATI DA CLAUSOLA DI SOLLECITAZIONE PER DIFFERENTI CONDIZIONI DEL SITO.

2. PROGRAMMARE E COORDINARE TUTTI I LAVORI DI DEMOLIZIONE CON L’UFFICIALECONTRAENTE E IL 31° SQUADRONE TELECOMUNICAIONI.

3. 3. MANTENERE I SERVIZI ESISTENTI SEMPRE OPERATIVI, ECCETTUATO QUANDOPROGRAMMATO CON L’UFFICIALE CONTRAENTE.

NOTE GENERALI

1. ADEGUARE AL LIVELLO

2. RIMUOVERE CAVI ELETTRICI DAL SEZIONATORE PRINCIPALENELL’EDIFICIO 103. RIPIEGARE I CAVI FINO ALPOZZETTO. PULIRE LA SPIRA AE ETICHETTARLA. TAPPARE ESIGILLARE LE PENETRAZIONI DEI CONDOTTI NEL POZZETTO.

3. RIMUOVERE CAVI ELETTRICI DAL SEZIONATORE PRINCIPALENELL’EDIFICIO 106. RIPIEGARE I CAVI FINO ALPOZZETTO. PULIRE LA SPIRA AE ETICHETTARLA. TAPPARE ESIGILLARE LE PENETRAZIONI DEI CONDOTTI NEL POZZETTO.

4. RIMUOVERE CAVI ELETTRICI E CAVIDOTTO ALLE UTENZE INCAMPO E AL CORPO DI GUARDIA EDIFICIO 1001.

5. RIMUOVERE CAVIDOTTI E POZZETTI COME RICHIESTO DALPOSIZIONAMENTO DELLA VASCA DI RITEGNO. ABBANDONARESUL POSRO LE TUBAZIONI NON INTERESSATE. CHIUDERE ESIGILLARE TUTTE LE APERTURE DEI CONDOTTI.

6. NUOVA LINEA MT COME DA PROGETTO ASJE 09-130 DALASCIARE AL SUO POSTO. COORDINARE CON CEN E GEO BASE.

NOTE CHIAVE

LEGENDA

PIANTA DEMOLIZIONI INFRASTRUTTURE ELETTRICHE

1. ADJUST TO GRADE

2. REMOVE ELECTRIC CABLES FROM MAIN SERVICE DISCONNECTIN BLDG 103. PULL CABLES BACK TO MANHOLE. NEATLY COIL,AND LABEL. CAP AND SEAL THE DUCT PENETRATIONS IN THEMANHOLE.

3. REMOVE ELECTRIC CABLES FROM MAIN SERVICE DISCONNECTIN BLDG 106. PULL CABLES BACK TO MANHOLE. NEATLY COIL,AND LABEL. CAP AND SEAL THE DUCT PENETRATIONS IN THEMANHOLE.

4. REMOVE ELECTRICAL CABLES AND DUCTBANK TO SITE LOADSAND BLDG 1001 GUARD SHACK.

5. REMOVE DUCTBANK AND MANHOLES AS REQUIRED TOACCOMMODATE RETENTION POND. ABAONDON IN PLACEUNAFFECTED DUCT. PLUG AND SEAL ALL DUCT OPENINGS.

6. NEW MV LINE WITH PROJECT ASJE 09-1030 TO REMAIN.COORDINATE WITH CEN AND GEO BASE.

EXISTING ELECTRICAL DUCT TO REMAINEx

ELECTRICAL DUCT DEMOLITION

ELECTRICAL MANHOLE

LINEA ELETTRICA ESISTENTE DA LASCIARE

DEMOLIZIONE CAVIDOTTO ELETTRICO

POZZETTO ELETTRICO

C:\p

ww

orki

ng\c

entra

l01\

d182

7302

\P-2

3005

-163

1931

-E-1

02.d

wg,

5, 4

/22/

2021

11:

08:4

4 A

M, L

TRA

VIS

X

X

X

X

XX

XX

XX

XX

X

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

XX

XX

XX

XX

X

XX

XX

XX

XX

X

X

X

X

X

SDx

F

F

C x

Cx

Cx

Cx

Cx

Cx

Cx

C x

CxCx

Cx

Cx

Cx

Cx

Cx

C x

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

Cx

C x

C x

C x

C x

C x

Cx Cx

Cx Cx Cx

Cx C

x

W

W

W

WW

WW

W

W

W

W

W

W

W

W

W

W

W

W

W

W

WW W W W W W W W W W W W W W

WW

WW

WW

W

W

WW W

W

W

W

WW

W

W

W

WW

WW

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

SDx

F

F

FF

FF

F

F FFF

F

F

F

F

F

F

FF F

F

F

F

F

F

F F

F

F

F

F

F

F

FF

F F

FF

F

F

FF

F

F

E x

E x

E x

E x

E x

Ex

Ex

Ex

Ex

E x

E x

Ex Ex

Ex

ExExEx

Ex

Ex

Ex

Ex

Ex

Ex

Ex

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SS x

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

SSx

C x

F

X

X

X

X

X

X

X

X

X

X

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

X

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

XX

X

X

X

W

W

W

WW

W

WW

F

F

F

FF

F

F

F

FF FSS

x

SS

SSx

AR

EA

A1

EN

TRY

CO

NTR

OL

PO

INT

NA

VA

L FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TEM

CO

MM

AN

D ~

ATL

AN

TIC

1917 S. 67TH STOMAHA, NE 68106-2973

(402) 399-1000

I HEREBY CERTIFY THAT THIS PLAN,SPECIFICATION, OR REPORT WAS PREPARED BY MEOR UNDER MY DIRECT SUPERVISION AND THAT I AM

A DULY LICENSED PROFESSIONAL ENGINEERUNDER THE LAWS OF THE STATE OF MINNESOTA.

PRINT NAME:

SIGNATURE:

DATE: LICENSE NO.

Andrew Kaner

52685

SEARCH OFFICEUFFICIO CONTROLLO

ID CHECK BOOTHCONTROLLO

GATEHOUSEORPO DI GUARDIA

4C - 110mm

3

2C - 4

0mm

2P - 4

0mm

EXISTING ITNITN ESISTENTE

2P - 140mm

B165 SUBSTATIONSOTTOSTAZIONE B165

OVERWATCH BOOTHGARITTA

GENERAL SHEET NOTES1. ROUTING OF DUCTBANKS SHOWN ARE DIAGRAMATIC. CONTRACTOR SHALL COORDINATE

WITH ALL NEW AND EXISTING UTILITES AND STRUCTURES AND ADJUST ROUTING ASREQUIRED TO AVOID INTERFERENCES. DO NOT EXCEED 130m BETWEEN CABLE ACCESSPOINTS.

2. NOT ALL CONDUITS ARE SHOWN. PROVIDE CONDUIT OF QUANTITY AND SIZES ASREQUIRED FOR FEEDER OR BRANCH CIRCUITS SHOWN ON ELECTRICAL PLANS ANDONELINE. REFER TO E-102.

3. 3PROVIDE A MINIMUM OF ONE EMPTY CONDUIT FOR POWER AND ONE EMPTY CONDUITFOR FOR TELECOMMUNICATIONS WITH PULL STRING AS SPARE. SPARE CONDUIT SIZESHALL MATCH LARGEST SIZE IN CORRESPONDING DUCTBANK.

1. TELECOMMUNICATION MANHOLE A12.1. EXTEND DUCT BANK INTO EXISTING MANHOLE.REPAIR MANHOLE AS REQUIRED AND SEAL DUCT PENETRATIONS..

2. ROUTE FO CABLE IN EXISTING DUCT BANK FROM MANHOLE A12.1 TO TERMINATION POINTIN THE INFORMATION TRANSFER NODE (ITN).

3. PROVIDE TWO CONDUITS FOR SECURITY, ONE CONDUIT FOR COMMUNICATION, AND ONESPARE CONDUIT. PROVIDE TWO 3-CELL FABRIC INNER DUCTS IN THE OCCUPIED CONDUITS.

4. STUB UP CONDUIT AND CAP FLUSH WITH PAVEMENT FOR SERVICE TO FUTURE GUARDBOOTH.

5. PROVIDE TWO 25MM COMMUNICATION CONDUITS.

6. PROVIDE TWO 50 MM COMMUNICATIONS CONDUITS.

7. PROVIDE THREE 50MM POWER CONDUITS.

8. PROVIDE TWO 50MM POWER CONDUITS.

9. PROVIDE CIRCUITS FROM SEARCH OFFICE PANEL SU TO ACTIVE VEHICLE BARRIERS.REFER TO PANEL SCHEDULE FOR DETAILS.

HHP2-(7)HHP3-(7)

HHC3-(7)

ID CHECK BOOTHCONTROLLO

2C - 103mm4P - 103mm

3

HHP1-(7)

TYP.4

SEARCH OFFICEUFFICIO CONTROLLO

GATEHOUSEORPO DI GUARDIA

1

2

3010 40201:500

0 50m

SCALE:

ELECTRICAL AND TELECOMMUNICATIONS DUCT BANK PLAN1:500

PLANNORTH

SCALE:

ENLARGED ID CHECK1:200

PLANNORTH 155 20m10

1:2000

SEE ENLARGED IDCHECK PLAN THIS SHEETVEDI INGRANDIMENTOPIANTA CONTROLLO SUQUESTA TAVOLA

8 5

7

6

7

67

6

GENERATORGENERATORE

GENERATORGENERATORE

FUTURE ID CHECK BOOTH

FUTURE ID CHECK BOOTHCONTROLLII FUTURI

E-103

HHP4-(9)

8 5 8 5

8 58 5

9

HHC2-(7)HHC1-(7)

2C - 40mm2P - 40mm

HHC5-(7)HHP5-(7)HHC4-(6)

1C - 110mm

2P -

140m

m1C

-110

MM

NOTE GENERALI DEL FOGLIO1. I PERCORSI DEI CAVIDOTTI MOSTRATI SONO SCHEMATICI. L’APPALTATORE DEVE

COORDINARLI CON TUTTI I NUOVI ED ESISTENTI SERVIZI A STRUTTURE ED AFFINARE ILPERCORSO COME RICHIESTO PER EVITARE INTERFERENCE. NON SUPERARE 130m TRA IPUNTI DI ACCESSO AL CAVO.

2. NON TUTTE LE TUBAZIONI SONO MOSTRATE. FORNIRE TUBAZIONI IN DIMENSIONE EQUANTITA’ NECESSARIA PER CIRCUITI DI ALIMENTAZIONE O DISTRIBUZIONENMOSTRATISULLE PIANTE ELETTRICHE E SUGLI SCHEMI UNIFILARI. VEDI E-102.

3. FORNIRE UN MINIMO DI UN CONDOTTO VUOTO DI RISERVA PER ENERGIA ED UNO VUOTO DIRISERVA PER TELECOMUNICAZIONI CON FILO PILOTA DI SCORTA. I TUBI DI RISERVADOVRANNO ESSERE DEL DIAMETRO PARI A QUELLO MASSIMO DELLE TUBAZIONI DELCAVIDOTTO.

NOTE CHIAVE1. CAMERETTA TELECOMUNICAZIONI A 12.1. PROLUNGARE IL CAVIDOTTO NELLA CAMERETTA

ESISTENTE, RIPARARLA COME RICHIESTO E SIGILLARE LE PENETRAZIONI DELLE TUBAZIONI.

2. INSTRADARE CAVO IN FO NEL CAVIDOTTO ESISTENTE DALLA CAMERETTA A12.1 AL PUNTOTERMINALENEL NODO DI TRASFERIMENTO DELLE INFORMAZIONI (ITN).

3. FORNIRE DUE TUBI PER LA SICUREZZA, UNO PER LE COMUNICAZIONI ED UN TUBO DI SCORTA. NEICONDOTTI UTILIZZATI FORNIRE DUE CONDUTTURE INTERNE A 3 CELLE.

4. RISALITA DELLA TUBAZIONE E CHIUDERE A FILO PAVIMENTO PER SERVIZIO DEL FUTURO POSTO DIGUARDIA.

5. FORNIRE DUE TUBI PER COMUNICAZIONI D 25 MM

6. FORNIRE DUE TUBI PER COMUNICAZIONI DA 50 MM

7. FORNIRE 3 TUBI DA 50MM PER ENERGIA

8. FORNIRE DUE TUBI DA 50 MM PER ENERGIA

9. FORNIRE I CIRCUITI DALL’UFFICIO DI ISPEZIONE ALLE BARRIERE PER VEICOLI DI TIPO ATTIVO.RIFERIRSI ALLE TABELLE DEI QUADRI PER DETTAGLI.

INGRANDIMENTO CONTROLLO

PLANIMETRIA CONDOTTI INTERRATI ELETTRICI E TELECOMUNICAZIONE

KEYNOTES

C:\p

ww

orki

ng\c

entra

l01\

d182

7302

\P-2

3005

-163

1931

-E-1

03.d

wg,

Lay

out1

, 4/7

/202

1 2:

27:3

0 P

M, L

TRA

VIS

TS

TS

LCP

LC

P

A3

EB105

A2

EC105

A2

EA106

A1

EA106

B2

E-509

A3

E-509

WRONG WAY DETECTION LOOP (TYP.)SPIRA RILEVAMENTO ERRORE DI PERCORSO (TIPICO)

A1

E-513

B4

E-512

BUILDING 110

HH

HH

HH

5TYP.

2TYP. U.N.O.

1

4

3

TYP.

A1

E-514

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/2

2/2

021

11:2

8:3

2 A

MB

IM3

60

://1

022

452

2_

NA

VF

AC

_A

1_

De

sig

n_

Avia

no_

Italy

_2

018

/102

245

22

-A-C

ano

py_

v2

018

.rvt

E-104

SE

CU

RIT

Y S

ITE

PLA

N -

PIAN

O DE

L SI

TO D

I SIC

UREZ

ZA

IBF

171

14090174

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 400 (AA201)A2

SECURITY SITE PLAN

KEY PLAN - PIANTA CHIAVE

SHEET KEYNOTES - NOTE CHIAVE

GENERAL NOTES - NOTE GENERALI

OVERWATCH

GATEHOUSESEARCH

ID CHECK

PLANNORTH

GRAPHIC SCALE: 1:400

0 84 1612 20 40

1. FOR SYMBOLS, ABBREVEATIONS AND GENERAL NOTES REFER TO DRAWING E-003.

1. (2) 50 MM CONDUITS TO SEC PANEL. REFER TO DRAWING EB105 FOR LOCATION AND DESCRIPTION.

2. (2) 50 MM CONDUITS (1) ACTIVE AND (1) SPARE WITH PULL WIRE TYPICAL.3. (1) 50 MM CONDUIT FROM OVERWATCH ENCLOUSER TO HH FOR CONNECTION TO

OVERWATCH MOBIL PANEL. 4. (2) 50 MM CONDUITS TO ELECTRICAL DUCTBANK BACK TO BUILDING 110. REFER TO

ELECTRICAL DRAWINGS FOR DUCTBANK. CONTRACTOR TO COORDINATE EXACT CONNECTION OF CONDUITS INTO DUCTBANK WITH ELECTRICAL CONTRACTOR. (1) CONDUIT ACTIVE (1) CONDUIT SPARE FOR FUTURE USE. SPARE CONDUIT SHALL BE PROVIDED WITH PULL WIRE.

5. CONDUIT FEEDS FOR SITE CAMERAS TO BE PROVIDED BY ELECTRICAL IN ELECTRICAL DUCTBANK. REFER TO ELECTRICAL DRAWINGS FOR LOCATION AND COORDINATION. TYPICAL FO ALL POLE MOUNTED CAMERAS.

PLANIMETRIA ESTERNA SICUREZZA

1. 2 TUBI 50 MM AL QUADRO SEC. RIFERIRSI AL DISEGNO EB105 PER POSIZIONAMENTO E DESCRIZIONE.

2. 2 TUBI 50 MM, 1 ATTIVO ED UNO DI RISERVA CON FILO PILOTA TIPICO.3. 1 TUBO DA 50 MM DAL RECINTO DELLA GARITTA A HH PER COLLEGAMENTO AL

PANNELLO MOBILE DELLA GARITTA 4. 2 TUBI DA 50 MM AL CAVIDOTTO ELETTRICO DI RITORNO ALL'EDIFICIO 110.

RIFERIRSI AI DISEGNI ELETTRICI PER IL CAVIDOTTO. L'APPALTATORE DEVE COORDINARE L'ESATTA CONNESSIONE DEI TUBI NEL CAVIDOTTO CON L'INSTALLATORE ELETTRICO. UN TUBO UTILIZZATO ED UNO DI RISERVA PER USO FUTURO. IL TUBO DI SCORTA DEVE ESSERE PROVVITO DI FILO PILOTA.

5. TUBI DI AIMENTAZIONE PER TELECAMERE DEVONO ESSERE FORNITI DALL'ELETTRICISTA NELLE CANALIZZAZIONI ELETTRICHE. RIFERIRSI AI DISEGNI ELETTRICI PER POSIZIONAMENTO E COORDINAMENTO. TIPICO PER TUTTE LE TELECAMERE MONTATE SU PALO.

1. PER SIMBOLI, ABBREVIAZIONI E NOTE GENERALI VEDI E-003

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

TS

TS

LCP

LCP

A3

EB105

A2

EC105

A2

EA106

A1

EA106

B2

E-509

A3

E-509

WRONG WAY DETECTION LOOP (TYP.)SPIRA RILEVAMENTO ERRORE DI PERCORSO (TIPICO)

A1

E-513

B4

E-512

BUILDING 110

HH

HH

HH

5TYP.

2TYP. U.N.O.

1

4

3

TYP.

A1

E-514

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:10

:38

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-105

SE

CU

RIT

Y S

ITE

PLA

N -

PIAN

O DE

L SI

TO D

I SIC

UREZ

ZA

IBF

171

14090174

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 400 (AA201)A2

SECURITY SITE PLAN

KEY PLAN - PIANTA CHIAVE

SHEET KEYNOTES - NOTE CHIAVE

GENERAL NOTES - NOTE GENERALI

OVERWATCH

GATEHOUSESEARCH

ID CHECK

PLANNORTH

GRAPHIC SCALE: 1:400

0 84 1612 20 40

1. FOR SYMBOLS, ABBREVEATIONS AND GENERAL NOTES REFER TO DRAWING E-003.

1. (2) 50.8MM CONDUITS TO SEC PANEL. REFER TO DRAWING EB105 FOR LOCATIONAND DESCRIPTION.

2. (2) 50.8 MM CONDUITS (1) ACTIVE AND (1) SPARE WITH PULL WIRE TYPICAL.3. (1) 50.8 MM CONDUIT FROM OVERWATCH ENCLOUSER TO HH FOR CONNECTION TO

OVERWATCH MOBIL PANEL. 4. (2) 50.8 MM CONDUITS TO ELECTRICAL DUCTBANK BACK TO BUILDING 110. REFER

TO ELECTRICAL DRAWINGS FOR DUCTBANK. CONTRACTOR TO COORDINATE EXACT CONNECTION OF CONDUITS INTO DUCTBANK WITH ELECTRICAL CONTRACTOR. (1) CONDUIT ACTIVE (1) CONDUIT SPARE FOR FUTURE USE. SPARE CONDUIT SHALL BE PROVIDED WITH PULL WIRE.

5. CONDUIT FEEDS FOR SITE CAMERAS TO BE PROVIDED BY ELECTRICAL INELECTRICAL DUCTBANK. REFER TO ELECTRICAL DRAWINGS FOR LOCATION AND COORDINATION. TYPICAL FO ALL POLE MOUNTED CAMERAS.

PLANIMETRIA ESTERNA SICUREZZA

1. 2 TUBI 50.8MM AL QUADRO SEC. RIFERIRSI AL DISEGNO EB105 PERPOSIZIONAMENTO E DESCRIZIONE.

2. 2 TUBI 50.8 MM, 1 ATTIVO ED UNO DI RISERVA CON FILO PILOTA TIPICO.3. 1 TUBO DA 50.8 MM DAL RECINTO DELLA GARITTA A HH PER COLLEGAMENTO AL

PANNELLO MOBILE DELLA GARITTA4. 2 TUBI DA 50.8MM AL CAVIDOTTO ELETTRICO DI RITORNO ALL'EDIFICIO 110.

RIFERIRSI AI DISEGNI ELETTRICI PER IL CAVIDOTTO. L'APPALTATORE DEVE COORDINARE L'ESATTA CONNESSIONE DEI TUBI NEL CAVIDOTTO CON L'INSTALLATORE ELETTRICO. UN TUBO UTILIZZATO ED UNO DI RISERVA PER USO FUTURO. IL TUBO DI SCORTA DEVE ESSERE PROVVITO DI FILO PILOTA.

5. TUBI DI AIMENTAZIONE PER TELECAMERE DEVONO ESSERE FORNITIDALL'ELETTRICISTA NELLE CANALIZZAZIONI ELETTRICHE. RIFERIRSI AI DISEGNI ELETTRICI PER POSIZIONAMENTO E COORDINAMENTO. TIPICO PER TUTTE LE TELECAMERE MONTATE SU PALO.

1. PER SIMBOLI, ABBREVIAZIONI E NOTE GENERALI VEDI E-003

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

F FF F F F F F

FF

F

9 10 11 12 13 14 15 16 17 18 19

4P250

4P630

4P250

4P250

4P160

4P160

4P400

4P630

4P630

4P100

4P100

225 500 160 175 100 160 300 400 400 100 100

lth x 10 lth x 10 lth x 10 lth x 10 lth x 10 lth x 10 lth x 10 lth x 10 lth x 10 lth x 10 lth x 10

FG7R3x95+1x95

FG70R2(3x120)+(1x120)

FG70R2(3x120)+(1x70)

FG70R2(3x120)+(2x95)

FG7R4x50

FG7R3x95+1x95

FG70R3x240+1x120

FG7R4x300

--

--

PANEL LAUNDRY

BUILDING 115

BUILDING 106

BUILDING 186

E.C.P. SERVICE PANEL

POWER FACTOR

COMP. SYS.

CENTRAL RIF. AUT

SPARE

RISERVA

SPARE

RISERVA

SPARE

RISERVA

SPARE

RISERVA

2A 2A 2A 2A 2A

3 3 3 3 3

DMM DMM DMM DMM DMM

TO PFCSTA 2000/5A

1

2A

3

4P2000 AF2000AT

20000AM

BTA

24Vcc

DMM

BAK

SECTION

SEZIONE"B"

VOLTAGE

TENSIONE380/220V-50Hz

lsc=40kA

3

BUILDING 165(SUBSTATION)

HAND HOLE

(N) SEARCH OFFICE

(N) U/G CONCRETE DUCTBANK

TERMINATE CIRCUIT IN DISTRIBUTION PANEL "DPS". REFER TO RISER DIAGRAM, SHEET E-502

CONFIRM TRIP SETTING IS SET FOR 400A

2A

DMM

FG7R4x300

2 3 4 5 6

4P250

4P250

4P32

4P1000

4P400

175 160 32 900 250

lth x 10 lth x 10 lth x 10 lth x 10 lth x 10

FG7R3x70+1x35

--

--

BUILDING110

PEDESTRI SPARERISERVA

2A 2A 2A 2A 2A

3 3 3 3 3

DMM DMM DMM DMM DMM

1

4P630

450

lth x 10

FG7R3x95+1x95

BUILDING 108

2A

3

DMM

FG7R3x70+1x35

FG7R3x95+1x70

SPARERISERVA

2A

3

4P1250 AF1000AT

10000AM

ATA

24Vcc

DMM

BAK

3

SECTION

SEZIONE"A"

VOLTAGE

TENSIONE220/127V-50Hz

lsc=40kA

TERMINATE FIBEROPTIC CABLE IN PV SOLAR MONITORING CABINET

TO FIBEROPTIC PATCH PANEL. COORDINATE WITH CE FOR EXACT LOCATION.

1

2

3

44

AL PATCH-PANEL F.O. COORDINARE CON CE PER L'ESATTA POSIZIONE

AL PATCH-PANEL F.O. COORDINARE CON CE PER L'ESATTA POSIZIONE TEMRINARE IL CAVO F.O.

NEL PANNELLO DI MINITOTAGGIO DEL PV SOLARE

(N) UFFICIO CONTROLLO

POZZETTO

EDIFICIO 165 (CABINA ELETTRICA)

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:25

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-501

PO

WE

R D

IAG

RA

MS

AN

D D

ETA

ILS

-DI

AGRA

MM

I E D

ETTA

GLI D

I POT

ENZA

KVK

172

14090175

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

B1SITE ONE LINE DIAGRAM

1 CONFIRM EXISTING CONDITIONS IN SUBSTATION PRIOR TO COMMENCINGWORK.

2 COORDINATE OUTAGES WITH BASE CE TO MINIMIZE DISRUPTIONS TOMISSION ACTIVITY.

1 INSTALL NEW FEEDER CIRCUIT FROM SPARE 400A BREAKER IN SWITCHGEARSECTION B, #16. UTILIZE EXISTING RELAY.

2 1x2-100mm CONDUIT DUCTBANK

3 INSTALL NEW DIGITAL MULTIMETER WITH CT'S, PT'S, AND WIRING. MATCHMAKE/MODEL OF EXISTING METERS. PROVIDE DATA CONNECTION FROMMETER TO EMCS (SAME BUILDING).

4 DISCONNECT AND REMOVE CABLE. CONDUIT, BREAKER, AND METER TOREMAIN FOR FUTURE USE.

SCHEMA UNIFILARE DEL SITO

1. CONFERMARE LE CONDIZIONI ESISTENTI NELLA SOTTOSTAZIONE PRIMA DI INIZIARE IL LAVORO

2. COORDINARE I FUORI SERVIZIO CON IL CE DELLA BASE PER MINIMIZZARE I DANNI ALLE ATTIVITA' DELLA MISSIONE.

1. INSTALLARE NUOVO CIRCUITO DDI ALIMENTAZIONE DA INTERRUTTORE DI RISERVA 400A NELLA SEZIONE DI QUADRO B, #16. UTILIZZARE LO SGANCIATORE ESISTENTE

2. 1x2-100mm CONDUIT DUCTBANK. CAVIDOTTO CON 2 TUBI DA 100MM.

3. INSTALLARE NUOVO MULTIMETRO DIGITALE CON RIDUTTORI E CABLAGGIO. STESSA TIPOLOGIA E MODELLO DI QUELLO ESISTENTE. FORNIRE COLLEGAMENTO DATI DAL MISURATORE AL EMCS (LO STESSO DELL'EDIFICIO).

4. SCOLLEGARE E RIMUOVERE CAVO. TUBAZIONE, INTERRUTTORE E MISURATORE RESTA PER USO FUTURO.

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTESNOTE GENRALI DI FOGLIO

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

G

200A(4P)

PANEL SE PANEL SU PANEL GL1PANEL SL1 PANEL GU PANEL GEPANEL SUT OW

UPS

UFFICIO CONTROLLO CORPO DI GUARDIA

100 KW

DISTRIBUTION PANEL

DPS

400A MCB

4-300mm2, 1-35mm2 GND,140mm C

4-50mm2, 1-10mm2 GND,50mm C

4-50mm2, 1-10mm2 GND,50mm C

ACTIVE VEHICLE BARRIER

60KVA/KW

4-95mm2, 1-16mm2 GND,60mm C

4-25mm2, 1-10mm2 GND,40mm C

4-25mm2, 1-10mm2 GND, 40mm C

4-25mm2, 1-10mm2 GND,40mm C

200A BREAKER

4-95mm2, 1-16mm2 GND,60mm C

4-95mm2, 1-16mm2 GND,60mm C

GENERATOR

ATS

SPD SPD SPD SPD SPD SPD SPD SPD

SURGE PROTECTIVE DEVICE (TYP)

FROM SUBSTATION (B165)

PANEL

4-25mm2, 1-10mm2 GND,40mm C

SPD

GARITTA

FROM ROOFTOP PV SYSTEMDAL SISTEMA FOTOVOLTAICO IN COPERTURA10kW, 400V, 3-PHASESEEAND

-C1 E-503-A1 E-5034-6mm2,

1-10mm2 GND,25mm C

LLA CABINA B165

1 BARRIERE VEICOLI ATTIVE

OVERWATCH

GATEHOUSESEARCH OFFICE

PROTEZIONE CONTRO LE SOVRATENSIONI (TIPICO)

63A MCB 200A MCB 100A MCB 63A MCB 100A MCB 63A MCB 63A MCB 63A MCB

SERVICE ENTRANCE EQUIPMENT(MAIN DISTRIBUTIONPANELBOARD DPS)

TYPICAL 400/230VPANELBOARD

G

N

G

N

MGB (SEARCH OFFICE)MGB (UFFICIO CONTROLLO)

70mm2

70mm2 CONNECTED TO GROUND RING70MM2 COLLEGATO ALL'ANELLO DI TERRA

LIGHTNING PROTECTIONDOWN CONDUCTORS

70mm2 AWG GROUND RING70MM2 ANELLO DI TERRA

SEARCH OFFICEUFFICIO CONTROLLO

G

GATEHOUSECORPO DI GUARDIA

MAIN400/230VPANELBOARD (SEPARATE BUILDING)QUADRO PRINCIPALE400/230V (EDIFICIO SEPARATO)

50mm2

25mm2 TO WATER PIPE25 MM2 ALLA TUBAZIONE IDRICA

25mm2 TO BUILDING STEEL25 MM2 ALLA STRUTTURA METALLICA FABBRICATO

25mm2 TO CONCRETEENCASED ELECTRODE25 MM2 ALL'ELETTRODO DEI FERRI DI FONDAZIONE

70mm2 CONNECTEDTO GROUND RING70MM2 COLLEGATO ALL'ANELLO DI TERRA

LIGHTNING PROTECTIONDOWN CONDUCTORS

50mm2 GROUND RING50MM2 ANELLO DI TERRA

N

MGB (GATEHOUSE)MGB (CORPO DI GUARDIA)

50mm2 GROUND RING50MM2 ANELLO DI TERRA

GENERATOR

70mm2 CONNECTED TO GROUND RING70MM2 COLLEGATO ALL'ANELLO DI TERRA

TO GENERATOR

ID CHECK

GB GB

70mm2 CONNECTEDTO GROUND RING70MM2 COLLEGATO ALL'ANELLO DI TERRA

16mm2

G

G

70mm2 TO GENERATOR GROUND RING

ATS

TO PANEL SE

N

PV ARRAY

2

LIGHTNING PROTECTIONDOWN CONDUCTORSCONDUTTORI CALATA PROTEZIONE ANTIFULMINE

TMGB

NEUTRO E TERRA DA CABINA B165

TMGB

G

SOLAR INVERTER

N

MGB (OVERWATCH)MGB (GARITTA)

70mm2 CONNECTED TO GROUND RING70MM2 COLLEGATO ALL'ANELLO DI TERRA

70mm2 AWG GROUND RING70MM2 ANELLO DI TERRA

OVERWATCHGARITTA

70mm2 TO CANOPY STRUCTURAL STEEL

G

N

APPARECCHIATURA INGRESSO SERVIZIO(QUADRO ELETTRICO PRINCIPALE DPS)NEUTRAL AND

GROUND FROM B165 SUBSTATION

70 MM2 ALL'ANELLO DI TERRA DEL GENERATORE

5

5

5

5

50mm2 GROUND RING50MM2 ANELLO DI TERRA

5

25mm2 TO WATER PIPE25 MM2 ALLA TUBAZIONE IDRICA

25mm2 TO BUILDING STEEL25 MM2 ALLA STRUTTURA METALLICA FABBRICATO

25mm2 TO CONCRETEENCASED ELECTRODE25 MM2 ALL'ELETTRODO DEI FERRI DI FONDAZIONE

6

6

6

MAIN400/230VPANELBOARD (SEPARATE BUILDING)QUADRO PRINCIPALE400/230V (EDIFICIO SEPARATO)

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:26

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-502

RIS

ER

DIA

GR

AM

& G

RO

UN

DIN

G D

IAG

RA

M -

SCHE

MA

RISE

R E

SCHE

MA

MES

SA A

TERR

A

KVK

173

14090176

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

C1ELECTRICAL RISER DIAGRAM

NOT TO SCALENON IN SCALA

A1GROUNDING DIAGRAM

1. ABBREVIATIONS:MGB - 300mm LONG POWER MAIN GROUNDING BAR.GB - 300mm LONG POWER GROUNDING BAR.TMBG - 300mm LONG TELECOMMUNICATIONS MAIN GROUNDING BAR

2. ALL CONDUCTORS SIZES BASED ON COPPER.

3. SEE SHEET 0E-503 FOR PV SOLAR SINGLE LINE DIAGRAM AND PV ARRAY ELEVATION.

1. PV SYSTEM WITH ANTI-ISLANDING PROTECTION AND RAPID SHUT-DOWN.

2. GROUND PV MODULE FRAME AND RACKING SYSTEM.

3. TO BUILDING STEEL, AND INVERTER GROUND BUS.

4. DO NOT GROUND NEUTRAL. SYSTEM NEUTRAL IS GROUNDED IN B165 SUBSTATION.

5. GROUND RODS CONNECTED TO GROUND RING

6. MANUFACTURER'S FRAME CONNECTION

1. SISTEMA FV CON PROTEZIONE ANTI-ISOLA E SPEGNIMENTO RAPIDO

2. METTERE A TERRA IL TEAIO DEL PANNELLO FV ED IL SISTEMA DI SUPPORTO

3. AI FERRI DELL'EDIFICIO, E SBARRA DI TERRA INVERTER

4. NON METTERE A TERRA IL NEUTRO, LA MESSA A TERRA DEL NEUTRO è EFFETTUATA NELLA CABINA B165.

5. SPANDENTI DI TERRA COLLEGATI ALL'ANELLO DI TERRA

6. MESSA A TERRA DEL QUADRO DA PARTE DEL COSTRUTTORE

1. ABBREVIAZIONI:MGB - SBARRA PRINCIPALE DI TERRA ELETTRICA 300 mm LUNGAGB - SBARRA DI MESSA A TERRA ELETTRICA 300 mm LUNGATMBG - SBARRA PRINCIPALE DI TERRA TELECOMUNICAZIONI 300mm LUNGA

2. TUTTE LE DIMENSIONI DEI CONDUTTORI SI RIFERISCONO AL RAME

3. VEDI TAV. 0E-503 PER SCHEMA UNIFILARE FV SOLARE E VISTA CAMPO FV

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTESNOTE GENRALI DI FOGLIO

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

SCHEMO RISER ELETTRICO

SCHEMO DI MESSA A TERRA

STRING INVERTER

TIPICO CIRCUITO SORGENTE: 13 MODULI FV IN SERIE

2 1

(+)

(-)

2 1

(+)

(-)

ARC FAULTDETECTOR

TO DC MONITORING

(+)

(-)

L1

L2

L3

400V21.7A

DCSWITCH

3 PHASE INVERTER

N

TO

DIS

TR

IBU

TIO

N P

AN

EL

DP

S

3

2

1

13 12

13 12

2-6mm2, 1000V CU, PV WIRE

1. PV MODULES - 10kW, 1000V, CRYSTALLINE PANELS. MODULES INCLUDE LEADS AND CONNECTORS. REFER TO SPECIFICATION 26 31 00.

2. INVERTER - 15kW, 400V, 3PH 4W, LISTED TO UL. INVERTER INCLUDES ANTI-ISLANDING PROTECTION, GROUND FAULT PROTECTION, AND AFCI CAPABILITY. REFER TO INSTALLATION MANUAL FOR REQUIREMENTS. REFER TO SPECIFICATION 26 31 00.

3. ARRAY CURRENT MONITORING.

4. REMOTE TRIP CONTROL BY EMERGENCY PUSHBUTTON AND BY FIRE ALARM CONTROL SYSTEM.

5. DC OPTIMIZER - 1000V, 10.4kW, TWO INPUTS

6. DDG - GENERATOR DEVICE

7. DDI - INTERFACE DEVICE (WITH <U RELAY AND RECLOSURE DEVICE). WHEN IN PRESENCE OF OTHER PV SYSTEM (AND DDI) INSIDE THE BASE ALL DDIs SHALL BE SWITCHED-OFF THROUGH "OR" LOGIC AT THE SAME TIME (CEI 0-16 ART.8.8.3.1)

8. PI - PROTECTION INTERFACE AS PER CEI 0-16 REQUIREMENT (WITH RELAYS 27-59-81)

9. SPI - INTERFACE PROTECTION SYSTEM (PI AND RELATED TRANSFORMER, UPS, MONITORING DEVICES)

10. UPS - AUXILIARY CONTINUOUS POWER SUPPLY COMPLYING WITH CEI 0-16 REQUIREMENT (ART. 8.5.12.4 . MINIMUM 1 HOUR AUTHONOMY)

4

4

1

DC OPTIMIZER

5

1. MODULO FV 10kW, 1000V, I PANNELLI CRISTALLINI INCLUDONO TERMINALI E CONNETTORI. RIFERIRSI ALLA SPECIFICA 26 31 00.

2. INVERTER - 15 kW, 400V, 3FASI 4 FILI, CERTIFICATO CE. L'INVERTER INCLUDE LA PROTEZIONE CONTRO IL FUNZIONAMENTO IN ISOLA, LA PROTEZIONE DI GUASTO A TERRA, E CAPACITA' DI INTERRUZIONE DELL'ARCO. RIFERIRSI AL MANUALE DI INSTALLAZIONE PER LE PRESCRIZIONI. RIFERORSI ALLA SPECIFICA 26 31 00

3. MONITORAGGIO DELLA CORRENTE DI CAMPO

4. CONTROLLO REMOTO DI SGANCIO DA PULSANTE DI EMERGENZA E DA SISTEMA DI ALLARME INCENDIO.

5. OTTIMIZZATORE CC - 1000V, 10.4 kW, DUE INGRESSI

6. DDG - DISPOSITIVO DI GENERATORE

7. DDI - DISPOSITIVO DI INTERFACCIA (CON RELE' DI MINIMA TENSIONE E DISPOSITIVO DI RICHIUSURA). QUANDO IN PRESENZA DI ALTRI IMPIANTI FOTOVOLTAICI (E DDI) NELLA BASE, TUTTI I DDI DEVONO ESSERE APERTI CON LOGICA "OR" IN CONTEMPORANEA (CEI 0-16 ART.8.8.3.1)

8. PI - PROTEZIONE DI INTERFACCIA CONFORME A CEI 0-16 (CON RELE' 27-59-81)

9. SPI - SISTEMA DI PROTEZIONE DI INTERFACCIA (PI E RELATIVI TRASFORMATORI, UPS, E DISPOSITIVI PER MONITORAGGIO)

10. UPS - ALIMENTATORE AUSILIARIO DI CONTINUITA' CONFORME A PRESCRIZIONE CEI 0-16 (ART. 8.5.12.4 . MINIMO 1 ORA DI AUTONOMIA)

TYPICAL SOURCECIRCUIT: 13 PVMODULES IN SERIES

PV INVERTER10KW, 400V

PV AC DISCONNECT30A

kWh

UPS

FO

FO

FO

FO

MONITORING/CONTROL CABINET

CT CABINET

PV METER

VOLTAGE REF.

F.O. TO B165 (SUBSTATION)

TO DISTRIBUTION PANEL "DPS"

4-6mm2, 1-10mm2 GND25mm C

NOTA:COORDINARE I REQUISITI CON L'ENERGY MANAGER DELLA BASE

REMOTE SHUTDOWN BUTTON (GATEHOUSE, CMND/CNTRL)PULSANTE SPEGNIMENTO REMOTO

NOTES:COORDINATE REQUIREMENTS WITH BASE ENERGY MANAGER.

9

7

108

6

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/7

/20

21 8

:49

:25

AM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-503

PV

SO

LAR

DE

TAIL

S -

DETT

AGLI

FOTO

VOLT

AICI

Checker

174

14090177

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

C1DC WIRING DIAGRAM

NOT TO SCALENON IN SCALA

A1AC SINGLE LINE DIAGRAM

SCHEMA ELETTRICO CC

SCHEMA UNIFILARE AC

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

KEYNOTES - NOTE CHIAVE

1. THE CONECTION OF THE PV SYSTEM TO THE ELECTRICAL NETWORK SHALL COMPLY WITH CEI 0-16 AND E-DISTRIBUZIONE REQUIREMENT.

2. COORDINATE REQUIREMENTS WITH BASE ENERGY MANAGER.

1. IL COLLEGAMENTO DELL'IMPIANTO FOTOVOLTAICO ALLA RETE ELETTRICA DEVE SODDISFARE I REQUISITI DELLA NORMA CEI 0-16 E QUELLI DI E-DISTRIBUZIONE.

2. COORDINARE I REQUISITI CON IL GESTORE DELL'ENERGIA DI BASE.

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

PV MODULE

STRING WIRING

TO INVERTER (SEARCH OFFICE)

JUNCTION BOX, TRANSITION TO UNDERGROUND

UNISTRUT P1000 OR APPROVED EQUIV.

LE

NG

TH

TO

SU

IT

(4) 3/8" Ø X 2" EMBED STAINLESS STEEL HILTI KB TZ OR APPROVED EQUIV. (CONCRETE OR FILLED CMU), OR (4) 3/8"Ø X 2" EMBED. HILTI HY20 OR APPROVED EQUIV. (HOLLOW MASONRY), OR (4) 1/4"Ø SCREWS (WOOD OR METAL STUD WALL)(4) HILTI KB TZ 3/8"DIAM. X 2" IN ACCIAIO INOX INCORPORATI, O EQUIVALENTI APPROVATI. (CEMENTO O BLOCCHI RIEMPITI CEMENTO), O (4) HILTI HY20 3/8"DIAM. X 2" O EQUIVALENTI APPROVATI IN BLOCCHI FORATI, O (4) VITI DA 1/4" DIAM. (LEGNO O ARMATURA METALLICA DI PARETI)

NEGATIVE HOMERUN

+

- + - + - + - +

- + - + - + - POSITIVE HOMERUN

+ -

- + - + - + - +

+ - + - +

JUMPER

-

E-504A4

E-504A3

NEGATIVE HOMERUN

POSITIVE HOMERUN

JUMPER

NOTE: SEE PLANS FOR EXACT MODULE QUANTITY AND LAYOUT.

TAPE LOCATIONPOSIZIONAMENTO NASTRO

NOTE:

1. LOCATE TAPE AT ALL DC CONDUCTOR TERMINATION2. REFER TO ELECTRICAL SPECIFICATIONS FOR COLOR CODING

NOTA:1. POSIZIONARE NASTRO A TUTTE LE TERMINAZIONI DI CONDUTTORI CC2. RIFERIRSI ALLE NOTE ELETTRICHE PER IL CODICE DEI COLORI

MIN. RADIUS 8X WIRE Ø(56mm)RAGGIO MINIMO 8 VOLTE DIAMETRO DEL CONDUTTORE

NOTE: ACTUAL WIRE ROUTING MAY VARY.NOTA: IL REALE PERCORSO DEI CAVI PUO' VARIARE

MIN. RADIUS FOR PV WIRE=

8X WIRE Ø (56mm)

PV WIRE

JUNCTION BOX ONBACK OF MODULESCATOLA DI GIUNZIONE SUL RETRO DEL MODULO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:27

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-504

PV

SO

LAR

DE

TAIL

S -

DETT

AGLI

FOTO

VOLT

AICI

KVK

175

14090178

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50C1

PV ARRAY ELEVATION

NOT TO SCALENON IN SCALA

A1TYP. WALL MOUNTED CONDUIT

NOT TO SCALENON IN SCALA

C3TYP. MODULE TO MODULE WIRE ROUTING

NOT TO SCALENON IN SCALA

A2DC CONDUCTOR TAPE LOCATION

NOT TO SCALENON IN SCALA

(E-504)A3

CONNECTOR WIRE BEND RADIUSNOT TO SCALENON IN SCALA

(E-504)A4

JBOX WIRE BEND DETAIL

SEZIONE CAMPO FOTOVOLTAICO TIPICO PERCORSO CAVI INTERCONNESSIONE PANNELLI

MONTAGGIO A PARETE (TIPICO) POSIZIONE NASTRO CONDUTTORE CC RAGGIO DI CURVATIURA DEL CAVO DI CONNESSIONE

PARTICOLARE CURVATURA CAVI ALLA SCATOLA DI GIUNZIONE

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

A

TOP, SIDES & BOTTOM#5 REINF. AT 150 EW

AND FIG. 12, SIZE 28 RESPECTIVELYFED. SPEC. A-A-60005 FIG. 4, SIZE 28FOR MANHOLE FRAME & COVER, SEE

SECTION A-A

BC 150

WITH CEMENT MORTARBRICK COLLAR LINED UP

GROUND ROD & CLAMP250

SLOPE 1:40

DUCT ENTRANCE

150

A

DUCT ENTRANCE

DEEP SUMP300 X 300 X 250

PLAN

MANHOLE DIMENSIONS

TYPE

1

2

A B C (AT HIGH PT.)

150

150300

150

150

150

1800 1800 2000

A

B

TO SUMP

LAP REINF. 600mm (TYP.)

WATERSTOP AT ALLCONSTR. JTS. (TYP.)

NOTES:

FOR DETAILS OF CABLE RACKS,DUCT ENTRANCE AND PULLING-INIRONS, SEE PLATE UG-7.

MINIMUM CONCRETE COMPRESSIVESTRENGTH SHALL BE 21 MPa.

1.

2.200025001800

25 PULLING-IN IRON

25 PULLING-IN IRON/o

/o

2.6m

75m

m

75m

m

50m

m C

LR

FINISH GRADEPAVIMENTO FINITO

.

.

LUMINAIRE POLEPALO ILLUMINAZIONE

ASOLA

GROUND STUDPERNO DI MESSA A TERRA

ANCHOR BOLTS, PER MANUFACTURERBULLONE DI ANCORAGGIO,SECONDO PRODUTTORE

BOND GROUND WIRE TO REBARCOLLEGARE CORDA DI TERRA AI FERRI DI ARMATURA

16mm2 EQUALLY SPACED,QTY 6

25mm2 TIES (RING BARS)CRAVATTE DA 25MM2 (FERRI AD ANELLO)

BOLT OR BASE COVERBULLONE O COPERTURA DELLA BASE

PACK GROUT UNDER POLE BASE TO ENSURE FULL CONTACT WITH FOUNDATION AND PREVENT LOOSENING OF LEVELING NUTS. PROVIDE DRAIN CHANNEL OR WICKING ROPE FOR DRAINAGE FROM THE POLE INTERIOR.CUSCINETTO DI MALTA SOTTO LA BASE DEL PALO PER GARANTIRE IL PIENO CONTATTO CON LA FONDAZIONE E PREVENIRE L'ALLENTAMENTO DEGLI SPESSORI DI LIVELLAMENTO. FORNIRECANALE DI DRENAGGIOO O CORDA TRASPIRANTE PER IL DRENAGGIO DAL'INTERNO DEL PALO.

150m

m

CONDUIT, QUANTITY AS REQUIRED

750m

m

BOND GROUNDWIRE TOGROUND RODCOLLEGARE IL CONDUTTORE DI TERRA ALLO SPANDENTE

GROUND RODSPANDENTE

16mm2 BARE COPPER GROUND WIRECORDA DI TERRA IN RAME NUDO DA 16MM2

75m

m C

LR

600mm

NOTE: COORDINATE WITH SECURITY DESIGN (B2-E509) FOR MOUNTING OF CAMERAS ON LIGHTING POLES.NOTE: COORDINARE CON IL PROGETTO DELLA SICUREZZA (B2-E509) PER IL MONTAGGIO DELLE TELECAMERE SUL PALO

75mm CLR

D

H

50m

m C

LR

2.6m

900m

m

75m

m C

LR

75m

m

75m

m

CONDUIT, QUANTITY AS REQUIRED

BOND GROUND WIRE TO REBARCOLLEGARE CORDA DI TERRA AI FERRI DI ARMATURA

16mm2 BARE COPPER GROUND WIRECORDA DI TERRA IN RAME NUDO DA 16MM2

16mm2 EQUALLY SPACED, QTY 6

25mm2 TIES (RING BARS)CRAVATTE DA 25MM2 (FERRI AD ANELLO)

BOND GROUNDWIRE TOGROUND RODCOLLEGARE CORDA DI TERRA ALLO SPANDENTE

ANCHOR BOLTS, PER MANUFACTURERBULLONE DI ANCORAGGIO,SECONDO PRODUTTORE

GROUND ROD

PACK GROUT UNDER POLE BASE TO ENSURE FULL CONTACT WITH FOUNDATION AND PREVENT LOOSENING OF LEVELING NUTS. PROVIDE DRAIN CHANNEL OR WICKING ROPE FOR DRAINAGE FROM THE POLE INTERIOR. USCINETTO DI MALTA SOTTO LA BASE DEL PALO PER GARANTIRE IL PIENO CONTATTO CON LA FONDAZIONE E PREVENIRE L'ALLENTAMENTO DEGLI SPESSORI DI LIVELLAMENTO. FORNIRE CANALE DI DRENAGGIOO O CORDA TRASPIRANTE PER IL DRENAGGIO DA L'INTERNO DEL PALO.

BOLT OR BASE COVERBULLONE O COPERTURA DELLA BASE

NOTE: COORDINATE WITH SECURITY DESIGN (B2-E509) FOR MOUNTING OF CAMERAS ON LIGHTING POLES.NOTE: COORDINARE CON IL PROGETTO DELLA SICUREZZA (B2-E509) PER IL MONTAGGIO DELLE TELECAMERE SUL PALO

FINISH GRADEPAVIMENTO FINITO

LUMINAIRE POLEPALO ILLUMINAZIONE

ASOLA

GROUND STUDPERNO DI MESSA A TERRA

P

P

P C C

CNOTE 1

DE

PT

H A

SS

PE

CIF

IED

75m

m M

INIM

UM

75mm MINIMUM 75mm MINIMUM300mm

DE

PT

H A

SS

PE

CIF

IED

75m

m M

INIM

UM

75m

m

MIN

IMU

MT

YP

ICA

L

NOTES:

1. NUMBER OF CONDUITS AS REQUIRED FOR THE APPLICATION.

2. P SUBSCRIPT ELECTRICAL POWER OR CONTROL CONDUIT.

3. C SUBSCRIPT COMMUNICATION (TELEPHONE, DATA, INSTRUMENTATION) CONDUIT.

CONCRETEENCASEMENT

WARNING TAPE

FINISH GRADE

MINIMUM

75mm MINIMUMTYPICAL

P

P

P C C

CNOTE 1

300m

m

75m

m M

INIM

UM

75mm MINIMUM 75mm MINIMUM

DE

PT

H A

SS

PE

CIF

IED

75m

m M

INIM

UM

75m

m

MIN

IMU

MT

YP

ICA

L

NOTES:

1. NUMBER OF CONDUITS AS REQUIRED FOR THE APPLICATION.

2. P SUBSCRIPT ELECTRICAL POWER OR CONTROL CONDUIT.

3. C SUBSCRIPT COMMUNICATION (TELEPHONE, DATA, INSTRUMENTATION) CONDUIT.

WARNING TAPE

FINISH GRADE

75mm MINIMUM TYPICAL

300mm

MINIMUM

750mm X 1200mm

600mm X 900mm

300mm X 600mm

300mm X 450mm

300mm X 300mm

HANDHOLE SIZINGDIMENSIONAMENTO POZZETTI

9

8

7

6

TYPE

5

CRUSHED ROCKROCCIA FRANTUMATA

150mm

PULL SLOT

150mm

250mm

150mm

LABEL

HANDHOLE REQUIREMENTS

1. HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A HEAVY WEAVE FIBERGLASS REINFORCING WITH COMPRESSIVE STRENGTH OF NO LESS THAN 70,000 kPA.

2. COVER AND BOX SHALL WITHSTAND A SERVICE LOAD OF NO LESS THAN 6,800 kg OVER A 250mm x 250mm AREA.

3. PROVIDE STAINLESS STEEL BOLTS AND INSERTS.4. PROVIDE WITH SOLID BOTTOM.5. PROVIDE LABEL "ELECTRICAL" FOR POWER HANDHOLES OR "TELEPHONE" FOR TELEPHONE

HANDHOLES, OR AS INDICATED.6. DEPTH OF HANDHOLE SHALL BE AS REQUIRED TO ALLOW DUCTBACK CONDUITS TO ENTER THE

HANDHOLE PERPENDICULAR.

STAINLESS STEEL HEX BOLT AND WASHERBULLONI ESAGONALI E RONDELLA IN ACCIAIO INOX

SKID RESISTANT SURFACESUPERFICIE ANTISCIVOLO

CONCRETE RING AROUND BOXANELLO DI CALCESTRUZZO INTORNO AL POZZETTO

BOX AND COVER

COMPACTED EARTHTERRENO COMPATTATO

SECTIONAL BOX WHEN REQUIREDPOZZETTO IN SEZIONI QUANDO RICHIESTO

CARATTERISTICHE POZZETTO

1. IL CORPO DEVE ESSERE IN CALCESTRUZZO CON POLIMERO RINFORZATOCON FIBRA DI VETRO A TESSUTO PESANTE CON RESISTENZA ALLA COMPRESSIONE NON INFERIORE A 70.000 Kpa

2. IL CHIUSINO ED IL CORPO DEVONO SOPPORTARE UN CARICO DI SERVIZIO NON INFERIORE A 6800kg SU UN AREA DI 250x250mm

3. FORNIRE BULLONI E INSERTI IN ACCIAIO INOSSIDABILE 4. FORNIRE FONDO CHIUSO5. FORNIRE MARCATURA “ELETTRICO” PER POZZETTI DI ENERGIA O “TELEFONO” PER POZZETTI

TELECOMUNICAZIONE, O COME INDICATO.6. LA PROFONDITA’ DEI POZZETTI SARA’ COME RICHIESTO PER CONSENTIRE L’INGRESSO

PERPENDICOLARE DELLE TUBAZIONI DEL CAVIDOTTO.

(mm)

NOTE:1. PER DETTAGLI DEI SUPPORTI CAVI,

INGRESSO TUBI E FERRI DI TIRO, VEDI PIASTRA UG-7

2. LA TENUTA MINIMA A COMPESSIONE DEL CALCESTRUZZO DEVE ESSERE 21 MPa

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:54

:30

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-505

ELE

CT

RIC

AL

DE

TAIL

S -

DETT

AGLI

ELET

TRIC

I

KVK

176

14090179

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

B2POLE BASE FOUNDATION

NOT TO SCALENON IN SCALA

C4POLE BASE FOUNDATION (RAISED)

NOT TO SCALENON IN SCALA

A1CONCRETE ENCASED DUCTBANK SECTION

NOT TO SCALENON IN SCALA

A2DIRECT BURIED CONDUITS(S) SECTION

NOT TO SCALENON IN SCALA

A3GROUND INSPECTION / TEST WELL DETAIL

NOT TO SCALENON IN SCALA

B1

STANDARD ELECTRICAL AND TELECOMMUNICATION HANDHOLE (NONTRAFFIC) (COMPOSITE/FIBERGLASS) TYPES 5, 6, 7, 8 & 9

NOT TO SCALENON IN SCALA

A4ELECTRICAL MANHOLE

PRE-CAST REINFORCED CONCRETE W/ CAST IRON LID GROUNDING INSPECTION/TEST WELL

20mm X 3m COPPER-CLAD STEEL GROUND ROD

20mm CAST BRONZE CALBE TO GROUND ROD CLAMP

COPPER CABLECOPPER CABLE

POZZETTO STANDARD ELETTRICO E TELECOMUNICAZIONI (AREA NON TRAFFICO) (FIBERGLASS COMPOSITO) TIPI 5,6,7,8 & 9

FONDAZIONE BASAMENTO PALO FONDAZIONE BASE PALO (IN RILEVATO)

SEZIONE CAVIDOTTO INCASSATO IN CALCESTRUZZO

SEZIONE CAVI DIRETTAMENTE INTERRATI PARTICOLARE ISPEZIONE/PROVA DI TERRA POZZETTO

CAMERETTA ELETTRICA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

9"

PROVIDE TWO HOLE BOLTED CONNECTORS WITH GROUND RATED BELLEVILLE WASHERS BETWEEN BUS AND CONNECTOR. PROVIDE FULL WRAP STRAP CONNECTORS. CLAMPING OF THE STRAPS SHALL BE WITH FULL SURFACE CLAMPING TOOL TO INSURE EVEN COMPRESSION AROUND THE CABLEFORNIRE CAPICORDA BULLONATI A DUE FORI CON RONDELLA DI TERRA BELLEVILLE TRA LA SBARRA ED IL CAPICORDA. FORNIRE UN CAPICORDA COMPLETAMENTE AVVOLGENTE. IL SERRAGGIO DEL CAPICORDA DEVE ESSERE EFFETTUATO CON UNA PINZA A SERRAGGIO COMPLETO DI TUTTA LA SUPERFICIE PER ASSICURARE L ASTESSA COMPRESSIONE INTORNO AL CAVO.

COPPER TMGB SIZE:100 mm HIGH BY 6 mm THICK BY 300 MM LONG MINIMUM.DIMENSIONI SBARRA DI TERRA IN RAME TMGB:100MM ALTEZZA X 6 MM SPESSORE PER 300MM LUNGHEZZA MINIMO.

25 mm SQ AWG MINIMUM GROUND WIRE TO PROTECTIVE ENTRANCE TERMINALS IN ROOM IF PRESENT.CAVO DI TERRA DA 25 MMQ MINIMO PER COLLEGAMENTO PET SE PRESENTE NEL LOCALE

STAND-OFF INSULATOR MOUNTED TO WALL. TYPICAL FOR TWO LOCATIONS.ISOLATORE DI DISTANZIAMENTO MONTATO A PARETE. TIPICO PER DUE DISPOSIZIONI

25 mm SQ AWG MINIMUM GROUND WIRE TO CABLE TRAY(S) IN ROOM.CAVO DO TERRA 25 MMQ MINIMO ALLA/E CANALINA/E NEL LOCALE

25 mm SQ AWG MINIMUM GROUND WIRE TO PANELBOARD ENCLOSURE IN ROOM.CAVO DO TERRA 25 MMQ MINIMO AL QUADRO ELETTRICO NEL LOCALE

25 mm SQ AWG MINIMUM GROUND WIRE TO CATV ENCLOSURE IN ROOM IF PRESENT.CAVO DO TERRA 25 MMQ MINIMO ALLA CASSETTA TVCC SE PRESENTE NEL LOCALE

GROUND WIRE TO EXPOSED BUILDING COLUMN IN ROOM IF PRESENT.CAVO DI TERRA ALLE COLONNE DELL’EDIFICIO SE A VISTA NEL LOCALE

25 mm SQ AWG MINIMUM GROUND WIRE TO METAL CONDUITS IN ROOM.CAVO DI TERRA 25 MMQ MINIMO ALLE TUBAZIONI METALLICHE NEL LOCALE

12"

95 mm SQ AWG GROUND WIRE TO BUILDING ELECTRICAL SERVICE MAIN GROUND BAR (MGB).CONDUTTORE DI TERRA DA 95MMQ ALLA SBARRA DI TERRA PRINCIPALE (MGB) DELL'EDIFICIO

16 mm SQ MINIMUMGROUND WIRE TOUNDERGROUNDCONDUIT STUB-UPS IF PRESENTCONDUTTORE DI TERRA DA 16 MMQ MINIMO AGLI INGRESSI DELLE TUBAZIONI INTERRATE SE PRESENTI

FINISHED FLOOR

16 mm SQ MINIMUMGROUND WIRE TO BUILDING OUTSIDE PLANT CONDUITS.CONDUTTORE DA 16 MMQ MINIMO DALL'EDIFICIO ALLA TUBAZIONE VERSO LA RETE ESTERNA

WALL

GROUND WIRETO EQUIPMENTCONDUTTORE DI TERRA ALLA APPARECCHIATURA

TMGB

STAND-OFF INSULATORMOUNTED TO WALLISOLATORE DI DISTANZIAMENTO MONTATO A PARETE

GROUND WIRETO EQUIPMENTCONDUTTORE DI TERRA ALLA APPARECCHIATURA

GATEHOUSESEARCH OFFICE

ID CHECK

ID CHECKOVER WATCH

BLDG110

(EXISTING)

24 STRAND SM FOFIBRA OTTICA MONOMODALE 24 FIBRE

12 STRAND SM FOFIBRA OTTICA MONOMODALE 12 FIBRE

(2) CAT 6

(2) CAT 6HHC2

HHC3

MH A12.1 (EXISTING)

EXISTING ITN ON 2ND FLOORITN EISTENTE AL 2° PIANO

TERMINATE FIBER OPTIC CABLE IN FO DISTRIBUTION PANELTERMINARE IL CAVO IN FIBRA OTTICA NEL PANNELLO DISTRIBUZIONE FO

HHC5

HHC1

PROVIDE BONDING LUG AT EACH END OF EACH CABLE TRAY SECTION AND CONNECT THE CABLE TRAY GROUND WIRE AT EACH LOCATION.FORNIRE UN MORSETTO DI COLLEGAMENTO A CIASCUNA ESTREMITÀ DI OGNI ELEMENTO DI CANALINA PER COLLEGAMENTO AL CAVO DI MESSA A TERRA DELLA CANALINA

PROVIDE 35 mm SQ COPPER CABLE TRAY GROUND WIRE THE ENTIRE LENGTH OF THE CABLE TRAY. PROVIDE WITH GREEN JACKETFORNIRE CAVO DI MESSA A TERRA IN RAME DA 35 mm2 , DI COLORE GIALLO/VERDE PER L’INTERA LUNGHEZZA DELLA CANALINA

CONDUIT WITH DATA, VOICE, OR CATV CABLE(S)TUBO CON CAVI DATI, VOCE,O TVCC

BELL BONDING BUSHING AT END OF CONDUIT BEFORE CABLE TRAY. PROVIDE 25mm SQ BONDING WIRE FROM BUSHING TO CABLE TRAY GROUND WIRE.GHIERA DI MESS A TERRA AL TERMINE DEL TUBO PRIMA DELLA CANALINA. FORNIRE COLLEGAMENTO IN CAVO DA 25MM SQ DALLA GHIERA AL CONDUTTORE DI TERRA DELLA CANALINA.

PROVIDE BONDING LUG ATEACH END OF EACH CABLETRAY SECTION AND CONNECT THE CABLE TRAY GROUND WIRE AT EACH LOCATION.FORNIRE CAPIPCORDA ALLA ESTREMITA’ DI OGNI ELEMENTO DI CANALINA E COLLEGARE LA CORDA DI TERRA DELLA CANALINA IN OGNI POSIZIONE.

DATA, VOICE, AND CATVCABLES IN CABLE TRAY.

SUPPORT HANGERS

CABLE TRAY SYSTEM

PROVIDE PROTECTIVE COATING OR SLEEVE OVER ALL EXPOSED THREADS AND SMILAR SURFACES, WHEN PROVIDED, FROM TOP OF TRAY TO 305 mm ABOVE THE TRAY.FORNIRE RIVESTIMENTO PROTETTIVO O MANICOTTI SOPRA TUTTE LE FILETTATURE E SUPERFICI SIMILARI, QUANDO FORNITO, A PARTIRA DALLA CANALINA FINO A 305 mm SOPRA DI ESSA

PROVIDE SUPPORT CABLES OR THREADED ROD ON EACH SIDE OF THE CABLE TRAY, SIZE AND SPACING, AS RECOMMENDED BY CABLE TRAY MANUFACTURER REQUIREMENTS FOR FULL CABLE TRAY AND SIESMIC REQUIREMENTS.FORNIRE CAVI DI SUPPORTO O ASTA FILETTATA SU OGNI LATO DELLA CANALINA, DIMENSIONAMENTO E SPAZIATURA, PRESCRIZIONI DI RIEMPIMENTO E SUPPORTO SISMICO COME CONSIGLIATO DAL PRODUTTORE CANALINA

2

3 14 DETAIL NOTES1. EXISTING EQUIPMENT CABINET WITH ACTIVE NETWORK

EQUIPMENT.

2. REMOVE THE 42 RU EQUIPMENT CABINET. REMOVE THE PDU & GROUNDING SYSTEM AND REINSTALL IN THE NEW EQUIPMENT CABINET. THE EXISTING CABINET DOES NOT CONTAIN ANY NETWORK EQUIPMENT OR CABLES.

3. PROVIDE 48 RU. 2135mm H x 685mm W x 915mm D EQUIPMENT CABINET TO MATCH SIZE (HxWxD) OF THE TWO EXISTING ACTIVE EQUIPMENT CABINETS.

4. PROVIDE 24 PORT FIBER OPTIC DISTRIBUTION PANEL TO TERMINATE OSP FIBER.

#

NOTE DEL PARTICOLARE1. ARMADIO APPARATI ESISTENTE CON APPARATI ATTIVI DI

RETE

2. 2. RIMUOVERE L’ARMADIO A 42 UNITA’. RIMUOVERE PDU E IL SISTEMA DI MESSA A TERRA E REINSTALLARLO NEL NUOVO ARMADIO APPARATI. L’ARMADIO ESISTENTE MON CONTIENE ALCUN APPARATO O CAVI DI RETE.

3. 3. FORNIRE UN ARMADIO APPARATI 48 RU 2135mm H x 685mm W x 915mm D , PER COMBACIARE CON LE DIMENSIONI DEI DUE ARMADI APPARATI ATTIVI ESISTENTI.

4. 4. FORNIRE UN PANNELLO DI DISRIBUZIONE FO A 24 PORTE PER TERMINARE LA FIBRA OSP.

#

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:30

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-506

TELE

CO

MM

UN

ICA

TIO

N D

ETA

ILS

-DE

TTAG

LI S

ULLE

TEL

ECOM

UNIC

AZIO

NI

KVK

177

14090180

JAZ LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

C1TYPICAL TELECOMMUNICATION MAIN GROUND BAR (TMGB)

NOT TO SCALENON IN SCALA

C3TYPICAL TMGB SIDE VIEW

NOT TO SCALENON IN SCALA

A1OUTSIDE PLANT (OSP) TELECOMMUNICATION RISER DIAGRAM

NOT TO SCALENON IN SCALA

C4TYPICAL CABLE TRAY MOUNTING AND BONDING

NOT TO SCALENON IN SCALA

A4BUILDING 110 ITN EQUIPMENT CABINET ELEVATION

SCHEMA VERTICALE TELECOMUNICAZIONI AREA ESTERNA (OSP) PROSPETTO ARMADIO APPARATI ITN EDIFICIO 110

TIPICO SBARRA PRINCIPALE DI MESSA A TERRA TELECOMUNICAZIONI (TMGB)

VISTA LATERALE TIPICA TMGB TIPICO MONTAGGIO E MESSA A TERRA CANALINA

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

120 mm SQUARE BY 55 mm DEEP JUNCTION BOX.

120 mm BY 120 mm PLASTER RING BOX COVER

DRYWALL

FLUSH MOUNTED COVER PLATE WITH OUTLETS AS IDENTIFIED.

CABLES IN 27 MM CONDUIT MINIMUM

BELL BONDING BUSHING AT END OF CONDUIT BEFORE CABLE TRAY. PROVIDE 25 mm SQ BONDING WIRE FROM BUSHING TO CABLE TRAY GROUND WIRE.

8P8COUTLET/CONNECTOR

TELECOMMUNICATIONOUTLET SINGLE GANGFACEPLATE WITH RECESSEDSINGLE OPENINGPLACCA PRESA TELECOMUNICAZIONE UN MODULO, CON UNICO TELAIO DI MONTAGGIO INCASSATO

MOUNTING LUG

MOUNTING LUG

LABEL OUTLETACCORDINGLYETICHETTA SECONDO PRESA RECESSED OUTLET

LABEL HOLDERPORTA ETICHETTA DELLA PRESA INCASSATO

TELECOMMUNICATION OUTLET SINGLE GANG FACEPLATE WITH (4) MODULAR OPENINGSPLACCA PRESA TELECOMUNICAZIONI UN MODULO CON 4 APERTURE MODULARI

8P8C OUTLET/CONNECTOR

4 PORT FACEPLATEPLACCA A QUATTRO PORTE

STANDARD OFFICE OUTLETPRESA STANDARD PER UFFICIO

PROVIDE BLANK INSERTS FOR UNUSED PORTSFORNIRE INSERTI BIANCHI PER PORTE NON UTILIZZATE

PROVIDE A CABLE MANAGEMENTSECTION UNDER EACH PATCH PANEL

20

19

18

17

4142

4344

48

4724

23

2246

45

21

12

11

10

9

3334

3536

40

3916

15

14

38

37

13

43

21

2526

2728

32

31 87

6

30

29

5

PPA

DAT

A

AFFIX PANEL IDLABLE ON LEFT SIDE

CABLE TO HAVE ID WITH OUTLET/PORTLABEL WITHIN 150 mm OF TERMINATIONCAVI CON IDENTIFICATIVO PRESA/PORTA ENTRO 150mm DALLA TERMINAZIONE

PROVIDE A 150 mm WIDE BY 150 mm DEEP HINGED WIRE MANAGEMENT ON EACH SIDE OF THE CABINET. FORNIRE UN SOSTEGNO INCERNIERATO PER I CAVI LARGO 150mm E PROFONDO 150mm

ALL PATCH PANELS SHALL HAVE SLIDE IN PLASTIC COVER TYPE LABEL ABOVE EACH PORT. STICK ON TAPE SHALL NOT BE ALLOWED. PROVIDE PORT LABEL IN THE INDICATOR WINDOW, PORT LABELS SHALL MATCH OUTLET LABELS. TUTTI I PANNELLI PATCH DEVONO AVERE UNA SLITTA DI COPERTURA DELLA TARGHETTA IN PLASTICA SU OGNI PORTA. NON E' AMMESSO L'IMPIEGO DI NASTRO ADESIVO. FORNIRE TARGHETTA DELLA PORTA NELLA FINESTRA DELL'INDICE. LE TARGHETTE DELLE PORTE DEVONO CORRISPONDERE A QUELLE DELLE PRESE.

PORTS SHALL BE LAID DOWN ON THE PATCH PANEL IN NUMERIC-ALPHA ORDER WITH THE LOWEST ROOM NUMBER BEING AT THE UPPERMOST LEFT PORTION OF THE FIRST PATCH PANEL AND THE HIGHEST ROOM NUMBER ON THE BOTTOM RIGHTLE PORTE DEVONO ESSERE DISPOSTE SUL PANNELLO PATCH IN ORDINE ALFA-NUMERICO CON IL PIU' BASSO NUMERO DI STANZA POSIZIONATO NELLA PARTE PIU' ALTA DEL LATO SINISTRO DEL PRIMO PANNELLO PATCH, ED IL NUMERO PIU' ALTO DI CAMERA NELLA PARTE IN BASSO A DESTRA.

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

670

124 D1124 D2

124 D3124 D4

124 D5124 D6

124 D7124 D8

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:31

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-507

TELE

CO

MM

UN

ICA

TIO

N D

ETA

ILS

-DE

TTAG

LI S

ULLE

TEL

ECOM

UNIC

AZIO

NI

KVK

178

14090181

JAZ LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

C4

TYPICAL TELECOMMUNICATION OUTLET,SINGLE GANG, RECESSED MOUNTING DETAIL

NOT TO SCALENON IN SCALA

A4OUTLET COVER PLATE CONFIGURATIONS

NOT TO SCALENON IN SCALA

A1PATCH PANEL

PANNELLO PATCH CONFIGURAZIONI DI PLACCA DI COPERTURA PRESA

TIPICO PRESA TELECOMUNICAZIONI, UN MODULO, DETTAGLIO MONTAGGIO INCASSATO.

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

ALUMINUM SWIVEL BASE ADHERED WITH GRAY SEALANT

ALUMINUM CABLE HOLDER EVERY 1000mm MAXIMUM ADHERED WITH GRAY SEALANT

CLASS I ALUMINUMLIGHTNING CONDUCTOR

GENTLY TAPERED SOLIDALUMINUM AIR TERMINAL

THE LIGHTNING PROTECTION SYSTEM HAS BEEN DESIGNED TO CONFORM WITH NFPA 780. THIS INCLUDES THE USE OF ALUMINUM MATERIALS WHERE REQUIRED TO AVOID THE USE OF DISSIMILAR METALS IN ACCORDANCE WITH SECTION 26 41 00 OF THE SPECIFICATIONS.

ASTA PARAFULMINE IN TONDO DI ALLUMINIO LEGGERMENTE CONICA

BASE GIREVOLE IN ALLUMINIO INCOLLATA CON ADESIVO GRIGIO

SUPPORTO PORTA CONDUTTORE OGNI 1000mm MASSIMO. INCOLLATO CON ADESIVO GRIGIO

CONDUTTORE PARAFULMINE CLASSE I IN ALLUMINIO

IL SISTEMA DI PROTEZIONE ANTIFULMINE E' STATO PROGETTATO IN CONFORMITA' ALLA NFPA 780. QUESTO PREVEDE L'USO DI MATERIALI IN ALLUMINIO DOVE NECESSARIO PER EVITARE L'USO DI MATERIALI DIVERSI IN CONFORMITA' ALLA SPECIFICA SEZIONE 26 14 00.

AIR TERMINAL

CLASS I ALUMINUMLIGHTNING CONDUCTOR

ALUMINUM BONDING PLATE

SCHEDULE 80 (UL LISTED)PVC CABLE GUARD - BREAKCONDUIT WHERE REQUIREDFOR BONDING CONNECTIONS

BIMETAL BONDING PLATE INSTALLED 450mm MINIMUM ABOVE FINISHED GRADE

CLASS I COPPERLIGHTNING CONDUCTOR

CONNECT TO GROUNDRING BELOW GRADE

ASTA DI CAPTAZIONE

CONDUTTORE PARAFULMINE IN ALLUMINIO CLASSE I

PIASTRA DI GIUNZIONE IN ALLUMINIO

PROTEZIONE CAVO IN PVC TIPO PESANTE SPESSORE 3mm -INTERROMPERE TUBO OVE RICHIESTO PER CONNESSIONI DI GIUNZIONE.

PIASTRA BIMETALLICA DI GIUNZIONE INSTALLATA A NON MENO DI 450mm DAL PIANO DI CALPESTIO.

CONDUTTORE PARAFULMINE IN RAME CLASSE I

COLLEGARE ALL'ANELLO DI TERRA INTERRATO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:32

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-508

LIG

HTN

ING

PR

OTE

CTI

ON

DE

TAIL

S -

PART

ICOL

ARI IM

PIAN

TO P

ARAF

ULM

INI

Checker

179

14090182

Designer Author

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOT TO SCALENON IN SCALA

(EC103)A1

AIR TERMINAL DETAILNOT TO SCALENON IN SCALA

(EC103)A3

DOWN CONDUCTOR DETAILCANOPY CANOPY - EXPOSED

TETTOIA PARTICOLARE ASTA DI CAPTAZIONE TETTOIA - PARTICOLARE CONDUTTORE DI CALATA A VISTA

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

CAMERA POLE

ACCESS PANEL

BUSHINGSBOCCOLE

FIBER OPTIC CABLE TO THE NEAREST IDFAVO F.O. AL PIU' VICINO IDF

4 ANCHOR BOLTS HOT DIPPEDGALVANIZED STEEL W/ 101 MM BEND4 BULLONI DI ANCORAGGIO ZINCATI A CALDO CON CURVATURA 100MM

GALVANIZED LOCKNUTSTACKWELDED (TYPICAL)CONTRODADI DI SERRAGGIO ZINCATI SALDATI (TIPICO)

ACCESS PANEL W/ TAMPER RESISTIVE SCREWS. PROVIDE TAMPER SWITCH FOR ALL ACCESS PANELSPIASTRA DI ACCESSO CON VITI ANTIEFFRAZIONE. FORNIRE INTERRUTTORE ANTIEFFRAZIONE PER OGNI PIASTRA DI ACCESSO.

REINFORCED CONC.CEMENTO ARMATO

CONDUIT FORSIGNALUBAZIONE PER SEGNALI

SURFACE MOUNT ELECTRICALLOCKABLE ENCLOSURE, NEMA4, 16 GAUGE CORROSION-RESISTANT WITH 1 PIECEOILTIGHT GASKET TO HOUSEPOWER SUPPLY & 120 VELECTRICAL POWERMOUNTED 914 MM ABOVE FOUNDATION PLATE

FOUNDATION PLATEPIASTRA DI FONDAZIONE

MMQ INSULATED COPPERCABLE FED UP THRUCAMERA POLE TO AIRTERMINALCAVO ISOLATO 16 MM2

CONDUIT CAPPED &WEATHER SEALED

19 MM x 3048 MM ROD COPPERWELD 50 MM MIN. BELOW GRADESPANDENTE COPPERWELD 19MM X 3048 MM, 50 MM MINIMO SOTTO IL LIVELLO DEL TERRENO.

GRADETERRENO

120V UPS POWER CONDUIT. REFER TODIVISION 26 DRAWINGS AND COORDINATEPOWER OUTLET REQUIREMENTS WITH DIV 26.TUBO PER ENERGIA 120V DA UPS. RIFERIRSI AI DISEGNI DELLA DIVISIONE 26 E COORDINARE I REQUISITI DELLE PRESE DI ENERGIA CON LA DIV. 26.

MIN. 182 CM APART

DATA + POWER ON CAT 6 TO THE CAMERA

CEILING STRUCTURESTRUTTURA DEL SOFFITTO

EXTERIOR TYPE DOME CAMERAINCLUDING PENDANTADAPTER (GFGI)TELECAMERA DA ESTERNO TIPO DOME COMPLETA DI ADATTAMENTO A SOSPENSIONE (GFGI)

ADJUSTABLE PENDANT POLE. ROUTEFLEXIBLE CONDUIT TROUGH POLE.TUBO SOSPENSIONE REGOLABILE. POSARE UN TUBO FLESSIBILE ATTRAVERSO IL TUBO.

SWIVEL CEILING ADAPTERPIASTRA GIREVOLE A SOFFITTO

FLEXIBLE CONDUITTUBO FLESSIBILE

SINGLE GANG BACKBOXSCATOLA POSTERIORE AD UN MODULO

19 MM CONDUIT TOIDF OR COMMUNICATION ROOM

NOTES:1. MOUNT AT HEIGHT AND LOCATION TO ENSURE UNOBSTRUCTED VIEW.

1. MONTARE A UN'ALTEZZA E UBICAZIONE TALE DA GARANTIRE UNA VISTA LIBERA DA OSTACOLI.

DOME CAMERA

TWO GANG BOX WITH MUD RINGSCATOLA A DUE MODULI CON ANELLO DA INCASSO

19 MM CONDUIT TOIDF OR COMMUNICATION ROOMTUBO DA 19 MM A IDF O LOCALE COMUNICAZIONI

VIDEO, CONTROL &POWER CABLES IN

MOUNTING ARMCAVI VIDEO, DI

CONTROLLO E DI ALIMENTAZIONE NEL BRACCIO DI

MONTAGGIO.

CAMERA MOUNTELEMENTO

MONTAGGIO TELECAMERA

GROUND WIRE(BY DIVISION 26)

CAVO DI TERRA (DA DIVISIONE 26)

ELECTRICAL LIGHT POLE

PALO ILLUMINAZIONE

HAND HOLE ACCESSASOLA DI ACCESSO

SURFACE MOUNT ELECTRICALLOCKABLE ENCLOSURE, NEMA 4, 16

GAUGE CORROSION- RESISTANTTO HOUSE SECURITY EQUIPMENT,

POWER SUPPLY & 120 V ELECTRICAL POWER.

CASSETTA LUCCHETTABILE MONTATA A VISTA, .............. RESISTENTE ALLA CORROSIONE PER CONTENIMENTO APPARECCHIATURE DI SICUREZZA. ALIMENTAZIONE ELETTRICA E 120V

1371 MM AFG1371 MM DAL PAVIMENTO FINITO

CAMERA TELECAMERA

FIBER TO THE NEAREST IDFFIBRA ALL'IDF PIU' VICINO

DATA + POWER ON CAT 6 TO THE CAMERADATI + ALIMENTAZIONE CON CAVO CAT 6 ALLA TELECAMERA

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:10

:44

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-509

SE

CU

RIT

Y C

AM

ER

A D

ETA

ILS

-DE

TTAG

LI D

ELLA

TEL

ECAM

ERA

DI S

ICUR

EZZA

IBF

180

14090183

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: NOT TO SCALEA3

CAMERA-POLE BASESCALE: NOT TO SCALE

A2CAMERA - PENDANT MOUNT EXTERIOR DOME GFGI

SCALE: NOT TO SCALEA1

CAMERA - WALL MOUNTED DOME

SCALE: NOT TO SCALEB2

CCTV CAMERA MOUNT ON LIGHT POLE

TELECAMERA MONTATA SU PALO ILLUMINAZIONE

TELECAMERA - DOME A PARETE TELECAMERA - DOME ESTERNA A SOSPENSIONE

FORNITA ED INSTALLATA DAL GOVERNO

BASE PALO TELECAMERA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

CONDUIT TOPREMISE CONTROL

UNIT

STRUCTURESTRUTTURA

JUNCTION BOX

FLEXIBLE CONDUITTUBO FLESSIBILE

CEILING

BACK BOX TO SUITSCATOLA POSTERIORE DA ADATTARE

MOTION SENSORSENSORE DI MOVIMENTO

BACKBOX BRACING TO NEAREST

CEILING SUPPORTS

DURESS SWITCHINTERRUTTORE ANTIRAPINA

FINGER LEVERLEVA PER DITO

DESK TOPRIPIANO DELLA SCRIVANIA

CAT 6 CABLE INSIDE WIREMOLD TO PUSH BUTTONCAVO CAT6 IN CANALINA AL PULSANTE

INSIDE CORNER OF DESKINTERNO SPIGOLO DELLA SCRIVANIA

SURFACE MOUNTED CAT 6 BLOCK ON BACK OF DESKBLOCCO CAT6 MONTATO A VISTA

SUL RETRO DELLA SCRIVANIA

BOTTOM OF DESKFONDO DELLA SCRIVANIA

ISOMETRIC FROM UNDERSIDE OF DESK/COUNTERTOP

FONDO DELLA SCRIVANIA

CAT 6 CABLE

SINGLE GANG FACEPLATE W/ 1 SINGLE CAT 6 JACK, 8 POSITIONPLACCA AD UN MODULO

CON 1 JACK SINGOLO

CAT6, POSIZIONE 8FINGER LEVERLEVA PER DITO

COUNTER TOP

SIDE VIEWELEVATION

STATUS INDICATORSEGNALAZIONE DI STATO

TWO GANG BACKBOX W/ SINGLE GANG MUD RINGCASSETTA PORTAFRUTTI A

DUE MODULI CON TELAIO

UNICO DA PARETE

CAT 6 JACK

NOTES:1. AT LOCATIONS WHERE DESK IS NOT LOCATED ADJACENT TO A WALL UTILIZE FLOOR BOXES. COORDINATE EXACT LOCATION AND INCORPORATE

OUTLETS INTO FLOOR BOX PROVIDE BY DIVISION 26.2. RJ-45 FOR WORK STATIONS, FACEPLATE AND BACKBOX W/ CONDUIT ROUTED TO LOCAL TC ROOM. MOUNT ADJACENT TO ELECTRICAL AND TELE/DATA

OUTLET. COORDINATE EXACT LOCATION W/ CONTRACTING OFFICER.NOTE:

1. NELLE POSIZIONI DOVE LA SCRIVANIA NON E' COLLOCATO IN ADIACENZA DELLA PARETE UTILIZZARE SCATOLA A PAVIMENTO. COORDINARE LA

ESATTA POSIZIONE E INCORPORARE LE PRESE IN CASSETTA DA PAVIMENTO. FORNIRE SECONDO DIVISIONE 26

2. POSTAZIONI DI LAVORO RJ-45, PLACCHE E CASSETTE PORTAFRUTTO CON TUBAZIONE POSATA FINO ALLA LOCALE STANZA TELECOMUNICAZIONI.

INSTALLARE IN ADIACENZA DI PRESA ELETTRICA E FONIA/DATI. COORDINARNE LA ESATTA POSIZIONE CON IL CONTRACTING OFFICER.

SECTIONSEZIONE

ELEVATION VIEWVISTA FRONTALE

CONDUIT TO JUNCTIONBOX ABOVE DOORTUBO CON CASSETTA DI GIUNZIONE SOPRA ALLA PORTAWALLPARETE

101 MM X 63 MM X 63 MMSINGLE GANG BOX

CARD READERLETTORE DI SCHEDA

CONNECTORRACCORDO

R CARD READER GFGILETTORE DI SCHEDA GFGI

D BIASED MAGNETIC DOOR POSITION SWITCH GFGIINTERRUTTORE MAGNETICO POLARIZZATO DI POSIZIONE DELLA PORTA GFGI

E ELECTRIC POWER TRANSFER (BY DIVISION 8)TRASFERIMENTO ENERGIA ELETTRICA (DA DIVISIONE 8)

C 19 MM CONCEALED CONDUITTUBO DA 19 MM INCASSATO

F FIRE ALARM INTERFACE(BY OTHERS WHERE APPLICABLE) REFERENCE NOTE CINTERFACCIA ALLARME INCENDIO (DA ALTRI OVE APPLICABILE) RIFERIMENTO NOTA C

U 102 MM X 63 MM X 63 MM SINGLE GANG UTILITY BOX WELDED TO DOOR FRAMECASSETTA SERVIZI 102X63X63MM AD UN MODULO SALDATA AL TELAIO DELLA PORTA

GENERAL NOTES:

A. SYMBOLS SHOWN DEPICT CONDUIT AND OUTLET BOXES ONLY UNLESS NOTED OTHERWISE.

B. USE MASONRY BOX WHERE APPLICABLE.C. DOOR UNLOCK RELAY DRY CONTACT FROM ACCESS CONTROL

SYSTEM.

GENERAL LEGENDS:LEGENDE GENERALI:

B 203 MM X 203 MM X 101 MM ENCLOSURE ABOVE FINISHED CEILING ON SECURE SIDE OF DOORCASSETTA 203X203X101 MM SOPRA IL SOFFITTO FINITO DAL LATO SICURO DELLA PORTA

J 152 MM X 152 MM X 101 MM ENCLOSURE ABOVE FINISHED CEILING ON SECURE SIDE OF DOORCASSETTA 152X152X101 MM SOPRA IL SOFFITTO FINITO DAL LATO SICURO DELLA PORTA

L ELECTRIC LOCKING DEVICE & CONNECTION TO REQUEST TO EXIT DEVICE (BY DIVISION 8)DISPOSITIVO SERRATURA ELETTRICA E COLLEGAMENTO AL DISPOSITIVO DI RICHIESTA USCITA (PER DIVISIONE 8)

NOTE GENERALI:

A. I SIMBOLI MOSTRATI DESCRIVONO SOLO I TUBI E LE CASSETTE DELLE PRESE SE NON DIVERSAMENTE INDICATO

B. UTILIZZARE SCATOLE IN MURATURA DOVE APPLICABILI C. CONTATTO SENZA TENSIONE RELE' SBLOCCO PORTA

D

CEILING LINEFILO SOFFITTO

J

25 MM CONDUIT BACK TO ASSIGNEDSECURITY EQUIPMENT ENCLOSURETUBO DA 25MM FINO ALLA RELATIVA CASSETTA DEGLI APPARATI DI SICUREZZA

D

SECURED SIDELATO SICURO

NON-SECURED SIDELATO NON SICURO

J

C

DE

B25 MM CONDUIT BACK TO ASSIGNEDSECURITY EQUIPMENT ENCLOSURE,

TYPICALTUBO DA 25MM FINO ALLA RELATIVA

CASSETTA DEGLI APPARATI DI SICUREZZA TIPICO

B

CEILING LINE

E

ELEVATION

PLAN VIEWSECURED SIDELATO SICURO

NON-SECURED SIDELATO NON SICURO

D

U

F

R

C

FINISHED FLOORPAVIMENTO FINITO

L

C

CEILING LINEFILO SOFFITTO

R

152 MM

1143 M

M

C

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:10

:50

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-510

SE

CU

RIT

Y D

ET

AIL

S -

DETT

AGLI

SULL

A SI

CURE

ZZA

IBF

181

14090184

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: NOT TO SCALEA3

MOTION SENSOR-CEILING MOUNTEDSCALE: NOT TO SCALE

A1DURESS-DESK MOUNTED

SCALE: NOT TO SCALED4

CARD READER GFGI

SCALE: NOT TO SCALEC3

TYPICAL SINGLE DOOR WITH DOOR POSITION SWINGES ONLYSCALE: NOT TO SCALE

C1TYPICAL SINGLE DOOR WITH ACCESS CONTROL

TIPICO PORTA AD UNA ANTA CON CONTROLLO ACCESSI TIPICO POSIZIONAMENTO SCAMBI PER PORTA AD UN'ANTA

LETTORE DI SCHEDA GFGI

SENSORE DI MOVIMENTO - MONTATO A SOFFITTOANTIRAPINA MONTATO SULLA SCRIVANIA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

PUSH BUTTONSPULSANTI

INDICATOR LAMPS (NOTE 2)LAMPA DI SEGNALAZIONE (NOTA 2)

2 AND 3 WAY SELECTOR SWITCHESSELETTORI A 2 E 3 VIE

SWITCH AND LAMP PLASTIC LAMINATE ENGRAVED LABEL PLATESTARGHETTE DI LAMINATO PLASTICO CON INCISO PER SELETTORI E LAMPADE

2 WAY KEYED SELECTOR SWITCHESSELETTORI A CHIAVE A 2 VIE

PUSH BUTTONS WITH HEAD GUARDPULSANTE CON COPERCHIO DI GUADRIA

GENERAL NOTES:

A. THE CONTROL PANEL LAYOUTS DEPICT AN ACP WITH A GATEHOUSE, SEARCH OFFICE 3 ID CHECK LANES, AN OVERWATCH POSITION, AND 4 ACTIVE VEHICLE BARRIERS.

B. SEE UFGS 34 41 26.00 10 "ACCESS CONTROL POINT CONTROL SYSTEM" APPENDIX A "SIGNS AND SIGNALS SAFETY SYSTEM" FOR DESCRIPTIONS OF THE REQUIRED BARRIER AND TRAFFIC CONTROL SEQUENCES.

C. THE BARRIER MODE SELECTOR SWITCHES, BARRIER "DOWN" AND "UP" SWITCHES AND THE EFO RESET SWITCH MAY BE LOCATED ON A SEPARATE PANEL CALLED THE MAINTENANCE PANEL. THE MAINTENANCE PANEL MUST BE LOCATED IN THE GATEHOUSE IN AN AREA OR CABINET THAT IS ONLY ACCESSIBLE TO THE CHIEF OF THE GUARDS.

NOTES :1.

2.

3.

4.

5.

6.

7.

8.

LEGEND

GRANDE SELETTORE A PULSANTE

LOCALON

KEY SWITCHSELETTORE A CHIAVE

LED LAMP COLOR SCHEDULE

SCHEDA COLORAZIONE LAMPADE

1

2

3

REDROSSO

AMBERAMBRA

GREENVERDE

NOTE GENERALI

A. IL LAYOUT DEL PANNELLO DI CONTROLLO RAFFIGURA UN POSTO DI CONTROLLO ACCESSI CON UN CORPO DI GUARDIA, UFFICIO CONTROLLO PER 3 ID CORSIE DI CONTROLLO, UNA GARITTA E 4 BARRIERE ATTIVE PER VEICOLI.

B. VEDI UFGS 34 41 26.00 10 “ACCESS CONTROL POINT CONTROL SYSTEM” APPENDIX A “SIGNS AND SIGNALS SAFETY SYSTEM” PER LA DESCRIZIONE DELLA SEQUENZA DI CONTROLLO RICHIESTA PER BARRIERE E CONTROLLO TRAFFICO.

C. I SELETTORI DELLE MODALITA’ DELLE BARRIERE, SELETTORI BARRIERA “GIU” E “SU” E IL SELETTORE DI RESET EFO POSSONO ESSERE POSIZIONATI SU UN PANNELLO SEPARATO, DEFINITO PANNELLO DI MANUTENZIONE. IL PANNELLO DI MANUTENZIONE DEVE ESSERE COLLOCATO NEL CORPO DI GUARDIA IN UN AREA O ARMADIO CHE E’ ACCESSIBILE AL SOLO CAPO DELLE GUARDIE.

PROVIDE A SEPARATE STAND ALONE EFO PUSH BUTTON SWITCH WITH KEYED RESET AND SAFETY COVER MOUNTED ON THE INSIDE OF THE GUARD BOOTH TO THE LEFT OF THE DOOR FRAME FOR EASY ACCESS BY THE GUARD WHO MAY BE STANDING OUTSIDE GUARD BOOTH DURING ID CHECKS.

THE BARRIER MODE SELECTOR SWITCHES SHALL BE KEY OPERATED WITH THE KEY REMOVABLE IN ALL MODES. EACH BARRIER SHALL HAVE A UNIQUE KEY.

a. UNDER NORMAL OPERATIONS, THE BARRIER MODE SELECTOR SWITCHES WILL BE IN THEIR EMERGENCY FAST OPERATE (EFO) POSITIONS WITH KEYS REMOVED AND STORED IN A LOCKED CABINET IN THE GATEHOUSE ACCESSIBLE ONLY BY THE CHIEF OF THE GUARDS.

b. WHEN PERFORMING BARRIER MAINTENANCE, MAINTENANCE PERSONNEL WILL OBTAIN THE KEY FROM THE CHIEF OF THE GUARDS, PUT THE SWITCH IN THE "LOCAL" POSITION, AND THEN REMOVE AND RETAIN THE KEY. THE MAINTENANCE PERSON WILL THEN PUT THE KEY IN THE MODE SELECTOR SWITCH ON THE BARRIERS LOCAL CONTROL PANEL LOCATED AT THE BARRIER AND TURN THE KEY TO THE "LOCAL" POSITION TO ACTIVATE THE OPEN AND CLOSE SWITCHES ON THE LOCAL CONTROL PANEL. WHEN MAINTENANCE IS COMPLETE, THE MAINTENANCE PERSON WILL PLACE THE MODE SELECTOR SWITCH ON THE LOCAL CONTROL PANEL BACK TO "AUTO" MODE, REMOVE THE KEY, AND RETURN THE KEY TO THE CHIEF OF THE GUARDS. THE CHIEF OF THE GUARDS WILL USE THE KEY TO PLACE THE BARRIER'S MODE SELECTOR SWITCH ON THE MASTER CONTROL PANEL IN THE "EFO" POSITION, AND THEN WILL REMOVE AND LOCKUP THE KEY.

c. A GUARD MAY TEST OPERATE A BARRIER BY FIRST OBTAINING THE BARRIER'S MODE SWITCH KEY FROM THE CHIEF OF THE GUARDS, PUTTING THE MODE SWITCH IN THE "TEST" POSITION, AND THEN OPENING OR CLOSING THE BARRIER WITH THE PUSHBUTTONS ON THE MASTER CONTROL PANEL. UPON COMPLETION OF THE TEST OPERATIONS, THE GUARD WILL RETURN MODE TO "EFO", REMOVE THE KEY, AND RETURN IT TO THE CHIEF OF THE GUARDS. PROCEDURES MUST BE IN PLACE TO ENSURE ALL OPERABLE BARRIERS' MODE SELECTOR SWITCHES ARE PLACED IN THE EFO POSITIONS FOR THE PROPER RESPONSE TO AN EFO COMMAND.

LAMP TEST PUSH BUTTON SHALL TURN ON ALL INDICATING LIGHTS WHILE BUTTON IS PUSHED WITHOUT AFFECTING ANY CONTROLS.

THE INDICATING LIGHT LABELED 'TROUBLE' SHALL COME ON FOR ANY PROBLEMS OR ALARM CONDITIONS AT THE BARRIER, e.g. LOW VOLTAGE, ETC. THE INDICATING LIGHT LABELED 'VPD ON' SHALL COME ON WHEN ANY OF THE BARRIER'S VEHICLE PRESENCE DETECTORS (VDL'S) GETS A CALL (VEHICLE DETECTED) FOR MORE THAN 15 SECONDS.

WRONG-WAY, AND DURESS ALARMS SHALL INCLUDE BACKLIT WINDOWS AND ADJUSTABLE AUDIBLE ALARMS. DURESS ALARMS SHALL BE ON OVERWATCH POSITION PANEL AND GATEHOUSE PANEL ONLY. DURESS ALARM ACKNOWLEDGEMENT SWITCH SHALL BE ON GATEHOUSE PANEL ONLY.

OVERWATCH POSITION PANEL SHALL INCLUDE A DURESS ALARM SILENCE SWITCH TO SILENCE THE AUDIBLE ALARM. ALL WRONG WAY ALARMS SHALL BE SELF CLEARING.

VOLUME ADJUSTABLE PEIZO SOUNDER.

BASE BID: PROVIDE EFO SWITCH ON SEARCH AREA CANOPY. INCLUDE IN SEC0501. SEE B2/E-511 FOR EFO SWITCH DETAILS. CLIN 0007: PROVIDE EFO SWITCH ON CONTROL PANEL AS INDICATED IN ADDITION TO EFO SWITCH ON CANOPY. INCLUDE IN SEC0401.

FORNIRE UN PULSANTE SEPARATO ISOLATO EFO CON CHIAVE DI RESET E COPERCHIO DI SICUREZZA MONTATO ALL’INTERNO DELLA CABINA DI GUARDIA PREFABBRICATA ALLA SINISTRA DEL TELAIO DELLA PORTA PER UNA FACILE ACCESSIBILITA’ DA PARTE DELLA GUARDIA CHE PUO’ TROVARSI ALL’ESTERNO DELLA GUARDIOLA DURANTE CONTROLLO ID.

I SELETTORI DELLE MODALITA’ DI FUNZIONAMENTO DELLE BARRIERE DEVONO ESSERE CON COMANDO A CHIAVE CON CHIAVE ESTRAIBILE IN OGNI POSIZIONE. OGNI BARRIERA AVRA’ LA SUA UNICA CHIAVE.

a. IN CONDIZIONI OPERATIVE NORMALI, I SELETTORE DI MODO DELLE BARRIERE STARANNO NELLA LORO POSIZIONE DI INTERVENTO RAPIDO DI EMERGENZA (EFO) CON LE CHIAVI RIMOSSE E CONSERVATE IN UN ARMADIETTO CHIUSO NEL CORPO DI GURADIA, ACCESSIBILE SOLO AL CAPO DELLE GUARDIE.

b. PER LA MANUTENZIONE DELLA BARRIERA, IL PERSONALE DELLA MANUTENZIONE DEVE OTTENERE LA CHIAVE DAL CAPO DELLE GUARDIE, PORRE IL SELETTORE NELLA POSIZIONE “LOCALE”, E POI ESTRARRE E CONSERVARE LA CHIAVE . IL PERSONALE DELLA MANUTENZIONE INSERIRA’ POI LA CHIAVE NEL SELETTORE DI MODO NEL PANNELLO DI CONTROLLO LOCALE DELLA BARRIERA UBICATO PRESSO LA MEDESIMA, E RUOTERA’ LA CHIAVE NELLA POSIZIONE “LOCALE” PER ATTIVARE I SELETTORI DI APERTURA E CHIUSURA SUL PANNELLO DI CONTROLLO LOCALE. AL TERMINE DELLA MANUTENZIONE, IL PERSONALE DI MANUTENZIONE PORRA’ IL SELETTORE SUL PANNELLO DI CONTROLLO LOCALE NUOVAMENTE IN MODO “AUTO”, RIMUOVERA’ LA CHIAVE, E LA RESTITUIRA’ AL CAPO DELLE GUARDIE. IL CAPO DELLE GUARDIE UTILIZZERA’ LA CHIAVE PER POSIZIONARE IL SELETTORE DI MODO NEL PANNELLO DI CONTROLLO PRINCIPALE NELLA POSIZIONE “EFO”, E SUCCESSIVAMENTE DOVRA’ RIMUOVERE LA CHIAVE E RICHIUDERE IL COPERCHIETTO.

c. UNA GUARDIA PUO’ EFFETTUARE UNA PROVA DI FUNZIONAMENTO DI UNA BARRIERA DAPPRIMA OTTENENDO LA CHIAVE DI MODO DELLA BARRIERA DAL CAPO DELLEL GUARDIE, POSIZIONARE IL SELETTORE DI MODO NELLA POSIZIONE “PROVA” E POI APRIRE O CHIUDERE LA BARRIERA CON I PULSANTI SUL PANNELLO DI CONTROLL PRINCIPALE. A COMPLETAMENTO DELLE PROVE, LA GUARDIA RIPRISTINA IL MODO “EFO”, RIMUOVE LA CHIAVE E LA RESTITUISCE AL CAPO DELLE GUARDIE. LE PROCEDURE DEVONO ESSERE SEGUITE PER GARANTIRE CHE I SELETTORI DI MODO DI TUTTE LE BARRIERE MANOVRABILI SIANO NELLA POSIZIONE “EFO” PER UNA IMMEDIATA RISPOSTA AD UN COMAMDO EFO.

IL PULSANTE DI PROVA DELLE LAMPADE DOVRA’ ATTIVARE TUTTE LE LAMPADE DI SEGNALAZIONE MENTRE IL PULSANTE RESTA PREMUTO, SENZA INTERFRERIRE CON QUALSIVOGLIA CONTROLLO.

LA LAMPADA SPIA CON TARGHETTA “ANOMALIA” SI DOVRA’ ILLUMINARE PER OGNI PROBLEMA O SITUAZIONE DI ALLARME ALLA PARRIERA, PER ESEMPIO TENSIONE BASSA, ETC. LA LAMPADA CON TARGHETTA “VPD ON” SI ILLUMINERA’ QUANDO UN SENSORE DI PRESENZA VEICOLO (VDL’S) AD UNA BARRIERA DIA UNA SEGNALAZIONE (PRESENZA VEICOLO) PER PIU’ DI 15 SECONDI.

ERRORE DI PERCORSO, E ALLARMI DI COERCIZIONE DEVONO INCLUDERE FINESTRE RETROILLUMINATE E ALLARMI ACUSTICI REGOLABILI. L’ALLARME DI COERCIZIONE DOVRA’ ESSERE ESCLUSIVAMENTE SUL PANNELLO DELLA GARITTA E SUL PANNELLO DEL CORPO DI GUARDIA. IL SELETTORE DI TACITAZIONE DELL’ALLARME DI COERCIZIONE SARA’ POSIZIONATO SOLO SUL PANNELLO DEL CORPO DI GUARDIA.

IL PANNELLO DELLA GARITTA DEVE INCLUDERE UN SELETTORE DI SILENZIAMENTO DELL’ALLARME ACUSTICO. TUTTI GLI ALLARMI DI ERRORE DI PERCORSO SARANNO AUTO RESETTATI.

SUONERIA PIEZO CON VOLUME REGOLABILE

OFFERTA DI BASE: FORNIRE SELETTORE EFO SU TETTOIA AREA DI VERIFICA. INCLUDERE IN SEC0501. VEDI B2/E-511PER DETTAGLI SELETTORE EFO. CLIN 0007:FORNIRE SELETTRORE EFO SU PANNELLO DI CONTROLLO COME INDICATO IN AGGIUNTA AL SELETTORE EFO DELLA TET

NOTE :1.

2.

3.

4.

5.

6.

7.

8.

EMERGEN CY

EFO

ACTIVATED

EN ABLED

YES

ENABLED

NO

RESET

ALARM

FINAL BARR IER

INBOUN D

EFO

U P

DOWN

FINAL BARRIER

OU TBOUN D

EFO

U P

DOWN

WRON G−WAY

STATU S

LAMP TEST

EMERGENCY

EFO

ACTIVATED

ENABLED

YES

ENABLED NO

RESET

ALARM

FINAL BARRIER

INBOUND

FINAL BARRIER

OUTBOUND

EFO

UP

DOWN

WRONG−WAY

STATUS

LAMP TEST

EFO

UP

DOWN

9144 MM

PORTABLE CONTROL CONSOLE (SEE DETAIL

ABOVE)CONSOLLE DI CONTROLLO

PORTATILE (VEDI DETTAGLIO A LATO)

25 MM NPT CHORD

GRIP

152 MM X 152 MM POLYESTERACTIVE BARRIERMOBILE CONTROLBOX

DETAIL

PORTABLE OVERWATCH CONTROL CONSOLE W/ CHORD

KEY NOTES:1. TYPE SOOW, 24 C 16 GA PORTABLE CABLE. (INCLUDES SPARE CONDUCTORS)2. 24 C 16 GA CONTACT CIRCULAR CONNECTOR POWER/DATA PLUG.3. 16MM MOMENTARY PB RED DPDT SWITCH.4. RED LED 24VDC PILOT LIGHT.5. GREEN LED 24VDC PILOT LIGHT.6. AMBER LED 24VDC PILOT LIGHT.7. MOMENTARY PB SWITCH SP 15A 28VDC WITH HEAD GUARD.8. PIEZO SOUNDER.

4

3

5

3

4565

4

6

7 4

2

1

8

3

2

1

3 1 2

1

2

2

NOTE CHIAVE:1. TIPO SOOW, 24C 16 GA CAVO PORTATILE (INCLUDE CONDUTTORI DI SCORTA)2. 24 C 16 GA SPINA DI CONNESSIONE CIRCOLARE ENERGIA/DATI3. PULSANTE 1ROSSO DPDT 16 MM4. LAMPADA SPIA ROSSA LED 24VDC 16 MM 5. LAMPADA SPIA VERDE LED 24VDC 16 MM 6. LAMPADA SPIA AMBRA LED 24VDC 16 MM 7. PULSANTE 15A 28VDC CON TESTA PROTETTA8. RONZATORE PIEZOLETTRICO9. SP 15A 28VDC WITH HEAD GUARD.

SECTION (CONCEALED MOUNTING)ELEVATION VIEW

TO NEAREST SEC

WALL

101MM X 63MM X 63MMSINGLE GANG BOX

PUSH-TO-ACTIVATE KEY-TO-RESET

OCTAGONAL BUTTON WITH MOLDED "PUSH"

RAISED MESSAGEREMERE PER ATTIVARE

RESET A CHIAVEPULSANTE

OTTAGONALE CON STAMPATO MESSAGGIO

"PUSH" IN RILIEVO

CONNECTOR

PUSH

LIFT HERE

FAST OPERATE

ACTIVE BARREIR

"FAST OPERATE" AND"ACTIVE BARRIER"RAISED MOLDEDMESSAGE

RED FACE PLATE SHELLPLACCA DI COPERTURA ROSSA

INDOOR/OUTDOORCLEARPOLYCARBONATESAFETY COVER

NOTE 1

PREFABRICATED ALUMINUM CONSOLE CASEINVOLUCRO CONSOLLE PREFABRICATA IN ALLUMINIO

MAIN CONTROL PANEL

LOCAL CONTROL PANEL

NOTE:PANEL SHALL BE SIZED AND CONSTRUCTED TO MEET REQUIREMENTS OF DEVICES FOR EACH LOCATIONIL PANNELLO DOVRA' ESSERE DIMENSIONATO E COSTRUITO SECONDO I REQUISITI DEI COMPONENTI PER CIASCUNA POSIZIONE

MAINTENANCE

INBOUND AVB

UP

DOWN

ALARM SILENCE

TROUBLE

LAMP TEST

3.175 MM BLACK SILK SCREENEDCONSOLE GRAPHIC LINES, TYPICALCONSOLLE GRAFICA TIPICA 3,175MM NERO SATINATO MAINTENANCE

OUTBOUND AVB

UP

DOWN

ALARM SILENCE

TROUBLE

LAMP TEST

NOTE 6

NOTE 7 NOTE 7

NOTE 6 NOTE 3

NOTE 3

LOCALAUTO

LOCALAUTO

BARRIER MAINTENACE BARRIER MAINTENACE

1

2

1

3

1

2

1

3

ALARM SILENCE

LAMP TEST

POWER

WRONG WAY

AVB EMERGENCY FAST OPERATE

ACTIVATED

OVERWATCH POSITION AVB EFO ARMED

No

Yes YES

NO

ACKNOWLEGE

DURESS

ACKNOWLEDGE

PANEL TAMPER

COMM LOSS

INBOUND FINAL AVB

AVB

UP

DOWN

LOOP RELEASETROUBLE

VDP ON

EFO MODEEFO TEST

MODE

EFO LOCAL

MODE

NOTE 6

3.175 MM BLACK SILK SCREENEDCONSOLE GRAPHIC LINES, TYPICAL

OUTBOUND FINAL AVB

AVB

UP

DOWN

LOOP RELEASETROUBLE

VDP ON

EFO MODEEFO TEST

MODE

EFO LOCAL

MODE

NOTE 7

NOTE 8

NOTE 5

NOTE 2

NOTE 4

NOTE 4

NOTE 2

NOTE 3

LOCALLOCALEFO

LOCALON

EFO

1 1

2

2

1 3 1

2

1

3

1

3

1

2

1

1 3 1

2

2

2

2

2

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:10

:57

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-511

SE

CU

RIT

Y D

ET

AIL

S -

DETT

AGLI

SULL

A SI

CURE

ZZA

IBF

182

14090185

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DERSCALE: NOT TO SCALEB4

SECURITY INTERCONNECT OVERWATCH PANEL MOBILE CABLINGSCALE: NOT TO SCALE

B2EMERGENCY FAST OPERATE (EFO) SWITCH

SCALE: NOT TO SCALEB1

TYPICAL GRAPHIC CONTROL PANEL SIDE VIEW

SCALE: NOT TO SCALEC4

MAINTENANCE LOCAL CONTROL PANEL - AVB

SCALE: NOT TO SCALEC1

GATEHOUSE GRAPHIC CONTROL PANEL

PANNELLO CONTROLLO SINOTTICO CORPO DI GUARDIA

INTERRUTTORE DI EMERGENZA AZIONAMENTO

RAPIDO

CABLAGGIO PANNELLO MOBILE DI INERCONNESSIONE DI SICUREZZA

POSTAZIONE DI CONTROLLO

CABLAGGIO PANNELLO MOBILE DI INERCONNESSIONE DI

SICUREZZA POSTAZIONE DI CONTROLLO

PANNELLO LOCALE CONTROLLO BARRIERA - AVB

PARTICOLARE CONNETTORE DI

INSERIMENTO GARITTA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

DETECTION WIRE ENCASED IN 19 MM SCH 40 PVC PROTECTOR PIPE AND INSTALLED PRIOR TO PLACEMENT OF PAVING MATERIALSPIRA DI RILEVAMENTO

INCASSATA IN TUBO DI

PROTEZIONE DA 19MM IN PVC SCH

40 E INSTALLATO PRIMA DELLA

POSA DEL MATERIALE DELLA PAVIMENTAZIONE

609

MM

609 MM

609 MM

(NO

TE

2)

(NOTE 1)

609 MM

FOUR (4) TURN COATED #14 MACHINE TOOL LOOP WISEANELLO RIVESTITO #14

4 VOLTE RUOTATO CON

ATTREZZO

CONDUIT AND LOOP WIRE TO HAND HOLE OR JUNCTION BOX AND EXTENSION CABLETUBO E CAVO AD ANELLO

AL POZZETTO O ALLA

SCATOLA DI GIUNZIONE ED

ESTENSIONE DEL CAVO

IF APPLICABLE, SMOOTHLY SAW-CUT EXISTING CONCRETE CURB IN (2) PLACES. AFTER PLACING PVC CONDUIT, CAREFULLY PATCH CURB WITH CONCRETE GROUT MATERIALSE APPLICABILE TAGLIARE

DELICATAMENTE L'ESISTENTE

CORDOLO IN CEMENTO IN 2

POSIZIONI. DOPO LA POSA DI

TUBO IN PVC, DELICATAMENTE

RACCORDARE IL CORDOLO CON

MATERIALE PER FUGHE IN

CALCESTRUZZO

CURB (IF APPLICABLE)

OUTLINE OF METAL-FREE ZONE (NOTE 1)

PLASTIC REINFORCING CHAIRS (USED IN CONCRETE INSTALLATION ONLY)

OUTLINE OF METAL-FREE ZONE (NOTE 1)

OUTLINE OF METAL-FREE ZONE (NOTE 1)

PLAN VIEW

NOTES:1. NO CONVENTIONAL STEEL REINFORCING STEEL OR ANCILLARY

HARDWARE AND EQUIPMENT SHALL BE PLACED WITHIN 609 MM OF THE LOOP ASSEMBLY IN CONCRETE PAVING APPLICATIONS.

2. FOR LOOP SIZE REFERENCE ENLARGED PLAN VIEWS 1S-400 SERIES.

CURE (IF APPLICABLE) NOTE 1

SECTIONAL VIEW - CONCRETE PAVING

NOTES:1. PLACE PVC LOOP CONDUIT ON PLASTIC REINFORGING CHAIRS.2. POUR CONCRETE ABOVE AND BELOW LOOP ASSEMBLY TO FINISHED GRADE LEAVING NO

VOID.3. NO FERROUS MATERIAS INCLUDING BUT NOT LIMITED TO REINFORCING BARS,

REINFORCING TIES AND SUPPORT CHAIRS SHALL BE PLACED WITHIN A 609 MM CLEAR ZONE AROUND THE LOOP ASSEMBLY.

NOTE:

1. NESSUNA ARMATURA IN FERRO O AUSILIARI IN FERRO ED APPARECCHIATURE

METALLICHE PU0' ESSERE POSIZIONATA ENTRO 609 MM DAL SISTEMA AD ANELLO

NELLE APPLICAZIONI DI PAVIMENTO IN CEMENTO.

2. PER LE DIMENSIONI DELL'ANELLO VEDI VISTE DI INGRANDIMENTO TAV. SERIE 1S-400.

NOTE:

1. POSARE ANLLO IN PVC SU SELLE IN PLASTICA RINFORZATA

2. VERSARE CEMENTO SOPRA E SOTTO AL SISTEMA AD ANELLO A LIVELLO DEL PIANO FINITO

NON LASCIANDO ALCUN VUOTO.

914 M

M558 MM

1524 MM

KEY NOTES:1. PRECAST CONCRETE, BOTTOMLESS PULL BOX REINFORCED FOR H20 BRIDGE LOADING.2. GALVANIZED STEEL TRAFFIC COVER WITH CHECKERED TOP SURFACE.3. LIFTING HOLE.4. UTILITY IDENTIFICATION TO SAY "ELECTRICAL" ON COVER IN 25 MM LETTERING.5. STAINLESS STEEL HEAD NUT AND SWING BOLT.6. PROVIDE MIN. 203 MM GRAVEL FILL BED UNDER BODY OF BOX FOR DRAINAGE.7. PROVIDE 19MM DIA. 3048 MM COPPER GROUNDING ROD.

6

4

2

1

3

7

5

NOTE CHIAVE:

1. POZZETTO DI PASSAGGIO SENZA FONDO PREFABBRICATO IN CEMENTO, RINFORZATO PER CARICO

A PONTE H20

2. COPERCHIO IN ACCIAIO ZINCATO CARRABILE CON SUPERFICIE SUPERIORE QUADRETTATA

3. ASOLA DI SOLLEVAMENT

4. IDENTIFICATIVO DEL SERVIZIO CON SCRITTA "ELECTRICAL" SU COPERCHIO CON LETTERE DA 25 MM

5. DADO CON TESTA E BULLONE OSCILLANTE IN ACCIAIO INOX

6. FORNIRE RIEMPIMENTO PER MIN. 203 MM DI GHIAIA SOTTO IL CORPO DEL POZZETTO PER

DRENAGGIO.

7. FORNIRE SPANDENTE DI TERRA IN RAME 19MM DIA 3048 MM LUNGO

CONDUIT BACK TO JUNCTION PULL BOX AT ISLAND

TUBO ALLA CASSETTA DI

GIUNZIONE ALL'ISOLA

SINGLE GANG JUNCTION BOXSCATOLA DI GIUNZIONE A 1

MODULO

RED 381 MM HIGH "X" INDICATING LANE CLOSED"X" ROSSA 381MM INDICANTE

LA CORSIA CHIUSA

GREEN 381 MM HIGH ARROW INDICATING LANE OPENFRECCIA VERDE 381MM

INDICANTE LA CORSIA

APERTA

DIRECT-VIEW LED TRAFFIC CONTROLLER W/ INTEGRATED SOLID STATE POWER SUPPLY

CONTROLLORE A VISTA LED TRAFFICO CON

ALIMENTATORE ALLO STATO SOLIDO INTEGRATO

MESSAGE MADE UP OF SUPER BRIGHT WIDE ANGLE VIEWING LEDSMESSAGGIO COSTITUITO DA LED A

VISTA SUPER BRILLANTI E CON

AMPIO ANGOLO DI EMISSIONE BRONZE ANODIZED EXTRUDEDALUMINUM CASECASSONETTO ESTRUSO IN

ALLUMINIO BRONZATO

3.175 MM THK ALUMINUM SWIVEL MOUNTING BRACKET

STAFFA DI MONTAGGIO RUOTANTE

IN ALLUMINIO DA 3.175 MM

64 MM

457 MM

457 MM

MANUFACTURERSUPPLIED MOUNTINGBRACKETSTAFFA DI

MONTAGGIO FORNITA

DAL PRODUTTORE

75 6

120VAC

3'-2"

SECTION A-AINTERCONNECT FACE PLATE DETAIL TOP OF

PAVEMENT

PIPE BOLLARDS(REFERENCE CIVILDETAIL SHEETS),TYPICAL 4 PLACES

30A/125VAC TWIST-LOCK OUTLET

CONNECTION TOPORTABLE OVERWATCHPANEL

1.

2.

3.

NOTES:ALL JACKS AND OUTLETS SHALL BE WATER AND DUST PROOF AND WATER AND DUST PROOFAND.INTERCONNECT BOX COVER AND IN-GROUND INTERCONNECT BOX SHALL BE FABRICATED

FROM 12GA STEEL WITH. CONTINUOUS WATER-TIGHT WELDS.

ALL LOCKS, HINGES AND ANCILLARY HARDWARE SHALL BE 316 STAINLESS STEEL.

MOUNTING STRAPSMOUNT PERMANUFACTURER'SSPECIFICATIONS.

SECURITY INTERCONNECTIONCABINET NEMA 4X, MOUNTED AT46" AFF, 16 GAUGE CORROSIONRESISTANT WITH GASKET & KEYLOCK.

TERMINAL ADAPTERSFOR 3 - 2" CONDUITS

3'-2"

120VAC

30A/125VAC TWIST-LOCK OUTLET30A/125VCA PRESA

CON ROTAZIONE DI

BLOCCO

CONNECTION TO PORTABLE OVERWATCH PANELCOLLEGAMENTO AL

PANNELLO PORTATILE

POSTAZIONE DI

CONTROLLO

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:11

:03

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-512

SE

CU

RIT

Y D

ET

AIL

S -

DETT

AGLI

SULL

A SI

CURE

ZZA

IBF

183

14090186

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: NOT TO SCALEB4

VDL INSTALLATION AT NEW PAVING

SCALE: NOT TO SCALEA3

HAND HOLESCALE: NOT TO SCALE

A4TRAFFIC SIGNAL AT ID CHECK CANOPY

SGNALETICA DI TRAFFICO ALLA TETTOIA DI CONTROLLO ID

INSTALLAZIONE VDL ALLA NUOVA PAVIMENTAZIONE

POZZETTO

SCALE: NOT TO SCALED1

ODDS HORN HARDWARE DETAIL

SCALE: NOT TO SCALEA1

SECURITY INTERCONNECT CABINET AT ACTIVE BARRIER OVERLOOK

SCALE: NOT TO SCALEC1

OVERWATCH PLUG IN SWITCH DETAIL

PARTICOLARE CONNETTORE DI

INSERIMENTO GARITTA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

LFINECORSAFINECORSA

SCALDIGLIA, 1400 WATTS @ 120 VOLTS

SCALDIGLIA, 1400 WATTS @ 240 VOLTS

OPZIONI COLORIBIANCO CON STRISCE GIALLE DA 150 MMNERO CON STRISCE GIALLE DA 150 MMBIANO CON STRISCE ROSSE DA 150 MM

FONDAZIONE - RIVESTIMENTO IN EMULSIONE DI ASFALTO PRIVA DI ASBESTO

TUTTI I COMPONENTI DI ACCIAIO SECONDO STANDARD AISCCRITERI DI DESIGN DI SALDATURA AWS D1.1 ULTIMA VERSIONE

ALL MILD STEEL COMPONENTS SANDBLASTED TO NEAR4.

3.

2.

NOTE: CONFIGURAZIONI OPZIONALI DISPONIBILI (PARZIALI)

1.

B2006

PART NO.

B1294

B2005

B1293

ZINCATURA A CALDO PRIMA DELLA VERNICIATURA

SIDE ELEVATION - UP POSITIONVISTA LATERALE - POSZIONE SU

GALV

FRONTPANEL

PANNELLO FRONTALE

CRASH ARRESTING

CHAIN SYSTEM

SISTEMA DI CATENA

DI ARRESTO URTOATTACK

DIRECTIONDIREZIONE DI

ATTACCO

122.5" [3110mm] OVERALLWIDTH

109" [2770mm] BARRIERWIDTH

STRUCTURALFOUNDATIONTIE-IN MEMBER

FRONT ELEVATION - UP POSITION

72"[1830mm]

STRUCTURALFOUNDATION

TIE-IN MEMBER

114.5" [2910mm] FRAMEWIDTH

ACCESS POINTSFOR HINGE BOLTS

RAM HAS (3) 19MM THREADED ATTACHMENT POINTS FORLIFTING. THE ATTACHMENT MEANS BETWEEN THE BARRIERRAMP AND THE LIFTING GEAR MUST BE SIZED OR DESIGNEDTO TAKE INTO CONSIDERATION BOTH VERTICAL LIFTING ASWELL AS SIDE LOADING CONDITIONS THE USE OF PROPERLYSIZED SPREADER BARS OR DUAL VERTICAL LIFTS ARERECOMMENDED.AM HA 3 PUNTI DI ATTACCO FOLETTATI DA 19MM PER SOLLEVAMENTO. I MEZZI DI SOLLEVAMENTO TRA LA RAMPA DELLA BARRIERA ED IL DISPOSITIVO DI SOLLEVAMENTO DEVE ESSERE DIMENSIONATO O PROGETTATO PER TENER CONTO SIA DEL SOLLEVAMENTO VERTIVALE CHE LE CONDIZIONI DI CARICO LATERALI. SI RACCOMANDA L'USO DI BARRE DI RIPARTIZIONE APPROPRIATAMENTE DIMENSIONATE O DI DUE SOLLEVATORI VERTICALI.

ANTI-SLIP FINISH ONBARRIER SURFACEFINITURA ANTISLITTAMENTO SULLA SUPERFICIE DELLA BARRIERA

PLAN VIEW - DOWN POSITION

ACCESS BOX MAY BE MOUNTED ON EITHER SIDESCATOLA DI ACCESSO PUO' ESSERE MONTATA SULL'ALTRO LATO

39.4"[1000mm]

24"[610mm]

78.5"[1990mm]

3"[80mm]

ISOMETRIC VIEW

A

A

BC

D

FOUNDATION - ASBESTOS FREE ASPHALT EMULSION UNDERCOAT.

WHITE W/ 150 MM WIDE YELLOW STRIPES

WHITE W/ 150 MM WIDE RED STRIPESBLACK W/ 150 MM WIDE YELLOW STRIPES

LIMIT SWITCH, FULLY DOWNLIMIT SWITCH, FULLY UP

HEATER, 1400 WATTS @ 120 VOLTS

HEATER, 1400 WATTS @ 240 VOLTS

OPTIONAL AVAILABLE FEATURES (PARTIAL)

COLOR OPTIONS:

WHITE METAL AFTER FABRICATION AND PRIOR TO COATING.

ALL STEEL MEMBERS PER AISC STANDARDSWELDING DESIGN CRITERIA AWS D1.1, LATEST REVISION.

ALL MILD STEEL COMPONENTS SANDBLASTED TO NEAR4.

3.

2.

NOTES:

1.

B2006

PART NO.

B1294

B2005

B1293

HOT-DIP GALVANIZING PRIOR TO PAINTING GALV

A

A

BC

D

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:11

:10

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-513

WE

DG

E G

AT

E D

ET

AIL

-DE

TTAG

LIO C

ANCE

LLO

A CU

NEO

IBF

184

14090187

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: NOT TO SCALEA1

WEDGE GATE DETAIL

PARTICOLARE CANCELLO A CUNEO

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

1 TYP

152 MMTYP

152 MM

76 MM

101 MM

203 MMTYP

152 MM

101 MM

101 MM

152 MM

203 MMTYP

101 MM

152 MM

50 MM

152 MMTYP

25 MMABOVE

ROADWAYTYP

25mm SOPRA IL LIVELLO STRADALE,

TIP.

20REBAR

ARMATURA

508 MM

25 MM

3403 MM

609 MMBARRIERDEPTH

ALTEZZA BARRIERA

50 MM

762 MM

228 MM

609 MM

AA

SECTION B-BSEZIONE B-B

B

B

SECTION A-ASEZIONE A-A

TR

AF

FIC

DIR

EC

TIO

ND

IRE

ZIO

NE

DE

L T

RA

FFIC

O

PLAN VIEWVISTA IN PIANTA

SIDE VIEWVISTA LATERALE

355 MM

355 MM

2794 MM

(REF)

3505 MM MIN3556 MM MAX

2819 MM MIN2921 MM MAX

508 MM

508 MM

304 MM

304 MM

3505 MM MIN

3556 MM MAX

ROADWAY LEVELLIVELLO STRADALE

BARRIER FRAMETELAIO BARRIERA

ACCESS BOXPOZZETTO DI ACCESSO

#4 REBARBARRE Ø14

76 MM

ROADWAYLEVELLIVELLO STRADALE

1. CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALLDIMENSIONS AND CONDITIONS AT THE JOB SITE.

2. FOUNDATION CONCRETE MAY BE PLACED DIRECTLY INTO NEATEXCAVATIONS, PROVIDED THE SIDES OF THE EXCAVATION ARE STABLE.WHERE CAVING OCCURS, PROVIDE SHORING. TYPE AND METHOD OFSHORING SHALL BE AT CONTRACTORS OPTION.

3. THE EXCAVATION SHALL BE KEPT DRY AT ALL TIMES. GROUND WATER,IF ENCOUNTERED, SHALL BE PUMPED FROM THE EXCAVATION.

4. CONCRETE SHALL BE LABORATORY DESIGNED, MACHINE MIXED,PRODUCING 3,000 PSI (20,68 MPA) AT 28 DAYS.

5. CEMENT SHALL BE TESTED PORTLAND CEMENT CONFORMING TOASTM C150, TYPE II ONLY.

6. AGGREGATES SHALL CONFORM TO ASTM C33 & B GRADE PER STANDARDSPECIFICATIONS. MAXIMUM SIZE OF AGGREGATE SHALL BE 1-1/2 INCHES(38mm).

7. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TOASTM A615, GRADE 60 (60,000 PSI OR 413.7MPA).

8. HOOKS AND BENDS SHALL CONFORM TO ACI STANDARD 318. LATEST REVISION.INSIDE DIAMETER OFF HOOKS AND BENDS SHALL BE AT LEAST SIX (6) BARDIAMETERS.

9. PROVIDE SPACER BARS, CHAIRS, SPREADERS, BLOCKS, ETC. ASREQUIRED TO POSITIVELY HOLD THE STEEL IN PLACE BEFORE CONCRETEIS POURED.

10. CONCRETE SHALL BE CONVEYED FROM THE MIXER TO FINAL DEPOSITBY METHODS THAT WILL PREVENT SEPARATION OR LOSS OF MATERIALS.

11. CONCRETE SHALL BE THOROUGHLY CONSOLIDATED BY SUITABLE MEANSDURING PLACEMENT AND SHALL BE THOROUGHLY WORKED AROUNDREINFORCEMENT AND EMBEDDED FIXTURES AND CORNERS OF FORMS.

12. CONCRETE SHALL BE MAINTAINED ABOVE 50°F (10°C) AND IN AMOIST CONDITION FOR AT LEAST SEVEN (7) DAYS AFTER PLACEMENT.ADEQUATE EQUIPMENT SHALL BE PROVIDED FOR HEATING CONCRETEMATERIALS AND PROTECTING CONCRETE DURING FREEZING OR NEARFREEZING WEATHER.

13. WHERE EXTERIOR WALL FACE REQUIRES SHORING AND/OR FORMING,THE FORMS SHALL BE SUBSTANTIAL AND SUFFICIENTLY TIGHT TOPREVENT LEAKAGE. FORMS SHALL NOT BE REMOVED UNTIL THECONCRETE IS SEVEN (7) DAYS OLD.

14. BACKFILLING SHALL BE DONE BY DEPOSITING AND TAMPING INTOPLACE CLEAN SAND OR POURING LEAN CONCRETE, TO 95% COMPACTION.WATER JETTING SHALL NOT BE ALLOWED.

15. CONDUITS AND PIPES OF ALUMINUM SHALL NOT BE ALLOWED.16. CONSTRUCTION JOINTS NOT INDICATED ON THE DRAWINGS SHALL NOT

BE ALLOWED. WHERE A CONSTRUCTION JOINT IS TO BE MADE, THESURFACE OF THE CONCRETE SHALL BE THOROUGHLY CLEANED ANDALL LAITANCE AND STANDING WATER REMOVED.

17. CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALLADJACENT AREAS AGAINST DAMAGE AND SHALL REPAIR OR PATCH ALLDAMAGED AREAS TO MATCH EXISTING IMPROVEMENTS.

18. CONTRACTOR SHALL KEEP THE CONSTRUCTION AREA CLEAN AT ALLTIMES AND AT COMPLETION OF WORK, REMOVE ALL SURPLUS MATERIALS,EQUIPMENT AND DEBRIS AND LEAVE THE PREMISES IN A CLEANCONDITION ACCEPTABLE TO THE OWNER OR OWNER'S REPRESENTATIVE.

CONCRETE NOTES & RECOMMENDED SPECIFICATIONS:

76 MM

152 MM

152 MM

152 MM

152 MM

152 MM

152 MM

1. L'APPALTATORE DOVRA' VERIFICARE E SARA' RESPONSABILE PER TUTTE LE DIMENSIONI E LE CONDIZIONI SUL CANTIERE.

2. LA FONDAZIONE IN CLS PUO' ESSERE POSTA DIRETTAMENTE NELLO SCAVO PULITO, SEMPRE CHE I LATI DELLO SCAVO SIANO STABILI. LADDOVE CI FOSSERO DEI CEDIMENTI PREDISPORRE PUNTELLATURE. TIPO E METODO DI PUNTELLAMENTO SARANNO A CURA E DISCREZIONE DELL'APPALTATORE.

3. LO SCAVO SARA' MANTENUTO ASCIUTTO AD OGNI MOMENTO. ACQUA DI FALDA SE INCONTRATA SARA' POMPATA DALLO SCAVO.

4. IL CALCESTRUZZO SARA' DISEGNATO IN LABORATORIO, MESCOLATO A MACCHINA PER PRODURRE 20.68 MPa A 28GG.

5. IL CEMENTO SARA' PORTLAND TESTATO IN CONFORMITA' CON ASTM C150, TIPO II SOLAMENTE.

6. GLI AGGREGATI SARANNO IN CONFORMITA' CON ASTM C33 PER SPECIFICHE STANDARD. LA DIMENSIONE MASSIMA DEGLI AGGREGATI SARA' 38mm.

7. L'ARMATURA DI ACCIAIO SARA' FORMATA DA BARRE AD ADERENZA MIGLIORATA CONFORMI ASTM A615, GRADO 60 413MPa.

8. GANCI E PIEGATURE SARANNO IN CONFORMITA' CON STANDARD ACI 318 ULTIMA REVISIONE. DIAMETRI INTERNI DI GANCI E PIEGATURE SARANNO ALMENO SEI (6) DIAMETRI DI BARRE.

9. PREDISPORRE SPAZIATORI, APPOGGI, SEPARATORI, BLOCCHI ECC. COME RICHIESTO PER SOSTENERE POSITIVAMENTE L'ACCIAIO IN POSIZIONE PRIMA DEL GETTO DI CLS.

10. IL CLS SARA' TRASPORTATO DAL MIXER AL DEPOSITO FINAL CON METODI CHE PREVENGANO LA SEPARAZIONE O PERDITA DI MATERIALE.

11. IL CLS SARA' CONSOLIDATO COMPLETAMENTE ATTRAVERSO METODI APPROPRIATI DURANTE IL GETTO E SARA' DISTRIBUITO INTORNO ALL'ARMATURA ED ALTRI ELEMENTI INCASSATI E GLI ANGOLI DELLE CASSEFORME.

12. IL CLS SARA' MANTENUTO AL DI SOPRA DEI 10°C E IN CONDIZIONI UMIDE PER ALMENTO 7GG DAL GETTO. ATTREZZATURA ADEGUATA SARA' FORNITA PER IL RISCALDAMENTO DEI MATERIALI E LA PROTEZIONE DEL CLS DURANTE LE GELATE O CONDIZIONI PROSSIME AL CONGELAMENTO.

13. LADDOVE LA SUPERFICIE DELLA PARETE ESTERNA RICHIEDA PUNTELLAMENTO E/O CASSEFORME, LE SUDDETTE SARANNO IMPORTANTI E SUFFICIENTEMENTE STRETTE DA IMPEDIRE PERDITE. LE CASSEFORME NON SARANNO RIMOSSE FINCHE' IL CLS SIA STAGIONATO 7GG.

14. IL RIEMPIMENTO SARA' EFFETTUATO CON IL DEPOSITO E COMPATTAZIONE DI SABBIA O CALCESTRUZZO MAGRO, AL 95% DI COMPATTAZIONE. SPRUZZI DI ACQUA NON SONO AMMESSI.

15. CANALINE E TUBAZIONI DI ALLUMINIO NON SONO AMMESSE.16. I GIUNTI DI COSTRUZIONE NON INDICATI NELLE TAVOLE NON SONO

AMMESSI. LADDOVE UN GIUNTO DI COSTRUZIONE VA INSERITO, LA SUPERFICIE DEL CLS SARA' PULITA COMPLETAMENTE E TUTTI I RESIDUI E ACQUA STAGNANTE SARANNO RIMOSSI.

17. L'APPALTATORE SARA' RESPONSABILE PER LA PROTEZIONE DI TUTTE LE AREE ADIACENTI CONTRO DANNI E DOVRA' RIPARARE TUTTE LE AREE DANNEGGIATE IN CONDIZIONI COME DA MIGLIORAMENTI ESISTENTI.

18. L'APPALTATORE DOVRA' MANTENERE L'AREA INTERESSATA DALLA COSTRUZIONE PULITA IN OGNI MOMENTO E AL COMPLETAMENTO DEL LAVORO RIMUOVERE TUTTI I MATERIALI DI RISULTA, ATTREZZATURE E RESIDUI E LASCIARE L'AREA IN CONDIZIONI PULITE ACCETABILI AL PROPRIETARIO O AI RAPPRESENTANTI DEL PROPRIETARIO.

NOTE CALCESTRUZZO E SPECIFICHE RACCOMANDATE:

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:11

:16

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

E-514

WE

DG

E G

AT

E F

OU

ND

AT

ION

DE

TA

IL -

DETT

AGLIO

FON

DAZI

ONE

CANC

ELLO

A C

UNEO

IBF

185

14090188

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: NOT TO SCALEA1

WEDGE GATE FOUNDATION DETAIL DETTAGLIO FONDAZIONE BARRIERA A CUNEOSCALA: NON IN SCALA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:33

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-601

LUM

INA

IRE

SC

HE

DU

LES

-OR

ARI D

EGLI

APP

AREC

CHI

KVK

186

14090189

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

NOTE GENERALI:

A. I CORPI ILLUMINANTI AVRANNO FINITURA DI FABBRICA IN COLORE ARGENTO. I PALI E I BRACCI SARANNO IN ACCIAIO

GALVANIZZATO.

B. FORNIRE PER II PALI GRUPPI DI BASE FRANGIBILI DOVE INDICATO NEI DISEGNI.

C. IL SUFFISSO "CAM" AGGIUNTO ALLA FINE DELL'IDENTIFICATIVO DEL CORPO ILLUMINANTE INDICA CHE UNA TELECAMERA TVCC

SARA' AGGIUNTA IN CAMPO AL PALO. IL COSTRUTTORE DOVRA' PROGETTARE IL PALO PER INSTALLARE LE TELECAMERE.

VEDI DETTAGLIO SU B2-E509.

GENERAL NOTES

A. LUMINAIRES SHALL HAVE FACTORY SILVER FINISH. POLES AND MOUNTING ARMS SHALL BE GALVANIZED STEEL.

B. PROVIDE FRANGIBLE BASE ASSEMBLY FOR POLES WHERE INDICATED ON DRAWINGS.

C. SUFFIX "-CAM" ADDED TO THE END OF THE LUMINAIRE ID INDICATES THAT FIELD INSTALLED CCTV CAMERAS WILL BE ADDED

TO THE POLE. MANUFACTURER SHALL DESIGN POLE TO ACCOMMODATE CAMERAS. SEE DETAIL ON B2-E509.

D2TWO LUMINAIRES, 2m ARM, 4000K, ROUND

TAPERED STEEL POLELED

15,000

(EACH)

182

(EACH)TYPE II 230 POLE 9m

S4SINGLE, 4000K, ROUND TAPERED STEEL

POLELED 9,000 75 TYPE IV 230 POLE 9m

S3SINGLE, 4000K, ROUND TAPERED STEEL

POLELED 9,000 75 TYPE III 230 POLE 9m

TYPE LUMENS WATTS TYPE HEIGHTID DESCRIPTION

SOURCEDISTRIBUTION VOLTS

MOUNTING

LUMINAIRE SCHEDULE - SITE

NOTE: WHERE LUMINAIRES ARE SHOWN ON THE DRAWINGS AS EMERGENY TYPE, PROVIDE INTEGRAL BATTERY AND EMERGENCY DRIVER AND REMOTE

TEST SWITCH

NOTA: DOVE LE ARMATURE ILLUMINANTI SONO INDICATE SUI DISEGNI COME TIPO IN EMERGENZA, FORNIRE BATTERIA E ALIMENTATORE DI EMERGENZA

INCORPORATO E INTERRUTTORE DI TEST REMOTO

X1 EMERGENCY EXIT SIGN LED - 10 230 CEILING -

H1 DOWNLIGHT, DAMP LOCATION LED 4,600 52 230 RECESSED CANOPY

G1 DOWNLIGHT LED 1,100 14 230 SURFACE -

F1 WEATHERPROOF WALLPACK LED 2,140 20 230 WALL 3m AFF

D3 WRAP LED 2,406 19 230 SURFACE / PENDANT -

D2 WRAP LED 7,074 58 230 SURFACE / PENDANT -

D1 WRAP LED 4,985 43 230 SURFACE / PENDANT -

B1 DOWNLIGHT LED 1,317 19 230 RECESSED -

A1 GRID TROFFER LED 2,230 22 230 RECESSED -

TYPE LUMENS WATTS TYPE HEIGHTID DESCRIPTION

SOURCEVOLTS

MOUNTING

LUMINAIRE SCHEDULE - BUILDING

GENERAL LIGHTING CONTROL SYSTEM NOTES

1. THE LIGHTING CONTROL DESIGNATION ON THE DRAWINGS INDICATES THE TYPE OF CONTROL REQUIRED IN THE CORRESPONDING ROOM/AREA. THE MANUFACTURER SHALL DETERMINE THE QUANTITY AND LOCATION OF SENSORS AND ACCESSORIES NECESSARY FOR COMPLETE COVERAGE AND PROPER SYSTEM OPERATION, AND PROVIDE DETAILED LAYOUT DRAWINGS ACCORDINGLY.

2. PROVIDE LOGIC BASED LOCAL RELAY/POWER DEVICES (WITH DIMMING WHERE APPLICABLE). THESE DEVICES SHALL HAVE DIGITAL PRIORITY ARRAYS TO ALLOW FOR MANIPULATION OF THE SEQUENCE OF OPERATIONS. DRY CONTACT LOGIC IS NOT ACCEPTABLE. RELAYS SHALL BE MECHANICALLY LATCHING TYPE.

3. ALL OCCUPANCY SENSORS SHALL BE LOW VOLTAGE CEILING MOUNTED. PROVIDE PASSIVE INFRARED (PIR) SENSORS IN CORRIDORS AND ULTRASONIC SENSORS IN RESTROOMS. ALL OTHER SENSORS SHALL BE DUAL TECHNOLOGY TYPE.

4. WALL CONTROL STATIONS SHALL BE LOW VOLTAGE WITH LED STATUS INDICATOR LIGHT. LINE VOLTAGE WALL DIMMERS ARE NOT ACCEPTABLE. EACH BUTTON SHALL HAVE ENGRAVED LABEL TO INDICATE FUNCTION SUCH AS ON/RAISE, OFF/LOWER.

5. PROVIDE INSTALLATION METHODS AND MATERIALS IN ACCORDANCE WITH SPECIFICATIONS, MANUFACTURER’S RECOMMENDATIONS AND AUTHORITY HAVING JURISDICTION, INCLUDING BUT NOT LIMITED TO WIRING TYPES AND REQUIREMENTS FOR SEPARATION FROM OTHER CIRCUITS/WIRING. PROVIDE PROGRAMMING, TESTING, OWNER TRAINING AND OPERATIONS AND MAINTENANCE MANUALS.

6. ALL WIRING SHALL BE INSTALLED IN CONTINUOUS RACEWAYS EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. WHEN IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE CODES AND LISTED FOR USE IN RETURN AIR PLENUMS, LOW VOLTAGE WIRING (30-VOLT OR LESS) MAY BE INSTALLED WITHOUT CONDUIT ABOVE ACCESSIBLE CEILINGS UNLESS NOTED OTHERWISE. ALL LOW VOLTAGE WIRING AT OTHER LOCATIONS (CONCEALED IN WALLS, ABOVE NON-ACCESSIBLE CEILINGS, EXPOSED AREAS WITHOUT CEILINGS, ETC.) SHALL BE INSTALLED IN CONDUIT. ALL CABLE INSTALLED WITHOUT CONDUIT SHALL BE NEATLY PLACED WITHIN JOIST SPACE ABOVE CEILINGS AND PROPERLY SUPPORTED. CABLE SHALL NOT BE PLACED ON OR SUPPORTED BY CEILING SYSTEM.

7. PROVIDE ISOLATED DRY CONTACTS FOR SENSORS WHERE INTEGRATED CONTROL OF HVAC OR OTHER AUTOMATED SYSTEMS ARE REQUIRED.

GENERAL NOTES

A. SEE GENERAL LIGHTING CONTROL SYSTEM NOTES THIS SHEET.B. PROVIDE PHOTOCELL INPUT FOR CONTROL OF SELECTED EXTERIOR LIGHTING CIRCUITS AS DIRECTED BY

THE FACILITY. PROVIDE HAND-OFF-AUTO CONTROL.C. THE LIGHTING CONTROL PANELS SHALL BE NETWORKED AND

ACCESSIBLE FOR PROGRAMMING FROM A REMOTECOMPUTER VIA THE DATA NETWORK. PROVIDE WIRING BETWEEN BUILDINGS AND PANELS ACCORDINGLY.

D. PROVIDE HARD-WIRED CONNECTIONS TO ALL SYSTEM COMPONENTS. BATTERY POWERED WIRELESS SYSTEMS AND/OR COMPONENTS ARE NOT ACCEPTABLE.

8 SPARE

7 SPARE

6 GE:11 SITE LIGHTING - RESPONSE ZONE

5 GE:9 SITE LIGHTING - APPOACH ZONE

4 GL1:14 SITE LIGHTING - PARKING LOT

3 GE:2 GATEHOUSE - EXTERIOR LIGHTING

2 GU:11 ID CHECK CANOPY LIGHTING

1 GE:7 ID CHECK CANOPY LIGHTING

CIRCUIT NO. LOCATIONLTG CKT NO.

PANEL & DESCRIPTION / REMARKS

LIGHTING CONTROL PANEL - LCGPANNELLO DI CONTROLLO ILLUMINAZIONE - LCG

8 SPARE

7 SPARE

6 SPARE

5 SPARE

4 SPARE

3 SE:2 SITE LIGHTING - RESPONSE ZONE

2 SU:4 SITE LIGHTING - AVB

1 SE:3 SEARCH OFFICE - EXTERIOR LIGHTS

CIRCUIT NO. LOCATIONLTG CKT NO.

PANEL & DESCRIPTION / REMARKS

LIGHTING CONTROL PANEL - LCSPANNELLO DI CONTROLLO ILLUMINAZIONE - LCS

d. MANUALE ON/REGOLAZIONE MANUALE/SENSORE ASSENZA OFF: LA PERSONA MANUALMENTE ACCENDE LA LUCE UNA VOLTA ENTRATO NELL'AMBIENTE. LA PERSONA PUO'

REGOLARE IL LIVELLO DELLA LUCE MANUALMENTE (AUMENTA O DIMINUISCE). LE LUCI SI SPENGONO DOPO UN PERIODO PRESTABILITO.

c. PRESENZA ON/REGOLAZIONE MANUALE/ASSENZA OFF: LA PERSONA ENTRA NELL'AMBIENTE E LE LUCI AUTOMATICAMENTE SI ACCENDONO AL 100% DEL FLUSSO LUMINOSO EMESSO. LA

PERSONA MANUALMENTE PUO' REGOLARE (IN AUMENTO O DIMINUZIONE) IL LIVELO DELLA LUCE. DOPO IL SEGNALE DI ASSENZA E LUCI SI SPENGONO DOPO UN PERIODO PRESTABILITO.

b. DOPO AVVIO AUTOMATICO L'ESTRATTORE PARTE E FUNZIONE PER 10 MINUTI DOPO IL RILEVAMENTO DI ASSENZA.

a. SOLO CONTROLLO MANUALE LOCALE

DESCRIZIONE DELLA STRATEGIA DEL CONTROLLO DELL'ILLUMINAZIONE

C. I CORPI ILLUMINANTI MOSTRATI CON CONNESSIONE AD UNA BATTERIA DI BACK-UP NON DEVONO ESSERE CONTROLLATI DA SENSORI DI PRESENZA.

B. L'INDICAZIONE DEL CONTROLLO DELL'ILLUMIAZIONE SUI DISEGNI DENOTA IL TIPO DI CONTROLLO RICHIESTO NELLA CORRISPONDENTE STANZA/AREA. IL PRODUTTORE DEVE DETERMNARE LA

QUANTITA' E LA POSIZIONE DEI SENSORI E DEGLI ACCESSORI NECESSARI PER LA COMPLETA COPERTURA E LA CORRETTA OPEATIVITA' DEL SISTEMA. VEDERE SPECIFICA SEZIONE 26 O9 46 PER

ULTERIORII REQUISITI.

A. OVE E' INDICATO UN DIMMER DA PARETE, FORNIRE UNA PULSANTIERA CON DUE INTERRUTTORI A PULSANTE (QUALORA NON INDICATO DIVERSAMENTE) CON CONTROLLO ON/SU E OFF/GIU'

PER CIASCUNA ZONA DI ILLUMINAMENTO COME INDICATO SUI DIISEGNI. OVE INDICATO SOLO ON/OFF PER CONTROLLO A PARETE , FORNIRE UNA PULSANTIERA A DUE ULSANTI CON ON E OFF.

CIASCUN AMBIENTE DEVE AVERE UN MINIMO DI UNA ZONA DI CONTROLLO E ZONE DI CONTROLLO AGGIUNTIVE COME INDICATO SUI DISEGNI.

NOTE GENERALI TABELLA CONTROLLO ILLUMINAZIONE

d. MANUAL ON/MANUAL ADJUST/VACANCY OFF: OCCUPANT MANUALLY TURNS THE LIGHTS ON UPON ENTERING SPACE. OCCUPANT CAN MANUALLY ADJUST (RAISE OR LOWER) LIGHT LEVEL.

UPON SENSING VACANCY LIGHTS TURN OFF AFTER TIME OUT PERIOD.

c. OCCUPANCY ON/MANUAL ADJUST/VACANCY OFF: OCCUPANT ENTERS SPACE AND LIGHTS AUTOMATICALLY TURN ON TO 100% OF FULL LIGHT OUTPUT. OCCUPANT CAN MANUALLY

ADJUST (RAISE OR LOWER) LIGHT LEVEL. UPON SENSING VACANCY THE LIGHTS TURN OFF AFTER TIMEOUT PERIOD.

b. UPON AUTO ON EXHAUST FAN SHALL START AND RUN FOR 10 MINUTES AFTER VACANCY IS DETECTED.

a. LOCAL MANUAL CONTROL ONLY

LIGHTING CONTROL STRATEGY DESCRIPTION

C. LUMINAIRES SHOWN WITH BATTERY BACK-UP POWER CONNECTION SHALL NOT BE CONTROLLED BY OCCUPANCY SENSORS.

B. THE LIGHTING CONTROL DESIGNATION ON THE DRAWINGS INDICATES THE TYPE OF CONTROL REQUIRED IN THE CORRESPONDING ROOM/AREA. THE MANUFACTURER SHALL DETERMINE THE

QUANTITY AND LOCATION OF SENSORS AND ACCESSORIES NECESSARY FOR COMPLETE COVERAGE AND PROPER SYSTEM OPERATION. SEE SPECIFICATION SECTION 26 09 46 FOR FURTHER

REQUIREMENTS.

A. WHERE DIMMER IS INDICATED FOR WALL CONTROL, PROVIDE ONE TWO BUTTON PUSHBUTTON SWITCH (UNLESS NOTED OTHERWISE) WITH ON/RAISE AND OFF/LOWER CONTROL FOR EACH

LIGHTING ZONE AS SHOWN ON THE DRAWINGS. WHERE ONLY ON/OFF IS INDICATED FOR WALL CONTROL, PROVIDE A TWO BUTTON STATION WITH ON AND OFF. EACH SPACE SHALL HAVE A

MINIMUM OF ONE ZONE OF CONTROL AND ADDITIONAL ZONES OF CONTROL ADDED AS SHOWN ON THE DRAWINGS.

LIGHTING CONTROL SCHEDULE GENERAL NOTES

E X GUARD BOOTH, OVERWATCHCABINA DI GUARDIA PREFABBRICATA, GARITTA a

D X EQUIPMENT, COMM. ROOMSALA APPARATI, LOCALE TELECOMUNICAZIONI a

C X X 10 X RESTROOMTOILETTE b, c

B X X 15 X BREAK, WAITINGBREAK, ATTESA d

A X SEARCH OFFICE, COMMAND AND CONTROLUFFICIO CONTROLLO, COMANDO E CONTROLLO a

CE

ILIN

G M

OU

NT

OC

CU

PA

NT

DE

TEC

TIO

NR

ILE

VA

TOR

E D

I PR

ES

EN

ZA A

SO

FFIT

TO

LUM

INA

IRE

MO

UN

T O

CC

UP

AN

T D

ETE

CTI

ON

RIL

EV

ATO

RE

DI P

RE

SE

NZA

MO

NTA

TO S

U C

OR

PO

ILLU

MIN

AN

TE

AU

TO O

N (5

0%)

AU

TO O

N (1

00%

)

MA

NU

AL

ON

(VA

CA

NC

Y S

EN

SO

R)

AC

CE

NS

ION

E M

AN

UA

LE/(S

EN

SO

RE

DI A

SS

EN

ZA)

OC

CU

PA

NT

DE

TEC

TIO

N T

IME

-OU

T (3

0 M

IN. M

AX

)R

ITA

RD

O IN

US

CIT

A R

ILE

VA

TOR

E D

I PR

ES

EN

ZA (3

0 M

INU

TI M

AX

.)

ON

/OFF

AC

CE

SS

O/S

PE

NTO

ON

/OFF

DIM

ME

RD

IMM

ER

AC

CE

SS

O/S

PE

NTO

DE

SIG

NA

TIO

ND

ES

IGN

AZI

ON

E

OCCUPANCY DETECTIONWALL

CONTROL

DA

YLI

GH

T S

EN

SO

R C

ON

TRO

L - D

IMM

ING

CO

NTR

OLL

O S

EN

SO

RE

LU

CE

ES

TER

NA

- R

EG

OLA

ZIO

NE

EX

AM

PLE

SP

AC

E T

YP

EE

SE

MP

IO T

IPO

LOG

IE D

I AM

BIE

NTE

RE

MA

RK

SO

SS

ER

VA

ZIO

NI

LIGHTING CONTROL STRATEGY SCHEDULE...

NOTE DEL SISTEMA DI CONTROLLO GENERALE DI ILLUMINAZIONE

1. L’INDICAZIONE DEL SISTEMA DI CONTROLLO SUI DISEGNI INDICA IL TIPO DI CONTROLLO RICHIESTO NELLA RISPETTIVA STANZA/AREA. IL PRODUTTORE DEVE DETERMINARE LA QUANTITA’ ED IL POSIZIONAMENTO DEI SENSORI E DEGLI ACCESSORI NECESARRI ALLA COMPLETA COPERTURA E CORRETTA OPERATIVITA’ DEL SISTEMA, E FORNIRE CONSEGUENTEMENTE DISEGNI DI LAYOUT DETTAGLIATI .

2. FORNIRE CON BASE LOGICA RELE’/COMPONENTI DI POTENZA (CON DIMMER OVE APPLICABILE). QUESTI COMPONENTI DOVRANNO AVERE ARRAY DI PRIORITA’ DIGITALE PER CONSENTIRE LA MODIFICA DELLA SEQUENZA DELLE OPERAZIONI. LOGICA CON CONTATTI SENZA POTENZIALE NON E’ ACCETTABILE. I RELE’ DOVRANNO ESSERE CON RITENUTA MECCANICA.

3. TUTTI I SENSORI DI PRESENZA DOVRANNO ESSERE A BASSA TENSIONE MONTATI A SOFFITTO. FORNIRE SENSORI AD INFRAROSSI PASSIVI (PIR) NEI CORRIDOI E AD ULTRASUONI NELLE TOILETTE. TUTTI GLI ALTRI SENSORI SARANNO A DOPPIA TECNOLOGIA.

4. LE STAZIONI DI CONTROLLO DA PARETE DEVONO ESSERE IN BASSA TENSIONE CON LED INDICATORI DELLO STATO DELLE LUCI. DIMMER DA PARETE A TENSIONE DI RETE NON SONO ACCETTABILI. CIASCUN PULSANTE AVRA’ ETICHETTA INCISA CHE NE MOSTRI LA FUNZIONE ON/AUMENTA, OFF/DIMINUISCE.

5. FORNIRE METODI DI INSTALLAZIONE E MATERIALI IN ACCORDO CON LE SPECIFICHE, LE RACCOMANDAZIONI DEI PRODUTTORI E DELLA AUTORITA’ AVENTE GIURISDIZIONE, INCLUSO MA NON LIMITATO AI TIPI DI CAVO ED ALLE PRESCRIZIONI PER LA SEPARAZIONE DA ALTRI CIRCUITI/CAVI, FORNIRE PROGRAMMAZIONE, PROVE, TRAINING DEL PROPRIETARIO E MANUALI DI USO E MANUTENZIONE.

6. TUTTI I CABLAGGI SARANNO INSTALLATI IN CAVIDOTTI CONTINUI, AD ECCEZIONE SE NON DIVERSAMENTE INDICATO. QUANDO IN CONFORMITA’ DEL NEC E DI ALTRI CODICI APPLICABILI E PRECRITTI PER L’USO NEI PLENUM DI RITORNO DELL’ARIA, CIRCUITI IN BASSA TENSIONE (30 VOLT O MENO) POSSONO ESSERE INSTALLATI SENZA TUBAZIONE NEI CONTROSOFFITTI SE NON DIVERSAMENTE INDICATO. TUTTI I CABLGGI IN BASSA TENSIONE NELLE ALTRE UBICAZIONI (INCASSATI NELLE PARETI, SOPRA CONTROSOFFITTI NON ACCESSIBILI, AREE A GIORNO SENZA CONTROSOFFITTI, ETC.) DEVONO ESSERE INSTALLATI IN TUBAZIONE. TUTTI I CAVI INSTALLATI SENZA CONDUIT DEVONO ESSERE ORDINATAMENTE INSTALLATI ALL’INTERNO DELLO SPAZIO DEI TRAVETTI SOPRA I SOFFITTI ED OPPORTUNAMENTE SOSTENUTI. I CAVI NON POSSONO ESSERE UBICATI O SOSTENUTI DALLA STRUTTURA DEL SOFFITTO.

7. FORNIRE CONTATTI SENZA POTENZIALE ISOLATI PER I SENSORI QUANDO SIANO RICHIESTI CONTROLLI INTEGRATI CON HVAC O ALTRI SISTEMI AUTOMATICI.

NOTE GENERALI:

A. VEDI NOTE GENERALI SISTEMA DI CONTROLLO ILLUMINAZIONE SU QUESTA TAVOLAB. FORNIRE INGRESSO FOTOCELLULA PER CIRCUITI SELEZIONATI DELL'ILLUMINAZIONE ESTERNA COME

DEFINITO DALLA FACILITY. FORNIRE CONTROLLO MANUALE-OFF-AUTOMATICO-C. I PANNELLI DI CONTROLLO DELL'ILLUMINAZIONE SARANNO COLLEGATI IN RETE ED ACCESSIBILI PER LA

PROGRAMMAZIONE DA UN COMPUTER REMOTO VIA RETE DATI. FORNIRE IL CABLAGGIO RELATIVO TRA GLI EDIFICI ED I PANNELLI.

D. FORNIRE COLLEGAMENTI IN CAVO TRA TUTTI I COMPONENTI DEL SISTEMA. BATTERIE E/O COMPONENTI ALIMENTATI CON SISTEMA SENZA FILI NON SONO ACCETTABILI

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:34

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-602

PA

NE

L S

CH

ED

ULE

S -

ORAR

I DEL

PAN

NELL

O

KVK

187

14090190

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

DESIGN LOAD (KVA)... 0.0 0.0 0.0 93.0 18.6 111.6 161 DESIGN AMPS

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 134 CONNECTED AMPS

CONNECTED LOAD (KVA)... 0.0 0.0 0.0 93.0 --- 93.0 400 LINE-TO-LINE VOLTS

LTS REC MECH MISC SPARE TOTAL

LOAD SUMMARY

20 SPD 30 3

19

181716151413121110987654 PV SOLAR 30 3 System size TBD. PV inverter located in Search Office.3 PANEL GL1 37.0 160 3 Located in Gatehouse.2 PANEL SE (ATS) 47.3 200 3 Located in Search Office.1 PANEL SL1 8.7 160 3 Located in Search Office.

NO. DESCRIPTION LTS REC MECH MISC AMPS PCKT CONNECTED LOAD (kVA) OCP

REMARKS

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

400/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

400 ENCLOSURE:CARPENTERIA:

IP30

DISTRIBUTION PNL: DPSQUADRO DI DISTRIBUZIONE PNL: DPS

DESIGN LOAD (KVA)... 0.0 1.4 5.5 1.8 1.7 10.4 15 DESIGN AMPS PHASE C (KVA) 2

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 13 CONNECTED AMPS PHASE B (KVA) 3

CONNECTED LOAD (KVA)... 0.0 1.4 5.5 1.8 --- 8.7 400 LINE-TO-LINE VOLTS PHASE A (KVA) 4

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

41 C 42

39 B 40

37 A

30 3 SPD

38

35 C 36

33 B 34

31 A 32

29 C 30

27 B 28

25 A 26

23 C 24

21 B 22

19 A 20

17 SPARE 20 1 C 20 1 SPARE 18

15 SPARE 20 1 B 20 1 SPARE 16

13 SPARE 20 1 A 20 1 SPARE 14

11 PV MONITORING 500 20 1 C 20 1 1,679 HP-05 12

9 GENERATOR CHARGER 500 20 1 B 20 1 1,679 HP-04 10

7 GENERATOR HEATER 750 20 1 A 20 1 2,134 HP-03 8

5 SPARE 20 1 C 30 1 SPARE 6

3 REC SEARCH OFF. 360 20 1 B 20 1 180 REC ELEC/MECH RM 4

1 REC EXTERIOR 720 20 1 A 20 1 180 REC ELEC/MECH RM 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

63/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

160 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: SL1

DESIGN LOAD (KVA)... 1.4 0.0 0.0 46.1 9.4 56.9 82 DESIGN AMPS PHASE C (KVA) 15

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 68 CONNECTED AMPS PHASE B (KVA) 15

CONNECTED LOAD (KVA)... 1.1 0.0 0.0 46.1 --- 47.2 400 LINE-TO-LINE VOLTS PHASE A (KVA) 16

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

41 C 42

39 B 40

37 A

30 3 SPD

38

35 C 36

33 B 34

31 A 32

29 C 30

27 B 28

25 A 26

23 C 24

21 SPARE 20 1 B 22

19 SPARE 20 1 A 20

17 SPARE 20 1 C 20 1 SPARE 18

15 B 20 1 SPARE 16

13 A 20 1 SPARE 14

11

SPARE 50 3

C 1,900 12

9 13,467 B 1,900 10

7 13,467 A

40 3

1,900

PANEL GE

8

5

UPS INPUT

13,467

100 3

C 20 1 SPARE 6

3 LTS-EXTERIOR 100 20 1 B 20 1 SPARE 4

1 LTS-INTERIOR 168 20 1 A 20 1 814 SITE LTG-RESP. ZN 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

200/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

200 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: SEQUADRO DI DISTRIBUZIONE PNL: SE

DESIGN LOAD (KVA)... 1.0 0.0 0.0 39.6 8.1 48.7 70 DESIGN AMPS PHASE C (KVA) 8

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 58 CONNECTED AMPS PHASE B (KVA) 17

CONNECTED LOAD (KVA)... 0.8 0.0 0.0 39.6 --- 40.4 400 LINE-TO-LINE VOLTS PHASE A (KVA) 15

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

41 SPARE 20 1 C 42

39 SPARE 20 1 B 40

37 SPARE 20 1 A

30 3 SPD

38

35 SPARE 20 1 C 20 1 SPARE 36

33 SPARE 20 1 B 20 1 SPARE 34

31 SPARE 20 1 A 20 1 SPARE 32

29 SPARE 20 1 C 20 1 SPARE 30

27 SPARE 20 1 B 20 1 2,400 CCTV CAM - SITE 28

25 SPARE 20 1 A 20 1 1,200 CCTV CAM - SITE 26

23 SPARE 20 1 C 20 1 SPARE 24

21 SPARE 20 1 B 20 1 SPARE 22

19 SPARE 20 1 A 20 1 SPARE 20

17 5,200 C 20 1 SPARE 18

15 5,200 B 30 1 5,760 AVB 16

13

PANEL GU

5,200

40 3

A 30 1 5,760 AVB 14

11 967 C 1,433 12

9 967 B 1,433 10

7

PANEL SUT

967

40 3

A

40 3

1,433

PANEL OW

8

5 VDL 500 20 1 C 20 1 44 LTS-SEARCH OFF. 6

3 VDL 500 20 1 B 20 1 728 SITE LTG-AVB 4

1 REC-VID SURVEIL. 500 20 1 A 20 1 200 DOOR OPERATORS 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

100/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

160 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: SUQUADRO DI DISTRIBUZIONE PNL: SU

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:48

:37

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

E-603

PA

NE

L S

CH

ED

ULE

S -

ORAR

I DEL

PAN

NELL

O

KVK

188

14090191

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

* INDICATES GFI BREAKER

DESIGN LOAD (KVA)... 0.6 4.9 22.3 0.0 5.5 33.3 48 DESIGN AMPS PHASE C (KVA) 3

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 40 CONNECTED AMPS PHASE B (KVA) 11

CONNECTED LOAD (KVA)... 0.5 4.9 22.3 0.0 --- 27.6 400 LINE-TO-LINE VOLTS PHASE A (KVA) 13

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

41 C 42

39 B 40

37 A

30 3 SPD

38

35 C 36

33 B 34

31 SPARE 20 1 A 20 1 720 ID CHECK-POLE REC. 32

29 SPARE 20 1 C 30

27 SPARE 20 1 B 28

25 ID CHECK-HVAC 2,500 20 1 A

20 3 SPARE

26

23 ID CHECK-HVAC 2,500 20 1 C 24

21 HP-02 1,679 20 1 B 22

19 HP-01 7,582 30 1 A

20 3 SPARE

20

17 SPARE 30 1 C 20 1 SPARE 18

15 EWH-01 3,000 30 1 B 30 1 5,000 EUH-01 16

13 EF-02 30 20 1 A 20 1 450 SITE LTG-PARKING 14

11 EF-01 30 20 1 C 20 1 540 REC - ID CHECK 12

9 REC EXTERIOR 720 20 1 B 20 1 540 REC - ID CHECK 10

7 REC MECH RM 180 20 1 A *20 1 180 REC BREAK RM 8

5 REC MECH RM 180 20 1 C 20 1 180 REC BREAK RM 6

3 REC MECH RM 180 20 1 B 20 1 180 REC BREAK RM 4

1 REC CMD/CNTRL 360 20 1 A 20 1 900 REC GENERAL 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

100/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

160 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: GL1QUADRO DI DISTRIBUZIONE PNL: GL1

DESIGN LOAD (KVA)... 3.1 0.0 3.3 0.0 1.2 7.5 11 DESIGN AMPS PHASE C (KVA) 3

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 8 CONNECTED AMPS PHASE B (KVA) 2

CONNECTED LOAD (KVA)... 2.5 0.0 3.3 0.0 --- 5.8 400 LINE-TO-LINE VOLTS PHASE A (KVA) 1

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

41 C 42

39 B 40

37 A

30 3 SPD

38

35 C 36

33 B 34

31 A 32

29 C 30

27 B 28

25 A 26

23 C 24

21 B 22

19 A 20

17 SPARE 20 1 C 18

15 SPARE 20 1 B 16

13 SPARE 20 1 A 14

11 SITE LTG-RESPONSE 953 20 1 C 20 1 SPARE 12

9 SITE LTG-APPROACH 375 20 1 B 20 1 SPARE 10

7 SITE LTG-CANOPY 728 20 1 A 20 1 SPARE 8

5 LTG - INTERIOR 270 20 1 C 20 1 1,650 CANOPY GATE ARM 6

3 SPARE 20 1 B 20 1 1,650 CANOPY GATE ARM 4

1 LTG RM 101 28 20 1 A 20 1 100 LTS-EXTERIOR 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

63/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

160 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: GEQUADRO DI DISTRIBUZIONE PNL: GE

DESIGN LOAD (KVA)... 0.6 1.3 0.1 13.8 3.1 18.9 27 DESIGN AMPS PHASE C (KVA) 6

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 23 CONNECTED AMPS PHASE B (KVA) 6

CONNECTED LOAD (KVA)... 0.5 1.3 0.1 13.8 --- 15.7 400 LINE-TO-LINE VOLTS PHASE A (KVA) 3

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

41 C 42

39 B 40

37 A

30 3 SPD

38

35 C 36

33 SPARE 20 1 B 34

31 SPARE 20 1 A 32

29 SPARE 20 1 C 30

27 CCTV CAM - GUARD 600 20 1 B 28

25 SPARE 20 1 A

20 3 SPARE

26

23 CCTV CAM - SITE 1,800 20 1 C 52 24

21 CCTV CAM - SITE 900 20 1 B 540 22

19 DOOR OPERATORS 200 20 1 A

20 3

50ID CHECK-LTG, SEC,DOOR OP, INT RECEPT

20

17 LANE STROBE/HORN 1,500 20 1 C 52 18

15 CCTV CAM - CANOPY 900 20 1 B 540 16

13 CCTV CAM - CANOPY 900 20 1 A

20 3

50ID CHECK-LTG, SEC,DOOR OP, INT RECEPT

14

11 SITE LTG-CANOPY 312 20 1 C 20 1 1,500 LANE OSP 12

9 MAIN CNTRL PNL 500 20 1 B 20 1 1,500 LANE LCS 10

7 IT RACK 750 20 1 A 20 1 88 LTS-CMD/CNTRL 8

5 IT RACK 750 20 1 C 20 1 180 REC COMM. RM 6

3 REC-VID SURVEIL. 500 20 1 B 20 1 500 REC-SEC CNTRL PNL 4

1 REC-VID SURVEIL. 500 20 1 A 20 1 500 REC-SEC CNTRL PNL 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

63/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

160 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: GUQUADRO DI DISTRIBUZIONE PNL: GU

1

1. PROVIDE GFI BREAKER FOR REFRIGERATOR CIRCUIT

NEW WORK KEYNOTES

DESIGN LOAD (KVA)... 0.0 1.9 0.0 1.0 0.6 3.4 5 DESIGN AMPS PHASE C (KVA) 2

DEMAND FACTORFATTORE DI CARICO...

1.25 1.00 1.00 1.00 20% --- 4 CONNECTED AMPS PHASE B (KVA) 1

CONNECTED LOAD (KVA)... 0.0 1.9 0.0 1.0 --- 2.9 400 LINE-TO-LINE VOLTS PHASE A (KVA) 0

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

23 C 24

21 B 22

19 A

30 3 SPD

20

17 C 18

15 B 16

13 A 14

11 SPARE 20 1 C 20 1 SPARE 12

9 SPARE 20 1 B 20 1 SPARE 10

7 SPARE 20 1 A 20 1 SPARE 8

5 REC IT RACK 750 20 1 C 20 1 750 REC IT RACK 6

3 SEC CNTRL PNL 500 20 1 B 20 1 500 SEC CNTRL PNL 4

1 REC COMM. RM 180 20 1 A 20 1 180 REC COMM. RM 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO:

NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA):

25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DIPROTEZIONE:

63/3 MOUNTING:MONTAGGIO:

SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A):

160 ENCLOSURE:CARPENTERIA:

IP30

PANELBOARD NO: SUTQUADRO DI DISTRIBUZIONE PNL: SUT

1. FORNIRE INTERRUTTORE MAGNETOTERMICO DIFFERENZIALE PER CIRCUITO FRIGORIFERO

DESIGN LOAD (KVA) 0.2 0.4 2.5 1.4 0.9 5.2 8 DESIGN AMPS PHASE C (KVA) 0

DEMAND FACTOR 1.25 1.00 1.00 1.00 20% --- 6 CONNECTED AMPS PHASE B (KVA) 1

CONNECTED LOAD (KVA) 0.1 0.4 2.5 1.4 --- 4.3 400 LINE-TO-LINE VOLTS PHASE A (KVA) 4

LTS REC MECH MISC SPARE TOTAL PHASE BALANCE

LOAD SUMMARY

23 C 24

21 B 22

19 A

30 3 SPD

20

17 C 18

15 B 16

13 SPARE 20 1 A 20 1 SPARE 14

11 SPARE 20 1 C 20 1 SPARE 12

9 CCTV CAM 300 20 1 B 20 1 SPARE 10

7 REC-VID SURVEIL. 500 20 1 A 20 1 2,500 HVAC 8

5 LTS-EXTERIOR 20 20 1 C 20 1 50 DOOR OPERATOR 6

3 REC EXTERIOR 180 20 1 B 20 1 116 LTS - INTERIOR 4

1 REMOTE CNTRL PNL 500 20 1 A 20 1 180 REC 2NO. DESCRIPTION LTS REC MECH MISC AMPS P AMPS P LTS REC MECH MISC DESCRIPTION NO.CKT CONNECTED LOAD (VA) OCP OCP CONNECTED LOAD (VA) CKT

200% NEUTRAL:200% NEUTRO:

NO SERVICE ENTRANCE LABEL:TARGA INGRESSO SERVIZIO: NO

WIRE:CONUTTORI:

4+GND INTERRUPTING RATING (KA):POTERE DI INTERRUZIONE (KA): 25

PHASE:FASI:

3 MAIN OC DEVICE:DISPOSITIVO PRINCIPALE DI PROTEZIONE: 63/3 MOUNTING: SURFACE

VOLTAGE:TENSIONE:

400Y/230 BUS RATING (A):PORTATA SBARRE (A): 160 ENCLOSURE: IP30

PANELBOARD NO: OWQUADRO DI DISTRIBUZIONE PNL: OW

SY

MD

ES

CR

IPTI

ON

DA

TEA

PP

R

12

10

11

RCP

3

2

LCP

5

4

3

3

TO PLC

FINAL DENIAL BARRIER (OUTBOUND)BARRIERA DI RIFIUTO FINALE (IN USCITA)

OVERWATCHGARITTA

TO PLC

2

LCP

5

4

FINAL DENIAL BARRIER (INBOUND)BARRIERA DI RIFIUTO FINALE (IN INGRESSO)

TO PLC TO PLC

14

COMM ROOM BREAK ROOM

14

R

9

MS

15

D

16

13

17

MCPR

9

12

D

16

13

SITE

TO SEC

TO SECTO SEC

COMMAND & CONTROL

JSHJ

LCS

7

8

JSH

JLCS

CANOPYTETTOIA

TO PLC TO PLC TO SEC

SHEET NOTES

1. REFER TO SHEET EY-003 FOR GENERAL NOTES, SYMBOLS AND ABBREVIATIONS.

2. ALL WORK INDICATED ON THIS SHEET IS GFGI AND ROUGH IN ONLY EXCEPT FOR ALL WORK RELATED TO FINAL AVB'S. PROVIDE ALL ROUGH INS AT A MIN OF 25.4MM CONDUIT. PROVIDE A SPARE 25.4MM CONDUIT AND PULL WIRE TO EACH CAMERA LOCATION FOR FUTURE USE. ALL WIRING UTILIZED FOR SECURITY SHALL BE YELLOW IN COLOR TO ALLOW FOR IDENTIFICATION BY THE OWNER.

3. PROVIDE A SPARE 19MM CONDUIT AND PULL WIRE TO ALL RCP AND LCP PANELS FOR CONNECTION OF IDS TAMPER SWITCH.

KEY NOTES:

1. WRONG WAY DETECTION - DIPOLE VDL'S.2. LOCAL CONTROL PANEL AT FINAL AVB FOR MAINTENANCE.3. DIPOLE VDL'S AT FINAL AVB.4. TRAFFIC CONTROL SIGNAL AT AVB.5. FINAL AVB'S.6. NOT USED.7. WRONGWAY DETECTION SIGNAGE AND HORN / SOUNDER.8. LANE CONTROL SIGNALING DEVICE.9. ACCESS CONTROL CARD READER / INTERCOM AND CONNECTION

TO DPS / LOCK / REX.10. REMOTE CONTROL PANEL (PLUG IN) TO BE USED AT OVERWATCH

POSITION.11. REMOTE CONTROL PANEL (RCP) BASE UNIT FOR RCP PLUG IN

CONNECTION.12. TYPICAL SITE CAMERAS REFER TO PLANS FOR LOCATION.13. DURESS ALARM PUSH BUTTON DEVICES.14. IDS DOOR POSITION SWITCHES FOR COMM ROOM AND EQUIPMENT ROOM

ENTRY DOORS.15. MOTION SENSOR FOR COMMAND AND CONTROL ROOM AND SEARCH

BUILDING.16. VIDEO SURVEILANCE MONITORS.17 MAIN GRAPHIC CONTROL PANEL FOR OPERATION OF ALL ACP DEVICES.18. EMERGENCY FAST OPERATION BUTTON FOR FINAL AVB DEPLOYMENT.19. SECURITY EQUIPMENT CABINET LOCATION FOR ALL AVB EQUIPMENT AND PLC

CONTROLLED DEVICES AND ALL GFGI EQUIPMENT INCLUDING VIDEO SURVEILLANCE, ACCESS CONTROL, DURESS, AND IDS.

20. (1) 50MM C BACK TO SEC THROUGH HANDHOLE. REFER TO FLOOR PLANS FOR LOCATIONS AND ROUTE.

21. (2) 50MM CONDUITS FROM SEC IN COMMAND AND CONTROL BUILDING TO SEC IN SEARCH BUILDING. (1) ACTIVE (1) SPARE WITH PULL WIRE.

22. (2) 50MM CONDUITS FROM SEC IN SEARCH BUILDING TO BUILDING 110 VIA ELECTRICAL DUCTBANK. (1) ACTIVE (1) SPARE WITH PULL WIRE.

3

3

3

33 3

3

OS

IC

TO SEC

SEARCH OFFICE

R

9

MS15 D

16

13

18EFO

TO PLC

TO SEC

TO SEC

PROGRAMMABLELOGIC CONTROLLER

VIDEO MANAGEMENTSYSTEM (VMS) GFGI

ACCESS CONTROLEQUIPMENT GFGI

19

COMM ROOM MECH/ELEC

3

3

3

3

3

3

JSHJ

LCS

TO PLC

7

8

GUARD BOOTHCABINA DI GUARDIA PREFABBRICATA

GUARD BOOTHCABINA DI GUARDIA PREFABBRICATA

GUARD BOOTH (FUTURE)CABINA DI GUARDIA PREFABBRICATA (FUTURA)

GUARD BOOTH (FUTURE)CABINA DI GUARDIA PREFABBRICATA (FUTURA)

GUARD BOOTH (FUTURE)CABINA DI GUARDIA PREFABBRICATA (FUTURA)

D D

TO SEC

18EFO

13 13

18EFO

TO PLC TO PLC

18

TO PLC

EFO M

MECH/ELEC

14

1414

12

12 12

1212

12

12 12

20 20 20

SEC

TO SEC

21

PROGRAMMABLELOGIC CONTROLLER

VIDEO MANAGEMENTSYSTEM (VMS) GFGI

ACCESS CONTROLEQUIPMENT GFGI

SEC

21

3

3

3

3

3

3

3

3

NOTE CHIAVE:

1. RILEVATORE CONTRO SENSO - DIPOLO CORSIA DI RILEVAMENTO VEICOLI (VDL)

2. PANNELLO DI CONTROLLO LOCALE PER MANUTENZIONE ALLA BARRIERA VEICOLI ATTIVA (AVB)

3. DIPOLO DELLA VDL ALLA BARRIERA FINALE AVB4. SEGNALE DI CONTROLLO TRAFFICO ALLA AVB5. TERMINE DELLE AVB6. NON ABITUATO A7. SEGNALE RILEVAMENTO CONTROMANO E TROMBA/SUONERIA8. DISPOSITIVO SEGNALAZIONE CONTROLLO CORSIA 9. LETTORE DI SCHEDA CONROLLO ACCESSO/INTERCOM E

COLLEGAMENT AL DPS/SERRATURA/REX10. PANNELLO DI CONTROLLO REMOTO (PARTE MOBILE) DA ESSERE

USATO ALLA POSIZIONE DI GUARDIA11. COLLEGAMENTO UNITA' BASE RCP PER INSERZIONE DEL PANNELLO

DI CONTROLLO REMOTO (RCP)12. RIFERIRSI ALLE PIANTE PER IL POSIZIONAMENTO TIPICO DELLE

TELECAMERE AREE ESTERNE13. DISPOSITIVO DI PULSANTE PER ALLARME COERCIZIONE14. INTERRUTTORI IDS DI POSIZIONE DELLA PORTA DI INGRESSO PER

LOCALE COMUNICAZIONI E APPARATI.15. SENSORE DI MOVIMENTO PER LOCALE DI COMANDO E CONTROLLO

ED EDIFICIO DI ISPEZIONE16. MONITOR DI VIDEOSORVEGLIANZA17. PANNELLO SINOTTICO PRINCIPALE PER OPERATIVITA' DI TUTTI GLI

APPARATI DEL SISTEMA CONTROLLO ACCESSI18. PULSANTE RAPIDO DI EMERGENZA PER AZIONAMENTO AVB FINALE19. POSIZIONE DELL'ARMADIO APPARATI DI SICUREZZA RELATIVI A

TUTTE LE APPARECCHIATURE DI AVB E DISPOSITIVI CONTROLLATI DA PLC ED APPARATI FORNITI ED INSTALLATI DAL GOVERNO INCLUSO VIDEOSORVEGLIANZA, CONTROLLO ACCESSI, ANTICOERCIZIONE E IDS.

20. N°1 CONDUIT 50MM FINO AL SEC ATTRAVERSO POZZETTO. RIFERIRSI ALLE PIANTE PER POSIZIONAMENTO E PERCORSO.

21. 2 TUBI DA 50MM DAL SEC NELL'EDIFICIO DI COMANDO E CONTROLLO AL SEC NELL'EDIFICIO DI ISPEZIONE. UNO UTILIZZATO ED UNO DI SCORTA CON FILO PILOTA.

22. 2 TUBI 50MM DAL SEC NELL'EDIFICIO DI ISPEZIONE ALL'EDIFICIO 110 ATTRAVERSO IL CAVIDOTTO ELETTRICO. UNO UTILIZZATO ED UNO DI SCORTA CON FILO PILOTA

NOTE DEL FOGLIO

1. FAR RIFERIMENTO ALLA TAV EY-003 PER NOTE GENERALI, SIMBOLI ED ABBREVIAZIONI

2. TUTTI I LAVORI INDICATI SU QUESTA TAVOLA SONO GFGI E SOLO INDICATIVI AD ESCLUSIONE DI QUELLI RELATIVI AGLI AVB FINALI. FORNIRE TUTTI APPROSSIMATI A TUBI DA 25MM. FORNIRE UN TUBO DA 25MM E FILO PILOTA ALLA POSIZIONE DI CIASCUNA TELECAMERA PER USO FUTURO. TUTTI I CABLAGGI UTILIZZATI PER LA SICUREZZA DOVRANNO ESSERE DI COLORE GIALLO PER PERMETTERNE LA IDENTIFICAZIONE DA PARTE DEL PROPRIETARIO.

3. FORNIRE UN TUBO DI SCORTA DA 20MM E RELATIVO FILO PILOTA A TUTTI I PANNELLI RCP E LCP PER IL COLLEGAMENTO DEGLI INTERRUTTORI IDS DI MANOMISSIONE

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DEP

ARTM

ENT

OF

THE

NAV

YN

AVAL

FAC

ILIT

Y EN

GIN

EER

ING

SYS

TEM

CO

MM

AND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NAV

AL F

ACIL

ITY

ENG

INEE

RIN

G S

YSTE

M C

OM

MAN

D ~

ATL

ANTI

CN

OR

FOLK

, VIR

GIN

IA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UNCL

ASSI

FIED

AVIA

NO A

IR B

ASE

AVIA

NO, IT

ALY

AREA

A1 E

NTRY

CON

TROL

POI

NT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/29

/202

1 9:

15:5

9 AM

BIM

360:

//102

2452

2_N

AVFA

C_A

1_D

esig

n_Av

iano

_Ita

ly_2

018/

1022

4522

-A-C

anop

y_v2

018.

rvt

E-604

SECU

RITY

SIN

GLE

LIN

E -SICUREZZA

LINEA

SINGOLA

IBF

18914090192

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

ATLA

NTI

C D

ESIG

N A

ND

CO

NST

RU

CTI

ON

RICHARD STEPHENS, PEDER

SCALE: NOT TO SCALEA1 SITE SECURITY RISER DIAGRAM

SCHEMA VERTICALE SICUREZZA DEL SITO

SYM

DES C

RIPT

I ON

DATE

APPR

22

LCG-1

SEE SHEET EA-102SEE SHEET EA-102

LCG-1

LCG-1 LCG-1

LCG-1 LCG-2

LCG-1LCG-1H1

H1

H1

H1

H1

H1

H1

H1

H1

H1

H1

H1 H1 H1

H1

H1

H1

H1

H1

H1

H1H1

LCG-2 LCG-2

LCG-1LCG-1

LCG-1 LCG-1

LCG-2 LCG-2 LCG-2

LCG-1 LCG-1LCG-1

4321

A

B

C

E E

GE-7

GE-7

GE-7

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:50

:03

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

EA101

LIG

HTI

NG

PLA

N -

ID C

HE

CK

-PI

ANO

DI IL

LUM

INAZ

IONE

-CO

NTRO

LLO

ID

KVK

190

14090193

ADK LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50A1

LIGHTING PLAN

ID CHECK

1. CONDUITS AND CIRCUITS FOR POWER AND LIGHTING FOR CANOPY AND GUARD BOOTHS SHALL BE ROUTED THROUGH THE POWER HANDHOLES.

2. WIRING FOR RECEPTACLE AND LIGHTING BRANCH CIRCUITS ROUTED BETWEEN HANDHOLES SHALL BE 16mm2 MINIMUM WIRE SIZE. WIRING FOR RECEPTACLE AND LIGHTING BRANCH CIRCUITS FROM HANDHOLE TO DEVICES AND LUMINAIRES SHALL BE 6mm2 MINIMUM WIRE SIZE (EXCEPT THAT 4mm2 MINIMUM WIRE SIZE OF LESS THAN 300mm LENGTH IS ACCEPTABLE FOR FINAL CONNECTION TO DEVICE.)

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

1. I TUBI ED I CIRCUITI PER LA F.M. E LUCE DELLA TETTOIA E DELLE POSTAZIONI DI GUARDIA DEVONO ESSERE ISTRADATE ATTRAVERSO I POZZETTI DI F.M.

2. I CABLAGGI PER I CIRCUITI SECONDARI DI LUCE E PRESE POSATI TRA I POZZETTI DOVRANNO AVERE SEZIONE MINIMA DI 16MM2. I CABLAGGI PER I CIRCUITI SECONDARI DI LUCE E PRESE DAI POZZETTI ALLE UTENZE ED ALLE LUCI DOVRANNO AVERE SEZIONE MINIMA DI 6mm2 (AD ECCEZIONE DELLA SEZIONE MINIMA DI 4 mm2 ACCETTABILE PER TUTTE LE CONNESSIONI FINALI DI LUNGHEZZA INFERIORE A 300mm)

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

PIANO DI

ILLUMINAZIONE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

J

J J J

J J J J J J

J

G GG G G G G G G G G G G G G G G G G G G

GG

G

GG

G GG G G G G G G G G G G G G G G G G G G

G GG G

G GG G

G G

G GG

GG

GG

GG

GG

GG

GG

GG

GG

GG

GG

GG

GFIWP

GFIWP

GB

GFIWP

MR

GFIWP

GFIWP

GFIWP

MR

GROUND TEST WELL

GROUND TEST WELL

GROUND RING

GFIWP

GFIWP

GFIWP

GB

TO LUMINAIRE AL CORPO ILLUMINANTE(EA-101)GU-24

GFIWP

4321

A

B

C

GU-17SH SH

LCS LCS LCS

GU-10 GU-10

OSPOSPOSP

GU-12 GU-12

GU-17SH

16

GL1-10

22

GU-20,22,24

GE-6GE-4

GL1-32

GU-17

GU-13

GU-15 GU-10

GU-12

12

3

44

2

1

GU-27

GU-14,16,183

GL1-12

5

GL1-23HVAC GL1-25

HVAC

GU-14

GU-20

TO LUMINAIRE AL CORPO ILLUMINANTE(EA-101)GU-18

2216

GROUND RING CONTINUES AROUND SEARCH OFFICE

GROUND RING CONTINUES AROUND SEARCH OFFICE

GROUND RING CONTINUES AROUND GATEHOUSE

GROUND RING CONTINUES AROUND GATEHOUSE

5

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:50

:04

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

EA102

PO

WE

R P

LAN

-ID

CH

EC

K -

POW

ER P

LAN

-CON

TROL

LO ID

KVK

191

14090194

ADK LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50A1

POWER PLAN

1. CONDUITS AND CIRCUITS FOR POWER AND LIGHTING FOR CANOPY AND GUARD BOOTHS SHALL BE ROUTED THROUGH THE POWER HANDHOLES.

2. WIRING FOR RECEPTACLE AND LIGHTING BRANCH CIRCUITS ROUTED BETWEEN HANDHOLES SHALL BE 16mm2 MINIMUM WIRE SIZE. WIRING FOR RECEPTACLE AND LIGHTING BRANCH CIRCUITS FROM HANDHOLE TO DEVICES AND LUMINAIRES SHALL BE 6mm2 MINIMUM WIRE SIZE (EXCEPT THAT 4mm2 MINIMUM WIRE SIZE OF LESS THAN 300mm LENGTH IS ACCEPTABLE FOR FINAL CONNECTION TO DEVICE.

3. COORDINATE WITH SECURITY DRAWINGS TO PROVIDE POWER TO ALL SECURITY DEVICES.

PLANNORTH

ID CHECK

GRAPHIC SCALE: 1:50

0 421 3 5

1 MOUNT RECEPTACLE UNDER THE EAVE

2 PROVIDE ELECTRICAL POWER FOR ACCESS CONTROL SYSTEM EQUIPMENT.COORDINATE REQUIREMENTS WITH EQUIPMENT SUPPLIER AND SECURITYSYSTEM DRAWINGS.

3 PROVIDE MULTIWIRE BRANCH CIRCUIT.

4 COORDINATE LOCATION OF RECEPTACLE WITH SECURITY EQUIPMENTSUPPLIER.

5 PROVIDE POWER FOR TRAFFIC ARM. COORDINATE WITH EQUIPMENTSUPPLIER.

1. I TUBI ED I CIRCUITI PER LA F.M. E LUCE DELLA TETTOIA E DELLE POSTAZIONI DI GUARDIA DEVONO ESSERE ISTRADATE ATTRAVERSO I POZZETTI DI F.M.

2. I CABLAGGI PER I CIRCUITI SECONDARI DI LUCE E PRESE POSATI TRA I POZZETTI DOVRANNO AVERE SEZIONE MINIMA DI 16MM2. I CABLAGGI PER I CIRCUITI SECONDARI DI LUCE E PRESE DAI POZZETTI ALLE UTENZE ED ALLE LUCI DOVRANNO AVERE SEZIONE MINIMA DI 6mm2 (AD ECCEZIONE DELLA SEZIONE MINIMA DI 4 mm2 ACCETTABILE PER TUTTE LE CONNESSIONI FINALI DI LUNGHEZZA INFERIORE A 300mm)

3. COORDINARE CON LE TAVOLE DELLA SICUREZZA PER FORNIRE LA ALIMENTAZIONE ELETTRICA A TUTTI I COMPONENTI DELLA SICUREZZA.

1. MONTARE PRESA SOTTO LA GRONDAIA

2. FORNIRE ALIMENTAZIONE ELETTRICA PER LE APARECCHIATURE DEL SISTEMA DI CONTROLLO ACCESSI. COORDINARE LE NECESSITA' CON IL FORNITORE DELLE APPARECCHIATURE ED I DOSEGNI DELL'IMPIANTO DI SICUREZZA.

3. FORNIRE CIRCUITI DI DISTRIBUZIONE SECONDARIA A PIU' FILI. FORNIRE INERRUTTORI MULTIPOLARI

4. COORDINARE IL POSIZIONAMENTO DELLE PRESE CON IL FORNITORE DELLE APPARECCHIATURE.

5. FORNIRE LA ALIMENTAZIONE ALLE BARRIERE DEL TRAFFICO. COORDINARE CON IL FORNITORE DELLE APPARECCHIATUR.

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

PIANO DI

ALIMENTAZIONE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

RCRCRC

DCDC

DC

RC

DC

4321

A

B

C

1

11

1

LPS CONDUCTOR35mm2 Cu MIN.(TYP.)

TRANSITION TO COPPER CONDUCTOR 450mm ABOVE GRADE. REFER TO E508 FOR DETAILS.

LPS CONDUCTOR50mm2 Al MIN.(TYP.)

AIR TERMINAL12.7mm DIAM, 300mm LENGTH SOLID AL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:50

:05

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

EA103

LIG

HTN

ING

PR

OT

EC

TIO

N P

LAN

-ID

CH

EC

K -

PIAN

O DI

PRO

TEZI

ONE

DAI F

ULM

INI -

CONT

ROLL

O ID

KVK

192

14090195

ADK LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50A1

LIGHTNING PROTECTION PLAN

PLANNORTH

ID CHECK

1. PROVIDE LIGHTNING PROTECTION SYSTEM IN ACCORDANCE WITH LIGHTNING RISK ASSESSMENT.

2. LIGHTNING PROTECTION SYSTEM MUST BE CERTIFIED.

GRAPHIC SCALE: 1:50

0 421 3 5

1. FORNIRE SISTEMA DI PROTEZIONE ANTIFULMINE COME DA CALCOLO DEL RISCHIO DI FULMINAZIONE

2. IL SISTEMA DI PROTEZIONE ANTIFULMINE DEVE ESSERE CERTIFICATO

PIANTA PROTEZIONE

ANTIFULMINE

1 CONNECT DOWN CONDUCTOR TO GROUND RING AND GROUND ROD OF THEBUILDING ELECTRODE SYSTEM

1. COLLEGARE I CONDUTTORI DI CLALATA ALL'ANELLO DI TERRA ED AGLI SPANDENTII DEL SISTEMA DI MESSA A TERRA DELL'EDIFICIO.

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

PV ARRAY(26) PV MODULES(2) STRINGS OF 13 MODULES IN SERIESCAMPO FOTOVOLTAICON° 26 PANNELLI FOTOVOLTAICIN° 2 STRINGHE DI 13 PANNELLI IN SERIE

4321

A

B

C

TO SEARCH OFFICE ELEC/MECH ROOM

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:50

:06

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

EA104

PV

SO

LAR

SIT

E P

LAN

-ID

CH

EC

K -

PIAN

O DE

L SIT

O SO

LARE

FOT

OVOL

TAIC

O -

CONT

ROLL

O ID

KVK

193

14090196

ADK LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50A1

PV SOLAR SITE PLAN

PLANNORTH

ID CHECK

1. PROVIDE ROOF-MOUNTED PV SYSTEM ON SOUTH FACET OF ID CHECK CANOPY. INSTALL PV MODULES AT THE SAME TILT AS THE CANOPY.

2. MAINTAIN ALL REQUIRED SETBACKS AND EQUIPMENT ACCESS.

3. ROUTE DC CIRCUITS DOWN BUILDING EXTERIOR AND TERMINATE IN DC DISCONNECT SWITCH LOCATED IN SEARCH OFFICE ELECTRICAL ROOM.

4. BOND ALL RACKING AND MODULE FRAMES TO GROUNDING ELECTRODE SYSTEM.

GRAPHIC SCALE: 1:50

0 421 3 5

1. FORNIRE UN SISTEMA FOTOVOLTAICO SULLA FACCIA SUD DELLA TETTOIA DI CONTROLLO ID. INSTALLARE I PANNELLI FOTOVOLTAICI CON LA STESSA PENDENZA DELLA TETTOIA.

2. MANTENERE TUTTE LE CONDIZIONI RICHIESTE E L'ACCESSO ALLE APPARECCHIATURE

3. POSARE I CIRCUITI CC GIU' SUL LATO ESTERNO DELL'EDIFICIO E ATTESTARLI AL SEZIONATORE CC POSIZIONATO NEL LOCALE ELETTRICO DELL'UFFICIO ISPEZIONI.

4. COLLEGARE A TERRA TUTTI I SOSTEGNI ED I TELAI DEI PANNELLI.

PIANTA F.V. DEL SITO

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

(2) (2)

A4

EA105____________________________________________________

A4

EA105____________________________________________________

4321

A

B

C

3

55

2

55

2

3

(2)

11

2

4

55

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:50

:07

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

EA105

TELE

CO

MM

UN

ICA

TIO

N P

LAN

-ID

CH

EC

K -

PIAN

O TE

LECO

MUN

ICAZ

IONI

-CO

NTRO

LLO

ID

KVK

194

14090197

JAZ LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50A1

TELECOMMUNICATIONS PLAN

NOT TO SCALENON IN SCALA

(EA105)A4

TELECOMMUNICATION RISER

PLANNORTH

ID CHECK

1. TELECOM DEVICES SHOWN SHALL BE CONNECTED IN THE GATEHOUSE TELECOM ROOM.

GRAPHIC SCALE: 1:50

0 421 3 5

1 PROVIDE CATEGORY 6 RATED SOLID STATE BUILDING ENTRANCE TERMINAL(BET) PRIMARY PROTECTOR WITH 110 CONNECTOR ON INPUT AND OUTPUTSIDE. GROUND PROTECTORS TO GROUND BAR.

2 PROVIDE IP 52 ENCLOSURE WITH HINGED LOCKABLE COVER TO HOUSEBET'S AND 915MM CABLE SERVICE LOOP. LOCATE ENCLOSURE UNDERCOUNTER.

3 PROVIDE 25MM CONDUIT FROM OUTLET BOX TO BET ENCLOSURE.

4 CATEGORY 6 HORIZONTAL CABLE.

5 SERVICE ENTRANCE CONDUITS. STUB UP SPARE CONDUIT 100MM AFF ANDCAP.

ID CHECK

1. FORNIRE UN PROTETTORE PRINCIPALE IN CATEGORIA 6 ALLO STATO SOLIDO PER TERMINAZIONE DI INGRESSO DELL'EDIFICIO (BET) CON CONNETTORI 110 SIA SUL LATO DI INGRESSO CHE QUELLO DI USCITA. METTERE A TERRA I PROTETTORI SULLA SBARRA DI TERRA.

2. FORNIRE UNA CASSETTA IP52 CON COPERCHIO LUCHETTABILE INCERNIERATO PER CONTENERE BET E UNA SPIRA DI 915MM DI SCORTA DEL CAVO. POSIZIONARE LA CASSETTA SOTTO IL RIPIANO.

3. FORNIRE UN TUBO DA 25MM DALLA CASSETTA DELLA PRESA ALLA CASSETTA DEL BET.

4. CAVO ORIZZONTALE CAT 6.

5. TUBI DI INGRESSO DEL SERVIZIO DI TELECOMUNICAZIONI. RISALITA A 100MM DAL PAVIMENTO PER IL TUBO DI SCORTA E SUA CHIUSURA CON TAPPO.

1. I COMPONENTI DI TELECOMUNICAZIONE MOSTRATI VANNO COLLEGATI AL LOCALE TELECOMUNICAZIONI DELLA STAZIONE DI CONTROLLO

VERTICALE TLC

CONTROLLO - PIANTA

TELECOMINCAZIONI

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

D

JJJ

J J J

D

RCPOS D

2 3 41

C

B

EFO

EFO

SH SH SH

LCSLCSLCS

HH HH HH

TO SEC LOCATION IN COM ROOM IN SEARCH BUILDING

STUB UP FOR FUTURE GUARD BOOTH TYPICAL

A1

E-509

A2

E-509

A1

E-510

A4

E-512

A4

E-512

A3

E-512

B2

E-511

D

WW

P P P

PPP

B1

EA106

C1

E-512

W

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:11

:34

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_A

via

no

_Ita

ly_

20

18

/10

22

45

22-A

-Ca

nop

y_

v2

018

.rvt

EA106

SE

CU

RIT

Y F

LOO

R P

LAN

-ID

CH

EC

K -

PIAN

O DI

SIC

UREZ

ZA -

CONT

ROLL

O ID

IBF

195

14090198

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 50 (AA201)A2

1ST FLOOR PLANSCALE: 1 : 50 (AA201)

A1OVERWATCH PLAN

OVERWATCH

ID CHECK

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

1. FOR SYMBOLS, ABBREVEATIONS AND GENERAL NOTES REFER TO DRAWING E-003.

PIANTA GARITTA PIANTA PRIMO PIANO

KEY PLAN - PIANTA CHIAVE

SHEET KEYNOTES - NOTE CHIAVE

GENERAL NOTES - NOTE GENERALI

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

REF

2

22

2

FD

FD

2

2 2

A1

A1A1

B1

D2

A1

A1A1

D1

B1

A1

A1

LCG-3LCG-3( )

LCG-3

LCG-3

LCG-3

a

b

a a

b

b

F1F1

F1

F1

F1

1 2

ACOMMAND & CONTROL

101

PASSAGE

103

TOILET

102

JANITOR

104

BREAK

106

MECH/ELEC

107

COMM

105

A

GU-1,8

GE-2

a b

C

D

D

B

B

D

GE-5

GE-5

GE-5

GE-5

GE-5

GE-5

GE-5

GE-5

GE-1GE-1

1GE-5

1

2

3

4

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:47

:38

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

EB101

LIG

HTI

NG

PLA

N -

GA

TEH

OU

SE

-PI

ANO

DI IL

LUM

INAZ

IONE

-GA

TEHO

USE

KVK

196

14090199

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

LIGHTING PLAN - GATEHOUSE

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

LIGHTING CONTROL PANEL (LCG)

GATEHOUSE

1 PROVIDE HAND-OFF-AUTO SWITCH CONNECTED TO THE LIGHTING CONTROLPANEL FOR CONTROL OF EXTERIOR SITE LIGHTING. PROVIDE ROGRAMMINGOF SYSTEM SUCH THAT LIGHTS DIRECTED BY THE INSTALLATION AREOPERATED FROM THIS SWITCH.

2 PROVIDE CONNECTION TO LIGHTING CONTROL PANEL 'LCS' IN SEARCHOFFICE.

3 INTERLOCK EXHAUST FAN WITH LIGHT SWITCH

4 PROVIDE REMOTE TEST SWITCH FOR EMERGENCY LIGHTING LUMINAIRES.

1. FORNIRE INTERRUTTORE MAN-0-AUT COLLEGATO AL PANNELLO DI CONTROLLO DELL'ILLUMINAZIONE ESTERNA. FORNIRE LA PROGRAMMAZIONE DEL SISTEMA IN MODO CHE LE LUCI DI QUESTO IMPIANTO SIANO COMANDATE DALL'INTERRUTTORE ANZIDETTO.

2. FORNIRE IL COLLEGAMENTO AL PANNELLO DI CONTROLLO DELL'ILLUMINAZIONE "LCS" NELL'UFFICIO DI ISPEZIONE.

3. INTERBLOCCARE I VENTILATORI DI ESTRAZIONE CON L'INTERRUTTORE DELLE LUCI

4. FORNIRE UN INTERRUTTORE DI PROVA A DISTANZA PER APPARECCHI DI ILLUMINAZIONE DI EMERGENZA

CORPO DI GUARDIA - PIANTA ILLUMINAZIONE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

REF

FD

FD

T

T

T

G GG G G

G GG G G G G G

GG

GG

GG

GG

GG

GG

GG

GG

G

GG

LIGHTING CONTROL PANEL (LCG)

GROUND TEST WELL

GROUND RINGANELLO DI TERRA

SECURITY CONTROL PANELPANNELLO CONTROLLO SICUREZZA

SECURITY CONTROL PANEL

+1mGFI

+1mGFI

+1mGFI

+1mGFI

GFIWP

+1.2mGFI

+1.2mGFI

GFIWP

GFIWP

+0.5mGFIWP

GFIWP

+1m

MGB

1 2

A

BREAK

106

PASSAGE

103

TOILET

102

JANITOR

104

COMM

105

MECH/ELEC

107

COMMAND & CONTROL

101

GU-1 GU-3

GL1-1

GL1-9

GU-9

2

GL1-2

GL1-9 GL1-9

GL1-9

GL1-3 GL1-7

GL1-5

GL1-19 GL1-21

GU-2GU-4

GU-6

GFI+1.2m

GFI+1.2m

GL1-4 GL1-6 GL1-8

GU

GL1

GE

MCP

HP-01

HP-02

EF-01

EF-02

GL1-11

GL1-13

TELECOM RACK

GU-5GU-7

TMGB

WH-01

1

1

1 1

2 2

VIDEO SURVEILLANCE WORKSTATION

VIDEO SURVEILLANCE WORKSTATIONPOSTAZIONE DI VIDEOSORVEGLIANZA

GU-25

GL1-1

3

PV SOLAR REMOTE SHUT-DOWN

45

5

MRMR

+1.2m

GENERATOR REMOTE ANNUNCIATOR PANEL

GL1-15

GL1-16

GROUND RING CONTINUES AROUND ID CHECK

GROUND RING CONTINUES AROUND ID CHECK

6

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:47

:38

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

EB102

PO

WE

R P

LAN

-G

ATE

HO

US

E -

IMPI

ANTO

ELE

TTRI

CO -

GATE

HOUS

E

KVK

197

14090200

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

POWER PLAN - GATEHOUSE

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

GATEHOUSE

1 PROVIDE ELECTRICAL POWER CONNECTION FOR ACCESS CONTROLSYSTEM EQUIPMENT. COORDINATE WITH EQUIPMENT SUPPLIER.

2 PROVIDE ELECTRICAL CONNECTIONS FROM THE OUTDOOR HEAT PUMP TOTHE INDOOR FAN COIL UNIT PER MANUFACTURER'S RECOMMENDATIONS.PROVIDE TWO POLE HORSEPOWER RATED DISCONNECT SWITCH AT THEINDOOR UNIT.

3 LOCATE RECEPTACLE IN SECURITY ENCLOSURE.

4 PROVIDE REMOTE SHUT-DOWN BUTTON FOR PV SOLAR SYSTEM. CONNECTTO PV MONITOR/CONTROL CABINET. REFER TO E-503.

5 INSTALL OFF DELAY RELAY FURNISHED WITH FAN ABOVE ACCESSIBLECEILING OF ADJACENT ROOM. CONNECT TO SWITCHED LIGHTING CIRCUITAND EXHAUST FAN TO TURN FAN ON WITH LIGHTS AND REMAIN ON 10MINUTES AFTER LIGHTS ARE TURNED OFF.

6 DEDICATED 230V, 16A RECEPTACLES FOR IT RACK EQUIPMENT.COORDINATE WITH EQUIPMENT REQUIREMENTS.

1. POWER TO SECURITY EQUIPMENT WITHIN THE BUILDING IS FROM SECURITY CONTROL PANEL.

1. L'ENERGIA ELETTRICA AGLI APPARATI DELLA SICUREZZA INTERNI ALL'EDIFICIO E' DERIVATA DAL QUADRO DI CONTROLLO SICUREZZA

1. FORNIRE COLLEGAMENTI ELETTRICI AGLI APPARECCHI DEL SISTEMA DI CONTROLLO ACCESSI. COORDINARLI CON IL FORNITORE DEGLI APPARATI.

2. FORNIRE COLLEGAMENTI ELETTRICI DALLA POMPA DI CALORE ESTERNA E L'UNITA' FAN-COIL INTERNA SECONDO LE INDICAZIONI DEL PRODUTTORE. FORNIRE UN SEZIONATORE BIPOLARE PER L'UNITA' INTERNA.

3. PSIZIONARE LA PRESA IN UN CONTENITORE DI SICUREZZA.

4. FORNRE PULSANTE REMOTO DI ARRESTO DI EMERGENZA DELLL’IMPIANTO FOTOVOLTAICO. COLLEGARLO AL PANNELLO DI MONITORAGGIO/CONTROLLO DELL’IMPIANTO FOTOVOLTAICO. VEDI TAV. E-503

5. INSTALLARE RELE’ DI APERTURA RITARDATA FORNITO CON IL VENTILATORE NEL CONTROSOFFITTO DEL LOCALE ADIACENTE. COLLEGARE AL CIRCUITO LUCE COMANDATO ED AL VENTILATORE DI ESTRAZIONE PER ATTIVAZIONE VENTILATORE IN CONTEMPORANEA CON ILLUMINAZIONE, E FUNZIONAMENTO PER ULTERIORI 10 MINUTI DOPO LO SPEGNIMENTO DELLA LUCE.

6. PRESE DEDICATE 230V, 16A PER RACK APPARATI IT. CORRDINARE CON LE NECESSITA' DELLE APPARECCHIATURE.

CORPO DI GUARDIA - PIANTA FORZA MOTRICE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

DC

DC

RC

RC

RC

RC

1 2

A

1

1

LPS CONDUCTOR35mm2 Cu MIN.(TYP.)

TRANSITION TO COPPER CONDUCTOR 450mm ABOVE GRADE. REFER TO E508 FOR DETAILS.

LPS CONDUCTOR50mm2 Al MIN.(TYP.)

AIR TERMINAL12.7mm DIAM, 300mm LENGTH SOLID AL

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:47

:39

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

EB103

LIG

HTN

ING

PR

OT

EC

TIO

N P

LAN

-G

ATE

HO

US

E -

PIAN

O DI

PRO

TEZI

ONE

DAI F

ULM

INI -

GATE

HOUS

E

KVK

198

14090201

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50

LIGHTNING PROTECTION PLAN - GATEHOUSE

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

GATEHOUSE

1 CONNECT DOWN CONDUCTOR TO GROUND RING AND GROUND ROD OF THEBUILDING ELECTRODE SYSTEM

1. COLLEGARE I CONDUTTORI DI CLALATA ALL'ANELLO DI TERRA ED AGLI SPANDENTII DEL SISTEMA DI MESSA A TERRA DELL'EDIFICIO.

IMPIANTO PROTEZIONE ANTIFULMINE - CORPO DI GUARDIA

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

REF

FD

FD

44

1,W

2

150 X 50 CABLE TRAYCANALINA 150X50

10

3

9

TYP.

B2EB104

1 2

A

11

FLOOR

(11)TYP

TYP

(6)LOCATED IN ID CHECK BOOTHSPOSIZIONATO NEL POSTO DI CONTROLLO ID

TYP

1

2

34

5

67

8

9

10

12

12

13

14

14

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:47

:39

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_D

esig

n_

Avia

no_

Ita

ly_2

01

8/1

02

24

52

2-M

EP

-Gate

ho

use_

v20

18

.rvt

EB104

TELE

CO

MM

UN

ICA

TIO

N P

LAN

-G

AT

EH

OU

SE

-PI

ANO

DI T

ELEC

OMUN

ICAZ

IONI

-GA

TEHO

USE

KVK

199

14090202

JAZ LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

TELECOMMUNICATIONS PLAN - GATEHOUSENOT TO SCALENON IN SCALA

(EB104)B2

TELECOMMUNICATION RISER DIAGRAM

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

GATEHOUSE

1 PROVIDE 24 PORT, 1RU COPPER PATCH PANEL.

2 PROVIDE 12 PORT, 1RU RACK MOUNTED FIBER OPTIC PATCH PANEL.

3 PROVIDE WALL MOUNTED EQUIPMENT CABINET WITH A MINIMUM OF 12 RUMOUNTING SPACE.

4 SPACE FOR OWNER PROVIDED NETWORK SWITCHES AND SERVERS.

5 NUMBER INDICATES APPROXIMATE QUANTITY OF CABLE DROPS.CONTRACTOR SHALL VERIFY EXACT QUANTITY WITH PLANS AND PROVIDEAPPROPRIATE NUMBER OF PATCH PANELS PER SPECIFICATIONS.

6 PROVIDE 1RU HORIZONTAL CABLE MANAGER.

7 CATEGORY 6 HORIZONTAL CABLE.

8 PROVIDE SINGLE MODE FIBER OPTIC BACKBONE CABLE FORTELECOMMUNICATIONS NETWORK.

9 TELECOMMUNICATION SERVICE ENTRANCE CONDUITS STUB UP 100MM AFF.CAP SPARE CONDUIT. ROUTE CONDUITS BELOW FLOOR SLAB. SEETELECOMMUNICATION SITE PLANS FOR CONTINUATION.

10 PROVIDE TELECOMMUNICATION PRIMARY BONDING BAR (PGB). SEE DETAILSHEET E-506 FOR REQUIRED GROUNDING AND BONDING CONNECTIONS.

11 PROVIDE PLYWOOD BACKBOARD 2440MM HIGH ON WALLS INDICATED.

12 PROVIDE CATEGORY 6 RATED SOLID STATE BUILDING ENTRANCE TERMINAL(BET) PRIMARY PROTECTOR WITH 110 CONNECTOR ON INPUT AND OUTPUTSIDE. GROUND PROTECTORS TO GROUND BAR.

13 PROVIDE 3000MM SERVICE LOOP IN BACKBONE CABLES. SUPPORT LOOP ONBACKBOARD.

14 PROVIDE 915MM SERVICE LOOP IN HORIZONTAL CABLES. SUPPORT LOOPON BACKBOARD.

1. FORNIRE PANNELLO PATCH 24 PORTE RAME UNA UNITA' RACK.

2. FORNIRE PANNELLO PATCH 12 PORTE F.O. UNA UNITA' RACK

3. FORNIRE UN ARMADIETTO MONTATO A PARETE CON UNO SPAZIO MINIMO DI 12 UNITA' RACK.

4. SPAZIO PER SWITCH DI RETE E SERVER FORNITI DAL PROPRIETARIO

5. IL NUMERO INDICA LA APPROSSIMATIVA QUANTITA' DI CAVI ALLE PRESE. L'APPALTATORE DEVE VERIFICARE L'ESATTA QUANTITA' SULLE PIANTE E FORNIRE L'APPROPRIATO NUMERO DI PATCH PANEL SECONDO SPECIFICA.

6. FORNIRE GESTORE DI CAVI DI 1 UNITA' RACK.

7. CAVO ORIZZONTALE CAT 6.

8. FORNIRE UN CAVO BACKBONE IN F.O. MONOMODALE PER LA RETE DI TELECOMINICAZIONI.

9. RISALITA DEI TUBI DI INGRESSO DEL SERVIZIO DI TELECOMUNICAZIONI A 100MM DAL PAVIMENTO FINITO. TAPPARE I TUNI DI SCORTA. POSARE I TUBI AL DI SOTTO DELLA SOLETTA. VEDI PIANTE DELLE TELECOMUNICAZIONI DEL SITO PER LA CONTINUAZIONE.

10. FORNIRE UNA SBARRA PRINCIPALE DI TERRA DELLE TELECOMUNIUCAZIONI (PGB). VEDI DETTAGLIO E-506 PER PRESCRIZIONI DI MESSA A TERRA E RELATIVI COLLEGAMENTI.

11. FORNIRE UN PANNELLO DI LEGNO COMPENSATO ALTO 2440MM SULLE PARETI INDICATE.

12. FORNIRE UN PROTETTORE PRINCIPALE IN CATEGORIA 6 ALLO STATO SOLIDO PER TERMINAZIONE DI INGRESSO DELL'EDIFICIO (BET) CON CONNETTORI 110 SIA SUL LATO DI INGRESSO CHE QUELLO DI USCITA. METTERE A TERRA I PROTETTORI SULLA SBARRA DI TERRA.

13. FORNIRE UNA SPIRA DI SCORTA DA 3000MM PER I CAVI BACKBONE. ALLOGGIARE LA SPIRA NELLA CANALINA PORTACAVI.

14. FORNIRE UNA SPIRA DI SCORTA DA 915 MM PER I CAVI ORIZZONTALI. ALLOGGIARE LA SPIRA NELLA CANALINA PORTACAVI.

PIANTA TELECOMUNICAZIONE - CORPO DI

GUARDIA

SCHEMA VERTICALE TELECOMUNICAZIONI

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PRGENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

REF

SEC

R

R

MS

MCP IC

DD

FD

FD

COMMAND & CONTROL

101

PASSAGE

103

BREAK

106

MECH/ELEC

107

JANITOR

104

COMM

105

TOILET

102

M

EF

O

TO MAIN SEC LOCATION IN COM ROOM AT SEARCH BUILDINGALL'ARMADIO DEGLI APPARATI DI

SICUREZZA DELLA STANZA

TELECOMUNICAZIONI

DELL'EDIFICIO DI ISPEZIONE.

C1

E-510

C3

E-510

D4

E-510

A3

E-510

C1

E-5111 2

A

W

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:51

:21

PM

BIM

360

://1

02

245

22

_N

AV

FA

C_A

1_

De

sig

n_

Avia

no

_Italy

_20

18

/10

22

45

22

-A-G

ate

ho

use_v20

18

.rvt

EB105

SE

CU

RIT

Y F

LOO

R P

LAN

-G

AT

EH

OU

SE

-PL

ANIM

ETRI

A DI

SIC

UREZ

ZA -

PORT

INER

IA

IBF

200

14090203

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 50 (A-504)A3

1ST FLOOR PLAN

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

GATEHOUSE

1. FOR SYMBOLS, ABBREVEATIONS AND GENERAL NOTES REFER TO DRAWING E-003.

PIANTA PRIMO LIVELLO

1. PER SIMBOLI, ABBREVIAZIONI E NOTE GENERALI VEDI TAV. E-003

KEY PLAN - PIANTA CHIAVE

SHEET KEYNOTES - NOTE CHIAVE

GENERAL NOTES - NOTE GENERALI

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

22bb

aaa

b

D3

D3

D3

D3

A1

A1

A1

A1

LIGHTING CONTROL PANEL (LCS)PANNELLO CONTROLLO ILLUMINAZIONE

F1F1

F1

F1

F1

SE-1

A

D

D

SE-3LCS-1( )

SU-6

SEARCH OFFICE

101

COMM ROOM

102

MECH/ELEC

103

1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:49

:13

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

EC101

LIG

HTI

NG

PLA

N -

SE

AR

CH

OF

FIC

E -

UFFI

CIO

RICE

RCA

PIAN

O DI

ILLU

MIN

AZIO

NE

KVK

201

14090204

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B2

LIGHTING PLAN - SEARCH OFFICE

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

SEARCH

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PRKEYNOTES - NOTE CHIAVE

1 PROVIDE REMOTE TEST SWITCH FOR EMERGENCY LIGHTING LUMINAIRES.

1. FORNIRE UN INTERRUTTORE DI PROVA A DISTANZA PER APPARECCHI DI ILLUMINAZIONE DI EMERGENZA

PIANO DI ILLUMINAZIONE - UFFICIO

CONTROLLO

T

T

T

D R

MS

GG

GG

GG

GG

GG

GG

G

G GG G

G GG G

GG

GG

G

GG GG

GG

G

G G

GG G G

GG

G

G GG

GG

GROUND TEST WELL

GROUND RING

GENERATOR

ATS

MGB

SL1

DPS

SE

SU

SUT

UPS

LCS

SECURITY CONTROL PANEL

+1m

+1m

GFIWP

+1m

GFIWP

+1m

PV INVERTER

PV DC DISCSEZIONATORE FV DC

GFIWP

SL1-8

SL1-10

SU:1

1

1

HP-03

HP-04

HP-05

TMGB

1

+1m+1m

SL1-12

TELECOM RACK

TMGB

SL1-1

SL1-3

SUT-2

SUT-3

SUT-4SUT-1

SUT-7

SL1-4SL1-2

SL1-9

SL1-7

SEARCH OFFICE

101

COMM ROOM

102

MECH/ELEC

103

GFIWP

SUT-5

SUT-6

MGB

1

1

1

2

3

4

4

4

5

VIDEO SURVEILLANCE WORKSTATION

PV AC DISCSEZIONATORE FV AC

PV MONITORING CABINET

MR

MR

MR

GROUND RING CONTINUES AROUND ID CHECK

GROUND RING CONTINUES AROUND ID CHECK

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:49

:15

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

EC102

PO

WE

R P

LAN

-S

EA

RC

H O

FF

ICE

-UF

FICI

O RI

CERC

A PO

WER

PLA

N

KVK

202

14090205

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

POWER PLAN - SEARCH OFFICE

GRAPHIC SCALE: 1:50

0 421 3 5

PLANNORTH

1. POWER TO SECURITY EQUIPMENT WITHIN THE BUILDING IS FROM SECURITY CONTROL PANEL.

SEARCH

1 PROVIDE ELECTRICAL POWER CONNECTION FOR ACCESS CONTROLSYSTEM EQUIPMENT. COORDINATE WITH EQUIPMENT SUPPLIER.

2 PROVIDE CIRCUITS FOR GENERATOR ENGINE BLOCK HEATER AND BATTERYCHARGER.

3 LOCATE RECEPTACLE IN SECURITY ENCLOSURE

4 PROVIDE ELECTRICAL CONNECTIONS FROM THE OUTDOOR HEAT PUMP TOTHE INDOOR FAN COIL UNIT PER MANUFACTURERS RECOMMENDATIONS.PROVIDE TWO POLE HORSEPOWER RATED DISCONNECT SWITCH AT THEINDOOR UNIT.

5 DEDICATED 230V, 16A RECEPTACLES FOR IT RACK EQUIPMENT.COORDINATE WITH EQUIPMENT REQUIREMENTS.

1. L'ENERGIA ELETTRICA ALLE APPARECCHIATURE DELLA SICUREZZA INTERNE ALL'EDIFICIO E' DERIVATA DAL QUADRO DI CONTROLLO DELLA SICUREZZA

1. FORNIRE ALIMENTAZIONE ELETTRICA PER LE APPARECCHIATURE DEL SISTEMA DI CONTROLLO ACCESSI. COORDINAMENTO CON IL FORNITORE DELLE APPARECCHIATURE.

2. FORNIRE CABLAGGIO PER SCALDIGLIA BLOCCO MOTORE DEL GENERATORE E CARICA BATTERIA.

3. COLLOCARE LA PRESA IN UN CONTENITORE DI SICUREZZA.

4. FORNIRE CABLAGGIO ELETTRICO DALLA POMPA DI CALORE ESTERNA ALFAN-COIL INTERNO SECONDO ISTRUZIONI DEL PRODUTTORE. FORNIRE SEZIONATORE BIPOLARE DIMENSIONATO PER LA POTENZA MOTORE DELL'UNITA' INTERNA.

5. PRESE DEDICATE 230V, 16A PER RACK APPARATI IT. CORRDINARE CON LE NECESSITA' DELLE APPARECCHIATURE.

PIANTA F-M- - UFFICIO CONTROLLO

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

DC

DC

RC

RC

RC

RC

1

LPS CONDUCTOR35mm2 Cu MIN.(TYP.)

TRANSITION TO COPPER CONDUCTOR 450mm ABOVE GRADE. REFER TO E-508 FOR DETAILS.

LPS CONDUCTOR50mm2 Al MIN.(TYP.)

AIR TERMINAL12.7mm DIAM, 300mm LENGTH SOLID AL

E-508A1

E-508A3

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:49

:16

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

EC103

LIG

HTN

ING

PR

OT

EC

TIO

N P

LAN

-S

EA

RC

H O

FF

ICE

-UF

FICI

O RI

CERC

A PI

ANO

PROT

EZIO

NE F

ULM

INI

KVK

203

14090206

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B2

LIGHTNING PROTECTION PLAN - SEARCH OFFICE

GENERAL SHEET NOTES

NEW WORK KEYNOTES

KEY PLAN

GRAPHIC SCALE: 1:50

0 421 3 5

1. PROVIDE LIGHTNING PROTECTION SYSTEM IN ACCORDANCE WITH LIGHTNING RISK ASSESSMENT.

2. LIGHTNING PROTECTION SYSTEM MUST BE CERTIFIED.

PLANNORTH

SEARCH

1 CONNECT DOWN CONDUCTOR TO GROUND RING AND GROUND ROD OF THEBUILDING ELECTRODE SYSTEM

1. FORNIRE SISTEMA DI PROTEZIONE ANTIFULMINE COME DA CALCOLO DEL RISCHIO DI FULMINAZIONE.

2. IL SISTEMA DI PROTEZIONE ANTIFULMINE DEVE ESSERE CERTIFICATO.

1. COLLEGARE I CONDUTTORI DI CALATA ALL'ANELLO ED AGLI SPANDENTI DI TERRA DEL SISTEMA DI MESSA A TERRA DELL'EDIFICIO.

PIANTA IMPIANTO PROTEZIONE ANTIFULMINE -

UFFICIO CONTROLLO

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

4

+1m

2

SECURITY EQUIPMENT CABINET (SEC)ARMADIO APPARATI DI SICUREZZA (SEC)

150 X 50 CABLE TRAY

A2EC104

12

12

12

10

3

11

2

+1m

(8)

FLOOR

TYP

TYP

(2)LOCATED IN OVERWATCH BOOTHPOSIZIONATO NELLA GARITTA

1

2

3

4

5

6

7

8

9

1010

11

1313

14

14

151616

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:49

:17

PM

BIM

360

://1

022

45

22

_N

AV

FA

C_A

1_

Desig

n_

Avia

no_

Italy

_2

01

8/1

0224

52

2-M

EP

-Sea

rch_

v20

18

.rvt

EC104

TELE

CO

MM

UN

ICA

TIO

NS

PLA

N -

SE

AR

CH

OF

FIC

E -

UFFI

CIO

RICE

RCA

PIAN

OTE

LECO

MUN

ICAZ

IONI

KVK

204

14090207

ADK LAT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

SHEET KEYNOTES

KEY PLAN

1 : 50A1

TELECOMMUNICATIONS PLAN - SEARCH OFFICE

GRAPHIC SCALE: 1:50

0 421 3 5NOT TO SCALENON IN SCALA

(EC104)A2

TELECOMMUNICATION RISER DIAGRAM

PLANNORTH

SEARCH

1 PROVIDE 24 PORT, 1RU COPPER PATCH PANEL.

2 PROVIDE 12 PORT, 1RU RACK MOUNTED FIBER OPTIC PATCH PANEL.

3 PROVIDE 45RU EQUIPMENT CABINET FOR TELECOMMUNICATIONS NETWORKEQUIPMENT.

4 SPACE FOR OWNER PROVIDED NETWORK SWITCHES AND SERVERS.

5 PROVIDE VERTICAL CABLE MANAGEMENT.

6 NUMBER INDICATES APPROXIMATE QUANTITY OF CABLE DROPS.CONTRACTOR SHALL VERIFY EXACT QUANTITY WITH PLANS AND PROVIDEAPPROPRIATE NUMBER OF PATCH PANELS PER SPECIFICATIONS.

7 PROVIDE 1RU HORIZONTAL CABLE MANAGER.

8 CATEGORY 6 HORIZONTAL CABLE.

9 PROVIDE SINGLE MODE FIBER OPTIC BACKBONE CABLE FROM THE ITN INBLDG 110 FOR TELECOMMUNICATIONS NETWORK.

10 TELECOMMUNICATION SERVICE ENTRANCE CONDUITS STUB UP 100MM AFF.CAP SPARE CONDUIT. ROUTE CONDUITS BELOW FLOOR SLAB. SEETELECOMMUNICATION SITE PLANS FOR CONTINUATION.

11 PROVIDE TELECOMMUNICATION PRIMARY BONDING BAR (PGB). SEE DETAILSHEET E-506 FOR REQUIRED GROUNDING AND BONDING CONNECTIONS.

12 PROVIDE PLYWOOD BACKBOARD 2440MM HIGH ON WALLS INDICATED.

13 PROVIDE 915MM SERVICE LOOP IN HORIZONTAL CABLES. STORE LOOP INCABLE TRAY.

14 PROVIDE CATEGORY 6 RATED SOLID STATE BUILDING ENTRANCE TERMINAL(BET) PRIMARY PROTECTOR WITH 110 CONNECTOR ON INPUT AND OUTPUTSIDE. GROUND PROTECTORS TO GROUND BAR.

15 PROVIDE SINGLE MODE FIBER OPTIC BACKBONE CABLE TO THEGATEHOUSE.

16 PROVIDE 3000MM SERVICE LOOP IN BACKBONE CABLES. STORE LOOP INCABLE TRAY.

1. FORNIRE PANNELLO PATCH 24 PORTE RAME UNA UNITA' RACK.

2. FORNIRE PANNELLO PATCH 12 PORTE F.O. UNA UNITA' RACK

3. FORNIRE UN ARMADIO DA 45 UNITA' RACK PER GLI APPARATI DI RETE DI TELECOMUNICAZIONE.

4. SPAZIO PER SWITCH DI RETE E SERVER FORNITI DAL PROPRIETARIO

5. FORNIRE GESTORE DI CAVI VERTICALE.

6. IL NUMERO INDICA LA APPROSSIMATIVA QUANTITA' DI CAVI ALLE PRESE. L'APPALTATORE DEVE VERIFICARE L'ESATTA QUANTITA' SULLE PIANTE E FORNIRE L'APPROPRIATO NUMERO DI PATCH PANEL SECONDO SPECIFICA.

7. FORNIRE GESTORE DI CAVI DI 1 UNITA' RACK.

8. CAVO ORIZZONTALE CAT 6.

9. FORNIRE UN CAVO BACKBONE IN F.O. MONOMODALE PER LA RETE DI TELECOMINICAZIONI DAL ITN DELL'EDIFICIO 110.

10. RISALITA DEI TUBI DI INGRESSO DEL SERVIZIO DI TELECOMUNICAZIONI A 100MM DAL PAVIMENTO FINITO. TAPPARE I TUNI DI SCORTA. POSARE I TUBI AL DI SOTTO DELLA SOLETTA. VEDI PIANTE DELLE TELECOMUNICAZIONI DEL SITO PER LA CONTINUAZIONE.

11. FORNIRE UNA SBARRA PRINCIPALE DI TERRA DELLE TELECOMUNIUCAZIONI (PGB). VEDI DETTAGLIO E-506 PER PRESCRIZIONI DI MESSA A TERRA E RELATIVI COLLEGAMENTI.

12. FORNIRE UN PANNELLO DI LEGNO COMPENSATO ALTO 2440MM SULLE PARETI INDICATE.

13. FORNIRE UNA SPIRA DI SCORTA DA 915 MM PER I CAVI ORIZZONTALI. ALLOGGIARE LA SPIRA NELLA CANALINA PORTACAVI.

14. FORNIRE UN PROTETTORE PRINCIPALE IN CATEGORIA 6 ALLO STATO SOLIDO PER TERMINAZIONE DI INGRESSO DELL'EDIFICIO (BET) CON CONNETTORI 110 SIA SUL LATO DI INGRESSO CHE QUELLO DI USCITA. METTERE A TERRA I PROTETTORI SULLA SBARRA DI TERRA.

15. FORNIRE UN CAVO F.O. MONOMODALE BACKBONE FINO ALLA STAZIONE DI CONTROLLO.

16. FORNIRE UNA SPIRA DI SCORTA DA 3000MM PER I CAVI BACKBONE. ALLOGGIARE LA SPIRA NELLA CANALINA PORTACAVI.

PIANTA TELECOMUNICAZIONI - UFFICIO CONTROLLO SCHEMA VERTICALE TELECOMUNICAZIONI

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

D R

MS

SEARCH OFFICE

101

COMM ROOM

102

MECH/ELEC

103

SEC

EFO

TO HAND HOLE AT ISLAND AND MAIN GUARD HOUSEAL POZZETTO ALL'ISOLA E

POSTO DI GUARDIA

PRINCIPALE

HH1 2

W

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 4

:59

:42

PM

BIM

360

://1

02

24

522

_N

AV

FA

C_

A1_

De

sig

n_A

via

no

_Ita

ly_20

18

/102

24

522

-A-S

ea

rch_v20

18

.rvt

EC105

SE

CU

RIT

Y F

LOO

R P

LAN

-S

EA

RC

H O

FF

ICE

-PL

ANIM

ETRI

A DI

SIC

UREZ

ZA -

UFFI

CIO

DIRI

CERC

A

IBF

205

14090208

AJM JMT

208

22 MARCH, 2021

APPROVED BY SCOTT KIBLERVIA E-MAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

DER

SCALE: 1 : 50 (AC201)A2

1ST FLOOR PLAN

PLANNORTH

GRAPHIC SCALE: 1:50

0 421 3 5

SEARCH

1. FOR SYMBOLS, ABBREVEATIONS AND GENERAL NOTES REFER TO DRAWING E-003.

1. (2) 50.8 MM CONDUITS BACK TO BUILDING 110 THROUGH HANDHOLE FOR SECURITY EQUIPMENT CONNECTIONS TO HEAD END EQUIPMENT. (1) ACTIVE AND (1) SPARE WITH PULL WIRE FOR FUTURE USE. CONDUITS ROUTED VIA DUCT ELECTRICAL DUCT BANK. REFER TO ELECTRICAL DRAWINGS FOR LOCATION AND DETAILS.

2. (2) 50.8 MM CONDUITS TO HAND HOLE AT ISLAND AND MAIN GUARD HOUSE SEC AT COMMAND AND CONTROL. (1) ACTIVE AND (1) SPARE. PROVIDE PULL WIRE IN SPARE FOR FUTURE USE.

PIANTA PRIMO LIVELLO

1. N°2 TUBI DA 50.8MM FINO ALL'EDIFICIO 110 ATRRAVERSO POZZETTO PER

COLLEGAMENTO APPARECCHIATURE DELLA SICUREZZA ALL'APPARATO DI TESTA.

UNO UTILIZZATO ED UNO DI SCORTA CON FILO PILOTA PER USO FUTURO.

TUBAZIONI POSATE SECONDO PERCORSO CAVIDOTTO ELETTRICO. FARE

RIFERIMENTO ALLE TAVOLE ELETTRICHE PER PERCORSO E DETTAGLI.

2. N°2 TUBI DA 50.8MM AL POZZETTO DELL'ISOLA ED ALL'ARMADIO DELLA SICUREZZA

DEL CORPO DI GUARDIA AL COMANDO E CONTROLLO. UNO UTILIZZATO ED UNO DI

SCORTA. FORNIRE FILO PILOTA IN QUELLO DI SCORTA PER USO FUTURO

1. PER SIMBOLI, ABBREVIAZIONI E NOTE GENERALI VEDI TAV. E-003

KEY PLAN - PIANTA CHIAVE

SHEET KEYNOTES - NOTE CHIAVE

GENERAL NOTES - NOTE GENERALI

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

2

F1

D3E

OW-5

OW-4

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:51

:01

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

ED101

LIG

HTI

NG

PLA

N -

OV

ER

WA

TCH

(B

ID O

PTI

ON

3)

-PIA

NO D

I ILLU

MIN

AZIO

NE -

OVER

WAT

CH (O

PZIO

NE O

FFER

TA 3)

KVK

206

14090209

ADK LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

LIGHTING PLAN - OVERWATCH

PLANNORTH

OVERWATCH

GRAPHIC SCALE: 1:50

0 421 3 5

IMPIANTO ILLUMINAZIONE - GARITTAKEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

RCP

G GG G G G GG

GG

GG

GG GGGG

GG

GG

GG

SU-8,10,12(SEARCH OFFICE)

OWPANEL

GFCIWP

MGB

GROUND TEST WELL

GROUND RINGOW-7

OW-3

1OW-2

REMOTE CONTROL PANEL BASE STATION

OW-8HVAC

OW-1

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:51

:01

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

ED102

PO

WE

R P

LAN

-O

VE

RW

ATC

H (

BID

OP

TIO

N 3

) -P

OWER

PLA

N -O

VERW

ATCH

(OPZ

IONE

OFFE

RTA

3)

KVK

207

14090210

ADK LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

POWER PLAN - OVERWATCH

PLANNORTH

OVERWATCH

GRAPHIC SCALE: 1:50

0 421 3 5

1 PROVIDE ELECTRICAL POWER FOR ACCESS CONTROL SYSTEM EQUIPMENT.COORDINATE REQUIREMENTS WITH EQUIPMENT SUPPLIER AND SECURITYSYSTEM DRAWINGS.

1. FORNIRE ALIMENTAZIONE ELETTRICA PER LE APARECCHIATURE DEL SISTEMA DI CONTROLLO ACCESSI. COORDINARE LE NECESSITA' CON IL FORNITORE DELLE APPARECCHIATURE ED I DOSEGNI DELL'IMPIANTO DI SICUREZZA.

IMPIANTO F.M. - GARITTA

KEYNOTES - NOTE CHIAVE

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP

PR

2

B3

ED103____________________________________________________

3

2

55

(2)

11

2

4

55 SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

CONSTR. CONTR. NO.

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

EPROJECT NO.:

DE

PA

RT

ME

NT

OF

TH

E N

AV

YN

AV

AL

FA

CIL

ITY

EN

GIN

EE

RIN

G S

YS

TE

M C

OM

MA

ND

NAVFAC METRIC DRAWFORM REVISION: 07 AUGUST 2018

PM/DM

BRANCH MANAGER

DESIGN DIRECTOR

FIRE PROTECTION

NA

VA

L F

AC

ILIT

Y E

NG

INE

ER

ING

SY

ST

EM

CO

MM

AN

D ~

AT

LA

NT

ICN

OR

FO

LK

, V

IRG

INIA

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CLA

SS

IFIE

D

AV

IAN

O A

IR B

AS

EA

VIA

NO

, IT

ALY

AR

EA

A1

EN

TR

Y C

ON

TR

OL

PO

INT

LET/JSL

DPS

1917 SOUTH 67TH STREETOMAHA, NE 68106

4/6

/20

21 5

:51

:02

PM

BIM

360

://1

022

45

22_

NA

VF

AC

_A

1_D

esig

n_

Avia

no_

Italy

_2

01

8/1

02

245

22

-ME

P-C

anop

y_

v2

018

.rvt

ED103

TELE

CO

MM

UN

ICA

TIO

NS

PLA

N -

OV

ER

WA

TCH

(B

ID O

PTI

ON

3)

-PIA

NO D

ITE

LECO

MUN

ICAZ

IONI

-OV

ERW

ATCH

(OPZ

IONE

OFF

ERTA

3)

KVK

208

14090211

JAZ LAT

208

APPROVED BY SCOTT KIBLERVIA EMAIL

1631931

N62470-21-C-0003

AT

LA

NT

IC D

ES

IGN

AN

D C

ON

ST

RU

CT

ION

RICHARD STEPHENS, PE

SEK

1 : 50B1

TELECOMMUNICATIONS PLAN - OVERWATCH

PLANNORTH

NOT TO SCALENON IN SCALA

(ED103)B3

TELECOMMUNICATIONS RISER

OVERWATCH

1. TELECOM DEVICES SHOWN SHALL BE CONNECTED IN THE SEARCH OFFICE TELECOM ROOM.

GRAPHIC SCALE: 1:50

0 421 3 5

1 PROVIDE CATEGORY 6 RATED SOLID STATE BUILDING ENTRANCE TERMINAL(BET) PRIMARY PROTECTOR WITH 110 CONNECTOR ON INPUT AND OUTPUTSIDE. GROUND PROTECTORS TO GROUND BAR.

2 PROVIDE IP 52 ENCLOSURE WITH HINGED LOCKABLE COVER TO HOUSEBET'S AND 915MM CABLE SERVICE LOOP. LOCATE ENCLOSURE UNDERCOUNTER.

3 PROVIDE 25MM CONDUIT FROM OUTLET BOX TO BET ENCLOSURE.

4 CATEGORY 6 HORIZONTAL CABLE.

5 SERVICE ENTRANCE CONDUITS. STUB UP SPARE CONDUIT 100MM AFF ANDCAP.

1. I COMPONENTI DI TELECOMUNICAZIONE MOSTRATI DEVONO ESSERE COLLEGATI AL LOCALE TELECOMUNICAZIONI DELL'UFFICIO ISPEZIONE

1. FORNIRE UN PROTETTORE PRINCIPALE IN CATEGORIA 6 ALLO STATO SOLIDO PER TERMINAZIONE DI INGRESSO DELL'EDIFICIO (BET) CON CONNETTORI 110 SIA SUL LATO DI INGRESSO CHE QUELLO DI USCITA. METTERE A TERRA I PROTETTORI SULLA SBARRA DI TERRA.

2. FORNIRE UNA CASSETTA IP52 CON COPERCHIO LUCHETTABILE INCERNIERATO PER CONTENERE BET E UNA SPIRA DI 915MM DI SCORTA DEL CAVO. POSIZIONARE LA CASSETTA SOTTO IL RIPIANO.

3. FORNIRE UN TUBO DA 25MM DALLA CASSETTA DELLA PRESA ALLA CASSETTA DEL BET.

4. CAVO ORIZZONTALE CAT 6.

5. TUBI DI INGRESSO DEL SERVIZIO DI TELECOMUNICAZIONI. RISALITA A 100MM DAL PAVIMENTO PER IL TUBO DI SCORTA E SUA CHIUSURA CON TAPPO.

PIANTA TELECOMUNCAZIONI - GARITTA VERTICALE TELECOMUNICAZIONI

KEYNOTES - NOTE CHIAVE

GENERAL SHEET NOTES

NOTE GENRALI DI FOGLIO

KEY PLAN - PIANTA CHIAVE

SY

MD

ES

CR

IPT

ION

DA

TE

AP