electrical installation condition report

34
This inspection and testing detailed in this report and accompanying schedules have been carried out in accordance with BS7671:2008 (IET Wiring Regulations) as amended to Where the overall assessment of the suitability of the installation for continued use above is stated as , recommend that any observations classified as 'Danger present' (code C1) or 'Potentially dangerous (code C2) are acted upon as a matter of urgency Investigation without delay is recommended for observations identified as 'further investigation required' Observation classified as 'Improvement recommended' (code C3) should be given due consideration. Subject to the necessary remedial action being taken recommend that the installation is further inspected and tested by , being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by signatures below), particulars of which are described above, having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information in this report, including the observations and attached schedules, provides an accurate assessment of the condition of the electrical installation taking into account the stated extent and limitations in section D of this report. Extent of Electrical Installation covered by this report: Agreed limitations including the reasons (See regulation 634.2) Operational Limitations including the reasons (See page No ) Agreed with name Client: Address: Purpose of this report: Date(s) on which Inspection: and testing was carried out General condition of the installations (In terms of electrical safety) Overall assessment of the installation *An unsatisfactory assessment indicates that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified. Domestic Description of premises: Records held By: Record of Installation available: Date of previous inspection: Evidence of alterations or additions: Other: Industrial Commercial Estimated age of wiring system: yrs yrs If yes estimated Age Address: Installation: Trading Title and address Inspectedandtestedby: Schedule(s) of inspection and Schedule(s) of test results are attached Reportauthorisedforissueby: Signature Name Position Date Date Position Signature Name The attached schedule(s) are part of this document and this report is valid only when they are attached to it. It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or underground, have NOT been inspected unless specifically agreed between the client and inspector prior to the inspection. Occupier: I NICEIC Enrolment Number Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance NHS Highland Glen Court Raigmore Hospital Inverness Highland No mains shutdown due to residents on site. 08/02/2013 Testing of all sub mains, lighting and power circuits, within the --See Additional Page-- 0 N/A NHS Highland N/A N/A UNSATISFACTORY 031362 NHS Highland Finance Department Assynt House Beechwood Park Inverness Nigel Simpson July 2011 PHS Compliance, Compliance House, Golborne Enterprise Park, Kid Glove Road, Warrington, WA3 3GR Page 1 of 28 Unsatisfactory N/A N/A David Warren Essential information requested by the client in accordance with the electricity at work regulations 1989. Fixed Wire Tester Not Known My 22/02/2013 Glen Court I IV2 3UJ 30 08/02/2013 6 I Bruce Barr Regulation 621.2 - Only a percentage of the installation has been dismantled for inspection purposes. The correct connection of --See Additional Page-- 08/02/2018 N/A Unable to access the sealed supply device characteristics. Ze --See Additional Page-- 12 Qualifying Manager ELECTRICALINSTALLATION CONDITIONREPORT 110008985 - Master A. Details of the Client/Person Ordering the Report B. Reason for Producing this Report C. Details of the Installation which is the Subject of this Report D. Extent and Limitations Inspection and Testing E. Summary of the Condition of the Installation F. Recommendations G. Declaration H. Schedule(s)

Upload: khangminh22

Post on 12-Nov-2023

0 views

Category:

Documents


0 download

TRANSCRIPT

This inspection and testing detailed in this report and accompanying schedules have been carried out in accordance with BS7671:2008 (IET Wiring Regulations) as amended

to

Where the overall assessment of the suitability of the installation for continued use above is stated as , recommend that any observations classified as

'Danger present' (code C1) or 'Potentially dangerous (code C2) are acted upon as a matter of urgency

Investigation without delay is recommended for observations identified as 'further investigation required'

Observation classified as 'Improvement recommended' (code C3) should be given due consideration.

Subject to the necessary remedial action being taken recommend that the installation is further inspected and tested by

, being the person(s) responsible for the inspection and testing of the electrical installation (as indicated by signatures below), particulars of

which are described above, having exercised reasonable skill and care when carrying out the inspection and testing, hereby declare that the

information in this report, including the observations and attached schedules, provides an accurate assessment of the condition of the electrical

installation taking into account the stated extent and limitations in section D of this report.

Extent of Electrical Installation covered by this report: Agreed limitations including the reasons (See regulation 634.2)

Operational Limitations including the reasons (See page No )

Agreed with name

Client:

Address:

Purpose of this report:

Date(s) on which Inspection:

and testing was carried out

General condition of the installations (In terms of electrical safety)

Overall assessment of the installation *An unsatisfactory assessment indicates that dangerous (code C1) and/or potentially dangerous (code

C2) conditions have been identified.

DomesticDescription of

premises:

Records held By:Record of

Installation available:

Date of previous

inspection:

Evidence of alterations

or additions:

Other:

IndustrialCommercial

Estimated age of wiring system:

yrs

yrs

If yes

estimated Age

Address:

Installation:

Trading Title

and address

Inspected and tested by:

Schedule(s) of inspection and Schedule(s) of test results are attached

Report authorised for issue by:

SignatureName Position Date

DatePosition SignatureName

The attached schedule(s) are part of this document and this report is valid only when they are attached to it.

It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces, and generally within the fabric of the building or underground, have NOT

been inspected unless specifically agreed between the client and inspector prior to the inspection.

Branch No. (If Applicable)

Occupier:

I

NICEIC Enrolment Number

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

NHS Highland

Glen Court

Raigmore Hospital

Inverness

Highland

No mains shutdown due to residents on site.

08/02/2013

Testing of all sub mains, lighting and power circuits, within the

--See Additional Page--

0

N/A

NHS Highland

N/A

N/A

UNSATISFACTORY

031362

NHS Highland

Finance Department

Assynt House

Beechwood Park

Inverness

Nigel Simpson

July 2011

PHS Compliance,

Compliance House,

Golborne Enterprise Park,

Kid Glove Road,

Warrington, WA3 3GR

Page 1 of 28

Unsatisfactory

N/A

N/A

000

David Warren

Essential information requested by the client in accordance

with the electricity at work regulations 1989.

Fixed Wire Tester

Not Known

My

22/02/2013

Glen Court

I

IV2 3UJ

30

08/02/2013

6

I

Bruce Barr

Regulation 621.2 - Only a percentage of the installation has been dismantled for inspection purposes. The correct connection of

--See Additional Page--

110008985 - Master

08/02/2018

N/A

Unable to access the sealed supply device characteristics. Ze

--See Additional Page--

12

Qualifying Manager

ELECTRICAL INSTALLATION

CONDITION REPORT

110008985 - Master

A. Details of the Client/Person Ordering the Report B. Reason for Producing this Report

C. Details of the Installation which is the Subject of this Report

D. Extent and Limitations Inspection and Testing

E. Summary of the Condition of the Installation

F. Recommendations

G. Declaration

H. Schedule(s)

One of the following codes, as appropriate, has been allocated to each of the observations made above to indicate to the person(s) responsible for the installation the

degree of urgency for remedial action.

C1 - Danger present. Risk of injury. Immediate remedial action required

C2 - Potentially dangerous - urgent remedial action required

C3 - Improvement recommended

Nominal

current rating

Type

BS(EN)

Supply protective deviceNature of Supply Parameters

2-Phase

(3 wire)

1-Phase

(2 wire)

a.c.

Number and Type of Live Conductors

IT

TT

TN-C

TN-C-S

TN-S

Earthing

Arrangements

3-Phase

(3 wire)

Short circuit

capacity

d.c.

3

Wire

Other

2

Wire

Other

Means of earthing

Distributor's

facility

Installation

earth electrode

Type (e.g. rod(s),

tape etc.)

Details of installation Earth Electrode (where applicable)

Resistance to

EarthΩ

Location

Method of

measurement

Earthing

Conductor

Main protective

bonding conductors

Material

Material

csa

csa

mm

mm

2

2

Connection and Continuity Verified

Connection and Continuity Verified

Bonding of Incoming Service

Water Gas Lightning Oil Steel Other Please State

Maximum Demand (Load)

Protective measure(s) against electric shock

Location

Type BS(EN)

Supply

Conductors

material

No of poles

Supply

Conductors

csa

Current

rating

Fuse/Device

rating or setting

Voltage

rating

A

A

V

if RCD main switch

mA

ms

ms

3-Phase

(4 wire)

Rated residual

operation current,

I n

Rated time delay

RCD Operating

time at, I n

Confirmation of supply polarity

Tick boxes and enter details as applicable

The following observations are madeNo remedial action is required.

Referring to the attached schedule(s) of Inspection and Test Results, and subject to the limitations specified at the Extent and Limitations of the Inspection and testing section.

Item No Code

Further

Investigation

RequiredObservations

kA

A

1-Phase

(3 wire)

mm2

(Note: (1) by enquiry, (2) by enquiry or

by measurement)

Number of

supplies

Ω(2)

ZeExternal loop

impedance

Prospective

fault currentlpf (2) kA

Hz(1)

fNominal

frequency

Nominal

VoltageU 0 V

VUNominal

Voltage

(1)

(1)230

80

0

N/A

N/A

N/A

N/A

200

N/A

10

200

N/A

N/A

Please see the additional sheet(s) at the end of the report.

Electrical Cupboard on Ground Floor

ADS

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

N/A

3

N/ALIM

N/A

0

400

N/A

N/A

Copper

1

N/A

N/A

Page 2 of 28

88-2 Fuse HRC

Copper

N/A

N/A

N/A

5419 Isolator

50

400

N/A

N/A

0

N/A

gG

SWA

N/A

N/A

N/A

No

N/A

LIMSteel

110008985 - Master

N/A

N/A

N/A

N/A

1

0.24N/A

Amps

LIM

120

200

0.97

N/A

110008985 - Master

I. Supply Characteristics and Earthing Arrangements

J. Particulars of Installation Referred to in the Report

Main Protective Conductors

Main Switch / Switch-Fuse / Circuit-Breaker / RCD

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

Ground Floor Electrical

Cupboard.Dorman

Smith.

N/A

N/A

LIM N/AMEC

H

N/A

N/A

Main Switch

120

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance Page 3 of 28

Sub Mains(DB Main Section Board) 1 MCCB Obsolete 200

N/A

B LIM1/TP D

N/A

5

N/A

110008985 - Master

N/A

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

08/02/2013

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

5792

N/A

Fixed Wire Tester

5792

N/A N/A

5792

N/A LIM NO

110008985 - Master

1/TP

Nigel Simpson

N/A

N/A

N/A

N/A

LIM

N/A

LIMLIM

N/A

Page 4 of 28

LIM

N/A

0.25

N/A

N/A

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

60

-

Ground Floor Electrical

Cupboard.Dorman

Smith.3 Way

LIM

N/A

35

-

400

LIM

LIM

SPARE

N/A

125

5

N/A

MCCB Obsolete

SWA

LIM

-

Sub Mains(DB E,DB H)

-

LIM

-

5

5

N/A

35

60

3

3

200

Sub Mains(DB GFF)

C

DB Main Section Board

10

B

3

SWA

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

MCCB Obsolete

2

MCCB Obsolete

-

2/L2

Page 5 of 28

35

5

3/L1

Calorifier

LIM

1

3/L2

35

MCCB Obsolete

-

Sub Mains(DB A,DB C,DB F)

-

35

5

D

MCCB Obsolete

-

60

N/A

1

SubMains(Main Switch, 1/TP)

3/L3

LIM

G 35

35

Sub Mains(DB B,DB D,DB G)

N/A

SWA

2/L3

G

C LIM

35

1/TP

LIMG

F

-

LIMC

125

D

N/A

B LIM

MCCB Obsolete

C

1

MCCB Obsolete

-

5

LIM

N/A

2/L1

-

110008985 - Master

125

Sub Mains(DB Stair L&P)

N/A

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

N/A

N/AN/A

LIM

LIM

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

5792

N/A

2/L3

N/A

-

Fixed Wire Tester

N/A 0.27

5792

N/A

3/L1

NO

N/A N/A

5792

-

NO

-

N/A

N/A

LIM

-

LIM

N/A

LIM

LIM

LIM

N/A

-

N/A

LIM

---

0.26LIM

3/L2 N/A

N/A

NO

110008985 - Master

LIMN/A

1/TP

Nigel Simpson

LIM

N/A

N/A

LIMN/A

NO

0.94

LIM

-

N/A

LIM2/L1

N/A

LIM

N/A

N/A

N/A

LIM

N/A

LIM

LIMN/A

0.25

LIM

-

0.26

N/A

0.26

LIM

Page 6 of 28

LIM

N/A

LIM

2/L2

NO

N/A

-

N/A

3/L3

0.31

--

0.27

N/A LIM

-

N/A

N/A

LIM

LIM

N/A

NO

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

30

4

Ground Floor Electrical

Cupboard.Dorman

Smith.9 Way

2.30

N/A

1.5

3

7

400

2.30

3871 MCB

3

Sockets Hall,Store & DSR

C

N/A

MIC

C

-

N/A

30

0.4

3

N/A

3871 MCB

10

-

0.4

SPARE

30

-

N/A

0.4

3

0.4

2.5

N/A

0.77

-

30

1

5

60

Sockets Laundry

B

DB GFF

2.5

10

B

30

5

C

4 3

3871 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

3871 MCB

-

3871 MCB

4

8/L1

3/L1

Page 7 of 28

-

0.4

3

5/L1

MIC

C

0.77

Cooker

0.77

Tumble Dryer

1

6/L1

3

1

1.5

3871 MCB

3871 MCB

Lights Hall,Gents WC,Laundry & Bell

3

1.5

-

B

3871 MCB

B

50

-

9

SubMains(DB Main Section Board,

7/L1

0.77

0.4

B 1.5

9/L1

4

Lights DSR,Ladies WC,Store & Common Room

N/A

4

4/L1

H

-

B 0.463

4

1/L1

H

3B

B

3

3B

10

B

N/A

0.4

B 3

MCCB Obsolete

-

3

-

4

Washing Machine

-

B

1

0.4

3

3

N/A

N/A

2/L1

0.77

110008985 - Master

10

Sockets Common Room

N/A

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

N/A

08/02/2013

9/L1

N/A

N/AN/A

-

>299

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

5792

>299

N/A

4/L1

N/A

>299

Fixed Wire Tester

0.12

N/A 1.03

5792

N/A

N/A

5/L1

N/A

NO

N/A N/A

N/A

5792

>299

N/A

NO

N/A

N/A

N/A

LIM

NO

0.28

-

>299

N/A

0.33

>299

0.11

>299

-

N/A

N/A

N/A

N/A

N/A

NON/A

0.36>299

NO

6/L1 N/A

-

NO

110008985 - Master

--

N/A

1/L1

Nigel Simpson

-

N/A N/A

N/A

N/A

LIM

LIM

N/A

NO

>299

0.89

-

LIM

N/A

>299

N/A

2/L1

-

>299

N/A

N/A

N/A

LIM

0.38

>299

-

N/A

-

0.01

>299N/A

0.26

0.77

N/A

0.37

N/A

-

8/L1

0.10

Page 8 of 28

>299

-

>299

>299

3/L1

NO

N/A

N/A

N/A

0.37

7/L1

0.27

0.02

0.59

N/A 0.11

N/A

-

N/A

LIM

LIM

N/A

-

LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

30

1.5

Ground Floor Electrical

Cupboard.Dorman

Smith.8 Way

-

N/A

-

3

1

230

2.30

3871 MCB

-

Fire alarm panel

N/A

-

15

0.4

-

3871 MCB

-

-

0.4

SPARE

10

-

N/A

-

3

0.4

2.5

-

-

30

1

-

60

Sockets Tank Room

-

DB Stair L&P

-

B

2

B

MEC

H

3

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

3871 MCB

-

3871 MCB

MEC

H

8/L2

3/L2

Page 9 of 28

-

0.4

5/L2

MEC

H

1.53

SPARE

0.77

-

6/L2

-

10

-

-

3871 MCB

SPARE

3

1.5

-

B

-

O

-

-

3

SubMains(DB Main Section Board,

7/L2

0.77

0.4

B MEC

H

4

Lights Tank Room

N/A

MEC

H

4/L2

-

- --

4

1/L2

B

--

-

3

3B

-

B

N/A

B 3

MCCB Obsolete

-

3

-

3

Lights Stairwell & Porch

-

C

-

3

3

N/A

N/A

2/L2

2.30

110008985 - Master

10

Sockets Stairwell

N/A

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

N/A

08/02/2013

N/A

N/AN/A

-

>299

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

5792

>299

N/A

4/L2

N/A

>299

Fixed Wire Tester

0.50

N/A 0.86

5792

-

5/L2

N/A

NO

- -

5792

>299

N/A

NO

- -

N/A

N/A

--

NO

0.49

-

>299

- -

-

>299

>299

-

N/A

N/A

-

NON/A

0.29>299

6/L2 N/A

-

-

110008985 - Master

--

N/A

1/L2

Nigel Simpson

-

N/A N/A

-

N/A

LIMN/A

-

0.84

-

LIM

N/A

>2992/L2

-

-

-

N/A

-

-

0.76

-

-

N/A

-

-

--

0.26

0.60

N/A

0.38

N/A

-

8/L2

-

0.03

Page 10 of 28

-

-

>299

- -

3/L2

NO

-

N/A

N/A

N/A

7/L2

-

0.23

-

N/A 0.12

-

N/A

-

N/A

LIM

LIM

N/A

-

LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

A.

H 12

4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

32

-

10

N/A

20

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

2X4

-

-

2.30

-

4

-

-

1060898 MCB

11/L3

-

6

1

- -

-

125

Lights Bedroom 4,Hall,Kitchen,WC & Bathroom

-

DB A

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L3

-

8/L3

3/L3

Page 11 of 28

-

0.4

12/L3

-

B

5/L3

SPARE

5

-

2X4 1.44

Cooker

7.67

Sockets Kitchen

1

6/L3

-

-

-

12

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L3

7.67

0.4

- -

9/L3

1.5

SPARE

2.30

N/A

1.5

4/L3

-

-

B

-

B 1.15B

Sockets Bedroom 4 and Hall

1.5

B

1/L3

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L3 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Bedrooms 1,2&3

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L3

-

110008985 - Master

-

Lights Bedrooms 1,2&3 and Hall Cupboard

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

32

-

9/L3

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L3

N/A

-

Fixed Wire Tester

0.04

- -

5792

N/A

-

-

5/L3

N/A

-

N/A

-

N/A

N/A

5792

-

0.27

NO

-

-

N/A

-

-

32

0.27

N/A

-

0.31

-

NO

-

-

-

-

-

-

N/A

-

-

0.03

>299

-

-

10/L3

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.74>299

NO

6/L3

-

-

-

-

NO

-

110008985 - Master

115

-

11/L3

-

-

LIM

-

NO

N/A

N/A

-

1/L3

Nigel Simpson

-

-

0.25

32

-

N/A

-

N/A

5792

LIM

0.04

LIM

-

N/A

-

>299

-

-

0.85

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L3

-

>299

-

N/A

-

-

-

LIM

-

0.31

>299

-

-

-

N/A

-

0.05

13/L3

-

--

0.27

-

-

- -

-

0.86

N/A

-

-

8/L3

-

0.47

Page 12 of 28

-

-

-

>299

>299

3/L3

-

NO

-

>299

-

-

N/A

0.30

7/L3

0.32

--

- -

N/A

-

N/A 0.59

-

-

12/L3

115

-

N/A

-

LIM

-

N/A

-

-

115LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

B.

H 12

4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

32

-

10

N/A

20

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

2X4

-

-

2.30

-

4

-

-

1060898 MCB

11/L2

-

6

1

- -

-

125

Lights Bedroom 8,Hall,Kitchen,WC & Bathroom

-

DB B

4

-

-

-

10

B

20

-

B

-

2X1.

5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L2

-

8/L2

3/L2

Page 13 of 28

-

0.4

12/L2

-

B

5/L2

SPARE

5

-

2X4 1.44

Cooker

7.67

Sockets Kitchen

1

6/L2

-

-

-

12

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L2

7.67

0.4

- -

9/L2

2X1.

5

SPARE

2.30

N/A

1.5

4/L2

-

-

B

-

B 1.15B

Sockets Bedroom 8 and Hall

1.5

B

1/L2

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L2 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Bedrooms 5,6&7

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L2

-

110008985 - Master

-

Lights Bedrooms 5,6&7 , Hall Cupboard and

Doorbell

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

32

-

9/L2

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L2

N/A

-

Fixed Wire Tester

0.04

- -

5792

N/A

-

-

5/L2

N/A

-

N/A

-

N/A

N/A

5792

-

0.28

NO

-

-

N/A

-

-

32

0.28

N/A

-

0.30

-

NO

-

-

-

-

-

-

N/A

-

-

0.01

>299

-

-

10/L2

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.73>299

NO

6/L2

-

-

-

-

NO

-

110008985 - Master

118

-

11/L2

-

-

LIM

-

NO

N/A

N/A

-

1/L2

Nigel Simpson

-

-

0.26

32

-

N/A

-

N/A

5792

LIM

0.03

LIM

-

N/A

-

>299

-

-

0.83

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L2

-

>299

-

N/A

-

-

-

LIM

-

0.31

>299

-

-

-

N/A

-

0.01

13/L2

-

--

0.27

-

-

- -

-

0.93

N/A

-

-

8/L2

-

0.46

Page 14 of 28

-

-

-

>299

>299

3/L2

-

NO

-

>299

-

-

N/A

0.28

7/L2

0.28

--

- -

N/A

-

N/A 0.66

-

-

12/L2

118

-

N/A

-

LIM

-

N/A

-

-

118LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

C.

H 12

4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

32

-

10

N/A

20

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

2X4

-

-

2.30

-

4

-

-

1060898 MCB

11/L3

-

6

1

- -

-

125

Lights Bedrooms 9,10&11 , Hall Cupboard and

Doorbell

-

DB C

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L3

-

8/L3

3/L3

Page 15 of 28

-

0.4

12/L3

-

B

5/L3

SPARE

5

-

2X4 1.44

Cooker

7.67

Sockets Bedroom 12 and Hall

1

6/L3

-

-

-

12

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L3

7.67

0.4

- -

9/L3

1.5

SPARE

2.30

N/A

1.5

4/L3

-

-

B

-

B 1.15B

Sockets Kitchen

1.5

B

1/L3

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L3 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Bedrooms 9,10&11

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L3

-

110008985 - Master

-

Lights Bedroom 12,Hall,Kitchen,WC & Bathroom

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

32

-

9/L3

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L3

N/A

-

Fixed Wire Tester

0.05

- -

5792

N/A

-

-

5/L3

N/A

-

N/A

-

N/A

N/A

5792

-

0.26

NO

-

-

N/A

-

-

32

0.26

N/A

-

0.36

-

NO

-

-

-

-

-

-

N/A

-

-

0.08

>299

-

-

10/L3

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.87>299

NO

6/L3

-

-

-

-

NO

-

110008985 - Master

138

-

11/L3

-

-

LIM

-

NO

N/A

N/A

-

1/L3

Nigel Simpson

-

-

0.24

32

-

N/A

-

N/A

5792

LIM

0.09

LIM

-

N/A

-

>299

-

-

0.85

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L3

-

>299

-

N/A

-

-

-

LIM

-

0.32

>299

-

-

-

N/A

-

0.02

13/L3

-

--

0.27

-

-

- -

-

0.71

N/A

-

-

8/L3

-

0.60

Page 16 of 28

-

-

-

>299

>299

3/L3

-

NO

-

>299

-

-

N/A

0.35

7/L3

0.29

--

- -

N/A

-

N/A 0.44

-

-

12/L3

138

-

N/A

-

LIM

-

N/A

-

-

138LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

D.

H 12

2X4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

20

-

10

N/A

32

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

4

-

-

2.30

-

2X4

-

-

1060898 MCB

11/L2

-

6

1

- -

-

125

Lights Bedrooms 13,14&15 , Hall Cupboard and

Doorbell

-

DB D

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L2

-

8/L2

3/L2

Page 17 of 28

-

0.4

12/L2

-

B

5/L2

SPARE

12

-

4 2.30

Cooker

7.67

Sockets Kitchen

1

6/L2

-

-

-

5

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L2

7.67

0.4

- -

9/L2

1.5

SPARE

1.44

N/A

1.5

4/L2

-

-

B

-

B 1.15B

Sockets Bedrooms 13,14&15

1.5

B

1/L2

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L2 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Bedroom 16 and Hall

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L2

-

110008985 - Master

-

Lights Bedroom 16,Hall,Kitchen,WC & Bathroom

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

26

-

9/L2

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L2

N/A

-

Fixed Wire Tester

0.08

- -

5792

N/A

-

-

5/L2

N/A

-

N/A

-

N/A

N/A

5792

-

N/A

NO

-

-

0.28

-

-

26

N/A

N/A

-

0.37

-

NO

-

-

-

-

-

-

N/A

-

-

0.09

>299

-

-

10/L2

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.86>299

NO

6/L2

-

-

-

-

NO

-

110008985 - Master

115

-

11/L2

-

-

LIM

-

NO

N/A

0.28

-

1/L2

Nigel Simpson

-

-

N/A

26

-

N/A

-

N/A

5792

LIM

0.10

LIM

-

N/A

-

>299

-

-

0.85

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L2

-

>299

-

N/A

-

-

-

LIM

-

0.35

>299

-

-

-

N/A

-

0.04

13/L2

-

--

0.27

-

-

- -

-

0.82

N/A

-

-

8/L2

-

0.59

Page 18 of 28

-

-

-

>299

>299

3/L2

-

NO

-

>299

-

-

N/A

0.36

7/L2

0.31

--

- -

0.27

-

N/A 0.55

-

-

12/L2

115

-

N/A

-

LIM

-

N/A

-

-

115LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

E.

H 12

4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

32

-

10

N/A

20

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

2X4

-

-

2.30

-

4

-

-

1060898 MCB

11/L1

-

6

1

- -

-

125

Lights Bedroom 20,Hall,Kitchen,WC & Bathroom

-

DB E

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L1

-

8/L1

3/L1

Page 19 of 28

-

0.4

12/L1

-

B

5/L1

SPARE

5

-

2X4 1.44

Cooker

7.67

Sockets Kitchen

1

6/L1

-

-

-

12

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L1

7.67

0.4

- -

9/L1

1.5

SPARE

2.30

N/A

1.5

4/L1

-

-

B

-

B 1.15B

Sockets Bedroom 20 and Hall

1.5

B

1/L1

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L1 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Bedrooms 17,18&19

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L1

-

110008985 - Master

-

Lights Bedrooms 17,18&19 , Hall Cupboard and

Doorbell

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

32

-

9/L1

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L1

N/A

-

Fixed Wire Tester

0.07

- -

5792

N/A

-

-

5/L1

N/A

-

N/A

-

N/A

N/A

5792

-

0.28

NO

-

-

N/A

-

-

32

0.26

N/A

-

0.30

-

NO

-

-

-

-

-

-

N/A

-

-

0.05

>299

-

-

10/L1

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.77>299

NO

6/L1

-

-

-

-

NO

-

110008985 - Master

118

-

11/L1

-

-

LIM

-

NO

N/A

N/A

-

1/L1

Nigel Simpson

-

-

0.29

32

-

N/A

-

N/A

5792

LIM

0.04

LIM

-

N/A

-

>299

-

-

0.88

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L1

-

>299

-

N/A

-

-

-

LIM

-

0.33

>299

-

-

-

N/A

-

0.01

13/L1

-

--

0.26

-

-

- -

-

0.94

N/A

-

-

8/L1

-

0.51

Page 20 of 28

-

-

-

>299

>299

3/L1

-

NO

-

>299

-

-

N/A

0.31

7/L1

0.27

--

- -

N/A

-

N/A 0.68

-

-

12/L1

118

-

N/A

-

LIM

-

N/A

-

-

118LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

F.

H 12

2X4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

20

-

10

N/A

32

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

4

-

-

2.30

-

2X4

-

-

1060898 MCB

11/L3

-

6

1

- -

-

125

Lights Bedrooms 21,22&23 , Hall Cupboard and

Doorbell

-

DB F

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L3

-

8/L3

3/L3

Page 21 of 28

-

0.4

12/L3

-

B

5/L3

SPARE

12

-

4 2.30

Cooker

7.67

Sockets Bedroom 24 and Hall

1

6/L3

-

-

-

5

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L3

7.67

0.4

- -

9/L3

1.5

SPARE

1.44

N/A

1.5

4/L3

-

-

B

-

B 1.15B

Sockets Bedrooms 21,22&23

1.5

B

1/L3

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L3 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Kitchen

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L3

-

110008985 - Master

-

Lights Bedroom 24,Hall,Kitchen,WC & Bathroom

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

32

-

9/L3

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L3

N/A

-

Fixed Wire Tester

0.03

- -

5792

N/A

-

-

5/L3

N/A

-

N/A

-

N/A

N/A

5792

-

N/A

NO

-

-

0.27

-

-

32

N/A

N/A

-

0.33

-

NO

-

-

-

-

-

-

N/A

-

-

0.09

>299

-

-

10/L3

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.84>299

NO

6/L3

-

-

-

-

NO

-

110008985 - Master

106

-

11/L3

-

-

LIM

-

NO

N/A

0.26

-

1/L3

Nigel Simpson

-

-

N/A

32

-

N/A

-

N/A

5792

LIM

0.06

LIM

-

N/A

-

>299

-

-

0.85

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L3

-

>299

-

N/A

-

-

-

LIM

-

0.30

>299

-

-

-

N/A

-

0.03

13/L3

-

--

0.27

-

-

- -

-

0.75

N/A

-

-

8/L3

-

0.57

Page 22 of 28

-

-

-

>299

>299

3/L3

-

NO

-

>299

-

-

N/A

0.36

7/L3

0.30

--

- -

0.27

-

N/A 0.48

-

-

12/L3

106

-

N/A

-

LIM

-

N/A

-

-

106LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

G.

H 12

2X4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

20

-

10

N/A

32

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

4

-

-

2.30

-

2X4

-

-

1060898 MCB

11/L2

-

6

1

- -

-

125

Lights Bedroom 28,Hall,Kitchen,WC & Bathroom

-

DB G

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L2

-

8/L2

3/L2

Page 23 of 28

-

0.4

12/L2

-

B

5/L2

SPARE

12

-

4 2.30

Cooker

7.67

Sockets Bedroom 28 and Hall

1

6/L2

-

-

-

5

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L2

7.67

0.4

- -

9/L2

1.5

SPARE

1.44

N/A

1.5

4/L2

-

-

B

-

B 1.15B

Sockets Bedrooms 25,26&27

1.5

B

1/L2

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L2 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Kitchen

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L2

-

110008985 - Master

-

Lights Bedrooms 25,26&27 and Hall Cupboard

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

32

-

9/L2

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L2

N/A

-

Fixed Wire Tester

0.03

- -

5792

N/A

-

-

5/L2

N/A

-

N/A

-

N/A

N/A

5792

-

N/A

NO

-

-

0.28

-

-

32

N/A

N/A

-

0.34

-

NO

-

-

-

-

-

-

N/A

-

-

0.02

>299

-

-

10/L2

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.71>299

NO

6/L2

-

-

-

-

NO

-

110008985 - Master

125

-

11/L2

-

-

LIM

-

NO

N/A

0.28

-

1/L2

Nigel Simpson

-

-

N/A

32

-

N/A

-

N/A

5792

LIM

0.07

LIM

-

N/A

-

>299

-

-

0.85

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L2

-

>299

-

N/A

-

-

-

LIM

-

0.30

>299

-

-

-

N/A

-

0.01

13/L2

-

--

0.27

-

-

- -

-

0.80

N/A

-

-

8/L2

-

0.44

Page 24 of 28

-

-

-

>299

>299

3/L2

-

NO

-

>299

-

-

N/A

0.29

7/L2

0.28

--

- -

0.27

-

N/A 0.53

-

-

12/L2

125

-

N/A

-

LIM

-

N/A

-

-

125LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

Live

mm 22

Supply to

distribution

board is from

No of phases

TO BE COMPLETED IN EVERY CASE ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED DIRECTLY TO THE ORIGIN

OF THE INSTALLATION

Overcurrent protective device for the distribution circuit

Associated RCD (if any)

BS(EN)

RCD No of

Poles

RCD Rating

A B C D E F G H O

PVC/PVC

cables

PVCcables

in

metallic

conduit

PVCcables

in

non-metallic

conduit

PVCcables

in

metallic

trunking

PVCcables

in

non-metallic

trunking

PVC/SWA

cables

XLPE/SWA

cables

Mineral insulated

cablesOther

Nominal Voltage

Type BS(EN) Rating

Max

per-

mitted

Zs

Circuit

number

and

phase

Circuit designationType of

wiring

Refe-

rence

method

No of

points

served

Circuit

conductors csa

cpc

mm

Max

per-

mitted

disc-

onnec-

tion

times

Overcurrent protective device RCD

Type

No

Rating

Short

circuit

capa-

city

Op.

currentBS(EN)

A

V

mA

Location of

Distribution

Board

Distribution

board

designation

A kA nI

-

6

-

Electrical Cupboard

Flat

H.

H 12

2X4

-

- -

30

-

-

-

B

-

230

-

60898 MCB

10

SPARE

B

-

4

-

30

-

20

-

10

N/A

32

- -

-

60898 MCB

-

10

-

SPARE

-

SPARE

-

-

-

-

-

B

-

0.4

4

-

-

2.30

-

2X4

-

-

1060898 MCB

11/L1

-

6

1

- -

-

125

Lights Bedroom 32,Hall,Kitchen,WC & Bathroom

-

DB H

4

-

-

-

10

B

20

-

B

-

1.5

-

B

60898 MCB

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

60898 MCB

-

-

-

10/L1

-

8/L1

3/L1

Page 25 of 28

-

0.4

12/L1

-

B

5/L1

SPARE

12

-

4 2.30

Cooker

7.67

Sockets Bedroom 32 and Hall

1

6/L1

-

-

-

5

-

60898 MCB

-

RCD Module (Split Board)

0.4

-

-

-

-

B

-

-

-

40

-

7

SubMains(DB Main Section Board,

7/L1

7.67

0.4

- -

9/L1

1.5

SPARE

1.44

N/A

1.5

4/L1

-

-

B

-

B 1.15B

Sockets Bedrooms 29,30&31

1.5

B

1/L1

B

-

-

-

B

-

--

-

-

B

N/A

0.4

B

13/L1 -

B

10

MCCB Obsolete

-

10

-

7

Sockets Kitchen

-

-

-

5

0.4

B 30

-

10

30

61008 RCD

2/L1

-

110008985 - Master

-

Lights Bedrooms 29,30&31 and Hall Cupboard

2

SPARE

110008985 - MasterSCHEDULE OF CIRCUIT DETAILS FOR THE INSTALLATION

Board Details

Circuit Details

Wiring Code

Rem

ark

s

se

eco

ntin

ua

tion

sh

ee

t

Maximum

measured

earth fault

loop

impedance

ONLY TO BE COMPLETED IF THE DISTRIBUTION BOARD IS NOT CONNECTED

DIRECTLY TO THE ORIGIN OF THE INSTALLATIONTEST INSTRUMENTS (SERIAL NUMBERS) USED

Circuit

number

and

phase

Circuit Impedances p

o

l

a

r

i

t

y

Live/

Neutral

Insulation resistance

Live/

Earth

At At

Te

st

butt

on

opera

tio

n

r1 (Line) rn (Neutral) r2 (cpc) (R1 + R2) (R2)

All circuits

(At least one

column

to be completed)Live/

Live

Earth/

Neutral

Date of

testing

Position

Name

Signature

Ipf

Zs

kA

Operating

times of

associated

RCD (if any) At 5I

At In

ms

msn

Ring final circuits only

(measure end to end)

RCD operating

times

Phase sequence confirmed

(where appropriate)

Correct supply

polarity

confirmed

Insulation

resistanceOther

RCD

Earth fault

loop

impedance

Continuity Other

ms ms

I n 5I n

-

08/02/2013

33

-

9/L1

-

N/AN/A

>299

-

N/A

-

>299

-

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

-

5792

>299

N/A

4/L1

N/A

-

Fixed Wire Tester

0.10

- -

5792

N/A

-

-

5/L1

N/A

-

N/A

-

N/A

N/A

5792

-

N/A

NO

-

-

0.27

-

-

33

N/A

N/A

-

0.36

-

NO

-

-

-

-

-

-

N/A

-

-

0.07

>299

-

-

10/L1

N/A

-

-

--

N/A

N/A

N/A

-

-

---

0.66>299

NO

6/L1

-

-

-

-

NO

-

110008985 - Master

135

-

11/L1

-

-

LIM

-

NO

N/A

0.28

-

1/L1

Nigel Simpson

-

-

N/A

33

-

N/A

-

N/A

5792

LIM

0.10

LIM

-

N/A

-

>299

-

-

0.88

-

-

-

-

-

N/A

N/A

>299

N/A

-

-

2/L1

-

>299

-

N/A

-

-

-

LIM

-

0.36

>299

-

-

-

N/A

-

0.02

13/L1

-

--

0.26

-

-

- -

-

0.76

N/A

-

-

8/L1

-

0.40

Page 26 of 28

-

-

-

>299

>299

3/L1

-

NO

-

>299

-

-

N/A

0.33

7/L1

0.28

--

- -

0.27

-

N/A 0.50

-

-

12/L1

135

-

N/A

-

LIM

-

N/A

-

-

135LIM

110008985 - MasterSCHEDULE OF CIRCUIT TESTS FOR THE INSTALLATION

Board Tests

Details of circuits and/or equipment vulnerable to damage

Circuit Tests

Tested By

within an area containing a shower/bath should be protected by RCD`s Reg 701.411.3.3 In order to comply

A Further 2 DB’s are part of the main Section Board and are wired in 35mm2 Singles contained within the

no access to bonds on pipe work.

Page 27 of 28

main section board is located.

obtained from the manufacturer).

Section Board and again protected by Obsolete MCCB’s.

outside Reg 411.3.3(ii) both of these require additional RCD protection . Also all circuits that terminate

exact route of the cables. There are general sockets throughout the installation which can be used by

every conductor and link throughout the premises cannot be ensured.

8 of the Sub-Main circuits from the section board are wired in SWA cable clipped direct to the building fabric

constraints of the agreed and operational limitation.

Regulation 522.6.6 of BS 7671:2008. Further investigation may need to take place, as I am limited to see the

with Regulation 514.9.1 of the BS 7671:2008.

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

mm from the surface. If they are not they need to be wired in a containment which will protect the cable from

All wiring entered as type O on report is FP200.

Circuit charts should be ascertained for each Distribution Board providing relevant information in accordance

to disconnect load.

and are afforded over current protection by Obsolete MCCB’s (the maximum Zs values for these should be

Cables which have been clipped direct through a cavity or partitioned wall shall be no less than a depth of 50

The installation is 30 years old and has evidence of alterations in the last 6 years.

the penetration of a nail, or have additional protection in the form of an RCD, in order to comply with

The majority of the final circuits are wired in PVC singles contained in metal conduit.

The final circuits are afforded over current protection by BS 3871 & BS 60898 Mcb's and BS 61008 RCD’s

unskilled people Reg 411.3.3.(i) and sockets that could potentially be used to supply portable appliances

and Ipf have been taken as close to the origin as possible.

10mm2 Main protective bonding conductors are present at the DB’s for the Water Service pipe work -these

with BS 7671:2008, these require additional RCD protection.

The supply enters the building in the main electrical cupboard on the ground floor of the building where the

Insulation resistance testing has been carried out to regulation 612.3.3 on circuits were it was impracticable

have been taken from the local DB for each flat (terminations are not visible),these could not be verified as

Extent of Electrical Installation covered by this report, Continued. from page 1

Agreed limitations including the reasons, Continued. from page 1

General condition of the installations (In terms of electrical safety), Continued. from page 1

110008985 - Master

11. Lhs - Left hand side.

5. RCD - residual current device.

Page 28 of 28

1. D.B.-distribution board.

9. C/w - comes with.

12. Csa - Cross sectional area.

the circuit protective conductors although this cannot always be ensured. On the distribution board

7. Cpc - Circuit protective conductor.

The installation is unsatisfactory. However in order for the installation to become satisfactory and up to date

2. Mcb - miniature circuit breaker.

radial circuits every effort has been made to carry out testing at the furthest point to check for continuity of

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

possible .The polarity of all accessible socket outlets have been checked and on carrying out testing of

8. TP - Three phase.

13.FT – Firetuff (FP200)

board only. Circuits may have been jointed with a different cable type further along the circuit.

10. Rhs - Right hand side.

Due to the installation being in use at the time of the inspection and test items that were obstructed by

3. Skts - sockets.

with the present British Standards, I suggest that all defects on page 2 of this report be rectified.

6. SWA - Steel wire armour.

Abbreviations used:

schedules of circuit details cable types and sizes have been typed in as what is visible at the distribution

furniture, etc were not tested although a visual inspection on such items would have been carried out where

4. Lts - lights.

110008985 - Master

CONDITION REPORT

GUIDANCE NOTES FOR RECIPIENTS

The purpose of this Condition Report is to confirm, so far as reasonably practicable, whether or not the

electrical installation is in a satisfactory condition for continued service (see Section E). The Report should

identify any damage, deterioration, defects and/or conditions which may give rise to danger (see Section K).

This report is an important and valuable document which should be retained for future reference.

1.

The person ordering the Report should have received the original Report and the inspector should have

retained a duplicate.

2.

The original Report should be retained in a safe place and be made available to any person inspecting or

undertaking work on the electrical installation in the future. If the property is vacated, this Report will provide

the new owner /occupier with details of the condition of the electrical installation at the time the Report was

issued.

3.

Where the installation incorporates residual current devices (RCD) there should be a notice at or near the

device stating that it should be tested quarterly. For safety reasons it is important that this instruction is

followed.

4.

Section D (Extent and Limitations) should identify fully the extent of the installation covered by this Report and

any limitations on the inspection and testing. The inspector should have agreed these aspects with the person

ordering the Report and with other interested parties (licensing authority, insurance company, mortgage

provider and the like) before the inspection was carried out.

5.

Some operational limitations such as such as inability to gain access to parts of the installation or an item of

equipment may have been encountered during the inspection. The inspector should have noted these in

Section D.

6.

For items classified in Section K as C1 (“Danger Present”), the safety of those using the installation is at risk,

and it is recommended that a competent person undertakes the necessary remedial work immediately.

7.

For items classified in Section K as C2 (“Potentially Dangerous”), the safety of those using the installation may

be at risk and it is recommended that a competent person undertakes the necessary remedial work as a

matter of urgency.

8.

Where it has been stated in Section K that an observation requires further investigation the inspection has

revealed an apparent deficiency which could not, due to the extent or limitations of this inspection, be fully

identified. Such observations should be investigated as soon as possible. A further examination of the

installation will be necessary, to determine the nature and extent of the apparent deficiency (see Section F).

9.

For safety reasons, the electrical installation should be re-inspected at appropriate intervals by a competent

person. The recommended date by which the next inspection is due is stated in Section F of the Report under

‘Recommendations’ and on a label at or near to the consumer unit / distribution board.

10.

Copyright © Amtech Group Ltd 2012, FastTest Pro [17th Edition] v2012.0.2, PHS Compliance

Item Description

1.0 OutcomeFurther

investigation

√ No

√ No

√ No

√ No

√ No

N/V No

N/A No

3.0 OutcomeFurther

investigation

3.1

√ No

N/A No

√ No

√ No

√ No

C2 (see section K) No

N/V No

N/V No

3.2

N/A No

N/A No

3.3

N/A No

N/A No

Other Methods Details

Non-conducting location (418.1) N/A No

Earth-free local equipotential

bonding (418.2)N/A No

Electrical separation for the supply

to more than one item of current

using equipment (Sec 413; 418.3)

N/A No

Double insulation (Section 412) N/A No

Reinforced insulation (Section 412) N/A No

Use of obstacles (417.2) N/A No

Placing out of reach (417.3) N/A No

5.0 OutcomeFurther

investigation

√ No

√ No

√ No

N/V No

√ No

√ No

√ No

√ No

C3 (see section K) No

√ No

√ No

N/A No

√ No

√ No

√ No

√ No

Master:110008985

Further

investigationOutcome

Presence of adequate arrangements for other services, such as Microgenerators (551.6; 551.7)2.0

Earthing / Bonding Arrangements (411.3; Chap 54)

Provision of earthing / bonding labels at all appropriate locations (514.13.1)

Presence and condition of earth electrode connection where applicable (542.1.2.3)

Presence of distributor’s earthing arrangement (542.1.2.1; 542.1.2.2)3.1.1

3.1.2

Service cable condition1.1

1.6

1.5

1.4

1.3

1.2

Condition of Isolator (where present)

Condition of metering equipment

Condition of tails - Consumer

Condition of tails - Distributor

Condition of Service head

5.7

4.4

4.5

4.6

5.16

4.7

5.4

5.5

5.8

5.9

Presence of other required labelling (Section 514)

5.12 Presence of alternative supply warning notice at or near consumer unit / distribution board

(514.15)

Examination of protective device(s) and base(s); correct type and rating (no signs of

unacceptable thermal damage, arcing and overheating (421.1.3)

Single-pole protective devices in line conductor only (132.14.1; 530.3.2)

Protection against mechanical damage where cables enter consumer unit / distribution board

(522.8.1; 522.8.11)

5.13

5.14

5.15

Presence of RCD quarterly test notice at or near consumer unit / distribution board (514.12.2)

Presence of non-standard (mixed) cable colour warning notice at or near consumer unit /

distribution board (514.14)

Adequacy of working space / accessibility to consumer unit / distribution board (132.1.2; 513.1)

Accessibility and condition of all protective bonding connections (543.3.2)

Condition and accessibility of main protective bonding conductor connections (543.3.2; 544.1.2)

Confirmation of main protective bonding conductor sizes (544.1)

(Where any of the methods listed below are employed details should be provided)

CONSUMER UNITS / DISTRIBUTION BOARDS

Plugs, sockets-outlets and the like not interchangeable with those of other systems within the

premises (411.7.5)

Source supplying at least simple separation (411.7)

3.1.6

3.1.7

3.1.8

5.1

5.2

3.2.2

3.3.1

3.2.1

Security of fixing (416.2.3)

FELV

5.10

5.11

Reduced low voltage

3.3.2

Condition of enclosure(s) in terms of fire rating etc (526.5)

Enclosure not damaged/deteriorated so as to impair safety (621.2 (iii))

Presence of linked main switch (as required by 537.1.4)

Operation of main switch (functional check) (612.13.2)

Manual operation of circuit-breakers and RCDs to prove disconnection (612.13.2)

Correct identification of circuit details and protective devices (514.8.1; 514.9.1)

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

DISTRIBUTOR'S / SUPPLY INTAKE EQUIPMENT

AUTOMATIC DISCONNECTION OF SUPPLY

4.0

OTHER METHODS OF PROTECTION

3.1.3

3.1.4

3.1.5

Confirmation of earthing conductor size (542.3; 543.1.1)

Accessibility and condition of earthing conductor at MET (543.3.2)

Plugs, sockets-outlets and the like not interchangeable with those of other systems within the

premises (411.8.5)

Adequacy of source (411.8.4)

Condition of enclosure(s) in terms of IP rating etc (416.2)

4.1

4.2

4.3

5.3

5.6

Master:110008985

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

5.0 OutcomeFurther

investigation

√ No

√ No

√ No

√ No

√ No

√ No

C3 (see section K) No

√ No

6.0 OutcomeFurther

investigation

√ No

√ No

√ No

√ No

√ No

√ No

√ No

√ No

√ No

√ No

C2 (see section K) No

√ No

√ No

6.14

N/V No

√ No

C3 (see section K) No

6.15

C2 (see section K) No

C3 (see section K) No

6.16

√ No

√ No

√ No

√ No

N/V No

N/V No

√ No

√ No

√ No

C2 (see section K) No

√ No

7.0 OutcomeFurther

investigation

7.1

√ No

√ No

√ No

√ No

√ No

N/A No

Isolators (537.2)

Temperature rating of cable insulation (522.1.1; Table 52.1)

Clearly identified by position and / or durable marking (537.2.2.6)

7.1.1

Acceptable location - if local or remote from equipment in question (537.2.1.5)

Presence and condition of appropriate devices for isolation (537.2.2)

General condition of wiring systems.

Suitability of circuit accessories for external influences (512.2)

ISOLATION AND SWITCHING

Condition of circuit accessories (Section 416)

Capable of being secured in the OFF position (537.2.1.2)

7.1.2

Provision of additional protection by 30mAmp RCD

6.15.2 For all socket outlets of 20 Amp or less provided for use by ordinary people. (411.3.3 (i))

Adequacy of connection at point of entry to enclosure (gland, bush or similar) (522.8)

6.16.2

7.1.6

7.1.5

7.1.4

Warning label posted in situations where live parts cannot be isolated by the operation of a single

device (514.11.1; 537.2.1.3)

Correct operation verified (612.13.2)

6.23

Suitability of containment systems for continued use (including flexible conduit) (Section 522)

Non-sheathed cables protected by enclosure in conduit, ducting or trunking (521.10.1)

Cables segregated / separated from non-electrical services (528.3)

Band II cables segregated Separated from Band I cables (528.1)

Cable installation methods / practices with regard to the type and nature of installation and

external influences (Section 522)

Cables concealed under floors, above ceilings, in walls / partitions less than 50 mm from a surface, and in partitions containing

metal parts.6.14.1

6.15.1

6.18

Connections under undue strain (522.8)

6.7

6.14.2

Coordination between conductors and overload protective devices (433.1; 533.2.1)

6.10

6.11

6.8

6.9

Adequacy of cables for current-carrying capacity with regard for the type and nature of installation

(Section 523)

Examination of cables for signs of unacceptable thermal or mechanical damage / deterioration

(421.1; 522.6.1)

Adequacy of protective devices: type and rated current for fault protection (Section 434)

Provision of additional protection by 30mAmp RCD (522.6.101; 522.6.103)

6.20

6.17 Provision of fire barriers, sealing arrangements and protection against thermal effects (Section

Where reasonably likely to be used to supply mobile equipment outdoors. (411.3.3 (ii))

Incorporating earthed armour or sheath, or run within earthed wiring system. or otherwise

protected against mechanical damage by nails, screws and the like (see Section D. Extent and

limitations) (522.6.101; 522.6.103) or

Installed in prescribed zones (see Section D. Extent and limitations) (522.6.101) or

Where exposed to direct sunlight, cable of a suitable type (522.11.1)

6.22

The basic insulation of a conductor visible outside an enclosure. (526.2)

6.21

Presence and adequacy of circuit protective conductors (411.3.1.1; 543.1)

6.19

6.12

6.13

6.14.3

Termination of cables at enclosures

6.16.3 Connections of live conductors adequately enclosed. (416.1)

6.16.4

6.2

6.5

7.1.3

6.16.1

5.23

Condition of insulation of live parts (416.1)

Adequacy / security of barriers (416.2)

Identification of conductors (514.3.1)

5.24

5.20

5.21

6.1

5.22

5.17

5.18

5.19

CONSUMER UNITS / DISTRIBUTION BOARDS Continued.

6.4

6.6

6.3 Condition of insulation of live parts (416.1)

Cables correctly supported throughout their run (522.8.5)

Confirmation that integral test button / switch causes RCD(s) to trip when operated (functional

check) (612.13.1)

Presence of diagrams, charts or schedules at or near equipment, where required (514.9.1)

Correct identification of circuit protective devices (533.1)

Protection against electromagnetic effects where cables enter consumer unit / distribution board /

enclosures (521.5.1)

RCD(s) provided for fault protection – includes RCBOs (411.4.9; 411.5.2; 531.2)

RCD(s) provided for additional protection - includes RCBOs (411.3.3; 415.1)

MAIN DISTRIBUTION & FINAL CIRCUITS

Cables correctly terminated in enclosures (Section 526)

Master:110008985

INSPECTION SCHEDULE FOR DISTRIBUTION BOARDS AND CIRCUITS

7.0 OutcomeFurther

investigation

7.2

√ No

√ No

√ No

√ No

√ No

7.3

N/A No

N/A No

N/A No

N/A No

7.4

√ No

√ No

8.0 OutcomeFurther

investigation

C2 (see section K) No

√ No

√ No

√ No

C3 (see section K) No

8.6

N/A No

N/A No

N/A No

N/A No

9.0 OutcomeFurther

investigation

C3 (see section K) No

N/A No

N/A No

N/V No

√ No

√ No

√ No

√ No

10.0 OutcomeFurther

investigation

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

N/A No

7.4.1

Clearly identified by position and / or durable marking (537.4.2.7)

Correct operation Verified (537.4.2.6)

Readily accessible for operation where danger might occur (537.4.2.5)

Presence and condition of appropriate devices (537.4.1.1)

7.3.4

7.3.3

10.15

8.3

8.4

8.5

Floor and ceiling heating systems (753)

Temporary electrical installations for structures, amusement devices and booths at fairgrounds,

amusement parks and circuses. (740)

Operating and maintenance gangways (729)

Electrical installations in caravans and motor caravans (721)

Mobile or transportable units (717)

Solar photovoltaic (PV) power supply systems (712)

10.5

10.4

10.3

10.2

10.1

Construction and demolition site installations (704)

Emergency switching / stopping (537.4)

No signs of overheating to surrounding building fabric (559.5.1)

Correct operation verified (537.5.1.3; 537.5.2.2)

Presence and condition of appropriate devices (537.5.1.1)

8.6.4

8.6.3

8.6.2

Presence and condition of appropriate devices (537.3.1.1)

CURRENT-USING EQUIPMENT (PERMANENTLY CONNECTED)

7.2.5 Clearly identified by position and / or durable marking (537.2.2.6)

Correct operation verified (612.13.2)

Capable of being secured in the OFF position (537.3.2.3)

Condition of equipment in terms of IP rating etc (416.1)

Equipment dose not constitute a fire hazard (Section 421)

Enclosure not damaged deteriorated so as to impair safety (Section 416)

Suitability for the environment and external influences (512.2)

Installed to minimize build-up of heat by use of "fire rated" fittings. Insulation displacement box or

similar. Cable entry holes in ceiling above luminaries, sized or sealed so as to restrict the spread

of fire: (421.1.1)

Recessed luminaries (down lighters)

Correct type of lamps fitted (559.4.1)

Security of fixing (416.2.3)

7.4.2

8.6.1

8.2

ADDITIONAL INSPECTION FOR APPLICABLE SPECIAL LOCATIONS

Exhibitions, shows and stands (711)

Medical locations (710)

Marinas and similar locations (709)

Electrical installations in caravan . Camping parks and similar locations (708)

Conducting locations with restricted movement (706)

Agricultural and horticultural premises (705)

Rooms and cabins containing sauna heaters (703)

Swimming pools and other basins (702)

10.6

Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5)

9.3 Shaver sockets comply with BS EN 61558-2-5 formally BS 3535 (701.512.3)

Low Voltage (e.g.230 volts) socket outlets at least 3m fromZone 1 (701.512.3)

No signs of overheating to conductors / terminations (526.1)

7.2.4

7.2.3

Acceptable location / Clearly identified by position and or durable marking (537.3.2.4)

10.8

10.7

9.4 Presence of supplementary bonding conductors, unless not required by BS 7671:2008

(701.415.2)9.5

LOCATION(S) CONTAINING A BATH OR SHOWER

8.1

7.2.1

9.6 Suitability of equipment for external influences for installed location in terms of IP rating

(701.512.2)9.7 Suitability of equipment for installation in a particular zone (701.512.3)

9.8 Suitability of current-using equipment for particular position within the location (701.55)

9.1 Additional protection for all low voltage (LV) circuits by RCD not exceeding 30mA (701.411.3.3)

9.2

10.14

10.13

10.12

10.11

10.10

10.9

7.3.2

7.3.1

Functional switching (537.5)

Switching off for mechanical maintenance (537.3)

7.2.2

ISOLATION AND SWITCHING Continued.

C1 - Danger present. Risk of injury. Immediate remedial action required

C2 - Potentially dangerous - urgent remedial action required

C3 - Improvement recommended

DB ReferenceMake & Model

(if applicable)Circuit Designation / Location Observation / Regulation Code

Further

Investigation

Required

1

All Cooker

control units

with socket

N/AAll Cooker control units with

socket

RCD protection shall be provided for socket outlets not exceeding 20

Amp intended for use by ordinary people. Reg 411.3.3 (i)C3 No

2 DB GFFDorman

SmithCircuits 2,3&4

RCD protection shall be provided for socket outlets not exceeding 20

Amp intended for use by ordinary people. Reg 411.3.3 (i)C3 No

3 DB GFFDorman

SmithCircuit 7 Laundry

No IP2X protection (>12mm hole) on the bottom surface of Light

Switch. Reg 416.1 & 416.2.1C2 No

4 DB GFFDorman

SmithCircuit 7 Hall Light

The diffuser is missing from the light fitting exposing live parts. Reg

559.10.5.2 & 416.1C2 No

5 DB Stair L&PDorman

SmithCircuit 4-Fire Alarm supply

Cables that are concealed within the wall not run in an earthed wiring

system and have no additional protection against nails; should be RCD

protected. Reg 522.6.101 - 522.6.103

C3 No

6 DB Stair L&PDorman

SmithCircuits 2&3

RCD protection shall be provided for socket outlets not exceeding 20

Amp intended for use by ordinary people. Reg 411.3.3 (i)C3 No

7 DB Stair L&PDorman

SmithCircuits 2&3

RCD protection shall be provided for socket outlets that could

potentially be used to supply portable appliances outside. Reg 411.3.3

(ii)

C2 No

8 DB Stair L&PDorman

SmithCircuit 6-Tank Room

The diffuser is missing from the light fitting exposing live parts. Reg

559.10.5.2 & 416.1C2 No

9 DB A HagerCircuit 2-Shaver Light Room

4

No IP4X protection (>1mm hole) on the top surface of Shaver Light.

Reg 416.2.2C2 No

10 DB A Hager Circuit 2-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

11 DB B Hager Circuit 7-Sockets Room 7 Damaged Back Box.Surface Back Box Cracked . Reg 416.2 C2 No

0

Description Outcome

10

Section K: Observations

Ite

m N

o

Master:110008985

One of the following codes, as appropriate, has been allocated to each of the observations made above to indicate to the person(s) responsible for the

installation the degree of urgency for remedial action.

13

DB ReferenceMake & Model

(if applicable)Circuit Designation / Location Observation / Regulation Code

Further

Investigation

Required

Description Outcome

Ite

m N

o

Master:110008985

12 DB B Hager Circuit 3Multiple circuits in the over current protective device. Reg 314.4 &

521.8.2C3 No

13 DB B Hager Circuit 2No IP2X protection (>12mm hole) on the bottom surface of Light

Switch. Reg 416.2.1C2 No

14 DB B Hager Circuit 3No IP2X protection (>12mm hole) on the bottom surface of Light

Switch. Reg 416.2.1C2 No

15 DB B Hager Circuit 2-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

16 DB C Hager Circuit 3-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

17 DB D Hager Circuit 3-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

18 DB E Hager Circuit 2-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

19 DB F Hager Circuit 3-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

20 DB G Hager Circuit 2-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

21 DB H Hager Circuit 2-BathroomAll circuits that terminate within an area containing a shower/bath

should be protected by RCD`s Reg 701.411.3.3C3 No

22 All DB's N/A N/AUnable to locate and verify the Main Protective Bonding Conductor is

present at the main incoming Water service. Reg 411.3.1.2 & 544.1C2 No

23

DB-Main

Section

Board

Dorman

SmithCircuit 1/TP

Over rated over current protective device in relation to the current

carrying capacity of the connected cables. 10mm SWA/PVC/SWA on

60A MCCB. Reg 433.1.1

C2 No