differential relays - siemens

10
Differential Relays Siemens LSA 2.2.1 . March 1997 1 Application The 7SD502 line differential protection is a fast and selective differential protection unit for cables and overhead lines. It is the successor of the 7SD22 and 7SD76 static differential protection. Com- bination with 7SD76 or 7SD22 is not pos- sible, i.e. 7SD502s must be used at both ends of the line. The connection between 7SD502s is made via a balanced pair of pilot–wires, i.e. existing pilot–wire con- nections can be used. Design Within its compact dimensions the unit contains all components for analog value acquisition and evaluation, the summa- tion current transformer, the pilot–wire trimming resistors, the operating and dis- play panel, the indication and command outputs, binary inputs and the auxiliary voltage converter. The unit can be supplied in two different housings. The one for flush mounting in a panel or cubicle has connections at the rear. The other for surface mounting on a panel has screw terminals accessible from the front. Method of operation The summation current transformer inte- grated in the housing of the 7SD502 per- mits the connection of any secondary currents of the primary current trans- former (see Fig. 2). The three primary windings of the summation current trans- former have the winding ratio 2 : 1 : 3. With 1 x I N as the three–phase, balanced short–circuit current, the secondary single–phase current I M1 of the summa- tion current transformer is 20 mA. The summation current transformer principle gives different short–circuit sensitivities depending on the connection, e.g. differ- ent weightings can be assigned to the earth fault. The 7SD502 acquires the secondary pul- sating current I M1 of its own substation, the current I a via the pilot–wires and the current I b in the trimming resistor R b . The pulsating current I M2 of the remote sta- tion is calculated from these quantities. With three–end protection, the boosting current I boo is acquired at the third line end and included in the calculation. The line is shut down if the protection system finds that the differential current I diff obtained by adding I M1 and I M2 indi- cates a short–circuit in the protection zone. Digital measured–value processing with consistent evaluation of the fundamental of the measured quantities largely elimi- nates the influence of high frequency transient phenomena, transient DC com- ponents and differing current transformer saturation. Features D Selective short–circuit protection for overhead lines and cables D Acquisition of pulsating current behind the summation current transformer and of currents via the pair of pilot– wires D Sensitivity to single–phase faults un- der rated current D 100 % protection against all types of short–circuit within the protection zone D Circuit–breaker intertripping and re- mote tripping of the remote station D Integrated pilot–wire monitoring D Software–controlled adaptation of the sensitivity of the differential protection to different wire resistances. This makes pilot–wire trimming unneces- sary D Overload protection with thermal char- acteristic D Two–stage definite–time/dependent time overcurrent protection as standby D Real–time clock and permanently stored status and fault indications in the event of auxiliary voltage failure. VDEW/ZVEI interface to the control system D Protection of three–end pilot–wires with two devices at each end of the line is possible. 7SD502 Line differential protection with two pilot–wires Fig. 1 7SD502 line differential protection 49 50 87 Scope of functions Siemens AG 1997 e

Upload: khangminh22

Post on 26-Jan-2023

4 views

Category:

Documents


0 download

TRANSCRIPT

Differential Relays

Siemens LSA 2.2.1 . March 1997 1

Application

The 7SD502 line differential protection isa fast and selective differential protectionunit for cables and overhead lines.It is the successor of the 7SD22 and7SD76 static differential protection. Com-bination with 7SD76 or 7SD22 is not pos-sible, i.e. 7SD502s must be used at bothends of the line. The connection between7SD502s is made via a balanced pair ofpilot–wires, i.e. existing pilot–wire con-nections can be used.

Design

Within its compact dimensions the unitcontains all components for analog valueacquisition and evaluation, the summa-tion current transformer, the pilot–wiretrimming resistors, the operating and dis-play panel, the indication and commandoutputs, binary inputs and the auxiliaryvoltage converter.The unit can be supplied in two differenthousings. The one for flush mounting in apanel or cubicle has connections at therear. The other for surface mounting on apanel has screw terminals accessiblefrom the front.

Method of operation

The summation current transformer inte-grated in the housing of the 7SD502 per-mits the connection of any secondarycurrents of the primary current trans-former (see Fig. 2). The three primarywindings of the summation current trans-former have the winding ratio 2 :1 :3.With 1 x �N as the three–phase, balancedshort–circuit current, the secondarysingle–phase current �M1 of the summa-tion current transformer is 20 mA. Thesummation current transformer principlegives different short–circuit sensitivitiesdepending on the connection, e.g. differ-ent weightings can be assigned to theearth fault.The 7SD502 acquires the secondary pul-sating current �M1 of its own substation,the current �a via the pilot–wires and thecurrent �b in the trimming resistor Rb. Thepulsating current �M2 of the remote sta-tion is calculated from these quantities.With three–end protection, the boostingcurrent �boo is acquired at the third lineend and included in the calculation.The line is shut down if the protectionsystem finds that the differential current�diff obtained by adding �M1 and �M2 indi-cates a short–circuit in the protectionzone.Digital measured–value processing withconsistent evaluation of the fundamentalof the measured quantities largely elimi-nates the influence of high frequencytransient phenomena, transient DC com-ponents and differing current transformersaturation.

Features

� Selective short–circuit protection foroverhead lines and cables

� Acquisition of pulsating current behindthe summation current transformerand of currents via the pair of pilot–wires

� Sensitivity to single–phase faults un-der rated current

� 100 % protection against all types ofshort–circuit within the protection zone

� Circuit–breaker intertripping and re-mote tripping of the remote station

� Integrated pilot–wire monitoring� Software–controlled adaptation of the

sensitivity of the differential protectionto different wire resistances. Thismakes pilot–wire trimming unneces-sary

� Overload protection with thermal char-acteristic

� Two–stage definite–time/dependenttime overcurrent protection as standby

� Real–time clock and permanentlystored status and fault indications inthe event of auxiliary voltage failure.VDEW/ZVEI interface to the controlsystem

� Protection of three–end pilot–wireswith two devices at each end of theline is possible.

7SD502 Line differential protection with two pilot–wires

Fig. 17SD502 line differential protection

49

50

87

Scope of functions

Siemens AG 1997�

Differential Relays

Siemens LSA 2.2.1 . March 19972

Serial interfaces

The device is equipped with two serialinterfaces.The operating interface on the front panelis suitable for the connection of aWINDOWS capable PC. The DIGSI oper-ating and analysis software allows easysetting, fault recording evaluation andcommissioning. The system interface isan 820 nm fibre–optic interface for linkingto the SINAUT LSA substation controland protection system or a protectionmaster unit (protocol to IEC 870–5–103recommendation). The operator withDIGSI can also be connected to the sys-tem interface.

Parameter setting

Using the integrated operating and dis-play panel or a PC all parameter settingscan be made under user guidance. Theparameters are written to a non–volatilememory so that they are retained evenafter the supply voltage has beenswitched off.

Self–monitoring

The hardware and software areconstantly monitored and irregularitiesare detected and signalled immediately.This considerably enhances safety, reli-ability and availability.

Differential protection for lines andcables

The differential protection of the 7SD502contains the following functions:� The summation current transformer

principle makes the sensitivity depen-dent on the type of error. Single–phaseerrors are dealt with higher priority andweighted with higher sensitivity be-cause of the dimensioning of thesummation current transformer.

� For differential protection, an overcur-rent enable can be parameterized. Theclose/open command of the differen-tial protection is only given when asettable value for the pulsating current�M1 is exceeded.

� Response characteristic for three–phase, balanced short–circuit currentas shown in Fig. 3. The response value�diff> and the gradient of the character-istic branches are parameterizable.

� Calculated compensation of the pilot–wire capacity.

� High stability with different currenttransformer saturations during an ex-ternal short–circuit because of the useof an integrated saturation detector.

� Insensitive to DC components andhigh–frequency transient phenomenabecause the fundamental is filteredout of the measured quantities usingdigital filters.

Pilot–wire connection to remote sta-tion/pilot–wire monitoring

The connection to the remote station ismade using a balanced pair of wires (e.g.telephone wires). The pilot–wire connec-tion is part of the differential protection.For this reason the pilot–wires areconstantly monitored by a pilot–wiremonitoring function integrated into the7SD502. To achieve this, 2 kHz pulseswith a defined pulse width ratio are trans-mitted to the remote station via the pilot–wires. The pulse length and pulse levelare evaluated using a filter processor so

that any break in the pilot–wire is de-tected reliably. Both stations have thesame priority and alternate betweenfunctioning as a sender and receiver.

7SD502 Line differential protection with two pilot–wires

Fig. 2Connection principle of the 7SD502

2

L2L1

1

3

L3

Ra

Rb

Ia

IM1

Ib

I1

Summation current transformer

Pilot–wire connec-tion to the otherstation

Fig. 37SD502 line differential protection

1 2 3 4 5 �stab

�N

1

2

3

4

�diff

�N

Normalizeddifferential current

Normalizedstabilization current

Fault characteristicwith single–end infeed

Tripping

Blocking

�Diff>m1

m2

Differential Relays

Siemens LSA 2.2.1 . March 1997 3

Circuit–breaker intertripping and re-mote tripping

It is possible to open the circuit–breakerat the other end if the infeed conditionsat that end are weak. Remote trippingcan also be initiated by a circuit–breakerstandby protection relay or transformerdifferential protection relay linked via abinary input.For both functions the integrated pilot–wire monitoring function is required. Itworks in both directions, but not at thesame time.

Thermal overload protection

Thermal overload protection with a pre–warning stage is integrated for the ther-mal protection of cables. It functions withpulsating current acquired behind thesummation current transformer. This pul-sating current is an image of the three–phase balanced load in normal or over-load operation.The tripping time characteristics (seeFig. 4) are exponential functions to IEC255–8 and they take account of heat lossdue to the service current and the ac-companying drop in temperature of thecooling medium. The previous load istherefore taken into account in the trip-ping time on overload. A settable warningstage can output a current or tempera-ture–dependent indication before the trip-ping point is reached.

Standby overcurrent–time protection

An overcurrent–time protection is usedas standby protection with a choice ofdefinite–time or inverse–time characteris-tics. The protection has two stages, i.e.an overcurrent stage (�>) and a high–cur-rent stage (�>>). The high–current stagealways has a definite–time characteristic.Both stages can be disabled via a binaryinput. The response value of the standbyprotection is derived from the pulsatingquantity so that there are different re-sponse values depending on the fault.

Fault recording

The digital measured values of the pul-sating current of the local station, of theremote station, and of the second remotestation in a three–ended pilot–wirescheme are stored along with the differ-ential and stabilization current in theevent of a fault. The current progressionscan either be directly transferred to a PCor read out by the SINAUT LSA stationcontrol system. If the VDEW/ZVEI inter-face to the control system is used, up toeight fault recordings are stored. Thefault recording buffer is a circulatingbuffer with a maximum length so that theoldest fault recordings are overwritten ifa further network fault occurs after thebuffer is full.

Indications

The 7SD502 unit provides detailed datafor the analysis of faults and for checkingstatuses. All the following indications arebacked up against supply voltage failure.� Clock time

As a standard a battery–backed clockis used that can be synchronized via abinary input or the system interface. Adate and time is assigned to all indica-tions.

� Fault indicationsFault indications are available for faultsstored in the unit.

� Status indicationAll indications that are not directly re-lated to a fault are stored in the statusindication buffer.

Marshallable command and alarmrelay, LEDs, binary inputs

All input/output relays including the LEDsare user–specific and can be marshalledindependently. Several events can be pro-grammed simultaneously on one input/output relay.

Commissioning

The following commissioning aids areprovided:� Display of pulsating currents the differ-

ential and stabilization current with ab-solute value and phase.

� Software–controlled level alignment ofthe pilot–wire monitoring function andtesting of the circuit–breaker intertrip-ping and remote tripping commandfunctions.

� Measuring of the loop–resistance andcapacity of the pilot–wires.

7SD502 Line differential protection with two pilot–wires

Fig. 4Tripping time characteristics of the overload protection function

t (min) t (min)

100

50

20

10

5

3

2

1

0.5

0.3

0.2

0.1

0.05

0.03

1000

500

100

50

10

5

1

1000

500

100

50

1051�M1

k · �N

1085431

with 90 % previous load

Parameter:set value time constant �� (min)

Parameter:set valuetime constant � (min)

�M1k · �N

100

50

20

10

5

3

2

1

0.5

0.3

0.2

0.1

0.05

0.031085431

without previous load

2 2

Differential Relays

Siemens LSA 2.2.1 . March 19974

Technical data

Input circuits Rated current �N

Rated frequency fN, settableMaximum load of current inputs thermal continuous

�10 s� 1 s

dynamic half–wave

1 or 5 A50 or 60 Hz4 x �N20 x �N100 x �N250 x �N

Auxiliary DC voltage Rated auxiliary voltage Vaux

Permissible range of the rated auxiliary voltage

Permissible maximum ripple at rated auxiliary voltagePower consumption not energized

energizedStored energy time at Vaux �110 V

24, 48 V or60, 110, 125 V or220, 250 V19 to 56 V48 to 144 V176 to 288 V�12 %approx. 9 Wapprox. 10.5 W�50 ms

Binary inputs Marshallable 7SD502DC operating voltageCurrent consumption

2/4 with/without pilot–wire monitoring24 to 250 Vapprox. 2.5 mA

Alarm contacts Number of alarm relays 7SD502 marshallableContacts per relayMaking/breaking powerSwitching voltagePermissible current

5See connection diagrams20 W/VA250 V AC/DC1 A

Command contacts Number of tripping relays 7SD502 marshallableContacts per relayMaking powerBreaking powerSwitching voltagePermissible current continuous

0.5 s

2/4 with/without pilot–wire monitoringSee dimension drawings1000 W/VA30 W/VA250 V AC/DC5 A30 A

LEDs Ready display greenFault display redMarshallable LEDs 7SD502 red

116

Design Housing, dimensionsTerminals Panel/cubicle flush mounting

Panel surface mountingDegree of protection to EN 60 529

7XP20, see dimension drawingscrimp–connectionstwo–tier screw terminalsIP51

Serial interfaces Operating interface V.24 (RS232C)

System interfaceProtocolSafetyTransmission rateMethodConnection of fibre–optic cables

Optical wavelengthPermissible path attenuationDistance

Front connector, not isolated, 25–pin,suitable for connection of a PCIsolated, for connecting to a central unitDIN 19 244 or IEC 870–5–103Hamming distance d = 44 800, 9 600 or 19 000 BdAsynchronousTwo integrated FSMA plug connectors forfibre–optic connection820 nmmax. 8 dB with glass fibre 62.5/125 �mmax. 1.5 km at 3 dB system reserve

CE–conformity, standards This product is in conformity with the directives of the Council ofthe European Communities on the approximation of the laws ofthe Member States relating to the electromagnetic compatibility(EMC Council Directive 89/336/EEC) and concerning electricalequipment for use within specified voltage limits (low–voltagedirective 73/23/EEC). The product conforms with the internationalstandard IEC 255 and the national standard DIN 57 435 part 303(corresponding to VDE 0435 part 303).The relay is designed for use in an industrial environment, forinstallation in standard relay rooms and compartments so thatwith proper installation electro–magnetic compatibility (EMC) isensured.

Conformity is proved by tests performedby Siemens AG in line with article 10 of theCouncil Directives in accordance with thegeneric standards EN 50081 and EN 50082for the EMC directive 89/336/EEC andstandard 60255–6 for the low–voltage di-rective.

Insulation tests

IEC 255–5, DIN 57 435 part 303High–voltage test (routine test), except d.c. voltage supply inputHigh–voltage test (routine test), only d.c. voltage supply inputImpulse voltage test (type test), all circuits, class III

2 kV (rms), 50 Hz2.8 kV DC5 kV (peak), 1.2/50 �s, 0.5 J,3 positive and 3 negative shots at intervalsof 5 s

7SD502 Line differential protection with two pilot–wires

Differential Relays

Siemens LSA 2.2.1 . March 1997 5

Technical data (continued)

EMC–tests; immunity (type test)

Standards: IEC 255–6, IEC 255–22(international product standard)EN 50082–2 (generic standard)VDE 0435 part 303 (Germanproduct standard)

High frequency test with 1 MHz interferenceIEC 255–22–1, class III and VDE 0435 part 303, class IIIElectrostatic dischargeIEC 255–22–2, class III and IEC 1000–4–2, class IIIRadio–frequency electromagnetic field, non–modulatedreport IEC 255–22–3, class IIIRadio–frequency electromagnetic field, amplitude modulatedIEC 1000–4–3, class IIIRadio–frequency electromagnetic field, puls modulatedENV 50204, class IIIFast transientsIEC 255–22–4 class III, IEC 1000–4–4 class III

Conducted disturbances induced by radio–frequency fields, amplitude modulatedIEC 1000–4–6, class IIIPower frequency magnetic fieldIEC 1000–4–8, class IVIEC 255–6

2.5 kV (peak), 1 MHz, � = 15 �s,400 shots/s, duration 2 s4 / 6 kV contact discharge, 8 kV air dis-charge, both polarities, 150 pF, Rl = 330 �

10 V/m, 27 to 500 MHz

10 V/m, 80 to 1 000 MHz, AM 80 %, 1 kHz,

10 V/m, 900 MHz, repetition frequency 200 Hz, duty cycle 50 %2 kV, 5/50 ns, 5 kHz, burst length = 15 ms,repetition rate 300 ms, both polarities, Rl = 50 ��� duration 1 min10 V, 150 kHz to 80 MHz, AM 80 %, 1 kHz

30 A /m, continuous, 300 A /m for 3 s, 50 Hz0.5 mT; 50 Hz

EMC–tests; emission (type test)

Standard: EN 50081–* (European generic standard)

Conducted interference voltage, auxiliary voltageCISPR 22, EN 55022 and VDE 0878 part 22Interference field strength CISPR 11, EN 55011 and VDE 0875 part 11

150 kHz to 30 MHz, class B

30 to 1 000 MHz, class A

Climatic stress tests permissible ambient temperature during serviceduring storageduring transport

permissible humidity

–5 to +55 °C–25 to +55 °C–25 to +70 °Cmean value per year �75 % relative humi-dity, on 30 days per year up to 95 % rela-tive humidity, condensation not permissible

Mechanical stress testsIEC 255–21–1, IEC 68–2

permissible mechanical stress during service

during transport

10 to 60 Hz, 0,035 mm amplitude60 to 500 Hz, 0,5 g acceleration5 to 8 Hz, 7,5 mm amplitude8 to 500 Hz, 2 g acceleration

Current differential protection Setting rangesResponse value �diff>/�N

TimesResponse times (double–end infeed)at � = 4 x set value �diff>/�N at � = 10 x set value �diff>/�N Additional time delay of the tripping commandMinimum command duration

Release value �diff>/�N

Tolerance of the response characteristics (stationary, single–endinfeed)Frequency range fN = 50 Hz

fN = 60 Hz

0.5 to 2.5 (step 0.01)

approx. 23 to 33 msapprox. 16 to 26 ms0 to 60 s (step 0.01 s)0.05 to 32 s (step 0.01 s)approx. 0.9 x set value�5 % from set value + 0.7 %/km pilot–wire45 to 55 Hz55 to 65 Hz

Overload protection Setting rangesFactor k to IEC 255.8 Step 0.01Time constant � Step 0.1 minTemperature warning stage �alarm/�trip Tripping temp.Current warning stage �alarm

1 to 51 to 999.9 min50 to 100 %�alarm � �max = k � �N

Tripping time characteristic t � �Ig�2 – �2

pre

�2 – (k � �N)2

Release conditions

Tolerances

�/�alarm approx. 0.99�/�trip approx. 0.99�/�alarm approx. 0.99Class 10 % to IEC

Pilot–wire Permissible range of loop resistancePermissible range of pilot–wire capacity

max. 2 000 �max. 1200 nF

Pilot–wire monitoring Pulse–code modulated 2 kHz send currentMax. send levelMin. receive level

8 mA = 100 %0.1 mA

7SD502 Line differential protection with two pilot–wires

Differential Relays

Siemens LSA 2.2.1 . March 19976

Technical data (continued)

Setting ranges

Overcurrent protection definite–time

Overcurrent pulsating current �M1>

High current pulsating current �M1>>

Delay timesTolerances

Response value for currentTiming intervalRelease time

�n1/�N = 0.1 to 30�n1/�N = 0.1 to 300 to 32 s or inactive

�5 % from set value�1 % or �10 msapprox. 30 ms

Overcurrent protection inverse–time Overcurrent pulsating current �M1>

Time multiplier tpEnergizing thresholdCharacteristic to IEC 255–4, Section 3.5.2 or BS 142Linear measuring rangeTolerances

Energizing thresholdTime interval

�p/�N = 0.1 to 200.05 to 32 s6.0 x �p

Normal, strong or extremely dependent40 x �N

�5 %�5 % for 2 (�/�p>) �20 and tp = 1 or 30 ms

Measurement Operating currentsMeasuring rangeTolerances

Overload protection valuesWinding temperatureMeasuring rangeTolerances

�M1, �M2, �M3, �diff, �stab

0 to 240 % �N

�2 % from rated value + 1 % /km pilot–wire

�/�trip calculated0 to 240 %�3 % with respect to �trip

Fault logging Fault indication Storage of the last 8 faults

Fault recording Line currents (instantaneous values)Time resolution of the instantaneous values

Max. number of recordingsSignal start

�M1, �M2, �M3, �diff, �stab

1.66 at fN = 50 Hz1.39 at fN = 60 Hz8 in 19 s recording bufferEnergizing, PC/LSA operation, tripping,binary input

7SD502 Line differential protection with two pilot–wires

Differential Relays

Siemens LSA 2.2.1 . March 1997 7

Selection and ordering data

Order No.7SD502 numerical two pilot–wire differential protection 7SD502 � – � � A 1 1 – 0 � A 0

Rated current, 50 to 60 Hz1 A5 A

15

Rated auxiliary voltage24, 48 V DC60, 110, 125 V DC220, 250 V DC

245

ConstructionHousing 7XP2040 for panel surface mountingHousing 7XP2040 for panel and cubicle flush mountingHousing 7XP2040 for panel and cubicle flush mounting (without glass cover)

BCE

Integrated pilot–wire monitoring/CB intertrippingwith

11

Serial system interfacewithoutwith

AC

Operation software (German and English are standard, other languages on request)

DIGSI program (suitable for all protection relays 7UM..., 7UT..., 7SJ..., 7SA..., ...) GermanEnglish

Test version: GermanEnglish

Connecting cables for protection relays (25-pin) – PC (9-pin); (other variations supplied on request)

7XS5020–0AA007XS5020–1AA00

7XS5021–0AA007XS5021–1AA00

7XV5100–2

Documentation

German: Katalogblatt LSA 2.2.1: Leitungsdifferentialschutz 7SD502 mit zwei HilfsadernHandbuch: Leitungsdifferentialschutz 7SD502 (V 3.0) mit zwei Hilfsadern

E50001–K5722–A111–A2C53000–G1100–C95–3

English: Catalog LSA 2.2.1: 7SD502 Line differential protection with two pilot–wiresManual: 7SD502 Line differential protection with two pilot–wires

E50001–K5722–A111–A2–7600C53000–G1176–C95–2

7SD502 Line differential protection with two pilot–wires

Differential Relays

Siemens LSA 2.2.1 . March 19978

7SD502 Line differential protection with two pilot–wires

Fig. 5Connection diagram of 7SD502 (with wiring as set in factory)

Summation current transformer

56

34

12

13

3132

12

11

60616263

10

1516

87868584

26

7

89

M1: Device: OPEN

M2: Diff. energization

M3: Spare generalenergization

M4: Fault wire

K1: General energization

K2: OPEN command

K3:

K4:

LSA FO connection

M5: Device ready

6968

7574

67969594939291727170

73

182021

2224252347495048

1943454644

==

FO interfaceLink with the general

equipment

Iboo

Ib

Ia

I1

B�2: LED Ack.

B�1: Connect.

Power SUPPLY

Itrans

Ireceive

+–

Pilot–wire monitoring

U2

1

3

Cblock

B�4: Remote OPEN

B�3: Differential protection blockscommand relay

L+

L+

L+

L+

1C1

2F12F21F11F22E12E21E1

1E2

4C14C23C13C22C12C2

4D1

1D21D31D4

4D2

5C

1E4

1D1

1C2

2A12A2

6A16A26A36A4

1A21A1

4A34A4

8D18D28D37D17D27D36D16D26D35D15D25D37D48D46D4

8C18C38C48C27C17C37C47C2

8A18A38A48A27A17A37A47A2

5CFOFO

Pilot–wire connection

Rb

Ra1E3

(Option)

Version for panel flush mounting/cubicle mounting

Version for panel surface mounting

Differential Relays

Siemens LSA 2.2.1 . March 1997 9

Dimension drawings in mm

Fig. 67SD502 with housing 7XP2040–2 (for panel flush mounting or cubicle mounting)

Front view Side view Panel cutout

206.5180

221

7.313.2

255.

8

245

266

231.5

30 29.5

1.5

5.4

225

220

244

172

10

Fibre–opticinterface

Diam. 5 or M4

Diam. 6

Fig. 77SD502 with housing 7XP2040–1 (for panel surface mounting)

Front view Side view

260

27 29.5

266

71Z

280

344

234

219

Fibre–optic interface

126

1.5

10051 75

5025

76

7.5

. . . . .

. . . . .

. . . . .. . . . .

Diam. 9

Detail Z:

Differential Relays

Siemens LSA 2.2.1 . March 199710

Conditions of Sale and Delivery

Subject to theGeneral Conditions of Supply and Deliveryfor Products and Services of theElectrical and Electronic Industryand to any other conditions agreed uponwith the recipients of catalogs.

The technical data, dimensions and weights are subject to change unlessotherwise stated on the individual pagesof this catalog.

The illustrations are for reference only.

We reserve the right to adjust the pricesand shall charge the price applying onthe date of delivery.

Export Regulations

In accordance with present provisions ofthe German Export List and the US Com-mercial Control List, export licences arenot required for the products listed in thiscatalog.

An export licence may however be requi-red due to country–specific application ofthe products.

Relevant are the criteria stated in the de-livery note and the invoice.

Subject to change without notice.

Trademarks

All product designations used are trade-marks or product names of Siemens AGor of other suppliers.

Dimensions

All dimensions in this catalog are given inmm.

Siemens online!

The Power Transmission and DistributionGroup can also be found in the Internet:

http://www.ev.siemens.de

Responsible for

Technical contents: Claus Wagner,Siemens AG, EV S V13, Nürnberg

General editing: Roland Reichel/Claudia Kühn–Sutiono,Siemens AG, EV S SUP22, Nürnberg/EV BK T, Erlangen

Conditions of Sale and Delivery � Export Regulations � Trademarks � Dimensions

A 9.91 a

Siemens Aktiengesellschaft

BereichEnergieübertragung und -verteilungGeschäftsgebiet SekundärsystemePostfach 48 06D-90026 Nürnberg

Order No.: E50001-K5722–A111-A2–7600Printed in GermanyKG K 0397 2.0 SC 10 En 321537 6101/U539

PowerTransmissionand Distribution