dnp 3.0 protocol database implementation
TRANSCRIPT
ssss
DNP 3.0 Protocol
Database Implementation
Centurion Recloser
LIMITATIONSThis document is copyright and is provided solely for the use of the recipient. It is not to be copied in any way,nor its contents divulged to any third party, nor is it to be used as the basis of a tender or specification withoutthe express written permission of Siemens Power Transmission & Distribution, Inc.
This document discloses confidential intellectual property that belongs to Siemens Power Transmission &Distribution, Inc. Receipt of this document does not invest any rights to Siemens Power Transmission &Distribution, Inc. intellectual property in the recipient. Moreover, the recipient is required not to disclose any ofthe intellectual property contained in this document to any other party unless authorized in writing by SiemensPower Transmission & Distribution, Inc.
NOTEThese instructions do not purport to cover all details or variations in equipment, or provide for every possiblecontingency to be met in conjunction with installation, operation or maintenance. Should further information bedesired or should particular problems arise which are not covered sufficiently for the purchaser’s purpose, thematter should be referred to the local sales office.
The contents of this instruction manual shall not become part of or modify any prior or exiting agreement,commitment, or relationship. The sales contract contains the entire obligation of Siemens Power Transmission& Distribution, Inc. The warranty contained in the contract between the parties is the sole warranty of SiemensPower Transmission & Distribution, Inc. Any statements contained herein do no create new warranties ormodify the existing warranty.
__________________________________________________________________________________________
Table of Contents
1 Introduction ................................................................................... 4
2 Overview ....................................................................................... 4
2.1 Status Points ................................................................... 4
2.2 Controls........................................................................... 4
2.3 Data Configuration........................................................... 4
2.4 Password Protection........................................................ 4
2.5 LBS vs ACR Point Mapping. ............................................ 5
2.6 Year 2000 Compliance Statement ................................... 5
3 SCADA System Design ................................................................. 5
4 Applicability ................................................................................... 6
4.1 Control Cubicle Software ................................................. 6
4.2 DNP V3.00 Protocol ........................................................ 6
4.3 Switchgear Type.............................................................. 6
4.4 Terminology..................................................................... 6
5 Protocol Configuration................................................................... 7
5.1 Transmission Services Configuration............................... 7
5.1.1 Overview............................................................................ 7
5.1.2 Transmission Services Parameters.................................... 7
5.1.3 Use of Application and Data Link Confirmation/Retries ...... 9
5.2 Unsolicited Response Configuration ................................ 9
5.2.1 Overview............................................................................ 9
5.2.2 Unsolicited Response Parameters ..................................... 9
5.2.3 Event Buffering ................................................................ 12
5.3 Data Configuration......................................................... 12
5.3.1 Overview.......................................................................... 12
5.3.2 Database Parameters ...................................................... 12
5.3.3 Database Size Permutations............................................ 13
5.3.4 Default Database Data Objects........................................ 13
5.3.5 Analog Deadband Parameters ......................................... 14
Analog Alarm Reporting............................................................ 15
5.3.7 Analog Alarm Parameters ................................................ 15
5.4 Example Configuration - Load Profile............................. 16
6 Physical Layer............................................................................. 17
6.1 Communications Ports Supported ................................. 17
6.2 RS-232 Communication Specifications.......................... 17
6.2.1 RS-232 Hardware Signals ............................................... 17
6.2.2 RS-232 Character Definition ............................................ 17
6.2.3 RS-232 Configuration Parameters ................................... 17
6.2.4 Carrier Detect .................................................................. 20
6.2.5 Transmitting a DNP Packet.............................................. 20
6.2.6 DTR................................................................................. 20
6.2.7 Dialing Modem Support ................................................... 20
6.3 V23 FSK Communication Specifications........................ 20
6.3.1 V23 Hardware Signals ..................................................... 20
6.3.2 V23 Configuration Parameters......................................... 20
6.3.3 V23 Handshaking Signals................................................ 23
6.4 Communication Statistics .............................................. 23
Appendix A Protocol Timings .............................................................. 24
Appendix B DNP V3.00 Device Profile ................................................ 25
Appendix C DNP V3.00 Implementation Table.................................... 28
Appendix D ACR - Binary Input Points (Status)................................... 34
Appendix E ACR - Analog Input Points (Status - Small Set) ................ 44
Appendix F ACR - Analog Input Points (Status – Full Set) .................. 46
Appendix G ACR - Counter Point ........................................................ 51
Appendix H ACR - Binary Output Points ............................................. 52
Appendix I ACR - Analog Output Points .............................................. 56
Appendix J LBS – Binary Points Data (Status) .................................... 57
Appendix K LBS - Analog Input Points (Status - Small Set)................. 62
Appendix L LBS - Analog Input Points (Status – Full Set) ................... 65
Appendix M LBS - Counter Points....................................................... 69
Appendix N LBS - Binary Output Points .............................................. 70
Appendix O LBS - Analog Output Points ............................................. 73
__________________________________________________________________________________________
Siemens Power Transmission & Distribution, Inc. 4
1 IntroductionThis document describes the DNP V3.00 implementationfor Centurion Automatic Circuit Reclosers (ACRs) usingthe Control and Protection Module types 4 & 5 (CAPM).For more information on Recloser operating modes,refer to the relevant instruction manual for yourRecloser.
This protocol implementation is more complex than mosttelemetry protocols. It is essential to read the Overviewsection in order to set up the SCADA system correctly.
2 OverviewThe CAPM controller combines the functions ofprotection relay and switchgear controller into a singleintelligent electronic device (IED). The controllerprovides a user-friendly operator interface on a four lineLCD control panel that allows configuration and controlof the switchgear.
In addition the controller generates time tagged “events”which are displayed on the operator control panel. Theseevents show the history of the switchgear operation forthe benefit of the operator and for post fault analysis andare optimized to provide the operator with the mostuseful information for analysis purposes. Examplesevents are as follows:
• Operator actions such as trip or close• Protection pick-up• Protection trips• Fault current levels• Auto-reclose actions
Electricity Utilities frequently link the controller into theirSCADA systems as a Remote Terminal Unit (RTU). Tosimplify this task, each control is supplied with thefollowing:
• Space & mounting tray for a radio or modem insidethe control cubicle.
• Integral power supply for the radio or modem insidethe control cubicle.
• Embedded protocol handler for the required SCADAprotocol in the controller firmware.
The DNP protocol allows digital and analog data to besent from the controller to the SCADA system with timetags attached. This facility has enabled the provision of asophisticated SCADA system interface that not onlyprovides the SCADA system with status information butalso allows the SCADA system to re-create the EventLog display on the operator control panel.2.1 Status PointsThis implementation provides a set of status informationabout the switchgear that can be used by a SCADAsystem to generate displays and events for operationalpurposes. This data is called the “Status Points”. Refer
to appendices D, E and F for ACR status points orappendices J, K and L for LBS status points.
For example:
• Open or Close Status• Lockout Status• Fault Flags• Line Currents and Voltages
Time tags are optional. If enabled, these status pointsare returned with time tags of either 10 or 500millisecond resolution.2.2 ControlsA list of the controls supported by the protocol handler isdetailed in Appendices H and N.
All controls have a corresponding binary status point.The master station must use these status points to verifythat the control action has been successful. Sometimesa control will be rejected because of an underlyingCAPM condition preventing the action. These conditionsare detailed in the table in the appendices.
The DNP V3.00 protocol handler can trigger two eventsto be recorded in the CAPM event log - “DNP3 Trip Req”and “DNP3 Close Req”. This event log reportingindicates only that the protocol handler has requested atrip or a close from the CAPM. It does not necessarilymean that the action has been taken. As detailedabove, the request may be over-ridden by operationalconditions.
The DNP protocol handler is designated as remote.Refer to the equipment manual for more information.2.3 Data ConfigurationSeveral means are provided to configure the data pointsrequired. These include:
• Selection of three sets of analog points –full, smalland none.
• Default data object type – with/with out flag/time;analog size
• Point class assignment.
2.4 Password ProtectionAll DNP panel fields require password entry unlessdescribed as ‘Display only’ or otherwise stated. Formore information on operator control panel usage referto the equipment manual.
Siemens Power Transmission & Distribution, Inc. 5
2.5 LBS vs ACR Point MappingThe DNP protocol handler supports independent pointmaps for the ACR and LBS (load break switchgear)types. The mapping for each is listed in the appendices.The type supported by the protocol handler is firmwaredependant and determined by the CAPM on power up.If an incorrect configuration is supplied please contactSiemens PT&D, Inc.
Use of DNP V3.00 for LBS switchgear is only availablewith CAPM V25.01.00+ software. This product istypically not available for NAFTA distribution systems.
2.6 Year 2000 Compliance Sta tementThe DNP V3.00 protocol software complies with rules 1,2, 3 and 4 of the British Standards Institute Year 2000Conformity Requirement (DISC PD2000-1 A Definition ofYear 2000 Conformity Requirements). A copy of thisstatement can be found on our web site(http://www.siemenstd.com/).
3 SCADA System Design
It is recommended that the SCADA system engineerread the rest of this manual and discus the options forimplementation provided by this protocol implementationwith the operations staff.
Some SCADA system implementation options are:
• Build Screens using the Status Points and use theirtime tags to generate SCADA system events.
• Build Screens using the Status Points and use theEvent Points to generate the SCADA system events.This means that the SCADA system event log willreplicate the controller event log.
• Build Screens using the Status Points and use theirtime tags to generate SCADA system events.
There are many other configuration parameters for theprotocol such as data rate, device address etc. refer toSection 1.
The controller has a fixed set of functionality and thepoint mapping has been implemented to reflect this byproviding the sets of data points described in theappendices. The SCADA engineer has the ability toselect from a variety of points sets and to configurevarious aspects of the point mapping as described inSection 5.3.
Siemens Power Transmission & Distribution, Inc. 6
4 Applicability4.1 Control Cubicle SoftwareThis document applies to Centurion Reclosers using aCAPM Controller that displays “DNP V3.00 ManualRCDNP ” on the controller capability pages.To find these pages refer to the main equipment manual.Some features described in this manual may only beavailable on later releases of the software. In this casethe manual will declare which version of softwareapplies.4.2 DNP V3.00 ProtocolThe protocol version implemented is DNP V3.00 and isdescribed in the following documents:
• Basic Four Documentation Set:1. “DNP V3.00 Application Layer”, DNP User Group,
dnpal.doc rev 0.032. “DNP V3.00 Transport Functions”, DNP User
Group, dnptf.doc rev 0.013. “DNP V3.00 Data Link Layer”, DNP User Group,
dnpdl.doc rev 0.024. “DNP V3.00 Data Object Library”, DNP User
Group, dnpdol.doc rev 0.02
• Subset Definitions Document:1. “DNP V3.00 Subset Definitions”, DNP User
Group, subset.wp6 rev 2.00
• Technical Committee Bulletins:1. “Control Relay Output Block Minimum
Implementation”, DNP User Group, 9701-0022. “DNP Confirmation and Retry Guidelines”, DNP
User Group, 9804-0023. “Cold/Warm Restart Sequence”, DNP User
Group, 9701-0034. “Analog Input Reporting Deadband”, DNP User
Group, 9809-001.
These documents are obtainable from the DNP usersgroup, which can be contacted via the web sitehttp://www.dnp.org/.
4.3 Switchgear TypeThis manual is applicable to the following Reclosers withCAPM4 or CAPM5 controls:
• Centurion, 3-phase, U-Series, ACR.• Centurion SP, 1-phase, W-Series, ACR.
4.4 TerminologyThe terminology used in this document is that EarthFault or Ground Fault is described as Earth / GroundFault and Sensitive Earth Fault (SEF) or SensitiveGround Fault (SGF) is described as SEF/SGF.
Also, bushing terminology used in this document is forCenturion Reclosers (U-series) and Centurion SP (Wseries) Reclosers, i.e., ‘I’ and ‘X’ for switchgearterminals. On N or RL series switchgear the ‘1’ side isdescribed as ‘I’ and the ‘2’ side is described as ‘X’. Alsonote that the phase terminology is ABC and refersalways to the phase set by the Terminal Designation or“Phasing” option, never to the physical bushing orterminal on the switchgear.
Siemens Power Transmission & Distribution, Inc. 7
5 Protocol Configuration
The DNP V3.00 protocol handler adds several pages tothe “System Status” menus. The additional pages fallinto the following groups,• Transmission Services Configuration (Section 5.1)• Unsolicited Response Configuration (Section 5.2)• Data Configuration (Section 5.3)• Communications Configuration (Sections 6.2 and 6.3)• Communication Statistics (Section 6.4)All protocol configuration parameters can be viewed,modified and stored on a personal computer with theCSS utility.5.1 Transmission Services Co nfiguration
5.1.1 OverviewThe DNP protocol has a number of data link andapplication layer parameters that form transmissionservice functions. The CAPM permits configuration of anumber of these:• Data link layer confirmation• Data link time out• Application layer confirmation time out
• Control select / operate time out period• Time Synchronization request operation5.1.2 Transmission Services Pa rametersThese pages allow the SCADA engineer to determinehow the Data Link and Application Layer of the DNPV3.00 protocol handler transmits DNP data packets.
---- DNP Transmission Services 1 ----S DL Cf Rqd SOMETIMES DL Cf TO 4000ms DL Max Retries 2 Apl Cf TO 84000ms Arm Select 10000ms
---- DNP Transmission Services 2 ----SDNP Address 5 Time Dly Rq 0min
Parameter DescriptionDL Cf Rqd Data Link Confirm Required
On some communications links it is necessary to have additional communications integrity to ensurethe master station has successfully received all data link frames.
• If NEVER, the protocol handler will not request acknowledgment messages from the master stationfor data link frame transmissions. It assumes all data link frames are received by the master stationand relies solely on application layer message integrity checking.
• If SOMETIMES, the protocol handler requests a data link acknowledge response from the masterstation only on multi-frame DNP messages.
• If ALWAYS, the protocol handler will expect a data link acknowledgment message from the masterstation to all data link frame transmissions.
Range: NEVER, SOMETIMES, ALWAYS.Factory default is SOMETIMES
DL Cf TO Data Link Confirm TimeoutWhen the CAPM DNP data link layer transmits a frame that requires an acknowledge response fromthe master station, it starts a timer. The timer is triggered upon transmission of the last byte of aframe.• If an acknowledge frame is not received from the master station with-in the data link confirm time out
period, DL Cf TO, then the frame is resent.• If the communications link has failed then the CAPM will continue retransmissions until DL Max
Retries failures occur after which it informs the application layer of the failure.
Range: 50 to 65535 ms.Factory default is 4000 ms
DL MaxRetries
Data Link Maximum RetriesMaximum number of times a frame is re-sent before communication failure is identified.
Range: 0 – 255.Factory default is 2
Apl Cf TO Application Layer Confirm TimeoutWhen the CAPM transmits some DNP messages, such as a application layer messages that containchange of state data, a DNP application layer confirm message is expected from the master station.When the last byte of one these messages is transmitted by the CAPM a timer is started.
Siemens Power Transmission & Distribution, Inc. 8
Parameter Description• If an application layer confirm message is not received from the master station with-in the time out
period then the message is deemed failed. Refer to section 5.2.3 for more information regardingfailed application layer message handling.
• If the application layer message is too large for a single data link frame, the protocol handlersegments the application message into multiple data link frames. The ‘application confirm timeout’period must therefore allow for multiple data link frames.
• If DL Cf Rqd is set to either SOMETIMES or ALWAYS then for correct operation of the confirmtimeouts Apl Cf TO must be set using the following formula:
Apl Cf TO >= ((DL Max Retries + 1) x DL Cf TO x 7)• The CAPM calculates this value and automatically overwrites a value that is entered which is less
than the calculated value.• If DL Cf Rqd is set to NEVER then the minimum Apl Cf TO is 0ms.
Range: 0 or (Apl Cf TOCalculated) to 3600000 ms.Factory default is 84000 ms
Arm Select Arm Select TimeoutMaximum time permitted, in milliseconds, between receiving a select command message and anoperate command message from the master station for the control action to be deemed valid.
Range: 50 to 65535 ms.Factory default is 10,000 ms
DNPAddress
DNP Station AddressThe station address of the CAPM on the communication link.
Changing this parameter will cause the DNP handler task to perform a warm restart. This will mean are-initialization of all communication parameters such as FCB, sequence numbers, restart internalindication, etc. A temporary loss of communications with the master station may occur. Also, anyqueued events will be deleted.This field is not configurable via CSS if ‘DNP V3.00’ communications is used.
Range: 0 to 65519Factory default is 5
Time Dly Rq Time Synchronization Request DelayThe DNP protocol allows for the master station to send time synchronization messages independentlyor at the request of the CAPM or both.
Time Dly Rq is the amount of time, in minutes, after the last master station time synchronizationmessage that the CAPM will wait before setting the ‘Time Synchronization Required’ internalindication bit (IIN1-4). This bit is sent to the master station in every CAPM DNP message.If this field is set to 0 then the internal indication bit is never set and the master station solelydetermines time synchronization operation.
Range: 0 – 65535 minutesFactory default is 0 minutes
Siemens Power Transmission & Distribution, Inc. 9
5.1.3 Use of Application and Da ta LinkConfirmation/Retries
The use of application and data link confirmations andretries depends upon the nature of data transfer on thecommunications link i.e., whether CAPM unsolicitedresponses are used or the master frequently polls fordata. When the CAPM is configured to transmitunsolicited response messages, it is recommended thatonly the CAPM be configured to use of data linkconfirmations and retries. It is the CAPM responsibility toensure that data is successfully transmitted to themaster station so it will attempt to retry sending amessage if it detects a failure. If the master station alsoperforms integrity polls on the same communications linkthen it should do so infrequently to limit collisionproblems.Alternatively, if a master station polls slaves frequentlyand CAPM unsolicited responses are not used then it isrecommended that only the master be configured to usedata link confirmations and retries. It is the masterstation’s responsibility to gather data. If the masterstation detects a communication failure and moves on topoll the next device on a multi-drop communication linkwhilst the CAPM is performing retries then collisions willoccur.For more information refer to the DNP User GroupTechnical Bulletin 9804-002 “DNP Confirmation andRetry Guidelines.”5.2 Unsolicited Response Con figuration
5.2.1 OverviewThe protocol handler’s DNP event processing informsthe master station that a change in a binary input hasoccurred or an analog input has exceeded its deadbandrange.The transmission of event data can be performed usingtwo methods:• Master initiated polling for event data.• CAPM initiated transmissions (called Unsolicited
Responses).Events can be reported in three data classes:• Class 1 - high priority event class• Class 2 - medium priority event class, and• Class 3 - low priority event classNote that the fourth DNP data class, Class 0, is not anevent class. It is used in the reporting of current (static)value of data and not change of state events.The event class of DNP binary and analog points can beconfigured using CSS. Setting a point to class 0 willprevent the protocol handler from reporting change ofstate events for that point to the master station. Thepoint will remain accessible via static data polls.The following CAPM display pages allow configuration ofUnsolicited Response behavior.
5.2.2 Unsolicited Response Par ameters
--------- DNP Unsolicited 1 --------SUnsolicited OFF Master Addr 3Unsol Retries 255 Unsol Dly 90s
--------- DNP Unsolicited 2 --------SC1 Count 1 C1 Delay 1sC2 Count 3 C2 Delay 5sC3 Count 5 C3 Delay 10s
--------- DNP Unsolicited 3 --------SC1 Timeout 0s C1 Buffered 0C2 Timeout 0s C2 Buffered 0C3 Timeout 0s C3 Buffered 0
Siemens Power Transmission & Distribution, Inc. 10
Parameter DescriptionUnsolicitedNote 1
Enable/Disable Unsolicited Responses If OFF, change of state events are buffered but only sent as responses to event polls from the master.Any Enable or Disable Unsolicited Messages commands received by the CAPM will result in the CAPMresponding with its ‘Function Code Not Implemented’ internal indication bit set.
If ON or FORCED, change of state events are buffered and are transmitted when:• A class count is exceeded, or• A class notification delay timer expires, or• As a response to a master station event poll.
When a class count is exceeded, or class notification delay timer expires, then only the events for thatclass are transmitted. Any other class’s events remain stored in the CAPM’s buffer.
If the master station issues an Enable or a Disable Unsolicited Messages command to the CAPM after theCAPM has sent its initial unsolicited ‘Null’ message then the mode of the CAPM will be overriddenregardless of ON or FORCED setting.
Note:1. If ON, the unsolicited reporting ability in the CAPM is enabled. The CAPM will inform the master
station of this ability via an initial unsolicited ‘Null’ message and will only transmit unsolicited responsechange of state events after it receives an ‘Enable Unsolicited Messages’ command from the masterstation. Setting this field to ON will mean that the CAPM DNP implementation is compliant with theDNP V3.00 specification.
2. If FORCED, the CAPM will transmit unsolicited response change of state events immediately withoutwaiting for the ‘Enable Unsolicited Messages’ command from the master station.Setting this field to FORCED will cause the CAPM DNP implementation to be non-compliant with theDNP V3.00 specification and is not recommended. This parameter setting has been provided forcompatibility with master station implementations that are in conflict with the specification.
Range: OFF, ON, FORCED.Factory default is OFF
Master AddrSee Note 1
DNP Master Station AddressThis is the DNP address to which the unsolicited responses are sent. If the CAPM is set up tocommunicate with CSS using ‘DNP V3.00 Radio’ communications then it is recommended that this fieldshould not be set to the CSS DNP master address.
Range: 0 to 65519Factory default is 3.
Unsol Retries Unsolicited Response Number of RetriesMaximum number of attempts to re-transmit an unsolicited response without getting a confirmation fromthe master. Refer to section 5.2.3 below for more information.
This limitation does not apply to an initial unsolicited ‘Null’ message. (A DNP3-2000 requirement.)A value of 0 means that only a single transmission is made and no re-transmits are attempted.A value of 255 means unlimited retries i.e., maximum limit is disabled.
Range: 0 to 255Factory default is 255
Unsol Dly Unsolicited Response Retry DelayIf the CAPM has not received a confirmation from the master station to an unsolicited response within AplCf TO period then this parameter determines when the next unsolicited response will be sent.
Siemens Power Transmission & Distribution, Inc. 11
Parameter Description
Unsol Dly(Cont’d)
The Apl Cf TO timer and Unsol Dly timers are started at the same time i.e., started immediately after thetransmission of the last byte of a CAPM message that expects a response from the master.• If Unsol Dly is less than Apl Cf TO then the ‘retry’ unsolicited message will be sent as soon as Apl Cf TO
expires.• If Unsol Dly is greater than Apl Cf TO then it will wait until Unsol Dly seconds after transmission of last
message before sending a retry.
Range: 1 to 86400 secondsFactory default is 90s
C1 Count Unsolicited Response Class 1 Notification Max CountThe number of events which must occur in Class 1 before they will be reported.Range: 1 to 255Factory default is 1 event.
C2 Count Unsolicited Response Class 2 Notification Max CountThe number of events which must occur in Class 2 before they will be reported.Range: 1 to 255Factory default is 3 events.
C3 Count Unsolicited Response Class 3 Notification Max CountThe number of events which must occur in Class 3 before they will be reported.Range: 1 to 255Factory default is 5 events.
C1 Delay Unsolicited Response Class 1 Notification DelayThe maximum time an event in this class will wait to be reported.Range: 1 to 86400 secondsFactory default is 1s.
C2 Delay Unsolicited Response Class 2 Notification DelayThe maximum time an event in this class will wait to be reported.Range: 1 to 86400 secondsFactory default is 5s
C3 Delay Unsolicited Response Class 3 Notification DelayThe maximum time an event in this class will wait to be reported. Range: 1 to 86400 secondsFactory default is 10s
C1 Timeout Unsolicited Response Class 1 Notification TimeThe number of seconds remaining before an unsolicited response class 1 transmission. (Display only)
C2 Timeout Unsolicited Response Class 2 Notification TimeThe number of seconds remaining before an unsolicited response class 2 transmission. (Display only)
C3 Timeout Unsolicited Response Class 3 Notification TimeThe number of seconds remaining before an unsolicited response class 3 transmission. (Display only)
C1 Buffered Unsolicited Response Class 1 Buffered EventsThe number of queued events in the unsolicited response class 1 buffer. (Display only)
C2 Buffered Unsolicited Response Class 2 Buffered EventsThe number of queued events in the unsolicited response class 2 buffer. (Display only)
C3 Buffered Unsolicited Response Class 3 Buffered EventsThe number of queued events in the unsolicited response class 3 buffer. (Display only)
Note1. Changing this parameter will cause the DNP handler task to perform a warm restart. This will mean a re-initialization of all
communication parameters such as FCB, sequence numbers, restart internal indication etc. A temporary loss of communicationswith the master station may occur. Also, any queued events will be deleted.
Siemens Power Transmission & Distribution, Inc. 12
5.2.3 Event BufferingMultiple DNP change of state events can be transmittedin the same message. When events are transmitted, thesoftware tags them as sent and retains them in the eventbuffer. All messages containing events require anapplication layer confirm response from the masterstation.
If the application layer receives a confirm responsewithin the application layer confirmation time out period(Apl Cf TO), then the tagged events are deleted from thebuffer. If a confirm message is not received within theapplication layer confirm time out period (Apl Cf TO)then all tagged events are untagged and are retained inthe event buffer and the protocol handler behaves asfollows:• If unsolicited response messages are not enabled
then the events are retransmitted when nextrequested by the master station.
• If unsolicited response messages are enabled thenthe protocol handler waits for the retry delay timer(Unsol Dly) to expire before attempting to sendanother unsolicited response. The new unsolicitedresponse message is not an identical retry of thefailed message but may contain the same data. Allmessage identification parameters (e.g., sequencenumbers) are incremented.
• If the maximum unsolicited response retry limit isenabled then after Unsol Retries the protocolhandler will cease attempting to send unsolicitedresponses until either:
1. A successful application layer message, of anyfunction code, addressed to it is received fromthe master station, or
2. A new event is queued in the buffer.
• If the 250 binary event buffer, or the 200 analogevent buffer, is full then the oldest queued event willbe over-written by a new event.
5.3 Data Configuration
5.3.1 OverviewData configuration is available for:
• Assigning default dead bands and high/low alarming tomatch the line conditions, these are set separately for
1. Phase Currents (A, B, C)2. Earth / Ground Current3. Phase Voltages (A, B, C)4. System Power (kVA, kVAR, kW)
• Selection of analog point sets (full, small, none) based onthe operational requirements and transmission bandwidthavailable, particularly during an integrity poll. Refer toappendices for points lists.
• Enabling / Disabling event points.• Point class assignment. The classes shown in the
appendices are factory defaults. The class of each pointcan be assigned using the CSS utility on a PC or via aDNP Assign Class commands from the master station.
5.3.2 Database ParametersThis page allows the SCADA engineer to determine thesize of the DNP Database and the type of data objectreport in a class event or integrity poll.
----- DNP Database Configuration ----SAnalog Alarms OFF Analog Pnts SMALLBinary Time ON Analog Time OFFAnalog Size 16bit Analog Flag OFF
Para-meter
Description
AnalogAlarms
Analog Alarming OperationThis field determines if analog threshold alarmingis enabled or disabled.• If ON, the operation of binary alarm points are
enabled. All alarms are independent of theprotocol handler analog configuration, e.g., Theevent class of the analogs does not effect alarmoperation. Similarly alarming is not effected bywhether the analogs are in the configuredAnalog Pnts set.
• If OFF, alarms are disabled. All binary alarmpoints are cleared. Refer to section 5.3.6 formore information.
Range: OFF, ONFactory default is OFF
AnalogPnts
Analog Point SetThis field determines which, if any, of the analogpoint mapping sets are included in the CAPM’sDNP Points list. A summary of all the availablemapping permutations is given in section 5.3.3.
Changing this parameter will cause the DNPhandler task to perform a warm restart. This willmean a re-initialization of all communicationparameters such as FCB, sequence numbers,restart internal indication etc. A temporary loss ofcommunications with the master station mayoccur. Also, any queued events will be deleted.
Range: OFF, SMALL, FULLFactory default is SMALL.
BinaryTime
Binary Time Tag UsageDetermines whether or not a time tag is includedwith DNP binary change of state eventstransmitted to a master station by the CAPM.
Range: ON, OFFFactory default is ON.
AnalogTime
Analog Time Tag UsageDetermines whether or not a time tag is includedwith DNP analog change of state eventstransmitted to a master station by the CAPM.
Range: ON, OFFFactory default is OFF
Siemens Power Transmission & Distribution, Inc. 13
AnalogSize
Default Analog Data Object SizeDetermines the size of the CAPM DNP defaultanalog objects. This size is transmitted by theCAPM for all static and event data responseswhere the master does not explicitly ask for datasize.
Range: 16, 32 bits (signed)Factory default is 16 bit
AnalogFlag
Analog Flag ReportingDetermines whether or not a byte containing theanalog’s status data is included with its value in aCAPM response to a static data scan.
If ON, the CAPM will always send a flag of either0x01 (point online) or 0x21 (point online andoverrange). It is recommended that this fieldshould only be set ON if the use of the analogflag bits is a master station requirement.
Range: ON, OFFFactory default is OFF
5.3.3 Database Size Permutation sTo enable optimization of communication bandwidth,three binary and analog input point sets are available.The selection of a set will determine the size of thelogical database used by the CAPM’s DNP V3.00protocol handler and thus determine the size of anintegrity poll response.
ACRAnalogPoints
Binary PointTable(s)
Analog PointTable(s)
OFF Appendix D No analogsSMALL Appendix D Appendix EFULL Appendix D Appendix F
LBSAnalogPoints
Binary PointTable(s)
Analog PointTable(s)
OFF Appendix J No analogsSMALL Appendix J Appendix KFULL Appendix J Appendix L
5.3.4 Default Database Data Obj ectsWhen master stations perform change of state orintegrity data polling then the reported data objectvariation is typically not specified. The request simplyasks for any data for a specific DNP class type and it isleft to the CAPM’s protocol handler to determine whichDNP object variation is to be transmitted. The CAPMdetermined object variations are referred to in thismanual as the ‘Default’ object variation. Some defaultdata object variations can be configured. The tablebelow lists the selectable variations and identifies therelevant configuration parameter required.
CAPM Configuration FieldDNP Data Object Binary
TimeTag
AnalogTimeTag
AnalogSize
AnalogFlag
Binary Input Changewithout time
(Object 2 Variation 1)
OFF
Binary Input Changewith time
(Object 2 Variation 2)
ON
32 Bit Analog Input
(Object 30 Variation 1)32 ON
16 Bit Analog Input
(Object 30 Variation 2)16 ON
32 Bit Analog Inputwithout flag
(Object 30 Variation 3)
32 OFF
16 Bit Analog Inputwithout flag
(Object 30 Variation 4)
16 OFF
32 Bit Analog ChangeEvent without time
(Object 32 Variation 1)
OFF 32
16 Bit Analog ChangeEvent without time
(Object 32 Variation 2)
OFF 16
32 Bit Analog ChangeEvent with time
(Object 32 Variation 3)
ON 32
16 Bit Analog ChangeEvent with time
(Object 32 Variation 4)
ON 16
16 Bit Analog InputDeadband
(Object 34 Variation 1)
16
32 Bit Analog InputDeadband
(Object 34 Variation 2)
32
The remaining default data objects used by the CAPMare:• Binary input status (Object 01 variation 01),• Binary counter status (Object 20 variation 05),• Frozen counter status (Object 21 variation 09), and• Binary output status (Object 10 variation 02).These object types are not configurable.
Siemens Power Transmission & Distribution, Inc. 14
5.3.5 Analog Deadband Parame tersEach of the protocol handler’s analog inputs has a non-volatile default deadband value. Refer to Appendix E,Appendix F, Appendix K and Appendix L for the values.Some default deadbands can be configured. Theseconfigurable deadbands are listed in the table below. UponCAPM startup, protocol handler restart, or a defaultdeadband setting change, the protocol handler copies alldefault settings to volatile memory over-riding any previoussettings. The protocol handler uses the volatile values in itsdeadband reporting logic.
All volatile analog input deadbands are configurable fromthe DNP master station on a per point basis. If volatiledeadband changes are to be maintained after the protocolhandler has restarted then it is the master station’sresponsibility for re-sending any updated deadbandvalues.
Deadband values are not reported in integrity or eventpolling. They are only available via reads and writes ofDNP analog input deadband objects.
All deadbands supported by the protocol handler are fixedvalue format – i.e., the deadband value represents ananalog input’s absolute value difference between the lastreported value and the threshold value that the currentvalue must exceed in order to generate an analog changeof state event.
For more information on DNP analog deadband objectsand behaviour refer to the DNP User Group TechnicalBulletin 9809-001 “Analog Input Reporting Deadband”
-------- DNP Default Deadbands -------SPhase Current 10A Phase Voltage 100VEarth Current 5A System Power 250
Parameter DescriptionPhase Current Phase Current Default
DeadbandThe A, B and C phase currentanalog inputs will have theirdeadband set to this value.
Range: 1 to 999AFactory default is 10A.
Phase Voltage Phase Voltage DefaultDeadbandThe A, B, and C phase voltageanalog inputs will have theirdeadband set to this value. Allphase-phase as well asphase-earth/ground voltagesare effected.
Range: 1 to 38000VFactory default is 100V.
Earth/GndCurrent
Earth/Ground CurrentDefault DeadbandThe earth/ground currentanalog input will have itsdeadband set to this value.
Range: 1 to 999AFactory default is 5A.
System Power System Power DefaultDeadbandAll power analog inputs willhave their deadband set to thisvalue i.e. KVA, KVAR, andKW.
Range: 1 – 54000 unitsFactory default is 250 units.
Siemens Power Transmission & Distribution, Inc.
H1HIGH THRESHOLD
LOW THRESHOLD
LOW + 90% (HIGH–LOW)
L2LOW + 10% (HIGH–LOW)
5.3.6 Analog Alarm Reporting
The protocol handler has four configurable alarm analogtypes: phase voltage, phase current, earth current andsystem power. Each analog type has a configurable highalarm threshold value as well as a configurable lowalarm threshold value. Each of these analog types alsohas a pair of binary alarm points in the protocol handlerdatabase. If an analog value passes the alarm threshold(eg H1 or L1 above) the binary alarm becomes active. Abinary alarm change of state event is put into the DNPevent buffers for reporting to the master station.
• If, after a HI Alarm, all analogs of the same type arebelow the high alarm reset threshold (e.g., H2above), then the HI binary alarm is turned off and abinary alarm change of state is put into the DNPevent buffers for reporting to the master station.
• If, after a LOW Alarm, the analogs of the same typeare above the low alarm reset threshold (e.g., L2above), and all other, then the LOW binary alarm isturned off and a binary alarm change of state is putinto the DNP event buffers for reporting to themaster station.
Alarming is enabled/disabled via configuration of theprotocol handler’s Analog Alarms field.
5.3.7 Analog Alarm ParametersThese pages allow the SCADA engineer to determinethe high and low alarms for phase current, phasevoltage, ground current and system power.
---- DNP High Alarm Configuration ---SPhase Current 999A Phase Voltage 38000VGnd Current 999A System Power 54000
ParameterPhaseCurrent
Phase CurrThe A, B aninputs will hthreshold se
Range: 1 toFactory def
PhaseVoltage
Phase VoltThe A, B, aanalog inpualarm thresThe type ofphase-phasis determinethe CAPM. manual for
Range: 1 toFactory def
Earth/GndCurrent
Earth/GrouThe earth/gwill have itsto this value
Range: 1 toFactory def
SystemPower
System PoAll power anhigh alarm ti.e. KVA, KV
Range: 1 – Factory def
Note: If a high alarm threto, its corresponding lprotocol handler will threshold back to its prev
A/V/kW
HI ALARM ON
HI ALARM OFF
LOW ALARM OFF
H2
LOW ALARM ON
L1Time
15
Descriptionent High Alarmd C phase current analogave their high alarmt to this value.
999Aault is 999A.age High Alarmnd C phase voltagets will have their highhold set to this value. voltage monitored,e or phase-earth/ground,d by the configuration of
Refer to the equipmentmore information.
38000Vault is 38000V.nd Current High Alarmround current analog input high alarm threshold set.
999Aault is 999A.wer High Alarmalog inputs will have theirhreshold set to this valueAR, and KW.
54000 unitsault is 54000 units.
shold is set lower than, or equalow alarm threshold then theautomatically reset the highious value.
Siemens Power Transmission & Distribution, Inc. 16
---- DNP Low Alarm Configuration ----SPhase Current 0A Phase Voltage 0VEarth Current 0A System Power 0
Parameter DescriptionPhaseCurrent
Phase Current Low AlarmThe A, B and C phase current analog inputswill have their low alarm threshold set to thisvalue.
Range: 0 to 998AFactory default is 0A.
PhaseVoltage
Phase Voltage Low AlarmThe A, B, and C phase voltage analog inputswill have their low alarm threshold set to thisvalue.The type of voltage monitored, phase-phaseor phase-earth/ground, is determined by theconfiguration of the CAPM. Refer to theequipment manual for more information.
Range: 0 to 37999VFactory default is 0V.
Earth/ GndCurrent
Earth/Ground Current Low AlarmThe earth/ground current analog input willhave its low alarm threshold set to this value.
Range: 0 to 998AFactory default is 0A.
SystemPower
System Power Low AlarmAll power analog inputs will have their lowalarm threshold set to this value i.e. KVA,KVAR, and KW.
Range: 0 – 53999 unitsFactory default is 0 units.
Note:If a low alarm threshold is set higher than, or equal to, itscorresponding high alarm threshold then the protocolhandler will automatically reset the low threshold back toits previous value.
5.4 Example Configuration - L oad ProfileTo configure the CAPM to transmit load profile data atleast once a day to the master station using unsolicitedresponses the following steps need to be taken:
1. Setup the event configuration data• Enable unsolicited response messages• Set unsolicited class 3 delay (C3 Delay) to
86400 seconds• Set unsolicited class 3 count (C3 Count) to 100• Set the master station’s DNP address
2. Setup the point configuration data• Enable time tag analogs• Set the analog size to 16 bits• Configure the analog deadbands to desired
values
3. Use CSS to assign data class• Configure the required analog values to data
class 3.
The CAPM fills its analog buffer with the class 3 events.If it reaches its maximum event count (C3 Count) in lessthan the desired update period (C3 Delay), or class 3delay timer expires, then the CAPM will automaticallytransmit its data. All of the analog buffer’s class 3 eventswill be transmitted and the delay timer will be reset foranother C3 Delay period. Similarly, if the master stationsends a poll which requests class 3 data then the allclass 3 events will be sent and the timer reset.
Note:1. If the analog buffer overflows then the oldest event,
irrespective of class, will be replaced with the newevent.
Siemens Power Transmission & Distribution, Inc. 17
6 Physical Layer6.1 Communications Ports Su pportedThe CAPM can communicate to the Master station viaone of the following ports.
• RS-232 Port P8• V23 FSK Port P10
6.2 RS-232 Communication Sp ecifications
6.2.1 RS-232 Hardware SignalsP8Pin
Direction Description
2 From CAPM Tx Data (TxD)3 To CAPM Rx Data (RxD)4 From CAPM Request To Send
(RTS)5 To CAPM Clear To Send
(CTS)7 - Signal Ground8 To CAPM Carrier Detect (CD)20 From CAPM Data Terminal
Ready (DTR)
Note that the CAPM uses RTS/CTS hardwarehandshaking. If not supported by the master then a loopback is required at the CAPM end of thecommunications link.
6.2.2 RS-232 Character Definitio nRS-232 characters are 8 bit, 1 stop bit, no parity
6.2.3 RS-232 Configuration Para metersThe following communications configuration pages allowthe user to specify parameters required for operation ofthe physical link between the recloser and the masterstation.
-------- DNP Communications 1 ------SP8 RS-232 RUNNINGPre-Tx 250ms Post-Tx 35msBaud 9600
-------- DNP Communications 2 ------SDialing DISABLEDPre-amble DISABLED First Char 0x55Repeat First 3 Last Char 0xFF
-------- DNP Communications 3 ------SDCD Ignore CA Delay 1000msTx Delay 0ms
None of these fields are configurable via CSS if ‘DNP V3.00’ communications is selected.Parameter Description
OFFP8 RS-232
P10 V23FSK
Port SelectionThis field selects the communications medium the DNP V3.00 protocol uses for transmission.• When OFF is selected, the protocol handler is disabled.• When P8 RS –232 is selected, the protocol uses the P8 serial port for all data. Also, the DNP
Communications 1 and 2 pages are automatically updated to reflect relevant RS-232 data as detailedbelow.
• When P10 V23 FSK is selected, the protocol uses the built in V23 modem on P10. Also, the DNPCommunications 1 and 2 pages are automatically updated to reflect relevant FSK data. Refer to section6.3 for the P10 configuration details.
Range: OFF, P8 RS-232, P10 FSK V23Factory default is P8 RS – 232
RUNNING
INACTIVE
Protocol StatusIndication of the current status of the communications. (Display only)• RUNNING means that the port has been seized and the protocol handler is running.• INACTIVE means that the protocol handler has been disabled via the OFF state above or has been
unable to lock onto a communication port. This is usually caused by another application already havingexclusive access to the port.
Range: INACTIVE, RUNNINGPre-Tx Pre-Transmission Period
The time delay between asserting RTS to when the message starts.Note: CTS must be asserted for transmission to occur else message is held until it is asserted.
Range: 0 to 1000 ms.Factory default is 250 ms
Siemens Power Transmission & Distribution, Inc. 18
Parameter DescriptionPost-Tx Post-Transmission Period
The time after the last character is sent before RTS is negated.
Range: 0 to 1000 ms.Factory default is 10 ms
Baud Communications Baud Rate
Range: 300, 1200, 2400, 4800, 9600 or 192001 baud.Factory default is 9600 Baud
DialupNumber
DialingDISABLED
PSTN Dial Up NumberThe PSTN number that the protocol handler will call when it needs to send an Unsolicited response. Thisfield supports a maximum of 18 digits.If this field is set to Dialing DISABLED then the protocol will not try to dial the modem.
Factory is Dialing DISABLED with default number field blankPre-amble
ENABLEDDISABLED
Preamble UsageDetermines whether the protocol transmits some preamble characters prior to the start of a protocolmessage. The message itself is not otherwise modified. Some modems require these characters to assistwith message reception and synchronization at the master station. Start of frame filtering at the masterstation ensures identification of the protocol message.ENABLED means that the preamble characters are transmitted prior to a protocol message.DISABLED means that protocol message are transmitted without any preamble characters.
Range: ENABLED, DISABLEDFactory default is DISABLED
First Char Preamble First CharacterThis is the first character to be transmitted as a preamble. The character is specified by entering its ASCIIcode in hexadecimal format.
Range: is 0 to FF hexadecimal.Factory default is 0x55
RepeatFirst
Number of Preamble First CharactersThis is the number of times the first character will be repeated as part of the preamble.Eg if all preamble settings are at default values then the preamble sent is 0x55, 0x55, 0x55, 0xFF
Range: 0 to 20.Factory default is 3
Last Char Last Preamble CharacterThis is the last char that will be sent as part of the preamble. The character is specified by entering its ASCIIcode in hexadecimal format.
Range: is 0 to FF hexadecimal.Factory default is 0xFF
DCDIgnore
DCD Don’tIgnore
DCD UsageIf the modem does not support a Data Carrier Detect (DCD) signal this parameter should be set to DCDIgnore.
Even if the modem does support a DCD signal this parameter is usually set to DCD Ignore. This is becausemost point-point systems using conventional modems run as full duplex so that the DCD is always assertedduring normal operation.
When set to this mode, the protocol uses any received data to build an incoming packet irrespective of DCDinput signal. Also the protocol will transmit irrespective of the DCD input signal.If the modem supports a Data Carrier Detect (DCD) signal this parameter can be set to DCD Don’t Ignore.When set to this mode, the protocol will only read data and build an incoming protocol packet when DCD isasserted. In addition, the protocol will not transmit when DCD is asserted. This is necessary for multi-droppedsystems or ones shared with voice users or some radio-modems.
Range: DCD Ignore, DCD Don’t IgnoreFactory default is DCD Ignore
CA Delay Collision Avoidance DelayOn a multidrop communications link this parameter can be used to provide priority access.If the CAPM prepares to transmit and finds the link busy (DCD asserted), it waits until it is no longer busy,then waits a back off time as follows:
1 19200 baud is only available with CAPM5 controllers.
Siemens Power Transmission & Distribution, Inc. 19
Parameter DescriptionBack off time = CA Delay + ([random delay with range 0.0 to 1.0] x CA Delay)
After the back off time the device tries again. If still unsuccessful then the CAPM will continue in an indefiniteloop until successful.If radio modems are used then Tx Delay must be configured to a value slightly larger than the masterstation’s post-transmission time. This is necessary to ensure that the incoming message’s tail does nottrigger back off operation.If the DCD usage is configured to DCD Ignore then the back off time is disabled.
Range: 0 to 180000 millisecondsFactory default is 1000 ms
Tx Delay Transmission DelayAdditional time in milliseconds between receiving a request and sending the response.This field is used when the master station requires time to disable its transmitter. If collision avoidance delay,CA Delay, is configured then this field should be set to a value slightly greater than the master station’s post-transmission period.
Range: 0 to 65535 ms.Factory default is 0 ms
Siemens Power Transmission & Distribution, Inc. 20
6.2.4 Carrier DetectWhen “DCD Ignore” is configured, the Data CarrierDetect (DCD) input is not used. All data is received andtransmitted irrespective of the state of the DCD signal.When “DCD Don’t Ignore” is configured, the CAPM willnot begin to transmit a packet until DCD is negated, andwill only receive data when DCD is asserted. Refer tothe DCD Usage parameter description for moreinformation.When “Dialup Number” is configured, the DCD input isused exclusively by the dialing modem and the “DCDIgnore/Don’t Ignore” parameter is not used. Refer tosection 6.2.7 for more information.6.2.5 Transmitting a DNP Packe tTransmission of a DNP packet follows the steps below1. RTS line is asserted2. CAPM waits until the pre-transmission delay expires
(Delay set from the panel) and CTS is asserted.3. The preamble is transmitted (Optional panel setting).4. Checks CTS is asserted.5. The DNP packet is transmitted6. Waits until the post-transmission delay expires (Delay
set from the panel)7. RTS is negated6.2.6 DTRDTR is asserted by the protocol handler at power-up orupon P8 selection.6.2.7 Dialing Modem SupportThe CAPM can support a Hayes compatible modem withdialing / auto answer capability on port P8 for remote dialup access using DNP. The protocol uses dialing modemsupport mode if the dialing field is ‘DNP Communications2’ shows a telephone number. If modem is active thenthe DCD Ignore parameter is ignored. The protocolhandler uses the state of the DCD input from the modemto determine the modem’s status. If DCD is asserted themodem is online. If DCD is negated the modem isconsidered offline.The modem must be setup to auto answer any call. Itshould not return results codes nor echo commands.When the modem is online (DCD asserted) the protocolwill examine the data being received and decode it asDNP packets.When the protocol needs to transmit data it will firstcheck if the modem is currently online. If the modem isonline the protocol will send the data immediately. If themodem is offline the protocol will first dial to the masterstation.To connect to the master station the protocol handlersends “ATDT” and then the phone number setup on thestatus page above to the modem. The protocol handlerwill then wait up to 90 seconds for the modem to assertthe DCD line. If the modem fails to assert the DCD linewithin 90 seconds the current packet will be discarded.The protocol handler will try to connect again when theUnsolicited retry timer expires.
The protocol handler will hang up the modem after adelay of 30 seconds with no valid packet received ortransmitted. To hang up the modem the protocol handlerwill:-• Wait 1 second• Send “+++”• Wait 1 second• And then send “ATH”• Wait 5 secondThe protocol handler will then check to ensure themodem has negated the DCD line.If this sequence fails to disconnect the line the protocolhandler will turn the radio power supply off (AUX+) for 1minute to disconnect power from the modem and resetit.6.3 V23 FSK Communication S pecifications
6.3.1 V23 Hardware Signals
StandardCable
Type N03-530
15 Way DFemale
P10Pin
Direction Use
5 5 - Signal Ground4 4 To CAPM Receive, 10kOhm
impedanceSensitivity 0.1V to
2V pk-pk15 15 From
CAPMPress To Talk
(PTT)11 11 From
CAPMTransmit(Tx), 600Ohm impedanceLevel 2.5V pk-pk
6 6 To CAPM Busy, 10kOhmimpedance
Signal frequencies conform to V23 standard. Theprotocol only supports half duplex (i.e., receive andtransmit can not occur at the same time) when using theV23 port. Baud rate is fixed at 1200 Baud.6.3.2 V23 Configuration Parame tersThe following communications configuration pages allowthe user to specify parameters required for operation ofthe physical link between the recloser and the masterstation.
-------- DNP Communications 1 ------SP10 V23 FSK RUNNINGPre-Tx 250ms Post-Tx 35msBusy Sense LOW
Siemens Power Transmission & Distribution, Inc. 21
-------- DNP Communications 2 ------STx NORMAL Rx IDLEPre-amble DISABLED First Char 0x55Repeat First 3 Last Char 0xFF
-------- DNP Communications 3 ------SDCD Don’t Ignore CA Delay 1000msTx Delay 0ms
Parameter Description
OFFP8 RS-232
P10 V23 FSK
Port SelectionThis field selects the communications medium the DNP V3.00 protocol handler uses for transmission.• When OFF is selected, the protocol handler is disabled.• When P8 RS –232 is selected, the protocol uses the P8 serial port for all data. Also, the DNP
Communications 1 and 2 pages are automatically updated to reflect relevant RS-232 data. Refer to section6.2 for the P8 configuration details.
• When P10 V23 FSK is selected, the protocol uses the built in V23 modem on P10. Also, the DNPCommunications 1 and 2 pages are automatically updated to reflect relevant FSK data as detailed below.
Range: OFF, P8 RS-232, P10 V23 FSKFactory default is P8 RS-232
RUNNING
INACTIVE
Protocol StatusIndication of the current status of the communications. (Display only)• RUNNING means that the port has been seized and the protocol handler is running.• INACTIVE means that the protocol handler has been disabled via the OFF state above or has
been unable to lock onto a communication port. This is usually caused by another applicationalready having exclusive access to the port.
Range: INACTIVE, RUNNINGPre-Tx Pre-Transmission Period
The time delay between keying PTT to when the data is transmitted.During this period the carrier is transmitted on the Tx line.
Range: 0 to 1000 ms.Factory default is 250 ms
Post-Tx Post-Transmission PeriodThe time after the last character is sent before PTT is negated. During this period the carrier istransmitted on the Tx line.
Range: 0 to 1000 ms.Factory default is 35 ms
Busy Sense
LOWHIGH
Polarity of Busy SignalThis field determines the polarity of the input signal from the radio (P10 pin 6) that the CAPM usesas BUSY.• “LOW” means that a low input signal will assert BUSY.• “HIGH” means that a high input signal will assert BUSY.
Range: LOW, HIGHFactory default is Busy Sense LOW.
Tx NORMAL
Tx TEST
Transmission ModeThis field can be used to test the radio transmitter.• Tx NORMAL means that the protocol handler controls the radio for normal DNP transmissions.• Tx TEST means that the protocol handler will send continuous text strings of “TX TEST”. This
string is transmitted as an asynchronous message with 8 bit, no parity, 1 stop bit, 1 start bitformat.
Range: Tx NORMAL, Tx TESTFactory default is Tx NORMAL.
Rx IDLE,
BUSY Signal StatusThe status of the BUSY signal into the CAPM (Display only)• “Rx IDLE” indicates that the signal is in the ‘not BUSY’ state.
Siemens Power Transmission & Distribution, Inc. 22
Parameter DescriptionRx BUSY • “Rx BUSY Asserted” indicates that the signal is in the ‘BUSY’ state. This usually means that the
radio squelch has opened.
Range: Rx IDLE, Rx BUSYPre-ambleENABLED
DISABLED
Preamble Usage• When ENABLED the protocol handler inserts a string of characters in front of a message
packet. The message frame is otherwise not affected. Start of frame filtering at the masterstation will ensure identification of the message. This parameter is sometimes required formodems to aid with their keying.
• When DISABLED the protocol handler does not insert any preamble characters.
Range: ENABLED, DISABLEDFactory default is DISABLED
First Char Preamble First CharacterThis is the first character to be transmitted as a preamble. The character is specified by entering itsASCII code in hexadecimal format.
Range: is 0 to FF hexadecimal.Factory default is 0x55
Repeat First Number of Preamble First CharactersThis is the number of times the first character will be repeated as part of the preamble.Eg if all preamble settings are at default values then the preamble sent is 0x55, 0x55, 0x55, 0xFF
Range: 0 to 20.Factory default is 3
Last Char Last Character of PreambleThis is the last char that will be sent as part of the preamble. The character is specified by enteringits ASCII code in hexadecimal format.
Range: is 0 to FF hexadecimal.Factory default is 0xFF
DCD Ignore
DCD Don’tIgnore
DCD Usage• The “DCD Ignore” mode is used when there is no busy signal available. eg A twisted pair link.
To operate in this mode the ‘Busy Sense’ needs to be set to HIGH so that the receiver is busy atall times. When set to this mode, the protocol uses any received data to build a DNP packet.The protocol is able to transmit at any time.
• The “DCD Don’t Ignore” mode is the normal operating mode for radio systems that have a busysignal available. When set to this mode, the protocol will only read data and build a DNP packetwhen busy is asserted. Also, the protocol will not transmit when busy is asserted. This reducesclashes with voice users.
Factory default is DCD Don’t IgnoreCA Delay Collision Avoidance Delay
On a multidrop communications link this parameter can be used to provide priority access.If the CAPM prepares to transmit and finds the link busy (DCD asserted), it waits until it is no longerbusy, then waits a back off time as follows:
Back off time = CA Delay + ([random delay with range 0.0 to 1.0] x CA Delay)
After the back off time the device tries again. If still unsuccessful then the CAPM will continue in anindefinite loop until successful.If radio modems are used then Tx Delay must be configured to a value slightly larger than themaster station’s post-transmission time. This is necessary to ensure that the incoming message’stail does not trigger back off operation.If the DCD usage is configured to DCD Ignore then the back off time is disabled.
Range: 0 to 180000 millisecondsFactory default is 1000 ms
Tx Delay Transmission Delay
Siemens Power Transmission & Distribution, Inc. 23
Parameter DescriptionAdditional time in milliseconds between receiving a request and sending the response.This field is used when the master station requires time to disable its transmitter. If collisionavoidance delay, CA Delay, is configured then this field should be set to a value slightly greater thanthe master station’s post-transmission period.
Range: 0 to 65535 ms.Factory default is 0 ms
6.3.3 V23 Handshaking SignalsThe protocol can operate in two separate modesdepending on the state of the ‘DCD Ignore’ flag.‘DCD Don’t Ignore’
When the BUSY line gets asserted, the CAPM will scanfor a valid DNP packet. When BUSY gets negated, thenthe Rx data is no longer read. The sensing of the BUSYline can be setup on the CAPM panel to be “Busy SenseLOW” or “Busy Sense HIGH”.
The CAPM checks the status of the BUSY line beforetransmission. If the BUSY line is negated the CAPM isfree to transmit.
The CAPM then asserts the PTT line before it beginstransmission. The CAPM waits until the pre-transmissiontimer expires, then waits for the optional pre-amble to betransmitted, then immediately begins transmission. Aftertransmission, the protocol waits for the post-transmissiontimer to expire, and then negates PTT.‘DCD Ignore’.
The protocol receives any characters coming in on theRX line and attempts to decode these as DNP packets.The CAPM is free to transmit at any time. The CAPMthen asserts the PTT line before it begins transmission.The CAPM waits until the pre-transmission timer expires,waits for the optional pre-amble to be transmitted, beginstransmission. After transmission, the protocol waits forthe post-transmission timer to expire, and then negatesPTT.6.4 Communication StatisticsThe communication statistics give communicationinformation, such as octets not being sent, received orprocessed or frames being incorrectly addressed. Thecommunication statistics page appears as below:
---- DNP Communication Statistics ---STx Count 946 Rx Count 582Rx Length Error 0 Rx CRC Error 0
Statistic DescriptionTx Count Transmission Message Count
The number of DNP datalinkmessages transmitted from thisrecloser into the DNP link.Range: 0 to 32768
Rx Count Receive Message CountThe number of DNP datalinkmessages received by thisrecloser from the DNP link.Range: 0 to 32768
RxLengthError
Receive Message Length ErrorCountThe number of message packetsreceived with a length errorRange: 0 to 999
Rx CRCError
Receive Message CRC ErrorCountThe number of message packetsreceived with a CRC errorRange: 0 to 999
All of the above counters are zeroed when: the CAPM isreset; a DNP cold or warm restart message is received;or a configuration parameter is changed that triggers aDNP handler warm restart; or the reset all button isselected in CSS.
Any field can be cleared via the operator control panelby selecting it and pressing either the left or right keys.All communication statistic parameters are not passwordprotected.
Siemens Power Transmission & Distribution, Inc. 24
Appendix A Protocol Timings
Initialization TimeThe protocol handler will not respond to master station requests for about 10 seconds after power up while it waitsfor the CAPM database to be initialized and for high priority boot up tasks to be completed.
Turnaround TimeThe turnaround time for the protocol, from the end of receiving a message until the start of the pre-transmissiontime, is typically < 40 milliseconds with a range of 5 to 100 milliseconds.
Latency of DataThe protocol task examines the real-time database every 500 ms to see if anything has changed and to constructthe underlying protocol database which is sent to the master station. This introduces a delay between the actualevent and updating the protocol database of up to 500 milliseconds. This is the data latency.
Accuracy of Time Tags• For points tagged to 500-millisecond accuracy, the time tag accuracy is –10 / +500 ms relative to CAPM
processor clock.• For points tagged to 10-millisecond accuracy, the points correspond to those in the operator panel event record.
Siemens Power Transmission & Distribution, Inc. 25
Appendix B DNP V3.00 Device Profile
The CAPM implementation complies with the DNP V3.00 Subset Definitions document. Additionalimplementation information is given in this section.
The DNP V3.00 device profile defines the mapping of all data points used, in the standard format recommendedby the DNP users group.
Siemens Power Transmission & Distribution, Inc. 26
DNP V3.00 Device Profile
DNP V3.00 Device Profile
Vendor Name: Siemens PT&D Raleigh, NC
Device Name: CAPM-4 Controller
Highest DNP Level Supported For Requests: 2 For Responses: 2
Device Function: Slave
Conforms to DNP V3.00 level 2 subset definition requirements with many additional level 3 featuresbuilt in.These extra features include the parsing of read requests (FC 1) for the following objects and/orqualifiers:• Binary Input (Object 1 Variations 0 Qualifiers 00, 01,07,08,17,28)• Binary Input (Object 1 Variation 1 Qualifiers 00, 01, 06,07,08,17,28)• Binary Output (Object 10 Variation 0 Qualifiers 00, 01, 07, 08, 17, 28)• Binary Output (Object 10 Variation 2, Qualifiers 00, 01, 06, 07, 08, 17, 28)• Binary Counter (Object 20 Variation 6 Qualifiers 00, 01, 06, 07, 08, 17, 28)• Frozen Counter (Object 21 Variation 10 Qualifiers 00, 01, 06, 07, 08, 17, 28)• Analog Input (Object 30 Variation 0, Qualifiers 00, 01, 07, 08, 17, 28)• Analog Input (Object 30 Variations 1, 2, 3, 4 Qualifiers 00, 01, 06,07,08,17,28)• Analog Change Event (Object 32 Variations 1, 2, 3, 4 Qualifiers 06, 07, 08)• Analog Input Deadband (Object 34 Variations 1, 2, Qualifiers 00, 01, 06,07,08,17,28)• Analog Output Status (Object 40 Variation 1, 2 Qualifiers 00, 01,07,08,17,28)• Analog Output Block (Object 41 Variation 1, 2 Qualifiers 00, 01, 07, 08, 17, 28)
Also, the following functions are included:• Function codes 7, 8, 9, 10 for Binary Counters (Object 20 Variation 6)• Function code 14 - Warm Restart• Function code 20 - Enable Unsolicited Messages• Function code 21 - Disable Unsolicited Messages• Function code 22 - Assign Data Classes
Maximum Data Link Frame Size (octets): Transmitted: 292 Received: 292
Maximum Application Fragment Size (octets): Transmitted: 2048 Received: 249
Maximum Data Link Retries: Configurable 0..255
Maximum Application Layer Retries: None
Requires Data Link Layer Confirmation:
Configurable, 3 settings Never, Always, Sometimes (on multi frame fragments only)
Requires Application Layer Confirmation:
Sometimes (only when reporting event data or when sending multifragment responses)
Siemens Power Transmission & Distribution, Inc. 27
Timeouts while waiting for: Data Link Confirm: Configurable Application Confirm: Configurable Need Time Delay: Configurable (on power up, an additional device start up delayapplies. Refer to appendix A). Select Operate Delay: Configurable Unsolicited Response Notification: Configurable Unsolicited Response Retry Delay: ConfigurableTimeouts not supported: Complete Appl. Fragment: None Complete Appl Response: NoneExecutes Control Operations: WRITE Binary Outputs: Never SELECT/OPERATE: Always DIRECT OPERATE: Always DIRECT OPERATE - NO ACK: Always Max number of controls that can operate simultaneously: 1 Pattern control operations are not supported
WRITE Analog Outputs: Never SELECT/OPERATE: Always DIRECT OPERATE: Always DIRECT OPERATE - NO ACK: Always Max number of outputs that can operate simultaneously: 1 Maximum Select/Operate Delay Time: Configurable 1 .. 65535 ms
Count > 1: Never Pulse On: Always Pulse Off: Always Latch On: Always Latch Off: Always Trip/Close: Sometimes Raise/Lower: Never Queue: Never Clear Queue: Never
Pulse On and Pulse Off times are ignored
Reports Binary Input Change Events whenno specific variation requested:
Configurable with / without time
Reports time tagged Binary Input ChangeEvents when no specific variation requested:
Binary Input Change with TimeSends Unsolicited Responses: Enable/Disable Unsolicited supported
Static Data in Unsolicited Responses:Never
Supports Collision Avoidance:Configurable
Collision Avoidance Detection Method:DCD
Default Counter Object:Default Object: 20Default Variation: 06
Counter Roll Over at: 65535
Sends Multi-Fragment Responses: Yes
Siemens Power Transmission & Distribution, Inc. 28
Appendix C DNP V3.00 Implementation Table
CAPM DNP V3.00 Implementation Table
OBJECT REQUEST(slave must parse)
RESPONSE(master must parse)
Obj Var Description Func Codes(dec)
Qual Codes(hex)
FuncCodes
QualCodes(hex)
00, 01 061 0 Binary Input - All Variations 1 22
07, 08, 17, 28
N/A N/A
00, 011 1 Binary Input 1 00, 01, 06,07, 08,17, 28
12917, 28Note 400, 011 2 Binary Input With Status 1 00, 01, 06,
07, 08,17, 28
129
17, 28Note 4
2 0 Binary Input Change - AllVariations
1 06, 07, 08 N/A N/A
2 1 Binary Input Change without Time 1 06, 07, 08 129, 130 17, 282 2 Binary Input Change with Time 1 06, 07, 08 129, 130 17, 282 3 Binary Input Change with Relative
Time1 06, 07, 08 N/A N/A
00, 01 0610 0 Binary Output - All Variations 107, 08, 17, 28
N/A N/A
00, 0110 2 Binary Output Status 1 00, 01, 06,07, 08,17, 28
12917, 28Note 4
00, 01, 07, 0812 1 Control Relay Output Block 3, 4, 5, 617, 28
129 Echo ofrequest
00, 01 0620 0 Binary counter – All Variations 1, 7, 8, 9, 1007, 08, 17, 28
N/A N/A
00, 0120 1 32 Bit Binary Counter with flag 1 00, 01, 06,07, 08,17, 28
12917, 28Note 400, 0120 2 16 Bit Binary Counter with flag 1 00, 01, 06,
07, 08,17, 28
12917, 28Note 400, 0120 5 32 Bit Binary Counter without flag 1 00, 01, 06,
07, 08,17, 28
12917, 28Note 400, 0120 6 16 Bit Binary Counter without flag 1 00, 01, 06,
07, 08,17, 28
12917, 28Note 4
00, 01 0621 0 Frozen Counter – All variations 1 2207, 08, 17, 28
N/A N/A
00, 0121 1 32 Bit Frozen Counter with flag 1 00, 01, 06,07, 08,17, 28
129
17, 28Note 4
Siemens Power Transmission & Distribution, Inc. 29
OBJECT REQUEST(slave must parse)
RESPONSE(master must parse)
Obj Var Description Func Codes(dec)
Qual Codes(hex)
FuncCodes
QualCodes(hex)
00, 0121 2 16 Bit Frozen Counter with flag 1 00, 01, 06.07, 08,17, 28
129
17, 28Note 400, 0121 9 32 Bit Frozen Counter without flag 1 00, 01, 06.
07, 08,17, 28
12917, 28Note 400, 0121 10 16 Bit Frozen Counter without flag 1 00, 01, 06.
07, 08,17, 28
12917, 28Note 4
00, 01 0630 0 Analog Input - All Variations 1 2207, 08, 17, 28
N/A N/A
00, 0130 1 32 Bit Analog Input 1 00, 01, 06,07, 08,17, 28
129
17, 28Note 400, 0130 2 16 Bit Analog Input 1 00, 01, 06,
07, 08,17, 28
129
17, 28Note 400, 0130 3 32 Bit Analog Input without Flag 1 00, 01, 06,
07, 08,17, 28
129
17, 28Note 400, 0130 4 16 Bit Analog Input without Flag 1 00, 01, 06,
07, 08,17, 28
129
17, 28Note 4
32 0 Analog Change Event - AllVariations
1 06, 07, 08 N/A N/A
32 1 32 Bit Analog Change Eventwithout Time
1 06, 07, 08 129, 130 17, 28
32 2 16 Bit Analog Change Eventwithout Time
1 06, 07, 08 129, 130 17, 28
32 3 32 Bit Analog Change Event withTime
1 06, 07, 08 129, 130 17, 28
32 4 16 Bit Analog Change Event withTime
1 06, 07, 08 129, 130 17, 28
34 0 Analog Input ReportingDeadband – All VariationsNote 6
1 00, 01, 06,07, 08,17, 28
N/A N/A
34 1 16 bit Analog Input DeadbandreportingNote 6
1, 2 00, 01, 06,07, 08,17, 28
129, 130 17, 28
34 2 32 bit Analog Input DeadbandreportingNote 6
1, 2 00, 01, 06,07, 08,17, 28
129, 130 17, 28
00, 01 0640 0 Analog Output Status - AllVariations
107, 08, 17, 28
N/A N/A
Siemens Power Transmission & Distribution, Inc. 30
OBJECT REQUEST(slave must parse)
RESPONSE(master must parse)
Obj Var Description Func Codes(dec)
Qual Codes(hex)
FuncCodes
QualCodes(hex)
40 1 32 Bit Analog Output Status 1 00, 01, 06,07, 08,17, 28
129 00, 0117, 28Note 400, 0140 2 16 Bit Analog Output Status 1 00, 01, 06,
07, 08,17, 28
129
17, 28Note 4
41 1 32 Bit Analog Output Block 3, 4, 5, 6 00, 01, 07, 08,17, 28
129 Echo ofrequest
00, 01, 07, 08,41 2 16 Bit Analog OutputBlock 3, 4, 5, 617, 28
129 Echo ofrequest
50 0 Time and Date 1 00, 01, 0607, 08,17, 28,
129 00, 0117, 28Note 4
00, 01, 0608, 17, 28
2
07(quantity = 1)
129 00, 0117, 28Note 4
50 1 Time and Date
1 00, 01, 0608, 17, 28,07(quantity = 1)
129 00, 0117, 28Note 4
52 2 Time Delay Fine N/A N/A 129 07,(quantity 1)
160 1 Class 0 Data20,,21
06 N/A N/A
160 2 Class 1 Data20,,21, 22
06, 07, 08 N/A N/A
160 3 Class 2 Data20, 21, 22
06, 07, 08 N/A N/A
160 4 Class 3 Data20, 21, 22
06, 07, 08 N/A N/A
80 1 Internal Indications 2 00 index = 7 N/A N/A112 Virtual Terminal Output Block
Note 52 00, 01, 06,
08, 17, 28N/A N/A
113 Virtual Terminal Event Data 1 06, 07, 08 129 17, 28No Object 13 14 23 N/A N/A N/A
Note1. All shaded areas are the additional level 3 or above function, objects, variations and/or qualifiers supported by
CAPM.2. Bold italics response function codes represent CAPM default objects. These are the object variations that the
CAPM will issue as in its response to an event (class 1, 2, 3) poll, an integrity (class 1, 2, 3, 0) poll, in a responseto a variation 0 read request, or in an unsolicited response message. Where more than one data object variationis highlighted then default object can be configured. Selection of default objects is explained in section 5.3.
3. All Request and Response options marked N/A are Not Applicable.
Siemens Power Transmission & Distribution, Inc. 31
4. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent withqualifiers 17 or 28, respectively. Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08,will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are alwaysresponded.)
5. The Virtual Terminal Objects (112 and 113) are used to transport SOS data between CSS and the CAPM.No other data is supported.
6. A write with an analog input deadband value of zero will be rejected. The response will have the ‘parameterin qualifier, range or data field not valid or out of range’ internal indicator bit (IIN2-2) set.
DNP Function Codes
Request ResponseFunctionCode
Description FunctionCode
Description FunctionCode
Description
1 Read 9 Freeze and Clear 129 Response2 Write 10 Freeze and Clear, No Ack3 Select 13 Cold Restart (Note 1)
130 UnsolicitedResponse
4 Operate 14 Warm Restart (Note 1)5 Direct Operate 20 Enable Unsolicited Msgs6 Direct Operate, No Ack 21 Disable Unsolicited Msgs7 Immediate Freeze 22 Assign Class8 Immediate Freeze, No Ack 23 Delay Measurement
Note1. When a cold or warm restart command is received by the CAPM it will restart the DNP3 protocol handler only. The
CAPM itself does not restart.It is recommended by the DNP User Group that master stations do not ask for a data link acknowledgement nor anapplication confirm on restart commands (refer to “Cold/Warm Restart Sequence”, Technical Bulletin 9701-003)The CAPM reports a time object of 500ms for both restart types. The master station should not initiate any messagesequences for this period. However, if the CAPM has unsolicited messages configured ON then it will automaticallyestablish communications on restart. This may be within the 500ms period.
DNP Qualifiers
Qualifier(Hex)
Use in a Request Use in a Response
00, 01 A range of static points, or a single point with apoint number.Object headers use either 8 bit (Q=00) or 16 bit(Q=01) start and stop range indices.
Static Objects
06 All points.Object headers and data sizes are determined byCAPM configured parameters.
Not valid
07, 08 A limited quantity of events or a single point withno number (eg Time and Date).Object headers have either 8 bit quantity fields(Q=07) or 16 bit quantity fields (Q=08).
A single point with no number (eg Time and Date)
17, 28 Controls (usually one or more unrelated points)Object headers have either 8 bit quantity field with8 bit indices (Q=17) or 16 bit quantity field with 16
Event objects (usually one or more unrelatedpoints)
Siemens Power Transmission & Distribution, Inc. 32
Qualifier(Hex)
Use in a Request Use in a Response
bit indices (Q=28)
DNP Internal Indication Bits
The following DNP response internal indication bits are not supported.• IIN1-6 Device trouble. For system health status refer to the ‘Abnormal Operator Conditions’ binary input point that
is described in Appendix D.• IIN2-4 Request already executing.• IIN2-5 Corrupt Configuration
DNP Object Status Flags
Binary Inputs.Only the on-line and status bits are supported. This means that, depending upon the point’s status, the reported flag willalways be either 0x01 or 0x81 since the CAPM always regards its points as on-line.Binary Outputs.Only the on-line and status bits are supported. Refer to the relevant binary output appendix for on/offline conditioninformation.Analog InputsOnly the on-line and over-range bits are supported. Since the CAPM always regards its points as on-line, the flag willalways be reported as either 0x01 or 0x21.
DNP Control OperationThe success or failure of control operation is returned in the control response message. The CAPM support forcontrol success is shown below.
ResponseStatus Value
CAPM Control Response Description
0 Control request accepted1 Control request denied. Select/Operate timed out. The time out parameter is configurable.2 Control request denied. Operate without select message.3 Control request denied. Formatting error4 Control request denied. Control operation not supported
Examples:• Trip control sent to a point that supports only Pulse or Latch operations. The supported
operations are indicated on a per point basis in the table in Appendix H or 0.• The binary output (or analog output) point number is out of range.• The analog output value is out of range.
5 Control request denied. Already Active6 Control request denied. Control rejected by CAPM because of an underlying condition
preventing the action. These conditions are indicated on a per point basis in the table inAppendix H or 0.
All binary output points have a matching binary input status point. The master station must always use thecorresponding binary status for the control to verify the success of the action.
Siemens Power Transmission & Distribution, Inc. 33
DNP Technical Bulletins
TechnicalBulletin
Description Manual Version Comment
2000-004 Application Layer Confirmation Messages N00-324R202000-003 Change Management - Note 12000-002 Control Retries N00-324R282000-001 Sequential File Transfer Objects - Not Applicable. Note 29912-003 Broadcast Message Confirmation and
Address ReservationN00-324R33
9912-002 Unsolicited Event Reporting; RetryConfiguration
N00-324R28
9905-001 Qualifier Code 11 - Not Applicable. Note 29809-001 Analog Input Reporting Deadband N00-324R289804-008 Unissued Object and Variation Numbers N00-324R209804-007 Clarification of Collision Avoidance
ProcedureN00-324R28
9804-006 Analog Object Floating Point Variations - Not Applicable. Note 29804-005 8 Bit Unsigned Integer Object 102 - Not Applicable. Note 29804-004 Virtual Terminal Objects 112 and 113 N00-324R279804-003 Recommended Layer Terminology N00-324R209804-002 DNP Confirmation and Retry Guidelines N00-324R209804-001 Rules for Synchronising Application
Sequence NumbersN00-324R20
9704-007 Implementation for Reset Link Frames N00-324R209701-006 Extension of Engineering Units for
Floating Point Objects- Not Applicable. Note 2
9701-004 Octet String Objects 110 and 111 - Not Applicable. Note 29701-003 Cold/Warm Restart Sequence N00-324R209701-002 Control Relay Output Block Minimum
ImplementationN00-324R20
9701-001 Datalink Restart Recovery N00-324R20
Note:1) It is policy that all technical bulletin rules that are required for the CAPM to be DNP3 level 2 compliant are
implemented.2) The following data types are not used by the CAPM:-
• File transfer objects• String objects• Analog input floating point and analog output floating point objects• Variable arrays objects• 8 bit unsigned integer objects
Siemens Power Transmission & Distribution, Inc. 34
Appendix D ACR - Binary Input Points (Status)Time resolution is as shown. Refer to Appendix A for more information on timing. W-series, Centurion SP (single phase)Recloser, support is indicated below by a ‘Y’. If indicated as ‘N’ then value is always OFF.
The phase designation A, B, C is determined by the user, refer to the equipment manual for more information.Phase and terminal terminology is explained in section 4.4.
DNP V3.00 ImplementationStatic: Object 01 Variation 01 – Single Bit Binary InputEvent: Configurable – refer to section 5.3Request Function Code: 01 – Read
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
0 AbnormalOperatorconditions
Y 1 For any of thefollowing conditions:-• Trip or Close
Isolated,• ACR
Mechanicallylocked open (ifapplicable)
• Work TagApplied
None of the specifiedconditions are true
This flag shows that theoperator has the ACR in anabnormal state such as “worktag applied”. This means that itwill operate differently to itsnormal mode of operation.
500ms
1 ACR Tripped(open)
Y 1 ACR Tripped ACR not Tripped
2 ACR Closed Y 1 ACR Closed ACR not Closed
These are repeats of themechanism travel switches.When the ACR is disconnectedfrom the control cubicle they areboth cleared.
500ms3 Controller
ModeY 2 LOCAL control
DisabledRemote controlEnabled
LOCAL ControlEnabledRemote ControlDisabled
The CAPM is either in LOCALor Remote Controller Mode.This affects the closingcommand the permission toset/remove work tag.
500ms4 Maintenance
RequiredY 1 For any of the
following conditions:-• Battery not
normal• Capacitor charge
failure• Low power
mode• Low SF6 gas
pressure (ifapplicable)
• ACR data notvalid (includesconnection to aninvalid switch
No maintenancerequired
The CAPM has detected one ormore conditions which requiremaintenance.This point cannot become Setuntil at least five minutes afterCAPM start.
500ms
Siemens Power Transmission & Distribution, Inc. 35
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
type)• Any vacuum
interruptercontact life isless than 20%
• Mechanicalfailure
• Aux supplyovervoltage
5 Work Tag Y 2 Work Tag Applied Work Tag Removed The CAPM can have a worktag. This affects the closingcommand
500ms6 Prot A Active Y 2 Protection Group A is
activeProtection Group A is notactive
7 Prot B Active Y 2 Protection Group B isactive
Protection Group B is notactive
These flags indicate theactive protection group. Ifneither A nor B is active (eg.Because C is active) thenflags will be clear and theanalog value point must beused to determine the activegroup.
500ms8 Prot C Active Y 2 Protection Group C is
activeProtection Group C is notactive
Only one protection group isactive at any one time.
9 Prot D Active Y 2 Protection Group D isactive
Protection Group D is notactive
10 Prot E Active Y 2 Protection Group E isactive
Protection Group E is notactive
500ms
11 Prot F Active Y 2 Protection Group F isactive
Protection Group F is notactive
12 Prot G Active Y 2 Protection Group Gis active
Protection Group G isnot active
13 Prot H Active Y 2 Protection Group H isactive
Protection Group H is notactive
14 Prot I Active Y 2 Protection Group I isactive
Protection Group I is notactive
15 Prot J Active Y 2 Protection Group J isactive
Protection Group J is notactive
16 Earth / GroundProtectionEnabled
N 2 Earth / GroundProtection ON
Earth / GroundProtection OFF
500ms
17 SEF/SGFProtectionEnabled
N 2 SEF/SGF protectionON
SEF/SGF protectionOFF
500ms
18 Auto Reclose Y 2 Auto Reclose ON Auto Reclose OFF 500ms
Siemens Power Transmission & Distribution, Inc. 36
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
19 Cold Load Idle Y 2 Cold Load is Idle or isturned off.This means that thethreshold multiplier isnot being affected bythe cold loadfunction.
Cold load is NOT Idle.This means that thethreshold multiplier isbeing raised by the coldload pickup function inorder to pick up coldload.
500ms
20 High CurrentLockout
Y 2 High Current LockoutProtection ON
High Current LockoutProtection OFF
500ms
21 Loss of PhaseProtection
N 2 Loss of PhaseProtection ON
Loss of Phase ProtectionOFF
500ms
22 SequenceControl
Y 2 Sequence ControlON
Sequence Control OFF 500ms
23 Live Loadblocking
Y 2 Live Load blockingON
Live Load blocking OFF 500ms
24 Protectionenable
Y 2 Protection Enabled Protection turned OFF 500ms
25 SwitchgearFamily
Y 3 Set for Load BreakSwitch
Clear For Recloser500ms
26 Power FlowDirection
Y 2 Source X, Load I Source I, Load X The power flow direction(source/load designation) isdetermined by the user. Referto the Power Flow Directionbinary output for moreinformation
500msProtection Trip Operation FlagsThis group of points indicates what happened in the last protection sequence. For example the recloser may havetripped, closed, tripped again and locked out. Or it may have tripped, closed and stayed closed because the faultwas cleared. In both cases the flags below are set to show the causes of the trips and whether the lockout statehas been reached or not.
A set of flags is available for each trip in a protection sequence. In addition analog data is available which shows thefault currents which occurred during the sequence and the number of trips which took place (refer Appendix F)Note that a sequence starts when there is a protection trip or a sequence advance.
Most of these flags are cleared either by protocol command or when the switchgear is tripped/closed by the operator orwhen a new protection sequence starts. This data is volatile i.e. it is zeroed on CAPM software reset.
General Protection Flags27 Sequence in
ProgressY 1 Start of sequence
That is a protectiontrip or sequenceadvance hasoccurred.
End of sequence. Eitherlockout or reclaim.
This shows that a protectionsequence has started and notyet completed.Note that operator trip does notcause a “sequence in progress.Event time is the time of the tripor sequence advance.
10ms
Siemens Power Transmission & Distribution, Inc. 37
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
28 ProtectionData Valid
Y 1 End of sequence,either lockout orreclaim
This shows that the protectionsequence is over and the otherflags are set.This could be used to drive anoperator alarm at the SCADAsystem to alert him to the factthat a protection sequence hasoccurred. Note that operator tripalone does not cause a“protection data valid”Event time is the time of lockoutor reclaim.
10ms29 Single Shot
ProtectionY 1 Single Shot
Protection was activeat the time of the trip.
One flag only provided becausea single shot trip forces lockout.Event time is the time of thepickup.
10ms30 Loss Of Phase
TripY 1 Trip was caused by
Loss of PhaseProtection
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
• Any Operator Closeaction
• CAPM softwarereset (data isvolatile)
• Start of a newsequence
One flag only provided becauseLOP protection forces lockout.Event time is the time of the trip.
10ms31 Loss Of Phase
- Phase AY 1 Phase A was lost at
time of Loss of Phasetrip
Set if A Phase is lost at time ofLoss of Phase trip
10ms32 Loss Of Phase
- Phase BN 1 Phase B was lost at
time of Loss of Phasetrip
Set if B Phase is lost at time ofLoss of Phase trip
10ms33 Loss Of Phase
-Phase CN 1 Phase C was lost at
time of Loss of Phasetrip
Set if C Phase is lost at time ofLoss of Phase trip
10ms34 High Current
LockoutY 1 The high current
lockout functionforced the CAPM tolockout during thelast protectionsequence
One flag only because HighCurrent Lockout forces lockoutTime stamp as for flags above.Event time is the time of thelockout event.
10ms35 Lockout Y 1 The CAPM is in
lockoutCleared by any closeaction
This flag shows that the CAPMis in lockout. Therefore no auto-reclosing will take place.If the ACR is closed this flag willbe clear. Therefore when thisflag is clear and the ACR isclosed it indicates that theprotection sequence cleared thefault. Event time is the time ofthe trip10ms
Siemens Power Transmission & Distribution, Inc. 38
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
36 Operator Trip Y 1 The most recent tripwas caused by alocal or remoteoperator
Cleared by any closeaction
One flag only because operatortrip forces lockout.Event time is the time of the trip10ms
Protection Trip 137 Phase Over
Current TripY 0 Trip was caused by
Phase OvercurrentProtection
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
10ms
38 Earth / GroundOver CurrentTrip
N 0 Trip was caused byEarth / GroundOvercurrentProtection
• Any Operator Closeaction 10ms
39 SEF/SGFOver CurrentTrip
N 0 Trip was caused bySensitive Earth /Ground FaultProtection
• CAPM softwarereset (data isvolatile)
10ms
40 SequenceAdvance
Y 0 Sequence advanceoccurred.
• Start of a newsequence 10ms
Protection Trip 241 Phase Over
Current TripY 0 Trip was caused by
Phase OvercurrentProtection
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
10ms
42 Earth / GroundOver CurrentTrip
N 0 Trip was caused byEarth / GroundOvercurrentProtection
• Any Operator Closeaction 10ms
43 SEF/SGFOver CurrentTrip
N 0 Trip was caused bySensitive Earth /Ground FaultProtection
• CAPM softwarereset (data isvolatile)
10ms
44 SequenceAdvance
Y 0 Sequence advanceoccurred.
• Start of a newsequence 10ms
Protection Trip 345 Phase Over
Current TripY 0
Trip was caused byPhase OvercurrentProtection
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
10ms
Siemens Power Transmission & Distribution, Inc. 39
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
46 Earth / GroundOver CurrentTrip
N 0 Trip was caused byEarth / GroundOvercurrentProtection
• Any Operator Closeaction 10ms
47 SEF/SGFOver CurrentTrip
N 0 Trip was caused bySensitive Earth /Ground FaultProtection
• CAPM softwarereset (data isvolatile)
10ms
48 SequenceAdvance
Y 0 Sequence advanceoccurred.
• Start of a newsequence 10ms
Protection Trip 449 Phase Over
Current TripY 0
Trip was caused byPhase OvercurrentProtection
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
10ms
50 Earth / GroundOver CurrentTrip
N 0 Trip was caused byEarth / GroundOvercurrentProtection
• Any Operator Closeaction 10ms
51 SEF/SGFOver CurrentTrip
N 0 Trip was caused bySensitive Earth /Ground FaultProtection
• CAPM softwarereset (data isvolatile)
10ms
52 Reserved N 0 • Start of a newsequence Always 0
Accumulated Protection Trip Operation FlagsMultiple Flags can be set in this section because they accumulate all the trips in the sequence
53 Phase OverCurrent Trip
Y 1 One or more tripswere caused byPhase OvercurrentProtection
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
.10ms
54 Earth / GroundOver CurrentTrip
N 1 One or more tripswere caused byEarth / GroundOvercurrentProtection
• Any Operator Closeaction 10ms
55 SEF/SGFOver CurrentTrip
N 1 One or more tripswere caused bySensitive Earth /Ground FaultProtection
• CAPM softwarereset (data isvolatile)
10ms
56 SequenceAdvance
Y 1 One or moresequence advancesoccurred.
• Start of a newsequence 10ms
Siemens Power Transmission & Distribution, Inc. 40
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
End of Protection Flags57 Close Isolate Y 2 Close Isolate Switch
OFF/ISOLATE(i.e.Close is disabled)
Close Isolate SwitchON/ENABLE (i.e. Closeis enabled)
58 Trip Isolate Y 1 Trip Isolate SwitchOFF (i.e. Trip isdisabled)
Trip Isolate SwitchON(i.e. Trip is enabled)
Shows the state of the Trip &Close isolate switches on thecontrol panel
10ms
59 Locked Y 1 ACR Locked Open ACR not locked open Shows that the ACR ismechanically and electricallylocked in the open position. Notsupported on the N-Serieswhere it will always be zero.
10ms60 ACR Memory
Data InvalidY 2 ACR Memory Data
not validACR Memory Data Valid Shows that the CAPM has
retrieved the data from the ACRmemory. When invalid theswitchgear attributes and thegas pressure are zeroed,
500ms61 Auxiliary
SupplyFail
Y 2 Auxiliary supply hasfailed
Auxiliary supply isnormal
500ms
62 SwitchgearConnection
Y 2 Switch disconnectedfrom control cubicle.
Switch connected fromcontrol cubicle.
Shows the connection state ofthe cable between theswitchgear and the CAPM.When connected to the ACRTrip, Close and Lockedindications are valid.When disconnected from theACR data will be forced invalid
500ms63 SF6 Gas
Pressure Lowor Invalid
N 2 Gas pressure Low orInvalid
Gas Pressure Normal, orNot Known, or Not aswitchgear which hasSF6.
Only set when switchgear isconnected and ACR memorydata is valid and switchgeartype has SF6.
500ms64 Battery Supply Y 2 Battery supply not
normal.This includes :-Battery OffBattery OvervoltBattery Low Volts
Battery supply normal 500ms
65 Contacts LifeLow
Y 2 When any vacuuminterrupter contact lifeis less than 20%.
When all vacuuminterrupters have contactlife >= 20%
500ms
66 Reserved N 267 Capacitor
ChargeFailure
Y 2 Capacitor ChargeFailed
Capacitor Charge OK The Trip/Close Capacitors havefailed to charge
500ms
Siemens Power Transmission & Distribution, Inc. 41
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
68 MechanismFailure
Y 2 Mechanism Failure Mechanism OK The switchgear has failed toTrip or Close electrically
500ms69 Phase Ai Live Y 1 Phase is live Phase is dead Shows if the phase bushings70 Phase Bi Live N 1 are above or below the live line71 Phase Ci Live N 1 threshold.72 Phase Ax Live
Note 3Y 1
73 Phase Bx LiveNote 3
N 1
74 Phase Cx LiveNote 3
N 1 10ms
75 SourceVoltage Status
Y 1 All of the source side areTerminals dead
76 Load VoltageStatusNote 3
Y 1
Shows that any of thethree phases of thedesignated Sourceside or Load side arelive.
All of the load side areTerminal dead
Note that these points aredifferent to the Load/SourceLive/Dead events in the CAPMevent record
10ms77 Load Current
OnY 1 Current of 2.5A or
more is flowing in atleast one phase
Current of less than 2.5Ais flowing in all threephases
10ms
78 Loop Auto On Y 2 Loop Automation isOn
Loop Automation is Off Note 1500ms
79 Auto RestoreOn
Y 2 Auto Restore is On Auto Restore is Off Note 1500ms
80 Loop AutoTie RestoreOn
Y 2 The Tie recloser isconfigured to restoresupply in bothdirections
The Tie Recloser willonly restore supply to itsLoad side or theRecloser type is not setto Tie
Note 1, 2500ms
81 Loop AutoType Feeder
Y 2 Recloser type is setto Feeder
Recloser type is not setto Feeder
Note 1500ms
82 Loop AutoType Midpoint
Y 2 Recloser type is setto Midpoint
Recloser type is not setto Midpoint
Note 1500ms
83 Loop AutoType Tie
Y 2 Recloser type is setto Tie
Recloser type is not setto Tie
Note 1500ms
84 Reserved N Reserved Reserved
85 Reserved N Reserved Reserved86 Loop Auto
Trip RequestY 2 Set when Loop
Automation issues aTrip Request.
Normal state, cleared onnext internal scan afterset
Note 110ms
87 Loop AutoClose Request
Y 2 Set when LoopAutomation issues aClose Request.
Normal state, cleared onnext internal scan afterset
Note 110ms
Siemens Power Transmission & Distribution, Inc. 42
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
88 Dummy CircuitBreakerClosed
Y 2 DCB Closed DCB Not Closed The dummy circuit breaker isan internal point useful forSCADA system testing. Thevalue of the DCB is non-volatile.
500ms89 Automatic
ProtectionGroupSelection
N 2 APGS is ON APGS is OFF 500ms
90 SupplyOutageMeasurement
Y 2 Supply OutageMeasurement ON
Supply OutageMeasurement OFF
500ms
91 Door Open N 2 Cubicle Door Open Cubicle Door Closed This point only valid if hardwareoption installed.
10ms92 Phase Current
HI AlarmY 2 Phase Current Alarm
ONPhase Current AlarmOFF
500ms
93 Phase CurrentLOW Alarm
Y 2 Phase Current AlarmON
Phase Current AlarmOFF
500ms
94 Phase VoltageHI Alarm
Y 2 Phase Voltage AlarmON
Phase Voltage AlarmOFF
500ms
95 Phase VoltageLOW Alarm
Y 2 Phase Voltage AlarmON
Phase Voltage AlarmOFF
500ms
96 Earth CurrentHI Alarm
N 2 Earth Current HIAlarm ON
Earth Current HI AlarmOFF
500ms
97 Earth CurrentLOW Alarm
N 2 Earth Current LOWAlarm ON
Earth Current LOWAlarm OFF
500ms
98 System PowerHI Alarm
Y 2 System Power HIAlarm ON
System Power HI AlarmOFF
500ms
99 System PowerLOW Alarm
Y 2 System Power LOWAlarm ON
System Power LOWAlarm OFF
500ms
100 AuxiliarySupply Fail(Delayed)
Y 2 Auxiliary Supply hasfailed for more than120 seconds
Auxiliary Supply hasbeen restored for morethan 20 seconds
500ms
101 Most RecentTrip Phase AOvercurrent
Y 1 Set if the most recenttrip was caused by aA Phase OvercurrentProtection Trip
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
10ms
102 Most RecentTrip Phase BOvercurrent
Y 1 Set if the most recenttrip was caused by aB Phase OvercurrentProtection Trip
• Any Operator Closeaction
10ms
Siemens Power Transmission & Distribution, Inc. 43
ACR Binary Input Points (Status)
DNP
ID
Nam
e
W S
erie
s
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
tan
dTi
me
Accu
racy
103 Most RecentTrip Phase COvercurrent
Y 1 Set if the most recenttrip was caused by aC Phase OvercurrentProtection Trip
• Protection turnedON
10ms
104 InstantaneousMost RecentTrip
Y 1 The peak current forthe most recent tripwas greater than theinstantaneous setting
• At the time of nexttrip - the flags arerefreshed
10ms
105 UnderFrequency
Y 1 Under frequencyprotection ON
Under frequencyprotection OFF
Note 4. 500ms
106 OverFrequency
Y 1 Over frequencyprotection ON
Over frequencyprotection OFF
Note 4. 500ms
107 NormalFrequencyClose
Y 1 Enable NormalFrequency Closeprotection ON
Enable NormalFrequency Closeprotection OFF
Note 4. 500ms
108 Source DeadProtection
Y 1 Source DeadProtection ON
Source Dead ProtectionOFF
Note 5 500ms
109 Source DeadLockout
Y 1 Set if a lockoutcaused by the ‘DeadLockout’ featureoccurred.
Cleared by:• protocol command• any operator close
or operator trip. Thisincludes remotecontrol commands.• Start of a new
sequence.
Note 5 10ms
110 ork Tag Trip Y 1 Work Tag Protectionwas active at the timeof the trip.
All fault flags are clearedby one of the followingactions :-• “Reset Fault Flags
and Currents”protocol controlcommand
• Any Operator Closeaction
• CAPM softwarereset (data isvolatile)
• Start of a newsequence
One flag only provided becausea work tag trip forces lockout.Event time is the time of thepickup.
10ms
110-130 Reserved
Note:1. These point are only valid when the Loop Automation option is enabled for the current configuration and are otherwise
always reported as OFF (‘0’).2. The power flow direction (source/load designation) is determined by the user. Refer to the ‘Power Flow Direction’
binary input for status and binary output for control.3. Not available on standard U-series ACR without external CVTs, value will always be 0.4. Not available on CAPM4 controllers5. Only available in Version 26 onwards.
Siemens Power Transmission & Distribution, Inc. 44
Appendix E ACR - Analog Input Points (Status - Small Set)This is the reduced set of analog status points available from the CAPM. All analog points have 500ms accuracy timetags. Refer to Appendix A for more information on timing.All analogs in the small analog data set can fit in a signed 16-bit DNP data object except where noted.Centurion SP (W series) support is indicated below by a ‘Y’. If indicated as ‘N’ then value is always 0.The phase designation A, B, C is determined by the user, refer to the equipment manual for more information.Phase and terminal terminology is explained in section 4.4.
DNP V3.00 ImplementationStatic: Configurable – Object 30 Variation 1, 2, 3, or 4 (refer to section 5.3)Event: Configurable – Object 32 Variation 1, 2, 3, or 4 (refer to section 5.3)Deadband: Configurable – Object 34 Variation 1, 2 (refer to section 5.3)Request Function Code: 01 – Read
ACR Analog Input Points (Small)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
Line Currents and System Power0 A Current Y 0 16000 1 A 10 A. 11 B Current N 0 16000 1 A 10 A. 12 C Current N 0 16000 1 A 10 A. 13 Earth / Ground Current N 0 16000 1 A 5 A. 14 System kVA Note 2 Y 0 1.9GVA 1 kVA 250 kVA. 15 System kVAR Note 2 Y 0 1.9GVAR 1 kVAR 250 kVAR. 16 Operations Counter Y 0 65535 1
Operation1Operation
2
Cumulative Protection Sequence DataThese points show all sources that record a max current event in the event log during a protectionsequence. If the same source has more than one max current event then the value in the point will bethe max current from the last trip of the sequence.All fault currents are cleared to zero by one of the following actions:-
• “Reset Fault Flags and Currents” protocol control command• Any Operator Close action• CAPM reset (data is volatile)• Start of a new sequence
7 A Fault Current – Written onan A-Max event.
Y 0 16000 1A 1A 1
8 B Fault Current – Written ona B-Max event.
N 0 16000 1A 1A 1
9 C Fault Current – Writtenon a C-Max event.
N 0 16000 1A 1A 1
10 Earth / Ground FaultCurrent - Written on a G-Max event. This includesSEF/SGF Fault currents.
N 0 16000 1A 1A 1
11 During a protectionsequence the valueincrements indicating thecurrent trip or sequenceadvance.After a protection sequencethe final trip or sequenceadvance that occurred.
Y 1 4 1 1 1
Siemens Power Transmission & Distribution, Inc. 45
ACR Analog Input Points (Small)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
12 Protection Group that wasin service at the start of thesequence0 = Group A1 = Group B…9 = Group J
Y 0 9 1 1 1
Voltage MeasurementsVoltage measurements are provided for all terminals with voltage measurements. This varies depending uponthe model of ACR.All x side voltages are not available in standard U-series ACR without external CVTs. Value always zero.The source/load designation of the voltages is determined by the user. Refer to the ‘Power Flow Direction’binary input for status and binary output for control.
13 Ai Phase-(Earth / Ground)Voltage
Y 0 30000 1 V 100 V. 2
14 Bi Phase-(Earth / Ground)Voltage
N 0 30000 1 V 100 V. 2
15 Ci Phase-(Earth / Ground)Voltage
N 0 30000 1 V 100 V. 2
16 Ax Phase-(Earth / Ground)Volts Note 3
Y 0 30000 1 V 100 V. 2
17 Bx Phase-(Earth / Ground)Volts Note 3
N 0 30000 1 V 100 V. 2
18 Cx Phase-(Earth / Ground)Volts Note 3
N 0 30000 1 V 100 V. 2
19 to 69 Reserved
Note1. The deadband for all analog points can be configured, refer section 5.3.5 for more information.2. These points may exceed the 16 bit limit and can be obtained using 32 bit analog input objects.3. Not available on standard U-series ACR without external CVTs, value will always be 0.
Siemens Power Transmission & Distribution, Inc. 46
Appendix F ACR - Analog Input Points (Status – Full Set)This is the complete set of analog status points available from the CAPM. All analog points have 500ms resolution timetags. Refer to Appendix A for more information on timing. All analogs in the full analog data set can fit in a signed 16-bitDNP data object except where noted.
Centurion SP (W-series) support is indicated below by a ‘Y’. If indicated as ‘N’ then value is always 0.The phase designation A, B, C is determined by the user, refer to the equipment manual for more information.Phase and terminal terminology is explained in section 4.4.
DNP V3.00 ImplementationStatic: Configurable – Object 30 Variation 1, 2, 3, or 4 (refer to section 5.3)Event: Configurable – Object 32 Variation 1, 2, 3, or 4 (refer to section 5.3)Deadband: Configurable – Object 34 Variation 1, 2 (refer to section 5.3)Request Function Code: 01 – Read
ACR Analog Input Points (Full)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
System Line Currents and Power0 A-Phase Current Y 0 16000 1 A 10 A. 1
1 B-Phase Current N 0 16000 1 A 10 A. 1
2 C-Phase Current N 0 16000 1 A 10 A. 1
3 (Earth / Ground) Current N 0 16000 1 A 5 A. 14 System kVA Note 2 Y 0 1.9GVA 1 kVA 250 kVA. 15 System kVAR Note 2 Y 0 1.9GVAR 1 kVAR 250
kVAR.1
6 Operations Counter Y 0 65535 1Operation
1Operation
2
Cumulative Protection Sequence DataThese points show all sources that record a max current event in the event log during aprotection sequence. If the same source has more than one max current event then the value inthe point will be the max current from the most recent trip of the sequence. All fault currents arecleared to zero by one of the following actions:-
• “Reset Fault Flags and Currents” protocol control command• Any Operator Close action• CAPM reset (data is volatile)• Start of a new sequence
7 A Fault Current – Writtenon an A-Max event.Note 10
Y 0 16000 1A 1A 1
8 B Fault Current – Writtenon a B-Max event.Note 10
N 0 16000 1A 1A 1
9 C Fault Current – Writtenon a C-Max event.Note 10
N 0 16000 1A 1A 1
10 Earth / Ground FaultCurrent - Written on a G-Max event. This includesSEF/SGF Fault currents.
N 0 16000 1A 1A 1
Siemens Power Transmission & Distribution, Inc. 47
ACR Analog Input Points (Full)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
11 During a protectionsequence the valueincrements indicating thecurrent trip or sequenceadvance.After a protectionsequence the final trip orsequence advance thatoccurred.
Y 1 4 1 1 1
12 Protection Group thatwas in service at the startof the sequence0 = Group A1 = Group B…9 = Group J
Y 0 9 1 1 1
Voltage MeasurementsVoltage measurements are provided for all terminals with voltage measurements. This variesdepending upon the model of ACR.All x side voltages are not available in standard Centurion U-series ACR without external CVTs. Valuealways zero.The source/load designation of the voltages is determined by the user. Refer to the ‘Power FlowDirection’ binary input for status and binary output for control.All voltages have a common deadband which can be configured (refer section 5.3.5).13 Ai Phase-(Earth /
Ground) VoltageY 0 30000 1 V 100 V. 2
14 Bi Phase-(Earth /Ground) Voltage
N 0 30000 1 V 100 V. 2
15 Ci Phase-(Earth /Ground) Voltage
N 0 30000 1 V 100 V. 2
16 Ax Phase-(Earth /Ground) VoltsNote 10
Y 0 30000 1 V 100 V. 2
17 Bx Phase-(Earth /Ground) VoltsNote 10
N 0 30000 1 V 100 V. 2
18 Cx Phase-(Earth /Ground) VoltsNote 10
N 0 30000 1 V 100 V. 2
19 A-Bi Phase-PhaseVoltage Note 2
N 0 38000 1 V 100 V. 2
20 B-Ci Phase-PhaseVoltage Note 2
N 0 38000 1 V 100 V. 2
21 C-Ai Phase-PhaseVoltage Note 2
N 0 38000 1 V 100 V. 2
22 A-Bx Phase-Phase VoltsNote 2, 10
N 0 38000 1 V 100 V. 2
23 B-Cx Phase-Phase VoltsNote 2, 10
N 0 38000 1 V 100 V. 2
Siemens Power Transmission & Distribution, Inc. 48
ACR Analog Input Points (Full)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
24 C-Ax Phase-Phase VoltsNote 2, 10
N 0 38000 1 V 100 V. 2
System Status25 System Power (kW)
This can be a signedquantity that indicatesdirection of power flow, oran unsigned quantity thatis always positiveregardless of thedirection of the powerflow. This is determinedby the CAPMconfiguration Note 2
Y -1.9GW 1.9GW 1 kW 250kW. 1
26 System Power FactorNote 6
Y 0.0 1.0 0.1 0.1 1
27 Gas Pressure, kPag.Note 3, 9
N -100 300 1 kPaG 5kPaG 2
28 Gas Pressure, psiNote 3, 9
N -14 44 1 psi 1psi 2
29 Code VersionNote 2, 4
Y 0 99,999,999 1 1 0
30 Configuration NumberNote 2, 5
Y 0 99,999 1 1 0
31 CAPM Serial Number Y 0 2147483647 1 1 032 ACR Serial Number
Note 2Y 0 2147483647 1 1 2
33 I Contact LifeNote 7
Y 0.0 100.0 0.1 % 0.1 % 2
34 II Contact LifeNote 7
N 0.0 100.0 0.1 % 0.1 % 2
35 III Contact LifeNote 7
N 0.0 100.0 0.1 % 0.1 % 2
36 Protection settingselection0 = Group A1 = Group B…9 = Group J
Y 0 9 1 1 1
37 Transmitted frame count Y 0 32768 1 1 038 Received frame count Y 0 32768 1 1 039 Received message
length errorY 0 999 1 1 0
40 Received message CRCerror
Y 0 999 1 1 0
Siemens Power Transmission & Distribution, Inc. 49
ACR Analog Input Points (Full)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
Protection Sequence DataThese analog points record data about the protection sequence including maximum faultcurrents. These are derived from the max current events that are seen in the Operator ControlPanel event record and record the current for each phase and for earth/ground.For any one protection trip or sequence advance more than one fault current can be set. Forexample a Phase/Phase fault might set an A-Phase current and a B-Phase current.Other data recorded includes the number of trips in the protection sequence and the ProtectionGroup that was active at the time of the protection operation.Data is cleared to zero by the following actions:-
• “Reset Fault Current” remote control command defined below• Any Operator Close or Trip action• Start of a new sequence.• This data is volatile, ie they are zeroed on CAPM software reset.
Protection Trip 141 A Fault Current – Written
on an A-Max event.Y 0 16000 1A 1A 1
42 B Fault Current – Writtenon a B-Max event.
N 0 16000 1A 1A 1
43 C Fault Current – Writtenon a C-Max event.
N 0 16000 1A 1A 1
44 Earth / Ground FaultCurrent - Written on a G-Max event. This includesSEF/SGF Fault currents.
N 0 16000 1A 1A 1
Protection Trip 2
45 A Fault Current – Writtenon an A-Max event.
Y 0 16000 1A 1A 1
46 B Fault Current – Writtenon a B-Max event.
N 0 16000 1A 1A 1
47 C Fault Current – Writtenon a C-Max event.
N 0 16000 1A 1A 1
48 Earth / Ground FaultCurrent - Written on a G-Max event. This includesSEF/SGF Fault currents.
N 0 16000 1A 1A 1
Protection Trip 3
49 A Fault Current – Writtenon an A-Max event.
Y 0 16000 1A 1A 1
50 B Fault Current – Writtenon a B-Max event.
N 0 16000 1A 1A 1
51 C Fault Current – Writtenon a C-Max event.
N 0 16000 1A 1A 1
52 Earth / Ground FaultCurrent - Written on a G-Max event. This includesSEF/SGF Fault currents.
N 0 16000 1A 1A 1
Siemens Power Transmission & Distribution, Inc. 50
ACR Analog Input Points (Full)
DN
P ID
Nam
e
W S
erie
s
Min
Max
Uni
ts
Def
ault
Dea
d B
and
Cla
ss
Protection Trip 4
53 A Fault Current – Writtenon an A-Max event.
Y 0 16000 1A 1A 1
54 B Fault Current – Writtenon a B-Max event.
N 0 16000 1A 1A 1
55 C Fault Current – Writtenon a C-Max event.
N 0 16000 1A 1A 1
56 Earth / Ground FaultCurrent - Written on a G-Max event. This includesSEF/SGF Fault currents.
N 0 16000 1A 1A 1
Miscellaneous57 Loop automation time
remaining prior to a trip orclose action occurring.For no action pendingvalue is zero.Note 8
Y 0 1800 1 second 10 second 2
58 Maximum AverageCurrent of all phases forthe previous day endingat 24:00
N 0 16000 1A 10A 1
59 FrequencyNote 11
N 45 65 1Hz 0.1Hz 2
60 to69
Reserved
Note1. The deadband for all analog points can be configured, refer section 5.3.5 for more information.2. These points may exceed the 16 bit limit and can be obtained using 32 bit analog input objects.3. If ‘ACR Memory Data Invalid’ binary status is set then value is 04. The code version is an eight digit number that has the form XXX-XXX.XX with the dash and point formatting removed.5. The configuration number is a five digit number that has the form XXXXX. It identifies the configuration loaded into the
CAPM-4 database.6. Power factor has a built in scale factor of 10 i.e. range 0.0 to 1.0 with resolution 0.1 is transmitted as 0 to 10 with
resolution 1.7. Contact life has a built in scale factor of 10 i.e. range of 0.0% to 100.0% with resolution 0.1% is transmitted as 0 to
1000 with resolution 1.8. This point is only valid when the Loop Automation option is enabled for the current configuration and is otherwise
always reported as zero.9. Not available on U-series ACR, value will always be 0.10. Not available on standard U-series ACR without external CVTs, value will always be 0.11. Frequency has a built in scale factor of 10 i.e. range 45 to 65 with resolution 0.1 is transmitted as 450 to 650 with
resolution 1. This option unsupported on CAPM-4 controllers.
Siemens Power Transmission & Distribution, Inc. 51
Appendix G ACR - Counter PointW-series support is indicated below by a ‘Y’. If indicated as ‘N’ then value is always 0.DNP V3.00 ImplementationBinary Counters Static Object: Object 20 Variation 05 – 32 Bit Binary Counter without Flag Request Function Codes: 01 – Read, 07 – Immediate Freeze, 08 – Immediate Freeze, No Ack, 09 – Freeze and Clear
10 – Freeze and Clear, No AckFrozen Counters Static Object: Object 21 Variation 9 – 32 Bit Frozen Counter without Flag Request Function Code: 01 – Read
ACR Counter Points
DNP
ID
Nam
e
W S
erie
s
Min
Max
Units
0 KWH Cumulative Note 1 Y 0 2147483647 KWH1 Source Outages Note 2, 3 Y 0 2147483647 Counts2 Source Outage Duration
Note 2, 3Y 0 2147483647 Seconds
3 Load Outages Note 2, 3 Y 0 2147483647 Counts4 Load Outage Duration
Note 2, 3Y 0 2147483647 Seconds
Note:1. This accumulates the total kWH flowing through the ACR. If the CAPM is set for Power Flow Unidirectional then the
cumulative total increases irrespective of the direction of power flow to show the total power that has passed throughthe device. If the CAPM is set for Bi-Directional power flow then the cumulative total can increase or decreasereflecting the nett power flow.
2. Resetting any Outage counter via a protocol counter reset command will result in the resetting of all outage counters.3. The power flow direction (source/load designation) is determined by the user. Refer to Power Flow Direction Binary
Input for status and Binary Output for control.
Siemens Power Transmission & Distribution, Inc. 52
Appendix H ACR - Binary Output PointsChanging some of these settings affects the currently active protection group. The change is put into effect immediatelyand is permanent for that group. In other words, it is the equivalent to selecting a protection group on the operator controlpanel, changing the setting, and then putting the change into service.
All binary output points have a matching binary input status point. The CAPM does not return binary output object statusin response to a class 0 or an integrity poll. It is recommended that the master station use the control’s correspondingbinary input status to verify the success of an action.
If Centurion SP (W series) is indicated as ‘Y’ below then point is supported otherwise no action is taken.
DNP V3.00 ImplementationBinary Output Status Static Object: Object 10 Variation 02 – Binary Output Status• The status of the offline/online bits is determined by the reject conditions shown in the table below. A point is reported
offline if it cannot be forced to the alternate state due to condition listed. Note that not all conditions that prevent acontrol from succeeding are listed. Some conditions (eg mechanical failure) may be undetermined at time of read.
Request Function Code: 01- ReadRelay Control Block Control Object: Object 12 Variation 01 – Control Relay Output Block
Control relay output block parameters supported:• Control types are accepted on per point basis as shown in the table below.
TC = Trip/Close, P = Pulse ON/OFF, L = Latch ON/OFF.Set (1) = Close, Pulse ON, Latch ONCleared (0) = Trip, Pulse OFF, Latch OFFRecommended control types is shown in bold font.
Note: Pulse OFF is not supported on most master station systems.
• The count, on-time, off-time, queue, and clear parameters are ignored.
Request Function Codes: 03 – Select, 04 – Operate, 05 – Direct Operate,06 – Direct Operate, No Ack
Response Codes: Refer to Appendix C for a table of reported status values
ACR Binary Output Points
DN
P ID
Nam
e
W S
erie
s
Set =
‘1’
Cle
ared
= ‘0
’
Con
trol
Typ
e
0 Earth / Ground Faultprotection
N Enable Earth / GroundProtectionRejected if:• earth/ground fault
OFF is not allowed.
Earth / GroundProtection OFF andSEF/SGF ProtectionOFFRejected if:• earth/ground fault
OFF is not allowed.
L, P
1 SEF/SGF protection N SEF/SGF protectionON andEarth / GroundProtection ONRejected if:• SEF/SGF is not
available
Disable SEF/SGFprotection
L, P
2 Auto Reclose Y Auto Reclose ON Auto Reclose OFF L, P
Siemens Power Transmission & Distribution, Inc. 53
ACR Binary Output Points
DN
P ID
Nam
e
W S
erie
s
Set =
‘1’
Cle
ared
= ‘0
’
Con
trol
Typ
e
3 ACR Control Y CloseRejected if:• Close coil is
isolated• CAPM is in LOCAL
control mode• SF6 gas pressure
is low (if applicable)AND low gaslockout is ON
• Work Tag isapplied
• Switchgear datainvalid
• Mechanicallyinterlocked (ifapplicable)
• Live load blockingON AND any loadside terminal live
• Trip and/or Closecapacitors arecharging or failed
TripRejected if:• Trip coil is isolated• SF6 gas pressure
is low (if applicable)AND low gaslockout is ON
• Switchgear datainvalid
TC,L, P
4 Work Tag Y Applies Work Tag.Rejected if:• CAPM is in LOCAL
Mode
Removes Work Tag.Rejected if:• CAPM is in LOCAL
Mode.
L, P
5 Cold Load Idle/Max Y Set cold load time to itsmaximum value. Thismeans that the coldload threshold currentwill be set to itsmaximum valueRejected if:• Cold load support
is OFF
Set cold load time tozero. This means thatthe threshold multiplierwill not be affected bythe cold load function.Rejected if:• Cold load support
is OFF
L, P
6 High Current Lockout Y Enable High CurrentLockout
Disable High CurrentLockout
L, P
7 Loss of Phase ProtectionRejected if:• LOP and Loop Auto
linked.• Single Phase switchgear.
N Enable Loss of PhaseProtection
Disable Loss of PhaseProtection
L, P
8 Sequence Control Y Enable SequenceControl
Disable SequenceControl
L, P
9 Live Load Blocking Y Live Load blocking ON Live Load blocking OFF L, P10 ` Reset Fault
Flags and CurrentsNote 1
Y Resets all Object 30Fault Currents to zeroand clears all Object 01protection trip flags
No Action L, P
Siemens Power Transmission & Distribution, Inc. 54
ACR Binary Output Points
DN
P ID
Nam
e
W S
erie
s
Set =
‘1’
Cle
ared
= ‘0
’
Con
trol
Typ
e
11 Protection Control Y Enable Protection Turn ALL ProtectionOFFRejected if:• protection OFF is
not allowed
L, P
12 Power Flow Direction Note 4 Y Source X, Load I Source I, Load X L, P13 Protection Group A Note 1, 3 Y Group A ON Note 5 No Action L, P14 Protection Group B Note 1, 3 Y Group B ON Note 5 No Action L, P15 Protection Group C Note 1, 3 Y Group C ON Note 5 No Action L, P16 Protection Group D Note 1, 3 Y Group D ON Note 5 No Action L, P17 Protection Group E Note 1, 3 Y Group E ON Note 5 No Action L, P18 Protection Group F Note 1, 3 Y Group F ON Note 5 No Action L, P19 Protection Group G Note 1,
3Y Group G ON Note 5 No Action L, P
20 Protection Group H Note 1, 3 Y Group H ON Note 5 No Action L, P21 Protection Group I Note 1, 3 Y Group I ON Note 5 No Action L, P22 Protection Group J Note 1,
3Y Group J ON Note 5 No Action L, P
23 Loop Automation ControlNote 2
Y Loop Automation ONRejected if:• Loop automation
capability notavailable
• Work tag applied• Trip coil isolated• Close coil isolated• Mechanism fail• Switchgear data
invalid• Battery not normal• SF6 Gas Pressure
is low (if applicable)AND Low GasLockout is ON
• Tripped AND(Midpoint ORFeeder)
• U Series AND noexternal CVTsAND (TIE OR AutoRestore ON)
Loop Automation OFFRejected if:• Loop automation
capability notavailable
L, P
24 Dummy Circuit Breaker Y DCB Close DCB Trip TC,L, P
Siemens Power Transmission & Distribution, Inc. 55
ACR Binary Output Points
DN
P ID
Nam
e
W S
erie
s
Set =
‘1’
Cle
ared
= ‘0
’
Con
trol
Typ
e
25 Automatic Protection GroupSelection
Y APGS ONRejected if:• APGS ON is Not
Allowed• Loop Automation
ON
APGS OFF L, P
26 Supply Outage MeasurementControl
Y Supply OutageMeasurement ON
Supply OutageMeasurement OFF
L, P
27 Supply Outage MeasurementReset
Y Resets all SupplyOutage countersvalues.
No Action L, P
28 Under Frequency Protection Y Enable under frequencyprotectionRejected if:• CAPM4
Disable underfrequency protectionRejected if:• CAPM4
L, P
29 Over Frequency Protection Y Enable over frequencyprotectionRejected if:• CAPM4
Disable over frequencyprotectionRejected if:• CAPM4
L, P
30 Normal Frequency CloseProtection
Y Enable normalfrequency closeprotectionRejected if:• CAPM4
Disable normalfrequency closeprotectionRejected if:• CAPM4
L, P
31 Source Dead Protection Y Enable Disable L, P
Note:1. The response for binary output status for these points will always be 0.2. This point is only valid when the Loop Automation option is enabled for the current configuration otherwise No Action
is taken.3. Only one protection group can be active at any one time. Activating any of these protection groups will automatically
reset the previously active setting.4. Changing the Source/Load direction affects the following aspects of the operation of the CAPM:
• Whether the source or load corresponds to I side or X side on the voltage measurements• Which side is the source or load for the Live Load Blocking• Which side is the source or load for the Directional Blocking• Which direction is positive power flow for the System Power Analog Input• Power Flow Direction Binary Input status
5. The number of protection groups available in the CAPM is configurable. If a control is not available because theprotection set is not supported then it is rejected.
Siemens Power Transmission & Distribution, Inc. 56
Appendix I ACR - Analog Output PointsChanging some of these settings affects the currently active protection group. The change is put into effect immediatelyand is permanent for that group. In other words, it is the equivalent to selecting that protection group on the operatorcontrol panel, changing the setting and then putting the change into service.All analog output points have a matching analog input point. The CAPM does not return analog output object status inresponse to a class 0 or and integrity poll. It is recommended that the master station use the output’s correspondinganalog input status to verify the success of an action.If W series is indicated as ‘Y’ below then point is supported otherwise no action is taken.DNP V3.00 ImplementationAnalog Output StatusStatic Object: Object 40 Variation 02 – 16 Bit Analog StatusRequest Function Code: 01 – ReadAnalog Output BlockControl Object: Object 41 Variation 02 – 16 Bit Analog Output BlockRequest Function Codes: 03 – Select, 04 – Operate, 05 – Direct Operate,
06 – Direct Operate, No Ack
ACR Analog Output Point
DNP
ID
Nam
e
W S
erie
s
Min
Max
Units
0 Protection Group Selection0 = Group A1 = Group B…9 = Group J
0 9Note 1
N/A
Note:1. The number of protection groups available in the CAPM is configurable. If the analog output block value is not
available because the protection set is not supported then it is rejected.
Siemens Power Transmission & Distribution, Inc. 57
Appendix J LBS – Binary Points Data (Status)
Time resolution is as shown. Refer to Appendix A for more information on timing.The phase designation A, B, C is determined by the user, refer to the equipment manual for more information.Phase and terminal terminology is explained in section 4.4.
DNP V3.00 ImplementationStatic: Object 01 Variation 01 – Single Bit Binary InputEvent: Configurable – refer to section 5.3Request Function Code: 01 – Read
LBS Binary Input Points (Status)
DNP
ID
Nam
e
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
t a
nd
Tim
e R
esol
utio
n
0 Abnormal Operatorconditions
1 For any of the followingconditions:-Trip or Close Isolated,LBS Mechanicallylocked open (ifapplicable)Work Tag Applied
None of the specifiedconditions are true
This flag shows that theoperator has the LBS inan abnormal state suchas “work tag applied”.This means that it willoperate differently to itsnormal mode ofoperation.
500ms 1 LBS Tripped (open) 1 LBS Tripped LBS not Tripped
2 LBS Closed 1 LBS Closed LBS not Closed
These are repeats of themechanism travelswitches. When the LBSis disconnected from thecontrol cubicle they areboth cleared.
10ms 3 Controller Mode 2 LOCAL control Disabled
Remote controlEnabled
LOCAL ControlEnabledRemote ControlDisabled
The CAPM is either inLOCAL or RemoteController Mode. Thisaffects the closingcommand thepermission toset/remove work tag.
500ms 4 Maintenance
Required1 For any of the following
conditions:-Battery NOT normalCapacitor charge failureLow power modeLow SF6 gas pressureLBS data not valid(includes connection toan invalid switch type)Any contact life is lessthan 20%Mechanical failureAux supply overvoltage
No maintenancerequired
The CAPM has detectedone or more conditionswhich requiremaintenance.This point cannotbecome Set until at leastfive minutes after CAPMstart.
500ms
Siemens Power Transmission & Distribution, Inc. 58
LBS Binary Input Points (Status)
DNP
ID
Nam
e
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
t a
nd
Tim
e R
esol
utio
n
5 Work Tag 2 Work Tag Applied Work Tag Removed The CAPM can have awork tag. This affects theclosing command
500ms 6 Detection A Active 2 Detection Group A is
activeDetection Group A is notactive
7 Detection B Active 2 Detection Group B isactive
Detection Group B is notactive
These flags indicatethe active protectiongroup. If neither A norB is active (eg.Because C is active)then flags will be clearand the analog valuepoint must be used todetermine the activegroup.
500ms 8 Detection C Active 2 Detection Group C is
activeDetection Group C is notactive
Only one detectiongroup is active at anyone time.
9 Detection D Active 2 Detection Group D isactive
Detection Group D is notactive
10 Detection E Active 2 Detection Group E isactive
Detection Group E is notactive
500ms
11 Detection F Active 2 Detection Group F isactive
Detection Group F is notactive
12 Detection G Active 2 Detection Group G isactive
Detection Group G is notactive
13 Detection H Active 2 Detection Group H isactive
Detection Group H is notactive
14 Detection I Active 2 Detection Group I isactive
Detection Group I is notactive
15 Detection J Active 2 Detection Group J isactive
Detection Group J is notactive
16 Power FlowDirection
2 Source X, Load I Source I, Load X The power flow direction(source/loaddesignation) isdetermined by the user.Refer to the Power FlowDirection binary outputfor more information
500ms 17 Close Isolate 2 Close Isolate Switch
OFF/ISOLATE(i.e. Closeis disabled)
Close Isolate SwitchON/ENABLE (i.e. Closeis enabled)
18 Trip Isolate 1 Trip Isolate Switch OFF(i.e. Trip is disabled)
Trip Isolate SwitchON(i.e. Trip is enabled)
Shows the state of theTrip & Close isolateswitches on the controlpanel10ms
Siemens Power Transmission & Distribution, Inc. 59
LBS Binary Input Points (Status)
DNP
ID
Nam
e
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
t a
nd
Tim
e R
esol
utio
n
19 Locked 1 LBS Locked Open LBS not locked open Shows that the LBS ismechanically andelectrically locked in theopen position..
10ms 20 LBS Memory Data
Invalid2 LBS Memory Data not
validLBS Memory Data Valid Shows that the CAPM
has retrieved the datafrom the LBS memory.When invalid theswitchgear attributesand the gas pressureare zeroed,
500ms 21 Auxiliary Supply
Fail2 Auxiliary supply has
failedAuxiliary supply isnormal
500ms
22 SwitchgearConnection
2 Switchgeardisconnected fromcontrol cubicle.
Switchgear is connectedto control cubicle.
Shows the connectionstate of the cablebetween the switchgearand the CAPM. Whenconnected to the LBSTrip, Close and Lockedindications are valid.When disconnectedfrom the LBS data willbe forced invalid
500ms 23 SF6 Gas Pressure
Low or Invalid2 Gas pressure Low or
InvalidGas Pressure Normal,or Not Known, or Not aswitchgear which hasSF6.
Only set whenswitchgear is connectedand LBS memory data isvalid and switchgeartype has SF6.
500ms 24 Battery Supply 2 Battery supply not
normal.This includes :-Battery OffBattery OvervoltBattery Low Volts
Battery supply normal 500ms
25 Switchgear Family 3 Set for Load BreakSwitch
Clear For Recloser500ms
26 Contacts Life Low 2 When any contact life isless than 20%.
When all contacts havecontact life >= 20%
500ms
27 Capacitor ChargeFailure
2 Capacitor Charge Failed Capacitor Charge OK The Trip/CloseCapacitors have failed tocharge. (where relevant)
500ms
Siemens Power Transmission & Distribution, Inc. 60
LBS Binary Input Points (Status)
DNP
ID
Nam
e
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
t a
nd
Tim
e R
esol
utio
n
28 Mechanism Failure 2 Mechanism Failure Mechanism OK The switchgear hasfailed to Trip or Closeelectrically
500ms 29 Phase Ai Live 1 Phase is live Phase is dead 30 Phase Bi Live 1 31 Phase Ci Live 1 32 Phase Ax Live 1
Shows if the phasebushings are above orbelow the live linethreshold.
33 Phase Bx Live 1 34 Phase Cx Live 1
10ms
35 Source VoltageStatus
1 All of the source side areTerminals dead
36 Load VoltageStatus
1
Shows that any of thethree phases of thedesignated Source sideor Load side are live. All of the load side are
Terminal dead
Note that these pointsare different to theLoad/Source Live/Deadevents in the CAPMevent record
10ms 37 Load Current On 1 Current of 2.5A or more
is flowing in at least onephase
Current of less than 2.5Ais flowing in all threephases
10ms
38 Dummy LBSClosed
2 Dummy LBS Closed Dummy LBS NOTclosed.
This point represents aninternal dummy LBS.This is an internal pointuseful for SCADAsystem testing. Thevalue of the dummy LBSis non-volatile.
500ms 39 Supply Outage
Measurement2 Supply Outage
Measurement ONSupply OutageMeasurement OFF
500ms
40 Reserved 1 2 Reserved Reserved 41 Phase Current HI
Alarm2 Phase Current Alarm
ONPhase Current AlarmOFF
500ms
42 Phase CurrentLOW Alarm
2 Phase Current AlarmON
Phase Current AlarmOFF
500ms
43 Phase Voltage HIAlarm
2 Phase Voltage AlarmON
Phase Voltage AlarmOFF
500ms
44 Phase VoltageLOW Alarm
2 Phase Voltage AlarmON
Phase Voltage AlarmOFF
500ms
45 Earth Current HIAlarm
2 Earth Current HI AlarmON
Earth Current HI AlarmOFF
500ms
46 Earth Current LOWAlarm
2 Earth Current LOWAlarm ON
Earth Current LOWAlarm OFF
500ms
47 System Power HIAlarm
2 System Power HI AlarmON
System Power HI AlarmOFF
500ms
48 System PowerLOW Alarm
2 System Power LOWAlarm ON
System Power LOWAlarm OFF
500ms
Siemens Power Transmission & Distribution, Inc. 61
LBS Binary Input Points (Status)
DNP
ID
Nam
e
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
t a
nd
Tim
e R
esol
utio
n
49 Auxiliary SupplyFail (Delayed)
2 Auxiliary Supply hasfailed for more than 120seconds
Auxiliary Supply hasbeen restored for morethan 20 seconds
500ms
Operator/Detection FlagsThese flags show the status of the operator controls and some of the detection flags.They are equivalent to the indications available on the Operator Control Panel of the CAPM.
50 Phase DetectionEnabled
2 Phase Detection ON Phase Detection OFF 500ms
51 Earth/GroundDetection Enabled
2 Earth/Ground DetectionON
Earth/Ground DetectionOFF
500ms
52 SEF/SGFDetection Enabled
2 SEF/SGF Detection ON SEF/SGF DetectionOFF
500ms
53 Sectionaliser Auto 2 Sectionaliser Auto ON Sectionaliser OFF (LoadBreak Switch)
500ms
54 Cold Load Auto 2 Cold Load auto-mode isarmed.This means the ColdLoad function is enabledand may, or may not, beaffecting the thresholdmultiplier.
Cold Load pickup isOFF.This means that the coldload function iscompletely disabled.
500ms
See ‘Cold Load Idle’(below)
55 Cold Load Idle 2 Cold Load is Idle or isturned off.This means that thethreshold multiplier is notbeing affected by thecold load function.
Cold load is NOT Idle.This means that thethreshold multiplier isbeing raised by the coldload pickup function.
500ms
56 Live Load Blocking 2 Live Load Blocking ON Live Load Blocking OFF 500ms 57 Automatic
Detection GroupSelection(Code Version 025-01 and later)
2 Automatic DetectionGroup Selection is ON
Automatic DetectionGroup Selection is OFF
500ms
Detection FlagsThis group of points indicates what happened in the most recent fault detection. Unlike the ACR, these flags don’tattempt to reconstruct a fault sequence. The flags are not cumulative, they are cleared as each new fault isdetected. For example, if there is an earth fault followed by a phase fault, the earth fault flag will be cleared whenthe phase fault flag is set.In addition analog data is available which shows the fault currents.Most of these flags are cleared either by protocol command or when the switchgear is tripped/closed by theoperator or when a new fault is detected.This data is volatile, i.e. it is zeroed on controller software reset.If there is more than one protocol running simultaneously in the controller this data is replicated between theprotocols so that each master station can clear its data independently from the others.
58 Sequence inProgress
2 Start of sequence Thatis a detection trip orsequence advance hasoccurred.
End of sequence. This shows that aDetection sequence hasstarted and not yetcompleted.
Siemens Power Transmission & Distribution, Inc. 62
LBS Binary Input Points (Status)
DNP
ID
Nam
e
Clas
s
Set =
‘1’
Clea
red
= ‘0
’
Com
men
t a
nd
Tim
e R
esol
utio
n
Note that operator tripdoes not cause a“sequence in progress”
10ms 59 A Phase
Overcurrent Fault2 A Phase Overcurrent
Fault 60 B Phase
Overcurrent Fault2 B Phase Overcurrent
Fault 61 C Phase
Overcurrent Fault2 C Phase Overcurrent
Fault 62 Earth/Ground
Overcurrent Fault2 Earth/Ground
Overcurrent Fault 63 SEF/SGF
Overcurrent Fault2 SEF/SGF Overcurrent
Fault
These flags show whichelements were pickedup since last clear action
10ms
64 Supply Interrupt 1 Supply Interrupt Set if a supply interruptoccurred after the mostrecent fault.
10ms 65 Sectionaliser Trip 1 Sectionaliser Trip
Cleared by• Operator trip• Any close• ‘Reset Flags’
Protocol Command• Supply Reset (if
enabled)
Set if switch trips tosectionalise
66–93
Reserved
Note:1. Only available on CAPM-5 controller
Appendix K LBS - Analog Input Points (Status - Small Set)This is the reduced set of analog status points available from the CAPM.All analog points have 500ms resolution time tags. Refer to Appendix A for more information on timing.All analogs in the small analog data set can fit in a signed 16-bit DNP data object except where noted.The phase designation A, B, C is determined by the user, refer to the equipment manual for more information.Phase and terminal terminology is explained in section 4.4.
DNP V3.00 ImplementationStatic: Configurable – Object 30 Variation 1, 2, 3, or 4 (refer to section 5.3)Event: Configurable – Object 32 Variation 1, 2, 3, or 4 (refer to section 5.3)Deadband: Configurable – Object 34 Variation 1, 2 (refer to section 5.3)Request Function Code: 01 – Read
Siemens Power Transmission & Distribution, Inc. 63
LBS Analog Input Points (Small)
DNP
ID
Nam
e
Min
Max
Units
Defa
ult D
ead
Band
Clas
s
Line Currents and System Power
0 A Current 0 16000 1 A 10 A. 1 1 B Current 0 16000 1 A 10 A. 1 2 C Current 0 16000 1 A 10 A. 1 3 Earth / Ground Current 0 16000 1 A 5 A. 1 4 System kVA Note 2 0 1.9
GVA1 kVA 250 kVA. 1
5 System kVAR Note 2 0 1.9GVAR
1 kVAR 250 kVAR. 1
6 Operations Counter 0 65535 1Operation
1 Operation 2
Voltage Measurements (Earth/Ground)Voltage measurements are provided for all terminals with voltage measurements.The source/load designation of the voltages is determined by the user. Refer to the ‘Power FlowDirection’ binary input for status and binary output for control.
7 Ai Phase-(Earth / Ground)Voltage 0 30000 1 V 100 V. 2
8 Bi Phase-(Earth / Ground)Voltage 0 30000 1 V 100 V. 2
9 Ci Phase-(Earth / Ground)Voltage 0 30000 1 V 100 V. 2
10 Ax Phase-(Earth / Ground)Voltage 0 30000 1 V 100 V. 2
11 Bx Phase-(Earth / Ground)Voltage 0 30000 1 V 100 V. 2
12 Cx Phase-(Earth / Ground)Voltage 0 30000 1 V 100 V. 2
Siemens Power Transmission & Distribution, Inc. 64
LBS Analog Input Points (Small)
DNP
ID
Nam
e
Min
Max
Units
Defa
ult D
ead
Band
Clas
s
Fault Detection DataThese analog points record data about the fault detection including maximum fault currents. Theseare derived from the max current events, which are seen in the Operator Control Panel event recordand record the current for each phase and for earth/ground.For any one fault more than one fault current can be set. For example a Phase/Phase fault might setan A-Phase current and a B-Phase current.Other data recorded includes the supply interrupt count and the Detection Group which was active atthe time of the fault detection.Fault Detection Data is cleared to zero by the following actions :-• “Reset Fault Current” remote control command defined below• Any Operator Close or Trip action• New fault detectedThis data is volatile, that is they are zeroed on controller software reset.If there is more than one protocol running simultaneously in the controller this data is replicatedbetween the protocols so that each master station can clear its data independently from the others.
13
Active Detection GroupThe number of the DetectionGroup active during thesequence.
0 9 1 1 1
14 Supply Interrupt CountThe number of SupplyInterrupts Counted.
1 10 1 1
15 Most Recent A-Phase FaultWritten on a Max Current eventfor A Phase
0 16000 Amps 1A 1
16 Most Recent B-Phase FaultWritten on a Max Current eventfor B Phase
0 16000 Amps 1A 1
17 Most Recent C-Phase FaultWritten on a Max Current eventfor C Phase
0 16000 Amps 1A 1
18
Most Recent Earth/GroundFault Current - Written on an E-Max event. This includesSEF/SGF Fault currents.
0 16000 Amps 1A 1
19-
29 Reserved
Note1. The deadband for all analog points can be configured, refer section 5.3.5 for more information.2. These points may exceed the 16 bit limit and can be obtained using 32 bit analog input objects.
Siemens Power Transmission & Distribution, Inc. 65
Appendix L LBS - Analog Input Points (Status – Full Set)
This is the complete set of analog status points available from the CAPM.All analog points have 500ms resolution time tags. Refer to Appendix A for more information on timing.All analogs in the full analog data set can fit in a signed 16-bit DNP data object except where noted.The phase designation A, B, C is determined by the user, refer to the equipment manual for more information.Phase and terminal terminology is explained in section 4.4.
DNP V3.00 ImplementationStatic: Configurable – Object 30 Variation 1, 2, 3, or 4 (refer to section 5.3)Event: Configurable – Object 32 Variation 1, 2, 3, or 4 (refer to section 5.3)Deadband: Configurable – Object 34 Variation 1, 2 (refer to section 5.3)Request Function Code: 01 – Read
LBS Analog Input Points (Status – Full Set)
DNP-
ID
Nam
e
Min
Max
Units
Defa
ult
Dead
Ban
d
Clas
s
System Line Currents and Power 0 A-Phase Current 0 16000 1 A 10 A. 1 1 B-Phase Current 0 16000 1 A 10 A. 1 2 C-Phase Current 0 16000 1 A 10 A. 1 3 (Earth / Ground) Current 0 16000 1 A 5 A. 1
4 System kVA Note 2 0 1.9GVA
1 kVA 250 kVA. 1
5 System kVAR Note 2 0 1.9GVAR 1 kVAR 250 kVAR. 1
6 Operations Counter 0 65535 1Operation 1 Operation 2
Voltage Measurements (Earth/Ground)Voltage measurements are provided for all terminals with voltage measurements.The source/load voltage designation is determined by the user. Refer to the ‘Power Flow Direction’binary input for status and binary output for control.All voltages have a common deadband which can be configured (refer section 5.3.5).
7 Ai Phase-(Earth/ Ground)Voltage
0 30000 1 V 100 V 2
8 Bi Phase-(Earth / Ground)Voltage
0 30000 1 V 100 V 2
9 Ci Phase-(Earth / Ground)Voltage
0 30000 1 V 100 V 2
10 Ax Phase-(Earth / Ground)Voltage
0 30000 1 V 100 V 2
11 Bx Phase-(Earth / Ground)Voltage
0 30000 1 V 100 V 2
12 Cx Phase-(Earth / Ground)Voltage
0 30000 1 V 100 V 2
Siemens Power Transmission & Distribution, Inc. 66
LBS Analog Input Points (Status – Full Set)
DNP-
ID
Nam
e
Min
Max
Units
Defa
ult
Dead
Ban
d
Clas
s
Fault Detection DataThese analog points record data about the fault detection including maximum fault currents. Theseare derived from the max current events, which are seen in the Operator Control Panel event recordand record the current for each phase and for earth/ground.For any one fault more than one fault current can be set. For example a Phase/Phase fault might setan A-Phase current and a B-Phase current.Other data recorded includes the supply interrupt count and the Detection Group which was active atthe time of the fault detection.Fault Detection Data is cleared to zero by the following actions :-• “Reset Fault Current” remote control command defined below• Any Operator Close or Trip action• New fault detectedThis data is volatile, that is they are zeroed on controller software reset.If there is more that one protocol running simultaneously in the controller this data is replicatedbetween the protocols so that each master station can clear its data independently from the others.
13 Active Detection GroupThe number of the DetectionGroup which was active duringthe sequence.
0 9 1 1 1
14 Supply Interrupt CountThe number of SupplyInterrupts Counted.
1 10 1 1
15 Most Recent A-Phase FaultWritten on a Max Current eventfor A Phase
0 16000 Amps 1A 1
16 Most Recent B-Phase FaultWritten on a Max Current eventfor B Phase
0 16000 Amps 1A 1
17 Most Recent C-Phase FaultWritten on a Max Current eventfor C Phase
0 16000 Amps 1A 1
18 Most Recent Earth/GroundFault Current – Written on anE-Max event. This includesSEF/SGF Fault currents.
0 16000 Amps 1A 1
Voltage Measurements (Phase/Phase) 19 A-Bi Phase-Phase Voltage
Note 20 38000 1 V 100 V 2
20 B-Ci Phase-Phase VoltageNote 2
0 38000 1 V 100 V 2
21 C-Ai Phase-Phase VoltageNote 2
0 38000 1 V 100 V 2
22 A-Bx Phase-Phase VoltageNote 2
0 38000 1 V 100 V 2
23 B-Cx Phase-Phase VoltageNote 2
0 38000 1 V 100 V 2
Siemens Power Transmission & Distribution, Inc. 67
LBS Analog Input Points (Status – Full Set)
DNP-
ID
Nam
e
Min
Max
Units
Defa
ult
Dead
Ban
d
Clas
s
24 C-Ax Phase-Phase VoltageNote 2
0 38000 1 V 100 V 2
System Status 25 System Power (kW)
This can be a signed quantitythat indicates direction of powerflow, or an unsigned quantitythat is always positiveregardless of the direction ofthe power flow. This isdetermined by the CAPMconfiguration Note 2
-1.9GW
1.9GW 1 kW 250kW. 1
26 System Power FactorNote 6
0.0 1.0 0.1 0.1 1
27 Gas Pressure, kPag.Note 3
-100
300 1 kPaG 5kPaG 2
28 Gas Pressure, psi Note 3 -14 44 1 psi 1psi 2 29 Code Version Note 2,
40 99,999,999 1 1 0
30 Configuration Number Note 2,5
0 99,999 1 1 0
31 CAPM Serial Number 0 2147483647 1 1 0 32 LBS Serial Number Note 2 0 2147483647 1 1 2 33 I/U Contact Life Note 7 0.0 100.0 0.1 % 0.1 % 2 34 II/V Contact Life Note 7 0.0 100.0 0.1 % 0.1 % 2 35 III/W Contact Life Note 7 0.0 100.0 0.1 % 0.1 % 2 36 Transmitted frame count 0 32768 1 1 0 37 Received frame count 0 32768 1 1 0 38 Received message length error 0 999 1 1 0 39 Received message CRC error 0 999 1 1 0
Detection State 40 Cold Load
Value is zero when Cold Loadis Idle or OFF. When Cold Loadis not idle this shows theoperational cold load time, i.e.the current time being used tocalculate the operational coldload threshold multiplier.
0 480 1 Min 1 Min 2
41 Detection Group currentlyselected0 = Detection Group A1 = Detection Group Bn = Other Detection Group
0 9 1 1 2
Miscellaneous
Siemens Power Transmission & Distribution, Inc. 68
LBS Analog Input Points (Status – Full Set)
DNP-
ID
Nam
e
Min
Max
Units
Defa
ult
Dead
Ban
d
Clas
s
42 Maximum Average Current ofall phases for the previous dayending at 24:00
0 16000 1A 10A 1
43-
53Reserved
Note1. The deadband for all analog points can be configured, refer section 5.3.5 for more information.2. These points may exceed the 16 bit limit and can be obtained using 32 bit analog input objects.3. If LBS Memory Data Invalid’ binary status is set then value is 04. The code version is an eight digit number that has the form XXX-XXX.XX with the dash and point formatting
removed.5. The configuration number is a five digit number that has the form XXXXX. It identifies the configuration loaded
into the CAPM database.6. Power factor has a built in scale factor of 10 i.e. range 0.0 to 1.0 with resolution 0.1 is transmitted as 0 to 10
with resolution 1.7. Contact life has a built in scale factor of 10 i.e. range of 0.0% to 100.0% with resolution 0.1% is transmitted as 0
to 1000 with resolution 1.8. This point is only valid when the Loop Automation option is enabled for the current configuration and is
otherwise always reported as zero.
Siemens Power Transmission & Distribution, Inc. 69
Appendix M LBS - Counter Points
DNP V3.00 ImplementationBinary Counters Static Object: Object 20 Variation 05 – 32 Bit Binary Counter without Flag Request Function Codes: 01 – Read, 07 – Immediate Freeze, 08 – Immediate Freeze, No Ack, 09 – Freeze and Clear
10 – Freeze and Clear, No AckFrozen Counters Static Object: Object 21 Variation 9 – 32 Bit Frozen Counter without Flag Request Function Code: 01 – Read
LBS Counter Points
DNP
ID
Nam
e
Min
Max
Units
0 KWH Cumulative Note 1 0 2147483647 KWH1 Source Outages Note 2, 3 0 2147483647 Counts2 Source Outage Duration
Note 2, 30 2147483647 Seconds
3 Load Outages Note 2, 3 0 2147483647 Counts4 Load Outage Duration
Note 2, 30 2147483647 Seconds
Note:1. This accumulates the total kWH flowing through the LBS.
If the CAPM is set for Power Flow Unidirectional then the cumulative total increases irrespective of the direction ofpower flow to show the total power that has passed through the device.If the CAPM is set for Bi-Directional power flow then the cumulative total can increase or decrease reflecting the nettpower flow.
2. Resetting any Outage counter via a protocol counter reset command will result in the resetting of all outage counters.3. The power flow direction (source/load designation) is determined by the user. Refer to Power Flow Direction Binary
Input for status and Binary Output for control.
Siemens Power Transmission & Distribution, Inc. 70
Appendix N LBS - Binary Output PointsChanging some of these settings affects the currently active Detection group. The change is put into effect immediatelyand is permanent for that group. In other words, it is the equivalent to selecting that Detection group on the operatorcontrol panel, changing the setting and then putting the change into service.
All binary output points have a matching binary input status point. The CAPM does not return binary output object statusin response to a class 0 or an integrity poll. It is recommended that the master station use the control’s correspondingbinary input status to verify the success of an action.
DNP V3.00 ImplementationBinary Output Status Static Object: Object 10 Variation 02 – Binary Output Status
The status of the offline/online bits is determined by the reject conditions shown in the table below. A point isreported offline if it cannot be forced to the alternate state due to condition listed. Note that not all conditions thatprevent a control from succeeding are listed. Some conditions (eg mechanical failure) may be undetermined attime of read.
Request Function Code: 01- Read
Relay Control Block Control Object: Object 12 Variation 01 – Control Relay Output Block
Control relay output block parameters supported:• Control types are accepted on per point basis as shown in the table below.
TC = Trip/Close, P = Pulse ON/OFF, L = Latch ON/OFF.Set (1) = Close, Pulse ON, Latch ONCleared (0) = Trip, Pulse OFF, Latch OFFRecommended control types is shown in bold font.Note: Pulse OFF is not supported on most master station systems.
• The count, on-time, off-time, queue, and clear parameters are ignored.Request Function Codes: 03 – Select, 04 – Operate, 05 – Direct Operate,
06 – Direct Operate, No AckResponse Codes: Refer to Appendix C for a table of reported status values
LBS Binary Output Points
DN
P ID
Nam
e
Set =
‘1’
Cle
ared
= ‘0
’
Con
trol
Typ
e0 LBS Control Close
Rejected if:• Close coil is
isolated• CAPM is in LOCAL
control mode• SF6 gas pressure
is low (if applicable)AND low gaslockout is ON
• Work Tag isapplied
• Switchgear datainvalid
• Mechanicallyinterlocked
• Live load blockingON AND any loadside terminal live
TripRejected if:• Trip coil is isolated• SF6 gas pressure
is low (if applicable)• Switchgear data
invalid• Mechanically
interlocked
TC,L, P
Siemens Power Transmission & Distribution, Inc. 71
LBS Binary Output Points
DN
P ID
Nam
e
Set =
‘1’
Cle
ared
= ‘0
’
Con
trol
Typ
e
• Trip and/or Closecapacitors arecharging or failed
1 Work Tag Applies Work Tag.Rejected if:• CAPM is in LOCAL
Mode
Removed the WorkTag.Rejected if:• CAPM is in LOCAL
Mode.
L, P
2 Cold Load Idle/Max Set cold load time to itsmaximum value. Thismeans that the coldload threshold currentwill be set to itsmaximum valueRejected if:• Cold load support
is OFF
Set cold load time tozero. This means thatthe threshold multiplierwill not be affected bythe cold load function.Rejected if:• Cold load support
is OFF
L, P
3 Live Load Blocking Live Load blocking ON Live Load blocking OFF L, P4 Reset Fault
Flags and CurrentsNote 1
Resets all Object 30Fault Currents to zeroand clears all Object 01Detection trip flags
No Action L, P
5 Power Flow Direction Note 4 Source X, Load I Source I, Load X L, P6 Detection Group A Note 1, 3 Group A ON Note 5 No Action L, P7 Detection Group B Note 1, 3 Group B ON Note 5 No Action L, P8 Detection Group C Note 1, 3 Group C ON Note 5 No Action L, P9 Detection Group D Note 1, 3 Group D ON Note 5 No Action L, P10 Detection Group E Note 1, 3 Group E ON Note 5 No Action L, P11 Detection Group F Note 1, 3 Group F ON Note 5 No Action L, P12 Detection Group G Note 1, 3 Group G ON Note 5 No Action L, P13 Detection Group H Note 1, 3 Group H ON Note 5 No Action L, P14 Detection Group I Note 1, 3 Group I ON Note 5 No Action L, P15 Detection Group J Note 1, 3 Group J ON Note 5 No Action L, P16 Dummy Circuit Breaker DCB Close DCB Trip TC,
L, P17 Automatic Detection Group
SelectionAPGS ONRejected if APGS ON isNot Allowed
APGS OFF L, P
18 Supply Outage MeasurementControl
Supply OutageMeasurement ON
Supply OutageMeasurement OFF
L, P
19 Supply Outage MeasurementReset
Resets all SupplyOutage countersvalues.
No Action L, P
20 Sectionaliser Auto Turn Sectionalising ON Turn SectionalisingOFF.
L, P
Note:
Siemens Power Transmission & Distribution, Inc. 72
1. The response for binary output status for these points will always be 0.2. This point is only valid when the Loop Automation option is enabled for the current configuration otherwise No Action
is taken.3. Only one Detection group can be active at any one time. Activating any of these Detection groups will automatically
reset the previously active setting.4. Changing the Source/Load direction affects the following aspects of the operation of the CAPM:
• Whether the source or load corresponds to I side or X side on the voltage measurements• Which side is the source or load for the Live Load Blocking• Which side is the source or load for the Directional Blocking• Which direction is positive power flow for the System Power Analog Input• Power Flow Direction Binary Input status
5. The number of protection groups available in the CAPM is configurable. If a control is not available because theprotection set is not supported then it is rejected.
Siemens Power Transmission & Distribution, Inc. 73
Appendix O LBS - Analog Output PointsChanging some of these settings affects the currently active Detection group. The change is put into effect immediatelyand is permanent for that group. In other words, it is the equivalent to selecting that Detection group on the operatorcontrol panel, changing the setting and then putting the change into service.All analog output points have a matching analog input point. The CAPM does not return analog output object status inresponse to a class 0 or and integrity poll. It is recommended that the master station use the output’s correspondinganalog input status to verify the success of an action.
DNP V3.00 ImplementationAnalog Output StatusStatic Object: Object 40 Variation 02 – 16 Bit Analog StatusRequest Function Code: 01 – ReadAnalog Output BlockControl Object: Object 41 Variation 02 – 16 Bit Analog Output BlockRequest Function Codes: 03 – Select, 04 – Operate, 05 – Direct Operate,
06 – Direct Operate, No Ack
LBS Analog Output Point
DNP
ID
Nam
e
Min
Max
Units
0 Detection Group Selected0 = Group A1 = Group B…9 = Group J
0 9 N/A
Note:1. The number of protection groups available in the CAPM is configurable. If the analog output block value is not
available because the protection set is not supported then it is rejected.
s Siemens Power Transmission & Distribution, Inc.P.O. Box 29503Raleigh, NC 27626-0503
Manual No. RCDNP - 4808ASeptember 2001Rev: MJ-RL Panel, 324 rev 34