division 23 - hvac section 23 25 00 section 23 25 … 25 00.pdf · b. base hvac water treatment on...

6

Click here to load reader

Upload: vanthuan

Post on 30-Jul-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Division 23 - HVAC Section 23 25 00 SECTION 23 25 … 25 00.pdf · B. Base HVAC water treatment on quality of water available at ... and requirements and guidelines of authorities

Division 23 - HVAC Section 23 25 00090070 Switzerland Beallsville K-12 HVAC WATER TREATMENT

SECTION 23 25 00 — HVAC WATER TREATMENT

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and General Provisions of the Contract, including General and Supplementary Conditions andDivision 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes the following HVAC water-treatment systems:

1. Chemical treatment test equipment.

2. HVAC water-treatment chemicals.

1.3 PERFORMANCE REQUIREMENTS

A. Water quality for HVAC systems shall minimize corrosion, scale buildup, and biological growth foroptimum efficiency of HVAC equipment without creating a hazard to operating personnel or theenvironment.

B. Base HVAC water treatment on quality of water available at Project site, HVAC system equipmentmaterial characteristics and functional performance characteristics, operating personnel capabilities,and requirements and guidelines of authorities having jurisdiction.

C. Closed hydronic systems, including hot-water heating heat pump loop (inside building and completegeothermal bore field), and chilled water, shall have the following water qualities:

1. pH: Maintain a value within 9.0 to 10.5.

2. "P" Alkalinity: Maintain a value within 100 to 500 ppm.

3. Boron: Maintain a value within 100 to 200 ppm.

4. Chemical Oxygen Demand: Maintain a maximum value of 100 ppm.

5. Soluble Copper: Maintain a maximum value of 0.20 ppm.

6. TDS: Maintain a maximum value of 10 ppm.

7. Ammonia: Maintain a maximum value of 20 ppm.

8. Free Caustic Alkalinity: Maintain a maximum value of 20 ppm.

9. Microbiological Limits:

a. Total Aerobic Plate Count: Maintain a maximum value of 1000 organisms/ml.

b. Total Anaerobic Plate Count: Maintain a maximum value of 100 organisms/ml.

c. Nitrate Reducers: Maintain a maximum value of 100 organisms/ml.

d. Sulfate Reducers: Maintain a maximum value of 0 ber organisms/ml.

e. Iron Bacteria: Maintain a maximum value of 0 organisms/ml.

1.4 SUBMITTALS

A. Product Data: For each type of product indicated.

23 25 00-1

Page 2: Division 23 - HVAC Section 23 25 00 SECTION 23 25 … 25 00.pdf · B. Base HVAC water treatment on quality of water available at ... and requirements and guidelines of authorities

Division 23 - HVAC Section 23 25 00090070 Switzerland Beallsville K-12 HVAC WATER TREATMENT

B. Shop Drawings: Pretreatment and chemical treatment equipment showing tanks, maintenance spacerequired, and piping connections to HVAC systems. Include plans, elevations, sections, details, andattachments to other work.

1. Wiring Diagrams: Power and control wiring.

C. Field quality-control test reports.

D. Other Informational Submittals:

1. Water-Treatment Program: Written sequence of operation on an annual basis for the applicationequipment required to achieve water quality defined in the "Performance Requirements" Articleabove.

2. Water Analysis: Illustrate water quality available at Project site.

1.5 QUALITY ASSURANCE

A. HVAC Water-Treatment Service Provider Qualifications: An experienced HVAC water-treatment serviceprovider capable of analyzing water qualities, installing water-treatment equipment, and applying watertreatment as specified in this Section.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intendeduse.

C. Chemical shall meet all state and local pollution control regulations.

1.6 WARRANTY

A. Provide a 1 year chemical service program including testing and required materials and additives.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Aqua-Chem, Inc.; Cleaver-Brooks Div.

2. Boland Trane Services.

3. GE Betz.

4. GE Osmonics.

5. H-O-H Chemicals, Inc.

6. Metro Group. Inc. (The); Metropolitan Refining Div.

7. ONDEO Nalco Company.

8. Watcon, Inc.

2.2 MANUAL CHEMICAL-FEED EQUIPMENT

A. Bypass Feeders: Steel, with corrosion-resistant exterior coating, minimum 3-1/2-inch fill opening in thetop, and NPS 3/4 bottom inlet and top side outlet. Quarter turn or threaded fill cap with gasket seal anddiaphragm to lock the top on the feeder when exposed to system pressure in the vessel.

1. Capacity: 5 gal.

23 25 00-2

Page 3: Division 23 - HVAC Section 23 25 00 SECTION 23 25 … 25 00.pdf · B. Base HVAC water treatment on quality of water available at ... and requirements and guidelines of authorities

Division 23 - HVAC Section 23 25 00090070 Switzerland Beallsville K-12 HVAC WATER TREATMENT

2. Minimum Working Pressure: 125 psig.

2.3 CHEMICAL TREATMENT TEST EQUIPMENT

A. Test Kit: Manufacturer-recommended equipment and chemicals in a wall-mounting cabinet for testingpH, TDS, inhibitor, chloride, alkalinity, and hardness; sulfite and testable polymer tests for high-pressureboilers, and oxidizing biocide test for open cooling systems.

B. Corrosion Test-Coupon Assembly: Constructed of corrosive-resistant material, complete with piping,valves, and mild steel and copper coupons. Locate copper coupon downstream from mild steel couponin the test-coupon assembly.

1. Two-station rack for closed-loop systems.

2.4 CHEMICALS

A. Chemicals shall be as recommended by water-treatment system manufacturer that are compatible withpiping system components and connected equipment, and that can attain water quality specified inPart 1 "Performance Requirements" Article.

B. Chemical treatment for the closed-loop systems shall consist of a corrosion inhibitor for the protection ofboth ferrous and nonferrous metals. It shall be a nitrite/borax-based inhibitor with dispersants andalkalinity boosters. Chromate, sulfite, silicate, and phosphate-based treatments shall not be acceptable.

2.5 SYSTEM COMPONENTS

A. Bypass Shot Feeders: Cast iron or steel, 1.8-gallon capacity, 125-psig working-pressure rating.

B. Conductivity Probe: Provide complete with probe and flow switch and dual flat switch surface carbonelements. Maximum pressure shall not exceed 150 psi and maximum temperature shall not exceed 140degrees F.

C. Positive-displacement diaphragm pumps: Provide with ball type check valves, foot valves, and injectionfittings.

D. Chemical Solution Tanks: 50 gallon.

E. Packaged conductivity controller: Electronic operation with bleed and feed relays, feed timer, and digitaldisplay for control setting and adjustments.

F. Cold-water meter: Provide complete with contacting register sized to meter twice the volume ofmaximum makeup water rate for system.

G. Solenoid valves: Provide and wire as required.

H. Electronic timers: Provide a biocide control timer and lockout control timer.

I. Conductivity meter that compensates for differences in temperatures and analog meter.

PART 3 - EXECUTION

3.1 OPERATIONAL CLEANING

A. Upon completion of the system piping, including operational re-circulating pumps, the system is to bechemically cleaned. The chemical shall be capable of removing oil, grease, corrosion byproducts,

23 25 00-3

Page 4: Division 23 - HVAC Section 23 25 00 SECTION 23 25 … 25 00.pdf · B. Base HVAC water treatment on quality of water available at ... and requirements and guidelines of authorities

Division 23 - HVAC Section 23 25 00090070 Switzerland Beallsville K-12 HVAC WATER TREATMENT

welding slag, dirt, and other debris. All boilers, chillers, closed-loops, and other pertinent piping andequipment is to be cleaned prior to operation.

1.

Closed Systems - The cleaning agent acceptable manufacturers are listed in 2.1. Procedure shallbe similar to the following:

a. Add liquid alkaline compound with emulsifying agents and detergents (for grease andpetroleum removal) to the system at a rate of one to two gallons per 100 gallons ofcapacity. Recommended point of addition is through the shot feeder.

b. Heat the water to 180°F. If this temperature is not practical, heat the water as much aspossible.

c. Circulate system for 30 minutes and then test for Ph.

d. If the pH is above 8.5, continue circulating the system water for three hours. If the pH isbelow 8.5, add cleaning agent as needed to reach the 8.5 level. Allow the water to circulatefor three hours.

e. Drain the system and flush until no foaming is evident. With fresh water in the system,circulate for 30 minutes and then drain system.

f. When the system is cleaned and flushed, the Heating Contractor shall inform the CM andthe Engineer by means of a written letter. The letter shall state that the applicable systemshave been cleaned to the satisfaction of the specification.

g. As soon as possible after system startup, the Heating Contractor shall inform the watertreatment vendor to perform the first of twelve monthly visits.

h. The vendor shall supply material safety data sheets to the engineer, Heating Contractor,and other concerned parties.

B. Prior to connecting the heat pump to the condenser and chilled water loop, the piping loops shall beflushed with a detergent and hot water (110-130° F) mixture to remove previously accumulated dirt andother organic compunds. In old piping systems with heavy encrustation of inorganic materials consult awater treatment specialist for proper passivation and/or removal of these contaminants.1. During the flushing 30 mesh (max.) Y-strainers (or acceptable equivalent) shall be in place in the

system piping and examined periodically as necessary to remove collected residue. The flushingprocess shall take no less than 6 hours or until the strainers when examined after each flushingare clean. Old systems with heavy encrustation shall be flushed for a minimum of 24 hours andmay take as long as 48 hours before the filters run clean. Detergent and acid concentrationsshall be used in strict accordance with the respective chemical manufacturers instructions. Afterflushing with the detergent and/or dilute acid concentrations the system loop shall be purged withclean water for at least one hour to ensure that all residual cleaning chemicals have been flushedout.

3.2 WATER ANALYSIS

A. Perform an analysis of supply water to determine quality of water available at Project site.

3.3 INSTALLATION

A. Install chemical application equipment on concrete bases, level and plumb. Maintain manufacturer'srecommended clearances. Arrange units so controls and devices that require servicing are accessible.Anchor chemical tanks and floor-mounting accessories to substrate.

B. Install water testing equipment on wall near water chemical application equipment.

C. Install interconnecting control wiring for chemical treatment controls and sensors.

D. Mount sensors and injectors in piping circuits.

23 25 00-4

Page 5: Division 23 - HVAC Section 23 25 00 SECTION 23 25 … 25 00.pdf · B. Base HVAC water treatment on quality of water available at ... and requirements and guidelines of authorities

Division 23 - HVAC Section 23 25 00090070 Switzerland Beallsville K-12 HVAC WATER TREATMENT

E. Bypass Feeders: Install in closed hydronic systems, including hot-water heating and chilled water, andequipped with the following:

1. Install bypass feeder in a bypass circuit around circulating pumps, unless otherwise indicated onDrawings.

2. Install water meter in makeup water supply.

3. Install test-coupon assembly in bypass circuit around circulating pumps, unless otherwiseindicated on Drawings.

4. Install a gate or full-port ball isolation valves on inlet, outlet, and drain below feeder inlet.

5. Install a swing check on inlet after the isolation valve.

3.4 CONNECTIONS

A. Piping installation requirements are specified in other Division 23 Sections. Drawings indicate generalarrangement of piping, fittings, and specialties.

B. Install piping adjacent to equipment to allow service and maintenance.

C. Make piping connections between HVAC water-treatment equipment and dissimilar-metal piping withdielectric fittings. Dielectric fittings are specified in Division 23 Section "Common Work Results forHVAC."

D. Install shutoff valves on HVAC water-treatment equipment inlet and outlet. Metal general-duty valvesare specified in Division 23 Section "General-Duty Valves for HVAC Piping."

E. Refer to Division 22 Section "Domestic Water Piping Specialties" for backflow preventers required inmakeup water connections to potable-water systems.

F. Confirm applicable electrical requirements in Division 26 Sections for connecting electrical equipment.

G. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems."

H. Connect wiring according to Division 26 Section "Low-Voltage Electrical Power Conductors andCables."

3.5 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, andadjust components, assemblies, and equipment installations, including connections. Report results inwriting.

B. Perform tests and inspections and prepare test reports.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspectcomponents, assemblies, and equipment installations, including connections, and to assist intesting.

C. Tests and Inspections:

1. Inspect field-assembled components and equipment installation, including piping and electricalconnections.

2. Inspect piping and equipment to determine that systems and equipment have been cleaned,flushed, and filled with water, and are fully operational before introducing chemicals for water-treatment system.

3. Place HVAC water-treatment system into operation and calibrate controls during the preliminaryphase of HVAC systems' startup procedures.

23 25 00-5

Page 6: Division 23 - HVAC Section 23 25 00 SECTION 23 25 … 25 00.pdf · B. Base HVAC water treatment on quality of water available at ... and requirements and guidelines of authorities

Division 23 - HVAC Section 23 25 00090070 Switzerland Beallsville K-12 HVAC WATER TREATMENT

4. Do not enclose, cover, or put piping into operation until it is tested and satisfactory test results areachieved.

5. Test for leaks and defects. If testing is performed in segments, submit separate report for eachtest, complete with diagram of portion of piping tested.

6. Leave uncovered and unconcealed new, altered, extended, and replaced water piping until it hasbeen tested and approved. Expose work that has been covered or concealed before it has beentested and approved.

7. Cap and subject piping to static water pressure of 50 psig above operating pressure, withoutexceeding pressure rating of piping system materials. Isolate test source and allow test pressureto stand for four hours. Leaks and loss in test pressure constitute defects.

8. Repair leaks and defects with new materials and retest piping until no leaks exist.

D. Remove and replace malfunctioning units and retest as specified above.

E. At eight-week intervals following Substantial Completion, perform separate water analyses on hydronicsystems to show that automatic chemical-feed systems are maintaining water quality withinperformance requirements specified in this Section. Submit written reports of water analysis advisingOwner of changes necessary to adhere to Part 1 "Performance Requirements" Article.

F. Water Service Program: The chemical treatment contractor shall provide the chemical and consultingservices for 1 year from date of acceptance of system by the Owner.

G. Comply with ASTM D 3370 and with the following standards:

1. Silica: ASTM D 859.

2. Acidity and Alkalinity: ASTM D 1067.

3. Iron: ASTM D 1068.

4. Water Hardness: ASTM D 1126.

3.6 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust,operate, and maintain HVAC water-treatment systems and equipment. Refer to Division 01 Section"Demonstration and Training."

END OF SECTION 23 25 00

23 25 00-6