dimmer-tech note
DESCRIPTION
One major factor is the fluctuating voltage conditions at site. Both higher & lower voltages – over the rated voltage of equipment add to losses. In any POWER METER Bill – the user pays for these losses and can save substantial money in Billing costs apart from saving in Maintenance & Life costs of the equipment. Other major factor in Industrial connections is on account of difference in Power Factor of the connected loads varying from 1. Issue is what is Power Factor. We have explained Power Factor in quite details in second part of this note but briefly it is ratio of ACTUAL POWER and APPARENT POWER of a particular load. We should be accountable to ACTUAL POWER USAGE but Supply companies now charge for Apparent Power because their equipment & net work has to handle Apparent Power that needs to have HIGHER CAPACITY of their equipment and hence their higher costs. Some times the users are not aware of the seriousness of this LOSS FACTOR in their set up and users are paying as much asTRANSCRIPT
WHAT IS A "Dimmer Dot"
SALIENT FEATURES
CONSTRUCTIONAL FEATURES
The "Dimmer Dot" is a Variable Transformer and provide continuously adjustable voltage A.C.supplies. In its "Auto Transformer" from (type-D, as manufactured by Green Dot ElectricCorporation), it is an efficient, reliable method of controlling A.C. voltage from zero to linevoltage by amplitude modulation of the A.C. waveform. Since the Current, Power, Heat, Lightand Motor speed are further functions of the voltage, the "Dimmer Dot" Variable Transformerfinds its varied use. A few of the applications are
***
*
*
*
*
The versatility of control are further high lighted in a separate publication "Tech Note" on"Dimmer Dot" Variable Transformers. The circuitories there in are only a few of theapplications.
Control of A.C. voltage in testing and development work.
Over voltage and undervoltage tests.
Voltage control of aging racks for lamps, vacuum tubes,
dry disk rectifiers, etc.
Voltage control in power supplies -as for Servo-type,
Automatic Voltage Stabilizers, constant current supplies etc.
Voltage control for meter calibration, phase-angle control in
the calibration of wattmeters and power-factor meters.
* Motor speed control.
Control of electric heaters and ovens in laboratory, pilot plant,
and production line.
Lighting control in theater, auditoriums, photographic studio
and dark rooms.
The "Dimmer Dot" Variable Transformer, type-D consists of single layer winding on toroidalsilicon-steel core. As the control knob is rotated, a carbon traverses the winding, tapping off aportion of the total voltage across the winding. The brush is in continuous contact with thewinding, and the voltage between turns is always less than I volt, even in the largest model; inthe smallest model it is only about 0.3 volt. The discrete voltage increments obtained as theknob is rotated are always less than the voltage between turns. Since the brush spans morethan one turn, the change in voltage is practically continuous. The brush is so designed thatexcessive heating can not occur in the turns that it spans.
"Dimmer Dot" have many operating advantages over any other manually operated voltagecontrol device for alternating-current use. Amongst the more important features are:
GOOD REGULATION - Output voltage is substantially independent ofload.
SMOOTH CONTROL - The "Dimmer Dot" can be set very closely set toany output within its range.
HIGH EFFICIENCY - Very low losses under all load conditions.
LONG LIFE - With the exclusive "Dura Dot" contact surface,the life of the "Dimmer Dot" Variable Transformer is
essentially the same as that of any standard fixed-ratio power trans
LINEAR OUTPUT VOLTAGE - Output voltage is continuously adjustablefrom 0 to 112% of line by approximately 340degrees and in certain models it is more in certainmodels. The dial reads directly in no load outputvoltage at rated line voltage or some dials arecalibrated fo rpercentage of the full range control.
MODERATE TEMPERATURE RISE - Less than 50 degrees forcontinuous operation.
ADVANCED MECHANICAL DESIGN - Rugged construction - no delicateparts-two or more units can be ganged on sameshaft-shaft is reversible for simple conversion
from front to back-of-panel mounting.
Constructional features as different from other Variable Transformers lie in respect ofINSULATION - that the insulation between windings and core is provided by mouldings so as toprevent any possibility of slackening of the turns during use and also to proved for a uniformhard bed under surface for the winding so as to make a strong base and under surface for longlife of the track.
Green Dot
Electric Limited
Tech NotesTech Notes 1
R
Variable VoltageAuto Transformers
Dimmer Dot
WINDINGS
BRUSH MECHANISM
FRAMES
BACK OF PANEL
-
BEARINGS -
GENERAL - the "DIMMER DOTS”
- are of high conductivity copper insulated with synthetic enamel of
thepolyvinyl acetal-phenol formaldehyde resin type providing good space factor,
extremely high abrasion resistance and having a good ability to resist the effects of
prolonged heating. The windings are done by toroidal winding machines specially
designed and developed by Green Dot during the past number of years to produce
Constant winding tension and even pith. The winding are prevented from any possible
movement during use by providing serrations on the winding rings and the further
fixing the under pressure & use of high temperature bearing epoxies, through a special
technique developed over years of experience.
- "DIMMER DOT" Transformers are known for their trouble free
brush gear. They have produced a self aligning brush mechanism which fulfils the
following requirements.
- Minimum heating and wear
- Maximum contact area
- Constant contact resistance and losses
The temperature rise of brush mechanism and winding in any Variable Transformer, is
dependent upon the contact pressure and the area of contact, which in turn decides the
current in the short circuit, which in turn decides the current in the short circuited turn
and brush face. "DIMMER DOT" brush mechanism have been developed to provide a
constant brush contact area. The brush mounting holds the brush vertically in the
direction of travel, so as to ensure that the same contact are is presented to the winding
at all times with constant pressure. This enables the full contact are to be maintained,
with resultant minimum contact temperature. They are provided with extra grip holder,
greatly increasing their physical strength and offering great resistance to damage from
shock and rough usage. The track cannot be shorted by metal brush holder fittings
even in the worst conditions.
the wound core are held strongly and insulated from mounting fixture so as
to proved minim high voltage standing of 2.5KV. The economised models are also
available for OEM uses. The facilities can be provided for fitting stops and micro
switches.
the units are fitted with bearings, of bush type of nylon or glass filled
nylon, for higher sizes, heat and light stabilized unaffected by atmospheric conditions,
or sintered modified bronze or sintered bronze, self lubricating type as not to need
lubrication through the life time of the product or the ball bearings as optional or the
motorised unit. While ganging up the units of two or more numbers, the intermediate
bearing guides are removed to provide rotary smooth operation. The Torque figures for
various models can be had on request.
are manufactured in certain fixed sizes determined by
the voltage and current ratings. Type-D are manufactured in 0.7, 2, 4, 8, 15, 28, 40,
50, 60, 75, 100, 150 and 200Amps., and voltages of Input 270 Volts for 1Phase with
taps at 0-30-240-270 voltages so that for 3 Phase operations, 3 single Phase unit can
be connected in Star so as to provide for 470 Volts phase to phase connection facility.
Invariably all 3 Phase units are ganged assemblies of 3 single Phase units
mounted on a common shaft. The facility exists for changing the shaft to make front
shaft unit to back shaft unit suitable for back of panel mounting for 4, 8, 15 and 28
Amps units of single phase type. The 3 Phase units of back of panel and mounting have
to be placed on supported structure at the back of the panel and the frond shaft can be
brought through panel hole, obviously such arrangements can be for the air natural
cooled unit. For the oil cooled units the containers have to be placed at the back of the
panel and mounted or suitably held by keeping the unit with shaft in vertical position. 3
phase units are not available in 0.7 Amps. All the units are either fitted with screen
printed insulating plates with schematic wiring diagram shown thereon or with a
connection marking plate fixed there upon. The standard connection diagram and
markings on the terminal plates are as follows
- "DIMMER DOT" Units type D, of 4, 8, 15 & 28 Amps. ratings, single
phase may be used either surface mounted or back of panel mounted. For ease of
packing and transportation, at times, standard models are supplied for surface
mounting, but the user can easily convert them to back of panel mounting, simply by
removing the shaft locks or clamping rings by simply loosening he screws thereupon.
The spindle or shaft is then adjusted after inserting from the other end,
spacers/washers are suitably placed so that proper free movement of the moving arm
without getting disturbed from the tail end and stopper is obtained with proper usable
length of the Carbon from the Carbon Brush Holder available on track. Sufficient
pressure from the spring holding the Carbon Brush must be ensured as available on the
winding track.
BRUSH MECHANISM
GreenDot Tech NotesTech Notes
-2-
Variable VoltageAuto Transformers
Dimmer DotR
1
METRIC CONVERSION
TRACK PREPARATION
LONGER LIFE
-
OVER LOADS
LESS MAINTENANCE
DIMMER DOT TECHNICAL SPECIFICATIONS :
RATING :
Small screws used in the models at present are B.A. sizes, 2, 4
& 6 B.A. having been used at small paces and conversions are being carried out to metric
size. The changes are being carried out in a phase manner & is being intimated by sales
department separately.
- "DURA DOT" track-" Green Dot " has developed over the years
sophisticated track preparation method which provide fine tracks, designed to providing
close tolerance surfaces. The optically ground tracks are plated with a hard silver alloy,
ensuring constant resistance. After a quarter of million operating cycles, the Brush wear
is only approximately 0.001 inch. This will allow for approximately 30 millions operating
cycles before Brush wear demands a replacement Brush. "DURA DOT" contact surface is
one of the most exclusive achievement made by "Dimmer Dot" for greater reliability, less
maintenance and longer life of the "DIMMER DOT" variable Transformers. The contact
surface eliminates all oxidation problems involved in the use of a carbon brush and care-
copper contact and have the further following features to claim
- essentially the same as that of any fixed ratio transformers. Failures in
any "DURA DOT" Dimmer are almost unknown. They are caused only by some
factorswhich affect any standard fixed ratio transformer: such as due to failure of
insulation because of prolonged over extended periods at currents in excess of rated.
HIGH INITIAL SURGE CURRENTS- all Dimmer with "DURA DOT" contact surface will
withstand initial surges ten times the rated current; they do not have to derated even for
incandescent lamp loads (with may draw up to nine times rated current when first turned
on)
- the time - current curve given in these pages is the safe allowable
overload for "DURA DOT" Coated Dimmer-these overloads are considerably higher than
the older types of Dimmers.
- under normal conditions, maintenance of "DURA DOTS" is
negligible-an occasional wiping of the contact surface with an alcohol-moistened rag
being all that is required-the "DURA DOT" contact surface is subject to no deterioration
when "DIMMER DOT" is operated with their rated loads.
Ratings quoted are for use in ambient temperature from -20'C to +50'C. Current
derating figures for temperatures above 50'C are as follows :
55'C 60'C 65'C 70'C
0.95 0.87 0.78 0.68
Generally, when the operation is required in ambient temperatures higher than
50'C output current must be reduced according to the curve shown below:
The current that may be drawn from a "Dimmer Dot" transformer through the brush is
not constant as in fixed auto wound transformers, but varies according to brush
position. At 50% and 110% of the line voltage, winding heat is the current limiting
factor. Near zero and line voltage, winding heat is low and brush heat becomes the
current limiting factor. Both factors operate at intermediate brush positions. This is
common to all continuously variable "Dimmer Dot" Transformers. The "Dimmer Dot"
ratings, in terms of "Rated Currents" "Maximum Currents" etc. should be fully
understood for optimum results.
100
90
80
70
60
50
40
30
20
10
03086 104 122 140 158 176 194 Deg. F
40 50 60 70 80 90 Deg.C
"Dimmer Dot" Auto Transformerderating resus ambient
temperature
%N
OR
MA
LR
AT
ING
AMBIENT TEMPERATURE
-3-
GreenDot Tech NotesTech Notes
R
Variable VoltageAuto Transformers
Dimmer DotR
1
CURRENT RATINGS
RATED CURRENT :
MAXIMUM CURRENT:
It is general practice to specify the current rating of Variable Transformer by two
values, the rated current and the maximum current.
Dimmer Dot have two current ratings because in any adjustable auto transformer,
heating of the winding varies with the brush setting. To limit these useful devices to
the current that can be drawn at any setting (RATED CURRENT) places an undue
restriction on the capabilities.
Most load (possible exceptions are some kind of motors and incandescent lamp loads)
which draw MAXIMUM CURRENT at line voltage may be safely regulated from zero to
line voltage without danger of overload. This MAXIMUM CURRENT is generally 20 to 30
percent above the RATED CURRENT and this concept may be safely used to full up the
gap in the capacities of the RATED CURRENT of the various model available.
The rated current can be drawn at any brush setting. When the over-voltage connection is
used, the load should not be drawn more than rated current.
May only be drawn near zero or near maximum output voltage when t h e
Dimmer Dot transformer is line connected, i.e. when connected for an output voltage
range of zero to line voltage. See Current Rating Curves.
CURRENT RATINGS
It is general practice to
The Maximum Current can only be drawn in line-voltage connection with the listed
(or lower) input voltage across the whole "Dimmer Dot" winding (e.g. 240 volts on a
240/270 volt unit), and can only be drawn near zero or at or near full output
voltage. A load having linear voltage/current load, line (constant impedance load
drawing maximum current at the line voltage can be controlled from zero to line
voltage.
The knowledge of the maximum current and the rated current for the particular end
application can be useful for filling in the capacity gap for the "Dimmer Dots" in the
range and thus intermediate current requirements can at time be met from the
particular rating valued "Dimmer Dots".
KVA RATINGS
OVER VOLTAGE CONNECTIONS:
SHORT TERM RATTING FOR INTERMITTENT OF SHORT TIME OPERATION:
Equals nominal input voltage multiplied by maximum current output. KVA rating for
over voltage connection, equals output voltage multiplied by rated current.
A "Dimmer Dot" transformer connected for over voltage provides an output of 12 %
above the supply voltage on load. Most models have terminations for line voltage or
over voltage connection, at the option of the user.
Rated' current only may be drawn when over voltage connected.
The short term rating is also indicated on the curve and this is a maximum current
that can be drawn on intermittent duty. This has been further discussed under the
heading "Overloading" how to select a "Dimmer Dot", load rating and a trade off-life
Vs increased rating. These all demonstrate high overload capacity of Dimmer Dot
transformers, particularly where high initial surge currents may be expected or
where high current is required for a short period of time. Care must be taken to
ensure that these rating are not exceeded.
120
MAX. CURRENT MAYBE DRAWN HERE
MAX. CURRENT MAYBE DRAWN HERE
110
100
90
80
70
60
50
40
30
20
10
10 20 30 40 50 60 70
BRUSH SETTING AS PERCENTAGE OF SUPPLY VOLTAGEOU
TPU
TC
UR
RE
NT
INP
ER
CE
NTA
GE
OF
RAT
ED
CU
RR
EN
T
80 90 100 1100
RATED CURRENT MUST NOT
BE EXCEEDED HERE
TUNGSTEN LAMP
LOAD
CURRENT DRAWN
BY CONSTANT
IMPEDANCE LOAD
LINE VOLTAGE LIMIT OF
Dimmer Dot RANGE WHEN
OVER VOLTAGE CONNECTION
IN NOT USED
MAX. PERMISSIBLE
CURRENT
"GREEN DOT "
RATING CURRENT
RATED CURRENT
-4-
GreenDot Tech NotesTech Notes Variable Voltage
Auto Transformers
Dimmer DotR
R
1
The load current capacity of the "DIMMER" is limited temperature
and life. Specified ratings assume a maximum ambient
temperature of 50'C and minimum life span of 7 years. If the
expected ambient is lower or forced cooling is possible, the auto
transformer can be updated without affecting life. Also, if a
shortened life is not a problem in your application, a further
uprating can be realized.
Further, if the load is expected to be switched on and off regularly
(as with a thermostatically-controlled heater), the Dimmer can be
uprated. In general, if the time for an on-off cycle is 2 hours or less
and the off time is 10% or more of the total cycle time, some
significant improvement in rating can be realized.
Thus the careful overloading of the "DIMMER DOT" Auto
Transformer can take advantage of any design trade-offs. To
amplify it further, as an example, the current rating of all models
assume trouble-free operation 24 hours a day, after day. If a
"DIMMER" IS TO BE U SED ONLY FOR 2 Hours or less per day,
significantly more than rated current can be drawn for that short
period. The figure below shows how upto 10 times the normal
rating can be realized.
EFFECT OF DUTY CYCLE
When the duty-cycle operation is contiguous, the rating should be
determined by considerations of "off-puls-on' time to "on-time";
the rated current can be multiplied by the square root of this ratio to
obtain the allowable uprated current. The following examples will
illustrate the calculations of permissible overloads for a typical 4
Amps. model.
Example 1: The load is on for 15 seconds out of every 4
minutes (240 seconds).
duty cycle = 4
duty-cycle uprated current = 4 A x 4 = 16 A
From figure for the "Short-time overload characteristic of "DIMMER
DOT" Auto Transformers with Line voltage connections", 15
seconds overload uprates the current by 500% so that,
short-term overload current =4 A x 5 = 20 A.
Since the lower rating takes precedence, the 16 Amps, limitation
imposed by the duty ratio is the maximum current permissible.
Note, on the overload curve of the figure, the lower curve must be
used for models with build-in-fuses.
Example 2: The load is one for 6 seconds out of
each minute (60 seconds) over a duration of one-
half hour.
Duty cycle = = 3.16
Short-term overload for 30 minutes = 133%
from duty cycle and 30 minute short-term overload
considerations:
uprated current = 4 A x 3.16 x 1.33 = 16.4 A
short-term overload current = 4 A x 7.25 = 29 A.
Since the lower rating takes precedence, the 16.4 A limitation
imposed by the duty-cycle and 30 minute short-term overload is
the maximum current permissible.
When the effects of temperature upon rating and upon insulation
life are combined, a new life load ambient relationship is obtained.
The figure "Life-load-ambient-curve" illustrates this relationship.
Except for reference to the effect of duty, cycle, all previous rating
methods have been based on steady-state, 24 hours-a-day
operation for a calculated minimum for increased rating or vice-
versa. Following the load-ambient curve, uprating or derating
could be done on the "DIMMER DOT" rating. The limit of ten times
the rated current should never, under any circumstances, be
exceeded.
As an example, consider the case of a 4 Amps. unit again. For
operation at 30'C ambient temperature, suppose there is a
requirement of 400 hours of minimum life expectation of the unit.
It is desired to find out the value of the allowable current under
such operating conditions. The calculations are as follows:
Uprating for 30'C ambient , 400 hours life 1.65
Duty cycle (as of the example 1) x 4
Resultant uprating factor 6.60
Rating of the unit x 4 A
Allowable current from duty cycle 26.6
Uprating for 30'C ambient, 400 hour life 1.65
15 second short-term overload factor .. x 5
Resultant uprating 8.25
Rating of the unit x 4 A
Allowable current from short-term overload . 34A
Since 26.6 is the smaller, it is the limiting value; thus the allowable
current is 26.6 amperes.
The Dimmer Dot variable transformers are manufactured to
conform to Indian Standard Specifications. IS:5142, Specification
for continuously variable voltage Auto-Transformers and the
manufacturers Test Report for the relevant Routine Test can be
furnished on demand. The Type Test are carried out only on sample
units in the production run to ensure conformity to the designs.
60'C average temperature rise measured by change of winding
resistance at rated current with brush set in maximum heating
position, i.e. with out voltage set at half input voltage on full load.
The temperature rise of the winding im immediately under the
brush, will of course higher than this. Operating temperatures of
the brush contact can be permitted up to 200'C depending on
model.
Standard Dimmer Dots are designed for 50/60 Hz. Supplies. All
models may be used on higher frequencies upto 400Hz. but slight
deterioration of regulation, and output current must be derated by
25%. High frequency models designed for 400-2500 Hz. Supplies
can be available.
Dimmer Dot transformer can be used on frequencies below 50 Hz.
if the input voltage is reduced in proportion. Output current
remains as listed and must not be increased.
All "Dimmer Dot" transformers are flash tested at 2500 Volts
R.M.S. for one minute during test.mediately under the brush, will
of course higher than this. Operating temperatures of the brush
contact can be permitted up to 200'C depending on model.
STANDARD SPECIFICATIONS
FREQUENCY:
TEMPERATURE RISE:
FLASH TEST:
606
-5-
GreenDot Tech NotesTech Notes
20
40
60
80
100
120
140
160
180
200
0.109 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
0.219 0 +10 20 30 40 50 60 70 80 90 100 110 120 130 140
0.438 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130
0.675 20 10- 0 +10 20 30 40 50 60 70 80 90 100 110 120
1.75 30 20 10- 0 +10 20 30 40 50 60 70 80 90 100 110
3.5 40 30 20 10- 0 +10 20 30 40 50 60 70 80 90 100
7 50 40 30 20 10- 0 +10 20 30 40 50 60 70 80 90
14 60 50 40 30 20 10- 0 +10 20 30 40 50 60 70 80
28 70 60 50 40 30 20 10- 0 +10 20 30 40 50 60 70
56 80 70 60 50 40 30 20 10- 0 +10 20 30 40 50 60
112 90 80 70 60 50 40 30 20 10- 0 +10 20 30 40 50
100
80
60
40
20
PercentNormalRating
Normal Rating
Normal Derating Point +50 Co
NormalMinimum
Life
MinimumLife-Years
Ambient TemperatureDegree Centigrade
MinimumLife-Hours
0.001
%N
OR
MA
LR
AT
ING
TIME IN MINUTES
0.01 0.1 1 2 5 10 100
200
300
400
500
600
700
900
800
1000
1000 10000
OVERLOAD LIMIT
Shaded area for units withover load protector ¼ HOUR-150%
½ HOUR-133%
1 HOUR-120%
24 HOUR-100%
Short- time over load characteristicof Green Dot Auto Transformers
Variable VoltageAuto Transformers
Dimmer DotR
R
240
15
1
NO LOAD LOSS
DRIVING TORQUE:
REGULATION:
OVERLOAD PROTECTION:
OUTPUT CONNECTIONS :
Measured in Watts at 50 Hz. for standard models and 400 Hz. for
higher frequency models at rated input voltage.
The no load losses include the core and brush loss and since the
brush always spans 2 more turns this also include the watt losses
due to the short circuit current over the brush position.
The figures for driving torque required to turn the shaft can be
provided on request. The figures quoted are maximum figures.
Although 'Dimmer Dot" are designed for arduous industrial use,
damage will occur if they are subjected to short circuit or
continuous severe overload.
It is therefore recommended that protective devices be fitted such
as a circuit breaker in the input circuit & and H.R.C. fuse in the load
circuit.
It is normal practice to provide a protective device in the input
circuit. Improved core materials, permitting higher flux densities
than was possible in the past, allow high inrush transient surges of
up to 10 times the rated current to occur at switch on. This is not
harmful except H.R.C. fuses or protective devices of instantaneous
operation. It is therefore recommended that input protection
"Dimmer Dot" is obtained by employing slow blow fuses or circuit
breakers with slight operating delay. Input protective devices
should be capable of handling 1000% overload for one cycle of the
supply frequency.
It is not always appreciated that a variable transformer with an
input voltage of 250 V and delivering say 10 amps to a load at 50 V
(0.5 KVA), will draw a current of only 2 amps from the supply
mains. It this instance, a 10 amp. fuse laced in the input circuit
would not rupture until the load current reached 50 amps . It is
obvious, therefore, that input protective device afford little
protection to the transformer against overloads at low output
voltage. The solution is, of course, to fuse the load circuit with an
H.R.C. fuse link.
"Line voltage connection" refers to the connection of a "Dimmer
Dot" transformer for an output voltage of zero to line voltage. "Over
voltage connection" refers to the input voltage connection for a
range of output voltage from zero to 12% of line voltage.
Regulation expressed as a percentage of supply voltage is defined
as output voltage change from no load to full load, with constant
input and set output voltage. Regulation varies because copper loss
will vary with brush setting. Resistance of the brush and leakage
reactance caused by stray flux also contributes to the regulation.
Typical regulation figures vary between 0.5% to 3.0% according to
model and brush setting.
The figure shows the regulation drop under load for the Dimmer
Dots. This curve applies to all model operated normally or rated
input voltage and RATED load current.With insignificant change it
applies equally to both OVERVOLTAGE and LINE-VOLTAGE output
connections.
The figure shows the regulation curve of Dimmer Dot operation
under conditions similar to those of previous figure except that this
curve applies to all models operating at one-half normal rated line
voltage and one-half normal rated current . This covers such
special connections as to secure 0 to 270 Volts output from a 155
Volts line.
RESOLUTION
KNOBS & HANDWHEELS:
DIALS:
ANGLE OF ROTATION:
WHEELED UNITS AND SEMI PORTABLE-LABORATORY
MODELS:
METERED UNIT:
:
"Dimmer Dot" resolution is extremely good as the resistive brush
always covers two or more turns, therefore the voltage increments
obtained by rotation of the knob will always be less than the
voltage between turns. Careful design of the brush ensures that
excessive heating cannot occur in the turns that it covers. Number
of turns for standard models data can be supplied on request.
"Dimmer Dot" standard fitting knob and handwheels are used
through out the range of "Dimmer Dot". For OEMs applications,
where knob, handwheels or dials are not needed suitable reduction
in prices is given.
Dials are anodized aluminium, printed either in percentage of
output voltage or approximately of output voltage for 240 Volts
input voltages. For panel applications, there type of dials are
available for variety purpose. Dials of 0-270 V, are also available
a fixed censor on the panel or alternately they may be mounted
on the panel and used to the pointer which is provided on
underneath of the knob.
All models, are supplied with a angle of rotation of approx. 320'
and effects are being made to increase the angle of rotation so as
to have better utilization of core and winding.
Enclosed unit of 40 Amps capacity and above are transportable on
wheeled enclosures. Smaller units can be supplied with 4 wheeled
enclosures or 2 wheel enclosures with additional two front stud
supports and a push trolley type handle on the wheeled end to
make them SEMI PORTABLE for laboratory use.
Metered units, fitted with Volt meter, or a Volt meter and an
Ammeter or only an Ammeter can be provided on request at extra
cost.
0 20 40 60 80 100
1
2
3
REG
ULATIO
NIN
%O
FLIN
EVO
LTS
DIAL SETTING IN PERCENT OF LINE VOLTAGE
LINE VOLTS
REG
ULATIO
NIN
%O
FLIN
EVO
LTS
DIAL SETTING IN PERCENT OF LINE VOLTAGE
15
10
5
040 80 120 160 200 240
6
5
4
3
2
1
60 90 120 150 180 210 240 27030
LINE VOLTAGECONNECTION
NO LOAD VOLTAGE
DRO
PIN
VO
LTAG
EO
NLO
AD
ING
LINE VOLTS
-6-
GreenDot Tech NotesTech Notes Variable Voltage
Auto Transformers
Dimmer DotR
R
1
CONNECTIONS (INSTALLATION)
STARTING UP (INSTALLATIONS)
MOTOR DRIVE (INSTALLATION)
INSTALLATION
MAINTENANCE
All transformers listed in our standard range are designed for continuous operation in
normal operating mode. Enquiries should be submitted as to loading capacities where
operation under severe loading is to be anticipated. The variable transformers are
connected after comparing the existing mains voltage supply with that shown on the
transformer data plate. The main input is to be connected at the places shown very
carefully. It has been seen that large number of damages to the variable transformers take
place on wrong connections at input mains, at the time of installations, and these damages
are at the time of permanent nature as to totally damage the variable transformer. In the
case of three phase toroidal variable transformers the neutral point is led out, and can be
subjected to full loading. In the case of distinctly a symmetrical mains systems the
transformer can suffer damage. Depending on local regulations it will either be necessary
for the transformer frame to be earthed or connected with the neutral conductor in the
mains system.
In the case of variable transformers in economizing circuit no winding terminal should be
earthed mains systems. If necessary a transformer with separate wending must be
coupled in series or a toroidal variable transformer with separate winding used.
With starting up care must be taken to ensure that the shaft on toroidal variable
transformer is not arrested at the top and bottom ends of the winding. Any attempt to
turn the shaft further will cause serious damage to the mechanical equipment.
Variable transformer must be protected sit with the plant against overload and short
circuits, e.g. fusible cutouts, circuit breakers or similar. It is also necessary to take account
of the current time parameter of the protective measure used. Attention is drawn to the
fact that unilateral protection can be inadequate, as the current transformation ratio is
variable.
Where fuse protection is the input end the user must take full account of the switch-on
process which in the case of transformers with core material of high permeability,
generates a cut in current surge which, in unfavorable circumstances, can achieve 20 times
the level of the current rating. This current surge may achieve 30 times the level of the
current rating in the case of variable transformers with separate windings. As this current
surge falls off extremely quickly it does not result in any damage to the transformer.
Automatic cutout and quick-action fuses can, however, react to this current surge, so that,
wherever possible, the use of slow action fuses or circuit breakers is recommended.
After checking the voltage data AC motor drive systems can be connected to the terminals
marked accordingly. Mains supply is connected to the terminals marked with relevant
voltages, the push-button for downward motion to "Min" and the centre terminal, the push
button for upward motion to "Max" and centre terminal. Three phase motor drive systems
are connected accordingly and these drive systems are controlled by reversing contactors.
DC motor drive systems are connected as per the recommended circuit diagram. With all
motor drive systems limit switches are normally set to "Min" and "Max". The switching
points can be varied as required by simply resetting the completes, where so ever
provided.
When installing the Dimmer Dot toroidal variable transformers care must be taken to avoid
impairing the cooling system, as otherwise the variable transformer could be subject to
overload as a result of heat buildup, even at rated operation levels and ambient
temperatures of 40 degree Centigrade. The transformer shaft may not be given any
mutually conductive connection with the surrounding metallic housing, as this will result in
shorted turns and consequent permanent damage to the transformer.
The carbon brushes and carbon rolls are subject to natural wear and tear which, in turn, is
governed very much by local operating condition and functional circumstances to which the
variable transformer is subject. Rapid wear, however, can result only form persistent
overloading and extraordinary fouling of the contact track. Regular maintenance is
advisable and, in normal operation, should be carried out at six-month intervals, as
follows:
The contact track must be cleaned of all traces of dirt, using a soft fluff-free cloth moistened
with a suitable degreasing fluid, e.g. alcohol or similar. The carbon roll bearings must not be
oiled.
Regular maintenance will guarantee satisfactory functioning and greatly increase
operational liability and durability. Fulfillment of warranty obligations is conditional upon
proof being furnished as to compliance with instructions for use. Where parts have to be
replaced only genuine replacements approved or manufactured by us may be employed.
-7-
GreenDot Tech NotesTech Notes Variable Voltage
Auto Transformers
Dimmer DotR
R
1
OIL-IMMERSED DIMMER DOTS:
MOTOR DRIVES :
Oil immersion provides increased current rating of approximately
70% and protection for use in adverse environments. Some of the
models are economical on a rating/cost basis when compared with
air-cooled types, providing intermediate or increased ratings.
When environmental protection, such as in electroplating
workshops, textile mills, oil and ghee plants, is needed, the
Dimmer Dots must always be used in oil immersed form.
Right angle drives can be fitted, for use when the Dimmer Dots, oil-
immersed types stand behind a panel.
Motor drives, with time for full sweep of 15, 30, 45, 60, 90 or 120
seconds, fitted with "Stepper Dot" A.C. Synchronous motor,
workable on 220-240 Volts, Single phase A.C. Supply. The motor
drives are fitted with micro switches at limits, to cut off the motor
supply extreme positions. The covered motorised units are fitted
with push button controls for raise and Lower operations and have
to be indicated at the time of ordering. The remote control facility
can be provided at extra cost, if the same is not amounted on the
unit.
Special motor drives fitted with D.C. motors or Low voltage motors
can be supplied to special order. Special assemblies can be
provided with switching and relays, giving a programmed
automatic sequence of operation.
Further details on the motor drives, separate technical note is
available.
SPECIAL VOLTAGE RANGE:
DRAWINGS:/
TECHNICAL ASSISTANCE:
HAZARD WARNING:
Where quantities are sufficient to warrant special productions,
special windings to suit customer's particular requirements can be
supplied.
Detailed drawings can be supplied in cases where dimensions are
critical.
Our sales Engineers are will qualified to advise and assist you with
the selection and application of "Dimmer Dot" transformers.
Dimmer Dot operate at mains voltage and above, and installation,
connection and maintenance must be carried out in accordance
with good engineering practice by qualified personnel. Open
models are intended only for installation as components and must
be considered carefully and the notes on installation and
maintenance and any specific information supplied with Dimmer
Dots adhered to strictly.
No warranty is implied as to fitness for use in any specific
application or installation unless full details have been provided
and we have given specific approval in writing.
Dimmer DotR
Variable Voltage AutoTransformers
D i v i s i o n
Green Dot
Electric CorporationGreen Dot Electric Corporation (the "Company"), New Delhi, warrants to the first end user purchaser (the "Purchaser",) of equipment
manufactured by the Company that such equipment, if new unused and in original unopened cartons at the time of purchase will be
free from defects in material and workmanship under normal use and service for a period of one year from date of delivery for the
Company or for a period of one year form the date of delivery from the business establishment of an authorised dealer of the Company
in the event that the equipment is purchased from an authorised dealer.
THE COMPANY'S OBLIGATION UNDER THIS WARRANTY SHALL BE STRICTLY AND EXCLUSIVELY LIMITED TO REPAIRING OF
REPLACING AT THE FACTORY OR A SERVICE CENTRE OF THE COMPANY, ANY SUCH EQUIPMENT OR PARTS THEREOF WHICH AN
AUTHORISED REPRESENTATIVE OF THE COMPANY FINDS TO THE DEFECTIVE IN MATERIAL OR WORKMANSHIP UNDER NORMAL USE
AND SERVICE WITHIN SUCH PERIOD OF ONE YEAR. THE COMPANY RESERVES THE RIGHT TO SATISFY SUCH OBLIGATION IN PULL BY
REFUNDING THE FULL PURCHASE OF ANY SUCH DEFECTIVE EQUIPMENT.
This warranty does not apply to any equipment which has been tampered with or altered in any way, which has been improperly
installed or which has been subject to misuse, neglect or accident.
THE FOREGOING WARRANTY IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATIONS,
ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, and of any other obligations or liabilities
on the part of the Company: and no person is authorised to assume for the company any other liability with respect to equipment
manufactured by the Company. The Company shall have no liability with respect to equipment not of its manufacture. THE COMPANY
SHALL HAVE NO LIABILITY WHATSOEVER IN ANY EVENT OF ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING, WITHOUT
LIMITATIONS, DAMAGES FOR INJURY TO ANY PERSON OR PROPERTY.
Written authorisation to return any equipment or part thereof must be obtained from the company. The Company shall not be
responsible for any transportation charges.
IF FOR ANY REASON ANY OF THE FOREGOING PROVISIONS SHALL BE INEFFECTIVE, THE COMPANY'S LIABILITY IS BASED ON
WARRANTY, CONTRACT, NEGLIGENCE, STRICT LIABILITY IN TORT OR OTHERWISE, SHALL BOT IN ANY EVENT EXCEED THE FULL
PURCHASE PRICE OF SUCH EQUIPMENT.
Any action against the Company based upon any liability or obligation arising hereunder or under any law applicable to the sale of
equipment, or the user thereof, must be commenced within one year after the cause of such action arises.
W A R R A N T Y
-8-
GreenDot Tech NotesTech Notes Variable Voltage
Auto Transformers
Dimmer DotR
R
1