Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter for Draft Range Applications TRUE DRAFT RANGE OFFERING Pressure range –3.0 to 3.0 inH 2 O (–750 to 750 Pa) with spans as small as 0.1 inH 2 O (25 Pa) Accuracy: ± 0.10% of range Redesigned capacitance sensor optimized for draft measurements Stable, accurate, and reliable for years of maintenance-free performance Based on standard Model 3051 design, reducing spare parts requirements APPLICATIONS Furnace and boiler draft HVAC: duct flow and clogging filter detection Room and chamber pressurization Clean room pressurization control systems Flow measurements with low differential pressures COMPLETE POINT SOLUTIONS Engineered solutions including primary flow elements Reduced engineering, procurement, and installation costs

Upload: others

Post on 05-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Product Data Sheet 00813-0600-4001

Pressure-111

Mo

del

3051

CD

0

Model 3051CD0 Draft Range

Digital Pressure Transmitterfor Draft Range ApplicationsTRUE DRAFT RANGE OFFERING

• Pressure range –3.0 to 3.0 inH2O (–750to 750 Pa) with spans as small as0.1 inH2O (25 Pa)

• Accuracy: ± 0.10% of range

• Redesigned capacitance sensoroptimized for draft measurements

• Stable, accurate, and reliable for years ofmaintenance-free performance

• Based on standard Model 3051 design,reducing spare parts requirements

APPLICATIONS

• Furnace and boiler draft

• HVAC: duct flow and cloggingfilter detection

• Room and chamber pressurization

• Clean room pressurizationcontrol systems

• Flow measurements with lowdifferential pressures

COMPLETE POINT SOLUTIONS™

• Engineered solutions including primaryflow elements

• Reduced engineering, procurement, andinstallation costs

Page 2: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Pressure-112

Model 3051CD0 Draft Range

Mo

del3051C

D0

INTRODUCING THE MODEL 3051CD0The Rosemount Model 3051CD0 Draft Rangepressure transmitter is a precision instrument ofsuperior quality and performance. The Model3051CD0 measures low to extremely low pressuredifferentials, with positive and negative pressurecapabilities. The Model 3051CD0 transmitter isideal for all types of combustion process air flowmeasurements, particularly designed for accuratemonitoring of:• Furnace and boiler pressure• Combustion air flows• Total, primary, and secondary air flows• Draft lossAdditionally, the Model 3051CD0 is ideal for HVACsystems, Clean Room applications, and other flowapplications that require small differentialpressure measurements.

FEATURESThe Model 3051CD0 Transmitter is based on thedesign of the Model 3051 transmitter, sharing thesame electronics board, electronics housing, LCDmeter, and terminal block. The Model 3051CD0 hasa redesigned capacitance sensor that is optimized forlow differential pressure measurements. Thestandardized parts significantly reduce yourspares inventory.Installation, calibration, and commissioning aremade easy by the compact modular design, withseparate sealed compartments for electronics andwiring terminals, and external span and zeroadjustments. The housing is explosion proof andweatherproof, and the optional local display LCDmeter simplifies inspection, maintenance, andtroubleshooting.

APPLICATIONSThe traditional uses for draft measurements areassociated with boiler pressures, furnace pressures,and flow measurements. With increasedenvironmental regulations, high performance draftrange applications are also becomingincreasingly prevalent.

Furnace and Boiler DraftThe Model 3051CD0 is ideal for furnace and boilerdraft range needs. The Model 3051CD0 measurescombustion air flow, exhaust gas flow, andcombustion chamber pressures, accurately andreliably.For more detailed information on furnace and boilerapplications, see pages 113 and 114.

HVAC SystemsHeating ventilation and air conditioning (HVAC)systems have several draft applications including airflow measurement, building and zonepressurization, and filter and heat exchangerclogging detection. The Model 3051CD0 can improveefficiency and help predict maintenance of all ofthese processes by monitoring pressure loss to asystem and pressure changes across sections.

Clean RoomsClean rooms have extensive draft range HVACrequirements. The Model 3051CD0 measures cleanroom pressures accurately and efficiently, helping toeliminate problems of both contamination and out ofbalance pressurization.

FlowA small differential pressure generated from aprimary element can result in a lower permanentpressure loss. With a static pressure limit of 750 psi(5171 kPa), the Model 3051CD0 is well-suited formeasuring flows in pipes where only a smalldifferential pressure is generated acrossa primary element.

The Model 3051CD0 for Draft Range Applications

Page 3: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure-113

Mo

del

3051

CD

0

3051

-305

1_11

A

Furnace

Air

Flo

w

Windbox

Fuel Flow

FurnacePressure

To Stack

BoilerBank

Flue GasAnalysis

andCleaning

Equipment

WindboxPressure

PT

PT

FeedwaterPressure

PT

Air

Flo

w

PT

FT

FTAir Flow

FTFuelFlow

FeedwaterFlow

DPT

DPT

PT = Pressure Transmitter

DPT = Differential Pressure Transmitter

= Flow TransmitterFT

PT

FIGURE 1. Model 3051CD0 Boiler Applications.

Model 3051CD0 Boiler Applications

FlowIn many boiler applications, air flow can be the mostdifficult measurement. Primary elements such asannubars, air foils, piezometer rings, or restrictionsin the duct work are used to create a usabledifferential. However, in many cases, pressure dropsof approximately only 1 inH2O (249 Pa) aredeveloped. A good air flow measurement isnecessary for precise control of fuel-to-air ratios, acritical parameter in maintaining boiler combustionefficiency and attaining fuel savings. The Model3051CD0 can measure this air flow to provide themost efficient combustion possible.

Other FlowsMany waste gases or other combustion-related airflows are supplied at very low static pressures.Primary measurement devices used in theseapplications will not develop large differentialpressures. Low range transmitters must be used forthese installations to assure compliance withenvironmental regulations.

FT

PressureMost boilers are designed to maintain a slightnegative pressure (approximately –0.25 inH2O[62 Pa]) in the furnace. This is accomplished bymodulating induced draft dampers or boiler outletdampers. A pressure tap is located in the chamberwhere combustion takes place. If the pressure is toolow, it can cause air infiltration and reduceefficiency. If the pressure is too high, it can causeharmful gases to escape into the boiler room.Efficient operation, safety, and protection ofequipment depends upon this measurement, and theModel 3051CD0 offers the solution.

Differential Pressure–Drops AcrossSections

Pressure drops across air heaters, scrubbers,economizers, and other parts of the boiler must beknown to determine if these components are dirty orbecoming plugged with soot or ash. The efficiency ofthe boiler depends on the proper operation of thesedevices. Electrostatic precipitators often have theirown fans, and pressure within these must be closelycontrolled. The Model 3051CD0 can accuratelymeasure these pressure drops to improve the overallefficiency of a system.

DPT

Page 4: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Model 3051CD0 Draft Range

Pressure-114

Mo

del3051C

D0

Combustion air fans force air into the furnace forcombustion of the fuel. Waste gases exiting thefurnace are regulated by a damper in the stack. Thestack damper must be properly positioned to create avery slight positive pressure in the furnace forefficient operation.

• If the furnace pressure is too high, it will causethe hot air needed for heating to escape throughthe furnace casing, reducing efficiency.

• If the furnace pressure is too low, it will causeexcessive air leaks through the furnace casingfrom the atmosphere into the furnace.

3051

-305

1_1

2A

PT

Preheat Zone Heat Zone

Drive

Product Flow

PC

FurnacePressure

PT = Pressure Transmitter

Exhaust

FIGURE 2. Model 3051CD0 Furnace Applications.

PC = Pressure Controller

Energy conservation has become an important issue.Good furnace pressure control is an effective meansof reducing fuel consumption. Accurate, reliableprocess measurement is a necessity, and the Model3051CD0 provides it.Ideally, a slight positive pressure of 0.05 inH2Oshould be maintained to minimize losses. A pressuretransmitter to control these losses should be selectedon the basis of resolution, repeatability, stability, andaccuracy. Whether it be a reheat furnace, soakingpit, kiln, or smelter, the Rosemount Model 3051CD0is an ideal measurement choice.

Model 3051CD0 Furnace Applications

Page 5: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure- Pressure-115

Mo

del

3051

CD

0

MODEL 3051CD0PRESSURE TRANSMITTER• Superior performance: 0.10% accuracy,

30:1 rangeability• Differential pressure: – 3.0 to 3.0 inH2O

(–750 to 750 Pa). Minimum span of0.1 inH2O (25 Pa)

• Stainless steel process isolators and flange bolts• Compact, rugged, and lightweight design for easy

installationTraditional Flange• Stainless steel construction

DIAMOND II+ ANNUBAR®

• Assembled, pressure-tested, calibrated, andready-to-install primary element and pressuretransmitter combination

• Innovative, patented Diamond II+ Annubardesign requires a single pipe penetration,enabling easy installation

• Low operating costs due to low permanentpressure drop

• Integral isolation and equalization valvingremoves the need for a manifold

• No moving parts to maintain

LOCAL SPAN AND ZERO ADJUSTMENTSLocal span and zero adjustments are standardunless otherwise specified

• Non-interactive external zero and spanadjustments simplify reranging

• Magnetic switches replace standardpotentiometer adjustments to optimizeperformance

• Local span and zero adjustments can be disabledusing the transmitter software

J1 Local Zero Adjustment OnlyJ3 No Local Zero or Span Adjustment

3051

-305

1B07

C3

051-

3031

E07

A,1

295-

0536

A

Annubar® Cross Section

3051

-303

1D02

A

Zero and SpanAdjustment Buttons

Product Offering

Page 6: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Pressure-116

Model 3051CD0 Draft Range

Mo

del3051C

D0

LOCAL DISPLAY LCD METERM5 Two-line, Five Digit Display• Direct reading of digital data for

higher accuracy• Displays digital output in pressure engineering

units, percent of analog range values, or custom-defined flow, level, or pressure units.

• Displays diagnostic messages for localtroubleshooting

• 90-degree rotation capability forupright viewing regardless of transmittermounting orientation

M6 Digital Meter with 316 Stainless Steel CoverFor use with stainless steel housing option(housing codes J, K, and L)

TRANSIENT PROTECTION• Integral transient protection terminal block• Meets IEEE Standard 587, Category B

1kV crest (10 3 1000 microseconds)3kV crest (8 3 20 microseconds)6kV crest (1.2 3 50 microseconds)

• Meets IEEE Standard 472, Surge WithstandCapability

SWC 2.5kV crest, 1 MHz wave form• Applicable standards: IEC 801-4, 801-5.T1 Integral Transient Protection Terminal Block

3051

-303

1A05

A

10-Pin InterconnectionHeader

LCD MeterMeterCover

Alarm and SecurityJumpers (top and bottom)

3051

-30

31F

02B

Page 7: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure- Pressure-117

Mo

del

3051

CD

0

TRADITIONAL FLANGEBRACKET OPTIONS

B1 Bracket for 2-in. Pipe Mounting• Bracket for mounting transmitter on

2-in. pipe• Carbon steel construction with carbon

steel bolts• Coated with polyurethane paint

B2 Bracket for Panel Mounting• Bracket for mounting transmitter on

wall or panel• Carbon steel construction with carbon

steel bolts• Coated with polyurethane paint

B3 Flat Bracket for 2-in. Pipe Mounting• For vertical mounting of transmitter

on 2-in. pipe• Carbon steel construction with carbon

steel bolts• Coated with polyurethane paint

B7 –B1 Bracket with SST BoltsSame bracket as the B1 option withSeries 300 stainless steel bolts

BA SST B3 Bracket with SST BoltsB1 bracket in SST with Series 300 SST bolts

B8 –B2 Bracket with SST BoltsSame bracket as the B2 option withSeries 300 stainless steel bolts

B9 –B3 Bracket with SST BoltsSame bracket as the B3 option withSeries 300 stainless steel bolts

BC Stainless Steel B3 Bracket with SST BoltsB3 bracket in stainless steel with Series 300stainless steel bolts

3051

-303

1C19

A,

3031

I19A

B1, B7, BA

3051

-30

31E

19B

,303

1J1

9B

B2, B8

3051

-30

51H

19A

,303

1J1

9A

B3, B9, BC

Page 8: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Pressure-118

Model 3051CD0 Draft Range

Mo

del3051C

D0

PERFORMANCE SPECIFICATIONS(Note: Zero-based spans, reference conditions, silicone oil fill,transmitter mounted in vertical orientation, and digital trim valuesequal to the span set points.)

Accuracy±0.10% of span.Note

For rangedowns greater than 1:2 and up to 1:30,accuracy = ±0.05% URL.Ambient Temperature Effect per 50 °F (28 °C)±(0.25% URL + 0.05% span).Static Pressure Effect

Zero Error (can be calibrated out at line pressure)±0.125% of URL/100 psi (689 kPa).Span Error±0.15% of span/100 psi (689 kPa).

Stability0.20% URL for one year.Mounting Position EffectZero shifts up to 2.5 inH2O (0.62 kPa), which can becalibrated out. No span effect.

FUNCTIONAL SPECIFICATIONSRange and Sensor LimitsUpper (URL): 3.0 inH2O (750 Pa).Lower (LRL): –3.0 inH2O (–750 Pa).Minimum Span: 0.1 inH2O (25 Pa).Time ResponseDead Time (Td): 45 milliseconds (nominal).Time Constant (Tc): 0.7 seconds (nominal).Update Rate: 20 times per second (minimum).Vibration Effect± 0.2% URL per g when tested from 15 to 2000 Hz inany axis relative to pipe-mounted processconnections.Power Supply EffectLess than 0.005% of calibrated span per volt.RFI Effect± 0.1% of span from 20 to 1000 MHz, and for fieldstrength up to 30 V/m.ServiceLiquid, gas, and vapor applications.Note: Calibrations at 68 °F (20 °C) per ANSI Z210.1.

Transient ProtectionMeets IEEE Standard 587, Category B.

1kV crest (10 3 1000 microseconds).3 kV crest (8 3 20 microseconds).6 kV crest (1.2 3 50 microseconds).Meets IEEE Standard 472, Surge WithstandCapability SEC 2.5 kV crest, 1 MHz wave form.General Specifications:Response Time: < 1 nanosecondPeak Surge Current: 5000 amps to housingPeak Transient Voltage: 100 V dcLoop Impedance: < 25 ohmsApplicable Standards: IEC 801-4, IEC 801-5.

4–20 mA OutputTwo-wire 4–20 mA, user-selectable for linear orsquare root output. Digital process variablesuperimposed on 4–20 mA signal, available to anyhost that conforms to the HART protocol.Power SupplyExternal power supply required. Standard transmitter(4–20 mA) operates on 10.5–55 V dc with no load.Load LimitationsMaximum loop resistance is determined by thevoltage level of the external power supply, asdescribed by:

Max. Loop Resistance = 43.5(Power Supply Voltage – 10.5)

(1) For CSA approval, power supply must not exceed 42.4 V.

Overpressure Limits0.5 psia to 750 psi (3.4 to 5171 kPa).Static Pressure LimitOperates within specifications between static linepressures of 0.5 psia and 750 psig.Burst Pressure LimitsBurst pressure is 10,000 psig (69 MPa).

Communication requires a minimum loop resistance of 250 ohms.

Lo

ad(O

hm

s)

3051

-01

03A

Voltage (V dc)

OperatingRegion

Specifications

Page 9: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure- Pressure-119

Mo

del

3051

CD

0

Failure Mode AlarmIf self-diagnostics detect a gross transmitterfailure, the analog signal will be driven eitherbelow 3.75 mA or above 21.75 mA to alert the user.High or low alarm signal is user-selectable byinternal jumper.

Temperature LimitsAmbientSilicone: –40 to 185 °F (–40 to 85 °C).Inert: 32 to 185 °F (0 to 85 °C).Ambient with Integral Meter:–4 to 175 °F (–20 to 80 °C).Process–40 to 212 °F (–40 to 100° C).Storage–50 to 212 °F (–46 to 100 °C).Storage with Integral Meter:–40 to 185 °F (–40 to 85 °C).

Humidity Limits0–100% relative humidity.Turn-on TimePerformance within specifications less than 2.0seconds after power is applied to transmitter.Volumetric DisplacementLess than 0.005 in3 (0.08 cm3).DampingAnalog output response to a step input change isuser-selectable from 0 to 36 seconds for one timeconstant. This software damping is in addition tosensor module response time.IndicationOptional 5-digit LCD meter.Hazardous Locations CertificationsSee Certifications section.

PHYSICAL SPECIFICATIONSElectrical Connections

1/2–14 NPT, PG 13.5, G1/2, and M20 x 1.5 (CM20)conduit. HART interface connections fixed toterminal block.

Process Connections1/4–18 NPT on 21/8-in. centers;1/2–14 NPT on 2-, 21/8-, or 21/4-in. centers.

Process-Wetted PartsProcess Isolated Diaphragms316L SST.Drain/Vent Valves316 SST.Process Flanges and AdaptersCF-8M (Cast version of 316 SST, material perASTM-A743).Wetted O-ringsGlass-filled TFE.

Non-Wetted PartsElectronics HousingLow-copper aluminum or CF-8M (Cast version of316 SST, material per ASTM-A743). NEMA 4X,IP 65, IP 66.Coplanar Sensor Module HousingCF-3M (Cast version of 316L SST, materialper ASTM-A743).BoltsAustenitic 316 SST.Sensor Module Fill FluidSilicone or inert halocarbon.PaintPolyurethane.Cover O-ringsBuna-N.

Shipping WeightsWithout options: 8.1 lb. (3.7 kg). The following tablelists shipping weights of Model 3051CD0 options:

Installation ConsiderationsTemperature performance will be optimized if thetransmitter is mounted with the isolators parallel tothe ground, reducing oil head effect.

Care should be taken to assure the transmitter ismounted securely. Tilting of the transmitter willappear as a zero shift in the output of thetransmitter.

TABLE 1. Transmitter Option Weights.

Code OptionAdd

lb (kg)

J, K, LM5M6B1, B2, B3B7, B8, B9BA, BC

Stainless Steel HousingLCD Meter for Aluminum HousingLCD Meter for SST HousingMounting Bracket for Traditional FlangeMounting Bracket for Traditional FlangeSST Bracket for Traditional Flange

3.1 (1.4)0.5 (0.2)1.25 (0.6)2.3 (1.0)2.3 (1.0)2.3 (1.0)

Page 10: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Pressure-120

Model 3051CD0 Draft Range

Mo

del3051C

D0

Stainless steel certification tag provided whenoptional approval is specified.

Factory Mutual (FM) ApprovalsE5 Explosion Proof for Class I, Division 1, Groups

B, C, and D. Dust-Ignition Proof for Class II,Division 1, Groups E, F, and G. Suitable forClass III, Division 1, indoor and outdoor(NEMA 4X) hazardous locations. Factory Sealed.

I5 Intrinsically Safe for use in Class I, Division 1,Groups A, B, C, and D; Class II, Division 1,Groups E, F, and G; Class III, Division 1 whenconnected in accordance with Rosemountdrawings 03031-1019 and 00275-0081 (whenused with HART Communicator Model 275),or 00268-0031 (when used with RosemountModel 268 Communicator). Temperature CodeT4. Non-incendive for Class I, Division 2,Groups A, B, C, and D. NEMA 4X. FactorySealed.

K5 Combination of E5 and I5.

BASEEFA/CENELEC Intrinsic Safety CertificationI1 EEx ia IIC T5 (Tamb = 40 °C).

EEx ia IIC T4 (Tamb = 70 °C).CENELEC Approved Entity ParametersUMax:in = 30 VIMax:in = 200 mAWMax:in = 0.9 WCeq = 0.012 mF

BASEEFA Non-incendive Type N CertificationN1 Ex N IIC T5 (Tamb = 70 °C).

CESI/CENELEC Flameproof CertificationE8 EEx d IIC T6 (Tamb = 40 °C).

EEx d IIC T5 (Tamb = 70 °C).

Japanese Industrial Standard (JIS)Flameproof Certification

E4 (3051C) Ex d IIB T4 + sG4 (Tamb = 60 °C)(3051T) Ex d IIB T5 (Tamb = 60 °C)

Canadian Standards Association (CSA) ApprovalsC6 Explosion Proof for Class I, Division 1, Groups

B, C, and D. Dust-Ignition Proof for Class II,Division 1, Groups E, F, and G. Suitable forClass III, indoor and outdoor hazardous locations,CSA enclosure 4X; factory sealed. Suitable forClass I, Division 2, Groups A, B, C, and D.Intrinsically Safe for Class I, Division 1,Groups A, B, C, and D when connected inaccordance with Rosemount drawings 03031-1024 and 00275-0081 (when used with theHART Communicator Model 275).Temperature Code T3C.

K6 Combined C6, I1, and E8.

Standards Association of Australia (SAA)Intrinsic Safety CertificationI7 Ex ia IIC T4 (Tamb = 70 °C).

Ex ia IIC T5 (Tamb = 40 °C).Special Conditions for Safe UseObserve barriers/entity parameters duringinstallation.SAA Approved Entity ParametersUMax= 30 VIMax= 200 mAIMax= 160 mA (Option Code T1)PMax = 0.9 WCl = 0.01 mF (Output Code A)Cl = 0.042 mF (Output Code M)Ll = 10 mHLl = 1.05 mH (Output Code A with T1)Ll = 0.75 mH (Output Code M with T1)Explosion Proof (Flameproof) Certificationÿþ Ex d IIC T6(Tamb = 40 °C)

Ex d IIC T5 (Tamb = 80 °C)DIP T6 (Tamb = 40 °C)DIP T5 (Tamb = 80 °C)

Type N CertificationN7 Ex n IIC T4 (Tamb = 70 °C)

Ex n IIC T5 (Tamb = 40 °C)

FM ApprovedEntity Parametersfor Model 3051C (1)

(1) When connected in accordance with Rosemount drawings3031-1019 and 00275-0081 (for use with the HARTCommunicator Model 275), or 00268-0031 (for use with theRosemount Model 268 Communicator).

FM Approved forClass I, II, III,Division 1 and 2,Groups

VMax = 40 V dcIMax = 165 mAIMax = 225 mAIMax = 160 mA (Option Code T1)PMax = 1 WCl = 0.01 mF (Output Code A)Cl = 0.042 mF (Output Code M)Ll = 10 mHLl = 1.05 mH (Output Code A with T1)Ll = 0.75 mH (Output Code M with T1)

A–GA–GC–GA–GA–GA–GA–GA–GA–GA–G

CSA ApprovedBarriers for Model 3051C (1)

(1) When connected in accordance with Rosemount drawings00275-0082 and 3031-1024.

CSA Approved forClass I, Division 1and 2, Groups

Out

put

Cod

eA

≤ 30 V, ≥ 330 V ≤ 28 V, ≥ 300 V≤ 25 V, ≥ 200 V ≤ 22 V, ≥ 180 V A–D

≤ 30 V, ≥ 150 V C–D

Certifications

Page 11: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure- Pressure-121

Mo

del

3051

CD

0

121

Certification Label

Span and ZeroAdjustments

(Standard)

Electronics Housing

Terminal Block

Cover O-ring

Cover

Electronics Board

Module O-ring

Sensor ModuleHousing Rotation Set Screw

(180° Maximum Rotation withoutFurther Disassembly)

FIGURE 3. Model 3051CD0 Pressure Transmitter Exploded View.

3051

-303

1B08

B

Drawings

Traditional Flangew/Flange Adapters

Page 12: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Pressure-122

Model 3051CD0 Draft Range

Mo

del3051C

D0

2.7(67)

7.1(181)

OPTION B1/B7/BA:TRADITIONAL

FLANGE 2-IN. PIPEMOUNTING BRACKET

OPTION B2/B8:TRADITIONAL FLANGE PANEL

MOUNTING BRACKET

5/16 x 7/8 Bolts for Panel Mounting(Not Supplied)

PANEL MOUNTING BRACKET

FIGURE 4. Traditional Flange Mounting Configurations with Optional Brackets for 2-inch Pipe or Panel Mounting.

NOTEDimensions are in inches (millimeters). PIPE MOUNTING BRACKET

305

1-30

31J1

9D,

3031

I19C

,30

31E

19C

,30

31C

19A

1.1 (28)

1.4(33)

ImpulsePiping

2.7(67)

3.8(95)

10.1(257)

OPTION B1/B7/BA:TRADITIONAL

FLANGE 2-IN. PIPEMOUNTING BRACKET

OPTION B2/B8:TRADITIONAL FLANGE PANEL

MOUNTING BRACKET

2.81(71)

NOTEDimensions are in inches (millimeters). PIPE MOUNTING BRACKET

4.2(106)

1.1 (28)

1.4(33)

4.6(116)

ImpulsePiping

2.7(67)

3.8(95)

9.6(243)

NOTEDimensions are in inches (millimeters).

FIGURE 5. Traditional Flange Dimensional Drawing.

TransmitterCircuitry

Meter Cover(Optional)

Nameplate

1/4–18 NPT on Traditional Flange forPressure Connection without the Useof Flange Adapters

TerminalConnections

HousingRotation

Set Screw

1/2–14 NPT ConduitConnection (Two Places,Other Sizes Available)

Certification Label

1/2–14 NPT on Optional FlangeAdapters.Adaptors Can Be Rotated to GiveConnection Centers of 2.00 (51), 2.125(54), or 2.25 (57).

1.7 (43)

2.2(56)

1.1(28)

3.4(87)

1.1(28)

Drain/Vent Valve

7.9(202)

0.75 (20)Clearancefor CoverRemoval

5.0(127)

4.3(110)

4.1(105)

0.75 (20)Clearancefor CoverRemoval

3051

-303

1D3

0A,3

031E

30A

Page 13: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure- Pressure-123

Mo

del

3051

CD

0

ORDERING INFORMATIONTABLE 2. Model 3051CD0 Pressure Transmitter Ordering Information.

Model Transmitter Type (Select One)

3051CD Differential Pressure Transmitter

Code Pressure Range/Min. Span

0 –3 to 3.0 inH2O/0.1 inH2O (–750 to 750 Pa/25 Pa)

Code Output

A 4–20 mA with Digital Signal Based on HART Protocol

Code Process Flange Type

0 Alternate Flange–Traditional Flange (Option H2) required

Code Isolating Diaphragm

2 316L SST

Code O-ring

A Glass-filled TFE

Code Fill Fluid

12

SiliconeInert fill (Halocarbon)

Code Housing Material Conduit Entry Size

ABCDJKL

Polyurethane-covered Aluminum ½–14 NPTPolyurethane-covered Aluminum M20 x 1.5 (CM20)Polyurethane-covered Aluminum PG 13.5Polyurethane-covered Aluminum G½SST ½–14 NPTSST M20 x 1.5 (CM20)SST PG 13.5

Code Options

H2(1)

B1B2B3B7B8B9BABC

S4

E5I5K5C6K6I1N1E8E4E7I7N7

L4(1)

M5M6

ALTERNATE FLANGETraditional Flange, 316 SST, SST Drain/Vent, SST Flange AdapterMOUNTING BRACKETSTraditional Flange Bracket for 2-in. Pipe Mounting, CS BoltsTraditional Flange Bracket for Panel Mounting, CS BoltsTraditional Flange Flat Bracket for 2-in. Pipe Mounting, CS BoltsB1 Bracket with Series 300 SST BoltsB2 Bracket with Series 300 SST BoltsB3 Bracket with Series 300 SST BoltsSST B1 Bracket with Series 300 SST BoltsSST B3 Bracket with Series 300 SST BoltsINTEGRAL MOUNT PRIMARY ELEMENTSFactory Assembly to Rosemount Primary Element (Diamond II+ Annubar)HAZARDOUS LOCATIONS CERTIFICATIONSFM Explosion-Proof ApprovalFM Non-incendive and Intrinsic Safety ApprovalFM Explosion-Proof and Intrinsic Safety ApprovalCSA Explosion-Proof and Intrinsic Safety Approval (Requires 42.4 V dc max. power supply)Combination of CSA and CENELEC Explosion-Proof and Intrinsic Safety ApprovalBASEEFA/CENELEC Intrinsic Safety CertificationBASEEFA Type N CertificationCESI/CENELEC Flameproof CertificationJIS Flameproof CertificationSAA Flameproof CertificationSAA Intrinsic Safety CertificationSAA Type N CertificationBOLTINGAustenitic 316 SST BoltsMETERSLCD Meter for Aluminum Housing (Housing Codes A, B, C, and D only)LCD Meter for SST Housing (Housing Codes J, K, and L only)

(1) Required option for Model 3051CD0 transmitter.

Page 14: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Pressure-124

Model 3051CD0 Draft Range

Mo

del3051C

D0

TABLE 2. (continued).

Code Options

Q4Q8J1(1)

J3(1)

T1(2)

C1C4(3)

P2P3D3D8V5

OTHER OPTIONSCalibration Data SheetMaterial Traceability Certification per EN 10204 3.1BLocal Zero Adjustment OnlyNo Local Zero or Span AdjustmentTransient Protection Terminal BlockCustom Software Configuration (Completed CDS 00806-0100-4001 required with order)Analog Output Levels Compliant with NAMUR Recommendation NE43, 18-January-1994Cleaning for Special ServiceCleaning for <1 PPM Chlorine/Fluorine1/4–18 NPT Process Connections (No flange adapters)Ceramic Ball Drain/VentsExternal Ground Screw Assembly

Typical Model Number: 3051CD 0 A 0 2 A 1 A H2 L4 B4

(1) Local zero and span adjustments are standard unless Option Codes J1 or J3 is specified.

(2) Not available with hazardous locations certification Option Code I1 or K6.

(3) NAMUR-Compliant operation is pre-set at the factory and cannot be changed to standard operation in the field.

Rosemount and the Rosemount logotype are registered trademarks ofRosemount Inc.SMART FAMILY is a registered trademark of Rosemount Inc.Coplanar and Multivariable are trademarks of Rosemount Inc.HART is a registered trademark of the HART Communications Foundation.Hastelloy C and Hastelloy C-276 are registered trademarks of Cabot Corp.Monel is a registered trademark of International Nickel Co.Syltherm 800, Dow Corning, and D.C. are registered trademarks of DowCorning Co.Neobee M-20 is a registered trademark of Stepan Chemical Co.The 3-A symbol is a registered trademark of the 3-A Sanitary StandardsSymbol Council.Fluorinert is a registered trademark of 3M Company.

Cover photo: 3051Hi-3051_02B

Page 15: Digital Pressure Transmitter - Automaatika · 2015. 3. 12. · Product Data Sheet 00813-0600-4001 Pressure-111 Model 3051CD0 Model 3051CD0 Draft Range Digital Pressure Transmitter

Rosemount Inc.

Pressure- Pressure-125

Mo

del

3051

CD

0

ORDERING INFORMATION (CONTINUED)Standard ConfigurationUnless otherwise specified, transmitter is shippedas follows:Engineering units: inH2O4 mA (1 V dc): 0 (engineering units above)20 mA (5 V dc): Upper range limitOutput: LinearFlange type: TraditionalFlange material: Stainless Steel (316 SST)O-ring material: Glass-filled TFEDrain/vent: Stainless Steel (316 SST)Integral meter: Installed or noneAlarm: UpscaleSoftware tag: (Blank)

Customer may specify the above itemsat no charge.Custom Configuration (Option Code C1)If Option Code C1 is ordered, the customer mayspecify the following data in addition to thestandard configuration parameters. Refer toConfiguration Data Sheet CDS 00806-0100-4001. Descriptor:16 alphanumeric characters.Message:32 alphanumeric characters.Date:Day, month, year.Damping: Seconds.Custom Meter OutputBurst Mode of HARTMultidrop Communication Rosemount SmartFamily® Instruments

ROSEMOUNT SMART FAMILY®

INSTRUMENTSRosemount SMART FAMILY instrumentsmay be installed in pressure, temperature, level, andflow applications.All SMART FAMILY instruments are designed tocommunicate using Highway Addressable RemoteTransducer (HART) protocol with the hand-heldHART Communicator and Fisher-RosemountControl Systems.

TaggingThree customer tagging options are available:

1. Standard SST tag is wired to the transmitter.Tag character height is 0.125 in. (3.18 mm),85 characters maximum.

2. Tag may be permanently stamped ontransmitter nameplate upon request,65 characters maximum.

3. Tag may be stored in transmitter memory.Software tag (8 characters maximum) is leftblank unless specified.

Output InformationAnalog output range points must be the same unitof measure. Available units of measure:

inH2O mbar mmHg kPainHg g/cm2 psi torrftH2O kg/cm2 bar atmmmH2O Pa inH2O@4°CmmH2O@4°C

Related Product Data SheetsModel 3051 Smart Pressure Transmitter Familysee page Pressure-5Diamond II+ Annubar® see page Flow-375