design of self sustained dc microgrid through energy audit ... report/16ee10.pdf · design of self...
TRANSCRIPT
Design of Self Sustained DC MicroGrid through
Energy Audit and illumination Level Study in
Substation
Intermediate Project Report – June 2016
Energy Efficiency Research Group
An International Energy Research Foundation
Since 2015
GREEN9
Design of Self Sustained DC MicroGrid through
Energy Audit and illumination Level Study in
Substation
Intermediate Project Report – June 2016
Authors
Ashok Kumar, Chandru Mahto
Member, Energy Efficiency Research Group
Member, MGR Vision 10MW, Dr. M.G.R Educational and Research Institute
Er. R. Regunarayanan
Astt. Executive Engineer TNEB and Member , GREEN9
Dr. L. Ramesh
Chairman (BOT), Energy Efficiency Research Group
Director, MGR Vision 10MW and Professor, Dr.M.G.R Educ., & Research Inst.,
GREEN9 publication 16Ee10- June 2016
ACKNOWLEDGEMENTS
An art of manipulation of electricity power paves the way for modernizing the
world with balanced development in every aspect but the unaccounted and heedless
use of electricity, particularly in the utilization side curtailing the growth rate and
dragging the power world towards the state of energy deficit. This electrical energy
deficit should be overcome necessarily to deliver the determined growth to our mankind.
An electrical energy audit pretence us, by the way of offering technical solution to bridge
the energy deficit gap. India’s substantial and sustained economic growth is placing
enormous demand on its energy resources. The demand and supply imbalance in
energy sources is pervasive requiring serious efforts by Government of India to
augment energy supplies as India faces possible severe energy supply constraints.
Achieving energy security in this strategic sense is of fundamental importance not only
to India’s economic growth but also for the human development objectives that aim at
alleviation of poverty, unemployment and meeting the Millennium Development Goals
(MDGs).The power once generated is distributed via substation where considerable
quantum of energy utilized for lighting purpose in the society. In the proposed project a
detailed analysis was conducted in the substation yards and it’s control room .The DC
source for the protection system is fed from the battery bank interfaced with the charger
rated in ampere hours. This is the normal arrangement universally. The demerit in the
system is in the event of failure of either battery or charger, there will be posture to the
regularity of control supply to the numerical relays etc. The DC distribution to the
numerous circuits in the substation is taken from the DC bus in the distribution panels.
Normally the current taken by every DC circuit will be in mA only. When the protection
system respond to the faults by the way of activation of relays then the rate of current
flow in amps .The substation is widespread in a very large area and there is a huge
scope for the installation of alternative energy sources. Hence the micro grid concept
implemented with the addition of Photo Voltaic panels, Wind turbine, etc with the scope
of no chance to the failure of DC supply to the protection system.
TABLE OF CONTENTS
Ch. No. TITLE PAGE NO.
ABSTRACT
List of Abbreviations
List of Figures
List of Tables
01 INTRODUCTION 1
1.1 Global Perspective on Electricity Generation 1
1.2 National Perspective on Electricity Generation 1
1.3 Tamil Nadu Perspective on Electricity Generation 2
02 LITERATURE REVIEW 3
2.1 Review of Literature
3
2.2 Proposed Methodology to Conduct Audit 7
03 DATA ACQUISTION 9
3.1 Work Execution In Stage 1
9
3.2 Work Execution In Stage 2
10
3.3 University Office Audit Procedure
12
3.4 Substation Audit Procedure
13
3.5 Energy Audit At University office
13
3.6 Energy Audit at Substation’s Switchyard
20
3.7 Control room Data Observation
22
04 RECOMMENDATION 40
4.1 Recommendations on University Office
41
4.2 Recommendations on Substation
46
05 DESIGN OF DC MICRO GRID 62
5.1 Design Calculation of micro grid with PV array and Wind mill
62
5.2 Description of Micro grid
65
5.3 Case study of Proposed Micro grid
67
5.4 Analysis of Micro Grid system
68
5.5 Comparison of Existing DC system with Proposed Micro Grid
System
69
06 CONCLUSION
74
REFERENCES
75
PUBLICATION DETAILS
77
LIST OF ABBREVIATIONS
DG - Distributed Generation
LED - Light Emitting Diode
W - Watts
V - Voltage
A - Ampere
ROI - Return on Investment
ECMs - Energy Conservation Measures
ECOs - Energy Conservation Opportunities
ETAP - Electrical Transient Analysis Program
PDB - Power Distribution Board
LDB - Light Distribution Board
UDB - Ups Distribution Board
LF - Load Flow
LIST OF FIGURES
Page No.
Figure No.2.1 Final Cost Saving of lightning 04
Figure No.2.2 Final Energy Consumption saving 04
Figure No.2.3 Energy Consumption area wise 05
Figure No.2.4 Methodology to Conduct Audit 08
Figure No.3.1 Description of Project 09
Figure No.3.2 Steps Involved in Execution Stage 10
Figure No.3.3 Layout of the Existing area 14
Figure No.3.4 Energy Wastage Percentage Assessment 15
Figure No.3.5 110 KV yard layout 21
Figure No.3.6 230 KV yard layout 21
Figure No.3.7 400 KV yard layout 21
Figure No.3.8 Control room layout 22
Figure No.3.9 110KV Visual Analysis 23
Figure No.3.10 230KV Visual Analysis 23
Figure No.3.11 400KV Visual Analysis 24
Figure No.3.12 Control room Visual Analysis 25
Figure No.3.13 Present live lux level of 110KV Switch yard 25
Figure No.3.14 Present live lux level of 230KV switch yard 26
Figure No.3.15 Present live lux level of 400KV switch yard 26
Figure No.3.16 Analysis of yard lightning 27
Figure No.3.17 Total Existing load Connected(KW) 29
Figure No.3.18 Yard lightning Bus nos. VS current 29
Figure No.3.19 Yard lightning Voltage(%) VS Bus nos 30
Figure No.3.20 Control room SLD 30
Figure No.3.21 Control room Bus no. VS Voltage(%) 31
Figure No.3.22 Control room Bus no. VS Current(%) 33
Figure No.3.23 Analysis of DC SLD 33
Figure No.3.24 Load in Network 1 34
Figure No.3.25 Load in Network 2 36
Figure No.3.26 Load flow report without fault in DC system(Vol. Vs Bus no.) 36
Figure No.3.27 Load flow report without fault in DC system(Vol. Vs Bus no.) 37
Figure No.3.28 Load flow report without fault in DC system(Cur. Vs Bus no.) 37
Figure No.3.29 Load flow report without fault in DC system(Cur. Vs Bus no.) 38
Figure No.3.30 Load flow report with fault in DC system(Vol. Vs Bus no.) 38
Figure No.3.31 Load flow report with fault in DC system(Vol. Vs Bus no.) 39
Figure No.3.32 Load flow report with fault in DC system(Cur. Vs Bus no.) 39
Figure No.3.33 Load flow report with fault in DC system(Cur. Vs Bus no.) 40
Figure No.4.1 Proposed Lighting Design 41
Figure No.4.2 Wastage Audit Saving Analysis 42
Figure No.4.3 Saving with Proposed LED lights 44
Figure No.4.4 Total saving after recommendation 44
Figure No.4.5 Energy Saved with PC and Xerox machine 45
Figure No.4.6 CFL and LED comparison 46
Figure No.4.7 Rearrangement lux level in 110 KV yard 47
Figure No.4.8 Rearrangement lux level in 230 KV yard 47
Figure No.4.9 Rearrangement lux level in 400 KV yard 48
Figure No.4.10 110KV Tier 1 lightning 50
Figure No.4.11 110KV Tier 2 lightning 50
Figure No.4.12 110KV Cost Comparison 51
Figure No.4.13 110KV Energy consumption 52
Figure No.4.14 23KV Tier 1 lightning 52
Figure No.4.15 230KV Tier 2 lightning 53
Figure No.4.16 230KV Cost Comparison 54
Figure No.4.17 230KV Energy consumption 54
Figure No.4.18 400KV Tier 1 lightning 55
Figure No.4.19 400KV Tier 2 lightning 55
Figure No.4.20 400KV Cost Comparison 56
Figure No.4.21 400KV Energy consumption 56
Figure No.4.22 Total Saving of Energy consumption in yard lightning 57
Figure No. 4.23 Analysis of Control room 58
Figure No.4.24 Substation Control room with LED cost analysis 59
Figure No.4.25 Substation Control room Energy Consumption 59
Figure No.4.26 Control room Fan Cost Analysis 66
Figure No.4.27 Control room Fan Energy Consumption 61
Figure No.5.1 Proposed Micro Grid 66
Figure No.5.2 LF report without fault in DC system(Vol. Vs Bus no.) 68
Figure No.5.3 LF report without fault in DC system(Vol. Vs Bus no.) 68
Figure No.5.4 LF report without fault in DC system(Curr. Vs Bus no.) 69
Figure No.5.5 LF report without fault in DC system(Curr. Vs Bus no) 69
Figure No.5.6 Comparison of Existing and proposed(Vol. Vs Bus no.) 70
Figure No.5.7 Comparison of Existing and proposed(Vol. Vs Bus no.) 70
Figure No.5.8 Comparison of Existing and proposed(Cur. Vs Bus no) 70
Figure No.5.9 Comparison of Existing and proposed(Cur. Vs Bus no) 71
Figure No.5.10 EB per year and Cost of PV array 71
Figure No.5.11 Difference in energy consumption of EB and PV 72
Figure No.5.12 EB per year and Cost of Wind Mill 72
Figure No.5.13 Difference in energy consumption of EB and Wind Mill 73
LIST OF TABLES
Page No.
Table No.3.1 Wastage Assessment with Time 15
Table No.3.2 Total Connected load 16
Table No.3.3 Lux value Measurement 17
Table No.3.4 Room Index Calculation 19
Table No.3.5 Total Lamp Connected 28
Table No.3.6 Real time Current rating 28
Table No.3.7 DC Bus Terminals 32
Table No.5.1 Total Connected load to Micro grid 62
Table No.5.2 PV Array Description 63
GREEN 9 Project Outcome Report –16EE10
II-1
I - INTRODUCTION
If you want to save your business energy and money then you are studying
the right report on Energy Conservation by Electrical Energy audit.
Electrical Energy audits can mean different things to different individuals. An
energy audit can be defined as a process to evaluate where a building uses
energy, by identifying the opportunities to reduce consumption as the power
consumers of the modern world start to think about the concept of “Right appliance
to the Right usage”.
1.1 Global perspective on Electricity Generation
Globally now there is an unbridgeable gap between electricity generation capacity
and the ever raising demand. The electrical energy audit is paving the way to
conserve electrical energy by the way of analyzing and adopting of standards
without any major investments. In a world becoming more global, where new
technologies foster bring faster innovations and demand changes in our
behavioural responses, the task of predicting the future becomes harder. Secure,
reliable, affordable, clean and equitable energy supply is fundamental to global
economic growth and human development and presents huge challenges for us.
Future energy supply and demand, future environmental and social contexts are
subject to a knot of uncertainties that are difficult to predict, such as the global
economic and geopolitical situations and new technical innovations[1]. Energy
saving of up to 80% can be achieved by modernizing our lighting system by
installing an intelligent light management system with day light triggered dimming
function and occupancy sensors. sincethere is a direct relationship to the cost of
the audit and how much data will be collected and analysed, and the number of
conservation opportunities identified.
1.2 National Perspective On Electricity Generation
India’s substantial and sustained economic growth is placing enormous demand
on its energy resources. The demand and supply imbalance in energy sources is
pervasive requiring serious efforts by Government of India to augment energy
GREEN 9 Project Outcome Report –16EE10
II-2
supplies as India faces possible severe energy supply constraints. Energy
requirement in our country is increasing at a very rapid rate. Holistic planning for
achieving these objectives requires quality energy statistics that is able to address
the issues related to energy demand, energy poverty and environmental effects of
energy growth.[2]
1.3 Tamil Nadu Energy Perspective
For an industrialized State like Tamil Nadu, the demand for quality power
increases exponentially and moves in tandem with the rate of economic and
population growth. As a result, the demand-supply gap is bound to persist. The
overall power situation in the State during the year 2012-13 was challenging,
eventhough the installed capacity rose from 10365 MW during 2011-12 to 10515
MW during 2012-13. Coupled with the rise in the number of consumers and their
consumption, the demand for power also steadily increased. The peak demand
for power during the year had crossed the mark of 11000 MW. The average
availability of power during the year stood at 8,500 MW. The State faced power
shortage due to the increased demand to rectify this gap the State is taking
several steps to improve uninterrupted quality power to the consumers; despite the
fact that it had faced a number of difficulties – growing number of consumers and
their consumption pattern, delay in commissioning of project, acute corridor
constraint for transmission of power and inadequate tie up with long-term sources
of power generation. Apart from this the State’s initiatives by way of effecting short
term (tenure less than 1 year) purchase of power from the local generators in
Tamil Nadu had paid rich dividends in quick time[3]. This electrical energy deficit
should be overcome necessarily to deliver the determined growth to our mankind.
An electrical energy audit pretence us the way
of offering technical solution to bridge the energy deficit gap. Energy audits are
severely undervalued. While they may be thought of as unnecessary and
ineffective, that could not be further from the truth. [4]. To cope up up this situation
local generation plays a very important role so a brief concept of Micro grid is also
discussed. Microgrid demonstrations and deployments are expanding in power
systems all around the world. Although goals are specific to each site, these
microgrids have demonstrated the ability to provide higher reliability and higher
power quality than utility power systems and improved energy utilization. [5]
GREEN 9 Project Outcome Report –16EE10
II-3
2. LITERATURE REVIEW
2.1 REVIEW OF LITERATURE
This chapter will review the various approaches to energy auditing and outline a
standard approach to organizing and conducting an energy audit. An energy audit
can be simply defined as a process to evaluate where a building or plant uses
energy, and identify opportunities to reduce consumption. There is a direct
relationship to the cost of the audit, how much data will be collected and analysed,
and the number of conservation opportunities identified. Thus, a first distinction is
made between costs of the audit which determines the type of audit to be
performed. The second distinctions made between the types of facility. In
connection to the energy conservation, audit and management, the views of the
selected researchers are presented as below.
In a paper M.Singh [6] out lined
‘electrical energy audit’ outcome of an industrial class load. According to his work
the New generation innovation and tremendous improvement in the field of
lightning has given rise to numbers of energy saving opportunities. According to
him lighting is an area which has major scope of saving energy while conducting
audit. According to his recommendation electronics chokes can be used in place
of electromagnetic chokes .they can be replaced one by one as they became
defective. metal halide lamp can be used in place of halogen and mercury lamps.
The indicating lamps also recommended to be replaced in a phased manner to
LED when existing lamps became defective. The tubes are not required during
day and should be switched off and better arrangement for the use of natural
daylight should be availed. The Right way to achieve energy efficiency is to start
planning at the design stage, use of modern efficient lamp , luminaries and gears
are also important apart from good practice. An industrial unit has been
undertaken as a case study as they are the major consumers of the power. After
case study the author has provided data in the paper which shows the different
ways of saving energy by incorporating certain changes and installation in the
present structure can make the present system more energy efficient.
GREEN 9 Project Outcome Report –16EE10
II-4
The author has also out lined that an energy auditor should see all possibilities
available in and around the proposed area. Energy conservation and exploring
new methods to reduce the demand and to save more energy can fulfill the
growing industrial demand in future. The author has also advocated that the
implementation of suggestion of energy audit can improve efficiency and thus
reduces the wastage.
Mr.S.Pramanik [7] working in the electrical engineering
department, Kalyani Government Engineering College also conducted energy
audit with similar audit recommendations. In his paper he presented very simple
ideas on energy conservation. In order to verify the ideas described in his paper, a
room size (25’x30`) belongs to the faculty members of the Electrical Engineering
has been considered as a case study. He envisaged that, the modern society is
strongly based on the energy for their economics.
Fig 2.2 Final Energy consumption saving
Fig 2.1 Final Cost Saving of lightning
GREEN 9 Project Outcome Report –16EE10
II-5
Production and supply of goods and energy consumption exercising strong effect
environmentally in local and global level which requires equitable balance
between the energy usage for the development of social welfare and the
environmental preservation. The misuse of energy and lavish handling may leads
to negative environmental impacts. The author has also stressed the need of the
energy management which is indeed the need of the hour. The conventional
resources beyond our limits might have been exhausted within some decades.
The paper has explored solutions for the energy reduction. The author has
recommended to use energy efficient appliances and implementation of
microcontroller based system along with power electronics based system which
can reduce the energy consumption. With these microcontroller based system
included in the control system of air conditioner, the percentage saving in energy
could have proven better.
A.K.Ahuja [8] along with his team conducted electrical
energy audit in the IIT Roorkee Campus and the data collected during May-
June‘09. They have conducted audit to find the new opportunities to improve the
energy efficiency of the campus. The audit was not only done to identify the
energy consumption pattern but also to find most energy efficient appliances.
Moreover, some daily practices relating to common appliances have been
provided which help them in reducing the energy consumption. The report gives a
detailed information regarding the energy consumption pattern of the academic
area , central facilities and bhawans , based on actual survey and detailed
analysis during the audit. The work comprises the area wise consumption traced ,
using suitable equipments.
Fig 2.3 Energy consumption area wise
GREEN 9 Project Outcome Report –16EE10
II-6
The ELEKTRA software was used for their audit purpose. The report compiles a
list of possible actions to conserve and efficiently access the available scarce
resources and identifying to save the potentials. The author has looked forward
towards optimization for adoption of set of mission for the authorities , students
and staff should follow the recommendation in the best possible way.The report is
based on certain generalizations and approximations wherever they found it
necessary.
According to the TS 317: Substation Design – Indoor and outdoor
lighting standard Issued in September 2014[] the technical standard is applicable
for all parties involved in the design and construction of substations. The Electricity
Act 1996 and Electricity (General) Regulations 2012, other statutory authority
requirements and relevant AS/NZS standards are the basis of TS 317[9]. For any
situation that is not covered in this standard, the requirements of current standards
including the Building Code of Australia apply. There may be additional
requirements and specifications which are project specific.
The purpose of indoor lighting is to provide sufficient light within the substation
building for normal work activities. However, for specific activities eg working in
panels, additional directional lighting may be required. The following general
design principles shall apply:
Lighting within substation buildings shall provide an average luminance of 100 to
160 lux at floor level
Typically indoor light fittings shall consist of standard single or double fluorescent
tubes light fittings.
Light fittings should be positioned such that the illuminance is spread evenly
across the building.Outdoor lighting of any SA Networks substation must fulfil the
following objectives:
Provide area lighting illumination in substation switchyard access areas
Provide illumination levels of sufficient intensity and clarity for safe movement of
personnel and their vehicles.
According to the Tennessee Valley Authority
Substation Lighting Guidelines[10] Permanent substation lighting advocated with
two-stage design. In his paper he envisaged the substation lighting system in
stages .
GREEN 9 Project Outcome Report –16EE10
II-7
The list could go on almost indefinitely, but the bottom line is that energy
management helps improve environmental quality. “Research on building energy
consumption audit and energy-saving measures for the starting point for any
lighting energy audit would be existing lighting scheme. With this input the audit
provides detailed information on retrofitting or replacing of existing luminaries, with
complete cost of project, annual energy savings and payback calculations. After
the calculations and necessary modifications, it is important to verify the luminance
levels on the task planes before and after changeover to make sure that ample
levels are maintained after the lighting system is modified. Business, industry and
government organizations have all been under tremendous economic and
Environmental pressures in the last few years. Being economically competitive in
the global marketplace and meeting increasing environmental standards to reduce
air and water pollution have been the major driving factors in most of the recent
operational cost and capital cost investment decisions for all organizations. Energy
management has been an important tool to help organizations meet these critical
objectives for their short term survival and long-term success. The measures
identified are electricity related and involve efficient lighting, power factor
improvement and control equipment besides the optimization of the contracts with
the electricity supplier. The identification of energy efficient measures that can be
implemented in a particular building requires the analysis of the energy flow in the
building, which is one of the main objectives of an energy audit. Researchers have
recommended methodology to appraise the performance of lighting systems in
terms of energy usage and optimization of energy use. If implemented during the
design stage the methodology can help in optimizing the performance of the
lighting system. It is important to think ways to manage energy intelligently and
reduce energy costs at the same time maintain required quality understanding the
opportunities and risks involved. This will help in planned decision making.
2.2 Proposed Methodology to Conduct Audit
There are many different types of energy audit methodologies that are used to
conduct the audit in an effective manner to reduce the power consumption in an
effective manner. MGR Vision 10MW is an energy awareness initiative forum that
was inaugurated in our university on 08/03/2014 this was inaugurated for reducing
GREEN 9 Project Outcome Report –16EE10
II-8
10MW generation of electrical energy. A purposed methodology is given in a flow
chart to conduct the audits in residential, commercial and in industries.
Fig.2.4. Methodology to Conduct Audit
The blocks shown above give the general steps involved in conducting the
Electrical energy audit keeping this as prime objective the work was started and
targets were fixed where collection of data was the main target so data collection
was initiated as explained in the next section of data acquisition.
Pre Site Review
Post Site Review
Data Collection
Single Line Diagram
Wastage study
Energy Management
Recommendations
Result
Outcome
GREEN 9 Project Outcome Report –16EE10
II-9
3 – DATA ACQUISTION
The power once generated is distributed via substation where considerable
quantum of energy utilized for lighting purpose in the society. The overall project
was subdivided into three stages :-
Stage 1 - “Illumination Level Study and Energy Assessment Analysis at
University Office”
Stage 2 - “ Analysis of Existing Dc System In ETAP”
Stage 3 – “ Design Of Self Sustained DC Micro Grid”
Fig 3.1 Description of project
3.1 – Work Execution In Stage 1 :-
The first phase of an energy audit started with site inspection work. The
measurements in all aspects have been taken for reckoning actual value of
prevailing luminous intensity level of the office. In this paper the details of possible
technical viability are analyzed and scope of saving both energy and cost has
been done through auditing in the university office. The first initiative is for going
for pre-site work, in this first we decide the location were to conduct this energy
audit in home, industry, schools etc. In this paper the first initiative we done is
doing auditing in university office and giving them a appropriate results and
GREEN 9 Project Outcome Report –16EE10
II-10
recommendation and suggestion regarding their usage of electricity and also
making an assumption to reduce the tariff of electricity bill. To create energy
awareness to the general public, Dr. M.G.R Educational & Research Institute,
University Chennai has taken initiative called ‘MGR Vision 10 MW’ under
leadership of Dr. L Ramesh to save 10 MW in 10 years. This work is the pilot
study work of Vision 10 MW. This study covers the waste audit analysis and
recommendation for the University office in the first stage.
3.2 Work Execution In Stage 2 :-
Fig no.-3.2 Steps involved
An innovative analysis of illumination level in the substation’s yard and control
room has been taken as a part of electrical energy audit and also the DC system
interfacing with the micro grid ,carried out with purpose oriented. In 400 / 230-110
KV substation, widespread in 83.33 acres comprising 3 yards of 400KV, 230 KV
and 110 KV and one control room with external bifurcation for battery room, LVAC
room, cable room, PLCC room , this project study undertaken. The substation
GREEN 9 Project Outcome Report –16EE10
II-11
switch yard spread over 60 acres approximately and is divided in to separate bays
for respective feeder control and some left for transformers associated with switch
gears . The EHV outdoor substation like 400 KV is subjected to high
electromagnetic radiation due to which the metal members are inducted with
mutual and self induction. The lighting in the substation yard requires special
design and study in such a way that illumination system should be adequate to
carryout emergency and night patrolling work without hindrance in the operational
point of view and make comfort to replace the failed equipment. The erection of
lighting fittings needs safer distance from the live equipments and bus, considering
all aspects of electrical safety too. The proposed paper dealt with an attempt
exercised with efficacy keeping an eye towards possible merits oriented energy
conservation. The method of two tier lighting in the yards, a new concept is taken
for analysis. This two tier lighting control is an innovative step to illumination
control where minimum lux value is maintained when no physical activity in the
any of the switch yard. That is referred as first tier of lighting system which is dim
level lighting. In the second tier lighting system is proposed when there will be
activity in the yards either routine or emergency, then adequate luminous intensity
will be maintained by other set of lighting system prescribing standards of
stipulations. The electricity generation power houses and substations are the
primary origins where judicial way of utilization of electricity should be started with,
and it shows a good sign to the consumers. Even the concepts of energy audit is
basically similar, but while adoption in the detailed audit, the methodology varies
industry to industry and concern to concern, and all basically depends upon the
energy auditor’s high profile in his discipline dealt with. The energy conservation is
partially depends psychological attitude of the society too. The proper awareness
and imparting knowledge through possible social means necessarily to reach
every common man to do energy conservation through his or her attitudinal
change with the energy related appliance right usage to practicable extent. In the
EHV substation audit study, the the present provision of lighting fitting on the
gantries which supports the connecting jumpers to the feeders etc, creates
inflexibility for maintenance personnel during replacement. And in safety point, this
method of light fittings spread in gantries not technically supportive. Instead of
studying uniform luminous level, the fittings are installed in random wherever
possible. This analysis, supported through the modern software, reveals the fact
GREEN 9 Project Outcome Report –16EE10
II-12
that the extent of possibility to make the lux level moreover uniforms without any
investment, just by relocating the fittings in the gantries itself. And in the analysis
‘with investment’ new system of lighting called ‘ Two tier system’ in which only
LEDs proposed to be installed. Another concept of poly vinyl chloride wrapping of
metal post from bottom to top are proposed to enhance the life of the lamp post
and prevent it against the soil corrosion and miscellaneous induction etc. As
already illustrated normal steel pole when exposed to environment subjected to
corrosion, that too the rate of corrosion is of higher magnitude where the metal
joins with earth. The corrosion rate still more stimulated due to the higher rate of
stray induction by the external field. In order to prevent the corrosion, an external
wrapping of polyvinyl chloride over the steel pole, both externally and internally. In
addition it adds mechanical strength.
3.3 University Office Audit Procedure
The data collected revealed the possibility of energy saving in the office envelope
of total area of approximately 225 square meters. This paper projects with energy
audit recommendations in the later part. The steps involved in the execution of
electrical energy audit are as below.
level calculation for the proposed area
GREEN 9 Project Outcome Report –16EE10
II-13
3.4 Substation Audit Procedure
To conduct substation audit the first work is to design the layout to conduct the
audit as shown in the chart given below in which the procedure how to conduct an
audit and to the manage it in an effective manner
A step by step procedure is adopted to carry out the audit. The steps involved are
1. Preliminary and detailed study in the control room area and all switch yards
2. Design and analysis of existing lighting system in VISUAL software.
3. Practical live lux level calculation.
4. Analysis of power flow to the luminary fixtures via SLD in ETAP
5. Design and analysis of proposed system in VISUAL software.
6. Analysis of the DC system in ETAP
7. Designing of Micro Grid for new system
8. Recommendations
3.5 Energy Audit At University office
I. DATA OBSERVATION
The first phase of an energy audit started with site inspection work. The
measurements in all aspects have been taken for reckoning actual value of
prevailing luminous intensity level of the office. In this paper the details of possible
technical viability are analyzed and scope of saving both energy and cost has
been done through auditing in the university office. The theoretical level of
illumination required as per the standards which studied with the actual level.
Every appliance has been subjected to audit and aggregate load details were
prepared. The room index for every partition was calculated and LUX levels were
recorded. The analysis of energy wastage in the university office was also done
on the merits of data collected by visiting different timing over the span of a week.
The data collected revealed the possibility of energy saving in the office envelope
GREEN 9 Project Outcome Report –16EE10
II-14
of total area of approximately 225 square meters. This paper projects with energy
audit recommendations in the later part.
1. Preliminary study about the prospective area
The following layout shows the university office and the way of spread of lighting
system. The load details with respect to room also explained further. The office
was subjected to electrical energy audit and solutions devised. The overall area
was divided into various segments named from A-K.
Fig3.3: layout of the existing area
Here mainly seating arrangement for most of the staff is in ‘K’ segment. The
prospective auditable area was calculated both in sq.feet and square meters. The
total area of the office comprises of 2470 sq feets with a staff strength of 40. Out
of that the major area is covered by the area “K” which is around 903 sq feets. “A”
is of 121sq feets , “B” is of 110 sq feets, “C” is of 130 sq feets, ‘D” is of 100 sq
feets, ‘E” is of 110sq feets, ‘F” is of 120sq feets, “G” is of 80 sq feets, “H” is of
264 sq feets, “I” is of 121 sq feets, “J” is of 33 sq feets, “L” is of 378 sq feets.
II. . WASTAGE AUDIT
This step is to ascertain the scope of the possible saving of energy during the
working hours of office. As to acquire reliable data, periodical visits have been
paid in different time slots and observed the nature of load running waste and
accounted its ratings. The computed consumption also worked out. An
independent enquiry also conducted without revealing the purpose among the
GREEN 9 Project Outcome Report –16EE10
II-15
staff to ascertain their style of functioning with energy equipments and also
collected the factors influencing the wastage of energy particularly in respect of
the operation of Photostat , personal computers etc. The average pattern of
energy running waste is tabulated below.
Table 3.1 : Wastage Assessment with Time
Time Fans Lights Rating (watts)
9:15 - 10:15AM 3 10 1260
10:30 - 11:15AM 2 12 1416
11:15 - 12:15PM 2 10 1200
12:15 - 1:15PM 3 12 1476
01:30 - 2:30PM 2 11 1308
02:30 - 4:00PM 1 10 1140
04:00 - 05:00PM 2 10 1200
05:00 - 06:00PM 2 8 984
Fig3.4: Energy Wastage Percentage Assessment
The graphical representation of the wastage audit with the data collected from the
university office has shown. From the table it can be vividly seen that the
maximum wastage occurs during 9.15 to 10.15 Hours, in the morning which is
being because of the college work starts from 9:30 but the equipments are
switched on by 9:00 hours and there is only one person who is switching on and
off all the lights and fans regularly. Considerable wastage occurs during 12:30 to
1:30 which is lunch time, while most of the equipments left in switched on state
GREEN 9 Project Outcome Report –16EE10
II-16
but less staff were found in the office. So here it can be seen that just due to
unawareness and ignorance precious energy is being wasted which can be
minimized by taking proper care. It is estimated that, by the way of effective
utilization around 10 kWh per day can be saved which roughly works out to the
figure of 3000 kWh units per annum. If the cost per unit is Rs 7 then estimated
saving of Rs 21000 per annum which reminds the proverb ‘ Little drop makes an
ocean’ . Already the office enclave is air-conditioned fully, hence under normal
conditions fans are not necessary. But considering extra ordinary occurrence in
the event of air-conditioning failure, the usage of fans can be opted. However
such a view not taken in to account in this audit study for calculation of saving
aspect. But reiterating to keep fans in off when office enclave in air conditioned
mode. Then the estimated saving will be higher.
Connected load
The table given below shows the total connected load of the office. From the
graph shown it can be easily depicts that the max energy consumption is due to
the UPS, The lightning on a whole adds a total load of 3KW in addition with fans,
computers the minimum consumption by the printers
Table 3.2: total connected load
Sl
No
Description Total
nos
Wastage Total
Load
1 CFL fitting
16 36 576
2 Sq. fitting
19 108 2052
3 Doom fitting
3 120 360
4 Photostat machine
1 300 300
5 Ceiling fan
20 60 1200
GREEN 9 Project Outcome Report –16EE10
II-17
6 Split A/c machine
3 2500 7500
7 Desk top computers
8 250 2000
8 Water purifier
1 300 300
9 UPS system 1 7.5KVA -
-
1 7.5 KVA ----
TOTAL LOAD
14.288 KW
C. Practical lux level
In fact it was conducted adopting two methodologies.
1. Measurement of actual level of lux at the center of the every working surface and
Tabulated. The lux level is measured at every working table. Among these
measurements it was noticed that the lux measurement level was below the
required value in a8 and b5 working table.
.
2. Measurement carried out in each cabin and hall, corridor etc as per the calculated
room Index and analyzed.
The available luminous intensity level of the corridor is more than the prescribed
level.
The illumination level of the office is non–uniform which can be improved by the
way of installing distributed illumination rather the single, single fixture or using
louvers.
GREEN 9 Project Outcome Report –16EE10
II-18
Table 3.3 Lux value measured
Room index: According to the bureau of energy efficiency ‘room index’ is the
number that describes the ratio factor of the room length, width and height.
SEGMENT AREA LUX LEVEL MEASURED AT WORKING
SURFACE
A ROOM 104
B ROOM 101
C ROOM 132
D ROOM 250
E ROOM 233
F ROOM 205
G ROOM 214
H ROOM 140
I ROOM 198
J ROOM 255
K OFFICE
HALL
a1: 124 b1 125 c 1 176
a 2 122 b 2 141 c 2 160
a 3 142 b 3 127 c 3 160
a 4 129 b 4 106 c 4 138
a 5 115 b 5 95 c 5 150
a6 135 b 6 110 c 6 155
a 7 110 b 7 127 c 7 164
a 8 92 b 8 150 c 8 155
L CORRIDO
R
NO WOKING TABLE
GREEN 9 Project Outcome Report –16EE10
II-19
Room index= (LxW) / (Hm(LxW))
L= length of the room , W= width of room , Hm= mounting height.
It doesn’t matters whether the dimensions are in meters or not, but the unit should
be same for all. The minimum number of measurement point can be ascertained
from the table shown below
Table 3.4 Room Index Calculation
Segment Description Prescribed
Level of Lux.
(advocated
Value)
Room
index
Meas. Reqd.
A ROOM 100 to 200 0.50 9
B ROOM 100 to 200 0.48 9
C ROOM 100 to 200 0.51 9
D ROOM 100 to 200 0.45 9
E ROOM 100 to 200 0.48 9
F ROOM 100 to 200 0.50 9
G ROOM 100 to 200 0.40 9
H ROOM 100 to 200 0.69 9
I ROOM 100 to 200 0.50 9
J ROOM 40 to 60 0.21 9
K OFFICE 100 to 200 1.28 16
L CORRIDOR 50 to 75 0.56 9
GREEN 9 Project Outcome Report –16EE10
II-20
As per the Code of practice of interior illumination – IS 3646-1 (1992) room index
is required to get the numbers of reading required to measure the theoretical lux
level of the proposed area. Using the above facts the required numbers of
reading are taken and tabulated as shown above.
Measurement carried out in each
cabin and hall, corridor etc as per the calculated room index and analyzed. Lux
level measured at every working table. In such measurement it was noticed that
the lux measurement level was below the stipulated value in a8 and b5 table.
Hence both the seat may be rearranged accordingly The available luminous
intensity level of the corridor is more than the prescribed level.The illumination
level of the office is not uniform which can be eliminated by intelligent lighting
system
C. Constraints for optimal lighting
The wall with brown wooden coverage even though appears good not supporting
for effective lighting spread due to more rate of diffusion and not supporting gross
illumination. The lights are provided above the two fans in ‘K’ segment may be
rearranged to improve shadowing effect which will be quiet annoying. In spite of
its technological merits in all aspects , it seems impractical to suggest all lighting
fittings by light emitting diode lamps owing to the initial high cost
3.6 Energy Audit At substation’s Switchyard
Preliminary study in the prospective area
A substation is an indigenous system normally before the electrical power left to
the consumer’s choice of utilisation. Substations do the function of
transform voltage level from higher to lower or vice versa to carry out specific or
generalized purpose oriented activity. Here the EHV substation comprises 400 KV,
230 KV, 110 KV switch yards with a control room. The switch yards are
geographically spread facilitating the drawl of feeders to other substations and the
switch yard of the generating stations.
GREEN 9 Project Outcome Report –16EE10
II-21
a. SWITCH YARDS LAYOUT
Among the switch yards of different voltage level, in the 110 KV yard comprises
twelve bays with the equal width of 9.18 meters and the last bay in south and north
side of 110 KV yard are at a distance of 16.76 meters and 19.8 meters
respectively from the bilateral roads.
Fig-3.5 110 KV yard layout
Fig: 3.6 230 KV yard lay out
GREEN 9 Project Outcome Report –16EE10
II-22
Fig 3.7 400KV YARD layout
There are 26 sodium vapour lamps each rated 250 watts are provided on the top
of the gantries. The location of lamps is marked with circular point and the
numbers of light fittings are shown in figure 1.1.The 110 KV yard is spread in
16060 square meters. The 110 KV switch yard is designed for double bus with bus
coupler and single breaker system .The 230KV yard comprises 12 bays each bay
is of 14m length the distance between first bay and the outer boundary is of 7.6m
and the last bay to outer boundary is 12meters.The 230 KV yard consists of total
52 sodium vapor lamp provisions. The lamp location and the area layout is as
shown above in the fig.1.2. The extent of 230KV yard is around 20116 sq meters.
The arrangement of switch gear is as like 110 KV yard. The design of 400 KV
yard is double bus one and half breaker system arrangement. The total spread of
400 KV yard alone is 110336 sq.meters. In the 400 KV yards the are numbers of
mercury vapor lamp fittings and numbers of sodium vapour lamps. The illumination
level in the three yards are not uniform in our vision and also the fittings are
provided in groups where ever easy possibility at a height of about 8 meters. The
low tension supply to the switch yards connected from the 500 KVA station
transformers from the local 110 KV substation with back feeding arrangement.
3.7 Control room Data Observation :
Control room is widespread into 515 square meters. All the control & relay panels,
RTCC panels, GPS system, SCADA system , communication panels, RTU, fire
protection annunciation panel etc are housed inside the control room logically in
GREEN 9 Project Outcome Report –16EE10
II-23
operation point of view. The control lightning design was done by one lead
concern in early 2000 with the spread of 65 twin lamps fittings of 40 watts
fluorescent 4 feet tube light. Thus total FTL lights in operation are 130 numbers
.
Fig3.8- CONTROL ROOM LAYOUT
I. Design and analysis of existing lightning system using Visual software.
a) Analysis of Yards
The diagram shown below is the illumination level analysis of 110KV, 230KV &
400KV yard done in VISUAL Software.
FIG-3.9 110KVVISUAL ANALYSIS
GREEN 9 Project Outcome Report –16EE10
II-24
FIG-3.10 230KV VISUAL ANALYSIS
FIG-3.11 400KV VISUAL ANALYSIS
On Analyzing the three Yards in the software it was found that the value of lux
obtained in the yards are not as per the prescribed value on par with the standards
the value of lux for the outdoor yard lighting which around 30 lux but the maximum
value of lux obtained is 20 lux below the lights and on an average value in each
yard is only 14lux. This lighting system not supporting the purpose for which these
are erected and annoy the working environment. In the figures also it was evident
due to dark patches. So it is recommended to change the fittings with higher
lumen value or on the other way reducing the height and it is better to go for
rearrangement of fittings so that the lux value obtained would be fair to carry out
operations even at night.
GREEN 9 Project Outcome Report –16EE10
II-25
b) Control Room
The picture shown below gives the illumination level analysis of Control Room via
VISUAL Software. Fig 2.7 shows the value of lux obtained in the control room.
However the average lux value obtained the control room is around the prescribed
value but the FTL fitting used in the control room becoming generation old model
and each fittings consists of twin lamps consuming of around 80W of power. The
same value of lumens can be obtained with less consumption of electrical power
by the presently available lights in the market. So in the recommendations it is
proposed to change the fittings with LED lamps where each fitting will consumes
below 40W of power consumption with long lasting life span about 50000 burning
hours without appreciable reduction in its luminous output. As in the control room
activities will go ahead in shifts, hence the lights are operating round the clock.
That will a reason, that the cost incurred for replacement will be got back within
short payback period.
FIG-3.12 CONTROL ROOM VISUAL ANALYSIS
II. Practical live lux level calculation –
a) Yards live lux calculation
The value of lux was calculated by the application of user friendly software. In fact
many equipments and devices are spread in, both at yards and the control room
which pose obstructions for ground level lighting, however that aspect was not
accounted while analyzing the lux level through VISUAL software. So a manual
GREEN 9 Project Outcome Report –16EE10
II-26
calculation was also carried out using the lux meter and the output obtained are
shown in layout diagram.
Fig3.13- Present live lux level of 110KV switch yard
Fig: 3.14-Present live lux level at 230 KV switch yard
Fig 3.15.Present live Lux level at 400 KV switch yard
GREEN 9 Project Outcome Report –16EE10
II-27
Data collection for the manual analysis of luminary fixtures started from the
measurement of 400 KV, 230 KV and 110 KV yards. In the twelve bays in 110 KV
yard comprises of twelve numbers of bays where the average values of lux
measurements seen as 14 lux. In the 230 KV yard also measured average lux
value will be 16 lux only. In the 400 KV yard the illumination level in average
accounted less than 20 lux. Either due to the present way of spread of lighting
fittings not supporting to attain the standards of outdoor lighting of switch yards of
minimum 50 lux level. The actual measurements of lux in the switch yard using the
digital lux meter have been taken after 20 hours for reliable values.
b) Control Room live lux level calculation
The control room is a centralized air conditioned hall with an area of 515 square
meters and distributed with the numbers of twin fluorescent lamps designed
optimally and the lux level is adequate. The twin FTL fittings fixed in false ceiling of
control room. The lighting design inside the control room with measurement of
luminous intensity is as per room index . The room index of the control room
worked out as approximately 3.
Room index: According to the bureau of energy efficiency ‘room index’ is the
number that describes the ratio factor of the room length, width and height.
Room index= (LxW) / (Hm (L+W)) = 3 for control room.
L= Length of the room , W= Width of room , Hm= Mounting height.
It doesn’t matters whether the dimensions are in meters or not, but the unit should
be same for all As per the Code of practice of interior illumination – IS 3646-1
(1992) room index is required to get the numbers of reading required to measure
the theoretical lux level of the proposed area.
GREEN 9 Project Outcome Report –16EE10
II-28
Analysis of luminary fixtures via SLD in ETAP –
[1] Yard lightning
Fig 3.16 Analysis of yard lightning
The SLD shown above gives the complete connection of lights in the yard here we
can easily identify that the main bus is overloaded and also the cables are
overloaded in 400 KV Yard there is no seprate switch connected so when the
lights ar eon all are on at the same time even if not on use this leads to heavy loss
also for the safety point of view it is not tolerable. Th Real time reading obtained
from the meter connected is tabulated in the coloumb below.
Table -3.5 Lamp connected
In 400KV yard 77 sodium vapor lamp are used and 19 metal halide lamps are
used and all the lights are in function. In 230KV yard 35 SVL are used and in
110KV yard 15 SVL are used. In 110KV and 230KV yards no metal halide lamps
are used. Single line diagram of the present connection of lightning fixtures was
drawn and analyzed in ETAP software. It was found that the controlling switches
for the entire outdoor lighting system provided in two locations. In the given single
GREEN 9 Project Outcome Report –16EE10
II-29
line diagram analysis it is found that the 110KV yard consumes 5KW of power ,
230KV yard consumes 12KW of power and 400KV yard uses 16KW of net power
being consumed in lightning. There is no separate arrangement of switch in 400KV
yard all the lights will glow together whether in use or not. In 110KV yard and in
230KV yard a single switch control given for complete yard. The Measurement of
ampere at night at two locations is furnished below.
Table-3.6 Real time current rating
Here it can be noticeable that the three phases are not equally loaded which
needs rearrangement in connection with similarity in loading.
Fig 3.17 Total Existing load Connected(KW)
The above graph shows the net connected load on the system. The major
consumption of load is by DC system then FTL consumes 23% of total load and
then the minimum consumption of power is by fan as there are only three fans
each of 100 Watts.
23%
2%
75%
FTL
Fan
DC load System
GREEN 9 Project Outcome Report –16EE10
II-30
Graph of yard lights and voltage
The existing system of yard lightning was analysed in the etap and the value of
voltage abd current obtained in response to the bus numbers are as shown below.
Fig. 3.18 Yard lightning Bus nos. VS current
The graph shown above gives the complete detailed analysis of yard current Vs
the buses number here we can easily identify that the current used by different
buses are not equal as load distribution is not equal. Here bus 33 and bus 3 is
heavily loaded.
Fig. 3.19 Voltage(%) VS Bus nos.
0
10
20
30
40
50
60
Am
ps
85
85.5
86
86.5
87
87.5
88
88.5
89
89.5
90
1 3 5 6 10 11 12 15 16 17 18 19 20 28 34
Vo
ltag
e(%
mag
)
No, of buses
GREEN 9 Project Outcome Report –16EE10
II-31
The graph shown above gives the graph of bus number Vs Voltage. Here the
variation in the value of the voltage is around +/- 5% ehich isn under the specified
value.
[2] Control room lightning
Fig 3.20 Control room SLD
The above SLD is of Control lightning Here each light connected is of 36 watts the
light used is FTL lamps. The graph of voltage and current obtained is as shown
below.
Control room graph for voltage and current
Fig. 3.21 Bus no. VS voltage(%)
99.5084
99.5086
99.5088
99.509
99.5092
99.5094
99.5096
99.5098
99.51
99.5102
BU
S93
BU
S96
BU
S99
BU
S10
2
BU
S11
6
BU
S11
9
BU
S12
2
BU
S19
2
BU
S19
5
BU
S19
8
BU
S20
1
BU
S21
5
BU
S21
8
BU
S22
1
BU
S22
4
BU
S24
9
BU
S25
2
BU
S25
5
Vo
ltag
e(%
Mag
).
GREEN 9 Project Outcome Report –16EE10
II-32
The above graph gives the value of bus number Vs voltage here almost the value
of voltage obtained is constant.This gives that the system is well connected and
properly loaded.
[3] DC Measurement
The power without protection is a useless’ is technical proverb normally spoken
among the power engineers. In every sub station, two battery system associated
with charger so called the main-1 protection system and main-2 protection system
are the normal systems used exclusively for protection circuits. Both the circuits
are separated and provided with the intension if any one system fails other
protection will act in event of fault. The operation of circuit breakers through the
tripping and closing coils are done by DC supply. The indication and annunciation
circuitry also being operated by direct current supply. Except the power flow in
alternating current transmission towers, the complex circuitry for the protection is
powered by direct current circuitry. In 400 KV substation, there are two sets of
batteries connected to independent system of charger normally 220 Volts, 600
ampere hour rating. During normal condition the batteries left in the state of
‘Floating’. The D.C system bus bar is used for pairing number of direct current
connections for the different protection schemes like overload protection , distance
protection, differential protection , over voltage or over flux protection, fire
emulsifier protection etc. Normal condition the D.C supply is used for the
operating voltage for the numerical relays. During fault conditions the respective
operating circuits energized by the other set of D.C supply causing to execute
desired protection related operation. Audible alarm and SCADA operations are
also being done by DC power extracted from battery and charger. The operation of
transducers , the power transformer protective system are based on D.C supply.
Hence maintenance of batteries are important as per the manufacturers directives
and the condition of battery charger should be taken care by selecting the mode of
‘boost’ and ‘ float’ which has to be decided as per values of specific gravity and
individual voltage per cell.
GREEN 9 Project Outcome Report –16EE10
II-33
DC SLD
The data taken for the drawing of SLD in ETAP is as given below
Table no.3.7 DC Bus terminals
No. of
Ferrules
DC Bus terminal
Number
Ope rating
Voltage(V)
Net current
consumed
(mA)
Total power
consumed(kw
)
84 DC Bus Terminals 1 220 37480 8.2456
84 DC Bus Terminals 2 220 28240 6.2128
As observed in the DC system there are total of 188 connections the overall
connection was placed in a two DC bus system in first system there are total of 84
connections as in the bus two. The operating volatege is found to be fixed at 220V
and the net current consumed by the susyem is around 65720mA. The net power
consumed by the DC system itself is around 15KW. This existing system is
analysed in ETAP software and the complete dtails is explained in next sections.
Etap Analysis of complete DC system
Fig 3.22 DC SLD
GREEN 9 Project Outcome Report –16EE10
II-34
As shown above the net load connected to the DC system is bifurcated in two
networks network 1 and network 2. The load connected in the network one and
network two is as shown below:-
Network one
Fig 3.23 load in network 1
Network two
Fig 3.24 load in network 2
GREEN 9 Project Outcome Report –16EE10
II-35
On analysizing the above system following draw backs in the present system :
1. The source for charging will be only through charger . In case if there ll be very
long interruption of input supply then the battery supply may be drooped which will
leave the protection system in to peril.
2. In the absence of standby charger, if any serious fault happened in the charger
then there ll be question for power system protection.
3. In the DC protection system in the major EHV substation , there will be more than
35 to 40 pairs of different tapping from the DC distribution bus for the various
scope of function and each pair normal requirement in milli amperage will also
different from each other.
4. During the device or numerical relays operations the DC burden requirement will
be manifold.
5. In even of operation of ‘bus bar protection scheme’ or ‘ local back up protection’
(LBB)
6. The amperage burden dragging from the DC source will be in quantum of amperes
only
7. In the proposed scheme taken for discussion in the paper , an Direct current micro
grid has been formulated and micro wind turbine , PV panels, DG generator all
incorporated within the micro grid along with the battery set interfacing with
conventional chargers connected with AC source.
8. The purpose will be strong DC source for the protection system in the event of any
black out or brown out happening in the transmission system. The main sources
to be wind mill or solar energy.
9. In this paper, it is taken for discussion that in so called DC micro grid the analysis
of absence of one source after other and also the requirement of burden during
the operation of protection system in every possible aspects.
10. The proposal of operation of DC lighting in the control room from the DC micro grid
also taken for simulation.
GREEN 9 Project Outcome Report –16EE10
II-36
11. In the 400 KV substation control room calculated with 65 twin 4 feet LED tube
lights taken for the simulation . The DC regulator also proposed to be provided for
continuous supply.
12. The graph obtained for the voltage and current Vs bus number is as shown below.
Graph of dc system for voltage and current
The complete analysis of the DC system was done in two stages in first stage only
those loads were taken into account which are static to the system further faults
were applied and a again the system was analysed.
1. First analysis dc bus voltage VS no. of buses
Fig. 3.25 Load flow report of DC load system without fault
The Graph shown above gives the Variation of voltage VS bus numbers of first
network. The variation was found to be within the prescribed limit of +/- 5%. This
demonstrates that the system is working properly with connections provided.
218.9
218.95
219
219.05
219.1
219.15
219.2
219.25
14 18 22 24 26 29 31 33 35 37 39 41 43 46 48 50 52 55 57 60
Vo
ltag
e(V
)
No. of buses
GREEN 9 Project Outcome Report –16EE10
II-37
Fig. 3.26 Load flow report of DC load system without fault
The Graph shown above gives the Variation of voltage VS bus numbers of first
network in continuation to the first graph second graph gives the variation in
second network. The variation found in the above graph is within the +/-5% which
is under the given specified value.
2. Analysis bus current VS nos. of buses
Fig. 3.27 Load flow report of DC load system without fault
The graph shown above gives the variation of current VS number of buses. The
load shown above gives the network one.
218.85
218.9
218.95
219
219.05
219.1
219.15
219.2
219.25
219.3
219.35
62 64 66 113 115 117 119 121 123 125 127 129 131 133 135 137 139 141 143 145 150
Vo
ltag
e(V
)
No. of buses
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
18 22 24 26 29 31 33 35 38 40 42 45 47 49 51 55 57 60 62 64
Cu
rre
nt(
amp
s)
No. of buses
GREEN 9 Project Outcome Report –16EE10
II-38
Fig. 3.28 Load flow report of DC load system without fault
In continuation to the graph one of network one second graph gives the variation
for second network . The output graph is shown in the above diagram and the
variation obtained in the existing system is shown.
3. Third analysis bus voltage VS nos. of buses during five fault
Fig. 3.29 Load flow report of DC load system with fault in five bus
The above graph shows the variation of current VS numbers of buses for
connection in network one.
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
1
65 112 114 116 118 120 122 124 126 128 130 131 133 135 137 139 141 143 145
Cu
rre
nt(
amp
s)
No. of buses
0
1
2
3
4
5
6
7
8
18 21 22 23 24 25 26 28 29 30 31 32 33 34 35 37 38 39 40 41 42 43 45 46 47 48 49 50 51 52 55 56 57 58 60 61 62
Cu
rre
nt(
amp
s)
No. of buses
GREEN 9 Project Outcome Report –16EE10
II-39
Fig. 3.30 Load flow report of DC load system with fault in five bus
The above graph shows the variation of current VS numbers of buses for
connection in network two. It is clear from the above two graph that the 21 ,120
,126 , 124 and 137 are loaded heavily then the other buses which leads to the
higher current consumption in the system.
4. Third analysis bus voltage VS nos. of buses during five fault
Fig. 3.31 Load flow report of DC load system with fault in five bus
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
63 65 112 114 116 118 120 122 124 126 128 130 131 133 135 137 139 141 143 145
Cu
rre
nt(
amp
s)
No. of buses
218.9 218.95
219 219.05
219.1 219.15
219.2 219.25
14 18 22 24 26 29 31 33 35 37 39 41 43 46 48 50 52 55 57 60 62 64
Vo
ltag
e (
volt
s)
NO. of buses
GREEN 9 Project Outcome Report –16EE10
II-40
Fig.3.32 Load flow report of DC system with fault in five buse
The above graph shows the variation of voltage VS numbers of buses for network
one and network two. In network one the voltage varies from 219.2 to 218.9 which
not of much difference but in network 2 there is a sudden drop from 220 to 208V
this may be due to improper cable connection to the system. Based on the data
observed in the above sections new methodologies were advised to adopt in the
further section of recommendations.
200 202 204 206 208 210 212 214 216 218 220 222
65 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 152 167 169 171
Vo
ltag
e (
V)
No. of buses
GREEN 9 Project Outcome Report –16EE10
II-41
4 – RECOMMENDATIONS
Recommendation is an act of suggestion or proposal as to the best of course of
action , especially one put forward by an authoritive body[6].In this methodology
the data aqua station is done by collecting data in a residential house, commercial
building and industries the data collection i.e. is collected gives the layout of usage
of electrical energy. The wastage of energy can be easily monitored and the
recommendation ideas with new forms of implementation of renewable energy in
effective manner to reduce the power demand and also motivating people to
undergo renewable energy resources. In these methods the tariff details, wattage
of each appliance, daily utilization chart, single line diagram and real time load
analysis etc. The details of these charts are given below with brief explanations.
The recommendation are designed in three manner and they are given below as
follows
Recommendation Without Investment
Recommendation With Investment
Recommendation with DG
These are some general tips to save energy at University and Substation.
1. Proper dusting and cleaning of exhaust fan should be done.
2. Instead of two fans you can replace it to one which you use frequently.
3. Instead of three CFL used in hall only one CFL can be used as the other two are
not necessary.
4. Decoration light should be especially used only occasionally
5. Use timer facility to save energy
6. Orient fan is placed in the room but the distance of light from the wall is not
proper.
7. You can use table fan as the room size is 25sqft only.
8. Instead of CFL used outside you can install LED bulb as it consume less energy.
GREEN 9 Project Outcome Report –16EE10
II-42
9. For air conditioner use windows with sun films and curtains
10. Don’t set your thermostat at a colder setting than normal when you turn on your air
conditioner. It will not cool your home any faster and could result in excessive
cooling.
11. Seal the door and windows properly.
4.1 Recommendations on University Office
A. Proposed Layout
:
Instead of recommending all lamps to be replaced by the present modern
technology energy star rated LED lamps which possess long span of life up to
50000 hours and environmental friendly, but due to the factor of cost ,it is
suggested the first phase of conversion for k segment, the main staff working area
and for the corridor as shown replacing 36x3 ( 108 w ) fluorescent fitting by
24x3(72w) . By these replacement, the luminous level will be more over same with
lesser involvement of cost. The system of LED can also provided with presently
available electronic control gear. The use of modern concept of lightning including
the use of daylight offers up to 75% potential to save energy.
Fig 4.1: Proposed Lighting Design
GREEN 9 Project Outcome Report –16EE10
II-43
B. Recommendation without investment:
1. Wastage Recommendation: The wastage audit reveals the fact that the
practice should be imparted that when leaving working table everyone should be
bound to switch off the lights and fans. There is considerable saving in long run. In
this audit, there will be estimated saving of 3000 kWh per annum which is roughly
saving of Rs 21000 per annum. Briefly to say that
All the equipment should be switched off when not in use.
Fans should be switched off when the AC is ON. It is advocated to keep a slogan
display on energy conservation in every one’s view with a advice of keeping fans
off when air condition system is operative.
Usage of minimum lights in the segment C, D, E , F ,G during day time because of
sunlight availability.
Fig.4.2 : Wastage Audit Saving Analysis
2. Rearrangement Recommendation:
It is seen that two lights are connected above the fans in segment ‘K’ and should
be rearranged to improve illumination and avoiding possible rotational shading
while the fan is rotating.
0
10000
20000
30000
40000
50000
Before wastage audit After Wastage audit
Wat
t H
ou
r
Energy wastage in watt Energy saved in watt
y y y y y
GREEN 9 Project Outcome Report –16EE10
II-44
a) Matching the proper lamp type to the respective work task , consistent with
color , brightness control and other requirements..
b) Establishing adequate light level without compromising objective and safety.
c) The decorating lighting fitting (TL-3nos) of 120 watt in the corridor normally
recommended to be kept off, except on special occasions
.
3. Recommendation with PC and Photostat Machine: According to the survey
of the wastage audit conducted by the energy audit team, it is noticed that most of
the system and the Photostat machines are left in the sleep mode. Hence, energy
is wastage in the form of no load loss. So the additional energy saved is used to
shut down the unit when there will be no work with it for longer period. The
computer systems, printers and Photostat machine are used effectively for 6 hours
in a day in the university office and left two hours in sleep mode as observed in
audit study then the energy loss will be more than 80 units per month.
Audit Observation: The energy saving per annum by avoiding sleep mode in PC
and Photostat machine is 960 units.
C. Recommendation with investment:
1. Recommendation with LED light:
In any energy audit report, if it fails to envisage to adopt modern efficient system at
least at its preliminary level in the area of the audit, then the suggestions and
directives are not up to the present technological yard stick. Hence it is
recommended to replace the existing 9 florescent lamp fitting of 108 watts in to 72
w in ‘K’ segment and 1 number in ‘G’ segment. These lamps are environment
friendly as it does not possess mercury and energy efficient. The life of the star
rated LED lamps will be more than 50000 hours. By this replacement using LED
lamps, estimated energy saving will be 1290 kWh per year. Considering the cost
GREEN 9 Project Outcome Report –16EE10
II-45
implication for conversion to LED lamps apparently thrice of other fittings, first
phase of conversion is suggested only for main staff working segment.
Fig 4.3 :Saving with Proposed LED lights
The given chart stresses that if we properly switch on and off the lights and avoid
using lights during day time will save the load of 1124 watt without any investment.
Audit observation:
Cost equivalent of 1290 unit per annum can be saved by the LED lamp
replacement.
2.Recommendation with Fan:
The energy audit team found that the fan installed in the in office is not star rated.
Available fan is consuming 60 W. It is recommended for replacement with energy
efficient star rated fan which will be available for 50 watts per fan. If the fans are
replaced by star rated fans in a pace manner the savings in that aspect will be:
Fig. 4.4 Total saving after recommendation
3300
2100
0
500
1000
1500
2000
2500
3000
3500
Existing CFL Proposed LED Light
Y
X
0
1000
2000
3000
4000
5000
wastage audit Reaarangement PC and xerox Total
kWh
r/Y
ear
Y
GREEN 9 Project Outcome Report –16EE10
II-46
Difference in watt = 10 watt
Saving =700 kwh per annum
.
Audit Observation: From the above data analysis, the possible saving of 700
units per annum is achieved, by
Replacing the old fans by new fans.
3.Recommendation with PC and Xerox machine:
The graph shown below gives the quantum of saving if the staff not preferred the
sleep mode in personal computers and Photostat machine.
Fig. 4.5 : Energy saved with pc and Xerox machine
Audit Observation: From the above data analysis, the possible saving of 900
units per annum is benefited, if the operator of PCs and Photostat machines are
not preferring sleep mode.
0
200
400
600
800
1000
1200
1400
1600
Energy Saving in PC Energy Saving in Xerox
Machine
Total
Wh
/Da
y
Y
GREEN 9 Project Outcome Report –16EE10
II-47
Fig. 4.6 : CFL and LED comparison
As the economic rises day by day so the use power also rises which puts a
tremendous stress on power utilities to increase the generation of the energy so as
to meet the demand .Taking this in mind an initiative “VISION 10MW” was started
with the aim of saving 10MW of energy within 10 years pilot project a case study in
University office was initiated because here it is possible to imbibe the energy
conservation knowledge and to use the equipments at its best way with minimum
wastage. The data provided in the paper gives a detailed information regarding the
saving of energy by incorporating changes in our personal habits as well as by
using more energy efficient equipments in continuation to this in phase 2 a
detailed analysis of the Substaion is done which explained in the next sections.
4.2 Recommendations on Substaion
Recommendation is an act of technical proposal for prospective implementation
to get the yield of the energy audit by the best course of action []. Basically there is
two modes of recommendations on fiscal basis, those are, without investment and
with investment
a) Without investment:
As such in the switch yards the light fittings provided in groups, with three to
seven fittings in a group facing different directions, not yielding even output.
Instead, the analysis with the software shows if the available sodium vapour and
mercury vapour fittings are evenly placed there will be prospective improvement in
the luminous level throughout the yard. The possible arrangement is as below in
0
200
400
600
800
1000
1200
1400
1600
1800
2000
Exiting CFL Proposed LED Light
kWh
r
Y
GREEN 9 Project Outcome Report –16EE10
II-48
400 KV , 230 KV , and 110 KV switch yard. The study reveals that the control room
luminous intensity is optimum only.
Fig 4.7.Rearragement lux level in 110 KV yard
Fig 4.8 Rearrangement without investment in 230 KV switch yard
GREEN 9 Project Outcome Report –16EE10
II-49
Fig 4.9 Rearrangement in 400 KV switch yard
Hence under the clause of recommendation on without investment the
rearrangement of the available lights should be placed in modified distribution form
to yield optimum result. The outcome of analysis of the existing system is shown in
the diagram, Fig 5.1 gives the rearrangement suggested in 110KV yard. On
rearranging the lights the output obtained is analyzed in VISUAL here minimum
value of lux obtained is 0.1 and maximum value obtained is 28.1 however the value
of lux is not constant that can be seen clearly from dark spots obtained in the
proposed layout similarly Fig 5.2 shows the rearrangement of 230KV switch yard ,
and Fig5.3 depicts the rearrangement of 400 KV switch yard.
b. With Investment:
1. As the sub-station yard is the special class of lighting area which is neither a
continuous process industrial area nor like a crowded public area. Hence concept
of keeping adequate lighting throughout the night hours do not serve any purpose.
By virtue of the nature of working, the’Two tier system ‘of lighting suggested
through this paper. This will be appropriate rather than keeping the required lux
level throughout the night. The advantage of the proposed scheme is manifold. The
two tier lighting system involves the stages of dim level lighting in the first stage and
standard luminous lighting in the Second level. During normal power flow occasion
it is advisable to keep yard with dim or low level lighting.
GREEN 9 Project Outcome Report –16EE10
II-50
2. In the second tier of adequate luminous system adequate luminous intensity
should be made available in the yard area to carry out patrolling, execution of
unforeseen works up to certain height from the yard ground etc. Separate design
factors have been taken up for discussion.
3. In this system of lighting the height of the lighting pole should be lesser than the
height of the isolators. Hence any arc in the isolators contacts and jumper
loosening faults can be visible to the operational staff in the first tier of lighting. The
first tier of lighting poles normally suggested to erect at the corners and
recommended to operate automatically by pre set timers.
4. In the second tier of lighting is preferred with manual switching of all lights when
it needed and the system holds the illumination level as per the standards. The
second tier lighting system that the consecutive poles suggested to be erected
just 10 meters a part.
5. The concept of wrapping the pole by poly vinyl chloride is recommended with the
practical touch to the paper to avoid deterioration of poles due to soil corrosion and
increase in the rate due to the stray induction in the EHV electro magnetic
induction. The height of the lighting poles may be 10 to 12 feets above the ground
level. This recommendation will enhance the life of the lighting pole manifold also
reduction of charge carriers.
6. The merit of the two tier system as like the sub-station yard fetch considerable
cost savings and longer the life of the costly lamps.
7. Replacement of SVL into LED : According to the survey of the energy audit
team it was observed that in the sub-station ,there are three yards of 400KV,
230KV,110KV . In 400KV yard, 77 sodium vapor lamps of 250W and 19 mercury
vapor lamps of same rating are connected. In 230 KV yard, 35 sodium vapor
lamps of 250W are connected. Similarly, in 110kv yard there are 28 sodium vapor
lamps of 250W are connected. SVL and MHL are gaseous discharge lamps lesser
efficient than LEDs light So ,if the 250W of sodium vapor lamp and mercury vapor
lamps are replaced by the 60W of LEDs light , can save the more energy. The
lumens output/lamp of SVL is 27100 of 250W which will be equated by the LED
with new design.
GREEN 9 Project Outcome Report –16EE10
II-51
8. The substitution of 4 feet 20 / 18 Watts LED lamp is recommended in place of 40
Watts FTL in all the 65 twin FTL provision bye passing ballasts.
a. 110KV Yard Analysis In VISUAL and cost comparison:
Fig4.10 . 110KV Tier1 lightning
Fig4.11 110KV Tier 2 lightning
1. Total no. of SVL in 110KV yards = 28 , Wattage of the one SVL = 250 W
Total Power Consumption in KW = (250 × 28) /1000 = 7KW ,
Duration of use in a year= 12×365 = 4380 hr/yr
Total power consumption in KWH = 7 × 4380 = 30660 KWH
Wattage of proposed LED light = 150 W , Total no of LED lights = 36
GREEN 9 Project Outcome Report –16EE10
II-52
Total Power Consumption in KW = 150 × 36= 5.4 KW ,
Duration of use in a year= 12×365 = 4380 hr/yr
Total power consumption in KWH = 5.4 × 4380 = 23652 KWH
The difference in power of lamps = 100W
Total energy consumption = (100 × 4380 × 36) / 1000 = 15768 KWH
Saving i.e. difference in energy bill ::
Cost / Unit @ Rs.7/- (1 unit = 1 KWh) = 7 × 15768=Rs- 1,10,376 /-
Cost of the existing SVL = 4570 /- ,
Total Cost of existing lamps = (4570 × 28) = 127960/-
Cost of the proposed LED Light = 23000/- , Total Cost = 36 × 23000 = 828000/-
The additional expense to the exchequer:= 828000 – 127960 = 700040/-
Pay Back Period: =700040 / 127960 = 5 years and 6 months.
Fig. 4.12 110KV Cost Comparison
0 100000 200000 300000 400000 500000 600000 700000 800000 900000
Existing SVL(250W)
Proposed LED(150W)
In R
up
ee
s
GREEN 9 Project Outcome Report –16EE10
II-53
Fig 4.13 Energy consumption
Audit Observation: : Life of SVL is approx 3 to 4 years. And life of LED of
standard brand comes around 50000 operating hours. The additional cost incurred
towards the replacement will be paid back in 5 and half year time period and eco
friendly too
b. 230KV Yard Analysis In VISUAL and cost comparison:
Fig: 4.14 ( 230 KV yard , Tier-1 )
0
5000
10000
15000
20000
25000
30000
35000
Existing SVL(250W)
Proposed LED(150W)
KW
H/Y
EAR
GREEN 9 Project Outcome Report –16EE10
II-54
Fig : 4.15 . ( 230 yard, Tier.2 )
Total no. of SVL in 110KV yards = 35 , Wattage of the one SVL = 250 W
Total Power Consumption in KW = (250 × 35) /1000 = 8.75kw , Duration of use
per year= 12×365 = 4380 hr/yr
Total power consumption in KWH = 8.75 × 4380= 38325 KWH
Wattage of proposed LED light = 150 W , Total no of LED lights = 36
Total Power Consumption in KW = 150 × 36= 5.4 KW , Duration of use per year=
12×365 = 4380 hr/yr
Total power consumption in KWH = 5.4 × 4380= 23652 KWH
The difference in energy consumption = 100w , Total energy consumption =
(100×4380× 36)/1000 = 15768kwh
Saving i.e. difference in energy bill ::
Cost / Unit @ Rs.7/- (1 unit = 1 KWh) = 7 × 15768 =Rs- 110376 /-
Cost of the existing SVL = 4570 /-
Total Cost of existing lamps = (4570 × 35) = 159950/-
Cost of the proposed LED Light = 23000/- , Total Cost = 36 × 23000 = 828000/-
The additional expense to the exchequer:= 828000 – 159950 = 668050/-
Pay Back Period: = 668050/ 110376 = 6.05 years
Audit Observation: : Life of SVL is approx 3 to 4 years. The additional cost
incurred towards the replacement will be paid back in 6.05 years time period.
GREEN 9 Project Outcome Report –16EE10
II-55
Fig. 4.16 230KV Cost Analysis
Fig. 4.17 Energy Consumption
0
100000
200000
300000
400000
500000
600000
700000
800000
900000
Existing SVL(250W) Proposed LED(150W)
Pri
ce in
ru
pe
es
Cost Comparison
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
Existing SVL Proposed LED
Ene
rgy
con
sum
pti
on
in K
WH
GREEN 9 Project Outcome Report –16EE10
II-56
c. 400KV Yard Analysis In VISUAL and cost comparison:
Fig4.18 230KV Tier1 lightning
Fig 4.19 230KV Tier2 lightning
Total no. of SVL & MHL in 400KV yards = 77+19= 96 , Wattage of the one SVL&
MHL = 250 W
Total Power Consumption in KW = (250 × 96) /1000 = 24kw , Duration of use per
year= 12×365 = 4380 hr/yr
Total power consumption in KWH = 24 × 4380 = 105120 KWH
Wattage of proposed LED light = 150 W , Total no of LED lights = 96
Total Power Consumption in KW = 150 × 96= 14.4 KW , Duration of use per year=
12×365 = 4380 hr/yr
Total power consumption in KWH = 14.4 × 4380 = 63072 KWH
The difference in energy consumption = 100w
Total energy consumption = (100 × 4380 × 96) / 1000= 42048 KWH
GREEN 9 Project Outcome Report –16EE10
II-57
Saving i.e. difference in energy bill :Cost / Unit @ Rs.7/- (1 unit = 1 KWh) = 7 ×
42048 =Rs- 294336 /-
Cost of the existing SVL = 4570 /- , Cost of the existing MHL = 4650 /-
Total Cost of existing lamps = (4570 × 77 +4650 × 19) = 440240/-
Cost of the proposed LED Light = 23000/- , Total Cost = 96 × 23000 = 2208000/-
The additional expense to the exchequer:= 2208000 – 440240 = 1767760/-
Pay Back Period:= 2208000 / 294336 = 7.5 years
Audit Observation: : Life of SVL is approx 3 to 4 years. The additional cost
incurred towards the replacement will be paid back in 7 and half year time period.
Fig. 4.20 400KV Cost Analysis
Fig. 4.21 400KV Energy Consumption
0
5
10
15
20
25
Existing SVL(250W) Proposed LED(150W)
Pri
ce in
lakh
s
0
20000
40000
60000
80000
100000
120000
Existing SVL Proposed LED
Ene
rgy
con
sum
pti
on
in K
WH
GREEN 9 Project Outcome Report –16EE10
II-58
Fig.4.22 Saving of Energy consumption in KWH/year
The above graph shows the net energy saving in different switchyard for the
lightning system.From the graoh it is very clearly understood that a net saving of
around 69000 KWh/Year can be done on replacement of existing lights to
prescribed LED lights.
d. Control Room Analysis In VISUAL and cost comparison:
Replacement of FTL into LED: There are totally 130 FTLs (4 feet) are connected in
the control room. The present technology in the lighting system is progressive with
LED. The LED possess its merits like eco friendly due to the absence of mercury
and lesser consumption of power for the same lumen output. The lumens
output/lamp of the FTL of 40 W is approximately 1700 ,but the lumens output/lamp
of 20 W LED is also approximately1700 .So the wattage difference is
20W.Suppose the usage hours is 24 hours and number of working days is 365.The
working sheet for the simple payback period is as follows. Here the proposal will be
merely replacing the existing fluorescent tube lights and provision of same
dimension LED disabling the ballast.
0
10000
20000
30000
40000
50000
60000
70000
110KV Yard light 230KV Yard light 400KV Yard light Total Saving
Un
it C
on
sum
pti
on
in
KW
H/y
ear
GREEN 9 Project Outcome Report –16EE10
II-59
Fig.4.23 control room
Total no. of FTL lights = 130 , Wattage of the one FTL= 40 W
Total Power Consumption in KW = 36 × 130=5.200 KW , Duration of use in a year=
24×365 = 8760 hr/yr
Total power consumption in KWH = 5.200 × 8760= 45,552 KWH
Wattage of proposed LED light = 20 W, Total no of LED lights = 130
Total Power Consumption in KW = 20 × 130= 2.6 KW , Duration of use in a year=
24×365 = 8760 hr/yr
Total power consumption in KWH = 2.6 × 8760 = 22776 KWH
The difference in energy consumption = 20 W,
Total energy consumption = (20×8760×130) /1000 =22776 KWH
Saving i.e. difference in energy bill ,
Cost / Unit @ Rs.7/- (1 unit = 1 KWh) = 7 × 22776 =Rs- 159432 /-
Cost of the existing 4 feet FTL = 50 /- , Total Cost = 50 × 130 = 6500/-
Cost of the proposed 4 feet LED Light = 900/- ,Total Cost = 130 × 900 = 1,17,000 /-
The additional expense to the exchequer: = 117000 – 6500 = Rs- 110500 /-
Pay Back Period:= 110500 / 159432= Within 9 months
Audit Observation: : Life of FTL is approx 10,000 hours but the life of the LEDs
are 5 times more than the FTL i,e 50000 hours. The additional cost incurred
towards the replacement will be paid back well within 9 months span.
GREEN 9 Project Outcome Report –16EE10
II-60
fig 4.24 sub station control room with LED cost analysis
Fig 4.25 substation control room
RECOMMENDATION WITH FAN: According to the survey of the energy audit
team regarding the ceiling fans , the three ceiling fans connected in the control
room are not star rated fans. The wattage of the existing fan is 100 W. So, it is
recommended to replace the old fan into star rated fan of 50W in place of 100W
fan.
Total no. of fans in connected = 3 , Wattage of one fan = 100W
0 20000 40000 60000 80000
100000 120000 140000
Existing FTL(36W)
Proposed LED(20W)
Ru
pe
es
Cost Comparision
0 5000
10000 15000 20000 25000 30000 35000 40000 45000
Existing FTL(36W)
Proposed LED(20W)
KW
H\Y
EAR
GREEN 9 Project Outcome Report –16EE10
II-61
Total Power Consumption in KW = (100× 3) /1000 = 0.3KW
Duration of use per year= 24×365 = 8760 hr/yr
Total power consumption in KWH = 0.3 × 8760= 2628 KWH
Wattage of proposed star rated fan = 50 W , Total no of star rated fan = 3
Total Power Consumption in KW = 50 × 3= 0.150 KW
Duration of use per year= 24×365 = 8760 hr/yr
Total power consumption in KWH = 0.150 × 8760 = 1314 KWH
The difference in energy consumption = 50W
Total energy consumption = (50 × 8760 × 3) / 1000 = 1314 KWH
Saving i.e. difference in energy bill :Cost / Unit @ Rs.7/- (1 unit = 1 KWh) = 7 ×
1314 =Rs- 9198 /-
Cost of the existing fan = 700 /-
Total Cost of existing fan = (700 × 3) = 2100/-
Cost of the proposed star rated fan = 2000/-
Total Cost = 3 × 2000 = 6000/-
The additional expense to the exchequer: = 6000 – 2100 = Rs-3900/-
Pay Back Period: = 3900 / 9198 = approximately 5 months
Fig. 4.26 Control Room Fan Cost Analysis
0 1000 2000 3000 4000 5000 6000 7000
Existing fan(100 W)
Proposed fan (50W)
In R
up
ee
s
GREEN 9 Project Outcome Report –16EE10
II-62
Fig. 4.27 Control Room Fan Energy Consumption
Audit Observation: : Life of FAN is approx 10,000 hours but the life of the
proposed are 5 times more than the FAN i,e 50000 hours. The additional cost
incurred towards the replacement will be paid back well within 5 months span.
0
500
1000
1500
2000
2500
3000
Existing fan(100 W)
Proposed fan (50W)
KW
H\Y
EAR
GREEN 9 Project Outcome Report –16EE10
II-63
5. Design of DC Micro Grid
A microgrid is a localised groping of electricity resources and loads that normally
operates connected to and synchronous with the traditional centralised grid but
can disconnect and function autonoumously as physicall and economic condition
dictates as per the CIGRE states ( Council international des grands reseaux
electriques states) Microgrids are electricity distribution system containing loads
and distributed energy resources ( such as distributed generators storage device ,
or controllable loads) that can be operated in a controlled , coordinated way either
while connected to the main power network.
5.1 Design Calculation of micro grid with PV array and Wind mill:
The total proposed load connected in the control room is:-
Name of equipment Total Rating in KW
LED 4 feet(130 nos of each 20 watt) 2.6
Fan (3 nos of each 50 watt) 0.15
AC (1 AC of 1700 watt) ------
DC Load System 15.11
Charger Load --------
Battery --------
Total Load 18
Table 5.1 Connected load to Microgrid
All loads are operated for24 hours = 18 × 24 = 428.64 KWH\DAY
For one year = 428.64 × 365 = 156453.6KWH\year
Electricity bill @ Rs- 7 per KWH unit per year = 7 × 156453.6 = Rs-1095175.2/-
DC current are measured obtained from manual ferrule.
Actual output power of PV panel = 285 × 0.75
=213.8 WP
Power used at end = Actual power × Combined effi.
GREEN 9 Project Outcome Report –16EE10
II-64
= 213.8 × 0.9 = 192.42 w
Energy produced /panel/day by PV panel = Actual power × sun ray \hr\day
= 192.42 × 6
=15588 Whr\day
No. of PV panel needed = 428000 / 15588
= 28 panels
Actual requirement is 28 panels for 8KW.
Description of each PV array
Watt/panel 285
No. of panel in series 7
No. of panel in parallel 4
Total no. of panels 28
Volts.dc 262
Amps.dc 30
KW .dc 8
Type of PV array Poly-crystalline
No. of cells in each panel 60
Table 5.2 PV Array Description
Each PV array generates 8KW using 28 panels of 285 Watts each , So here we
used 3 numbers of 8KW PV array{8*3=24KW). Hence required numbers of
panels is 28*3=84 panels
Cost of one 285w PV panel = Rs-15000/-
Total cost = 84 × 15000 = Rs-1260000/-
Payback period = 1260000 /1095175.2 = 1.15 years
GREEN 9 Project Outcome Report –16EE10
II-65
Government subsidiary = 30 %
= (1260000 × 30)/100
= Rs-378000/- = 1260000-378000= 882000
Payback period after subsidiary = 882000/1095175.2 = 0.845 years
1. Size of PV array:
Size of the PV panel:-
Length= 77.01 inch
Width =39.06 inch
Time zone - UTC + 05:30, Chennai
Declinator =17.407 degree ; solar altitude =3.47 degree
2. Wind Turbine generator:
All loads are operated for24 hours = 18 × 24 = 428.64 KWH\DAY
For one year = 428.64 × 365 = 156453.6KWH\year
Electricity bill @ Rs- 7 per KWH unit = 7 × 156453.6 = Rs-1095175.2/-
Actual energy consumption = 428.64 × 365 = 156453.6 KWH
Cost of performance = 0.41
Wind speed =10m/s
Density of air = 1.225 kg/m2
Capacity factor = 0.30
No, of hour/year = 8760 hr/year
Power density of wind = 0.5 × 1.225 × 103 = 612.5 w/m
Overall losses = Cp × Trans. Loss × Generation loss= 0.4 × 0.9 × 0.9 = 0.324
Actual power density = 612.5 × 0.325 = 199 w/m2
Actual power density useful = 199 × 8760 =1743240 wh/m2 = 1743.24 kwh/m2
GREEN 9 Project Outcome Report –16EE10
II-66
Rotor size = Total available energy / useful energy density = 156453.6 /1743.24 =
90 m2
Radius of rotor blade
3.14 × R2 = 90
R = (90/3.14)0.5 = 5.3 m
Power rating of turbine = Actual power × area of rotor density= 199 × 90 = 18 KW
Actual power rated of actual turbine rating = Power rating / Capacity factor
= 18 / 0.7 = 26KW
Cost of 1KW wind turbine generator = Rs-23000/-
Total cost of 26KW wind turbine generator = 26 × 23000 = Rs-598000/- = 6 lakhs
Payback period = 600000 / 1065175.2 = 0.56 years
5.2 Description of Micro grid
The Microgrid shown above Consists of PV panels and Wind mills Supplying the
whole load of the system. The designed Microgrid is a DC microgrid here the
supply from EB is taken as an optional which will supply if in case there is an error
in the system. The net supply received is sent to an intelligent block system this
block is used to provide intelligent decision to the system. Here Dc Microgrid is
proposed because the maximum load consumed is by the switch yard which
consumes a net of 15KW of DC supply. Here solar and wind is used as alternative
supply whose installation cost will be around 18.6 lacks which will be reimbursed
against the electricity bill within 3 years. Here EB supply is completely removed
and all loads are connected directly to the PV and turbine.A new DC bus system is
installed where supply from EB and Genset is used as backup source or as
compensating source in case of low output from the alternative sources.
An intelligent block of
system is also discussed in the sytem which can be used to trip the system under
fault condition. Under normal condition if the supply obtained from anyone of the
source is not enough then the intelligent block will compensate the power from
other source.
GREEN 9 Project Outcome Report –16EE10
II-67
Fig 5.1 Proposed microgrid
1. In the proposed scheme taken for discussion in the project , an Direct current
micro grid has been formulated and micro wind turbine , PV panels, DG generator
all incorporated within the micro grid along with the battery set interfacing with
conventional chargers connected with AC source.
2. The purpose will be strong DC source for the protection system in the event of any
black out or brown out happening in the transmission system. The main sources
to be wind mill or solar energy.
3. In this paper, it is taken for discussion that in so called DC micro grid the analysis
of absence of one source after other and also the requirement of burden during
the operation of protection system in every possible aspects.
4. The proposal of operation of DC lighting in the control room from the DC micro grid
also taken for simulation.
GREEN 9 Project Outcome Report –16EE10
II-68
5. In the 400 KV substation control room calculated with 65 twin 4 feet LED tube
lights taken for the simulation . The DC regulator also proposed to be provided for
continuous supply.
6. The wind generator discussed in this paper is a micro one which is designed for
low cut in speed and can be set in to operation even 3 to 4 m/sec velocity of wind
speed onwards.
7. The PV panels erection can be done at the top of the control room. The erection of
wind mill should be away from the normal data transmission system normally
provided on the terrace of the control room. The preventive measures like
overcharging and overvoltage should be incorporated for successful
implementation of the system primly for protection.
5.3 Case study of the proposed micro grid
Here Dc Microgrid is proposed because the maximum load consumed is by
the switch yard which consumes a net of 15KW of DC supply.
Here solar and wind is used as alternative supply whose installation cost
will be around 18.6 lacks which will be reimbursed against the electricity bill
within 3 years.
Here EB supply is completely removed and all loads are connected directly
to the PV and turbine.A new DC bus system is installed where supply from
EB and Genset is used as backup source or as compensating source in
case of low output from the alternative sources.
In sevre case such as heavy rain or flood where it is difficult to obtain
supply from EB , Solar and Wind then a bidirectional structure of supply
from gensate is provided
The Gensate supplies to the same DC bus where input from solar and wind
is provided in continuation with that a seprate bus system is also provided
which directly feeds the main load bus this will be used in case of fault.
GREEN 9 Project Outcome Report –16EE10
II-69
5.4 Analysis of Microgrid system
The proposed Microgrid system is analyswd in ETAP and the report obtained is
explained in the graphical format as shown below
Fig. 5.2 Load flow report without fault in DC system
Fig. 5.3 Load flow report without fault in DC system
The Graph shown above gives the no of buses VS voltage , the voltage obtained
above is from solar and wind which is found to be as per the gives prescribed
value. Here variation is less then the range of +/-2 % which demonstrates that the
proposed model is perfect to take care of connectes load.
221.15 221.2
221.25 221.3
221.35 221.4
221.45 221.5
221.55 221.6
221.65
16 18 21 22 23 24 25 26 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 45 46 47 48 49 50 51 52 53 55 56 57 58
Vo
ltag
e(v
olt
s)
No. of buses
221.15
221.2
221.25
221.3
221.35
221.4
221.45
221.5
221.55
221.6
221.65
60 62 64 66 113 115 117 119 121 123 125 127 129 131 133 135 137 139 141 143 145 150
Vo
ltag
e(v
olt
s)
No. of buses
GREEN 9 Project Outcome Report –16EE10
II-70
Fig 5.4 Load flow report without fault in DC system
Fig. 5.5 Load flow report without fault in DC system
The Graph shown above gives the no of buses VS current , the current obtained
above is from solar and wind which is found to be as per the gives prescribed
value. Here variation is less then the range of +/-2 % which demonstrates that the
proposed model is perfect to take care of connectes load.
5.5 Comparision of Existing DC system with Proposed Micro Grid
System
The proposed system of DC and Existing system of DC is compared for voltage
and current with bus numbers and the complete analysis is as shown below.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
18 21 22 23 24 25 26 28 29 30 31 32 33 34 35 37 38 39 40 41 42 43 45 46 47 48 49 50 51 52 55 56 57 58 60 61
curr
en
t(am
ps)
No. of buses
0
0.2
0.4
0.6
0.8
1
1.2
62 64 66 113 115 117 119 121 123 125 127 129 152 132 134 136 138 140 142 144 146
Cu
rre
nt(
amp
s)
No. of buses
GREEN 9 Project Outcome Report –16EE10
II-71
Fig.5.6 Comparision of Existing and proposed
Fig.5.7 Comparision of Existing and proposed
The graph shown above gives the comparision of voltage between existing and
proposed system in existing system the variation was from 219.5V to 220.5V that
means the net deviation is of +/-0.5V. In the proposed system the variation
obtained from 220.50V to 221.58V So the variation is around +/- 1.5V which is
within the given prescribed value.
Fig.5.8 Comparision of Existing and proposed
217
218
219
220
221
222
16 21 23 25 28 30 32 34 36 38 40 42 45 47 49 51 53 56 58 61
Vo
ltag
e(v
olt
s)
No. of buses
Existing
Proposed
217
218
219
220
221
222
62 64 66 113 115 117 119 121 123 125 127 129 131 133 135 137 139 141 143 145 150
Vo
ltag
e(v
olt
s)
No. of buses
Existing
Proposed
0
0.2
0.4
0.6
0.8
1
1.2
18 22 24 26 29 31 33 35 38 40 42 45 47 49 51 55 57 60
Cu
rre
nt(
amp
s)
No. of buses
Existing
Proposed
GREEN 9 Project Outcome Report –16EE10
II-72
Fig.5.9 Comparision of Existing and proposed
The graph shown above gives the variation of current in existing and proposed
system. The variation Obtained is found to be within the prescribed value.The
variation obtained is +/- 0.2amps.
Fig.5.10 EB per year and Cost of PV array
The graph shown above gives cost comparision of Proposed PV with the existing
EB power supply. Here it can be seen that after government subsidiary the cost is
around 8.82L which is less then EB electricity bill/year.
0
0.2
0.4
0.6
0.8
1
1.2
62 64 66 113 115 117 119 121 123 125 127 129 152 132 134 136 138 141 143 145
Cu
rre
nt(
amp
s)
No. of buses
Existing
Proposed
0
200000
400000
600000
800000
1000000
1200000
1400000
Electricity bill per year Cost of PV array After Government subsidary
Pri
ce in
ru
pe
es
GREEN 9 Project Outcome Report –16EE10
II-73
Fig.5.11 Difference in energy consumption
The above system shows the difference in energy consumotion of power grid and
proposed system. There is a net saving of 3.5KWh/year.
Fig.5.12 EB per year and cost of WTG
The graph shown above gives cost comparision of Proposed WTG with the
existing EB power supply. Here it can be seen that after government subsidiary
the cost is around 5.82L which is less then EB electricity bill/year.
16.5
17
17.5
18
18.5
19
19.5
20
20.5
Existing Power grid Proposed PV array MG
Un
it c
on
sum
pti
on
KW
/ye
ar
0
200000
400000
600000
800000
1000000
1200000
EB per year Cost of WTG
Pri
ce in
ru
pe
es
GREEN 9 Project Outcome Report –16EE10
II-74
Fig.5.13 Difference in energy consumption
The above system shows the difference in energy consumotion of power grid and
proposed system. There is a net saving of 2.5KWh/year.
16.5
17
17.5
18
18.5
19
19.5
20
20.5
Existing Power Grid Proposed Wind MG
Un
it C
osu
mp
tio
n in
KW
/ye
ar
GREEN 9 Project Outcome Report –16EE10
II-75
6. CONCLUSION
A famous quote “Energy saved is Energy generated”[10]. This shows that
apart from increasing the generation capacity with investment, one must go for the
energy audit to save the electricity at lower cost[9]. As the economic rises day by
day so the use power also rises which puts a tremendous stress on power utilities
to increase the generation of the energy so as to meet the demand .Taking this in
mind an initiative “VISION 10MW” was started with the aim of saving 10MW of
energy within 10 years and as a pilot project a case study in University office was
initiated and in next step the detailed analysis of substation was carried out along
with the establishment of new microgrid system.
In stage one of the work electrical
energy audit of the lightning system was done and new methodologies were
proposed. Here Instead of recommending all lamps to be replaced by the present
modern technology energy star rated LED lamps By these replacement, the
luminous level will be more over same with lesser involvement of cost. The system
of LED can also provided with presently available electronic control gear. Here
without investmentt includes reducing the wastage by reducing thw wastage a net
of 726 Units can be saved annually. With replacement of FTL with new modern
LED lamp a net saving of 1290 units can be saved annually. The installation cost
can be recovered within 2.5 years.
In second stage of work illumination
level analysis of of the switch yard was carried out. Here rearrangement is
proposed with the existing luminaries fixtures to achieve optimal Lux level and with
investment includes converting existing fixtures to high performance LED lamps
which gives an anual saving of 63918 units the investment can be recovered
within 4.56 years.
In third stage of work a new
system of DC Micro Grid is proposed. The DC Micro Grid proposed consists of
various alternative energy sources ranging from PV panels to Wind turbine. The
installation cost involved for setting up of MG is around 18.58 L which can be
recope against the electricity bill within 2 years.
GREEN 9 Project Outcome Report –16EE10
II-76
REFERENCES
[1] Report on “World Energy Scenarios” Composing energy futures to 2050
published in “World Energy Council 2013” pp - 1
[2] Report on “CENTRAL STATISTICS OFFICE NATIONAL STATISTICAL
ORGANISATION” published by “MINISTRY OF STATISTICS AND PROGRAMME
IMPLEMENTATION GOVERNMENT OF INDIA” website- www.mospi.gov.in pp-1
[3] Report on “Statistics at a Glance, 2012-13, Tamil Nadu Generation and
Distribution Corporation Limited, Chennai – 2” published by Tamil Nadu
Government. Pp-1 - 2
[4] Online Report published on website
“https://en.wikipedia.org/wiki/Energy_audit” by BEE pp-2
[5] Paper published on “DC Microgrids Scoping Study—Estimate of Technical and
Economic Benefits” published on March 2015 New Mexico 87185 and Livermore,
California 94550. SAND2009-135192. Pp 2-3
[6] Paper published on “http://www.innovativejournal.in/index.php” Ajcsit paper
published by M. SINGH during may 2014. Pp3-4
[7] Report published by A.K.Ahuja © Energy Audit Team, IIT Roorkee during
august 2013.pp 4-5
[8] Paper published by S. Pramanik on electrical energy audit of institutional area
in “International Journal of Advanced Research in Electrical, Electronics and
Instrumentation Engineering “ during September 2008. Pp-5-6
[9] Report published on energy audit in “Code of practice of interior illumination” –
IS 3646-1 (1992) in feb 2009. Pp 6
[10] Workbook published by Washington State University on “Energy Program via
Energy Audit “ on website “http://www.gogle.com/searchjournal.aspx”. During May
-2015. Pp-6-7
[11] V.Salehi, A.Mazloomzadeh, and O.Mohammed, “Development and
Implementation of a Phasor Measurement Unit for Real-Time Monitoring, Control
GREEN 9 Project Outcome Report –16EE10
II-77
and Protection of Power Systems,” in IEEE Power Engg. Society .General
Meeting, Jul.24-29,2011. Pp-10-11
[12] International Journal of Engineering Research and Technology. ISSN 0974-
3154 Volume 6, Number 5 (2013), pp. 619-624 © International Research
Publication House http://www.irphouse.com. Pp - 11
[13] International Journal of Engineering and Applied Sciences
© 2012 EAAS & ARF. All rights reserved, www.eaas-journal.org. Pp- 11-12
[14] Paper published on website “http://www.ijifr.com/searchjournal.aspx” Volume -
1 Issue -4, December 2013. ID: IJIFR/V1/E4/035. Pp-15
[15] Zhenyu Huang and Jeff Dagle, SynchroPhasor Measurements: System
Architecture and Performance Evaluation in Supporting Wide-Area Applications.
PA:IEEE Power Engineering Society General Meeting 2008 .Pp-48-49
[16] “ETAP Microgrid Integrated Power System Simulation, Planning, Protection &
RealTime Microgrid Master Controller” book published on “http:// www.
Etap.com” Pp- 62
[17] Paper Published on “Smart DC Micro-grid for Effective Utilization of Solar
Energy” in “International Journal of Scientific & Engineering Research Volume 3,
Issue 12, December-2012 ISSN 2229-5518. Pp-67
GREEN 9 Project Outcome Report –16EE10
II-78
PAPER PUBLICATION DETAILS
“Illumination Level Study and Energy Assessment Analysis at University Office” at 2nd International Conference on Intelligent Computing and Applications (ICICA 2015) February 5 – 6th, 2016 ( SPRINGER)