Dr. A.Hussain DESIGN AND IMPLEMENTATION OF A MICROCONTROLLER-BASED MULTIFUNCTION RELAY Electrical Engineering Department Team Advisors A.Al-Garni Dr. M.Abido S.BOSAEED N.AL-NAFJAN M.Al-Ahmadi First , the current comes form the motor to the current transformer to reduce it with a ratio of 5/1000 so the conditioning circuit can handle it. Second, the conditioning circuit takes input signal from a current transformer, then come out with a proper signal for a Microcontroller-Based Multifunction Relay, involves: filtering, shifting and regulating. Then, the microcontroller reads the signal coming from the conditioning circuit and convert it to digital to make a decision if there is an overcurrent in the line. Finally, if overcurrent is detected, a signal form the microcontroller is set to trigger the circuit breaker and shut down the motor. Why? Protection relay is a device which by means of measuring power system quantities (currents and voltages) and processing them through its internal logic which has the capacity to control the operation of a circuit breaker. The internal logic allows the relay to initiate a tripping sequence when irregular conditions arise within the power system. Configuration Electrical Power System protection is required for protection of both user and the system equipment itself from fault, hence electrical power system is not allowed to operate without any protection devices installed. Power System fault is defined as undesirable condition that occurs in the power system. These undesirable conditions such as short circuit, current leakage, ground short, over current and over voltage. In summary, the needs of power protection are: User/Personnel Safety Equipment Safety How it works Circuit Breaker Motor C.T Microcontroller Source + 220 V - Current Transformer C.C Conditioning Circuit Protection Relay Results 0 5 10 15 20 25 30 35 40 45 0 20 40 60 80 Time Three Phase RMS Value 0 5 10 15 20 25 30 35 40 45 0 0.2 0.4 0.6 0.8 1 Time Trip Trip signal in MATLAB simulation Fault message in microcontroller LCD During this semester, the project goals have been achieved. Starting by surveys about relays, current transformers and circuit breakers. Also MATLAB has been used to test the algorithm that used to detect the RMS value from the Four-Sample Method. After that, designing the conditioning circuit and the power circuit has started as well programming the microcontroller. In the end, connection of the conditioning circuit, the power circuit and the microcontroller have been done for final testing in the lab and completion of the project. Conclusion START I<I PICKUP ? RETURN Y=Y+G(I).dt OVERCURRENT DETECTOR=1 Y=0 Y Y N N Y>1 ? Decision Maker This is the procedure followed to make a decision if there is an over current in the microcontroller This flow diagram can be understood by assuming the tripping time , T0 to be a function F(I): T 0 = F(I) G(I)= 1/F(I) G(Ij) . T0 = 1 T0= n . dT LAB Work Motor Connection Conditioning Circuit, Relays and Current Transformers C.T Relay Microcontroller

Upload: others

Post on 22-May-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Design and implementation of a microcontroller-based relay

Dr. A.Hussain

DESIGN AND IMPLEMENTATION OF A MICROCONTROLLER-BASED MULTIFUNCTION

RELAY

Electrical

Engineering

Department

Team Advisors A.Al-Garni Dr. M.Abido S.BOSAEED N.AL-NAFJAN M.Al-Ahmadi

First , the current comes form the motor to the current

transformer to reduce it with a ratio of 5/1000 so the

conditioning circuit can handle it.

Second, the conditioning circuit takes input signal from a

current transformer, then come out with a proper signal for a

Microcontroller-Based Multifunction Relay, involves: filtering,

shifting and regulating.

Then, the microcontroller reads the signal coming from the

conditioning circuit and convert it to digital to make a

decision if there is an overcurrent in the line.

Finally, if overcurrent is detected, a signal form the

microcontroller is set to trigger the circuit breaker and shut

down the motor.

Why?

Protection relay is a device which by means of measuring

power system quantities (currents and voltages) and

processing them through its internal logic which has the

capacity to control the operation of a circuit breaker. The

internal logic allows the relay to initiate a tripping sequence

when irregular conditions arise within the power system.

Configuration

Electrical Power System protection is required for protection of

both user and the system equipment itself from fault, hence

electrical power system is not allowed to operate without any

protection devices installed. Power System fault is defined as

undesirable condition that occurs in the power system. These

undesirable conditions such as short circuit, current leakage,

ground short, over current and over voltage.

In summary, the needs of power protection are:

User/Personnel Safety

Equipment Safety

How it works

Circuit Breaker

Motor

C.T

Microcontroller

Source +

220 V

-

Current Transformer C.C

Conditioning Circuit

Protection Relay

Results

0 5 10 15 20 25 30 35 40 450

20

40

60

80

Time

Thre

e P

hase R

MS

Valu

e

0 5 10 15 20 25 30 35 40 450

0.2

0.4

0.6

0.8

1

Time

Trip

Trip signal in MATLAB

simulation

Fault message in microcontroller

LCD

During this semester, the project goals have been achieved.

Starting by surveys about relays, current transformers and circuit

breakers. Also MATLAB has been used to test the algorithm that

used to detect the RMS value from the Four-Sample Method.

After that, designing the conditioning circuit and the power circuit

has started as well programming the microcontroller. In the end,

connection of the conditioning circuit, the power circuit and the

microcontroller have been done for final testing in the lab and

completion of the project.

Conclusion

START

I<IPICKUP?

RETURN

Y=Y+G(I).dt

OVERCURRENT

DETECTOR=1

Y=0

Y

Y

N

N Y>1 ?

Decision Maker

This is the procedure followed to make a decision if

there is an over current in the microcontroller

This flow diagram can

be understood by

assuming the tripping

time , T0 to be a

function F(I):

T0 = F(I)

G(I)= 1/F(I)

G(Ij) . T0 = 1

T0= n . dT

LAB Work

Motor Connection

Conditioning Circuit, Relays and Current Transformers

C.T

Relay

Microcontroller