design a protection system of 220-33 kv ramah grid station

51
Design a protection System of 220/33kV Grid Station United Arab Emirates University College of Engineering Saif Mohammed AL Aryani 200304349 Ahmed Soruor AL Shamisi 200304148 Mohammed AL Manei 200204241 Madyan Ahmed Assirri 200337000 Project Advisor: Dr. Ahmed Gaouda Examination Committee: Dr. Muftah El-Naas Dr. Imad Barhumi Dr. Hassan Nikkhajoei Graduation Project Code: EEMI-9

Upload: anand-kumar

Post on 14-Apr-2015

102 views

Category:

Documents


8 download

DESCRIPTION

prrtcn

TRANSCRIPT

Page 1: Design a Protection System of 220-33 Kv Ramah Grid Station

Design a protection System of 220/33kV Grid Station

United Arab Emirates UniversityCollege of Engineering

Saif Mohammed AL Aryani 200304349Ahmed Soruor AL Shamisi 200304148Mohammed AL Manei 200204241Madyan Ahmed Assirri 200337000

Project Advisor: Dr. Ahmed Gaouda

Examination Committee:Dr. Muftah El-Naas Dr. Imad Barhumi Dr. Hassan Nikkhajoei

Graduation Project Code: EEMI-9

Page 2: Design a Protection System of 220-33 Kv Ramah Grid Station

• Introduction• Protection System• Single Line Diagram of Ramah Grid• Busbar Protection• Transformer Protection• Distance Protection• Implementation• Conclusion & Recommendations

OUTLINE

Page 3: Design a Protection System of 220-33 Kv Ramah Grid Station

• The graduation Project of our group is proposed from TRANSCO to UAE University.

• Transco Company is building now new Grid Substation in RAMAH to provide the enough power to that area.

Introduction

Page 4: Design a Protection System of 220-33 Kv Ramah Grid Station

• Substation is the place where the power is stepped up or down.

• Substation contains:• Feeder• Transformer• Busbar• Bus coupler.• Other Protection equipment

• Ramah Grid Substation power is stepped down by transformers from 220 KV to 33 KV.

Introduction

Page 5: Design a Protection System of 220-33 Kv Ramah Grid Station

Design a complete Protection System of 220 KV / 33KV Grid Station using ADWEA standard.

Comparing the design results with existing systems and simulated results.

Implantations of the simulated results.

Introduction Objectives

Page 6: Design a Protection System of 220-33 Kv Ramah Grid Station

Building a grid substation is very expensive.

The protection of power system is the first thing that designer thinks about to safe the money and efforts.

Any small mistake in the protection system can cause large damages and the designers will be blamed.

The three goals of this protection are:

Safety of HumansSafety of EquipmentSafety of Supply

Introduction Environmental Effects

Page 7: Design a Protection System of 220-33 Kv Ramah Grid Station

• Complete arrangement of protection equipments and other devices.

• Protection Equipments:– Current & Voltage Transformers ( CT & VT ). – Circuit Breaker (CB)– Relay

Protection System

Page 8: Design a Protection System of 220-33 Kv Ramah Grid Station

• Relays are like human brain• A device that measures the (Current or voltage) of the system.

.

Protection System Relay

Page 9: Design a Protection System of 220-33 Kv Ramah Grid Station

• CT steps down the current to small value to be Suitable to the relay.

Protection System CT

Page 10: Design a Protection System of 220-33 Kv Ramah Grid Station

• A switch like a (fuse) that used to interrupt the current flow. It opens on Relay Command.

Protection System Circuit Breaker

Page 11: Design a Protection System of 220-33 Kv Ramah Grid Station

Reasons for Zones:Amount of power carriedPhysical Structure.Function.

Protection System Protection Zones

Page 12: Design a Protection System of 220-33 Kv Ramah Grid Station

Single Line Diagram of RAMAH Grid

Page 13: Design a Protection System of 220-33 Kv Ramah Grid Station
Page 14: Design a Protection System of 220-33 Kv Ramah Grid Station

Incoming2Incoming1 Outgiong1 Outgiong2 Bus coupler

The busbar is a bar of copper or aluminum built in switchgear

Bus-Bar Protection Single Line Diagram

Page 15: Design a Protection System of 220-33 Kv Ramah Grid Station

In Fault Condition

All Circuit Breaker will open

Bus-Bar Protection

Page 16: Design a Protection System of 220-33 Kv Ramah Grid Station

Bus-Bar Protection Simulated System in Normal Condition

Page 17: Design a Protection System of 220-33 Kv Ramah Grid Station

Bus-Bar Protection Simulated System in Fault Condition

Page 18: Design a Protection System of 220-33 Kv Ramah Grid Station

I1

I2

D +

F

+

I3

I4

D +

F

+G

+

I5

D +

F

-Ix > IocIx 1

2

A

B

Ctrl

Ctrl = 10

TripSignal

CB1

0

| X |

Delay

T

Incoming Current

Outgoing Current

Differential Current

Tripping CBs

Bus-Bar Protection Logics of Busbar Protection

Page 19: Design a Protection System of 220-33 Kv Ramah Grid Station

Fault Starts after 1 s

CBs opens after 0.1 s from fault

Bus-Bar Protection Logics of Busbar Protection

Page 20: Design a Protection System of 220-33 Kv Ramah Grid Station

Simulation

Bus-Bar Protection

Page 21: Design a Protection System of 220-33 Kv Ramah Grid Station

The electrical protection of the Transformer comprises of the following:

Differential Current Protection.

REF (Restricted Earth Fault).

AVR (Automatic Voltage Regulator).

Over current protection.

Transformer Protection

Page 22: Design a Protection System of 220-33 Kv Ramah Grid Station

•Id = I1 – I2 ≠ 0

Transformer Protection Differential Current Protection

Page 23: Design a Protection System of 220-33 Kv Ramah Grid Station

Transformer zone

Transformer Protection Simulated System

Page 24: Design a Protection System of 220-33 Kv Ramah Grid Station

Transformer Protection Logics of Differential Protection

Page 25: Design a Protection System of 220-33 Kv Ramah Grid Station

In the event of failure or non- availability of the primary protection some other means of ensuring that the fault is isolated must be provided. These secondary systems are referred to as ‘back-up protection.

Back-up protection

Back- Upprotection

Transformer Protection Over Current Protection

Page 26: Design a Protection System of 220-33 Kv Ramah Grid Station

Back- Upprotection B1

Transformer Protection Logics of Transformer Protection

Page 27: Design a Protection System of 220-33 Kv Ramah Grid Station

Advanced Graph Frame

1.280 1.300 1.320 1.340 1.360 1.380 1.400 ... ... ...

-1.5k

-1.0k

-0.5k

0.0

0.5k

1.0k

1.5k

y

CT1_a CT1_a

-0.60

-0.40

-0.20

0.00

0.20

0.40

0.60

y

CT1_aa CT2_ab Id IP=0.155

CT

2C

T1

#1

#3

#2

50 [MW] 50 [MVAR]

1.0

e-0

06

1.0

e-0

06

1.0

e-0

06

1.0

e-0

06

T3

B1

CB

2C

B1

Transformer Protection System in Normal Condition

Page 28: Design a Protection System of 220-33 Kv Ramah Grid Station

Advanced Graph Frame

0.960 0.980 1.000 1.020 1.040 1.060 1.080 1.100 1.120 1.140 1.160 ... ... ...

-150.00k

-100.00k

-50.00k

0.00

50.00k

100.00k

150.00k

y

CT1_a CT1_a

-300

-200

-100

0

100

200

300

y

Id IP=0.155

Advanced Graph Frame

0.980 1.000 1.020 1.040 1.060 1.080 1.100 1.120 1.140 1.160 1.180 ... ... ...

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

y

SF " 0.15 "

CT

2

CB

1

CT

1

#1

#3

#2

50 [MW] 50 [MVAR]

1.0

e-0

06

1.0

e-0

06

CB

2

1.0

e-0

06

1.0

e-0

06

B1

T3

Transformer Protection System in differential fault condition

Page 29: Design a Protection System of 220-33 Kv Ramah Grid Station

Advanced Graph Frame

0.0 1.0 2.0 3.0 4.0 5.0 ... ... ...

-150.00k

-100.00k

-50.00k

0.00

50.00k

100.00k

150.00k

y

CT1_a CT1_a

-300

-200

-100

0

100

200

300

y

CT1_aa CT2_ab Id IP=0.155

Advanced Graph Frame

0.0 1.0 2.0 3.0 4.0 5.0 ... ... ...

-0.40

-0.20

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

y

Trip signal ( CB1 CB 2)

CT

2

CB

1

CT

1

#1

#3

#2

50 [MW] 50 [MVAR]

1.0

e-0

06

1.0

e-0

06

CB

2

1.0

e-0

06

1.0

e-0

06

B1

T3

Transformer Protection System in differential fault condition

Page 30: Design a Protection System of 220-33 Kv Ramah Grid Station

0.4 s

CT

2

CB

1

CT

1

#1

#3

#2

50 [MW] 50 [MVAR]

1.0

e-0

06

1.0

e-0

06

1.0

e-0

06

1.0

e-0

06

B1

T3

CB

2

Transformer Protection System in over current fault condition

Page 31: Design a Protection System of 220-33 Kv Ramah Grid Station

Simulation

Transformer Protection

Page 32: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance protection is used mainly for overhead lines protection.

The main function of distance relays is to make high and fast protection system for the overhead lines.

Distance Protection

Page 33: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance Protection Single Line Diagram of outgoing OHLs

Page 34: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance =30 Km

Zone1 covers 80% (24 km)

Zone2 covers 100% (30 km)

Distance Protection RAMAH –ALANJAH Overhead Line

Page 35: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance Protection is applied to this line

It is divided in two zones:

– Zone-1 Covers 80 % of the Line (24 Km)– Zone-2 covers 100 % of the Line (30 Km)

Distance Protection

Page 36: Design a Protection System of 220-33 Kv Ramah Grid Station

The distance is depending on the impedance of the line.

• The voltage is calculated through VT.• The Current is calculated through CT.

)(

)()(

Icurrent

VvoltageZimedance

Distance Protection

Page 37: Design a Protection System of 220-33 Kv Ramah Grid Station

• If fault happens in A:• CB1 will operate after time t1

• If fault happens in B:• CB2 will operate.• if it is not operated. CB1 will operate after time t1+0.3s

• If fault happens in C:• CB1 and CB2 will not operate

A BcCB1 CB2

Distance Protection

Page 38: Design a Protection System of 220-33 Kv Ramah Grid Station

The impedance of the Line is :

The calculated impedance by Relay:

Z < 80 % Zline

Fault happens in zone-1

80% Zline < Z < Zline

Fault happens in Zone-2

Z> Zline

No Fault happens in Line

Distance Protection

Page 39: Design a Protection System of 220-33 Kv Ramah Grid Station

•If calculated impedance in Zone-1:

Relay will trip after t1

•If calculated impedance in Zone-2:

Relay will trip after t1 + 0.3 s

•If calculated impedance outside zones:

Relay will block

Distance Protection

Page 40: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance Protection Simulated System in Normal Condition

Page 41: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance Protection Fault occurs in Zone-1

Page 42: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance Protection Fault occurs in Zone-1

Page 43: Design a Protection System of 220-33 Kv Ramah Grid Station

Distance Protection Fault occurs in Zone-1 & CB2 doesn’t operate

Page 44: Design a Protection System of 220-33 Kv Ramah Grid Station

vam vbm vcm

vap

vbp

vcp

X1

X2

X3

Ph1

Ph2

Ph3

Mag1 Mag2 Mag3

(7)

(7)

(7)

(7) (7) (7)

dc1 dc2 dc3

F F T

F = 50.0 [Hz]

1

v

2

3

1 2 3

12

3

|A|

/_A

|B|

/_B

|C|

/_C

|P|

/_P

|N|

/_N

|Z|

/_Z

ABC

+-0

vam

vbm

vcm

vap

vbp

vcp vzp

vnp

vpp

vzm

vnm

vpm

Va

Voltage Magnitude

Phase

Voltages and phases for sequences

Frequency Scanner Sequence Filter

Distance Protection Logics of Distance Protection

Page 45: Design a Protection System of 220-33 Kv Ramah Grid Station

iap

ibp

icp

iam

X1

X2

X3

Ph1

Ph2

Ph3

Mag1 Mag2 Mag3

(7)

(7)

(7)

(7) (7) (7)

dc1 dc2 dc3

F F T

F = 50.0 [Hz]

1

i

2

3

1ibm

2icm

3

12

3

iam

ibm

icm

iap

ibp

icp izp

inp

ipp

izm

inm

ipm|A|

/_A

|B|

/_B

|C|

/_C

|P|

/_P

|N|

/_N

|Z|

/_Z

ABC

+-0

Ia

Current and phases for sequences

Current Magnitude

Phase

Frequency Scanner Sequence Filter

Distance Protection Logics of Distance Protection

Page 46: Design a Protection System of 220-33 Kv Ramah Grid Station

TripSignal

O1

B1

iam

iap

izp

izm

vam

vap

VM

IM

I0M

VP

IP

I0P

R

XVa

Ia+ kI

0

Ra

Xa

R

X

21RMS

RMSOpen

BreakerB1

S

XX2

X2

D +

F

+Ix > IocIx

TripSignal

B2

OpenBreaker

B2

SDelay

T

Delay

T

0De

lay TV & I parameters

R-X Plane

Define the Zone of fault

Trip CB1

Trip CB2

Distance Protection Logics of Distance Protection

Page 47: Design a Protection System of 220-33 Kv Ramah Grid Station

CB opens after 0.3 s from fault

Fault Starts after 1 s

Distance Protection

Page 48: Design a Protection System of 220-33 Kv Ramah Grid Station

Simulation

Distance Protection

Page 49: Design a Protection System of 220-33 Kv Ramah Grid Station

Implementation

Page 50: Design a Protection System of 220-33 Kv Ramah Grid Station

• In this GP; there were long steps of calculations and simulation using PSCAD program which allows the designer to simulate the large values of power in details.

• After doing all these steps; the simulated results will be sent to Transco Company to be as a real setting for the protection system..

Conclusion

Page 51: Design a Protection System of 220-33 Kv Ramah Grid Station

Thanks for Good Listening

Any Questions?