december 2, 2008 campus lighting retrofits university of illinois at urbana-champaign in conjunction...
TRANSCRIPT
December 2, 2008
Campus Lighting Retrofits University of Illinois
at Urbana-Champaignin conjunction with ICECF
Eva Sweeney, P.E., LC, LEED© AP
ISTC Sustainability SeriesTuesday, December 2, 2008
12/2/2008
UIUC Sustainability Goals
• Energy reduction policy – 10% in 3 years• Signatory to American College and University Presidents
Climate Commitment• Required to develop plan to reach carbon neutrality
• New construction must be LEED Silver Certified at a minimum.• Business Instructional Facility• Lincoln Hall Renovation• Huff Hall Addition• NCSA Petascale Computing• Illinois Fire Service Institute
• Several aspects of sustainability in Campus Strategic Plan• Need for comprehensive sustainability policy
12/2/2008
Urbana Campus Energy Costs
FY 2003: $26,612,000FY 2004: $35,684,000 (+34%)FY 2005: $52,282,000 (+47%)FY 2006: $70,778,000 (+35%)FY2007: $58,830,000 (-17%)FY2008: $78,449,000 (+33%)FY2009?
12/2/2008
Big Ten Energy Usage, 2007
0.00
5.00
10.00
15.00
20.00
25.00
30.00
Institution
kw
h p
er
GS
F
kwh/GSF
12/2/2008
Other Motivating Factors
• Large number of existing facilities--700 locations
• Utility fund shortfalls• $400M deferred maintenance backlog• Need for an “across the board” fix• Need “boots on the ground” quickly• Limited staff resources• Cost!
12/2/2008
Why Lighting?
• Easy and Non-invasive
• Upgrades increase quality and productivity
• Highly visible to building occupants
• Improved reliability & maintainability
• 2-5 year payback
• Low-hanging fruit
12/2/2008
Environmental Impact
12/2/2008
Illinois Clean EnergyCommunity Foundation
• http://www.illinoiscleanenergy.org
• Four projects currently at UIUC•Biomass (Miscanthus) Power Plant
($825K)
•Wind Turbine ($2.0M)
•Campus Lighting Retrofits ($1.18M)
•Business Instructional Facility ($75K)
12/2/2008
ICECF Energy Efficient Lighting Upgrade Grant
Program• Incentive based on demand reduction
(60¢/watt)
• Applicable to new or retrofit fixtures
• Fluorescent, HID, LED exit signs, controls
• Must apply & be pre-approved
• Reimbursement after project completion
12/2/2008
DCEO Public Sector Electric Efficiency Program
• http://www.illinoisenergy.org• Incentives based on Prescriptive methods
•Many specific upgrades & replacements•High-Performance T8: $7.00/lamp
• Custom incentive option available (7¢/kWH)• Must apply & be pre-approved• Reimbursement after project completion
12/2/2008
UIUC Campus Lighting Retrofit data
• 44 buildings representing ~7M sq.ft.
• Highest energy users
• Linear fluorescent T12 to High-Performance T8
• Estimated total cost $4.2 million
• Project budget $2.8 million
• ICECF commitment $1.18 million
12/2/2008
UIUC Campus Lighting Retrofit data
• 80,233 light fixtures
• 2.9 MW reduction
• ~$900,000 annual cost savings (12 hr/day)
• 12.8 million kWh saved per year
12/2/2008
12/2/2008
Building Audit Spreadsheet
12/2/2008
Technical Considerations
• Lamp: lumens, color, life, warranty
• Ballast: input watts, ballast factor, instant start vs. rapid start
• “High Performance” T8 system ≥ 90 LPW
• Luminaire: Lens, Reflector, Environment•4-lamp to 2-lamp reflector kits save 75%
• Controls
Other Lighting Upgrade Programs
• New construction / LEED
• Remodeling
• CFL replacement as routine maintenance
• LED Exit signs (DCEO)
• Targeted applications & individual projects• Gymnasiums
• Pools / Ice Rink
• Warehouses
12/2/2008
Lighting Upgrades: A Guide for Facility Managers (Damon Wood, 2004)
12/2/2008
Typical Efficacy for Various Light Sources
12/2/2008
Color Temperature
Color Spectrum - Sunlight
12/2/2008
Color Spectrum
12/2/2008
Color Spectrum
12/2/2008
12/2/2008
Fluorescent Lamp Data
Lamp Manufacturer Part #Initial Lumens
Mean Lumens Watts
Life @ 3hr/start CRI
Philips T12 "Cool White" F34/CW/RS/EW/ALTO 2650 2300 34 20000 62
Philips Universal (standard T8) F32T8/TL835/ALTO 2950 2800 32 20,000 85Philips Plus (long life) F32T8/TL835/PLUS/ALTO 2950 2800 32 30,000 85Philips Advantage F32T8/ADV835/ALTO 3100 2950 32 30,000 85Philips Energy Advantage F32T8/ADV835/XEW/LL/ALTO 25 2400 2280 25 24,000 85Philips Energy Advantage F32T8/ADV835/EW/LL/ALTO 30 2850 2700 30 24,000 85Sylvania Octron FO32/835 XPS ECO 3100 2945 32 30,000 85
12/2/2008
Lamp Lumen Maintenance
12/2/2008
Ballast Data
12/2/2008
Execution Method
• No A/E needed
• In-house audits & inventories
• Direct materials purchase--no contractor markup
• Labor-only contract hire (specialty firms)
• Multiple crews, one per building
• Staff electricians where practical
Side Benefits
• Improved quality of light (CRI)
• Eliminate magnetic ballast flicker
• Improved lumen maintenance (quantity)
• Occupants report very positive response
• Remove PCB-containing and high-mercury materials
• Less trash and waste than new fixture purchase
• Lamp/ballast warranty & reduced maintenance needs
12/2/2008
Lessons Learned (so far…)
• Consider sensitive areas & need for shift work
• Contact department staff prior to start date
• Have a recycling plan before you start!
• Identify a secure lay-down area for materials
• Labor costs on per-fixture basis
• Keep room-by-room “as built” records
12/2/2008
Triple Bottom Line
12/2/2008
Discussion
11/18/2008
Eva Sweeney, P.E., LC, LEED© APUIUC Facilities & Services Engineering
[email protected](217) 333-2271
http://www.fs.uiuc.edu/http://www.energymanagement.uiuc.edu/
Thank you!