dcs thyristor power converters for dc drive...

50
DCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description DCS 600 MultiDrive

Upload: others

Post on 01-Apr-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F i

DCS Thyristor Power Convertersfor DC Drive Systems

25 to 5150 A

System DescriptionDCS 600 MultiDrive

Page 2: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F ii

List of contents

II F SYSTEM DESCRIPTION1 DCS 600 MultiDrive - the power converter II F 1-1

2 DCS 600 MultiDrive components overview II F 2-12.1 Environmental conditions .............................................. II F 2-32.2 DCS 600 power converter modules .............................. II F 2-42.3 DCS 600 overload withstand capability ........................ II F 2-72.4 Field Supply .................................................................. II F 2-92.5 Options for power converter modules ......................... II F 2-11

In-/output signals ....................................................... II F 2-12Serial interfacesOperation by the panel .............................................. II F 2-13Panel (control and display panel) .............................. II F 2-14Operation by the PC .................................................. II F 2-15Drive control ............................................................... II F 2-15

2.6 Options ........................................................................ II F 2-17Line reactors for armature (DCS600) andfield (DCF600) supply ................................................ II F 2-17Aspects of fusing for armature circuits and fieldsupplies of DC drives .............................................. ...II F 2-20Fuses and fuse holders for armature and field supplyII F 2-22Transformer for field supply ....................................... II F 2-22Line reactor ................................................................ II F 2-23Electronic system / fan supply ................................... II F 2-23Auxiliary transformer .................................................. II F 2-23Earth fault monitor ..................................................... II F 2-23EMC filters ................................................................. II F 2-24

3 Overview of Software (Vers. 15.xxx) ......... II F 3-13.1 Basic structure of DCS 600 MultiDrive .......................... II F 3-13.2 Control modes ............................................................... II F 3-13.3 Start, Stop and Fault reactions ..................................... II F 3-23.5 Torque control ............................................................... II F 3-43.4 Speed control ................................................................ II F 3-43.5 Torque control ............................................................... II F 3-43.6 HMI (Human Machine Interface) ................................... II F 3-43.7 Torque generation ......................................................... II F 3-53.7 Software diagrams ........................................................ II F 3-6

4 Connection examples ................................. II F 4-1

How the DCS 600 MultiDrive Documentation Sys-tem works

This is to give you an overview how the system ofinformation for DCS 600 MultiDrive converters isbuilt up. The shaded part indicates the volume withinthe total system you are just now working with. Inaddition you see all other available documents for thesame system.

System Description DCA 600 Enclosed

3ADW000121

Volume II F1

Oper. InstructionsDCS(F) 600 3ADW000080

Volume IV F

SW DescriptionDCS(F) 6003ADW000076

Volume V F

Technical Data3ADW000165

Volume III

System Description DCS(F) 6003ADW000072

Volume II F

Installation Man.DCA 600 ... 3ADW000091

Volume VI F1

Service ManualDCS 500/600

3ADW000093

Volume VI A

12-Pulse ManualDCS 600

3ADW000115

Volume II F2

Page 3: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 1-1

1 DCS 600 MultiDrive - the power converter

state-of-the-art technology flexible design user-friendly

Unit rangeThe range comprises of 4 sizes, C1, C2, A5 and C4.We can deliver both modules and standard cabinets.

Basic hardware components Thyristor bridge(s) (from size A5 with installed

branch fuses) Temperature monitor for the thyristor bridge(s) Fan Integrated power supply for the electronics Microprocessor board AMC (Application Motor Control) board with DSP

(Digital Signal Processor) for drive control andDDCS link

Additional components integrated in the module Field supply converter

– uncontrolled full wave diode bridge, 6A or– half-controlled diode/thyristor bridge, 16A

Control panel

Moreover, the accessories listed below can be usedto individually customize the drive package in ac-cordance with the application intended External field supply units 12-Pulse parallel configuration 12-Pulse serial/sequential configuration Additional I/O boards (isolated) Interface modules for various communication pro-

tocols EMC filter PC programs

C1 - Module Cabinet

ABB’s long years of experience with variable-speed DCdrives, plus use of the latest state-of-the-art technolo-gies, have been combined to create this product. TheDCS 600 MultiDrive contains a complete programwith ratings between 25 A and 5150 A as a powerconverter module (in 12-pulse parallel configurationappr. 10,000 A). It is suitable for all commonly usedthree-phase systems.

All our products are CE approved.

The DC drives factory of ABB Automation Products,Drives Division in Lampertheim has implemented andmaintains a quality management system according toDIN EN ISO 9001 and an environmental manage-ment system according to DIN EN ISO 14001.

DCS 600 MultiDrives are approved according to UL(Underwriters Laboratory).

They also comply with the relevant EMC standards forAustralia and New Zealand and are C-Tick marked.

DCS 600 MultiDrive converter units are suitable forstandard and system drive applications.

Appropriate PC programs ensure that the drives areengineered for user-friendly operator control.

Page 4: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 1-2

Design and commissioning toolsDriveWindowPC program for commissioning and maintenance un-der Windows® for:

Parameter settingFault detectionTrendingData loggerFault loggerLocal operation (Drives Panel)

CDP 312 removable control and display panel withplain text display for:

Parameter settingFault detectionParameter uploading and downloadingLocal operation

Monitoring functionsSelf-testNon-volatile fault memoryMotor protectionIn the event of:• Speed feedback error• Overtemperature• Overload• Overspeed• Zero speed• Armature overcurrent• Armature ripple• Armature overvoltage• Minimum field current• Field overcurrentPower converter protection• Overtemperature• Software errors (watchdog function)Incorrect supply protection• Mains overvoltage and undervoltage• Auxiliary undervoltage• Incorrect mains phase sequence (only inform.)

Basic functionsAll units are provided with the same digital controlboards and software. The DCS 600 MultiDrive flexi-bility allows the user to configure functions of the driveeasily, suitable for different applications. Functions ofthe DCS 600 MultiDrive are normally activated byparameters.

The basic software includes the following options:• Processing the speed reference with a speed ramp

generator (S-ramp capability, accel/decel ramp)• Processing the speed feedback• Speed controller• Torque reference processing• Current controller• Field weakening• Automatic/manual field reversal• Autotuning of current controller• Speed monitor• Drive control logic• Remote/local operation• Emergency stop• Electronic circuits are not sensitive to line phase

sequence• Electrical and mechanical brake control• Motor overload supervision• Dual field• Programmable analogue outputs• Field supply• Master follower via fibre optics

Controlling and operatingvia I/O's

analogue and digital inputs and outputs

via bus systemse.g.: Profibus, Modbus Plus, AF100 etc.

via HMI (Human Machine Interface)Outputs:

AlarmsFaultsStatus informationParameter settingLocal control of the drive

Page 5: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-1

2 DCS 600 MultiDrive Components Overview

The DCS 600 MultiDrive power converter range is asystem of components and complete standard cabinets tocontrol DC motors. It consists of individual components,based on the DCS 600 power converter modules. This

chapter provides a brief description of the DCS 600MultiDrive components available for matching the drivewith the conditions on site.

This overview has been designed to help you to familiarize yourselfwith the system; its main components are shown in the diagram above.The system’s heart is the DCS 600 converter module.

Fig. 2/1: DCS 600 MultiDrive Components overview for armature converters

DCS 600 Armature converter

DCF 601 / 602

X1

X2

X17

AM

C-D

C

X11

X33

DS

P

V260

CH

3

CH

0

CH

2

CO

N 2

P X16

7 3

8 4

X14

72IO

E 1

Mo

nit

ori

ng

LE

D b

ar

NL

MD

Pan

elC

DP

312

L1K1

T2

Q1

F2

F3

M

T

T

83

85

PC

+D

rive

Win

do

w+

FC

B

DCF 503A / 504A

PO

W 1

PIN

1x

PIN

51

IOB

2x

IOB

3

PS

5311P

IN 2

0xB

T3

F1

K5

K3

6

90V

1

000V

-ND

PA

-02

-ND

PC

-12

-NIS

A-0

3 (I

SA

)

FE

X 1

FE

X 2

M

PIN

41

PIN

41

L3N

DB

U95

(PC

MC

IA)

X12

X13X37

Mul

tiD

rive

sock

etN

DP

I

A92

T90

DC

S 6.

.-....

-.1-1

5....

. (..

.. -.1

-18.

....)

X10 X

16(2

4V)

X37

X12

X13

X12

X13

X12

X13

X2

X3

X4,

5X

6X

4X

3X

3X

5X

2X

1

X2

X17

X1

U1

V1

W1

C1

D1

X1

X1

X1

X1

X14

X14

U1

V1

U1

V1

W1

C1

D1

C1

D1

X16

X2

X99

X1

CO

N x

- sh

ort

des

igna

tio

n o

f co

mpo

nen

ts

anal

og

ue in

pu

t / o

utp

ut

alte

rnat

ive

EM

C f

ilter

Ear

th-f

ault

mo

nito

r

to th

e P

LC

opt

ical

fib

red

igit

al in

put

/ o

utp

ut

Leg

end

7.1

- d

etai

led

desc

riptio

n se

e ch

apte

r 7.1

PL

C-A

dvan

t c

on

tro

l

- o

ptio

nal

I/O

- M

aste

r/ F

ollo

wer

Fie

ld B

us

Ad

apte

rM

od

ule

Nxx

x

to other drives

Rev

D o

r la

ter

12-P

uls

e lin

k

Pow

ersu

pply Three-phase field supply

* co

nnec

tion

see

Tech

nica

l dat

a c

hapt

er 5

*

Page 6: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-2

The DCF 600 field supply converter range is a system ofcomponents and complete standard cabinets to controlthe field supply of DC motors. It consists of individualcomponents, based on the DCS 600 power convertermodules. The difference to the armature converter is only

the modified power interface board SDCS-PIN-1x (ifused) and the reduced range of current and voltage types(see table 2.2/2). The function for field supply will beselected by software parameters.Note: Armature and field converters use the same firmware.

This overview has been designed to help you to familiarize yourselfwith the system; its main components are shown in the diagram above.The system’s heart is the DCF 600 field supply converter module.

Fig. 2/2: DCS 600 MultiDrive Components overview for field supply converters

DCF 600 Field supply converter

AM

C-D

C

DS

P

CH

3

CH

0

CH

2

CO

N 2

PM

on

ito

rin

gL

ED

ba

rN

LM

D

Pan

elC

DP

312

Mul

tiD

rive

sock

etN

DP

I

L1K3

T2

Q1

F2

M

83

85

PC

+D

rive

Win

do

w+

FC

B

DCS 600

PO

W 1

PIN

1x

DCF 506

IOB

2x

IOB

3

F1

K5

6

90V

6

00V

M

DC

F 6.

.-....

-.1-1

5....

.

ND

BU

95

-ND

PA

-02

-ND

PC

-12

-NIS

A-0

3 (I

SA

)

(PC

MC

IA)

72IO

E 1

7 3

8 4

CZD-0x

PIN

20x

B

V260

X10 X

16(2

4V)

X37

X12

X13

X12

X13

X1 X3

X4,

5X

6X

4X

3X

2X

1

X2

X17

X1

U1

V1

W1

C1

D1

C1

D1

X11

X12

X16

X1

X2

X17

X11

X33

X16

X14

X12

X13X

37

X4

X99

CO

N 2

- sh

ort

des

igna

tio

n o

f co

mpo

nen

ts

anal

og

ue in

pu

t / o

utp

ut

alte

rnat

ive

EM

C f

ilter

Ear

th-f

ault

mo

nito

r

to th

e P

LC

optic

al fi

bre

dig

ital

inp

ut /

out

pu

t

Leg

end

7.1

-

deta

iled

desc

riptio

n se

e ch

apte

r 7.1

PL

C-A

dvan

t c

on

tro

l

- o

ptio

nal

I/O

- M

aste

r/ F

ollo

wer

Fie

ld B

us

Ad

apte

rM

od

ule

Nxx

x

to other drives

mod

ified

Rev

D o

r la

ter

to a

dig

ital i

nput

of D

CF

600

Page 7: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-3

2.1 Environmental Conditions

System connectionVoltage, 3-phase: 230 to 1000 V according to IEC 38Voltage deviation: ±10% continuous; ±15% short-time *Rated frequency: 50 Hz or 60 HzStatic frequency deviation: 50 Hz ±2 %; 60 Hz ±2 %Dynamic: frequency range: 50 Hz: ±5 Hz; 60 Hz: ± 5 Hz

df/dt: 17 % / s

* = 0.5 to 30 cycles.Please note: Special consideration must be taken for voltage deviationin regenerative mode.

Degree of protectionConverter Module and accessories(line chokes, fuse holder,field supply unit, etc.): IP 00Enclosed converters: IP 20/21/31/41

Paint finishConverter module: NCS 170 4 Y015REnclosed converter: light grey RAL 7035

Fig. 2.1/1: Effect of the site elevation above sea levelon the converter’s load capacity.

Current reduction to (%)

Fig. 2.1/2: Effect of the ambient temperature on theconverter module load capacity.

Current reduction to (%)

Environmental limit valuesPermissible ambient temp. withrated I DC: 0 to +40°CRelative humidity (at 5...+40°C): 5 to 95%, no condensationRelative humidity (at 0...+5°C): 5 to 50%, no condensationAmbient temp. converter module: +40°C to 55°C; s. Fig. 2.1/2Change of the ambient temp.: < 0.5°C / minuteStorage temperature: -40 to +55°CTransport temperature: -40 to +70°CPollution degree: Grade 2

Site elevation:<1000 m above M.S.L.: 100%, without current reduction>1000 m above M.S.L.: with current reduct., see Fig. 2.1/1

Vibration converter module: 0.5 g, 5 Hz to 55 Hz

Sound pressure as module in the ABB standardlevel (1 m distance): cabinet

Size LP LP

C1 59 dBA 57 dBAC2 71 dBA 64 dBAA5 75 dBA 73 dBAC4 83 dBA 76 dBA

Regulatory ComplianceThe converter module and enclosed converter components are designed for use inindustrial environments. In EEA countries, the components fulfil the requirements of theEU directives, see table below.

North American StandardsIn North America the system componentsfulfil the requirements of the table below.

70

80

90

100

110

30 35 40 45 50 55°C

Note:Only for Converter Modules

50

60

70

80

90

100

1000 2000 3000 4000 5000 m

European Union Directive Manufacturer's AssuranceHarmonized Standards

Converter module Enclosed converter

Machinery Directive89/392/EEC93/68/EEC

Declaration ofIncorporation

EN 60204-1[IEC 204-1]

EN 60204-1[IEC 204-1]

Low Voltage Directive73/23/EEC93/68/EEC

Declaration of Conformity

EN 60146-1-1[IEC 146-1-1]EN 50178 [IEC --]see additionalIEC 664

EN 60204-1[IEC 204-1] EN 60439-1 [IEC 439-1]

EMC Directive89/336/EEC93/68/EEC

Declaration of ConformityProvided that all installationinstructions concerningcable selection, cabling andEMC filters or dedicatedtransformer are followed.

EN 61800-3 ➀[IEC 1800-3]

EN 61800-3 ➀[IEC 1800-3]

were limits are under considerationEN 50081-2 / EN 50082-2 has been supplied

➀ in accordance with3ADW 000 032

➀ in accordance with3ADW 000 032/3ADW 000 091

The Technical Construction File to which thisdeclaration relates has been assessed byReport and Certificate from ABB EMCCertification AB being the competent Bodyaccording to EMC Directive.

rewoProfytefaStnempiuqEnoisrevnoc

≤≤≤≤≤ V006

eludomrofdradnatSC805LU rofelbaliava;

seludomretrevnocdleiflanretnignidulcni(,1Csezis)stinureticxe

;2Crofnoitaraperprednu

4Cdna5Asezis

lortnoclairtsudnIlairtsudni:tnempiuqE

stcudorp ≤≤≤≤≤ V006

5941.oN.2.22CASC ;,1Csezisrofelbaliava

;4C,2Crofnoitaraperprednu

5Aezis

Page 8: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-4

2.2 DCS 600 Power Converter Modules

The power converter modules are modular in construc-tion. They are based on the housing, which contains thepower section with the RC snubber circuit. There are 4different sizes, depending on current and voltage. Allunits are forced cooled.

The power section is controlled by the unit’s electronicsystem, which is identical for the entire product range.Parts of the unit’s electronic system can be installed inthe unit, depending on the particular application in-

volved, e.g. a field supply for the motor, or an interfaceboard to connect the converter to an overriding controlsystem. A control/display panel is available for theoperator. It can be mounted to the power convertermodule or installed in the cabinet's door by means of amounting kit.

Accessories such as external fuses, line reactors and thelike are available, for putting together a complete drivesystem.

Reference variablesThe voltage characteristics are shownin Table 2.2/1. The DC voltage char-acteristics have been calculated usingthe following assumptions:

• UVN

= rated mains voltage, 3-phase• Voltage tolerance ±10 %• Internal voltage drop approx. 1%• If a deviation or a voltage drop has

to be taken into consideration incompliance with IEC and VDEstandards, the output voltage orthe output current must be re-duced by the actual factor accord-ing to table 2.2/1.

➀ in case of a 2-Q converter, which is used in regenerative mode, 4-Q voltagevalues have to be used.

Table 2.2/1: DCS 600 max. DC voltages achievable with a given mains voltage.

Mains DC voltage Ideal DC Recommended voltage (max. Motor voltage) voltage DCS 600

Uv Ud without load Voltage class2-Q ➀ 4-Q Udi0 y=

230 265 240 310 4380 440 395 510 4400 465 415 540 4415 480 430 560 4440 510 455 590 5460 530 480 620 5480 555 500 640 5500 580 520 670 5525 610 545 700 6575 670 600 770 6600 700 625 810 6660 765 685 890 7690 800 720 930 7790 915 820 1060 81000 1160 1040 1350 91190 1380 1235 1590 1

Page 9: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-5

Converter type y → y=4 (400 V) y=5 (500 V) y=6 (600 V) y=7 (690 V)

x=1 → 2-Q IDC [A] IAC [A] P [kW] P [kW] P [kW] P [kW]

x=2 → 4-Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q 4Q 2Q

DCS60x-0025-y1 25 25 20 20 10 12 13 15DCS60x-0050-y1 50 50 41 41 21 23 26 29DCS60x-0050-61 50 50 41 41 31 35DCS60x-0075-y1 75 75 61 61 31 35 39 44DCS60x-0100-y1 100 100 82 82 42 47 52 58DCS60x-0110-61 110 100 90 82 69 70DCS60x-0140-y1 140 125 114 102 58 58 73 73

DCS60x-0200-y1 200 180 163 147 83 84 104 104DCS60x-0250-y1 250 225 204 184 104 105 130 131DCS60x-0270-61 270 245 220 200 169 172DCS60x-0350-y1 350 315 286 257 145 146 182 183DCS60x-0450-y1 450 405 367 330 187 188 234 235 281 284DCS60x-0520-y1 520 470 424 384 216 219 270 273DCS60x-0680-y1 680 610 555 500 282 284 354 354DCS60x-0820-y1 820 740 670 605 340 344 426 429DCS60x-1000-y1 1000 900 820 738 415 418 520 522

DCS60x-0903-y1 900 900 734 734 563 630 648 720DCS60x-1203-y1 1200 1200 979 979 498 558 624 696DCS60x-1503-y1 1500 1500 1224 1224 623 698 780 870 938 1050 1080 1200DCS60x-2003-y1 2000 2000 1632 1632 830 930 1040 1160 1400 1600

DCF60x-0025-y1 25 25 20 20 10 12 13 15DCF60x-0050-y1 50 50 41 41 21 23 26 29DCF60x-0075-y1 75 75 61 61 31 35 39 44DCF60x-0100-y1 100 100 82 82 42 47 52 58DCF60x-0200-y1 200 180 163 147 83 84 104 104DCF60x-0350-y1 350 315 286 257 145 146 182 183DCF60x-0450-y1 450 405 367 330 187 188 234 235DCF60x-0520-y1 520 470 424 384 216 219 270 273

Table 2.2/2: Table of DCS 600 / DCF 600 units - construction types C1, C2, A5

Converter type y → y=4 (400 V) y=5 (500 V) y=6 (600 V) y=7 (690 V) y=8 (790 V) y=9 (1000V) y=1 (1190V)

➀IDC [A] IAC [A] P [kW] P [kW] P [kW] P [kW] P [kW] P [kW] P [kW]

2-Q convertersDCS601-2050-y1 2050 1673 1435 1640 1876 2378DCS601-2500-y1 2500 2040 1163 1450 1750 2000DCS601-2650-y1 2650 2162 3074 3658DCS601-3200-y1 3200 2611 2928 3712 4417DCS601-3300-y1 3300 2693 1535 1914 2310 2640DCS601-4000-y1 4000 3264 1860 2320 2800 3200 3660 4640 5520DCS601-4750-y1 4750 3876 3325 3800 4346DCS601-5150-y1 5150 4202 2395 2987

4-Q convertersDCS602-2050-y1 2050 1673 1281 1476 1681 2132DCS602-2500-y1 2500 2040 1038 1300 1563 1800DCS602-2650-y1 2650 2162 2756 3280DCS602-3200-y1 3200 2611 2624 3328 3960DCS602-3300-y1 3300 2693 1370 1716 2063 2376DCS602-4000-y1 4000 3264 1660 2080 2500 2880 3280 4160 4950DCS602-4750-y1 4750 3876 2969 3420 3895DCS602-5150-y1 5150 4202 2137 2678

➀ These converters are equipped with additional components. More information on request

Table 2.2/3: Table of DCS 600 units - construction type C4

Higher currents up to 15,000 A are achieved by paralleling converters. More information on request.

Page 10: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-6

Construction type C2

Construction type C1

Converter type ➂ Dimensions Weight Clearances Construct. Power loss Fan Semiconductor H x W x D top/bottom/side type at 500V connection Fuses

[mm] [kg] [mm] PV [kW]

DCS60x-0025-y1 420x273x195 7.1 150x100x5 C1 < 0.2 230 V/1 ph externalDCS60x-0050-y1 420x273x195 7.2 150x100x5 C1 < 0.2 230 V/1 ph externalDCS60x-0050-61 420x273x195 7.6 150x100x5 C1 - 230 V/1 ph externalDCS60x-0075-y1 420x273x195 7.6 150x100x5 C1 < 0.3 230 V/1 ph externalDCS60x-0100-y1 469x273x228 11.5 250x150x5 C1 < 0.5 230 V/1 ph externalDCS60x-0110-61 469x273x228 11.5 250x150x5 C1 - 230 V/1 ph externalDCS60x-0140-y1 469x273x228 11.5 250x150x5 C1 < 0.6 230 V/1 ph external

DCS60x-0200-y1 505x273x361 22.3 250x150x5 C2 < 0.8 230 V/1 ph externalDCS60x-0250-y1 505x273x361 22.3 250x150x5 C2 < 1.0 230 V/1 ph externalDCS60x-0270-61 505x273x361 22.8 250x150x5 C2 - 230 V/1 ph externalDCS60x-0350-y1 505x273x361 22.8 250x150x5 C2 < 1.3 230 V/1 ph externalDCS60x-0450-y1 505x273x361 28.9 250x150x10 C2 < 1.5 230 V/1 ph externalDCS60x-0520-y1 505x273x361 28.9 250x150x10 C2 < 1.8 230 V/1 ph externalDCS60x-0680-y1 652x273x384 42 250x150x10 C2b < 1.6 230 V/1 ph externalDCS60x-0820-y1 652x273x384 42 250x150x10 C2b < 2.0 230 V/1 ph externalDCS60x-1000-y1 652x273x384 42 250x150x10 C2b < 2.5 230 V/1 ph external

DCS60x-0903-y1 1050x510x410 110 300x100x20 A5 - 230 V/1-ph internalDCS60x-1203-y1 1050x510x410 110 300x100x20 A5 < 5.2 230 V/1-ph internalDCS60x-1503-y1 1050x510x410 110 300x100x20 A5 < 5.5 230 V/1-ph internalDCS60x-2003-y1 1050x510x410 110 300x100x20 A5 < 6.6 230 V/1-ph internal

DCS60x-2050-y1 2330x820x624 ➀ ➁ 350 C4 - 400/690 V/3-ph➃ internalDCS60x-2500-y1 2330x820x624 ➀ 350 C4 < 12 400/690 V/3-ph➃ internalDCS60x-2650-y1 2330x820x624 ➀ ➁ 350 C4 - 400/690 V/3-ph➃ internalDCS60x-3200-y1 2330x820x624 ➀ ➁ 350 C4 - 400/690 V/3-ph➃ internalDCS60x-3300-y1 2330x820x624 ➀ 350 C4 < 15 400/690 V/3-ph➃ internalDCS60x-4000-y1 2330x820x624 ➀ ➁ 350 C4 < 16 400/690 V/3-ph➃ internalDCS60x-4750-y1 2330x820x624 ➀ 350 C4 - 400/690 V/3-ph➃ internalDCS60x-5150-y1 2330x820x624 ➀ 350 C4 < 20 400/690 V/3-ph➃ internal

➀ The dimensions for modules with busbar connection on the right side are 2330x800x624 mm (Busbar connection on the right side is optional)Example for the type designation: connection left DCS60x-2050-y1L; connection right DCS60x-2050-y1R

➁ The depth of 1000 V / 1190 V units is 654 mm➂ x=1 → 2-Q; x=2 → 4-Q; y=4...9/1 → 400...1000 V/1190 V supply voltage➃ Supply voltages up to 400 V in delta connection; 415 V or higher in star connection

Also available as field supply converter DCF60x- (for 500 V units see table 2.2/2). Data are the same as the armature current converter DCS60x

Table 2.2/4: Table of DCS 600 units

Construction type A5

to be installedin cabinet

Construction type C4Left busbar connection ➀

Page 11: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-7

2.3 DCS 600 Overload Capability

To match a drive system as efficiently as possible with the driven machine’sload profile, the armature power converters DCS 600 can be dimensioned by me-ans of the load cycle. Load cycles for driven machines have been defined in theIEC 146 or IEEE specifications.

Unit type IDC I

IDC II

IDC III

IDC IV

contin- 100 % 150 % 100 % 150 % 100 % 200 %uous 15 min 60 s 15 min 120 s 15 min 10 s

400 V / 500 V [A] [A] [A] [A]DCS60x-0025-41/51 25 24 36 23 35 24 48DCS60x-0050-41/51 50 44 66 42 63 40 80DCS60x-0075-41/51 75 60 90 56 84 56 112DCS60x-0100-41/51 100 71 107 69 104 68 136DCS601-0140-41/51 125 94 141 91 137 90 180DCS602-0140-41/51 140 106 159 101 152 101 202DCS601-0200-41/51 180 133 200 111 198 110 220DCS602-0200-41/51 200 149 224 124 219 124 248DCS601-0250-41/51 225 158 237 132 233 130 260DCS602-0250-41/51 250 177 266 147 260 147 294DCS601-0350-41/51 315 240 360 233 350 210 420DCS602-0350-41/51 350 267 401 258 387 233 466DCS601-0450-41/51 405 317 476 306 459 283 566DCS602-0450-41/51 450 352 528 340 510 315 630DCS601-0520-41/51 470 359 539 347 521 321 642DCS602-0520-41/51 520 398 597 385 578 356 712DCS601-0680-41/51 610 490 735 482 732 454 908DCS602-0680-41/51 680 544 816 538 807 492 984DCS601-0820-41/51 740 596 894 578 867 538 1076DCS602-0820-41/51 820 664 996 648 972 598 1196DCS601-1000-41/51 900 700 1050 670 1005 620 1240DCS602-1000-41/51 1000 766 1149 736 1104 675 1350DCS60x-1203-41/51 1200 888 1332 872 1308 764 1528DCS60x-1503-41/51 1500 1200 1800 1156 1734 1104 2208DCS60x-2003-41/51 2000 1479 2219 1421 2132 1361 2722DCS60x-2500-41/51 2500 1830 2745 1740 2610 1725 3450DCS60x-3300-41/51 3300 2416 3624 2300 3450 2277 4554DCS60x-4000-41/51 4000 2977 4466 2855 4283 2795 5590DCS60x-5150-41/51 5150 3800 5700 3669 5504 3733 7466600 V / 690 VDCS60x-0050-61 50 44 66 43 65 40 80DCS601-0110-61 100 79 119 76 114 75 150DCS602-0110-61 110 87 130 83 125 82 165DCS601-0270-61 245 193 290 187 281 169 338DCS602-0270-61 270 213 320 207 311 187 374DCS601-0450-61 405 316 474 306 459 282 564DCS602-0450-61 450 352 528 340 510 313 626DCS60x-0903-61/71 900 684 1026 670 1005 594 1188DCS60x-1503-61/71 1500 1200 1800 1104 1656 1104 2208DCS601-2003-61/71 2000 1479 2219 1421 2132 1361 2722DCS60x-2050-61/71 2050 1502 2253 1426 2139 1484 2968DCS60x-2500-61/71 2500 1830 2745 1740 2610 1725 3450DCS60x-3300-61/71 3300 2416 3624 2300 3450 2277 4554DCS60x-4000-61/71 4000 3036 4554 2900 4350 2950 5900DCV60x-4750-61/71 4750 3734 5601 3608 5412 3700 7400790 VDCS60x-2050-81 2050 1502 2253 1426 2139 1484 2968DCS60x-3200-81 3200 2655 3983 2540 3810 2485 4970DCS60x-4000-81 4000 3036 4554 2889 4334 2933 5866DCS60x-4750-81 4750 3734 5601 3608 5412 3673 73461000 VDCS60x-2050-91 2050 1577 2366 1500 2250 1471 2942DCS60x-2650-91 2650 2000 3000 1900 2850 1922 3844DCS60x-3200-91 3200 2551 3827 2428 3642 2458 4916DCS60x-4000-91 4000 2975 4463 2878 4317 2918 58361190 V

Data on request

x=1 → 2-Q; x=2 → 4-Q

The currents for the DC I to DC IV types of load (see table 2.3/2) for the power converter modulesare listed in the table below.

Table 2.3/1: Power converter module currents during corresponding load cycles.The characteristics are based on an ambient temperature of max. 40°C and an elevation of max. 1000 m.

Page 12: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-8

Load Load for Typical applications Load cycle cycle converter

DC I IDC I continuous (IdN) pumps, fans

DC II IDC II for 15 min and extruders, conveyor belts1,5 * IDC II for 60 s

DC III * IDC III for 15 min and extruders, conveyor belts1,5 * IDC III for 120 s

DC IV * IDC IV for 15 min and2 * IDC IV for 10 s

100%

150% 100%

150% 100%

200% 100%

15 min

15 min

15 min

If the driven machine’s load cycle doesnot correspond to one of the exampleslisted, you can determine the necessarypower converter using the DCSize soft-ware program.

This program can be run under Microsoft ® Windows,and enables you to dimension the motor and the powerconverter, taking types of load (load cycle), ambienttemperature, site elevation, etc. into account. Thedesign result will be presented in tables, charts, and canbe printed out as well.

To simplify the start-up as much as possible, everypower converter can be adjusted to the current requiredby means of parameters.

Fig. 2.3/1: Entry screen of DCSize.

Microsoft is a registered trademark. Windows is a designation of the Microsoft Corporation.

Types of load

* Load cycle is not identical with menu item Duty cycle in DCSize !Table 2.3/2: Definition of the load cycles

Page 13: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-9

2.4 Field Supply

General data

SDCS-FEX-1• Diode bridge.• 6 A rated current.• Internal non adjustable minimum field current

monitor.• Construction and components have been designed

for an insulation voltage of 600 V AC.• Output voltage U

A:

9.0*%100

%100*

TOLUU VA

TOL = tolerance of line voltage in %U

V = Line voltage

• Recommendation:Field voltage ~ 0.9 * U

V

SDCS-FEX-2• Half controlled thyristor/diode bridge (1-Q)• Microprocessor control, with the electronic system

being supplied by the armature converter.• Construction and components have been designed

for an insulation voltage of 600 V AC.• Fast-response excitation is possible with an appro-

priate voltage reserve; de-excitation takes place byfield time constant.

• Output voltage UA:

9.0*%100

%100*

TOLUU VA

TOL = tolerance of line voltage in %U

V = Line voltage

• Recommendation:Field voltage 0.6 to 0.8 * U

V

All field power converters (except for the SDCS-FEX-1) are controlled by the armature converter via a seriallink with a speed of 62.5 kBaud. The link serves toparameterize, control and diagnose the field powerconverter and thus provides an exact control. Moreo-ver, it enables you to control one internal (SDCS-FEX-2) and one external (DCF 503A/4A, DCF 601/2) ortwo external field supply units (2 x DCF 503A/4A,DCF 601/2). The respective software function re-quired is available in every DC power converter.

Field converter types

• Currents from 6 to 520 A.• Minimum field current monitor.• Integrated or external field power converter or in a

completely separate cabinet.• 2-phase or 3-phase model.• Fully digital control (except SDCS-FEX-1).

We recommend integrating an autotransformer in thefield power converter's supply to adjust the AC inputvoltage to the field voltage, to reduce the voltage andcurrent ripple of the field.

Page 14: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-10

DCF 503A• Half controlled thyristor/diode bridge (1-Q).• Microprocessor control with the control electronics

being supplied separately (115...230 V/1-ph).• Construction and components have been designed

for an insulation voltage of 690 V AC.• Output voltage U

A:

9.0*%100

%100*

TOLUU VA

TOL = tolerance of line voltage in %U

V = Line voltage

• Recommendation:Field voltage 0.6 to 0.8 * U

V

DCF 504A• like DCF 503A, but• fully controlled antiparallel thyristor bridges (4-Q).• With this unit fast response excitation / de-excita-

tion and field reversal is possible. For fast responseexcitation an appropriate voltage reserve is neces-sary.In steady-state condition, the fully controlled bridgeruns in half controlled mode to keep the voltageripple as low as possible. With a fast changing fieldcurrent, the bridge runs in fully controlled mode.

DCF 600This field power converter is used mainly for armatureconverters with rated currents of 2050 to 5150 A. It isa modified armature circuit converter.• Output voltage U

A respectively U

dmax 2-Q :

see table 2.2/1.• Recommendation:

Field voltage 0.5 to 1.1 * UV

• The three-phase field supply converters DCF 600needs a separate active overvoltage protection unitDCF 506 for protecting the power part against toohigh voltages.The overvoltage protection unit DCF 506 is suitablefor 2-Q converters DCF 601 and for 4-Q convertersDCF 602.

auxiliary supply (115...230V) if necessary via matching trans-former; external fuse; Dimensions HxWxD: 370x125x342 [mm]

DCF506-140-51,shown without cover

DCF601/602

Assignment Field supply converter to Overvol-tage protection unit

Field supply converter Overvoltage Protectionfor motor fields

DCF60x-0025-y1 ➀ ... DCF506-0140-51DCF60x-0100-y1 ➀

DCF60x-0200-y1 ➀DCF60x-0350-y1 ➀ ... DCF506-0520-51DCF60x-0520-y1 ➀

➀y = 400...500 V

DCF503A/4A

Unit type Output Supply Installation Remarkscurrent IDC ➀ voltage site

[A] [V]

SDCS-FEX-1-0006 0.02...6 110V -15%...500V/1-ph +10% internal external fuse, 6 A ⇒ IFrated

SDCS-FEX-2-0016 0.3...16 110V -15%...500V/1-ph +10% internal ext. fuse, reactor; for C1: 0.3 ... 8 A ➀, not to be used for C4 modules!

DCF 503A-0050 0.3...50 110V -15%...500V/1-ph +10% externalDCF 504A-0050 0.3...50 110V -15%...500V/1-ph +10% external

DCF 60x-xxxx-41/51 see table 200V...500V/3-ph external2.2/2

➀Current reduction see also 2.1 Environmental conditions Fig.: 2.1/1 and 2.1/2Table 2.4/1: Data field converter units

are based on the hardware of the DCS 600 and additionalhardware components (DCF 506); auxiliary supply (115/230 V)

Page 15: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-11

In-/output signalsaddition to this an extension of I/O´s by SDCS-IOE 1is possible.

Fig. 2.5/1: I/O´s via SDCS-CON-2Analogue I/O´s: standardDigital I/O´s: not isolatedEncoder input: not isolated

Fig. 2.5/2: I/O´s via SDCS-CON-2 and SDCS-IOB-2Analogue I/O´s: standarddigital I/O´s: all isolated by means of

optocoupler/relay; the signalstatus is indicated by LED

Fig. 2.5/3: I/O´s via SDCS-CON-2 and SDCS-IOB-3Analogue I/O´s: more input capacitydigital I/O´s: not isolatedencoder input: isolatedcurrent source for: PT100/PTC element

Fig. 2.5/4: I/O´s via SDCS-IOB-2 and SDCS-IOB-3Analogue I/O´s: more input capacitydigital I/O´s: all isolated by means of

optocoupler/relay; the signalstatus is indicated by LED

current source for: PT100/PTC element

The converter can be connected in 4 different ways toa control unit via analogue/digital links. Only one ofthe four choices can be used at the same time. In

X3: X4: X5: X6: X7:

X2: X1:

X17:

SDCS-CON-2

1 2

X3: X4: X5:

X2: X1:

X17:

SDCS-CON-2

X3: X1:

SDCS-IOB-2

1

4

X1: X2:

SDCS-IOB-3

X6: X7:

X2:

X17:

X1:

3

2

SDCS-CON-2

X2:

SDCS-IOB-3

X2:

X17:

SDCS-CON-2

X1:

SDCS-IOB-2

X1:

X1: X3:

3 4

2.5 Options for DCS 600 MultiDrive converter modules

Page 16: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-12

Description of I/O signals SDCS-CON-2

Mechanical system integrated in control board

TerminalsScrew type terminals for finely stranded wires up to 2.5 mm2

Functionality 1 tacho input

Resolution: 12 bit + sign; differential input; common mode range ±20 V3 ranges from 8...30...90...270 VDC with nmax

4 analogue inputsRange -10...0...+10 V, 4...20 mA, 0...20 mAAll as differential inputs; RE = 200 kΩ; time constant of smoothingcapacitor ≤2 msInput 1: Resolution: 12 bit + sign; common mode range ±20 VInputs 2, 3, 4: Resolution: 11 bit + sign; common mode range ±40 V

2 outputs+10 V, -10 V, IA ≤ 5 mA; sustained short-circuit-proofvoltage supply for reference potentiometer

1 analogue outputbipolar current actual - from power section; decoupledIdN = ±3 V; IA≤ 5 mA, short-circuit-proof

2 analogue outputsRange -10...0...+10 V; IA ≤ 5 mAOutput signal and scaling can be selected by means of softwareResolution: 11 bit + sign

1 pulse generator inputVoltage supply for 5 V/12 V/24 V pulse generators (sustained short-circuit-proof)Output current with 5 V: IA ≤ 0.25 A

12 V: IA ≤ 0.2 A24 V: IA ≤ 0.2 A

Input range: 12 V/24 V: asymmetrical and differential5 V: differential

Pulse generator as 13 mA current source: differentialLine termination (impedance 120Ω), if selectedmax. input frequency ≤300 kHz

Description of I/O signals SDCS-IOB-2x & SDCS-IOB-3

Mechanical system always external, outside the module

TerminalsScrew type terminals for finely stranded wires up to 2.5 mm2

Functionality of SDCS-IOB-3 1 tacho input

Resolution: 12 bit + sign; differential input; common mode range ±20 VRange 8 V- with nmax; if higher tacho voltages are in use tacho adaptationboard PS 5311 is needed.

4 analogue inputsAll as differential inputs; time constant of smoothing capacitor ≤2 msInput 1: Range -10 V...0...+10 V; -20 mA...0...+20 mA; 4... 20 mAunipolar; RE = 200 kΩ/ 500Ω/ 500Ω; Resolution: 12 bit + sign; commonmode range ±20 VInputs 2+3: Range see input 1, in addition -1 V...0...+1 VRE = 200 kΩ/ 500Ω/ 500Ω/ 20kΩ; Resolution: 11 bit + sign; commonmode range with -1 V...0...+1 V range ±10 V, otherwise ±40 VInput 4: Range see input 1RE = 200 kΩ/ 500Ω/ 500Ω; Resolution: 11 bit + sign; common moderange ±40 V

Fault current detection (Earth fault) in combination with analogueinput 4 (sum of phase currents ≠ 0)

2 outputs+10 V, -10 V; IA ≤ 5 mA; sustained short-circuit-proofvoltage supply for reference potentiometer

1 analogue outputBipolar current actual - from power section; decoupledIdN = ±3 V (at gain = 1); IA≤ 5 mA; UAmax = 10 V; gain can be adjusted bymeans of a potentiometer between 0.5 and 5; short-circuit-proof

2 analogue outputsRange -10...0...+10 V; IA ≤ 5 mA; short-circuit-proofOutput signal and scaling can be selected by means of softwareResolution: 11 bit + sign

Current source for PT 100 or PTC elementIA = 5 mA / 1.5 mA

1 pulse generator inputVoltage supply, output current, input range: see SDCS-CON-2Inputs electrically isolated from 0 V (housing) by means of optocouplerand voltage source.

Functionality of SDCS-IOB-2x3 different designs available: SDCS-IOB-21 inputs for 24...48 V DC; RE = 4.7 kΩ SDCS-IOB-22 inputs for 115 V AC; RE = 22 kΩ SDCS-IOB-23 inputs for 230 V AC; RE = 47 kΩ

TerminalsScrew type terminals up to 4 mm2

8 digital inputsThe functions can be selected by means of software.The signal status is indicated by LED.All isolated by means of optocouplers.Input voltage: IOB-21:0...8 V ⇒ "0 signal", 18...60 V ⇒ "1 sig."

IOB-22:0...20 V ⇒ "0 signal", 60...130 V ⇒ "1 sig."IOB-23:0...40 V ⇒ "0 signal", 90...250 V ⇒ "1 sig."

Filter time constant: 10 ms (channels 1...6); 2 ms (channels 7+8)Auxiliary voltage for digital inputs: +48 V DC; ≤ 50 mA; sustained short-circuit-proof; referenced to the unit housing potential.

8 digital outputsThe functions can be selected by means of software.The signal status is indicated by LED.6 of them potential isolated by relay (N.O. contact: AC: ≤250 V/ ≤3 A /DC: ≤24 V/ ≤3 A or ≤115/230 V/ ≤0.3 A), protected by VDR component.2 of them potential isolated by optocoupler, protected by zener diode(open collector) 24 V DC external, IA ≤ 50 mA.

8 digital inputsThe functions can be selected by means of software.Input voltage: 0...8 V ⇒ "0 signal", 16...60 V ⇒ "1 signal"Time constant of smoothing capacitor: 10 msRE = 15 kΩThe signal refers to the unit housing potential.Auxiliary voltage for digital inputs: +48 V DC, ≤ 50 mA, sustained short-circuit-proof

7+1 digital outputsThe function can be selected by means of software.7 outputs: relay driver with free-wheeling diode, total current limitation≤ 160 mA; short-circuit-proof.1 relay output - on power board SDCS-POW-1 (N.O. contact:AC: ≤250 V/ ≤3 A / DC: ≤24 V/ ≤3 A or ≤115/230 V/ ≤0.3 A) protectedby VDR component.

Page 17: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-13

There are various serial interface options available foroperation, commissioning, diagnosis and controlling.For the control and display panel CDP 312 are serialconnections X33:/X34: on the SDCS-CON-2 availa-ble. Three additional serial interfaces are available onthe SDCS-AMC-DC 2 board.These interfaces use plastic or HCS optical fibres.Channel 3 is used for drive/PC interfacing. Channel 0for fieldbus module interfacing or communication tothe overriding control system. Channel 2 is used forMaster-Follower link or for I/O extension. All threeserial interfaces are independent from each other.

Fig. 2.5/5: Options for serial communication

Different SDCS-AMC 2 boards are available to adaptoptical cables, cable length and serial interfaces. Thedifferent SDCS-AMC 2 boards are equipped with 10or 5 Mbaud optical transmitter and receiver devices.A few basic rules must be considered:• Never connect 5 Mbaud and 10 Mbaud devices.• 5 Mbaud can handle only plastic fibre optic.• 10 Mbaud can handle plastic or HCS cable.• The branching unit NDBU 95 extends the maxi-

mum distance.• The maximum distance and suitable configuration

can be found in the manual Configuration Instruc-tions NDBU 85/95; Doc no.: 3ADW000100.

Fig. 2.5/6: LED Monitoring Display

LED Monitoring DisplayIf the MultiDrive door Mounting kit is used it ispossible to insert up to three LED monitoring displaysfor indicating status as run, ready and fault and aselectable parameter indicator (0...150%) per drive.The display is connected to the SDCS-CON-2 board(X33:/X34:) or to the panel socket NDPI through auniversal Modbus link.

RDY

RUN

FLT 0 50 100 1501

Remark:Fieldbus modules Nxxx(CH0) require theSDCS-AMC-DC Classic 2board - all others (FCI,AC80...) require theSDCS-AMC-DC 2 board.

Fig. 2.5/7: Connection of the LED Monitoring Display

Serial interfaces

Operation by panel

Panel locationThere are different possibilities for mounting the panel:• On the converter module.• With MultiDrive door mounting kit.

X16:

PC

3 m

CDP 312

D20

0C

H 3

TxD

RxD

CH

2Tx

D

RxD

CH

0Tx

D

RxD

D40

0

SDC

S-A

MC

-DC

2SD

CS-

AM

C-D

C C

lass

ic 2

AC800M

FCIAC80

Nxxx Nxxx-01xxxxxxxxADAPTER

BUST ERM INAT ION

ON

OFF

RXD

T XD

PE SHF DG D(N) D(P)X1

X2PE SHF DG D(N) D(P)SH

XM IT

REC

ERRO R

+24V 0V SH

X33:X34:

SDCS-CON-2

electricalconnection

optic

al fi

bre

Power supply

Control Operation

- Master-Follower link- I/O Extension

to the PLC

Interface

X33:/X34:

SDCS-CON-2

RDY

RUN

FLT 0 50 100 1501

NLMD

SDCS-CON-2 NDPI

NLMDRDY

RUN

FLT 0 50 100 1501

CDP 312

X33:/X34:

Page 18: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-14

Panel (control and display panel)The CDP 312 control and display panel communicateswith the power converter via a serial connection inaccordance with the RS 485 standard at a transmissionrate of 9.6 kBaud. It is an option for the converter unit.After completion of commissioning, the panel is notnecessarily required for diagnostic. The basic unit has a7-segment display indicating errors.

Fig. 2.5/8: Function keys and various displays on the removablecontrol and display panel.

ActualSelects the display of feedback values plus the

signal group and the error memory group.

ParametersFor selecting and adjustingall parameters and signals.

FunctionSelects the “functions” operating mode; can be usedto perform special functions such as uploading anddownloading of parameter sets.

Drivefor extensions

Twin arrow keysare used to change the group. In the parameter and

reference presetting modes, you can alter the param-eter value or the reference setting ten times faster by

means of the twin arrow keys than by means of thesingle arrow key.

Arrow keysare used to select parameters within a group. You al-ter the parameter value or the reference setting inthe parameter and reference presetting modes. Inthe feedback signal display mode, you select the lineyou want.

Enteris used in the following modes:Parameter setting: enter new parameter valueActual valuesignal display: enter the current signal selec-

tion modeSignal selection: accept selection and return to

the feedback value signal dis-play mode

Local/Remoteis used to select local (control

panel) or remote control.

ResetFault acknowledge key.

Referenceis used to activate the reference presetting mode.

Startstarts the drive in local mode.

Stopshuts the drive down if you are in local mode.

Onin local mode switches the main contactor on.

Offin local mode switches the main contactor off.

Features• 16 membrane pushbuttons in three function groups• LCD display has four lines with 20 characters each• Language: English• Options for the CDP 312:

– Cable to separate the panel from the converter.– Kit for mounting the panel in the cabinet door.

Status row

Functions to be selected

Display contrastsetting

0 L 0,0 rpm 00UPLOAD <==DOWNLOAD ==>CONTRAST

Groupand name

Subgroupand name

0 L 0,0 rpm 0017 RAMP GENERATOR08 ACCEL 1 20.0 s

Value

0 L 0,0 rpm 00SPEEED ACT 0,0 rpmCONV CUR 0 AU ARM ACT 0 V

ID number of thedriveselected

ControllocationL = local

= remote

Main contactorstatus0 = open1 = closed

Speedreferencerpm

Run status1 = Run0 = Stop

Status row

Actual signalname and value

Cursor showsthe row selected

0 L 0,0 rpm 001 LAST FAULTEmergency stop3212:59:35:56

1 = last fault2 = last-but-one fault99 = last fault

Total time afterswitch-on

HHHH:MM:SS.ss

Name of Fault or alarm

Page 19: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-15

Drive controlComponents required:• Plastic optical fibre for distances up to 15 m.• Field bus module Nxxx-xx• FCI (CI810)• AC80 (PM825)• AC800 M

Functionality:Depends on the used module, interface e.g. to:• PROFIBUS with NPBA-12• MODBUS+ with NMBP-01• AF100 with FCI (CI810)• AC80 (PM825) or• AC800 M• further modules on requestYou will find more detailed information on data ex-change in the specific PLC or fieldbus module docu-mentation.

Operation by PCComponents required:• Plastic optical fibre for distances up to 20 m.• Network up to 200 drives (same as for ACS 600).• HCS optical fibre cable up to 200 m.

See separate manual Configuration InstructionsNDBU 85/95; Doc no.: 3ADW000100.

Functionality:• DriveWindow software package➀ for commission-

ing, diagnosis, maintenance and trouble shooting;structure of connections see Technical Data; Docno.: 3ADW000165.

System requirements/recommendation:• PC (IBM-compatible) with 486 processor or higher

(min. 50 MHz).• 8 MB RAM.• DOS version 5.0 or later.• Windows 3.1, 3.11, Windows95/98; Windows

NT4.0.• VGA monitor.• CD-ROM drive.• PCMCIA or ISA card slot.In addition to the options provided by the CDP 312control and display panel, there are further functionsavailable, and these are described on the following page.

➀ For further information see the specific publications

Page 20: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-16

Operation by PC (continued)

DriveWindowDriveWindow is the most comprehensive commis-sioning and maintenance tool available for ABB prod-ucts. DriveWindow is a PC tool designed for onlinecommissioning and maintenance of ABB products. Itprovides several different displays to effectively andeasily utilize the tool. DriveWindow is able to connectto various target devices through several different typesof communication links.

System Configuration Display

The System Configuration Display provides an over-view of the system as well as the type and status ofeach product connected to the communication link(s).Included in the System Configuration Display arepreviously saved files located on the hard drive of thecomputer. This display is built automatically by theDriveWindow by scanning the communication links tofind the configuration of the system.

Drives Panel Display

The Drives Panel Display is used for controlling theoperation of a selected drive within the system. Youcan control different drives by changing the targetdrive selection. The following commands are avail-able with the Drives Panel:- Start and Stop.- Set speed reference.- Change reference direction.- Reset active fault.- Change to Local/Remote control mode.

Signals and Parameters Display

The Signals and Parameters Display is used forhandling signals and parameters of the target drive.The signal and parameter list is uploaded from thedrive and can be viewed, saved to a file or comparedto another parameter set. Previously set values canbe downloaded to the active drive. You can also setthe parameter values in either offline or online mode.

Monitor Display

The Monitoring Display is used for monitoring graphi-cally the actual values of the target. The followingfunctions are also supported:- Zoom-in and Zoom-out- Scaling the graphs- Setting the sampling interval- Setting the time window- Triggering on specific conditions- Signals from multiple drives can be displayed in

the same view

Data Logger Display

The Data Logger Display provides facilities for view-ing the contents of the data loggers in the drive. Youcan display the data in either graphical or numericalform as well as setting up the data logger triggeringconditions.

Event Logger Display

The contents of the Event Logger can be viewed andcleared by using this display.

Fault Logger Display

The contents of the Fault Logger can be viewed andcleared by using this display.

Application Display

Application programs can be downloaded and de-bugged with this display.

Please note:For more information obout DriveWindow use thehelp function of the program.

Fig. 2.5/9: Display of DriveWindow

Page 21: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-17

2.6 Options

Line reactorsFor armature (DCS 600) and field (DCF600) supply

When power converters are operated with thyristors,the line voltage is short-circuited during commutationfrom one thyristor to the next. This operation causesvoltage dips in the mains. For the connection of a powerconverter system to the mains, following configura-tions can be made:

Configuration AWhen using the power converter, aminimum of 1% impedance is requiredto ensure proper performance of thesnubber circuit. A line reactor can beused to meet this minimum impedancerequirement. The value must thereforenot drop below 1% u

k (relative imped-

ance voltage). It should not exceed 10%u

k, due to considerable voltage drops.

Configuration BIf special requirements have to be met atthe connecting point, different criteriamust be applied for selecting a linereactor. These requirements are mostoften defined as a voltage dip in percentof the nominal supply voltage.The combined impedance of Z

Line and

ZLR

consists of the total series imped-ance of the installation. The ratio be-tween the line impedance and the linereactor impedance determines the volt-

age dip at the connecting point. In such cases linereactors with an impedance of about 4% are used.

VoltagedipZ

Z ZLine

Line LR

*100%

Example:Maximum allowable voltage dip is 20% at the powerconverter's connecting point. Above equation used andchanged to:

Z ZLR Line 4 * (1)

Since the line impedance is seldom known (it can bedetermined by means of a measurement), and theshort-circuit power at the same point is more frequentlyavailable, the line reactor can be calculated by means ofthis value.

Connectingpoint

LineLLine

LLR

Connectingpoint

Line

uk LR ca. 1%

Assumption: The system's short-circuit power at thepower converter’s connecting point is 180 times thepower converter’s rated power.• The system’s relative impedance voltage u

k can be

determined:

uk Line

1180

100% 055%* .

• In accordance with equation (1), the followingapplies for the line reactor:

u Uk LR K Line 4 2 2%* .

• Since the line reactor has to be sized specific to thepower converter, the relative variable U

k must be

converted into an absolute value. For this purpose,use following equation:

uI f L

Uk

dN N LR

N

* * * * *23

3 2

IdN: rated direct current of the converterfN: rated frequency of the systemUN: rated line voltageLLR: line reactor inductance

Configuration CIn the case of high power converteroutputs or high currents, a power con-verter transformer must be used fre-quently to match the voltage. If anautotransformer is used for this pur-pose, a commutating reactor must addi-tionally be used if special conditionsmust be complied with as per configu-ration B. The reason for this is that theu

k of commonly used autotransformers

is generally too small. If you do not havespecial conditions of this kind, you must neverthelesscheck whether the u

k of the autotransformer concerned

is sufficient to satisfy configuration A.

Connectingpoint

Line

LLR

An examination of volume and costs results in thefollowing configuration:Configuration D

If an isolating transformer is used, it isoften possible to comply with certainconnecting conditions per configura-tion B without using an additional linereactor. The condition described in con-figuration A will then likewise be satis-fied, since the u

k is >1 %.

Connectingpoint

Line

Page 22: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-18

With reference to the power converter:

- The line reactors listed in the table (2.6/1)- have been allocated to the converter's nominal

current- are independent of converter's voltage classifica-

tion; at some converter types the same line chokeis used up to 690 V line voltage

- are based on a duty cycle- can be used for DCS 600 as well as for DCF 600

converters- The duty cycle taken into account varies from line

choke to line choke and is between 80% and 100%.If the converter is sized on a duty cycle or is used fora drive running with high load all time like extrudersdo next steps to check the overall selection:- Calculate the I

DCrms based on the duty cycle and the

motor current- Multiply the I

rms of the line choke by 1.2

- In case Irms

is higher than IDCrms

the combination isokay

- In case Irms

is lower than IDCrms

take the line chokeused for the next bigger converter with the samevoltage classification

- If the line choke should be used for a DCF 600converter make sure the nominal field current doesn'texceed the thermal current of the choke. In case thefield current is higher than I

rms of the line choke take

the one used for the next bigger converter with thesame voltage classification

- For units >2000 A or >690 V, we recommend usingone isolating transformer per power converter asseem in configuration D.

Page 23: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-19

Fig. 1 Fig. 2 Fig. 3

DCS Type Line choke Fig. Line choke Design400V-690V type for type for Fig.50/60 Hz configur. A configur. B

DCS60x-0025-41/51 ND01 1 ND401 4DCS60x-0050-41/51 ND02 1 ND402 4DCS60x-0050-61 ND03 1 on request -DCS60x-0075-41/51 ND04 1 ND403 5DCS60x-0100-41/51 ND06 1 ND404 5DCS60x-0110-61 ND05 1 on request -DCS60x-0140-41/51 ND06 1 ND405 5

DCS60x-0200-41/51 ND07 2 ND406 5DCS60x-0250-41/51 ND07 2 ND407 5DCS60x-0270-61 ND08 2 on request -DCS60x-0350-41/51 ND09 2 ND408 5DCS60x-0450-41/51 ND10 2 ND409 5DCS60x-0450-61 ND11 2 on request -DCS60x-0520-41/51 ND10 2 ND410 5DCS60x-0680-41/51 ND12 2 ND411 5DCS601-0820-41/51 ND12 2 ND412 5DCS602-0820-41/51 ND13 3 ND412 5DCS60x-1000-41/51 ND13 3 ND413 5

DCS60x-0903-61/71 ND13 3 ND413 5DCS60x-1203-41/51 ND14 3 on request -DCS60x-1503-41/51/61/71 ND15 3 on request -DCS60x-2003-41/51 ND16 3 on request -DCS601-2003-61/71 ND16 * 3 on request -

* with forced cooling

Line reactors L1

Table 2.6/1: Line reactors (for more information see publication Technical Data)

Fig. 5

Page 24: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-20

General

Unit configurationProtection elements such as fuses or overcurrent tripsare used whenever overcurrents cannot entirely be ruledout. In some configurations, this will entail the follow-ing questions: firstly, at what point should whichprotective element be incorporated? And secondly, inthe event of what faults will the element in questionprovide protection against damage?Possible sources of faults are:

Fig. 2.6/1 Arrangement of the switch off elements in thearmature circuit converter

Faults within the unit electronics• Usually the coverter will limit the current. The

maximum current corresponds to the set currentlimit. If this limitation or one of its componentsfails, then the current will often rise sharply.Output current I >> I

RATED ; Fault: 1

• If one or more false firing pulses are generated, e.g.due to component failures or other factors, then thecurrent will likewise rise sharply.Output current I >> I

RATED ; Fault: 2

• If in 4-Q units thyristors of both bridges becomeconductive, circulating current is the consequence.The cause may be component defects or otherfactors. The current on the three-phase side will risesharply.I

AC >> I

RATED ; Fault: 3

Defective system conditions leading to commutationfailure• In the case of regeneration, the ratio of motor voltage

to line voltage rises above 1.05, which is followed bya situation called “shoot-through”. The current risessubstantially.Output current I >> I

RATED ; Fault: 4

Possible causes:- Network problems (line undervoltage).- Overspeed (load accelerates motor) or control er-

ror.- Field supply generates a field current larger than

IFRATED

or control error in the field weakeningrange.

Faults caused by components• Semiconductor faults can be, that a thyristor no

longer fires (5a), or in that it is permanently conduc-tive (5b). Depending on the system condition (4-Qoperation, regeneration, etc.), these two cases willthen show similar symptoms like cases 3 and 4.Faults: 5a, 5b

• Insulation faults may occur within the cabling of themains supply, the power converter and the motor.These can be subdivided into faults finally resultingin a short-circuit and those leading to an earth fault.- In the event of a short-circuit, the following

generally applies: I >> IRATED

- In the event of an earth fault, depending on wherethe fault has occurred, the current may rangebetween I = I

RATED and I >> I

RATED.

Fault: 6

Fusing of the armature-circuit supplyThe table below shows the fault cases in which semicon-ductor fuses (super fast) can protect the drive systemconsisting of motor and converter. Those cases marked(X) would protect the motor only, and not the convert-er.

Semiconductor fusesFault on the AC side on the DC side

1 X (X)2 X (X)3 X4 X

5a ⇒ 3 X5b ⇒ 4 X

6 X X

Before deciding whether fuses are going to be used onthe DC side, you must first check in which workingpoints the drive is used and how often (proportion oftime compared to the overall duration of operation).

Following general rule applies:- Analogue systems are more sensitive and more vul-

nerable to malfunctions than digital systems.- Digital systems are able to detect critical situations

much easier and have features to prevent the equip-ment from being shut down.

Aspects of fusing for armature circuits and field supplies of DC drives

M..

.

.

.

3

2

2

For field supplysee Fig. 2.6/2

AC supply: public mains / plant's mains

Cabinet

Page 25: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-21

Conclusion for the armature supply

Due to cost saving standard fuses are used instead of themore expensive semiconductor fuses at some applica-tions. Under normal and stable operating conditions,this is understandable and comprehensible, as long ascartain fault scenarios can be ruled out.

In the event of a fault , however, the saving may causevery high consequential costs. Exploding power semi-conductors may not only destroy the power converter,but also cause fires.

Adequate protection against short-circuit and earthfault, as laid down in the EN50178 standard, is possi-ble only with appropriate semiconductor fuses.

Complies with Basic Principles on:1 – Explosion hazard yes2 – Earth fault yes3 – “Hard“ networks yes4 – Spark quenching gap yes5 – Short-circuit yes6 – 2-Q regenerative yes

M M

DCS converter

2-Q non-regen.

Semiconductorfuses

Semiconductorfuses

Semiconductorfuses

4-Q resp.2-Q regenerative

DCS converter

ABB's recommendations

Fusing of the field supply

Basically similar conditions apply to both field supplyand armature circuit supply. Depending on the powerconverter used (diode bridge, half-controlled bridge,fully controlled 4-Q bridge), some of the fault sourcesmay not always be applicable. Due to special systemconditions, such as supply via an autotransformer or anisolating transformer, new protection conditions haveto be added.

In opposite to the armature circuit supply, fuses arenever used on the DC side for the field supply, since afuse trip might under certain circumstances lead togreater damage than the cause tripping the fuse in thefirst place (small, but long lasting overcurrent; fuseageing; contact problems; etc.).

Fault 4 can also occur in the case of field supply units,but will not cause such a rapid and substantial currentrise as encountered with the armature circuit supply.This is due to the significantly higher inductance of thefield winding.

If conditions similar to those for armature circuitsupply are to apply, like for example protection of thefield supply unit and the field winding, then semicon-ductor fuses (super fast F3.1) must be used.

The following configurations are relatively frequentused:

Fig 2.6/2 Configurations for field supplies

F3.3

2

2

2

F3.2

F3.1

RK

F3.1

F3.1

F

R Possible field supply units:- SDCS-FEX-1: uncontrolled diode bridge; Fault: 5a, 6- SDCS-FEX-2: half-controlled bridge, 1-Q; Fault: 1, 5a, 6- DCF 503A: half-controlled bridge, 1-Q; Fault: 1, 5a, 6- DCF 504A: fully controlled bridge, 4-Q; Fault: 1, 3, 4, 6The faults listed here are described under “Aspects of fusing for armature circuitsand field supplies”.

Note: in the case of 1, 4, and 6, the current is limited to relatively small overcurrentsdue to the ohmic content of the field winding, so that the fuses may not trip.

K See section Line reactors

F The F3.2 and F3.3 fuse types serve as line protectors and cannot protect the fieldsupply unit. Only pure HRC fuses or miniature circuit breakers may be used.Semiconductor fuses would be destroyed by the inrush current.

Page 26: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-22

Field converter type for field current Transformer≤≤≤≤≤500 V; 50/60 Hz IF type 50/60 Hz

Uprim ≤≤≤≤≤500 VSDCS-FEX-1 ≤6 A T 3.01SDCS-FEX-2 ≤12 A T 3.02SDCS-FEX-2 ≤16 A T 3.03DCF503A/4A-0050 ≤30 A T 3.04DCF503A/4A-0050 ≤50 A T 3.05

Uprim ≤≤≤≤≤600 VSDCS-FEX-1 ≤6 A T 3.11SDCS-FEX-2 ≤12 A T 3.12SDCS-FEX-2 ≤16 A T 3.13

Uprim ≤≤≤≤≤690 VDCF503A/4A-0050 ≤30 A T 3.14DCF503A/4A-0050 ≤50 A T 3.15

Table 2.6/4: Autotransformer data (details see Technical Data)

Transformer T3 for field supply to match voltage levels

Fig. 2.6/3: T3 autotransfor-mer

Type of converter Manufacturer / Type Fuse holder

DCS60x-0025-41/51 Bussman 170M 1564 OFAX 00 S3LDCS60x-0050-41/51 Bussman 170M 1566 OFAX 00 S3LDCS60x-0050-61 Bussman 170M 1566 OFAX 00 S3LDCS60x-0075-41/51 Bussman 170M 1568 OFAX 00 S3LDCS60x-0100-51 Bussman 170M 3815 OFAX 1 S3DCS60x-0110-61 Bussman 170M 3815 OFAX 1 S3DCS60x-0140-41/51 Bussman 170M 3815 OFAX 1 S3DCS60x-0200-41/51 Bussman 170M 3816 OFAX 1 S3DCS60x-0250-41/51 Bussman 170M 3817 OFAX 1 S3DCS60x-0270-61 Bussman 170M 3819 OFAX 1 S3DCS60x-0350-41/51 Bussman 170M 5810 OFAX 2 S3DCS60x-0450-41/51/61 Bussman 170M 6811 OFAS B 3DCS60x-0520-41/51 Bussman 170M 6811 OFAS B 3DCS60x-0680-41/51 Bussman 170M 6813 OFAS B 3DCS60x-0820-41/51 Bussman 170M 6813 OFAS B 3DCS60x-1000-41/51 Bussman 170M 6166 3x 170H 3006

Table 2.6/2: Fuses and fuse holders (details see Technical Data)

Fuses F1 and fuse holders for armature and 3-phase field supply(DCS 600 - DCF 600)The converter units are subdivided into twogroups:– Unit sizes C1 and C2/C2b with rated

currents up to 1000 A require externalfuses.

– In unit sizes A5 and C4 with rated cur-rents up to 5150 A, the semiconductorfuses are installed internally (no addition-al external semiconductor fuses are need-ed).

The semiconductor fuses for C1 and C2/C2b unit sizes are blade fuses except170M6166. The relevant data is listed intable 2.6/2.The fuses’ type of construction requires spe-cial fuse holders.

The field supply units’ insulation voltage ishigher than the rated operating voltage (seechapter Field supply). This provides the op-tion in systems with more than 500 V tosupply the armature of the converter directlyfrom the mains. An autotransformer is usedto match the field supply to its rated voltage.Moreover, you can use the autotransformerto adjust the field voltage (SDCS-FEX-1diode bridge) or to reduce the voltage ripple.Different types (primary voltages of 400...500V and of 525...690 V) with different ratedcurrents are available.

Depending on the protection strategy dif-ferent types of fuses are to be used. The fusesare sized according to the nominal current ofthe field supply. If the field supply is con-nected to two phases of the network, twofuses should be used. In case the unit isconnected to one phase and neutral only thefuse in the phase can be used. Table 2.6/3lists the fuses currents with respect to Fig.2.6/2.The fuses can be sized according to themaximum field current of the motor. In thiscase take the fuse, which fits to the fieldcurrent levels of the motor.

Fuses F3.x and fuse holders for 2-phase field supply

Field conv. Field current F3.2 F 3.3

SDCS-FEX-1 IF ≤ 6 A OFAA 00 H10 10 ASDCS-FEX-2

SDCS-FEX-2 IF ≤ 12 A OFAA 00 H16 16 A

SDCS-FEX-2 IF ≤ 16 A OFAA 00 H25 25 ADCF 503ADCF 504A

DCF 503A IF ≤ 30 A OFAA 00 H50 50 ADCF 504A

DCF 503A IF ≤ 50 A OFAA 00 H63 63 ADCF 504A

Type of protection elements LV HRC type circuit breakerfor 690 V; fuse for 500 V orhold. OFAX 00 690 V

Table 2.6/3: Fuses and fuse holders for 2-phase field supply

Page 27: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-23

Electronic system / fan supply

The converter unit requires various auxiliary voltages.E.g. the unit’s electronics require 115 V/1-ph or 230 V/1-ph. The unit fans require 230 V/1-ph or 400 V/690V/3-ph, according to their size. The T2 auxiliary trans-former is available to supply the unit’s electronic systemand the single-phase fans.

Earth fault monitor

An earth fault monitor is provided by the standardsoftware. If needed, the analogue input AI4 has to beactivated. A current signal of the three phase currentsshould be supplied to AI4 by a current transformer. Ifthe addition of the three current signal is different fromzero, a fault is generated (details see Technical Data).

Line reactor

When using the SDCS-FEX-2 field power converter,you should additionally use a line reactor because ofEMC considerations. A line reactor is not necessary forthe SDCS-FEX-1 (diode bridge). In DCF 503A/504Afield power converters a line reactor is already installed.

Converter Reactor≤≤≤≤≤500 V; 50/60 Hz

SDCS-FEX-2 ND 30

Table 2.6/5: Line reactor (details see Technical Data)

Auxiliary transformer T2

Input voltage: 380...690 V/1-ph; 50/60 HzOutput voltage: 115/230 V/1-ph

Fig. 2.6/4: T2 auxiliary transformer

Page 28: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-24

Fig. 2.6/5: Classification

Not applicable

First environment (residential area with light industry) with restricted obtainability

Not applied, since general obtainability sales channel excluded

satisfied

satisfied

The paragraphs below describe selection of the electri-cal components in conformity with the EMC Guide-line.

The aim of the EMC Guideline is, as the name implies,to achieve electromagnetic compatibility with otherproducts and systems. The guideline ensures that theemissions from the product concerned are so low thatthey do not impair another product's interferenceimmunity.

In the context of the EMC Guideline, two aspects haveto be considered:• the product's interference immunity

• the product's actual emissionsThe EMC Guideline expects EMC to be taken intoaccount when a product is being developed. However,EMC cannot be designed in, it can only be quantita-tively measured.

Note on EMC conformityThe conformity procedure is the responsibility of boththe power converter's supplier and the manufacturer ofthe machine or system concerned, in proportion totheir share in expanding the electrical equipment in-volved.

EMC filters

MM

Mains filter

Converter

Line reactor

Mountingplate

Supply transformer for a residential area (rating normally 1,2 MVA)

Earthed public 400-V network with neutral conductor

Medium-voltage network

Earthed neutral

To

othe

r lo

ads,

e.g

. driv

e sy

stem

s

An isolating transformer with an earthed screen and earthed iron core renders mains filter and line reactor superfluous.

Operation at public low-voltage network

together with other loads of all kinds.

Residential area

To

othe

r lo

ads

whi

ch h

ave

to b

e pr

otec

ted

from

the

syst

em d

istu

rban

ces

caus

ed b

y po

wer

con

vert

ers

(HF

inte

rfer

ence

and

com

mut

atio

n no

tche

s)

Converter

MMMM MM

alte

rnat

ive

alte

rnat

ive

Line reactor + Y-capacitor

Mountingplate

Medium-voltage network

Supply transformer for a residential area (rating normally 1.2 MVA)

Earthed neutral Earthed public 400-V

network with neutral conductor

To

othe

r lo

ads,

e.g

. driv

e sy

stem

s

Mains filter

Line reactor

Converter Converter

Mains filter

Line reactor

Converter Converter

An isolating transformer with an earthed screen and earthed iron core renders mains filter and line reactor superfluous.

Operation at public low-voltage network

together with other loads of all kinds.

To

othe

r lo

ads,

e.g

. driv

e sy

stem

s

To

othe

r lo

ads

whi

ch h

ave

to b

e pr

otec

ted

from

the

syst

em d

istu

rban

ces

caus

ed b

y po

wer

con

vert

ers

(HF

inte

rfer

ence

and

com

mut

atio

n no

tche

s)

Earthed public 400-V network with neutral conductor

Operation at public low-voltage network together with other loads of all kinds.

Light industry Residential area

Page 29: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-25

EN 61800-3

EN 50081-1

EN 50081-2

EN 50082-2 EN 61000-6-2

EN 50082-1

satisfied

satisfied

Second environment (industry) with restricted obtainability

on customer's request satisfied

Not applicable

Standards Classification

The following overviewutilises the terminologyand indicates the actionrequired in accordancewith Product Standard

EN 61800-3For the DCS 600 series,the limit values for emit-

For compliance with the protection objectives of theGerman EMC Act (EMVG) in systems and machines,the following EMC standards must be satisfied:

Product Standard EN 61800-3EMC standard for drive systems (PowerDriveSys-tem), interference immunity and emissions in resi-dential areas, enterprise zones with light industryand in industrial facilities.

This standard must be complied with in the EU forsatisfying the EMC requirements for systems and

machines!

In cases where the product standard is not applied, the generic standards EN50081 and EN 50082 are sometimes adduced.For emitted interference, the following apply:EN 50081-1 Specialised basic standard for emissions in light industry can be

satisfied with special features (mains filters, screened powercables) in the lower rating range.

EN 50081-2 Specialised basic standard for emissions in industry

For emitted interference, the following apply:EN 50082-1 Specialised basic standard for interference immunity in residen-

tial areasEN 50082-2 Specialised basic standard for interference immunity in industry.

The EN 61000-6-2 standard replaces EN 50082-2. If this standardis satisfied, then the EN 50082-1 standard is automatically satis-fied as well.

The field supply is not depicted inthis overview diagram. For thefield current cables, the samerules apply as for the armature-circuit cables.

ted interference are complied with,provided the action indicated is car-ried out. This action is based on theterm Restricted Obtainability usedin the standard (meaning a sales chan-nel in which the products concernedcan be placed in the stream of com-merce only by suppliers, customersor users which individually or jointlypossess technical EMC expertise).

For power converters without addi-tional components, the followingwarning applies:This is a product with restrictedobtainability under IEC 61800-3.This product may cause radio inter-ference in residential areas; in thiscase, it may be necessary for theoperator to take appropriate action(see adjacent diagrams).

MMMM

Supply transformer for a residential area (rating normally 1.2 MVA)

Earthed 400-V network with neutral conductor; 3~ 400 A

Operation at low-voltage network together with other loads of all kinds, apart from some kinds of sensitive communication equipment.

To

othe

r lo

ads,

e.g

. driv

e sy

stem

s

Line reactor + Y-capacitor Line reactor

Converter Converter

Mains filter

Earthed neutral

Medium-voltage network

Industrial zone

alte

rnat

ive

alte

rnat

ive

MMMM

Convertertransformer

Cas

e-re

fere

nced

EM

C a

naly

sis

alte

rnat

ive

Converter transformer with earthed

iron core (and earthed screen where appropriate)

alte

rnat

ive

I > 400 A and/or U > 500 V

Operation with separate power converter transformer. If there are other loads at the same secondary winding, these must be able to cope with the commutation gaps caused by the power converter. In some cases, commutating reactors will be required.

To

othe

r lo

ads,

e.g

. driv

e sy

stem

s

Converter Converter

Line reactor

Medium-voltage network

Industrial zone

PE + PE- + PE- + PE- + PE-

Legend

Unscreened cable with restriction

Screened cable

Field-current conductor

Armature-circuit conductor

PE protective earth conductor

Cable rack acts as screening against

HF emissions

Page 30: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-26

Three - phase filtersEMC filters are necessary to fulfill EN 50081 if aconverter shall run at a public low voltage networks, inEurope for example with 400 V between the phases.Such networks have a directly earthed conductor. ABBoffers suitable three-phase filters for 400 V and25 A....600 A and 500 V filters for 440 V networksoutside Europe.

Networks with 500 V to 1000 V are not public. Theyare local networks inside factories, and they do notsupply sensitive electronics. Therefore converters donot need EMC filters if they run with 500 V and more.

Converter type Rated DC current Filter type

xxx = Voltage

[A]

DCS60x-0025-x1 25 NF3-xxx-25DCS60x-0050-x1 50 NF3-xxx-50DCS60x-0075-x1 75 NF3-xxx-64DCS60x-0100-x1 100 NF3-xxx-80DCS60x-0140-x1 140 NF3-xxx-110DCS60x-0200-x1 200 NF3-xxx-320DCS60x-0250-x1 250 NF3-xxx-320DCS60x-0350-x1 350 NF3-xxx-320DCS60x-0450-x1 450 NF3-xxx-600DCS60x-0520-x1 520 NF3-xxx-600DCS60x-0680-x1 610 NF3-500-600DCS601-0820-x1 740 NF3-500-600DCS602-0820-x1 820 NF3-690-1000DCS60x-1000-x1 900 NF3-690-1000DCS60x-0900-x1 900 NF3-xxx-1000DCS60x-1200-x1 1200 NF3-xxx-1000DCS60x-1500-x1 1500 NF3-xxx-1600DCS60x-2000-x1 2000 NF3-xxx-1600DCS60x-2500-x1 2500 NF3-xxx-2500

Filters 25... 2500 A are available for 440 V and 500 V.Filters 600...2500 A are available for 690 V as well.

➊ The filters can be optimized for the real motor currents:IFilter = 0.8 • IMOT max ; the factor 0.8 takes the current rippleinto account.

Table 2.6/6: Three-phase filters

Converter type of DC current Filter typefield supply unit Umax = 250 V

[A]

SDCS-FEX-1 6 NF1-250-8SDCS-FEX-2 8 NF1-250-8SDCS-FEX-2 16 NF1-250-20DCF 503A-0050 50 NF1-250-55DCF 504A-0050 50 NF1-250-55further filters for 12 NF1-250-12

30 NF1-250-30

➊ The filters can be optimized for the real field currents:IFilter = IField

Table 2.6/7: Single-phase filters

Filter in a grounded line (earthed TN or TTnetwork)The filters are suitable for grounded networks only, forexample in public European 400 V networks. Accord-ing to EN 61800-3 filters are not needed in insulatedindustrial networks with own supply transformers.Furthermore they could cause safety risks in floatingnetworks (IT networks).

Single-phase filters for field supplyMany field supply units are single-phase converters forup to 50 A excitation current. They can be supplied bytwo of the three input phases of the armature converter.In that case a field supply unit does not need its ownfilter.

If one phase voltage to neutral is taken (230 V in a400 V network) then a separate filter is necessary. ABBoffers such filters for 250 V and 6...30 A.

Page 31: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-27

Commutation and line reactors(see also Section Line reactors in this chapter)Due to the maximum power of public 400 V trans-formers (P

MAX = 1.2 MVA ⇒ I

MAX = 1732 A) and due

to their relative voltage drop of 6% or 4% the maxi-mum AC current which is available for a converter is346 A or 520 A (I

DC ≤ 422 A or 633 A).

Isolating transformersAn isolating transformer makes line chokes unneces-sary because of its leakage inductance, and a groundedscreen between its windings saves an EMC filter. Thescreen and the iron core must be well connected withthe mounting plate of the converter.

Converter transformersA converter transformer transfers a high power directlyfrom a medium voltage network to a single largeconverter or to a local low voltage network for severalconverters. Furthermore it acts as isolating transformer.

If such a converter transformer has no screen the EMCdemands are nevertheless fulfilled in most cases, be-cause the RF interference can hardly get via the medi-um-voltage network and the transformer of the publicnetwork to the loads which must be protected againstdisturbances.

PE

PE

Installation hints• All metal cabinets available on the market can be

used.• The mounting plate must be made from steel with

zinc coating and without any painting. It must beconnected with the PE busbar by several bolts/cables.

• The converter, the line reactors, fuses, contactorsand the EMC filter are to be placed on the mountingplate so that the connections are as short as possible,especially those from the converter via the line choketo the filter.

• The cables for digital signals which are longer than3m and all cables for analogue signals must bescreened. Each screen must be connected at bothends by metal clamps or comparable means directlyon clean metal surfaces. In the converter cubicle thiskind of connection must be made directly on thesheet metal close to the terminals.

• The necessity of a screen for power cables dependson the length of the cable and on the environmentaldemands. If a screen is necessary then it must bepressed by a well conducting metal clamp directlyagainst the mounting plate or the PE busbar of theconverter cabinet.

• Screened cables to the armature and to the excitationwinding cause the lowest noise level. The armaturecurrent cable must contain a wire for a PE connec-tion if the copper cross section of the screen cannotfulfil the safety demands.

• If a screen is not necessary the armaturecurrent cable must be a four-wire cable.Two wires are needed as PE to dischargethe parasitic RF currents from the motorto the EMC filter in the cabinet.

Page 32: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 2-28

Connection example in accordance with EMC

Fig. 2.6/6: Connection example in accordance with EMC

Important hint:The example shows the principle structure ofa DC drive and its connections. It is a notbinding recommendation, and it cannot takeall conditions of a plant into account.Therefore each drive must be consideredindividually and with respect due to its specialapplication. Additionally the general installa-tion and safety rules must be taken intoaccount.

M

A1 A2

F1

F2

A1 A2

F1

F2

L1

L2

L3

PE

U1

V1

W1C1

D1

U1

V1 F-F+

PE

PE

PE

PE

A

F

A FTacho

A FTacho

T

AF

AF

I/O

Mounting plate

DC motor

Tach

o

ScreensContact to the motorhousing at the whole

screen perimeter

Filter

Mounting plate with PE busbar and terminals

PE bar

DC motor

Tach

oSc

reen

Mounting plate with PEbusbar and terminals

PE bar

lower edgeof the PCB

carrier

Encoder inputs andanalogue I/O at the PCB

Fieldsupplyunit

Armature and field cables with screens for

"first environment"

Armature and field cables without

screens suitable for "second

environment"

Hint: The armature current cable must contain a third wire for a PE connection if the copper cross section of the screen cannot fulfil the PE safety demands.

Page 33: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-1

3 Overview of software (Version 15.xxx)

3.1 Basic structure ofDCS 600 MultiDrive

The control hardware of DCS 600 MultiDrive consistsof 2 parts:• converter control board SDCS-CON-2• drive control board SDCS-AMC-DC 2

(AMC = Application Motor Control)

Accordingly, the software is split into 2 parts:• All control functions superimposed to the torque

reference are done inside the AMC board. In addi-tion, all HMI (Human Machine Interface) andcommunication functions are part of the AMCboard's software. Also the Start/Stop functions('Drive Logic') are realized by the AMC board'ssoftware. All parameters and signals of the drive areaccessed via an on the AMC board residing datastructure called 'AMC-table'.

• All converter related functions and the handling ofstandard I/O are done by the SDCS-CON-2 soft-ware:• Armature current control• Field weakening• Motor protection• I/O handling

In general, the software functions are distributed be-tween the SDCS-CON-2 board and the SDCS-AMC-DC 2 board according to the following diagram:

3.2 Control Modes

The Control mode selects the source of control wordand references.

Local ModeCommissioning tool DriveWindow is connected toDDCS channel 3 of the AMC board and can use localmode. Local mode is also available on the panel CDP312.

Remote ModeReference and control word are supplied by an overrid-ing control system or a fieldbus adapter connected tothe DDCS channel 0.

Master/Follower ModeReference and control word are supplied to the followerdrive by the master drive via DDCS channel 2.

Fig. 3.1/1: Distribution of software functions

Human Machine Interface & Communication

SDCS-CON-2Software 15.2xx

Application ControlSDC

S-A

MC

-DC

2So

ftwar

e 15

.6xx

Drive Control

I/O handling

Torque Control

Page 34: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-2

3.3 Start, Stop and Fault Reactions

Power upWhen the electronics power supply is switched on thedrive stays in the ON_INHIBIT state until ON = 0 isdetected. In case of a fault the drive stays in the FAULTstate.

Normal startStatus bit RDY_ON = 1 signals that no faults arepending and that the device is ready to close the main,fan and field contactor.A rising edge of the ON command closes fan, field andmain contactor and activates the field control.Status bit RDY_RUN = 1 indicates that the fieldconverter is active and that the drive is ready to generatetorque.A rising edge of the RUN command activates speed andtorque control.Status bit RUNNING = 1 indicates that the drive is innormal operation.

Normal stopRUN = 0 sets the speed reference to zero and the drivedecelerates.After the actual speed has reached zero the status bitRUNNING is reset, the armature converter sets thefiring angle to maximum. The state RDY_RUN isentered, when the actual current has reached zero.ON = 0 sets RDY_RUN = 0 and the field currentreference to zero. The field converter sets the firingangle to maximum . The contactors are opened, whenthe actual current has reached zero.ON = 0 internally forces RUN = 0.

Emergency offField and armature current are removed as fast aspossible. After the current has reached I

DC = 0 the

contactors are opened. The normal start command isaccepted when OFF2_N = EME_OFF_N = 1.

Emergency stopCommand EME_STOP = 0 gives the same procedureas RUN = 0 (normal stop) except that the ramp isswitched from deceleration to emergency stop and thestate ON_INHIBIT is entered when the speed hasreached zero.The normal start command is accepted when OFF3_N= EME_STOP_N = 1.The reference handling and current limitation is con-trolled by EME_STOP_MODE.

Fault reactionDepending on the actual fault the armature currentand/or field current is reduced to zero as fast as possiblewith single pulses and maximum firing angle. Contac-tors are opened when the current has reached zero.Then the state TRIPPED is entered and after a success-ful reset the state ON_INHIBIT.

The following state diagram shows the transitionsbetween the different states.

Table 3.1/1: States of the drive

During operation, the drive is in one of the followingstates (ABB Drive profile):

TIBIHNI_NO

potsycnegremeretfAffoycnegremero)N_3FFO(

sietatssiht)N_2FFO(0=NOlitnuderetne

FFON_3FFO,ffosirotcatnocniaM

evitcaN_2FFOro

NO_YDR ffosirotcatnocniaM

NUR_YDR

rotcatnocnafdnadleif,niaMlortnocdleif,desolcera

nurrofydaer,detavitcadnammoc

FER_YDRlla,gninnursievirD

desaelererasrellortnoc

DEPPIRT detluafsievirD

N_ATS_2_FFO

oteudgnitsaocsievirDeht;dnammocffoycnegreme

F_DNA_A_OREZsetats →.deretneeraTIBIHNINO

N_ATS_3_FFO

ehtotgnidroccaspotsevirDpotsycnegremedemmargorp

demmargorpehtdnapmarta;edompotsycnegreme

etatseht,deepsorez.deretnesiTIBIHNI_NO

Page 35: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-3

Fig. 3.3/1: Control and status

Voltageswitched off

Switch oninhibit

not readyto swich on

Power ON OFF 1 (MCW Bit0=0)

Status Disable(MSW Bit6=1)

Status Not ready for startup(MSW Bit0=0)

ready to switch on Status Ready for startup

(MSW Bit0=1)

Main Control word basic condition(MCW=XXXX XXXX XXXX X110)

ON (MCW Bit0=1)

InhibitOperation active

operationdisabled

disable operation(MCW Bit3=0 RUN)

Ready Status Ready for operation

Releaseoperation

(MCW Bit3=1)

A B C D

OFF1

(n=0 / I=0) OR (MCW Bit3=0 (RUN))

OFF1 (MCW Bit0=0)

from every device status

OFF3active

Stop drive *)according toparameter 21.04eme stop mode

(MSW Bit5=0)n=0 / I=0

Emergency StopOFF3 (MCW Bit2=0)

from every device status

OFF2

(MSW Bit4=0)

Emergency OffOFF2 (MCW Bit1=0)

from every device status

Fault Stop drive

(MSW Bit3=1)

Fault

from every device status

EnableOperation

Release electronics and pulses (MSW Bit2=1)

RFG-output free

(MCW Bit4=1)RFG: Enable

output

RFG-output released

(MCW Bit5=1)

B

RFG: Acceleratorenable

Setpoint released

(MCW Bit6=1)

C

D

A

Operatingstate

D

n = n_set

(MSW Bit8=1)

MCW = Main Control WordMSW = Main Status Wordn = SpeedI = Power input currentRFG = Ramp Function Generator

Error correctedconfirm by RESET (MCW Bit7= 1)

B C D

C D

RFG-outputdisable(MCW Bit4=0RAMP_OUT_ZERO)

RFG stop(MCW Bit5=0RAMP_HOLD)

Setpointdisabled(MCW Bit6=0RAMP_IN_ZERO)

ABB Drive Profilefor DC-drives

Control andStatus

Inching 1 ActiveDrive Running Inching 1 setpoint

to speed control

MCW: Bit 4 = 0 and Bit 5 = 0 and Bit 6 = 0

INCHING 1 ON (MCW Bit 8 = 1)

Purpose: Main speed ref. is deactivated

Inching 2 setpointto speed control

INCHING 2 ON (MCW Bit 9 = 1)

Inching 2 ActiveDrive Running

INCHING 1 OFF (MCW Bit 8 = 0)

INCHING 2 OFF (MCW Bit 9 = 0)

ON INHIBIT

OFF

RDY_ON

RDY_RUN (MSW Bit1=1)

RDY_REF Status Operation released

OFF_3_STA

Coast Stop(no torque)

OFF_2_STA

TRIPPEDStatus:

Status:Status:

RUN

RAMP_OUT_ZERO

RAMP_HOLD

RAMP_IN_ZERO

AT_SETPOINT

activeactive

E F

E

F

dcs_600\docu\fig_4.dsf

Stop drive *) according to- DECELER TIME (22.02) at speed control- TORQ RAMP DOWN (25.06) / TORQ REF A FTC (25.02) at torque controlthen open Main ContactorStatus:OFF(not ready for startup,MSW Bit0=0)

*) while the drive is being stopped, status bit RDY_REF (MSW bit 2) remains at "1" as long as the drive generates torque.

Inhibitconverter pulsesStatus:Operation Disabled(MSW Bit2=0 RDY_REF)

Page 36: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-4

3.4 Speed Control

The speed controller is located in the AMC boardsoftware.

Speed referenceThe source of the reference is depending on the oper-ating mode.

Overriding controlsystem, fieldbus adapters remote mode, DDCS

via AMC boardDriveWindow local mode, DDCS via

AMC boardPanel CDP312 local mode, connector

on CON-2Analogue inputs local I/O

Speed reference features• Speed reference limiter• Additional speed ramp for emergency stop• Variable slope rate• Speed correction• Reference for inching before the ramp• 2 different references for inching behind the ramp

Speed measurementThe actual speed may be calculated from:• Armature voltage• Analogue tachometer• Pulse encoder

Controller features• PID controller• 2 first order low pass filters• Window control• Acceleration compensation• Speed and torque adaptation• Droop• Additional torque references• Torque limitation and gear backlash function (the

integral part of the controller is set to a suitable valueon limitation)

• Oscillation damping (band rejection filter for speederror)

The diagram Fig. 3.8/2 shows the functionality of thespeed reference chain as well as of the speed controller.

3.5 Torque Control

Flux and Torque CalculationThe torque control is in general an open loop control.The flux is adjusted by the field current. The referenceof the field current is generated by the superimposedarmature voltage control.The torque is adjusted by the armature current. Theconversion from torque to current reference is done bymeans of the calculated flux (based on the field currentand saturation characteristic).

Torque reference features• Torque reference A with 1st order filter and load

share• Torque reference B with torque ramp• Torque reference limiter• Torque correction and torque step• Torque correction by means of analogue input 1

A good behaviour in the field weakening requires speedmeasurement by tachometer or encoder.

A simplified scheme of the torque reference chain isgiven in diagram fig. 3.8/2.

3.6 HMI (Human Machine Interface)The HMI is performed by CDP 312 control panelor by DriveWindow.Both tools contain:• Display of drive signals• Setting of drive parameters• Display fault and alarm messages• Control the drive in local operation

Page 37: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-5

3.7 Torque Generation

Interface between SDCS-AMC-DC 2 board andDC control board SDCS-CON-2The major signals exchanged each 2 ms between CON-2 and AMC-DC 2 are:

SPEED_ACTUAL speed actual value fromCON-2

TORQ_USED_REF active torque reference toCON-2

In addition, the calculated torque limits are read fromthe CON-2 each 8 ms:

TC_TORQMAXTC_TORQMIN

The addition of the torque correction TQ_CORRfrom an analogue input of CON-2 is done by theCON-2 software.

Armature voltage ControlThis controller enables operation in the field weaken-ing range. It generates the field current reference. At lowspeeds the field current is constant and armature volt-age is roughly proportional to the speed. At higherspeeds (≥ base speed) the field current reference isreduced so that the armature voltage doesn’t exceed itsreference.

Field Current ControlTwo field exciters can be operated simultaneously fortwo different motors.The first field exciter can be operated with fixed currentreference, in field weakening or with a reduced refer-ence for field heating.The second field exciter has a fixed current reference(no field weakening possible). However, it may bereduced for field heating purposes.A field reversal control is available for the first fieldexciter.Optitorque is a special control method where the fluxis reduced at small torque reference. This is available fordrives with and without field reversal.

Armature Current ControlThe armature current reference is calculated from torquereference and flux. Then it is processed by a ramp,limitation and speed dependent limitation.The actual value of the armature current is the meas-ured mean value between two firing pulses.The armature voltage reference is generated by a PIcontroller.The firing angle is calculated from this voltage referencedepending on the actual line voltage and the conduc-tion time (adaptation between continuous and discon-tinuous state of the converter current).

A simplified scheme of the armature current control isgiven in diagram fig. 3.8/3.

Page 38: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-6

3.8 Software diagrams

IntroductionThe designation of parameters and signals consist of agroup and a index.

XParameter

01.02

23.05Signal

GroupIndex

The structure of the software is given. Changes of thefunctions or pointers are realized through setting pa-rameters.

This can be done via panel, DriveWindow (PC utility),fieldbus or overriding control system.

Changed parameters or pointers are stored immediate-ly in the non-volatile flash PROM.

All parameters can be transferred to the PC and bestored on a data medium by using DriveWindow.

Fig. 3.8/1: Parameter/signal designation

On the following pages the simplified software struc-ture is shown. Additionally there are specific tables for:

• Main Control Word (MCW)• Auxiliary Control Words (ACW)• Main Status Word (MSW)• Auxiliary Status Word (ASW)• Digital Inputs (Armature converter mode)• Digital Inputs (Field converter mode)• Digital Outputs (Armature converter mode)• Digital Outputs (Field converter mode)• Analogue Inputs (Armature converter mode)

Page 39: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-7

Fig. 3.8/2: Speed reference chain

50.0

6AC

W B

8

24.1

3

24.1

2

24.2

024

.19

24.1

8

24.1

7

24.1

024

.09

24.0

6

24.0

5

24.0

4

24.0

3

20.0

820

.07

LOC

AL R

EF1

+

23.0

5

+ +-

D

0

0

+

RE

F1

ACT1

98.0

2LO

CAL MO

TOR

SPEE

D

STAR

T / S

TOP

CO

NTR

OL

PULS

EEN

CO

DER

INTE

RFA

CE

KPS

VAL

MAX

SPE

ED

KPS,

TIS

TIS

VAL

MIN

SP

EED

mot

or s

peed

KPS

TIS

MIN

SPE

ED

KPS

TIS

MAX

SPE

ED

WIN

DO

W

SPEE

D R

EFER

ENC

E C

HAI

N

SPEE

D C

ON

TRO

L

SPEE

DM

EASU

REM

ENT

DIG

ITAL

INPU

T

CDP

312

orD

RIVE

SW

IND

OW

LOC

AL C

TRL

PAN

EL

SPEE

D SH

ARE

MO

TOR

SPEE

DFI

LT

SPEE

DR

EF 2

SPEE

DAC

TUAL

SPEE

D R

EF 3

SPEE

DC

ORR

ECTI

ON

SPEE

DER

ROR

NEG

DRO

OP

RAT

E

TOR

Q A

CC

COM

P R

EF

2.07

ACC

ELER

ATIO

NC

OM

PENS

ATIO

N

ACC

CO

MP

DER

TIM

E

ACC

CO

MPF

ILT

TIM

E

24.0

2

Dat

aset

s[7

0.20

]+0

... [7

0.20

]+14

MC

W

RE

F2

MSW

ACT2

CO

MM

MO

DULE

CO

NST

SPE

ED 2

(INCH

ING

2)

CONS

T SP

EED

1(IN

CHI

NG 1

)M

CW

B8,

B9

23.0

3

23.0

2

24.1

4

24.1

5

23.1

0SP

EED

STE

P

2.03

PID

- CO

NTR

OLL

ERTO

RQ

UE

DER

REF

TOR

QUE

PRO

P RE

F2.

06

2.04

LIM

ITER

SPC

TOR

QM

AXSP

C T

OR

QM

INTO

RQ

REF

2

TOR

QU

E IN

TEG

REF

BAL

REF

BAL_

NCO

NT

SPC

TOR

QM

AX

KPS

SPC

TORQ

MIN

KPS

KPS

MIN

KPS

WEA

KPO

INT

KPS

WP

FILT

TIM

E

TIS

TIS

INIT

VAL

UE

KPS

TIS

MIN

SPE

ED

KPS

TIS

MAX

SPE

ED

KPS

VAL

MIN

SPE

EDTI

S VA

L M

IN S

PEED

DER

IVAT

ION

TIM

E

DERI

V. F

ILT

TIM

E

KPS

TIS

TOR

QR

EF 2

MC

W B

x =

MAI

N CO

NTRO

L W

ORD

(7.0

1)AC

W B

x =

AUX

CONT

RO

L W

ORD

(7.0

2)

B

= bi

t

SPEE

D ER

RO

R F

ILT

WIN

DO

W IN

TG O

N

WIN

DOW

WID

TH P

OS

WIN

DO

W W

IDTH

NEG

23.0

6

23.0

7

23.0

8

23.0

9

(-1)FILT

ER

23.0

4

2.02

2.16

DV/

DT

RAM

P BY

PASS

BAL

RAM

P R

EF

BAL

RAM

P O

UT

VAR

IABL

E SL

OPE

RAT

E

VAR

IABL

E S

LOPE

SHAP

E TI

ME

EME

STO

P R

AMP

DEC

ELER

TIM

E

ACC

ELE

R T

IME

2.01

1.04

1.01

22.0

1

22.0

2

22.0

3

22.0

4

22.0

5

22.0

6

22.0

7

ACW

B3

22.0

8

ACW

B2

MC

W B

5

FILT

ER

SP A

CT

FILT

TIM

E

MAX

IMU

M S

PEED

MIN

IMU

M S

PEED

LIM

ITER

A

CC/

DEC

/SHA

PEM

CW

B4

MC

W B

6

20.0

1

20.0

2

50.0

4

50.0

3

50.0

2

50.0

1

rese

rved

SPEE

D SC

ALIN

GSP

EED

MEA

S M

ODE

SPEE

D FB

SEL

ENCO

DER

PU

LSE

NR

50.1

3S

P AC

T F

TC

ABB

DR

IVE

PRO

FIL

CO

NTR

OL

MCW

7.01

MAI

N C

ONT

RO

L W

ORD

ON

OFF

2O

FF3

RU

NR

AMP_

OU

T_ZE

RO

RAM

P_H

OLD

RAM

P_IN

_ZER

OR

ESET

INC

HIN

G1

INC

HIN

G2

VALI

D_C

OM

MAN

D

B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B11

B12

B13

B14

B15

TAC

HO

AI1

1 2 3 4 7.01

7.02

8.01

8.02

DIG

ITAL

OU

TPU

TS

2000

0 =

Spee

d sc

alin

g

HO

LD

RAM

P

RA

MP

TIM

E S

CAL

E

PI

FIEL

DBU

SAD

APTE

R

FILT

ER

dcs_

600\

docu

\fig_

1a.d

sf

7.03

8.05

23.1

2R

AMPE

D IN

CH R

EF

23.1

3SP

EED

CORR

RAM

P

AN

IN 1

VAL

UE

AN

IN 2

VAL

UE

AN

IN 3

VAL

UE

AN

IN 4

VAL

UE

AN

IN T

AC

HO

VAL

UE 0

Selector

13.1

7AI

SPE

ED S

ELEC

TAC

W B

12

2.17

USE

D SP

EED

REF

2.18

CON

AMC

23.0

1SP

EED

REF

7.02

AU

X C

ONT

ROL

WO

RD

ACW

B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B11

B12

B13

B14

B15

RE

STAR

T_DL

OG

TRIG

G_L

OG

GER

RA

MP_

BYP

ASS

BAL

_RAM

P_O

UT

DYN

_BR

AKE

_ON

_APC

HO

LD_N

CO

NT

WIN

DO

W_C

TRL

BAL

_NC

ON

TS

YNC

_CO

MM

AND

SYN

C_D

ISA

BLE

RE

SET_

SYN

C_R

DY

JOG

_REF

DIG

_OU

T4D

IG_O

UT5

DIG

_OU

T6

7.03

AU

X C

ONT

ROL

WR

D 2

ACW

2

B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B11

B12

B13

B14

B15

DIG

_OU

T_7

DIG

_OU

T_8

DR

IVE_

DIR

SPE

ED_E

XT

MSW

8.01

MAI

N S

TATU

S W

OR

D

B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B11

B12

B13

B14

B15

RD

YON

RD

YRU

NR

DYR

EF

TRIP

PED

OFF

_2_S

TAO

FF_3

_STA

ON

_INH

IBIT

ALA

RM

AT_

SETP

OIN

TR

EM

OTE

ABO

VE_

LIM

IT

8.02

AUX

STA

TUS

WO

RDAS

W

B0

B1

B2

B3

B4

B5

B6

B7

B8

B9

B10

B11

B12

B13

B14

B15

LOG

G_D

ATA_

REA

DY

OU

T_O

F_W

IND

OW

EMER

G_S

TOP_

CO

AST

ON

_DIS

ABL

ED

SYN

C_R

DY

FEX1

_AC

KFE

X2_A

CK

LIM

ITIN

GTO

RQ

_CO

NTR

OL

ZER

O_S

PEED

EMF_

SPEE

DFA

ULT

_OR

_ALA

RM

DR

IVE_

DIR

_AS

WAU

TO_R

ECLO

SIN

G

8.05

DI S

TATU

S W

ORD

DI S

TATU

S W

ORD

B0 B1 B2 B3 B4 B5 B6 B7 B8 B9 B10

B11

B12

B13

B14

B15

DI1

C

ON

V FA

N A

CK

DI2

M

OT

FAN

AC

KD

I3

MAI

N C

ON

T A

CK

DI4

co

nfig

urab

leD

I5

conf

igur

able

DI6

co

nfig

urab

leD

I7

conf

igur

able

DI8

co

nfig

urab

leD

I9D

I10

DI1

1D

I12

DI1

3D

I14

DI1

5

LOC

AL

Dat

aset

s[7

0.20

]+1

... [7

0.20

]+15

2.05

24.1

1

SPEE

D RE

F 4

Spee

d lim

its13

5.02

and

135

.04

appl

y he

re a

lso

2.09

EMF

99.0

2

99.0

5M

OTO

R NO

M S

PEED

MO

TOR

NO

M V

OLT

AGE

to TORQUE REF. SELECTOR

Page 40: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-8

Fig. 3.8/3: Torque control chain

TOR

QU

E C

ON

TRO

L C

HAI

N

LOC

AL

LOAD

SH

AR

E

FILT

ER

TOR

Q R

EF A

FTC

TOR

Q R

EF A

25.0

1

25.0

2

25.0

3

25.0

4

TOR

Q R

EF B

LOC

AL

TOR

QU

E R

EF(L

OC

AL R

EF 2

)TO

RQ

RA

MP

UP

TOR

Q R

AM

P D

OW

N

RAM

PIN

G

20.0

9

20.1

0

LIM

ITE

R

TREF

TO

RQ

MA

X

TRE

F TO

RQ

MIN

TOR

Q R

EF 1

2.08

+ +

0 12

3 45

6

2.09

SPE

ED C

ON

TRO

LLE R

OU

TPU

T

TOR

Q R

EF 2

TOR

QU

E R

EFE

REN

CE

SELE

CTO

R (2

6.01

)

TOR

QU

E S

ELE

CTO

R

MIN

MA

X

TOR

Q R

EF 3

2.10

26.0

3

26.0

2

TOR

QU

E ST

EP

LOAD

CO

MPE

NS

ATIO

NTO

RQ

RE

F 4

2.11

TOR

Q R

EF 5

2.12

20.0

5

20.0

6

2.19

2.20

TOR

QU

E LI

MIT

ER

MAX

IMU

M T

OR

QU

E

MIN

IMU

M T

OR

QU

E

TC T

OR

QM

AX

TC T

OR

QM

IN

TOR

Q U

SED

RE

F

2.13

D

A

AN

OU

T x

NO

M V

AL

AN

OU

T x

NO

M V

OLT

AN

OU

T x

OFF

S V

OLT

[AN

OU

T x

IND

EX]

AO

1(A

O2)

AN

OU

T 1

IND

EX

14.0

4A

N O

UT

1 N

OM

VAL

14

.03

AN

OU

T 1

OFF

S V

OLT

14

.02

AN

OU

T 1

NO

M V

OLT

14

.01

AN

OU

T 2

IND

EX

14.0

8A

N O

UT

2 N

OM

VAL

14

.07

AN

OU

T 2

OFF

S V

OLT

14

.06

AN

OU

T 2

NO

M V

OLT

14

.05

Anal

ogue

out

puts

+ +

A

D

AN

IN x

HI V

AL

AIx

AN

IN x

VA

LUE

Anal

ogue

inpu

ts

25.0

5

25.0

6

dcs_600\docu\fig_2a.dsf

AN

IN x

LO

VA

L

AN

IN T

AC

HO

VAL

UE

(sig

nal)

5.01

AN

IN T

AC

H H

I VA

L (a

t +10

V)

13.0

1A

N IN

TA

CH

LO

VAL

(at -

10V)

13

.02

AN

IN 1

VA

LUE

(sig

nal)

5.02

AN

IN 1

HI V

AL

(at +

10V

) 13

.03

AN

IN 1

LO

VAL

(at -

10V

) 13

.04

AN

IN 2

VA

LUE

(sig

nal)

5.03

AN

IN 2

HI V

AL

(at +

10V

) 13

.05

AN

IN 2

LO

VAL

(at -

10V

) 13

.06

AN

IN 3

VA

LUE

(sig

nal)

5.04

AN

IN 3

HI V

AL

(at +

10V

) 13

.07

AN

IN 3

LO

VAL

(at -

10V

) 13

.08

AN

IN 4

VA

LUE

(sig

nal)

5.05

AN

IN 4

HI V

AL

(at +

10V

) 13

.09

AN

IN 4

LO

VAL

(at -

10V

) 13

.10

AM

C

CO

N

AUX

CO

NTR

OL

WR

D 2

B 9

(SP

EED

_EXT

)

26.0

1TO

RQ

UE

SELE

CTO

R

Selector

26.0

4M

OD

E S

WIT

CH

SEL D

I1D

I2D

I3D

I4D

I5D

I6D

I7D

I8

1 2

0 1 8

2.19

+/- T

C T

OR

QM

AX

gear

back

lash

com

pen-

satio

n

from

PID

cont

rolle

r

to S

UM

Page 41: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-9

Fig. 3.8/4: Armature current control

TOR

QU

EC

OR

REC

TIO

N

TOR

Q U

SED

RE

F

2.13

2.14

FLU

X R

EF

FLD

WE

AK

3.14

CU

R R

EF S

LOP

E

di/d

t

41.1

0

SCAL

E

HL

LL20.1

2

CU

R L

IM M

OT

BRID

GE

20.1

3

CU

R L

IM G

EN B

RID

GE

CU

R R

EF

3

3.12

CU

RR

ENT

CO

NTR

OLL

ER

CO

NTR

OL

TYP

E SE

L

AR

M C

UR

PI P

-GA

IN

AR

M C

UR

PI I

-GA

IN

AR

M C

UR

IP P

-GA

IN

AR

M C

UR

IP I-

GA

IN

DIS

CO

NT

CU

R L

IMIT

43.0

1

43.0

2

43.0

3

43.0

4

43.0

5

43.0

6

PI-I

P

+ -

LOAD

CU

R A

CT

1.27

4096

==

Mot

or n

omin

al c

urre

ntLO

AD C

UR

AC

T FI

LT

1.28

Arm

atur

eC

urre

ntM

easu

rem

.

EMF

Cal

c.

HL

LL

20.1

4

MA

X FI

RIN

G A

NG

LE

20.1

5

MIN

FIR

ING

AN

GLE

ALPH

A_M

AXC

alc.

3.13

FIR

ING

AN

GLE

FIR

E U

NIT

1.19

SELE

CTE

D B

RID

GE

MO

TOR

NO

M V

OLT

AGE

MO

TOR

NO

MC

UR

REN

T

99.0

2

99.0

3

CO

NV

NO

M C

UR

R

4.13

Mai

nsVo

ltage

Mea

sure

m.

Con

verte

rC

urre

ntM

easu

rem

.

U_S

UPP

LY

42.0

6

RL

MAI

NS

VOLT

AC

T

MA

INS

VO

LT A

CT

RL

CO

NV

CU

R A

CT

CO

NV

CU

R A

CT

1.11

1.12

1.15

1.16

MM

MO

TOR

1M

OTO

R 2

Fiel

dC

urre

ntM

easu

rem

.

RE

L FI

ELD

CU

R M

1

FIE

LD C

UR

M1

3.19

3.20

3.21

3.22

Fiel

dC

urre

ntM

easu

rem

.

RE

L FI

ELD

CU

R M

2

FIE

LD C

UR

M2

FIR

STFI

ELD

EXC

ITER

MO

T 1

NO

M F

LD C

UR

41.0

3FI

ELD

CU

R R

EF

M1

3.17

US

ED F

EX

TYPE

15.0

51,

2,4,

5,6,

7,8,

9,10

,11,

12,1

3

FIE

LD C

UR

RE

F M

2

3.18

3,4

FLD

CU

R @

40%

FLU

X41

.14

41.1

5FL

D C

UR

@70

% F

LUX

41.1

6FL

D C

UR

@90

% F

LUX

FLU

X/FI

ELD

LIN

EAR

IZAT

ION

RL

EMF

VOLT

AC

T

1.17

EMF

CO

NTR

OLL

ER

46.0

3E

MF

CO

N K

P46

.04

EM

F C

ON

KI

FLU

XC

ON

TRO

L

MO

TOR

NO

MS

PEED

99.0

5

INT

EMF

REF

41.1

9

MO

TOR

SPE

ED

1.02

MN

= 1

0000

=M

max

= 3

.2 *

MN

4096

= 1

00%

of

I_M

OTx

_FIE

LD_A

ARM

ATU

RE

CU

RR

ENT

CO

NTR

OL

SEC

ON

DFI

ELD

EXC

ITER

MO

T 2

NO

M F

LD C

UR

41.1

7

dcs_

600\

docu

\fig_

3a_a

.dsf

FLU

X R

EF F

LD W

EAK

EMF

RE

F

45.0

3

45.0

2flu

x/em

f ref

sel

= EX

T R

EF

FLU

X R

EF

45.0

1

3.14

45.0

2 fl

ux/e

mf r

ef s

el =

EXT

REF

OR

46.0

7 fl

ux re

f sel

= E

XT R

EF

CU

R R

EF

2

3.28

FLU

X R

EF

SUM

3.15

AI V

REF

3.29

MU

X

EMF

RE

F SE

L

46.0

8

0 321

V R

EF 1

3.24

FLU

X R

EF

EMF

3.26

46.1

2V

REF

SLO

PE

46.0

5E

MF

CO

N B

LOC

KLE

V

46.1

0V

CO

R46

.11

V S

TEP

46.1

3V

LIM

P46

.14

V L

IM N

V re

f Mod

ifica

tion

V R

EF 2

3.25

VOLT

AC

TUA

L3.

23

EM

F A

CT

FILT

TC 46.0

6

Dia

gram

for

OP

ER M

OD

E S

ELEC

T (1

5.16

) < 5

FIE

LD 2

REF

44.2

3via

driv

e lo

gic

MA

XIM

UM

FLU

X45

.07

FLU

X C

OR

43.2

0

20.1

220

.13

2.19

2.20

torq

ue li

mit

clac

ulat

ion

set t

o 0,

if F

IX fi

eld

sele

cted

(15.

06)

set t

o M

AXIM

UM

FLU

X (4

5.07

), if

FIX

field

sel

ecte

d (1

5.06

)

OPT

ITO

RQ

UE

Fiel

d re

vers

al

+ +

scal

ed to

NO

M S

UPP

LY V

OLT

(42.

06)

from TORQUE Limiter

Page 42: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-10

Fig. 3.8/5: Inductive load current control

CUR

REF

SLO

PE

di/d

t

41.1

0

HL

LL

CUR

LIM

MO

TBR

IDG

E

CUR

LIM

GEN

BRI

DG

E

CUR

REN

T CO

NTR

OLL

ER

CO

NTR

OL

TYP

E S

EL

AR

M C

UR

PI P

-GA

IN

AR

M C

UR

PI I

-GA

IN

AR

M C

UR

IP P

-GA

IN

AR

M C

UR

IP I-

GA

IN

DIS

CO

NT

CU

R L

IMIT

43.0

1

43.0

2

43.0

3

43.0

4

43.0

5

43.0

6

PI-I

P+ -

LOAD

CU

R A

CT

4096

==

Load

nom

inal

cur

rent

LOAD

CU

R A

CT

FILT

Arm

atur

eC

urre

ntM

easu

rem

.

EM

FC

alc.

HL

LL

MAX

FIR

ING

AN

GLE

MIN

FIR

ING

AN

GLE

ALPH

A_M

AXC

alc.

FIR

ING

AN

GLE

FIRE

UN

IT

SELE

CTE

D B

RID

GE

MO

TO

R N

OM

VO

LTAG

E

MO

TO

R N

OM

CU

RR

ENT

99.0

2

99.0

3

CO

NV

NOM

CU

RR

Mai

nsV

olta

geM

easu

rem

.

Con

verte

rC

urre

ntM

easu

rem

.

U_S

UPP

LY

RL

MAI

NS

VOLT

AC

T

MAI

NS

VOLT

ACT

RL

CO

NV C

UR

AC

T

CO

NV

CUR

AC

T

RL

EMF

VOLT

ACT

EM

FC

ON

TRO

LLE

R 46.0

3E

MF

CO

N K

P46

.04

EM

F C

ON

KI

INT

EMF

REF

IND

UC

TIVE

LO

AD C

UR

REN

T C

ON

TRO

L

dcs_

600\

docu

\fig_

3b_a

.dsf

EMF

REF

45.0

2flu

x/em

f ref

sel

= EX

T R

EF

AI V

REF

MUX

EMF

REF

SEL

0 321

V RE

F 1

FLU

X RE

F EM

F

46.1

2V

RE

F S

LOP

E46

.05

EM

F C

ON

BLO

CK

LEV

46.1

0V

CO

R46

.11

V S

TEP

46.1

3V

LIM

P46

.14

V L

IM N

V re

f Mod

ifica

tion

V RE

F 2

CUR

REN

T RE

F

AI C

UR

REF

MUX

FLU

X RE

F SE

L

0 321

CUR

REF

1

0

INT

CUR

REF

4

FEX

LINK

REF

Ref

eren

ceSe

lect

ion

and

min

/max

-Lo

gic

FLU

X CO

R

FLU

X ST

EP

REF

SEL

43.1

5SE

L M

AX M

IN43

.16

43.1

5R

EF

SE

L

CUR

REF

1

V A

CT

SE

L

I AC

T S

EL

V I

SE

L 1

V I

SE

L 2

AR

M R

46.2

0

46.1

9

46.2

1

46.2

2

41.1

2

EM

F A

CT

FILT

TC

46.0

6V

AC

T C

AL

46.1

6

AR

M L

41.1

1

VOLT

AC

TUAL

3.23

actu

al v

olta

gese

lect

ion

Dia

gram

for

OPE

R M

OD

E SE

LEC

T (1

5.16

) = 5

TOR

QUE

USE

D R

EF

TOR

QUE

CO

RR

ECTI

ON

not u

sed

- CU

R R

EF 1

:= L

OC

AL R

EF 3

, i

f loc

al m

ode

and

REF

SEL

(43.

15) <

3- C

UR

REF

1 :=

LO

CAL

CUR

REF

(43.

19),

if l

ocal

mod

e an

d RE

F SE

L (4

3.15

) >=

3

3.25

3.27

45.0

3

3.29

41.1

9

46.0

8

3.24

3.26

43.2

1

3.11

43.2

0

3.30

43.1

7

46.0

7

2.14

2.13

3.27

20.1

2

20.1

3

1.27

20.1

5

3.13

1.19

20.1

4

42.0

6

1.11

1.12

1.15

4.13

1.16

1.28

1.17

FLD

CU

R @

40%

FLU

X41

.14

41.1

5FL

D C

UR

@70

% F

LUX

41.1

6FL

D C

UR

@90

% F

LUX

FLU

X/FI

ELD

LIN

EAR

IZA

TIO

N

CUR

REF

33.

12

FLU

X RE

F SU

M

3.15

CUR

REF

2

3.28

V RE

F 1

:= L

OCA

L R

EF 3

,if

loca

l mod

e;sc

aled

toN

OM

SUP

PLY

VOLT

(42.

06)

(EXC

ITAT

ION

: 15.

16 =

5)

Page 43: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-11

Control and Status WordsIn remote mode, the drive is controlled by the main control word and the auxiliary control words.The drive’s status is read from the main status word and the auxiliary status word.

Table 3.8/1: Main Control Word

Table 3.8/2: Auxiliary Control Word

Table 3.8/3: Auxiliary Control Word 2

droWlortnoCniaM )10.7(

tiB emaN noitcnuF

0 )N_1FFO(NOesolcdnadleif,snaftrats

rotcatnocniam

1 N_2FFO potstsaoc

2 N_3FFO potsycnegremerofdevreser

3 NUR ecnereferdetceleshtiwnur

4 OREZ_TUO_PMARdecrofsituptuopmardeepS

orezot

5 DLOH_PMAR deppotssignipmardeepS

6 OREZ_NI_PMARdecrofsitupnipmardeepS

orezot

7 TESERtluafaegdelwonkca

noitacidni

8 1_GNIHCNI)2.32(1deepstnatsnoC

detceles

9 2_GNIHCNI)3.32(2deepstnatsnoC

detceles

01 DNAMMOC_DILAVdrowlortnocniamezeerF:0dilavsidrowlortnocniaM:1

11 devreser )devreser(

21 devreser )devreser(

31 devreser )devreser(

41 devreser )devreser(

51 devreser )devreser(

droWlortnoCyrailixuA )20.7(

tiB emaN noitcnuF

0 GOLD_TRATSERton(reggolatadfotratseR

)elbaliava

1 REGGOL_GIRT gnireggirtreggolataD

2 SSAPYB_PMAR dessapybsipmardeepS

3 TUO_PMAR_LAB tuptuopmarfognicroF

4-_NO_EKARB_NYD

CPAgnikarbcimanydetavitca

5 devreser )devreser(

6 TNOCN_DLOHdeepsehtfognidloHrotargetnis’rellortnoc

7 LRTC_WODNIW detavitcalortnocwodniW

8 TNOCN_LABs’rellortnocdeepsfognicroF

tuptuo

9 DNAMMOC_CNYS dnammocgnisinorhcnys

01 ELBASID_CNYS delbasidsignisinorhcnys

11 YDR_CNYS_TESER ydaerdesinorhcnysteser

21 FER_HCNI_DEPMARottupnipmardeepshctiwS

FERHCNIDEPMAR )21.32(

31 )11.41(4TUO_GID 4tuptuolatigid

41 )41.41(5TUO_GID 5tuptuolatigid

51 )71.41(6TUO_GID 6tuptuolatigid

2droWlortnoCyrailixuA )30.7(

tiB emaN noitcnuF

0 7_TUO_GID 7tuptuolatigid

1 8_TUO_GID 8tuptuolatigid

2 1_TUO_GID DMCNOSNAF

3 2_TUO_GID DMCNODLEIF

4 3_TUO_GID DMCNOTNOCNIAM

7..5 devreser )devreser(

8 RID_EVIRD0 evitisopnoitceridevird:1 evitagennoitceridevird:

1etonees

9 TXE_DEEPS

0 ecnerefereuqrot:xam/nimotgnidrocca

rotceleseuqrotninoitaulave5dna4sedom

1 rellortnocdeepsecrof:euqrotnignidroccatuptuo

5dna4sedomrotceles

01ot

devreser )devreser(

51 devreser )devreser(

:1etoN ecitcategnoitceridevirddednammocehtfosegnahCybevirdgninnurafolasrever;NUR_YDRetatsehtniylno

.elbissoptonsitiblortnocsihtfosnaem:2etoN .tluafedera3OD...1ODrofsgnitteS

Page 44: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-12

Table 3.8/4: Main Status Word

Table 3.8/5: Auxiliary Status Word

droWsutatSniaM )10.8(

tiB emaN noitcnuF

0 NO_YDR rotcatnocehtesolcotydaer

1 NUR_YDR euqrotetarenegotydaer

2 FER_YDRgnitarepolortnoceuqrot

)gninnur(

3 DEPPIRT006SCDnitluaffonoitacidni

evirDitluM

4 N_ATS_2_FFO evitcaN_2FFOoN:1

5 N_ATS_3_FFO evitcaN_3FFOoN:1

6 DETIBIHNI_NO detibihninohctiwS

7 MRALAnimralafonoitacidni

evirDitluM006SCD

8 TNIOPTES_TAgnirotinomeulav.tca/tniopteS

ecnarelotehtni

9 ETOMERlacoL:0/lortnocetomeR:1

lortnoc

01 TIMIL_EVOBA)01.05(eulavdlohsertdeeps

dehcaer

11 devreser )devreser(

21 devreser )devreser(

31 devreser )devreser(

41 devreser )devreser(

51 devreser )devreser(

droWsutatSyrailixuA )20.8(

tiB emaN noitcnuF

0 YDAER_ATAD_GGOLsireggolatadfostnetnoC

elbadaer

1 WODNIW_FO_TUOsieulavlautcadeepSdenifedehtfoedistuo

wodniw

2-OC_POTS_GREME

TSAnoitcnufpotsycnegremE

deliafsah

3 devreser )devreser(

4 DELBASID_NO

NOgnikcolretnilanretxE2TIBIHNINOro1TIBIHNI-celesstupnilatigiddeRO(

)51.51dna41.51ybdetnurehttneverp

5 YDR_CNYSretnuocnoitisoP

sutatsydaersuonorhcnys

6 KCA_1XEF xeFts1foegdelwonkca

7 KCA_2XEF xeFdn2foegdelwonkca

8 devreser )devreser(

9 GNITIMILlangisees,gnitimilsievirD

30.8

01 LORTNOC_QROT dellortnoceuqrotsievirD

11 DEEPS_OREZ orezsilautcadeepsrotoM

21 DEEPS-FMEkcabdeefdeepsFME

LESBFDEEPSfidetceles1=)30.05(

31 MRALA_RO_TLUAF evirdfomralarotluaF

41 WSA_RID_EVIRDnoitceridevirdevitageN

evitca

51 GNISOLCER_OTUAcigolgnisolcerotua

detavitca

Page 45: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-13

Table 3.8/8: Digital outputs Armature converter mode (DCS600) Table 3.8/9: Digital outputs Field converter mode (DCF600)

Digital inputs/outputs

Depending on the drive modes there are differentpossibilities for digital inputs and outputs.

Table 3.8/6: Digital inputs Armature converter mode (DCS 600)

Table 3.8/7: Digital inputs Field converter mode (DCF 600)

stupnIlatigiD edomretrevnocerutamrA

tupnI langiS esu noitpircseD

1ID 1ID

elbarugifnoc→

nafretrevnoCKCA31.21nafrotoMKCA41.21

rotcatnocniaMKCA51.21POTSycnegremE61.21

tcennocsidlacirtcele31.511TIBIHNINO41.512TIBIHNINO51.51

rekaerbCDKCA81.51ekarbNYDKCA02.51

)pirt1rotom(noxilK81.82)pirt2rotom(noxilK52.82

2ID 2ID

3ID 3ID

4ID 4ID

5ID 5ID

6ID 6ID

7ID 7ID

8ID 8ID

neht)O/Ilacol(1=22.51LESDNAMMOCfiNUR=8ID;NO=7ID;teseR=6ID

stupnIlatigiD edomretrevnocdleiF

tupnI langiS esu noitpircseD

2ID TLOVREVO_KCA xifegatlovrevoegdelwonkcA

605/505FCDnoitcetorp

1ID 1ID

elbarugifnoc→

nafretrevnoCKCA31.21nafrotoMKCA41.21

rotcatnocniaMKCA51.21POTSycnegremE61.21

tcennocsidlacirtcele31.511TIBIHNINO41.512TIBIHNINO51.51

rekaerbCDKCA81.51ekarbNYDKCA02.51

)pirt1rotom(noxilK81.82)pirt2rotom(noxilK52.82

:etoN rof2IDtcelestonoD!snoitcnufeseht

3ID 3ID

4ID 4ID

5ID 5ID

6ID 6ID

7ID 7ID

8ID 8ID

neht)O/Ilacol(1=22.51LESDNAMMOCfiNUR=8ID;NO=7ID;teseR=6ID

stuptuOlatigiD edomretrevnocerutamrA

tuptuO langiS esu noitpircseD

1OD 1TUO_GID

elbarugifnoc→

yb.margorp/eerf 20.21DMCNOSNAF:tluafed

2OD 2TUO_GIDyb.margorp/eerf 50.21

DMCNODLEIF:tluafed

3OD 3TUO_GIDyb.margorp/eerf 80.21

NOTNOCNIAM:tluafedDMC

4OD 4TUO_GID yb.margorp/eerf 01.41

5OD 5TUO_GID yb.margorp/eerf 31.41

6OD 6TUO_GID yb.margorp/eerf 61.41

7OD 7TUO_GID yb.margorp/eerf 91.41

8OD 8TUO_GID yb.margorp/eerf 22.41

stuptuOlatigiD edomretrevnocdleiF

tuptuO langiS esu noitpircseD

1OD 1TUO_GID

elbarugifnoc→

yb.margorp/eerf 20.21DMCNOSNAF:tluafed

2OD 2TUO_GIDyb.margorp/eerf 50.21

DMCNODLEIF:tluafed

3OD 3TUO_GIDyb.margorp/eerf 80.21

NOTNOCNIAM:tluafedDMC

4OD 4TUO_GID yb.margorp/eerf 01.41

5OD 5TUO_GID yb.margorp/eerf 31.41

6OD 6TUO_GID yb.margorp/eerf 61.41

7OD 7TUO_GID yb.margorp/eerf 91.41

8OD 8TUO_GID yb.margorp/eerf 22.41

Page 46: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 3-14

Table 3.8/10: Analogue inputs Armature converter mode (DCS600)

Analogue inputs

Depending on the drive modes there are differentpossibilities for analogue inputs.

stupnIeugolanA edomretrevnocerutamrA

:hguorhtlangisrofdesulennahC

lennahC CATIA 1IA 2IA 3IA 4IA

ycaruccA 6904± 6904± 8402± 8402± 8402±

langiS

EUQROTNOITCERROC

LES_LAV_1IA1=61.31

ECNEREFERDEEPSTCELESDEEPSIA

5=71.31TCELESDEEPSIA

1=71.31TCELESDEEPSIA

2=71.31TCELESDEEPSIA

3=71.31TCELESDEEPSIA

4=71.31

DLEIF.TXE.KCARETICXE

LES_CXEF9=50.51

LES_CXEF01=50.51

LES_CXEF11=50.51

LES_CXEF21=50.51

LES_CXEF31=50.51

.PMET1.TOMTNEMERUSAEM

LES_IA_PMET_1TOM5...1=90.82

.PMET2.TOMTNEMERUSAEM

LES_IA_PMET_2TOM5...1=21.82

TLUAFHTRAEGNIROTINOM

LES_TLF_RUC_HTRAE1=91.82

DEEPSTNEMERUSAEM

EDOM_SAEM_DEEPS4=30.05

Page 47: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 4-1

4 Connection examples

Fig. 4.1/1: DCS 600 Armature current converter wiring diagram

4.1 Armature current converter DCS 600

CH

0

X96:

DO

8

12

X99:

12

X2:

45

X2:1

23

U1W

1V1

PEX1

:1

7

K3K1

L1L2

L3

400V

50H

z

F1

F3

K11

35

24

6

K31

3

24

L1L3

M ~

T3

F21 2

3 4

F6

2 1

4 3

6 5

2 1

4 3

6 5

2 1

4 3

6 5

UV

W

M 3~

K6

F7

1 2

3 4K5

F4F5

1 2

1 2

T2

111 10 9 8 7 6 5 4 3 2

690V

660V

600V

575V

525V

500V

450V

415V

400V

380V

12 13 14

115V

230V

K16

K16

K11

F6

K6K5

X2:4

X2:

5

K10

500V

460V

415V

400V 36

5V35

0V26

5V25

0V 90V

60V

30V

8 7 6 5 4 3 2 1

12 11 10 9

X33

PAN

ELC

DP

312

C 1

D 1

X1:

53

AIT

ACA

I1A

I2A

I3AI

4+1

0V-1

0VAO

1AO

2IA

CT

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

+48V

DO

1D

O2

DO

3D

O4

DO

5D

O6

DO

7_

__

__

++

++

+

T

TM

0V0V

0V0V

0V

X3:

12

34

56

78

910

X4:

12

34

56

78

910

X6:

12

34

56

78

910

X7:

12

34

56

78

1...1

0X5

:+

_+

_

+ _

K1

K6

K5

K11

K10

S4 56

K15

K12

* [K13

]

K13K1

2

CH

2

CH

3

K12

K15

K16

K15

DC

S 60

0

AMC-DC 2

Con

trol b

oard

(CO

N-2

)

Pow

er s

uppl

y(P

OW

-1)

Con

verte

rm

odul

e

ELEC

TR.

DIS

CO

N-

NEC

T

EMER

.ST

OP

Fiel

d ex

cite

run

it (F

EX-1

/2)

depe

ndin

g on

the

unit

type

(C1,

C2,

A5,

C4)

the

pola

ritie

s ar

e sh

own

for m

otor

ing

if th

ere

are

inte

rmed

iate

term

inal

s

e.g.

Pre

ssur

e sw

itch

at C

4 m

odul

e

* if c

onta

ctor

rela

y K

13 is

use

d

If SD

CS-

IOB-

2 is

in u

se K

10,

K11

and

K12

are

not

nece

ssar

y

Page 48: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 4-2

Fig. 4.2/1: DCF 600 Field supply converter wiring diagram

4.2 Field supply converter DCF 600N

ote:

In c

ase

the

supp

ly v

olta

ge fo

r the

exc

itat

ion

is sw

itch

ed o

n th

e pr

imar

y si

de o

f its

supp

lytr

ansf

orm

er a

ddit

iona

l ove

rvol

tage

pro

tec-

tion

is r

equi

red.

Ple

ase

cont

act A

BB

!

CH

0

X96:

DO

8

12

X99:

12

X2:

45

X2:1

23

U1W

1V1

PEX4

:1

2

K1

L1L2

L3

400V

50H

z

F1 K11

35

24

6

L1

M ~F21 2

3 4

1 2

3 4K5

F4F5

1 2

1 2

T2

111 10 9 8 7 6 5 4 3 2

690V

660V

600V

575V

525V

500V

450V

415V

400V

380V

12 13 14

115V

230V

K16

K16

K5

X2:4

X2:

5

K10

X33

PAN

ELC

DP

312

C 1

D 1

X11

X12

AIT

ACA

I1A

I2A

I3AI

4+1

0V-1

0VAO

1AO

2IA

CT

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

+48V

DO

1D

O2

DO

3D

O4

DO

5D

O6

DO

7_

__

__

++

++

+

M

0V0V

0V0V

0V

X3:

12

34

56

78

910

X4:

12

34

56

78

910

X6:

12

34

56

78

910

X7:

12

34

56

78

1...1

0X5

:+

_+

_

K1

K5

K11

K10

S4 56

K12

* [K1

3]

K13K1

2

CH

2

CH

3

K12

K16

DC

F 50

6D

CF

600

AMC-DC 2

Con

trol b

oard

(CO

N-2

)

Pow

er s

uppl

y(P

OW

-1)

Fiel

d su

pply

conv

erte

rm

odul

e

ELEC

TR.

DIS

CO

N-

NEC

T

depe

ndin

g on

the

unit

type

(C1,

C2)

* if c

onta

ctor

rela

y K

13 is

use

d

If S

DC

S-I

OB

-2

is in

use

K10

, K

11 a

nd K

12

are

not

nece

ssar

y

Ove

rvol

tage

prot

ectio

n

K11

= A

larm

Page 49: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 4-3

Notes

Page 50: DCS Thyristor Power Converters for DC Drive Systemsdownload.gongkong.com/file/company/abb/DCS600_Sysdes.pdfDCS Thyristor Power Converters for DC Drive Systems 25 to 5150 A System Description

II F 4-4

Since we aim to always meet the latest state-of-the-artstandards with our products, we are sure you willunderstand when we reserve the right to alter particularsof design, figures, sizes, weights, etc. for our equipmentas specified in this brochure.

3AD

W 0

00 0

72 R

0401

RE

V D

08_2

002

ABB Automation Products GmbHPostfach 118068619 Lampertheim • GERMANYTelefon +49(0) 62 06 5 03-0Telefax +49(0) 62 06 5 03-6 09www.abb.com/dc

*072R0401A2340000**072R0401A2340000*