data and installation mimic led driver...

6
These instructions cover the Mimic LED Driver Card (S4-34600) and Connection converter (S4-34494), which are designed to be used in Custom panels. The Mimic LED Driver connects to a Master Repeat Card which in turn connects to a loop circuit of a Vigilon fire system. Each Mimic LED Driver Card can control up to 768 LEDs and this leaflet covers the connection of up to 2 Mimic LED Driver Cards. The Connector converters that holds the terminals for wiring LEDs. Custom Panel LED selection Only use high efficiency Red, Amber or Green LEDs with a Mimic LED Driver Card. " Do not use Blue or White LEDs as these are not suitable for use with the Mimic LED Driver Card. Compatibility The Mimic LED Driver Cards are compatible for use in Vigilon system where the Control panel has specific MCC/MCB software, see technical data section. The Master Repeat Card is configured using the Mimic Configuration Tool. 4188-951_issue 2_01/12_Part 1_Mimic LED driver 1 Data and Installation Mimic LED Driver Card S4-34600 & S4-34494 by Honeywell S4-34600 Mimic LED Driver Card S4-34494 Connection Converter 26-way 300mm ribbon cable 20-way 200mm Flat flexible cable B A 01 L1 02 L2 0C LC P9 L N P17 BT+ + RS485 0V 24V - WRITE PROTECT BUZZER DISABLE P8 DANGER DO NOT REMOVE L N P5 FS2 FS4 P16 P4 P2 P1 SW3 PB2 WD1 P14 P7 USB FS3 2A(QB) RESET Mimic Repeat Card P3 P2 P1 P16 P15 P14 P13 P12 P11 P4 OUT Mimic LED Driver Card 2 WARNING Removal of cover exposes live parts DANGER P3 P2 P1 P16 P15 P14 P13 P12 P11 P4 OUT Mimic LED Driver Card 1 Connector Converter 6 Connector Converter 1 LED Bank 1 (768 LEDs) LED Bank 2 (768 LEDs) 2 4 6 10 8 12 14 16 18 20 22 26 24 1 3 5 9 7 11 13 15 17 19 21 25 23 2 4 6 10 8 12 14 16 18 20 22 26 24 1 3 5 9 7 11 13 15 17 19 21 25 23 2 4 6 10 8 12 14 16 18 20 22 26 24 1 3 5 9 7 11 13 15 17 19 21 25 23 2 4 6 10 8 12 14 16 18 20 22 26 24 1 3 5 9 7 11 13 15 17 19 21 25 23 Maximum of up to 1536 LEDs can be controlled with 2 Mimic LED Driver Cards 01 L1 02 L2 0C LC P9 L N P16 Custom Panel Backbox Door 20 way cable 26 way cable Vigilon device loop To mains fused spur unit Address P3 Address P3 B + + - - No link fitted One link fitted * * * No links are fitted here for this application. Links set LED board orientation. A B

Upload: others

Post on 12-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Data and Installation Mimic LED Driver Cardgentexpert.co.uk/downloads/Addressable/Loop_Devices/A3_mimic/4188-951.pdf · These instructions cover the Mimic LED Driver Card (S4-34600)

These instructions cover the Mimic LED DriverCard (S4-34600) and Connection converter(S4-34494), which are designed to be used inCustom panels.

The Mimic LED Driver connects to a Master RepeatCard which in turn connects to a loop circuit of aVigilon fire system. Each Mimic LED Driver Cardcan control up to 768 LEDs and this leaflet coversthe connection of up to 2 Mimic LED Driver Cards.

The Connector converters that holds the terminalsfor wiring LEDs.

Custom Panel

LED selection

Only use high efficiency Red, Amber or GreenLEDs with a Mimic LED Driver Card.

� Do not use Blue or White LEDs as these arenot suitable for use with the Mimic LED Driver Card.

Compatibility

The Mimic LED Driver Cards are compatible for usein Vigilon system where the Control panel hasspecific MCC/MCB software, see technical datasection. The Master Repeat Card is configuredusing the Mimic Configuration Tool.

4188-951_issue 2_01/12_Part 1_Mimic LED driver 1

Data and Installation

Mimic LED Driver CardS4-34600 & S4-34494

by Honeywell

S4-34600Mimic LED Driver Card

S4-34494Connection Converter

26-way300mm ribbon cable

20-way200mm Flat flexible cable

B

A

01 L1 02 L20C LC P9L NN

P17

DANGER

BT

+B

T-

+RS485

0V 24V-

WRITE PROTECT

BUZZERDISABLE

P8

DANGERDO NOTREMOVE

L N

P5

FS2

FS4P16

P4

P2

P1

SW3

PB2

WD1P14P7USB

FS32A(QB)

RESET

Mimic Repeat Card

P3

ADDRESS

P2BOARD

UPSIDEDOWN

ROTATE

P1

P5

IN

P16P15P14P13P12P11

P4

OUT

MimicLED DriverCard 2

WARNINGRemoval of

cover exposeslive partsDANGER

P3

ADDRESS

P2BOARD

UPSIDEDOWN

ROTATE

P1

P5

IN

P16P15P14P13P12P11

P4

OUT

MimicLED DriverCard 1

ConnectorConverter 6

ConnectorConverter 1

LED Bank 1 (768 LEDs)LED Bank 2 (768 LEDs)

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523Maximum of up to1536 LEDs can becontrolled with2 Mimic LED DriverCards

01 L1 02 L20C LC

P9L N

P16

Custom Panel

Backbox

Door 20 waycable

26 waycable

Vigilon device loop To mains fused spur unit

Address

P3

Address

P3

B

+ +- -

No link fittedOne link fitted

* *

* No links are fitted here

for this application.Links set LEDboard orientation.

A

B

Page 2: Data and Installation Mimic LED Driver Cardgentexpert.co.uk/downloads/Addressable/Loop_Devices/A3_mimic/4188-951.pdf · These instructions cover the Mimic LED Driver Card (S4-34600)

Mounting

It is recommended that the Mimic LED Driver Cards are mounted inside a Custom panel using suitable PCBstandoffs, there are 6-3mm PCB fixing holes provided on the card. The Connection converters are mountedon 35mm DIN rails. The LEDs and associated wiring must also be contained inside the same enclosure formechanical protection.

� The designer of the Custom panel in which the Mimic LED Driver Cards, Connection converters and LEDs aremounted must ensure the panel enclosure is EMC compliant and is CE marked.

Cables

The internal connection from the Connection converter to each LED inside the Custom panel is made usinga standard PVC cable. Each LED can be positioned a maximum of up to 3m cable distance away from theterminals of a Connection Converter.

For recommendations on loop cable type refer to the manual supplied with the Vigilon control panel.

Earth

The Custom panel must be earthed. The loop cable screen must be continued through the Custom panel,whether the earth is connected to the Custom panel or not.

�Do not use any part of building structure for earthing.

Mains supply

The mains supply to the Custom panel must be via an unswitched 5A fused spur unit. A disconnect devicemust be provided to disconnect both poles and must have a minimum gap of 3mm. The disconnect deviceshould be available as part of the building installation and must be easily accessible after installation iscomplete.

�Before removal of any card or disconnection of any cable from the Custom panel ensure both mains and battery supplies

are disconnected.

Battery supply

Data and Installation Mimic LED Driver Card

2 4188-951_issue 2_01/12_Part 1_Mimic LED driver

FS2

3.15A(T)Ceramic

(Anti Surge)

Battery Fuse

BT

+B

T-

+RS485

0V 24V-

BUZZERDISABLE

DANGERDO NOTREMOVE

P5

FS2P1

SW3

PB2

WD1P14P7USB

FS32A(QB)

DANGER

WARNINGRemoval of

cover exposeslive parts.

+ +- -

Master Repeat Card

Black

Red

Battery lead

Link lead

6V 7Ah Battery6V 7Ah Battery

Leave the final connection of the battery for the Servicing organisation.This connection is made during power up and commissioning.

You can use 1 - 12V 7Ah battery (VSRPT-BATT)or 2 - 6V 7AH batteries as shown.(VSRPT-BATT-A3)

Page 3: Data and Installation Mimic LED Driver Cardgentexpert.co.uk/downloads/Addressable/Loop_Devices/A3_mimic/4188-951.pdf · These instructions cover the Mimic LED Driver Card (S4-34600)

To connect multiple Mimic LED Driver Cards

You can daisy chain up to two Mimic LED driver cards to the Master Repeat Card using the 20 way flat

flexible cable .

How to connect a flat flexible cable

Hold the locking tab by the edges and lift it upwards a little� and insert the flat flexible cable� into the

socket. Ensure the cable contacts are on the opposite side to the locking tab. Push down the locking tab�to lock the flat flexible cable.

How to disconnect a flat flexible cable

Hold the locking tab by the edges at positions �and lift it upwards one side at a time� to disengage the flat

flexible cable. Then remove the cable� from the socket.

To connect the ribbon cables from Mimic LED Driver card to Connection converters

Connect one end of the 26 way ribbon cable to the IDC header on the Mimic LED Driver card (P11) andthe other end to a Connection converter. The Mimic LED Driver card can accommodate up to 6 - 26 wayribbon cable for wiring LEDs via 6 Connection converters.

4188-951_issue 2_01/12_Part 1_Mimic LED driver 3

Mimic LED Driver Card Data and Installation

P13P4

OUT

P5

IN

Master Repeat Card

P4

OUT

P5

IN

Mimic LED DriverCard 1

To connect a flat flexible cable

P13P13

To disconnect a flat flexible cable

Mimic LED DriverCard 2

B B

A

B

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

ConnectorConverter 1

P16P15P14P13P12P11

Mimic LED Driver Card

26 way ribbon cable

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

ConnectorConverter 2

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

26 way ribboncablesConnector

Converter 6

Connection to 128 LEDsConnection to 128 LEDsConnection to 128 LEDs

A

Page 4: Data and Installation Mimic LED Driver Cardgentexpert.co.uk/downloads/Addressable/Loop_Devices/A3_mimic/4188-951.pdf · These instructions cover the Mimic LED Driver Card (S4-34600)

Relationship between Terminals and external LEDs

Technical data

S4-34600 Mimic LED Driver Card

Dimensions 160mm height x 150mm width x 30mm depth

Card weight 150g

Storage temperature -30ºC to +70ºC

Operating temperature -10ºC to +60ºC

Relative Humidity Up to 95% - Temperature +5ºC to +45°C (Non condensing)

LED output perMimic LED Driver Card

Up to 768 high efficiency LEDs can be driven by a Mimic LED Driver Card

Each LED can be 3m cable distance away from the Connection converter.Use only high efficiency Red, Amber or Green LEDs.

Vigilon Panelcompatibility

Fully compatible with LPC = V3.93 / V4.35 & MCC/MCB = V3.94 / V4.37.

Data and Installation Mimic LED Driver Card

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof withoutobligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk

Telephone: +44 (0) 116 246 2000 Technical support: www.gentexpert.co.uk Fax (UK): +44 (0)116 246 2300

4 4188-951_issue 2_01/12_Part 1_Mimic LED driver

by Honeywell

Do not dispose of with your normal household waste.Do not burn.

WEEE Directive:At the end of their useful life, the packaging,product and batteries should bedisposed of via a suitable recycling centre.

At the end of their useful life, the packaging,product and batteries should be disposed ofvia a suitable recycling centre and inaccordance with national or local legislation.

2 4 6 108 12 14 16 18 20 22 2624

1 3 5 9

711 13 15 17 19 21 2523

LEDRef

+ - LEDRef

+ - LEDRef

+ - LEDRef

+ - LEDRef

+ - LEDRef

+ - LEDRef

+ - LEDRef

+ -

1 26 8 9 25 8 17 24 8 25 23 8 33 22 8 41 21 8 49 20 8 57 19 8

2 26 7 10 25 7 18 24 7 26 23 7 34 22 7 42 21 7 50 20 7 58 19 7

3 26 6 11 25 6 19 24 6 27 23 6 35 22 6 43 21 6 51 20 6 59 19 6

4 26 5 12 25 5 20 24 5 28 23 5 36 22 5 44 21 5 52 20 5 60 19 5

5 26 4 13 25 4 21 24 4 29 23 4 37 22 4 45 21 4 53 20 4 61 19 4

6 26 3 14 25 3 22 24 3 30 23 3 38 22 3 46 21 3 54 20 3 62 19 3

7 26 2 15 25 2 23 24 2 31 23 2 39 22 2 47 21 2 55 20 2 63 19 2

8 26 1 16 25 1 24 24 1 32 23 1 40 22 1 48 21 1 56 20 1 64 19 1

65 18 8 73 17 8 81 16 8 89 15 8 97 14 8 105 13 8 113 12 8 121 11 8

66 18 7 74 17 7 82 16 7 90 15 7 98 14 7 106 13 7 114 12 7 122 11 7

67 18 6 75 17 6 83 16 6 91 15 6 99 14 6 107 13 6 115 12 6 123 11 6

68 18 5 76 17 5 84 16 5 92 15 5 100 14 5 108 13 5 116 12 5 124 11 5

69 18 4 77 17 4 85 16 4 93 15 4 101 14 4 109 13 4 117 12 4 125 11 4

70 18 3 78 17 3 86 16 3 94 15 3 102 14 3 110 13 3 118 12 3 126 11 3

71 18 2 79 17 2 87 16 2 95 15 2 103 14 2 111 13 2 119 12 2 127 11 2

72 18 1 80 17 1 88 16 1 96 15 1 104 14 1 112 13 1 120 12 1 128 11 1

Terminal numbers on aConnection converter

LED Ref 1

Connection Converter

LED Ref 34

Page 5: Data and Installation Mimic LED Driver Cardgentexpert.co.uk/downloads/Addressable/Loop_Devices/A3_mimic/4188-951.pdf · These instructions cover the Mimic LED Driver Card (S4-34600)

The illumination of LEDs connected to the Connection Converters of a Mimic LED Driver Card isdetermined by the configuration held at the Master Repeat Card (MRC).

The following information show how to load a LED Driver template file and associate LED shapes withterminals of Connection converter and configure each LED shape with a system event using the MimicConfiguration tool.

How to load the 'Mimic LED Driver template.s19' file

The Master Repeat Card is configured using the Mimic Configuration Tool. The tool requires an 'LEDDriver template' file to be loaded to configure a Mimic LED Driver Card connected to the MRC. To open

the template file follow steps� to�.

How Mimic LED ‘Shapes’ relate to the Mimic LED Driver Card and Terminals

The 'LED Driver template' file has defined LED shapes of each possible LED that can be connected to theConnection converters associated with a Mimic LED Driver Card.

4188-951_issue 2_01/12_Part 2_Mimic LED driver 1

Commissioning information

Mimic LED Driver CardS4-34600 & S4-34494

by Honeywell

Do not alter these settings as they arepre defined in the LED Driver template file.

7 P16_24_8

Shape number 7

Related to IDC Connector P16on the Mimic LED Driver Card

IDC connector P16 is ribboncabled to Connection connectorand its terminals:Terminal 24 is + LEDTerminal 8 is - LED

When the linked function is activeyou can define the LED action to:

P13

Master Repeat Card

P4

OUT

P5

IN

Mimic LED DriverCard 1

P15P13

P14

P11

P12

Connectionconverter 1

Connectionconverter 6

Address

P9

2 4 6 108

12 14 16 18 20 22 2624

1 3 5 97 11 13 15 17 19 21 2523

Connection Converter

P16

From the directoryselect ‘ ’to load the configuration templatefor the .

DataFiles

LED Driver card 1

LED Driver template.s19

If two LED Driver Cards are fitted insidea Custom panel, both daisy chainconnected to a ,then you will need another

.

Master Repeat CardLED Driver

template file.

Page 6: Data and Installation Mimic LED Driver Cardgentexpert.co.uk/downloads/Addressable/Loop_Devices/A3_mimic/4188-951.pdf · These instructions cover the Mimic LED Driver Card (S4-34600)

How to link Mimic LED ‘Shapes’ to system events

Each used LED shape must be linked with a system event, such as:

� Device fire

� Device fault

� Channel fire

� Channel fault

� Zone fire

� Zone fault

� Card fire

� Card fault or

� Supervisory Command Build.

Below is a typical example that shows how a shape can be linked to a zone:

For full information on configuration see the instructions supplied with the Mimic Configuration tool.

Test

Test the Custom panel and ensure it gives the correct indication for the configured Vigilon System event.

Commissioning information Mimic LED Driver Card

Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof withoutobligation to notify any person of such revisions of changes.

Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk

Telephone +44 (0) 116 246 2000 Fax (UK): +44 (0)116 246 2300

2 4188-951_issue 2_01/12_Part 2_Mimic LED driver

by Honeywell

Drag and drop an LED ‘Shape’ onto thea system event in the system tree. Thisexample shows being droppedonto so the two are linked.

Shape 5Zone 5,

The LED Shape here is linked to

.

So when has a fire event then the LED connectedto terminals and will be lit (On).Note also the is associated withIDC Connector on the

5 P16_26_8Zone 5 - Fire

Zone 526 8

P16

Connection ConverterConnection Converter

Mimic LED Driver Card.