Data AireMini Ceiling Systems1, 1.5, 2, and 2.5 ton capacities
R-407C
ISO 9001 Certifi ed
3
Data Aire®
… the pioneer and builder of the
most complete line of
precision cooling equipment
Data Aire’s fi rst precision cooling system was developed by data processing engineers who sought optimum
environmental conditions for early computers. It was clear that “people comfort” air conditioning system
were unable to meet the environmental requirements of computers and data processing equipment. Precision
environmental control equipment with high sensible cooling ratios was a necessity. Problems with paper
sticking , head crash, and static electricity were eliminated. Humidity fl uctuation were controlled saving
possible electrical and mechanical failures and more importantly – Downtime. Data Aire’s innovative
response to the challenge of eliminating problems within the computer room environment was the start of
wide use precision cooling.
As in the past, Data Aire is meeting today’s challenge of not only the computer room but also the ever
expanding telecommunications industry where precision cooling is vital to our everyday communications.
Telecommunication equipment requires a controlled environment with clean and properly distributed air.
As in the computer room, the environment must be precisely controlled – 24 hour a day, 365 days a year.
Data Aire produces solutions. We have offered environmental control solutions to meet specifi c needs in
the smallest of places and in areas of thousands of square feet. We are prepared to assist you, your in-house
engineering department, consulting engineer, or construction department in defi ning the proper solutions
and bringing them to a predefi ned outcome.
Data Aire is committed to being the supplier of choice for environmental process cooling with fl exibility,
reliability, and expertise required to meet our customer’s needs. To be successful, it is essential to be
creative and use our resources to their fullest capabilities. The Data Aire goal is to benefi t the employees,
partners, and most of all – our customers with honesty and integrity.
Data Aire Delivers!
4
Design Features .................................................................................................6Options ..............................................................................................................8Confi guration Drawings Package Systems ..............................................................................9 Split Systems .................................................................................11Performance Data Air and Water Cooled ........................................................13Electrical Data Air Cooled ......................................................................................16 Water Cooled..................................................................................19Performance Data Chilled Water .....................................................................20Electrical Data Chilled Water ..........................................................................21Dimensional and Component Drawings .........................................................22Guide Specifi cations ........................................................................................38Weights ............................................................................................................42
Mini Ceiling System1, 1.5, 2, and 2.5 ton
Air and Water Cooled and Chilled Water
R-407C
TABLE OF CONTENTS
5
PRECISION COOLING Computers, batteries, electronic and telephone equipment have special comfort requirements. These spaces require air which is clean with precisely controlled temperature and humidity. Data Aire Mini Ceiling SystemsTM are de-signed with this in mind. Building or “people comfort” systems simply are not designed to meet demands.
PEOPLE COMFORT
Although “thru-the-wall” systems may help cool your staff, they still fall short where precision cooling is needed. Data Aire’s Mini Ceiling Systems are the practical answer. It will keep your equipment on-line and will add to your personnel’s comfort as well.
PERFORMANCE, LOW COST
Engineered and built by the people who introduced com-puter room air conditioning, the Mini Ceiling unit offers quality at a competitive price. Every Mini Ceiling System comes with Data Aire’s commitment to excellence which began with our fi rst air con-ditioner and has been tested and proven for more than forty years.
Units shown with optional side drain connections.
DATA AIRE DELIVERS
Data Aire’s reputation for speedy delivery applies with special emphasis to the Mini Ceiling System. Units are shipped within a few days from receipt of order. Call your nearest Data Aire representative for details.
DATA AIRE, FOR ALL THE RIGHT REASONS!
6
CONTROLS
Precise temperature regulation is provided by a built-in con-trol system. All electrical components, including capacitors, contactors, relays, and control transformers are pre-wired and contained in an electrical box that is hinged and swings out for easy access and servicing. A factory installed micro-switch will disable the unit prior to condensate pan overfl ow should the drain line become plugged with debris. Each unit is shipped with a thermostat and subbase as standard. A red indicator light is unit mounted to indicate a condensate prob-lem. Units with the optional Mini Data Alarm Processor-IITM have a high condensate water level alarm standard.
CABINET
Units are designed with a supply and return air plenum that fi ts in a 2 ft x 4 ft opening of a standard dropped ceiling grid. The fi eld installed supply and return air plenum is constructed of aluminum and fi nished with off-white textured paint. Both the supply and return air grilles are hinged for easy access when replacing fi lters. A 2 inch, 30% effi cient fi lter (based on ASHRAE Std. 52.1-1992) is provided behind the return air grille. Mini Ceiling Systems are constructed with tubular steel frames for strength and service access. Removable pan-els of galvanized steel are lined with 1/2 inch thick, closed cell insulation for quiet and effi cient operation.
EVAPORATOR SECTION
The evaporator coil contained in each unit is constructed with copper tubes and aluminum fi ns mounted in a stainless steel drain pan. The drain pan is made with a bottom drain connection and installed in a manner that provides a positive drain to prevent standing water in the condensate pan. The refrigeration circuit includes a scroll compressor with inter-nal overload protection and crankcase heater. The circuit includes an expansion valve with an external equalizer, fi lter drier, sight-glass, and high and low pressure safety switches. The high and low pressure safety switches are connected
to the refrigerant system with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnecessary.
The blower assembly is a draw-through type with a cen-trifugal, forward curved, double width, double inlet blower confi guration engineered for quiet, reliable operation. The belt driven variable pitch drive provides adjustable air fl ow capability to match the requirements of the controlled space. The draw-through design insures even distribution across the coil, low internal cabinet losses, and static sealing of the fi lter section. The motor has internal overload protection and is mounted on an
SELF-CONTAINED UNITS
Air Cooled - The cabinet houses the evaporator section, evaporator blower assembly, fi lter section (located in air distribution plenum), and the condenser coil. The condenser coil is constructed of copper tubes and aluminum fi ns. The condenser blower section is fi eld installed. The condenser fan is double inlet, double width, with direct drive type two-speed motor that is controlled with a temperature operated switch. The condenser blower motor electrical connection is through a factory wired plug.
Water Cooled - The cabinet houses the evaporator section, evaporator blower assembly, and fi lter section (located in air distribution plenum). In addition, a high effi ciency plate fi n condenser with head pressure activated 2-way water regulat-ing valve is built into the refrigeration system and is contained in the evaporator section. The capillary tube connection from the water regulating valve to the refrigerant system is con-nected with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnecessary.
Chilled Water - All components are housed within the cabi-net. Chilled water units utilize an existing chilled water loop. Chilled water fl ow is controlled by a 2-way valve for accurate and economical temperature control and dehumidifi cation. The maximum operating water pressure is 150 psi.
MINI CEILING SYSTEMSTM
1, 1.5, 2, and 2.5 ton capacities • Air Cooled • Water Cooled • Chilled Water
Data Aire’s Mini Ceiling Series is the perfect environmental control system for small computer centers, electronic, telephone, and battery rooms, or wherever spot cooling may be necessary and space is a problem. While vertical supply/return air units are designed to fi t in a 2 ft x 4 ft standard T-bar ceiling grid space, hori-
zontal units hang in the ceiling space with duct work connected to supply and return connections. The system offers an unsur-passed combination of features and options along with a high standard of performance. Mini Ceiling Systems are available as air cooled, water cooled, or chilled water systems with a variety of return and supply air arrangements. Air cooled can be specifi ed as packaged indoor units or split systems with either remote outdoor condensers or condensing units.
7
SPLIT SYSTEMS
Air cooled systems are available with an outdoor condensing unit or remote air cooled condenser.
Remote Outdoor Condensing Unit - The outdoor condensing unit contains the scroll compressor, sight-glass, fi lter drier, high and low pressure safety switches, and condenser coil. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The condenser coil is constructed with copper tubes and alumi-num fi ns. Air discharge is vertical. The condenser fan is variable speed for head pressure control down to -20° F. The capillary tube connection from the fan speed control to the refrigerant sys-tem is connected with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnec-essary. Field piping and wiring is required from the condensing unit to the indoor evaporator section.
Remote Outdoor Air Cooled Condenser - Condensers are in-dustrial duty design with galvanized corrosion resistant housing, aluminum fi nned/copper tube coils, coated fan guard, energy ef-fi cient, thermally protected motor, and variable fan speed control with an integral factory wired and tested control panel. The capillary tube connection from the fan speed control to the re-frigerant system is connected with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Air discharge is vertical. Field piping and wiring is required from the condenser to the indoor compressor/evaporator section.
Mini Ceiling Systems - OPTIONS
Mini Data Alarm Processor-II - The microprocessor based Mini Data Alarm Processor-II is wall mounted and has a single row, 16 character liquid crystal display (LCD) in clear vernacular format. The Mini Data Alarm Processor-II not only controls and monitors your room’s temperature, humidity, air fl ow, and cleanliness, but also provides alarm history and an automatic self-test of the microprocessor system start-up. Multiple messages will be displayed by automatically scroll-ing from each message to the next. Multiple alarms will be displayed sequentially in order of occurrence.
Each Mini Data Alarm Processor-II is shipped with 25 feet of cable for fi eld connection, (additional cable is available). Con-tact factory for cable lengths in excess of 75 feet.
For full details on the Mini Data Alarm Processor-II, see product brochure.
Operation - Unit on/off operation is controlled by a slide switch and push button control switches which allow menu se-lection for programming, operational information, diagnostics, and historical data. A password feature prevents unauthorized access. Menu programmed information for basic system opera-tion and alarm parameters is nonvolatile.
Programmable Functions/Monitoring - The user friendly switch permits step-by-step programming and display of the following functions:
• Temperature setpoint (60-80° F, 15.6-26.7° C) • Temperature sensitivity (+1 to + 5° F or .5 to 2.7° C, in 0.1° increments) • Humidity setpoint (30-70% RH) • Humidity sensitivity (+1 to +15% RH in 0.1% increments) • Temperature alarm points (50-90° F, 10-32.2° C) • Humidity alarm points (10-90% RH) • Unit start time delay • Interstage time delay • Password 1st level • Password 2nd level • Audio alarm level • Restart mode • Firestat trip temperature
• Local alarm function
Normal functions are monitored and displayedon the LCD and include, in addition to theabove set points, the following:
• Current temperature (°F or °C) • Current humidity (% RH) • Cooling • Reheat • Humidifi cation • Dehumidifi cation• • Date and time
Alarms - Alarm conditions are monitored on the LCD and are enunciated by an audible alarm. The alarm silence button will quiet the audible alarm but the display will continue to indicate the alarm condition until the problem is corrected.
The following alarms are standard:
• High temperature • Low temperature • High humidity • Low humidity • Compressor high pressure • Compressor short cycle • High condensate water • Firestat tripped • No air fl ow alarm • Humidity sensor failure • Temperature sensor failure
Historical Data - The current temperature and humidity, with minimum and maximum readings for the last 24 hours of operation can be recalled and displayed. Alarm history of the last fi ve alarms is maintained in sequential order.
Diagnostics - Automatic and manual diagnostics sequences simplify troubleshooting.
8
Site Monitoring
DARA-4 (Data Aire Relay Autochangeover)Controls up to four Mini Ceiling units using a dry set of re-lay contracts. The DARA-4 provides unit rotation, backup capacity and the ability to interface with most BMS systems.
Unit Options
Remote Mounted Temperature andHumidity Sensors
Temperature and humidity sensors are provided in a wall mounted plastic case for remote sensing of temperature and humidity. Standard unit sensors are removed. Requires fi eld wiring of (fi eld provided) shielded cable. Remote temperature and humidity sensors option only available when used with the Mini Data Alarm Processor-II.
Steam Generator Humidifi er
The steam generator humidifi er eliminates air contamination caused by mineral deposits. The totally self-contained system includes a quick change, disposable cartridge, and automatic fl ush cycle. When steam generator humidifi er option is se-lected, a Mini Data Alarm Processor-II is required.
Electric Reheat
Low-watt density fi nned tubular sheathed coils are constructed of stainless steel and provide ample capacity to maintain room dry bulb conditions on a call for dehumidifi cation. Low-watt density coils eliminate ionization associated with open wire electrical resistance heating. Electric reheat is available in 2, 4, or 5 kW capacities, shipped factory installed with high limit cutout.
Low Ambient Control Damper
A low ambient control damper is available for use with ducted outside condenser air. The low ambient control damper kit is fi eld installed and consists of a 14” x 14” damper section and head pressure operator. The low ambient control damper al-lows unit to operate down to -30° F (-34.4° C). The capillary tube connection from the head pressure control to the refrig-erant system is connected with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnecessary.
Condensate Pumps
Condensate pumps can be provided for fi eld mounting. Pump capacity is 60 GPH at 8 feet of head. Field installed con-densate pumps require either separate 110 or 230 volt power source. The pump body should be placed exterior to the unit. Option 210, side mounting kit, is available for easy installation.
Horizontal, Front, or Side Supply Air
Units may be ordered with optional horizontal supply air confi gurations of front or either side. Optional supply air converts unit for ducted supply air connection.
Side Return Air
Units may be ordered with optional side return consisting of a factory modifi ed fl anged for ducting return air. Optional side return air converts unit for ducted return air connection. An additional option provides ceiling mounted return air fi lter grille, ceiling mounted return air fi lter box with hinged grille, and fi lter for duct connection. Filter included with this option is a 20” x 20” x 2” deep, 30% effi cient (based on ASHRAE Std. 52.1-1992) pleated fi lter.
Extended Compressor Warranty
Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs.
9
CONFIGURATION VERSATILITY
Data Aire Mini Ceiling Systems allow for a wide variety of supply and return options capable of satisfying the most demanding installation requirements.
PACKAGED SYSTEMSStandard Confi guration - is provided with one ducted attachment, the condenser air out from the end of the unit with fl ange. Condenser air intake is supplied from the side and top. Evaporator return air is supplied from below and the evaporator supply air is returned to the space below.
Mini Ceiling Systems with non-ducted condenser supply air
Ducted alternate end supply air
Shown with option 260
Ducted alternate return air and alternate end supply air
Shown with options 260 and 263
Ducted alternate front air supply
Shown with option 261
Ducted alternate rear air supply
Shown with option 262
10
Ducted alternate end supply air
Shown with option 260
PACKAGED SYSTEMSMini Ceiling Systems with non-ducted condenser supply air
PACKAGED SYSTEMSMini Ceiling Systems with fl ange for condenser supply air
Standard Confi guration - has fl ange for condenser air intake and condenser discharge air. Evaporator re-turn and supply air are from the space below.
Ducted condenser air intake
Shown with options 262 and 263
Ducted alternate return air andalternate rear supply air
Shown with options 261 and 263
Ducted alternate return air andalternate frontsupply air
Shown with options 261 and 263
Ducted alternate return air and alternate front supply air
11
CONFIGURATION VERSATILITY continued
PACKAGED SYSTEMS - continued
SPLIT SYSTEMSConfi guration of a split system is the same as the package system, except that you don’t have to take into consideration the condenser supply and return air. Typical confi guration is with the evaporator supply and return air from the space below, however all the following options are available to meet your require-ments.
Standard confi guration with standard supply air and standard return air
Ducted alternate return air and alternate rear supply air
Shown with options 262 and 263
Ducted alternate return air and alternate end supply air
Shown with options 260 and 263
Ducted alternate front supply air
Shown with option 261Shown with option 260
Ducted alternate end supply air
12
Ducted alternate front supply air and alternate return air
Shown with options 261 and 263
SPLIT SYSTEMS - continued
Ducted alternate end supply air and special return air
Shown with options 260 and special
Ducted alternate end supply air and alternate return air
Shown with option 260 and 263
Shown with options 262 and special
Ducted alternate front supply air and alternate return air
Ducted alternate rear supply air and alternate return air
Shown with option 262 and 263
13 R-407C
AIR COOLED: Performance data - R-407C
MODEL NUMBER DAMA-01 DAMA-1.5 DAMA-02 DAMA-2.5
CAPACITY in Btu/hr - Gross
80° DB/67° WB Total 16,300 20,300 25,600 31,600 50% RH Sensible 12,400 16,100 21,300 25,700
75° DB/62.5° WB Total 15,100 18,800 23,700 29,300 50% RH Sensible 12,000 15,600 20,600 24,800
75° DB/61° WB Total 14,500 18,300 23,000 28,500 45% RH Sensible 12,800 16,600 22,100 26,600
72° DB/60° WB Total 14,300 17,900 22,600 27,900 50% RH Sensible 11,800 15,200 20,100 24,300
72° DB/58.6° WB Total 13,900 17,500 22,000 27,200 45% RH Sensible 12,500 16,200 21,500 25,900
GLYCOL COOLED: Performance data - R-407C
MODEL NUMBER DAMG-01 DAMG-1.5 DAMG-02 DAMG-2.5
CAPACITY in Btu/hr - Gross
80° DB/67° WB Total 15,900 19,800 25,200 31,000 50% RH Sensible 12,300 15,900 21,200 25,500
75° DB/62.5° WB Total 14,700 18,400 23,300 28,700 50% RH Sensible 11,900 15,400 20,400 24,600
75° DB/61° WB Total 14,200 17,900 22,500 27,900 45% RH Sensible 12,700 16,500 21,800 26,400
72° DB/60° WB Total 13,900 17,500 22,200 27,400 50% RH Sensible 11,600 15,000 19,900 24,000
72° DB/58.6° WB Total 13,600 17,100 21,400 26,600 45% RH Sensible 12,400 16,100 21,100 25,700
WATER COOLED: Performance data - R-407C
MODEL NUMBER DAMW-01 DAMW-1.5 DAMW-02 DAMW-2.5
CAPACITY in Btu/hr - Gross
80° DB/67° WB Total 17,100 21,100 26,700 32,900 50% RH Sensible 12,700 16,400 21,700 26,200
75° DB/62.5° WB Total 15,800 19,600 24,800 30,600 50% RH Sensible 12,300 15,900 21,000 25,300
75° DB/61° WB Total 15,200 19,000 24,100 29,800 45% RH Sensible 13,100 17,000 22,500 27,200
72° DB/60° WB Total 15,000 18,600 23,700 29,200 50% RH Sensible 12,100 15,500 20,600 24,800
72° DB/58.6° WB Total 14,400 18,200 23,100 28,500 45% RH Sensible 12,800 16,500 21,900 26,500
14R-407C
AIR, GLYCOL and Water COOLED: Performance data
MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5
EVAPORATOR BLOWER
Airfl ow - CFM 550 775 1000 1225Standard motor - horsepower 1/2 1/2 3/4 3/4External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5
EVAPORATOR COIL
Face area - sq ft 2.4 2.4 2.4 2.4Face velocity - fpm 229 323 417 510Rows of coil 3 3 4 4
CONDENSER COIL Air cooled indoor packaged units
Face area - sq ft 2.4 2.4 2.4 2.4Face velocity - fpm 500 500 500 500Rows of coil 4 4 6 6
CONDENSER BLOWER Air cooled indoor packaged units
Standard airfl ow - CFM 1,200 1,200 1,200 1,200Standard motor - horsepower 1/2 1/2 1/2 1/2External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5
CONDENSER DATA Water cooled units
Type Plate-fi n Plate-fi n Plate-fi n Plate-fi nWater regulating valve 2-way 2-way 2-way 2-waySize - inches 3/8 3/8 3/4 3/4Maximum working pressure - PSI 150 150 150 150
ENTERING WATER Water cooled units
Using 65° F EWT GPM 1.2 1.9 2.5 3.1 PD in PSI 1.3 2.9 2.1 3.0Using 75° F EWT GPM 2.0 3.0 3.9 4.9 PD in PSI 2.0 4.3 3.1 4.5Using 85° F EWT GPM 2.8 4.2 5.6 7.0 PD in PSI 3.0 6.7 4.8 6.9With Fluid Cooler GPM 3.5 5.3 7.0 8.8 PD in PSI 5.8 12.4 9.2 13.3
COMPRESSOR DATA
Type Scroll Scroll Scroll ScrollQuantity 1 1 1 1Cooling stages 1 1 1 1Refrigerant type R-407C R-407C R-407C R-407CCrankcase heater Standard Standard Standard Standard
* Insert: A - Air cooled, G - Glycol cooled, W - Water cooled
15 R-407C
AIR, GLYCOL and Water COOLED: Performance data
MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5
REHEAT SECTION Optional
Type - Electric Capacity- kW 2 2 2 2 Btu/hr 6,830 6,830 6,830 6,830 Capacity - kW 4 4 4 4 Btu/hr 13,660 13,660 13,660 13,660 Capacity- kW N/A N/A 5 5 Btu/hr 17,075 17,075
HUMIDIFIER SECTION Optional
Type - Steam Generator Capacity - lb/hr 5 5 5 5 kW 1.7 1.7 1.7 1.7
FILTER SECTION
Type Pleated Pleated Pleated PleatedQuantity 1 1 1 1Size - inches 20x20x2 20x20x2 20x20x2 20x20x2Effi ciency - percentage 30 30 30 30
CONNECTION SIZES
Condensate drain - fpt 3/4 3/4 3/4 3/4Humidifi er 1/4 1/4 1/4 1/4
With air cooled condensing unit: Liquid line - O.D. Copper 1/2 1/2 1/2 1/2 Suction line - O.D. Copper 3/4 3/4 3/4 3/4
With air cooled condenser: Liquid line - O.D. Copper 1/2 1/2 1/2 1/2 Hot gas line - O.D. Copper 1/2 1/2 1/2 1/2
Water and glycol cooled: Condenser water - In/Out 3/4 3/4 3/4 3/4
16R-407C
AIR COOLED: Electrical data
ELECTRICAL SECTION
AIR COOLED (Packaged Systems)
MODEL NUMBER DAMA-01-P DAMA-1.5-P DAMA-02-P DAMA-2.5-P
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 16/19/25 16/19/25 19/22/30 21/25/35 277 V FLA/MCA/MOP 15/17/25 15/17/25 17/19/25 19/22/30
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 24/29/35 24/29/35 27/32/40 30/35/45 277 V FLA/MCA/MOP 21/25/30 21/25/30 23/27/30 26/30/40
Electrical data based on: 2 kW electric reheat -YES, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 26/31/35 26/31/35 28/34/40 31/37/45 277 V FLA/MCA/MOP 22/26/30 22/26/30 24/28/35 27/31/40
Electrical data based on: 4 kW electric reheat -YES, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 35/43/45 35/43/45 38/46/50 41/49/50 277 V FLA/MCA/MOP 29/35/40 29/35/40 31/37/40 34/40/45
Electrical data based on: 2 kW electric reheat -YES, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 26/31/35 26/31/35 28/34/40 31/37/45 277 V FLA/MCA/MOP 22/26/30 22/26/30 24/28/35 27/31/40
Electrical data based on: 4 kW electric reheat -YES, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 35/43/45 35/43/45 38/46/50 41/49/50 277 V FLA/MCA/MOP 29/35/40 29/35/40 31/37/40 34/40/45
AIR COOLED (Split Systems with Outdoor Condensing Unit)
MODEL NUMBER DAMA-01-AO DAMA-1.5-AO DAMA-02-AO DAMA-2.5-AO Electrical data based on: electric reheat - NO, steam generator humidifi er - NO. 208-230 V Indoor FLA/MCA/MOP 4.0/5.0/15 4.0/5.0/15 5.3/6.6/15 5.3/6.6/15 Outdoor FLA/MCA/MOP 12/14/20 14/17/25 16/18/25 18/22/35 277 V Indoor FLA/MCA/MOP 3.6/4.5/15 3.6/4.5/15 4.3/5.4/15 4.3/5.4/15
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES. 208-230 V Indoor FLA/MCA/MOP 12/15/20 12/15/20 14/17/20 14/17/20 Outdoor FLA/MCA/MOP 14/17/25 14/17/25 16/18/25 18/22/35 277 V Indoor FLA/MCA/MOP 9.7/12/15 9.7/12/15 10/13/15 10/13/15
Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available.
FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device
17 R-407C
AIR COOLED: Electrical data
AIR COOLED (Split Systems with Outdoor Condensing Unit)
MODEL NUMBER DAMA-01-AO DAMA-1.5-AO DAMA-02-AO DAMA-2.5-AO
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V Indoor FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 Outdoor FLA/MCA/MOP 14/17/25 14/17/25 16/18/25 18/22/35 277 V Indoor FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V Indoor FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 Outdoor FLA/MCA/MOP 14/17/25 14/17/25 16/18/25 18/22/35 277 V Indoor FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V Indoor FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 Outdoor FLA/MCA/MOP 14/17/25 14/17/25 16/18/25 18/22/35 277 V Indoor FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V Indoor FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 Outdoor FLA/MCA/MOP 14/17/25 14/17/25 16/18/25 18/22/35 277 V Indoor FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25
Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available.
FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective devices
18R-407C
AIR COOLED (Split Systems with Remote Air Cooled Condenser)
MODEL NUMBER DAMA-01-CO DAMA-1.5-CO DAMA-02-CO DAMA-2.5-CO
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO. 208-230 V Indoor FLA/MCA/MOP 14/16/25 14/16/25 16/19/30 19/22/35 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 11/13/20 11/13/20 13/16/25 16/19/30
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES. 208-230 V Indoor FLA/MCA/MOP 22/26/30 22/26/30 24/29/35 27/32/40 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 17/21/25 17/21/25 19/23/30 22/26/35
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V Indoor FLA/MCA/MOP 23/28/35 23/28/35 26/31/35 28/34/45 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 19/22/25 19/22/25 21/25/30 23/28/35
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V Indoor FLA/MCA/MOP 33/40/45 33/40/45 35/43/45 38/46/50 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277V Indoor FLA/MCA/MOP 26/31/35 26/31/35 28/34/35 30/37/45
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V Indoor FLA/MCA/MOP 23/28/35 23/28/35 26/31/35 28/34/45 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 19/22/25 19/22/25 21/25/30 23/28/35
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V Indoor FLA/MCA/MOP 33/40/45 33/40/45 35/43/45 38/46/50 Outdoor FLA/MCA/MOP 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 4.6/5.8/15 277 V Indoor FLA/MCA/MOP 26/31/35 26/31/35 28/34/35 30/37/45
FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device
AIR COOLED: Electrical data
19 R-407C
WATER COOLED (Packaged Systems)
MODEL NUMBER DAMW-01 DAMW-1.5 DAMW-02 DAMW-2.5
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 14/16/20 14/16/20 16/19/25 16/19/30 277 V FLA/MCA/MOP 11/13/20 11/13/20 13/16/25 13/16/25
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 22/26/30 22/26/30 24/29/35 24/29/35 277 V FLA/MCA/MOP 18/22/25 17/21/25 19/23/30 22/26/35
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 23/28/35 23/28/35 26/31/35 26/31/35 277 V FLA/MCA/MOP 17/21/25 19/22/25 21/25/30 21/25/30
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 33/40/45 33/40/45 35/43/45 35/43/45 277 V FLA/MCA/MOP 26/31/35 26/31/35 28/34/35 28/34/35
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 23/28/35 23/28/35 26/31/35 26/31/35 277 V FLA/MCA/MOP 19/22/25 19/22/25 21/25/30 21/25/30
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 33/40/45 33/40/45 35/43/45 35/43/45 277 V FLA/MCA/MOP 26/31/35 26/31/35 28/34/35 28/34/35
COMPRESSORS and MOTORS (DX Units, Air Cooled, and Water Cooled)
MODEL NUMBER DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5
EVAPORATOR FAN MOTOR Standard motor - horsepower 1/2 1/2 3/4 3/4 FLA at 208-230 V 4.0 4.0 5.3 5.3 FLA at 277 V 3.6 3.6 4.3 4.3
CONDENSER FAN MOTOR (Air Cooled Indoor Packaged Units) Standard motor - horsepower 1/2 1/2 1/2 1/2 FLA at 208-230 V 3.2 3.2 2.6 2.6 FLA at 277 V 3.6 3.6 3.6 3.6
CONDENSER FAN MOTOR (Air Cooled Split Systems - Condensing Units or Air Cooled Condensers) Standard motor - horsepower 3/4 3/4 3/4 3/4 Motor FLA at 208-230 V 4.2 4.2 4.2 4.2
COMPRESSOR Standard motor - horsepower 1.5 1.5 2.0 2.5 FLA at 208-230 V 8.3 8.3 10.3 13.5 FLA at 277 V 7.7 7.7 8.7 11.5
FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device
WATER or GLYCOL COOLED: Electrical data
20
MODEL NUMBER DAMC-01 DAMC-1.5 DAMC-02 DAMC-2.5
CAPACITY in Btu/hr - Gross
80° DB/67° WB Total 15,800 21,300 28,700 33,900 50% RH Sensible 12,200 16,500 22,400 26,60075° DB/62.5° WB Total 12,500 16,800 22,800 26,900 50% RH Sensible 11,000 14,900 20,200 24,00075° DB/61° WB Total 11,900 16,000 21,700 25,600 45% RH Sensible 11,400 15,400 21,000 24,90072° DB/60° WB Total 10,800 14,600 19,800 23,300 50% RH Sensible 10,200 13,700 18,700 22,20072° DB/58.6° WB Total 10,500 14,100 19,200 22,700 45% RH Sensible 10,400 14,000 19,200 22,700
Note: Chilled Water capacity based on 45° F entering chilled water temperature.
CHILLED WATER COIL
Face are - sq ft 2.4 2.4 2.4 2.4Rows of coil 3 3 4 4Face velocity - fpm 229 323 417 510
BLOWER SECTION
Airfl ow - cfm 550 775 1000 1225Standard fan motor - hp 1/2 1/2 3/4 3/4 External Static Pressure (E.S.P.) - inches of W.G. 0.5 0.5 0.5 0.5Number of fans 1 1 1 1
CHILLED WATER REQUIRED (Maximum 150 PSI)
Using 45° F EWT GPM 3.0 4.5 6.0 7.5 PSI 2.4 5.3 7.7 10.5
CHILLED WATER VALVE
Valve body 2-WAY 2-WAY 2-WAY 2-WAYValve size - inches 3/4 3/4 3/4 3/4
REHEAT SECTION (Optional)
Electric kW 2 2 2 2 Btu/hr 6,825 6,825 6,825 6,825 kW 4 4 4 4 Btu/hr 13,650 13,650 13,650 13,650 kW N/A N/A 5 5 Btu/hr N/A N/A 17,075 17,075
HUMIDIFIER SECTION (Optional)
Steam generator Capacity - lbs/hr 5 5 5 5 kW 1.7 1.7 1.7 1.7
CHILLED WATER: Performance data
21
MODEL NUMBER DAMC-01 DAMC-1.5 DAMC-02 DAMC-2.5 FILTER SECTION
Type Pleated Pleated Pleated PleatedQuantity 1 1 1 1Size - inches 20x20x2 20x20x2 20x20x2 20x20x2Effi ciency - percentage 30 30 30 30
CONNECTION SIZES
Chilled water in/outO.D. copper 3/4 3/4 3/4 3/4Condensate drain - FPT 3/4 3/4 3/4 3/4Humidifi er 1/4 1/4 1/4 1/4
ELECTRICAL SECTION
Electrical data based on: electric reheat - NO, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 4.0/5.0/15 4.0/5.0/15 5.3/6.6/15 5.3/6.6/15 277 V FLA/MCA/MOP 3.6/4.5/15 3.6/4.5/15 4.3/5.4/15 4.3/5.4/15
Electrical data based on: electric reheat - NO, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 12/15/20 12/15/20 14/17/20 14/17/20 277 V FLA/MCA/MOP 9.7/12/15 9.7/12/15 10/13/15 10/13/15
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 277 V FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - YES. 208-230 V FLA/MCA/MOP 23/29/30 23/29/30 25/31/35 25/31/35 277 V FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25
Electrical data based on: 2 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 14/17/20 14/17/20 15/19/20 15/19/20 277V FLA/MCA/MOP 11/14/15 11/14/15 12/14/15 12/14/15
Electrical data based on: 4 kW electric reheat - YES, steam generator humidifi er - NO. 208-230 V FLA/MCA/MOP 23/29/30 23/29/30 26/31/35 26/31/35 277 V FLA/MCA/MOP 18/23/25 18/23/25 19/23/25 19/23/25
BLOWER SECTION Standard motor - hp 1/2 1/2 3/4 3/4 FLA at 208-230 V 3.5 3.5 5.3 5.3 FLA at 277 V 3.4 3.4 4.3 4.3
FLA - Full load amps MCA - Minimum circuit amps wire sizing amps MOP - Maximum rating of the Overcurrent Protective device
CHILLED WATER: Performance data
22
Air Cooled Split with DARC Outdoor Condenser DAMA-XXXX-CO
23
Air Cooled Split with DARC Outdoor Condenser DAMA-XXXX-CO
24
Air Cooled Split with DRCU Outdoor Condensing Unit DAMA-XXXX-AO
25
Air Cooled Split with DRCU Outdoor Condensing Unit DAMA-XXXX-AO
26
Air Cooled Packaged DAMA-XXXX-P
27
Air Cooled Packaged DAMA-XXXX-P
28
Air Cooled Split with Indoor Condenser DAMA-XXXX-CI
29
Air Cooled Split with Indoor Condenser DAMA-XXXX-CI
30
Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI
31
Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI
32
Water/Glycol Cooled DAMW-XXXX
33
Water/Glycol Cooled DAMW-XXXX
34
Chilled Water DAMC-XXXX
35
Chilled Water DAMC-XXXX
36
Condenser and Condensing Unit Dimensional Drawings
Condenser Unit
Condensing Unit
37
5 1/2"
Duct Work Supplied�and Installed by Others
Connect to�Schrader Valve Fitting�on Discharge Line
16" x 16" Ambient Controlled�Damper Supplied by�Data Aire�(Shipped Loose)
5/8" Threaded Rod�(4) Required
5/8" Flat Washer
5/8" Nut
5/8" Jam Nut
All Mounting Hardware�Field Provided
See�Damper�
Detail
See�Mounting�Detail
MINI CEILING SYSTEMTYPICAL
HANGING INSTALLATIONDETAIL
MINI CEILING SYSTEMLOW AMBIENT DAMPER
CONTROL PACKAGE(Optional)
Return Air Filter Box
Typical Hanging Installation Detail
38
Provide and install an air conditioning system designed specifi cally for use in small computer/data processing areas, or controlled offi ce environments, and shall be capable of cooling, humidifying, dehumidifying, and fi ltering air.
Units shall be ETL or UL listed.
The frame shall be constructed of 14 gauge welded tubular steel and be coated with a heavy corrosion in-hibiting fi nish for long life. The side panels shall be of galvanized steel. The cabinet shall be insulated with one-half inch (1/2”) thick, closed cell insulation. The plenum shall be of cold rolled steel and painted in a cloud white fi nish. The plenum (vertical unit only) shall be fi eld mounted. The unit shall be serviceable through the removable side panels.
The vertical air fl ow unit is to be ceiling mounted and sized to fi t a standard 2 ft x 4 ft T-bar ceiling grid open-ing. The horizontal supply/return air unit is to be ceiling hung with duct work attached to supply and return open-ings. The total cooling capacity shall be ______ Btu/hr at ____ degree F DB and ____ degree F WB entering air temperature. The voltage shall be ___, 1 ph, 60 hz.
Electrical - All electrical components including contac-tors, relays, control transformers, and capacitors shall be pre-wired. The control circuit voltage shall be 24 volts. A micro-switch shall disable the unit operation prior to condensate pan overfl ow should the drain line become plugged with debris.
Filter - Provide a two (2”) inch, 30% effi cient (based on ASHRAE Std. 52.1-1992) disposable fi lter of twenty inches square (20” x 20”). The fi lter shall be located be-hind and accessible through the hinged return air grille.
Air Cooled Self-Contained - The refrigeration system shall be self-contained, factory assembled, charged, and tested. No refrigerant piping shall be required. The unit shall contain an evaporator and condenser section.
The evaporator section shall have a cooling coil con-structed with copper tubes and aluminum fi ns. The single refrigeration circuit shall include the expansion valve with external equalizer, fi lter drier, high and low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable.
The evaporator blower assembly shall be draw-through confi guration consisting of a double inlet, double width, direct drive centrifugal fan with belt drive and variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be con-structed of stainless steel and provide a positive drain to prevent standing water in the condensate pan.
The fi eld attached condenser section shall have a con-denser coil constructed with copper tubes and alumi-num fi ns and built into the refrigeration system. The condenser fan shall be double inlet, double width, direct drive type. The condenser blower motor electrical con-nection shall be through a factory wired plug.
Air Cooled Split System (with outdoor con-densing unit) - The refrigeration system shall be split consisting of an evaporator section and remote outdoor condensing unit. The evaporator and condensing unit shall be factory assembled and tested.
The evaporator section shall have a cooling coil con-structed with copper tubes and aluminum fi ns. The single refrigeration circuit shall include the expansion valve with external equalizer, fi lter drier, and high and low pressure safety switches. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnec-essary. The scroll type compressor shall have internal overload protection. Units with capillary tube meter-ing devices shall not be acceptable. The evaporator blower assembly shall be draw-through type consisting of a double inlet, double width, centrifugal fan with belt drive and variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stainless steel.
The condensing unit shall be constructed of heavy duty gauge corrosion resistant steel with a powder coated fi n-ish and contain a scroll type compressor with crankcase heater, fi lter drier, sight glass, and condenser coil. The coil shall be constructed with copper tubes and alumi-num fi ns. The condenser fan motor shall be variable speed for head pressure control down to -20 degrees F. The capillary tube connection from the fan speed con-
Mini Ceiling SystemsGuide Specifi cations
General
39
trol to the refrigerant system shall be connected with a Schrader fi tting that allows replacement without affect-ing the refrigerant charge, making recovery unnecessary. The condenser motor shall be direct drive with a propel-ler type fan.
Air Cooled Split System (with outdoor condenser) - The refrigeration system shall be split consisting of an evaporator section and remote outdoor condenser. The evaporator and condenser shall be factory assembled and tested.
The evaporator section shall have a cooling coil con-structed with copper tubes and aluminum fi ns. The single refrigeration circuit shall include the expansion valve with external equalizer, fi lter drier, and high and low pressure safety switches. The scroll type compres-sor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through confi guration consisting of a double inlet, double width, centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horse-power. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stain-less steel.
The condenser section shall be a low profi le, slow speed, direct drive propeller fan type. The condenser shall be constructed of heavy duty gauge corrosion resistant steel with a powder coated fi nish and contain a copper tube aluminum fi n coil with vertical air discharge. The condenser shall have fan speed control with transducers to modulate the speed of the condenser fan and provide positive start-up and operation at ambient temperatures to -20° F. All controls including the fan speed control, shall be factory mounted in the air cooled condenser.
Water Cooled Self-Contained - The refrigeration sys-tem shall be self-contained, factory assembled, charged and tested. No refrigerant piping connections shall be required. The unit shall contain an evaporator and con-denser section.
The evaporator section shall have a cooling coil con-structed with copper tubes and aluminum fi ns. The single refrigeration circuit shall include the expansion valve with external equalizer, fi lter drier, and high and
low pressure safety switches. The scroll type compres-sor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through confi guration consisting of a double inlet, double width, centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horse-power. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stain-less steel and provide a positive drain to prevent stand-ing water in the condensate pan.
A high effi ciency plate-fi n water cooled condenser with head pressure activated water regulating valve built into the refrigeration system shall be provided. The capillary tube connection from the water regulating valve to the refrigerant system shall be connected with a Schrader fi tting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Maxi-mum operating water pressure shall be 150 psi.
Chilled Water - Provide a packaged system designed to utilize an existing chilled water loop. The unit shall be factory assembled, piped, wired, and tested. A chilled water coil consisting of copper tubes and aluminum fi ns shall be provided. The chilled water fl ow shall be controlled by a two-way valve for accurate and eco-nomical temperature control and dehumidifi cation. The blower assembly shall be drawn through a confi guration consisting of a double inlet, double width, direct drive centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horse-power. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stain-less steel and provide a positive drain to prevent stand-ing water in the condensate pan. All components shall be housed within the same cabinet.
Controls -The control system shall be electromechani-cal type, utilizing a 24 volt thermostat. A sub-base shall be provided for remote wall mounting of thermostat. The controls shall be accessible through the side panel of the unit and contained in a hinged electrical box that shall swing out for easy access and servicing.
Removal of the unit from the ceiling space shall not be required for access.
GUIDE SPECIFICATIONS continued
40
Unit Control
Mini Data Alarm Processor-II - The control system shall be furnished with the microprocessor based Mini Data Alarm Processor-II. The panel shall in-clude unit switching functions and display normal functions, malfunctions, and service diagnostics on a one row, 16 character liquid crystal display (LCD) in clear vernacular format. The panel shall automati-cally display temperature and humidity along with all operational and alarm messages. The panel shall recall and display the high and low temperature and the high and low humidity for the last 24 hours, date and time, reheat, humidifi cation, dehumidifi cation, and chilled water operation (as applicable).
Programming shall have a two level password secu-rity to prevent unauthorized access. Programming shall be accomplished entirely from the micropro-cessor. Programmable functions shall be entered on nonvolatile EEPROM to insure program retention should power fail. Multiple messages shall be dis-played by automatically scrolling from each message to the next. Alarm conditions, in addition to being displayed, shall enunciate an audible alarm with vari-able output. Additional test or service terminals shall not be required for any functions.
An alarm condition shall continue to be displayed un-til the malfunction is corrected. Multiple alarms shall be displayed sequentially in order of occurrence and only those alarms which have not been acknowledged shall continue to sound an audible alarm. The Mini Data Alarm Processor-II shall perform an automatic self-test on system start-up. A user accessible diag-nostic program shall aid in system component trouble shooting by displaying on the unit LCD screen output relay number, terminal plug and pin number for each controlled item.
The following functions shall be programmable: Temperature setpoint (60-80° F, 15.6-26.7° C), Temperature sensitivity (1-5° F, .5-2.7° C in 0.1° increments), Humidity setpoint (30-70% RH), Humidity sensitivity (1-15% RH in 0.1% increments), Temperature alarm points, Humidity alarm points, Unit start time delay,
Interstage time relay, Password 1st level, Password 2nd level, Audio alarm level, Restart mode, Firestat trip temperature, Local alarm function
The following normal functions shall be moni-tored and displayed: Current temperature (°F or °C), Current humidity (Percentage RH), Cooling, Reheat, Humidifi cation, Dehumidifi cation, Date and time
The following alarm functions shall be monitored and displayed when they occur, in addition to enunciating an audible alarm: High temperature, Low temperature, High humidity, Low humidity, Compressor high pressure, High condensate water, Firestat tripped, No air fl ow, Compressor short cycle, Temperature sensor error, Humidity Sensor error
The following switching and control functions shall be included: System On/Off switch, Menu selection button for: Programming operational information, Diagnostics, Historical data, and Alarm silence/program set button
Site Monitoring
DARA-4 (Data Aire Relay Autochangeover)Controls up to four Mini Ceiling units using a dry set of relay contracts. The DARA-4 pro-vides unit rotation, backup capacity and the abil-ity to interface with most BMS systems.
CONTROLS
41
Unit Options
HUMIDIFIER
Provide a steam generator type humidifi er. The steam humidifi er shall be of the self-contained cyl-inder type with electronic controls. The humidifi er shall discharge pure steam with no material dust carry-over, and shall have self-regulating fl ush cycle. Cylinders shall be disposable not requiring cleaning or maintenance. Humidifi er rate shall au-tomatically adapt, both in frequency and duration, to variations in the incoming water. The humidifi er capacity shall be 5 pounds per hour with power consumption of 1.7 kW.
(Note: When specifying the steam generator type humidifi er, a Mini Data Alarm Processor-II is re-quired.)
REHEAT
Provide electric reheat. The electrical heating ele-ment shall be of the fi nned tube resistant type and constructed of stainless steel with high limit cutout. The capacity shall be ____ kW, _____ Btu/hr.
CONDENSATE PUMP
A condensate pump shall be provided with the unit and shall have a capacity of 60 GPH at 8 feet of head. The pump shall be shipped loose for fi eld mounting and installation. Pump should be located exterior to the unit. The pump voltage shall be ___.
LOW AMBIENT CONTROL DAMPER
Provide a low ambient control damper for ducting of outside condenser air. The low ambient control damper shall consist of a 14” x 14” damper sec-tion with headpressure operator. The control shall enable the unit to operate down to -30° F ambi-ent. The capillary tube connection from the head pressure control to the refrigerant system shall be connected with a Schrader fi tting that allows re-placement without affecting the refrigerant charge, making recovery unnecessary.
HORIZONTAL SUPPLY AND RETURN AIR
Supply and return air shall be horizontal for ducted connection. Refer to the project drawings.
FRONT SUPPLY AIR
Supply air shall be through the front of the unit for ducted connection. The unit shall be provided with a fl ange connection. Refer to the project drawings.
SIDE SUPPLY AIR
Supply air shall be through the side of the unit for ducted connection. The unit shall be provided with a fl ange connection. Refer to the project drawings.
SIDE RETURN AIR
Return air shall be through the side of the unit for ducted connection. The return air shall be through a factory provided ceiling mounted return air grille. The ceiling mounted return air grille shall be hinged for easy access and shall contain a 30% effi cient (based on ASHRAE Std. 52.1-1992) 20” x 20” x 2” pleated fi lter. Refer to the project drawings.
EXTENDED COMPRESSOR WARRANTY
Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs.
OPTIONS
42
Weights - lbs Operational Shipping 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5Packaged SystemsAir Cooled 425 425 425 425 450 450 450 450Water Cooled 350 350 350 350 375 375 375 375Chilled Water 300 300 300 300 325 325 325 325
Split Systems*Air Cooled - AO 280/300 280/300 280/300 280/300 305/340 305/340 305/340 305/340Air Cooled - CO 325/260 325/260 325/260 325/260 350/300 350/300 350/300 350/300
* Weights provided are for the evaporator section (inside-fi rst number) and condensing or condenser section (outside-second number). Each section shipped separately. Weights shown are for standard units.
230 W. BlueRidge AvenueOrange CA 92865
800-347-2473www.dataaire.com e-mail: [email protected]
A Member of the CS Group of Companies© 2010 Data Aire Inc.
Data Aire, Inc. reserves the right to make design changes for the purposes of product improvement, or to withdraw any design without notice.
DAMCS-R-407C - 0810 Rev A