Piping and Valves 4 4.2.4 Installation 4.2.4.1 Installation type For the direction of flow and the suitability for vertical and/or horizontal installation, please refer to section 4.2.2.3. 4.2.4.2 Installation positi- on The installation position is determined by: • The function of the valve • Functional framework conditions • Accessibility and operability These three criteria are of equal importance when selecting an installation position for a valve. All of them have to be taken into account for an acceptable project solution. Function of the valve The first point to consider when selecting an installation position for a valve is its operational The following examples serve to illustrate this point: • The gate valve at the discharge side of the pump serves to close the pipe if the pump or swing check valve needs to be repaired. It should ideally be located immediately downstream of the pump and swing check valve. However, the functional framework conditions (maximum fluid level in the pump sump) and the operability require a different (higher) position. • The swing check valve should ideally be located directly downstream of the pump, as mentioned above. Again, the fluid level and accessibility demand a more practical location in the piping. • The position of the aeration and vent valve should always be selected from an operational point of view, which is at the highest point of the piping. Suitable structures to provide accessibility must be provided. Functional framework conditions The installation position can be determined by functional framework conditions. For example: • Installation criteria provided by the valve manufacturer (vertical/horizontal) • Routing of the discharge line • If the discharge line has a long vertical section, the swing check valve must not be installed at a low position in the vertical pipe axis as the function of the swing check valve will be impaired by deposits of contamination (sand, stones, sludge). Stones falling back down onto the valve could also cause some direct damage. In this case, the swing check valve should be fitted in a horizontal pipe section which has to be planned for in the piping layout. • Maximum fluid level • Individual discharge lines joining collecting lines 66

Upload: sohail-hanif

Post on 21-Nov-2015

213 views

Category:

Documents


0 download

DESCRIPTION

Data 443

TRANSCRIPT

  • Piping and Valves4

    4.2.4

    Installation

    4.2.4.1

    Installation type

    For the direction of flow and the

    suitability for vertical and/or

    horizontal installation, please

    refer to section 4.2.2.3.

    4.2.4.2

    Installation positi-

    on

    The installation position is

    determined by:

    The function of the valve

    Functional framework

    conditions

    Accessibility and operability

    These three criteria are of equal

    importance when selecting an

    installation position for a valve.

    All of them have to be taken into

    account for an acceptable project

    solution.

    Function of the valve

    The first point to consider when

    selecting an installation position

    for a valve is its operational

    The following examples serve to

    illustrate this point:

    The gate valve at the discharge

    side of the pump serves to

    close the pipe if the pump or

    swing check valve needs to be

    repaired. It should ideally be

    located immediately

    downstream of the pump and

    swing check valve. However,

    the functional framework

    conditions (maximum fluid

    level in the pump sump) and

    the operability require a

    different (higher) position.

    The swing check valve should

    ideally be located directly

    downstream of the pump, as

    mentioned above. Again, the

    fluid level and accessibility

    demand a more practical

    location in the piping.

    The position of the aeration

    and vent valve should always

    be selected from an

    operational point of view,

    which is at the highest point of

    the piping. Suitable structures

    to provide accessibility must be

    provided.

    Functional framework

    conditions

    The installation position can be

    determined by functional

    framework conditions.

    For example:

    Installation criteria provided

    by the valve manufacturer

    (vertical/horizontal)

    Routing of the discharge line

    If the discharge line has a long

    vertical section, the swing

    check valve must not be

    installed at a low position in

    the vertical pipe axis as the

    function of the swing check

    valve will be impaired by

    deposits of contamination

    (sand, stones, sludge). Stones

    falling back down onto the

    valve could also cause some

    direct damage. In this case, the

    swing check valve should be

    fitted in a horizontal pipe

    section which has to be

    planned for in the piping

    layout.

    Maximum fluid level

    Individual discharge lines

    joining collecting lines

    66