Universal Time Delay Relay
Type NT 10
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 2/8
2 ABB
ABB – a global leader
Advantage ABB
120 years of technology and innovation
Unparalleled domain competence
Vast global experience
Total solution provider
Large installed base
Environment-friendly technologies
ABB is a global leader in Power and Automation
technologies that enable utility and industry
customers to improve performance while lowering
environmental impact. The ABB Group of companies
operates in around 100 countries.
ABB has been present in India since 1928. Today it
has 14 manufacturing facilities in the country.
Customers are served through an extensive
countrywide presence of around 30 marketing
offices, 8 service centres, 3 logistic warehouses and
a network of over 775 channel partners.
ABB’s Power Technologies business offers electric,
gas and water utilities as well as industrial and
commercial customers a wide range of products,
systems and services for power generation,
transmission and distribution. ABB’s turnkey solution
capabilities in the sector range from bulk power
transmission, turnkey substations and complete
electrification to substation automation and network
management systems.
The product offering covers a wide spectrum of
technologies across the entire voltage range
including indoor and outdoor circuit breakers, air
and gas insulated switchgear, instrument
transformers, disconnectors, capacitor banks and
filters for reactive power compensation, power anddistribution transformers and a range of power
distribution products like Compact Secondary
Substations (CSS) and Ring Main Units (RMU).
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 3/8
ABB 3
Universal Time Delay Relay type NT 10
Features * 4-User configurable operating modes
* Wide timing range
* Easy Setting through DIP switches
* Manual Reset 'Flag' LED indication
* Both signaling duty and trip duty
contacts available
* Micro-controller based design for
high accuracy
Application: The NT 10 relay is intended for use
where high operating requirements are
necessary, such as in protection relay
systems, control equipment, industrial
processes, and control and signal
systems.
The multiple user selectable options
provide flexibility to user, for use in
various applications. The wide timing
range, high timing accuracy and
consistency of operation can replace
any other time relays.
Description: The time delay relay type NT 10 is high
precision, numerical time relay with
builtin electro mechanical output relays
providing- two CO signaling duty
contacts and one NO trip duty contact.
The micro-controller based relay designprovides accurate timing and varied
operating modes. The four operating
modes are: ON Delay, OFF Delay,
Flasher and Interval. The required
timing and operating mode can be set
by adjusting the DIP switches on the
front panel.
The timing function is triggered by
control input depending on the mode
selection. The control input has same
rated voltage as auxiliary voltage andis galvanically isolated.
The four LEDs on the front panel
indicates status of relay. The presence
of healthy auxiliary supply is indicated
by green 'Uaux' LED. The operation of
relay is indicated by red 'TRIP' LED.
The yellow 'Start' LED indicates,'timing' status in 'ON Delay' and 'OFF
Delay' modes. In 'Flasher' and 'Interval'
mode Start LED indicates the status of
control input.
The start LED additionally indicates the
change of mode selection. When mode
setting is changed, yellow 'Start' LED
blinks and the relay does not respond
to the control input till mode setting
change is applied by pressing 'Reset'
push button. The 'IRF' LED indicates the internal
relay fault.
Block Diagram:
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 4/8
4 ABB
OperationalModes:
The following modes are possible when the relay is energized with auxiliary supply.
ON Delay: In this mode, the timing starts when the control input is applied and after
the set time has elapsed, the delayed output switches to the operate condition
OFF Delay: In this mode, the output immediately switches to operate condition
when applying the control input and in which the timing starts when the control
input is disconnected and the output switches to released condition after set time
has elapsed
Interval: In this mode, the relay switches the output to operate condition for set
time when the control input is applied or removed
Reset PB will not have any
effect in this mode
Flasher: In this mode, the output periodically switches on and off with substantially
identical pulse on time and pulse off time as long as the control input is applied
Reset PB will not have any
effect in this mode
Universal Time Delay Relay type NT 10
Uaux
Control I/P
Start LED
TRIP LED
O/P Contact
Resett t
Uaux
Control I/P
Start LED
TRIP LED
O/P Contact
Resett t
Uaux
Control I/P
Start LED
Trip LED
O/P Contact
Resett t
Uaux
Control I/P
Start LED
Trip LED
O/P Contact
Reset
t t
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 5/8
ABB 5
Technical Data General
Energizing quantities, rated values and limits:
Rated Auxiliary Voltage Un (X1- 2,4) : 18 - 80V dc
80 - 265V ac/dc
Control Input (X2- 1,2) : 24 - 250 V ac/dc
Rated Frequency: 50HzPower Consumption, Uaux
Before Operation : < 3W
After Operation : < 4W
Power Consumption, Control Input < 0.6W
Rated ambient temperature: -100 C to 550 C
Weight 1.1 Kg
Terminals Suitable for 2.5 sq.mm wire
Performance Specification:
Time delay Range: 0.01- 1.65 sec, 0.1- 16.5sec, 1- 165 sec,
10- 1650 sec *
Time Adjustment: 00 - 165 * 10ms/ 100ms/ 1s/ 10s
Accuracy
Setting Accuracy: +/- 5ms or <1% of set value, whichever
is greater @reference conditions
Repeat: +/- 5ms or <1% of set value, whichever
is greater @reference conditions
Change in operate time at voltage
change within rated range: +/- 3ms
Change in operate time at
temperature change within rated
range: +/- 3ms
* - In OFF delay mode minimum
operate time is 30ms.
Contact Data:
Tripping contact
Terminals: X2- 9,10
Rated voltage : 250 V dc / ac
Rated current : 5A
Make and carry for 0.5 s : 30A
Make and carry for 3.0 s : 10A
Breaking capacity for dc circuit with L/R
< 40 ms,at 48/110/220 V dc : 5A/ 3A/ 1A
Contact material: AgNi
Signaling contacts
Terminals: X2, 3- 4- 5; X2, 6- 7- 8
Rated Voltage : 250 V dc / ac
Rated current : 5A
Make and carry for 0.5 s : 10A
Make and carry for 3.0 s : 8A
1Breaking capacity for dc circuit with L/R
< 40 ms,at 48/110/220 V dc : A/ 0.25A/ 0.15A
Contact material: AgNi
Electrical endurance, IEC 255-23: 10,000 operations, at 110V dc, 0.35A
resistive, 360 op/hr
Universal Time Delay Relay type NT 10
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 6/8
6 ABB
Electrical tests:
Insulation, IEC 60255-5
Dielectric test 2KV, 50Hz, 1min
Impulse test 5KV, 1.2/50us, 0.5J
Insulation resistance test >100M Ohm at 500V dc
Power supply tests, IEC 60255-11Interruption of dc voltage 40ms/ 80v, 10ms/ 18v
Interruption of ac voltage 70 ms/ 80v
Ripple in dc voltage max. 12% of dc value
Electromagnetic compatibility tests:
1 MHz burst disturbance test,
IEC 60255-22-1 Class III
Common mode: 2.5KV, 1MHz, 400 pulses/sec
Differential mode: 1.0KV, 1MHz, 400 pulses/sec
Electrostatic discharge test,
IEC 60255-22-2 Class III
Contact discharge: 6KV, 150 pF/ 330 ohm
Air discharge: 8KV, 150 pF/ 330 ohm
Radiated electromagnetic field
immunity test, IEC60255-22-3 10V/m, f = 80...1000MHz
Fast transient disturbance test,
IEC 60255-22-4 Level III
Power supply ports: 2KV, 5/50 ns, 50 Ohm, class B
I/O ports: 2KV, 5/50 ns, 50 Ohm, class B
Surge immunity test, IEC 60255-22-5 Class III
Common mode: 2 kV, 1.2/50 us, Rs = 12 ohm
Differential mode: 1 kV, 1.2/50 us, Rs = 2 ohm
Immunity to conducted disturbancesinduced by radio frequency fields, 10V, f=150KHz...80MHz
IEC 60255-22-6
Conducted and radiated radio-frequency
emission tests, IEC 60255-25, EN55011-
CISPRII
Conducted emission (mains) Class A
Radiated emission Class A
Power frequency magnetic field
immunity test, IEC 61000-4-8
Continuous 100 A/m
Short Duration 300 A/m
Mechanical tests:
Vibration response and endurance test,
IEC 60255-21-1 Class I, 10…150Hz
Shock response and endurance test,
IEC 60255-21-2 Class I, 11ms
Bump test, IEC 60255-21-2 Class I, 10g, 1000 bumps/dir
Seismic Test, 60255-21-3 Class I
Universal Time Delay Relay type NT 10
Technical Data
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 7/8
ABB 7
Environmental tests:
Degree of protection by
enclosure when panel mounted
(front side), IEC 60529 IP 54
Dry heat test, IEC 60068-2-2 + 550 C/ +700 C
Dry cold test, IEC 60068-2-1 - 100
C/ -250
C Transport & Storage temp range,
IEC 60068-2-48 -400 C/ +700 C
Damp heat test, cyclic (12 + 12hr cycle)
test, IEC 60068-2-30
Condition 96% RH, 6 days
Ordering Details:Relay Type: NT 10 Article No.
Contact : 1NO + 2 CO
Rated Voltage: 18 - 80 Vdc 1MYN596701-A
80 - 265 Vac/dc 1MYN569701-B
Dimensions
Universal Time Delay Relay type NT 10
Technical Data
8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V
http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 8/8
1 M D B 0 8 2 2 1 - Y N 0 7 / 0 8
www.abb.co.in
ABB Limited
Maneja,
Vadodara 390013, India
Tel: +91-265-2604386
Fax: +91-265-2638922
Regional Marketing Offices:
No.14, Mathura Road
P.O. Amar Nagar
Faridabad 121 003
Tel: +91 129 2275592,
2279627, 5049000
Fax: +91 129 2279692/5019
5th Floor, West Wing
Khanija Bhavan
49, Race Course Road
Bangalore 560 001
Tel: +91 80 22949779
Fax: +91 80 22949808
North South
Century Plaza
No. 3C, 3D & 3F, 3rd Floor
561 / 562, Anna Salai
Teynampet (Mount Road)
Chennai 600 018
Tel: +91 44 24340201
Fax: +91 44 24340282
4th & 5th Floor
Maruti Heights
Aamanaka, G E Road
Raipur 492 099
Tel: +91 771 4701016
FF-9A, 1st Floor
Manasarover Commercial
Complex
Hoshangabad Road
Bhopal 462016
Tel: +91 755 4223572
Fax: +91 755 4253323
SCO No.13-14-15
(3rd Floor)
Sector 34-A
Chandigarh 160 022
Tel: +91 172 2606093
Fax: +91 172 2601618
Central
ABB House
Dr. S B Path
Ballard Estate
Mumbai 400 038
Tel: +91 22 56318231 – 39
Fax: +91 22 56318276/77
West
4th Floor
No. 9, Elgin Road
Kolkata 700 020
Tel: +91 33 22832906/8
Fax: +91 33 22832990
East