http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 2/8

2 ABB

ABB – a global leader

Advantage ABB

120 years of technology and innovation

Unparalleled domain competence

 Vast global experience

  Total solution provider

Large installed base

Environment-friendly technologies

 ABB is a global leader in Power and Automation

technologies that enable utility and industry

customers to improve performance while lowering

environmental impact. The ABB Group of companies

operates in around 100 countries.

 ABB has been present in India since 1928. Today it

has 14 manufacturing facilities in the country.

Customers are served through an extensive

countrywide presence of around 30 marketing

offices, 8 service centres, 3 logistic warehouses and

a network of over 775 channel partners.

 ABB’s Power Technologies business offers electric,

gas and water utilities as well as industrial and

commercial customers a wide range of products,

systems and services for power generation,

transmission and distribution. ABB’s turnkey solution

capabilities in the sector range from bulk power

transmission, turnkey substations and complete

electrification to substation automation and network

management systems.

 The product offering covers a wide spectrum of 

technologies across the entire voltage range

including indoor and outdoor circuit breakers, air

and gas insulated switchgear, instrument

transformers, disconnectors, capacitor banks and

filters for reactive power compensation, power anddistribution transformers and a range of power

distribution products like Compact Secondary

Substations (CSS) and Ring Main Units (RMU).

8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V

http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 3/8

 ABB 3

Universal Time Delay Relay type NT 10

Features * 4-User configurable operating modes

* Wide timing range

* Easy Setting through DIP switches

* Manual Reset 'Flag' LED indication

* Both signaling duty and trip duty

contacts available

* Micro-controller based design for

high accuracy

Application:  The NT 10 relay is intended for use

where high operating requirements are

necessary, such as in protection relay

systems, control equipment, industrial

processes, and control and signal

systems.

 The multiple user selectable options

provide flexibility to user, for use in

various applications. The wide timing

range, high timing accuracy and

consistency of operation can replace

any other time relays.

Description:  The time delay relay type NT 10 is high

precision, numerical time relay with

builtin electro mechanical output relays

providing- two CO signaling duty

contacts and one NO trip duty contact.

 The micro-controller based relay designprovides accurate timing and varied

operating modes. The four operating

modes are: ON Delay, OFF Delay,

Flasher and Interval. The required

timing and operating mode can be set

by adjusting the DIP switches on the

front panel.

 The timing function is triggered by

control input depending on the mode

selection. The control input has same

rated voltage as auxiliary voltage andis galvanically isolated.

 The four LEDs on the front panel

indicates status of relay. The presence

of healthy auxiliary supply is indicated

by green 'Uaux' LED. The operation of 

relay is indicated by red 'TRIP' LED.

 The yellow 'Start' LED indicates,'timing' status in 'ON Delay' and 'OFF

Delay' modes. In 'Flasher' and 'Interval'

mode Start LED indicates the status of 

control input.

 The start LED additionally indicates the

change of mode selection. When mode

setting is changed, yellow 'Start' LED

blinks and the relay does not respond

to the control input till mode setting

change is applied by pressing 'Reset'

push button. The 'IRF' LED indicates the internal

relay fault.

Block Diagram:

8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V

http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 4/8

4 ABB

OperationalModes:

 The following modes are possible when the relay is energized with auxiliary supply.

ON Delay: In this mode, the timing starts when the control input is applied and after

the set time has elapsed, the delayed output switches to the operate condition

OFF Delay: In this mode, the output immediately switches to operate condition

when applying the control input and in which the timing starts when the control

input is disconnected and the output switches to released condition after set time

has elapsed

Interval: In this mode, the relay switches the output to operate condition for set

time when the control input is applied or removed

Reset PB will not have any

effect in this mode

Flasher: In this mode, the output periodically switches on and off with substantially

identical pulse on time and pulse off time as long as the control input is applied

Reset PB will not have any

effect in this mode

Universal Time Delay Relay type NT 10

Uaux

Control I/P

Start LED

TRIP LED

O/P Contact

Resett t

Uaux

Control I/P

Start LED

TRIP LED

O/P Contact

Resett t

Uaux

Control I/P

Start LED

Trip LED

O/P Contact

Resett t

Uaux

Control I/P

Start LED

Trip LED

O/P Contact

Reset

t t

8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V

http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 5/8

 ABB 5

Technical Data General

Energizing quantities, rated values and limits:

Rated Auxiliary Voltage Un (X1- 2,4) : 18 - 80V dc

80 - 265V ac/dc

Control Input (X2- 1,2) : 24 - 250 V ac/dc

Rated Frequency: 50HzPower Consumption, Uaux

Before Operation : < 3W

 After Operation : < 4W

Power Consumption, Control Input < 0.6W

Rated ambient temperature: -100 C to 550 C

Weight 1.1 Kg

 Terminals Suitable for 2.5 sq.mm wire

Performance Specification:

 Time delay Range: 0.01- 1.65 sec, 0.1- 16.5sec, 1- 165 sec,

10- 1650 sec *

 Time Adjustment: 00 - 165 * 10ms/ 100ms/ 1s/ 10s

 Accuracy

Setting Accuracy: +/- 5ms or <1% of set value, whichever

is greater @reference conditions

Repeat: +/- 5ms or <1% of set value, whichever

is greater @reference conditions

Change in operate time at voltage

change within rated range: +/- 3ms

Change in operate time at

temperature change within rated

range: +/- 3ms

* - In OFF delay mode minimum

operate time is 30ms.

Contact Data:

Tripping contact

 Terminals: X2- 9,10

Rated voltage : 250 V dc / ac

Rated current : 5A

Make and carry for 0.5 s : 30A

Make and carry for 3.0 s : 10A

Breaking capacity for dc circuit with L/R

< 40 ms,at 48/110/220 V dc : 5A/ 3A/ 1A

Contact material: AgNi

Signaling contacts

 Terminals: X2, 3- 4- 5; X2, 6- 7- 8

Rated Voltage : 250 V dc / ac

Rated current : 5A

Make and carry for 0.5 s : 10A

Make and carry for 3.0 s : 8A

1Breaking capacity for dc circuit with L/R

< 40 ms,at 48/110/220 V dc : A/ 0.25A/ 0.15A

Contact material: AgNi

Electrical endurance, IEC 255-23: 10,000 operations, at 110V dc, 0.35A

resistive, 360 op/hr

Universal Time Delay Relay type NT 10

8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V

http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 6/8

6 ABB

Electrical tests:

Insulation, IEC 60255-5

Dielectric test 2KV, 50Hz, 1min

Impulse test 5KV, 1.2/50us, 0.5J

Insulation resistance test >100M Ohm at 500V dc

Power supply tests, IEC 60255-11Interruption of dc voltage 40ms/ 80v, 10ms/ 18v

Interruption of ac voltage 70 ms/ 80v

Ripple in dc voltage max. 12% of dc value

Electromagnetic compatibility tests:

1 MHz burst disturbance test,

IEC 60255-22-1 Class III

Common mode: 2.5KV, 1MHz, 400 pulses/sec

Differential mode: 1.0KV, 1MHz, 400 pulses/sec

Electrostatic discharge test,

IEC 60255-22-2 Class III

Contact discharge: 6KV, 150 pF/ 330 ohm

 Air discharge: 8KV, 150 pF/ 330 ohm

Radiated electromagnetic field

immunity test, IEC60255-22-3 10V/m, f = 80...1000MHz

Fast transient disturbance test,

IEC 60255-22-4 Level III

Power supply ports: 2KV, 5/50 ns, 50 Ohm, class B

I/O ports: 2KV, 5/50 ns, 50 Ohm, class B

Surge immunity test, IEC 60255-22-5 Class III

Common mode: 2 kV, 1.2/50 us, Rs = 12 ohm

Differential mode: 1 kV, 1.2/50 us, Rs = 2 ohm

Immunity to conducted disturbancesinduced by radio frequency fields, 10V, f=150KHz...80MHz

IEC 60255-22-6

Conducted and radiated radio-frequency

emission tests, IEC 60255-25, EN55011-

CISPRII

Conducted emission (mains) Class A

Radiated emission Class A

Power frequency magnetic field

immunity test, IEC 61000-4-8

Continuous 100 A/m

Short Duration 300 A/m

Mechanical tests:

 Vibration response and endurance test,

IEC 60255-21-1 Class I, 10…150Hz

Shock response and endurance test,

IEC 60255-21-2 Class I, 11ms

Bump test, IEC 60255-21-2 Class I, 10g, 1000 bumps/dir

Seismic Test, 60255-21-3 Class I

Universal Time Delay Relay type NT 10

Technical Data

8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V

http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 7/8

 ABB 7

Environmental tests:

Degree of protection by

enclosure when panel mounted

(front side), IEC 60529 IP 54

Dry heat test, IEC 60068-2-2 + 550 C/ +700 C

Dry cold test, IEC 60068-2-1 - 100

C/ -250

C Transport & Storage temp range,

IEC 60068-2-48 -400 C/ +700 C

Damp heat test, cyclic (12 + 12hr cycle)

test, IEC 60068-2-30

Condition 96% RH, 6 days

Ordering Details:Relay Type: NT 10 Article No.

Contact : 1NO + 2 CO

Rated Voltage: 18 - 80 Vdc 1MYN596701-A

80 - 265 Vac/dc 1MYN569701-B

Dimensions

Universal Time Delay Relay type NT 10

Technical Data

8/3/2019 D - 481_Relay NT10 Brochure - Revised 5V

http://slidepdf.com/reader/full/d-481relay-nt10-brochure-revised-5v 8/8

   1   M   D   B   0   8   2   2   1  -   Y   N   0   7   /   0   8

www.abb.co.in

 ABB Limited

Maneja,

  Vadodara 390013, India

 Tel: +91-265-2604386

Fax: +91-265-2638922

Regional Marketing Offices:

No.14, Mathura Road

P.O. Amar Nagar

Faridabad 121 003

 Tel: +91 129 2275592,

2279627, 5049000

Fax: +91 129 2279692/5019

5th Floor, West Wing

Khanija Bhavan

49, Race Course Road

Bangalore 560 001

 Tel: +91 80 22949779

Fax: +91 80 22949808

North South

Century Plaza

No. 3C, 3D & 3F, 3rd Floor

561 / 562, Anna Salai

 Teynampet (Mount Road)

Chennai 600 018

 Tel: +91 44 24340201

Fax: +91 44 24340282

4th & 5th Floor

Maruti Heights

 Aamanaka, G E Road

Raipur 492 099

 Tel: +91 771 4701016

FF-9A, 1st Floor

Manasarover Commercial

Complex

Hoshangabad Road

Bhopal 462016

 Tel: +91 755 4223572

Fax: +91 755 4253323

SCO No.13-14-15

(3rd Floor)

Sector 34-A

Chandigarh 160 022

 Tel: +91 172 2606093

Fax: +91 172 2601618

Central

 ABB House

Dr. S B Path

Ballard Estate

Mumbai 400 038

 Tel: +91 22 56318231 – 39

Fax: +91 22 56318276/77

West

4th Floor

No. 9, Elgin Road

Kolkata 700 020

  Tel: +91 33 22832906/8

Fax: +91 33 22832990

East