ctg029

Upload: laurentiucucu4392

Post on 03-Jun-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 CTG029

    1/35

    LightingBest Practice Northern Ireland

    Funded by

    Technology guide

    enter

  • 8/11/2019 CTG029

    2/35

  • 8/11/2019 CTG029

    3/35

    Menu

    3Lighting

    Types of lighting

    Colour appearance andcolour rendering

    Colour appearance (g.1) denes a lights

    whiteness, which can be bluish (cool), white or

    reddish (warm). This is measured in degrees

    Kelvin (K). A colour appearance of less than

    3,500K is warm white, a colour appearance of

    3,500K is mid-white, and a colour appearance

    above 3,500K is cooler white.

    Colour rendering (g. 2) is the ability of a light

    source to give good colour representation

    of the colour it is illuminating. This is measured

    on a scale of Ra0-100 with Ra100 the best

    representation. Daylight would be Ra100.

    Below Ra80 the human eye does not

    differentiate the different hues well.

    Fig. 2 Colour rendering

    (a) Low pressure sodium (SOX) Ra~5, (b) Daylight Ra100

    Fig. 1 Colour appearance of various

    light sources

    North Light/Blue Sky

    8,500

    Overcast Sky

    6,500 7,500

    Summer Sunlight

    5,500

    Metal Halide Lamp

    Tungsten Halogen

    Lamp

    50W Tungsten

    Lamp

    40W Lamp

    Candle

    High Pressure Sodium

    Compact Fluorescent

    Lamp

    Full Spectrum

    Intermediate Fluorescent Tube

    Warm Fluorescent Tube

    Sodium Street Lamp

    Cool Fluorescent Tube

    9,000

    8,000

    8,500

    7,000

    6,000

    5,000

    4,000

    3,000

    2,000

    7,500

    6,500

    5,500

    4,500

    3,500

    2,500

    1,500HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    4/35

    Menu

    4Lighting

    Fig. 3 Summer daylight (Ra100), which has a

    cool appearance (5,500K) on white walls and

    shows the red ceramics in their true colour.

    Fig. 4 Tungsten light and tungsten halogen(Ra100), which has a warm appearance and

    shows the white walls as warm white (2,600K)

    and accentuates the red on the ceramics.

    Fig. 5 Standard single phosphor uorescent light

    (Ra58), which has a cool appearance (6,000K) on

    white walls and reduces the colour rendering on

    the ceramics.

    Comparing types of light

    The charts overleaf compares the colour

    appearance and colour rendering of different

    lamps. It also shows the lumen efcacy (theamount of light provided for each watt of power

    used), and the lifespan. This last feature shows

    the number of hours when the lamp fails

    completely or when tubes and discharge lamps

    degrade and fall to 80% of their original level.

    Theres no accepted standard or regulation for

    dening the lifespan of LEDs yet, so as a guide

    Fig. 5 Standard single phosphor uorescent

    light (Ra58)

    Fig. 4 Tungsten light and tungsten halogen

    (Ra100)

    an LED should provide 70% of the

    initial lumens at 35,000 hours. The maximum life

    of an electronic driver, which operates the LED is

    50,000.

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    5/35

    Menu

    5Lighting

    Lamp type Luminous

    efcacy

    (Lumens/

    Watt)

    Colour

    appearance

    (Kelvin)

    Colour

    rendering

    (Ra)

    Life

    (Hours)

    Tungsten 12 2600 100 1000

    Tungsten Halogen 8.75

    5.25

    18 20

    2500

    2500

    3000

    100

    100

    100

    6000

    16000

    2000 8000

    Compact Fluorescent (2) 47 82 2700 4000 85 8000+

    38mm T12 White F/Tube (1) 36 71 3500 59 7000+

    25mm T8 White F/Tube (1) 37 68 3500 58 8000+

    25mm T8 White F/Tube (2) 55 80 3500 58 8000+

    25mm T8 Full spectrum multiphosphor (2) 64 5000 95 17500

    25mm T8 H/F Triphosphor (2) 71 92 2700 6000 80+ 12000 24000

    25mm T8 H/F Triphosphor Extreme (2) 71 3000 4000 80+ 40000

    60000

    25mm T8 H/F Triphosphor (2) 57 82 2700 6000 90+ 12000+

    16mm T5 H/F Triphosphor (HE) (2) 66 82 2700 6500 80+ 16000+

    16mm T5 H/F Triphosphor (H0) (2) 62 76 2700 6500 80+ 16000+

    7mm T2 H/F Triphosphor (2) 55 3500 6000 85 8000 12000

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    6/35

    Menu

    6Lighting

    Lamp type Luminous

    efcacy

    (Lumens/

    Watt)

    Colour

    appearance

    (Kelvin)

    Colour

    rendering

    (Ra)

    Life

    (Hours)

    Metal Halide (1) 71 83 3000 6000 65 85 8000 20000

    Metal Halide (2) 86 95 3000 6000 65 85 8000 20000

    Mercury (1) 31 57 3900 4200 36 49 12000+

    Mercury Deluxe (1) 31 57 3300 3500 47 58 12000+

    Low Pressure Sodium/E (2) 148 173 1800 0 12000

    High Pressure Sodium (1) 65 103 2000 25 12000

    30000

    High Pressure Sodium D/L (1) 78 85 2200 65 12000

    White Sodium (2) 31 46 2500 80 8000+

    Induction (2) 62 70 2700 4000 85 10000

    60000

    Light Emitting Diodes (LEDs) (2) 50/100 Saturated

    /3- 6000

    70/80 50/100000

    1 Operated on standard electromagnetic control gear2 Operated on electronic high frequency control gear

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    7/35

    Menu

    7Lighting

    Recommended light levels

    This chart sets out the recommended light levels

    for a range of activities, as provided by Chartered

    Institution of Building Services Engineers (CIBSE).

    Standard Maintained illuminance (lux)

    50 Cable tunnels, indoor storage tanks, walkways

    100 Corridors, changing rooms, bulk stores, auditoria

    150 Loading bays, medical stores, plant rooms

    200 Foyers and entrances, monitoring automatic processes, casting concrete, turbine halls, dining

    rooms

    300

    300-500

    Libraries, sports and assembly halls, teaching spaces, lecture theatres, packing

    Ofces

    500 Engine assembly, painting and spraying, kitchens, laboratories, shops

    750 Drawing ofces, ceramic decoration, meat inspection, chain stores

    1000 General inspection, electronic assembly, gauge and tool rooms, retouching paintwork, cabinet

    making, supermarkets

    1500 Fine work and inspection, hand tailoring, precision assembly

    2000 Assembly of minute mechanisms, nished fabric inspection

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    8/35

    Menu

    8Lighting

    Lighting in the hospitality sector

    Lighting in this sector accounts for nearly a third of a companys electricity costs. By switchingto energy efficient, effective lighting either using new bulbs or lamps in existing fittings or

    changing to new light sources its possible to save up to 70% of the energy.

    The rst consideration is whether you can get the

    same level of lighting (or better) using new bulbs

    or tubes, or whether youll need to change ttings.

    In some settings, there are statutory standards for

    the level of illumination you need to provide.

    Many areas in hotels use standard tungsten

    lament bulbs. New legislation means these wont

    be available within the next few years (see g. 7),

    so youll need to nd replacements. Most will

    change over to compact uorescent lights with

    integrated electronics (CFLi) or tungsten halogen

    globe or candle shaped lamps. Cheaper LED globe

    or candle shaped lamps may become available too.

    At the moment, CFLi are available in dimmable

    models and a range of shapes, and tungsten

    halogen lamps are dimmable as standard.

    Some, but not all LED models can be dimmed.

    See appendix 1 for more detail.

    Fig. 7 The EU ban on incandescent lamps

    Examples and solutions

    1. Hat problms sig tgst lamps

    An immediate advantage is that the CFLi (15,000

    hours) and LED (50,000 hours) replacements for

    tungsten lamps (1,000 hours) work at a lower

    temperature, so are less likely to burn fabric

    shades. See g. 8.

    The EU ban on incandescent lamps:

    2009

    Ban on sales

    fromSeptember 1

    2010

    Ban on salesfrom

    September 12011

    Ban on salesfromSeptember 1 2012

    Ban on salesfromSeptember 1

    GLSincandescentlamps

    (950 Im) and allfrosted GLSincandescentlamps*

    from 80W

    GLSincandescentlamps

    (725 Im)

    from 65W

    GLSincandescentlamps

    (450 Im)

    from45W

    GLSincandescentlamps

    (60 Im)

    from 7W

    Fig. 8

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    9/35

    Menu

    9Lighting

    Fig. 9 Examples of dimming and non-

    dimming compact uorescent lamps (CFLi).

    Refer to Appendix 1 for further lamp detail.Energy Equation Refer to Chart in Appendix 2.

    Another option is to replace the existing 60W

    (1,000 hours) tungsten lamp with a 6W LED.

    The table lamp in the foreground is 6W LED;

    the others are 60W tungsten. See g. 10.

    Fig. 10

    Refer to Appendix 1 for further lamp detail.Energy Equation Refer to Chart in Appendix 2.

    2. Rplacig stadard tgst cadl or

    glob tgst lamps (1,000 hors) with

    dimmabl tgst halog lamps

    Sometimes CFLi lamps might not be suitable

    because of their appearance. You can still save

    30% of the energy by using tungsten halogen IRC

    (2,000 hours) lamps. See g. 11.

    3. Ifcit T12 orsct tbs

    You can save between 30% and 49% in energy

    use by replacing the old technology of T8 and T12

    uorescent tubes, operated by electromagnetic

    ballasts, with new T5 or T8 uorescent tubes,

    operated by electronic high-frequency ballasts.

    The added benets are an instant start and no

    ickering. When the tubes have reached the end

    of their life, they simply go out no more of that

    irritating ashing. See g. 12.

    You can also adapt old ttings to take the new

    tubes using a T5 electronic adaptor (g. 12). These

    are best suited for 600mm, 1.2m and 1.5m tubes.

    Fig. 11

    Refer to Appendix 1 for further lamp detail.Energy Equation Refer to Chart in Appendix 2.

    Fig. 12 Inefcient uorescent tubes

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    10/35

    Menu

    10Lighting

    4. Rplacig 20W MR16 50mm low voltag

    dichroic (2,000 hors) lamps with 3.6W

    LeDs (35-50,000 hors) i bdrooms

    You can get the same lighting effect for less energy

    and with easier maintenance by changing low

    voltage tungsten halogen lamps for LEDs. See gs

    13 and 13a.

    Fig. 1320W MR16

    Fig. 13a 3.6W LED

    Refer to Appendix 1 for further lamp detail.Energy Equation Refer to Chart in Appendix 2

    5. Rplacig Gu10 tgst halog dichroic

    lamps (1,500 hors) with 4W LeDs

    (35/50,000 hors) i bdroom lobbis

    6. Rplacig 50W MR16 low voltag dichroic

    lamps with 5W LeDs i corridors

    Its a good idea to test LED lamps because their

    colour, rendering and lifespans differ. Take lighting

    levels to make sure they reach the required

    standard of an average of 100 lux. In gs 14 and

    14a, well-chosen LEDs give good lighting while

    cutting costs.

    Fig. 14a 4W LED

    Fig. 14 20W GU10

    Fig. 15 50W MR16 Fig. 15a5W LED

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    11/35

    Menu

    11Lighting

    Choosing LEDs for colour,lifespan and brightness

    When youre choosing LEDs, you need to

    remember that they differ even though thewattage may be the same. They come with

    different colour appearance, colour rendering and

    lifespan. See g. 16 A good quality LED light

    should give 70% of the initial light output after

    35,000 hours.

    Fig.16 shows two 4W LED lamps. The one on the

    left has a colour appearance of 3,000K and a

    colour rendering index of Ra80. The one on the

    right has a colour appearance of 4,500K and acolour rendering index of Ra60. The warmer LED

    lamp in this scenario gives a preferable lighting

    effect as well as providing more light.

    Fig. 16 4W LED lamps

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    12/35

    Menu

    12Lighting

    Lighting in the industrial sector

    Improvements include re-evaluating the light levels

    needed, changing the types of lamp, positioning

    ttings for easier maintenance and making lighting

    more controllable using daylight or movement

    sensors. All these measures many of them very

    simple can reduce operating costs and save energy.

    The case study illustrated in Figures 17 & 18

    demonstrates the advantages. The 250W metal

    halide lamps (16,000 hours) are mounted at roof

    level, which makes them difcult and costly to

    maintain. This type of tting needs to warm up

    when rst switched on, and to cool down before

    they can relight after the power supply is

    interrupted. This delay means the introduction of

    daylight or occupancy controls is often impractical.

    The Carbon Trust re-evaluated this area and found

    that lighting levels could be maintained by lowering

    the height and installing lower wattage lamps. The

    new lamps are longer lasting and, because they

    turn on instantly, can be linked to daylight sensors.

    Each light was replaced with prismatic reector

    lights with 165W inductive lamps (g. 15), which

    have a 60,000-hour life.

    Fig. 17 These 250W metal halide lamps are

    mounted high up and are difcult to maintain.

    Theyre not suitable for automatic switching onand off using a daylight sensor because they

    have a start-up delay.

    Fig. 18 The height wasnt actually important

    there were no cranes to pass under them, for

    example so lights could be tted at lower level,

    making maintenance easier. Lower heights meant

    the lamps could be replaced for more efcient

    types linked to daylight sensors.

    Fig 18

    Energy Equation

    250W mtal halid = 277W ach

    165W idctiv = 165W ach

    ergy savig = 112W (40%)

    Fig 17

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    13/35

    Menu

    13Lighting

    Evaluating your lighting

    Large open-plan areas are the norm in production

    areas and can seem a challenge when it comes to

    lighting. Follow these simple steps to work outwhere you could save.

    1. What level of lighting do you really need?

    If you have task lighting in some areas of an open

    plan space, you may nd you can reduce general

    lighting from between 300 -500 lux to 100-150 lux,

    which is the standard for circulation areas.

    2. Are all areas occupied?

    If some areas arent occupied for some of the

    time, you can zone your lighting, using manual

    or automatic switching.

    3. Are you making the most of daylight?

    If theres daylight in some areas, you can link

    dimmable lighting to a photocell control or constant

    lux sensor. When natural light levels are high enough,

    your lights will automatically dim to a pre-set level.

    Distribution and controls

    When a light shines very widely and there are no

    existing lighting controls, you have immediate

    scope to save energy without losing brightness.

    In the factory in g. 19, the high bay lights used

    400W metal halide white lamps (430 circuit watts)

    providing 75 lumens per watt. These were

    replaced with four-lamp 55W PLL compact

    uorescent lamps (222 circuit watts) providing

    86 lumens per watt. The narrower beam gave

    the same level of illumination.

    The PLL compact uorescent lamps can also be

    dimmed when used with appropriate control gear.Programmable, integrated presence and daylight

    sensors mean the factory can cut energy use

    and costs by zoning areas and using daylight

    when available.

    Fig. 20

    Energy Equation400W mtal halid = 430W ach

    4 x 55W PPL CFL = 236W ach

    ergy savig = 194W (45%)

    Fig. 19 Steps one to three apply here

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    14/35

    Menu

    14Lighting

    Scope for energy savings

    These four photographs show areas where

    energy savings can be made using T5

    or compact uorescent lighting, with eitherintegral or integrated daylight and presence

    detection. The lighting here is metal halide

    and standard T8 switch-start uorescent tubes.

    The cost of replacing these would be recouped

    in less than four years.

    This controlled lighting system saves energy

    by switching off the lighting when there is

    enough daylight.

    The benet of using a uorescent light source is

    that they can be dimmed, therefore daylight and

    presence sensors can be used to reduce the light

    level to the required amount. By utilising integral

    presence and daylight detection, further savings

    are achievable as particular zones within the space

    can be controlled accordingly.

    These images show good examples of where

    daylight sensors could be utilised, in common

    installations, to incorporate the natural daylight

    ingression providing energy savings from this

    free valuable resource.

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    15/35

    Menu

    15Lighting

    Wasted light

    In many settings, changes to the internal layout

    or simply racking being moved can interfere

    with the existing lighting. When you makechanges to the space, re-evaluate what

    lighting levels you need.

    a) Re-positioning the uorescent lights can

    increase lighting levels. If higher light levels

    arent needed, you can take a tube out of each

    tting 50% energy savings1.

    b) If changes mean lighting isnt needed any

    more, check that its disconnected or removed

    100% energy saving on each lamp.

    c) The best way to light corridors is to t lights

    parallel to the walls a 30% reduction in

    energy for the required 100 lux level.

    Use a lux meter to check that youre not over-

    lighting any areas. Providing you stick to the

    regulation levels, you can remove bulbs or tubes

    if theyre not needed. This example is an over-lit

    corridor. A tube could be removed from eachtting or every other tting could be disconnected.

    1 Check with your electrician or original lighting supplier to

    conrm performance of the tting or lighting circuit will not be

    affected by the removal of a tube or disconnection of a tting.

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    16/35

    Menu

    16Lighting

    Case study

    Montupet Factory

    A factory with a larg oor ara of arod 51,000m2 had lightig datd from th 1970s. Thr

    wr 2,300 twi T12 orsct tbs, ach 2.4m (8) log ad with a circit ratig of 229W.

    Th total factory lightig dmad was 527kW.

    By rplacig ths ot-datd tbs with modr twi 49W T5 orsct tbs with

    triphosphor coatigs ad high-frqcy cotrol gar (circit ratig of 111W ach), lightig

    lvls wr improvd for th workforc for lss tha half th powr dmad.

    Th w lightig cost arod 110,000, bt rgy costs fll by mor tha 130,000 a yar,

    so th payback priod was lss tha a yar. Th compay also savd 1,022t of CO2a yar.

    Bfor Aftr

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    17/35

    Menu

    17Lighting

    Savings checklist

    Done

    1 Ar th color apparac ad color rdrig right for th applicatio?

    2 Ar lightig lvls right?You can reduce the number of lights if an area is too bright, providing it meets regulation levels.

    3 Ar lights i th right plac?Check lights arent blocked by racking or other structures. Consider lowering the height of ttings when replacing lamps.

    4 Ar yo makig th most of cotrols?

    Fit photocell sensors to switch off or dim lights when theres enough daylight. Fit presence detectors to zone areas that arent used all the time.Can any existing high-intensity discharge (HID) lighting be zoned or linked to daylight?

    5 Ar yo still sig old T12 orsct lightig?Replace with T8 or T5 electronic high-frequency models. Evaluate the cost of replacing HID with T5 or compact uorescent lights with

    integrated controls.

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    18/35

    Menu

    18Lighting

    Lighting in offices

    To make ofce lighting efcient, effective and

    energy-saving, there are four basics.

    1. When lights needed, it should be used as

    economically as possible.

    2. The level and distribution of light should be

    right for the task.

    3. When lightings not needed, it should be

    switched off.

    4. The lights should need little maintenance.

    Replacing inefcient uorescent tubes

    Many ofces still use old T12 uorescent tubes.

    These lamps work with electromagnetic ballasts,

    which use between 10 and 14W of electricity foreach tube. These should be replaced with ttings

    that take either T5 or T8 triphosphor uorescent

    tubes or compact uorescent lamps with

    electronic high-frequency ballasts.

    The typical energy used by a four-way 20W

    600mm x 600mm tting using T12 tubes (21),

    uses 120W, whereas a twin 40W PLL compact

    uorescent light (2) gives better light levels and

    uses only 84W a 30% energy saving.

    This twin 40W PLL compact uorescent recessed

    light tting (22) complies with CIBSE LG7 and has

    an integral presence detector, which automatically

    switches the light off when the area isnt being used.

    A photocell or constant lux sensor allows the light to

    be dimmed or switched off if there is enough daylight.

    Fig. 21

    Fig. 22

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    19/35

    Menu

    19Lighting

    This example (Fig. 23) shows effective ofce

    lighting that maximises energy efciency. The

    twin T5s shine both up and down, avoiding the

    tunnel effect of dark ceilings. The T5 lights are

    suspended and are controlled by a daylight sensorand presence detector.

    The twin surface-mounted lights (Fig. 24) use

    inefcient T12s with electromagnetic ballasts.

    There diffusers limit light output and they dont

    comply with the CIBSE LG7 guide for ofce

    lighting. Each uses 102W of electricity. Replacing

    them with twin 28W T5s with approved diffusers

    would save 40W an energy reduction of 40%.

    The lights shown here (Fig. 25) have a low output

    ratio (LOR). To get the right levels, this means

    more lights have had to be installed. Instead,

    fewer lights with higher output could be used,

    saving up to 60%. There would be even higher

    savings with presence sensors.

    Simply using daylight (Fig. 26) could save you

    4,500 hours of lighting a year. Photocells or

    daylight sensors dim or switch off the lighting at a

    pre-set level.

    Fig. 23

    Fig. 24

    Fig. 25

    Fig. 26

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    20/35

    Menu

    20Lighting

    Savings checklist

    Done

    1 Choos T5, T8 triphosphor or compact orsct lights with lctroic ballasts.

    2 Choos lights with a high otpt ratio (LOR) of 65% or mor.

    3 Fit daylight ad prsc dtctor cotrols to switch or dim lights atomatically.

    4 Choos ttigs ad lamps that qalify for ehacd Capital Allowacs (eCA).

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    21/35

    Menu

    21Lighting

    Lighting in the leisure sector

    Good lighting in sports and leisure buildings

    should not only look attractive to users, it should

    give just the right type and level of light for a range

    of activities. And, of course, it should be effective,

    energy efcient and need minimum maintenance.

    Get these factors right, and combine electric

    lighting with good use of daylight, and you can

    dramatically reduce energy costs.

    These examples (g. 27 and 28) show typical

    lighting schemes. The lights are left on whenever

    the building is open whether its being used or

    not because theres a delay before the lights

    reach full brightness.

    Both use metal halide lamps in high bay ttings.

    Although these are relatively efcient, using T5

    tubes or compact uorescent lamps with the same

    light output would mean presence detectors anddaylight switching or dimming could be used. A

    250W metal halide high mount light uses 279W

    (circuit watts), whereas a four x 55W compact

    uorescent high mount light uses 222W (circuit

    watts). This simple change gives an energy saving of

    20%. Presence detectors could save another 30%.

    This example (g. 29) is typical of a sports hall that

    has some daylight. Using either T5 or compact

    uorescent lamps with photocell or constant lux

    sensors, the lights can be dimmed or switched off

    when theres enough daylight to maintain a

    pre-set level. This can save around 30% of theenergy.

    Fig. 28

    Fig. 29

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    22/35

    Menu

    22Lighting

    Savings checklist

    Done

    1 Ar th color apparac ad color rdrig right for th applicatio?

    2 Ar lightig lvls right?You can reduce the number of lights if an area is too bright, providing it meets regulation levels.

    3 Ar lights i th right plac?Check lamps arent blocked by racking or other structures. Consider lowering the height of ttings when replacing lamps.

    4 Ar yo makig th most of cotrols?

    Fit photocell sensors to switch off or dim lights when theres enough daylight. Fit presence detectors to zone areas that arent used all the time.Can any existing high-intensity discharge (HID) lighting be zoned or linked to daylight?

    5 Ar yo still sig old T12 orsct lightig?Replace with T8 or T5 electronic high-frequency models. Evaluate the cost of replacing HID with T5 or compact uorescent lights with

    integrated controls.

    HELP

    L

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    23/35

    Menu

    23Lighting

    Lighting in the retail sector

    Shops and stores have a variety of different needs

    for their lighting. Fashion and jewellers shops, for

    example, need good general light levels but also

    use a lot of accent lighting. Supermarkets and

    warehouse stores, on the other hand, use mainly

    general or ambient lighting.

    There are some techniques that can be used

    whatever the situation, though, and there are

    energy savings to be made in almost all cases.

    Ambit lightigUsing triphosphor tubes or compact uorescent

    lamps for general lighting gives a wide spread of

    light so that customers can see and inspect items

    and make their way around the shop. Customers

    should be able to read labels and information

    about products easily.

    Acct lightigMetal halide highlighting or spotlighting provides

    contrast and draws the attention to particular items.

    Badly positioned lights, however, will cause glare,

    making viewing uncomfortable for customers.

    Primtr lightigFluorescent or LED lighting helps establish the

    overall image of the shop and denes its

    boundaries when used to light vertical surfaces.

    Shlf ad display cas lightigLED lighting can be enclosed in display cabinets

    or positioned very close to products without

    damaging them.

    This example (g. 30) shows recessed lights that

    have three 55W PLL compact uorescent lamps

    and low brightness louvres. These luminaires have

    a low output ratio (LOR) of 57%, which means

    more lamps have to be used to light up the retail

    area. Each lamp uses 174W of energy.

    Swap to a light with a 76% LOR, using two 55W

    PLL compact uorescent lamps, and you get thesame light levels but use only 115W a 36%

    energy saving and savings on lamp replacements

    in the future.

    This next example (g. 31) shows an effective,

    energy efcient retail lighting scheme. There are

    recessed twin 24W T5 uorescent tubes with

    matte louvres to avoid the ceiling being dark. They

    have an LOR of 70% and use just 51W per light.

    Fig. 30

    Fig. 31

    HELP

    24

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    24/35

    Menu

    24

    Chillr ad frzr cabitsThese tend to use 1.2m 36W uorescent tubes

    (g. 32), operated by electromagnetic switch-start

    ballasts, and use 46W (circuit Watts). Replacing

    each uorescent tting with a 25W LED strip

    saves around 40% of the energy.

    LED lights (g. 33) operate better at cooler

    temperatures they are 60% brighter at -20 C.

    A T8 uorescent tube provides only 70% of its

    original light at +5c, and a T5 tube provides

    70% at +20C.

    LEDs also last far longer than uorescent tubes,

    which keeps costs lower, A 38mm diameter T8

    tube lasts between 15,000 hours and 20,000

    hours, depending on whether its single or

    triphosphor lamps. An LED strip should last for

    50,000 hours before the whole strip would need

    replacing, and at 35,000 hours should still give

    70% of its original light output.

    Fig. 32

    Fig. 33

    HELP

    25Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    25/35

    Menu

    Fig. 34 Fig. 36

    Fig. 35 Fig. 37

    25Lighting

    Exterior lightingTo make outside lighting efficient, effective and energy-saving, there are four basics.

    1. Bulbs need to give you more than 15,000

    hours life.

    2. Light tting should be directed where

    its needed without spilling and causing

    light pollution.

    3. Lights should have a high output of more than

    65% LOR.

    4. There should be daylight sensors and timers

    to switch lights on and off automatically.

    Examples of inefcientoutside lighting

    Both the lights in these examples (g. 34 and 35)

    give poor illumination because of the opaque

    cover. This style of light also shines above the

    horizontal, causing light pollution, reducing the

    amount of light that gets to where its actually

    needed and wasting energy.

    Post-top lights (g. 36) with thick plastic, opalHELP

    26Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    26/35

    Menu

    26Lighting

    spheres have poor light output and shine 50% of

    their light above the horizontal. Energy is wasted

    and theres limited illumination.

    Tungsten halogen lighting (g. 37) is inefcient

    and has a relatively short life. It should be avoided

    wherever possible. When instant-start lighting

    is needed for security lighting with automatic

    presence detection (PIR), for example use

    compact uorescent lamps.

    When you use standard oodlighting (g. 38, 39

    and 40), a high percentage of light shines above

    the intended target. Its a waste and can also be

    a nuisance for neighbouring properties.

    Examples of effectiveoutside lighting

    When the right sort of lighting is used, as in this

    hockey eld (g. 41, theres no light pollution and

    you save around 40% of the energy. Have a look

    at g. 42 too for an illustration of how efcient

    asymmetrical oodlighting can be.

    This good example of illuminating a car park (g. 43)

    takes into account the risk of light pollution for

    nearby houses. The lights have been directed into

    the car park and are controlled by daylight sensors.

    Fig. 38 Fig. 41

    Fig. 39

    Fig. 42

    Fig. 40 Fig. 43HELP

    27Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    27/35

    Menu

    27Lighting

    Savings checklist

    Done

    1 Is th light shiig whr its dd?If the light is shining too widely, especially up into the sky, it wastes energy, causes light pollution and can be a nuisance for neighbours.

    2 Ar yo sig th most fcit ad ffctiv typ of light?Consider the lifespan of the bulbs and the controllability of your lights.

    3 Do yor lights giv yo th right color apparac ad color rdrig?This is very important if you are using CCTV, as colours need to show up accurately.

    4 Ar yo makig th most of cotrols?

    Fit photocell sensors to switch off lights when theres enough daylight. Fit presence detectors to zone areas that arent used all the time.

    HELP

    28Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    28/35

    Menu

    g g

    Lighting controlsBy using timers, daylight sensors or presence detectors, you can control your lighting so that it

    turns on and off or dimming automatically. Because lights are only on when needed, you saveenergy and extend the life of your lights.

    Below are three examples of the possible savings

    if automatic controls are installed:

    Manufacturing, hotels,

    hospitals, petrol stations

    Annual operational hours = 8,760

    Lighting is needed for around 4,000 hours

    45% saving.

    Ofces and schools

    Annual operational hours = 3,000

    Lighting needed for only part of this time

    More than 50% saving.

    Retail, licensed premises

    Annual operational hours = 5,000

    Lighting needed for only part of this time

    Savings from cutting window area lighting

    to 3,500 hours

    25-30% saving in back-of-house areas.

    Without controlled lighting

    Using controls with these 20 1.5m twin T8 switch-

    start uorescent lights in this car park

    (g. 44), you could save 1,152 a year (calculated

    at 4,000 hours a year and 10p per electrical unit).

    In g. 45 to 49, you could expect to save energy

    by using daylight sensors (between 4,000 and

    8,760 hours a year).

    Fig. 44

    Fig. 45

    Fig. 46HELP

    29Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    29/35

    Menu

    g g

    These lights (g. 50) are illuminating windows. Its

    ineffective and wasteful. There would be energy

    savings with a minimum of 4,000 hours a year.

    These lights (g. 51) shine upwards and the light is

    then lost out of window. There would be energy

    savings with a minimum of 4,000 hours a year.

    A 24/7 operation (g. 52) with no effect. You could

    save 100% of the energy here (8,760 hours a year).Fig. 47

    Fig. 48

    Fig 49

    Figure 50

    Fig. 52

    Fig. 51 Fig. 53

    With controlled lighting

    Daylight and presence sensors switch off this

    lighting (g. 53) when there is enough daylight.

    At night, the lighting is switched on only whensomeone comes into the area.

    HELP

    30Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    30/35

    Menu

    Automatic daylight sensors control this high

    intensity discharge lighting (g. 54 and 55). Not

    only does it save energy, but lamps dont need to

    be replaced as often. Skylights need to be kept

    clean to maximise the natural light.

    Fig. 54

    Fig. 55HELP

    31Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    31/35

    Menu

    LeD GLS 4W 50,000-hor lif

    35W IRC R111 Tgsthalog 4,000-hor lif

    35W IRC MR16 low voltag 5,000-hor lif

    LeD 8W MR16 low voltag 50,000-hor lif

    50W mais voltag Gu10 50,000-hor lif

    Appendix 1 Types of lamp

    Tgst halogGLS 2,000-hor lif

    Compact orsct cadl 8,000-hor lif

    Compact orsct rctor 15,000-hor lif

    Compact orsct 8,000-hor lif

    Dimmabl compactorsct 10,000-hor lif

    LeD 3.6W low voltag 40,000-hor lif

    LeD 4W Gu10 50,000-hor lif

    HELP

    32Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    32/35

    Menu

    Appendix 2 Energy comparison chart

    Type Existing

    energy

    Proposed

    energy

    Energy

    saving

    Hours

    per year

    Unit

    cost

    Annual

    savings

    ()

    GLS to CFLi 40W 7W 33W 8,760 10p 28.90

    GLS to LeD 60W 4W 56W 8,760 10p 49.05

    Cadl to IRC cadl 40W 28W 12W 8,760 10p 10.51

    GLS to IRC 60W 42W 18W 8,760 10p 15.77MR16 to LeD 20W 3.6W 17.4W 8,760 10p 15.3

    MR16 to LeD 50W 5W 45W 8,760 10p 39.42

    MR16 to LeD 50W 8W 42W 8,760 10p 36.79

    GLS standard tungsten lamp; CFLi compact

    uorescent lamp with integral electronic gear;

    T8 26mm diameter uorescent tube;

    T12 38mm diameter uorescent tube;

    IRC infrared coated tungsten halogen lamps;

    LED lamps with light-emitting diode;

    MR16 dichroic spotlamp with low voltage (12v)

    GX5.3 or mains voltage GU10

    GU10

    GU10 mains voltage dichroic lamp

    LED Light-emitting diode

    (low voltage 12V retrot)

    HELP

    33Lighting

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    33/35

    Menu

    Savings checklist

    Done

    1 Are you using tungsten bulbs in any areas?

    Change to compact uorescent (CFLi), tungsten halogen or LED 75% to 90% energy saving.

    2 Are there areas where lighting is left on unnecessarily?

    Use daylight sensors or presence detectors to automatically switch lighting off and on as needed 30% to 60% energy saving.

    3 Are you using tungsten halogen low voltage (GX 5.3) or mains voltage (GU10) in any areas?

    Swap to infrared coated (IRC) tungsten halogen versions or appropriate LEDs to replace low voltage versions. Use LEDs (GU10)

    of CFLi (GU10) to replace mains voltage versions.

    4 Are you using T12 or T8 switch-start uorescent tubes?Replace with new T5 ttings or t a T5 electronic adaptor.

    HELP

    http://../J7502%20CT%20Energy%20Management%20Guide%20/NI%20Best%20Practice%20Energy%20Management%20Guide/StageAW/J7502_NI_BP_EnergyManagement_Guide_AW_Interactive.pdf
  • 8/11/2019 CTG029

    34/35

    Contents menu

    each dot hlps yo avigat

    to a diffrt chaptr of th

    pblicatio. If yo roll ovr a

    dot yo will gt a pop-p tab

    with th am of th chaptr.

    Clickig o a dot will tak yoto th start of that chaptr.

    How this

    PDF works

    This PDF has been designed

    with interactive elementsto help you navigate your

    way around and get as much

    from it as you can.

    To the right is an overview

    of how the buttons in the

    PDF work.

    If you would like to view thishelp screen again, press the ?

    button at any time.

    Page navigation

    Click to go to th xt pag.

    Click to go to th prvios pag.

    This PDF cotais liks which

    may tak yo to rlvat

    iformatio i diffrt chaptrs

    withi th docmt.

    Click this btto to go back

    to th pag whr yo startd.

    Miscellaneous

    Click to show this ovrviw.

    Rollovr/click to viw th glossary.

    Click to dowload a prit-fridly

    vrsio of this PDF.

    nxt pag

    Prvios pag

    Back

    Introduction

    Menu

    HELP

    CTG029The Carbon Trust is a not-for-prot company with the mission to accelerate the move to a low carbon economy.We provide specialist support to business and the public sector to help cut carbon emissions, save energy and

  • 8/11/2019 CTG029

    35/35

    The Carbon Trust receives funding from Government including the Department of Energy and Climate Change, the Department

    of Transport, the Scottish Government, the Welsh Assembly Government and Invest Northern Ireland. In Northern Ireland

    Carbon Trust activities are part nanced by the European Regional Development Fund under the European Sustainable

    Competitiveness Programme for Northern Ireland.

    Whilst reasonable steps have been taken to ensure that the information contained within this publication is correct , the

    authors, the Carbon Trust, its agents, contractors and sub-contractors give no warranty and make no representation as to itsaccuracy and accept no liability for any errors or omissions. Any trademarks, service marks or logos used in this publication,

    and copyright in it, are the p roperty of the Carbon Trust. Nothing in this publication shall be construed as granting any licence

    or right to use or reproduce any of the trademarks, service marks, logos, copyright or any proprietary information in any way

    without the Carbon Trusts prior written permission. The Carbon Trust enforces infringements of its intellectual property

    rights to the full extent permitted by law.

    The Carbon Trust is a company limited by guarantee and registered in England and Wales under Company

    number 4190230 with its Registered Ofce at: 6th Floor, 5 New Street Square, London EC4A 3BF.

    Published in the UK: March 2010.

    The Carbon Trust 2010. All rights reserved.

    We provide specialist support to business and the public sector to help cut carbon emissions, save energy and

    commercialise low carbon technologies. By stimulating low carbon action we contribute to key UK goals of lower

    carbon emissions, the development of low carbon businesses, increased energy security and associated jobs.

    W hlp to ct carbo missios ow by:

    providing specialist advice and nance to help organisations cut carbon

    setting standards for carbon reduction.

    W rdc pottial ftr carbo missios by:

    opening markets for low carbon technologies leading industry collaborations to commercialise technologies

    investing in early-stage low carbon companies.

    www.carbontrust.co.uk

    0800 085 2005

    http://www.carbontrust.co.uk/Pages/Default.aspxhttp://www.carbontrust.co.uk/Pages/Default.aspx