cryocooler analysis

Upload: rohit-pansara

Post on 14-Apr-2018

229 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/30/2019 Cryocooler Analysis

    1/36

    1

    DC FLOW ANALYSIS OF PULSE TUBE CRYOCOOLER

    Prepared by:

    ROHIT H. PANSARA

    (B.E. MECHANICAL)

  • 7/30/2019 Cryocooler Analysis

    2/36

    2

    INDEX

    SR NO. CONTENT PAGE NO.

    Chapter 1 Introduction of cryogenics 1-11

    1.1 Application of Cryogenic temperature 2

    1.2 Limitation of vapour compression

    Refrigeration system 2

    1.3 Classification of cryocooler 4

    1.3.1 Sterling cryocooler 5

    1.3.2 Gifford Mc-Mahon cryocooler 7

    1.3.3 pulse tube cryocooler 10

    Chapter 2 Pulse tube cryocooler 12-18

    2.1 Working mechanism of pulse tube

    cryocooler 12

    2.2 conditions of working 12

    2.3 principle of pulse tube cryocooler 12

    2.4 types of pulse tube cryocooler 14

    2.4.1 basic pulse tube cryocooler(BPTC) 14

    2.4.2 orifice pulse tube cryocooler(OPTC) 15

    2.4.3 double inlet pulse tube cryocooler

    (DIPTC) 17

    2.4.4 inertance type pulse type cryocooler

    (IPTC) 18

    Chapter 3 Various loose in pulse tube cryocooler 19-23

    3.1 Loss due to regenerative ineffectiveness 19

    3.2 Temperature swing loss 20

    3.3 Loss due to pressure drop in regenerator 21

    3.4 Conduction loss 21

  • 7/30/2019 Cryocooler Analysis

    3/36

    3

    3.5 Losses due to DC flow 22

    Chapter 4 Modeling of DC flow losses 24-28

    4.1 The assumption for developing model 25

    4.2 Governing equation for calculation 27

    SR NO. CONTENT PAGENO.

    Chapter 5 Result and Discussion 29-34

    5.1 Result for variation in pulse tube cold end Temperature 29

    5.2 Result for different average pressure 31

    5.3 Result for different frequency 32

  • 7/30/2019 Cryocooler Analysis

    4/36

    4

    CHAPTER 1

    INTRODUCTION OF CRYOGENICS

    In a Greek language Cryogenics means Creation or Production by means of

    cold.Cryogenics is a science dealing with low temperature. The low temperature is the

    governing parameter in any cryogenics application. The temperature range of cryogenic is 0K to

    123K. This range separates it from the temperature range generally used in refrigeration

    engineering.

    Cryogenics, the science of producing and maintaining low temperatures, had its beginning

    in the later half of last century. It is concerned with design and development of cryocoolers that

    are capable of producing and maintaining low temperature. It is a branch of low temperature

    physics concerned with the effects of very low temperature was first investigated by Michael

    Faraday who demonstrated that gases could be liquefied leading to the production of low-

    temperature around 173 K.

    The first cryogenic temperature system was primarily developed for the solidification of

    carbon dioxide (CO2) and the liquefaction of a subsequent fractional distillation of gases such asair, O2, N2, H2 and He.

    Oxygen (O2) was liquefied in 1877 by Coilletet and Pietet. H2 was liquefied in 1898 by

    Dewar using Joule Thomson expansion gases. The liquid Oxygen boils at 90.2K and liquid

    Hydrogen at 20.4K.The liquefaction of He (Helium) was accomplished in 1908 by

    H.Kamerlingh in the famous cryogenic lab of university of LAIDEN. Initially, by evaporation

    of liquid He (Helium) under high vacuum, the temperature as low as 1.1K was obtained. But by

    making improvements in apparatus, a temperature of 0.7K was reached by the year 1928.

    In term cryocooler is generally used for refrigerators of small size which are capable of

    reaching temperature below 123K (-150 C).

  • 7/30/2019 Cryocooler Analysis

    5/36

    5

    1.1. APPLICATIONS OF CRYOGENIC TEMPERATURE

    (1) Cooling infrared sensors used on satellites and in missile guidance, night vision and rescue,atmospheric studies involving ozone hole and green house effect, low noise amplifiers.

    (2) Commercial purpose such as cryopump for semiconductor fabrication, superconductor forcellular phone station, voltage standards, high-speed computer and process monitoring.

    (3) Medical purpose like cooling super conducting magnets for MRI (magnetic Resonance andprocess monitoring). System, SQUIDs (Superconducting Quantum Infrared Device)

    magnetometer for heart and brain studies, Croyogenic catheter and cryosurgery.

    (4) Cryogenics Temperature also wildly used in Expansion Fitting, Cryobiology,Semen Preservation, Cryosurgery, Space Research, Computer Engineering, Cryogenic for

    under Ground Power Lines, Miscellaneous Uses.

    1.2. LIMITATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM

    The solidification temperature of the refrigerants limits the use of VCR system for the

    production of low temperature inherently. The following Table 1.1 shows the freezing

    temperature of commonly used refrigerants in VCR.

    Table 1.1: Freezing Temperature of Refrigerants Used in VCR

    The refrigerants used must have a freezing temperature well below the required temperature

    to be obtained. Thus the refrigerants R-113, NH3, CO2 and SO2 cannot be used for low

    temperature refrigeration systems.

    Refrigerants R-11 R-12 R-21 R-22 R-30 R-40 R-113R-717

    (NH3)

    R-744

    (CO2)

    R-764

    (SO2)

    Freezing

    Temp (K) 162 215.5 138 113 176.4 175.5 238 195.2 216.3 197.4

  • 7/30/2019 Cryocooler Analysis

    6/36

    6

    (a)The pressure required to be maintained in the evaporator for the required temperature is farbelow atmospheric pressure and it is difficult to maintain such high vacuum in the evaporator.

    The pressure required to be maintained in the evaporator for maintaining 213K for different

    refrigerants is given below in Table 1.2

    REFRIGERANTSVACUUM PRESSURE

    mm of Hg Bar

    R-12 590 0.776

    R-22 480 0.631

    NH3 595 0.782

    Table 1.2: Evaporator Pressures of Different Refrigerants

    b) The specific volumes of the refrigerants at such a low temperature are extremely high and it isdifficult to operate the compressors efficiently under such low pressure when large volumes

    of the gases are to be pumped.

    c) With decrease in temperature, the compression ratio required may be as high as 200 and it stillincreases with decrease in evaporator temperature. The desired high compression ratio

    reduces the volumetric efficiency of the compressors and also results in high temperature of

    discharge gas leaving the compressor. The single stage reciprocating compressors are limited

    to compression ratio of 12. As the volume displacements of the reciprocating compressors are

    very low, they are not used at all for low temperature application.

    d) The Horse Power (HP) required per ton of refrigeration increase in evaporating temperature.The performance is very poor at low temperature refrigeration system when single stage

    compressor is used. The COP (Coefficient of Performance) of the VCR is very low for the

  • 7/30/2019 Cryocooler Analysis

    7/36

    7

    production of low temperature. Below 173 K the COP of a single stage VCR system is lower

    than cop of air refrigeration system in the same range of temperature.

    e) Multistage compressor system can be used to overcome few difficulties but the majordrawback of multistage system is that the oil may not return to high-pressure compressor. Oil

    may accumulate in one of the compressor, starving others. Suitable means as traps equalizing

    float controls are required to prevent this.

    1.3. CLASSIFICATION OF CRYOCOOLERS

    Device which is use to produce cryogenics low temperature is called as cryocoolers.The term

    cryocooler has generally been used for refrigerator of small and intermediate size, which is

    capable to obtain and maintain temperature below 123K.

    Crocoolers, invented in early 1960, are mainly classified in to two groups.

    a) Recuperativeb) Regenerative

    The Recuperative types utilize a continuous flow of the cryogen in the one direction, analogous

    to a DC electrical system. The recuperative coolers use only recuperative heat exchanger and

    operate with a steady flow of cryogen through the system the compressor operates with a fixed

    inlet and outlet pressure. If the compress is reciprocating type, it must have inlet and outlet

    valves to provide steady flow. The uses of valves in compressor needed for recuperative

    cryocoolers limits the efficiency of the compression process about 50% and significantly limit

    the overall efficiency of recuperative cryocooler.

    In theRegenerativecycles the cryogen undergoes an oscillating pressure analogous to an

    AC electrical system. The compressor or pressure oscillator for the regenerative cycles needs no

    inlet or outlet valve. However, an oscillating pressure can be generated from a valve compressor

    by using another set of valves to switch between the high and low pressure sides of the

    compressor, as is done in the Gifford-McMahon cryocooler. The regenerator has only one flow

  • 7/30/2019 Cryocooler Analysis

    8/36

    8

    channel and the heat is stored for a half-cycle in the regenerator matrix, which must have a high

    heat capacity (>98%).

    Expansion type cryocoolers are mainly of three types:

    1) Stirling Cryocooler2) Gifford-McMahon Cryocooler3) Pulse tube cryocooler1.3.1 Stirling Cryocooler

    The cycle consists of four stages as shown in Figure 1. The Figure 2 shows Pressure vs.

    Volume diagram and temperature profile respectively. The sequence of operations for the Stirling

    cryocooler is as follows:

    Phase 1:

    During this process the gas is compressed isothermally. During the compression pressure is

    increase and as the process is isothermal the volume is decreased. For making the process

    isothermal the heat generated, as the result of compression is removed by heat exchanger at

    ambient temperature.

  • 7/30/2019 Cryocooler Analysis

    9/36

    9

    Phase 2:

    During this process the volume of fluid is constant. As fluid passes through the regenerator it

    been cooled (because the effect of the cold fluid, when it is passed through regenerator during 4th

    process). Here also as the temperature decreases, by the constant volume, the pressure is also

    decreases.

    Phase 3:

  • 7/30/2019 Cryocooler Analysis

    10/36

    10

    During this process as the displacer is moving part it work freely and displace towards left and

    fluid get expand. As the fluid is expanded the pressure is decreasing slightly and the volume is

    increasing. Here we get expansion effects of fluid. As whatever the cooling effects produced is

    used for making the evaporator at the required temperature, the process is been isothermal

    expansion. At point D we get maximum cooling effect.

    Phase 4:

    During this process, the displacer forced the fluid towards right. The fluid gets hot as it passes

    through regenerator from left to right. As the volume is been constant the pressure is increasing.

    Thus, by repetition of these all four phases from 1 to 4 we get the useful and continuous cooling

    at point D.

    Stirling cycle cryocooler operate on a closed thermodynamic cycle with two external heat

    exchange processes and two internal constant volume regenerative processes.

    It is well known that an ideal Stirling cycle has the same efficiency as that of the Carnot cycle and

    thus the Stirling system is potentially very efficient. The actual refrigeration available to cool

    thermal load is that available in an ideal case less the thermal and pneumatic losses in the system.

    The practical realization of the Stirling cycle has only become possible with the development of

    efficient regenerator.

    1.3.2. Gifford-McMahon Cryocooler:

    Because of the pressure oscillates everywhere within the Stirling cryocooler, excess void

    volumes must be minimized to maintain a large pressure amplitude for a given swept volume of

    the piston. Thus oil removal equipment cannot be tolerated which means that the moving piston

    and displacer must be oil-free. But long lifetime then becomes difficult to achieve.

    In the mid of 1960s Gifford and McMahon showed that the pressure oscillation for

    cryocoolers could be generated by the use of a Distribution Valve that switches between high and

    low pressure sources.

  • 7/30/2019 Cryocooler Analysis

    11/36

    11

    The G-M cryocooler has the same low temperature parts as the Stirling cryocooler. The

    irreversible expansion through the valves significantly reduces the efficiency of the process, but

    the advantage of this approach is that it allows for an oil-lubricated compressor with oil-removal

    equipment on the high side to supply the high and low pressure sources. Oil-lubricated

    compressors were readily available at low cost from the air-conditioning industry by the mid

    1960s with continuous operation.

    To maintain a 1 to 3 years lifetime for the PTFE based seals on the displacer and the

    Distribution Valve, G-M used low speeds of 1 Hz to 2 Hz for those two components in the cold

    head. The cold head could be placed quite some distance from the compressor and connected by

    flexible lines for the high and low-pressure gas.

    The G-M cryocoolers are now manufactured at a rate of about 20,000 per year for use in

    cryo-pumps. Schematic of the Gifford-McMahon cryocooler is shown inFigure1.5

    This system consists of a compressor, a cylinder closed at both ends, a displacer within the

    cylinder and a regenerator. Here no work is transferred from the system during the expansion

    process. The displacer serves the purpose of moving the gas from one expansion space to another

  • 7/30/2019 Cryocooler Analysis

    12/36

    12

    and would do zero work in the ideal case of zero pressure drops in the regenerator. The

    temperature vs. entropy diagram for G-M cryocooler is shown inFigure 1.6.

    The sequence of operations for the Gifford-McMahon Cryocooler is as follows:

    Process 1-2:

    With the displacer at the bottom of the cylinder, the inlet valve is opened and the pressure within

    the upper expansion space is increased from lower pressure P1 to a higher pressure P2. The

    volume of the lower expansion space is practically zero during this process because the displacer

    is at its lowest position.

    Process 2-3:

    During this the inlet valve still open and the exhaust valve closed, the displacer is moved to the

    top of the cylinder. This action moves the gas that was originally in the upper expansion space

    down through the regenerator to the lower expansion space. Because the gas is cooled as it passes

    through the regenerator, it will decrease in volume so that gas will be drawn in through the inlet

    valve during this process to maintain a constant pressure within the system.

    Process 3-4:

  • 7/30/2019 Cryocooler Analysis

    13/36

    13

    With the displacer at the top of the cylinder, the inlet valve is closed and the exhaust valve is

    opened. Thus by redirecting the 3-way valves and allowing the gas within the lower expansion

    space for expand to the initial pressure P i. During this the gas passes through the evaporator and

    gives the cooling.

    Process 4-5:

    The low temperature gas is forced out of the lower expansion space by moving the displacer

    downward to the bottom of the cylinder. This cold gas flows through a heat exchanger in which

    heat is transferred to the gas from low temperature sources.

    Process 5-1:

    The gas flows from the heat exchanger through the regenerator, in which the gas is warmed back

    to near ambient temperature.Thus the cycle is repeated in this way and we get the cooling effect.

    1.3.3. Pulse tube cryocooler:

    In Stirling Cryocoolers, the pressure of moving part in the cold region gives rise to vibration,

    friction, wears and tears problems, which are its main drawbacks. A major advantage of the G-M

    system is the ease with which several units may be multistage to achieve temperature as low as 15

    K to 20 K. The Pulse tube cryocooler develops by Gifford and Longworth derives cooling from

    the compression and expansion of gas. As the Pulse Tube contains no moving parts in the cold

    region, it has greater reliability and lifetime than the former ones. The only obstacle to its wide

    applications is relatively low refrigeration performance as compared to other types. The minimum

    temperature attained by one stage was much higher than 79 K so 2 or 3 stages are necessary to

    reach very low temperature.

    Pulse tube refrigeration is based on the cyclic process such that a gas column with cold and

    warm end temperatures, Tcand Tw, respectively, is compressed, displaced towards the warm end,

    expanded, and re-displaced towards the cold end.

  • 7/30/2019 Cryocooler Analysis

    14/36

    14

    The process is realized by feeding adequate gas flows to both ends of the tube. Those flow

    rates must be different in size and in phases. The various types of pulse tube refrigerators differ

    mainly by the performance of the phase shifter which can by realized by use of passive or active

    elements. Using those flow rates as basic quantities, alternative types of operational diagrams for

    describing the differences and the common features of various types of pulse tube refrigerators,

    are derived. They provide simple means for the basic layout and for its optimization. Those

    results will be compared with more detailed numeric simulations and also with experiments from

    the literature. The single stage VCR system for the different refrigerants is limited to an

    evaporator temperature of 234 K.

  • 7/30/2019 Cryocooler Analysis

    15/36

    15

    CHAPTER 2

    PULSE TUBE CRYOCOOLER

    2.1 WORKING MECHANISM OF PULSE TUBE CRYOCOOLER

    Pulse Tube Cryocooler was built by Gifford and Longworth [1] in 1960s. It has no moving

    part in low temperature region and is inherently simple and reliable, with low vibration and long

    lifetime. Mikulin et al [2] invented Orifice Pulse Tube Cryocooler. He has reached 3.6K with 3-

    stage Orifice Pulse Tube Cryocooler. It uses modest pressure and pressure ratio. It has low

    refrigeration rate per unit mass flow. In 1989, Shaowei introduced the double inlet method. They

    obtained the lowest temperature of 132k using Double Pulse Tube Cryocooler while it was 175k

    obtained from Orifice Pulse Tube under the same operating conditions. S.Zhu built the latest

    development in the field of Pulse Tube Cryocooler. It has higher efficiency than the previous

    types.

    2.2 CONDITIONS FOR WORKING

    There are three conditions that are necessary for the Pulse Tube Cryocooler to work:

    1. The gas must reach the low temperature point without carrying a lot of heat (as measured bythe enthalpy flow in the regenerator).

    2. The amplitude of the gas flow and pressure oscillation in the Pulse Tube section must belarge enough to carry away (by enthalpy flow) the heat applied to the cold heat exchanger.

    3. The phase relationship between the pressure the gas flow in the Pulse Tube section must beappropriate to carry heat away from the cold point (by enthalpy flow from cold end to the hot

    end).

  • 7/30/2019 Cryocooler Analysis

    16/36

    16

    2.3 PRINCIPLE OF PULSE TUBE CRYOCOOLER

    When a gas at room temperature is admitted to one end of tube (shown in Figure 2.1),

    closed at far end, so that pressure in tube is raised, there will be a tendency for a temperature

    gradient to be established within part of the tube.

    F igure 2.1: Pr inciple of Pulse Tube Cryocooler

    This gradient will be most pronounced if the gas enters with plug flow, without turbulent

    mixing in tube and with minimal heat transfer to the wall. Then all gas initially within the tube

    will undergo isentropic compression and its temperature T can be given by relationship:

  • 7/30/2019 Cryocooler Analysis

    17/36

    17

    This gas is displaced towards the closed end of the tube. Between, gas at hot end regionthat is at higher temperature due to isentropic compression and the gas at the open end of the

    tube, which is still at T0, a temperature gradient will be established in the tube. If heat is rejected

    in the region of closed end (hot end) of the tube to restore the gas temperature to near To and the

    pressure suddenly released through the opened end of the tube, the gas will be expanded by a

    near isentropic process back to its original pressure and will reoccupy most of the tube. This gas

    will be at the temperature below T0, and there for will be capable of performing refrigeration.

    In the field of cryogenics Pulse Tube Cryocooler is attractive as a high reliability and low

    vibration cryocooler because there is no moving part at the cold section. Also due to improved

    thermodynamic efficiency the Pulse Tube Cryocoolers are now getting more importance.

    2.4 TYPES OF PULSE TUBE CRYOCOOLER

    2.4.1 Basic Pulse Tube Cryocooler (BPTC)

    The basics Pulse Tube Cryocooler was originally developed by Gifford and Longsworth

    [1]. It consists of compressor, flow reversing valve, regenerator and an open tube as shown in

    Figure 2.2. The flow-reversing valve is located after the compressor and controls the pressure in

    the Pulse Tube.

    Operation of the Pulse Tube Cryocooler begins by opening an inlet valve, which permits high-

    pressure gas to flow through the regenerator, where transferring energy to the regenerator cools

    it. The gas then enters open end of the Pulse Tube where the first heat exchanger is located. The

    heat exchanger raises the temperature of the gas at constant pressure. This partially heated gas

    behaves like a gas piston, adiabatically compressing the gas already in the tube. This

    compression results in a temperature rise of the gas inside the tube and forces the gas to the

    second heat exchanger.

  • 7/30/2019 Cryocooler Analysis

    18/36

    18

    In the second heat exchanger, to maintain a constant temperature the gas is cooled by exchanging

    heat with cooling water. Once the pressure in the reaches a specified level, the inlet valve closes

    and the exhaust valve opens, allowing expansion of the gas inside the tube accompanied by a

    cooling effect. The temperature of the gas leaving the Pulse Tube is lowers that the temperature

    at which it entered, creating the refrigeration effect. The expanding gas flows back through the

    exit valve.

    Once the original low-pressure level in the pulse tube is reached, the exit valve close, the gas is

    recompressed polytropically and the process begins again. The lower half offigure 2.1 depicts a

    temperature versus position graph for the entire refrigeration cycle. By cycling the gas back and

    forth many times per minute, large temperature gradient can be achieved and maintain.

    F igure2.2: Basic Pul se Tube Cryocooler (BPTC)

    2.4.2 Orifice Pulse Tube Cryocooler (OPTC)

  • 7/30/2019 Cryocooler Analysis

    19/36

    19

    The minimum temperature attained by BPTC was limited to 100K and to go below this

    temperature it requires multistage. This barrier has been overcome by the important

    breakthrough made during the last few years.

    In 1984, Mikulin et al [2] installed an orifice and gas reservoir at the top of the Pulse Tube to

    allow some gas to pass in to and out of large reservoir volume. This type of Cryocooler called an

    Orifice Pulse Tube Cryocooler (OPTC), as shown in figure 2.3. It is capable of reaching much

    lower temperature than the basic type. Mikulin et al [2] have attained low temperature of 79K.

    F igure 2.3:Ori f ice Pulse Tube Cryocooler (OPTC)

    Advantages of OPTC over BPTC are as follows:

    a) Only one moving part and that is also at room temperature It uses modest pressure andpressure ratios. It is possible to achieve works on ideal gas, which implies one fluid for all

    temperature.

  • 7/30/2019 Cryocooler Analysis

    20/36

    20

    b) Large orifice will not collect impurities at high temperature part of cycle.c) It has good intrinsic efficiency.d) It can be operate with several stages from the same pressure wave generator.

    In OPTC, the available phase angle of gas displacement at the hot end of Pulse Tube

    corresponding to piston motion is restricted between 00

    and 900. Thus OPTC cannot achieve

    optimum phase angle, which is between 900

    and 1800. The other disadvantage is the low

    refrigeration rate per unit mass flow, which means that the better regenerators are required.

    2.4.3 Double Inlet Pulse Tube Cryocooler (DIPTC)

    S. Zhu et al [3] introduced the double inlet method, which further improved the

    performance.

    It was found that due to another inlet at the hot end of the P.T., mass flow from cold end to hot

    end could be reduced. In other words, refrigeration power per unit mass flow rate through the

    regenerator will be increased. This type of Pulse Tube cryocooler as shown inFigure 2.4 can be

    called as DIPTC. The lowest temperature was 132K with DIPTC and 175K using OPTC under

    same operating conditions.

    The experiment also showed that the rate of temperature drop in DIPTC was greater than OPTC,

    which means increased gross refrigeration.

    The main contribution of double inlet Pulse Tube is to adjust the phase shift between the pressure

    wave and mass flow in the Pulse Tube and to increase their amplitude. It was found that the

    improvement achieved with DIPTC could be explained by their capability to reach phase angle

    beyond 900.

  • 7/30/2019 Cryocooler Analysis

    21/36

    21

    F igure 2.4: Double Inlet Pulse Tube Cryocooler (DI PTC)

    2.5.4. Inertance Type Pulse Tube Cryocooler (IPTC)

    The earliest use of an IPTR appears to be that reported by Kanao. They measured performance as

    a function of the diameter and length of the tube, as well as of frequency. They concluded that neither

    the single orifice nor the double inlet configuration provided better performance than the inertance

    configuration. The first detailed analysis of the IPTR was reported by Zhu et al [3]. They called the

    inertance tube the "long neck tube", and carried out computer calculations providing the performance as

    a function of the diameter and length of the tube. The calculations were verified by an experiment in

    which a long tube was connected directly between the reservoir and the compressor volume.

    The inertance tube is placed between the pulse tube proper and the reservoir. For proper values

    of its length and diameter, this arrangement conceivably results in improved performance, when

    compared with other arrangements. This is because the inertance tube offers a good deal of flexibility,

    potentially resulting in oscillating velocity and pressure with a phase relationship similar to that in

    Stirling refrigerator. Present work comprises of design, development and testing of the inertance type

    of pulse tube cryocooler.

  • 7/30/2019 Cryocooler Analysis

    22/36

    22

    Figure 2.5: I nertance Type Pulse Tube Cryocooler (IPTC)

    CHAPTER 3

    VARIOUS LOSSES IN PULSE TUBE CRYOCOOLER

    It can be revealed from the literature that the pulse tube cryocooler operates on a cycle

    similar to Stirling cycle. Refrigeration capacity of a cryocoolers decreases due to the losses like

    regenerator ineffectiveness, shuttle heat conduction, temperature swing, pumping action,

    instantaneous pressure drop, heat conduction through various solid parts etc. Dead volumes also

    give rise to losses and should be reduced to minimum. If the effects of all individual losses

    identified are combined, as they are in the real situation, then the net refrigerating power is

    substantially reduced from that pertaining to the ideal case. The loss analysis of a cryocooler is

    very important to estimate the efficiency and realistic performance.

    3.1 Loss Due to Regenerator Ineffectiveness:

    In pulse tube cryocooler the amount of gas that passes through the regenerator is quite

    large and consequently the load on regenerator is also large. Hence, the regenerator is a critical

    component that influences the performance of pulse tube cryocooler and the regenerator

  • 7/30/2019 Cryocooler Analysis

    23/36

    23

    efficiency is critical to the overall performance. The regenerator performance varies with

    different mesh structures used and also with properties of mesh matrix material.

    The incoming gas is cooled to a slightly higher temperature than to which it can, in the

    regenerator due to its ineffectiveness and thereby causing loss of refrigeration power. As

    suggested by Miyabe [6] this loss can be calculated as under:

    (13)

    The fractional time is the effective fraction of total cycle time during which the steady

    flow of gas enters into the pulse tube through regenerator. If the effect of pressure change duringthe gas flow through the regenerator is considered than the above equation can be rewritten as

    { } .(14)

    To calculate this loss on a cyclic basis, the effectiveness is to be calculated for each

    fractional time in the regenerator. The loss due to ineffectiveness of the regenerator for every

    interval is to be calculated and summed up to cumulative value of this loss.

    3.2 Temperature Swing Loss:Temperature swing loss accounts for the temperature changes in the matrix of the

    regenerator during the cycle. It is the heat taken up by the matrix due to its finite capacity. The

    drop in the temperature of regenerator matrix all along the length due to the single flow of the

    gas should be calculated as described by Martini [8].

    Temperature swing of the regenerator matrix material can be obtained as;

  • 7/30/2019 Cryocooler Analysis

    24/36

    24

    .(15)

    The temperature swing loss is calculated when the gas moves through the regenerator during

    pressurization process during the cycle and therefore, is equal to

    (16)

    3.3 Loss Due To Pressure Drop In The Regenerator:

    Due to pressure drop in the regenerator and other parts the actual pressure in the pulse

    tube will be lower than the supply pressure. During the expansion process the gas cant be

    expanded in the pulse tube to the lowest possible pressure due the same reason. This results in

    reduction of p-v area of gas III and hence reduction of the refrigeration power. It is dependent of

    flow acceleration and core friction. The flow acceleration term can be ignored for full cycle. To

    estimate this loss, first of all the pressure drop is to be estimated based on viscosity of gas,

    density of gas, mass velocity, Reynolds number and friction factor as under;

    .(17)

    To calculate this loss, the refrigerating effect with this pressure drop is to be subtracted fromthat obtained without considering pressure drop i.e. the gross refrigeration power.

    3.4 Conduction Losses:

  • 7/30/2019 Cryocooler Analysis

    25/36

    25

    This loss is basically due to heat conduction from high temperature region to low

    temperature region. It occurs through the pulse tube, regenerator tube liner and regenerator

    matrix. These losses also reduce the net refrigeration power and can be calculated from the basic

    heat transfer equations in the cyclic manner

    (i) Conduction through Pulse tube

    ..(18)

    (ii) Conduction through Regenerator Liner

    ..(19)

    (iii) Conduction through Matrix

    ..(20)

    The conductivity of matrix (kMatrix) can be obtained as;

    ..(21)

    The factorKX can be obtained as;

    ..(22)

    Net refrigeration power is calculated by subtracting all the losses from the gross

    refrigeration power.

    3.5 Losses due to dc flow

  • 7/30/2019 Cryocooler Analysis

    26/36

    26

    Adding second orifice valve between the hot end of pulse tube and the compressor, according

    to the opening of the orifice valve dc flow is established in the pulse tube. When the mass flow is

    counter clockwise from cold end of regenerator to the cold end heat exchanger is called

    positive dc flow and mass flow is in the clockwise cold end heat exchanger to the regenerator

    cold end is called negative dc. Complete explanation of the DC flow is in the chapter 4.

    CHAPTER-4

    MODELLING OF DC FLOW LOSSES

    Adding a second orifice valve between the hot end of the pulse tube and the compressor

    significantly improves the performance by decreasing the mass flow rate through the regenerator

    that does not contribute to the actual cooling power generation. However, this new configuration

    also introduces a possibility for unbalanced, unidirectional flow, analogous to direct current in an

    electrical circuit. Figure 4.1 shows a schematic diagram of a G-M type double-inlet pulse tube

    refrigerator. During the compression process, high pressure gas flows out of the compressor and

    is divided into two flow streams one to the hot end of the regenerator, and the other to the hot

    heat exchanger through the orifice valve. Flow resistances of the regenerator and the double-inlet

    orifice valve determine the ratio of the mass flow rates into the system. During the expansion

    process, mass flows from the regenerator and the hot heat exchanger back to the compressor.

    However, the flow resistance for gas that returns to the compressor can be different from that for

    the gas coming out of the compressor. Typically orifice valves have directional characteristics,

    i.e. the mass flow rate at the same pressure ratio may be different when the orifice valve is

    installed in the reverse direction. Also, in the regenerator, the pressure drop that is represented as

  • 7/30/2019 Cryocooler Analysis

    27/36

    27

    flow resistance is a function of the pressure difference between the regenerator ends, as well as

    the temperature, density and other fluid dynamic values such as velocity. The pressure drop can

    be different for the compression and expansion process. This potential imbalance in flow

    resistance can generate a unidirectional net mass flow rate in a pulse tube system. The net mass

    flow is zero for an ideal balance of flow resistances. However, in actual conditions, the net mass

    flow can be counterclockwise (i.e., a positive DC flow through the cold heat exchanger) or

    clockwise (i.e., a negative DC flow through the cold heat exchanger) in figure 4.1 If the system

    has a positive DC flow, more cold gas flows from the cold end of the regenerator to the cold end

    of the pulse tube with the result that the gas temperature can be lower during the expansion

    process. In other words, the system ideally produces more cooling power. However, a positive

    DC flow also increases the mass flow rate through the regenerator and the pressure drop in the

    regenerator. The mass flow rate in the regenerator is also unbalanced. On the other hand, a

    negative DC flow increases the heat load to the cold end of the pulse tube. As the mass flow

    from the hot end to the cold end of the pulse tube is increased, higher temperature gas may reach

    the cold end of the pulse tube and this additional mass flow decreases the cooling power of the

    system. As mentioned above, DC flow causes several different effects and its impact on the

    system performance is not obvious. In the G-M type pulse tube refrigerator, valves (V1~V

    4)

    perform the function of the double-inlet orifice valve. Therefore the system has the possibility

    for DC flow. The numerical cycle simulation described above can evaluate the direction andamount of DC flow.

    In present work DC flow in Pulse tube cryocoolers is modeled using MATLAB software.

    Effect of frequency, cold end temperature, orifice and double inlet opening on DC flow and

    hence on performance of the system can be studied using the present model.

    The model is explained in following section. The assumption made to develop the model

    is listed below.

    4.1 The assumption for developing model:

    1. Helium, the working gas, behaves as a perfect gas (an ideal gas with constant specificheat).

  • 7/30/2019 Cryocooler Analysis

    28/36

    28

    2. Flow in the system is one dimensional, so that there is no velocity component normalto the walls in each component.

    3. The effectiveness of the regenerator is unity and the regenerator wall temperaturedistribution is constant.

    4. The pressure drops in the regenerator and connection tubings are neglected. Thepressure in the regenerator, pulse tube and heat exchangers are the same at any time.

    5. In the cold and hot heat exchangers, the gas temperature is the same as that of thewall temperature of the heat exchanger, which is constant, i.e., heat transfer is perfect

    in the heat exchanger.

    6. In the pulse tube, the flow is adiabatic

    7. Flow through the orifice valves is adiabatic.

    8. The temperature of the reservoir is isothermal.

  • 7/30/2019 Cryocooler Analysis

    29/36

    29

    Figure 4.1 G-M type pulse tube cryocooler

    4.2 Governing equation use for calculation.

    For calculation of mass flow through orifice 3, 4 and 5 we are using nozzle

    equation because there is needle valve which outlet area is not equal inlet area but it is variable.

  • 7/30/2019 Cryocooler Analysis

    30/36

    30

    [

    (

    )

    ]

    .. (4.1)

    The value of, and are calculated using above equation of the orifice valve.Now these values of the mass flow are put in the equation of change in pressure with respect totime dP/dt as below.

    .. (4.2)

    In above equation and are primary flow and it is negligible for calculation ofDC losses so it not use in calculation purpose. Now calculating the mass flow in the regenerator

    respective equation for mass conservation in regenerator, For mass conservation we are dividing

    regenerator in to the 5 discrete part because for different part there is different temperature of the

    part as shown in the figure 4.1.

    .. (4.3)

  • 7/30/2019 Cryocooler Analysis

    31/36

    31

    ...... (4.4)

    ...... (4.5)

    .... (4.6)

    .... (4.7)

    And finally we are putting the value of the mr5 in given below equation and we get the

    value of losses due to DC flow.

    *h .... (4.8)Where h=Enthalpy of helium at that temperature

    ...... (4.9)

    CHAPTER-5

    RESULT AND DISCCUSION

  • 7/30/2019 Cryocooler Analysis

    32/36

    32

    5.1 Results for variation in pulse tube cold end temperature

    The present model is used to understand the DC flow losses at various operating

    parameters. As discussed in earlier section DC flow is harmful but inevitable in pulse tube

    crycoolers. DC flow is affecting the overall performance of the G-M type pulse tube cryocoolers.

    Temperature 40 0.9017 7.2278 7.4276 4.0111

    50 1.3235 7.6496 7.0058 4.7101

    60 1.8076 8.1338 6.5216 5.3609

    70 2.3497 8.6759 5.9795 5.9730

    80 2.9464 9.2725 5.3829 6.5534

    Table 5.1 Effect of cold end temperature on cooling power

    Graph 5.1

  • 7/30/2019 Cryocooler Analysis

    33/36

    33

    Graph 5.2

    Effect of DC flow loss & other losses at different temperature are predicted from model. The

    result of DC flow loss at cold end temperature is shown in graph 5.1 & net refrigeration power at

    cold end temperature is shown in graph 5.2.As shown in graph 5.1 cold end temperature increase

    heat loss due to the DC flow is increase & according to the graph 5.2 as cold end temperature

    increase net refrigeration power is decrease.

    Graph 5.3

  • 7/30/2019 Cryocooler Analysis

    34/36

    34

    Graph 5.4

    The results are tabulated in table 5.1 regenrator mass flow at various temperature are

    calculated and shown in graph 5.3 & effect of regenrator mass flow rate on DC flow losses is

    shown in graph 5.4.In graph 5.3 shows that as cold end temperature increases mass flow through

    the regenrator increases, and graph 5.4 shows that as mass flow increases DC flow heat loss also

    increase.

    5.2 Results for different average pressure

    Effect of avarage pressure is studied and results are shown in graph 5.5 & 5.6 for DC loss

    and refrigeration power respectivly model predicts that lower avarage pressure results in lower

    losses and higher refrigeration power. The results are tabulated in table 5.2.

    Pressure 13 2.8008 9.1269 5.5285 6.2295

    14 2.9464 9.2725 5.3829 6.5534

    15 3.0858 9.4119 5.2435 6.8634

    16 3.2204 9.5465 5.1089 7.1628

    17 3.3510 9.6772 4.9783 7.4534

    Table 5.2 Effect of average pressure on cooling power

  • 7/30/2019 Cryocooler Analysis

    35/36

    35

    Graph 5.5

    Graph 5.6

    As shown in graph 5.5 which is Vs average pressure which is indicated that as averagepressure is increase DC flow loss is also increse, and in graph 5.6 indicate that as average

    pressure increase net refrigeration power is decreases.

    5.3 Resuls for different frequances

    Effect on DC flow losses and net refrigeration power at different frequency are

    predicated from the model. The results are tabulated in table 5.3.The resuls of DC losses at

    different frequency shown in graph 5.7 and net refrigeration power at different frequency as

    shown in graph 5.8.

    Frequency 1 4.8562 11.1823 3.4731 10.8012

  • 7/30/2019 Cryocooler Analysis

    36/36

    2 4.7176 11.0437 3.6117 10.4928

    3 4.6900 11.0161 3.6393 10.4315

    4 4.6802 11.0063 3.6491 10.4097

    5 4.6756 11.0017 3.6537 10.3995

    Table 5.3 Effect of frequancy on cooling power

    Graph 5.7

    Graph 5.8

    In graph 5.7 shows frequency Vs DC loss graph as frequency increases DC losses aredecreases and as shown in graph 5.8 shows graph of frequency Vs Qnet as frequency increases

    net refrigeration power also increases.