SINGAPORE STANDARD CP 10 : 2005 (Ies 13.220.20; 13.320) \ . ",1. CODE OF PRACTICE FOR Installation and servicing of electrical fire alarm systems / , , Published by SPRING Singapore 2 Bukit Merah Central Singapore 159835 SPRING Singapore Website: www.spring.gov.sg Standards Websile: www.slandards.org.sg SPRING smgapore

Upload: smoki

Post on 02-Apr-2015

3.224 views

Category:

Documents


163 download

TRANSCRIPT

Page 1: CP 10 2005

SINGAPORE STANDARD

CP 10 : 2005(Ies 13.220.20; 13.320)

\ .",1.

CODE OF PRACTICE FOR

Installation and servicing ofelectrical fire alarm systems

/

,,

Published bySPRING Singapore2 Bukit Merah CentralSingapore 159835SPRING Singapore Website: www.spring.gov.sgStandards Websile: www.slandards.org.sg

~SPRING

smgapore

Page 2: CP 10 2005

SINGAPORE STANDARD

CP 10 : 2005(ICS 13.220.20; 13.320)

CODE OF PRACTICE FOR

Installation and servicing ofelectrical fire alarm systems

All rights reserved. Unless otherwise specified, no part of this SingaporeStandard may be reproduced or utilised in any form or by any means,electronic or mechanical, including photocopying and microfilming, withoutpermission in writing from the SPRING Singapore at the address below:

HeadStandardisation DepartmentSPRING Singapore2 Bukit Merah CentralSingapore 159835Telephone: 62786666 Telefax: 62786667Email: [email protected]

ISBN 981-4154-01-6

Page 3: CP 10 2005

CP 10: 2005CP 10 : 2005

This Singapore Standard was approved by the Electrical and Electronic Standards Committee onbehalf of the Standards Council of Singapore on 22 March 2005.

The Technical Committee on Emergency Alarm and Communication Systems appointed by theElectrical and Electronic Standards Committee and responsible for the preparation of this standardconsists of representatives from the following organisations:

The Electrical and Electronic Standards Committee appointed by the Standards Council consists ofthe following members:

First published, 1980First revision, 1993Second revision, 2005

The experts of the Working Group are nominatedlrecommended by the following organisations:

The Working Group appointed by the Technical Committee to assist in the preparation of this standardcomprises the following experts who contribute in their individual capacity:

Singapore Manufacturers' Federation

SPRING Singapore

Housing & Development Board

Infocomm Development Authority of Singapore

Institution of Engineers Singapore

Singapore Electrical Trades Association

Singapore Civil Defence Force

Land Transport Authority

PSB Corporation Pte Lld

Fire Safety Managers' Association (Singapore)

PSB Corporation Pte Lld

Member, Electrical and Electronic StandardsCommittee

Capacity

Mr David Goh King Siang

Mr Benjamin Gan

Mr Eddie Lai

Mr Kenneth Liu

Mr Loke Yee Weng

Cpt Md Nizam Agil

Mr Ong Chew Seng

Mr George Tan Hai Ping

Name

Mr David Goh King Siang

Mr Ong Chih Hsing

Mr Chan Gabin

Mr Foo Chee Yan

Mr Loke Yee Weng

Mr Low Kim Seong

Cpt Md Nizam Agil

Mr Sng Chun Hui

Mr George Tan Hai Ping

MrJohn Wu

Mr Yee Cheong In

Mr Kenneth Liu

Convenor

Members

Chairman

DeputyChairman

Secretary

MembersMember, Standards Council

Member, Standards Council

SPRING Singapore

Nanyang Technological University

PSB Corporation pte Lld

SP PowerGrid Lld

Housing & Development Board

Association of ConSUlting Engineers Singapore

Nanyang Technological University

Singapore International Chamber of Commerce

National University of Singapore

Association of ConSUlting Engineers Singapor~

Institution of Engineers Singapore

Singapore Electrical Contractors and LicensedElectrical Workers Association

SPRING Singapore

Institution ofEngineers Singapore

Singapore Manufacturers' Federation

Land Transport Authority

Singapore Manufacturers' Federation

Energy Market Authority

Singapore Electrical Trades Association

National University of Singapore

Capacity

Mr Renny Yea Ah Kiang

Mr Michael Ong

Er. Ong Ser Huan

Mr K Seshadri

Mr Sim Wee Meng

Mr Tan Boon Chong

Mr Tan Hak Khoon

Mr Jimi Wong Yick Chee

Prof Yeo Tat Soon

Name

Mr Lim Say Leong

Mr Ong Chih Hsing

Assoc Prof Chan Tat Wai

Mr Chong Weng Hoe

Mr Chua Kok Yong

Mr Ho Fui Chan

Er. Adeline Koh

Assoc Prof Koh Liang Mong

Mr Peter Leong

Prof Liew Ah Choy

Mr Kenneth Liu

Mr Ng Kim Leong

Mr Ng Kin Ming

Chairman

DeputyChairman

Secretary

Members

Co-optedMember Er. Ng Eng Kiong Individual Capacity Celtec Systems pte Lld

Donnelley Simpson G.leary & Oehlers

GIB Automation Pte Lld

Loke & AssociatesPatent Engineering Co Pte Lld

PSB Corporation Pte LldSingapore Civil Defence ForceVision Fire and Security

2 3

Page 4: CP 10 2005

GP 10 : 2005 GP 10: 2005

Contents

Page

Foreword _

CLAUSES

Section One - Scope and general requirements

8

1.11.21.31.41.4.11.4.21.4.31.4.4

Scope _

Application _Definitions _

General requirements _Areas to be protected _

Locations where protection is not required ~ _Alarm zone limitation _

Connection to alarm monitoring station _

1010101212141516

Section Two - Design considerations

(blank page)

4

2.12.1.12.1.22.1.32.1.42.1.52.22.2.12.2.22.2.32.2.42.2.52.2.62.2.72.2.82.2.92.2.102.2.112.2.122.32.3.12.3.22.3.32.3.42.3.52.42.4.12.4.2

System components and equipment _General _Compatibility _

Special environment _BUilding management system _

Design process for limitation of false alarms _Alarm panel --,- _

Main/sub alarm panel _Zone chart/mimic panel _Location ~ _

Alarm zone facilities _Precaution against failure _

Visible indication for alarm panels _

Other indications during the fire alarm condition ~-

Identification and marking of indicators _Signals to fire service signalling transmitter _Fire alarm panel cabinet _Records _

Program controlled fire alarm system _Power supply _Operating voltage _Form of supply _Batterycharger _Battery capacity _Battery location _

Connection of additional equipment _When permitted _Connection requirements _

5

1717

.1717171818181919192020212122222222232323232323242424

Page 5: CP 10 2005

CP 10: 2005

Page

CP 10 : 2005

Page

2.52.5.12.5.22.5.32.5.42.5.52.5.62.5.72.5.82.5.92.5.102.5.112.62.6.12.6.22.6.32.6.42.6.52.6.62.6.72.72.7.12.7.22.7.32.82.8.12.8.22.8.32.92.9.12.9.22.9.32.9.42.9.52.9.6

Audible and visual alarms _General _

Audible alarm sounders _Audibility of general alarms _Code signalling ~ _Restricted alarms _Multi-stage alarm _

Visual alarm signal -::- _Fire alarm sounder silencing _Fire alarm buzzer silencing _

Fault buzzer silencing _-:-:-:-:=:- _Alarm verification feature (AVF) _Manual call points _

General --::-~:-------------------------Manual call point _Special environment _Operation _Supervision _Location _Alarm zone _

Heat detection systems _General _

Detectors --:-:_--::-_~:----------------------Spacing and location of detectors _Smoke detection systems _General _

Detectors ---:-:---::-_-:- _Spacing and location of detectors _Flame detection systems _General _:-_-::-:-::- _Stability and sensitivity _Spacing and location of detectors _Fixing of detectors _Detector lenses . _Outdoor applications _

24242424252525262626272728282828282828282828'29293535353544444444444444

3.4 Maintenance -----------------------3.4.1 General _3.4.2 False alarm _

3.4.3 Regular testing and inspection _3.5 Operations _

ANNEXES

A Guidance for the selection of detectors (Informative) _B Fire alarm symbols _

C Daily log - Records for automatic fire alarm installations _D Components of a fire alarm system _

FIGURES

1 Typical heat detector spacing - Flat ceilings _

2 Heat detector locations for concealed spaces with apex and sloping roof -----3 Design criteria for point-type heat detectors _4 Typical smoke detector spacing - Flat ceilings _

5 Point-type smoke detector locations for concealed spaces with apex andsloping roof _

6 Typical beam-type smoke detector iocations for sloping surfaces _7 Design criteria for point-type and beam-type smoke detectors located at apex of

ceiling or roof _

8 Smoke detector locations _

9 Design criteria for pOint-type smoke de\.ectors in structures with deep beams _A1 Typical field of view of flame detector _A2 Typical floor area protected by 9ne flame detector _A3 MUltiple coverage provided by four flame detectors _D1 The components of a typical fire alarm system _

4646474749

50596062

31323338

3940

414343.58585862

Section Three - Installation and maintenance

3.13.1.13.1.23.1.33.1.43.1.53.1.63.1.73.23.3

Installation _General --:--:--:- _Cables and wiring _

Conductor sizing --:- :- _Protection against electromagnetic interference _Joints and terminations _Mounting of detectors _-:- _Separation from other systems _

Operation and maintenance manuals and "as installed" drawings _Symbols _

6

45454545464646464646

7

Page 6: CP 10 2005

CP 10: 2005

Foreword

This Singapore Standard is a revision of CP 10 : 1993 and was prepared by the Technical Committeeon Emergency Alarm and Communication Systems under the purview of the Electrical and ElectronicStandards Committee. The Code provides recommendations for the installation and servicing of firealarm systems in buildings.

In this revision, eXisting requirements were reviewed and revised to bring the Code in line with thelatest fire alarm concept and technology. The principal changes made in this revision are as follows:

a) The requirements for locations where fire protection is not required have been updated (1.4.2);

b) A new requirement for permitted extension of zones extending beyond a single fire compartmenthas been added (1.4.3.2);

c) New features and requirements for main/sub alarm panels and repeater panel have beenincluded, in line with new technology (1.3.18, 2.2.1,2.2.5,2.2.6,2.2.7,2.5.8 and 3.1.2);

d) The requirements for zone chart/mimic panei have been included, as advised by the regulatoryauthority (2.2.2);

e) New requirements for the aiarm verification feature (AVF) have been added (2.5.11);

f) The requirements for spacing between detectors have been updated to be in line with AS 1670.1: 1995. The previous edition of CP 10 was based on AS 1670: 1986 (2.7 and 2.8);

g) Guidelines on the design process and maintenance of the fire alarm system and the selection ofdetectors to limit false alarms are provided (2.1.5, 3.4.2 and A.2.2);

h) The design requirement for beam-type smoke detectors is provided (2.8.3.2.2 and 2.8.3.8).

In the preparation of the standard, reference was made to the following standards:

CP 10 : 2005

i',,1,

Acknowledgement is made to Standards Australia and British Standards Institute for the use of theinformation in the above standards.

Attention is drawn to the possibility that some of the elements of this Singapore Standard may be theSUbject of patent rights. SPRING Singapore shall not be held responsible for identifying any or all ofsuch patent rights.

AS 1670.1 : 1995

BS 5839-1 : 2002

BS EN 54-2 : 1998

Automatic fire detection and alarm systems - System design,installation, and commissioning

Fire detection and fire alarm systems for buildings - Part 1 : Codeof practice for system design, installation, commissioning andmaintenance

Fire detection and fire alarm systems - Part 2 Control andindicating equipment

In particular, the follOWing requirements have been based on the AS 1670.1 : 1995:

a) The spacing, location and mounting of heat, smoke and flame detectors;

b) Optical beam line-type smoke detector and aspirating smoke detection systems.

8

NOTE

1.

2.

Singapore Standards are subject to periodic review to keep abreast of technological changes and newtechnical developments. The revisions of Singapore Standards are announced through the issue ofeither amendment slips or revised editions.

Compliance with a Singapore Standard does not exempt users from legal obligations.

9

Page 7: CP 10 2005

CP 10: 2005

Code of practice for installation and servicing of electrical firealarm systems

Section One - Scope and general requirements

CP 10: 2005

1.3.6 Corridor

A narrow enclosed thoroughfare (other than a lift lobby, smoke stop lobby and fire fighting lobby) withina building not more than 3.6 m wide and not used for trade or storage purposes.

1.3.7 Extra low voltage

Normally not exceeding 50 V a.c. or 120 V d.c., whether between conductors or to Earth.

1.1 Scope 1.3.8 Fire alarm device

This Code of Practice applies to the installation and servicing of electrical fire alarm system inbuildings. It covers alarm systems using manual call points, heat detectors, smoke detectors andflame detectors.

Component of a fire alarm system, not incorporated in the control and indicating equipment, which isused to give a warning of fire.

1.3.9 Fire alarm monitoring station

1.2 Application

All installations of automatic fire detection and alarm systems shall comply with the generalrequirements of Clause 1.4, with the additional requirements of Section 2 according to the detectortype, and with th.e installation a.nd maintenance requirements of Section 3. Manual call points installedIn conjunction with an automatic fire detection and alarm system or as a separate system shall complywith the general installation requirements of Section 2 with the additional requirements of Clause 2.6.

Where an automatic fire detection and alarm system is ancillary to an automatic fire-extinguishingsystem and/or an engineered smoke control system, the detection system shall comply with theappropriate requirements of this Code.

1.3 Definitions

A centre that monitors the fire detection and transmits the signals to the fire fighting authority foractivation of the fire fighting measures.

1.3.10 Fire compartment

Parts of building separated by walls, floors and ceilings, having an approved fire-resistance rating, withopenings protected by approved devices.

1.3.11 Fire detector

A component of a fire detection system which contains at least one sensor which constantly monitorsat least one suitable physical and/or chemical phenomenon associated with fire, and that provides atleast one corresponding signal to the control and indicating equipment.

For the purpose of this Code the following definitions shall apply:

1.3.1 Addressable system

A system in which signals from each detector, call point and/or activating device are individuallyidentified at the control panel.

1.3.2 Alarm indicator

A device which by visual means indicates the zone and/or compartment from which an alarm hasoriginated.

1.3.3 Alarm zone

A subdivision of the protected premises such that the detection of a fire within it will be indicatedseparately and independently from an indication of fire in any other subdivision.

1.3.4 Alarm zone facility

Part of the control and indicating equipment which registers and indicates signals (alarm and fault)received from its alarm zone circuit.

1.3.5 Control and indicating equipment (CIE)

A. compo~ent of a fire detection and fire alarm system which controls the receipt and transmission ofSignals "':Ithln .the fire detection and alarm system or initiates other action, and provides indication ofany warning Signals (alarm and fault) received.

10

1.3.12 Fire service signalling transmitter/

A device to transmit signals to an approved monitoring station.

1.3.13 Flat ceiling

A ceiling having a slope not exceeding 1 in 20.

1.3.14 Main alarm panel (MAP)

A control and indicating equipment that controls the receipt and transmission of signals from the subalarm panel (SAP) and all other alarm signals within the fire alarm system or initiates other actions andtransmits such signals to the alarm monitoring station if required.

1.3.15 Manual call point

Component of a fire detection and alarm system which is used for the manual initiation of an alarm.

1.3.16 Mimic panel

A panel which repeats the alarm zone indication in a diagrammatic form.

1.3.17 Protected area

An area of a building eqUipped with an automatic fire detection and alarm system installed inaccordance with this Code or an approved automatic fire suppression system.

11

Page 8: CP 10 2005

CP 10 : 2005

1.3.18 Repeater panel

A duplicate alarm panel for indication only.

CP 10 : 2005

1.4.1.3 Specific locations

1.4.1.3.1 Concealed spaces

Protection and adequate access for maintenance requirements shall be provided in all concealedspaces, except the following:

1.3.19 Shall

Indicates a mandatory requirement.

1.3.20 Should

Indicates a recommendation.

1.3.21 Sounders

An audible fire alarm device which is used to give a warning of fire.

(a)

(b)

(c)

(d)

Concealed spaces to which there is no access and which do not contain electrical servicesand combustible materials;

Concealed spaces below raised floor not more than 150 mm;

Concealed spaces not more than 800 mm deep in roofs;

Concealed ceiling spaces not more than 800 mm deep.

1.3.22 Sub alarm panel (SAP)

A control and indicating equipment that is located remotely from the main alarm panel and havingeither alarm zone facilities or indicators to show the location of the alarm and transmits such alarmsignal to the main alarm panel.

1.4 General requirements

The colour of all fire panels and bells shall be red. Other colours may be used subject to the approvalof the relevant authority. However, the colour of the manual call point must be red.

1.4.1 Areas to be protected

1.4.1.1 General

The following general consideration shall apply in determining the areas to be protecled:

(a) Detectors and manual call points shall be installed throughout all parts of the building asrequired by the relevant authority and under Sections 1, 2 and 3.

NOTE - Areas specified in 1.4.2 are exempted from this requirement.

(b) Each room shall be separately protected. Where a room is divided into sections by walls,partitions or storage racks reaching within 300 mm of the ceiling (or of the soffits of the beamswhere there is no false ceiling), each section shall be separately protected. Goods ormaterials shall not be piled so as to divide rooms into sections unless separate protection isprovided for each such section.

Where personnel entry to the concealed space is reqUired, the access dimensions shall be not lessthan 450 mm x 350 mm.

Where a concealed space less than 800 mm deep in roof or ceiling contains electrical equipmentconnected to the electricity supply mains and such equipment is not enclosed in a non-combustiblecontainer, the equipment shall have a detector mounted in the concealed space not more than 1.5.mof the equipment location. Electrical wiring approved by the relevant authority does not requireprotection.

Detectors installed in concealed spaces shall be provided with remote alarm indicators located in aposition clearly visible from the occupied area. If necessary, a label or zone chart should be providedto show the location of the detector(s).

1.4.1.3.2 Vertical shafts and openings

Hoists, lift hoistways, vertical risers and other such openings exceeding 0.1 m2 in area betweenstoreys shall be protected within the riser at tl)e top. Where such openings are not fire-isolated,detectors shall be placed on the ceiling at each fioor level, not more than 1.5 m horizontally distantfrom such openings.

Any area Which contains a non-fire-isolated opening exceeding 9 m2 between storeys shall have onedetector located on the ceiling within 1.5 m of each side of the opening and spaced not more than 7.2m apart around the perimeter of the opening. Such detectors may be regarded as part of the generalprotection of the area. If the opening is less than 0.5 m from a wall, detectors are not reqUired betweenthe wall and the opening. ~

A fire-isolated lift hoistway with approved automatic self-closing fire-rated doors does not require adetector within 1.5 m of the lift door. Normal spacing of the detectors shall, therefore, apply in the liftlobby.

1.4.1.2 Clearances

(c) The area covered by detectors that may be rendered out of operation due to any electricalwiring fault shall not be more than 2000 m2

• Such fault(s) shall not affect detectors of otherareas.

1.4.1.3.3 Staircases

Approved fire-isolated staircases should not require protection. All other staircases shall be protectedat each main floor level.

All alarm panels shall be located and mounted such that the indicators and controls are clearly visibleand readily accessible for operation and maintenance purposes.

Except in shop windows, a clear space of at least 300 mm radius, to a depth of 600 mm, measuredfrom the detector shall be maintained. No goods or materials shall be placed within the area.

12

NOTE - As a form of good practice, it is advisable that all staircases should be protected at each main floor levei.

1.4.1.3.4 Near fire doors

A detector shall be placed inside the protected area not more than 1.5 m from any fire door, where thedoor separates the protected area from an unprotected area (see also 1.4.1.3.2). Where a fire doorseparates two protected areas, a detector is not necessary within 1.5 m of the fire door.

13

Page 9: CP 10 2005

-I ,--

CP 10: 2005. ,.'

CP 10: 2005

1.4.1.3.5 Return air ducts (e) Skylights, as follows:

(g) Concealed spaces as follows (see 1.4.1,3.1):

(i) Concealed spaces to which there is no access and which do not contain electricalservices and combustible materials;

(iii) That have less than 4.0 m2 area, a recess height of not more than 800 mm and arenot used for ventilation;

(iv) With an opening on the ceiling of less than 0.15 m2

,

Air locks, not used as a washroom, with opening on both sides into protected areas, providedthat air locks do not contain electrical equipment or are not used for the storage of goods orfor access to cupboards,

(iI) Concealed spaces below raised floor not more than 150 mm;

(iii) Concealed spaces not more than 800 mm deep in roofs;

(iv) Concealed ceiling spaces not more than 800 mm deep.

Any walk-in type enclosure which is less than 2 m high or having side extending to the ceilingand has:

Installed in areas not requiring detection (such as sanitary spaces);

With an opening on the ceiling of less than 0.5 m2 and not used for ventilation;(i)

(iI)

(h)

(f)

Detectors may be omitted from under open grid portions of the ceiling which have not less than two­third of the ceiling area open to the free flow of air and have detectors installed on the ceiling abovethe open grid. Where any solid portion of the ceiling has a dimension in excess of 2 m and has anarea in excess of 5 m2

, normal protection shall be supplied to the solid portion of the open grid ceiling.

Where flame detectors are used they shall be installed both above and below the open grid ceiling.

Where smoke detection is required in the return air duct under SS CP 13, such detection should bedone via an air sampling device,

Where a structure has a monitor, sawtooth or gable ceiling or roof, a row of detectors shall be installedbetween 0.5 m and 1.5 m from the apex measured horizontally (see Figures 3b and 7b).

The rest of the ceiling or roof shall be protected in accordance with the general requirements of thisCode.

Tunnels linking two or more buildings shall be protected unless the buildings are fire-isolated from thetunnel by approved means.

1.4.1.3.6 Open grid (or egg crate) ceilings

1.4.1.3.7 Monitor, sawtooth or gable ceilings or roofs

1.4.1.3.8 Tunnels

1.4.1.3.9 Strongrooms, vaults, or the like

In a strongroom, vault, or the like, each room shall have a separate alarm zone facility or a suitablylabelled and monitored indicating device installed outside the room. The indication'shall latch on untilthe alarm zone facility is manually reset.

(i)

(iI)

a floor area not exceeding 1 m2, provided its content is of minimal fire risk;

a floor area not exceeding 0.3 m2 if housing electrical or communication equipment.

1.4.1.3.10 Other structures (i) Exhaust ducts: in ducts eXhausting from toilets, or rooms containing single ironing and laundryfacilities.

Additional protection should be provided where any special feature or condition calls for suchprotection. 1.4.3 Alarm zone limitation

Notwithstanding the foregoing requirements, detectors are not required in the following locations:

1.4.2 Locations where protection is not reqUired

NOTE - Under loading platfonns, mechanically ventilated cupboards, vertical service ducts, spray painting booths,kitchen hoods, walk-in type air handling plants and the like should be considered as requiring additional protection.

1.4.3.2 Permitted extension

Detectors protecting concealed spaces not exceeding 500 m2 area may be connected to thealarm zone below the concealed space, prOVided that the total number of detectors does ~ot

exceed the number specified in 1.4.3.1 and the total area covered does not exceed 2000 m ;

(a)

Notwithstanding 1.4.3.1, extension of the area covered by one alarm group may be permitted underthe follOWing circumstances:

1.4.3.1 Area limitation

A separate aiarm zone shall be provided for each 2000 m2 of protected floor area. The number ofdetectors required for this area shall not exceed the number specified in Clauses 2.7 to 2.9, accordingto the type of detector fitted.

There shall be a separate alarm zone for each floor and each fire compartment.

Protected areas to which there is no access from inside the building shall have separate alarm zonefacilities from those having access.

NOTE - For intennixing of detector systems - intennixing of the various detectors on one alann zone circuit ispennitted, provided that the detectors are suitably rated for the system voltages and are compatible.

Any non-recessed or free-standing switchboard or switchboard cubicle protected by thenormal protection of the area in which it is contained.

Sanitary spaces: any water closet, shower-recess or bathroom, with a floor area of less than3.5 m2 and opening off a protected area.

Covered ways: verandas, balconies, colonnades, open-sided covered walkways andstaircases (one-sided or more), overhanging roof areas, and the like constructed of materialnot deemed combustible, and not used for the storage of goods or as a car park.

Under all structures such as platforms, hoods, ducts and the like, within a protected room orarea, which are less than 2 m in width and do not obstruct the free flow of air from reachingthe detector(s) mounted above.

(d)

,~(a)

~ (b):1

Si~

(c)

14 15

Page 10: CP 10 2005

CP 10 : 2005

,-

CP 10: 2005

(b) The mezzanine fioor may be connected to the same alarm zone as the main fioor, providedthat the total number of detectors does not exceed the number specified in 1.4.3.1 and thetotal area covered does not exceed 2000 m2

;

(b)

(c)

"Leased-line" or "wireless system" failure/restored;

Fire alarm system fault/restored.

(c) Where a zone extends beyond a single fire compartment, the zone boundaries should beboundaries of fire compartments and the fioor area of the zone should not exceed 300 m2 •

Such signals shall appear as indicators in the monitoring stations in both audio and visual forms.

1.4.3.3 Fire extinguishing alarm initiating devices

Flow switches, pressure switches and the like associated with fixed fire extinguishing systems that areused to initiate an alarm, shall be individually connected under separate alarm zones on the fire alarmpanel. Flow switches used shall incorporate time-delay devices to avoid false alarm due to watersurges.

Initiation of the alarm signal shall occur within 90 seconds of water flow at the alarm-initiating devicewhen flow occurs that is equal to or greater than that from a single sprinkler of the smallest orifice sizeinstalled in the system.

1.4.3.4 Connection to existing alarm systems

Where the work is an extension of an existing alarm system, the combined systems shall bethoroughly tested to ensure that all parts of the systems are compatible and that it will satisfactorilyperform the required function. The new part of the system shall comply with the requirements of thisCode.

1.4.4 Connection to alarm monitoring station

1.4.4.1 Fire service signalling transmitter

All transmitting equipment shall be approved by the relevant authority. The transmitting equipmentshall have at least the following features:

If other signals such as security alarm signals are to be transmitted through the same "leased-line" or"wireless system", then the transmission of the fire alarm signals shall have an overriding priority overother non-fire alarm signals.

1.4.4.5 Box for transmitting equipment

The transmitting equipment shall be housed in a tamper resistance box consistent with that of themain alarm panel. The transmitting module may be housed within the main alarm panel.

Section Two - Design considerations

2.1 System components and equipment

2.1.1 General

The purpose of a fire alarm system is to detect fire at the earliest time and to give an alarm so thatappropriate action can be taken. It may be installed for the protection of life, property, or both. Thecontrol and indicating equipment of a fire alarm system shall be contained within its own enclosure(s).Other systems should only be connected to the fire alarm system if their connection does not causethe performance of the system or any component to fail outside the limits specified by relevant parts ofthis Code. Interfacing is permitted to provide data to the BUilding Management System. An illustrationof the components of a typical fire alarm system can be seen in Annex D.

(a)

(b)

(c)

(d)

Transmission of signal via "leased-line" or "wireless system";

Alternative transmission path via direct exchange telephone line which serves as back up;

Be designed so that all connections are completely enclosed and not accessible tounauthorised persons;

Indications for status of phone line, system test, alarm and power supply.

All system equipment used shall be listed by institutions recognised by the relevant authority, andsuitable for use locally. Consideration shall be given for local ambient conditions such as temperatureand relative humidity.

2.1.2 Compatibility

All the individual components of a fire alarm system shall be compatible. This is particularly importantif the components of an installation are made by different manufacturers.

1.4.4.2 Power supply

The power supply requirement for transmitting equipment shall comply with the relevant requirementof Clause 2.3. It may be derived from the same power source of the main alarm panel.

1.4.4.3 Means of transmission

"Leased-line" or ''wireless system" shall be the primary means of signal transmission with an automaticswitch over to normal direct exchange telephone line upon failure of the "leased-line" or ''wireless system".

1.4.4.4 Signal transmission

The following signals shall be transmitted to the monitoring station:

(a) Fire alarmlfire alarm reset;

16

2.1.3 Special environment

If any equipment is located in a position where it is exposed to dampness, corrosion, extremetemperature, large fiuctuation of temperature or other special condition, the design and constructionshall be such that the reliability of the system is not adversely affected by these conditions. Inparticular any equipment which is installed in places where fiammable or explosive gas or dust may bepresent shall comply with the appropriate Singapore Standard or any other standards accepted by therelevant authorities for the use in such hazardous environment.

2.1.4 BUilding management system

Where a Building Management System (BMS) is installed in a building, the BMS shall not be used toreplace in total or in part the fire alarm system specified in this Code. If the BMS is meant to providesurveillance as well as monitoring of the fire alarm system, the fire alarm system shall be capable ofoperating independently at all times.

17

Page 11: CP 10 2005

CP 10: 2005 CP 10 : 2005

2.1.5 Design process for limitation offalse alarms

At the design stage of every system, there should be formal consideration of the potential for falsealarms, with a view to confirming the design is such that the frequency of false alarms is likely to beacceptable.

In principle, measures to limit false alarms may be divided into:

Siting and selection of manual call points;

(j)

(k)

Fire alarm buzzer silencing switchA switch to silence only the fire alarm buzzer, and may be the same as that used for silencingthe fault warning buzzer (see 2.5.9).

Fire alarm sounder silencing switchA switch to acknowledge that the fire alarm has been noted by the operator and to silence thefire alarm sounder (see 2.5.8). A yellow visible indication shall be shown when the fire alarmsounder is being silenced.

Selection and siting of automatic fire detectors;

Protection against electromagnetic interference;

(I) Evacuation switchA switch to energise all the alarm sounders so as to alert all personnel that a fire has beendetected and to leave the premises immediately.

Performance monitoring of newly commissioned systems;(m) Indicator test facility

A manual operation to energise all visible and audible indicators to detect any faulty ones.

System management;

Regular servicing and maintenance.

(n) Fire alarm signal for remote monitoringA provision for the automatic transmission of fire alarm signals to the fire service signallingtransmitter (see 2.2.9). The transmission of the signal shall be indicated by a red visibleindicator, and shall remain until the fire alarm condition is reset.

2.2.2 Zone chart/mimic panel

/

NOTE - Each general visible indication and system energisation indication shall be given via a separate Iight­emitting indicator.

Fault signal for remote monitoringA provision for the automatic transmission of fault signals to the fire service signallingtransmitter (see 2.2.9). This output shall signal all faults specified in 2.2.5.

For sub alarm panel, items (n) and (0) are not applicable.

(0)

Where sub alarm panels are used, each sub alarm panel is to be provided with a single alarm zonefacility at the main alarm panel. Sub alarm panel shall be required in a large building or multi-buildingcomplex.

2.2.1 Main/sub alarm panel

(a) Fire alarm indication (Red)A general visible indicator followed by a separate visible indicator for each zone, to identify thesource of the alarm location.

2.2 Alarm panel

(b) System fault indication (Yellow)A generai visible indicator followed by a separate visible indicator for each fault covered in2.2.5.

The main/sub alarm panel with the associated control and supervisory functions shall consists of thefollowing:

II

!,

I:!;1

(c)

(d)

System energisation indication (Green)A visible indicator to show that the system is energised.

Isolation indication (Yellow)A general visible indicator followed by a separate visible indicator for each zone, to show thatthe alarm zone has been isolated.

A zone chart shall be provided at each alarm panel location. For fire alarm panel that uses onlyalphanumeric display to identify its alarm location, indicators shall be fixed on the diagram of the mimicpanel to show its alarm location. The mimic diagram shall be installed in accordance with its floor orbuilding orientation.

2.2.3 Location

(e)

(f)

(g)

(h)

System reset facilityA switch to reset the system to normal after the fault and/or alarm has been cleared.

Power supply monitoring facilityA circuitry to monitor the condition of the system power supply.

Audible fault warning buzzerA buzzer to alert the operator that a fault is present in the system.

Fault buzzer silencing switchA switch to silence the fault warning buzzer (see 2.5.10).

The main alarm panel shall be sited in the building fire command centre. If a fire command centre isnot available, it should be sited ideally in a position clearly visible from the main entrance lobby.Alternatively, where the main fire alarm panel is mounted in a remotely located control pointacceptabie to the relevant authority, a mimic or repeater panel should be installed in a position cleariyvisible from the main entrance lobby. If necessary, a suitable notice should indicate its position.

Where sub alarm panels are used, they shall be located at the fire lift lobby, smoke stop lobby,protected staircase in that order of priority or at the main point of entry into the area covered by thealarm zone.

2.2.4 Alarm zone facilities

(i) Fire alarm buzzerA buzzer to inform the operator that a fire alarm has been activated, and may be the same asthat used for fault warning.

Each alarm zone shall be provided with the following facilities:

(a) Alarm indication. A visible indication by means of a separate light-emitting indicator for eachzone and/or an alphanumeric display for ease of identifying its alarm location.

1819

Page 12: CP 10 2005

CP 10 : 2005 CP 10: 2005

(iii) The total number of zones In alarm shall be permanently displayed.

(b)

(c)

Fault indication. A visible indication by means of a separate light-emitting indicator for eachzone and/or an alphanumeric display for ease of identifying its fault location.

Isolation facility. A means to manually Isolate an alarm zone. A visible indication by means ofa separate light-emitting indicator for each zone and/or an alphanumeric display for ease ofidentifying its isolated location. Only authorised personnel appointed by the buildingmanagement shall have access to this function. Upon isolation of an alarm zone, the facilityshall Inhibit all subsequent fault and fire signals from that isolated zone and shall not impairthe normal functioning of any other alarm zones in the system.

(ii)

(iv)

The most recent zone in alarm shall be permanently displayed in another field.

Zones in alarm not currently indicated shall be capable of being displayed. A singlemanual action shall be required for the display of each additional zone in alarm, whichshall either be in the field used for the first zone in alarm, or in another field. In theformer case, the display shall revert to the first zone in alarm between 15 seconds and30 seconds following the last interrogation.

NOTE - CPU fault visible indication shall be given by means of a separate light-emitting indicator.

2.2.5 Precaution against failure

2.2.6 Visible indication for alarm panels

A separate visible and audible fault indication shall be given on the panel. The visible indications may besuppressed during the fire alarm condition for the following faults except items (c), (d), (I), (m) and (n): The presence of fault indications that have been suppressed shall be indicated;

Suppressed indications shall be capable of being displayed, independently of otherindications, by means of a manual operation.

The presence of isolation indications that have been suppressed shall be indicated;

Suppressed fault indications shall be capable of being displayed by means of amanual operation, which interrogates only fault indications.

(i)

(il)

Fault warning condition. If the indication is on an alphanumeric display, which cannotsimultaneously indicate all of the faults due to Its limited capacity, the following shall apply:

(i)

(il)

Isolated condition. If the indication is on an alphanumeric display, which cannot simultaneouslyindicate all of the isolation due to its limited capacity, the following shall apply:

(a) Information not related to the fire alarm condition shall be suppressed, unless the display hasmore than one window, one of which is exclusively reserved for fire alarm indications.

If the fire alarm indications are on an alphanumeric display, the following shall apply to the display ofother information: ...

2.2.7 other indications during the fire alarm condition/

The arrangement of indicators shall be such that the operation of any indicator clearly shows the alarmzone location.

2.2.8 Identification and marking of indicators

(b) Suppressed indications of faults and isolations shall each be capable of being displayed at anytime by manual operations. If the display is in the field where the first zone in alarm isdisplayed, the indication shall revert to the first zone in alarm between 15 seconds and 30seconds following the last interrogation.

Where, because of the size of the building and the location of the detectors, it is not possible toadequately describe all detector locations concisely on the main/sub alarm panel, the location of thedetectors should be permanently indicated on a separate panel, within or adjacent to the main/subalarm panel.

(c)

NOTE 2 - All visible indicators shall be visible on the fire alarm panel, without the need to open a door.

NOTE 1 - The indications on alphanumeric displays do not require the use of different colours. However, ifdifferent coiours are used it shall follow the relevant colour codes for fire alarm, fault warning and isolatedconditions.

(b)

Electrical earth fault of cables containing direct power source;

Removal of any detector from its circuit;

Disconnection of a transmission path, which affects the transmission of fault signals to the fireservice signalling transmitter;

Short-circuit of a transmission path, which affects the transmission of fire alarm signals to thefire service signalling transmitter;

Short-circuit of a transmission path, which affects the transmission of fault signals to the fireservice signalling transmitter;

Disconnection of any leads to fire alarm devices (sounders) external to the fire alarm panel;

CPU fault in the case of a software-controlled fire alarm panel (see 2.2.12).

Short-circuit in any cable of alarm zone circuit;

Open circuit in any cable of alarm zone circuit;

Short-circuit of any leads to fire alarm devices (sounders) external to the fire alarm panel;

Disconnection of call point from its circuit;

Disconnection of a transmission path, which affects the transmission of fire alarm signals tothe fire service signalling transmitter;

Short-circuit of primary power supply source, battery charging equipment and battery;

Disconnection of primary power supply source, battery charging equipment and battery;

The visible indication shall be by means of a separate light-emitting indicator and/or an alphanumericdisplay. No filament lamp shall be used for visible indication. If the indication is on an alphanumericdisplay, the following conditions shall apply:

(a)

(b)

(c)

(d)

(e)

(f)

(g)

(h)

(i)

Ul

(k)

(I)

(m)

it(n) .

i,

(a) Fire alarm condition. If the zonal indications are on an alphanumeric display, which due to itslimited capacity cannot simultaneously indicate all the zones in alarm, the following shall apply:

(i) The first zone in alarm shall be displayed in a field at the top of the display.

I 20 21

Page 13: CP 10 2005

CP 10 : 2005

2.2.9 Signals to fire service signalling transmitter

If the fire alarm indications are on an alphanumeric display, a field shall be capable of containing atleast the following:

CP 10: 2005

Power supply2.3

2.3.1 Operating voltage

The primary power supply for the fire alarm system shall be a.c. supply from an authorised electricityprovider and shall be exclusive to the alarm system. The secondary (standby) power supply shall bein the form of storage batteries with an automatic charger.

The secondary power supply shall be capable of operating the alarm system in the event of failure ofthe primary power supply and vice versa.

2.3.2 Form of supply

The operating voltage for the alarm system shall be extra low voltage.

16 characters, where the display of a fire aiarm uses a cross-reference to other information toidentify the location;

40 characters, where the display Is intended to include complete information on the location ofa fire alarm.

(b)

(a)

The m~in alarm panel shall be able to transmit fire alarm and fault signals to the fire service signallingtransmitter. There shall be no delay and no isolation is allowed for the transmission of fire alarm andfault signals to the fire service signalling transmitter. Fault output signal to the fire service signallingtransmitter shall be provided If the CIE is de-energised.

2.2.10 Fire alarm panel cabinet Fault warning shall be given in the event of failure of the primary/secondary power supply.

(a) The cabinet shall be red and of robust construction; 2.3.3 Battery charger

(b) The fire alarm panel must be easily identifiable;

(c) The manufacturer's name, together with any other appropriate means of identification of thealarm system, shall be clearly and permanently marked on the front face of the fire alarmpanel. The above information shall include the type of panel and the model number.

2.2.11 Records

A battery charger of the appropriate type and rating shall keep the storage batteries under constantvoltage charge. The charger shall incorporate automatic control features with output designed tocharge and maintain the batteries within the limits specified by the battery manufacturer, taking intoaccount any quiescent load imposed by the associated system.

The charger shall be designed and rated so that a battery discharged to its final voltage can berecharged to at least 80 % of its rated capacity within 24 hours and to its rated capacity within another48 hours.

A log record shall be. kept in which details of all alarms (genuine, false, practice, or test), 'faults,service, ~ests and routine attention given shall be properly maintained and updated. The log recordshall be In the form of soft copy, pnnt out or log book. If the log record is kept in the form of a logbook, a recommended format for the log book is described in Annex C.

2.2.12 Program controlled fire alarm system

A progra~ controlled fire .alarm system performs its primary function via microprocessors or similardeva::es, In which the particular c~aracteristics of a system are dependent on a stored program. Inaddition to the reqUirements listed In this Code, such systems shall comply with the following:

The charger should be connected to the building emergency mains supply if the supply is available.The primary power supply shall come directly from the electrical distribution board and the circuit shallnot be used for any other purposes. The protective Isolating device controlling this circuit shall beclearly labelled to indicate that it controls the fire a!arm system. The primary power supply circuit shallbe terminated inside the fire alarm panel or its Integral power supply unit. No external intermediaryswitch shall be proVided between the protective isolation device at the electrical distribution board andthe fire alarm panellintegral power supply,unit.

2.3.4 Battery capacity

NOTE - When an extemal CPU is used to record the events and/or generate graphics, this equipment isacceptable as an enhancement to the mam fire alarm system only.

(c) The op~ration of. processors shall be continuously monitored. This is partiCUlarly importantwhere It IS P?sslbie for the stored program to be accidentally corrupted (e.g. by transientInterference) m such a way as to interfere with the correct operation of the system. In theevent of a faJiure, a fault warning shall be given (see 2.2.5) and shall remain until a manualreset and/or another manual operation. The restart procedure should check the contents ofthe memories, and if necessary re-initialise running data to ensure that the fire alarm systementers a safe operating state.

(a)

(b)

Facilities provided for the alteration of the stored program shall be protected againstunauthorised alteration.

Those function~ of the system which are required in this Code shall not depend on programsstored on rotating diSks, other storage media using moving parts, or any other form of easilycorruptible memory.

The capacity of the storage battery used to power the alarm system shall be such that in the event ofprlm~ry power supply failure, the battery Is capable of maintaining the system in normal workingcondition for at least 24 hours. Thereafter it shall be capable of supplying an additional load resultingfrom an alarm originating in two separate alarm zones for a period of half an hour and, if utilised tosupply ~mergency evacuation alarms, It shall in addition be capable of supplying the full emergencyevacuation alarm load for a period of at least 10 minutes.

NO"!"E - Care shall be taken to size the battery capacity to include the load controlling the operation of ancillaryequipment (see 2.4.2).

2.3.5 Battery location

Batteries shall be kept in a separate cool, dry and well-ventilated location. They shall be kept in alocked cabinet. Such cabinet or container shall be readily accessible for inspection and shall not beab~ve the control cabinet. The interior of the cabinet or container shall be protected against corrosion.Maintenance-free batteries need not have a separate location.

22 23

Page 14: CP 10 2005

CP 10 : 2005 CP 10: 2005

2.4.1 When permitted

2.4.2 Connection requirements

Voltages in excess of extra low voltage associated with remote control functions shall not enter thealarm panels. This requirement does not apply to the primary power supply feeding the alarm panels.

AnciJIary equipment not forming an essential part of the approved fire alarm system may be connectedeither through relay(s) or interfacing device(s), provided that such additional device(s) wiJI notadversely affect the system or otherwise prejudice the performance of the approved system.

In discos, night-clubs and other places of entertainment, the sound system shall be electricallyinterlocked with the fire alarm system to enable the sound to be automatically cut-off in the event thatthe fire alarm is activated.

2.5.4 Code signalling

Generally, all alarm sounders in the building shall be activated simultaneously in the event of an alarmunless it is permissible under 2.5.6.

Code signalling on audible alarms, for example: one ring means "first floor" and two rings means"second floor" etc., shall not be used. Such coded signals on audible alarms are liable tomisinterpretation.

Connection of additional equipment2.4

I1,!!

Where provision is to be made for the operation of anciJIary equipment under fire alarm conditions asrequired by the relevant authority (such as the control of air handling equipment, lift homing,pressurisation fans and fire suppression system), a current limited extra low voltage supply may beprovided from the fire alarm panel to operate a relay or similar operating device controlling theequipment in question. The circuit controlling this operation shall be supervised or be of a 'fall-safe"type. Visible and audible fault indications shall be prOVided at the front of alarm panel.

Overload protection shall be provided such that any short circuit or malfunction of any anciJIaryeqUipment cannot impede the proper functioning of other anciJIary equipment, the fire alarm panel andother connected equipment. In cases where electrically operated anciJIary equipment requirescontinuous power supply, such power supply shall be separate and distinct from the power supply ofthe fire alarm system.

2.5 Audible and visual alarms

2.5.1 General

The installation of an automatic fire alarm system using audible and visual alarms appliances shallcomply with Sections 1 and 2, in so far as they are applicable and appropriate, and with this clause.

Audible alarm appliances shall form part of the fire alarm system and shall be installed in a building sothat audible alarm signals are clearly audible throughout the bullding(s)!fIoor(s) in which they areinstalled. It is essential that audible alarm signals are sufficient in nature and of the extent to warn andinitiate evacuation of all persons for whom the alarm signals are intended.

2.5.5 Restricted alarms

In some installations, and sUbject to the approval of the relevant authority, where the control point isunder continuous and competent watch during the whole time the premises are occupied, it may beadvisable that in order to avoid unnecessary dislocation, to restrict the alarm in the first place to thelocality from which It arises and to resort to the sounding of a audible general alarm only if aresponsible person considers it desirable to do so. Such a restricted alarm system shall alwaysincorporate suitable means of summoning fire-fighting staff to the outbreak on the operation of thealarm.

An audible general alarm is undesirable where distress or disturbance might arise as in health carefacilities and the like. In such places, it is desirable that the alarm system shall be restricted to theprOVision of audible alarms out of hearing of the public or patient. The aUdible alarms shall besupplemented by adequate visual alarms throughout the premises for staff recognition only and/or bydiscreet special sounders. The staff in such premises should be sufficient in number and properlydriJIed to conduct other occupants to safety in the event of an activation of fire alarm. In all cases,there shall be effective arrangements for giving an audible general alarm throughout the premises. Anacceptable arrangement is to provide a delay timer to set off the audible general alarm after apredetermined delay to be approved by the relevant authority. A manual evacuation switch shall beprOVided to give an immediate audible general alarm. The relevant authority should be consulted veryearly in the design stage as to the best method of providing an appropriate system.

In the case where the system is directly lfnked to the fire alarm monitoring station, the delay timer shallnot delay the immediate transmission of the fire signal to the fire alarm monitoring station.

2.5.6 Multi-stage alarm2.5.2 Audible alarm sounders

All audible alarm sounders shall generate the continuous tone of an alarm bell. In specialenvironments where the use of alarm bell tone is impractical or in areas of high background noiselevel, other tones may be used, in which case the relevant authority's permission must be sought. It isessential that all audible alarm sounders in a particular installation shall produce a similar tone.

2.5.3 Audibility of general alarms

The number of audible alarm sounders used shall be sufficient to produce a minimum sound level ofeither 65 dBA, or 5 dBA above the ambient noise level likely to persist for a period longer than 30seconds, whichever is greater. In all parts of the bUildings, the sound level produced by audible alarmsounders signalling shall not exceed 120 dBA. If levels higher than this are required, special provisionssuch as Visual alarm signal should be considered (refer to 2.5.7).

In certain large and/or high rise bUllding(s), a multi-stage fire alarm arrangement might be moreappropriate. In the multi-stage fire alarm system, the initial warning of fire is given in a restricted area,or is restricted to key personnel, but can be extended in the further stages to ultimately warn alloccupants of the premises.

For evacuation, it might be desirable to firstly evacuate from those floors of the premises at the greaterrisk, usually those closest to the fire or immediately above and below the f1oor(s). Other floors areevacuated thereafter. In such a case, a mUlti-stage alarm shall be subjected to the approval of therelevant authority.

It is important that in such a system, an evacuation manual switch shall be prOVided at the main alarmpanel to activate all the fire alarm sounders for total evacuation. In any case if the alarm is notacknowledged/reset after a predetermined delay specified by the relevant authority, all the fire alarmsounders in the building shall be activated.

In order to prevent excessive sound levels in some areas, it may be preferable to install a largernumber of quieter alarm sounders rather than a few very loud sounders.

24 25

Page 15: CP 10 2005

CP 10: 2005 CP 10 : 2005

2.5.7 Visual alarm signal 2.5.10 Fault buzzer silencing

The silencing of the fault buzzer whilst a fault condition exists shall:

2.5.11 Alarm verification feature (AVF)

The principle of system operation shall be such that once a fault condition has been received, the faultbuzzer shall continue to operate until normal conditions have been restored.

The activation of the AVF function for the selected zone shall be through selector switch orprogramming.

not prevent the proper receipt of fault warning on any circuit not already providing the fault.

not cancel the indication of the faUlt or any indicator concerned;(a)

(b)

Such an alarm verification feature, if provided, shall operate in the following manner. Upon activationof a detector in any zone, the fire alarm system shall go into an alarm retard state for a period notexceeding 20 s at the control unit. After the expiry of this period, the fire alarm system shall go into analarm confirmation state for a period not less then 120 s and not exceeding 300 s. Only when thesame detector or another detector within the same zone or panel is activated during this alarmconfirmation period, shall the fire alarm system go into full operation.

To reduce the effects of transient environmental conditions, Which may cause various types ofdetectors to be activated, an automatic fire alarm system may be provided with an alarm verificationfeature, subject to the approval of the relevant authority.

The silencing of fire alarm sounders whilst an alarm condition exists shall:

2.5.8 Fire alarm sounder silencing

In general, visual signals shall not be used in place of audible alarms. The intensity of the light shallbe sufficient to draw the attention of people in the vicinity.

In areas where audible alarms may be ineffective, e.g. where the background noise is excessive,where there are people with impaired hearing or where hearing protection is likeiy to be worn, visualaiarm signals shall be provided.

The principle of system operation shall be such that once an alarm has been given the fire alarmsounders shall continue to operate until normal conditions have been restored. No isolation and delayfacilities shall be allowed for the transmission of fire alarm signals to fire alarm sounders.

If a building does not have an approved emergency voice communication system complying with SSCP 25, whenever the fire alarm system enters a new fire alarm condition, only the first alarm shall bepermitted to be silenced after 3 minutes and any sUbsequent alarms may be silenced immediately. Anappropriate instruction shall be provided for this function. Where a building is provided with anapproved emergency voice communication system complying with SS CP 25, alarm sounders may besilenced immediately. In this case when the fire alarm sounder is silenced, a recorded voice messageshall automatically be activated to inform the occupants in the building of the alarm. A yellow visibleindication that the alarm has been silenced shall be provided at the front of the main/sub alarm panel.The indication of the alarm on any indicator concerned shall not be cancelled whilst the fire alarmsounders are still in operation.

I

(a)

(b)

(c)

not prevent the transmission of the alarm signal to the approved monitoring station;'

not cancel the indication of the alarm or any indicator concerned;

not prevent the proper receipt of alarm signal on any circuit not already proViding the alarmfrom other zones, and shall not prevent the restarting of the fire alarm-sounder;

Receipt of firstalarm signal

- ------±---------;;I;;-...:./-. ---;=t-:.,.,.- Time (s)I 1 [o 20 140 (min)320 (max)

When the fire alarm system is in the AVF mode, the activation of the system reset facility shall notreset the AVF operation.

A visible indication in the form of a yellow light-emitting indicator or an alphanumeric display shall beprovided when the fire alarm system enters into the alarm retard state and/or alarm confirmation state.

The follOWing components of the fire alarm system shall not be SUbject to this feature:

(a) Alarm zone facilities containing only manual call points;

Normal stateAlarm confirmationstate

Alarm retardstate

Normal stale

The silencing of the fire alarm buzzer whilst an alarm condition exists shall:

The principle of system operation shall be such that once a fire alarm condition has been received, thefire alarm buzzer shall continue to operate until normal conditions have been restored. The fire alarmbuzzer shall not be silenced automatically.

(a) not cancel the indication of the alarm or any indicator concerned;

2.5.9 Fire alarm buzzer silencing

(d) not prevent the correct operation of any control for starting or restarting the fire alarmsounders.

The silencing of the general fire alarm sounders shall only be permitted at the activated main/SUbalarm panel.

,'I'I'I:1IH11,I11

(b) not prevent the proper receipt of alarm signal on any circuit not already providing the alarmfrom other zones, and shall not prevent the restarting of the fire alarm buzzer.

(b)

(c)

(d)

(e)

Circuits between sub alarm panels and the main alarm panels;

Detectors used to activate fire suppression systems;

Detectors installed in high risk areas;

Alarm zone cirCUits from fire suppression systems.

26 27

Page 16: CP 10 2005

CP 10 ; 2005 CP 10: 2005

2.6.1 General

2.6 Manual call points This clause applies only to conventional point-type heat detectors. Fire alarm systems based on adifferent heat detection concept may be used subject to the approval of the relevant authority.

2.7.2 DetectorsManual call points shall be provided in accordance with the latest Code of Practice for FirePrecautions in BUildings. There are two main types of heat-sensitive elements in each form as follows:

2.6.2 Manual call point

Manual call point shall be bright red in colour and shall be of the "break glass" type. The glass of thecall point shall be of the non-fragmental type. Other types of manual call point may be used subject tothe approval by the relevant authority. .

(a)

(b)

Rate-of-rlse of temperature elements which are designed to operate when their temperaturerises abnormally quickly;

Fixed-temperature (static) elements which are designed to operate when they reach apreselected temperature.

2.6.3 Special environment

Special consideration shall be given to provide suitable type of call points installed in extremeconditions such as outdoor, damp, corrosive, flammabie or explosive environment.

2.6.4 Operation

Detectors containing only rate-of rise elements shall not be used.

The delay between the activation of a heat detector and activation of the generai alarm shall notexceed 10 seconds.

The type of detectors used shall be as follows:

The method of operation of all manual call points in an installation shall be identical unless there is aspecial reason for differentiation.

The delay between operation of a call point and activation of the general alarm shall not exceed 3seconds.

2.6.5 Supervision

Manuai call points shall be connected to the alarm zone circuit protecting the area where they areinstalled and it shall be electrically supervised.

2.6.6 Location

Manual call points shall be provided on every storey of the bUilding or part of the building. It should belocated on exit routes preferably next to hose reels and in particular on the floor landings of exitstaircases and at exits to the street(s).

Manual call points should be fixed at a height of 1.4 m above the finished floor level and shall belocated at easily accessible and conspicuous position free from obstructions. It shall be so locatedthat no person needs to travel more than 30 m from any position within the building to activate thealarm. It shall also be installed in well-lighted positions and against a contrasting background so thatthey can be seen easily.

2.6.7 Alarm zone

Manual call points shall not share the same alarm zone with other detectors.

(a)

(b)

(c)

(d)

(e)

Type A - Normal temperature duty, incorporating both fixed-temperature and rate-of-riseactuation. This type of detector shall be considered for use in the majority of applications withmoderate ambient temperatures below 45 ·e where rapid temperature increases are notnormally experienced (see Note).

Type B - Normal temperature duty, fixed-temperature actuation only. This type of detectorshall be considered where rapid temperature increases are normally encountered and themaximum ambient temperature does not normally exceed 45 ·e.

Type e - High temperature duty, incorporating both fixed-temperature and rate-of-riseactuation. This type of detector shall be considered for use in applications with high ambienttemperatures below 75 ·e where rapid temperature increases are not normally experienced(see Note). /

Type 0 - High temperature duty, fixed-temperature actuation only. This type of detector shallbe considered where rapid temperature increases are normally encountered and themaximum ambient temperature does not normally exceed 75 ·e.

Type E - Special purpose fixed-temperature actuation. Type E detectors are intended toprovide protection in areas which cannot be satisfactorily protected by Types A to 0 owing tosome factors associated with the environment, such as extremely high ambient temperatures,severe corrosion, and the like.

The maximum coverage of Type E detectors is 9 m' for a detector of point-type construction.(For all other types of Type E detectors, the advice of the relevant authority should be soughtprior to the inclusion of this type of detector in a fire protection system, if it is to be consideredas the only type of detector for the area.)

Each manual call point should have its alarm zone number indelibly marked on the unit so that it isclearly visible.

2.7 Heat detection systems

2.7.1 General

The installations of automatic fire alarm system using heat detectors shall comply with Sections 1 and2, in so far as they are applicable and appropriate, and with this clause.

28

NOTE - Although Type A or Type e detectors are intended to protect the majority of areas, specialcircumstances may prevent or interfere with reliable operation. Such circumstances may dictate the use of aType B, Type D, or Type E detector manufactured to suit the special environment.

2.7.3 Spacing and location of detectors

2.7.3.1 General

The location of detectors shall be to the best advantage for detecting a fire. The maximum spacingand location of detectors shall comply with the requirements of s 2.7.3.2 to 2.7.3.7 (see Figures 1, 2and 3 for detector locations).

29

Page 17: CP 10 2005

CP 10: 2005

.-

CP 10: 2005

2.7.3.2 Location

Detectors shall be installed in the highest point of the ceiling where appropriate. However, where theceiling is constructed with beams or joists less than 300 mm deep, the detector may be installed onthe underside of the beam or joist. '

Isolated attachments to the ceiling such as lighting fittings and iuminaries do not normally act asobstructions to the general fiow of smoke or hot gas. They may, however cause a local disturbance,and detectors should not be mounted too close to such attachments; the distance should be morethan twice the depth of the attachment.

Care shall be taken in the location of detectors to ensure that their correct operation is not prejudiced. by special conditions of dampness, high ambient temperature (see 2.7.2), vibration, air currents (e.g.from air conditioning outlets) or the like. Detectors shall not be installed closer than 400 mm to any airsupply outlet.

2.7.3.3 Spacing between detectors for flat ceilings

(a)

(b)

(c)

Concealed spaces with upper level surfaces in excess of 2 m high shall have detectorsspaced in accordance with 2.7.3.3,2.7.3.4 and 2.7.3.5.

For concealed spaces with upper level surfaces less than 2 m high and having downwardprojections, such as beams and ducts, not exceeding 300 mm from the upper surface of thespace, the spacing between detectors shall not exceed 10 m. Where the downwardprojections exceed 300 mm, the spacing of detectors shall be in accordance with 2.7.3.4 and2.7.3.5.

For concealed spaces with apices, the spacing between detectors in the longitudinal directionat the apex and sloping roof shall not exceed 7.2 m and 14.4 m respectively. On the slopingroof, the horizontal distance between rows parallel to the apex shall not exceed 7.2 m with thelowest row of detectors located not more than 7.2 m measured horizontally towards the apexfrom a position where the vertical height, between the upper and lower surfaces of the space,is 800 mm. The longitudinal spaces between the detectors on the lower rows shall bearranged so that the detectors are spaced equally between the detectors on the adjacent rows(see Figure 2).

For fiat ceiling, excluding corridors, the distance from any point on the ceiling of the protected area tothe nearest detector does not exceed 5.1 m (see Figure 1a). In addition, the distance betweendetectors shall not exceed:

(a) 7.2 m for areas other than corridors (see Figure 1a);

(b) 10.2 m for corridors (see Figure 1b).

2.7.3.4 Spacing of detectors from walls or partitions

2.7.3.7 Detector mounting

Each detector shall be installed in such a way that the sensing element is not less than 15 mm or morethan 100 mm below the ceiling or roof. Where roof purlins inhibit the free flow of heat to the detector,the detector may be installed on the underside of such purlins provided that the sensing element is notfurther than 350 mm from the roof.

Heat detectors beneath roofs and ceilings SUbject to solar radiation shall be installed with the sensingelement between 180 mm and 350 mm vertically below the roof or ceiling.

2.7.3.5 Reduced spacing

For all types of heat detectors, closer spacing may be required to take into account the special structuralcharacteristics of the protected area. In particular, the following requirements shall be observed:

The distance from the nearest row of detectors to any wall or partition shall not be less thaA 300 mmor exceed half the relevant maximum allowable distance between detectors given in 2.7.3.3, 2.7.3.5and 2.7.3.6. For corridors, this distance shall only be taken from end walls.

J

Ii

iII

(a)

(b)

Where the ceiling of the protected area is segmented by beams, joists or ducts, and thevertical depth of such members is greater than 300 mm, the distance between detectors shallbe reduced to but not exceeding:

(i) 5 m for areas other than corridors;

(iI) 7 m for corridors.

Where the height of the fiat ceiling exceeds 3.5 m, the distance between detectors shall bereduced to but not exceeding:

(i) 6 m for areas other than corridors;

2.7.3.8 Arrangement of alarm zones

Not more than 40 heat detectors shall be connected on a single alarm zone. (see 1.4.3.1)

NOTE - Where a single alarm circuit is connected,with more than 40 heat detectors, means shall be specifiedand provided which ensure that a short circuit or an interruption in this detection alarm circuit does not preventthe indication of a fire alarm from more than 40 heat detectors..

360~3600

7200 , 7200 , 7200 ,-\. \.r.. \.

,,~

7200 <,

, ) , ,-::y -:: \.i \...

(a) Spacing for open areas

(iI) 8 m for corridors.

Where the height of the ceiling above the protected area is greater than 6 m, it is recommended that amore sensitive type of detector be considered.

2.7.3.6 Spacing of detectors in concealed spaces

Concealed spaces for which protection is required, other than those exempted under 1.4.1.3.1, shallbe protected in accordance with the following:

30

ilf-----"5-'-'10"'0'----_+I---------'1-"-0=-20"'0'-------~+I--------

(b) Spacing for Corridors

Dimensions in millimetres

Figure 1 - Typical heat detector spacing - Flat ceilings

31

Page 18: CP 10 2005

CP 10: 2005

7200 max. (Note 2)

1 I I I1500 max.

500 min. M

II Site detector

~i_'-,n:,£:~~soa-,!,:~:x,,--.~------i~

CP 10: 2005

1500 max.

500min.MJn Site detector

~in this area

I I

I '! 7200 max.

Glassor similar

7200 max.

~omax.

et300 min. I

1

1

II

(e) Ceiling or roof with skylight

,'-'

(b) Sawtooth ceiling or roof

.'

Ct

______7....,2""0""0-"m~a"'x'__. 1

(c) Equal slope ceiling or roof

Side detectorin this area

7200 max.

,I

- I I( \1 I

4e;~atl~e

Site detectorin this area

1500 max.

~~I Irk l

Louvers~: I\J I

~IIIIIIII

(d) Louvred ceiling or roof with louvred riser

NOTE - Detector always on side with least slope.

Dimensions in millimetres

1500 max. 1500 max.

(a) Unequal slope ceiling or roof

Ct

l14400 Ct--.-

CtJ 14L

CtJ

7200I

Ct-+I

7200

Ct-+3600

3600

Ct-+I

7200I

Cti Ct7200

I

Cti7200

Ct-+ CtI

7200

Ct-+I

7200

Ct-+ CtI

7200I

Cti

(Note 1)

Figure 3 (in part) - Design criteria for point-type heat detectorsDimensions in millimetres

NOTE

1. Alternate rows offset.

2. See 2.7.3.6 (c).

3. t.owest row measurement from 800 mm height.

Figure 2 - Heat detector locations for concealed spaces with apex and sloping roof

32 33

Page 19: CP 10 2005

CP 10: 2005 CP 10: 2005

500 min.2000 max.

~

< 500

tiProtective Hood~

r~~cl

(f) Ventilated ridge

I

Louvers~

II

(g) Narrow apex

I,,III

~..~

cll~, ,

max.

2.8 Smoke detection systems

2.8.1 General

The installations of an automatic fire alarm system using smoke detectors shall comply with Sections 1and 2, in so far as they are applicable and appropriate, and with this ciause.

This clause applies only to point-type and opticai beam line-type smoke detectors. Fire alarm systemsbased on a different smoke detection concept may be used subject to the approval by the relevantauthority.

2.8.2 Detectors

The type of detectors for use in various locations is described in Annex A.

2.8.3 Spacing and location of detectors

2.8.3.1 General

The location of detectors shall be to the best advantage for detecting a fire. The maximum spacingand location of detectors shall comply with the requirements of of 2.8.3.2 to 2.8.3.7 (See Figures 4, 5,6,7,8 and 9 for detector locations).

2.8.3.2 Location

2.8.3.2.1 In determining point detector position, consideration shall be given to the following:

(h) Narrow ridge vent

> 2000

I" ·1~

Louvers ___! 1

1

f

--~ :, ,

(a)

(b)

(c)

(d)

High temperatures close to ceilings or roofs. It may be necessary to extend the location of thedetector downwards below the ceiling to obtain earliest response.

Detector mounting height over 3 m from the floor. The minimum distances of the sensingelements beiow the ceiling line shall comply with Figure 8.

Effects of airflow on the detector and the movement of smoke. Detectors shall not be installedcloser than 400 mm to any air sup-ply outlet.

Isolated attachments to the ceiling such as light fittings and luminaries normally do not act asobstructions to the general fiow of smoke. They may however cause local disturbance.Detectors should not be mounted too close to such attachments; the distance should be morethan twice the depth of the attachment.

(i) Broad ridge vent

7200 mal<. 7200 max.

et'""

.12.8.3.2.2 In determining optical beam line-type detector position, consideration shall be given to thefollowing:

(a) High temperatures close to ceilings or roofs. It may· be necessary to extend the location of thedetector downwards below the ceiling to obtain earliest response.

Dimensions in millimetres

NOTE

(b) Detector mounting height over 8 m from the floor. The minimum distances of thetransmitter/receiver units below the ceiling line shall comply with Figure 8.

(c)Infrared scans of a building have shown heat pockets at apices of roof structure due to solar radiation.Therefore, to obtain effective fire detection, the detectors must be located below these pockets.

Figure 3 (in part) - Design criteria for point-type heat detectors

34

Care should be taken to ensure that beam detectors' receiver units are not exposed to stronglight, especially direct sunlight.

2.8.3.3 Spacing between detectors for flat ceilings

For flat ceiling, the distance from any point on the ceiling of the protected area to the nearest detectorshall not exceed 7.2 m. In addition, the distance between point-type detectors shall not exceed 10.2 m.(see Figure 4).

35

Page 20: CP 10 2005

CP 10: 2005

For optical beam line-type detectors, the distance to the next transmitter I receiver shall not exceed 14 m.

NOTE - For ceiling height above 10 m the same spacing requirements may still be applicable provided thedetector has been type-tested and approved for use in aparticular situation.

CP 10 : 2005

2.8.3.7 Spacing of detectors in concealed spaces

Concealed spaces for which protection is required under 1.4.1.3.1 shall be protected in accordancewith the following:

2.8.3.4 Spacing of detectors from walls or partitions

The distance from the nearest row of detectors to any wall or partition shall not be less than 300 mmor exceed half the relevant maximum allowable distance between detectors given in 2.8.3.3, 2.8.3.5and 2.8.3.6. For the purpose of this clause, smoke barriers shall be considered partitions.

2.8.3.5 Spacing of detectors where additional protection is required

(a)

(b)

Concealed spaces with upper level surfaces in excess of 2 m high shall have detectorsspaced in accordance with 2.8.3.3 and 2.8.3.4.

For concealed spaces with upper level surface not exceeding 2 m high and having downwardprojections, such as beams and ducts, not exceeding 300 mm from the upper surface of thespace, the spacing between detectors shall not exceed 15 m. Where the downwardprojections exceed 300 mm, the spacing of detectors shall be in accordance with 2.8.3.5.

Where roofs or level surfaces are compartmentalised by structural features which could have theeffect of restricting the free flow of smoke, the detectors shall be located so that early detection isensured, sUbject to the following for point-type detectors (see Figure 9):

(a) For areas with ceiling height equal to or greater than 4 m and beam depth exceeding 100 mm(see Area 4, Figure 9), detectors shall be mounted on the underside of the beams and spacedin accordance with 2.8.3.3 and 2.8.3.4.

NOTE - Additional detectors shall be provided in interbeam area in cases where the interbeam area isso large that the spacing of detectors located on the underside of beams does not comply with 2.8.3.3and 2.8.3.4.

(c) For conceaied spaces with apices, the spacing between detectors in the longitudinal directionat the apex and sloping roof shall not exceed 10.2 m and 20.4 m respectively. On the slopingroof, the horizontal distances between rows parallel to the apex shall not exceed 10.2 m withthe lowest row of detectors located not more than 10.2 m, measured horizontally towardstheapex from a position where the verticai height, between the upper and lower surfaces of thespace, is 800 mm. The longitudinal spaces between the detectors on the lower rows shall bearranged so that the detectors are spaced equally between the detectors on the adjacent rows(see Figure 5).

2.8.3.8 Detector mounting

!Ij

(b)

(c)

(d)

(e)

For areas with ceiling height greater than 2 m but not exceeding 4 m, beam depth exceeding300 mm (see Area 3, Figure 9) and the interbeam area less than 4 m2

, detectors shall bemounted on the underside of the beams and spaced in accordance with 2.8.3.6.

For areas such as item (b) above, where the interbeam area is equal to or greater than 4 m2,

detectors shall be mounted in each interbeam area (see Area 3, Figure 9).

For areas with ceiling height not exceeding 4 m and beam depth not exceeding 300 mm (seeArea 1, Figure 9), the spacing of the detectors shall be in accordance y;ith 2.8.3.3 and 2.8.3.4.

For areas with ceiling height not exceeding 2 m and beam depth exceeding 300 mm (seeArea 2, Figure 9), the spacing of detectors shall be in accordance with 2.8.3.3 and 2.8.3.4.

NOTE - Where airflow reduces the response of the detector located in these areas, the detectorsshould be relocated in a more favourable position. Nevertheless, the spacing requirements of the aboveclauses should not be exceeded.

The sensing element for ceiling mounted point-type detectors shall be not less than 25 mm andnormally not more than 600 mm, below the ceiling or roof (see Figure 8).

Optical beam line-type smoke detactors shall be mounted not less than 300 mm and not more than600 mm below the ceiling or roof. Additional optical beam line-type detectors should be installed invertical shafts, e.g. atria and warehouse etc at lower levels (see Figure 8).

2.8.3.9 Arrangement of alarm zones

Not more than 20 smoke detectors shall be connected on a single alarm zone.

NOTE - Where a single alarm circuit is connected with more than 20 paint-type smoke detectors, then meansshall be specified and provided which ensure that a short circuit or an interruption in this detection alarm circuitdoes not prevent the indication of a fire alarm from more than 20 point-type smoke detectors.

2.8.3.6 Reduced spacing

For all types of smoke detector, closer spacing may be required to take account of specialcharacteristics of the protected area. The distance between detectors shall not exceed 7 m in thefollowing areas where:

(a)

(b)

the ceiling height is greater than 2 m but not exceeding 4 m, the beam depth exceeding 300mm and the interbeam area less than 4 m2

; or

the number of air changes exceeds 15 per hour.

NOTE - For areas with high air velocities Le. in excess of 3 m/s, the detector spacing may need to be furtherreduced or more sensitive detection equipment may need to be installed.

3637

Page 21: CP 10 2005

CP 10 : 2005 - .' CP 10: 2005

I

S}-----{ }-----(S}-----(S

I

10 200 max. (Note 2)

I I I I ! I I I, , r "

'f, f +® .-®

5100 10200

I® 20400

(b) Spacing for corridors

®

®

®

5100

®-+I

10200I

®-+ ®I

10200I

®-+I

10200I

®-+ ®I

10200I

®-+I

10200I

®-+ ®I

10200I

®-+ .-®

10 fOO I®-+ ®20400

I10200

®-f5100

®

®

®

® l.-®

®.. ®

I20400 ®

I®-'- ®

(Note 1)

(a) Spacing for open areas

Figure 4 - Typical smoke detector spacing - Flat ceilings

NOTE - Smoke detector spacing in corridors are the same as general areas.

Dimensions in miliimetres

I

i

Figure 5 - Point-type smoke detector locations for concealed spaces withapex and sloping roof

NOTE 1 Alternate rows offset.

NOTE 2 See 2.8.3.7 (c).

NOTE 3 Lowest row measurement taken from 800 mm height.

Dimensions in millimetres

38 39

Page 22: CP 10 2005

CP 10 : 2005. ","

CP 10: 2005

Xmax.

Site detectorin this area

1500 max.

500 min.

ISite detectorin this area

, _~---=-----_rsVr---- X max. _

1500 max.

500 min.

~s~s~s~s~s~s(§)s

(Note 2)

'""" I ."'" I """' L'""'~""""' L' 000 I "000 I . '""'[800 11 I~Ss ~ I!(Note1~~S ·t ~~

(a) Unequal slope ceiling or roof (b) Sawtooth ceiling or roof

"VS

Xrnax.

(c) Equal slope ceiling or roof

NOTE 1 - Lowest row measurement taken from 800 mm height applies to concealed spaces only.

NOTE 2 - Arrangement of siting of transmitter I receiver position shall be in accordance to the manufacturer'srecommendation.

NOTE - Detector always on side with least slope.

y,-,-------.-,

® Glass.JS or similar

300 min.

(e) Ceiling or roof with skylight

yS

Side detectorin this area

Xmax.

y

,,IS

(d) Louvred ceiling or roof with louvred riser

1500 max.

500 min.I,,

Louvers~ :

-:,,II,,I

----'

(S)s(S)s(S)s(S)s(S)s(S)s

(Note 2)

(S)S

Dimensions in millimetres Dimensions in millimetres

Figure 6 - Typical beam-type smoke detector locations for sloping surfacesFigure 7 (in part) - Design criteria for point-type and beam-type smoke detectors located

at apex of ceiling or roof

40 41

Page 23: CP 10 2005

CP 10: 2005 CP 10 : 2005

,,,,,,

~

MiNIMUM SENSING ELEMENT DISTANCE BELOW ROOF OR CEiLING LINE. mm

Figure 8 - Smoke detector locations

NOTE - Fire aerosols are transported by means of warm air from the fire source and their vertical progress isimpeded when the temperature of the smoke equals that of the surrounding air; therefore, for high ceilings alarger fire source is necessary to transport the smoke to the detector. For this reason, it is necessary for smokedetectors to be installed below the warm air pockets at roof levels as indicated by the graph.

Point-typesmoke detector

Beam detector

I500 600400

300

2 I-+--+--+--+----1--+--1o 100 20025

20 --,------,----,---r----.-.-./~I

18 I '/16 I V

E ~~ I /1/

~ ': I IL/r''------¥//'---/-+--+--II 6 ,-+1--+--+--+--1

4 I

/1/

-----y-~rl-S"5100

max.

(g) Narrow apex

500 min.2000 max.

~,Louvers ----J

,,

~

(f) Ventilated ridge

< 500

Protective Hoodb/~"",

/ : ~Cl

(h) Narrow ridge vent

>2000~ II I~., ,

Louvers --------..J :, ,I I

(11/ (( (tLjll ~ I (Ill ~(( (11

I Llnterbeam -r;; .area

h

777l (( (I (( (1/ I (( II (Ill ((.' (

6000

s s 50004 (see Clause 2.8.3.5 (a»

E Detector on beamE 4000 -f----r--------------gI

I

II ',

NOTE 1X =10 200 for point -type detectorX =14 000 for beam-type detectorsY =distance in accordance with Figure 8

Xmax. Xmax.

(i) Board ridge vent

f0-B 3000[ijI

~ 2000::J[ijo

1000

1(see

Clause2.8.3.5 (d»

3 (see Clause 2.8.3.5 (b) and (c»

lnterbeam areas I Detector on beam

2 (see Clause 2.8.3.5 (e»

Normal spacing

NOTE 2Infrared scans of a building have shown heat pockets at apices of roof structures due to solar radiation.Therefore, to obtain fire detection, the detectors must be located below these pockets.

100 200 300 400 500 600 700 800 900 1000

BEAM DEPTH (d). mm

Dimensions in millimetresFigure 9 - Design criteria for point-type smoke detectors in structures with deep beams

Figure 7 (in part) Design criteria for point-type and beam-type smoke detectors locatedat apex of ceiling or roof

42 43

Page 24: CP 10 2005

CP 10: 2005

2.9.4 Fixing of detectors

bl ort so that vibration or shocks will not cause spuriousI b ..dly fixed to a sta e supp .

Detectors shal e.ng~ f th detector leading to loss of protection.alarm signals or misalignment 0 e

I~I

I

I

! I

I

Suitable additional protection for the cable shall be provided at any point where they are likely to besubjected to mechanical damage.

Section Three - Installation and maintenance

3.1 Installation

PVC insulated non-sheathed cable shall be laid in metal conduit complying with SS 504 or metaltrunking complying to SS 249, exclusive to the fire alarm system. The cable shall comply with therequirements of SS 358. Rigid PVC conduits and fittings may be used in situations where the ambienttemperature is below 60 QC. Suitable additional protection for the conduits shall be provided at anypoint where they are likely to be subjected to mechanical damage.

CP 10 : 2005

3.1.1 General

45

Wiring for fire alarm system shall comply with the requirements stipulated in this Code. All other wiringshall be installed in accordance with the appropriate provisions of SS CP 5, except as stipulated by3.1.2 to 3.1.7.

,If a common duct or trunking is to be used to contain both fire alarm circuits and those of any otherservices, the fire alarm circuits shall be wired in fire resistant cable. Alternatively they may be wired inPVC insulated cable provided they are separated from the cables of other services by a rigid andcontinuous partition of non-combustible material affording them complete enclosure when the coversof the duct or trunking are in place.

Particular attention should be given to the protection and segregation of the fire alarm system fromother systems. If fibre optics are used in the fire alarm system, then approval by the relevant authorityis required.

3.1.2 Cables and wiring

Cables insulated with general purpose PVC shall not be installed in any situation where the sustainedambient air temperature is liable to exceed 65 QC for long periods. If such situations cannot beavoided, cables having heat resistant PVC insulation complying with the requirements of SS 299 shallbe used.

Cables laid underground shall be run in ducts. PVC insulated and sheathed cable conforming to therequirements of IEC 60227-4 shall be used. Cables laid direct in the ground shall be PVC insulatedand sheathed, armoured and sheathed overall.

Any telephone-type cable should be allowed for use in the wiring between the fire alarm panel and therepeater or mimic panel for secondary indication and shall be protected against mechanical damageby the use of conduit or trunking.

All cable conductors shall be sized to comply with the requirements of the relevant SingaporeStandard(s).

3.1.3 Conductor sizing

In selecting conductor sizes, regard should be paid to physical strength and to limitations imposed byvoltage drop. Voltage drop across a cable should not be such as to prevent devices from operatingwithin their specification limits, even under minimum supply and maximum load conditions.Consideration should be given to any possible extensions to the system.

Flame detection systems

2.9.5 Detector lenses. h fI e radiation is received shall be appropriately designed

Lenses of flame detectors through WhlCt ame placed in environments likely to lead to the build-up offor the coverage required. Wh~re debteffic ors ar purging eqUipment shall be fitted to ensure that the

. the lens appropnate a es orparticles, on s'lt',vity i~ retained between service periods.detector s sen

2.9.6 Outdoor applications

f th eatherproof type. They shall be fixed and supported sot d outdoors shall be 0 e wDetectors moun e

l. ble to movement due to wind or other causes.

that they are not ,a44

2.9.2 Stability and sensitivity

h th t incorrect operation does not occur as aThe stability and sensitivity of detectodr:> St.hO~ld bea~~~Ciall~ght sources or steady infrared sources, orresult of extraneous natural light or ra la Ion romof variations in ambient temperature.

NOTE _ Regarding use in special situafions, refer to 2.1.3.

2.9.3 Spacing and location of detectors

. t t the radiation emitted from flame. Accordingly,Flame detectors do not rely on convection, but ~et~~ are not in any case, affected by stratification.they do not need to be mounted on ceilings, an Y their distance from the fire increases, as theTheir sensitivity to a fire does decrease, ~owever: as ortion to the square of the distance from ItSintensity of the radiation decreases appro~,mateIY ~n t~f relatively low level within a hign space tosource. On t~e .other hand't they ~~yve~ p~eoc~~d~ early detection of a shielded fire.maximise senSitiVity to a fire a groun e ,

Detectors shall be spaced to ensure that the risk areas are protected with a minimum of shadowing or

blind spots.

. f fI d tectors should be within maximum limits specified by the manufacturer.Spacing 0 ame e

. . neral area/special hazard(s) protection, there should be aWhere flame. detectors are Inte~ded to pr~(~d)~:n the protected area and one or more flame detectors.clear line of Sight between all pOlnts/hazar

2.9.1 General. I t in which flame-responsive

The design installation and maintenance of automatic fre ~:': ~Y;n~~sand 2 in so far as they aredetectors a~e used as a fire warn~ng system shall comp y WI ec I ,applicable and appropriate, and With this clause.

. . . . . b fi e Both types usedetect the infrared and/or ultraviolet radiation that IS emitted y am .

Fla~~ detectorts cells that "see" fire either directly or through built-in lenses or reflectors.radlatlon-sensl Ive .

fi h t ristics such as flicker, sizeInfrared flame detectors are usually designed to rTespon? :~ndae~~~ ~~~~o~r use can be designed to

th one specific radiation frequency. ypes In . ror more an 'fi 'nfrared frequency bands that are not characteristic of solar radla Ion.respond to specI IC I

. . th th t the ozone layer filters out of solarUltraviolet flame detectors normally operate Within wla

lveleng ~ t a unlight and may generally be used

radiation. Hence, ultraviolet detectors do not norma y respon 0 soutdoors.

2.9

Page 25: CP 10 2005

3.4.3 RegUlar testing and inspection

3.4.3.1 General

Record the false alarm in theId'og recor and Inform the organisation responsible for servicing.

If one detector or group of detectors gives false alfor servicing ~!,ould be informed and required to inv:~~;a~::eatedlY then the organisation responsible

Any installations, detectors or detector I r ..special investigation. oca Ions having higher false alarm rates should be subject to

(c)

The details of any service call shall be entered in t . "reference. The alarm monitoring station and he iog record which shall be provided for convenientany portion of a system is isolated for m~~ter or owne~'srepr~sentativeare to be notified whenreconnected. enance an likeWise notified when this portion is

Operating instruction comprising EVACUATE, ALARM SILENCERESET should be proVided prominently at the fire aiarm panel. ' FAULT SILENCE & SYSTEM

3.4.2 False alarm

False alarms can be a major hazard to any fire alarm .the system. It is important that any alarm from th srte~ since they lead to a loss of confidence inproved to be false, rather than being treated as f ~yS e~1 e treated as an alarm of fire until it can bebeen found to be false, the following immediate aat~e un ~ proven to be a fire. Where an alarm hasa person to whom he has delegated this duty: c Ions s ould be taken by the responsible person or

(a) Where possible, identify the particular dete t ..detectors having individual indicators are in ~~~ o~ call pOln! which has initiated the alarm. Ifand hence it is important that the detect ' ny indications Will be cancelled by resetting

ors are examined before the system is reset. '

(b) Where possible, establish the cause of the fal I . .the alarm would have been lost in the ope r se a arm: It IS pOSSible that the actual cause ofrecord should be kept of any events or ~~tl07-S resulling from the alarm. Where this is so aalarm. IVI les near the detector immediately prior to the

47

CP 10: 2005

It is the responsibility of the owner of the rotected bG; .measures to prevent activation of the def t Idlng to prevent false alarms, by taking adequatecooking, exhaust fumes, etc. ec ~rs caused by cutting, weiding, sawing, smoking, heating,

It is the responsibility of the owner of the rotected .. .accordance with the requirements specifi~d in this ~~~dIn9 to ensure that the Installation is tested inreqUired by the relevant authority. The tests should be ~oand with any additional tes!s which may beresponsible for the maintenance of the installati d 11 nducted by the owner or his representativelog record as prescribed in 2 2 11 and k on

ladn a results of the tests should be entered in the

appropriate. . . ac nowe ged by the owner and/or his representative as

It is important to ensure that regular testin and . . .The occupants of the premises should begn rfi ~e~,clng operations do not result in a false alarmsounders being operated. 0 I le 0 any test of the system that may result in th~

3.4.3.2 Daily check

A check should be made every day to ascert i 'f .should be recorded and steps taken immedia~e~ 't the system IS operating normally. Fault(s) detectedy 0 ensure that the fault(s) is rectified.

----------".,.~

To ensure continuous reliability of the system, the owner or owner's representative should establish anagreement to carry out regular maintenance of the installation with the manufacturer or manufacturer'srepresentative or a competent contractor. The arrangements for maintenance should be such as willensure that a qualified person is available on call at all times to provide service in the event of any faultthat developS at the installation. The name and telephone number of the servicing organisation shouldbe prominently displayed at the control and indicating equipment. Where a service contract cannot bearranged, the owner or owner's representative with suitable experience of fire alarm system andspecial training with the manufacturers, suppliers or contractors should carry out simple servicing.However, he should be instructed not to attempt to exceed the scope of such training.

3.4.1 General

operation and maintenance manuals and "as installed" drawings of the complete installation includinga single-line diagram of the system, the fire alarm panel layout and the positions of the detectors andalarm zones should be provided to the user before a final inspection is made.

3.2 Operation and maintenance manuals and "as installed" drawings

The mains feed to the power supply equipment of the fire alarm system shall be segregated from thewiring of all other services and also from all other circuits of the fire alarm system.

The wiring of the fire alarm system shall be kept separate and distinct from the wiring of any otherservices. Except in common duct or trunking as provided for in 3.1.2, fire alarm wiring shall be spacedat least 50 mm away from the wiring of any other service. Where crossings are unavoidable, however,a bridge of suitable non-combustible insulating material at least 6 mm thick shall be securely fitted atthe crossing. In no case shall the fire alarm equipment or connections be mounted in or on boxes,cover plates or blocks carrying accessories of connections of any other service unless effectively

separated by means of strong and rigidly fixed covering or partitions.

3.1.7 Separation from other systems

Provision shall be made to prevent contact between live parts (including terminals) and the ceiling onwhich the detector is mounted. The loop-in system of wiring shall be observed throughout.

3.3 Symbols

3.1.6 Mounting of detectors

Symbols as shown in Annex B shall be used on all drawings relevant to the fire alarm systems.

3.4 Maintenance

46

Joints and terminations shall only be made in a suitable terminal box.

A loop-in system of wiring shall be used for parallel connected detectors, call points and sounders etc;each incoming and outgoing conductor of the same potential shall be connected to the appropriate

terminal provided.

3.1.5 Joints and terminations

3.1.4 Protection against electromagnetic interference

In order to minimise equipment damage and false alarms, equipment (including cabling) should not besited in places likely to have high levels of electromagnetic interference. Adequate electromagnetic

protection should be provided if such an arrangement could not be achieved.

CP 10: 2005

Page 26: CP 10 2005

CP 10: 2005

III,

'I"

11'!lj,'

II1

IJ

1,'

ill

'1'"

Visually inspect the condition of components, terminations and cables.

Ensure that faUlty parts are satisfactorily replaced and recorded. Enter in the log record anyfault(s) that requires repair.

Check that all switches are returned to their operating positions after the test.

Enter the test results and follow-up actions, if any, in the log record.

CP 10: 2005

The maintenance personnel should arrange to check the operation of at least 20 percent ofthe detectors In an Installalton each year. The selection of detectors to be tested should be~pread over as many zones as possible and should be made in such a way that all detectorsIn an installation should have been checked at least once in 5 years.

The checking of the detectors should take the form of in situ testing to ensure it is operational.

Circuits connecting ancillary equipment which require automatic voltage regulated suppliesshould be checked to ensure correct operation and voltage output.

Where the heat-sensitive element of thermal detectors or the enclosure of other detectors arefound to be coated with paint or any other material likely to affect the operation of thedetectors, such material should be cleaned off or if necessary, have the detector replaced.

The smoke d~tectors shall be cleaned, tested or calibrated according to the manufacturer'srecommendation.

49

The owner shall appoint a competent person to supervise and coordinate all matters in relation to thefire alarm systems. The person should be trained in operating the fire alarm system effectively.

When a ~ignal is. annunciated on the fire alarm panels, fire or non-fire, the person should be capableof analySing and interpreting the Signal correctly and taking appropriate actions.

In a false .alarm or other fault annunciation, the source of the false alarm or fault signal shall be madeavailable. In a log record. Recommendations to prevent recurrence of such events should also beIncluded In the log record. .

The person shall. also be responsible for keeping all the log records on routine preventivemaintenance, repair and alteration works carried out on the systems.

.

(e)

3.5 Operations

(c)

(d)

(b)

(k)

(I)

(a)

(m)

The annual test should consist of all the inspection and testing procedures specified in 3.4.3.4 and thefollOWing:

(n) Enter the test results and follow-up actions, if any, in the log record.

3.4.3.5 Annual test

48

Check operation of all alarm sounders.

Check and confirm the battery monitoring function is operational.

Test the system under the failure of electrical suppiy to the fire alarm panel to confirm it isoperational (see 2.2.5 (e), 2.2.5(f), 2.3.3 and 2.3.4).

Simulate fire alarm conditions and check the output signals available to initiate the remoteauxiliary functions that is required to be in operation in the event of fire.

Check and ensure the fire alarm panels, zone charts and all necessary indicators, printer,where applicable, are clean and in clearly visible condition.

Check to ensure that all indicating lights are operating correctly and replace if faulty.

Simulate fire and fault condition on all alarm zones to ensure it is operational. Confirm withthe monitoring station that the fire alarm and fault signals have been received.

Check charger voltage and charging current in accordance with the manufacturer's instructions.

Check batteries and their terminals as specified by the manufacturer to ensure that they are ingood serviceable condition. Carry out measurement of the impedance of the battery.

Check condition of battery cabinet for corrosion and ensure that batteries are stored in a

secure condition.

Carry out a simulation & transmission of fire alarm and fault signals to the monitoring station

and confirm it is functioning correctly;

NOTE _ It will be necessary to contact the monitoring station prior to the transmitti~g ofthe simulatedfire alarm and fault signals to inform them of the test and alsoJo check with the momto,,~g station aftercompletion of the test to ensure the fire alarm and fault signals were received and to adVise them whenthe system has been normalised.

(i)

(f)

(g)

(h)

(e)

(d)

(b)

(c)

(a)

3.4.3.4 Monthly test

In addition to the weekly test specified above, the following checking and testing procedures should be

carried out each month:

(b) Check the battery voltage and conditions;

(c) On completion of the test, take corrective action immediately on any abnormality or fault(s)

encountered within the system;

(d) Enter the test result(s) and follow-up actions, if any, in the log record.

(a)

The following tests and checks should be made every week:

3.4.3.3 Weekly test

If a fault is detected, the responsible person should ensure that the following actions are taken:

(a) Determine the area affected by the fault and decide whether special action (such as fire

patrols) are needed in that area;

(b) If possible, determine the cause of the fault, or note the activities immediately prior to the fault

in the area affected;

(c) Enter the fault in the log record, inform the organisation responsible for servicing and arrange

for repair.

Page 27: CP 10 2005

CP 10: 2005

A.2.1 Choice of fire detectors

"1

i

l

'.!;1

'111'1

"

'I'

I

I

!I

il!

1

I

I'I!1

1,

I1 :'I

d

.

1'1

1

'.

I'I

1'1

1I

51

Aesthetics (aspirating pipe work might be run in floor voids, with a capillary tube sampling airfrom the space below via a small hole drilled in the ceiling);

Height of the space (the high sensitiVity of some aspirating systems, coupled with thepossibi!ity of running p!pe work vertically on walls and storage racks, can provide enhancedprotectIon compared with POint smoke detectors mounted at high level);

Temperature of the space (e.g. in cold stores, the detector can be located outside the space,so that it is not directly exposed to low temperature).

In any automatic fire detection system, the detector has to discriminate between a fire and the normalconditions existing within the building. The system chosen should have detectors that are suited tothese conditions and provide the earliest reliable warning. Each type of detector responds at adifferent rate to different kinds of fire. With a slowly developing smouldering fire such as the initialstages of a fire involving cardboard, a smoke detector would probably be activated first. A fire thatevolves heat rapidly and with very little smoke could activate a heat detector before a smoke detector.With a flammable liquid fire, a flame detector could be activated first.

Aspirating smoke detection systems are also used, sometimes, to protect spaces in which point-typesmoke detectors would present difficulties on the basis of:

In general: smoke detectors give appreciably faster responses than heat detectors, but may be moreliable to give false alarms, so care must be taken in their selection and location. Where there areproductions or other processes that produce smoke, fumes, dust, etc., which might activate smokedetectors, an appropriate type of fire detector should be used.

If detectors are installed for the protection of a room's occupants and have a direct effect on theirescape routes, smoke detectors should be used. If detectors are installed in order to give warning offire before it spreads to other areas of the building, then either smoke or heat detectors may be used.

Heat and smoke detectors rely on the transport of products from the fire to the detector by convection.The plume above a fire is relatively narrow, and in general these detectors rely on the presence of aceiling (or other similar near-horizontal surface) to direct the products outwards from the plume to thedetectors. Heat and smoke detectors are therefore suitable for use in most buildings, but aregenerally unsuitable for complete open-air applications.

'"~adiation (flame) detectors are particularly suited to outside applications, where there is no ceiling todirect the products outwards. They are especially suited to risks in which smouldering is unlikely (suchas in liquid fuels). Flame detectors in bUildings"are mainly suitable for supplementing heat and smokedetectms in high ceiling compartments, provided that an unobstructed view is possible, and for specialapplications such as outdoor storage and chemical processes employing flammable liquids.

Aspirating smoke detection systems commonly incorporate a detector of much higher sensitivity thanpoint or optical beam smoke detectors. Such "high sensitivity aspirating detection systems" are oftenused to protect critical electronic equipment rooms, in which even a very small fire can result inunacceptable damage.

The lik~ly fire behaviour of the contents of each part of the building, the processes taking place, andthe deSign of the bUilding should be considered. The susceptibility of the contents to heat, smoke, andwater damage should also be considered.

No ~ne type of detector is the most suitable for all applications and the final choice will depend onIndividual circumstances. In some premises, it may be useful to combine different types of detectorsto achieve the best results.

combustion gas (such as carbon monoxide)

infrared or ultraviolet radiation.

In some fire detection systems, a fire signal is initiated when the characteristic reaches a pre­determined threshold. A signal may, instead or in addition, be initiated when the rate-of-change of thecharacteristic is representative of a fire.

Explosive or flammable atmospheres require special suppression systems automatically actuated bythe detection system.

Premises where people sleep require different criteria for the selection of the detection and alarmsystem from those for premises where occupants are continuousiy supervising the area.

In multi-sensor fire detectors, each detector contains more than one sensor and thus monitors morethan one of the characteristic fire phenomena (e.g. heat and smoke). By analysis of the signalsreceived from the sensors, potentiai response to phenomena other than fire can be reduced while stillproviding an adequate response to fire.

A fire detection instaliation is intended to enable a fire to be detected at a sufficiently early stage sothat people who are at risk can be made safe either by escaping from the fire, or by the fire beingextinguished (also to prevent extensive property damage). Neither of these measures can be useduntil people are made aware of the fire.

The effectiveness of the fire detection and alarm system depends on the stage of the fire at which it isoperated. In order for all the occupants to escape without too much difficulty, an early alarm shouldoperate before the escape routes becomes smoke-logged to such an extent as will cause occupantsto have difficulty finding their way out of the building.

50

Fire detectors are designed to detect one or more of the four characteristics of a fire, namely:

In the case of point detectors, the characteristic is detected at a defined point(s) within the protectedarea. In contrast, "line" detectors are capable of detecting the characteristic along a defined line withinthe protected space. In an "integrating line detector", the effect of the characteristic on the detector isintegrated along the line. In a "non-integrating line detector", this is not the case, and the detectorbehaves, effectively, as though it comprises an infinite number of point detectors arranged along theline.

Guidance for the selection of detectors(Informative)

AnnexA

smoke

heat

A.2 General notes on detectors

These recommendations should be applied with due regard to the attributes of each type of detectorand its prime function for life safety and protection.

A.1 Introduction

CP 10 : 2005

Page 28: CP 10 2005

52

u

53

CP 10 : 2005

Heat detectors with rate-of-rise elements .vary siowly, while fixed tem t are more sUitable Where ambient telikely to fluctuate rapidly ove~:~~rture dedtectors are more suitable where the a~~rernattutres are low orpeno s. emperature IS

It must be appreciated that a rate-of-rise detector .

~~;or~in:~:.~~::~:r~~u~:te~fo~s ~~~~~~h of t its f:~liI~~s~~n~:~s:e r~~~~e~ncc~eo:::: ~~n~~ns fatsterprotection of areas. ra e-o -nse and fixed-temperature is f pera ure.. pre erred for general

Where enVironmental conditions of a b 'Id'?wing to normally occurring ra id' UI Ing are not conducive to the use of rat _ _.Installation of fixed-temperature ~p "~r~a~es In temperature, consideration ShoUI~ ~f nse detectorsare typical examples Where e e ec ors to reduce the incidence of false e given to thefurnaces, kitchens, cold-roomsS~~hthrtemperature variations can be expected' a~aOrlm'esr' The follOWing

, ooms, and laundries. . rooms, above

A.4 Smoke detectors

A.4.1 General

There are two smoke sensing principles commonly used for smoke detectors as follows'

(a) Ionization chamber type Which t .ch b opera es on the chang .am er upon entry of smoke particles. e In current flOWing through an ionisation

(b) Optical type Which operates on th .light beam. e scattenng or absorption of light by smoke rt· I .pa Ices In a

There are single-point and multi ointbased on optical or ionisation princiPI~s~tectors that detect smoke at one or more positions and may be

Duct sampling units draw air from within the duct to p . t t. . ._ OIn - ype smoke detectors.

MultrpOlnt aspirating smoke detepipe network. The sen . ctors sampleair from the protected area t

~~~~~:; ~~rti~les. H~IC:S'~~I~:~g~e~h:o~~:ryn~~~~:~~i~Vi% and/esponds

o

t~ ~~~~~nd~~~~o~~~k:sensitivity I e design tools are commonly used to deterr::. air rom specific. locations as required.

. Ine correct holes size and sampling point

Optical beam sm k dbea 0 e etectors are effectively Iin d tbetw':e~e~~~t~~sd ~~7dal~o detect thermal turbule~cee~yC~C:~a~~~~n;f ~~o~scuration principl:s. Some

air. eam at turbulent Interfaces

Ionisation chamber smokproduced in clea . e detectors respond quickly to smoke . .particles which ~ bUr~Ing fires, but may respond slOWly to oPtic~~~t~lnIng small particles normallysmoulde~ing produ: . e. jr~dUCed by smouldering materials Certai~nset~oke containing large

maIn y arge particles to which ionisation det t ma enals, e.g. PVC, whenOptical ec ors are less sensitive.d smoke detectors respond . kletectors have SUfficiently wid qUlc y to smoke that is optically dense B th

e ranges of response for general use. . 0 optical and ionisation

A.4.2 Application

A4.2.1 General

Operation of all typchamber or r es of smoke detectors depends on co .detectors Ight beam. Where SUfficient concentration' mbustlon Prod~cts. entering the sensing-hot fire Wil~~ .usually mounted on the ceiling response t!S pr~sent, operation IS obtained. Since theheat, ther f nve th: combustion products up'to the ceil' Ime ~pends upon the nature of the fire. A

e ore the time for smoke to reach the detect InlglbraPldlY. A smouldering fire produces little

or WI e Increased.

Ambient conditions such as heat, smoke or fiame from cooking or work processes, fumesfrom engine exhaust, or high air velocities due to strong winds outside the building;

(b)

(g) The build-up of dust or dirt within a detector, or the entry of insects;

(f) Inadequate maintenance and servicing;

(e) Electrical transients or radio interference;

(d) Communication faults arising from servicing or testing work carried out without priornotification to the alarm monitoring station;

A.3.1 General

(c) Work being carried out in a protected area without knowledge of, or in neglect of, thenecessary precautions;

(i) Accidental or malicious activation of manual call points or detectors;

A.3 Heat detectors

G> Changes of outdoor environmental conditions e.g. temperature, relative humidity.

(h) Change of use or changes within the building;

Heat detectors are in general, less sensitive than smoke detectors. They are unlikely to respond tosmouldering fires, and as a simple rule of thumb, wlll require the flames from the fire to reach aboutone-third of the distance to the ceiling before they wlll operate. They are therefore not suitable for theprotection of places where unacceptable losses could be caused by small fires, e.g. in computer rooms.

There are two main forms of heat-sensitive detector. One is the "poinf' type of detector which isaffected by the hot gas layer immediately adjacent to it. The other is the "line" type of detector which issensitive to the heat effect produced along any portion of the detector line.

Point-type heat detectors are generally suitable for use in most buildings. Line-type heat detectorsmay be particularly suitable for protecting items of plant or cabling. When used for these purposes,the detector should be mounted as close as possible to the place where fire or overheating mightoccur, and be either mounted above the risk or in contact with it.

Installations, detectors or detector locations having higher false alarm rates should be subject tospecial investigation.

(a) Mechanical and electrical faults, often resulting from the effects of vibration, impact orcorrosion;

It is essential that utmost care should be taken by system designers, installers and users to reduce theincidence of false alarms. Common cause of false alarms include the following:

A.2.2 False alarms

All fire detectors wlll respond to some extent to phenomena other than fire and therefore carefulchoice of detectors and their location is essential.

For aspirating systems, specialist application guidance needs to be sought from the manufacturer.

The choice of fire detector may also be affected by the environmental conditions within the premises.In general, heat detectors have greater resistance to adverse environmental conditions than other

types.

CP 10: 2005

Page 29: CP 10 2005

CP 10 : 2005

The optical beam smoke detector will respond when the light path at the receiver is interrupted orobscured. It is important therefore that the light path be kept clear of obstacles at all times.

Smoke detectors other than those incorporating thermal turbulence detectors do not detect fumesfrom burning alcohol and other clean burning liquids which do not produce smoke particles. This isnot a serious disadvantage because a fire will normally involve other combustible materials at an earlystage. Combined optical beam smoke detectors and thermal turbulence detectors may be suitable forsuch risk, but heat or flame detectors should also be considered.

Smoke detectors incorporating thermal turbulence detectors may be unsuitable for installationimmediately above ceiling-mounted blower heaters or industrial processes that produce appreciableheat.

Multi-sensor detectors contain more than one sensor, each of which responds to a different physicaland/or chemical characteristic of fire. The purpose of combining sensors in this way is to enhance theperformance of the system in detection of fire, or its resistance to at least certain categories of falsealarm, or both.

The method (if any) of combining the signals from each sensor varies between different proprietarymulti-sensor fire detection systems. In some such systems, there is significant potential for reductionof many types of false alarms.

Aspirating smoke detection systems are suitable for applications where a very high sensitivity isdesirable. They are also suitable for large areas where smoke detection is required at high andnormal sensitivity levels. However, where a large area is covered the precise location of the smokesensed cannot be determined.

A.4.2.2 Location considerations

Location of smoke detectors should result from an evaluation based upon engineering judgement orfield test. Ceiling shape and surfaces, ceiling height, configuration of contents, burning characteristicsand ventilation are some of the factors that must be considered.

CP 10 : 2005

For atria type constructions, smoke beams at several levels may be necessary because ofstratification (see A.4.2A). Natural or forced ventilation assists the smoke reaching detectors at highceiling levels (see AA.2.5).

A.4.2.4 Stratification

As mentioned in AA.2.3, smoke is driven upwards by the heat from the fire source.

Smoke released from slow burning or small fires may not be hot enough to penetrate the normallyheated air which collects at the ceiling. This is especially true in warehouses with metal roofs. Duringthe day, the air under the roof is heated by the sun and a thermal barrier exists which prevents thewarm combustion products from reaching the ceiling. The smoke will then stratify at a level whichprevents the warm combustion products from reaching the ceiling. The smoke will then stratify at alevel beneath the ceiling. Generally at night this condition will not exist. Proper protection may requiredetectors at two levels; one group at the ceiling level and another at some distance below the ceiling.

A.4.2.5 Airflow

Smoke can be diluted by airflow caused by updraughts, open windows, forced ventilating systems orair-conditioning systems.

It may be necessary to conduct air circulation observation tests in a room to ensure proper placementof detectors.

For air-conditioned facilities and others where forced ventilation is present, it is good practice to takeadvantage of air currents to transport smoke to a detector. However, in such situations, smokedilution and high airflow may cause the detector to respond slowly.

The effects of airflow on the detector and the movement of smoke where detectors are installed nearair ducts and in air-conditioned rooms may in some cases require repositioning of the detector.

A.4.2.6 Special environmental considerations

In extreme environments the selection of smoke detectors shouid be confined to those capable ofwithstanding the environmental conditions.

A.4.2.3 Ceiling surfaces

As mentioned in A.4.2.2, the ceiling surface is one of the factors that must be considered before thelocations of smoke detectors are established.

Some typical ceiling surfaces where the use of smoke detectors should be evaluated are as follows:

The location of smoke detectors should be determined taking into consideration the specialenvironments where false activation or non-activati~n is likely.

Some typical environments where the use of smoke detectors should be carefully evaluated are asfollows:

(a) Smooth ceilings. Heated air and smoke usually rise. When they reach smooth ceilings, theytravel along the ceiling. As these products flow along the ceiling, their concentrationdecreases as the distance from the source increases.

(a)

(b)

(c)

Areas where gases may be present from exhausts and normal manufacturing processes;

In kitchens, bathrooms, and other areas subject to cooking fumes and vapours;

Near openings, such as doors, windows, or other inlets, where the introduction of outsideindustrial gases or products of combustion may be possible;

(c)

(b) Other ceilings. Where deep beams or other obstructions form pockets in the ceiling, theproducts collect in the pocket and, if sufficient products are being generated, will eventually"spill over" into adjacent pockets.

Sawtooth, sloping, open joist, beam construction, or other shaped ceilings must receivespecial consideration as smoke usually travels in a longitudinal direction at the highest point.

High ceilings. As smoke rises from a fire, it tend~ to spread up~ards in th~ gener~l form of aninverted cone. Therefore the concentration within the cone vanes approximately Inversely asthe square of the distance from the source.

In high ceilings, such as high rack storage warehouses, it may be necessary to install de!ectors atmore than one level to take advantage of the higher concentrations near the floor to provide fasterresponse.

54

(d)

(e)

(f)

(g)

(h)

In areas where the detector is subject to movement and excessive vibration, in particularwhere beam detectors are used;

In dusty areas or in areas where particulate matter, such as aerosols, could enter the detector;

Areas where high concentrations of tobacco smoke are expected;

In areas where steam or condensation vapour is expected;

In the vicinity of certain materials, such as polyvinyl chloride (PVC), which during smoulderingproduce mainly large particles to which optical detectors are more responsive.

55

Page 30: CP 10 2005

CP 10: 2005 CP 10 : 2005

A.5 Flame detectors A.5.4 Field of view considerations

A.5.1 Flame characteristics

Flames from most fire sources emit electromagnetic radiation which includes an ultravioletcomponent, visible light, and infrared radiation in various intensities characteristic of each particularsource. Flames from sources such as petrol and oil tend to generate greater quantities of infraredradiation, whereas gas flames and solvents such as methylated spirits have a much higher ultravioletcomponent. Other sources, particulariy sunlight and building lighting, generate radiation in the sameparts of the spectrum and therefore flame detectors must be selected to discriminate flame from otherradiation sources.

A.5.2 Detector characteristics

Flame (radiation) detectors are sensitive to radiation that travels from the fire to the detector innegligible time irrespective of distance. They may be of the ultraviolet or infrared type and respondwhen the radiant energy in their respective sensing band exceeds a preset threshold. The amount ofradiation received by the detector will be reduced, and the response time of the detector may beincreased, with increased distance from the fire. A clear line of sight to the protected area is desirable,although reflected radiation, e.g. by mirrors, may actuate a detector with reduced sensitivity.

The distance from the seat of the fire to the detectors influences radiation intensity. The intensity ofthe radiation striking the detector decreases by the square of the distance from the seat of the fire.This means that if this distance is doubled, the intensity of the fire must be four times greater in orderto activate an alarm.

Flame detectors are essentially "line of sighf' devices which can sense the presence of flames in a setfield of view. This field is generally described (see Figure A1) by the cone of vision angle and themaximum perpendicular sensitivity in metres, although other considerations are important.

Where a flame detector is placed at a fixed height above the floor, then a protected area, within whicha particular fire size will be detected, can be determined from the manufacturer's data (see Figure A2).

The aim of designers should be to provide full coverage of the area to be protected with maximummultiple coverage to account for obstructions in the line of sight of some detectors

Figure A3 shows a typical layout of four flame detectors protecting an aircraft hangar with multiplecoverage.

A.5.5 Spurious alarms

There are a number of sources of radiation which occur in installations for which some measures ofprotection must be taken to prevent spurious alarms.

For ultraviolet flame detectors, potential sources of spurious alarm include the following:

(a) Lightning, electric arcs;

(b) Cutting and welding operations;

In order to discriminate flames from other sources, many infrared flame detectors operate on the"fiicker principle" Le. they have a filter which only allows them to respond to radiation pulsing around acentral frequency of 5 Hz to 15 Hz which is characteristic of many types of flames.

(c)

(d)

Ultraviolet lamps;

Quartz halogen lamps.

Ultraviolet flame detectors mostly discriminate flames from sunlight by sensing only radiation atwavelengths between 185 nm and 270 nm which is outside the solar spectrum.

A.5.3 Selection

Flame detectors should be chosen for applications where there is the likelihood of rapid flamedevelopment so that an alarm can be raised before products of combustion or heat would havereached smoke detectors or heat detectors. Combinations UV/IR, IRlIR and IR

3detectors can be

used to reduce or eliminate the potential for spurious alarms in applications where UV or IR detectorsmay experience problems.

The choice of infrared or ultraviolet detectors or some combination will depend on the typical radiationfrom the expected fire hazard and the presence of false alarm sources in the vicinity. For example inaircraft maintenance hangars where aviation kerosene is a strong infrared source and welding,lightning and non-destructive inspection, are potential ultraviolet spurious alarm sources, infrareddetectors would be appropriate. However, if potential infrared spurious alarm sources such as highfrequency radio transmission equipment and running aircraft auxiliary power units are present in thehanger, then a combination of UVIIR detector would be more appropriate. Similarly, for a storecontaining solvents which burn cleanly, with a low infrared radiation component, and which is lit byincandescent lamps (good infrared source), ultraviolet detectors should be selected. The environmentin which the detector is to be installed would also influence the choice, e.g. contamination of lenses.

Other typical applications of flame detectors are storage tanks and pipework containing flammableliquids, chemical processes, and large open warehouses.

56

Where ultraviolet detectors must be used in these environments, appropriate shielding must be fittedto prevent the non-flame ultraviolet radiation falling on the detector or combination UVIIR detectorsmay be considered. -'

For infrared flame detectors, potential sources of sp~rious alarm include the following:

(a) Very hot objects;

(b) Ovens/furnaces;

(c) Sunlight;

(d) Incandescent lamps.

Most infrared flame .detect?rs use the fiicker principle and/or narrow band optical filter to guard againstthese sources, but, If rotation of a fan or motor or rippling on a liqUid surface causes radiation from thesource to flicker at the same frequency as a flame, a spurious alarm may occur.

Some flame detectors are fitted with a time delay to eliminate the effects of short-term transientsignals. Howev~r, where detectors are. u~ed to actuate extinguishing or high-speed suppressionsystems, these time delays should be eliminated or reduced considerably. An alternative is to usedual sensor operation whereby both sensors must detect the presence of flames before thesuppression system is activated.

57

Page 31: CP 10 2005

CP 10 : 2005

Field of view

Distance

1IiI

Maximum perpendicularsensitivity (metres)

CP 10 : 2005

Annex B

Fire alarm symbols

The following symbols are those which are in common use to indicate on drawings the various itemsof equipment:

I SAP I

I MAP I

I RP I

Sub alarm panel

Main alarm panel

Repeater panel

et

Heat detector in concealedunde~fioorspaCeS(Nmel)

Heat detector in ceiling or roof spaces(Note 1)

Heat detector (exposed or surfacemounted) (Note 1)

Angle+90·

~L_-:::-c-;:1---Coneof vision

_90·

Flame detector

Figure A1 - Typical field of view of flame detectorSmoke detector (exposed or surfacemounted) (Note 2) @ Mimic panel

Figure A2 - Typical floor area protected by one flame detector

//

Flame Detector

Cone of vision

Detector aiming point

--""<,.-----Horizontalfield of view

Smoke detector in ceiling or roofspaces (Note 2)

Smoke detector in concealed under­fioor spaces (Note 2)

Smoke detector with sampling device(Note 2)

Remote visual indicator

Smoke detector (beam-type)

Flame detector (Note 3)

@B

Manual call point

Batteries

/Fire alarm bell

Electromagnetic doorholder

Pressure switch

Flow switch

oI BAT I

PS I

FS I

NOTE 1 - If other than Type A, indicate Type S, C, D or E.NOTE 2 - Indicate Type of Smoke detector, e.g. I =Ionization, P = Photo-electric I opticalNOTE 3 - Indicate Type of Flame detector, e.g. UV, IR, UV/IR.

-L-Linear heat detectorEOlEnd of line device

Smoke sampling system(X= sampling point)

~ 4 Detector coverage

~ 1 Detector coverage

f-?JI 2 Detector coverage

ffi]ill 3 Detector coverageDetector

Figure A3 - Multiple coverage provided by four flame detectors

58 59

Page 32: CP 10 2005

CP 10 : 2005CP 10: 2005

Annex C Weekly/monthly/annual test report

61

• Delete if not applicable+ Tick if satisfactory; put '>c' if unsatisfactory and give explanation under the remarks space.

TIME: _

DATE: _

Tester's Name _

I HEREBY CERTIFY THAT THE ABOVE TESTSHAVE BEEN CARRIED OUT

Signatute, _

Signature, _

Owner's Name, _

OWNER : _

LOCATION : _

TYPE OF TEST : WEEKLY/MONTHLY/ANNUAL'

REMARKS: _

ALARM ZONE NUMBER

THERMAL ALARM TEST

FAULT TEST

ISOLATION

SMOKE ALARM TEST

DEVICES+ FAULT TEST

ISOLATION

FLAME ALARM TEST

FAULT TEST

ISOLATION

MANUAL ALARM TESTCALL FAULT TESTPOINT

ISOLATION

OPERATIVE NON- REMARKSOPERATIVE

POWER SUPPLY+ MAIN SUPPLY

CHARGER

BATTERY

ALARM MONITORING ALARM TESTSTATION

FAULT TEST .ALARMS+ AND ALARM SOUNDERANCILLARY

ANCILLARY CONTROLS

60

Daily log - Records for automatic fire alarm installations

en.JetE~

0W

W ........ Wet.Jo~

0U

Z0i=uetll-:::l;:0.J.J0"-

en.Jeti=~

en -:.:::a:et:;;Wa:

"-0zoen- ........ z5!:wa:>U Wenw0

<.9zCl W.J :;;::::> i=COu.. (/)

0 (/)w ww 0::: ....

:2 Cl et« Cl 0z «

III

Page 33: CP 10 2005

CP 10: 2005

Annex D

CP 10 : 2005

Standards referred to:

Components of a fire alarm system

~ C

A Fire Alarm Signal

E - F

B Fault SignalI--

0

'[~'[~J....................

II

-

KeyA Fire detector(s);B Control and indicating equipment;C Fire alarm device(s);D Manual call point(s);E Fire service signalling transmitter;F Alarm monitoring station;G Control for automatic fire protection equipment;H Automatic fire protection equipment;I Power supply equipment.NOTE 1. Items G and H may need to be provided with a separate power supply.NOTE 2. The lines linking the various components indicate information flows, and not physical

interconnections.NOTE 3. The dotted line that link items G and H mean that these two items are optional features, which will be

included into the system having an automatic fire-extinguishing installation.

Figure D1 - The components of a typical fire alarm system

62

IEC 60227-4: 1997

CP 5: 1998

CP 13: 1999

CP 25: 1999

SS 249; 1981

SS299:-

SS358:-

SS504;-

Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V

Part 4 ; Sheathed cables for fixed wiring

Code of practice for electrical installations

Code of practice for mechanical ventilation and air-conditioning in buildings

Code of practice for emergency voice communication system In buildings

Specification for steel surface cable trunking and accessories

Specification for fire resistance cables

Part 1 : 1998 Performance requirements for cables required to maintaincircuit integrity under fire conditions

Specification for polyvinyl chloride insulated cables of rated voltages up toand including 450 / 750 V

Part 1 : 1996 General requirements

Part 2 : 1998 Test methods

Part 3 : 1996 Non-sheathed cables for fixed Wiring

Part 5 : 1998 Flexible cables (cords)

Specification for conduit systems for cable management

Part 21 : 2003 Particular requirements for rigid conduit systems

63

Page 34: CP 10 2005

CP 10: 2005

STANDARDS, PRODUCTIVITY AND INNOVATION BOARD (SPRING SINGAPORE)

SPRiNG's mission is to enhance the competitiveness of enterprises for a vibrant Singapore economy.We work to nurture a pro-business environment that encourages enterprise formation and growth,facilitate the growth of industries, enhance productivity & innovation and capabilities of enterprises,and heip increase access to markets and business opportunities. Our vision is to nurture a host ofdynamic and innovative Singapore enterprises.

Strategic Thrust 1: Nurture a pro-business environment that encourages enterprise formationand growth

SPRING takes on the role of a steward to nurture a pro-business environment. In this role, SPRINGhelps to ensure that there is a conducive environment for enterprises to form, compete and grow.SPRING promotes the review and removal of rules and regulations that stifle enterprises. It alsofacilitates enterprise access to key factor inputs like iand, labour, technoiogy and finance.

Strategic Thrust 2: Facilitate the growth of industries

SPRING adopts an integrated ciuster deveiopment approach in enhancing the vibrancy andcompetitiveness of selected industries.

Strategic Thrust 3: Enhance productivity & innovation and capabilities of enterprises

SPRING helps enterprises to enhance their productivity & innovation and capabilities. These includeeqUipping enterprises with capabilities to upgrade their know-how, and creating conditions thatencourage a productivity & innovation and service focus in enterprises. Focused assistance wili beprovided for promising enterprises.

Strategic Thrust 4: Increase access to markets and business opportunities

SPRING helps enterprises gain access to markets by reducing technical barriers to trade, providingquality assurance for Singapore products/services and linking local enterprises to businessopportunities, both locally and overseas.

SPRING Singapore2 Bukit Merah CentralSingapore 159835Tel: 6278 6666Fax: 6278 6667E-mail: [email protected]: http://www.spring.gov.sg

ABOUT THE NATIONAL STANDARDISATION PROGRAMME

SPRING is also the national standards body in Singapore. Under the national standardisationprogramme, SPRING Singapore helps companies and industry to meet international standards andconformity requirements by creating awareness of the importance of standardisation to enhancecompetitiveness and improve productivity, co-ordinating the development and use of SingaporeStandards and setting up an information infrastructure to educate companies and industry on thelatest developments.

SPRING Singapore is vested with the authority to appoint a Standards Council to advise on thepreparation, publication and promulgation of Singapore Standards and Technical References andtheir implementation.

64

CP 10: 2005

Singapore Standards are in the form of specifications for materials and products, codes of practice,methods of test, nomenclature, services, etc. The respective standards committee wili draw up thestandards before seekmg final approval from the Standards Council. To ensure adequaterepresentation of all viewpoints in the preparation of Singapore Standards, all committees appointedconsist of representatives from various interest groups which include government agencies,professional bodies, tertiary institutions and consumer, trade and manufacturing organisations.

Technical. Reference~ are iransition do~uments developed to heip meet urgent industry demand forspecifications or requirements on a particular product, process or service in an area where there is anabsence of reference standards. Unlike Singapore Standards, they are issued for comments over aperiod of two years before assessment on their suitability for approval as Singapore Standards. Allcomm~nts are considered when a technical reference is reviewed at the end of two years todetermine the feasibility of its transition to a Singapore Standard. Technical References can thereforebecome Singapore Standards after two years, continue as Technical References for furthercomments or be withdrawn.

In the international arena, SPRING Singapore represents Singapore in the International Organisationof Standardisation (ISO), the Asia-Pacific Economic Co-operation (APEC) Sub-committee forStandards and Conformance (SCSC) and in the ASEAN Consultative Committee on Standards andQuality (ACCSQ). The Singapore National Committee of the International ElectrotechnicalCommission which is supported by SPRING Singapore, represents Singapore in the IEC.