Corrosion and Odor Control in Wastewater Systems

Upload: phammien

Post on 23-Mar-2018

221 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Corrosion and Odor Control in Wastewater Systems

Page 2: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Topics to be covered Hydrogen Sulfide Formation and Consequences

What has changed since the Clean Water Act

Corrosion in Wastewater systems

Liquid Phase Odor and Corrosion control

Air Phase Odor control

An comprehensive approach to Odor and Corrosion control

Page 3: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Hydrogen Sulfide Formation and Consequences

Hydrogen Sulfide (H2S) is produced in sewer systems when dissolved oxygen is depleted and Sulfate reducing bacteria use the oxygen from Sulfate (SO4) for their metabolism. The resultant product is hydrogen sulfide.

Page 4: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Other bacteria present in the

water convert sulfates to

sulfides. This causes the rotten

egg smell, hydrogen sulfide gas

(H2S).

When the dissolved oxygen

concentration falls below 0.1

mg/l, the water becomes

septic.

H2S Gas H2S GasH2S Gas H2S Gas

pH ~ 7

D.O.<0.1 mg/l

Bacteria in the

wastewater

consume oxygen.

O2

O2 O2

Sewer

WastewaterBacteria

Page 5: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

SO42- HS- H2S

H2S Gas H2S Gas

H2S Gas

H2S H2SH2S

In water at pH 7,

about 50% of the

dissolved sulfide

converts to H2S gas.

0.00

1.00

2.00

3.00

4.00

5.00

6.00

0

200

400

600

800

1000

1200

3 4 5 6 7 8 9 10

H2S

(aq

) and H

S-

in s

olu

tion (

mg/L

)

H2 S

(g) in

air (ppm

)

pH

H2S(g)

H2S(aq)

HS-

Page 6: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

On the surfaces above

the water, H2S gas is

converted to strong

sulfuric acid by

Thiobacillus bacteria.

Acid corrosion then

dissolves the

infrastructure.

SO42- HS- H2S

H2S

Thiobacillus

+ O2 = H2SO4

Acid Attacks

Concrete

Page 7: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Collapses routinely occur

when preventable

corrosion is allowed to

continue unchecked.

SO42- HS- H2S

H2S + O2 = H2SO4

Acid Attacks

Concrete

Once rebar is exposed, the

sewer is structurally

compromised.

Page 8: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

What Has Changed Since the Clean Water Act Was Enacted??

Page 9: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Over the past 25 years,

wastewater has changed.

Page 10: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

1980 1985 1990 1995

0

10

20

0

5

10

15

D

ISS

OL

VE

D S

UL

FID

E

CO

NC

EN

TR

AT

ION

(m

g/l)

T

OT

AL

ME

TA

LS

CO

NC

EN

TR

AT

ION

(m

g/l)

DISSOLVED SULFIDE VS. TOTAL METALS HYPERION WWTP

Corrosion Threshold

Metals Sulfid

es

Courtesy of the City of Los Angeles

Page 11: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

0.00

1.00

2.00

3.00

4.00

5.00

6.00

0

200

400

600

800

1000

1200

3 4 5 6 7 8 9 10

H2S

(aq

) and H

S-

in s

olu

tion (

mg/L

)H

2 S(g

) in air (p

pm

)

pH

H2S(g)

H2S(aq)

HS-

Relationship Between Total Sulfides and Gas That Can Be Released

Page 12: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

According to the EPA, the primary reasons

sulfide levels have risen are:

• Pretreatment

• Longer Retention – FM/grav. Centralization, lower flow

plumbing

• Higher BOD - low flow plumbing, dewatering/transport

strategies

Page 13: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Corrosion in Wastewater systems

Page 14: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Sulfide odor complaints are an

indication that acid corrosion is

occurring within your system.

SO42- HS- H2S

H2S+ O2 = H2SO4

Acid Attacks

Concrete

Page 15: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

L.A.County San Districts

0.001 0.01 0.1 1.0

Corrosion Rate (in./year)

7

6

5

1

0

pH

Corr

osio

n R

ange

4

3

2

0.25

20

Years of

Life(2” of sacrificial

concrete)

100

Su

rfac

e

8

Page 16: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

When the surface pH falls below four,

sewer life cycle cost assumptions are no

longer valid.

1250%

For example, the difference in annual

cost between surface pH 4 and 2 is…

Page 17: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Consequences of H2S Related Crown Corrosion

Page 18: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Corrosion at and above the spring line

Page 19: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Headworks Corrosion at and above the water line w/liner

Page 20: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Wetwells with Liners and Air Phase units

Page 21: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Manhole Corrosion

Page 22: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Acid corrosion, not

“aging” is the primary

cause of failing sewers.SO4

2- HS- H2S

H2S + O2 = H2SO4

Acid Attacks

Concrete

Bacteria cause odor and

produce acid. Today,

this phenomenon is

much more commonly

causing sewers to have

surface pH of 2 or less.

Page 23: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

314 313

311

310 312

309

316 317 318

315

301

300 324

ODOPHOS

346 349

350

323

321 319 322

320

327

306

307 305 308

325

338

337 339 336 340

335

345

347 363 348

326

344

341

342 343

302

376 375 377 304 303

374 378 370

362

361

371

372 356

373 358

360

364 359 365

448 357

355

353 352 354

450

ODOPHOS

351

451 452 455 456

449

461

453

Pinellas County

W. E. Dunn

W R F

PS Surface pH Model

F:\users\UTLOP71\WPDOCS\SOP's\North

County PS pH Model.doc

Last saved by D Decker 4/3/2006

460

459

443

444 445

437 464

438 462

439 463

446

382 409 381

413

380 379

383

385

384

405

404

403

419

408

391

422

397

386

390

407

402

401

421

467

466 433

435

389

388

432

400

434

ODOPHOS &

BIOCUBE

393

458

395

394

396

392

406 398 411 410 440

416

399

417 415

412 457

430

431

465

468

RED 2 pH

YELLOW 3 – 4 pH

GREEN 5 – 6 pH

OUTLINE 7 pH

ODOPHOS 387

441 442 447

Oldsmar

WRF

436

414

418

420

Page 24: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Liquid Phase Odor and Corrosion control

Page 25: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Classes of Liquid Phase Treatment

Oxidizers

Metal Salts

pH Control

Hybrid Methods

Biologics

Page 26: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Oxidizers Chlorine/Sodium Hypochlorite

Aeration

Oxygen Super Saturation

Hydrogen Peroxide

Nitrate Compounds

Potassium Permanganate

Page 27: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Chlorine and Hypochlorite

Abundantly available

Can be hazardous to handle

Can be corrosive

Takes large quantities to oxidize the sulfides

Due to competing reactions may take as much as 10-15 parts by weight of chlorine to oxidize one part of sulfide

Page 28: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Aeration

Wetwell aeration

Can only raise DO to near saturation

May release sulfides and other odors in the wetwell during aeration

DO does not last long enough for effective long-term downstream odor control

Page 29: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Oxygen Supersaturation

Provides oxygen for as an oxidizer and DO source

Provides oxygen for a longer period of time in the sewer than wetwell aeration.

Requires high purity oxygen source – O2 production facility or liquid oxygen storage and vaporization facility.

Financial analysis is needed

Page 30: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Hydrogen Peroxide Effectively oxidizes Sulfides

Provides DO to wastewater

Once DO is depleted there is no more preventative power

Should be added fairly close to odor problem

Must be added at multiple locations on long sewer lines to be effective.

Hazardous material and requires special handling and storage

Page 31: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Nitrate Compounds Provide a combined Oxygen Source to control the H2S

production by the Sulfate Reducing Bacteria

Oxygen from nitrates (NO3) is preferentially used before sulfate (SO4)reduction begins

Once all the oxygen is consumed from the NO3 nitrogen gas is released and there is no residual action

Very effective for short problem forcemains.

If large amounts of nitrate is used, there have been instances of gas binding in force mains due to excessive N2 release due to denitrification.

Is not effective for long distances

Page 32: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Potassium Permanganate

Very strong oxidizer

Effective for sulfide oxidization

Stains all surfaces it touches

Difficult to handle

No long term preventative power

Page 33: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Iron Salts Ferrous Sulfate Fe(SO4)

Ferric Sulfate Fe2(SO4)3

Ferric Chloride Fe Cl3 Ferrous Chloride FeCl2

FeSO4 + H2S FeS + H2SO4

SO4 HS- H2S

Page 34: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Negatives of Iron Salts 4.5 lbs. of ferrous sulfate to remove 1 pound of H2S.

Many times 2-3 times that amount is necessary for sulfide reduction

Why, there are competing reactions in wastewater that will consume iron. Phosphorus, chlorides, sulfates, hydroxide, carbonate, oxygen and other common compounds compete for the iron especially in wastewaters high in saltwater infiltration.

Byproducts – acid and precipitate

Unintended consequence – More sulfide production

Page 35: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

pH Control

Lime Addition

Sodium Hydroxide addition

Magnesium Hydroxide addition

The only Liquid phase treatment that will not consume VFA needed for Anaerobic Selectors in BNR

Page 36: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Property 50% NaOH 30% Ca(OH)2 60% Mg(OH)2

% Hydroxide 42.5 45.9 60.3

Solubility (H2O, g/100ml) 42 0.185 0.0009

Per million gallons 1750 tons 7.7 tons 75 lbs

Reactive pH 14 12.5 9.0

Freezing Point °F 61 32 32

Weight Equivalency 1.37 1.25 1

9.09.0

Chemical Properties of

Commercial Alkali's

Page 37: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Sodium Hydroxide (Caustic Soda) Can be used to “burn out slime layers in pipes”

Can be used to raise pH to between 8-9 for H2S control (has a reactive pH of 14.0)

Hazardous Chemical requiring special storage and handling

Raises pH very quickly

Can create hot spots if not mixed well

Must be carefully controlled to prevent scaling and corrosion

Page 38: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Lime

Can be used to raise pH to 8-9 in sewers for odor control

Has a reactive pH of 12.5 Must be controlled to keep from increasing pH

above 9.0 Has no residual effectiveness for downsteam

odor control Every pound of lime added creates 4.5 pounds

of sludge

Page 39: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Magnesium Hydroxide

Can be used to raise the pH to between 8 and 9 for odor prevention and control.

Is non hazardous and safe to handle

Has a reactive pH of 9.0

Solubilizes over long periods of time and remains effective in the down stream collection system.

Prevents sulfate reducing bacteria (SRB) growth.

Mg++ combines with HS- to form a soluble complex

Page 40: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

SRB Growth S

RB

Gro

wth

Rate

Page 41: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Mg2+ + HS- MgHS+ Mg2(HS)

High pH zone

~ 10.5

Slowly Dissolving

Mg(OH)2 Particle

Surface

OH-

OH-

OH-

OH-

OH-

OH-

Mg2+

Mg2+

Mg2+

Mg(OH)2

HS-

HS-

HS-

H2O

H2O

H2O

H2O

H2O

H2O

HS-

HS-

HS-

Unlike iron salts however, there are no appreciable

reaction precipitants.

Page 42: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Hybrid Liquid Phase Treatment Peroxide regenerated Iron Treatment

Nitrate treatment enhanced with alkali

Iron treatment enhanced with Magnesium Hydroxide

Lime treatment enhanced with Anthraquinone

Sulfur scavengers (amine compounds)

Page 43: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Biologics Anthraquinone

Bacteria Addition

Enzymes

Page 44: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Air Phase Odor Control

Page 45: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Air Phase Unit Operation Units placed at the site of an odor problem as a

method to remove odors from the air being discharged from a Wastewater Facility

Do not prevent odors from forming

Do not prevent corrosion at the structure being treated

Does nothing for upstream corrosion or odor control

While the cost appears to be less than liquid phase treatment, if replacement capital costs are considered this treatment may not be the bargain it appears to be.

Page 46: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Types of Air Phase Treatment Chemical Scrubbers

Biofilters

Carbon Adsorbers

Impregnated media filters

Page 47: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Chemical Scrubbers Most common type use plastic media, caustic soda, and

bleach The chemical is sprayed at the top of the tower and allowed

to contact the air to be treated as it trickles down through the media.

Caustic Soda (NaOH) is usually used in the first stage and controlled by pH monitoring

Bleach is used in the second stage and is controlled by ORP control. ORP must remain positive.

Magnesium Hydroxide has been used successfully as a replacement for Caustic Soda

Sulfur Scavengers have also been used successfully to remove sulfides.

Page 48: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power
Page 49: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Biofilters The most common type of Air Phase Unit in the

Marketplace

The unit depends on a biological growth that is promoted on media in the filter housing

A nutrient solution is sprayed on the media to promote the growth

The units are effective in removing sulfides but often have other organic odors in the exhaust that require polishing

Page 50: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Biofilters Continued The units operate at a pH between 1.7 and 2.4 which is

also the pH of the drainage from the filter that is discharged back to the sewer.

The media varies greatly from mulch to sea shells

Some units are not in fiberglass tanks but are large beds of mulch

Page 51: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power
Page 52: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power
Page 53: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Carbon Adsorbers

• H2S adsorbs on the activated carbon• Other odors also adsorb on the carbon• Effective until there is H2S or other odor

break-through• Some carbons can be regenerated

chemically• Some carbon can be thermally regenerated• Most is landfilled and replaced• Very effective as polishing units downstream

of liquid phase treatment.

Page 56: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

A Comprehensive Approach to Odor and Corrosion Control

Use an effective liquid phase odor and corrosion control program in the collection system.

Supplement the liquid phase treatment with air phase polishing.

Institute physical and structural methods to minimize gas release.

Eliminate aeration and agitation from cascading flows, harsh transitions, splashing, etc.

Use liners where effective as a back-up to the above

Use non Corrosive materials

Page 57: Corrosion and Odor Control in Wastewater  · PDF fileCorrosion and Odor Control in ... dewatering/transport strategies. ... Once DO is depleted there is no more preventative power

Questions