Monitor Activation Process:

IST MaintSelectionV3.php. Setup

August 2006

Copyright, 2006: Invisible Service Technicians, LLC

Monitor Configuration

1) Sales Order Procedure-see DN1040

2) Product Shipped

5) Data Center Updated

8) Create Customer(Profile Management)

3) IST Installed

4) IST Calls Collection Server

10) Enter “Monitored Equipment”(Data Center)

7) Enter “Installation information”(Data Center)

6) Contractor sends Info.-see DN1008, 1009 & 1011

7) Create Contractor (Profile Management)

12) Complete “Sensor Mapping”(Data Center)

13) Enter “Viewing Privileges”(Data Center)

11) Complete “Sensor Edit”(Data Center)

14) Enter “Alert Recipients”(Data Center)

15) Edit General Tab(IST Maint.)

17) Edit Thermo. Sensors Tab(IST Maint.)

16) Edit Temp Sensors Tab (IST Maint.)

19) Edit Calculations Tab(IST Maint.)

18) Edit Digital Sensors Tab(IST Maint.)

20) Edit Accumulator Tab(IST Maint.)

21) Edit Cycles Tab(IST Maint.)

22) Edit Alarms Tab(IST Maint.)

Copyright, 2006: Invisible Service Technicians, LLC

Always select and press “Update IST Initial Setup” button to save modifications made to viewed section, if not when you select and move to other tabs the section will return to previous settings.

Op DelayName = Short name on board.Sensor = Digital or Thermo sensor used to trigger delay.State = Binary state of sensor to cause trigger of delay 1= closed 0= opened.Delay = Delay time in minutes.

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

LED On = 0LED Off = 9LED Flashing = 10

Photo CellOpen = offNO = LED offPhoto CellClosed = onNC = LED on

Outdoor Temperature Sensor:By default the OAT sensor is set to “Temp6”. The OAT sensor is used for on the board calculations of Heat days and Cool days.

Flash Code 1By default is set to Control 1 (Reader 1) Digital 5

Flash Code 2By default is set to Control 2 (Reader 2) Digital 6

Set the Code 1 and Code 2 to the normal condition of LED

General Tab: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Long Name: Displayed on Reports, and Data Center

Short Name: Displayed on board

Secondary min/max temperature2 Lim Src = Digital, or Thermo source to trigger 2 min/max.2 Lim Stat = Condition of source to cause trigger of 2 min/max.Delay = Source trigger delay in minutes.

2 min/max Delay and Op Delay work in parallel. They initiate at same time.

Ability to Enable or Disable installed Temperature sensor.

Indicates sensors that have been checked as installed on Data Center.

Temp Sensors: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Dep 1 Src and Dep 2 SrcSelect options:Digital sensors (Digital1- Digital8)Thermo sensors (Thermo1- Thermo8)

Conditional Logic for sensors:Dep * Stat on, offDep Op or, and

Logic Statement includes: (Op delay, Dep 1 Src, Dep 1 Stat, Dep Op, Dep 2 Src, Dep 2 Stat) This statement has to be True before the initiation of alarm.

Temp Sensors: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Thermo sensor inputs offer status of thermostat operating condition. Wiring is paralleled off thermostat terminal strip. (G,Y1,Y2,W1,W2,REV,E)

Thermo sensors detect the presence of applied 24v + off T-Stat.

If using a Thermo sensor to detect status from relay ensure that 24v+ is applied to input and that the voltage originates from same control transformer providing power to monitor. Must share same common.

Thermo sensors must be wired and set to “Enabled NO” to trigger accumulator.

Thermo. Sensors: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Thermo sensor status is immediately indicated by monitor, the delays and dependencies only affect output to Alarm.

Spare Thermo sensor (Aux3)

EnabledEnabled NOEnabled NCDisabled

Thermo. Sensors: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Short Name: 8 characters, used on board.

Long Name: 50 characters, used in Data center, & Reports.

EnabledFlash Cde DetEnabled NOEnabled NCDisabled

When selecting “Flash Cde Det” for enabled condition you must perform the following:Set normal conditions of LED “General” tab.

oLED on = 0oLED off = 9oLED Flashing = 10

Flash code descriptions and alert condition (If alert is to be sent for 1 or all flash counts) “Data center”.Enable alarm for specific Digital “Alarm” tab.

Digital Sensors: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Digital sensors can be set to either “Enabled NC” or “Enabled NO” to trigger accumulator.

Digital sensor status is immediately indicated by monitor, the delays and dependencies only affect output to Alarm.

Digital Sensors: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Op Delays are Dependent upon power being applied to one of the following: Y1, Y2, W1, W2

Src 1, Src 2Selections available are Temp sensors, and Calculations that have been defined with short Name.

OperatorMath functions available (Add, Subtract, Multiply, and Divide).

2 min/maxAbility to apply 2 min/max temp values for alarm output.

Enable or Disable Calculation

Logic StatementThese statements operate the same in all tab’s and must always be True before alarm is issued.

Calculations: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

AccumulatorsAccumulators track run minutes of applied source. Accumulated minutes are sent each transmission and reset to 0 on board after completion of transmission.

SourceSelections available are Digital and Thermo sensors.

Accumulators: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

CyclesThis function counts the cycles (on / off) of source. Cycles are sent each transmission and reset to 0 on board after completion of transmission.

SourceSelections available are Digital and Thermo sensors.

Cycles: IST Maint SETUP

Copyright, 2006: Invisible Service Technicians, LLC

Primary min/max Temperatures

Secondary min/max Temperatures

2 min/max Temps are triggered by Digital or Thermo sensors located in “Temp Sensor”, and “Calculation” sections.

Min Max AlarmEnable or Disable Alarm output for both primary and secondary min/max temperatures.

Alarm SectionAlarm section is dependent on Logic statement for each sensor (device) being True before issuing alert. Refer to Calculations tab (last 5 options: Dep 1 Src, Dep 1 St, Dep Op, Dep 2 Src, Dep 2 St)

Alarm Text MessageEnable or Disable Text Message

Alarms: IST Maint SETUP