coordinated stablity control

Upload: atul-mishra

Post on 07-Apr-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/6/2019 Coordinated Stablity Control

    1/29

    1

    ABSTRACT:

    An adaptive coordination scheme is proposed to improve the transient stability,

    voltage security and frequency damping of a power system network by optimally scheduling

    the parameters of the available controllers. A set of real-time stability indicators, including a

    transient stability index, transient voltage stability index and damping factor are used to

    reflect the stabilities of power systems. Then, the relative significances of a group of

    controllers to the power system are used as references for the optimiser to schedule new

    controller parameters. This coordinated control scheme effectively allocates power system

    resources to handle different stability issues in different time frames. The results suggest that

    power system security can be further enhanced by means of coordinated control.

    1. Introduction:Power systems are becoming more complex with the increasingly stressed stability

    margins resulting from the electricity market. Traditional vertically integrated power systems

    are being replaced by market-based operation after deregulation. Consequently, it becomes

    more difficult to predict the behavior of power systems. Furthermore, the introduction of

    independent power producers and power electronic loads, which are nonlinear in nature, have

    also complicated the operation of the grid. Although the operation and the interconnection of

    power systems are evolving, two classes of approaches appear in the mainstream control of

    power systems. The first approach is a decentralised controller design where classical linear

    controllers as well as modern nonlinear controllers are designed for handling predictable local

    problems [1,2]. Although remote interactions can be considered in terms of local control

    variables, decentralised controllers rarely coordinate together to resolve any particular

    problems from the viewpoints of the network, not to mention problems of an unusual nature.

    The other approach is a hierarchical control design based on a wide-area measurement [35].

  • 8/6/2019 Coordinated Stablity Control

    2/29

    2

    Accelerated by fast communication facilities, the upper level controllers can obtain remote

    information from different local controllers, and if local controllers have conflicting effects

    with upper level control objectives, they will tune these local control systems in a coordinated

    way according to various global optimisation procedures. These hierarchical optimal

    controllers usually can achieve good performance for a single control objective or two, such

    as transient stability, voltage regulation or oscillation damping, but may neglect the other

    potential stability issues in power systems.

    Power system stability issues are not mutually exclusive. There have been qualitative studies

    [1, 6] showing that some controller interactions could degrade the power system stability

    under certain circumstances for which they are not designed. The concept of coordinated

    different control evolved from previous works [713]. A novel global control strategy was

    introduced for coordinated transient stability and voltage regulation by excitation in [7, 8],

    developing a framework for more general schemes involving the coordination of many

    controls with diverse control goals. The framework was further refined in [9, 10], applied to a

    benchmark test system and covered more different network scenarios. In addition, preventive

    and emergency control actions were coordinated to enhance transient stability in [11, 12], and

    an adaptive optimal control scheme has been applied against cascading blackouts in China

    [13].

    This paper extends the framework [8] to investigate coordinated security control. First,

    various system trajectories are utilised to analyse the instability symptoms of transient

    stability, voltage security assessment and small signal stability. The formulation of remedial

    actions has to be based on the due consideration of thesesymptoms. Then, therelative

    effectiveness of local controllers is evaluated for the capabilities to resolve transient

    instability, voltage instability and small signal oscillatory problems.

  • 8/6/2019 Coordinated Stablity Control

    3/29

    3

    Power system signals such as rotor angles of the generators, bus voltage profiles and

    oscillating frequencies are sensed and used to calculate the transient voltage and small signal

    stability costs. Later, a sensitivity function is formed, which is used by the optimizer

    later as a reference for control parameter scheduling. The severities of the stability issues are

    compared based on their weighted costs, and a new set of controller parameters are optimally

    calculated with the aim of reducing the total cost of system stability. It is to be emphasised

    that it is not a centralised controller design but rather the maximal exploitation of available

    control resources. The simulation results for a benchmark system show that this coordinated

    control scheme is effective, robust and provides significant stability improvement for many

    kinds of system disturbances.

    The paper is structured as follows. The coordinated control scheme is described in Section 2.

    Section 3 presents the power system models and the formulation of the coordinate control

    system. The example power system, its coordinated control system and simulation results are

    provided in Section 4, followed by discussions in Section 5 and conclusions in Section 6.

    2. Coordinated control schemeThe goal of the proposed adaptive coordinated control is to maintain system stability

    under all operating conditions, especially unforeseeable ones. It is a framework within

    which a variety of methods and different controllers can be coordinated to handle

    complex system problems to the extent allowed by the available information and

    communication technology. Hill et al. and Guo et al. [7, 8] offered the possibility of

    coordinating control actions across the whole system geographically and for all operating

    situations in an adaptive way. Hill et al. [7]

    referred to the collection of available control elements swarming onto the problems as

    they arise.

  • 8/6/2019 Coordinated Stablity Control

    4/29

    4

    The coordinated control framework as shown in Fig. 1 has a two-tier structure, which is

    local control and some degree of central coordinated control. The local controllers

    perform their normal operations with the original local settings until an abnormal

    situation occurs where the coordination control takes over. Based on the global control

    objectives for the power system, a set of high-level coordination controllers (CCs) is built

    as the supervisory controllers for the existing local controllers. This system-wide

    coordinated control has four main tasks, namely: (1) indicator processing, (2) scheduling,

    (3) optimisation and (4) actuation. The function

    of each task is described as follows:

    2.1. Indicator processing : The signal-processing layer of the CC collects and processes

    raw network information from local controllers in real-time such as power flow, system

    frequency, bus voltages and alarm signals. The signal is then transformed into

    meaningful signals such as stability indicators. The CC will then determine the severity

    of each kind of instability, that is to decide whether the system is in the proximity of

    transient, voltage or frequency instability.

    2.2. Scheduling : Depending on the severity of the particular type of instability, a group of

    control actions will be scheduled (typically of the switching type) which have the

    capacity, with further tuning, to overcome the instability.

    2.3.Optimisation : The optimisation layer measures the degree of instability of the power

    system and determines the necessary amount of control action to be provided from each

    selected local controller. The stabilising effects of each local controller towards different

    types of instabilities are calculated beforehand. The results can be recorded in the CC

    either in the form of a lookup table or a set of linear/nonlinear equations.

  • 8/6/2019 Coordinated Stablity Control

    5/29

    5

    The information enables the optimisation algorithms to fine tune the action plan established

    by the scheduler in step 2 for optimal performance.

    Fig.1 Adaptive coordination control framework

    Remark 1: The upper level CCs can handle either one single issue (such as voltage

    regulation, oscillation damping and so on.) across a wide area or regional tasks,

    spanning multiple stability issues from a small regional area to a wider interconnected

    power grid. The designs of these upper level controllers are based on the global control

    objective of the power system.

  • 8/6/2019 Coordinated Stablity Control

    6/29

    6

    These coordinated controllers can be installed in different areas of the power system and

    linked together via a communication network, which will necessarily be limited in structure

    and speed. Note that if a communication link to the controller is broken down, local

    controllers can still provide adequate performance although it may not maximise their

    contributions to the optimisation of the whole power system.

    Remark 2: In real-time utilisation, the availability of Phase Measurement Units (PMUs) and

    the locations of local controllers have to be considered such that the optimization procedure

    can be simplified and the global control objective(s) guaranteed. In addition, the two-tier

    structure of the coordinated control framework enables information processing and decision

    making to be made at the local control systems by the use of distributed computation

    technology. This can significantly reduce the computational burden on the CC and, thus,

    reaction to the event in real time is possible. The proposed control scheme should be able to

    reduce the overall processing time in comparison with the centralised control scheme.

    3. Power system models and controller design3.1 Power system models :

    The dynamics of interconnected power systems can be represented by a set of high-

    order nonlinear differentialalgebraic formulas as follows

    x = f (x, y, u, m)

    0 = g(x, y, u, m) (1)

    where the differential equation describes the dynamics of the power system components

    including generators, dynamic load and control devices; the algebraic equation expresses the

    voltage, current and network power flow equations in the system; x Rn

    is the dynamic state

    vector of the power system; y Rl

    is the algebraic constraint vector ; u Rp

    is disturbances,

  • 8/6/2019 Coordinated Stablity Control

    7/29

    7

    which make the power system move from one equilibrium point to another; and m Rq

    is the

    control vector, which consists of adjustable system parameters.

    The operating point (x, y) of the power system (1) varies according to the disturbance and

    the control vector m. When the specific disturbance 0 occurs, control vector =0++

    where

    0 is the control vector of the original steady state and +

    is the adjusted control vector. The

    aim of the proposed control scheme in Section 2 is to obtain the optimised adjustable control

    vector . At the equilibrium point (x0, y0), power system dynamic state vector xand

    disturbances u 0are equal to zero.

    3.2. Stability assessment and cost

    Three categories of stability analysis [6] are mainly involved in the systematical

    controller design of power system, includingtransient stability, voltage stability and smallsignal stability analysis. In order to effectively allocate power system resources to handle

    different stability issues in different time frames and situations, stability assessments and

    indices are evaluated through various system trajectories in real time.

    Despite different methods to study transient stability, the responses of power angle of the

    generators are always regarded as the key trajectories to analyze the synchronization of

    power system. Thus, it is obviously proper to employ power angle excursions to calculate

    transient stability cost Cts , which is an important transient stability indicator for the

    optimisation of the CCs.

    For voltage stability assessment, a cost Ctvs which is based on the trajectories of bus voltages,

    is used to measure how voltage unstable the system is.

  • 8/6/2019 Coordinated Stablity Control

    8/29

    8

    In the case of small signal oscillation, it is common that many different modes of oscillation

    are presented in a multimachine power system. Each mode is characterised by its natural

    frequency and damping factor. The normalized deviation of the damping factor of the

    targeted mode is used to evaluate the small signal stability cost Css .

    The costs Cts, Ctvs and Css can be estimated in real-time and are dependent on the existing

    power system state variable x0, algebraic variables y0, disturbances u0 , controller parameters

    0 and adjusted control variables +

    . Thus, the estimated costs can be written as

    WhereCts , Ctvsand Css represent the changes of transient stability cost Cts, voltage

    stability cost Ctvs

    and small signal stability cost Css

    when control variables are adjusted.

    The changes of stability cost Cts , Ctvsand Css are the indications of the capabilities of

    the power system local controllers for different stabilities. In this paper, the sensitivity

    matrix is proposed to measure the changes of stability cost at a nominal operating point. As a

    first-order approximation, the relationship between cost changes and controller parameters

    can be represented as follows

    (3)

    Where C is the sum of changes of different stability costs, A is the gradient between the

    change of stability costs and the adjusted controller parameters K, that is the sensitivity

    matrix.

  • 8/6/2019 Coordinated Stablity Control

    9/29

    9

    (Note that K can be any controller parameters, such as for load shed. Generally, K is the

    parameters of the controllers and affects the output of the controllers .) The details of

    calculating different stability costs will be provided later.Certainly, higher order nonlinearcontroller function can be designed, but it is not the focus and is therefore not covered in this

    paper.

    3.3. Optimisation

    The determination of the local controller parameter actuation is formulated as a

    constrained optimisation program. A quadratic objective function is proposed

    minJ =tsC2

    ts+ tvsC2

    tvs+ ssC2

    ss (4)

    and

    ts +tvs +ss = 1 (5)

    Where the coefficients ts, ssand tvs are the weights for the corresponding stability indices.

    They are determined with the aim to balance the contribution of each kind of stability in

    different time intervals.

    ThereforeJ is a function of current power system conditions and predicted optimal control

    parameters,

    J = J (x0, y0, u0, ) (6)

    This objective function is subject to two inequality constraints

    (a)Upper and lower boundslb ub (7)

  • 8/6/2019 Coordinated Stablity Control

    10/29

    10

    (b)Limited rate of change in controller parameters

    (8)

    The inequalities can be converted into the following general form

    Gi () 0 (9)

    3.4 Coordinated control design

    The proposed coordinated controller design provides a supervisory feedback for the

    adjustments of local controller parameters according to different network structures, distinct

    operating conditions and various control objectives. The CC design involves the following

    procedure:

    1. design the scopes of upper level CCs based on the global control objectives and local

    controllers in the existing state of the power system prior to any contingencies;

    2. Choose the corresponding methods for upper level CCs to assess transient, voltage and

    small signal stability;

    3. Calculate different stability costs of local controllers and create a set of local controller

    schedules for overcoming potential instabilities of power systems;

    4. Analyse the relationship between cost changes and controller parameters and form the A-

    matrix in (3);

    5. solve the objective optimisation (4) and set up the relative significances of a group of

    control actions according to the sensitivity matrix A and

    6. schedule the actuation of the local controller parameters.

  • 8/6/2019 Coordinated Stablity Control

    11/29

    11

    4. Case study :To illustrate the proposed control framework, control of a typical two-area power

    system will be investigated.

    4.1 Two-area power system

    Fig. 2 shows the diagram of a modified version of the two area system described in

    [14]. The modifications are as follows:

    Line 67 and line 910 are split into double circuits

    Fig. 2 A modified 2-area system

    Line 78 and line 89 are turned into four-line circuits Two static VAr compensators (SVC) are installed at Bus 7 and Bus 9

    The 0.50.6 Hz inter-area mode of oscillation, which has the lowest damping factor

    compared with other local modes of oscillation, is chosen as the target for damping in this

    paper [1, 14]. Other modes are not adversely affected to an extent that they need special

    attention in this system. All the dynamic data of the generators and static data of the system

    remain unchanged from that given in [14].

  • 8/6/2019 Coordinated Stablity Control

    12/29

    12

    Throughout this paper, a number of contingencies are referred to. The descriptions of them

    are as follows:

    C1: Three-phase fault at Bus 7. Fault is cleared by tripping line 78 at 0.1 s later;

    C2: Three-phase fault at Bus 8. Fault is cleared by tripping line 78 and line 89 at

    0.1 s later;

    C3: Three-phase fault at Bus 9. Fault is cleared by tripping line 89 at 0.1 s later;

    C4: 10% load increase at Bus 9.

    Fig. 3. Block diagrams of simple exciter system, PSS and SVC

  • 8/6/2019 Coordinated Stablity Control

    13/29

    13

    In the two-area power system, each of the four generators is equipped with a simple exciter

    and power system stabilizer (PSS). The control blocks of the simple exciter, PSS and the

    SVC are shown in Fig. 3. The parameters are listed in the Appendix.

    4.2. Controller sensitivity tests

    Power system controllers are mostly designed for some kind of primary

    objectives. For example, PSS is designed for damping and SVC is for voltage support.

    However, their contributions to other types of stability controls are also valuable. Information

    like the relative strength of each controller is required for the coordinated control system to

    formulate suitable switching actions.

    In this paper, the stability assessments were calculated by using Powertechs Dynamic

    Security Assessment Software Tools (DSA ToolsTM

    ).

    4.2.1 Transient stability assessment:

    The transient stability

    index of a multi-machine system

    can be computed by using the

    extended equal area criteria

    (EEAC) [15]. This method

    separates the system generators

    into two groups, that is the critical

    cluster and the rest. The cluster of

    critical machines is identified as

    the group of candidate critical

    machines which give the smallest

    critical clearing time (CCT). Fig. 4. Power angle diagram

  • 8/6/2019 Coordinated Stablity Control

    14/29

    14

    The stability index is obtained by calculating the difference between the acceleration area

    and deceleration area in the corresponding EEAC assessment. Fig. 4 identifies the quantities

    referred to. Then the index

    Where Ainc is equal to kinetic energy increasing area (during fault) and Adec is equal to kinetic

    energy decreasing area (post fault).

    The initial gain values of the exciter, PSS and SVC are set to be 200, 30 and 200,

    respectively. By varying the gain of one kind of controller at a time, the transient stability

    indices are found (see Fig. 5).

    The following points are observed:

    Small load change (in this case, 10%) does not affect transient stabilitysee Case C4;There are discontinuities in the stability indices. This is because the EEAC algorithm

    separates different machines into different clusters according to the degrees they are

    affected. Different combinations of critical generators will change the inertia base of the

    calculation, resulting in the discontinuity of the plots;

    It shows that increased gain in the excitation system does not always increase thestability index, and increase in PSS gain does not necessarily worsen the transient

    stability. These two figures show that the actions of the excitation system and PSS in

    transient stability tend to be oppositional; Increase in SVC gain does not improve the transient stability

  • 8/6/2019 Coordinated Stablity Control

    15/29

    15

    Fig. 5. Transient stability index with adjustable excitation, PSS and SVC gains

  • 8/6/2019 Coordinated Stablity Control

    16/29

    16

    4.2.2 Transient voltage stability assessment:

    Voltage stability refers to the ability of a power system to maintain steady voltages at

    all buses in the system after being subjected to a disturbance from a given initial operating

    condition [6]. By estimating the distance to the proximity of voltage collapse, many

    stability indices have been proposed [16]. In this paper, voltage security (or transient voltage

    Stability), which describes the deviation of transmission system voltage from its nominal

    value is used [17]. Based on signal energy analysis [18], a transient voltage instability index,

    which measures the normalised distance of the transient voltage from the steady-state value,

    is chosen.

    The equation is stated below

    where tvs is the transient voltage instability index, ncl is the time step at the clearing time;

    and the subscript i denotes buses and i denotes the time step. Note that unlike the transient

    stability index, ts (that the larger the index value, the more stable is the system), bigger tv

    implies that the system is more voltage unstable.

    Inspection on Fig. 6 reveals that:

    the transient voltage instability index increases monotonically in a close-to-linearfashion as the excitation gains change from 100 to 300;

    change in PSS gains has relatively much less effect on transient voltage stability; the SVC is the most effective device for transient voltage stability improvement; load variation has minimal effect on transient voltage stability.

    It is therefore concluded that a reduction in excitation gain and an increase in SVC gain can

    improve transient voltage stability.

  • 8/6/2019 Coordinated Stablity Control

    17/29

    17

    Fig. 6. Transient voltage stability index with adjustable excitation, PSS and SVC gains

    4.2.3 Small signal stability assessment:

    Different modes of oscillation are present in a multi-machine power system. Each

    mode is characterised by its natural frequency and damping factor.

  • 8/6/2019 Coordinated Stablity Control

    18/29

    18

    Pronys method [19] is a common way to extract the frequency information in real-time. It

    considers the sampled data as a linear combination of exponentials.

    for 1 n N, where T is the sample interval,Ak is the amplitude, kis the damping factor,

    fkis the sinusoidal frequency, k is the sinusoidal initial phase.

    The p-exponent discrete-time function of (12) can be expressed in the form

    (13)

    The damping factor (), corresponding frequency (f) and damping index (ss) can be

    calculated by

    (14)

    (15)

    ss =

    (16)

    The diagrams in Fig. 7 show the damping variations with different controller gains. It is noted

    that the damping ratio of the inter-area mode increases almost linearly with the increase of

    PSS gains. On the other hand, although the damping factor increases in the excitation gain

    ranges from 0 to about 60, it begins to decrease monotonically after the peak. The increase of

    SVC gains also decreases the damping ratio in this case.

  • 8/6/2019 Coordinated Stablity Control

    19/29

    19

    Fig.7 Small signal stability index with adjustable excitation, PSS and SVC gains

    (Frequency = 0.55 Hz)

  • 8/6/2019 Coordinated Stablity Control

    20/29

    20

    In general, the procedure of sensitivity measurements demonstrated above can be adopted for

    any kinds of dynamic problems, indices and control actions. Those chosen here are for

    illustration.

    4.2.4 Stability costs:

    Although the transient stability index from EEAC is a well-accepted indicator

    for transient stability, it cannot provide a continuous assessment of the overall status of the

    generator angles. A modified method to measure the overall rotor angle deviation is, thus,

    proposed

    (17)

    where Mi is the moment of inertia of the ith machine in the S-cluster, Mj the moment of inertia

    of the jth machine in the A-cluster, i the rotor angle of the ith machine in the S-cluster, j the

    rotor angle of the jth machine in the A-cluster

    To represent the angle excursion as a cost to the power system transient stability, the

    following function is used

    (18)

    Where dc is the critical angle of the system. The value of C ts is between 0 and 1. The

    transient stability limit is defined by Cts = 1.

    Transient voltage instability index can be directly used as the cost to be minimised for

    transient voltage stability, that is

    (19

  • 8/6/2019 Coordinated Stablity Control

    21/29

    21

    Note that the value of the transient voltage stability cost is kept below l. During

    phase-to-earth faults, voltage would momentarily drop to zero. The voltage deviation (thus

    voltage stability cost) from the nominal value would be large when compared with other

    stability costs. However, transient stability cost is considered to be the most important during

    the fault period. For illustration here l is taken as 0.3, which covered the voltage fluctuations

    encountered.

    The small signal stability cost is the normalised deviation of the damping factor of the

    frequency from the targeted one

    where ss0 is the target damping factor. The maximum value of Css is 1 and the minimum

    value is limited to 0, even ifssss0.

    4.2.5 Sensitivity matrix:

    From the analysis of above three sections, the relative effectiveness of three

    controllers, namely an excitation controller, PSS and SVC have been evaluated for the

    capabilities to resolve transient instability, voltage instability and small signal oscillatory

    problems. Thus, the sensitivity matrix A in (3) can be summarised at a nominal operating

    point. Due to the relatively simple relationship between cost changes and controller

    parameters actuation, a linearised sensitivity matrix is formed as follows

    The value of this A-matrix is provided in the Appendix.

    (20)

  • 8/6/2019 Coordinated Stablity Control

    22/29

    22

    4.2.6 Optimisation function:

    In order to realise the coordinated control and actuate various local controller

    parameters, the quadratic objective function (4) must be chosen in advance. Since the two-

    area power system is a comparatively small system and system response after disturbances

    with limited time interval, the coefficients ts, ssand tvs are considered as constants. The

    values are taken to be [0.6, 0.3, 0.1], respectively, in the simulation.

    4.3. Simulation results

    In this section, a network contingency scenario is demonstrated. The effects of the

    global coordinated control scheme are compared with a conventional method where no global

    control is used, that is parameters are fixed at values determined in the Appendix. The control

    scheme is tested by simulations in MATLAB Power System Toolbox [20].

    The load at Bus 9 is increased by 10% at t = 2.0 s. Then at t = 6.0 s, a fault occurs at Bus 8.

    The fault is cleared by tripping one line 89. The results are shown in Figs. 8a8d. Fig. 8a

    shows that the bus voltage under global control settles at a new equilibrium much faster than

    the conventional scheme. The cost comparisons in Figs. 8b and 8c confirm that transient

    stability, transient voltage stability and damping are improved by the proposed control

    scheme. The controller gains in Fig. 8d highlight the point that the controllers can

    automatically reschedule their parameters for successive events.

  • 8/6/2019 Coordinated Stablity Control

    23/29

    23

    Fig. 8 Figure 8 Responses of the global coordinated control with successive events

    a Voltage magnitude at Bus 8

    b Stability cost of the power system with global control

    c Stability cost of the power system without global control

    d Actual controller gain scheduling

  • 8/6/2019 Coordinated Stablity Control

    24/29

    24

    5. DiscussionsThe simulations have shown some significant improvements over a wide range of

    power system stability problems by the proposed coordination scheme. There are some

    points worth noting:

    1. The coordinated control scheme used in Section 4 only coordinates controllers of

    similar types. In general, the global control will be capable of handling a mixture (hybrid)

    of continuous and discrete, dynamic and static control actions. Furthermore, advanced

    controllers like FACTS devices are also suitable for this scheme [9].

    2. This coordinated control scheme utilises a basic feedback control algorithm to improve

    power system stability. Other advanced control algorithms such as model predictive

    control [21] can also be adopted to predict the power system behaviour and to evaluate

    parameters in advance.

    3. The voltage cost in the objective function only considerstransient voltage stability

    Long-term voltage stability can also be taken into account as an additional cost to the

    objective function. Indicators like loading margin can be used and remedial actions

    such as load shedding and capacitor switching can also be coordinated for voltage

    regulation.

  • 8/6/2019 Coordinated Stablity Control

    25/29

    25

    6. ConclusionsThis paper presented a generic adaptive coordinated control scheme for

    power systems as a further step towards universal type controllers which flexibly

    respond to all stability problems. The controller uses measurable network

    information to determine the locality and type of the stability nproblems. By

    formulating and coordinating the necessary control actions from all available local

    control actions, we can overcome system-wide power system problems. This

    framework is flexible to adopt new elements such as stability indicators and

    optimisation algorithms. The development of tests and models is further needed for

    evaluating the capabilities of different controllers under different instabilities.

  • 8/6/2019 Coordinated Stablity Control

    26/29

    26

    7. References

    [1] KUNDUR P.: Power system stability and control (McGraw-Hill, 1994)

    [2] CHAPMAN J.W., ILIC M.D., KING C.A., ENG L., KAUFMAN H.:

    Stabilizing a multimachine power system via decentralized feedback linearizing

    excitation control, IEEE Trans. Power Syst., 1993, 8, (3), pp. 830839

    [3] TAYLOR C.W., ERICKSON D.C., MARTIN K.E., WILSON R.E.,

    VENKATASUBRAMANIAN V.: WACS-Wide-Area stability and voltage

    control system: R&D and online demonstration, Proc. IEEE Energy Infrastruct.

    Defense Syst., 2005, 93, (5), pp. 892906

    [4] OKOU F., DESSAINT L.A., AKHRIF O.: Power systems stability

    enhancement using a wide-area signals based hierarchical controller, IEEE Trans.

    Power Syst., 2005, 20, (3), pp. 14651477

    [5] MARQUES A.B., TARANTO G.N., FALCAO D.M.: A knowledge-based

    system for supervision and control of regional voltage profile and security, IEEE

    Trans. Power Syst., 2005, 20, (1), pp. 400407

    [6] KUNDUR P., PASERBA J., AJJARAPU V., ANDERSSON G., BOSE A.,

    CANIZARES C., ET AL.: Definition and classification of power system

    stability, IEEE Trans. Power Syst., 2004, 19, (3), pp. 13871401 [IEEE/CIGRE

    Joint Task Force on Stability Terms & Definitions]

    [7] HILL D.J., GUO Y., LARSSON M., WANG Y.: Global hybrid control of

    power systems. Preprints of Bulk Power System Dynamics and Control V, 2631

    August 2001

  • 8/6/2019 Coordinated Stablity Control

    27/29

  • 8/6/2019 Coordinated Stablity Control

    28/29

    28

    [15] XUE Y., CUTSEM T.V., RIBBENS-PAVELLA M.: Extended equal area

    criterion justifications, generalizations, applications, IEEETrans. Power Syst.,

    1989, 4, (1), pp. 4452

    [16] Voltage Stability Assessment: Concepts, Practices and Tools: IEEE PES,

    Power System Stability Subcommittee Special Publication, August 2002

    [17] HISKENS I.A., HILL D.J.: Energy functions, transient stability and voltage

    behaviour in power systems with nonlinear loads, IEEE Trans. Power Syst., 1989,

    4, (4), pp. 15251533

    [18] TUGLIE E.D., DICORATO M., SCALA M.L., SCARPELLINI P.: A

    corrective control for angle and voltage stability enhancement on the transient

    time-scale, IEEE Trans. Power Syst., 2000, 15, (4), pp. 13451353

    [19] MARPLE S.L. JR., CAREY W.W.: Digital spectral analysis with

    applications (Prentice-Hall, 1987)

    [20] CHOW J.H.: Power system toolbox, a set of coordinated M-files for use with

    MATLAB (Cherry Tree Scientific Software, 1996)

    [21] LARSSON M., HILL D.J., OLSSON G.: Emergency voltage control using

    search and predictive control, Int. J. Electr. Power Energy Syst., 2002, 24, pp.

    121130

  • 8/6/2019 Coordinated Stablity Control

    29/29

    8. Appendix The simple exciters have the following parameters:TR = 0.01,TA = 0.2, KEXC = 200.0,VRMAX = 7.0,VRMIN = 27.0, KEXC(MAX) = 300.0,

    KEXC(MIN) = 0.0

    The time constants (s) of the power system stabiliser are:T1 = .05, T2 = 0.02, T3 = 3.0, T4 = 5.4, Tw = 10, KPSS = 30.

    The SVC parameters are specified as follows:TR = 0.05, KSVC = 200.0, BMAX = 3.0, BMIN = 23.0, KSVC(MAX) = 300.0,

    KSVC(MIN) = 0.0

    The upper and lower bounds of PSS are 150 and 0. The sensitivity matrix used is:

    [ -0.2, 0.01, 0.05; 0.2, - 0.02, - 25 10-6

    ; 0.01, 0.005, -1.5]