  • IntroductionSystem Schematic

  • IntroductionNetwork SchematicMax 126 nodes Control Panels, Network Repeaters, Network ModulesTopologyFire rated RS485 screened twisted pair, ie, Draka 9102341000m cable max of copper network between boostersData AvailablePanel Number, Loop Number, Device No. / Desc / type, Zone No. / desc

  • IntroductionAdvanced Network Modules RangeNCDRDual Redundancy Network Card (V2)

    CFSFL01/02LON (network) to Fibre Optic interface, max 15K FO length

    EC400LON (network) to TCP/IP interface

    EC540LON (network) booster, splits network and resends data to increase rangeECO232LON (network) to RS232: Site Graphics & Site Monitor

    EC200LON (network) to BMS Gateway

    EC650LON (network) to BACnet interface

    EC700BMS Gateway to ModBus interface

  • Standard HardwareStandard Network Card ConnectionsCableEnhanced fire rated data cable, Max 1000m lengthDraka 910234 2 core twisted pair with screenScreeningConnect screen to ground at one end onlyTerminationResistor termination 102 (2 x 51 ) per cardRadial NetworkRemove resistors at all network cards except the two ends102 at each end = 51 across networkRing NetworkRemove resistors at all network cards except oneLink out 1 resistor leaving 51 across networkEC540 Booster: treat the network either side as separate networks

  • Standard HardwareStandard Network TerminationRadial NetworkRemove resistors at all network cards except the two ends102 at each end = 51 across network

  • Standard HardwareStandard Network TerminationRadial Network with BoosterRemove resistors at all network cards except the two ends102 at each end = 51 across network

  • Standard HardwareStandard Network TerminationRing NetworkRemove resistors at all network cards except oneLink out 1 resistor leaving 51 across network

  • Standard HardwareStandard Network TerminationResistor Termination on network card102 (2 x 51 resistor)To give 51 reading across network pair at any pointRadial NetworkRemove resistors at all network cards except the two ends102 at each end = 51 across networkRing NetworkRemove resistors at all network cards except oneLink out 1 resistor leaving 51 across network

  • Advanced HardwareNCDR: Network Card Dual RedundancyDual Network ChannelsCableEnhanced fire rated data cable, Max 1000m lengthDraka 910234 2 core twisted pair with screenScreeningConnect screen to ground at one end onlyTerminationAs per standard network card, but for each channel

  • Advanced HardwareNCDR: Network Card Dual RedundancyDual Network ChannelsNetwork 1 and Network 2 Automatic Switching in event of faultNetwork Protocol V2 option must be selected

  • Advanced HardwareCFSFL01/02: Lon (Network) to Fibre Optic InterfaceSingle or Dual ChannelRequires 2 for a dual networkFibreSingle Mode x 2 (Tx & Rx)9/125 micron15Km maxSC Type connectors

  • Advanced HardwareCFSFL01: Lon (Network) to Fibre Optic InterfaceSingle Channel networkRadial, ring or part network

  • Advanced HardwareCFSFL01: Lon (Network) to Fibre Optic InterfaceSingle Channel networkRadial, ring or part network

  • Advanced HardwareCFSFL02: Lon (Network) to Fibre Optic InterfaceDual Channel networkRadial, ring or part network

  • Advanced HardwareCFSFL01/2: Lon (Network) to Fibre Optic InterfaceMany possible combinations

  • Advanced HardwareEC400: Lon (Network) to TCP/IP InterfaceNetwork via PC network / internet / etcRequires 2 for a dual networkUse Hyper Terminal for configurationIP addressInbuilt Web Server for IP configurationIP addressPasswords

  • Advanced HardwareEC400: Lon (Network) to TCP/IP InterfaceRequires fixed IP addressUseful for facilities management

  • Advanced HardwareEC540: Lon (Network) BoosterExtend radial network lengthEffectively splits a network into multiple networksRequires 2 for a dual networkMax 5 per networkAny more may cause transmission delays

    NETWORK CONNECTION24V DC

  • Advanced HardwareEC540: Lon (Network) BoosterRadial NetworkTerminate network either side of booster

  • Advanced HardwareEC0232: Lon (Network) to RS232 InterfacePC connectionNo network address requiredVersionsEC0232: Site Monitor, Site Graphics, EC0232PAVA: EVAX HMX PAVAEC0232PAVA3D: EVAX HMX PAVA 3 minute time delay

  • Advanced HardwareEC0232: Lon (Network) to RS232 InterfaceTypical Example

  • Advanced HardwareEC200: Lon (Network) to BMS GatewayTranslation for BMS connectionRequires EC700

  • Advanced HardwareEC700: BMS Gateway to MODbus interfaceTranslation for BMS connectionRequires EC700Verify requirement spec as protocol implementation may vary

  • Advanced HardwareMODbus InterfaceTypical Example

  • Advanced HardwareEC650 to BACnet interfaceTranslation for BMS connectionDirect network connectionVerify requirement spec as protocol implementation may vary

  • Advanced HardwareBACnet InterfaceTypical Example

  • NetworkStandard Network SetupAt each control panelNumber of panels on networkPanel AddressE.g., Panel 1 of 4Network Response (to commands received)SilenceResetEvacuateFireFaultPre AlarmNetwork FilterSelect which Panels to respond to

  • OperationFault Finding a NetworkLon Network ErrorCheck panel address and totals settingsCheck network terminationCheck network cable insulation and continuity readings

    MiscHard reset panel, then clear watchdog fault with soft resetGenerate fire or fault and check transmission and reset