control of a shunt active power filter
TRANSCRIPT
-
8/11/2019 Control of a Shunt Active Power Filter
1/6
AbstractThis paper presents a control method of a NPC three-level four-wire inverter of a shunt active power filter (SAPF) byswitching functions. The switching functions of the inverter areextracted by equations of the inverter averaged model to compensate
load harmonic currents. The averaged model of the inverter isaccording to allowable switching states of the inverters switches(IGBTs). In this paper, the control system of SAPF based onswitching functions employs THD calculation block diagram to
generate signal-gates of the inverter switches. The proposed controlmethod is applicable under asymmetrical and non-sinusoidal three-
phase source. The principles of the presented control method areanalyzed in this paper. Also, the control method is modeled and
simulated in MATLAB/Simulink to validate effectiveness of theproposed control method.
KeywordsShunt active power filter, Multi-level inverter,averaged model, switching function, THD
I.
INTRODUCTION
dvent of non-linear electrical loads, such as diode
rectifiers, uninterruptable power supplies and adjustable
speed drive systems causes harmonic current injection in to
the electrical grids and degrades the power quality. Low
power quality may cause other problems, such as additional
losses in the transmission lines, overheating of electricalequipment, EMI problems and some undesirable effects.
Limitation of the harmonic currents and the harmonic voltages
are specified by the international standards (IEEE519,
IEC61000-3-2 and EN50160). These standards determine
allowable amount of harmonic injection of electrical
equipment and the facilities. There are several methods to
improve the power quality and to decrease the harmonic
currents injected to the grid. The simplest solution is parallel
passive filter (PPF). The PPFs are widely used for decreasing
of the harmonic currents in the utilities due to their low cost
and high efficiency, but they have some drawbacks, such as
the effects of the source impedances on their characteristics,
series and parallel resonance with the source and the loads and
over-voltage under no-load or light load conditions. [1, 2, 3]
Shunt active power filters (SAPFs) is a suitable solution
method without disadvantages of the PPFs. Since the SAPFs
are adapted to the load currents, no over voltage, no under
M. Asadi is with Dept of Elec. Eng., Iran University of Science and
Technology, Tehran, Iran (e-mail: [email protected]).A. Jalilian is with the Dept of Elec. Eng., and Center of Excellence for
Power System Automation and Operation, Iran University of Science and
Technology, Tehran, Iran (Corresponding author, e-mail: [email protected]).
voltage and no resonance are occurred [3, 4].
Control system of the SAPF consists of two main unit,
reference signal extraction unit and controller and modulation
unit. Reference signals extraction of the SAPF is the first step
for design of the control system. Reference signals are
extracted in two domains of time and frequency. The time
domain techniques are p-q, d-q, SRF 1, DPC2, DC BEB3
theories [5, 6 and 7] and the others are expressed in frequency
domain such as Fourier transformer [5, 7]. For control design,
modeling of SAPF is necessary. The inverter model based on
the state-space model or the transfer function model is done byaveraged model in papers of [8-10].
In the recent years, multi-level inverters are widely used
in power quality conditioners such as shunt active power
filters, hybrid active power filters and STATCOMs. Not only
in high voltage applications, the multi-level inverters are good
ideas, but also they are suitable for decrease of output current
ripples, reduction of electrical strain such as dV/dt on IGBTs
and small size of output passive filter of the inverter [11-12].
In this paper, a NPC three-level inverter is used in SAPF.
Due to using of three-level inverter in configuration of the
SAPF, it is suitable for high voltage applications. The current
control of the inverter is based on switching function extracted
by averaged model of NPC three-level inverter. A blockdiagram of THD calculation is used to extract switching
functions too. Whereas, system voltages and output current of
the inverter are considered as parameters to extract switching
functions, the harmonic currents are effectively compensated
under asymmetrical and non-sinusoidal source voltages
conditions.
II.
AVERAGED MODEL AND SWITCHING FUNCTIONS
Figure (1) shows the configuration of the SAPF comprising
a NPC three-level inverter and control circuit of DC-link. The
inverter is connected in parallel with the source and the loads
through three inductors at the points of common coupling
(PCC). The PCC voltages are shown by VAFa,b,c in figure (1).
Some parameters of the circuit shown in figure (1) are listed in
table I.
1Synchronous Reference Frame
2 Direct Power Control3 DC Bus Energy Balance
Control of a Shunt Active Power Filter based on
THD Tracking under Unbalanced Condition
Mehdi Asadi, and Alireza Jalilian
A
2nd International Conference on Advances in Electrical and Electronics Engineering (ICAEEE'2013) Dec. 20-21, 2013 Bali (Indonesia)
55
-
8/11/2019 Control of a Shunt Active Power Filter
2/6
Control System
LAFb
Lsa
Lsb
Lsc
Vsa
Vsb
Vsc
Acti ve Part
(4-Wire 3-Leg inverter)
Linear
and
Non-
Linear
Loads
LLa
LLb
LLc
C1
C2
LAFa LAFc
iAFa iAFb iAFc
iLa
iLb
iLc
isa
isb
isc
VAFa
VAFb
VAFc
RAFa RAFb RAFa
RDC-link
RDC-link
DC Cont.
System
IGBT1
IGBT2
Q1a
Q2a
Q3a
Q4a
Q1b
Q2b
Q3b
Q4b
Q1c
Q2c
Q3c
Q4c
Fig. 1 The shunt active power filter
TABLE I. SOME SYSTEM PARAMETERS
The source inductances Lsa=L sb=Lsc=0.1mH
The line inductances
LLa,b,c=0.1mHThe capacitance of DC-Link
capacitorsC1,2=2350 F
The inductance of the inverter LAFa,b,c=10mH
RAFa,b,c=1
Rdc-Link1 , Rdc-Link2 2000
A. The averaged model based on switching functions
Since the four-wire three-level inverter is employed in the
SAPF topology, each phase of the inverter shown in figure (1)
is independent of the others. For switching functions
extraction, all of the possible switching states must be
investigated. Each phase of NPC three-level inverter has four
states as shown in table (II). Assuming that parameters dKa,b,c
are defined as switching functions phases a, b and c, they canbe expressed as:
=
stateoffareQif
stateonareQifd
cbKa
cbKa
cbKa
,,
,,
,, ,0
,1 (1)
Where, index K is 1 or 2. The switches Q3a,b,c and Q4a,b,c are
complement of switches Q1a,b,cand Q2a,b,crespectively.
TABLE II. SWICHING TABLE OF THE SAPF
d1 d2 VF iC1 iC2
Phase-a
0 0 -VC 0 - iAF
0 1 0 0 0
1 0 0 0 0
1 1 +VC iAF 0
Phase-b
0 0 -VC 0 - iAF0 1 0 0 0
1 0 0 0 0
1 1 +VC iAF 0
Phase-c
0 0 -VC 0 - iAF
0 1 0 0 0
1 0 0 0 0
1 1 +VC iAF 0
The inverter output voltages and the DC-link capacitors
currents are shown in table (II). Considering equation (1) and
table (II), the output voltage of the inverter and the capacitors
currents can be written based on the switching functions as
follows:
C
cc
bb
aa
Fc
Fb
Fa
V
dd
dd
dd
V
V
V
+
+
+
=
1
1
1
21
21
21 (2)
[ ]
=
AFc
AFb
AFa
ccbbaaC
i
i
i
ddddddi 2121211
(3)
[ ]
=
AFc
AFb
AFa
ccbbaaC
i
i
i
ddddddi )1)(1()1)(1()1)(1( 2121212
(4)
Therefore, the NPC three-level inverter can be modeled as
shown in figure (2).
C1
C2
vC
vC
+
-
+
-
LSa
LSb
LSciSc
iSb
iSaVSa
VSb
VSc
VAFa
VAFb
VAFc
iC1
iC2+ _
+ _
+ _
LAFc
LAFb
iAFb
LAFa
iAFa
vFc
vFb
vFa
iAFc
Linear and
Non-Linear
Loads
LLa
LLb
LLc
iLb
iLc
iLa
RAFa
RAFb
RAFc
Fig. 2 The averaged model of the SAPF
Figure (3) shows the averaged model of the SAPF, where
the inverter is considered as two controlled current sources
(iC1 and iC2) and three controlled voltage sources (V Fa, VFb
and VFc). Considering that, the output voltages of the inverter
are dependent on the switching functions; the output currentsof the inverter are controllable. In this paper, capacitors
voltages of inverter are controlled by separated control system
based on hysteresis controllers. Therefore, the DC-link of the
inverter can be considered as two constant voltage sources.
B.Switching function ratios
The NPC three-level inverter of the SAPF consists of three
legs. Each leg has four gate-signals which the gate-signals of
the lower switches (Q3a,b,c and Q4a,b,c) are complement of the
upper switches (Q1a,b,c and Q2a,b,c).
=
)(
)(
)(
)(
)(
)(
1
2
1
2
1
2
c
c
b
b
a
a
QON
QON
QON
QON
QON
QON
c
b
a
T
T
T
T
T
T
MR
MR
MR (5)
In this paper, switching function ratio is used for gate
signals generation. The switching function ratio is a good
approach to extraction of gate-signals of Q 1a,b,cand Q2a,b,c . The
ratios of on-state times of Q 1a,b,c to on-state times of Q2a,b,c
2nd International Conference on Advances in Electrical and Electronics Engineering (ICAEEE'2013) Dec. 20-21, 2013 Bali (Indonesia)
56
-
8/11/2019 Control of a Shunt Active Power Filter
3/6
are defined as MRa,b,c4 respectively. Therefore, the switching
functions can be written as:
=
c
b
a
c
b
a
c
b
a
d
d
d
MR
MR
MR
d
d
d
1
1
1
2
2
2
00
00
00 (6)
The switching function ratios are determined based on THD
Tracking of the source current specified by internationalstandard, in this paper.
III.
REFERENCE SIGNALS EXTRACTION AND THD
CALCULATION
Figure (3) shows equivalent single-phase circuit of the
system shown in figure (2) in harmonic domain.
LS
iS(h)VS(h)
+
_
LAF
vF(h)=(d1+d2-1)VC
iAF(h)
iD(h)
iAF(h)
VAF(h)iL(h)
Fig. 3 single-phase circuit of the SAPF
Considering current detectors locations, the source and
detected currents are expressed as [11, 12]:
[ ] [ ] cbDadqodqocbahDcbahL iTHPFTii ,,1
,,)(,,)(
== (7)
[ ] [ ] cbAFadqodqocbahAF
VTHPFTV ,,1
,,)(
= (8)
where iL,iD , VAF, Tdqo and HPF are the load current, the
detected current of the sensor S 1, the load voltage,
transformation matrix and high pass filter respectively. Also
the index (h) denotes the harmonic components. The
transformation matrix Tdqois given as:
[ ]( ) ( )( ) ( )
+
+
=
2
1
2
1
2
13
2sin3
2sinsin
32cos
32coscos
3
2
ttt
ttt
Tdqo
(9)
Considering to equations (7) and (8), extraction block
diagrams of currents and voltages are shown in figure (4).
abc
to
dqo
vAFa
HPF
dqo
to
abc
vAFb
vAFc
vAF(h)a
vAF(h)b
vAF(h)c
PLL
abc
to
dqo
iDa
iDb
iDc
HPF
iDd
iDq
iDo
dqo
to
abc
iD(h)a
iD(h)biD(h)c
two
two
two
two
Fig. 4 The extarction of currents and voltages components
The detected signals are sent to transformation matrix of
4Modulation Ratio
Tdqoand, are passed through the high pass filters to generate
harmonic components of them in d-q-o coordination system.
Finally, inverse of Tdqo is used to produce harmonic
components in a-b-c coordination system. In this paper, THDs
of currents are employed to generate modulation ratios
MRa,b,c . The equation (10) shows extraction of the source
currents.
cbAFacbDacbSa iii ,,,,,, = (10)
The extraction method of THDs of the source currents can
be implemented by block diagrams shown in figure (5). After
extraction of the fundamental and harmonic components of the
source currents, squares of them are passed through low pass
filters to produce their mean squares.
_ +
_ +
_ +
iSaiSb
iSc
iDaiDb
iDciAFa
iAFb
iAFc
abc
to
dqo
HPF
dqo
to
abc
()2
LPFiSha
()2
LPF
_
+
iSa iS(1)a ()-1
()2
LPF
()2
LPF
_
+
iSb iS(1)b ()-1
()2
LPF
()2
LPF_+
iSc iS(1)c ()-1
iShb
iShc
THDa
THDb
THDc
two
two
Fig. 5 The extarction method of the THDs of the source currents
=
)()1(
)()(
)()1(
)()(
)()1(
)()(
rmscS
rmschS
rmsbS
rmsbhS
rmsaS
rmsahS
c
b
a
i
i
i
i
i
i
THD
THD
THD (11)
Where, iSand T denote the source current and periodic time
of grid voltages.
The extracted THDs are employed to determine themodulation ratios of the three-level inverter of the SAPF.
IV. THE CONTROL STRATEGY
Whereas the SAPF compensates the harmonic components
of the loads, it should be analyzed in domains of harmonic
frequencies. Figure (3) shows equivalent circuits of the system
in harmonic domains. As shown in the figure, the three-level
inverter of the SAPF is considered as a harmonic source
voltage. Considering KVL equations in figure (3), the inverter
currents can be written as:
+
=
AFc
chAFchF
AFb
bhAFbhF
AFa
ahAFahF
chAF
bhAF
ahAF
AFc
AFc
AFb
AFb
AFa
AFa
chAF
bhAF
ahAF
L
vv
L
vv
L
vv
i
i
i
L
R
L
R
L
R
dt
didt
didt
di
)()(
)()(
)()(
)(
)(
)(
)(
)(
)(
00
00
00 (12)
In order to effective harmonic compensation, the source
currents of iSha,b,c should be near to zero, So in harmonic
domains, the inverter currents can be decided as:
cbahDcbahAF ii ,,)(,,)( = (13)
2nd International Conference on Advances in Electrical and Electronics Engineering (ICAEEE'2013) Dec. 20-21, 2013 Bali (Indonesia)
57
-
8/11/2019 Control of a Shunt Active Power Filter
4/6
-
8/11/2019 Control of a Shunt Active Power Filter
5/6
Fig. 7 The source currents
Fig. 8 THD of the source currents
TABLE IV. FUNDAMENTAL AND THD OF THE SOURCE CURRENT
Isa Isb Isc
Before Applying of the SAPF
THD (%) 15.58 18.7 15.93
I(1)(A) 8.58 7.78 8.4
After Applying of the SAPF I(1)(A) 8.48 8.46 8.47
Figure (9) shows the modulation ratios produced by control
system under the worst condition. As shown in figure (10), the
capacitors voltages are effectively fixed around 330V.
Figure 1. Modulation ratios of the inverter
Fig. 9 DC-link voltages of the inverter
VI. CONCLUSIONS
In this paper, a control method of an active power filter is
discussed based on averaged model to produce switching
functions. The switching functions are employed to
compensate the source current harmonic components. The
extraction of switching functions is based on allowable THDs(within 5% limits) of the source currents specified by
international standards such as IEEE 519. Based on
MATLAB-Simulink, simulations were carried out under non-
sinusoidal and asymmetrical three-phase system. Whereas the
voltages of the HAPF are used in the control method, the
switching functions can effectively compensate the harmonic
components of the source currents under non-sinusoidal and
asymmetrical three-phase grid.
REFERENCES
[1] Hurng-Liahng Jou, Kuen-Der Wu, Jinn-Chang Wu, and Wen-JungChiang,'' A Three-Phase Four-Wire Power Filter Comprising a Three-Phase Three-Wire Active Power Filter and a ZigZag Transformer'',
IEEE Transactions on Power Electronics, Vol. 23, No. 1, Jan. 2008.
[2]
G. K. Singh,Power system harmonics research: a survey, EuropeanTransactions on Electrical Power (ETEP) , Vol. 19, 29 August 2007, pp.151-172
[3]
M.Asadi, A.Jalilian, Using Magnetizing Reactances of Transformer inHybrid Active Power Filter, In Proc.of 2ndPower Electronics & DriveSystems and Technology Conference, 16-17 Feb. 2011, Tehran, Iran, pp268 - 273
[4]
B. Singh, K. Al-Haddad, A. Chandra, Active Power Filter forHarmonic and Reactive Power Compensation in Three-Phase, Four-Wire Systems Supplying Non-Linear Loads, European TransactionsOn Electrical Power (ETEP), Vol. 8, No. 2, MarcMApril 1998, pp. 139-145
[5]
G.Tsengense, G.Adamidis,'' An Improved Current Control Techniquefor the Investigation of a Power System with a Shunt Active Filter'', InProc. Of International Symposium on Power Electronics, ElectricalDrives, Automation and Motion Conference, 2010,
[6]
Mara Isabel Milans Montero, Enrique Romero Cadaval and FermnBarrero Gonzlez,'' Comparison of Control Strategies for Shunt ActivePower Filters in Three-Phase Four-Wire Systems'' , IEEE Transactionson Power Electronics , Vol. 22, No. 1, Jan. 2007,pp 22
[7] T.C. Green and J.H. Marks, Control techniques for active powerfilters, IEE Procceding on Electric Power Application, Vol. 152, No. 2,March 2005.
[8]
N.Kroutikova, C.A.Hernandez and T.C.Green,'' State-Space Model ofGrid-Connected inverters Under Current Control Mode'', IETTransactions on Electr. Power Appl. Vol.1, No.3, May 2007, pp 329-338
2nd International Conference on Advances in Electrical and Electronics Engineering (ICAEEE'2013) Dec. 20-21, 2013 Bali (Indonesia)
59
-
8/11/2019 Control of a Shunt Active Power Filter
6/6
[9]
Guijun Yao, Lars Norum,'' New Transfer Function Model for PWMPower Converter'', In Proc. Of 16th Annual Conference of IndustrialElectronics Society (IECON), 27-30 Nov. 1990, pp 1135 - 1142
[10]
H.Y.Kanaan, A.Hayek and K.Al-Haddad,'' Averaged Model-BasedNonlinear Control of a PWM Three-Phase Four-Leg Shunt ActivePower Filter'', In Proc. of Canadian Conference on Electrical andComputer Engineering (CCECE), 22-26 April 2007, pp 1002 1005
[11]
Cheng-Che Chen and Yuan-Yih Hsu, A Novel Approach to the Designof a Shunt Active Filter for an Unbalanced Three-Phase Four-WireSystem under Nonsinusoidal Conditions, IEEE Treansactions on
Power Delivery, Vol. 15, No. 4, Oct. 2000, pp 1258 1264[12]
M. Asadi, A. Jalilian,An Improved Current Control Method of ShuntActive Power Filter Based on State-Space Variables UnderAsymmetrical and Non-Sinusiodal Conditions, In Proc.of the 5thInternational Power Engineering and Optimization Conference(PEOCO2011), Shah Alam, Selangor, Malaysia, June 2011.
2nd International Conference on Advances in Electrical and Electronics Engineering (ICAEEE'2013) Dec. 20-21, 2013 Bali (Indonesia)
60
http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=510http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=510http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=510http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=510