control of a scig wind farm connected to a single power converter

Upload: yo-molo-mazo

Post on 03-Jun-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Control of a SCIG Wind Farm Connected to a Single Power Converter

    1/6

    Control of a squirrel cage induction generator wind

    farm connected to a single power converter

    Llus Trilla, Oriol Gomis-Bellmunt , Adria Junyent-Ferre, Agust Egea Alvarez and Antoni Sudria-Andreu

    Catalonia Institute for Energy Research (IREC)

    Josep Pla 2, B2 Planta Baixa - 08019 Barcelona (Spain).

    Email: [email protected] dInnovacio Tecnologica en Convertidors Estatics i Accionaments (CITCEA-UPC)

    Departament dEnginyeria Electrica. Universitat Politecnica de Catalunya - 08028 Barcelona (Spain).

    AbstractThe aim of this paper is to analyze the control ofseveral wind power generators based on squirrel cage inductiongenerators with one common power converter. This configurationis especially useful for offshore wind farms with a VSC-HVDCtransmission. A comparison with a configuration where eachgenerator is connected to one power converter, is done focusingin the total power extraction. Scalar-controlled squirrel cageinduction generators have been implemented in both cases. Thecontrol scheme has been modified implementing an aggregatedmodel in order to allow the common converter to performappropriated control tasks. A fault ride-through control protectsthe DC bus from overvoltages, it varies the torque and slipreference to limit the total output power. Results have beenvalidated by means of simulation in both scenarios showing thedifferences in the total power obtained and the influence of thegenerator operating point. The performance of the system underonshore grid faults has been simulated.

    I. INTRODUCTION

    The increasing demand on clean energy is making the

    development of wind power more interesting [9]. Offshore

    options are becoming more appealing since the difficulty of

    finding good onshore locations with strong, regular winds thatare also close to the grid is increasing. Offshore wind farms

    situated further than 60 km from the shore can be connected to

    the grid through DC links [1] [11] [12]. In this case an offshore

    power converter has to perform the DC power conversion,

    different connection topologies have been studied by other

    authors [7] [10]. Transmission using HVDC requires a full

    power converter onshore that adapts the power to the needs

    of the grid. This transmission system has some advantages,

    as it smooths the impact of the wind farm on grid stability,

    especially in areas with weak AC systems.

    In modern wind power plants, usually each generator is

    controlled by one power converter, which keeps the machine

    working at its optimum operating point while maximizingwind power capture. As more devices are working in the

    wind farm the probability of failure of one of them becomes

    higher. This is an important factor because of the difficulties

    accessing an offshore park. In addition, each power converter

    adds a percentage to the energy loss and implies a higher initial

    investment.

    This paper analyzes a topology and control scheme where

    one power converter controls several machines at the same

    time. This configuration allows the wind farms to be divided

    into clusters, controlled with a reduced number of power

    converters. In the proposed scheme the control of various

    squirrel cage induction generators is performed by variation of

    system frequency and voltage, keeping the flux in the generator

    constant.

    Control actions have to manage a set of wind power

    generators. In order to calculate the control reference valuesan aggregated model has been implemented. These models

    are used in simulations of large wind farms testing different

    connection topologies [13]. In the aggregated model different

    incoming wind speeds are considered for each turbine, and

    the generator angular speed is measured with sensors, then

    the mean speed of all the machines is used by the controller

    to compute the frequency and the voltage.

    An analysis of the reaction when a wind speed change

    is done and a comparison between this configuration and a

    classic topology is presented here. A full power converter is

    necessary to convert the AC medium voltage to HVDC. As

    will be shown, the use of this converter to do control tasks,

    and the elimination of individual power converters leads toa poorer performance since the operating point of the park is

    moved away from the optimum. On the other hand the number

    of elements offshore is reduced and thus there is less energy

    loss.

    In order to keep the DC bus voltage constant the controller

    modifies the torque reference signal limiting the total output

    electrical power. The line fault ride through performance of

    the implemented control scheme is shown via simulation and

    the resultant effect of the torque control is analyzed.

    This paper is organized as follows: the wind farm connec-

    tion topology proposed is introduced in Section II, followed

    in Section III by a description of the model used. The control

    scheme is explained in Section IV and simulation results arepresented in Section V. Conclusions are in Section VI.

    I I . CONNECTION TOPOLOGY

    In order to test the capacity of controlling several machines

    in different operating points a common converter configuration

    is modelled. This topology consists of several wind power

    generators interconnected to the wind farm grid and controlled

    by one full power converter. The DC conversion for the trans-

    mission to the onshore grid is done by this power converter.

    UPEC2010

    31st Aug - 3rd Sept 2010

  • 8/12/2019 Control of a SCIG Wind Farm Connected to a Single Power Converter

    2/6

  • 8/12/2019 Control of a SCIG Wind Farm Connected to a Single Power Converter

    3/6

    D. Wind park grid and HVDC transmission

    A transformer is connected to each generator and a medium

    voltage AC grid has been considered. A high voltage trans-

    former delivers the total power to the offshore converter and

    the HVDC transmission cables are implemented according to

    the Cigre benchmark model [15].

    IV. CONTROL SCHEME

    A. Scalar Control

    The widely used scalar control [2], [4] has been imple-

    mented to drive multiple generators. The scalar-controlled

    devices have been used for a long time in industry for single

    machine control and are easy to implement, although they give

    inferior performance then vector control schemes. In general,

    the scalar control is applicable when the speed does not have

    to change rapidly in the machine.

    In this control scheme the ratio voltage/frequency

    (V olt/Hz) is kept constant. Assuming that the voltage isproportional to the frequency, flux amplitude is maintained

    constant = Use

    , neglecting stator resistance Rs.

    It is necessary to measure the generator speed and thus use acommunication link in order to send the data to the controller

    and compute the torque and the optimum torque. The slip

    frequency necessary to minimize the calculated error can be

    obtained with a classic PI. The torque is kept proportional to

    the slip while the machine is in the linear working area, which

    is close to zero slip speed.

    In the practical implementation a boost voltage U0 = Rsisis added in order to compensate the drop at the stator re-

    sistance. The boost voltage becomes important at low speeds

    because the stator resistance tends to absorb more voltage but

    is negligible at high frequencies.

    B. Aggregated ModelThere are several ways to simulate a wind farm [8], depend-

    ing on the topology of the park, the needs of the control or

    the variables of interest in the simulation.

    In this case it is important to note that the control system

    does not control each machine individually; instead, it obtains

    information about the whole set of generators. Thus, its task

    is to apply the proper control actions to all the machines at

    the same time. In order to get the data of the set of generators,

    it is worth aggregating the models at some point before the

    controller reads it. Fig. 2 illustrates the control scheme used.

    In this scheme the aggregation is performed once the rotor

    speed is sensed in each machine. When the whole set of speed

    of generators is computed the total torque can be calculated as = Pe

    gusing the total electric power obtained at the power

    converter.

    It is worth noting that the total power is obtained from

    the total voltage and current applied to the system. This

    fact prevents the controller computing the individual torque

    of each machine (even knowing their individual angular

    speed) because the actual power of each separate generator

    is unknown. In this scheme the mean speed (9) of all the

    generators involved has been used and the control action is

    computed as only one machine has to be controlled. Voltage

    and frequency, applied by the converter, are the same for all the

    generators because they are sharing the same grid. Other types

    of aggregation (e.g. torque, speed square) can be considered

    in order to improve the control performance but comparison

    of these techniques is out of the scope of this paper.

    g =

    N

    i=1gi

    N (9)

    Wheregi is the electrical angular speed of each generatorand N is the number of generators involved. The optimumtorque

    =KCp 2

    g (10)

    wherepis the number of pole pairs and r is the mechanicalangular speed of the rotor. Once the slip is computed with the

    PI controller the frequency can be calculated e = slip +g =slip+pr and be imposed to the system.

    C. Line Fault Ride Through

    During a voltage sag in the AC grid the capacity of energyevacuation of the onshore converter drops drastically. When

    the DC bus voltage increases and exceeds a minimum level

    the controller reduces the torque and the slip reference in order

    to decrease the amount of power generated. This reduction is

    proportional to the voltage level reached by the DC bus, if this

    voltage goes beyond a maximum level the torque and the slip

    reference are set to zero until the voltage is back to its nominal

    value. In Fig. 2 can be seen a schematic representation of the

    line fault ride through control.

    D. Onshore converter

    The VSC converter controls independently active and re-

    active power. This converter has to keep constant the HVDCvoltage adjusting the active power delivered to the grid and

    reactive power use to support the grid voltage when a line

    fault is detected as is implemented by [16]. There is no

    communication between offshore and onshore controllers and

    they act separately. When the system is facing a voltage dip the

    onshore converter has a limited rank of action, if the HVDC

    voltage control is lost the offshore controller starts to operate.

    V. SIMULATION RESULTS

    Topology and the control scheme have been tested in sim-

    ulation using Matlab/SimulinkR, modelling three turbines of

    2MW each one. Reactions when facing wind speed variations

    and their adaption to these changes for the whole set ofgenerators and each individual machine have been checked.

    In the model some simplifications have been made, en-

    ergy losses have been considered in cables, transformers and

    converters but harmonic distortion in power converter and

    transformer saturation are not considered. The parameters used

    to simulate the model of generator can be found in [5] and in

    Table I.

    Two different systems have been compared using the same

    wind series, the wind steps used can be seen at Fig. 3.

  • 8/12/2019 Control of a SCIG Wind Farm Connected to a Single Power Converter

    4/6

    Fig. 2. Control scheme

    TABLE IPARAMETERS OF THE GENERATOR IN P.U. 50HZ, 2MW, 690V

    Rs 0.048 R

    r 0.018 Xm 3.800Xs 0.075 X

    r 0.120

    5 10 15 20 25 30 35 408

    8.5

    9

    9.5

    10

    10.5

    11

    11.5

    12

    time(s)

    windspeed(m/s)

    Incoming wind speed

    Fig. 3. Incoming wind speed

    The system has a common power converter and three wind

    power generators. The controller performs the control tasks

    using the aggregated model. In order to show a comparison

    with classical topology another system is modelled connecting

    one power converter to each generator. The control schemeused in this case is a classic scalar control.

    The total power generated is shown in Fig. 4. Solid line

    represents the power generated with the common converter

    configuration, and the dashed line is the power generated

    with the individual topology. The results show variation in

    the power extracted when the incoming winds are different

    (the common power converter scheme generates less power

    because not all the machines are operating at their optimum

    point). In fact as the difference in the incoming winds received

    by the turbines increases, its optimum becomes further from

    the operating point, and thus less power is generated. However,

    when incoming winds are equal for the three turbines the

    power generated reaches its maximum level and becomes

    the same with both topologies, because all the turbines are

    working at their optimum level.

    10 15 20 25 30 35 400.52

    0.525

    0.53

    0.535

    0.54

    0.545

    0.55

    time(s)

    Power(p.u.)

    Total electric power

    Common converter

    Individual converter

    Fig. 4. Total electrical power extracted

    The individual power generated by each machine is plotted

    in Fig. 5 where the horizontal lines mark the limit of the energy

    extraction (this limit is reached with the individual converter

    topology). As can be seen turbine number 2 is operating closeto its optimum because its operating point is in the middle of

    the other two turbines.

    The maximum energy extraction is reached when the Cp co-efficient reaches its optimum, in Fig 6. is shown the evolution

    of this parameter.

    In order to check the performance of the LFRT control a

    voltage sag to the 0.1 p.u. has been simulated, Fig. 7. Wind

    speed is kept constant but different for each turbine. The

    evolution of the torques (solid lines) of the machines and the

  • 8/12/2019 Control of a SCIG Wind Farm Connected to a Single Power Converter

    5/6

  • 8/12/2019 Control of a SCIG Wind Farm Connected to a Single Power Converter

    6/6

    10 11 12 13 14 15 16 17 18 19 200.9

    0.95

    1

    1.05

    1.1

    1.15

    time(s)

    Voltage

    (p.u

    )

    DC voltage

    Fig. 9. HVDC voltage

    10 11 12 13 14 15 16 17 18 19 200

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    time(s)

    Power(p.u.)

    Total electrical power

    Electric power

    Fig. 10. Total power

    without strong transient states.

    APPENDIX

    The parameters used to model the turbine can be find in

    Table II.

    TABLE II

    PARAMETERS OF TURBINE

    Inertia 16 105 kg m2 Gear ratio 65.27 c2 116 c7 21Radius 37.5 m c1 0.5 c6 5 c9 0.035

    ACKNOWLEDGMENT

    This work was supported by the Ministerio de Ciencia e

    Innovacion under the project ENE2009-08555.

    10 11 12 13 14 15 16 17 18 19 20134

    136

    138

    140

    142

    144

    146

    148

    time(s)

    An

    gularspeed(rad/s)

    Angular speed

    Generator1

    Generator2

    Generator3

    Electrical angular speed

    Fig. 11. Mechanical and electrical speeds

    REFERENCES

    [1] N.M. Kirby, M.J. Luckett, L. Xu, W. Siepmann.HVDC transmission forlarge off shore wind farms. IEE AC-DC Power Transmission, pp. 162-168, Conference Publication No. 485, London 2001.

    [2] M.P. Kazmierkowski, R. Krishnan, F. blaabjerg. Control in Power Elec-tronics: Selected Problems. Academic Press, 2002.

    [3] D. Jovcic, N. Strachan. Offshore wind farm with centralised powerconversion and DC interconnection. IET Gener. Transm. Distrib., Vol.3, Iss. 6, pp. 586-595, 2009.

    [4] B.K. Bose. Modern Power Electronics and AC Drives. Prentice-Hall,2001.

    [5] A. Sumper, O. Gomis-Bellmunt, A. Sudria-Andreu, R. Villafafila-Robles,J. Rull-Duran. Response of Fixed Speed Wind Turbines to System Fre-quency Disturbances. IEEE Transactions on Power Systems. Vol. 24, No.1, February 2009.

    [6] X. Liu, S. Islam. Reliability issues of Offshore Wind Farm Topology.Probabilistic Methods Applied to Power Systems. PMAPS 08. pp.1-5,25-29 May 2008.

    [7] K. Zhou, X. Fu, M. Cheng, X. Zhu, W. Wang, T. Wang. Topologiesand Control of VSC-HVDC Systems for Grid Connection of Large-ScaleOff-Shore Wind Farms. Electrical Machines and Systems. ICEMS 2008.pp.2357-2361, 17-20 Oct. 2008

    [8] L.M. Fernandez, J.R. Saenz, F. Jurado. Dynamic models of wind farmswith fixed speed wind turbines. Renewable Energy, Vol. 31, Iss 8, pp.1203-1230, July 2006.

    [9] L. Wang, J. Wei, X. Wang, X. Zhang.The development and prospect ofoffshore wind power technology in the world WNWEC 2009, pp.1-4,September 2009.

    [10] D. Jovcic.Interconnecting offshore wind farms using multiterminal VSC-based HVDC. Power Engineering Society General Meeting, 2006. IEEE.

    [11] A.B. Morton, S. Cowdroy, J.R.A. Hill, M. Halliday, G.D. Nicholson.AC or DC? economics of grid connection design for offshore wind farmsACDC 2006. The 8th IEE International Conference on, pp. 236-240,March 2006.

    [12] F. Wang, P. Yunqing, D. Boroyevich, R. Burgos, K. Ngo. Ac vs. dcdistribution for off-shore power delivery. IECON 2008. 34th AnnualConference of IEEE, pp.2113-2118, November 2008.

    [13] J.G. Slootweg, W.L. Kling. Aggregated modelling of wind parks inpower system dynamics simulations. Power Tech Conference Proceedings,2003 IEEE Bologna. Vol.3, pp. 6, June 2003.

    [14] Z. Lubosny. Wind Turbine Operation In Electric Power Systems: Ad-vanced Modeling. Ed Springer-Verlag New York. September 2003.

    [15] M. Szechtman, T. Wess, C.V. Thio. First benchmark model for HVDCcontrol studies. Electra, no. 135, pp. 54-67. April 1991.

    [16] O. Gomis-Bellmunt, A. junyent-Ferr, A. Sumper, J. Bergas-Jan. RideThrough control of a doubly fed induction generator under unbalancedvoltage sags, IEEE Transactions on energy Conversion, vol, 23. no 4. pp.1036-1045, 2008.