contents 1 introduction 2 vlt functional...

31
Contents 1 Introduction 3 Safety 3 Introduction 4 About this Manual 4 Assumptions 4 HP/kW conversion 5 2 VLT Functional Features 7 Drive Operation (03-14) 7 Motor and Drive Thermal Protection (15, 16, 18) 7 Set-up 1-4 and Day/Night operation (17, 29) 7 Current Monitoring and Limits (19) 7 Direction of Rotation (22) 7 Start/Stop (23) 7 Freeze Mode (25, 26) 8 Coast (27, 28) 8 Motor Ramp-up and Ramp-down Rate (31, 32) 8 Hand/Auto Modes (34) 8 CMD RUN STOP (35) 8 Bus Functions (36, 37) 8 Jog Frequency and Command (38, 39) 8 Relay Out 1, 2 (40, 41, 43, 44) 8 PID Control Functions (61-65) 8 Sleep Mode (59) 9 Terminals 53, 54, (87-88) 9 Warnings and Alarms (90-94) 9 Error Status (99) 9 3 VLT Network Strategies 11 Strategy one 11 Strategy two 11 Strategy three 12 Strategy four 12 4 VLT Special Functions 15 Special functions 15 Analog input monitoring 15 Drive relay control 15 5 Network Connection 17 VLT ® HVAC Drive FLN Operating Instructions Contents MG.11.Z2.02 - VLT is a registered Danfoss trademark 1

Upload: vuongkhanh

Post on 27-Sep-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

Contents

1 Introduction 3

Safety 3

Introduction 4

About this Manual 4

Assumptions 4

HP/kW conversion 5

2 VLT Functional Features 7

Drive Operation (03-14) 7

Motor and Drive Thermal Protection (15, 16, 18) 7

Set-up 1-4 and Day/Night operation (17, 29) 7

Current Monitoring and Limits (19) 7

Direction of Rotation (22) 7

Start/Stop (23) 7

Freeze Mode (25, 26) 8

Coast (27, 28) 8

Motor Ramp-up and Ramp-down Rate (31, 32) 8

Hand/Auto Modes (34) 8

CMD RUN STOP (35) 8

Bus Functions (36, 37) 8

Jog Frequency and Command (38, 39) 8

Relay Out 1, 2 (40, 41, 43, 44) 8

PID Control Functions (61-65) 8

Sleep Mode (59) 9

Terminals 53, 54, (87-88) 9

Warnings and Alarms (90-94) 9

Error Status (99) 9

3 VLT Network Strategies 11

Strategy one 11

Strategy two 11

Strategy three 12

Strategy four 12

4 VLT Special Functions 15

Special functions 15

Analog input monitoring 15

Drive relay control 15

5 Network Connection 17

VLT® HVAC Drive FLN Operating Instructions Contents

MG.11.Z2.02 - VLT is a registered Danfoss trademark 1

6 Parameters 19

Parameter settings 19

7 Start-up and Troubleshooting 21

Start-up 21

Start-up of FLN control 21

Troubleshooting 21

Faults, warnings and alarms 21

Alarms and warnings 21

Index 30

Contents VLT® HVAC Drive FLN Operating Instructions

2 MG.11.Z2.02 - VLT is a registered Danfoss trademark

1 Introduction

1.1 Safety and Caution

1.1.1 Safety

Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical work conform to

National Electrical Code (NEC) and all local regulations. Installation, start-up and maintenance should be performed only by qualified

personnel.

Factory recommended procedures, included in this manual, should be followed. Always disconnect electrical power before working on the unit. Although

shaft couplings or belt drives are generally not furnished by the manufacturer, rotating shafts, couplings and belts must be protected with securely

mounted metal guards that are of sufficient thickness to provide protection against flying particles such as keys, bolts and coupling parts. Even when the

motor is stopped, it should be considered “alive” as long as its controller is energized. Automatic circuits may start the motor at any time. Keep hands

away from the output shaft until the motor has completely stopped and power is disconnected from the controller.

Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be

exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit

to use only one hand when checking components. Always work with another person in case of an emergency. Disconnect power whenever possible to

check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating

equipment.

Safety Guidelines

1. The drive must be disconnected from the AC line before any service work is done.

2. The “Stop/Off” key on the LCP of the drive does not disconnect the equipment from the AC line and is not to be used as a safety switch.

3. Correct protective grounding of the equipment must be established. The user must be protected against supply voltage and the motor must be

protected against overload in accordance with applicable national and local regulations.

4. Ground currents are higher than 3 mA.

Warning against Unintended Start

1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or

references. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stops are not sufficient.

2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing

parameters.

3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC

line or a fault in the motor connection or other fault clears.

4. If the “Local/Hand” key is activated, the motor can only be brought to a stop by means of the “Stop/Off” key or an external safety interlock

NB!

It is responsibility of user or person installing drive to provide proper grounding and branch circuit protection for incoming power and

motor overload according to National Electrical Code (NEC) and local codes.

The Electronic Thermal Relay (ETR) in UL listed VLTs provides Class 20 motor overload protection in accordance with NEC in single motor applications,

when par. 1-90 Motor Thermal Protection is set for ETR TRIP 1, ETR TRIP 2, ETR TRIP 3, or ETR TRIP 4, and par. 1-24 Motor Current is set for rated

motor (nameplate) current.

The frequency converter DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard,

disconnect the frequency converter from the mains before carrying out maintenance. Wait at least as follows before doing service on

the frequency converter:

VLT® HVAC Drive FLN Operating Instructions 1 Introduction

MG.11.Z2.02 - VLT is a registered Danfoss trademark 3

1

Voltage (V) Min. Waiting Time (Minutes)

4 15 20 30 40

200 - 240 1.1 - 3.7 kW 5.5 - 45 kW

380 - 480 1.1 - 7.5 kW 11 - 90 kW 110 - 250 kW 315 - 1000 kW

525-600 1.1 - 7.5 kW 11 - 90 kW

525-690 11 - 90 kW 45 - 400 kW 450 - 1400 kW

Be aware that there may be high voltage on the DC link even when the LEDs are turned off.

1.3.1 Introduction

The Siemens Floor Level Network (FLN) is a master/ slave control network for serial communication with various control devices. The FLN controller is

RS-485 compatible, half duplex, with an operating rate of 4800 or 9600 baud. Recommended wiring is shielded, twisted pair. The FLN software protocol

is designed to be general in nature to accommodate any unique properties of each device type. The node address system allows up to 96 devices to be

used on any one system.

The Danfoss VLT is a programmable frequency converter, which controls the operation of 3-phase, standard induction electrical motors in the HVAC

industry. The VLT control card has FLN communication protocol software built-in. The drive uses optical isolation for fault tolerance and noise immunity.

The FLN communicates directly with the VLT via the RS-485 serial interface bus. In addition to being able to control the drive, most drive configuration

and control parameters can be reviewed and changed through the FLN. Also, the operational status of the drive can be read and monitored through the

bus. Diagnostic and operational information stored in the VLT is easily available, such as kWh of energy used, total operation hours, drive status, motor

speed, and many other useful items which can be accessed and monitored through the FLN.

The FLN is designed to communicate with any controller node that supports the interfaces defined in this document.

1.3.2 About this Manual

The documentation in this manual provides comprehensive information on the connection, programming, and startup of the VLT for use with the FLN. It

is intended as both an instruction and reference manual. Functions and features of the VLT are also briefly reviewed to serve as a guideline to optimize

your communication system. Read this manual before programming since important information is provided in each section. For detailed information on

using the VLT, see the Operating Instructions.

1.3.3 Assumptions

This manual assumes that the controller node supports the interfaces in this document and that all the requirements and limitations stipulated in the

controller node and the VLT are strictly observed. It is assumed that the user understands the general capabilities and limitation of the controller node

and the VLT.

1.3.4 Available literature for VLT HVAC Drive

- Operating Instructions MG.11.Ax.yy provide the necessary information for getting the frequency converter up and running.

- Operating Instructions VLT HVAC Drive High Power, MG.11.Fx.yy

- Design Guide MG.11.Bx.yy entails all technical information about the frequency converter and customer design and applications.

- Programming Guide MG.11.Cx.yy provides information on how to programme and includes complete parameter descriptions.

- Mounting Instruction, Analog I/O Option MCB109, MI.38.Bx.yy

- Application Note, Temperature Derating Guide, MN.11.Ax.yy

- PC-based Configuration Tool MCT 10, MG.10.Ax.yy enables the user to configure the frequency converter from a Windows™ based PC environ-

ment.

1 Introduction VLT® HVAC Drive FLN Operating Instructions

4 MG.11.Z2.02 - VLT is a registered Danfoss trademark

1

- Danfoss VLT® Energy Box software at www.danfoss.com/BusinessAreas/DrivesSolutions then choose PC Software Download

- VLT® VLT HVAC Drive Drive Applications, MG.11.Tx.yy

- Operating Instructions VLT HVAC Drive Profibus, MG.33.Cx.yy.

- Operating Instructions VLT HVAC Drive Device Net, MG.33.Dx.yy

- Operating Instructions VLT HVAC Drive BACnet, MG.11.Dx.yy

- Operating Instructions VLT HVAC Drive LonWorks, MG.11.Ex.yy

- Operating Instructions VLT HVAC Drive Metasys, MG.11.Gx.yy

- Operating Instructions VLT HVAC Drive FLN, MG.11.Zx.yy

- Output Filter Design Guide, MG.90.Nx.yy

- Brake Resistor Design Guide, MG.90.Ox.yy

x = Revision number

yy = Language code

Danfoss technical literature is available in print from your local Danfoss Sales Office or online at:

www.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/Technical+Documentation.htm

1.3.5 Abbreviations and standards

Abbreviations: Terms: SI-units: I-P units:a Acceleration m/s2 ft/s2

AWG American wire gauge Auto Tune Automatic Motor Tuning

°C Celsius I Current A Amp

ILIM Current limit Joule Energy J = N∙m ft-lb, Btu°F Fahrenheit FC Frequency Converter f Frequency Hz Hz

kHz Kilohertz kHz kHzLCP Local Control Panel mA Milliampere ms Millisecond min Minute MCT Motion Control Tool

M-TYPE Motor Type Dependent Nm Newton Metres in-lbsIM,N Nominal motor current fM,N Nominal motor frequency PM,N Nominal motor power UM,N Nominal motor voltage par. Parameter PELV Protective Extra Low Voltage Watt Power W Btu/hr, hp

Pascal Pressure Pa = N/m² psi, psf, ft of waterIINV Rated Inverter Output Current RPM Revolutions Per Minute SR Size Related T Temperature C Ft Time s s,hr

TLIM Torque limit U Voltage V V

Table 1.1: Abbreviation and standards table .

1.3.6 HP/kW conversion

A conversion index for determining kW and HP ratings is shown below.

VLT® HVAC Drive FLN Operating Instructions 1 Introduction

MG.11.Z2.02 - VLT is a registered Danfoss trademark 5

1

kW HP kW HP0.25 0.33 45 600.37 0.5 55 750.55 0.75 75 1000.75 1.0 90 1251.1 1.5 110 1501.5 2.0 132 1752.2 3.0 160 2003.0 4.0 200 3004.0 5.0 250 3505.5 7.5 315 3507.5 10 355 45011 15 400 50015 20 450 600

18.5 25 22 30 30 40 37 50

1 Introduction VLT® HVAC Drive FLN Operating Instructions

6 MG.11.Z2.02 - VLT is a registered Danfoss trademark

1

2 VLT Functional Features

The FLN protocol built into the VLT frequency converter allows programming of numerous features and monitoring of the drive via the serial bus and the

standard RS-485 port. The VLT also has the capability to control closed or open loop systems on its own and has been designed specifically for HVAC

applications. Always accessible in real-time are the system status, what the motor and drive are doing, and if there are any problems. The VLT continuously

monitors all aspects of motor and drive status and issues alarms or warnings for adverse conditions. The FLN interacts with the drive based upon a point

map database and the selected interface strategy. Many, but not all, drive features are accessible through the point map. See the Operating Instruc-

tions for more drive details. Table Point Mapping lists the map points and Table Point database definitions supplies definitions. Below is a review of some

frequently used drive features and the associated point map numbers.

2.1.1 Drive Operation (03-14)

These points provide the FLN with operational status information such as output frequency, motor current, output voltage, power and energy. The run

time in hours that power has been supplied to the motor is also stored for display, along with cumulative energy used in kWh.

2.1.2 Motor and Drive Thermal Protection (15, 16, 18)

The motor and drive are protected against thermal overload. The percentage of thermal load is displayed. Point 18 indicates if either the motor or drive

thermal limit has been exceeded.

2.1.3 Set-up 1-4 and Day/Night operation (17, 29)

In the FLN system it is not recommended to operate in multible set-up. The drive should remain in Set-up 1 at all times.

The drive is capable of maintaining four independent program set-ups. Each set-up supports independent point map configurations. Seasonal changes,

various acceleration or deceleration rates, or other operation modes can be accommodated. Point 17 indicates which setup is active. The set-up change

is programmed through the drive’s keypad or digital I/Os. Day/night operation is implemented in the point map (29).

2.1.4 Current Monitoring and Limits (19)

The maximum current that the drive provides to the motor can be limited. This tends to limit the torque that can be produced by the motor. Data point

19 indicates if the motor is operating at that current limit.

2.1.5 Direction of Rotation (22)

The drive responds to serial commands to reverse direction of the motor. The drive can safely reverse motor rotation while in operation. Many applications

benefit from this ability, such as vane axial fans reversed for smoke extraction or cooling towers for deicing. par. 8-54 Reversing Select, must be set to

serial communication for point 22 to command the feature.

2.1.6 Start/Stop (23)

To run the drive from the FLN or in Auto mode from the drive‘s digital control terminals, a start command must be given at data point 23. When a stop

command is given at this point, the drive will only run in Hand mode.

2.1.7 Ramp Select (24)

Datapoint 24 selects the active ramp.

VLT® HVAC Drive FLN Operating Instructions 2 VLT Functional Features

MG.11.Z2.02 - VLT is a registered Danfoss trademark 7

2

2.1.8 Freeze Mode (25, 26)

If desired, the frequency of the drive can be frozen at its present value. The mode is indicated by data point 25. It is an option available when serial

interface is lost.

2.1.9 Coast (27, 28)

The coast command (28) shuts down the inverter and makes the motor freewheeling, which normally brings it to stand still. The drive cannot be restarted

in any mode before the coast command is removed. It is, therefore, often used as a safety interlock. Data point 27 indicates when the drive is coasted.

2.1.10 Motor Ramp-up and Ramp-down Rate (31, 32)

The time to accelerate or decelerate the drive between 0 Hz and the motor’s nominal frequency can be programmed. The drive is capable of settings

between one to 3600 seconds (one hour). Only Ramp1 is accessible from the FLN network.

2.1.11 Hand/Auto Modes (34)

The SEL HND.AUTO shows which mode the drive is in. The drive can be commanded into either Hand or Auto mode by pressing the respective keys on

the keypad of the drive. Hand mode disables any programmed control strategies and allows the drive keypad to be used to set the drive speed. The only

serial communication command that can override Hand mode is data point 28, CMD COAST.

2.1.12 CMD RUN STOP (35)

Set data point 35 to ON to run the drive from the FLN with default drive parameter settings. In the OFF mode, the drive will run only in Hand mode or

in Auto mode from the drive‘s digital control terminals. par. 8-53 Start Select, controls the interaction of point 35 and the digital run command.

2.1.13 Bus Functions (36, 37)

The amount of time the drive will wait between communication packets is programmable. If the time is exceeded, the drive will assume serial commu-

nication has stopped and respond with programmable choices. The drive can ignore the loss, freeze its current output, stop, run at a predetermined jog

frequency, run at maximum output frequency or stop and trip while issuing an alarm. Wait time is selected at point 36 and the function after a timeout

at point 37. See descriptions for par. 8-03 Control Timeout Time and par. 8-04 Control Timeout Function in the VLT HVAC Drive Programming Guide.

2.1.14 Jog Frequency and Command (38, 39)

The Jog Frequency can be set by data point 38. Setting data point 39 to [On] will cause the frequency converter to send the Jog Frequency to the motor.

2.1.15 Relay Out 1, 2 (40, 41, 43, 44)

Two programmable relay outputs (Form C, 240 VAC, 2 Amp) are available. These can be triggered through the serial bus by command points 40 and 41.

This allows the FLN to utilize the drive’s built-in relays as additional network programmable relays. The data points 43 and 44 indicate whether the relay

is triggered or not (On/Off). Parameters 5-40.0 and 5-40.1, Function Relay 1 and Function Relay 2, must be set to [45] Bus controlled, [46] Bus controlled

1, if timeout or [47] Bus controlled 0, if timeout.

2.1.16 PID Control Functions (61-65)

The VLT has a sophisticated built-in proportional, integral, derivative (PID) controller. The PID controller is activated by setting par. 1-00 Configuration

Mode, to Closed loop through the drive’s keypad.

2 VLT Functional Features VLT® HVAC Drive FLN Operating Instructions

8 MG.11.Z2.02 - VLT is a registered Danfoss trademark

2

The PID controller in the VLT supports two feedback values and two setpoints. The feedback can be received in the form of network bus signals and/or

standard 0-10 V transmitters. The 2 set-point controller is capable of controlling return fans based on a fixed differential flow, secondary pumping systems,

and so on. This can be used to supplement the BMS system to save on points or capacity. For details on use of the two feedback/setpoint feature, refer

to the Operating Instructions. Data points 43 and 44 show the status of an FLN command to the drive.

The points PI GAIN and PI TIME are gain parameters similar to the P and I gains in the FLN TECs. The Danfoss PI loop is structured differently than the

Siemens loop, so there is not a one-to-one correspondence between the gains. The following formulas allow translation between Danfoss and Siemens

gains.

Converting from Danfoss PI gains to Siemens P and I gains:

P GainSIEMENS = PI GainDANFOSS × 0.0015I GainSIEMENS =

PI GainDANFOSSPI Time DANFOSS

× 0.0015

Converting from Siemens P and I gains to Danfoss PI gains:

PI GainDANFOSS = P GainSIEMENS × 667PI Time DANFOSS =

P GainSIEMENSI GainSIEMENS

× 667

2.1.17 Sleep Mode (59)

Sleep mode automatically stops the drive when demand is low over a period of time. When the system demand increases, the drive restarts the motor

to reach the desired output. Sleep mode has great energy savings potential and saves wear and tear on equipment. Unlike a setback timer, the drive is

always available to run when a preset “wakeup” demand is reached. See parameter group 22-4* Sleep Mode and 22-2* No-Flow Detection in the VLT

HVAC Drive Programming Guide for more detail.

2.1.18 Terminals 53, 54, (87-88)

Two analog voltage/current input terminals 53 and 54 (0-10 VDC)/(0-20 mA) are provided for reference or feedback signals. The applied electrical signal

can be read by data points 87 to 88 in volts and mA. This can be very useful during commissioning to calibrate transmitters. This can also be used to

convert any other analog transmitter in the installation into a digital bus signal, even if the signal is not used by the drive. In this case, the input terminal

should be programmed to No Function so it does not influence the operation of the drive.

2.1.19 Warnings and Alarms (90-94)

The drive displays a warning or tripped by a fault condition. It also can retrieve the last warning or fault trip for display. The drive can be reset through

the FLN serial bus to resume normal drive operation.

2.1.20 Error Status (99)

Data point 99 is implemented in the point map but is not used in this application.

VLT® HVAC Drive FLN Operating Instructions 2 VLT Functional Features

MG.11.Z2.02 - VLT is a registered Danfoss trademark 9

2

3 VLT Network Strategies VLT® HVAC Drive FLN Operating Instructions

10 MG.11.Z2.02 - VLT is a registered Danfoss trademark

3

3 VLT Network Strategies

The VLT has its own internal PID closed loop controller. This can be turned on or off, depending on the requirements of the control strategy. A brief

summary of possibilities follows. This is meant to illustrate possibilities rather than be all-inclusive. An actual application may combine features from a

more than one of these strategies.

3.1.1 Strategy one

FLN Function – Monitor drive operation

FC Control – From a conventional, hardwired system

FC Mode – Open Loop.

The VLT follows hard-wired run/stop signals. An external, hard-wired PID controller provides the drive with a speed reference signal. The FLN monitors

the operation of the drive without control function.

Network Inputs to the VLT:

Because the FLN is simply monitoring the operation of the drive, it provides no inputs.

Network Outputs from the VLT:

The following points are monitored by the FLN to indicate system status. This list could be expanded or shortened, depending on the requirements of

the system.

03 FREQ OUTPUT

08 POWER 10 KWH

23 STOP.RUN

92 ALARM

3.1.2 Strategy two

FLN Function – Control all aspects of frequency converter operation

FC Control – From FLN network

FC Mode – Open Loop

The frequency converter follows run/stop and speed reference signals from the FLN. The FLN receives the feedback signal from the controlled system,

compares this to a set-point value, and uses its own PID control loop to determine the required drive speed.

Network Inputs to the frequency converter:

The following drive points might be controlled by the FLN.

Speed Command:

53 CMD REF This is the speed reference command. This is set as a percentage of the drive’s reference range, determined

by par. 3-02 Minimum Reference and par. 3-03 Maximum Reference. Setting point 53 to 0 gives the drive a reference command

equal to the value stored in par. 3-03 Maximum Reference. Setting point 53 to 16384 gives the drive a reference command

equal to the value stored in par. 3-03 Maximum Reference. Intermediate values for point 53 change the reference linearly

between these two values.

NB!

In general, any other reference signal is added to the bus reference. Disable all other drive reference inputs when using a bus reference

to control drive speed.

Start/Stop Command:

To give a start command from the FLN, the following points must be set. The frequency converter can also respond to discrete run/stop control signals

that are hard wired to its control terminals. The point used to stop the frequency converter through the FLN determines the capability of these discrete

command signals.

VLT® HVAC Drive FLN Operating Instructions 3 VLT Network Strategies

MG.11.Z2.02 - VLT is a registered Danfoss trademark 11

3

28 CMD COAST In most cases, it is necessary to set this point to [NO] to make the drive run. If this is set to [COAST]

while the VLT is running, the drive will shut off immediately and the motor will coast to a stop. When

set to [COAST], the lower right corner of the drive display shows Coast. The drive will not start in either

HAND mode or through discrete control signals until point 28 is set to [NO]. VLT par. 8-50 Coasting

Select, can defeat this. See the VLT HVAC Drive Operating Instructions for details. Because point 28

can keep the drive from operating in any mode, this is commonly used to provide a safety interlock

function.

35 RUN ENABLE In most cases, it is necessary to set this point [ON] to make the drive run. If this is set to [OFF] while

the drive is running, the drive will decelerate to a stop. When set to [OFF], the lower right corner of

the display shows STAND BY. When OFF, the drive can be started in HAND mode from the keypad. It

can also be started using a hard-wired discrete run command, as when par. 8-53 Start Select, is set

to digital input.

Network Outputs from the VLT:

The points listed in Strategy One are commonly used.

3.1.3 Strategy three

FLN Function – Monitor frequency converter operation

FC Control – From a hard-wired system, including system feedback

FC Mode – Closed Loop

The frequency converter follows hard-wired run/stop signals. It uses its internal PID controller to control motor speed. The feedback signal is hard wired

to the analog input and the set-point is programmed into the drive. The FLN is used to monitor the status of the FC and the value of the PID controller

set-point and feedback.

Network Inputs to the frequency converter:

Because the FLN is simply monitoring the operation of the frequency converter, it provides no inputs.

Network Outputs from the frequency converter:

In addition to the points listed in Strategy One, it may be useful to monitor the following points related to the operation of the PID controller.

Feedback:

53 CMD REF This is the set-point for the PID controller. Please consult the VLT HVAC Drive Design Guide for further information

on how to set up the PID controller.

65 FEEDBACK This is the value of the feedback signal in % for the PID controller.

3.1.4 Strategy four

FLN Function – Provide the frequency converter with set-point and feedback values using the PID controller to determine motor speed

FC Control – From the FLN

FC Mode – Closed Loop

The frequency converter follows run/stop signals from the FLN. The FLN receives the feedback signal from the controlled system. It sends this and the

desired set-point to the PID controller. The frequency converter compares the feedback signal with the set-point and adjusts the speed of the FC ac-

cordingly.

3 VLT Network Strategies VLT® HVAC Drive FLN Operating Instructions

12 MG.11.Z2.02 - VLT is a registered Danfoss trademark

3

Network inputs to the frequency converter:

In addition to start/stop control, which was discussed in Strategy Two, the FLN provides the frequency converter with feedback and set-point information

using the following points.

Feedback:

69 BUS FBK 1 A value of -163.83 % represents the minimum feedback signal. A value of +163.83 % represents the maximum

feedback signal. This should be the feedback used if only one feedback signal is supplied to the frequency converter.

NB!

If the frequency converter terminal 53 is programmed by means of par. 20-00 Feedback 1 Source, for feedback, any signal applied to

terminal 54 is added to value provided at point 53 CMD REF. Therefore, it is generally advisable not to program par. 20-00 Feedback

1 Source for feedback.

Example:

In a cooling tower application, the feed-back signal comes from a temperature sensor with a range of 40 °F to 140 °F. To unbundle BUS FBK 2 (point

70) for the temperature sensor:

1. Set par. 20-13 Minimum Reference/Feedb. to 40.

2. Set par. 20-14 Maximum Reference/Feedb. to 140.

3. Intercept = 40 (since the minimum feedback value is 40)

4. Slope can be calculated as follows:

Slope = (Desired Range) × (Slope of Existing Point)Range of Existing Point = (140 − 40) × 0.1

16383 = 0.00061

Set-point:

66 SET-POINT 1 This is the PID controller’s set-point, expressed in the units that were chosen in par. 20-02 Feedback 1 Source

Unit. It can be set to any value between par. 3-02 Minimum Reference and par. 3-03 Maximum Reference. If an

attempt is made to set point 69 to a value outside of this range, the set-point will not be changed. SET-POINT 1 can

also be programmed using par. 20-21 Setpoint 1.

67 SET-POINT 2 This PID controller's set-point is used for applications, where multible feedback signals will be compared to inde-

pendent set-points. Refer to the VLT HVAC Drive Design Guide for more details. SET-POINT 2 is expressed in the

units selected in par. 3-03 Maximum Reference. If an attempt is made to assign point 70 to a value outside of this

range, the set-point will not change. Set-point 2 can also be programmed using par. 20-22 Setpoint 2.

PID Controller Adjustments:

The following points adjust the operation of the PID control loop. They are generally set during start-up and only adjusted if changes in the system require

it. These values can also be set using parameters. See the VLT HVAC Drive Programming Guide for more details.

61 PI START FREQ

(par. 20-83 PID Start Speed

[Hz])

This sets the frequency to which the FC will accelerate following a start command. After it reaches this fre-

quency, the frequency converter will activate its PID controller. Point 61 can have a value between the drive’s

minimum frequency (as set in par. 4-12 Motor Speed Low Limit [Hz]) and its maximum frequency (as set in

par. 4-13 Motor Speed High Limit [RPM]). If an attempt is made to set point 61 to a value outside of this range,

the drive value will not change.

63 PI GAIN (par. 20-93 PID

Proportional Gain)

This sets the value of proportional gain for the PID controller. It can have a value between 0 and 10.

Network Outputs from the VLT:

The points listed in Strategy One are commonly used.

VLT® HVAC Drive FLN Operating Instructions 3 VLT Network Strategies

MG.11.Z2.02 - VLT is a registered Danfoss trademark 13

3

4 VLT Special Functions VLT® HVAC Drive FLN Operating Instructions

14 MG.11.Z2.02 - VLT is a registered Danfoss trademark

4

4 VLT Special Functions

4.1.1 Special functions

In addition to the control strategies described above, the frequency converter provides additional control flexibility to allow it to integrate into special

control system requirements. The following are just a few examples.

4.1.2 Analog input monitoring

Points 87 and 88 can be used to monitor the value of the analog control signals applied to terminals 53 and 54. These points are active even when NO

FUNCTION is programmed for the analog input of the drive. As a result, it is possible to use the frequency converter analog inputs as analog input for

the FLN.

4.1.3 Drive relay control

While relay 1 and 2 in the FC usually provide drive status indications, these indications are generally not needed, when the drive is connected to a FLN

network. In some applications, it can be useful to have the FLN control these relays. For example, by controlling one of the relays, the FLN could select

the active pump in a pump sequencing system. For the FLN to control a drive relay, the appropriate FC parameter (5-40.0 or 5-40.1) must be set to [Bus

Control]. Setting point 40 or 41 to [On] will then activate the corresponding relay.

VLT® HVAC Drive FLN Operating Instructions 4 VLT Special Functions

MG.11.Z2.02 - VLT is a registered Danfoss trademark 15

4

5 Network Connection VLT® HVAC Drive FLN Operating Instructions

16 MG.11.Z2.02 - VLT is a registered Danfoss trademark

5

5 Network Connection

5.1.1 Network connection

Connect the frequency converter to the RS-485 network as follows (see also diagram):

1. Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on the main control board of the frequency converter.

2. Connect the cable screen to the cable clamps.

NB!

Screened, twisted-pair cables are recommended in or-

der to reduce noise between conductors.

Illustration 5.1: Network Terminal Connection

����

����

���

Illustration 5.2: Control card terminals

5.1.2 Frequency converter hardware setup

Use the terminator dip switch on the main control board of the frequency

converter to terminate the RS-485 bus.

Illustration 5.3: Terminator Switch Factory Setting

The factory setting for the dip switch is OFF.

5.1.3 Electrical installation

NB!

Electrical installation: Please see VLT HVAC Drive Operating Instructions, MG.11.Ax.yy.

x=version ; yy=language code.

VLT® HVAC Drive FLN Operating Instructions 5 Network Connection

MG.11.Z2.02 - VLT is a registered Danfoss trademark 17

5

6 Parameters VLT® HVAC Drive FLN Operating Instructions

18 MG.11.Z2.02 - VLT is a registered Danfoss trademark

6

6 Parameters

6.1.1 Parameter settings

The frequency converter has a unique FLN address, which is transmitted over the RS-485 serial bus. The network will recognize the FC, which may then

be programmed for setup options. The parameters listed in the table below need to be set for each FC on the FLN network. FLN communication related

parameters can only be set by using the LCP.

NB!

As a minimum, it is required to set par. 8-30 Protocol to FLN; par. 8-31 Address, to the proper address and par. 8-32 Baud Rate to the

proper baud rate. (See VLT HVAC Drive Programming Guide).

Par. 8-50 Coasting Select through par. 8-56 Preset Reference Select are options that select control of the drive through the digital and/or the FLN serial

port.

Parameter Default Desired setting

*par. 8-03 Control Timeout Time 0

*par. 8-04 Control Timeout Function 0ff

*par. 8-30 Protocol FC FLN

*par. 8-31 Address 1 through 98

*par. 8-32 Baud Rate 9600 4800 or 9600

**par. 8-50 Coasting Select Logic or

**par. 8-52 DC Brake Select Logic or

**par. 8-53 Start Select Logic or

**par. 8-54 Reversing Select Digital input

**par. 8-55 Set-up Select Logic or

**par. 8-56 Preset Reference Select Logic or

Table 6.1: Frequency converter parameter settings

* Minimum parameters, which must be set to operate the frequency converter via the FLN serial interface.

** When [Digital input] or [Logic or] is selected, digital inputs may interfere with serial bus commands. The setting [Serial communication] allows serial

bus commands to be carried out only. See the VLT HVAC Drive Programming Guide for detailed descriptions.

NB!

The frequency converter can store preset references programmed in parameters 3-10.0 through 3-10.7, Preset Reference (1-8). To

avoid these values modifying serial bus references, set par. 3-04 Reference Function to [External/Preset]. See VLT HVAC Drive Pro-

gramming Guide for detailed descriptions.

VLT® HVAC Drive FLN Operating Instructions 6 Parameters

MG.11.Z2.02 - VLT is a registered Danfoss trademark 19

6

7 Start-up and Troubleshooting VLT® HVAC Drive FLN Operating Instructions

20 MG.11.Z2.02 - VLT is a registered Danfoss trademark

7

7 Start-up and Troubleshooting

7.1 Start-up

7.1.1 Start-up of FLN control

This procedure assumes that the frequency converter has been installed properly and is operational in Hand control mode. It also assumes the Siemens

FLN data bus is connected to an operational controller. Start the FC in accordance with the following procedure.

1. Ensure that the assumptions in this procedure are correct.

2. Check that the network connections are securely fastened in accordance with Figure Network Terminal Connection

Verify compliance with all safety requirements listed in this manual.

3. Apply power to the frequency converter.

4. Ensure that the minimum settings listed in Table 6.1 Frequency converter parameter settings are selected.

5. Ensure that the switch positions in Illustration 5.3 Terminator Switch Factory Setting are set correctly.

6. Optional settings may be changed to meet or enhance frequency converter operation, depending on the application requirements.

7. For FLN control of the drive, press the AUTO START key on the LCP. FC operation can then be controlled through the host network device in

accordance with its operation instructions.

NB!

Default setting for point number 35, CMD RUN STOP, is [OFF]. Drive will not operate until Run Enable [ON] signal is given through

serial communication network.

7.2 Troubleshooting

7.2.1 Faults, warnings and alarms

A stopped motor may start unexpectedly if faults occur in electronics of drive, or if an active fault clears, such as a fault in supply AC

line, fault in motor connection or overload.

The frequency converter output faults, warnings and alarms on the FLN serial bus in a numerical code. The code numbers are described in Table Faults,

Warnings and Alarms Description. The Reset key is used for manually resetting the drive after an alarm (fault trip). In this case, the top line of the display

will show TRIP (RESET). If the top line of the display shows TRIP (AUTO START), the drive will automatically restart. If the top line of the display shows

TRIPLOCK (DISC. MAINS), input power to the drive must be cycled off and on again before the trip can be reset.

Refer to the VLT HVAC Drive Operating Instructions for detailed descrip-

tions.

7.2.2 Alarms and warnings

A warning or an alarm is signalled by the relevant LED on the front of the frequency converter and indicated by a code on the display.

A warning remains active until its cause is no longer present. Under certain circumstances operation of the motor may still be continued. Warning messages

may be critical, but are not necessarily so.

VLT® HVAC Drive FLN Operating Instructions 7 Start-up and Troubleshooting

MG.11.Z2.02 - VLT is a registered Danfoss trademark 21

7

In the event of an alarm, the frequency converter will have tripped. Alarms must be reset to restart operation once their cause has been rectified. This

may be done in four ways:

1. By using the [RESET] control button on the LCP control panel.

2. Via a digital input with the “Reset” function.

3. Via serial communication/optional fieldbus.

4. By resetting automatically using the [Auto Reset] function, which is a default setting for frequency converter. see par. 14-20 Reset Mode in VLT

HVAC Drive Programming Guide, MG.11.Cx.yy

NB!

After a manual reset using the [RESET] button on the LCP, the [AUTO ON] button must be pressed to restart the motor.

If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also table on following page).

Alarms that are trip-locked offer additional protection, means that the mains supply must be switched off before the alarm can be reset. After being

switched back on, the frequency converter is no longer blocked and may be reset as described above once the cause has been rectified.

Alarms that are not trip-locked can also be reset using the automatic reset function in par. 14-20 Reset Mode (Warning: automatic wake-up is possible!)

If a warning and alarm is marked against a code in the table on the following page, this means that either a warning occurs before an alarm, or it can

be specified whether it is a warning or an alarm that is to be displayed for a given fault.

This is possible, for instance, in par. 1-90 Motor Thermal Protection. After an alarm or trip, the motor carries on coasting, and the alarm and warning

flash on the frequency converter. Once the problem has been rectified, only the alarm continues flashing.

7 Start-up and Troubleshooting VLT® HVAC Drive FLN Operating Instructions

22 MG.11.Z2.02 - VLT is a registered Danfoss trademark

7

No. Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference1 10 Volts low X 2 Live zero error (X) (X) par. 6-01 Live Zero Time-

out Function3 No motor (X) par. 1-80 Function at

Stop4 Mains phase loss (X) (X) (X) par. 14-12 Function at

Mains Imbalance5 DC link voltage high X 6 DC link voltage low X 7 DC over voltage X X 8 DC under voltage X X 9 Inverter overloaded X X 10 Motor ETR over temperature (X) (X) par. 1-90 Motor Thermal

Protection11 Motor thermistor over temperature (X) (X) par. 1-90 Motor Thermal

Protection12 Torque limit X X 13 Over Current X X X 14 Earth fault X X X 15 Incomp. HW X X 16 Short Circuit X X 17 Control word timeout (X) (X) par. 8-04 Control Time-

out Function23 Internal fans 24 External fans 25 Brake resistor short-circuited X 26 Brake resistor power limit (X) (X) par. 2-13 Brake Power

Monitoring27 Brake chopper short-circuited X X 28 Brake check (X) (X) par. 2-15 Brake Check29 Power board over temp X X X 30 Motor phase U missing (X) (X) (X) par. 4-58 Missing Motor

Phase Function31 Motor phase V missing (X) (X) (X) par. 4-58 Missing Motor

Phase Function32 Motor phase W missing (X) (X) (X) par. 4-58 Missing Motor

Phase Function33 Inrush fault X X 34 Fieldbus communication fault X X 35 Option fault X 36 Mains failure 38 Internal fault X X 40 Overload T27 41 Overload T29 42 Overload X30/6-7 47 24 V supply low X X X 48 1.8 V supply low X X 49 Speed limit 50 AMA calibration failed X 51 AMA check Unom and Inom X 52 AMA low Inom X 53 AMA motor too big X 54 AMA motor too small X 55 AMA parameter out of range X 56 AMA interrupted by user X 57 AMA timeout X 58 AMA internal fault X X 59 Current limit X 60 External interlock 62 Output Frequency at Maximum Limit X 65 Control Board Over-temperature X X X 66 Heat sink Temperature Low X 67 Option Configuration has Changed X 68 Safe Stop Activated X 70 Illegal FC configuration 80 Drive Initialised to Default Value X 92 No-Flow X X Par. 22-2*93 Dry Pump X X Par. 22-2*94 End of Curve X X Par. 22-5*95 Broken Belt X X Par. 22-6*96 Start Delayed X Par. 22-7*97 Stop Delayed X Par. 22-7*98 Clock Fault X Par. 0-7*

Table 7.1: Alarm/Warning code list

VLT® HVAC Drive FLN Operating Instructions 7 Start-up and Troubleshooting

MG.11.Z2.02 - VLT is a registered Danfoss trademark 23

7

No. Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference200 Fire Mode X Par. 24-0*201 Fire Mode was Active X Par. 0-7*202 Fire Mode Limits Exceeded X Par. 0-7*250 New spare part 251 New type code

Table 7.2: Alarm/Warning code list, continued..

(X) Dependent on parameter

LED indicationWarning yellowAlarm flashing red

Trip locked yellow and red

Alarm Word and Extended Status WordBit Hex Dec Alarm Word Warning Word Extended Status Word0 00000001 1 Brake Check Brake Check Ramping1 00000002 2 Pwr. Card Temp Pwr. Card Temp AMA Running2 00000004 4 Earth Fault Earth Fault Start CW/CCW3 00000008 8 Ctrl.Card Temp Ctrl.Card Temp Slow Down4 00000010 16 Ctrl. Word TO Ctrl. Word TO Catch Up5 00000020 32 Over Current Over Current Feedback High6 00000040 64 Torque Limit Torque Limit Feedback Low7 00000080 128 Motor Th Over Motor Th Over Output Current High8 00000100 256 Motor ETR Over Motor ETR Over Output Current Low9 00000200 512 Inverter Overld. Inverter Overld. Output Freq High10 00000400 1024 DC under Volt DC under Volt Output Freq Low11 00000800 2048 DC over Volt DC over Volt Brake Check OK12 00001000 4096 Short Circuit DC Voltage Low Braking Max13 00002000 8192 Inrush Fault DC Voltage High Braking14 00004000 16384 Mains ph. Loss Mains ph. Loss Out of Speed Range15 00008000 32768 AMA Not OK No Motor OVC Active16 00010000 65536 Live Zero Error Live Zero Error 17 00020000 131072 Internal Fault 10V Low 18 00040000 262144 Brake Overload Brake Overload 19 00080000 524288 U phase Loss Brake Resistor 20 00100000 1048576 V phase Loss Brake IGBT 21 00200000 2097152 W phase Loss Speed Limit 22 00400000 4194304 Fieldbus Fault Fieldbus Fault 23 00800000 8388608 24 V Supply Low 24V Supply Low 24 01000000 16777216 Mains Failure Mains Failure 25 02000000 33554432 1.8V Supply Low Current Limit 26 04000000 67108864 Brake Resistor Low Temp 27 08000000 134217728 Brake IGBT Voltage Limit 28 10000000 268435456 Option Change Unused 29 20000000 536870912 Drive Initialised Unused 30 40000000 1073741824 Safe Stop Unused

Table 7.3: Description of Alarm Word, Warning Word and Extended Status Word

The alarm words, warning words and extended status words can be read out via serial bus or optional field-bus for diagnosis. See also par. 16-90 Alarm

Word, par. 16-92 Warning Word and par. 16-94 Ext. Status Word.

7 Start-up and Troubleshooting VLT® HVAC Drive FLN Operating Instructions

24 MG.11.Z2.02 - VLT is a registered Danfoss trademark

7

Poin

tno

.

6000

poin

tno

.D

escr

ipto

rFa

ctor

yde

faul

t(S

I)

Engr

.U

nit

(SI)

Slop

e(S

I)In

terc

ept

(SI)

On

text

Off

text

Rang

eM

axva

ue(S

I)

Min

valu

e(S

I)

Poin

tty

pe

Clas

sTy

pe(N

ote

1)

Read

Onl

yPa

r.N

o.

11

CTRL

AD

-D

RESS

0-

10

--

255

255

02

LAO

Yes

8-31

22

APPL

ICA-

TIO

N27

59-

10

--

1638

316

383

02

LAO

Yes

-

{3}

3FR

EQ O

UT-

PUT

0H

Z0,

10

--

1638

316

38,3

03

LAI

Yes

16-1

3

{4}

-PC

T O

UT-

PUT

0PC

T0,

01-1

63,8

3-

-32

767

163,

83-1

63,8

33

LAI

Yes

16-1

5

{5}

-REF

PCT

0PC

T0,

1-1

638,

3-

-32

767

1638

,3-1

638,

33

LAI

Yes

16-0

2{6

}6

CURRE

NT

0A

0,1

0-

-32

767

3276

,70

3LA

IYe

s16

-14

{7}

-CT

RL.C

RD.T

MP

0D

EG C

10

255

255

03

LAI

Yes

16-3

9

{8}

8PO

WER

KW

0KW

0,1

0-

-32

767

3276

,70

3LA

IYe

s16

-10

{9}

-PO

WER

HP

0H

P0,

10

--

3276

732

76,7

03

LAI

Yes

16-1

1{1

0}10

KWH

0KW

H1

0-

-10

2310

230

3LA

IYe

s15

-02

{11}

-M

WH

0M

WH

10

--

3276

732

767

03

LAI

Yes

15-0

2{1

2}12

RUN

TIM

E0

HR

40

--

3276

713

1068

03

LAI

Yes

15-0

1

{13}

13D

C BU

SVO

LT0

V1

0-

-40

9540

950

3LA

IYe

s16

-30

{14}

14O

UTP

UT

VOLT

0V

10

--

4095

4095

03

LAI

Yes

16-1

2

{15}

15M

OTO

RTH

ERM

0PC

T1

0-

-25

525

50

3LA

IYe

s16

-18

{16}

16D

RIV

ETH

ERM

0PC

T1

0-

-25

525

50

3LA

IYe

s16

-35

{17}

17AC

TIVE

SET

-U

P0

-1

0-

-25

525

50

3LA

IYe

s0-

10

{18}

-H

EATS

INK

TMP

0D

EG C

10

--

255

255

03

LAI

Yes

16-3

4

{19}

19CU

R.L

IM.S

TAT

OK

-1

0LI

MIT

OK

255

255

03

LDI

Yes

16-0

3 [1

4]

2020

OVR

D T

IME

0H

RS

10

--

255

255

02

LAO

No

7.2

.3P

oin

t m

appi

ng

tabl

e

VLT® HVAC Drive FLN Operating Instructions 7 Start-up and Troubleshooting

MG.11.Z2.02 - VLT is a registered Danfoss trademark 25

7

Poin

tno

.

6000

poin

tno

.D

escr

ipto

rFa

ctor

yde

faul

t(S

I)

Engr

.U

nit

(SI)

Slop

e(S

I)In

terc

ept

(SI)

On

text

Off

text

Rang

eM

axva

ue(S

I)

Min

valu

e(S

I)

Poin

tty

peCl

ass

Type

Read

Onl

yPa

r.N

o.

{21}

21FW

D.R

EVFW

D-

10

REV

FWD

255

255

03

LDI

Yes

Not

e[3]

{22}

22CM

DFW

D.R

EVFW

D-

10

REV

FWD

255

255

01

LDO

No

CTW

[15

]

{23}

23RU

N.S

TOP

STO

P-

10

RUN

STO

P25

525

50

3LD

IYe

s16

-03

[11

]

{24}

-RAM

P SE

-LE

CTRAM

P1-

10

RAM

P2RAM

P125

525

50

1LD

ON

oCT

W [

09]

{25}

25FR

EEZE

OU

TO

FF-

10

ON

OFF

255

255

03

LDI

Yes

16-9

5 [1

4]

{26}

26CM

DFR

EEZE

OFF

-1

0O

NO

FF25

525

50

1LD

ON

oCT

W [

05]

{27}

27CO

ASTI

NG

OFF

-1

0O

FFCO

AST

255

255

03

LDI

Yes

16-0

0 [0

3]{2

8}28

CMD

CO

AST

OFF

-1

0O

FFCO

AST

255

255

01

LDO

No

CTW

[03

]

2929

DAY

.NIG

HT

(Not

e 2)

DAY

-1

0N

IGH

TD

AY25

525

50

1LD

ON

o-

{31}

31AC

CEL

TIM

E1

0* (

Not

e 4)

SEC

11

--

4095

3600

11

LAO

No

3-41

{32}

32D

ECEL

TIM

E1

0* (

Not

e 4)

SEC

11

--

4095

3600

11

LAO

No

3-42

{34}

34H

AND

.AU

TOAU

TO-

10

HAN

DAU

TO25

525

50

3LD

IYe

s16

-95

[01]

{35}

35CM

DRU

N.S

TOP

STO

P-

10

RUN

STO

P25

525

50

1LD

ON

oCT

W [

06]

{36}

36BU

S TI

ME-

OU

T0*

SEC

11

--

3276

718

000

11

LAO

No

8-03

{37}

37BU

S FU

NC-

TIO

N0

(Not

e 6)

-1

0-

-25

510

01

LAO

No

8-04

{38}

-JO

G F

REQ

10.0

HZ

0,1

0-

-16

383

1638

,30

1LA

ON

o3-

11{3

9}-

CMD

JO

GN

O-

10

YES

NO

255

255

01

LDO

No

CTW

[08

]

{40}

40CM

D.R

ELAY

1O

FF-

10

ON

OFF

255

255

01

LDO

No

CTW

[11

]

7 Start-up and Troubleshooting VLT® HVAC Drive FLN Operating Instructions

26 MG.11.Z2.02 - VLT is a registered Danfoss trademark

7

Poin

tno

.

6000

poin

tno

.D

escr

ipto

rFa

ctor

yde

faul

t(S

I)

Engr

.U

nit

(SI)

Slop

e(S

I)In

terc

ept

(SI)

On

text

Off

text

Rang

eM

axva

ue(S

I)

Min

valu

e(S

I)

Poin

tty

peCl

ass

Type

Read

Onl

yPa

r.N

o.

{41}

41CM

D.R

ELAY

2O

FF-

10

ON

OFF

255

255

01

LDO

No

CTW

[12

]

{42}

-CM

D A

O1

0PC

T0,

010

--

1638

316

3,83

01

LAO

No

6-53

{43}

43RE

LAY

1ST

ATO

FF-

10

ON

OFF

255

255

03

LDI

Yes

16-7

1 [0

4]

{44}

44RE

LAY

2ST

ATO

FF-

10

ON

OFF

255

255

03

LDI

Yes

16-7

1[03

]

{45}

-AO

1 ST

AT0

MA

0,01

0-

-40

9540

,95

03

LAI

Yes

16-6

5{4

6}-

DI

18 S

TAT

OFF

-1

0O

NO

FF25

525

50

3LD

IYe

s16

-60

[05]

{47}

-D

I 19

STA

TO

FF-

10

ON

OFF

255

255

03

LDI

Yes

16-6

0 [0

4]{4

8}-

DI

27 S

TAT

OFF

-1

0O

NO

FF25

525

50

3LD

IYe

s16

-60

[03]

{49}

-D

I 29

STA

TO

FF-

10

ON

OFF

255

255

03

LDI

Yes

16-6

0 [0

2]{5

0}-

DI

32 S

TAT

OFF

-1

0O

NO

FF25

525

50

3LD

IYe

s16

-60

[01]

{51}

-D

I 33

STA

TO

FF-

10

ON

OFF

255

255

03

LDI

Yes

16-6

0 [0

0]{5

2}52

AT S

PEED

OFF

REF

-1

0O

N.R

EFO

FFREF

255

255

03

LDI

Yes

16-0

3 [0

8]{5

3}53

CMD

REF

0PC

T0,

010

--

3276

720

00

1LA

ON

oRE

F

{54}

-AC

CEL

TIM

E2

0*SE

C1

1-

-40

9536

001

1LA

ON

o3-

51

{55}

-D

ECEL

TIM

E2

0*SE

C1

1-

-40

9536

001

1LA

ON

o3-

52

{56}

-BY

PASS

CMD

DRI

VE-

10

BYPA

SSD

RIV

E25

525

50

1LD

ON

o31

-00

{57}

-BY

PASS

STAT

0-

10

--

3276

732

767

03

LAI

Yes

31-1

0

{58}

-BO

STA

RTD

LY30

SEC

10

--

4095

300

1LA

ON

o31

-01

{59}

59SL

EEP

STA-

TUS

NO

-1

0SL

EEP

NO

255

255

03

LDI

Yes

[21]

{60}

-BO

TRIP

DLY

0SE

C1

0-

-40

9530

00

1LA

ON

o31

-02

VLT® HVAC Drive FLN Operating Instructions 7 Start-up and Troubleshooting

MG.11.Z2.02 - VLT is a registered Danfoss trademark 27

7

Poin

tno

.

6000

poin

tno

.D

escr

ipto

rFa

ctor

yde

faul

t(S

I)

Engr

.U

nit

(SI)

Slop

e(S

I)In

terc

ept

(SI)

On

text

Off

text

Ran

geM

axva

ue(S

I)

Min

valu

e(S

I)

Poin

tty

peCl

ass

Type

Read

Onl

yPa

r.N

o.

{61}

61PI

STR

TFR

EQ(N

ote

3)0

Hz

0,1

0-

-16

383

1638

,30

1LA

ON

o20

-83

{62}

42PI

STR

TFR

.S0

Hz

0,1

0-

-16

383

1638

,30

3LA

IYe

s20

-83

{63}

63PI

GAI

N0,

5-

0,01

0

10

2310

01

LAO

No

20-9

3{6

4}64

PI I

TIM

E20

SEC

0,30

5184

80,

01-

-32

767

1000

00,

011

LAO

No

20-9

4{6

5}62

FEED

BACK

0PC

T0,

01-1

63,8

3-

-32

767

163,

83-1

63,8

33

LAI

Yes

16-0

5

{66}

69SE

TPO

INT

1(N

ote

3)0

UN

IT0,

1-1

638,

3-

-32

767

1638

,3-1

638,

31

LAO

No

20-2

1

{67}

70SE

TPO

INT

2(N

ote

3)0

UN

IT0,

1-1

638,

3-

-32

767

1638

,3-1

638,

31

LAO

No

20-2

2

{68}

-SE

TPO

INT

30

UN

IT0,

1-1

638,

3-

-32

767

1638

,3-1

638,

31

LAO

No

20-2

3{6

9}73

BUS

FBK

10

PCT

0,01

-163

,83

--

3276

716

3,83

-163

,83

1LA

ON

o8-

94{7

0}74

BUS

FBK

20

PCT

0,01

-163

,83

--

3276

716

3,83

-163

,83

1LA

ON

o8-

95{7

1}-

BUS

FBK

30

PCT

0,01

-163

,83

--

3276

716

3,83

-163

,83

1LA

ON

o8-

96

{76}

76VO

LTAG

EST

ATO

K-

10

LIM

ITO

K25

525

50

3LD

IYe

s16

-03

[13]

{77}

77IN

VERT

STAT

OK

-1

0ST

ALL

OK

255

255

03

LDI

Yes

16-0

3 [1

2]

{78}

78FR

EQ S

TAT

OU

TRN

G-

10

IN.R

NG

OU

TRN

G25

525

50

3LD

IYe

s16

-03

[10]

{79}

-FI

REM

.ST

ATN

ORM

-1

0FI

RE

NO

RM

255

255

03

LDI

Yes

16-9

4 [2

5]

{80}

-O

VC A

C-TI

VEN

ORM

-1

0O

VCN

ORM

255

255

03

LDI

Yes

16-9

4 [1

5]

7 Start-up and Troubleshooting VLT® HVAC Drive FLN Operating Instructions

28 MG.11.Z2.02 - VLT is a registered Danfoss trademark

7

Poin

tno

.

6000

poin

tno

.D

escr

ipto

rFa

ctor

yde

faul

t(S

I)

Engr

.U

nit

(SI)

Slop

e(S

I)In

terc

ept

(SI)

On

text

Off

text

Rang

eM

axva

ue(S

I)

Min

valu

e(S

I)

Poin

tty

peCl

ass

Type

Read

Onl

yPa

r.N

o.

{81}

81RA

MPI

NG

NO

RM-

10

RAM

PN

ORM

255

255

03

LDI

Yes

16-9

4 [0

0]

{82}

82RU

N R

E-Q

UES

TN

ORM

-1

0RE

QN

ORM

255

255

03

LDI

Yes

16-9

5 [1

5]

{83}

-JO

GG

ING

NO

RM

10

JOG

NO

RM

255

255

03

LDI

Yes

16-9

5 [1

6]

{84}

-TE

RM

. 53

TYP

CURR

-1

0VO

LTCU

RR

255

255

03

LDI

Yes

16-6

1

{85}

-TE

RM

. 54

TYP

CURR

-1

0VO

LTCU

RR

255

255

03

LDI

Yes

16-6

3

{86}

86Q

.STO

PST

ATN

ORM

-1

0Q

.STO

PN

ORM

255

255

03

LDI

Yes

16-0

0 [0

4]

{87}

87TE

RM

53

STAT

0V.

MA

0,00

10

--

3276

732

,767

03

LAI

Yes

16-6

2

{88}

88TE

RM

54

STAT

0V.

MA

0,00

10

--

3276

732

,767

03

LAI

Yes

16-6

4

{89}

-RE

F U

NIT

0U

NIT

0,1

-163

8,3

--

3276

716

38,3

-163

8,3

3LA

IYe

s16

-01

{90}

90W

ARN

ING

OK

-1

0W

ARN

OK

255

255

03

LDI

Yes

16-0

3 [0

7]{9

1}91

TRIP

LO

CKN

OLO

CK-

10

LOCK

NO

LOCK

255

255

03

LDI

Yes

16-0

3 [0

6]{9

2}92

ALAR

MO

K-

10

ALAR

MO

K25

525

50

3LD

IYe

s16

-03

[03]

{93}

93LA

ST A

LARM

0(N

ote

8)-

10

--

255

255

03

LAI

Yes

15-3

0 [0

]

{94}

94RE

SET

ALAR

MO

FF-

10

RES

ETO

FF25

525

50

1LD

ON

oCT

W [

07]

{95}

-RES

ET K

WH

NO

-1

0RES

ETN

O25

525

50

1LD

ON

o15

-06

{96}

-RE

SET

R.H

RS

NO

-1

0R

ESET

NO

255

255

01

LDO

No

15-0

7

{97}

-JO

G F

REQ

.S0

HZ

0,1

0-

-16

383

1638

,30

3LA

IYe

s3-

11

9999

ERRO

R ST

A-TU

S(N

ote

2)0

-1

0-

-25

525

50

3LA

IYe

s-

VLT® HVAC Drive FLN Operating Instructions 7 Start-up and Troubleshooting

MG.11.Z2.02 - VLT is a registered Danfoss trademark 29

7

IndexAAbbreviations And Standards 5

Alarms And Warnings 21

Analog Input Monitoring 15

BBus Functions (36, 37) 8

CCaution 3

Cmd Run Stop (35) 8

Coast (27, 28) 8

Current Monitoring And Limits (19) 7

DDirection Of Rotation (22) 7

Drive Operation (03-14) 7

Drive Relay Control 15

EElectrical Installation 17

Error Status (99) 9

FFaults, Warnings And Alarms 21

Freeze Mode (25, 26) 8

Frequency Converter Hardware Setup 17

JJog Frequency And Command (38, 39) 8

LLiterature 4

MMotor And Drive Thermal Protection (15, 16, 18) 7

Motor Ramp-up And Ramp-down Rate (31, 32) 8

NNetwork Connection 17

PParameter Settings 19

Pid Control Functions (61-65) 8

Pid Controller Adjustments: 13

Point Mapping Table 25

RRamp Select (24) 7

Relay Out 1, 2 (40, 41, 43, 44) 8

SSet-up 1-4 And Day/night Operation (17, 29) 7

Sleep Mode (59) 9

Special Functions 15

Start/stop (23) 7

Start-up Of Fln Control 21

Index VLT® HVAC Drive FLN Operating Instructions

30 MG.11.Z2.02 - VLT is a registered Danfoss trademark

Strategy Four 12

Strategy One 11

Strategy Three 12

Strategy Two 11

TTerminals 53, 54, (87-88) 9

VVlt Network Strategies 11

WWarnings And Alarms (90-94) 9

VLT® HVAC Drive FLN Operating Instructions Index

MG.11.Z2.02 - VLT is a registered Danfoss trademark 31