    ProtectIT

     

    Multifunction Protection and Switchgear Control Unit 

    Model REF542 plus 

    Configuration Tool Manual

    Analog

    20mA

    LON

    MODBUS

    Ethernet

    IEC 60870-5-103

    GPS

    Binary I/O

       U

       /   I

       I   /   O

       B   U   S

    REF 542 plus

    RS232

    CANPortable PCwith standardbrowser asHMI

    HMI as Local

    Control Unit8 analoginputs for U / I

    Embedded

    Web-Server 

    Protection

    and control

     

  • 8/20/2019 Configuration Tool Manual R2

    2/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 2 / 176 

    Table of Contents

    1  About this manual...................................................................................4 

    1.1  Read it first! ...........................................................................................4

    1.2  IndustrialIT ..............................................................................................4

    1.3  Document information..........................................................................4

    2  Abbreviations...........................................................................................5 

    3  Safety Information ..................................................................................5 

    3.1  System requirements ...........................................................................6

    3.2  Installation..............................................................................................6

    3.2.1  Installable components.............................................................6

    3.2.2  Installing a new version of the tool .........................................9

    3.2.3  Restart after an installation......................................................9

    3.3  How to remove the tool ........................................................................9

    3.4  Starting the configuration tool...........................................................10

    3.5  Using the configuration tool ..............................................................11

    3.5.1  Operating tool ..........................................................................11

    3.5.2  First steps in creating or editing an application ..................11

    3.5.3  Working with projects .............................................................11

    3.5.4  Selecting the language version .............................................133.5.5  Setting the PC and REF542 plus connection ......................13

    3.5.6  Configuring the REF542 plus .................................................13

    3.5.7  Creating a function chart (FUPLA) .......................................14

    3.5.8  Upload/Download configuration............................................18

    3.5.9  Description of the menu items...............................................20

    3.5.10  Description of the status bar ..................................................35

    4  Setting up REF542 plus ........................................................................36 

    4.1  Basic information ................................................................................36

    4.2  Connecting inputs and outputs .........................................................36

    4.3  General settings..................................................................................36

    4.3.1  Serial Port.................................................................................37

    4.3.2  Global Settings ........................................................................39

    4.3.3  Hardware ..................................................................................42

    4.3.4   Analog inputs ...........................................................................43

    4.3.5   Analog Input 0/4 – 20 mA ......................................................45

  • 8/20/2019 Configuration Tool Manual R2

    3/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 3 / 176 

    4.3.6   Analog outputs.........................................................................46

    4.3.7  Single Line Diagram ...............................................................49

    4.3.8  Display language.....................................................................56

    4.3.9  Char Maps ................................................................................56

    4.3.10  Led Bars ...................................................................................58

    4.4  Function and configuration of the function blocks .........................60

    4.4.1  Control panel on HMI Control unit ........................................60

    4.4.2  Binary IO (switching objects).................................................69

    4.4.3  Digital logic 1..........................................................................117

    4.4.4  Digital logic 2..........................................................................122

    4.4.5  Flip-Flops................................................................................124

    4.4.6   Analog components ..............................................................134

    4.4.7  Communication objects ........................................................152

    4.4.8  CAN Communication Objects .............................................171

    4.4.9  Miscellaneous objects ..........................................................171

  • 8/20/2019 Configuration Tool Manual R2

    4/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 4 / 176 

    1 About this manual

    1.1 Read it first!Before attempting any configuration of the REF542 plus, read carefully this manual first.

    This manual describes how to use the configuration tool program of the REF542 plus.

    This manual is addressed to engineering personnel and to anyone who needs toconfigure the REF542 plus.

    1.2 IndustrialIT 

    This product has been tested and certified as Industrial IT Enabled. All productinformation is supplied in interactive electronic format, compatible with ABB Aspect

    ObjectTM  technology. The Industrial IT   commitment from ABB ensures that every

    enterprise building block is equipped with the integral tools necessary to install, operate,and maintain efficiently throughout the product lifecycle.

    Detailed information on IndustrialIT

     is available at .  

    1.3 Document information

    Revision History

    Version Date Note

    1VTA100003-Rev.2, en 22.10.2002 First release

    1VTA100172-Rev 3, en 22.11.2003 Updated to version 4D02

    Applicability

    This manual is applicable to REF542 plus Release 2.0, software version V4D02.

  • 8/20/2019 Configuration Tool Manual R2

    5/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 5 / 176 

    2 Abbreviations

     AR Auto-Reclosure

     ASDU Application Service Data Unit (IEC 60870-5-103 communicationprotocol).

    CT Current Transformer

    CAN Control Area Network

    DFT Discrete Fourier Transformation

    FUPLA Function block Programming Language, also used as abbreviation forfunction plan or chart

    HMI Human Machine Interface

    LCD Liquid Crystal Display

    LD HMI Local Detached Human Machine Interface, same meaning as HMI

    LED Light Emitting Diode

    LAG Lon Application Guideline

    MC MicroController

    MSI Microsoft Installer technology

    PC Personal Computer

    PLC Programmable Logical Controller

    VDEW Association of German Utilities

    3 Safety Information

    There are safety warnings and notes in the following text. They are in a different format todistinguish them from normal text.

    Safety warning

    The safety warnings should always be observed. Non-observance can result in death,personal injury or substantial damages to property. Guarantee claims might not beaccepted when safety warnings are not respected. They look like below:

    Warning!Every application must undergo a functional test with the panel for which it wascreated. The protection functions must be thoroughly checked in this test

    Note

     A note contains additional information worth noting in the specific context, and looks likebelow:

    Note Please read this section completely for information on the various formats for safetynotes.

  • 8/20/2019 Configuration Tool Manual R2

    6/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 6 / 176 

    3.1 System requirements

    IBM compatible personal computer, Intel Pentium processor

    min. 32 MB RAM

    (optional) 3.5 “ disk drive

    (optional) CD-ROM drive or DVD-ROM drive

    Mouse

    Hard drive space: 20 MB free.

    Microsoft Windows® NT 4.0 at least Service Pack 6, or Windows

    ® 2000.

    3.2 Installation

    To start the installation software, start the set up.exe program (e.g. double-click the left

    mouse button when the mouse cursor is over the file) on the disk.

    Note There are two different versions of the tool. The configuration tool can only be usedby REF542 plus companies. The operating tool use has no restrictions. Theconfiguration tool allows inserting protection function blocks. The protection functionmenu is disabled in the operating tool.

    The installation software automatically selects the language, used to guide the userthrough the installation process, based on the User Locale Settings of the Windows®system. The following languages are available: English (US), German, Italian, Czech and

    Slovak (in all the other cases, English is taken as default). Please follow the instructionsand observe the information provided by the installation program. Every step in theinstallation process can be reversed or the entire program can be cancelled.

    3.2.1 Installable components

    Following the set up wizard it is possible to choose two set up types: complete andcustom.

  • 8/20/2019 Configuration Tool Manual R2

    7/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 7 / 176 

    Figure 1: Set up Type

    The complete set up will install automatically the following components:

    • The configuration tool (mandatory). This component contains: the executable andlanguage libraries, the Latin and Cyrillic fonts for the HMI, the English andRussian, String files (STC), the Analog Input Boards definition (.xml file), and theWeb Server configuration file.

    •  An example of drawing (optional). An empty drawing into the Drawings folder.

    • The character map bitmaps (for Latin and Cyrillic ASCII chars). These bitmapscan be used to customize the characters downloaded to the HMI.

    The custom set up instead allows the user to select/deselect the optional components.

    Figure 2: Custom set up

  • 8/20/2019 Configuration Tool Manual R2

    8/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 8 / 176 

    Clicking on the component is possible to select/deselect a component, as shown in thefigure below.

    Figure 3: Custom Set up – select and deselect features

    Note Complete set up is recommended.

  • 8/20/2019 Configuration Tool Manual R2

    9/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 9 / 176 

    3.2.2 Installing a new version of the tool

     A new installation does not overwrite older configuration tools. Any older configurationtool not used anymore should be uninstalled from the system.

    Note First uninstall old tools if you intend to reuse the target directory or group names of anolder installation.

    3.2.3 Restart after an installation

    Depending on the update status of your Windows® libraries the installation softwarecould ask for a computer restart at the end of the process. This is strongly recommended.

    3.3 How to remove the tool

    The installed tool is compliant with MSI (Microsoft Installer) technology. Thus it is alwayspossible to repair or remove the tool from the machine.

    To remove REF542 plus configuration tool, follow the steps below:

    1. Go to the Start Menu and choose Settings.

    2. Go on to Control Panel and select Add/Remove Programs.

    Mark the REF542 plus configuration tool you would like to uninstall and press Remove.

    Follow the instructions.

  • 8/20/2019 Configuration Tool Manual R2

    10/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 10 / 176 

    3.4 Starting the configuration tool

     After the installation has been completed as described above, the tool can be started asfollows:

    The program groups here are accessed through the Start button. By default the programgroup with the REF542 plus configuration software is in:

    \ABB Industrial IT\Protect IT\REF542plus\….

    For example:

    C:\Program Files\ABB Industrial IT\Protect IT\REF542plus\ConfToolV4D02b\.  

    This folder structure is not mandatory, but strongly suggested because it is widely usedfor all the Industrial IT certified products, like REF542 plus. In particular, the common“ABB Industrial IT” folder is followed by the suite name (Protect IT) and the product name.It is suggested to leave the version in the tool folder name to easily handle the installationside-by-side (at the same time) on the same computer of different, e.g. newer,configuration tools.

    Figure 4: Configuration software Main View

    The menu is described in the paragraph 3.5.8. The status bar of the main view isdescribed in 3.5.10.

    Note Pay attention to the version shown in the main view of the configuration tool or intothe About box (available in the Help menu). Ensure it is the last available and it iscompatible with the firmware version of the REF542 plus to be configured.

  • 8/20/2019 Configuration Tool Manual R2

    11/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 11 / 176 

    3.5 Using the configuration tool

    The following subsections provide basic information on using the configuration tool. Themost important activities in creating or editing an application are described.

     Another section explains the menu items in the main menu and the character menu in thesequence in which they appear.

    Note The limitations of the customer version that are described below are not explainedany further in the configuration software documentation.

    3.5.1 Operating tool

    The operating tool has the following limitations:

     Additional protection functions cannot be added to the application. If a protection functionin the application is deleted, it cannot be added again later.

    3.5.2 First steps in creating or editing an application

    Not all the configuration tool functions are described in the following section. All menuitems in the configuration tool are described in a separate section.

    The sequence of the following subsection corresponds to the same sequence of stepsrequired when defining a new application. When an existing application is opened, allbasic settings are of course already specified. The function chart is also complete.However, the procedure for editing an application is the same as for creating a new one.

    3.5.3 Working with projects

    The set of files that belong to an application in connection with the configuration tool isreferred to a project. Projects can be created, opened and saved in the configuration tool.

     After starting the configuration tool, a new project with the name new.ref is created.

    Note When saving a new project for the first time, always select the menu item MainMenu/File/Save as F7. Otherwise the name "new.ref" will be used.

    The table on the next page describes the set of files associated with a project. Not all ofthem will be created in every application. In addition, the table shows when the files arecreated or updated. If the files need to be created, the corresponding menu „GenerateReport File“ must be activated.

  • 8/20/2019 Configuration Tool Manual R2

    12/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 12 / 176 

    Table 1: 

    File Contents Created Updated

    *.ref File comprising:

    - Drawing- Parameter- HMI LCD configuration- LCD texts All other files can be recreated from this file, withthe exception of the fault records files and of theSCL file (WEBREF configuration)

    When saving When saving

    *.bak Application back-up file When opening When opening

    *.doc - Device configuration- Rated values of the analog inputs- Configured protection functions with setting values

    When printing orgeneratingreports

    When printing orgeneratingreports

    *.wir All connections in use are counted, the connectionnumber and the associated text is saved. The objectnumber sorts the connections to which they are

    connected and by the number of the connector pin. Also the object type to which the connection islinked is written to this file.

    When printing orgeneratingreports

    When printing orgeneratingreports

    *.lst All events generated by the application are listedhere.

    When printing orgeneratingreports

    When printing orgeneratingreports

    *.can CAN related information (I/O blocks, addresses, etc) When printing orgeneratingreports

    When printing orgeneratingreports

    *.lcu The mimic diagram configuration of the currentapplication.

    When exportinga mimic diagram

    When exportinga mimic diagram

    *.scl Information regarding device Web server settings ofthe current application. The format is the IEC 61850

    Substation Control Language.

    When saving ifWeb interface is

    enabled ormanuallygenerating theSCL file

    When saving ifWeb interface is

    enabled ormanuallygenerating theSCL file

    *.svg The mimic diagram configuration of the currentapplication in Standard Vector Graphic format.

    Whengenerating theSVG file if theWeb interface isenabled

    Whengenerating theSVG file if theWeb interface isenabled

    *.ri1 The setting parameter set 1 of the distanceprotection. The Omicron test set uses this file forautomatic testing.

    When saving anapplication withdistanceprotection

    When saving anapplication withdistanceprotection

    *.ri2 The setting parameter set 2 of the distance

    protection. The Omicron test set uses this file forautomatic testing. 

    When saving an

    application withdistanceprotection

    When saving an

    application withdistanceprotection

    *.cfg Configuration file for the fault recorder module. When exportinga fault record

    *.dat Fault record file with the recorded data. When exportinga fault record

    Only files with the names *.ref can be opened directly in the configuration tool.

  • 8/20/2019 Configuration Tool Manual R2

    13/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 13 / 176 

    Note When the Web Interface is enabled, then the configuration of the device isrepresented by the *.ref file and by the *.scl file. For a better and easier handlingplease leave the name of the *.scl file as the *.ref one: in this way the configurationsoftware will be able to handle (open and save) automatically also the web serverconfiguration.

    The user can also handle manually the Web server configuration by importing andgenerating manually the *.scl file via Configuration menus.

    3.5.4 Selecting the language version

    To have the menu bars, dialogs and messages of the configuration software in thedesired language, select the menu item Main Menu/Options/Language/ [English, German,Italian, Czech]. The desired language will be used in the menu and set immediately. Thissetting is also kept after closing the software.

    3.5.5 Setting the PC and REF542 plus connection

    To download the application from the PC to the REF542 plus or to upload an application

    or other data from the REF542 plus, the connection must be established first. Theserial/optical cable is needed. One end is plugged into the optical interface of the HMI.The other end is plugged into the PC serial RS232 interface. 

    To enable data to be transferred over this connection, the dialog MainMenu/Transfer/Serial Port must be started in the configuration software.

    Note Ensure that the parameters of the dialog Serial Interface … as set in the configurationsoftware also conforms to the parameters for the serial interface, which can beconfigured in the operating system.

    Note 

    Ensure that the slave address of the dialog Serial Interface … as set in the

    configuration software is the same of the connected Base Unit. If this is different, thenthe communication between PC and REF542 plus cannot be established.

    3.5.6 Configuring the REF542 plus 

    It is best to define the display language (Main Menu/Configure/HMI/Display Language…)before continuing the configuration. This setting influences the translation to REF542 plus fonts of strings on the Configuration Software in case of non-Latin characters (e.g.Cyrillic, Chinese, Hebrew, etc).

    To be able to configure the application, the hardware module installed in the REF542 plus must be entered into the configuration software. To do this, start the dialog window MainMenu/Configure/Global Settings and Main Menu/ Configure/Hardware.

    The analog inputs and outputs should be defined before making the application settings.

    Start the dialog window Main Menu/Configure/Terminals/Analog Inputs and if necessaryMain Menu/Configure/Terminals/Analog Outputs. If an analog output board is not used,this menu item cannot be selected.

    The analog inputs 0/4-20 mA can be defined, if necessary, in the dialog MainMenu/Configure/Terminals/Analog Inputs 4-20 mA. If an analog input 4-20 mA board isnot used, this menu item cannot be selected.

    To enable the Web Server check the submenu Main Menu/Configure/Enable WebInterface.

  • 8/20/2019 Configuration Tool Manual R2

    14/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 14 / 176 

    3.5.7 Creating a function chart (FUPLA)

    To create the function chart, start the function chart editor with the menu item MainMenu/Configure/Drawing.

    Note  Before the function chart editor can be started, make the settings for a newapplication in the configuration dialogs Main Menu/Configure/Global Settings andMain Menu/Configure/Hardware.

    The first page of the application will appear. To make an application more manageable, itcan be distributed over several pages. One page is larger than the PC screen. All areasof the current page can be viewed by using the scroll bars to the right and at the bottomof the drawing editor window. The arrow keys (cursor keys) on the keyboard can also beused for this.

    3.5.7.1 Add or move function blocks

    Function blocks can be added and moved in the working mode.

    Add function block

    Select Drawing Menu/Insert. A submenu with various function groups appears. Selectinga function group brings up another submenu listing the individual function blocks. Theselected function block is placed on the top left of the page.

    Example: Select Drawing Menu/Insert/Control Panel/Indication LED to select theindication LED function block.

    Move function block

    To move, hold the left mouse button down when the cursor is on the function block anddrag it with the mouse. 

    Restrictions

    Note that not all function blocks can be combined together.

    Restrictions for function blocks and connections are listed in the table below.

    Table 2: Restrictions in the FUPLA

    Function block Restrictions

    Protection function Max. 24 protection functionsMax. 250 protection parameters100% DSP load

    Fault recorder Max. 1 fault recorder and

    Min. 1 configured protection function

    Digital store object Max. 1

    Power counter Max. 15

    Switching object Max. 62

    Threshold object Max. 10 per analog input

     Analog Input 0-20 mA object Max. 48

    Direct read write object Max. 100

  • 8/20/2019 Configuration Tool Manual R2

    15/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 15 / 176 

    Function block Restrictions

    Net number Max. 512

    Wire Max. 1000

    Signaling LED Max. 32 on 4 sides of 8 LED's each

    Number of pages Max. 99

    Determining the cycle time

    Note Once a new application has been created and loaded into the REF542 plus, its cycletime must be checked. The cyclic time is displayed on the HMI menu Service page,submenu Statistics.

    Warning!The application cycle time must be less than 30ms to ensure properfunctioning of the REF542plus. Longer times can result in poor and dangerousperformances like missing events and binary I/O changes.

    3.5.7.2 Add or move connection

    The function blocks can be linked one to each other in the drawing mode. By positioningthe mouse cursor over a connection point on a function block or at the beginning or onthe end point of a connection, the mouse cursor will change to the shape of a solderingiron.

     A total of 512 connections can be added. There are 502 numbers available for

    connections (11 … 512). Connection numbers 0 … 10 are for internal use.

    Add connection 

    When the soldering iron appears, hold the right mouse button down and drag the mouseto make a connection. The connection will end when the mouse button is released.

    The terminals of two function blocks can be connected in this way. The connection canalso end in the FUPLA without connecting to a terminal. The connection number isautomatically 1 or 2 in this case to indicate that it does not connect two function blocks.Now use the configuration dialog to assign a previously used connection number to theconnection. Connections with the same connection number linked even if they do notcontact each other.

    Connections run at right angles or in a straight line (therefore, also diagonally), depending

    on their setting. The relevant setting is made with the menu item Drawing Menu/View/Wires/Right-angled

    Or

    Drawing Menu/View/Wires/Straight.

    Move connections 

    When the soldering iron appears, hold the left mouse button down and drag the mouse tomove a connection point. When the mouse button is released, the connection point willremain at this position.

  • 8/20/2019 Configuration Tool Manual R2

    16/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 16 / 176 

    Note When a connection point is dragged or moved from one function block terminal toanother function block terminal, ensure that the connection is properly positioned atthe function block

    Check connections after a move

    There are two options for carrying out the above check: 

    Move the mouse pointer over the connection wire. Double-click the left mouse button tostart the configuration dialog for the wire. The terminal information area shows thenumber of the wire that is properly terminated. The numbers 11 and 12 indicate that thereis still no connection.

    OR 

    Move the function block in the FUPLA. If the connections are moved with it, theconnection is correct.

    3.5.7.3 Starting configuration dialogs

     A dialog window can be opened for all function blocks and connections. To start it, movethe mouse cursor over the function block or the wire. The configuration dialog appearsafter double-clicking the left mouse button.

    Configuration dialog function block

     As shown in Figure 1, this enables the function block to be configured and/or providesinformation on the terminated connections.

    Configuration dialog connection

    Figure 5: Configuration dialogue for a connection

    Enter field Net number: Enter the wire connection number here. The currently assignedconnection number will appear, a 1 or a 2. The numbers 1 or 2 only appear when theconnection ends with a terminal point in the FUPLA. To find the currently assigned

  • 8/20/2019 Configuration Tool Manual R2

    17/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 17 / 176 

    connection number, the configuration software searches the connection numbers from 11upwards for a free connection.

    The connection number is also shown in the function chart beside the connection.Setting range: 11 … 512 (Steps: 1)Default: Currently assigned connection, 1 or 2

    Information field Next unused net number: The next free connection is assigned here.The configuration software searches the connection numbers from 11 upwards for a freeconnection.

    Information field Maximum Number of Wires: This shows the maximum possible numberof connections in the current function chart. A total of 560 connections can be used.There are 502 connection numbers available.

    Information field used: This shows how many connections are already set up in thefunction chart.

    Input field Comment: Enter a comment, a name, for the connection here. The name willalso appear in the function chart beside the connection. This name will be assigned to allconnections with the same connection number.Setting range: 0 … 21 characters of the standard character set

    Default: Empty

    Button Choose next free: Click on this button to assign the next free connection numberto the connection. The dialog window is then closed, and the connection has thecorresponding number.

    OK: All settings are saved in the configuration software. The dialog window is closed.

    Cancel: Settings are not saved in the configuration software. The dialog window is closed.

    3.5.7.4 Deleting objects in the function chart

    Various options are available here:

    Delete a function block: Move the mouse pointer over the function block that is to bedeleted. Double-click the right mouse button. A confirmation query appears. Click the OK button to delete the function block or Cancelto keep the function block.

    Delete a connection: Move the mouse pointer over the connection which is to be deleted.Double-click the right mouse button. A confirmation query appears. Click the OK button to delete the connection or Cancel tokeep the connection.

    Delete the current page: Select the menu Draw Mode/Edit/Delete Page. A confirmationquery appears. Click the OK button to delete the page or Cancel to keep the page.

    Delete all connections in the application: Select the menu Draw Mode/Edit/ Delete

     All/Wires. A confirmation query appears. Click the OK button to delete the connections orCancel to keep the connections.

    Deleting all pages in the application: Select the menu Draw Mode/Edit/Delete All/Pages. A confirmation query appears. Click the OK button to delete the pages or Cancel to keepthe pages.

    3.5.7.5 Check function chart

    The function chart can be checked both in draw mode and connection mode:

  • 8/20/2019 Configuration Tool Manual R2

    18/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 18 / 176 

    Press the F9 function key on the keyboard or

    Select the menu item Drawing Menu/Utilities/Check Drawing F9 or

    Select the menu item Main Menu/Utilities/Check Drawing F9

    The check routine of the configuration software runs the following tests:

    Binary inputs and outputs: Availability of the numbers of the binary inputs and outputsused in the application. The availability depends on the number and type of binary inputand output boards in use.

    Device configuration: Availability of a device configuration. Has the configuration dialog inthe menu item Main Menu/Configure/Hardware been processed?

    Function blocks: All function blocks must be linked to at least one connection.

    DSP load: The DSP load (load on the protection and measuring unit) can be a maximumof 100%, a maximum of 250 protection parameters can be used and a maximum of 24protection functions can be used.

    Connections: The number of connections must not exceed 512.

    Double connections: Connections with the same number may only be connected to onefunction block output.

    Calculation of power: The configuration of the analog inputs must match the type ofpower calculation.

    Switching objects: A maximum of 62 switching objects may be configured.Every switching object must have its own interbay bus address and binary outputrepresented by the switching object must be physically present.

    Direct write-read command: A maximum 100 function blocks of this type are permitted.

    3.5.7.6 Setting the LCD screen and display language

    When the application has been set up, the mimic diagram for the LCD screen can beconfigured and the language in which the messages appear on the LCD screen selected.Select the menu items Main Menu/Configure/Display and Main Menu/Configure/DisplayLanguage.

    3.5.8 Upload/Download configuration

    Once the configuration is completed, the next action is usually to download it to thedevice. The Configuration Tool is able to perform such action, if the following conditionsare valid:

    • The communication between REF542 plus  LD HMI unit and the Configuration

    Tool has been established and it is working. To check such connection, ask theVersion of the REF542 plus  device (see 3.5.9.2). The following problems canhappen:

    o General communication error, the REF542 plus  device is not available.The problems and the possible solutions could be:

    REF542 plus base unit is not turned on: connect the right powercable to the Power Supply.

  • 8/20/2019 Configuration Tool Manual R2

    19/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 19 / 176 

    REF542 plus  LD HMI is not turned on: connect the right powercable to the power port of the LD HMI.

    REF542 plus  LD HMI is not connected to the REF542 plus  baseunit: connect it with the serial cable the right ports.

    REF542 plus  LD HMI is not ready (it is ready when waiting a

    configuration or when a configuration has been alreadydownloaded).

    Broken Cable: replace the cable.

    Coupling of optical connector to the HMI not perfect: re-insert theconnector.

    PC COM port malfunction: change the COM port or the PC.

    COM settings on Configuration tool not matching the currentconnection: change the COM settings (see 3.5.5 and 4.3.1). Inparticular, pay attention to: baud rate, data bits and base unitslave address.

    PC COM port already used by another software: close theapplication (e.g. TeraTerm), which is using the COM port, andset again the COM settings in the Configuration Tool.

    o Not all the version information is published but the REF542 plus device. Ifthe mandatory information is not published then the download action isnot allowed. A REF542 plus V4D.02 version should publish the followinginformation:

    REF542 plus  software/firmware versions: these are mandatory.Whatever is the version REF542 plus has to publish them

    Configuration information (partially available with version olderthan V4D.02): optional information. Remember, that sometimesthe information can be also a blank space (that can be a valid

    value)

    Char map information (only available with V4D.02 REF542 plus versions): mandatory information

    • The version of the REF542 plus must be compliant with the Configuration Tool.For example, if the device is a V4D.02 then also the Configuration tool must beV4D.02.

    • The Char Map on the REF542 plus device must match with the String file (STC)active into the configuration to be downloaded. For example, if the devicecontains the Latin char map, then only configurations with String file using thischar map are downloadable. The REF542 plus device is provided by default witha Latin char map, thus if another one is needed, then download first the newchar map (e.g. Cyrillic, see 4.3.9).

    The configuration of REF542 plus  is always up-loadable from the device. TheConfiguration Tool is able to perform such action, if the following conditions are valid:

    • Communication between REF542 plus  LD HMI unit and Configuration Toolestablished and working. To check such connection, ask the Version of theREF542 plus  device (see 3.5.9.2). Please follow the troubleshooting of thedownload action above.

  • 8/20/2019 Configuration Tool Manual R2

    20/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 20 / 176 

    • The version of the REF542 plus  device must be at least, V4B.0x. During theupload, the configuration information is translated to the V4D.02 version.

    3.5.9 Description of the menu items

    The following subsections provide a description of all menu items of the configurationsoftware. They are grouped into main and drawing menus.

    The main menu is displayed after starting the configuration software. The drawing menuis displayed when the menu item Main Menu/Configure/Drawing has been selected in themain menu.

    3.5.9.1 Main Menu/File

    New

     A new project under the name new.ref is created. Save it immediately under a different

    name, because this name is always reserved for new projects.

    Open… F2

     A dialog window for opening a file opens. The default file ending for the file format is ref. Ifnecessary, move through the disk and directory structure to open a configuration file.

    The dialog for opening the file will also appear when the F2 key on the PC keyboard ispressed.

     After the project has been opened, a drawing check is run. Any error messages must firstbe acknowledged before the project can be edited.

    Save F6

    The open application file is saved. If a new application file has been created, the filenew.ref will be saved in the default work directory of the configuration software. In thecase of a new file, use the menu item Save as … when it is saved for the first time.

     An application can also be saved by pressing the F6 function key on the PC keyboard.

    Note Before saving, the configuration software runs a check of the application. Anymessages that appear must be acknowledged before saving.

    Save as… F7

     A dialog window for saving a file appears. The file can be given any desired name andlocation. The default file ending for the file format is ref.

    The dialog can also be started by pressing the F6 function key on the PC keyboard.

    Note Before saving the configuration software runs a check of the application. Any messa-ges that appear must be acknowledged before saving.

  • 8/20/2019 Configuration Tool Manual R2

    21/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 21 / 176 

    Send E-Mail...

    Calls the default e-mail software and put the currently opened *.ref-file of theconfiguration software as attachment.

    Print

     A dialog window appears. Its appearance depends on the operating system and theinstalled printer. Additional inputs regarding the print process can be made here. 

    DrawingThe function chart is printed out, on several pages if necessary. 

    Parameters A file is printed with a list of all the parameters input in the application sorted by theirorigin. For example, this includes the device settings and also the parameter sets for theprotection functions. 

    Eventlist A file that lists all possible events that could be generated by the application is printedout. They are sorted by the function block that generated them. 

    ConnectionsThe connection numbers and the associated comments are printed out in list form. 

    CAN Settings All the configured CAN addresses. Not applicable for the time being. 

    Print Set Up

    When the configuration program is installed, the default printer is activated. If required,another printer can be directly selected and defined as the default printer.

    Print Preview

    It shows the preview of the drawing.

    MRU (Most Recently Used files)

    The four most recently used configuration files.

    Exit Application

    Ends the session of the configuration software.

    3.5.9.2 Main menu/Connect

    Note To use this menu the REF542 plus must be connected to the PC.

    Serial Port

    Starts the configuration dialog for the connection from the PC to the REF542 plus via theserial port. 

  • 8/20/2019 Configuration Tool Manual R2

    22/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 22 / 176 

    Send to REF542 plus 

    Sends (or download) the data from the opened application in the PC to the REF542 plus.

    Load from REF542 plus 

    Load (or upload) the application currently in the REF542 plus from the unit to the PC.  

    Read Faultrecorder…

    Load (or upload) the fault record data saved in the REF542 plus  into the PC when theNew Data button is pressed in the dialog window.

    Input Status…

    Load (or upload) the current status of the binary inputs of the first two input/output boardsof the REF542 plus when the New Data button is pressed in the dialog window. The dataare marked with the current PC system date and time and can be saved and printed.

    Output Status…

    Load (or upload) the current status of the binary outputs of the first two input/outputboards of the REF542 plus when the New Data button is pressed in the dialog window.The data is marked with the current PC system date and time and can be saved andprinted.

    Measurement…

    Load (or upload) the current status of the operational measured values from theREF542 plus. These are certain values that can also be displayed in the LC displayscreen above the mimic diagram.

    The continuous measured value transmission to the PC can be configured in theoperational measured values dialog window. The operational measured values and, ifdesired, the values from the binary inputs and outputs, will then be regularly transmitted

    from the REF542 plus to the PC.

    The data is marked with the current PC system date and time and can be saved andprinted.

    Condition Monitoring

    Not applicable for the time being.

    Version

    Reads the current versions of the REF542 plus  micro controllers (MC) and theconfiguration software. The information is displayed in a dialogue window. If a connectionto the REF542 plus cannot be established, an error message will be shown.

    Figure 6: Connection warning when REF542plusis not reachable

  • 8/20/2019 Configuration Tool Manual R2

    23/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 23 / 176 

    If the REF542plus is available, then the version dialog is shown.

    Figure 7: Version dialog

    The versions are divided in three groups:

    • Software: micro controller, DSP, HMI, field bus type, analog input 20mA,configuration software versions. The REF542plus version must be equal to theconfiguration tool version in order to download a configuration (the upload isalways possible).

    • FUPLA: the configuration information. There are: file name, project name, feedername, FUPLA date, strings file name, license key.

    • Char Map (HMI char set used): header version, char map version, char mapdescription and code page (and char map family code page, which is a reservedparameter). The REF542plus stored char map must be equal to the downloadedconfiguration STC file. For example, if the configuration tool is on English STCfile, then the char map on the device must be Latin. If not, it is necessary todownload first the char map into the device (see 4.3.9) and then the configurationdownload.

    3.5.9.3 Main menu/View

    Toolbar

    Opens the tool bar on the top side of the configuration software

  • 8/20/2019 Configuration Tool Manual R2

    24/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 24 / 176 

    Status Bar

    Sets the status bar at the bottom of the configuration software

    Transfer Bar

    Opens the transfer bar below the toolbar

    3.5.9.4 Main menu/Configure

    Global Settings…

    Starts a configuration dialog in which the basic settings are made. Functions such as faultmonitoring, coil monitoring and default values such as the general filter time and thedevice address are defined here. In addition, the system messages (events), which canbe sent from the system itself to a station control system, can be configured in two otherdialogs.

    Note This configuration dialog must be edited before an application can be created.

    Hardware...

    Starts a configuration dialog in which settings that describe the delivery variations of theREF542 plus can be made.

    Note 

    This configuration dialog must be edited before an application can be created.

    Terminals

    This menu item enables the selection of two submenu items. With them the analog inputsand outputs can be configured. Correct configuration of the analog inputs in particular isextremely important if the REF542 plus is to function properly.

    Analog Inputs...

    Starts a configuration dialog in which settings can be made to adapt the analog inputs ofthe REF542 plus  to the sensors or transducers used. Information important for startingand tripping protection functions is sent to the bay control and protection unit via theseinputs. Measured values are also recorded with these sensors or transducers.

    This configuration dialog allows also the arrangement of other parameters: networksettings and calculated values, such as the selection of metering system and the type ofpower calculation.

    Note The same measurement recorders are used for the protection and the measurementfunctions.

  • 8/20/2019 Configuration Tool Manual R2

    25/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 25 / 176 

    Analog Inputs 4-20 mA...

    Starts a configuration dialog in which settings can be made to adapt the analog inputs 4-20 mA board of the REF542 plus used.

    Analog Outputs...

    Starts a configuration dialog in which settings that influence the REF542 plus  analogoutputs can be made. The operational measured values that must be output are selectedand the dynamic range of the output signal can be influenced.

    Component

    Not applicable for the time being

    Drawing

    Starts the function chart editor. Function blocks can be added, connected and configuredhere to set the desired functions for the bay control and protection unit.

    The menu bar with the drawing menu appears. The menu items of the drawing menu will

    be described later.

    HMI/Single Line Diagram…

    Starts the editor for the LCD screen. The single line diagram can be set up here. Itselements are connected to the corresponding function blocks. At any time it is alwayspossible to select IEC or ANSI bitmaps to be shown on the HMI.

    HMI/Display Language…

    Starts the dialog that sets the language version for the texts displayed on the LCDscreen. At the same time the correct message texts for the application are selected. Thedialog shows also the char set code page of the selected language. The configurationtool uses this value in order to handle properly the non-Latin character, like Arabic,

    Cyrillic, Hebrew, etc.

    HMI/Key Code

    This menu contains two sub-menus that allow on-line setting up of the protection andcontrol keys. If the REF542plus is connected properly, the current key is shown in thedialog. The key can, then, be changed. When the OK button is pressed the key is senttoe the REF542plus.

    The key can be composed of maximum 16 alphanumeric chars.

    Set protection keyIt opens the dialog to change the current protection key.

    Set control key

    It opens the dialog to change the current control key.

    HMI/Char Maps…

     Allow to manage the Char Maps bitmap fonts both on the PC and into the device. See4.3.9.

    HMI/LED Bars...

     Assigns the display of the measurement values to the LED-bars according to thefollowing configuration dialog.

  • 8/20/2019 Configuration Tool Manual R2

    26/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 26 / 176 

    Figure 8: Configuration dialog to assign the measurement values of the LED bars

    Enabled Web Interface

    The Web Server and the communication interface can be enabled by the selection of thesubmenu Main Menu/Configure/Enable Web Interface.

    The Web Server Options are into the submenu Main Menu/Configure/Web ServerOptions.

    Web Server Options/Enable Configuration Download

    It can be selected in order to allow the download also of the Web Server configurationwith the FUPLA configuration. The de-selection can speed up the download wheneveronly a parameterization on protections is performed.

    Web Server Options/User Administration…

    Set the user accounts of the server. The user name and the password can be set. Thesesettings influence which actions is allowed via a web browser.

  • 8/20/2019 Configuration Tool Manual R2

    27/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 27 / 176 

    Figure 9: Configuration dialogs to assign the Web Server users name and password

    Web Server Options/SMS Configuration…

    The REF542 plus can be set as itself an SMS gateway via a GSM modem, or it can referto another device connected via TCP/IP. Usually only one REF542 plus  in a switchgearhas a GSM modem, thus all the others refer to this one.

  • 8/20/2019 Configuration Tool Manual R2

    28/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 28 / 176 

    Figure 10: Configuration dialogs to set the SMS messaging system parameters

    Web Server Options/TCP IP Configuration…

    This important menu launch the following dialog.

    Figure 11: Configuration dialog for the TCP/IP configuration of the Web Server

    The IP address of the REF542 plus, the subnet mask and the default gateway. Theseparameters are crucial for the TCP/IP communication.

    Web Server Options/Web Pages Languages

    The following dialog handles the web pages languages.

  • 8/20/2019 Configuration Tool Manual R2

    29/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 29 / 176 

    Figure 12: Configuration dialog for the languages available on the web pages

    Web Server Options/Generate SVG File

    It saves the Standard Vector Graphic file, which represents the configured Single LineDiagram.

    Web Server Options/Generate SCL File

    It saves the Web Server Configuration file based on the standard IEC 61850 SubstationControl Language.

    Web Server Options/Import SCL File

    It imports the Web Server Configuration from an existing *.scl file. It overwrites the currentconfiguration.

    3.5.9.5 Main menu/Utilities

    Check Drawing F9

    Starts the software routine that checks the drawing according to specific criteria. Ifnecessary, relevant error messages appear after the check.

    Generate Report Files

    Creates report file of the currently opened configuration file

    Protection Functions...

    Lists all protection function configured. The configuration dialog for the setting parametercan be opened by double clicking the desired protection function

  • 8/20/2019 Configuration Tool Manual R2

    30/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 30 / 176 

    3.5.9.6 Main menu/Options

    Language

    Only one more submenu needs to be selected to select the language version of theconfiguration software. All menu items, dialogs and messages will then appear in the

    selected language. This setting is kept every time the software is started in future.

    3.5.9.7 Main menu/Help

    Function Keys F1

    Opens an information window that shows the assignment of the function keys on the PCkeyboard. The appropriate function key is also shown with the corresponding menu items.

    The following table shows the assignment of the function keys in the main menu and inthe drawing menu.

    Table 3: Assignment of the function keys

    Key Main Menu Drawing Menu

    F1 Help on function keys Information dialog function keys

    F2 Open file… -

    F3 - Wire mode: Connect FUPLA symbols

    F4 - Draw mode: Move FUPLA symbols

    F5 - Refresh drawing (screen refresh)

    F6 Save Save

    F7 Save as… -

    F8 - Repeat last add action (only for logicsymbols)

    F9 Check Drawing Check Drawing

    F10 - Sequences ON/OFF

    F11

    F12 FUPLA Monitor

    About…

    Opens an information window with copyright and version information of the configurationsoftware.

    3.5.9.8 Drawing menu/File

    Save F6

    The open application file is saved. If a new application file has been created, the filenew.ref will be saved in the default work directory of the configuration software. In thecase of a new file, use the menu item Save as … when it is saved for the first time.

  • 8/20/2019 Configuration Tool Manual R2

    31/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 31 / 176 

     A project can also be saved by pressing the F6 function key on the PC keyboard.

    Note Before saving, the configuration tool runs a check of the application. Any messagesthat appear must be acknowledged before saving.

    Exit Edit

    The editor used to create and edit the function chart is closed. The function chart displaydisappears and the main menu menu bar appears again.

    3.5.9.9 Drawing menu/Edit

    Copy Page…

    The shown page on the editor is copied into the Windows® clipboard.

    Paste Page…

    If the Windows® clipboard contains a Drawing page, then it is pasted into the shownpage. The Configuration Tool checks the pasted object. Thus, if an object reached themaximum number of installations then it will not be pasted into the page.

    Insert Page…

    Starts a dialog with which a page can be added. The number of the page is entered in theinput field before an empty page is added. An information window shows the last pagethat has been used in the application.The Accept and Cancel buttons are used to add the page or to cancel the procedure. Thedialog window is closed and the user is returned to the drawing menu.

    The configuration software provides a maximum of 99 pages for one application.

    Delete Page…

    Starts a dialog with which the current page can be deleted. The Accept and Cancelbuttons are used to delete the page or to cancel the procedure. The dialog window isclosed and the user is returned to the drawing menu.

    Delete All

    This menu item has two submenu items. They provide the option of deleting allconnections or all pages.

     After making the selection, a confirmation window appears. Click the OK button to confirmthe deletion or Cancel to delete nothing. The dialog window is closed and the user is

    returned to the drawing menu.

    Domain

    Not applicable for the time being

    Search Wire…

    Opens a dialog window where all connections with the same number can be found. Theconnection number is entered into the appropriate input field.

  • 8/20/2019 Configuration Tool Manual R2

    32/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 32 / 176 

    The OK button closes the dialog window and the connections with the number input aremarked red on all pages of the function chart.

    The Cancel button closes the dialog window and returns the user to the drawing menu.

    Search Object…

    This menu item has two submenu items. They enable a function block (referred to as anobject here) to be searched either by its interbay bus address or its object number.

     A dialog window appears after making the selection. The interbay bus address or theobject number can be entered into the input field.

    The OK button closes the dialog window and the object with the interbay bus address orthe object number that was entered is displayed in the function chart.

    The Cancel button closes the dialog window and returns the user to the drawing menu.

    3.5.9.10 Drawing menu/view

    Toolbar

    Opens the toolbar on the top side of the configuration software

    Status Bar

    Sets the status bar at the bottom of the configuration software

    Sequences F10

    This menu item shows and hides all labels on the function blocks and connections. TheF10 function key on the PC keyboard does the same thing.

    Wires

    This menu item has two submenu items. This enables the user to select whether con-nections can run only at right angles (perpendicular and horizontal) or in straight lines(perpendicular, horizontal and diagonal).

    This setting may be changed at any time and affects all connections.

    Next page PgDn

    Shows the next page in the function chart. The PgDn (Page Down) key or Screen↓ on thePC keyboard does the same thing.

    Previous page PgUp

    Shows the previous page in the function chart. The PgUp (Page Up) key or Screen↑  onthe PC keyboard does the same thing.

    Go to page...

    Starts a dialog with which any page of the function chart can be displayed. The number ofthe page required is entered into the input field. An information window shows the lastpage that has been used in the application.The OK and Cancel buttons show the page or cancel the procedure. The dialog windowis closed and the user is returned to the drawing menu.

    The configuration software provides a maximum of 99 pages for one application.

  • 8/20/2019 Configuration Tool Manual R2

    33/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 33 / 176 

    Zoom…

    Opens a dialog window with which the page view can be enlarged. The percentage factoris entered into the appropriate input field. It is always based on the default size of 100%.

    Redraw F5

    Refreshes the display on the screen. The size and the markings of searched objectsremain as before.

    Reset

    Removes the markings on searched objects and resets the size to the default factor of100%. Page 1 of the application also appears.

    3.5.9.11 Drawing menu/Insert

     A menu with all possible function blocks arranged by function groups appears. Thevarious submenus are used to select the corresponding function blocks. The selected one

    is then added to the function chart.

    There, the sequence of descriptions corresponds to the menu structure of the Insertmenu described here. Therefore, a list of the function groups with their function blocks isnot given here.

    3.5.9.12 Drawing menu/Utilities

    Check drawing F9

    Starts the software routine for checking the drawing according to specific points. Ifnecessary, relevant error messages appear after the check.

    FUPLA Monitor F12

    This menu item can be marked by selecting it. A then appears beside the menuitem. If also the special cable for the optical – RS 232 interface for the communicationbetween the PC with the HMI Control Unit is connected, the logical level of the connectionin the FUPLA can be shown on line.

    Switching objects…

     An information dialog appears. It lists the interbay bus addresses available for the swit-ching objects. Additional information is also shown adjacently:

    ----------: The interbay bus address is not used by a switching object.

    “EXAMPLE TEXT“:Text from the Comment input field in the configuration dialog of theswitching object.

    “empty“: The interbay bus address is used by a switching object. However, no commenttext has been entered.

    Note When the mouse cursor is placed over a line with the data of a switching object andthe left mouse button is double-clicked, the dialog is closed and the switching objectis marked in the function chart.

  • 8/20/2019 Configuration Tool Manual R2

    34/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 34 / 176 

    Protection functions…

    The dialog window shown below appears. It lists the protection functions in theapplication.

    Figure 13: Dialog drawing menu/Utilities/protection functions…

    Double-clicking a protection from the list, then the protection function block on the editoris shown and marked.

    The Close button ends the dialog.

    Wires…

     An information dialog with the numbers of the connections in use opens. The number ofconnections with this number is shown adjacently in parentheses. At the end the text thatwas entered into the comment field of the configuration dialog of the connection follows.

    Note When the mouse cursor is placed over a line with the data of a connection and theleft mouse button is double-clicked, the dialog is closed and all relevant connectionsare marked in the function chart.

    3.5.9.13 Drawing menu/options

    Block Moving of Objects

    This menu item can be marked by selecting it. A then appears beside the menuitem. The function blocks in drawing mode are moved only when the Shift key is helddown.

    Move Objects Transparently

    If this menu item is marked, the white colored area of the function blocks becomestransparent when it is moved.

  • 8/20/2019 Configuration Tool Manual R2

    35/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 35 / 176 

    FUPLA Monitor

    The color of the logical high and low level can be defined.

    Line Color High LevelThe line color for logical high level can be selected

    Line Color Low LevelThe line color for logical low level can be selected

    Unicode Font

    This menu item can be marked by selecting it. A then appears beside the menuitem.

    Selecting this menu item the FUPLA editor uses the Arial font, which supports most of theUNICODE characters (e.g. Latin, Arabic, Hebrew, Cyrillic, etc.).

    De-selecting this menu item the FUPLA editor uses the Courier font, which supports only ASCII-Latin characters.

    On certain screen, and with certain resolutions the Unicode font (which is also True Type)

    can be less readable due to Windows scaling functionality. It is up to the engineer tochoose the preferred one.

    3.5.9.14 Drawing menu/Help

    Function keys F1

    Opens an information window that shows the assignment of the function keys on the PCkeyboard. The function keys are also shown with the corresponding menu items.

    About…

    Opens an information window with copyright and version information of the configurationsoftware.

    3.5.10 Description of the status bar

    The main view status bar shows the following information:

    COM port settings: the selected COM port and the base unit address

    Web Server settings: it appears if the Web server is enabled. The IP address is shown aswell between square brackets.

    String file name (STC). When the opened configuration is an old one (Release 1 – V4C orolder) the file name is not shown. Then it is strongly suggested to update it with the new

    STC files.

    Charset and codepage. It represents the charset used by the configuration tool in order tointerpret and convert the UNICODE strings of the configuration to the ASCII charshandled by the REF542 plus.

  • 8/20/2019 Configuration Tool Manual R2

    36/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 36 / 176 

    4 Setting up REF542 plus 

    In this chapter you will find the following information: 

    On the options for adding required functions to your bay control and protection device. 

    On the settings that can be made in the configuration software to adapt the REF542 plus to the application. 

    On configuring the function plan (FUPLA) to the bay in which the unit is operating. 

    On implementing the protection functions by using the related function blocks. 

    On all other function blocks that can be added to the FUPLA. 

    If the unit has been delivered with a custom application, this section will assist inunderstanding the function blocks with respect to their function and configuration.

    4.1 Basic informationThe variety of functions offered by the REF542 plus  results mainly from the PLC-likeprogramming option provided by the configuration software. Various function blocks arelinked to one another in one FUPLA.

    The objects that can be added to the function chart are referred to as function blocks.They are used to address binary and analog inputs and outputs and to define switchingoperations, interlocking and protection functions.

    Each function block has inputs and/or outputs that can be used within the FUPLA.Double-click the left mouse button to open the configuration dialog of the function blockon which the mouse cursor is resting.

    Normally a configuration or application has been created to be precisely customized for

    the purpose and location of the REF542 plus switchbay control and protection device. Thisconfiguration has been loaded into the REF542 plus  and saved there. It specifies whatprotection functions are tripped under what conditions, when and what interlockings areactivated and what initial variables are set for the analog and binary outputs of theREF542 plus. The application implemented with the FUPLA provides exactly theprotection, measurement, supervision and control functions that are required.

    4.2 Connecting inputs and outputs

    The REF542 plus  receives a great variety of information on the equipment beingmonitored through its analog and binary inputs. These input quantities are digitallyprocessed in the function chart. The REF542 plus outputs are addressed from the FUPLA,

    for example to trip the switching objects in the bay.To enable the REF542 plus  inputs and outputs to be used in the function chart, they arerepresented by function blocks, the switching objects. This enables several inputs andoutputs to be combined.

    4.3 General settings

    Before a FUPLA can be created and exported to the REF542 plus, some settings must bemade in the PC and the bay control and protection unit for which the application is to beprogrammed.

  • 8/20/2019 Configuration Tool Manual R2

    37/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 37 / 176 

    4.3.1 Serial Port

    To enable the Serial Port (RS232) of the computer to be used to transmit theconfiguration/application, the applicable dialog window must be edited. After starting the

    configuration software, open the menu Main Menu/Connect/Serial Port . The dialogwindow has five option fields where settings for the computer Serial Port can be made.

    Configuration dialog

    Figure 14: Configuration dialog for the REF542 plus Serial Port

    Option field ComPort: Here enter the active interface on the computer to enablecommunication from the PC to the REF542 plus over a special serial optical cable.

    Setting range: [COM1, COM2]

    Default: COM 1

    Option field BaudRate: Here enter the baud rate of the COM port. Release 2 supports19200 bps.

    Setting range: [9600, 19200]

    Default: 19200

    Option field Data Bits: Here enters the data bits of the COM port. REF542plus V4D.02works with 8 bits. Older versions work with 7 bits.

    Setting range: [7,8]

    Default: 8

    Edit field Slave Address: Here enter the REF base unit slave address. This addressallows the user to connect more REF base unit to the same HMI. It has nothing to do withthe REF542plus communication card interface.

  • 8/20/2019 Configuration Tool Manual R2

    38/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 38 / 176 

    Setting range: [1..254]

    Default: 99

    Note Since it is possible to connect more REF542plus base units to the LD HMI, theengineer must configure the referred base unit. In fact, the configuration tool

    uploads/downloads the configuration from/to the REF542plus base unit addressed bythe base unit slave address field in the Serial port configuration.

    Figure 1 shows a PC with the Configuration Tool that is connected to an LD HMI via serialcommunication port (COM1 or COM2). The LD HMI is shared by three REF542plus baseunits, which have three different addresses (on a RS485 bus). In order to connect theconfiguration tool with a certain REF542plus base unit it is necessary to configure theright salve unit address. For example if the configuration tool wants to communicate withthe first REF542plus base unit, then the Slave Address base unit (in the Serial portdialog) must be set to 99.

    Figure 1: PC connected via LD HMI to several base units

    Note The base unit address set in the Serial Port dialog can be different from the slaveaddress set into the hardware configuration (see next paragraph). This is the case,when it is necessary to change a slave address of a REF542plus base unit. For

    example if I need to change the second REF542plus base unit address (in Figure 1)from 100 to 103, it is necessary to talk with the current base unit which has address100, but then configure the Hardware configuration with 103. After the download ofthe configuration, the REF542plus restarts with the new address 103. So any furtherconnection request with address 100 will fail.

  • 8/20/2019 Configuration Tool Manual R2

    39/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 39 / 176 

    Note By default, in production, REF542plus base unit is set with address 99 (which is thedefault of the configuration tool as well).

    Note The following options are set. Option field Parity:

    Default: Even Option field Stop BITS:

    Default: 1

    Button OK: All settings are saved in the configuration software. The dialog window isclosed.

    Button Cancel: Settings are not saved in the configuration software. The dialog window isclosed.

    4.3.2 Global Settings

    The "Global Settings" dialog window is to be opened with the menu MainMenu/Configure/Global Settings . The desired general configuration inputs are madehere. With the exception of those for trip circuit supervision, the inputs are independent ofthe REF542 plus model supplied.

    Note 

    It is absolutely essential to edit the configuration dialogs Main Menu/Configure/

    Global Settings and Main Menu/Configure/Hardware before the drawing editor isopened.

  • 8/20/2019 Configuration Tool Manual R2

    40/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 40 / 176 

    Configuration

    Figure 15: Configuration dialog for the REF542 plus Global Settings

    Input field Node address: The Node address sets the addressing of the bay control andprotection unit over the interbay bus. Every device installed on an interbay bus isassigned a unique device address.Setting range: 1 ... 255Default: 99

    Input field Project: Enter a name for the project here. The name entered is only for a moreprecise description and has nothing to do with the name under which the application canbe saved. One project can include several bays.Setting range: 0 … 20 characters (standard character set)

    Input field Feeder: Enter a name for the feeder for which the application will be created as

    part of the above project. The name entered is only for a more precise description andhas nothing to do with the name under which the application can be saved.Setting range: 0 … 20 characters (standard character set)

    Input field Global filter time: Time in ms required for an input signal to address the binaryinput to be detected as such. The general filter time is valid for all binary inputs and isadded to a non-adjustable filter time that is set by the design of the unit (1 ms). The last isreferred to as the hardware filter time.Setting range: 0 … 999 ms (Increment: 1 ms)Default: 20

  • 8/20/2019 Configuration Tool Manual R2

    41/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 41 / 176 

    Input field active protection set: Parameter set of the protection parameter that is intendedto be active when the REF542 plus is started. The active parameter set can be changedlater with the local control on the REF542 plus operator view.Setting range: 1 … 2 (Increment: 1)Default: 1

    Information field changes: A variable that shows the number of changes to theconfiguration for the service in encrypted form appears here.

    Information field Name of configuration: This shows the name under which the applicationfile/configuration file is saved.

    Input range coil supervision: There are four checkboxes here that enable trip circuitsupervision (=coil supervision) to be activated for two trip circuits each for a maximum oftwo binary input and output boards.

    Checkbox board 1_1: Activates or deactivates trip circuit supervision for binary output 1on the 1st input and output board.

    Checkbox board 1_2: Activates or deactivates trip circuit supervision for binary output 2on the 1st input and output board.

    Checkbox board 2_1: Activates or deactivates trip circuit supervision for binary output 1on the 2nd input and output board.

    Checkbox board 2_2: Activates or deactivates trip circuit supervision for binary output 2on the 2nd input and output board.

    Checkbox board 3_1: Activates or deactivates trip circuit supervision for binary output 1on the 3nd input and output board.

    Checkbox board 3_2: Activates or deactivates trip circuit supervision for binary output 2on the 3nd input and output board.

    Checkbox Errorsupervision: Activates fault supervision here by checking the box. Itmonitors the switching of the controlled binary outputs. If the relays have not reacted tothe switching command, an error message will appear on the LCD screen of the

    REF542 plus HMI Control Unit.

    Checkbox Doubleswitching: This provides the option of activating double actuation. Then,after selecting a switching object once on the LCD screen of the REF542 plus HMI ControlUnit, the option of sending two switching commands to this switching object is available.In general, three seconds are available for sending a switching command after selecting aswitching device. If double actuation is activated, another 10 seconds is available to sendanother switching command after the first switching command.

    Checkbox events: Mark this checkbox to allow event data to be generally sent to a stationautomation system. See also the system events 1 and 2 buttons.

    Checkbox autoreclosure (AR): Not applicable for the time being.

    Option field test mode: Select whether entry to the test mode is generally allowed via theHMI Control Unit.

    Button OK: All settings are saved in the configuration software. The dialog window isclosed.

    Button Cancel: Settings are not saved in the configuration software. The dialog window isclosed.

    Button system events 1: Clicking on this button starts a dialog window in which variousdevice-based events can be enabled. If they occur they are then sent to the stationautomation system.

  • 8/20/2019 Configuration Tool Manual R2

    42/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 42 / 176 

    See also button system events 2 and checkbox events. Events may also be enabled inthe configuration dialogs of some function blocks and they are then based on these.

    Button system events 2: Clicking on this button starts another dialog window in whichvarious device-based events can be enabled. If these events occur they are then sent tothe station control system.

    See also button system events 1 and checkbox events. Events may also be enabled inthe configuration dialogs of some function blocks and they are then based on these.

    4.3.3 Hardware

    The hardware configuration dialog window is opened with the menu Main Menu/Configure/Hardware. General inputs on the REF542 plus  model for which theconfiguration/application is to be created may be made there.

    Note It is absolutely essential first to edit the configuration dialogs Main Menu/ Configure/Global Settings and Main Menu/Configure/Hardware to get to the drawing editor.

    Figure 16: Dialog window for the REF542 plus hardware configuration

  • 8/20/2019 Configuration Tool Manual R2

    43/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 43 / 176 

    Input range REF542 plus housing: Various inputs regarding the type of housing in use canbe made here:

    Options IO-slots: Specifies whether a normal housing (2 input/output slots) or a widehousing (4 input/output slots) is in use.

    Input range binary IO boards:

    and buttons: Increase or reduce the number of active binary input and outputboards. The desired number is shown in the information field on the left.

    Options relay: Enter the type of relay that is used on the active binary input and outputboards. Either conventional (mechanical) relays or Solid State (transistor) relays.

    Warning! Different binary I/O boards; with mechanical relays and with solid state relays,cannot be combined in one REF542 plus device.

    Information field binary inputs, binary outputs: This shows how many binary inputs andoutputs are available depending on the number and type of boards in use.

    Input range analog input 4-20 mA boards: Configure the number of analog input 4-20 mAboards in use here. These boards can only be used in the deep housing.

    Input range analog output boards: Configure the number of analog output boards in usehere. These boards can only be used in the deep housing.

    The and buttons are used for settings. The information field shows the number ofpossible analog outputs.

    Option field field bus: Mark whether the process bus is to be used or not. CAN option isunused with this version, for the time being CAN is not applicable.

    Input range communication interface: Use the button that opens the list field to openthe interbay bus variation selection list. Depending on the type of interbay bus theparameters button is then activated.

    Button parameters: a dialog appears depending on the protocol selection. When the SPAis selected, the REF542plus slave address is required and the network topology. WhenMODBUS is selected the first and the second port addresses can be set. When IEC60870-5-103 is chosen, it is possible to change the unit address, the baud rate and the ASDU type. When LON is used, only the unit address can be set.

    Input value base unit slave address: Configure the address of the configured REF542 plus base unit. This value can be different to the current one (see Serial Port settings).

    Button OK: All settings are saved in the configuration software. The dialog window isclosed.

    Button Cancel: Settings are not saved in the configuration software. The dialog window isclosed.

    4.3.4 Analog inputs

    The menu Main Menu/Configure/Terminals/Analog Inputs opens the dialog windowshown below. The analog measurement inputs of the REF542 plus can be configured andset for the transducers in use. The settings are particularly important for the safe andproper functioning of the unit.

  • 8/20/2019 Configuration Tool Manual R2

    44/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 44 / 176 

    Figure 17: Analog Inputs page into the configuration dialog

    The Inputs page shows the complete overview of the Analog Inputs settings: sensors,nominal values, calculated values.

    The Analog Input Board field represents the ID of the installed board onto theREF542 plus. The configuration software automatically configures the sensor when theuser selects the board from the dialog below, by pressing Get group data button.

    Figure 18: Analog Boards Dialog

    Selecting the board from the list, the sensors type appear on the right. The sensor

    acronyms are: CT – current transformer, RC – current rogowsky coil, VT – voltagetransformer, VS – voltage sensor, CT 0.2 – current transformer with Input Nominal Valueset to 0.2 A.

    The REF542plus Analog boards definition is into the Boards\REF542plusAI.xml file.

    It is always possible to configure manually all the sensors just double-clicking on thecorrespondent row into the table, or by pressing Space on the keyboard. The sensordialog is shown below.

  • 8/20/2019 Configuration Tool Manual R2

    45/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 45 / 176 

    Note Every time a new analog board is selected from the analog boards dialog, all thechannel values (RPV, RSV, etc.) are overwritten with the default values.

    Note The analog board name (e.g. 750170/814) is substituted by the “Custom board” namewhen the user makes any changes to the analog input channels type.

    Please, refer to the REF542plus Protections Manual document for additional informationon the analog input configuration.

    4.3.5 Analog Input 0/4 – 20 mA

    The 20mA input board is employed to interface sensors using a current signal in the

    range from 4 up to 20 mA for signal transmission. Up to 6 sensors can be connected tothe board. Density and temperature sensors are available in the typical application of thisboard.

    The configuration of this board is available in the dialog shown below.

    Figure 19: Configuration dialog for the analog input 0/4-20mA

    Multiple choice Sensor Type: It is the type of the sensor. The user can choose in thecorresponding Combo Box among four possibilities: Not used, Trafag, Density 4-20 mA,General purpose 4-20 mA.

  • 8/20/2019 Configuration Tool Manual R2

    46/176

     

    ProtectIT Multifunction Protection and Switchgear Control Unit, model REF542 plus,

    Configuration tool manual

    1VTA100003-Rev.3, en PTMV, 22.10.03 46 / 176 

    Multiple choice Density Unit: It is the unit identifier for the density measurement to bevisualized on the HMI when sensor type is “Trafag” or “ Density 4-20mA”. The unit can beselected through the Combo box among three possibilities: Kpa, Kg/m

    3, Psi.

    Edit box Measure Unit: In case of General Purpose Sensor the unit name must be editedthrough this dedicated text box. The box is disabled when sensor type is “Unused”,“Trafag” or “ Density 4-20mA”. The string can be 7 characters long at most.

    Edit box Measure name: This is the string descriptor of the measurement acquired by thesensor. It is what the user sees on the HMI Measurement Table. The name has to be 20characters long at most.

    Edit box Temperature name: This is the descriptor of the temperature measurementacquired by the Trafag sensor. It is what the user sees on the HMI Measurement Table. Ifthe Sensor Type is not Trafag the text box is disabled. The name has to be 22 characterslong at most.

    Edit box Data value at 4mA and 20 mA: These are the engineering values correspondingto the current levels of 4mA and 20mA. The text box for setting this parameter is enabledonly in case of Sensor Type “Density 4-20mA” and “Gen. Pur. 4-20mA”. If Sensor Type is“Unused” or “Trafag” then the parameters are not used and the corresponding text boxes

    are disabled. The unit is the one