cona -control - ari armaturen...edition 04/18 - data subect to alteration - regularly updated data...

8
Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com! Data sheet 685001 englisch (english) External test chamber - with flanges (Fig. 685....1) - with screwed sockets (Fig. 685....2) - with socket weld ends (Fig. 685....3) - with butt weld ends (Fig. 685....4) Bolt-on test chamber (as option for ARI-CONA ® ) CONA ® -control Monitoring system for steam traps CONA ® -control - Monitoring system for steam traps Features: • Identification of failes steam traps - Leaking steam trap (energy wastage) - Blocked steam traps (poor plant performance) • Patent applied, safe temperature sensor • Local indication of maintenance requirement • Continous monitoring of trap performance for instant indication of failure • External chamber and sensor may be used on all types and makes of steam trap • Network compatible by AS-i-Bus linking of chambers and sensors (optional) • Single operation with relay outputs (optional) • AS-i-Bus gives the opportunity for visual display (optional) Central status indication External test chamber Bolt-on test chamber Bus circuit PC connection Linear topology Tree topology Steam trap Steam trap with bolt-on test chamber and sensor External test chamber with sensor Measuring amplifier Inclusive: - AS-i-Master - Power supply Measuring amplifier AWH ARMATUREN- WERK HALLE GMBH ® HALLE A member of the ARI group

Upload: others

Post on 18-Feb-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

  • Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com! Data sheet 685001 englisch (english)

    External test chamber - with flanges (Fig. 685....1) - with screwed sockets (Fig. 685....2) - with socket weld ends (Fig. 685....3) - with butt weld ends (Fig. 685....4)

    Bolt-on test chamber (as option for ARI-CONA®)

    CONA®-controlMonitoring system for steam traps

    CONA®-control - Monitoring system for steam traps

    Features: • Identificationoffailessteamtraps-Leakingsteamtrap(energywastage)-Blockedsteamtraps(poorplantperformance)

    • Patentapplied,safetemperaturesensor• Localindicationofmaintenancerequirement• Continousmonitoringoftrapperformanceforinstantindicationoffailure

    • Externalchamberandsensormaybeusedonalltypesandmakesofsteamtrap

    • NetworkcompatiblebyAS-i-Buslinkingofchambersandsensors(optional)

    • Singleoperationwithrelayoutputs(optional)• AS-i-Busgivestheopportunityforvisualdisplay(optional)

    Central status indication External test chamber Bolt-on test chamber

    Bus circuit

    PC connection Lineartopology

    Treetopology

    Steamtrap

    Steamtrapwithbolt-ontestchamberandsensor

    Externaltestchamberwith

    sensor

    Measuringamplifier

    Inclusive:

    -AS-i-Mas

    ter

    -Powersu

    pply

    Measuringamplifier

    AWH ARMATUREN-�WERK HALLE GMBH

    ®

    HALLE

    AmemberoftheARIgroup

  • 2 Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!

    Central status indication •Centralstatusindicationofupto30steamtraps•ConnectionofmeasuringamplifierbyAS-i-Bus•IntegratedAS-i-Master/Gateway•IntegratedpowersupplyforAS-i-Bussystem•Oneindicationcardnecessaryforeachmeasuringamplifier

    Technical data

    InternalBus-systemforsteamtraps: AS-i-Bus

    Interfaceforsuperiorsystems: ProfibusDPotherBussystemsonrequestAmbienttemperature: 0to+50°C

    Supplyvoltage: 100-240V~optional:24V~Dimensionsofbody(HxWxD): 360x200x160mm

    Bodymaterial: PC/ABS

    Enclosure: IP65

    Measuring amplifier •IndicationofoperatingstatusforthesupervisingsteamtrapsbyLED’s•Adjustablecategorytemperaturefor„Blockage“indication•AS-i-bussystemoption(necessaryforconnectiontothecentralstatusindication)•Optionallysingleoperationwithrelayoutputs(evaluatione.g.overSPSpossible)•Measuringamplifierrequiredforeachtestchamber•Maybewallorpanelmounted•Maximumdistancetothesensorapprox.1m

    Technical data

    Ambienttemperature: 0upto+70°C

    Supplyvoltage: 18-36VDCorbyAS-i-Bus

    Dimensionsofbody(HxWxD): 75x125x60mm

    Bodymaterial: Aluminum

    Enclosure: IP65

    Currentconsumption:

  • Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com! 3

    CONA®-control 685 External test chamber - PN40 - DN15-25

    rotatedview

    External test chamber (Forged steel, Stainless steel)

    Fig. 685....1 with flanges

    Fig.685....2withscrewedsockets

    Fig.685....3withsocketweldends

    Fig.685....4withbuttweldends

    Figure Nominal pressure Material Nominal diameter / NPSOperating pressure

    PSInlet temperature

    TS45.685 PN40 1.0460 DN15-25/1/2"-1" 32barg 250°C55.685 PN40 1.4541 DN15-25/1/2"-1" 32barg 250°CDIN/EN-ConstructionsrefertodatasheetCONA®-controlANSI

    Types of connection Othertypesofconnectiononrequest.• Flanges....1___________ acc.toDINEN1092-1• Screwedsockets....2 ___Rpthreadacc.toDINEN10226-1orNPTthreadacc.toANSIB1.20.1• Socketweldends....3___ acc.toDINEN12760• Buttweldends....4_____ Weldpreparationacc.toENISO9692identificationNo.1.3and1.5

    (Noterestrictiononoperatingpressure/inlettemperaturedependingtodesign!)Features •Installationdirectlyinfrontofthesteamtrap•Patentapplied,integratedtemperaturesensor•Installationposition:horizontal,capdownwards!•ApplicableforballfloatsteamtrapsCONAS/SC,steamtrapsofothermanufacturersorifasteamtrapwithscreenisnecessary

    Types of connection Flanges Screwed sockets Socket weld ends Butt weld ends

    DN 15 20 25 15 20 25 15 20 25NPS 1/2" 3/4" 1" 1/2" 3/4" 1" 1/2" 3/4" 1"

    Face-to-face acc. to data sheet resp. customer requestL (mm) 150 150 160 95 95 95 250 250 250

    DimensionsH (mm) 73 73 73 73 73 76 73 73 73S (mm) 60 60 60 60 60 60 60 60 60SQR (mm) 54 54 54 54 54 54 54 54 54ØD (mm) 95 105 115 -- -- -- -- -- --ØK (mm) 65 75 85 -- -- -- -- -- --nxØd (nxmm) 4x14 4x14 4x14 -- -- -- -- -- --

    WeightsFig.685 (approx.) (kg) 3,2 3,2 4,2 1,7 1,6 2,1 2,2 2,3 2,4

    PartsPos. Sp.p. Description Fig. 45.685 Fig. 55.6851 Body P250GH,1.0460 X6CrNiTi18-10,1.45411.8 CapSensor X6CrNiTi18-10,1.45412 x Sensor,cpl. X6CrNiMoTi17-12-2,1.4571

    └Spareparts

    Information/restrictionoftechnicalrulesneedtobeobserved!Resistanceandfitnessmustbeverified(contactmanufacturerforinformation,refertoProductoverviewandResistancelist).Operatingandinstallationinstructionscanbedownloadedatwww.ari-armaturen.com

  • 4 Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!

    CONA®-control 685 External test chamber - PN40 - DN40-50

    External test chamber (Forged steel, Stainless steel)

    Fig. 685....1 with flanges

    Fig.685....2withscrewedsockets

    Fig.685....3withsocketweldends

    Fig.685....4withbuttweldends

    Figure Nominal pressure Material Nominal diameter / NPSOperating pressure

    PSInlet temperature

    TS45.685 PN40 1.0460 DN40-50/11/2"-2" 32barg 250°C55.685 PN40 1.4541 DN40-50/11/2"-2" 32barg 250°CDIN/EN-ConstructionsrefertodatasheetCONA®-controlANSI

    Types of connection Othertypesofconnectiononrequest.• Flanges....1___________ acc.toDINEN1092-1• Screwedsockets....2 ___Rpthreadacc.toDINEN10226-1orNPTthreadacc.toANSIB1.20.1• Socketweldends....3___ acc.toDINEN12760• Buttweldends....4_____ Weldpreparationacc.toENISO9692identificationNo.1.3and1.5

    (Noterestrictiononoperatingpressure/inlettemperaturedependingtodesign!)Features •Installationdirectlyinfrontofthesteamtrap•Patentapplied,integratedtemperaturesensor•Installationposition:horizontal,capdownwards!•ApplicableforballfloatsteamtrapsCONAS/SC,steamtrapsofothermanufacturersorifasteamtrapwithscreenisnecessary

    Types of connection Flanges Screwed sockets Socket weld ends Butt weld ends

    DN 40 50 40 50 40 50 NPS 1 1/2" 2" 1 1/2" 2" 1 1/2" 2"

    Face-to-face acc. to data sheet resp. customer requestL (mm) 230 230 onrequest

    DimensionsH (mm) 78,5 78,5

    onrequest

    S (mm) 60 60SQR (mm) 105 105ØD (mm) 150 165ØK (mm) 110 125nxØd (nxmm) 4x18 4x18

    WeightsFig.685 (approx.) (kg) 9,8 11,2 onrequest

    PartsPos. Sp.p. Description Fig. 45.685 Fig. 55.6851 Body P250GH,1.0460 X6CrNiTi18-10,1.45412 x Sensor,cpl. X6CrNiMoTi17-12-2,1.45716 CoverSensor P250GH,1.0460 X6CrNiTi18-10,1.454126 x Sealingring Graphite(CrNilaminatedwithgraphite)27 Cheeseheadscrew 21CrMoV5-7,1.770928 Hexagonalnut 21CrMoV5-7,1.7709

    └SparepartsInformation/restrictionoftechnicalrulesneedtobeobserved!Resistanceandfitnessmustbeverified(contactmanufacturerforinformation,refertoProductoverviewandResistancelist).Operatingandinstallationinstructionscanbedownloadedatwww.ari-armaturen.com

  • 5Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!

    CONA®-control Bolt-on test chamber - PN40 - M20 x 1,5

    Bolt-on test chamber (Forged steel, Stainless steel)

    Options Bolt-on test chamber

    Figure Nominal pressure Material Thread Operating pressure PSInlet temperature

    TSBolt-ontestchamber PN40 1.0460 M20x1,5 32barg 250°CBolt-ontestchamber PN40 1.4541 M20x1,5 32barg 250°CDIN/EN-ConstructionsrefertodatasheetCONA®-controlANSI

    Types of connection • Thread_______________M20x1,5(forCONAsteamtraps)Features •Suitableforhorizontalorverticalinstallationpositionofthesteamtraps;Test chamber diagonally downwards!! •Patentapplied,integratedtemperaturesensor•ApplicableforCONAB(Fig.601)andCONAM(Fig.612)withY-bodyDN15-25(designofthesteamtrapsseecorrespondingdatasheets)

    Typesofconnection Thread

    Size M20 x 1,5

    Dimensions Dimensions and weights of the CONA®-steam traps see corresponding data sheetH1 (mm) 117S1 (mm) 25

    Weights (approx.) (kg) 1,2

    PartsPos. Sp.p. Description Options Bolt-on test chamber1 x Sensor,cpl. X6CrNiMoTi17-12-2,1.45718 CapSensor P250GH,1.0460 X6CrNiTi18-10,1.454110 Socket X6CrNiMoTi17-12-2,1.4571

    └Spareparts

    Information/restrictionoftechnicalrulesneedtobeobserved!Resistanceandfitnessmustbeverified(contactmanufacturerforinformation,refertoProductoverviewandResistancelist).Operatingandinstallationinstructionscanbedownloadedatwww.ari-armaturen.com

  • 6 Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!

    CONA®-control Circuit diagram

    Operation with central status indication

    Single operation without central status indication

    Measuringamplifier Measuringamplifier

    Sensor Sensor

    AS-iPowersupply AS-iMaster Indicationcardmax.30

    StandardProfibus

    Measuringamplifier Measuringamplifier

    Sensor Sensor

    Powersupply

    Centralstatusindication

    Measuringamplifier Measuringamplifier

    Sensor Sensor

    Powersupply

    Single operation without central status indication with relay outputs

    K1=ColdcondensateK2=Steamflow

    max.30

    max.30 max.30

  • 7Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!

    CONA®-control Indications of the system

    Illustration of test chamber and steam trap LED indication at the measuring amplifier - Indication by Bus Operating status

    TrapInspect*

    Blockage

    SteamLeakage

    System/steam trap not in operationSensorincoldair/steamandthetemperatureis

    belowthespecifiedtemperature

    TrapInspect*

    Blockage

    SteamLeakage

    Steam traps works correctSensorinhotcondensate

    TrapInspect*

    Blockage

    SteamLeakage

    Steam leakageSensorinsteamandthetemperatureisabovethe

    specifiedtemperature

    TrapInspect*

    Blockage

    SteamLeakage

    Blocked steam trapSensorincoldcondensate,thecondensateis

    belowthespecifiedtemperature

    *Whenusingthe„Centralstatusindication“theerrorwillbesavedandtheLED„TrapInspect“isblinking.

  • 8 Edition 04/18 - Data subject to alteration - Regularly updated data on www.ari-armaturen.com!8

    Informations about pipe weldingWelding groove acc. to DIN 2559ThematerialusedforARIvalveswithbuttweldendsare: 1.0460 P250GHacc.toDINEN10222-2

    1.4541 X6CrNiTi18-10acc.toDINEN10222-5Note: Noterestrictiononoperatingpressure/inlettemperaturedependingtodesign!Duetoourexperience,werecommendtoapplyanelectricweldingprocess.Becauseofthedifferentmaterialcompositionsandwallthicknessofthesteamtrapsandthepipegasweldingshallnotbeapplied.Quenchingcracksandcoarsegrainstructuremaydevelop.Steamtrapswithsocket-weldendsshallonlybeweldedbyarcwelding(weldingprocess111acc.toDINEN24063).Ifduringthetimeofwarrantyothersthanthemanufacturerorbythemanufacturerauthorizedpersonsareinterferingintheproductand/orthesetting,therightofclaimforwarrantywilllapse!

    CONA®-control Informations about pipe welding

    ARI-ArmaturenAlbertRichterGmbH&Co.KG,D-33750SchloßHolte-Stukenbrock,Tel.+495207/994-0,Telefax+495207/994-158or159Internet:http://www.ari-armaturen.comE-mail:[email protected]

    Technology for the Future. G E R M A N Q U A L I T Y V A L V E S

    I9001ISO

    §19WHG

    Q

    UA

    L IT Y

    M A N AG E ME

    NT

    S Y S T E MS

    AWH ARMATUREN-�WERK HALLE GMBH

    ®

    HALLE

    AmemberoftheARIgroup

    CONA-controlElektronic componentsMeasuring amplifierPower supplyCentral status indicationIndication card

    Test chamberExternalFig. 685 DN15-25 (Forged steel, Stainless steel)Operating limitsTypes of connectionFeaturesDimensionsWeightsParts

    Fig. 685 DN40-50 (Forged steel, Stainless steel)Operating limitsTypes of connectionFeaturesDimensionsWeightsParts

    Bolt-onPN40 - M20 x 1,5 (Forged steel, Stainless steel)Operating limitsTypes of connectionFeaturesDimensionsWeightsParts

    Circuit diagramIndications of the system

    CONA-control ANSI - Monitoring system for steam traps