computational modelling of large aerated lagoon hydraulics
TRANSCRIPT
ARTICLE IN PRESS
Available at www.sciencedirect.com
WAT E R R E S E A R C H 4 1 ( 2 0 0 7 ) 2 1 0 9 – 2 1 1 6
0043-1354/$ - see frodoi:10.1016/j.watres
�Corresponding auE-mail address:
journal homepage: www.elsevier.com/locate/watres
Computational modelling of large aerated lagoonhydraulics
Konstantin Pougatcha, Martha Salcudeana,�, Ian Gartshorea, Philip Pagoriab
aDepartment of Mechanical Engineering, University of British Columbia, 2054-6050 Applied Science Lane, Vancouver, BC, Canada V6T 1Z4bEnvironment, Health and Safety, Weyerhaeuser Company, 32901 Weyerhaeuser Way South, Federal Way, WA 98003, USA
a r t i c l e i n f o
Article history:
Received 29 July 2006
Received in revised form
7 February 2007
Accepted 12 February 2007
Available online 6 April 2007
Keywords:
Aerated lagoons
Surface aerators
Computational fluid dynamics (CFD)
Residence time distribution (RTD)
nt matter & 2007 Elsevie.2007.02.019
thor. Tel.: +1 604 822 2732;[email protected] (M. Sa
a b s t r a c t
A good understanding of the hydraulic performance of aerated lagoons is required for their
design and operation. A comprehensive numerical procedure has been developed for the
three-dimensional computational modelling of the flow in large lagoons including high-
speed floating mechanical surface aerators. This paper describes the procedure that
consists of separate aerator modelling, then applying the obtained results as boundary data
for a full lagoon model. A model application to an industrial aerated lagoon serves as an
example of flow analysis. Post processing of the results by calculating the local average
residence time (age of fluid) provides a powerful and intuitive technique to visualize and
analyse the lagoon performance. The model has been verified by comparing the local
average residence time predictions with measurements from a dye study. It is shown that
the numerical modelling proposed is feasible and constitutes an effective new tool in
improving the performance and design of industrial lagoons.
& 2007 Elsevier Ltd. All rights reserved.
1. Introduction
Very large aerated lagoons are commonly used in the pulp
and paper industry for biological wastewater treatment.
Atmospheric oxygen transferred at the water surface is not
sufficient for the aerobic bacterial process and has to be
supplemented by mechanical aeration. Mixing is necessary to
maintain partial suspension of bacterial solids and ensure
adequate contact with organic pollutants. Floating mechan-
ical surface aerators provide simultaneously both mixing and
oxygenation. Aerators are strategically placed to ensure a
partially mixed flow regime that supports both biological
reactions and staged solids settling. To improve lagoon
performance a greater understanding of flow patterns is
required. There are limited quantitative and qualitative
means to characterize the mixing process in an aerated
lagoon. A common procedure is to inject a tracer into the
lagoon inlet, and by measuring its outlet concentration,
r Ltd. All rights reserved.
fax: +1 604 822 2403.lcudean).
obtain a residence time distribution (RTD) curve. The
procedure is thoroughly described by NCASI (1983). The RTD
curves can be analysed as functions or by central tendencies
parameters, such as the mean, median, and peak residence
time. These central tendencies can be compared with the
theoretical residence time that equals the liquid volume of
the lagoon divided by the flow rate. In addition to measuring
the outlet tracer concentration, the measurements are
sometimes done throughout the lagoon (NCASI, 1983; Schu-
macher and Pagoria, 1997) in order to obtain the distribution
of the tracer in the system, or the age distribution function.
Tracer studies are labour intensive, expensive and do not
permit predictive capabilities for engineering analysis of
alternatives. Modelling could be utilized to understand the
impact of aerator and baffle placement on lagoon perfor-
mance. A complete model has to include computation of the
fluid flow (hydraulic) coupled with biological reaction me-
chanisms. However, based on the premise that biological
ARTICLE IN PRESS
Nomenclature
A age distribution function, s�1
C tracer concentration, kg m�3
Deff effective diffusivity (molecular+turbulent), m2 s�1
~r position vector, m
t time, s
U spray velocity, m s�1
~U water velocity (at the surface), m s�1
~V water velocity, m s�1
Greek symbols
e water volume fraction in a spray
y relative residence time
r density, kg m�3
t local average residence time, s
Subscripts
ex exit of the lagoon
n normal component
r radial component
w water
WAT E R R E S E A R C H 4 1 ( 2 0 0 7 ) 2 1 0 9 – 2 1 1 62110
processes have minimal impact on the fluid flow, these two
aspects of the lagoon operation usually are studied separately.
The initial models that connected lagoon geometry and the
number of aerators with the residence times and/or pollutant
removal were mostly algebraic. Most of them started with a
one-dimensional concentration transport equation (Murphy
and Wilson, 1974; Ferrara and Harleman, 1981). Depending on
the value of the diffusion coefficient, the model becomes a
plug flow model (the coefficient is zero), completely mixed
model (the coefficient is infinity), or an axial dispersion model
(finite non-zero value of the coefficient). Most of the
researchers followed Danckwerts (1953) in describing partial
mixing with a dispersion number, which is the inverse of the
Peclet number. A dispersion model proposed by Polprasert
and Bhattarai (1985) connected the pond’s length, depth,
width, and the flow rate with the dispersion number.
Agunwamba (1992) suggested a slightly different expression
for the dispersion number by using physical modelling and
connecting the model lagoon with the real one through some
dimensionless expressions. Length-to-width ratios were stu-
died by Arceivala (1983) who put forward optimal values by
studying empirical data. Dorego and Leduc (1996) evaluated
Polprasert and Bhattarai (1985) and Arceivala (1983) models by
applying them to the tracer study. A number of researchers
have done comparative studies on various hydraulic models.
Nameche and Vasel (1998) evaluated the models described
above plus a few other models by comparing them with a
number of tracer study results. They found that in most of the
cases the simple approaches produce the same results as
more complicated models.
Computational fluid dynamics (CFD) methods that involve
solving a full set of flow equations have been introduced to
lagoon modelling by Wood et al. (1995). They investigated the
influence of baffle placement in a hypothetical rectangular
pond. Even though they assumed flow uniformity in the
vertical direction (two-dimensionality of the problem) and
modelled an aerator as an arbitrary radial acceleration
around the circle, their work showed benefits that can be
obtained by applying numerical methods into the lagoon
analysis. Ta and Brignal (1998) applied a computational model
to an industrial reservoir. They calculated various inlet, outlet
and baffle arrangements and compared the RTD curves for
each case. It has to be noted that even though the geometry
they studied was three-dimensional, their lagoon configura-
tion did not have aerators. Another application of numerical
modelling to the non-aerated lagoon was presented by Baleo
et al. (2001). They introduced a post processing procedure that
allows determining the local age distribution function.
Peterson et al. (2000) used numerical modelling to assess
sedimentation quality in an aquaculture pond. The pond was
aerated by paddlewheels and propeller aspirators which were
modelled as a body force added to the momentum equation.
In their following work (Peterson et al., 2001) the researchers
applied CFD model to optimize the aerator placement. More
recent study done by Kretser et al. (2002) shows an application
of a CFD modelling approach to the simulation of an aerated
lagoon used to treat wastewater from a pulp and paper mill.
Unfortunately, their paper provides limited information about
the assumptions involved with the aerator modelling.
Despite the limitations of the referenced works it has
become clear that the application of the numerical methods
into lagoon analysis has great potential to improve and
optimize lagoon design by studying the velocity field in detail,
including investigation of possible back flow, short circuiting,
and dead zones.
The objective of this work is to establish a comprehensive
numerical model that accounts for the flow in and around
aerators and their effect on lagoon performance in order to
fully understand the resulting flow patterns. The method
accounts for both mass and momentum transfer resulting
from the action of aerators, because mass transfer plays a
significant role in high-speed floating mechanical surface
aerators and, therefore, cannot be ignored, as done in
previous work. In addition, the computational procedure
has to be feasible for very large-scale industrial lagoons, with
a significant number of aerators. These lagoons have surface
areas an order of magnitude larger than those previously
investigated.
2. Model description
2.1. Modelling approach
A hydraulic model can provide important knowledge for the
design of mechanically aerated lagoons and can also serve as
a base for further studies. Knowing the velocity and turbu-
lence field, residence time information can be obtained and
ARTICLE IN PRESS
WAT E R R E S E A R C H 41 (2007) 2109– 2116 2111
analysed. Moreover, the hydraulic model can be the basis for a
comprehensive lagoon model that includes complex biologi-
cal processes.
First of all, the model has to reflect three-dimensionality of
the velocity field in the lagoon. As aerators are the dominant
factor impacting the flow field, special care has to be taken to
simulate them correctly. The flow through an aerator is fairly
complex and multiphase involving liquid sprayed in the air.
Furthermore, there are typically multiple aerators throughout
a lagoon. To make the solution practical we propose to
decouple the aerator flow from the lagoon flow. This means
that an aerator is modelled separately and the modelling
results applied as boundary conditions in the lagoon model.
Also, it is reasonable to assume that each aerator of the same
type and size can be represented with similar boundary
conditions. As the difference in the water level at the
entrance and at the exit is relatively small, the model does
not include hydrostatic forces: the flow is driven by the
pressure gradients developing from the assigned inlet mass
flow rate. Finally, in order to avoid a computationally
expensive free surface modelling, a smooth frictionless
surface at the top of the lagoon is assumed (rigid lid
assumption).
2.2. Aerator model
A surface aerator is schematically shown in Fig. 1. The
impeller pushes the liquid upwards through the intake cone
and draft tube. After hitting a deflector plate, the liquid
atomizes and acquires a radial momentum. The water
Impeller
Flotationring
plate
Intakecone
Motor shaft
Drafttube
Water spray
Fig. 1 – Aerator schematic.
Fig. 2 – Water volume fraction
droplets then fly outwards before landing on the water
surface. The whole assembly is kept afloat by a flotation ring.
The approach to the aerator simulation is dictated by the
requirements of its implementation in the lagoon model. It is
necessary to obtain a correct mass and momentum transfer
from the aerator to the lagoon. The droplet size distribution,
interactions between sprays and the water surface, and other
small-scale details are of a lesser importance for a large-scale
flow in the lagoon. With these reasons in mind, the Eulerian
multiphase method was chosen to model the aerator flow. It
assumes that the two phases (air and water) are interpene-
trating and the separate mass and momentum conservation
equations are solved for each phase. The turbulence is limited
to the air phase with no influence from the droplets. Water
droplets are assumed to be spheres with a constant diameter
of 1 mm. To assess the solution dependency on the droplet
diameter, additional cases with a range of diameters from 0.5
to 5 mm were calculated and the results proved to be similar.
It is necessary to note that the atomization is a very complex
process and cannot be modelled accurately with this
approach; however, the method truthfully represents the
resulting momentum transfer to the lagoon.
A computer code solving the Eulerian set of equations in
curvilinear coordinates was developed at UBC (Pougatch et al.,
2005) based on Spalding (1980) IPSA procedure. Aqua-Aero-
bics’ 75 hp (55.9 kW) ‘‘Aqua-Jet’’ floating high-speed mechan-
ical surface aerators were chosen for modelling, as this is the
aerator used in the example industrial application. As the
aerator flow is axisymmetric, the model can be reduced to
two-dimensions. At the bottom of the draft tube, a known
water mass flow rate of 1.26 kg s�1 was imposed; the
secondary phase (air), which appears after the impeller due
to cavitation and the air entrainment, is assumed to have the
same velocity as the primary phase (water). The secondary
phase volume fraction is assumed to be 10% (it has been
observed that the influence of this parameter on the
momentum transfer to the lagoon is minimal).
The contours of the liquid volume fraction presented in Fig.
2 show the water flowing vertically in the draft tube, then
hitting the deflector plate, and being sprayed in a radial
pattern. The graph of the water volume fraction (Fig. 3) at the
surface illustrates the splashing pattern. The maximum
contours (dimensionless).
ARTICLE IN PRESS
WAT E R R E S E A R C H 4 1 ( 2 0 0 7 ) 2 1 0 9 – 2 1 1 62112
diameter of the simulated spray pattern (6.4 m) is lower than
the one provided by the manufacturer (9.1 m). This difference
is to be expected as the simulation does not account for the
droplet break-up and formation of secondary droplets.
2.3. Application of an aerator model to a small pond
In order to investigate the aerator sub-model application to
aerated lagoon modelling, a simple case of a round pond, 50 m
in diameter and 4 m in depth with a single aerator placed in
the centre was considered for modelling (Fig. 4). Reynolds
averaged Navier–Stokes equations are solved in a computa-
Fig. 3 – Water volume fraction along the surface.
R = 25m
H = 4m
Intake cone
Draft tube
Flotation ringWater
Water surface
Fig. 4 – Test pond schematic diagram.
Fig. 5 – Velocity vectors in a test pond. Shade indicates the ar
(mixing area).
tional domain together with the k-epsilon turbulence model.
The computer code used for these computations has also
been developed at UBC (Nowak and Salcudean, 1996). The
boundary conditions for this model take into account the
results of the aerator simulations. The only aerator compo-
nents that are explicitly included are the intake cone and the
draft tube, which are needed to provide a realistic outflow
condition from the pond into an aerator. The surface area
where the aerator spray lands corresponds to the inlet
condition or the splash zone for the pond model. It is a
ring-shaped surface extending from the outside edge of the
flotation ring to the farthermost point reached by the spray.
The normal velocity at the splashing zone can be easily
defined from mass conservation:
�wrw~Un ¼ rw
~~Un. (1)
The radial velocity can be determined from conservation of
the total momentum assuming that the entire momentum of
the droplets is transferred to the water.
�wrw~Un
~Un þ ~Ur
� �¼ rw
~~Un~~Un þ
~~Ur
� �. (2)
Such definitions ensure full conservation of mass and
momentum along the splash zone aerator boundary. Even
though the droplets have some tangential velocity due to a
rotational action of the impeller, this velocity is small
compared with the radial and the normal components and
it is neglected in the current model application. The point
values are calculated from the profiles of velocities and
volume fractions obtained from the aerator model. The
remaining portion of the top boundary representing the free
surface has a free slip condition. In order to analyse the
modelling results velocity vectors in the pond are plotted (Fig.
5). A strong recirculation area is formed around the aerator.
The diameter of the recirculation zone, defined as the area
where the average velocity value is higher than 0.01 m s�1,
equals 36 m and is in good agreement with the mixing zone
diameter �39.6 m—provided by the aerator manufacturer. In
addition to the case where the splash zone boundary is
defined with the use of the velocity profiles, another calcula-
tion was made that uses the average values of velocities
applied to a ring with the outer radius equalling 3 m in a way
that ensures the same total mass and momentum flow rates.
ea where the velocity magnitude is greater than 0.01 m s�1
ARTICLE IN PRESS
Fig. 6 – Radial velocity at the top of the pond for profile and
averaged spray boundary.
W = 315 m
L = 315.6 m
Fig. 7 – Lagoon schematic with aerator locations. An arrow
shows a called North location.
WAT E R R E S E A R C H 41 (2007) 2109– 2116 2113
The difference between the results for the two cases is limited
to a small area near the aerator centre; at the distances
greater than 4 m from the axis, the two solutions are
practically indistinguishable (Fig. 6). The recirculation zone
diameter for this case remains the same as for the previous
one. It is interesting to note that for other cases with averaged
boundary conditions calculated with different values of the
splash radius (R ¼ 2 and 5 m), the recirculation area diameter
still does not change much, whilst there are noticeable
variations in the velocity distribution near the boundary. In
further modelling a uniform boundary with a 3 m splashing
radius is used, assuming that the flow near the aerator axis
has little effect on the general flow pattern in the lagoon.
3. Analysis of the lagoon flow
3.1. Lagoon description and computational procedure
The described approach has been applied to a first cell of a 2-
cell aerated lagoon located at the Weyerhaeuser pulp mill in
Grande Prairie, Alberta. The first cell geometry together with
the aerator placement is schematically shown in Fig. 7. The
cell is almost square in shape with sides of 315.6 and 315.0 m,
respectively. The wastewater inlet is located near the upper
left corner and the effluent exit is at the right through the
midpoint channel. The cell has slanted walls all around and
its depth is 2.85 m, taking into account that 40% of the design
volume is lost to uniform sludge deposition. The cell contains
nineteen aerators, 55.9 kW each. The average influent waste-
water flow rate is 58,059 m3 day�1 that provides a theoretical
residence time for this cell of 4.88 days. A three-dimensional
structured curvilinear grid that contains about 1.6 million
computational cells arranged in 54 segments has been
developed to represent the lagoon geometry. It is highly
non-uniform: the grid is refined near the aerators to
accurately resolve the flow where the velocity gradients are
high and relatively coarse, far enough from the aerators to
keep the computational cost within practical limits. As a
result, the volume of the computational cell varies from
3�10�3 to 1.7 m3. The aerator boundary conditions are the
same as described for the small pond case. As all of the
aerators are the same, the aerator boundaries are also the
same throughout the lagoon. At the lagoon inlet the known
wastewater mass flow rate is imposed. After some prelimin-
ary studies that found the buoyancy is much less than the
forced convection due to a negligible surface to bottom
temperature gradient, the buoyancy force is ignored in the
computations. The presence of large differences of scales in
the velocity field (the velocity magnitude near the aerator is
about 1 m s�1 and far from it is about 1 mm s�1) makes the
convergence very slow and, therefore, needs extensive under-
relaxation of flow parameters. It takes about 10 days of
computational time on a PC with PIII at 1.2 GHz to obtain a
converged solution.
3.2. Lagoon characterization
The numerical solution provides us with the knowledge of the
pressure and the velocity field, as well as the turbulence
parameters in the entire lagoon. However, for better under-
standing and characterisation of the lagoon performance
some post processing is required. It has been customary in
industry to characterise the lagoon with an exit RTD curve.
However, such an approach treats the lagoon essentially as a
black box, because the RTD curve does not provide informa-
tion about the local features of the flow necessary for
improvements and optimizations. We believe that the best
lagoon characterization can be achieved with the description
of the local residence times. In addition, such a description is
also more suitable for the numerical modelling.
3.3. Mean average residence time calculation and modelvalidation
It was chosen to solve an additional differential equation for
the mean average residence time that was obtained by
Sandberg (1981) and used by Baleo and Le Cloirec (2000) for
a non-aerated lagoon. This technique has its roots from the
ARTICLE IN PRESS
WAT E R R E S E A R C H 4 1 ( 2 0 0 7 ) 2 1 0 9 – 2 1 1 62114
tracer experiments when a pulse of dye is injected at the inlet.
The age distribution function is defined as
Að~r; tÞ ¼Cð~r; tÞR1
0 Cð~r; tÞdt. (3)
It shows the normalized tracer concentration at any point
and at any time. The local average residence time can be
obtained by multiplication by time and integration of the age
distribution function:
t ¼Z 1
0Að~r; tÞt dt ¼
R10 Cð~r; tÞt dtR10 Cð~r; tÞdt
. (4)
The propagation of tracer in the lagoon is governed by a
concentration transport equation:
qCqtþr ~VC
� �¼ rðDeffrCÞ. (5)
It can be multiplied by time (t) and integrated from zero to
infinity. After a few transformations one can obtain the
equation for the local residence time:
r ~Vt� �
¼ rðDeffrtÞ þ 1. (6)
Boundary conditions for this equation can be obtained from
boundary conditions of a concentration transport equation by
a similar multiplication-integration operation. Zero value of
the residence time at the inlet, zero flux through the walls
and free surface, and zero gradient at the exit complete the
problem description. Flow parameters, such as pressure,
velocity and turbulence are obtained from the flow solution
and assumed constant during the solution of the local
residence time equation. It is also assumed that the flow
inside an aerator is well mixed as it goes up through the
impeller, resulting in the uniform distribution of concentra-
tion throughout the top aerator boundary.
The first test to confirm the validity of the model is to
ensure the computational results are consistent with the
established analytical relationships. The mean average resi-
dence time at the exit, obtained by averaging across the cross-
section, should equal the theoretical residence time for
steady incompressible flows (Spalding, 1958). Our modelling
results show the exit value of 5.08 days, this is within 4% error
margin of the theoretical value of 4.88 days. In order to further
verify the model performance, we compare the predicted
values of the local average residence time at the corners of
the lagoon (except one corner near the inlet, where the value
Table 1 – Comparison of measured and predicted valuesof local average residence time at three corner points
Measuredtime, days
Calculatedtime, days
Difference,%
SW
corner
4.72 4.93 +4.4
NE
corner
5.54 5.28 �4.7
SE
corner
5.25 5.13 �2.3
Directions are as noted in Fig. 7.
is almost zero) and the measured ones obtained by Schuma-
cher and Pagoria (1997). The comparison presented in Table 1
confirms the model capability to represent the actual lagoon
conditions; the simulation results are within 5% of the
experimentally measured values. Considering the complexity
of the problem, the experimental uncertainties, and a number
of simplifications, such as an assumption of the flat sludge
bottom profile and an isolation of the first cell of the lagoon,
the agreement is remarkably good and indicates the robust-
ness of the model.
3.4. Flow analysis and discussion
For further analysis we plot the contours of the relative local
residence time, which is defined as the local residence time
divided by its value at the exit of the lagoon (Fig. 8).
y ¼ttex
. (7)
If the lagoon was operated as an ideal mix reactor, the value
of the relative local average residence time (age of fluid)
would be unity throughout the domain. However, we can see
an area at the left and the lower side of the plot where the
liquid spends less time than average. This area can be
interpreted as the counter-clockwise bypass flow from the
entrance to the exit. In order to improve mixing there the
addition of some aerators would be beneficial. On the other
hand, the relative residence time is more than unity in an
area in the upper right part of the cell. It is likely that there is
more internal recirculation and less interchange with the
surrounding areas. Some changes in the aerator positioning
may be beneficial to promote flow in this area. Another
means to quantify lagoon mixing performance, is to plot the
graph showing the distribution of the lagoon volume (normal-
ized) that falls within certain intervals of the local average
residence times (Fig. 9). The dispersion value of this distribu-
tion characterizes the deviation of the lagoon from the ideally
mixed reactor, for which the dispersion equals zero.
It is evident that the flow information provided by the
numerical model not only helps uncover the undesirable flow
patterns in the lagoon, it is also points to potential reasons
why they appear, thus paving the way for improvements. The
numerical model can be used during the lagoon design stage
as well as during its operation to optimize aerator placement.
The computational modelling opens a black box, the aerated
lagoons or other complex engineering systems used to be, by
allowing the analyst to look inside it. The discovered flow
patterns are often not obvious, because they depend on an
interaction of a variety of factors, such as lagoon geometry,
aerator placements, and inlet and outlet locations. Even
though there are analytical and one-dimensional models that
can predict exit RTD, the engineers still have to rely on their
intuition to guess what causes the undesirable lagoon
behaviour. The industry standard dye propagation experi-
ments also have only an exit RTD curve as a result most of the
time. Measuring the dye concentration throughout the lagoon
during a long time interval, necessary to obtain the local age
of fluid, is very costly and rarely done. When it is done the
number of measurement points is limited and some flow
features may be lost. This is not to say that the dye
ARTICLE IN PRESS
Fig. 8 – Relative local average residence time contours (dimensionless). Aerator locations are shown with dots in the plot.
Fig. 9 – Distribution of relative local average residence time
throughout the lagoon.
WAT E R R E S E A R C H 41 (2007) 2109– 2116 2115
experiments or the analytical models become obsolete. On
the contrary, they all may grow to be the parts of an integral
method of the lagoon design and optimization. Dye tracer
studies can provide the CFD model with data for its
verification or tuning, which might be necessary. The
analytical model can use the computational results to make
the understanding of the flow easier and provide quick
evaluations of some proposed modifications.
Further, numerical model simplifications involving the
neglect of the recirculatory flow around an aerator is not a
viable option. Suffice it to say that the lagoon inlet flow rate is
about one half of a single aerator flow. Moreover, what is more
important is that the amount of wastewater that recirculates
in the mixing zone surrounding an aerator is about ten times
more than the flow going through the aerator itself. Clearly,
the lagoon flow would be very different without the aerators
and there is no practical value in trying to resolve it.
Application of the current model to other industrial aerated
lagoons with high-speed mechanical surface aeration re-
quires only an accurate description of lagoon geometry and
aerator placement.
4. Conclusions
The velocity field in an aerated lagoon is determined by
geometry of the liquid volume, inlet and exit locations, and
most of all, by aerators. The proposed modelling method
allows for the determination of velocity field and local
average residence times by applying a three-step method. In
the first step the aerator is simulated in a stand-alone model,
in the second step the resulting boundary conditions are
applied to simulate the flow in the lagoon, and in the third
step the local average time distribution is obtained by solving
the corresponding equation.
The most important condition to obtain a correct repre-
sentation of the aerator is to ensure the mass and momentum
conservation from the aerator to the lagoon. The numerical
model accurately represents an aerator mixing diameter that
remains practically unchanged for various boundary condi-
tions implementations as long as the mass and momentum
flow rates are kept constant.
ARTICLE IN PRESS
WAT E R R E S E A R C H 4 1 ( 2 0 0 7 ) 2 1 0 9 – 2 1 1 62116
Application of the model to an industrial lagoon predicts
the flow behaviour and provides an engineering tool for
analysing impacts of aerator placement and lagoon design. A
post processing done by solving an extra differential equation
provides visual and quantitative information to describe
internal lagoon mixing characteristics. The aerated lagoon
numerical model has been verified by comparing its predic-
tions with experimental data. Knowing the flow patterns and
average local residence time distribution helps to modify or
optimize lagoon hydraulics to better achieve desired perfor-
mance. To the best of our knowledge this is the first
time a CFD model that includes the mass transfer due to
the action of aerators has been applied to a large industrial
wastewater treatment lagoon with high-speed floating
mechanical aerators.
Acknowledgement
The financial contribution from Natural Sciences and En-
gineering Research Council of Canada (NSERC) and Weyer-
haeuser is greatly acknowledged. The cooperation and
support led by Dave Lincoln of the Weyerhaeuser Grande
Prairie operations is also gratefully acknowledged. Curtis
Bryant and William Barkley of Weyerhaeuser Environment,
Health and Safety contributed technical review and insights
in aerated lagoon design and operation. In addition, the
authors appreciate the encouragement provided by Dr Eric
Hall from UBC.
R E F E R E N C E S
Agunwamba, J.C., 1992. Field pond performance and designevaluation using physical models. Water Res. 26 (10),1403–1407.
Arceivala, S.J., 1983. Hydraulic modeling for waste stabilizationponds. J. Environ. Eng. Div. 109 (1), 265–268.
Baleo, J.-N., Le Cloirec, P., 2000. Validating a prediction method ofmean residence time spatial distributions. AIChE J. 46 (4),675–683.
Baleo, J.-N., Humeau, P., Le Cloirec, P., 2001. Numerical andexperimental hydrodynamic studies of a lagoon pilot. WaterRes. 35 (9), 2268–2276.
Danckwerts, P.V., 1953. Continuous flow systems. Chem. Eng. Sci.2 (1), 1–13.
Dorego, N.C., Leduc, R., 1996. Characterization of hydraulic flowpatterns in facultative aerated lagoons. Water Sci. Technol. 34(11), 99–106.
Ferrara, R.A., Harleman, D.R.F., 1981. Hydraulic modeling forwaste stabilization ponds. J. Environ. Eng. Div. 107 (4),817–830.
Kretser, D., Matthews, B., Williams, M., 2002. Maryvale mill usescomputational fluid dynamics to investigate natural andmechanically induced flows in an aerated lagoon. PaperTechnol. 43 (9), 35–38.
Murphy, K.L., Wilson, A.W., 1974. Characterization of mixing inaerated lagoons. J. Environ. Eng. Div. 100 (5), 1105–1117.
Nameche, Th., Vasel, J.L., 1998. Hydrodynamic studies andmodelization for aerated lagoons and waste stabilizationponds. Water Res. 32 (10), 3039–3045.
NCASI Technical bulletin No. 408. A review of procedures forconducting conservative tracer studies in the hydrauliccharacterization of effluent treatment basins. September1983.
Nowak, Z.P., Salcudean, M., 1996. Turbulent flow calculations bythe nonlinear multi-grid method. Zeitschrift fuer AngewandteMathematik und Mechanik, ZAMM. Appl. Math. Mech. 76 (8),463–469.
Peterson, E.L., Harris, J.A., Wadhwa, L.C., 2000. CFD modellingpond dynamic process. Aquac. Eng. 23, 61–93.
Peterson, E.L., Wadhwa, L.C., Harris, J.A., 2001. Arrangement ofaerators in an intensive shrimp grow out pond having arectangular shape. Aquac. Eng. 25, 51–65.
Pougatch, K., Salcudean, M., Gartshore, I., 2005. Modelling ofmultiphase and multicomponent flows. Internal report. Uni-versity of British Columbia, Vancouver, Canada.
Polprasert, C., Bhattarai, K.K., 1985. Dispersion model for wastestabilization ponds. J. Environ. Eng. Div. 111 (1), 45–59.
Sandberg, M., 1981. What is ventilation efficiency? Build. Environ.16 (2), 123–135.
Schumacher, K., Pagoria, P., 1997. Grande Prairie aerated lagoonRTD analysis, Weyerhaeuser Technical Report, WeyerhaeuserEHS Technical Networks
Spalding, D.B., 1980. Numerical computation of multiphase flowand heat transfer. In: Taylor, C., Morgan, K. (Eds.), RecentAdvances in Numerical Methods in Fluids, vol. 1. PineridgePress, Swansea, pp. 139–168.
Spalding, D.B., 1958. A note on mean residence-times insteady flows of arbitrary complexity. Chem. Eng. Sci. 9 (1),74–77.
Ta, C.T., Brignal, W.J., 1998. Application of computational fluiddynamics technique to storage reservoir studies. Water Sci.Technol. 37 (2), 219–226.
Wood, M.G., Greenfield, P.F., Howes, M.R., Johns, M.R., Keller, J.,1995. Computational fluid dynamics modelling of wastewaterponds to improve design. Water Sci. Technol. 31 (12), 111–118.