To: Dave Bryant Composite Technology Corporation 2026 McGaw Avenue Irvine, CA 92614 USA SELF DAMPING TEST ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION Kinectrics North America Inc. Report No.: K-422024-RC-0008-R00 October 15, 2004 Michael Kastelein Transmission and Distribution Technologies Department 1.0 INTRODUCTION A Self-Damping Test was performed on an Aluminum Conductor, Composite Core – Trapezoidal Wires (ACCC/TW) conductor for Composite Technology Corporation (CTC). The conductor is 1020 kcmil with an outside diameter of 28.1 mm (1.108 inch). There are 24 aluminum trapezoidal wires stranded in 2 layers over a single composite fiberglass/carbon fiber core. The specification for the conductor is contained in Appendix A. A 795 kcmil, 28.1 mm (1.108 inch), “Drake” ACSR conductor with round wires was also tested. The testing was conducted April 20-23, 2004 by Kinectrics North America Inc. personnel at 800 Kipling Avenue, Toronto, Ontario, M8Z 6C4, Canada. Important Note: This report documents the results of Self Damping Tests performed on 1020 kcmil ACCC/TW conductor and 795 kcmil ACSR conductor. The reader should be aware that the aluminum wires are fully annealed, trapezoidally- shaped for the ACCC conductor and are hard drawn, round-shaped for the ACSR conductor. This difference has significant influence on the self-damping characteristics of the conductors. The differences are mostly a function of the shape of the aluminum wires. The core material has less influence on self-damping the conductor than the aluminum wires. The reader is cautioned that, although the results are presented together, direct comparisons should not be made and that interpretations of the self damping characteristics of each conductor should be made in the proper context. PRIVATE INFORMATION Contents of this report shall not be disclosed without authority of the client. Kinectrics North America Inc., 800 Kipling Avenue, Toronto, Ontario M8Z 6C4.

Upload: dangkien

Post on 25-Mar-2018

223 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

To: Dave Bryant

Composite Technology Corporation 2026 McGaw Avenue Irvine, CA 92614 USA

SELF DAMPING TEST

ON 1020 KCMIL ACCC/TW CONDUCTOR FOR COMPOSITE TECHNOLOGY CORPORATION

Kinectrics North America Inc. Report No.: K-422024-RC-0008-R00

October 15, 2004

Michael Kastelein Transmission and Distribution Technologies Department

1.0 INTRODUCTION A Self-Damping Test was performed on an Aluminum Conductor, Composite Core – Trapezoidal Wires (ACCC/TW) conductor for Composite Technology Corporation (CTC). The conductor is 1020 kcmil with an outside diameter of 28.1 mm (1.108 inch). There are 24 aluminum trapezoidal wires stranded in 2 layers over a single composite fiberglass/carbon fiber core. The specification for the conductor is contained in Appendix A. A 795 kcmil, 28.1 mm (1.108 inch), “Drake” ACSR conductor with round wires was also tested. The testing was conducted April 20-23, 2004 by Kinectrics North America Inc. personnel at 800 Kipling Avenue, Toronto, Ontario, M8Z 6C4, Canada. Important Note: This report documents the results of Self Damping Tests performed on 1020 kcmil ACCC/TW conductor and 795 kcmil ACSR conductor. The reader should be aware that the aluminum wires are fully annealed, trapezoidally-shaped for the ACCC conductor and are hard drawn, round-shaped for the ACSR conductor. This difference has significant influence on the self-damping characteristics of the conductors. The differences are mostly a function of the shape of the aluminum wires. The core material has less influence on self-damping the conductor than the aluminum wires. The reader is cautioned that, although the results are presented together, direct comparisons should not be made and that interpretations of the self damping characteristics of each conductor should be made in the proper context.

PRIVATE INFORMATION

Contents of this report shall not be disclosed without authority of the client. Kinectrics North America Inc., 800 Kipling Avenue, Toronto, Ontario M8Z 6C4.

Page 2: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 2

2.0 PURPOSE OF TEST The purpose of the Self Damping Test is to measure the power dissipation characteristics of overhead conductors. The data are used to assist in the selection of aeolian vibration dampers for the cable. 3.0 TEST SET-UP The logarithmic decay method was used to perform these tests. The method is described in IEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI 1979. The general arrangement used for the self damping test is shown in Figure 1. The test was carried out in a temperature-controlled laboratory at 22ºC ± 2ºC. The conductor was tensioned using a cantilever weight arm at one end and a hydraulic cylinder at the other end. A load-cell was placed between the hydraulic cylinder and the deadend to measure the tension in the conductor. The hydraulic cylinder was used to set the initial tension and the weight arm maintained the tension throughout the test. The conductor length between deadend clamps was approximately 32 m (105 ft). The conductor was rigidly clamped to intermediate abutments using square-faced clamps approximately the same diameter as the conductor. The clamping arrangement minimized the loss of vibration energy from of the span. An electromagnetic shaker was positioned near one end on the test span. A function generator providing a sinusoidal output controlled the electromagnetic shaker. An accelerometer measured the free-loop vibration amplitude of the conductor at mid-span. A quick release mechanism was used to detach the conductor from the shaker with minimal disturbances. A digital acquisition system recorded the output from the accelerometer. The calibratable instruments used in the test are listed in Appendix B. 4.0 TEST PROCEDURE Data Collection The conductors were tested at 5 tensions: 15, 20, 25, 30, and 40 percent of the conductor’s rated breaking strength (RTS). The conductor was tested several different frequencies. The frequencies tested were the closest test span resonance to the frequencies that are generated in the wind velocity range from 10-30 km/hr (6.2-18.6 mph). The relationship between frequency, wind velocity and conductor diameter is: f(Hz) = 50 X wind velocity (km/hr) / conductor diameter (mm) The phase angle between the force signal and the accelerometer’s signal was used to indicate when the conductor was at a resonant frequency. After the conductor had stabilized at the resonance for a few minutes the shaker was disconnected. The signal from the accelerometer was integrated in its amplifier so that the output of the amplifier is proportional to velocity. The velocity signal was recorded by a digital data acquisition system while the vibration of the conductor decayed.

Page 3: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 3

Data Reduction The decay of the free loop velocity (Figure 2) from the test condition at the 25% RTS and 14.887 Hz is shown in Figure 2. This trace is used to illustrate the response of the conductor after being released from the shaker. The trace shows the envelope of the natural decay of the sinusoidal vibrations. Other test conditions decay at longer or shorter rates. A curve is fitted through the peak values of each cycle in the decay and is used to filter out small disturbances. The resulting fitted curve for the test condition in Figure 2 is shown in Figure 3. The peak-to-peak amplitude, Y, of the conductor was calculated from the peak velocity, V. Y = 1000*V / (π f) where Y = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) f = frequency (Hz) The decay of the conductor was calculated from the equation of the fitted curve and is expressed in terms of logarithmic decrement. δ = 1/n ln(Yo/Yn) where:

δ = log decrement n = number of cycles Yo = peak-to-peak amplitude (mm) Yn = peak-to-peak amplitude at “n” cycles after Yo (mm) The power dissipated by the conductor’s self-damping is calculated by: P = ½ f m Vo

2 δ where:

P = power dissipated (watts per metre) f = frequency (Hz)

m = mass per unit length of the conductor (kg/m) Vo = peak loop velocity at amplitude Yo (m/sec)

δ = log decrement The power dissipation is plotted as Power versus Normalized Amplitude where: Normalized Amplitude = Y/D where Y = average peak-to-peak amplitude between Yo and Yn

= (Yo + Yn)/2 D = conductor diameter (mm)

Page 4: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 4

5.0 TEST RESULTS Tables 1 to 5 show the data collected for the tests at 15, 20, 25, 30, and 40 percent RTS, respectively. Not all data are reported in the tables in order to make them a manageable size. Figures 4 to 8 show the graphs of the conductor’s power dissipation characteristics at 15, 20, 25, 30, and 40 percent RTS, respectively. The self damping of this conductor at 15% and 20% was too high to tune the vibration to a natural frequency for frequencies above 20 Hz and 25Hz, respectively. Only natural frequencies that could “locked-in” are analyzed. The self damping data for the 795 kcmil, “Drake” ACSR round wire conductor are plotted in red on Figures 1,3 and 5 for 15%, 25% and 40% RTS. The ACSR round wire conductor has a lower self-damping than the ACCC/TW. Higher self-damping is a benefit of all trapezoidal-shaped wire conductors compared to round wire conductors. This is true irrespective of the construction of the core of the conductor. Prepared by:

Michael Kastelein Technical Specialist Transmission and Distribution Technologies Department

Reviewed by:

C.J. Pon Principal Engineer Transmission and Distribution Technologies Department

Approved by:

Dr. J. Kuffel General Manager

Transmission and Distribution Technologies Department MK:JC

DISCLAIMER Kinectrics North America Inc., has prepared this report in accordance with, and subject to, the terms and conditions of the contract between Kinectrics North America Inc. and Composite Technology Corporation. Kinectrics North America Inc., 2004.

Page 5: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 5

Table 1 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 15% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test Span: 32 m (105 ft) Mass/Length: 1.424 kgf/m (0.957 lbf/ft) Test Tension: 3048 kgf (6720 lbf) Condition: New 15% RTS

Frequency Loop Length Yo V Yn n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mW/m)

10.85 0.396 4.75 10 106.67 0.277 2.74 0.100 1.96 10 2.74 0.084

11.60 1.99 1.58 0.058 1.33 10 0.47 0.052 1.14 0.042 0.98 10 0.21 0.038 0.85 0.031 0.73 10 0.12 0.028 0.62 0.023 0.53 10 0.07 0.021 4.95 0.231 2.74 5 67.17 0.137 1.73 0.081 1.25 5 4.53 0.053

14.88 1.55 0.99 0.046 0.84 5 0.75 0.033 0.74 0.035 0.66 5 0.29 0.025 0.60 0.028 0.54 5 0.17 0.020 0.49 0.023 0.44 5 0.11 0.016 1.60 0.091 1.15 5 7.16 0.049 0.84 0.048 0.63 5 1.70 0.026

18.20 1.27 0.49 0.028 0.39 5 0.46 0.016 0.32 0.018 0.27 5 0.14 0.011 0.24 0.014 0.21 5 0.06 0.008 0.19 0.011 0.18 5 0.03 0.007

Notes: Yo = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Yn = peak-to-peak amplitude at “n” cycles after Yo (mm) P = power dissipated (mW/m) Y/D = normalized amplitude = (Yo + Yn)/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 15% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 4.

Page 6: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 6

Table 2 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 20% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test span: 32 m (105 ft) Mass/Length: 1.424 kgf/m (0.957 lbf/ft) Test Tension: 4064 kgf (8959 lbf) Condition: New 20% RTS

Frequency Loop Length Yo V Yn n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mW/m)

12.94 0.541 8.68 7 157.91 0.384 5.99 0.251 4.28 7 28.55 0.183

13.31 2.01 3.19 0.133 2.48 7 6.08 0.101 2.00 0.084 1.68 7 1.65 0.066 1.46 0.061 1.29 7 0.61 0.049 1.16 0.049 1.06 7 0.30 0.039 6.99 0.375 3.75 7 151.82 0.191 2.24 0.120 1.51 7 9.89 0.067 1.13 0.061 0.92 7 1.33 0.036

17.07 1.57 0.78 0.042 0.68 7 0.42 0.026 0.60 0.032 0.53 7 0.22 0.020 0.47 0.025 0.41 7 0.15 0.016 3.34 0.219 1.65 7 71.31 0.089 0.94 0.061 0.62 7 3.35 0.028

20.86 1.28 0.46 0.030 0.37 7 0.40 0.015 0.32 0.021 0.28 7 0.12 0.011 0.25 0.016 0.22 7 0.06 0.008 0.20 0.013 0.18 7 0.04 0.007 1.27 0.098 0.69 7 14.58 0.035 0.41 0.032 0.27 7 1.07 0.012

24.66 1.08 0.20 0.016 0.16 7 0.14 0.006 0.13 0.010 0.11 7 0.04 0.004 0.10 0.008 0.09 7 0.02 0.003 0.08 0.006 0.07 7 0.01 0.003

Notes: Yo = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Yn = peak-to-peak amplitude at “n” cycles after Yo (mm) P = power dissipated (mW/m) Y/D = normalized amplitude = (Yo + Yn)/2 The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 20% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 5.

Page 7: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 7

Table 3 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 25% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test span: 32 m (105 ft) Mass/Length: 1.424 kgf/m (0.957 lbf/ft) Test Tension: 5080 kgf (11199 lbf) Condition: New 25%RTS

Frequency Loop Length Yo V Yn n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mW/m)

16.81 0.561 13.80 30 15.67 0.544 11.32 0.378 9.29 30 7.15 0.366

10.63 2.81 7.61 0.254 6.24 30 3.25 0.246 5.10 0.170 4.17 30 1.48 0.165 3.40 0.114 2.77 30 0.67 0.110 2.26 0.075 1.83 30 0.30 0.073 10.69 0.500 8.55 25 23.72 0.342 6.85 0.320 5.51 25 9.51 0.220

14.89 2.01 4.44 0.208 3.60 25 3.85 0.143 2.93 0.137 2.40 25 1.58 0.095 1.98 0.093 1.65 25 0.67 0.065 1.39 0.065 1.18 25 0.29 0.046 8.47 0.510 6.60 20 44.30 0.268 5.16 0.310 4.05 20 15.85 0.164

19.14 1.56 3.20 0.192 2.54 20 5.76 0.102 2.04 0.123 1.65 20 2.15 0.066 1.36 0.082 1.13 20 0.83 0.044 0.96 0.057 0.82 20 0.34 0.032 6.04 0.444 4.03 20 66.45 0.179 2.74 0.202 1.91 20 12.26 0.083

23.42 1.28 1.37 0.101 1.02 20 2.54 0.043 0.78 0.058 0.62 20 0.63 0.025 0.51 0.038 0.43 20 0.20 0.017 0.37 0.027 0.32 20 0.09 0.012 5.55 0.481 4.27 10 118.65 0.174 3.30 0.286 2.56 10 40.97 0.104

27.59 1.08 1.99 0.172 1.56 10 14.32 0.063 1.23 0.106 0.97 10 5.10 0.039 0.78 0.068 0.63 10 1.88 0.025 0.52 0.045 0.44 10 0.72 0.017

Notes: Yo = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Yn = peak-to-peak amplitude at “n” cycles after Yo (mm) P = power dissipated (mW/m) Y/D = normalized amplitude = (Yo + Yn)/2

The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 25% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 6.

Page 8: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 8

Table 4 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 30% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test Span: 32 m (105 ft) Mass/Length: 1.424 kgf/m (0.957 lbf/ft) Test Tension: 6096 kgf (13439 lbf) Condition: New 30% RTS

Frequency Loop Length Yo V Yn n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mW/m)

26.52 0.975 19.92 40 56.76 0.825 15.07 0.554 11.52 40 17.21 0.472

11.70 2.80 8.91 0.327 6.98 40 5.44 0.282 5.56 0.204 4.51 40 1.83 0.179 3.72 0.137 3.13 40 0.67 0.122 2.69 0.099 2.35 40 0.27 0.090 10.28 0.529 8.08 30 26.32 0.326 6.44 0.332 5.22 30 8.99 0.207

16.39 2.00 4.30 0.222 3.61 30 3.34 0.141 3.09 0.159 2.69 30 1.38 0.103 2.37 0.122 2.13 30 0.64 0.080 1.93 0.100 1.77 30 0.33 0.066 7.59 0.503 5.65 30 37.41 0.235 4.29 0.285 3.33 30 10.23 0.136

21.10 1.55 2.65 0.176 2.16 30 3.16 0.086 1.81 0.120 1.54 30 1.13 0.060 1.34 0.089 1.19 30 0.48 0.045 1.07 0.071 0.97 30 0.24 0.036 6.20 0.502 4.20 30 60.10 0.185 2.94 0.239 2.14 30 11.19 0.090

25.81 1.27 1.61 0.130 1.25 30 2.61 0.051 1.00 0.081 0.82 30 0.79 0.032 0.69 0.056 0.59 30 0.31 0.023 0.51 0.041 0.44 30 0.14 0.017 3.89 0.374 2.55 30 43.13 0.114 1.79 0.172 1.33 30 6.38 0.055

30.62 1.07 1.03 0.099 0.82 30 1.58 0.033 0.67 0.065 0.56 30 0.56 0.022 0.47 0.045 0.40 30 0.24 0.015 0.35 0.033 0.30 30 0.11 0.011

Notes: Yo = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Yn = peak-to-peak amplitude at “n” cycles after Yo (mm) P = power dissipated (mW/m) Y/D = normalized amplitude = (Yo + Yn)/2

The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 30% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 7.

Page 9: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 9

Table 5 Self Damping Data for CTC ACCC/TW 1020 kcmil Conductor at 40% RTS Conductor: CTC ACCC/TW, 1020 kcmil Diameter: 28.1 mm (1.108 inch) Grease: Normal Manufacturing Alum. Strands: Trapezoidal, 2 layers, 24 strands Test Span: 32 m (105 ft) Mass/Length: 1.424 kgf/m (0.957 lbf/ft) Test Tension: 8128 kgf (17919lbf) Condition: New 40% RTS

Frequency Loop Length Yo V Yn n P Y/D (hz) (m) (mm) (m/s) (mm) (cycles) (mW/m)

16.54 0.698 12.51 50 25.97 0.516 9.95 0.420 8.28 50 6.20 0.324

13.43 2.81 7.16 0.302 6.37 50 2.03 0.241 5.80 0.245 5.35 50 0.91 0.198 4.99 0.211 4.69 50 0.53 0.172 4.43 0.187 4.19 50 0.37 0.153 9.20 0.544 7.69 50 14.17 0.300 6.50 0.384 5.54 50 6.29 0.214

18.83 2.01 4.79 0.283 4.18 50 2.90 0.159 3.70 0.219 3.32 50 1.41 0.125 3.01 0.178 2.77 50 0.72 0.103 2.57 0.152 2.42 50 0.38 0.089 6.06 0.461 4.92 50 15.31 0.195 4.11 0.313 3.54 50 5.14 0.136

24.24 1.56 3.11 0.236 2.77 50 2.18 0.104 2.51 0.191 2.29 50 1.14 0.085 2.11 0.161 1.95 50 0.70 0.072 1.81 0.138 1.69 50 0.47 0.062 4.30 0.401 3.53 50 13.43 0.139 2.96 0.276 2.53 50 5.09 0.098

29.69 1.27 2.20 0.205 1.94 50 2.23 0.073 1.73 0.161 1.56 50 1.13 0.058 1.42 0.132 1.30 50 0.65 0.048 1.20 0.111 1.10 50 0.41 0.041 3.29 0.364 2.71 50 12.99 0.107 2.26 0.250 1.91 50 5.19 0.074

35.20 1.07 1.64 0.182 1.43 50 2.32 0.055 1.25 0.139 1.11 50 1.16 0.042 0.99 0.110 0.90 50 0.63 0.034 0.81 0.090 0.74 50 0.37 0.028

Notes: Yo = peak-to-peak amplitude (mm) V = peak free loop velocity (m/sec) Yn = peak-to-peak amplitude at “n” cycles after Yo (mm) P = power dissipated (mW/m) Y/D = normalized amplitude = (Yo + Yn)/2

The power dissipation characteristics for the ACCC/TW 1020 kcmil conductor at 40% RTS is plotted as Power Dissipated, P, versus Normalized Amplitude, Y/D, and is shown in Figure 8.

Page 10: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

Deadend Assembly

Load CellClamp

Hydraulic Ram

CanteleverWeight Arm

ClampElectromagnitic Shaker Accelerometer

Figure 1: Set-up of Self-Damping Test

8

#RE

PO

RT

NU

MB

ER

10

K

-422024-R

C-0008-R

00

Page 11: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 11

-0.6

-0.4

-0.2

0

0.2

0.4

0.6

0 5 10 15 20 25 30

Time - Seconds

Vel

ocity

- m

/s

Figure 2 Typical Decay Trace

Conductor at 25% RTS, 7 Vibration Loops, 14.887 Hz

0

0.1

0.2

0.3

0.4

0.5

0.6

0 5 10 15 20 25 30

Time - Seconds

Pea

k V

eloc

ity -

m/s

Figure 3 Curve Fitted Through Peak Value of Vibration Cycles

Conductor at 25% RTS, 7 Vibration Loops, 14.887 Hz

Page 12: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

CTC ACCC/TW 15%RTS(Red represents 795 ACSR round wire conductor)

0.01

0.1

1

10

100

1000

0.01 0.1 1 10

Normalized Amplitude - Y/D

Pow

er D

issi

patio

n -

mw

/m

11.60 Hz

14.88 Hz

18.20 Hz

Series1

Figure 4 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 15% RTS (Logarithmic Decrement Method)

12

K-422024

-RC

-0008-R00

Page 13: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

CTC ACCC/TW 20%RTS

0.01

0.1

1

10

100

1000

0.01 0.1 1 10

Normalized Amplitude - Y/D

Pow

er D

issi

patio

n -

mw

/m

13.31 Hz

17.07 Hz

20.86 Hz

24.66 Hz

Figure 5 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 20% RTS

(Logarithmic Decrement Method)

13

K-422024

-RC

-0008-R00

Page 14: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

CTC ACCC/TW 25%RTS(Red represents 795kcmil ACSR round wire conductor)

0.01

0.1

1

10

100

1000

0.01 0.1 1 10

Normalized Amplitude - Y/D

Pow

er D

issi

patio

n -

mw

/m

10.63 Hz

14.89 Hz

19.14 Hz

23.42 Hz

27.59 Hz

31.91 Hz

36.18 Hz

40.46 Hz

Figure 6 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 25% RTS

(Logarithmic Decrement Method)

14

K-422024

-RC

-0008-R00

Page 15: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

CTC ACCC/TW 30%RTS

0.01

0.1

1

10

100

1000

0.01 0.1 1 10

Normalized Amplitude - Y/D

Pow

er D

issi

patio

n -

mw

/m

11.70 Hz

16.39 Hz

21.10 Hz

25.81 Hz

30.62 Hz

35.42 Hz

40.33 Hz

45.31 Hz

Figure 7 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 30% RTS

(Logarithmic Decrement Method)

15

K-422024

-RC

-0008-R00

Page 16: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

CTC ACCC/TW 40%RTS(Red represents 795 ACSR Round Wire)

0.01

0.1

1

10

100

1000

0.01 0.1 1 10

Normalized Amplitude - Y/D

Pow

er D

issi

patio

n -

mw

/m

13.43 Hz

18.83 Hz

24.24 Hz

29.69 Hz

35.20 Hz

40.78 Hz

46.41 Hz

52.23 Hz

Figure 8 Power Dissipation Characteristics of CTC 1020 kcmil ACCC/TW at 40% RTS

(Logarithmic Decrement Method)

16

K-422024

-RC

-0008-R00

Page 17: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 A-1

APPENDIX A

DATA SHEET FOR CTC ACCC/TW 1020 KCMIL CONDUCTOR

Page 18: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

K-422024-RC-0008-R00 A-2

Cable Design for Trapezoidally Shaped Conductor

Code Name: 1020 kcmil ACCC/TW Custom Design (24 wire) Type: 14

Governing Standard ASTM or CSA ASTM Total Cross Sectional Area of cndr 0.9116 in² ( 588.1 mm²)AAC, ACSR, or ACSS ACSS Annular Alum area 1087.4 kcmilAluminum Cross-Sectional Area 1020. kcmil ( 516.7 mm²) Fill factor 93.8 %Calculated Cable OD 1.108 in ( 28.15 mm ) Design Area Alum. 1020.0 kcmilDiameter of a strand wire in Core Strand 0.3750 in ( 9.53 mm ) Actual Alum. area 1020.1 kcmilNo. Strand(s) in Core 1 No. Al. strands 24No. of Alum. Wire Layers 2 No. Strands in 1st Layer 9 Al. in 1st layer 37.64 %No. Strands in 2nd Layer 15 Al. in 2nd layer 62.36 %No. Strands in 3rd Layer 0 Al. in 3rd layer 0.00 %No. Strands in 4th Layer 0 Al. in 4th layer 0.00 % Steel - GA, MA, HS, MS or S1A or S3A or AW CTC Core Conductivity of outer aluminum (%IACS) 63.0 % ASTM B857 for overall conductorConductivity of inner core (%IACS) .0 % ASTM B609 for 1350 O temper aluminumFrequency of Operation 60 Hz CTC Composite Fiberglass/ Carbon Fiber Core

Conductor Design:

Diameter of Steel Core .3750 in ( 9.53 mm )

1st Layer - number of wires = 9 Equiv. Round Wire Dia. .2066 in ( 5.25 mm ) Area per strand 42.66 kcmil Diameter Over Layer .7416 in ( 18.84 mm ) Height "t" 0.1833 in

2nd Layer - number of wires = 15 Equiv. Round Wire Dia. .2059 in ( 5.23 mm ) Area per strand 42.41 kcmil Diameter Over Layer 1.1082 in ( 28.15 mm ) Height "t" 0.1833 in

3rd Layer - number of wires = 0 Equiv. Round Wire Dia. .0000 in ( .00 mm ) Area per strand . kcmil Diameter Over Layer .0000 in ( .00 mm ) Height "t" 0.0000 in

4th Layer - number of wires = 0 Equiv. Round Wire Dia. .0000 in ( .00 mm ) Area per strand . kcmil Diameter Over Layer .0000 in ( .00 mm ) Height "t" 0.0000 in

Mechanical Properties:Aluminum (1350)

Conductor Mass 957 lb/kft 1425 kg/km 86 lb/kft 128 kg/km 1043 lb/kft 1553 kg/kmConductor Area .8012 sq.in. 516.9 sq.mm .1104 sq.in. 71.3 sq.mm .9116 sq.in. 588.1 sq.mmRated Strength 6540 lb 29.1 kN 33130 lb 147.4 kN 39700 lb * 176.5 kNTensile Strength Basis 8500 psi 300000 psi * value rounded to nearest 100lb unit

Strength Derating Factor 0.96 1

Thermal Heat Capacity 230.4 W.s/ft per F 414.7 ... per C tbd

Electrical Properties: @ 60 Hz Temperature dc Resistance

20 C 0.016486 ohm/kft 0.01687 ohm/kft 0.0891 ohm/mile 0.0553 ohm/km ( 0.054091 ohm/km)

25 C 0.016829 ohm/kft 0.01720 ohm/kft 0.0908 ohm/mile 0.0564 ohm/km50 C 0.018544 ohm/kft 0.01888 ohm/kft 0.0997 ohm/mile 0.0620 ohm/km75 C 0.020258 ohm/kft 0.02057 ohm/kft 0.1086 ohm/mile 0.0675 ohm/km

100 C 0.021973 ohm/kft 0.02226 ohm/kft 0.1175 ohm/mile 0.0730 ohm/km125 C 0.023687 ohm/kft 0.02395 ohm/kft 0.1265 ohm/mile 0.0786 ohm/km150 C 0.025402 ohm/kft 0.02565 ohm/kft 0.1354 ohm/mile 0.0842 ohm/km175 C 0.027116 ohm/kft 0.02735 ohm/kft 0.1444 ohm/mile 0.0897 ohm/km200 C 0.028831 ohm/kft 0.02905 ohm/kft 0.1534 ohm/mile 0.0953 ohm/km

ac Resistance

CTC Core Total

ac Resistance ac Resistance

Page 19: Composite Technology Corporation 2026 McGaw Avenue · PDF fileIEEE Std 664-1993, IEEE Std 563-1978 and the Transmission Line Reference Book – Wind-Induced Conductor Motion, EPRI

ISO-9001 Form: QF11-1 Rev 0, 97-10

APPENDIX B - INSTRUMENT SHEET

Test Description: Self-Damping Test Test Start Date: April 20, 2004 Project Number: K-422024-8 Test Finish Date: April 23, 2004

TEST

DESCRIPTION EQUIPMENT

DESCRIPTION MAKE MODEL ASSET # or

SERIAL # ACCURACY

CLAIMED CALIBRATION

DATE CALIBRATION

DUE DATE TEST USE

Load cell Aries TRC 10000 11137-0 1% February 11, 2004 February 11, 2005 Cable Tension

Data acquisition National

Instruments PCI-603E CCC804 0.1% September 14, 2003 September 14, 2004 Data recording Self-Damping

Accelerometer B&K 4382 1320143 2% August 24, 2003 August 24, 2004 Displacement

B-1

K-422024

-RC

-0008-R00