components used in control panelshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter...

115
29 Chapter- III COMPONENTS USED IN CONTROL PANEL 3.1 INTRODUCTION [29]: Electrical Components plays a vital role in the design process of control panel. Normally these components are specified with different IS Codes which specifies the characteristics of that particular component. In this chapter the most commonly used electronics and electrical components are studied. A power control centre of Motor control centre which consists of bus bars, functional units and cables apart from other devices plays a vital role in the distribution system of a plant.. Great care should be given to the selection of right switchgear for the right application. In spite of having selected the switchgear properly, if proper consideration is not given for the busbar, it will again be troublesome and dangerous.. Here we will look at the important points that has to be considered while designing a panel, excluding the discussion on mechanical aspects. The three main points that has to be remembered and followed throughout panel design are 1. Safety 2. Reliability 3. Maintainability. A panel can be divided into three distinct zones namely 1. Busbar zone 2. Unit chamber (Functional units) 3. The cabling zone. Each of these zones individually as well as their

Upload: others

Post on 02-Feb-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

29

Chapter- III

COMPONENTS USED IN

CONTROL PANEL 3.1 INTRODUCTION [29]:

Electrical Components plays a vital role in the design process of control panel.

Normally these components are specified with different IS Codes which specifies

the characteristics of that particular component. In this chapter the most

commonly used electronics and electrical components are studied.

A power control centre of Motor control centre which consists of bus bars,

functional units and cables apart from other devices plays a vital role in the

distribution system of a plant.. Great care should be given to the selection of right

switchgear for the right application. In spite of having selected the switchgear

properly, if proper consideration is not given for the busbar, it will again be

troublesome and dangerous.. Here we will look at the important points that has to

be considered while designing a panel, excluding the discussion on mechanical

aspects.

The three main points that has to be remembered and followed throughout

panel design are

1. Safety

2. Reliability

3. Maintainability.

A panel can be divided into three distinct zones namely

1. Busbar zone

2. Unit chamber (Functional units)

3. The cabling zone.

Each of these zones individually as well as their

Page 2: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

30

Figure 3.1: Distinct Zones of Panel

Interaction with other units has to be designed with a view to have safety,

reliability and maintainability

3.1.1 BUSBAR ZONE:

This zone comprises of the horizontal busbars, the vertical busbars and

associated supporting system.

The busbar system design should take care of the following points.

Bus bar should be able to carry

1. The rated current.

2. The current that could flow under abnormal conditions (short circuit)

Also the busbar system should be protected against.

3. Vermin, falling tools and hardware's which tend to bridge phases and

initiate arcing faults.

4. Dust and conducting deposits which accelerate tracking and supporting

surfaces and consequently cause failure of the supporting system.

Let us, now look at the parameters for proper design.

Thermal withstand capacity and short circuit withstand capacity play an

important roll for designing a bus bar.

1. Thermal Withstand Capacity:

Thermal withstand capacity depends on the following

• Busbar Material

Page 3: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

31

• Final Operating Temperature Of Busbars

• Configuration Of Busbars

• Orientation Of Busbars

• Single Or Multiple Busbars

• Ambient Temperature

• Volume Of Enclosure And Ventilation

• Busbar Bending

• Busbar Jointing

• Bolts And Bolting Schedule

• Contact Surface And Joint Compound

• Aluminium To Copper Connection

• Contact Pressure

2. Short circuit Withstand Capacity:

Short circuit withstand depends on the following:

• System Fault Level

• Clearance And Creepage

• Insulating Support

• Insulation Of Busbars

• Material Of Insulating Supports

3.1.1.1 THERMAL WITHSTAND CAPACITY:

1. Busbar Material:

Copper and aluminum are the two common materials used for

manufacturing the bus bar. Though copper has got better conductivity when

compared copper has got better conductivity when compared to Aluminium, the

increased cost of copper and indigenous availability of Aluminium are the points

that are in favor. Though the main reason is cost and availability, Aluminium has

got some advantages over copper. They are

Page 4: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

32

• The density of Aluminium is 2.95 gm/cm3 compared to 9.7 gm/

cm3 of copper. Because of its lower density, an aluminium busbar

will weigh only one half for same current rating.

• Because of the increased area, the Aluminium busbar will run

cooler than their copper busbar.

• The weight ratio of copper to Aluminium is in the range of 2.00 to

2.63, which once again helps to reduce the cost.

• The IS for Aluminium Busbar is IS 5082-1981. The conductivity

of Aluminium or copper busbars are referred to international standard

copper and expressed as a percentage.

2. Final Operation Temperature of Busbars:

As we had seen, the final operating temperature is limited by the withstand

capacity of bus bar itself. For Aluminium, the final operating temperature is

limited to 850 C because

• The operating temperature of a bus bar must be limited to a level

where there will be no long term deterioration of the conductor, the

joints or to the equipment connected to the busbar. The mechanical

strength is reduced at elevated temperature. Since the busbars are

required to withstand short circuit forces, mechanical strength is of

prime importance and so the final operating temperature is

restricted to safe value of 850 C. If mechanical strength is not of

importance and by giving particular attention to factors such as

joint design and thermal expansion, the busbars may be operated at

much higher temperatures. In general busbars are not operated at

levels that will cause reduction in mechanical strength.

Page 5: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

33

Figure 3.2: Types of Busbar Arrangement

3. Configuration of Busbars:

The current carrying capacity of busbar system is affected by the

configuration in which the busbars are placed. When a busbar installation consists

of several conductors in parallel, each conductor must dissipate the heat generated

in it since there is no metallic thermal connection between the conductors. In

horizontally arranged three phase systems, the total busbar rating is limited by the

temperature rise of one conductor even when the remaining parts may be

relatively cool. The area available for heat dissipation is more for the outer side

conductors than that of the inner ones and so they will be at lower temperature

than the inner ones.

This is explained in the figure 3.2 , where the current carrying capacity are

given for various configuration of conductors of same cross-sectional area and for

the same final temperature.

4. Orientation of Busbars:

When the busbars are arranged in a panel, for a 3 phase system, they can

be arranged in two ways as shown in fig. 3.3**** The volume of space available

above the busbar decides the amount of heat dissipated and in horizontal

orientation, the busbars have more space above than the vertical orientation. The

vertical orientation helps in reducing the magnitude of short circuit forces.

Page 6: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

34

Figure 3.3: Orientation of Busbars

5. Single Busbar or Multi Busbar:

The current distribution in a busbar (in case of AC currents) is affected by

the inductive effect due to the current in the conductor itself. This is known as

Skin Effect. Because of this, the current tries to concentrate in the outer portion

of the conductor.

If two or more conductors are there, then current distribution in one

conductor is distorted by the current in the adjacent conductors. This effect is

known as Proximity Effect.

Fig. 3.4: Number of Holes in a Busbar

Part of busbar material may be removed for holes provided. In order to ensure

temperature rise within specified limits it is necessary to keep control on busbar

material removal for holes.

Page 7: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

35

There are two guidelines provided by standards

• The remaining material at any cross section along the length of the

busbar has at least 70% of the required ampacity.

• The remaining metal in any 150 mm length of the busbar is at least

93% of the metal of a bus having the required ampacity.

1Bar 2Bar 3Bar 4Bar

Size in

mm

D.C.

50c/s

A.C.

D.C.

50c/s

A.C.

D.C.

50c/s

A.C.

D.C.

50c/s

A.C.

25.4 x

6.35

38.1 x 6

.35

50.8 x

6.35

63.5 x

6.35

356

356

520

520

672

670

820

812

718

715

1030

1020

1315

1290

1550

1510

980

970

1380

1350

1765

1705

2100

2000

1120

1100

1585

1315

2050

1940

2430

2260

76 .2 x

6.35

101.6 x

6.35

127.0 x

6.35

152.4 x

6.35

970

958

1260

1235

1545

1505

1840

1780

1805

1740

2260

2140

2700

2510

3130

2860

2440

2310

3060

2800

3660

3240

4290

3680

2860

2620

3640

3200

4410

3700

5250

4240

50.8 x

9.53

76.2 x

9.53

840

830

1210

1180

1560

1500

2180

2050

2090

1970

2940

2660

2460

2260

3510

3030

Page 8: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

36

101.6 x

9.53

127.0 x

9.53

152.4 x

9.53

203.2 x

9.53

1550

1495

1940

1860

2260

2120

2940

2750

2710

2480

3290

2930

3770

3340

4800

4150

3660

3150

4450

3660

5140

4080

6500

4900

4400

3560

5400

4200

6300

4680

8060

5740

76.02 x

12.7

101.6 x

12.7

127.0 x

12.7

152.4 x

12.7

203.2 x

12.7

254.0 x

12.7

1405

1355

1830

1740

2230

2080

2620

2420

3380

3060

4080

3640

2450

2240

3100

2720

3720

3120

4300

3500

5450

4450

6500

5000

3290

2830

4170

3360

5040

3900

5850

4400

7420

5300

8860

6000

4000

3240

5100

3900

6170

4550

7200

5100

9110

6150

10900

6850

Table 3.1: Busbar Ampacity

Note:

1. Ratings are for 500 C rises over 350 C ambient temperatures in still but

unconfined air.

2. For multiple-bar arrangements, the space between bars is equal to the bar

thickness.

3. A.C. ratings are based on spacing at which proximity-effect is negligible.

Page 9: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

37

Figure 3.5: Derating factor for proximity effect

Table 3.2 gives derating factor for proximity effect.

Phase Spacing Derating Factor

3W

4W

5W

6W

> 6W

0.82

0.89

0.95

0.99

1.00

Table 3.2: Derating Factor for Proximity Effect

t = Thickness of busbar

w = width of busbar

The area available for heat dissipation for the busbar that is placed in middle is

reduced. Because of this and due to skin effect and proximity effect, the current

carrying capacity of busbar system is not increased by the multiples of no. of

busbars. Current rating of Aluminium busbar given by one of the leading

manufacturer is given in table 3.2 for reference.

Page 10: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

38

Figure 3.6: Phase Spacing

6. Average Ambient Temperature: Referring to table No. 3.2, the foot note

says, 'Ratings are for 500 C rise over 350 C ambient temperature. The ambient

temperature, referred here, is the temperature surrounding the bus bars inside the

enclosure and not the atmospheric temperature. In Indian conditions the ambient

temperature is around 450 C to 500 C. So the ratings given in the table 3.2, are to

be suitably derated to take care of this.

The derating factor can be found out from empirical formula:

Drating Factor =

1/1.7T 2

T1

Where,

T1 = Temperature rise at the ambient

Temperature as referred by the busbar manufacturer.

T2 = Temperature rise at the ambient temperature

Where the panel will be installed.

The derating factor to be applied on the ratings given in for 500 C ambient is =

1/1.735

50

= 0.81

Page 11: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

39

7. Volume of Enclosure and Ventilation:

When the busbars temperature increases heat is dissipated through air.

Now the amount of heat dissipated is directly related to the volume of air

available inside the busbar chamber which is decided by the volume of busbars to

the total volume of busbar chamber.

Busbar rating claimed by the manufactures is in open condition. When the

busbars are kept inside the panel, they have to be suitably derated.

The amount of heat carried away depends upon the ventilating system. Busbars

are assumed to have natural ventilation. The derating factors for volume of

enclosure / ventilation are given in table 3.3

Table 3.3: Derating Factor for volume of enclosure / ventilation

8. Busbar Bending:

When making busbar joints, bending is an important process. Aluminium

busbar can easily be bend up to 900 and the bend radius varies between 1t to 2t ('t'

= thickness of busbar).

Enclosure

Installation

Cross-Sectional Area

Of Busbar/Total

Cross-Sectional Area

Of Enclosure

Derating

Factor

Outdoors ….

< 1%

5%

10%

0.95

0.90

0.85

Indoors where the

enclosure itself in a Well-

ventilated room

< 1%

5%

10%

0.85

0.70

0.65

Indoors where the

enclosure itself is poorely

ventilated and the room

temperature is high

< 1%

5%

10%

0.65

0.60

0.50

Page 12: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

40

If the bend radius is require is less than t or the bend angle is more than

900, this is possible to achieve by heating the bar under controlled conditions upto

2500 C.

It has to be ensured that there shall not be any crack developed at the bend

portion. Because it will reduce the cross section and mechanical strength of

busbars.

9. Jointing:

The simplest and most widely used method of jointing sections of busbar

is to overlap the busbar and bolting or clamp the sections together. Bolting and

clamping methods provide joints that have a fully satisfactory service life.

The main requirement for any busbar joint is that electrical efficiency should

remain stable under all conditions of service. To achieve this, the following

factors have to be taken into account when the joint is made. They are:

• Proper contact pressure must be applied and maintained.

• The surface of the Aluminium must be cleaned before bolting up.

• Air and Moisture must be excluded from the joint.

10. Bolts and Bolting Schedule:

Bolts for busbar joints may be of various grades of steel or aluminum

alloys, in case of Al. busbars.

Bolt size used shall depend on the width of flat normally following

guidelines are followed

Flat Width

Mm

Bolt Size

Mm

Min. No. of

Bolts / Joint

40 – 60

80 – 120

160 – 200

M12

M12

M12

2

4

8

Table 3.4: Guidelines for Bolt Sizes

Washers shall have sufficient thickness, proportionate to their size. There is little

point in increasing the size of the washer unless the thickness is also increased

sufficiently to prevent the washer from bending.

In addition to the plain washers, spring lock washers should also be used.

Page 13: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

41

If flat width is more than 80 mm and./or flat thickness is more than 6 mm

then it is recommended to have Slitting of busbar

Figure 3.7: Slitting of Busbar

The length of slit shall be more than width of overlap of busbars.

11. Contact Surfaces and Joint Compounds:

Before bolting up a joint, oxide and dirt must be removed from the contact

surfaces. Mechanical removal is preferred when comparing to chemical cleaning.

Grease based compounds designed to provide high stability and long term

protection against the ingress of moisture, can be applied.

The requirements to establish a good joint are:

• The surface of the Busbar must be clean and free of oxide.

• Air and moisture must be excluded from the joint to prevent formation

of the oxide during service.

• Proper contact pressure must be applied and maintained.

To achieve these,

• The contact surfaces of the Busbars should be cleaned

vigorously by hand with dry coarse emery cloth or by a power

driven wire brush. This should be done immediately prior to

the assembly of the joint.

Page 14: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

42

• A light application of a grease compound should be made to

the contact surface of each bar immediately after cleaning and

the joint should be made immediately.

The function of this compound is to exclude air and moisture from the surfaces.

The compound should be applied like a thin film. Over/liberal application of

compound can be harmful. The use of petroleum jelly is not recommended

because of its tendency to run off the joint at elevated temperatures.

The recommended compounds are HPCL multipurpose grease and Indian

Oil Corporation multipurpose grease.

12. Aluminium to Copper Connections:

The same procedures as detailed above should be used in making

Aluminium to copper connections. Preferably the copper should be cleaned with a

separate wire brush or emery cloth that will not be used on Aluminium busbars,

after ords. Since in Aluminium to copper joints, two dissimilar metals are in

electrical contact, it is necessary to ensure that moisture is excluded. If no

moisture is present, there is no possibility of electrolytic or corrosion.

13. Contact Pressure:

In bolted joints the pressure exerted on the joint interface by the bolts is

concentrated almost entirely upon the area beneath the heads of the bolts.

If fish plates are used in the joint, a slit can be provided on the fish plates.

The slit improves the joint efficiency by utilizing a greater portion of the bolt

torque in applying joint pressures, rather than on overcoming distortions on the

fish plate.

14. Material of Insulating Supports:

The final operating temperature of bus bar is limited by

• Withstand temperature of supports

• Busbar itself.

As the temperature increases, insulating Material loses the insulating

property which may lead to a flashover. But with the latest insulating materials

like SMC which can safely withstand 1500 C, temperature withstand capacity of

insulating supports is not a constraint.

Page 15: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

43

3.1.1.2 Short Circuit Withstand Capacity:

1. System Fault Level:

In case of short circuit fault busbars and insulating supports should

withstand electrodynamic forces developed during fault. While design busbars

and its supports structure it is necessary to find out maximum fault current of the

system. Refer chapter 6 for fault level calculations.

2. Clearance between Busbars:

Clearance is defined as the shortest distance between two conductors at

different potential. Clearance plays an important role in deciding the size of the

panel because more the clearance between busbars, bigger will be the size of the

panel.

Indian Standard specifies the safe minimum value of clearances, which are given

in IS but with certain assumptions. Hence it is required to give more clearance

depending upon the conditions prevailing in the area where the panel is to be

installed.

3. Creepage Distances:

The distance between two conductors at different potential, measured

along the Table 6 Minimum values of clearances and creepage distances Surface

of the insulating support is called as creepage distance. To increase the creepage

distance, it is normal practice to have the insulating supports with ribs.

Figure 3.8: Creepage Distance

Page 16: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

44

IS specifics the safe minimum value of creepage distance and the method for

measuring the creepage distance. The values are given in table 3.5.

Rated

Insulation

Voltage

Clearances

Mm

Creepage Distance

mm

I < 63A I 63 > A I < 63A I > 63A

Up to 60

60 to 250

251 to 380

381 to 500

501 to 660

661 to 750 ac

661 to 800 dc

751 to 1000

dc

800 to 1200

dc

L-L L-A L-L L-A L-L L-A L-L L-A

2

3

4

6

6

10

10

14

14

3

5

6

8

8

14

14

20

20

3

5

6

8

8

10

10

14

14

5

6

8

10

10

14

14

20

20

2

3

4

6

8

10

10

14

14

3

4

6

10

12

14

14

20

20

3

5

6

8

10

14

14

20

20

4

8

10

12

14

20

20

28

28

Table 3.5: Minimum Values of Creepage Distance

Note 1 – When the clearance L-A is greater than the corresponding creepage

distance specified in co 'a' or col 'b', then the creepage distance from the live part

to the accidentally dangerous part must be not less than the clearance.

Note 2 – The clearance and creepage distances for control and auxiliary circuits

should be those given for I L 63 A.

"The values of clearances and creepage distances specified in table 5 are based on

the assumption that the air is clean and its relative humidity does not exceed 50

percent at temperature of 400 C".

Measurement of Creepage Distance:

In determining a creepage distance, ridges less than 2 mm high should be

neglected which is shown in above figure (3.9)

Page 17: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

45

Figure 3.9: Measurement of Creepage Distance

Those at least 2 mm high are either measured along their contour, if they one

integral part of a component in insulating material.

Figure 3.10: Measurement of Creepage Distance Insulating Material

Figure 3.11: Recommended Creepage Distance

The application of the recommendation is illustrated in the figure, 3.10 and 3.11

where,

A = Insulating Material

C = Conducting Part

Page 18: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

46

F = Creepage Distance

4. Insulating Supports:

The supports play a vitally important role in the overall quality of the busbar

system. The material used for the supports should have the following desirable

properties.

1. High mechanical strength

2. High dielectric strength

3. High temperature withstand

4. Non flammable properties

5. Non hygroscopic properties

6. High comparative tracking Index.

Figure 3.12: Insulating Supports

1) High mechanical strength is required because the support should be able to

withstand short circuit forces developed. The mechanical strength is expressed in

kgf / mm2

2) High dielectric strength:

High dielectric strength is also required because the dimension of

support will be affected. The unit for dielectric strength is volt/mm. If the material

is having more dielectric strength then the size of support becomes low.

Page 19: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

47

3) High temperature withstand:

The final operating temperature of panel will be decided by the

temperature withstand capacity of busbars and the insulating support should have

non-hygroscopic property, which may lead to a flashover if it is otherwise.

4) Non Flammable properties:

Non flammable property is required because in case of any flashover in

the panel, the insulating material should not propagate the fire.

5) Non hygroscopic properties:

Hygroscopic means the tendency of the material to absorb moisture. Insulating

support should have non-hygroscopic property, which may lead to a flashover if it

is otherwise.

6) High comparative tracking Index:

The importance of having high comparative tracking Index will be best

understood, if we go through the definition on Comparative Tracking Index.

(Abbreviated as C.T.I.)

Insulation breakdown occurs either through its volume or over its surface

or in both ways. Such failure may arise from flashover or from the progressive

degradation of the insulation by small localized sparks.

Such sparks are the result of breaking if a surface film of conducting

contaminant through it. The rapid break in the leakage current produces an over

voltage at the size of discontinuity and an electric spark is produced.

These sparks may cause carbonization on organic insulation and may lead

to a carbon track between points at different potentials.

This process is known as tracking which is explained in the figure 3.13 in

steps.

One of the most common forms of contamination is atmospheric dust,

which in the presence of moisture, forms a surface film.

Page 20: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

48

Figure 3.13: Tracking Process

This surface film is conducive to track formation on the underlying insulation.

Table 3.6 shows comparison of some Insulation Material

Property Hylam Porcelain Epoxy SMC/DMC

Mechanical

strength

Dielectric

strength

CTI (VOLTS)

Tempt. Withstand

Inflammable

Moisture

absorption

Moulding to

Different shapes

Low

High

133

120

Yes

High

NO

Brittle

High

500

High

No

Low

Difficult

High

High

800

250

No

Low

Yes

High

High

1000

200-250

No

Low

Yes

Table 3.6: Comparison of Insulating Materials

Page 21: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

49

Comparative Tracking Index

The surface profile of the insulator / support is also extremely important.

Ribs and creepage barriers, which are integrated into the supports, break the

continuity of the conducting deposits and prevent tracking due to leakage currents

and surface break down.

Test for CTI:

The composition of dust is so varied that the tests using dust as the

contaminant are not suitable for standard purpose. So tests using arbitrary surface

contamination have been developed to classify materials in order of tracking

resistance (Ammonium Chloride)

Figure 3.14: Test for CTI

The unit of CTI is volts. The voltage which will cause failure with the application

of 50 drops of the electrolyte and used as a measure of the susceptibility of the

material to tracking.

The CTI is a measure of the susceptibility of the insulation material to

electrical tracking. It is defined as the voltage, determined under specific

conditions, which will cause failure with the application of 50 drops of an

electrolyte. The electrolyte essentially simulates the pollutant in industry.

Some typical CTI values for different insulating materials are given in table 3.7

below.

Page 22: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

50

Table 3.7: CTI Values

6. Insulation of Busbar:

An analysis of faults which occurred in the seventies indicate that 85% of

the faults are due to vermin of falling tools or hardware shorting the phases

momentarily and initiating arcing faults.

The easiest way to reduce possibility of arcing faults is to insulate the bus

bars. Refer Chapter 13 page no.67 gives detailed information about insulation of

busbar.

7. Short Circuit Forces On Busbars:

Electro magnetic forces will be appreciably higher than all the other forces

like weight, and thermal expansion forces.

When current is passing in a conductor, a magnetic field is set up around the

conductor. Now if another current carrying conductor is placed in parallel to the

former, electro magnetic forces will be produced between the conductors. The

forces will be produced between the conductors. The forces may be either

attractive or repulsive depending upon the direction of current.

When the currents in the two conductors have the same direction, the

forces are attractive.

When the currents in the conductors are in opposite direction, the forces

are repulsive.

Material Typical value of

CTI (in V)

1. Phenolic moldings

2. Phenolic laminated

(SRBP / SRBF)

3.Glass fiber reinforced

Polyester moldings

(SMC / DMC)

130

130

1000

Page 23: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

51

The magnitude of force depends upon the value of current (peak value of current)

and the distance between the conductors.

Figure 3.15 and 3.16: Short Circuit Forces on Busbars

The formula for finding out the Electro magnetic forces (peak) in case of three

phase short circuit between the phase conductors, is

3.2 POWER CONTACTORS:

Contactor is a mechanical switching device capable of making, carrying

and breaking currents under normal circuit conditions including operating

overload conditions.

Fm = 0.02(IP)2 ×

L

a----- kgf

Where,

Fm = Major force kgf

IP = Peak Current in kA.

L = Support Span in mm.

a = Center to center

distance between phases in mm

Page 24: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

52

Figure 3.17: Contractor

3.2.1 ELECTROMAGNETIC CONTACTORS:

A contactor in which the force for closing the normally open main

contacts or opening the normally closed main contacts is provided by an electro

magnet.

Contactor is primarily a switching device. All the regular switching

operations are done by contactor. Due to this contactor needs to have high

mechanical electrical life.

Some of the applications require switching on and off at very high

frequency. This demands that contactor should be capable of working at very high

frequency of operations. Contactors can be remotely operated.

Figure 3.18: Contractor Features

Page 25: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

53

Contactors are not designed to break short circuit currents. Thus, they are said to

have limited breaking capacity. Due to this reason backup short circuit switching

device like MPCB or MCCB is required in feeder circuits. The contactor must

however withstand the short circuit current till the back-up device clear the fault.

Normal Current

Overload Current

Short Circuit Current

A contactor has two separate electrical circuits

1. Main Circuit

2. Control Circuit

Figure 3.19: Contractor Circuits

1. Main Circuit:

The main circuit involves power contacts and handles the power. The main circuit

mainly consists of contacts and terminals. Double break contact system ensures

long contact life. Typical power contact is shown in Fig. 3.20.

2. Control Circuit:

The control circuit involves coil and auxiliary contacts. Auxiliary contacts are in

built and are used for interlocking signaling etc. The coils are vacuum

CONTACTOR Break

x

Contactor

Main Circuit Control Circuit

Page 26: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

54

impregnated or resin cast. The coil, if totally enclosed by the power magnet

ensures low power consumption. Change in control circuit may necessitate

additional auxiliary contacts. Add-on auxiliary contact blocks are provided to

meet this need.

Figure 3.20: Typical Power Contact

Contact Properties:

(a) To make circuit:

• Good resistance to environmental conditions.

• High hardness to withstand impact on closing and to permit

developing the required contact pressure.

• Surface properties that allow metallic contacts to be established during

the closing operation.

(b) To carry the current:

• Good electrical and thermal conductivity and low contact surface

resistance to reduce heating.

• Relatively higher contact pressure and larger terminals improve the

capacity to carry current.

• High melting temperature to resist excessive deformation under

current flow.

• Freedom from formation of permanent weld at the contact pressures,

within the range of current carried.

Page 27: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

55

(c) To break the current:

• Good resistance to welding and to arcing damage, to allow separation

of contacts and to conserve contact material

• High melting point to reduce material loss.

• Good thermal conductivity to reduce material loss by removing heat

from the arc spot. Relatively larger terminals help this. Strong

contactor help to break the welds formed during continuous operation.

Following are some of the factors affecting the life and performance of contacts:

1. Humidity: Saline atmosphere and humidity damage contact surface and

increase effective surface resistance.

2. Dust: Dust prevents metallic contacts from being established and reduces heat

dissipation.

Utilization Categories

A combination of specified requirements related to the conditions in which

the switching device or the fuse fulfils its purpose, selected to represent a

characteristic group of practical applications. The specified requirements may

concern for e.g. the value of making capacities (if applicable), breaking capacities

and other characteristics, the associated circuits and the relevant conditions of use

and behavior.

Table 3.8 shows utilization categories

Kind of

Current

Utilization

Categories

Typical applications

A.C.

AC-1

AC-2

AC-3

Non-inductive or slightly inductive

Loads, resistance furnaces.

Slip ring motors: starting, switching off

Squirrel-cage motors: starting

Switching off motors during running.

Page 28: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

56

D.C.

AC-4

AC-5a

AC-5b

AC-6a

AC-6b

AC-7a

AC-7a

AC-8a

AC-8b

DC-1

Squirrel-cage motors: starting, plugging,

inching.

Switching of electrical discharge lamp

control.

Switching of incandescent lamps.

Switching of transformers.

Switching of capacitor banks.

Slightly inductive loads in household

Application and similar applications.

Motor-loads for household application.

Hermetic refrigerant compressor motor

Control with manual resetting of overload

releases.

Hermetic refrigerant compressor motor

Control with automatic resetting of over

load releases.

Non-inductive of slightly inductive loads,

resistance furnaces.

Shunt-motors: starting, plugging, inching

dynamic breaking of D.C. motors.

Series-motors: starting, plugging, inching

Page 29: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

57

DC-3

DC-5

DC-6

dynamic breaking of D.C. motors.

Switching of incandescent lamps.

Table 3.8: Utilization Categories

1. AC-3 category may be used for occasional inching (jogging) or plugging for

limited time periods such as machine set-up; during such limited time periods the

number of such operations should not exceed five per minute or more than ten in

a min. period.

2. Hermetic refrigerant compressor motor is a combination consisting of a

compressor and a motor, both of which are enclosed in the same housing, with no

external shaft of shaft seals, the motor operating in the refrigerant.

Resistive loads draw only full load current during starting. Therefore, making

current is In. Breaking current is also In. The breaking duty is simple because

current is broken at almost unity P.F.

Figure 3.21: Utilization Category AC1

Current

Time

Utilization Category AC1

Making Current In Breaking Current In

Page 30: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

58

Figure 3.22: Utilization Category AC2

Squirrel cage induction motor draws 6 x In on DOL starting. Motor is switched

off after the starting current has come down to the load current. Breaking current

is In+6.

Figure 3.23: Utilization Category AC3

Squirrel cage induction motor with inching duty is switched off on starting

current. Breaking current is also 6 x In.

Current

Time

Utilization Category AC3

Making Current In

6 * In

Breaking Current In

Current

Time

Utilization Category AC2

Making Current In

2.5 * In

Breaking Current In

2.5 * In

In

Page 31: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

59

Figure 3.24: Utilization Category AC4

How to read life curve of a contactor:

Both X-axis and Y-axis are in log scale. Assume the life curve is for utilization

category AC-3. We take an example of 70 A Contactor. The vertical straight line

ab presents AC-3. Life for 70 A contactor. Point b projected on Y-axis is e. The

life of contactor for 70 A current is e. No. of operating cycles.

Figure 3.25: Life Curve of Contractor

The same contactor when used for 40 A current gives life cd Point d projected on

Y-axis is f. The life 70 A contactor for 40 A current is f. no. of operating cycles.

Here, f>e

1 10 40 70 100 1000

f

e b

d

c

Current in Amperes

Current

Utilization Category AC4

Making Current In 6 * In

Breaking Current In 6 * In

Time

Page 32: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

60

There is increase in no. of operations for a contactor when used for lower current

than rated.

Control Circuit:

The control circuit voltage has extra significance in defining (1) the circuit

voltage in which the contactor will hold positively and (2) the drop-off voltage.

Various coils for different voltages can be given for both a.c. and d.c.

Limits of Operation of contactor (a.c.Coil):

Electromagnetic contactors shall close satisfactorily at any value between

85% and 110% of their rated control supply voltage (Us), for wide band coils,

85% shall apply to the lower value and 110% to the higher.

Figure 3.26: Limits of Operation of Contractor

The limits between which contactors shall drop off out and open fully are 75% to

20% for a.c. their rated control supply voltage (Us). For wide band coils, 20%

shall apply to the higher value and 75% to the lower. These limits apply to a.c.

declared frequency. Pick-up band for d.c. coils is same as that of a.c. coils. The

limits between which contactors will d.c. coils shall drop out and open fully are

75% to 10% of rated control supply voltage. Where the range is declared 10%

shall apply to the higher value and 75% to the lower.

For a.c. coil

100

Drop off Band

Pick Up Band

0 20 75 85 110

Page 33: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

61

Limits of operation of contactors (a.c.coil):

Figure 3.27: Operation of Contractor

Frequency:

In a.c. magnet system contactor coils are designed for 50 Hz frequency at the

rated coil voltage. For frequency other than 50 Hz, V/f ratio shall be kept

constant. Special 60 Hz, keeping V/f constant are available as a standard feature.

This is required to maintain the coil performance as specified above. Special coils

for 60Hz application are also available.

Voltage at frequency f Hz:

Uf f

-------- = -------

U 50 50

Uf = Voltage at frequency f Hz

U50 = Voltage at frequency 50 Hz

Pick up and Hold-on Vas:

Pick-up VA is product of pick-up current and rated coil voltage.

For a.c. coil

100

Drop off Band

Pick Up Band

0 10 75 85 110

Page 34: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

62

Calculations of coil currents for AC coils:

For coil voltage = 110V.

Pick-up current = = 2100/100

= 19.09 A.

Pick-up current = = 95/100

= 0.86 A.

When the contactor is open, air gap is present between moving magnet and fixed

magnet. The air gap introduces high reluctance in the magnetic circuit.

Due to high reluctance, magnetic flux is low. Lower magnetic flux reduces

the reactance of the coil. Lower coil reactance leads to higher current during pick-

up.

Figure 3.28: Contractor Open and Close

Once the contactor has closed, air gap is zero. This given rise to a high magnetic

flux, in the magnet. This magnetic flux, linking to the coil, increases the

reactance. Increased reactance leads to reduction in the coil current during hold-

on.

Pick Up VA

Coil Vtg

Hold On VA

Coil Vtg

Page 35: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

63

Application of a.c. coil for d.c.:

A quick adaptation of a.c. coil to d.c. is possible by the use of economy

resistance. An economy resistor helps reduce the d.c. current to the level of a.c.

current. The arrangement is as shown in the figure. Deposite its quick adaptation

it has the disadvantage of (a) power dissipation in Rg and (b) time delay in the nC

contact.

`

Figure 3.29: Application of AC coil for DC

3.3 THERMAL OVERLOAD RELAYS:

3.3.1 Motor failures:

Fig. 3.30 shows general reasons for motor failure. This pie chart also gives

percentage contribution of each reason towards failure.

From pie chart overload and single phasing put together contribute to

about 44% towards motor failure.

Bearing Fail

13%

Overloads

30%

Contaminates

19%

Misc

9%

Single Phasing

14%

Rotor Fail

5%

+

-

Rg

Page 36: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

64

Figure 3.30: Motor Failures

3.3.2 Factors Leading to Overheating:

• Overload

• Supply variations

• Heavy starting

• High Duty

• High Starting frequency

• Single phasing

• Locked rotor

• Faulty bearing and other mechanical reasons.

• High ambient

• Anomalies in cooling

Temperature Withstand of Motors:

A large percentage of motor failure are due to our misconceptions

concerning motor ratings and motor protection, Fig 2.2 shows a typical

temperature withstand curve for a motor.

Figure 3.31 shows typical Motor Damage Curve.

This curve indicates that the motor winding may carry its full rated current for an

indefinite period of time without any damage. This condition is possible because

the heat generated in the motor winding as a result of I2R can be properly

dissipated before an abnormal temperature is reached. As long as the motor

winding is clean and dry, the air passages in the motor winding are open and a

Page 37: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

65

supply of relatively cool air is available to dissipate the heat generated, the above

conditions will prevail.

Figure 3.31: Motor Damage Curve

The same curves indicate that if twice the normal full-load current is passed

through the motor winding, the heat generated in motor is mote than the heat

dissipation and therefore the motor temperature will rise. However there is a

specific time interval during which this may be allowed to happen. The same

holds goods if 300, 400, 500, 600 of even 1000 percent of the motor full load

current is passed through the motor windings. Heat generation will be greater than

heat dissipation, but there will be a specific time interval before any damage is

done to the motor winding. The objective of motor protection is to prevent an

excessive temperature rise which would damage the motor winding.

Device of protection:

Various types of protection devices can be broadly classified in three categories:

(a) Temperature Sensing

(b) Current Sensing

(c) Voltage Sensing

Following figure 3.32 illustrates the various devices that are available today for

protecting the motors. This covers only devices for general application and is not

exhaustive.

Current (% motor full load)

Page 38: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

66

The user, depending on the importance of the application, severity of

environment and supply

Figure 3.32: Motor Protection Devices

Conditions and expenses that he is prepared to incur, has to make a judicious

choice.

Out of these devices those that offer closet protection are:

Temperature sensing device:

These devices, to the extent that they are able to sense that exact temperature of

winding, offer protection against all the abnormal situations listed above.

Current Sensing devices:

These devices, being an indirect sensing device cannot offer protection against:

(a) Excessive ambient temperature

(b) Over Voltage

(c) Frequency variation.

These have to be taken care by other means. Thermal bimetallic relays.

They are the most economical devices of all protective devices that are available.

Relays offer protection both against single phasing as well as overloads and thus

Page 39: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

67

are one of the most popular devices for motor protection. The principle of

operation is as follows,

A thermal bimetallic relay works on a principle that the bimetal deflects

when heated and if one end of the bimetal is fixed, the other deflects in proportion

to the heat input.

In an overload relay intended to protect a 3 phase motor, there are three

bimetals for sensing line or phase currents.

The bimetal deflects when heated and, on reaching a predetermined condition,

trips a mechanism (open a contact). The amount or deflection required to trip is

more or less depending on the setting of the relay.

A compensating bimetal is used to ensure a consistent trip time in case of

variation in ambient temperature.

Relay characteristics:

Designers make their thermal overload relay with heat shortage

characteristics similar to those of the motor, but enough faster so that the relay

will always reach the tripping temperature before the danger temperature. The

relay characteristics should be below the motor damage curve. If it lies very much

below the motor curve, it can lead to unwanted trippings. The relay characteristics

chosen should be as close as possible to the motor damage curve.

Specification:

IS 13947 (Part 4/Sec 1) :1993/IEC 60947 (Part 4/Sec 1) lays down the

specifications that are to be satisfied by thermal bimetallic relays.

Table 3.9 shows this

Conditions to be met with at Test current as multiples of set current

Conditions Max. non-trip

currents

A

Min. Trip

Currents

B

1. All poles energized

2. When two poles are energized

3P 1.05

3P 1.2

Page 40: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

68

Relays without protection

against single phasing

Relay with protection against

single phasing

2P 1.05

2P 1.0

1P 0.9

2P 1.32

2P 1.15

1P 0

Table 3.9: Thermal Bimetallic Relay Specifications

The relays shall comply the requirements given in table 11when tested as follows

as per IS 13947/IEC 60947 Part 4. Table 3.10 shows this

TRIP CLASS TRIPPInG TIME In SECOnDS WHEN

TESTED AT CURREnT 7.2 TIMES

10 A

10

20

30

2 < Tp < = 10

4 < Tp < = 10

6 < Tp < = 20

9 < Tp < = 30

Table 3.10: Relay Compliments

Tips for application:

Further for relays operating on double slide principle the protection

against single phasing is substantially better at maximum setting. The following

tips will therefore be useful to achieve the best protection against single phasing.

• Select a relay such that motor current lies towards maximum setting.

• This necessitates that the relay family should be such that there is a

consistent overlap between two successive ranges.

• Setting ratio of the relay range should be the maximum. Relay

available today have a setting ratio of 1.3 to 1.66

Page 41: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

69

Max. Relay set current

Setting ratio = --------------------------------------

Min. Relay set current

Generally Relay setting is recommended as per actual current drawn by the

Motor.

Too large or too small cross section of cable terminals may result in

excessive temperature rise and nuisance tripping, or non-tripping of relay at

higher overloads.

Overload relay with manual reset should always be used where continuous

contact devices are connected (e.g. limit switches, pressure switches) to avoid

restarting automatically. Reset button to be fitted as an external feature in order to

make it accessible to all personnel. Overload with auto reset can be used only

with impulse contact devices such as push buttons, because on these the cooling

of the bimetal strip cannot lead to automatic reconnection.

Backup fuse:

Backup fuse for instantaneous trip are needed to protect not only the motor

but also the relay against the effect of short circuit. These are clearly marked on

the relay as MAX.BACKUP FUSE. However a lower rating of fuse can be

selected to minimize the damage to the contactor and other system. Refer fuse

selection for further clarification.

Overload protection of high starting time motors:

The starting time of a motor depends upon the motor and load torque and the total

inertia of the system.

• A is main Contactor

• B is by pass Contactor

• Control by timer

Page 42: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

70

Figure 3.33: Overload Protection for Motors

The starting time can be long when the motor is started on heavy inertia loads.

This results in high current to flow through the relay for longer duration. The

normal trip time for thermal overload relays at 6 x In is in the range of 5 – 12 sec.

Hence, the relay set at normal full load current for a motor trips during heavy

starting, resulting in nuisance tripping. To avoid this problem two solutions are

available.

• Saturable core CT operated relay.

• Relay bypass during starting.

Saturable core CT operated relay:

Saturable of the core of CT is achieved by using a saturation kit in series

with the relay. The secondary current of the CT is not as per the current

transformation ratio of CT due to saturation.

To bypass the overload relay during starting:

This method is to be used when motor starting time is beyond permitted

by Saturable core CT operated relay. In this method, the relay is bypassed during

starting by the addition of a contactor connected in parallel with the relay. After a

set time delay‘t’, the contactor B is de-energized and the relay is introduced in the

power circuit. The power scheme is shown in Fig. 3.32.

Thermistor protection devices:

Thermistors are semi-conductor device whose resistance varies with

temperature. There are two types of thermistors viz.

nTC – negative temperature coefficient.

Page 43: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

71

PTC – Positive temperature coefficient.

Resistance of nTC thermistors decreases sharply with specified increase in

temperature, resistance of PTC thermistor increase with temperature and also it

has a short cutt-off temperature, while for PTCs there is a sharp cut-off

temperature. These have to be embedded in the motor winding. Typically 3 or 6

such devices are used.

PTCs and nTCs give signal to control unit which in turn trips the motor.

Because of the sharp cut-off characteristics of PTCs it is possible to design a

standard control unit for all temperature, while nTCs requires the unit to be tailor-

made.

In PTC based unit, the increase in resistance is detected as fault. Any

break in lead, therefore, indicates a fault. PTC based systems are thus fail safe. BS

4999 prohibites the use of nTC based devices for protection of motors PTCs are

available for 1000C to 1400C in steps of 100C since it is the temperature of the

winding that is sensed. Thermistors offer the ultimate in protection.

Electronic Single Phasing Preventors:

The text Single Phasing Preventor is a misnomer. The devices do not prevent

any single phasing but protect the motors from getting damaged irreparably due to

single phasing. Protection against overload conditions should be taken care by a

relay. The devices operating on two different principles are available today.

•••• Current sensing: These work on the principle of negative phase sequence

currents. When motor gets only two phases – ve phase sequence currents

are produced and these are sensed by relay. It isolates the motor from

supply irrespective of the load on the motor. To avoid nuisance tripping

due to unbalance currents in winding these devices tolerate imbalance up

to 10%. This limit can be lowered if better supply conditions can be

assured. Typical operating time is 10-20 seconds on On LOAD and 5-15

seconds on FULL LOAD. These are to be connected in series with the

motor.

•••• Voltage Sensing: These devices sense the absence of voltage, and are to

be connected across the line. Refer Fig 3.19

Page 44: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

72

They suffer following drawbacks-

- Downstream faults are not protected.

- Current unbalance due to inter-turn short is not detected.

Figure 3.34: Single Phasing Preventors.

3.4 STARTERS FOR SQUIRREL CAGE INDUCTION

MOTOR:

Three phase squirrel cage induction motor constitute major portion of

industrial drives. Smooth starting of motor is important for load and source as

well. This chapter deals with purpose and operation of DOL and STAR- DELTA

starters for three phase squirrel cage induction motors.

Generally, percentage of squirrel cage induction motor load goes as high as

90% of total industrial load as illustrated in Fig 3.34. Thus we would be

concentrating the discussion mainly on starting of Squirrel cage motors.

Page 45: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

73

Figure 3.35: Squirel Cage Motor % Use

Fig. 3.36 shows location of starter in a motor feeder circuit.

3-phase supply:

Figure 3.36: Location of Starter

The need of starter for S.C.I.M.

1. Switch On/OFF

2. Remote On/OFF

3. Limit starting current/torque.

Fuse Switch Unit

STARTER

MOTOR

Page 46: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

74

Types of squirrel cage Induction Motor Starter:

Figure 3.37: Types of SCIM

DOL Starter:

Motor Starter windings are permanently connected in Delta. Full 3-phase line

voltage is applied at starting. The starting current drawn by the motor is about 6-8

times the rated current of the motor.

Starting torque developed by motor with DOL starter.

Figure 3.38: DOL Starters

Starter

Full Voltage Reduced Voltage

Star - Delta Auto Transformer

DOL Direct On Line

Page 47: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

75

For Induction Motors

V2

T a --------- Where

S Tr = Full load torque

I r = Full load current

Sr = Slip at full load

Tst ( Ist )2 Tst= Torque at starting

---- = ------ x Sr Ist= Starting current

Tr ( Sr)

Advantage of DOL starter:

Following are advantages of DOL starters

• High starting torque.

• Rapid acceleration of motor.

• Low cost of control gear required.

Limitations of DOL starter:

• Heavy inrush starting current can cause a dip in the system voltage.

• Starting of large motors on DOL would demand increase in capacity of

sources.

• kVA maximum demand would increase.

Star – Delta Starter:

First motor stator windings are connected in star.

Figure 3.39: Star Starters

Page 48: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

76

Motor windings get phase voltage although full 3-phase line voltage is switched

on. Thus, it is reduced voltage starting. Motor is allowed to run in STAR till such

a time it has reached 80% if the rated speed. After this, motor is reconnected in

DELTA

Figure 3.40: Star Delta Starters

Power circuit of Star-Delta starter:

Sequence of contactor operations:

1. Star contactor pick-up

2. Hold-on contactor pick-up. Motor starts in star.

3. Star contactor opens.

4. Delta contactor pick-up. Motor switched from star to Delta.

Figure 3.41: Power Circuit of Star Delta Starter

Page 49: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

77

Types of Star Delta Starters:

Figure 3.42: Types of Star Delta Starters

Changeover scheme for hand-operated starter:

Figure 3.43: Changeover for Handheld Starters

Changeover scheme for semiautomatic Star-Delta starter:

The motor would continue to run in star till the star push button is pressed. When

start push button is released the motor would be switched to delta.

Star Delta Starter

Fully Automatic Semi-Automatic Hand Operated

Thermal Timer Electronic Timer

Page 50: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

78

Figure 3.44: Changeover for Semiautomatic Starters

Change over scheme for fully automatic starter with thermal timer:

Figure 3.45: Changeover for Fully Automatic Thermal Starters

Change over scheme for fully automatic starter with electronic timer:

Pause time: During the change over from star to delta, star contactor drops.

Arcing occur between the contacts for a short period. During the same time if

Page 51: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

79

delta contactor picks-up before arching in star, which results in leading to welding

of delta contacts and blowing of fuse.

Figure 3.46: Changeover for Fully Automatic Electronic Starters

Torque developed during star-delta starting:

The voltage applied at starting is phase voltage. Thus, the starting current drawn

by the motor is ILR/3 where ILR is locked rotor current of the motor.

For Induction Motor

V2 Where,

T a --------- T = Torque

S V = Applied Voltage

S = Slip

__________________________________

We know that,

I2 (V/ 3)2

T f a ---------- and Tst a -------------

Sf St

----------------------------------------------------------------------------

Therefore

T 1 ( I )2

Page 52: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

80

-------st- = ------ -----LR-- x Sf

T f 3 (If)

Typical curves of currents during star-delta start.

Figure 3.46: Torque Characteristic for Star Delta Starters

Typical curves of torque during star-delta start

CMD = Motor torque

CMY= Load torque

Figure 3.48: Typical Curve of Star Delta

Page 53: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

81

Timers for fully automatic star-delta starter:

Thermal timer:

Figure 3.49: Timers for Fully Automatic Starters

The time delay in the timer is achieved through displacement of a bimetallic

element which operates on current drawn from the secondary of a transformer.

After each timing cycle, the operating coil must be de-energized so that bimetal

cools and resets to its initial position.

Electronic Timer:

Figure 3.50: Electronic Timer Circuit

On energization of the timer, the output star relay energizes instantly. After

completion of preset delay time, output delta relay energizes after fixed pause

time this pause time is 60 ms. This provides shortest possible ‘current off’ pause

and simultaneously ensures smooth changeover.

Page 54: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

82

Figure 3.51: Electronic Timer Connection

Auto-transformer starter:

A starter for an induction motor which uses for starting one or more reduced

voltages derived from an auto-transformer.

Transition types with ATS:

Figure 3.52: Transition types with ATS

Open transition: A circuit arrangement such that the supply of the motor is

interrupted and reconnected with changing over from one step to another.

Closed transition: A circuit arrangement such that the supply of the motor is not

interrupted when changing over from one step to another.

ATS

Open transition Closed transition

Page 55: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

83

Typical curves of currents during ATS start:

IR = Motor current at rated voltage

LT= Motor current at reduced voltage

I L= Line current at reduced voltage

Figure 3.53: Current Characteristics during ATS Start

Typical curves of torques during ATS start:

CR = Load torque

CM = Motor torque

CMR= at rated voltage

CMT= at reduced voltage

Figure 3.54: Torque Characteristic during ATS Start

Page 56: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

84

3.5 SWITCH, SWITCH DISCONNECTOR AND FUSE

COMBINATION UNIT:

Disconnector:

A mechanically switching device which, in an open position,

complies with the requirements specified for the isolating function.

A disconnector is capable of opening and closing a circuit when

either a negligible current is broken or made, or when no significant change in the

voltage across the terminals of each of the poles of the disconnector occurs. It is

also capable of carrying current under normal circuit conditions and carrying for a

specified time currents under abnormal conditions such as those of short circuits.

Switch:

A mechanical switching device capable of making, carrying and

breaking current under normal circuit conditions which may includes specified

operating overload conditions and also carrying for a specified time currents

under specified abnormal circuit conditions such as those of short-circuit.

A switch may be capable of making, but not breaking, short-circuit

currents.

Switch disconnector:

A switch which, in the open position, satisfies the isolating

requirements specified for a disconnector,

Switch-disconnector:

A switch which, in the open position, satisfies the isolating

requirements specified for a disconnector.

Disconnector-fuse:

A disconnector in which one or more poles have a fuse in a

composite unit.

Switch disconnector fuse:

A switch –disconnector in which one or more poles have a fuse in

series in a composite unit.

Fuse-disconnector:

Page 57: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

85

A disconnector in which a fuse-link or fuse-carrier with fuse-link

forms the moving contact.

Fuse-switch:

A switch in which a fuse-link or fuse a fuse-carrier with fuse-link

forms the moving contact.

Fuse-switch-disconnector:

A switch-disconnector in which a fuse-link or a fuse-carrier with

fuse-link forms the moving contact.

Distinction between AC-23 and AC-3 rating of switches:

AC-23 duty is defined in IS 13947, (Part3) as switching of motor

loads or other highly inductive loads.

NAC-23n utilization category referred in IS 13947 (part3) does not

apply to equipments normally used to start or stop individual motors. AC-3

utilization category is squirrel cage motors: starting and switching off of motors

during running.

Hence, AC-23 application necessarily means that two switching

devices are connected in series. One is to be used for switching of motor (starter,

for e.g.) and other (switch) as backup. Therefore a starter is to be used for normal

on / off operation of the motor and the switch is used only as a back up devices

required operating sparingly.

Figure 3.55: Distinction of AC-23 and AC3 Switches

Page 58: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

86

Under normal condition, i.e. when contactor is functional, the switch is normally

expected to make / break rated current at rated voltage. However, if the contactor

is welded, & the rotor of the motor is locked, them the switch may have to make /

break 10 or 8 times the rated current at the rated voltage. This is because the

switch is used as a backup device.

AC-3 rating apply only is the switch directly switches on the motor

as shown above. If the switch is of backup, AC-3 rating has no significance.

Table 3.11 shows utilization categories for AC-3 switches

Utilization Category Making Make-break

I/Ie U/Ue Cos Ø Ic/Ie UrUe Cos Ø

AC – 20 A/B

AC – 21 A/B

AC – 22 A/B

AC – 23 A/B

---

1.5

3

10

---

1.05

1.05

1.05

---

0.95

0.65

0.45

---

1.5

3

8

---

1.05

1.05

1.05

---

0.95

0.65

0.45

Table 3.11: Utilization Categories for AC-3 Switches

Utilization

Category

Typical Application

AC – 20 A/

AC – 20 B

AC – 21 A/

AC – 21 B

AC – 22 A/

Connecting and disconnecting under

no-load conditions

Switching of resistive loads including

Moderate overloads.

Switching of mixed resistive and

Page 59: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

87

AC – 22 B

AC – 23 A/

AC – 23 B

Inductive loads, including moderate overloads.

Switching of motor loads or other3

Highly inductive loads.

DC – 20 A/

DC – 20 B

DC – 21 A/

DC – 21 B

DC – 22 A/

DC – 22 B

DC – 23 A/

Connecting and disconnecting under

No-load conditions.

Switching of resistive loads including

Moderate overloads.

Switching of mixed resistive and

Inductive loads, including moderate overloads.

Switching of highly inductive loads.

Table 3.12: Utilization Categories for Different Switches

3.6 HRC FUSE LINKS:

Fuse:

A switching device that, by the fusion of one or more of it’s

specially designed and proportioned components, opens the current in which it is

inserted and breaks the current when this exceeds a given value for a sufficient

time. The fuse comprises all the parts that forms the complete switching device.

Fuses have four things to do in a circuit:

• The fuse must sense faults.

• The fuse must open quickly and clear itself when a short circuit occurs.

Page 60: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

88

• The fuse must also sense a normal or harmless overload before it becomes

excessive or prolonged.

• The fuse must not change or later the characteristic of the circuit during

normal operation.

Construction:

Figure 3.56: HRC Switch Construction

Fuse link parts Material

1. Fuse body

2. Quartz powder

3. Knife

4. Fuse element

5. Globute

Steatite.

Quartz

Copper with silver plating.

Copper with silver plating.

Solder / Tin.

Table 3.13: Fuse Link Parts and Material

Definition:

Refer Fig. 3.42

P – Prospective peak current of a circuit

C – Cut-off current

t1 – Pre-arcing time.

t2 – Arcing time.

Page 61: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

89

T – Total operating time.

Pre-arcing time (Melting time t1):

The time between the commencement of a current large enough to

cause the fuse element(s) to melt and the instance when an arc is initiated.

Figure 3.57: Characteristic of Pre-arcing Time

Arcing-time (t 2):

The interval of time between the instance of the initiation and the

instant of final are extension.

Operating time (T):

The sum of the pre-arcing time and the arcing-time.

Prospective current (P):

The current that would flow in a circuit if a fuse situated therein was replaced by a

link of negligible impedance without any other change in the circuit or of the

supply.

Cut-off current(C):

The maximum instantaneous value reached by the current during

the breaking operation of a fuse when the fuse operates in such a manner as to

prevent the current from reaching the otherwise attainable maximum.

Fuse characteristics:

• Time / current characteristics

Page 62: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

90

• I2t characteristics.

• Cut-off and let-through current characteristics.

1. Time/Current characteristic:

A curve giving the pre-arcing time as a function of the prospective

breaking current under stated conditions of operations.

2. I2t (joule integral):

The integral of the square of the current for a given time interval is

t1

I2t = I2dt

to

I 2t characteristics:

A curve giving I2t values (pre-arcing I2t and / or operating I2t) as a

function of prospective current under stated conditions of operation. HRC fuse-

links offer one of the best forms of protection for motor starting applications in

view of very low short circuit stresses generated in case of a fault as compared to

other protective devices. However, the best possible rating of a HRC fuse-link

selected / recommended for such application depends on following basic

requirements:

(a) Ability to withstand motor starting current:

The fuse-link selected should withstand repeated starting currents without any

deterioration. The rating of fuse-link is decided by:

1. The motor starting current and its starting time. This will depend on two

factors:

- Type of starter (e.g. DOL or Star-Delta)

- Motor characteristics.

2. Time current characteristics of the fuse link.

(b) SCPD co-ordination:

As per the standard IS 13947, part4 section1/IEC 60947 part 4 sec. 1, for the short

circuit protective device co-ordination, ntwo types of co-ordinations are

Page 63: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

91

permissible ‘Type 1 or 2’. Thus the fuse-link selection will also depend on its

short-circuit characteristics i.e. the cut-off current and I2t characteristics.

(c) Discrimination:

There should exist discrimination between the overload relay and the SCPD i.e.

the fuse link This means that for overload currents less than Ic (Ic=the current

corresponding to the intersection point of overload relay and the fuselink

characteristics.) the relay should operate and protect the device and not the fuse-

link. Also there should be no damage to the starter. The contactor breaking

capacity should be greater than Ic. For overload currents more than Ic, the

fuselink should operate before the relay protect the circuit. Here the fuse link is

selected based on its time current characteristics and the time-current

characteristics of the overload relay.

(d) Low power loss:

One of the most important factors while selecting a HRC fuse-link is its power-

loss. The rated power-loss of the fuse-link is the power-loss value as stated by the

manufacturer when the fuse-link is carrying its current under specified conditions.

The fuse-link selected should preferably have low power-loss.

The advantages of having such fuse-link with low power loss are:

• Saving in power / energy.

• Lower temperature rise at fuse-switch terminals and fuse-knives.

Type 2 co-ordination:

IS/IEC standard actually defines different levels of protection for system’s motor

starters after a fault or over current has occurred. These levels are defined as

nType 1n and nType 2n co-ordination.

For Type 1 co-ordination, the standard states that under fault conditions

the contactor or starter shall cause no danger to persons or installation and may

not be suitable for further service without repair or replacement of parts.

For Type 2 co-ordination, a higher level of protection, the IS/IEC standard

states that under fault conditions the contactor or starter shall cause no danger to

persons or installation and shall be suitable for further use. The risk of light

contact welding is noted and each manufacturer should provide direction to

Page 64: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

92

maintain their equipment. Type 2 protections reduces fire and safely hazards,

minimizes disruption in production and system downtime, minimizes replacement

costs, provides solutions for no damage protection requests and provides simple

starter selection.

Obtaining type 2 protection: (p,q, r current tests):

Each combination of contactor, overload relay, and short circuit protective

device must be evaluated and tested. The tests are as follows.

Discrimination test: (‘p’ test)

Discrimination testing verifies that the overload relay will protect from

over current conditions and that the fuse will protect under fault conditions. This

test must be performed to verify overload protection. The currents for the tests

shall be:

1. 0.75 Ic + 0%, -5% and (Relay must trip)

2. 1.25 Ic + 5%, -0% (Fuse must blow)

Ic being the current corresponding to the crossover point of the mean curves

representing the time current characteristics of the overload relay and the SCPD

respectively.

Low level fault test:

A discrete low level fault test is performed at rated voltage, related to

starter’s operating current. This is the more severe test on the starters and the test

that will most likely cause contact welding because of the slower operation of the

short circuit protective device.

Performance under short circuit: (‘r’ test)

Test at protective current nrn.

The test is performed at appropriate value of prospective test current nrn. The

value very with operational current of starter and are given in following table as

per IS 13947 (part 4/Sec 1): 1993/ IEC 60947 Part4, Sec.1

The circuit shall be adjusted to the prospective test current. The contactor

or starter and the associated SCPD or the combination or the protected starter,

shall then be connected in the circuit. The following sequence of operations shall

be performed:

Page 65: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

93

• One breaking operation of the SCPD with all the switching devices closed

prior to the test.

• One breaking operation of SCPD by closing contactor.

3.7 FAULT LEVEL CALCULATIONS:

All important criteria for the proper selection of a circuit breaker or other

interrupting device for use at any point in an electrical network is the knowledge

of fault current likely to be available at that point.

Two types of fault currents need to be calculations.

• Min. fault current – This decides settings for short circuit protection.

• Max. fault current – This decides equipments withstand capacity. Proper

selection of breaking capacity for the circuit opening device in any

network result in more safe design of the system.

Type of faults:

1. Symmetrical fault:

- 3 phase fault

R

Y

B

2. Unsymmetrical faults:

- Line to line fault

- Double line to earth fault

- Line to earth fault

R

Y

B

E

Page 66: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

94

R

Y

B

E

R

Y

B

E

Figure 3.58: Types of Fault

Typical oscillogram of a short circuit current. The short circuit current consists of

following two components. AC component & DC component. AC part of the fault

current is fed by the supply. DC part comes from sorted energy in inductances and

capacitance of network components. If fault occurs at zero on the sinusoidal wave

from, magnitude of DC components is maximum. AC components are

symmetrical and sinusoidal where as DC component is exponentially decaying.

The decay depends on the time constant of the system which can be given by ratio

X / R. AC components is superimposed on DC component. Thus short circuit

wave is initially disposed asymmetrically about the zero axis. DC components die

out in 3 to 4 cycles. This gives AC sinusoidal current as sustained fault current.

Figure 3.59: Current Characteristic

Page 67: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

95

= Initial symmetrical rms S/C current

= Steady state rms S/C current

= Peak S/C current

= Initial Value Of decay in DC component

Sources of short circuit currents mainly are

1. Source of supply

- Transformers

- D.G. Sets (Information on DG set will be shared in next article)

2. Loads

- Induction Motor

- Synchronous Motors

Shunt Capacitors

3.8 AIR CIRCUIT BREAKERS:

A circuit breaker is an electrical device that opens and closes a set of electrical

contacts of an electrical circuit.

Figure 3.60: Circuit Breaker

Fig. 3.61 shows circuit breaker contacts in closed position.

Figure 3.61: Closed Circuit Breaker

RRRR YYYY

BBBB

RRRR YYYY

BBBB

Page 68: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

96

Fig. 3.62 shows circuit breaker contacts in open position.

Figure 3.62: Open Circuit Breaker

Fig 3.63 shows a four pole circuit breaker.

The neutral is switched ON and OFF along with three poles in four pole circuit

breakers. This figure shows circuit breaker contacts in open position. Circuit

breaker is a mechanical switching device, capable of making, carrying and

breaking current under normal circuit conditions and also making, carrying for a

specified time and breaking currents under specified abnormal circuit conditions

such at those of short circuit. In air circuit breakers the contacts open and close

in air, at atmospheric pressure.

Fig 3.64 shows a simplified diagram of an air circuit breaker. The wires represent

the breaker’s connection to the main power circuit. The major parts of the circuit

breaker are a stationery contact, a movable contact, a spring and a latching

mechanism. The spring is compressed or charged and contacts are closed. The

latching mechanism holds the cotacts closed.

Figure 3.63: Four Pole Circuit Breaker

RRRR YYYY BBBB

NNNN

Page 69: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

97

In the Fig. 3.65 the latching mechanism shown is operated manually by

pressing a button. After the button has been pressed, the latch has moved, and the

spring has discharged to force the contacts open. Any action that causes the

contacts to open is known as tripping the breaker.

Figure 3.64: Latching Mechanism for Circuit Breaker

Arcing:

When circuit breaker contacts are opened under load, an arc is drawn between

them. Arcing is undesirable because:

• It causes pitting of the contacts, leading to high resistance, and

• Current flow in the circuit continues as long as the arc remains.

Circuit breakers are designed to contain and rapidly extinguish arcing.

Effects of arcing:

Even if arcing is quenched quickly, the circuit breaker contacts will still become

pitted over a period of time. Pitting reduces the area of smooth contact surface,

resulting in increased resistance across the contacts. Current flowing through the

contacts can cause overheating, leading to further damage.

Circuit breaker contacts:

To prevent the effects of arcing from interfering with the operation of the circuit

breaker, two sets of contacts are used:

Page 70: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

98

• The arcing contacts close first and open last, making and breaking the

circuit.

• The main contacts carry the full load current.

Figure 3.65: Circuit Breaker Contacts

The main contacts are the breaker’s main current carrying conductors when a

circuit operates at normal load. The arcing contacts are connected in parallel with

the main contacts. They are designed to handle arcs that occur as the breaker

opens. The contacts associated with any one phase of a breaker are often referred

to as poles.

Fig.3.66 shows the position of the movable main and arc contacts as a

breaker trips. The main contacts open first. No arc occurs, because the primary

power circuit is still complete through the arcing contacts. They are thus

controlled by confirming its occurrence to the gap between the movable arcing

contacts and the stationary arcing contact. The arcing contacts are more rugged

and are made to withstand the heat of the arc. As the movable arc contacts pulls

away from the stationery contacts, the arc forms. At this point, the arc can be

extinguished.

Formation of Arc:

Circuit breakers operate by putting a set of contacts apart. As the contacts

separate, a gap forms between them. The current flowing through the circuit tries

Page 71: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

99

to maintain the circuit by jumping the gap between the contacts. This results in an

arc, as shown in Fig. 3.67

Figure 3.66: Formation of Arcs

At normal room temperature, air is a very poor conductor of electricity. However,

when air becomes hot enough, it becomes a very good conductor. If the arc is not

extinguished, it will eventually vaporize the contacts and other circuit components

in its path. Even an arc that lasts only a fraction of a second may be able to cause

significant circuit and plant damage.

Factors in Extinguishing Arcs:

To extinguish arcs, breakers utilize three physical factors: Speed, distance

and cooling. In terms of speed, the rate at which the movable arc contacts separate

from the stationery arc contacts has a direct bearing on weather an arc is

extinguished. The faster the arc formation, because the air has less time to get hot

enough to maintain current flow between the contacts.

As the distance increases when the movable arc contacts separate from the

stationary contacts, an arc stretches, or elongates. Fig 3.68 is a simplified drawing

of an arc forming between a breaker’s movable and stationery arc contacts that

are closed together. Fig. 7.8 B shows the same attempt to sustain current flow

between the two contacts. Elongating the arc increases the chance of

extinguishing it, because the greater the distance an arc must travel, the greater

the voltage needed to sustain it.

Page 72: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

100

Figure 3.67: Effect of Distance on an arc.

Arc Chutes: In circuit breakers, arc chutes are installed above the movable and

stationery arc contacts. The arc chutes provide a good conducting material to

direct the path of the arc. The arc chutes are surrounded by a material that

insulates the fins from one another. An arc is electrical current: so, as in any

current-carrying conductor, a magnetic field is produced around an arc as it forms.

The magnetic field will induce a voltage in conductors such as de-ion plate. This

induced voltage is opposite to the voltage that is forcing the arc to jump the gap

between the movable and stationary arc contacts. The voltage that is induced in a

single de-ion plate is not sufficient to overcome the arc’s voltage. The sum of the

induced chutes voltages opposes enough of the arc’s voltage to reduce current

flow as the arc passes through the rack of de-ion plates.

Figure 3.68: Arc Cuts

Page 73: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

101

Since cool air is a good insular, mixing cool air with the heated air that occurs

when an arc forms will help cool and extinguish the arc. Cooler air is directed at

the arc’s path when an arc is confined in arc chute. An arc chute is a device that is

similar in operation to a simple chimney. The chute confines and directs the arc

and the air that surrounds it. Hot air rises within the chute, and cooler air is drawn

in at the base of the chute and directed t the arc. The cooler air will help cool and

extinguish the arc.

Type of Mechanism:

Breaker can be operated manually or electrically. In manually operated

breaker the closing is made independent of the force offered by the operator by

means of closing spring. An operator has to go to the breaker for nONn operation.

In electrically operated breaker the charging of the spring is by a motor.

The spring stores energy for closing and a closing command enables the breaker

to switch nONn. Spring charging motors are available to suit different control

voltages.

Figure 3.69: Different Breaker Mechanisms

1. MF

- Manually operated Fixed type

ACB

Manually Operated

Electrically Operated

Fixed Fixed

Drawout Drawout

Page 74: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

102

2. MDO

- Manually operated Draw out type

3. EF

- Electrically operated fixed type

4. EDO

- Electrically operated Draw out type

Accessories:

1. Shunt release:

The latching mechanism shown in Fig. 3.70 is operated electrically by means of

device called a shunt trip. In this example, the shunt trip consists of a coil and a

movable metal plunger. Wires connect the coil to a separate control source. Often,

this control is actuated from a remote location.

Figure 3.70: Shunt Release of Breaker

Figure 3.71: Remote Control of Breaker

Page 75: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

103

In Fig. 3.72, the breaker contacts are closed. In Fig. 3.72 the control circuit has

been activated. When the coil is energized, the shunt trip is activated. Magnetic

attraction draws the plunger up and extends the rod that moves the latch

mechanism tripping the breaker.

2. Under voltage release:

This release could be instantaneous or fixed time delay with different voltages,

Releases with time delay are used where transient voltage fluctuations are more.

Under voltage coils are continuously rated.

3. Earth fault releases:

These releases are generally required for giving E.F. protection. It will be

necessary to specify the percentage of earth fault setting and also to specify a 3

phase 3 wire systems or a 3 phase 4 wire systems.

4. Micro switches:

These can be incorporated in the ACB for given various trip and position in

dictations, indicating circuit load should not exceed the rated current value and

burden of the micro switches.

5. Auxiliary contacts:

Number of auxiliary contacts and rating are important from the point of view of

the maximum load and number of control contacts that can be wired through a set

of contacts.

6. Safety shutters:

These are required only in case of draw-out breakers. These shutters provide

protection against accidental contacts with the power circuit where the breaker is

isolated.

Indications:

If the breaker is made to communicate its status through certain

indications the pressure on the maintenance personnel can be eased. It will be

necessary to look into what indications the breaker can offer like:

1. ON / OFF

2. TRIP INDICATION

- OVER LOAD TRIP

Page 76: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

104

- SHORT CIRCUIT TRIP

- UNDER VOLTAGE TRIP

- SHUNT TRIP

- EARTH FAULT TRIP

3. POSITION INDICATIONS

- SERVICE

- TEST

- ISOLATED

4. SPRING CHARGED / DISCHARGED

Locks and interlocks:

Consideration must be given to see the type of lock and interlocks that can

be provided.

Locks –

• Lockable trip push button.

• Service / Test / Isolated position.

Interlocks –

• Door interlock

• Between 2 or 3 circuit breakers.

Overload protection:

Figure 3.72: Overload Protection Latching Mechanism

If a circuit problem occurs so that current flow exceeds a pre determined value,

the bimetallic strip heats and bends. The direction of bending and the amount of

Page 77: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

105

the bend are determined by the construction of the bimetallic strip. As the strip

bends, the latching mechanism is tripped and the contacts open.

Figure 3.73: Overload Protection

Short circuit protection:

Fig. 3.75 illustrates typical electro magnetic trip device connected to a

breaker. The trip device consists of a coil, connected to secondary side of the CTs,

and a movable metal core. The core is inside the coil. The core is held in place by

the spring, which acts a restraining mechanism. The latching mechanism consists

of two parts, an insulated latch and a metal trip bar.

Figure 3.74: Electromagnetic Trip Device

If an excessive amount of current flows through the circuit, the magnetic field

intensifies. The increased magnetic attraction draws the core into the coil,

overcoming the resistance of the spring. The metal trip bar is attached to the core

and it moves, forcing the latch to move, as shown in Fig. 3.75. This action trips

the breaker.

Page 78: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

106

Figure 3.75: Short Circuit Protection

Selection of ACB:

1. Current rating

Current Rating is decided based on application

1) For source Protection [transformer & D.G. Set]

Transformer Rating in KVA

KVA x 1000

I Full Load = ---------------------

3 x VL

Most Transformers normally can be overloaded for 10% of its capacity.

2) For load Protection [P.C.C. feeder MCC feeder & loads]. Full load current

& its overloading capacity.

The nominal rating of ACB should be equal to more than source rating or

continuous current of load. Rating specified by the manufacturer as per IS are at

400C. Correction factors may have to be applied for higher ambient.

Considering above two factors the rating of ACB (A) is greater than or equal to

1.1 x I Full Load.

2. Rated Ultimate Short-Circuit Breaking Capacity: (Icu)

It is the value of ultimate short-circuits breaking capacity assigned to that

circuit Breaker by the manufacturer for the corresponding rated operational

voltage under specified condition. The prescribed condition according to the

specified test sequence does not include the capability of the circuit breaking to

carry its rated current continuously. It is expressed as the value of the prospective

breaking current in kA (RMS).

Page 79: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

107

Rated service breaking capacity: (Ics)

It is the value of service short circuit breaker by the manufacturer for the

corresponding rated operational voltage under prescribed condition according to

the specified test sequence include the capacity of the circuit breaker to carry its

rated current continuously. It is expressed as the value of prospective breaking

current in kA (RMS), corresponding to one of the specified percentage of the

rated ultimate short circuit breaking capacity. Ics & Icu.rating should be greater

than or equal to IF Fault current calculated as per fault level calculation.

3. Making capacity:

Important condition arises when the ACB is closed on fault. When the

breaker is closed on such a fault the current rises from zero to fault level i.e. a

switching source takes place, putting the ACB to a more severe duty.

Making capacity depends on:

• Power factor

• Instant of switching

The multiplying factor ‘n’ for finding the making capacity can be found from the

following table 3.13

Breaking Capacity Std.P.F. Min. Making Capacity

I cn (Amps) CosØ (n x 1cn)

Icn < 1500

1500 < Icn < 3000

3000 < Icn < 4500

4500 < Icn < 6000

6000 < Icn < 104

104 < Icn < 2 x 104

2 x 104 < Icn < 5 x 104

5 x 104 < Icn

0.95

0.90

0.80

0.70

0.50

0.30

0.25

0.20

1.41

1.42

1.47

1.53

1.70

2.00

2.10

2.20

Table 3.14: Making Capacity

Page 80: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

108

4. Type of protective teleases:

Depends on type of releases

1. Thermo-magnetic 2. Solid state

3. Microprocessor based 4. Numeric

In order to get more accurate protection and wider range of setting, the

Electronic releases were developed. These releases are capable of offering not

only, overload, short circuit protection but also earth fault protection without any

other coil or accessories. Like electromechanical release, they can also be

designed to give direct mechanical trip command to circuit breaker for cleaning

the fault. Besides,

They can give all protection with wider range of pick up setting and adjustable I-T

curve, i.e. with time delay. To protect the system against repeated overload fault,

release can have thermal memory also due to which breaker trips faster on such

faults.

For short circuit protection, these releases offer wider range of pick up

setting and also selectable variable time delay in milliseconds. Hence only one

variety of release is required in irrespective of location of breaker in the system

close or away from transformer and thus reduction in inventory carrying cost.

For earth fault protection also release offers wider range of pick up setting

and selectable variable time delay in milliseconds. Due to provision of time delay

system can be discriminated (time base discrimination)easily, and nuisance

tripping due to system disturbance can be avoided.

In order to understand on which fault circuit breaker has tripped

annunciator module is used. For achieving intelligent protection & co-ordination,

micro-processor is used in the release. The advantages of microprocessor are

more – accurate protection, fine range of settings, flags for displaying the type of

fault, communication between two releases and self diagnostic of circuitry.

These releases also offer overload and short circuit protection with time delay,

instantaneous and earth fault protection. The salient features of various

protections with microprocessor-based releases are:

Page 81: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

109

• The overload protection with fine range of pick up setting and to

protect the system against repeated overload faults, release has

selectable thermal memory i.e., this memory can be blocked also when

not required.

• The short circuit protection is also with fine range of pick up setting

and also wide adjustable time delay in milliseconds. This type of

release can give blocking signal to upstream release of same make,

thus helps in achieving better time base co-ordination between circuit

breakers.

• An additional, instantaneous protection (short circuit) with wider range

of pick up current having no intentional time delay trips circuit breaker

on very high magnitude fault.

• The earth fault protection with fine range of pick up setting and also

adjustable time delay in milliseconds. Due to provision of time delay

and communication, it helps in achieving better time base co-

ordination between circuit breaker.

In modern protection system the expectations form protection release is not only

to protect system against various faults but also to record the fault data,

measurement of various parameters, control of circuit breakers and computer

communication. The numerical (digital) release performs above mentioned

activities by using micro-processor along with memory for data storage. The basic

advantage of digital technology is inputs are converted in to digital values, then

compared with set values (which are digital) and finally appropriate digital output

signals are produced. This release offers following protections:

• Overload protection (as low set) with all features of microprocessor

based release.

• Short circuit protection (as High set) with additional facility of

Automatic Doubling of High set value during switching on the feeder

circuit breaker to avoid nuisance tripping of circuit breaker. These can

also give blocking signal to upstream any make numerical (digital)

Page 82: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

110

release, thus help in achieving better time base co-ordination between

circuit breaker.

• Earth fault protection with all features of microprocessor based release

and with additional features like third harmonics filter to avoid

unwanted tripping of circuit breaker. Due to provision of time delay

and blocking function, it helps in achieving better time base co-

ordination between circuit breakers.

The setting of these releases is done by push buttons, which are on front panel of

the release. In addition to protection, the release display current value of all three

phases continuously in scrolling mode and the starting current of the feeder. It

also records on which fault circuit breaker has tripped, magnitude of fault current,

faulty phase and how many times faults has occurred in past. They have the

capability of communication with personnel computer or laptop through a RS 485

to RS 232 converter. These facilities to view all trip data on personnel computer,

one can do programming or setting from control room and the circuit breaker

control through personnel computer.

5. Rated Short time withstand Current (Icw):

It is the value of the current that the circuit breaker can carry for short

period (1 sec or 3 sec.) without damaging Circuit Breaker, under short circuit fault

condition.

6. Type of mechanism MF, MDO, EF, and EDO

7. Accessories

8. Indications

9. Locks and Interlocks

10. Ease of maintenance

11. Available of spares

Page 83: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

111

Figure 3.76: ACB Layout

Typical layout of system (fig) Fig. shows typical layout of system. In this system

there are three breakers in series (A, B, C) when overload fault of 3200A occurs

at location F1, only Circuit breaker C trips. The CBs A, B, & C are coordinated

for overload protection because (current rating of A>B>C.)

Figure 3.77: CB Layout

When short circuit torque of 15 KA occurs at location F1. It is expected that C

circuit breaker should trip. But all three CBs trips. Thus the continuity of supply

to healthy feeders is affected; hence to overcome this situation two methods are

available.

• Documents base discrimination

• Time based discrimination

1) Current based discrimination:

For achieving current base discrimination short circuit pick up setting of

protection release of immediate upstream ACB should be greater than fault level

at the location of downstream ACB i.e. [circuit breaker A’s short circuit setting,

greater than circuit breaker B greater than circuit breaker C]

Page 84: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

112

Figure 3.78: Current Based Discrimination

2) Time based discrimination:

For achieving time base discrimination short circuit setting of protection

release of all Circuit Breaker may be lesser than or equal to the fault current at

given location.

The minimum impulsion time (MIT) of protect ion release of immediate

upstream ACB should be greater than total operation time of downstream ACB.

e.g. if CBC’s MIT is 25ms & its total operation time is 90 ms than Circuit Breaker

B’s MIT should be greater than 90ms.

3.9 MCCB AND MCB:

Moulded case circuit breaker is a totally insulated air circuit breaker. It

can be used in distribution scheme in place of ACB. It can also replace a fuse

switch unit in a motor feeder.

(a) Protections in MCCB:

1. Overload protection

2. Short Circuit protection

Overload protection is given by bimetal strips Short Circuit protection is achieved

by magnetic actuation.

(b) Accessories for MCCB:

1. Under voltage release

2. Shunt release

3. Auxiliary contact block

4. Rotary operating handle

5. Remote operator

Page 85: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

113

6. Earth fault relay

There are two types of MCCBs

1. Conventional MCCB

2. Current Limiting MCCB

1. Conventional MCCB :

In event of short circuit, the conventional MDDB, the fault is cleared in

about 15-20 msec. During this half cycle the entire system would under go

tremendous stress, at times resulting in damage to the downstream equipment.

2. Current Limiting MCCB :

Figure 3.79: Current Limiting MCCB

As per IS 13947/IEC 60947 (Part2): 1993 current limiting breaker should have

break time short enough to prevent the short circuit current reaching its

prospective peak value. To meet this requirement, the current limiting MCCB

must respond quickly in case of fault. To achieve high speed contact separation,

closely spaced contact fingers carrying current in opposite direction create a

strong magnetic repulsion between the conductors. High speed contact separation

is actually produced by electromagnetic repulsion forces generated by the fault

current itself. The higher the current, the greater is the force pushing the contact

apart. Although rapid contact opening is important, just opening the contact

quickly is not enough. The next concern is to control the arc voltage across the

contacts to ensure proper arc extinction. This is accomplished by forcing the arc

Upper Contact

Repulsive Force

Incoming Terminal Outgoing Terminal

Lower Contact

Page 86: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

114

into the chute and is cooled and broken into segments in the arc chute until it is

de-ionized and ceases to conduct current, thus being extinguished

MCCB for motor protection:

Figure 3.80: Fuse and MCCB as SCPD

Fuse as SCPD:

Fuses are traditionally used as SCPDs because of the low initial capital

cost and there capability to interrupt faults faster. Fuses have excellent current

limiting characteristics and can be applied on systems having high fault levels

using fuses for short circuit protection is found to be the easiest and most effective

way of achieving Type 2 co-ordination,

Comparison of fuses with MCCBs:

M M

Relay

Contractor

Fuse as

SCPD

MCCB as

SCPD

Page 87: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

115

One constraint against MCCB is the initial cost when compared to the cost

of SFU / FSU. However with MCCB as SCPD following are the factors which are

superior to fuse links.

• Ease of maintenance

• Reduced down time

• Simplicity of operation

• No recurring costs.

Current limiting MCCBs do have a number of practical advantages over fuses if

one considers these to be worth the extra cost. These advantages will have to be

weighed against the advantages offered by fuses like low initial cost, very high

breaking capacity, very low peak cut-off current and let-through energy, etc.

A fuse is better than a current limiting MCCB in providing protection

against the effects of short circuits at very high fault levels. But in most of the

cases, the short circuit currents are limited by the contactor, relay, cable and

source impedance, generally upto 30 times the rated current of the motor. In such

events, the MCCB acts faster than any other type of protective device available.

MCCB selection criteria:

In selecting MCCBs for motor protection,the following points are to be taken care

of

• The thermal rating of MCCB should be greater than or equal to the

motor full load current.

• The breaking capacity of the MCCB should be greater than or equal to

the prospective fault current at its installation point.

• The magnetic threshold of the MCCB should be selected In such a way

so as to avoid nuisance tripping during starting of the motor.

• The contactor should be able to break any current up to the magnetic

threshold of the breaker.

• The starter should be able to withstand the let-through energy of the

breaker.

• The selection of MCCB can be done on the basis of application. There

are certain applications where we need high breaking capacity medium

Page 88: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

116

breaking capacity and low breaking capacity MCCBs. In motor feeder

application we need only short circuit protection from MCCB.

• For protection sources there are MCCBs suitable for transformer

protection and stand by DG set protection. The special application like

monitoring of HRC fuses.

Following are the functions a MCB can do:

Figure 3.81: MCCB Functions

Advantage of MCB:

• It can be used by skilled/unskilled workmen.

• The overload and short circuit settings can not be tempered since they

are non adjustable.

• Mechanism of MCB is trip free.

• It can be used as a functional switch.

• MCB can be used as an isolator.

• It’s a fully enclosed unit and hence no ageing problems.

• MCB is a cost effective device.

Motor Protection Breaker:

Conventional motor feeder: Conventional Motor feeder consist of SDF &

fuse link switching isolation & short circuit protection purpose OLR for overload

protection & contactor for remote operation & no volt protection as well as

frequent ON/OFF operation though it is possible to achieve co-ordination between

the equipments it is very difficult to maintain even a small change in the current

rating may effect complete co-ordination & to be specific (type-2) co-coordinator.

Page 89: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

117

Thus the very purpose of providing “Type-2” co-ordination gets defeated cause of

simple but unavoidable reasons the using wrong letting of use cause unavailability

of correct single rating of fuse in the stock/ store or replacing relay / contractor

rating.

To achieve and maintain a temper proof ‘type-2’ co-ordination motor

protection circuit breaker is the solution. Fig. 3.83 and 3.84 shows the ‘type-2’ co-

ordination graph for conventional motor feeder and for MPCB motor feeder.

Figure 3.82: Motor Protective Breaker

Protections offered by MPCB:

• Overload protection.

• Short Circuit protection.

• Phase loss sensitivity.

• Under voltage protection – if a contractor is used with MPCB.

Page 90: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

118

Figure 3.83: MPCB and Contactor

The motor protection circuit breaker can be connected in 2 ways, as stand alone

application and in association with contactor as shown below.

Figure 3.84: Fuse and Relays Characteristic

To achieve type-2 co-ordination with MNPCB is much simpler as compare to fuse

relay combination as in case of conventional motor feeder. Fig. 7.8 shows the

type-2 characteristics for conventional motor feeder and fig. 7.9 shows

characteristics with MPCB. It is clear that in case of MPCB since both overload

and short circuit protection are offered by single unit, to achieve and maintain

type-2 co-ordination is simpler.

Page 91: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

119

Figure 3.85: Coordination Characteristic

Applications of MPCB:

• Stand alone motor protection

• DC switching

• Fuse Monitoring

A special MPCB is used for monitoring fuses in the system. The current rating of

this MPCB is very low and magnetic threshold is also set at low value of 1A or

lower. This is required to be connected as shown in fig. 3.87.

Fuse monitoring MPCB operates whenever any of the fuse in line blows as

the current in that line gets diverted thru MPCB. The auxiliary contact associated

with MPCB can be used for audio/visual alarm, thus announcing single phasing

condition. In case of healthy conditions the current passes thru fuses as it offers

least resistance path.

3.10 CURRENT TRANSFORMERS:

OBJECTIVE:

In this chapter we would learn:

Selection of current transformer for metering & protection application.

A current transformer (CT) is used to transform primary current quality in terms

of its magnitude and phase to a secondary value such that in normal condition a

secondary value is substantially proportional to the primary value for measuring

and protective application.

Page 92: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

120

Figure 3.86: Current Transformer

The advantages of using CTs are

1. Moderate size instruments are used for metering

2. Low power consumption

3. Meter & relay circuit is electrically isolated

4. Instruments & meter can be standardized so that over all saving in cost.

Depending upon the construction the CTs can be classified as:

1. Wound type ACT having a primary winding of more than one full turn wound

on core

2. Bar type ACT in which primary winding consists of a bar of adequate size &

material forming an integral part of the current transformer

3. Ring Type ACT as an opening of circular safe to accommodate primary

conductor thru it

Definitions:

1. Actual transformation ratio: The ratio of the actual primary current to the

actual secondary current.

Page 93: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

121

2. Ratio Error: The error which transformer introduces into the measurement of a

current and which arise form the fact that the actual transformation ratio.

(Kn Is – Ip)

% Ratio Error =-------------------- x 100

Ip

Kn = Rated Transformation ratio.

Ip = Actual Primary Current.

Is = Actual Secondary Current.

3. Rated Transformation Ratio: The ratio of the rated primary current to the rated

secondary current.

4. Phase displacement: The difference in phase between the primary and

secondary current vectors, the direction of the vectors being so chosen that the

angle is zero for a perfect transformer. The phase displacement is said to be

positive when the secondary current vectors leads the primary current vectors.

It is usually expressed in minutes.

5. Accuracy Class: A designation assigned to a current transformer. It states that

the error remain within specified limits.

6. Rated Burden: The burden on which accuracy requirements are based is called

as rated burden. The burden is usually expressed as the apparent power in VA

absorbed at a specific p.f. and it the rated secondary current.

7. Rated Secondary current: It is the value of the secondary current on which the

performance of the C.T. is based on secondary current can be 1 Amp. Or 5

Amp. The 1 Amp secondary current of C.T. is used for large length of

secondary cable where as 5Amp C.T. is used for shorter length of secondary

cables. CTs are broadly classified in three types

• Measuring CT

• Protection CT

• Class PS CT

Page 94: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

122

1. Measuring CT:

CT intended to supply indicating instruments, integrating meters and similar

apparatus is called measuring current transformer. Measuring CTs need to

perform very accurately but only over the normal range of load up to, say, 120%

full load current. Measuring CTs are specified in terms of:

• Ratio

• Rated VA secondary burden

• Accuracy class

Accuracy classes recognized by IEC 185 are 0.1, 0.2, 0.5, and 1, Accuracy classes

3 and 5 are available from manufacturers. For each class. The ratio and phase

angle error must be within specified limits at 5, 20, 100, and 120% of rated

Primary current.

A class 0.2 measuring CT mean that at 100 – 120 % of the rated current

the percentage ratio error will be+ 0.2% i.e. for a class 0.2 CT with a rated

secondary current the of 5A the actual secondary current would be 5A + 0.01A.

Phase displacement error is also specified in the IEC standard. For special

applications an extended current range up to 200% may be specified. Above these

ranges accuracy is considered to be unimportant since these conditions will only

occur under abnormal fault conditions. There is an advantage in the CT being

designed to saturate under fault conditions so that the connected metering

equipment will have a lower short – time thermal withstand requirement.

Accuracy

Class

+ Percentage Current Error AT % of

Rated Current

5 20 100

120

+ Phase

Displacement in

Minute At 100%

Rated Current

0.1

0.2

0.5

0.4 0.2 0.1

0.1

0.75 0.35 0.2

0.2

5

10

30

Page 95: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

123

1.0 1.5 0.75 0.5

0.5

3.0 1.5 1.0

1.0

60

Table 3.15: Accuracy Class and Rated Current

The CT is to be marked by rated output followed by the accuracy class e.g. 15 VA

class 0.5 or 15/0.5

2. Protective Current Transformers:

A current transformer intended to supply protective devices (relays, trip

coils) is called as protective current transformer.

Protection CTs, unlike measuring CTs may be required to operate at many

times full load current. Line rarity under these conditions is not of great

importance. The essential point is that saturation must be high enough to drive the

magnetizing current and the secondary current under fault conditions. Various

Terms are used in connection with protection CTs and these are described below.

1. Composite Error : The rms value of the difference (Kn is – ip) integrated over

the cycle under steady state condition gives the composite error

100 T

Composite Error = ---------- --------- (Kn Is - Ip )2 dt

Ip T

Ip = Rms value of primary Current

T = Duration of one Cycle in Sec.

Kn = Rated Transformation ratio

Is = Instantaneous secondary crrent

Ip = Instantaneous primary current

The composite error is generally expressed as a % of the rms value of the primary

current.

Page 96: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

124

2. Rated accuracy limit primary current: It is the value of the highest primary

current up to which CT will comply with the specified limits of composite

error.

3. Accuracy Class: The accuracy class shall be designed to the highest

permissible percentage Composition error at the rated accuracy limit primary

current prescribed for the accuracy class concerned followed by the letter “P”

(meaning protection). The standard accuracy class for CT shall be 5P, 10P,

15P

4. Accuracy limit factor: To designate a protective CT standard accuracy class is

allowed by accuracy limit factor.

Rated limit primary current

Accuracy limit factor = ----------------------------------------

Rated primary current

The standard accuracy limit factor shall be 5, 10, 15, 20 and 30.

Hence the protective CT designation becomes

Figure 3.87: Accuracy Limit Factor

Accuracy Class 5P 10P 15P

Current rated At Rated Ip (in %) +1 +3 +5

Phase Displacement at Rated Ip

(In Minutes)

+60 --- ---

Composite Error at Accuracy

Limit Primary Current

5 10 15

Table 3.16: Limits of Error for Standard Accuracy

30 / 5P 10P

VA Burden

Accuracy Class

Accuracy Limit Factor

Page 97: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

125

Limits of error for standard accuracy class are as shown in table 3.15.

3. Class PS CTs:

When the operation of the relays is more precisely dependent upon the

magnitude and phase relationship of voltage and current. The CTs used are called

class PS CTs. e.g. restricted earth fault and differential protection.

For such applications CT characteristics are normally specified in terms of

1. Knee point voltage

2. Exciting current at knee point voltage

3. Resistance of secondary winding.

Knee point voltage:

It is that voltage appearing at the secondary terminals of the CT, with all

other windings being open circuited, which when increased by 10%, causes the

exciting current to be increased by 50%. A typical CT magnetizing characteristics

is shown in above figure.

Figure 3.88: Knee Point Voltage

3.11.POWER CABLES:

Selection procedure of power cables:

Electricity is the most versatile form of energy. It can be easily converted

into other form and is easier when it comes to transmission. Electrical wires and

cables are the vehicle in transmission of electricity.

Cable is a general name given to an insulated conductor or group of conductors

and is extensively used in indoor and outdoor distribution systems.

Fig. 3.90 show the cut section view of the cable

Page 98: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

126

The first covering over the core (Conductor) is called insulation. Commonly used

cables in L T systems are as follows.

• PVC insulated cables

• Paper Insulated cables

• Cross linked polyethyl e n e cables (XLPE)

• Flame retardant low smoke cables (FRLS)

1) PVC INSULATED CABLES:

PVC cables consist of polyvinyl-chloride synthetic material with vinyl

chloride as a principal material. The main advantages of PVC cables are-High

dielectric & mechanical strength over a wide range of temperature Moisture,

Acids, Alkalies do not affect PVC insulated cables – cables can be bent to smaller

radius,- flame retardant cables, does not support combustion.

In PVC cables, serious damages can occur, when cables are subjected to

appreciably higher temperature, even for short period than those permissible for

continuous operation. Therefore the current rating of PVC cables are determined

not only by maximum conductor temperature admissible for continuous running,

but also by the temperature likely to be attained under conditions of excess

current, PVC cables are suitable for maximum conductor terperature up to 700C.

2) PAPER INSULATED CABLES:

The paper insulation consist of a number of layers of impregnated paper tape of

0.1 to 0.15 mm thickness. These cables are suitable for maximum conductor

temperature of 800C.

3) CROSS LINKED POLYETHYLENE CABLES (XLPE):

XLPE cables are being used extensively in power stations and in industrial plants.

These cables are ideally suited for chemical and fertilizer industries where cable

insulation is exposed to chemical corrosion or in heavy industries where severe

load fluctuations occur. The excellent bending properties permit the cable to be

used even under most difficult cable routing conditions and also is cramped.

XLPE cables permit maximum continuous conductor operating temperature

of 900C and short ckt. Temperature of 2500C. XLPE cables are having greater

short circuit withstand capacity than PVC or paper cables.

Page 99: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

127

Other advantages of XLPE cables are

• Low dielectric loss and hence saving in running cost.

• Low weight and small bending radius required so laying and

installation of cable is very easy.

• High safely against mechanical damage and vibrations.

4) FLAME RETARDANT LOW SMOKE CABLES (FRLS):

FRLS cables are specially designed for building and installations where a high

degree of safety of personnel and equipment is desired. These cables are

especially recommended for use in the hospitals, theatre, underground trains,

industrial complex, and schools etc.

FRLS cables should fulfill the following four criteria.

1) Flame retardance

- Ability to restrict flame propagation

2) Low smoke emission

- Smoke emitted should not obstruct visibility

3) Low acid gas emission

- Gases which when combined with water produce high corrosive

acids which damages plant and equipment.

4) Low toxic gas emission

- Gases less injurious to health.

FRLS cables are available with PVC and XLPE based insulation. Continuous

current ratings and short circuit ratings of these cables are corresponding to those

for PVC and XLPE insulated cables.

Types of Cables:

Type Designation:

Codes Abbreviation

A

Y

W

Aluminium conductors

PVC insulation

Steel round wire armour

Page 100: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

128

F

WW

FF

Y

AW

sm

nm

Re

Steel trip armour

Steel double round wire armour

Steel double strip armour

PVC outer sheath

Aluminium wire armour

Sector shaped conductor

Multi stranded circular conduct

Single stranded conductor

Table 3.17: Type Designation of Cables

Selection of Cable:

While selecting cable following parameters needs to be considered

1) Type of insulation: - Paper PVC, XLPE … etc.

Table 3.17 shows comparison of properties of insulating material used for low

tension cables.

2) Type of conductor: - Copper or Aluminium

Aluminium is the most common material used as the current carrying part of

power cables. Aluminium is cheap and lighter in weight in comparison with

copper, Handling of aluminium cable is more easy as compared to copper cables,

Generally in practice copper is used as a conductor in control cables.

3) Type of cable: - Armoured or unarmoured Single core or Multi core.

Type of cable to be used depends upon conditions of installation. For examples, it

there is no likely possibility of mechanical damage after laying of cable, cheaper

unarmoured cables can-be used instead armoured cables. Sometimes especially in

power stations, it would be economical to use single core cable instead of multi

core power cable on account of their low bending raddi.

Page 101: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

129

4) Continuous current carrying capacity of the conductor by considering various

derating factors:

IS 3961-1967 Part I, II, III, IV, and V gives recommended current ratings for

Paper, PVC (Heavy Duty), Rubber, Polythene and PVC (Light duty) cables

respectively.

Tables 3.17 gives current rating for 1.1 KV grade PVC cables. Above current

ratings are given based on following assumptions.

a) Maximum conductor temperature 700C

b) Ambient air temperature 400C

c) Ground temperature 300C

d) Thermal resistivity of soil 1500C cm/Watts

e) Depth of laying 750mm

f) Thermal resistivity of PVC 6500C cm/Watt

If any of the parameter is different than above, the current rating of the

cable is to be corrected by applying respective rating factor.

Sr.No. Property XLPE PAPER PVC

01.

02.

03.

04.

05.

06.

Operating Temperature 0C

Emergency Overload

Temp 0C

Short Circuit Temp 0C

Dielectric Constant

Thermal Resistivity 0C

Cm/watt

Moisture Sebsitivity

90

130

250

2.35

350

Excellent

65/80

100

160

3.4

500

Poor

70

120

160

6.8

600

Good

Page 102: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

130

07. Current carrying capacity

For 3 phase, 3 core

6.35/11kV cables in

ground

(a) 35sq. mm2 Al.

(b) 120 mm2 Al.

(c) 300mm2 Al.

120

240

385

100

205

335

105

200

330

Table 3.18: Comparison of Properties of Insulating Material

5) Voltage rating and permissible maximum voltage drop across the cable:

Cables are graded into various groups such as LT, HT, EHT cable. Select

the cable matching to required voltage level.

It is a good practice to design the cable from Transformer LT to main

distribution board in actual practiced voltage drop of 2 to 3%, keeping in mind

that another 2 to 3%, drop will occur from main distribution board to terminal

point.

In case of direct LT connection from electricity board, total voltage drop

should be limited to 3%.

Table 3.11 shows voltage drop in volts / km / Amp with respect to cross

sectional area of conductor.

6) Overload protection of cables:

Cables insulated with some thermoplastic material like PVC may sustain serious

damage when subjected, even for relatively short periods, to temperature which

are appreciably higher than those permissible for continuous operation.

Therefore current rating of PVC cables are determined not only by the

maximum conductor temperature admissible for continuous operation, but also by

the temperature likely to be attained under condition of excess current.

Page 103: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

131

PVC insulated cables can safely withstand overload current 1.45 times its

continuous rating for the period of 4 hours.

ex motor rating = 75 H.P

Full load current of motor (ib) = 100 amp

Overload relay setting (In) = 100 amp

Minimum operating current of relay (12) = 100 x 1.2 = 120

Cable current rating (Iz) amps = 100 amps

As per IEE regulations 1.45 Iz > 12 i.r. 1.45 x 100 > 120

7) Short circuit rating of the conductor:

The cable selected shall be able to withstand the short circuit current till the time

protective devices like fuses, ACB’s MCCBs clear the fault. This time can be

maximum 1 sec. Table 12 gives permissible maximum short circuit ratings for

PVC cables. These values are based on full load conductor temperature prior to

short ckg. Is 700C.

For any other duration of short circuit the values given in table for 1 sec

should be divided by Vt, where t is the duration of short circuit. E.g. For 150

sq.mm Aluminium conductor PVC cable short circuit. Rating for 1 sec is 10.7 KA

So for 2 sec. it is 10.7 / 2 = 7.56 KA.

3.12. EQUIPMENT EARTHING:

Selection of cross sectional area of protective conductor

Selection of ELCBs

EQUIPMENT EARTHING:

In order to ensure safety in electrical installations it is essential that all

metal casings containing conductors (ex. Conduits, the frames of the Motors

and other applications) must be connected to general mass of earth. This is

known is equipment earthing or Grounding. To understand the utility of

earthing consider a non earthed Water Heater.

If fault develops causing contact between the conductor and the body, the

body becomes live with respect to earth by acquiring a potential equal to that

of the phase wire.

Page 104: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

132

When a person touches the body of the applications, the fault current flows

through the persons body to earth. In this condition person gets shock.

Figure 3.89: Effect of Unearthed Equipment

If body is well earthed, its potential cannot rise appreciably and immediately upon

occurrence of a severe type of fault, a large current flows to the earth and earth

fault relay operates to isolate the faulty circuit.

In this case even if person touches the faulty enclosure, he does not get severe

shock, because majority of current flows through earth wire as well as persons

body resistance is considerably high as compared to resistance of earth

connection.

Figure 3.90: Current Flow for Properly Earthed Equipment.

Page 105: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

133

Many portable electric tool such as drilling m.c. grinding m/c. … etc. also

have to be grounded.

Tools that have metal casings should be equipped with three pin plugs. Tge

third pin connects the casing to a earthing point. If an electrical tool is double

insulated, it does not have to have ground connection.

Use of battery operated portable tools is a very safe and convent practice.

Calculation for cross sectional area of protective conductors:-

Definitions:-

1. Exposed conductive part: A conductive part of electrical equipment which

can be touched and which is not normally live but which may become live

under fault conditions.

2. Protective Conductor (PE): A conductor required by some measures for

protection against electric shock for electrically connecting any of the

following parts:

- Exposed conductive parts:

- Extraneous conductive parts:

- Main earthing terminal:

- Earth electrode:

- Earthed point of the source or artificial neutral.

3. Earth Fault Current: A fault current which flows through and return to

source.

4. Protection Against Direct Contact: Prevention of dangerous contact of

person with live parts.

5. Protection Against Indirect Contact: Prevention of dangerous contact of

person with exposed conductive parts.

Calculations

(With regard to thermal stresses due to current of short duration.)

The following formula may be used to calculate cross section of protective

conductors necessary to withstand the thermal stresses.

Page 106: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

134

I t

Sp = -------------

K

Where,

Sp = cross sectional area, in square mm

I = RMS value of a.c. fault current for a fault of negligible impedance which can

flow through the protective device in Amp.

t = Operating time of the disconnecting device in second

k = Factor dependent on the material of the protective conductor, the insulation

and other parts and the initial and the final temperature.

Selection of K value

Initial Temp. – 300C

Final Temperature - 2500C

Material of insulation – Bare conductor (busbars)

Material of conductor

Copper

K

176

Aluminium

Steel

110

64

Table 3.19: K Factor for Materials

Earth Leakage Circuit Breakers:

In our day to day life all of us would have come across the following events -

Housewives complaining about a shock while switching on the kitchen mixie of

washing machine.

- Carpenter while working with drilling machine gets a shock.

- Children getting shock while opening the bathroom taps.

All the above “ill effects” are mainly due to ground faults or current leaking to

earth through human body.

Page 107: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

135

“ill effects” means beginning with an unpleasant sensation, it could end with

fatality .

Limiting Value Of Leakage Current On Human Body:-

On the basis of experiments carried out in India, it was decided that 30mA (peak)

should be the limit for leakage current. This is used on what is called as

unpleasant sensation.

Use of earth-leakage circuit breakers (ELCB) are an extremely effective way of

protecting human life and property. Leakage current of 300mA and above cause

insulation failure leading to electrical sparks which can spread major fires. Such

leakage can be quickly detected by ELCB and human life and property can be

saved.

Old and substandard wiring also lead to leakages. ELCB detects such leakage

currents and help us to rectify the fault and thus save the installation.

To ensure safety of life and property and minimize to the maximize possible

extent the wastage of power Indian Electricity Rules made it mandatory to use the

ELCBs.

I

Figure 3.91 – IE Rule about ELCBs

ELCB working Principle:-

Figure 3.94 shows the circuit of ELCB under normal condition. The current

flowing in the two wire is equal in magnitude and opposite in direction.

IE Rules - 1956 61-A Earth Leakage Protective Device:- The supply of energy to every electrical installation other than low voltage installation below 5KW shall be controlled by an earth leakage protective device so as to disconnect the supply instantly on occurrence of earth fault or earth leakage of current.

Page 108: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

136

i.e. Ires = I1 + I2 = 0

Since the magnitude of fluxes will cancel each other, no voltage will be induced

on the secondary side of the Toroid.

Current flowing through toroid in healthy circuit

Ires = I1 + I2 = 0

Current flowing through toroid in circuit with earth fault 13

Ires = I3 + I1 = 12

Figure 3.92: ELCB Working Principal

However if an earth leakage fault is produced in the circuit, there will be

difference between the current flowing in the two lines and this differential will

produce in output in the secondary side of the toroid proportional to the

differential current.

i.e. Ires = I3 = I1 - 12

This output will cause the ELCB to trip. The tripping device will operate and

interrupt the circuit if the leakage current in the circuit/apparatus exceeds its and

rated sensitivity. It is most important that the line and neutral conductors are

passed through the ELCB A common cause of nuisance operation is the failure to

connect the neutral through the device.

Page 109: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

137

ELCBs work just as well on three phase and neutral circuits, but when the

neutral is distributed it must pass through it. ELCB are also called as Residual

Current Circuit Breaker (RCCB)

RCCBs are not suitable for use on DC systems and unearthed networks.

RCCBs For domestic installation:

RCCBs can be installed in two ways

• Whole house protection.

• Selective house protection.

Whole house protection is provided typically by a distribution board where the

RCCB device serves as the main switch. Although very popular this suffers from

a disadvantage of all circuits are disconnected in the event of fault.

Selective protection can be provided by associating the RCCB with

identified high risk circuits.

The 30 mA sensitivity RCCB when installed protects a human being to the widest

extent. This RCCB trips in less than 30 ms. The risk associated with indirect as

well as direct contact with live parts is totally eliminated.

RCCB Selection:

Following parameters are generally to be considered for selection of right type of

RCCB

1) Sensitivity of Current

Sensitivity Application

30 mA

100 mA

300 mA

For protection against direct contact

For protection against indirect contact

For less sensitive protection suitable for large

installations having high level of leakage current.

Protection against electrical fire.

Table 3.20: RCCB Sensitivity and Applications

Page 110: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

138

2) Current rating

Select the current rating of ELCB based on load current as 10, 16, 25, 32, 40, 63,

or 100 Amp.

3) No of Poles:

2 Poles – For Single phase circuits

4 Poles – For three phase circuits

In both the cases it may prove fatal unless proper precautions are taken. Proper

earthing is not the only answer.

3.13 INGRESS PROTECTION:

Selection of enclosure for electrical equipment

Ingress Protection

Right selection of enclosure for electrical equipment is essential because an

enclosure with inadequate protection shall result in

1. Reduction in the life of the equipment

2. Dangerous to human life.

The Ingress Protection (IP) for all low voltage enclosure up to 1000 V a.c. and

1500 V d.c. is defined in the identical fashion by the standards BSEN 60529 –

IEC 529 it comprises the letters IP followed by two character numerals:

The first character numerals:

Indicates the degree of protection provide by the enclosure with respect to

persons, also to the equipment inside the enclosure.

The second character numerals:

Indicates the degree of protection provide by the enclosure with respect

with respect to harmful ingress of water; a third character may be used to indicate

mechanical strength.

The First Character Numeral

Protection against Solid Substance

Page 111: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

139

IP Test Short Description Definition

0 Non Protection No Special Protection

1

Protection against solid

objects greater than

50mm shall not be able

to touch the live parts

inside the enclosure

A large surface of the

body, such as a hand

(but no protection

against deliberate

access) solid object

exceeding 50 mm in

diameter

2

Protection against solid

objects greater than 12.5

mm shall not be able to

touch live parts

Fingers or similar

objects not exceeding

80 mm in length;

solid objects greater

than 12.5 mm

3

Protection against solid

objects greater than 2.5

mm shall not be able to

touch

Tools, wire, etc….

Of diameter of

thickness greater than

2.5mm. solid objects

exceeding 2.5 mm in

a diameter

4

Protection against solid

objects greater than 1.0

mm shall not be able to

touch

Wires or strip of

thickness greater than

1.0 mm; solid objects

exceeding than 1.00

in a diameter

Page 112: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

140

5

Dust-Protected

Ingress of dust is not

totally prevented but

dust does not enter in

sufficient quantity to

interface with

satisfactory operation

of the equipment

The First Character Numeral

Protection Against solid Substance

IP Test Short

Description

Definition

0 Non Protected No Special Protection

6

Dust - tight No ingress of Dust

The Second Character Numeral

Protection Against Liquid Substance

IP Test Short

Description

Definition

0 Non Protected No Special Protection

Page 113: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

141

1

Protected

against

dripping water

Dripping water

(vertically falling

drops) shall have no

harmful effect.

2

Protect against

dripping water

when titled up

Vertically dripping

water shall have no

harmful effect When

the 150C enclosure is

titled at any angle up

to 150 from its normal

position.

3

Protect against

spraying water

Water falling as spray

at an angle up to 600

from the vertical shall

have no harmful

effect

4

Protected

against

splashing water

Water splashed

against the enclosure

from any direction

shall have no harmful

effect.

Page 114: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

142

5

Projected

against water

jets

Water protected by a

nozzle against the

enclosure from any

direction shall have

no harmful effect

The Second Character Numeral

Protection Against Liquid Substance

IP Test Short

Description

Definition

0 Non Protected No Special

Protection

6

Protected

against heavy

seas

Water from heavy

seas or water

projected in powerful

jets shall not enter the

enclosure in the

harmful quantities.

7

Protect against

the effect of

immersion

Ingress of water in a

harmful quantity shall

not be possible when

the enclosure is

immersed in water

under defined

condition of pressure

and time.

Page 115: COMPONENTS USED IN CONTROL PANELshodhganga.inflibnet.ac.in/bitstream/10603/85563/11/11_chapter 3.pdf · • The density of Aluminium is 2.95 gm/cm 3 compared to 9.7 gm/ cm 3 of copper

143

8

Protected

against

submersion

The equipment is

suitable for

continuous

submersion in water

under conditions

which shall be

specified by the

manufacturer.

Table 3.21: Ingress Protection