comparing a low-volume piezometer to traditional wells in

40
University of South Florida Scholar Commons Graduate eses and Dissertations Graduate School 4-2-2008 Comparing a Low-Volume Piezometer to Traditional Wells in Evaluating Hydraulic Lag Caused by Low-Permeability Sediments John M. Spencer University of South Florida Follow this and additional works at: hps://scholarcommons.usf.edu/etd Part of the American Studies Commons is esis is brought to you for free and open access by the Graduate School at Scholar Commons. It has been accepted for inclusion in Graduate eses and Dissertations by an authorized administrator of Scholar Commons. For more information, please contact [email protected]. Scholar Commons Citation Spencer, John M., "Comparing a Low-Volume Piezometer to Traditional Wells in Evaluating Hydraulic Lag Caused by Low- Permeability Sediments" (2008). Graduate eses and Dissertations. hps://scholarcommons.usf.edu/etd/508

Upload: others

Post on 08-Dec-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Comparing a Low-Volume Piezometer to Traditional Wells in

University of South FloridaScholar Commons

Graduate Theses and Dissertations Graduate School

4-2-2008

Comparing a Low-Volume Piezometer toTraditional Wells in Evaluating Hydraulic LagCaused by Low-Permeability SedimentsJohn M. SpencerUniversity of South Florida

Follow this and additional works at: https://scholarcommons.usf.edu/etd

Part of the American Studies Commons

This Thesis is brought to you for free and open access by the Graduate School at Scholar Commons. It has been accepted for inclusion in GraduateTheses and Dissertations by an authorized administrator of Scholar Commons. For more information, please contact [email protected].

Scholar Commons CitationSpencer, John M., "Comparing a Low-Volume Piezometer to Traditional Wells in Evaluating Hydraulic Lag Caused by Low-Permeability Sediments" (2008). Graduate Theses and Dissertations.https://scholarcommons.usf.edu/etd/508

Page 2: Comparing a Low-Volume Piezometer to Traditional Wells in

Comparing a Low-Volume Piezometer to Traditional Wells

in Evaluating Hydraulic Lag Caused by Low-Permeability Sediments

by

John M. Spencer

A thesis submitted in partial fulfillment of the requirements for the degree of

Master of Science Department of Geology

College of Arts and Sciences University of South Florida

Major Professor: Mark Stewart, Ph.D. Charles Connor, Ph.D.

Mark Rains, Ph.D.

Date of Approval: April 2, 2008

Keywords: Time-Lag, Diaphragm, Clay, Pore Pressure, Response

© Copyright 2007, John M. Spencer

Page 3: Comparing a Low-Volume Piezometer to Traditional Wells in

i

Table of Contents

List of Tables ii

List of Figures iii

Abstract iv

Chapter One - Introduction 1

Description of Field Site 6

Statement of Problem 7

Chapter Two - Methods 9

Plotting and Statistics 17

Chapter Three - Results 18

Discussion 26

Conclusion 30

References 32

Page 4: Comparing a Low-Volume Piezometer to Traditional Wells in

ii

List of Tables

Table 1 Table of Estimated Time Lags for Various Soil Types (Hvorslev 1951) 5

Page 5: Comparing a Low-Volume Piezometer to Traditional Wells in

iii

List of Figures

Figure 1 A Cross-Section of a Traditionally-Constructed Observation Well 3

Figure 2 Well Nest Locations at Ft. Meade CSA 10

Figure 3 An Example of a Manometer (Moore and Gobdwin 1941) 11

Figure 4a First Low-Volume Piezometer Design 13

Figure 4b Second Low-Volume Piezometer Design 13

Figure 5a Hydrographs of Traditionally-Constructed Wells in the CSA 19

Figure 5b Hydrographs of the Surficial Aquifer Surrounding the CSA 20

Figure 6 Initial Insertion of the Original Low-Volume Piezometer Design 22

Figure 7 Locations of Low-Volume Piezometer Head Measurements 23

Figure 8 Selected Recorded Measurements Using the Second

Low-Volume Piezometer Design 24

Figure 9 Hydrographs of Low-Volume Piezometer and Traditionally-Constructed

Wells within the saturated clay layer. 25

Figure 10 Scatter plot of the Low-Volume Piezometer and

Traditionally-Constructed Well 1W8. 27

Figure 11 Scatter plot of the Low-Volume Piezometer and

Traditionally-Constructed Well 1N15. 28

Page 6: Comparing a Low-Volume Piezometer to Traditional Wells in

iv

Comparing a Low-Volume Piezometer to Traditional Wells in Evaluating Hydraulic Lag Caused by Low-Permeability Sediments

John Spencer

ABSTRACT

Traditionally-constructed wells are commonly used to measure hydraulic head in

all saturated systems, even in fine-grained sediments. Previous studies (Hvorslev 1951,

Penman 1961) have shown that time lag in response to head changes between traditional

wells and the surrounding fine-grained sediments can be a significant source of error.

Time lag is caused by the time required for water to flow into or out of the well to reflect

the appropriate change in head.

A low-volume piezometer was constructed to measure changes in hydraulic head

without requiring a change in fluid volume within the piezometer by directly measuring

pore pressure in the surrounding sediments. The low-volume piezometer used a

commercially-available pressure transducer that is hydraulically connected to the

surrounding sediment by a porous-ceramic cylinder. The device is attached to a drive

point that allows for quick insertion without creating excessive over-pressure so that

equilibrium is achieved rapidly.

The low-volume piezometer was inserted near traditionally-constructed wells in

3-4 m thick, saturated clay in west-central Florida. The low-volume piezometer was field

tested to compare measured pore pressures with observed levels in traditionally-

Page 7: Comparing a Low-Volume Piezometer to Traditional Wells in

v

constructed wells. The comparison highlights any head difference between the two

methods, and determines if there is a time lag between the two measurement methods and

its magnitude.

The low-volume piezometer was installed next to a traditionally-constructed well

and heads in both wells were monitored for three months. Results show that the low-

volume piezometer can take up to a month to reach equilibrium. Using Hvorslev’s

equations, traditionally-constructed wells have time lag of roughly 6 orders of magnitude

greater than the low-volume piezometer. If this is correct, it could take up to 83,000

years for a traditionally-constructed well to reach equilibrium.

However, when a trend analysis is performed on the hydrographs from the low-

volume piezometer and the two traditional wells, the correlation coefficients are 0.95 and

0.96. The very strong correlation suggests that the low-volume piezometer and the

traditional wells both respond similarly to changes in head. More field data need to be

collected, but it appears that contrary to theory, time lag in traditionally-constructed wells

may be negligible.

Page 8: Comparing a Low-Volume Piezometer to Traditional Wells in

1

Chapter 1 - Introduction

Low-permeability units have significant influence on the hydrology of aquifer

systems, and are common in hydrogeologic settings. However, the hydraulic function of

low permeability units is rarely examined. The leakance (K’/b’) of a confining unit is

usually calculated from aquifer stress test data, but the unstressed hydrology of the low-

permeability unit is seldom evaluated. Hydraulic head is rarely measured within fine-

grained sediments, yet it is a critical piece of information when estimating horizontal and

vertical groundwater gradients and fluxes into or out of the system. Accurate head

measurements are essential to understand the flow system within the unit of study and to

determine its effect on surrounding systems. Hydraulic head within a low-permeability

unit is one of the simplest and most useful aspects to study, however, it may be the

hardest to accurately measure.

Low-permeability units are often treated like more permeable units, in that, if they

are to be monitored for any period of time, observation wells are inserted into the unit

and the corresponding water levels are recorded. However, many studies such as suggest

that using traditional observation wells and standpipe piezometers in very low hydraulic

conductivity units causes large errors in measured heads [Hvorslev 1951, Penman 1961,

Hanschke and Baird 2001].

Hvorslev (1951) is the most frequently-referenced study focusing on the

possibility that observed water levels in traditionally-constructed wells are directly

Page 9: Comparing a Low-Volume Piezometer to Traditional Wells in

2

influenced by both the construction of the traditional well and the surrounding water-

bearing sediments. Traditional observation wells and piezometers require moving

volumes of water into or out of the well to change water levels within the well (Fig. 1.).

For this reason, a large volume of water may need to pass into or out of the well and the

surrounding well pack for water levels in the well to accurately reflect changes in

hydraulic head within the surrounding matrix. The time required for water to flow into or

out of a device until a desired degree of pressure equalization with the surrounding matrix

is attained is called the hydrostatic time-lag (Hvorslev 1951). If the permeability of the

matrix is sufficiently large, the time-lag is small and little lag effect is observed in the

piezometer. However, silts and clays with permeabilities of 10-5 to 10-8 cm/sec can

potentially cause significant time-lags in traditional observation wells and standpipe

piezometers.

Hvorslev derived several analytical solutions to approximate time-lag error with

several different types of standard piezometer construction.

For a standard, flush-bottom piezometer,

kdT

11π

= (1)

where T is basic time-lag (T), d is the diameter of the piezometer (L), and k is hydraulic

conductivity (L/T) (Hvorslev 1951).

Hvorslev (1951) also derived equations on time-lag using diaphragm piezometers

instead of standpipe piezometers. Diaphragm piezometers can measure the direct pore

pressure from surrounding sediments instead of requiring a volume of water to flow into

or out of the standpipe. The direct measurement of pore pressure to measure changes in

Page 10: Comparing a Low-Volume Piezometer to Traditional Wells in

3

Figure 1. A cross-section of a traditionally-constructed well. The water level within a traditionally-constructed observation well is directly influenced by the flux of water moving into and out of the well screen.

Page 11: Comparing a Low-Volume Piezometer to Traditional Wells in

4

head in the surrounding matrix makes a diaphragm piezometer ideal for low-permeability

situations. Diaphragm piezometers need such a small volume change to accurately

measure fluid pressure that they can even be potentially grouted into a borehole

(Mikkelsen, 2003).

Hvorslev’s (1951) standard time-lag equation for a diaphragm piezometer is,

kd

hT επ

22= (2)

where d is the diameter of the diaphragm (L), ε is the deflection of the diaphragm in the

pressure cell (L), h is head (L) and k is hydraulic conductivity (L/T) (Hvorslev 1951).

Hvorslev (1951) calculated time-lags for various soil types (Table 1). For the

estimated time-lag for a soil with a permeability of 10-6 cm/s, a piezometer with a 5.08

cm casing and a flush bottom will have an approximate time-lag of 17 days, where a

diaphragm piezometer in direct contact with the soil will have an approximate time-lag of

4 seconds.

Penman (1961) further investigated Hvorslev’s time-lag analytical solutions by

performing bench tests on several standpipe piezometers and electrical diaphragm

piezometers. The experiment consisted of a testing apparatus much like a triaxial cell

filled with London Clay with a permeability of ~10-8 cm/s. The cell was filled with clay

and the piezometer was inserted into the center. A pressure of about 0.703 kg/cm2 was

then applied to the cell and the piezometer was monitored until the measured equilibrium

was reached. The standpipe piezometer consisted of a vertical capillary tube 1mm bore

connected to a ceramic filter. The standpipe took 885 minutes to reach equilibrium, by

far the longest of the methods tested. The electric diaphragm piezometer consisted of a

Page 12: Comparing a Low-Volume Piezometer to Traditional Wells in

5

Table 1. Table of Estimated Time-lags for Various Soil Types (Hvorslev 1951). The Basic Time Lag, T column represents estimated time-lags for different head measurement methods in a soil with a coefficient of permeability of 10-6cm/s.

Page 13: Comparing a Low-Volume Piezometer to Traditional Wells in

6

vibrating wire connected to a diaphragm with a ceramic filter at the end. The diaphragm

piezometer was able detect a pressure change within 6 seconds of pressure alteration and

reached equilibrium within 10 minutes.

Most test data presented in literature written concerning time-lag error in

traditionally-constructed wells have been obtained on a bench scale with little or no field

data presented (Hvorslev 1951, Penman 1961, Hanschke and Baird 2001, Mikkelsen

2003). The objective of the current test is to conduct a field scale study of 4.5-6.0 m of

saturated clay to determine if heads can be accurately measured in a fine-grained

sediment system. Two methods of head measurement were chosen: traditionally-

constructed well nests and a newly designed low-volume piezometer. The field study also

provided data on the effect of time-lag on the traditional wells and the low-volume

piezometer.

Description of Field Site

Florida stratigraphy contains a Miocene-age, phosphate-and-clay-rich layer

(Hawthorn Formation) that acts as a semi-confining unit between a sandy, surficial

aquifer and a karstic limestone aquifer below (Miller 1986, Scott 1988). The Bone

Valley Member of the Hawthorn Formation has been mined extensively for phosphatic

ore since the beginning of the 20th century. In the mining process, the surficial sands

above the Bone Valley Member are removed by large drag lines and set aside for land

reclamation. After the surficial sands are removed, the drag lines excavate the underlying

ore matrix and send it to a screening plant where the phosphatic ore can be separated

from the sand and clay matrix. The matrix is made up of approximately 1/3 clay, 1/3

sand, and 1/3 pebble phosphate. During beneficiation, the matrix materials are put into

Page 14: Comparing a Low-Volume Piezometer to Traditional Wells in

7

suspension. The residual clay slurry after beneficiation contains 3-5% solids and is

pumped into clay settling areas (CSA) to dewater and consolidate. The overlying water

is drained off and recycled into the phosphate beneficiation process. After 3-5 years the

CSA develops a hard crust about 20 – 30 cm thick with saturated clay underneath

(Florida Institute of Phosphate Research, 2004.). CSA’s make up about 40-50% of all

reclaimed mining land in Florida.

The selected field site is a CSA located about 8 km west of Ft. Meade, Florida.

The CSA covers an area of 2.6 square kilometers and the clay slurry has a thickness of

4.5-6.0 m. The clay slurry was deposited on top of unmined surficial sand and is

contained on all four sides by a berm made of the same sand. After approximately 20

years since formation, the CSA has formed a hummocky surface with a dry crust capable

of supporting vegetative cover. The dried clay is predominantly covered by cogan grass

in the uplands and willows in the depressional wetlands.

Statement of Problem

Traditionally-constructed, 5.08 cm diameter observation wells were installed to

monitor head in the saturated clay. After months of monitoring water levels, the

traditionally-constructed clay wells appeared to possibly be disconnected from each other

and the surficial aquifer. Literature and previous studies seemed to support the idea that

the apparent disconnection between the clay wells was caused by time-lag between the

traditionally-constructed wells and the fine-grained sediment system. A low-volume

piezometer was designed to measure direct pore pressures from the fine-grained sediment

system to greatly reduce or even eliminate the possible time-lag. The heads measured by

the low-volume piezometer were compared with the heads measured in the traditionally-

Page 15: Comparing a Low-Volume Piezometer to Traditional Wells in

8

constructed observation wells to test the hypothesis that well construction, or more

specifically, well volume, can be a significant source of time-lag when measuring heads

in fine-grained sediment systems.

Page 16: Comparing a Low-Volume Piezometer to Traditional Wells in

9

Chapter Two - Methods

Traditionally-constructed observation wells were installed in the CSA itself and in

the surficial aquifer both directly beneath and surrounding the CSA. The wells installed

in the CSA were augered to 2.5 and 4.0 m below land surface at three different sites

within the CSA. Two wells at each CSA site were installed at a depth of 12.0 and 30.5 m

below land surface to monitor heads in the surficial aquifer, beneath the CSA. Nine other

wells were installed to the north, east, and west of the CSA. The nine wells surrounding

the CSA were installed at a depth of 4.0 m below land surface to monitor the surficial

aquifer around the CSA. (Fig. 2.).

Each well was constructed of 5.08 cm PVC with a 1.5 m slotted well screen. The

screen was surrounded with a 15.25 cm diameter well pack consisting of medium sand.

A drawback of traditionally-constructed wells is that the well screen is not directly in

contact with the surrounding material due to the sand pack buffer. A device that can

measure pore pressure and can be placed directly in contact with the clay pores would

provide a much more accurate measurement of hydraulic heads than traditional wells and

piezometers.

A manometer was first considered (Fig. 3.). A manometer is generally

constructed out of a hollow steel tube with a hard, porous membrane at one end, and a

clear, flexible tube to view head changes at the other. The manometer is filled with water

and driven into the soil to the determined depth. The porous membrane allows pore

Page 17: Comparing a Low-Volume Piezometer to Traditional Wells in

10

Figure 2. Well Nest Locations at Ft. Meade CSA. 1E, 1N, and 1W nests contain wells of 2.5 m, 4.0 m, 12.0 m, and 30.5 m BLS. 2E, 2N, and 2W nests contain wells of 7.75 m and 13.5 m BLS.

Page 18: Comparing a Low-Volume Piezometer to Traditional Wells in

11

Figure 3. An example of a manometer (Moore and Gobdwin 1941). Section A is the soil probe, B is the manometer consisting of flexible tubing, capillary tubing, a mercury meniscus, and a manometer bulb. Section C is the probe point consisting of a porous ceramic cell, synthetic rubber gaskets, and a hardened point.

Page 19: Comparing a Low-Volume Piezometer to Traditional Wells in

12

pressures from the soil to be transmitted through the membrane and cause the water level

to rise or fall accordingly in the manometer. The manometer doesn’t need a large volume

change of water to measure a head change in the soil, and it can be driven directly into

the ground so no borehole with a surrounding sand pack is needed. However, the

manometer is mainly designed to help identify rough vertical gradients in a shallow

groundwater system by recording the rise or fall of the water level in the viewing tube.

All of the data would need to be manually recorded, hindering long term monitoring, and

the actual pressure changes would be difficult to calculate. A manometer also is a large

and heavy piece of equipment which would make quick measurements at a field site

difficult.

Ideally, a device that has the qualities of both a diaphragm piezometer and a

manometer would be ideal for head measurements. It could be driven into the sediment

with little disturbance and could quickly reach equilibrium with the surrounding pore

pressure and give an accurate head measurement. After the needed data are collected, the

device can be quickly removed and reused, unlike current diaphragm piezometer designs.

A low-volume piezometer was designed specifically for monitoring heads within fine

sediments, using a commercially-available pressure transducer, and constructed to

function like a manometer. The low-volume piezometer is ideal for field situations,

lightweight, easily transportable, and can log measurements for as long as needed (Figs.

4a & 4b).

The original prototype (Fig. 4a) featured a hard, porous, ceramic cup threaded on

the end of the pressure transducer. The pressure transducer was fixed to 1.9 cm

Page 20: Comparing a Low-Volume Piezometer to Traditional Wells in

13

Figure 4a. First low-volume Figure 4b. Second low-volume piezometer design. piezometer design.

Page 21: Comparing a Low-Volume Piezometer to Traditional Wells in

14

galvanized pipe with a set screw. The transducer cable was run through the

galvanized pipe to the surface where it could be used for real-time monitoring or for data

download.

Two setbacks occurred with the first prototype. First, the rounded end of the

ceramic cup allowed a large over-pressurization of fluid within the low-volume

piezometer as the device was driven, making quick readings impossible. Overpressures

from driving the device created heads 2-3 m above equilibrium heads. Equilibrium

pressures were normally not reached until four to six hours after insertion. Second, the

set screw could not withstand the stress of being pushed into the sediment, and multiple

failures occurred. The set screw also required the transducer to be inserted and removed

from the galvanized pipe before and after every field use. This made an accurate

measurement of the correct length of the device time consuming because it needed to be

re-measured every time or the correct depth of the pressure measurement would not be

known.

The second design incorporates several improvements (Fig 4b). The ceramic cup

is replaced with a ceramic cylinder. A metal tube runs from the end of the pressure

transducer, through the ceramic cup, and is threaded into a drive point. The metal tube is

slotted where it meets the ceramic cylinder to allow horizontal flow between the saturated

ceramic cylinder and the pressure transducer. The pressure transducer can be directly

threaded onto the end of the galvanized steel pipe, creating a much stronger attachment

and a standard length. The drive point prevents the large over pressurization from

occurring which allows for more rapid equalization and allows the piezometer to be

driven into stiffer sediments.

Page 22: Comparing a Low-Volume Piezometer to Traditional Wells in

15

Before deployment in the field, the low-volume piezometer was initially tested on

a bench-scale water column. The ceramic cylinder was saturated and attached to the

pressure transducer before being placed into the water. The pressure transducer

measured the water level at 1 second intervals and was monitored on a computer screen.

The low-volume piezometer immediately recorded level changes as soon as the ceramic

cylinder entered the water and continued recording changes until the low-volume

piezometer reached the bottom of the water column. There was no apparent time-lags.

The low-volume piezometer was used to compare pore pressures within the clay

to the water levels in the traditionally-constructed clay wells. The low-volume

piezometer was placed at 2.5 and 4.0 m depths below land surface at the 1N, 1E, and 1W

well clusters. The piezometer was then used to measure horizontal and vertical head

gradients within the clay. The low-volume piezometer gathered point measurements at

depths of 2 m, 3 m, and 4 m bls at three locations between the 1N well cluster and the

northern berm of the CSA, as well as three locations between the 1E well clusters and the

eastern edge of the CSA. The low-volume piezometer was left in the clay on average 5

hrs to reach what was then estimated to be 90% of equilibration. It was moved after 90%

equilibration because Hvorslev (1951) found that equilibration time before and after the

90% threshold were nearly equal. The low-volume piezometer was also left to run

overnight when possible to record an accurate equilibrium. After the point measurements

were taken near the clay well clusters, the low-volume piezometer was installed near the

1N8 well for approximately 3 months to monitor seasonal changes in head within the

CSA.

Page 23: Comparing a Low-Volume Piezometer to Traditional Wells in

16

Clay samples were taken at various depths near the well clusters to calculate an

average gravimetric moisture content and hydraulic conductivity from falling-head

permeability tests. The clay samples were taken at two locations near the 1N cluster as

well as two locations near the 1E cluster. At each location two samples were gathered at

depths of 0.3 m and 1 m bls.

Falling-head permeability tests were performed on the clay samples to estimate

hydraulic conductivity (ASTM D5856-95). Each clay sample was placed into a rigid

compaction-mold permeameter and connected to a falling head hydraulic system. The

permeameter is designed to prevent swelling of the clay by using porous disks to contain

the clay. The tests were run for over 24 hours and results were collected when four

values of hydraulic conductivity were equal (Cira 2008).

Atterburg limits were obtained from clay samples along with gravimetric moisture

content measurements to determine the physical properties of the clay. If the saturated

clay is acting as a liquid then the density of the clay would have to be added when

calculating the total heads for the CSA; if the clay is acting as a plastic solid, it can be

treated like any other water-bearing sediment when determining the heads. The plastic

limit was determined using a standard rolling method, while the liquid limit was

determined by a cone penetration method (ASTM D4318-05). The bench tests were

performed on samples taken at 10 cm, 38 cm and at 1.5 m below land surface. Each

sample was tested five times and the mean of the results was used to ascertain the limits

Cira (2008).

Page 24: Comparing a Low-Volume Piezometer to Traditional Wells in

17

Plotting and Statistics

A trend analysis was utilized to quantify how closely the heads from traditionally-

constructed wells 1N15 and 1W8 correlate with the low-volume piezometer. Scatter

plots were created for the recorded heads from June 2007, until September 2007 for each

traditionally-constructed well versus the low-volume piezometer. A least-squares

regression line with a high residual sum of squares would confirm a close correlation

between the traditionally-constructed wells and the low-volume piezometer. If the wells

and the piezometer do have a close correlation, then the probability that time-lag is

affecting the traditional wells is low.

Page 25: Comparing a Low-Volume Piezometer to Traditional Wells in

18

Chapter Three - Results

The clay is a light grey color with moisture content increasing with depth. In

some areas of the CSA, a small percentage of silt or sand is present (10-30%), but

otherwise the clay is homogeneous. The surface of the clay is hard with many fractures

running through it. The hard, fractured layer begins at land surface and continues down

to about 0.3 m below land surface. From 0.3 m to 0.6 m the fractures end and the clay

becomes plastic and stiff. Below 0.6 m the lay becomes totally saturated, sticky, and

very plastic with little shear strength. Little down pressure is needed when coring

through the clay below 0.6 m.

Generally the clay has a gravimetric water content of 90% to 100% 30-38 cm

below land surface, increasing to 120% to 150% at 0.5 m to 1.5 m below land surface.

Because the clay is so homogeneous, it is assumed that the clay contains no more than a

150% gravimetric water content. Atterburg limits for the clay were 67% and 228% for

the plastic limit and the liquid limit respectively. Falling head permeability test results

indicate an average hydraulic conductivity of 10-8 cm/s, which is common for clay (Fetter

1980).

During a year of monitoring, the water levels within the traditionally-constructed

clay wells had very different water levels when compared between themselves and also

when compared with wells in the surrounding surficial aquifer wells (Figs. 5a and 5b.).

Wells in the clay open to the same depth within 4-5 meters from each other, had water

Page 26: Comparing a Low-Volume Piezometer to Traditional Wells in

19

37.00

38.00

39.00

40.00

41.00

42.00

43.00

44.00

45.00

46.00

47.00 Jun‐06

Aug

‐06

Oct‐06

Jan‐07

Mar‐07

Jun‐07

Time

Hydraulic head (NGVD 1929m)

1E8

1N8

1N15

a1N

15b

1W8

1W15

Figure 5a. Hydrographs of traditionally-constructed wells in the CSA.

Page 27: Comparing a Low-Volume Piezometer to Traditional Wells in

20

Figure 5b. Hydrographs of traditionally-constructed wells in the Surficial aquifer surrounding the CSA.

35.00

36.00

37.00

38.00

39.00

40.00

41.00

42.00

43.00

44.00

45.00 Jun‐06

Jul‐06

Sep

‐06

Oct‐06

Dec

‐06

Feb

‐07

Mar‐07

May

‐07

Tim

e

Hydraulic head (NGVD 1929 m)

1E40

1N40

1W40

3E15

3N35

3W15

Page 28: Comparing a Low-Volume Piezometer to Traditional Wells in

21

levels that consistently differed by 1.5 to 2.0 m. Water levels in the shallow wells in the

clay at a depth of 2.5 m, (1E8, 1W 8 and 1N8; Fig. 2.) rose by ~1.5 m from July ’06 to

Oct ’06 while water levels in wells in the surficial aquifer outside the CSA rose 0.5 m

during the same span of time. Water levels in the shallow wells in the clay also rose

during February and March of 2007, a period when the wells in the surficial aquifer were

at their lowest levels.

The first low-volume piezometer design was inserted into the clay near the 1N

cluster at 2.5 m below land surface. An overpressure occurred immediately after

insertion and did not reach equilibrium until 3.5 hours later (Fig.6.). The low-volume

piezometer was driven further to 4.0 m below land surface, insertion overpressures

occurred again with equilibrium reached after 10 hours.

The second piezometer design was inserted near the 1E well clusters, the 1W well

clusters, and at various points near the 1N and 1E well clusters (Fig. 7.). The drive point

for the new design was able to minimize the initial overpressure that occurred with the

first design. The head rises on a logarithmic curve until an apparent equilibration is

reached (Fig. 8.). However, equilibrium time-lags are highly variable, with the required

time for the low-volume piezometer to reach the apex of the apparent equilibrium curve

taking between 1 hr and 15 hrs, and full equilibration taking between 2 hrs and 46 hrs.

Equilibration for the long term head monitoring event appears to reach a stable

level after 27 days (Figure 9). While the pressure in the low-volume piezometer is rising

to reach equilibrium, the water levels in the traditionally-constructed wells remain steady.

After the peak in the pressure of the low-volume piezometer, all three levels in the low-

Page 29: Comparing a Low-Volume Piezometer to Traditional Wells in

22

Figure 6. Initial insertion for the original low-volume piezometer design. A large immediate overpressure was measured by the pressure transducer. The overpressure took between 3 and 15 hours to fully dissipate.

43.00

44.00

45.00

46.00

47.00

48.00

49.00

50.00

51.00

52.00

53.00 0.

001.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

10.00

Elaps

ed Tim

e (hrs)

Hydraulic head (NGVD 1929 m)

1N @

 2.5 m

1N @

 4.0m

Page 30: Comparing a Low-Volume Piezometer to Traditional Wells in

23

Figure 7. Location at the Ft. Meade CSA where the low-volume piezometer was used to measure hydraulic heads in the clay.

Page 31: Comparing a Low-Volume Piezometer to Traditional Wells in

24

Figure 8. Selected recorded measurements using the second low-volume piezometer design. Total equalization times as well as 90% equalization times varied greatly with no known cause.

0

0.2

0.4

0.6

0.81

1.2

1.4

010

2030

4050

6070

8090

100

Elap

sed

Tim

e

Hydraulic Head (m)

1E 3

.75

m 2

007-

05-2

130

m e

ast o

f 1E

@ 3

m 2

007-

05-2

2 60

m e

ast o

f 1E

@ 3

m95

m e

ast o

f 1E

@ 3

m 2

007-

05-2

51W

@ 2

.5 m

200

7-05

-27

1W @

4 m

200

7-05

-29

30 m

Nor

th o

f 1N

@ 4

m 2

001-

05-3

0 60

m n

orth

of 1

N @

4 m

200

7-05

-31

Page 32: Comparing a Low-Volume Piezometer to Traditional Wells in

25

Figure 9. Hydrographs of Low-Volume Piezometer and Traditionally-Constructed Wells within the saturated clay layer.

43

43.544

44.545

45.546

46.5 May

‐07

Jun‐07

Jul‐0

7Aug

‐07

Sep

‐07

Tim

Elevation (m NGVD)

Piezo

meter

Traditio

nal W

ell 1

N15

Traditio

nal W

ell 1

W8

Page 33: Comparing a Low-Volume Piezometer to Traditional Wells in

26

volume piezometer and traditionally-constructed wells 1W8 and 1N15 steadily decrease

in tandem until the end of the recorded period.

The results from the trend analysis show a tare during a time when the

traditionally-constructed well measured a rain event, but the low-volume piezometer did

not. A trend line was plotted for the initial arm and the final arm of each scatter plot. The

residual sum of the squares for the piezometer vs. 1W8 is 0.992 and 0.998 with a p-value

of 0.98. For the piezometer vs. 1N15, the R2 is 0.996 for the first arm and 0.99 for the

second, the p-value for the scatter plot is 0.99 (Figs 10 and 11).

Discussion

One concern in measuring the heads within the clay is that the clay contains a

very high water content (150%) and is loosely consolidated only 30-50 cm below land

surface. Atterburg limits were measured to determine if the clay unit is a plastic solid or

a viscous liquid. Atterburg limits for the clay are 67% for the plastic limit, and 228% for

the liquid limit. The estimated gravimetric water content for the clay is 150%, and is well

below the liquid limit of 228%, which means that the clay can be treated as a saturated

solid and not a viscous liquid.

The permeability of 10-8 cm/s established in the falling-head permeability test

was used with Hvorslev’s equations to determine an analytical estimation of time-lag for

the traditionally-constructed observation wells (eq. 1) and an estimated time-lag for the

low-volume piezometer (eq. 2). The estimated time-lag for a 5.08 cm standard well in

direct contact with the surrounding soil with a permeability of 10-8 cm/s is 1679 days.

The estimated time-lag for a diaphragm piezometer with a diameter of 1.9 cm and in

contact with the same soil is 2.15 min.

Page 34: Comparing a Low-Volume Piezometer to Traditional Wells in

27

Figure 10. A scatter plot of the Low-Volume Piezometer and the Traditionally-Constructed Well 1W8. The graph shows a very strong correlation between the two.

y = 1.313

2x ‐ 15.16

4R

2  = 0.992

y = 1.331

8x ‐ 16.17

4R

2  = 0.997

5

44.30

44.40

44.50

44.60

44.70

44.80

44.90

45.00

45.10 45

.30

45.40

45.50

45.60

45.70

45.80

45.90

46.00

Piezo

meter

1W8

Page 35: Comparing a Low-Volume Piezometer to Traditional Wells in

28

Figure 11. A scatter plot of the Low-Volume Piezometer and the Traditionally-Constructed Well 1N15. The graph shows a very strong correlation between the two also.

y = 1.077

6x ‐ 5.209

6R

2  = 0.995

9

y = 1.414

3x ‐ 20.74

2R

2  = 0.990

5

43.50

43.60

43.70

43.80

43.90

44.00

44.10

44.20

44.30

44.40 45

.20

45.30

45.40

45.50

45.60

45.70

45.80

45.90

46.00

Piezo

meter

1N15

Page 36: Comparing a Low-Volume Piezometer to Traditional Wells in

29

The calculated time-lag for a low-volume piezometer, as well as the results of

laboratory bench test for low-volume piezometer response times, differed greatly from

the field response times observed at the CSA. The low-volume piezometer is calculated

to have a time-lag of 2.15 min using Hvorslev’s equation and Penman observed a time-

lag of ~ 10 min for total equalization in a bench test using homogeneous clay of 10-8

cm/s.

The initial field test using the second low-volume piezometer design indicated

equilibrium times varied anywhere between 1.5 hours and 2 days. Each curve seemed to

reach some sort of equilibrium, yet the long term field test indicates that the short

equilibrium time may not be a true equilibrium. The long term test shows that it might

take up to 1 month before a piezometer that is directly measuring pore pressures can

reach equilibrium. If traditionally-constructed wells have a time-lag error of roughly 6

orders of magnitude greater than the low-volume piezometer it could take up to 83,000

years for a traditionally-constructed well to reach equilibrium. However, when a trend

analysis is performed on the hydrographs from the low-volume piezometer, traditional

wells 1N15, and 1W8, the correlation coefficients are 0.95 and 0.96, respectively. The

very strong correlation shows that the low-volume piezometer and the traditional wells

have very similar responses to changes in head in the clay.

One hypothesis to explain the fast reaction times of both the wells and the low-

volume piezometer to head changes within the wells is that the clay could be a dual flow

system. Fractures were observed in the clay up to 1 m below land surface. Flow in a

fracture system could allow the levels in the wells to respond rapidly to changes in head

Page 37: Comparing a Low-Volume Piezometer to Traditional Wells in

30

in the clay. The clay below 1 m however, is saturated and extremely plastic. Flow in

open fractures beneath 1 m seems improbable.

Another hypothesis is that the current estimation of time-lag is wrong. If the low-

volume piezometer was seated correctly into the clay, and the wells were installed

correctly, then the observed heads are true. If the field data are accurate, the error in head

measurements caused by time-lag of recorded water levels to heads within traditionally-

constructed wells in fine-grained sediments could be small.

Conclusion

Traditionally-constructed wells were installed in a fine-grained system to measure

the hydraulic heads within the system and estimate groundwater movement. After

months of monitoring, the water levels within adjacent wells appeared to be

disconnected, and a solution was sought. Analytical estimates from Hvorslev (1951)

show that hydrologic time-lag can be a significant source of error by causing head

changes in the sediments to be delayed by up to four years before being reflected in the

monitoring wells. A low-volume piezometer was designed to directly measure pore

pressures from the clay and effectively eliminate the time-lag error derived by Hvorslev.

Initially, the low-volume piezometer appeared to reach equilibrium levels

between 4 hours and 2 days. Point measurements between the low-volume piezometer

and the traditionally-constructed wells also indicated a difference in measured heads by

an average of 0.6 m. However, long term monitoring of heads by the low-volume

piezometer and a traditionally-constructed well suggest that the time required for the low-

Page 38: Comparing a Low-Volume Piezometer to Traditional Wells in

31

volume piezometer to reach equilibrium is much longer than first anticipated. Also, the

observed heads from both the low-volume piezometer and the traditionally-constructed

wells correlate so closely that they can considered almost identical. The comparison

between the low-volume piezometer and two traditionally-constructed wells point to the

possibility that time-lag in the response of traditional wells to head changes is small, even

in systems with extremely-low hydraulic conductivities.

Time-lag is a largely accepted theory in the hydrogeologic community. The

theory is often referenced in literature, especially in reference to fine-grained sediments;

however, there appears to be no conclusive field data that confirms the idea. Further

research at the present field site can quantify how head measurements in traditionally-

constructed wells are affected by fine-grained systems. Accurate field data will be the

key in deciding whether time-lag is a real source of error in traditionally-constructed

wells, or if it is not significant.

Page 39: Comparing a Low-Volume Piezometer to Traditional Wells in

32

References

Brown, Mark T., Carstenn, Susan M., Baker, John, Bukata, B.J., Gysan, Tim,

Jackson, Kristina, Chinners Reiss, Kelly, and Sloan, Mellini. Successional Development of Forested Wetlands on Reclaimed Phosphate Mined Lands in Florida. Volumes 1 & 2. University of Florida, Center for Wetlands; August 2002 Cira, Aidee, Results from Doctoral Dissertation Research, University of South Florida, College of Engineering, 2008

Florida Institute of Phosphate Research Home Page. 1855 W. Main St. Bartow,

FL 33830, 2004 <www.fipr.state.fl.us> Hanschke, Thomas, and Baird, A.J., Time-Lag Errors Associated with the use of Simple Standpipe Piezometers in Wetland Soils The Society of Wetland Scientists (Vol. 21, No. 3, ) pp. 412-421; 2001

Hvorslev, M.J., Time-lag and Soil Permeability in Groundwater Observations. Bulletin No. 36, U.S. Waterways Experimentation Station, Vicksburg, MS; 1951

Lewelling, B.R. and Wylie, R.W. Hydrology and Water Quality of Unmined and Reclaimed Basins in Phosphate-Mining Areas, West-Central Florida. Tallahassee, Fl; 1993 Mikkelsen, P.E., and Green, G.E., Piezometers in Fully Grouted Boreholes Symposium on Field Measurements in Geomechanics, Oslo, Norway; 2003

Miller, J.A., Hydrogeologic Framework of the Upper Floridan Aquifer system in Florida, and parts of Georgia, Alabama, and South Carolina, U.S. Geological Survey Professional Paper 1403-B; 1986 Moore, R.E., and Gobdwin, K.R., Hydraulic Head Measurements in Soils with High Water Tables American Society of Agricultural Engineers (vol.22 no.7), St. Joseph, MI; 1941

Reigner, Walter R. and Winkler III, Cornelis. Reclaimed Phosphate Clay Settling Area Investigation: Hydrologic Model Calibration and Ultimate Clay Elevation Prediction. Final Report. BCI Engineers & Scientists, Inc., Lakeland, Florida; August 2001

Page 40: Comparing a Low-Volume Piezometer to Traditional Wells in

33

Ross, Mark A. et al. Hydrogeology of Clay Settling Areas. University of South Florida Tampa, FL; 2003

Scott, T.M., Lithostratigraphy of the Hawthorn Group (Miocene) of Florida, Florida Geological Survey Bulletin No. 59, 1988