communications distribution system drawings
TRANSCRIPT
OIT Enterprise Infrastructure – Telecommunications Division
6/15/2020
COMMUNICATIONS
DISTRIBUTION SYSTEM
DRAWINGS
6/11/2020
TABLE OF CONTENTS
SECTION A: SAMPLE ISP BUILDING FACE PLATE SYMBOL LIST FP1
SECTION B: TYPICAL LARGE EQUIPMENT ROOM LAYOUT ER-1 TYPICAL MEDIUM EQUIPMENT ROOM LAYOUT ER-2 TYPICAL SMALL NEW EQUIPMENT ROOM LAYOUT ER-3 TYPICAL SHALLOW EQUIPMENT ROOM LAYOUT ER-4 TYPICAL TELECOMMUNICATIONS ROOM LAYOUT TR-1 TYPICAL SHALLOW TELECOMMUNICATIONS ROOM LAYOUT TR-2 POWER AND TELCOM FLOORBOX INSTALLATION DETAIL 1 FB-1 POWER AND TELCOM FLOORBOX INSTALLATION DETAIL 2 FB-2 TYPICAL FLUSH MOUNTED INSTALLATION FOR NEW CONSTRUCTION FM-1 TYPICAL GROUNDING AND BONDING REQUIREMENTS GB-1 TYPICAL EQUIPMENT ROOM RACK LAYOUT RL-ER TYPICAL CABLE AND HARDWARE LABELING DETAILS S-2 TYPICAL LIGHTNING PROTECTION/TERMINATION LABELING DETAIL S-3 TYPICAL LABELING AID – ISP/OSP OPTICAL FIBER S-5 TYPICAL STI – EZ PATH INSTALLATION SCENARIOS S-6 TYPICAL STI – READY SLEEVE INSTALLATION SCENARIOS S-7
SECTION C: TYPICAL FIRESTOPPING DETAIL GYPSUM WALL SECTIONS ED-14A TYPICAL FIRESTOPPING DETAIL CONCRETE OR WALL SECTIONS ED-14B TYPICAL BONDING DETAIL FOR GROUND WIRE IN CONDUIT ED-15A BACKBONE CABLE SHIELDS DETAIL ED-15B GROUNDING AND BONDING TMGB &TGB BUSBAR DETAIL ED-15C ELEVATION HARDWARE DETAIL CIRCA 1880B1-100 TIE ED-16A ELEVATION HARDWARE DETAIL CIRCA 1880B1-100 TIE/RISER ED-16B TYPICAL ISP BACKBONE FIBER TERMINATION LAYOUT-ER’s FTL-1 TYPICAL ISP BACKBONE FIBER TERMINATION LAYOUT-TR’s FTL-2 TYPICAL OSP FIBER TERMINATION LAYOUTS FTL-3 TYPICAL RISER POLE GUARD INSTALLATION DETAIL RP-1
SECTION D: COVER SHEET TELECOMMUNICATIONS PLAN T0-1 ABBREVIATIONS & SYMBOLS LIST TELECOMMUNICATIONS PLAN T0-2 TELECOMMUNICATIONS RISER DIAGRAM TELECOMMUNICATIONS PLAN T2-1 TYPICAL TELECOMMUNICATIONS GROUNDING AND BONDING DETAILS T2-2
6/11/2020
EQUIPMENT ROOM DETAILS & ELEVATIONS TELECOMMUNICATIONS PLAN T2-3 TELECOMMUNICATIONS ROOM DETAILS & ELEVATIONS TELECOMMUNICATIONS PLAN T2-4 TYPICAL 110 BLOCK TERMINATIONS TELECOMMUNICATIONS PLAN T2-5 TYPICAL CABLE HARDWARE LABELING DETAILS TELECOMMUNICATIONS PLAN T2-6 LABELING DETAILS TELECOMMUNICATIONS PLAN T2-7
SECTION E: DUCTBANK TRENCH DETAILS DB-1
Switchcraft
PUSH
S
W
IT
CHCR
A
F
T
Switchcraft
PUSH
S
W
IT
CHCR
A
F
T
Switchcraft
PUSH
S
W
IT
CHCR
A
F
T
Switchcraft
PUSH
S
W
IT
CHCR
A
F
T
S
W
I
TC
HC
R
A
F
T S
W
I
TC
HC
R
A
F
T
S
W
IT
CHCR
A
F
TS
W
IT
CHCR
A
F
T
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
EQUIPMENT ROOM LAYOUT
TYPICAL LARGE
1 ADM
2/10/14 GENERAL REVISION
2 ADM11/19/19
UPDATED PER LATEST STANDARDS
DH
SAO
WZ
3/26/02
ER-01
ER-1
5 RACKS (2 ROWS)
(256 FT )
2
3 ADM
3/17/2020 UPDATE
DH
4 ADM4/2/2020
UPDATE
DH
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR,
24" AFF (SEE NOTE 7)
PROVIDE SERVICE LOOP FOR ALL HORIZONTAL VOICE, DATA, AND
VIDEO CABLES NOT TO EXCEED 10 FEET. LOCATION TO BE
DETERMINED BY THE RUPM.
MOUNT QUAD OUTLETS WITH TOP OF BACKBOX AT 1" BELOW
LADDER TRAY OR AT 85" AFF, WHICHEVER IS LOWER. LOCATIONS TO
BE COORDINATED WITH RUTGERS UNIVERSITY.
3/4" AC FIRERATED PLYWOOD ON ALL WALLS, PAINTED WITH WHITE
FIRE RETARDANT PAINT (DO NOT PAINT PLYWOOD LABEL). MOUNT
PLYWOOD VERTICALLY AT 22" AFF WITH STAINLESS STEEL
HARDWARE.
PROVIDE (3) 30A SPARE CIRCUITS IN ELECTRIC PANEL.
CORE AND DISTRIBUTION RACKS MUST BE ADJACENT.
120 VAC DUPLEX
CONVENIENCE
OUTLET, 18" AFF
(TYPICAL FOR 3)
(SEE NOTE 6)
4.
8.
2.
3.
1.
NOTES:
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
ELECTRIC PANEL
SERVING ROOM,
(SEE NOTES 2 & 6)
3/4" FIRERATED, PAINTED
PLYWOOD ON ALL WALLS
(SEE NOTES 3 & 6)
18" LADDER TRAY,
MOUNTED 86" AFF
(SEE NOTE 5)
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
4" SLEEVES/CONDUITS
AS REQUIRED
BY IT/COMMUNICATIONS CONTRACTOR.
BY ARCHITECT/ROOM CONSTRUCTION CONTRACTOR.
COORDINATE LOCATION WITH RUTGERS UNIVERSITY.
BY IT CONTRACTOR FOR EXISTING ROOMS.
BY BUILDING CONTRACTOR FOR NEW ROOMS.
7.
6.
5.
SEE NOTE 5
(TYPICAL FOR
ALL RACKS/
CABINETS)
L6-30R TWISTLOCK OUTLET MOUNTED TO
LADDER TRAY,
DEDICATED (TYPICAL FOR
ALL RACKS UNLESS NOTED,
OTHERWISE SEE NOTE 6).
CA
BIN
ET
CA
BIN
ET
CA
BIN
ET
CA
BIN
ET
CA
BIN
ET
CA
BIN
ET
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
EQUIPMENT ROOM LAYOUT
TYPICAL MEDIUM
1 ADM
2/10/14 GENERAL REVISION
2 ADM11/19/19
UPDATED PER LATEST STANDARDS
DH
ER-2
ER-02
3/26/02
WZ
SAO
5 RACKS (160 FT )
2
3 ADM
3/17/2020 UPDATE
DH
4" SLEEVES/CONDUITS
AS REQUIRED
3/4" FIRERATED, PAINTED
PLYWOOD ON ALL WALLS
(SEE NOTES 3 & 6)
ELECTRIC PANEL
SERVING ROOM.
(SEE NOTES 2 & 6
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
120 VAC DUPLEX CONVENIENCE
OUTLET, 18" AFF (TYPCIAL FOR 3)
(SEE NOTE 6)
12" LADDER TRAY,
MOUNTED 86" AFF
(SEE NOTE 5)
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR, 24" AFF
(SEE NOTE 7)
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTE 4 & 6)
3.
2.
1.
4.
5.
7.
6.
BY IT CONTRACTOR FOR EXISTING ROOMS.
BY BUILDING CONTRACTOR FOR NEW ROOMS.
BY ARCHITECT/ROOM CONSTRUCTION CONTRACTOR.
COORDINATE LOCATION WITH RUTGERS UNIVERSITY.
BY IT/COMMUNICATIONS CONTRACTOR.
PROVIDE (3) 30A SPARE CIRCUITS IN ELECTRIC
PANEL.
3/4" AC FIRERATED PLYWOOD ON ALL WALLS,
PAINTED WITH WHITE FIRE RETARDANT PAINT (DO
NOT PAINT PLYWOOD LABEL). MOUNT PLYWOOD
VERTICALLY AT 22" AFF WITH STAINLESS STEEL
HARDWARE.
MOUNT QUAD OUTLETS WITH TOP OF BACKBOX AT 1" BELOW
LADDER TRAY OR AT 85" AFF, WHICHEVER IS LOWER. LOCATIONS TO
BE COORDINATED WITH RUTGERS UNIVERSITY.
PROVIDE SERVICE LOOP FOR ALL HORIZONTAL
VOICE, DATA, AND VIDEO CABLES NOT TO EXCEED
10 FEET. LOCATION TO BE DETERMINED BY THE
RUPM.
NOTES:
(1) L6-30R
TWISTLOCK
CABINET CABINET
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
EQUIPMENT ROOM LAYOUT
TYPICAL SMALL
1 CMW
12/11/17 GENERAL REVISION
2 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
ER-3
ER-03A
8/27/13
WZ
SAO
3 RACKS (120 FT )
2
3 ADM
3/17/2020 UPDATE
DH
4 ADM
4/2/2020UPDATE
DH
DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR,
24" AFF (SEE NOTE 7)
4" SLEEVES/CONDUITS
AS REQUIRED
DUPLEX
CONVENIENCE
OUTLET, 18" AFF
(TYPICAL FOR 2)
(SEE NOTE 6)
12" LADDER TRAY,
MOUNTED 86" AFF
(SEE NOTE 5)
3/4" FIRERATED, PAINTED
PLYWOOD ON ALL WALLS
(SEE NOTE 3 & 6)
ELECTRIC PANEL
SERVING ROOM
(SEE NOTES 2 & 6)
SEE NOTE 5
(TYPICAL FOR
ALL RACKS/
CABINETS)
NOTES:
3.
2.
1.
4.
5.
7.
6.
BY IT CONTRACTOR FOR EXISTING ROOMS.
BY BUILDING CONTRACTOR FOR NEW ROOMS.
BY ARCHITECT/ROOM CONSTRUCTION CONTRACTOR.
COORDINATE LOCATION WITH RUTGERS UNIVERSITY.
BY IT/COMMUNICATIONS CONTRACTOR.
PROVIDE (3) 30A SPARE CIRCUITS IN ELECTRIC PANEL.
3/4" AC FIRERATED PLYWOOD ON ALL WALLS, PAINTED WITH WHITE
FIRE RETARDANT PAINT (DO NOT PAINT PLYWOOD LABEL). MOUNT
PLYWOOD AT 22" AFF VERTICALLY WITH STAINLESS STEEL
HARDWARE.
MOUNT QUAD OUTLETS WITH TOP OF BACKBOX AT 1" BELOW
LADDER TRAY OR AT 85" AFF, WHICHEVER IS LOWER. LOCATIONS TO
BE COORDINATED WITH RU.
PROVIDE SERVICE LOOP FOR ALL HORIZONTAL VOICE, DATA, AND
VIDEO CABLES NOT TO EXCEED 10 FEET. LOCATION TO BE
DETERMINED BY THE RUPM.
L630R TWISTLOCK OUTLET MOUNTED TO
LADDER TRAY,
DEDICATED (TYPICAL, SEE NOTE 6).
CA
BIN
ET
DEDICATED
QUAD OUTLET,
1" BELOW TRAY
(SEE NOTES 4 & 6)
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
EQUIPMENT ROOM LAYOUT
TYPICAL SHALLOW
1 ADM
2/10/14GENERAL REVISION
ER-4
TR-02
3/26/02
WZ
SAO
2 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
3 ADM
3/17/2020UPDATE
DH
4 ADM
4/2/2020 UPDATE
DH
NOTES:
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW TRAY
(SEE NOTES 4 & 6)
ELECTRIC PANEL
SERVING ROOM
(SEE NOTE 2 & 6)
3/4" FIRERATED, PAINTED
PLYWOOD ON ALL WALLS
(SEE NOTES 3 & 6)
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR,
24" AFF (SEE NOTE 7)
4" SLEEVES/CONDUITS
AS REQUIRED
12" LADDER TRAY,
MOUNTED 86" AFF
(SEE NOTE 5)
120 VAC DUPLEX
CONVENIENCE OUTLET,
18" AFF (TYPICAL FOR 1)
(SEE NOTE 6)
SEE NOTE 5 (TYPICAL FOR
ALL RACKS/CABINETS)
L6-30R TWISTLOCK OUTLET MOUNTED TO
LADDER TRAY,
DEDICATED (TYPICAL FOR
ALL RACKS UNLESS NOTED,
OTHERWISE SEE NOTE 6).
BY ARCHITECT/ROOM CONSTRUCTION CONTRACTOR.
COORDINATE LOCATION WITH RUTGERS UNIVERSITY.
BY IT CONTRACTOR FOR EXISTING ROOMS.
BY BUILDING CONTRACTOR FOR NEW ROOMS.
PROVIDE SERVICE LOOP FOR ALL HORIZONTAL VOICE, DATA, AND
VIDEO CABLES NOT TO EXCEED 10 FEET. LOCATION TO BE
DETERMINED BY THE RUPM.
MOUNT QUAD OUTLETS WITH TOP OF BACKBOX AT 1" BELOW
LADDER TRAY OR AT 85" AFF, WHICHEVER IS LOWER.
LOCATIONS TO BE COORDINATED WITH RUTGERS UNIVERSITY.
3/4" AC FIRERATED PLYWOOD ON ALL WALLS, PAINTED WITH WHITE
FIRE RETARDANT PAINT (DO NOT PAINT PLYWOOD LABEL). MOUNT
PLYWOOD VERTICALLY AT 22" AFF WITH STAINLESS STEEL
HARDWARE.
BY IT/COMMUNICATIONS CONTRACTOR.
6.
5.
4.
3.
2.
1.
PROVIDE (3) 30A SPARE CIRCUITS IN ELECTRIC PANEL.
7.
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
TELECOMMUNICATIONS ROOM LAYOUT
TYPICAL
TR-1
TR-01
3/26/02
JF
SAO
1 ADM
2/10/14 GENERAL REVISION
2 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
1 RACK (80 FT )
2
3 ADM
3/17/2020 UPDATE
DH
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
120 VAC DUPLEX
CONVENIENCE OUTLET,
18" AFF (TYPICAL FOR 2)
(SEE NOTE 6)
ELECTRIC PANEL
SERVING ROOM
(SEE NOTE 2 & 6)
4" SLEEVES/CONDUITS
AS REQUIRED
3/4" FIRERATED, PAINTED
PLYWOOD ON ALL WALLS
(SEE NOTES 3 & 6)
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
12" LADDER TRAY,
MOUNTED 86" AFF
(SEE NOTE 5)
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR,
24" AFF (SEE NOTE 7)
SEE NOTE 5 (TYPICAL FOR
ALL RACKS/CABINETS)
BY ARCHITECT/ROOM CONSTRUCTION CONTRACTOR.
COORDINATE LOCATION WITH RUTGERS UNIVERSITY.
BY IT CONTRACTOR FOR EXISTING ROOMS.
BY BUILDING CONTRACTOR FOR NEW ROOMS.
PROVIDE SERVICE LOOP FOR ALL HORIZONTAL VOICE, DATA, AND
VIDEO CABLES NOT TO EXCEED 10 FEET. LOCATION TO BE
DETERMINED BY THE RUPM.
MOUNT QUAD OUTLETS WITH TOP OF BACKBOX AT 1" BELOW
LADDER TRAY OR AT 85" AFF, WHICHEVER IS LOWER.
LOCATIONS TO BE COORDINATED WITH RUTGERS UNIVERSITY.
3/4" AC FIRERATED PLYWOOD ON ALL WALLS, PAINTED WITH WHITE
FIRE RETARDANT PAINT (DO NOT PAINT PLYWOOD LABEL). MOUNT
PLYWOOD VERTICALLY AT 22" AFF WITH STAINLESS STEEL
HARDWARE.
BY IT/COMMUNICATIONS CONTRACTOR.
6.
5.
4.
3.
2.
NOTES:
1.
PROVIDE (3) 30A SPARE CIRCUITS IN ELECTRIC PANEL.
7.
L6-30R TWISTLOCK OUTLET MOUNTED TO
LADDER TRAY,
DEDICATED (TYPICAL FOR
ALL RACKS UNLESS NOTED,
OTHERWISE SEE NOTE 6).
CA
BIN
ET
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
TELECOMMUNICATIONS ROOM LAYOUT
TYPICAL SHALLOW
SAO
WZ
3/26/02
ER-4
TR-2
1 ADM
2/10/14GENERAL REVISION
2 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
3 ADM
3/17/2020UPDATE
DH
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
120 VAC DUPLEX CONVENIENCE
OUTLET, 18" AFF (TYPICAL FOR 1)
(SEE NOTE 8)
12" LADDER TRAY,
MOUNTED 86" AFF
(SEE NOTE 5)
120 VAC, 20A DEDICATED
QUAD OUTLET, 1" BELOW
TRAY (SEE NOTES 4 & 6)
4" SLEEVES/CONDUITS
AS REQUIRED
TELECOMMUNICATIONS MAIN
GROUNDING BUSBAR,
24" AFF (SEE NOTE 7)
SEE NOTE 5
(TYPICAL FOR
ALL RACKS/
CABINETS)
NOTES:
3.
2.
1.
4.
5.
7.
6.
BY IT CONTRACTOR FOR EXISTING ROOMS.
BY BUILDING CONTRACTOR FOR NEW ROOMS.
BY ARCHITECT/ROOM CONSTRUCTION CONTRACTOR.
COORDINATE LOCATION WITH RUTGERS UNIVERSITY.
BY IT/COMMUNICATIONS CONTRACTOR.
PROVIDE (3) 30A SPARE CIRCUITS IN ELECTRIC PANEL.
3/4" AC FIRERATED PLYWOOD ON ALL WALLS, PAINTED WITH WHITE
FIRE RETARDANT PAINT (DO NOT PAINT PLYWOOD LABEL). MOUNT
PLYWOOD VERTICALLY AT 22" AFF WITH STAINLESS STEEL
HARDWARE.
MOUNT QUAD OUTLETS WITH TOP OF BACKBOX AT 1" BELOW
LADDER TRAY OR AT 85" AFF, WHICHEVER IS LOWER. LOCATIONS TO
BE COORDINATED WITH RUTGERS UNIVERSITY.
PROVIDE SERVICE LOOP FOR ALL HORIZONTAL VOICE, DATA, AND
VIDEO CABLES NOT TO EXCEED 10 FEET. LOCATION TO BE
DETERMINED BY THE RUPM.
L6-30R TWISTLOCK OUTLET MOUNTED TO
LADDER TRAY,
DEDICATED (TYPICAL FOR
ALL RACKS UNLESS NOTED,
OTHERWISE SEE NOTE 6).
3/4" FIRERATED, PAINTED
PLYWOOD ON ALL WALLS
(SEE NOTES 3 & 6)
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
INSTALLATION DETAIL 1
POWER & TELCOM FLOORBOX
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
FB-1
FB-01
4/5/02
JF
SAO
POWER CONDUITS TO ABOVE
NEAREST ACCESSIBLE CEILING
POWER CONDUITS
FIRESTOP AS REQUIRED TO
MEET FLOOR FIRE RATING
CORE DRILL WITH
FIRESTOP AS REQUIRED
IF SLAB ON GRADE,
CONTRACTOR MUST PROVIDE
SUFFICIENT ADDITIONAL FILL
TO ACCOMMODATE CONDUIT
BEND AT FLOORBOX
AND/OR WALL
TELECOMMUNICATIONS CONDUITS
NOTE: SEE DRAWING FB-2 FOR RELATED INFORMATION
FLOOR BOX
FINISHED CEILING
WALL
TELECOMMUNICATIONS
CONDUITS TO ABOVE
NEAREST ACCESSIBLE
CEILING
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
INSTALLATION DETAIL 2
POWER & TELCOM FLOORBOX
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
JF
4/5/02
FB-02
FB-2
BOX IS NOT RATED FOR CONTACT WITH GRADE - CONTRACTOR IS
TO PROVIDE SUFFICIENT PAD BELOW BOX AS REQUIRED TO MEET
LOCAL CODE.
SPECIAL NOTES FOR SLAB ON GRADE CONDITION
CONDUIT DIRECTION UPON LEAVING FLOORBOX ARE FOR
EXAMPLE ONLY AND ARE NOT FOR CONSTRUCTION.
AC DIVIDER PLATE
TELECOMMUNICATIONS CONDUIT
1.
SEE DRAWING FB-1 FOR RELATED DETAILS.2.
1.
NOTES:
POWER CONDUIT
POURED CONCRETE FLOOR
TOP OF FLOORBOX COVER
MUST BE FLUSH WITH FINISHED FLOOR
CARPET PILE
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
FOR NEW CONSTRUCTION
TYPICAL FLUSH MOUNTED INSTALLATION
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
JF
3/26/02
FM-01
FM-1
1 IN. CONDUIT STUBOUT TO ABOVE
ACCESSIBLE CEILING
90 DEGREE BEND
CONDUIT BUSHING
4 IN. x 4 IN. x 3 IN.
FLUSH MOUNTED BACKBOX
WITH SINGLE GANG MUD RING
FINISHED FLOOR
SEMI-FLUSH MOUNTED FACEPLATE
18"
DRYWALL CONSTRUCTION
DROP CEILING
SECTION
N.T.S.
S.A.O.
GB-1
DWG. #
CHECKED BY:
DRAWN BY:
DATE:
MS
4/03/02
GB-01
TITLE:
ADM 2/10/14REVISED BY:
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
TYPICAL GROUNDING AND
BONDING REQUIREMENTS
TO TIE CABLE SHIELD/CBC
(BY IT CONTRACTOR)
TYPICAL GROUNDING & BONDING REQUIREMENTS
EQUIPMENT RACK
GROUNDING CONDUCTORS
TO CABLES, CONDUITS,
ETC. (BY IT CONTRACTOR)
GROUNDING CONDUCTOR,
WHERE APPLICABLE
(SEE NOTE 3)
GROUNDING CONDUCTOR
(BY IT CONTRACTOR)
GROUNDING CONDUCTOR
(BY IT CONTRACTOR)
GROUNDING CONDUCTOR,
WHERE APPLICABLE
(SEE NOTE 3)
CONNECTION
(BY CLOSET CONTRACTOR)
GROUNDING CONDUCTOR
(BY CLOSET CONTRACTOR)
ALL CABLES AND CONNECTIONS BY IT CONTRACTOR EXCEPT WHERE INDICATED OTHERWISE.
BONDING CONDUCTOR
FOR TELECOMMUNICATIONS
(SEE NOTE 3)
CONNECTION
(BY CLOSET CONTRACTOR)
BASEMENT
ALL CABLES SHALL BE #6 AWG. OR LARGER.2.
1.
NOTES:
TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
(SEE NOTE 3)
TMGB
MAIN ENTRANCE
ELECTRIC PANEL
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
FOURTH FLOOR
GROUNDING CONDUCTORS
TO CABLES, CONDUITS, ETC.
(BY IT CONTRACTOR)
TELECOMMUNICATIONS GROUNDING BUSBAR
(SEE NOTE 3)
CONNECTION
(BY CLOSET CONTRACTOR)
TELECOMMUNICATIONS
BONDING BACKBONE (TBB),
(SEE NOTE 3)
BOND
(SEE NOTE 3)
PANEL
ELECTRIC
EQUIPMENT ROOM
(ER)
CONNECTION
(BY CLOSET CONTRACTOR)
GROUNDING CONDUCTOR
(BY CLOSET CONTRACTOR)
CONNECTION
(BY CLOSET CONTRACTOR)
TELECOMMUNICATIONS
ROOM (TR)
EQUIPMENT RACK
TGB
ELECTRIC
PANEL
GROUNDING CONDUCTOR,
WHERE APPLICABLE
(BY RU, FUTURE)
GROUNDING CONDUCTOR
(BY RU, FUTURE)
GROUNDING CONDUCTOR,
WHERE APPLICABLE
(SEE NOTE 3)
TELECOMMUNICATIONS
BONDING BACKBONE
(SEE NOTE 3)
TELECOMMUNICATIONS
GROUNDING BUSBAR
(SEE NOTE 3)
TO TIE CABLE SHIELD/CBC
(BY IT CONTRACTOR)
GROUNDING CONDUCTORS
TO RACKS, CABLES, CONDUITS,
ETC. (BY RU, FUTURE)
TGB
CLOSET CONTRACTOR:
ELECTRICAL CONTRACTOR BUILDING THE CLOSET
IT CONTRACTOR:
INFORMATION TECHNOLOGY/COMMUNICATIONS
CONTRACTOR
EXISTING DEMARC
EXISTING TELEPHONE
DEMARC
TO ADDITIONAL TGBs
WHERE APPLICABLE
(SEE NOTE 3)
ELECTRIC
PANEL
LEGEND
BY IT CONTRACTOR FOR EXISTING CLOSETS.3.
BY CLOSET CONTRACTOR FOR NEW CLOSETS.
#6 (MIN.) GROUND WIRE TO BUSBAR
WRAP TWO LAYERS OF VINYL
TAPE STICKY SIDE OUT AND
PUSH DOWN UNDER CABLE
SHIELD
PLACE INNER CLAMP BETWEEN
TAPE AND SHEILD
BACKBONE CABLE SHIELDS
#6 (MIN.) GROUND WIRE
GROUND LUG (TYP.)
GROUND CLAMP (TYP.)
WIRE EXITING CONDUIT
TYPICAL BONDING FOR GROUND WIRE IN CONDUIT
CONDUITWIRE ENTERING CONDUIT
BOLT CONNECTOR (TYP.)
#6 (MIN.) GROUND WIRE
#6 (MIN.) GROUND WIRE
DO NOT REMOVE CORE
WRAP
CUT SHEATH AND SHIELD
WITH TABBING SHEARS
#6 (MIN.) GROUND WIRE
WRAP WITH TWO HALF-LAPPED
LAYERS OF VINYL TAPE
#6 (MIN.) GROUND WIRE
OR #10 COUPLED BONDING
CONDUCTOR (CBC), (TYP.)
READY TO:
TERMINATE PAIRS
BOND SHIELD
PLACE:
OUTER CLAMP
FLAT WASHER
LOCK WASHER
NUT
TIGHTEN SECURELY
BUSBAR
TMGB & TGB BUSBAR DETAIL
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
TYPICAL EQUIPMENT ROOM RACK LAYOUT
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
RL-ER
RL-B2
3/26/02
JF
SAO
3 ADM
2/4/2020 UPDATE
DH
2 ADM
1/31/2020 UPDATE
DH
4 ADM
2/27/2020 UPDATE
DH
5 ADM
3/17/2020 UPDATE
DH
6 ADM
4/2/2020 UPDATE
DH
NOTES:
2.
1.
DETAILS OF THE EQUIPMENT NEEDED WILL VARY FROM BUILDING TO BUILDING.
WIRE MANAGERS, VIDEO SPLITTERS, FIBER TERMINATION PANELS AND SPLICE TRAYS TO BE
INSTALLED IN A DEDICATED OSP RACK. DETAILS OF THE EQUIPMENT NEEDED WILL VARY FROM
BUILDING TO BUILDING.
OSP RACK
(SEE NOTE 1)
1U WIRE MANAGER &
VIDEO SPLITTER
AS NEEDED
6" VERTICAL WIRE MANAGERS
P
R
O
T
E
C
T
IO
N
G
N
D
O
K
P
O
W
E
R
ON
OFF
20
A
M
P
ISP RACK
(SEE NOTE 2)
1U WIRE MANAGER &
4U TERMINATION PANEL
(FOR EVERY 4 TR's)
(ISP)
48 PORT PATCH PANELS,
2U FOR SWITCHES
& 1U & 2U WIRE MANAGERS
AS NEEDED.
MAXIMUM OF 192 PORTS
PER RACK
(ISP)
1U WIRE MANAGERS,
4U TERMINATION PANELS,
5U SPLICE TRAYS &
2U WIRE MANAGERS
AS NEEDED
(OSP)
Catalyst
4506-E
Cisco Systems
R
ON
OFF
ON
OFF
Cisco Systems
R
TYPICAL CABLE AND HARDWARE
LABELING DETAILS
1 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
EACH FACEPLATE WILL BE LABELED BLACK ON WHITE LABELS WITH BOLD FONT.
EACH 110 PUNCH DOWN BLOCK WILL BE LABELED.
A.)RISER CABLE. (WHITE)
B.)HORIZONTAL CABLES. (BLUE)
C.)TIE CABLE. (GREEN)
EACH VOICE, DATA, COAX CABLE AND GROUND WIRE THAT IS PULLED WILL BE
LABELED ON BOTH ENDS OF THE CABLE WITH A PRINTED WRAP
AROUND CABLE LABEL.
EACH DATA PATCH PANEL PORT WILL BE LABELED IN THE CENTER OF THE PATCH PANEL
WHITE LABEL.
TIE, RISER AND BACKBONE CABLE SLEEVE.
THE VOICE CABLE (RISER & TIE) ID WILL BE CRV-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE VOICE CABLE (BACKBONE) ID WILL BE CBV-CAMPUS NAME-SEQUNETIAL NUMBER.
THE FIBER CABLE (RISER) ID WILL BE CRF-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE FIBER CABLE (BACKBONE) ID WILL BE CBF-CAMPUS NAME-SEQUNETIAL NUMBER.
THE COAX CABLE (RISER) ID WILL BE CRC-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE COAX CABLE (BACKBONE) ID WILL BE CBC-CAMPUS NAME-SEQUNETIAL NUMBER.
TERMINATION HARDWARE NUMBERS AND RACK NUMBER.
THE TERMINATION HARDWARE NUMBERS WILL BE DETERMINED
THE FOLLOWING WAYS:
A.) DATA PATCH PANEL TH-BUILDING#-ER/TR ROOM#-100 THROUGH 199.
B.) VOICE PUNCHDOWN BLOCK (RISER) CRV-BUILDING#-SEQUENTIAL#
(TO MATCH RISER CABLE NUMBER).
C.) VOICE PUNCHDOWN BLOCK (TIE) CRV-BUILDING#-SEQUENTIAL#
(TO MATCH TIE CABLE NUMBER).
D.) VOICE PUNCHDOWN BLOCK (STATION) TH-BUILDING#-ER/TC ROOM#-200 THROUGH 299.
E.) ISP FIBER TH-BUILDING#-ER/TR ROOM#-300 THROUGH 399.
F.) OSP FIBER TH-BUILDING#-ER/TR ROOM#-400 THROUGH 499.
G.) VIDEO TH-BUILDING#-ER/TR ROOM#-500 THROUGH 599.
FIBER LABELING:
1.) INSIDE PLANT LABEL AS FOLLOWS:
CONNECTOR PANEL LOCATION IN HOUSING-CRF-BUILDING#-SEQUENTIAL#-TUBE#(s)
TO:RM# IT IS FEEDING.
2.) OUTSIDE PLANT LABEL AS FOLLOWS:
CONNECTOR PANEL LOCATION IN HOUSING-CBF-CAMPUS NAME-CABLE#-TUBE COLOR
TO:BLDG# - BLDG. NAME IT IS FEEDING.
GROUNDING LABELING:
1. GROUND BARS WILL BE LABELED WITH
TMGB OR TGB-THE # OF THE GND BAR AND THE BUILDING.
2. GROUND CONDUCTORS WILL BE LABELED
A.) BONDING CONDUCTORS (FROM TMGB TO THE TGB'S OR SERVICE GND AND
BLDG STEEL) WILL BE BC AND A SEQUENTIAL NUMBER THROUGHOUT THE ROOM.
B.) EQUIPMENT BONDING CONDUCTOR (LADDER RACKS FREESTANDING, SWING GATE, AND
CONDUITS) EC AND A SEQUENTIAL NUMBER THROUGHOUT THE ROOM.
C.) CABLE BONDING CONDUCTOR (THE BONDING CONDUCTOR THAT IS RUN
WITH THE BACKBONE CABLE) CC AND THE NUMBER OF THE TIE OR
RISER CABLE IT IS ASSOCIATED WITH.
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
FOR LABELING INFO.
SEE NOTE #3
TYPICAL WP
1001V 1002V
1002D1001D 1001C
FOR LABELING INFO.
SEE NOTE #2
FOR LABELING INFO.
SEE NOTE #6A
RACK # SEQUENTIAL NUMBER PER ROOM
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #7
FOR LABELING INFO.
SEE NOTES #4A & #6B
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTES #4C & #6B
FOR LABELING INFO.
SEE NOTE #6F
SEE NOTE #8
FOR LABELING INFO.
SEE NOTE #6E
SEE NOTE #8
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTES #4B & #6B
CR
F-6
61
7-3
CB
F-B
US
-1
CR
V-6
61
7-3
CRC-6617-2
CRF-6617-2
CRV-6617-2
CR
V-6
61
7-2
CR
V-6
61
7-1
CRC-6617-2
CRF-6617-2
CRV-6617-2
CR
V-6617-1
CR
V-6617-2
FOR LABELING INFO.
SEE NOTES #1 & 7
FOR LABELING INFO.
SEE NOTE #7
VIDEO RISER
FIBER RISER
VOICE RISER
FOR LABELING INFO.
SEE NOTE #1
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #1
FOR LABELING INFO.
SEE NOTE #1
FOR LABELING INFO.
SEE NOTE #1
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #5
E-CBF-BUS-1-YL TO:BLDG#6618-JONES HALL
TH-6617-003-400
A-CBF-BUS-1-BL TO:BLDG#6618-JONES HALL
D-
C-
B-CBF-BUS-1-OR TO:BLDG#6618-JONES HALLF-
TH-6617-003-300
A-CRF-6617-1 TUBE(S):1,2 TO:RM004E-CRF-6617-5 TUBE(S)1,2 TO:RM344
D-CRF-6617-2 TUBE(S)3 TO:RM215
C-CRF-6617-2 TUBE(S)1,2 TO:RM215
B-CRF-6617-1 TUBE(S):3 TO:RM004F-CRF-6617-6 TUBE(S)3,4 TO:RM344
BC
#2
EC
#2
CC
#4
EC
#9
EC
#8
EC
#3
BC
#1
CC
#3
CC
#2
CC
#1
TMGB #01
EC
#
7
EC
#
6
1001C
1001V1001V
1001D1001D
1001C
CC
#
3
EC
#
7
CC
#
1
EC
#
6
CC
#
2
CRV-6617-1
CRV-6617-1
TH-6617-003-202
TH-6617-003-202
CRV-6617-2
CRV-6617-2
WHITE LABELS
RISER CABLE
VOICE RISER CABLE
110 DETAIL
GREEN LABELS
VOICE TIE CABLE
110 DETAIL
TIE CABLE
OUTSIDE PLANT FIBER CABINET
INSIDE PLANT FIBER CABINET
10
8
24
Size
BLUE LABELS
Aerial Black-Regular
Aerial Black-Regular
Aerial-Regular
Font
Panduit CPPLF-5
Panduit PLL22P01
Panduit DS110-GR
Label Type or Equal
VOICE STATION CABLE
110 DETAIL
Patch Panel Port
Tie 110 Block
Patch Panel
1.
3.
2.
Equipment/Cable
8,27,13
8
8,27,13
12
11
24
24
24
12
12
12
12
13
13
24
13
Aerial-Regular
Bold
Aerial Black-Regular
Bold
Bold
Aerial Black-Regular
Aerial Black-Regular
Aerial Black-Regular
Panduit DS110-BU
Panduit JLEFPS-1
Panduit PLL22P01
Panduit PLL22P01
Panduit JLEFPD-1
P-Touch Tape TZ-231 9MM Black on White
P-Touch Tape TZ-231 9MM Black on White
P-Touch Tape TZ-SE4 18MM Black on White
Aerial Black-Regular
Aerial Black-Regular
Aerial Black-Regular
Bold
Bold
Bold
Aerial Black-Regular
Aerial Black-Regular
Panduit PLL22P01
Panduit PLL-11-Y3-2.5
Panduit PLL-11-Y3-2.5
Panduit PLL-12-Y3-2.5
Panduit PLL-11-Y3-2.5
Panduit SLCT-WH sleeve with P-Touch Label
SLCT-WH sleeve with P-Touch Label
P-Touch Tape TZ-SE4 18MM Black on White
Panduit PLL22P01 Aerial Black-Regular
Station 110 Block
6.
5.
7.
8.
Rack Panduit
9.
10.
12.
11.
Ground Bar ID
Ground Cable
Data Station Cable
15.
14.
16.
17.
Voice Station Cable
Coax Station Cable
Voice Riser Cable
Coax Riser Cable
19.
18.
21.
20.
13.
WP Station Single Gang
WP Station Double Gang
WP Station Single Gang
WP Station Double Gang
ISP Fiber Cabinet TH
ISP Fiber terminations
OSP Fiber Cabinet TH
OSP Fiber terminations
Fiber Optic Riser Cable22. Panduit SLCT-WH sleeve with P-Touch Label Bold
Riser 110 Block 4. Panduit DS110 Aerial-Regular 8
TMGB GROUND BAR
CLOSET CONNECTOR HOUSING PANELS
RISER CONDUIT DETAIL
COAX RISER
FIBER OPTIC RISER
VOICE RISER
COAX STATION
VOICE STATION
DATA STATION
21
3 4
65
12
10
11
9
87
109
1211
84 6
73 5
21
TGB #01
FOR LABELING INFO.
SEE NOTE #1 & #7
TH-6617-003-100
1012D1011D
1035D1036D
1006D1005D
1030D1029D
1023D1024D
CC
#
03
RACK #1
1018D1017D
CC
#
02
CC
#0
1
EC
#
10
EC
#
11
BC
#
01
1009D
1033D
1010D
1034D
1003D
1027D
1004D
1028D
1022D1021D1016D1015D
EQUIPMENT RACK
1008D1007D
1031D1032D
1002D
1026D
1001D
1025D
TGB GROUND BAR
DATA PATCH PANEL
1020D1019D1014D1013D
8,27,13
8,27,13
TYPICAL LIGHTNING PROTECTION/
TERMINATION LABELING DETAIL
1 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
TERMINATION HARDWARE NUMBERS:
PANDUIT PLL22P01 WHITE.
THE TERMINATION HARDWARE NUMBERS WILL BE DETERMINED
THE FOLLOWING WAYS:
A.) VOICE PUNCHDOWN BLOCK (110 BLOCK): TH-BUILDING#-ER/TR ROOM#-200 THROUGH 299.
(TO MATCH LIGHTING PROTECTION BLOCK NUMBER). NOTE: NOT PHYSICALLY LABELED ON 110 BLOCK.
B.) VOICE LIGHTNING PROTECTION BLOCK: TH-BUILDING#-ER/TR ROOM#-200 THROUGH 299.
OSP CABLE AND OSP PIGTAIL CABLE SLEEVE:
PANDUIT SLCT-WH WHITE SELF-LAMINATING CABLE MARKER HOLDER
PANDUIT RECOMMENDED LABELS FOR THE MARKER HOLDER
(PLL-17-Y2-1) AND (JL41PO-0.2).
CABLE IDs WILL BE CBV-CAMPUS NAME-SEQUENTIAL NUMBER.
EACH 110 PUNCH DOWN BLOCK/LIGHTNING PROTECTION BLOCK:
A.) PANDUIT DS110-BN FOR THE OSP AND OSP PIGTAIL CABLE. (BROWN)
1.
3.
2.
NOTES:
CB
V-B
US
-1
CB
V-B
US
-1
CB
V-B
US
-1
CB
V-B
US
-1
CB
V-B
US
-1
CBV-BUS-1
CBV-BUS-1
CBV-BUS-1
CBV-BUS-1
110 Block, 110 Portion of Lightning Protection Block
Equipment/Cable
1.
2.
3. OSP Voice Cable, OSP Pigtail Cable
Lightning Protection Block
LabelFont Size
TYPICAL LIGHTNING PROTECTION/
TERMINATION HARDWARE
LABELING DETAIL
SLCT-WH sleeve with P-Touch Label
Panduit DS110-GR
Panduit PLL22P01
Bold 13
Aerial-Regular 8
Aerial Black-Regular 24
CBV-BUS-1
CBV-BUS-1
CBV-BUS-1
CBV-BUS-1
FIBER LABELING:
THE LABEL WILL BE A P-TOUCH TZ-3/4" TAPE FROM THE P-TOUCH PT330 MACHINE.
A.) INSIDE PLANT LABEL WILL BE AS FOLLOWS:
CONNECTOR PANEL LOCATION IN HOUSING-CRF-BUILDING#-SEQUENTIAL#-TUBE#(s)
TO:RM# IT IS FEEDING.
B.) OUTSIDE PLANT LABEL AS FOLLOWS:
CONNECTOR PANEL LOCATION IN HOUSING-CBF-CAMPUS NAME-CABLE#-TUBE COLOR
TO:BLDG# - BLDG. NAME IT IS FEEDING.
C.) LABEL FOR OSP COMING FROM UTILITY POLE, MANHOLE OR OTHER SPLICE LOCATION.
EXAMPLE:
TO UTILITY POLE UP-CAC-61832
FINAL DESTINATION:
(B-C 6SM/6MM) CBF-CAC-00389
BLDG. 3115 COLLEGE OF NURSING
TO MANHOLE MH-CAM-0054
FINAL DESTINATION:
(A-C 12SM/12MM) CBF-CAM-00074
BLDG. 7004 CAMDEN STUDENT CENTER
3.
TERMINATION HARDWARE NUMBERS AND RACK NUMBER.
PANDUIT PLL22P01 WHITE.
THE TERMINATION HARDWARE NUMBERS WILL BE DETERMINED
THE FOLLOWING WAYS:
A.) ISP FIBER TH-BUILDING#-ER/TR ROOM#-300 THROUGH 399.
B.) OSP FIBER TH-BUILDING#-ER/TR ROOM#-400 THROUGH 499.
TIE, RISER AND BACKBONE CABLE SLEEVE.
PANDUIT SLCT-WH WHITE SELF-LAMINATING CABLE MARKER HOLDER
PANDUIT RECOMMENDED LABELS FOR THE MARKER HOLDER
(PLL-17-Y2-1) AND (JL41PO-0.2)
THE FIBER CABLE (RISER) ID WILL BE CRF-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE FIBER CABLE (BACKBONE) ID WILL BE CBF-CAMPUS NAME-SEQUNETIAL NUMBER.
2.
1.
NOTES:
SEE NOTE #3B
& #3C
SEE NOTE #2B
SEE NOTE #1
INSIDE PLANT FIBER CABINET
OUTSIDE PLANT FIBER CABINET
F-CRF-6617-6 TUBE(S)3,4 TO:RM344B-CRF-6617-1 TUBE(S):3 TO:RM004
C-CRF-6617-2 TUBE(S)1,2 TO:RM215
D-CRF-6617-2 TUBE(S)3 TO:RM215
E-CRF-6617-5 TUBE(S)1,2 TO:RM344A-CRF-6617-1 TUBE(S):1,2 TO:RM004
TH-6617-003-300
F-B-CBF-BUS-1-OR TO:BLDG#6618-JONES HALL
C-
D-
A-CBF-BUS-1-BL TO:BLDG#6618-JONES HALL
TH-6617-003-400
E-CBF-BUS-1-YL TO:BLDG#6618-JONES HALL
CB
F-B
US
-1
CR
F-6
61
7-3
SEE NOTE #1
SEE NOTE #3A
SEE NOTE #2A
Cables
Section View
Kick-in
Concrete Wall
Section View
Kick-in
EZ-Path
Concrete Floor
EZ-PathKick-in
EZ-Path
Kick-in
Top View
Concrete Floor
Cable Types as specified in
UL System No. F-A-3037.
Section A-A
A
A
EZ-PATH
Series 44
FLOOR OPENING
DIMENSIONS
SpecSealâ
Composite Sheet
INSTALLATION INSTRUCTIONS
1. Form or cut nom 6 in. by 12-1/2 in. opening in floor. (See Fig. 3)
2. Install Floor Grid Frame (Part No. EZDG444) as specified in Series 44 Modular
Grid System Installation Guide over opening.
3. Assemble Pathway Module as specified in Installation Guide and
using three (3) Series 44 EZ-Path Pathways.
4. Obtain Composite Sheet Filler Panel from EZG844 or EZG1644 kits that is not in use.
5. Cut Filler Panel to 5 in. width so that it measures 6-3/4 in. by 5 in. (See Fig 2.)
6. Obtain three (3) Panel Clips from EZG844 or EZG1644 kits that are not in use.
7. Install pre-cut Composite Sheet Filler Panel and three (3) Panel Clips as shown in
Fig. 1 above.
8. Insert previously assembled Pathway Module in step 3 as specified in Installation Guide.
Tighten two (2) bolts and two (2) nuts (Provided) onto frame on one side. On second
side, install two (2) No. 10 self tapping steel sheet metal screws using two (2) min 3/8 in.
diam steel fender washers (Purchased Separately).
COMPOSITE SHEET
DIMENSIONS
Fig. 1
Panel Clip
Floor Grid Frame
Floor Grid Frame Outline
Fig. 2 Fig. 3
®
EZ-PATH
7/C-10 AWG Cable
Gypsum Wall
EZ-PATH
7/C-10 AWG Cable
Concrete Wall
Concrete Floor
EZ-PATH
12
1
2
6
6
5
R
STI
R
STI
R
STI
R
STI
NOTE:
Follow UL System and
Instructions to Install EZ-PATH.
This is an engineering judgment
that supplements UL System Nos.
W-L-3218, W-J-3098, F-A-3015,
and F-A-3021.
TYPICAL STI - EZ PATH
INSTALLATION SCENARIOS
1 ADM11/19/19
UPDATED PER LATEST STANDARDS
DH
TYPICAL STI - READY SLEEVE
INSTALLATION SCENARIOS
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
F Rating - 3 Hr
T Rating - 0 Hr
1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3)
concrete. Floor may also be constructed of min 6 in. thick hollow-core Precast Concrete Units* . Max diam of opening is
4-1/2 in. (114 mm).
See Precast Concrete Units (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Firestop Device* - Steel sleeve device centered within opening and installed in accordance with the accompanying
installation instructions. Steel sleeve device secured in place by means of steel escutcheon plates installed with gasketing
material supplied with product. Steel escutcheon plates installed on both sides of floor and secured to device by means of
steel screws provided with device. As an option, device may be cast into floor assembly. Steel sleeve device provided in nom
1, 2 and 4 in. (25, 51 and 102 mm) sizes. The min and max opening diameters for each device are tabulated below:
When device is cast in place, the gasketing and escutcheon plates are optional.
SPECIFIED TECHNOLOGIES INC - FS100, FS200, FS201, FS400 and FS401 SpecSeal Ready-Sleeves
3. Cables - Aggregate cross-sectional area of cables in sleeve to be max 48 percent of the cross-sectional area of the sleeve.
Tight bundle of cables to be installed in the steel sleeve. The annular space within the sleeve shall be a min of 0 in. (0 mm,
point contact) to a max of 2 in. (51 mm). Cables to be rigidly supported on both sides of the floor assembly. Any combination
of the following types and sizes of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket.
C. Max 3/C No. 2/0 AWG (or smaller) copper conductor PVC jacketed aluminum clad or steel clad TECK 90 cable.
D. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket.
E. Max 1/C 1000 kcmil (or smaller) copper conductor power cable with XLPE or PVC insulation and XLPE or PVC jacket.
F. Max RG59/U (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.
G. Max 62.5/48 fiber optic cable with PVC insulation and jacketing.
H. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with PVC insulation and jacket.
1
3
2
5
4
Device Size
1 in. (25 mm)
2 in. (51 mm)
4 in. (102 mm)
Min Opening Diam
1.12 in. (28 mm)
2.38 in. (60 mm)
4.50 in. (114 mm)
Max Opening Diam
1.25 in. (32 mm)
2.50 in. (64 mm)
4.50 in. (114 mm)
F Ratings - 2 hr
T Rating - 0 Hr
1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or
1600-2400 kg/m3) concrete. Floor may also be constructed of min 6 in. thick hollow-core Precast Concrete
Units *. Min distance between periphery of through opening and edge of two-piece steel plate (Item 3) is 1 in. (25
mm).
See Precast Concrete Units (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Cables - Aggregate cross-sectional area of cables in steel sleeve to be max 48 percent of the aggregate
cross-sectional area of the sleeve. Cables to be rigidly supported on both sides of floor assembly. Any
combination of the following types and sizes of copper conductor cable may be used:
A. Max 400 pair No. AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and
insulation.
B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation
and jacket.
C. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation
and jacket.
D. Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and
XLPE or PVC jacket.
E. Nom 5/8 in. (16 mm) (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.
F. Nom 5/8 in. (16 mm) fiber optic cable with PVC insulation and jacketing.
G. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with PVC insulation and jacket.
H. Max 4/C No. 2/0 aluminum or copper conductor aluminum or steel Metal-Clad# or Armored-Clad# cable.
I. Max 1/C-750 kcmil copper conductor cable with XLPE jacket and insulation.
3. Firestop Device * - Device consisting of steel sleeve halves provided with two-piece steel plates. Steel sleeve
device shall be installed around cables in accordance with the accompanying installation instructions. Steel
sleeve device secured in place by means of two-piece steel plates installed with gasketing material supplied with
product. Steel plates and gaskets installed on both sides of floor assembly and secured to device by means of
steel screws provided with device. Steel sleeve device provided in nom 1, 2 and 4 in. sizes. Steel plates
fastened to floor assembly by means of nom 1/4 in. (6 mm) diam by 1-1/4 (32 mm) long steel concrete screws.
As an alternate to the steel concrete screws, nom 1-1/4 in. (32 mm) long steel powder actuated fasteners may be
used to secure steel plates. Steel plates shall be aligned on both sides of the floor assembly to cover opening
with min 1 in. (25 mm) overlap beyond periphery of through opening. The min and max opening sizes for each
sleeve device are shown in the table below:
4. Packing Material - Min 4 pcf (64 kg/m3) mineral-wool batt insulation tightly packed into sleeve to fill device to
min 3 in. (76 mm) depth with min 2 in. (51 mm) of the packing material depth within the confines of the floor
thickness. Packing material recessed from top edge of device as required to accommodate fill material (Item 5).
5. Fill, Void or Cavity Material * - Putty - Min 1/2 in. (13 mm) thickness of fill material applied atop mineral wool
packing material (Item 4) flush with top edge of device (Item 2).
SPECIFIED TECHNOLOGIES INC - SpecSeal Putty
*Bearing the UL Classification Mark
4
5
2
3
1
Device Size
1 in. (25 mm)
2 in. (51 mm)
4 in. (102 mm)
Min Opening Diam
1.12 in. (28 mm)+
2.38 in. (60 mm)+
4.50 in. (114 mm)+
Max Opening Diam
1.25 in. (32 mm)
2.50 in. (64 mm)
4.50 in. (114 mm)
F Ratings - 1 and 2 hr (See Item 1)
T Rating - 0 Hr
1. Wall Assembly - The 1 hr or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and
in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire
Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4
in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and
spaced max 24 in. (610 mm) OC.
B. Gypsum Board * - 5/8 in. (16 mm) thick, 4 ft (1.2 m) wide with square or tapered edges. The gypsum board type,
thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400
or V400 Series Design in the UL Fire Resistance Directory.
The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Firestop Device * - Steel sleeve device centered within opening and installed in accordance with the accompanying
installation instructions. Steel sleeve device secured in place by means of steel escutcheon plates installed with gasket
material supplied with product. Steel escutcheon plates installed on both sides of wall and secured to device by means
of steel screws provided with device. Steel sleeve device provided in nom 2 in. and 4 in. (51 and 102 mm) sizes. The
min and max opening sizes for each sleeve device are shown in the table below:
2A. Firestop Device * - (Not Shown) - As an alternate to Item 2, device consisting of steel sleeve halves provided with
two-piece steel plates. Steel sleeve device shall be installed around cables in accordance with the accompanying
installation instructions. Steel sleeve device secured in place by means of two-piece steel plates installed with gasket
material supplied with product. Steel plates and gaskets installed on both sides of wall and secured to device by means
of steel screws provided with device. Steel sleeve device provided in nom 2 in. and 4 in. (51 and 102 mm) sizes. Steel
plates fastened to gypsum board layers with nom 1/8 in. (3.2 mm) diam steel hollow-wall anchors. Steel plates shall be
aligned on each side of the wall and installed to lap min 1 in. (25 mm) beyond periphery of through opening. The min
and max opening sizes for each sleeve device are shown in the table below:
3. Cables - Aggregate cross-sectional area of cables in steel sleeve to be max 33 percent of the aggregate
cross-sectional area of the sleeve. Cables to be rigidly supported on both sides of wall assembly. Any combination of
the following types and sizes of copper conductor cable may be used:
A. Max 300 pair No. AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and
jacket.
C. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and
jacket.
D. Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and XLPE
or PVC jacket.
E. Max RG/U (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.
F. Max 62.5/48 fiber optic cable with PVC insulation and jacketing.
G. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC insulation and jacket.
H. Max 4/C No. 2/0 aluminum or copper conductor aluminum or steel Metal-Clad# or Armored-Clad# cable.
I. Max 750 kcmil power cable with XLPE jacket and insulation.
4. Fill, Void or Cavity Materials * - Plug - Nom 2 in. (51 mm) or 4 in. (102 mm) diam plug firmly installed within the sleeve
or opening such that the outer circumference of the dome-shaped plug is flush with both ends of sleeve. Plug cut to fit
around the cable bundle and installed tightly within the opening or sleeve.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series FP Firestop Plug
#Bearing the UL Listing Mark
*Bearing the UL Classification Mark
Min Opening Diam
2-3/8 in. (60 mm)+
4-1/2 in. (114 mm)+
Device Size
4 in. (102 mm)
2 in. (51 mm)
Max Opening Diam
2-1/2 in. (64 mm)
4-1/2 in. (114 mm)
Min Opening Diam
2-3/8 in. (60 mm)+
4-1/2 in. (114 mm)+
Device Size
4 in. (102 mm)
2 in. (51 mm)
Max Opening Diam
4 in. (102 mm
6 in. (152 mm)
3
1A
2
1B
4
4
F Ratings - 1 and 2 hr (See Item 1)
T Rating - 1 Hr
1. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory
and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51
by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610
mm) OC.
B. Gypsum Board * - 5/8 in. (16 mm) thick, 4 ft (1.2 m) wide with square or tapered edges. The gypsum board type,
thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400
Series Design in the UL Fire Resistance Directory. Min distance between periphery of through opening and edge of
two-piece steel plate (Item 3) is 1 in. (25 mm).
The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Cables - Aggregate cross-sectional area of cables in steel sleeve to be max 48 percent of the aggregate cross-sectional area
of the sleeve. Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes
of copper conductor cable may be used:
A. Max 400 pair No. AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket.
C. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket.
D. Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and XLPE or PVC
jacket.
E. Nom 5/8 in. (16 mm) (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.
F. Nom 5/8 in. (16 mm) fiber optic cable with PVC insulation and jacketing.
G. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with PVC insulation and jacket.
H. Max 4/C No. 2/0 aluminum or copper conductor aluminum or steel Metal-Clad# or Armored-Clad# cable.
I. Max 1/C-750 kcmil copper conductor cable with XLPE jacket and insulation.
3. Firestop Device * - Device consisting of steel sleeve halves provided with two-piece steel plates. Steel sleeve device shall be
installed around cables in accordance with the accompanying installation instructions. Steel sleeve device secured in place by
means of two-piece steel plates installed with gasketing material supplied with product. Steel plates and gaskets installed on
both sides of wall and secured to device by means of steel screws provided with device. Steel sleeve device provided in nom 1,
2 and 4 in. sizes. Steel plates fastened to gypsum board layers with nom 1/8 in. (3.2 mm) diam steel hollow-wall anchors.
Steel plates shall be nom aligned on each side of the wall to cover opening with min 1 in. (25 mm) overlap beyond periphery of
through opening. The min and max opening sizes for each sleeve device are shown in the table below:
4. Fill, Void or Cavity Material * - Putty - Fill material supplied with firestop device (Item 3) applied to 1 in. (25 mm) thickness
flush with each end of steel sleeve device . At point contact location, min 3/8 in. (9 mm) diam bead of fill material applied at
grouped cable/steel sleeve interface on each side of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal Putty
*Bearing the UL Classification Mark
2
1A
3
1B
4
4
Size
Min. Opening
1.12 in. (28mm)+
Device Size
1 in. (25mm)
Size
Max. Opening
2.50 in. (64 mm)
2.38 in. (60mm)+2 in. (51mm) .00 in. (102 mm)
4.50 in. (114mm)+4 in. (102mm) 6.00 in. (152 mm)
R
STI
R
STI
R
STI
R
STI
Through Penetrating Product* - 3A. (Not Shown) - Max 4/C No. 2/0 AWG (or smaller) steel or aluminum Armored Cable+ or
Metal Clad Cable+ with copper or aluminum conductors. Diam of cable bundle (Item 3) including armored cable not to exceed
4 in. (102 mm). Through penetrating product to be rigidly supported on both sides of a floor assembly.
AFC CABLE SYSTEMS INC
Packing Material - 4. Min 4 pcf (64 kg/m3) mineral-wool batt insulation tightly packed into sleeve to fill device to min 3 in. (76
mm) depth with min 2 in. (51 mm) of the packing material depth within the confines of the floor thickness. Packing material
recessed from top edge of device as required to accommodate fill material (Item 5).
Fill, Void or Cavity Material* - Putty - 5. Min 1/2 in. (13 mm) thickness of fill material applied atop mineral wool packing
material (Item 4) flush with top edge of device (Item 2). At point contact location, apply min 3/8 in. (10 mm) diam bead of fill
material at grouped cable/steel sleeve interface on top surface of floor. SPECIFIED TECHNOLOGIES INC - SpecSeal Putty
*Bearing the UL Classification Mark
3A.
4.
+ - When opening is greater than the min opening size specified,
steel fasteners are required.
FSR100, FSR200, FSR400 Ready Split Sleeves
SPECIFIED TECHNOLOGIES INC -
+ - When opening is greater than the min opening size specified,
steel fasteners are required.
FSR100, FSR200, FSR400 Ready Split Sleeves
SPECIFIED TECHNOLOGIES INC -
+ - When opening is greater than the min opening size specified,
steel fasteners are required.
FS200, FS201, FS400 and FS401 SpecSeal Ready Split Sleeves
SPECIFIED TECHNOLOGIES INC -
DWG. #
DATE:
CHECKED BY:
DRAWN BY: SAO
JF
3/26/02
ED-14A
ED-14A
TITLE:
GYPSUM WALL SECTIONS
TYPICAL FIRESTOPPING DETAIL
1 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
1. GYPSUM WALLBOARD WALL - WALL THICKNESS MAY VARY.
2
3
1
2. METALLIC PIPE OR CONDUIT - NOMINAL 4 INCH DIAMETER
OR SMALLER SCH. 5 OR HEAVIER STEEL PIPE, EMT OR RMC.
3. NELSON LBS SEALANT - APPLIED TO FILL THE ANNULAR SPACE
AROUND PIPE TO A MINIMUM 5/8 INCH DEPTH. APPLY AN
ADDITIONAL 3/8" BEAD OF LBS AROUND THE PIPE AT ITS
INTERFACE WITH BOTH WALL SURFACES. NOMINAL 1/2
POLYURETHANE BACKER ROD MAY BE USED TO CONTROL
DEPTH OF SEALANT.
THE SYSTEM DESCRIBED IN THIS DETAIL HAS TESTED
SUCCESSFULLY TO ASTM E814 AND ANSI/UL 1479 AND
HAS ACHIEVED F AND T RATINGS AS SHOWN
IN THE ILLUSTRATION BOX.
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
CONCRETE OR WALL SECTIONS
TYPICAL FIRESTOPPING DETAIL
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
ED-14B
ED-14B
3/26/02
JF
SAO
4
2
1
3
1. CONCRETE FLOOR OR WALL ASSEMBLY - MINIMUM 4-1/2 INCH THICK
LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE FLOOR OR
WALL OR CMU BLOCK WALL. ANNULAR SPACE MAY RANGE FROM
1/2 INCH TO 2-1/4 INCHES.
3. FORMING MATERIAL - MINIMUM 4 INCH THICKNESS OF
MINIMUM 4 PCF MINERAL WOOL OR CERAMIC FIBER TIGHTLY PACKED
INTO OPENING AND RECESSED 1/2 INCH FROM TOP SURFACE OF FLOOR OR
BOTH WALL SURFACES.
4. NELSON LBS SEALANT - APPLY LBS OVER THE FORMING MATERIAL
TO A MINIMUM 1/2 INCH DEPTH, FLUSH WITH TOP SURFACE OF FLOOR
OR BOTH WALL SURFACES.
THE SYSTEM DESCRIBED IN THIS DETAIL HAS TESTED
SUCCESSFULLY TO ASTM E814 AND ANSI/UL 1479 AND
HAS ACHIEVED F AND T RATINGS AS SHOWN
IN THE ILLUSTRATION BOX.
2. METALLIC PIPE OR CONDUIT - NOMINAL 4 INCH DIAMETER
OR SMALLER EMT.
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
FOR GROUND WIRE IN CONDUIT
TYPICAL BONDING DETAIL
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
JF
3/26/02
ED-15A
ED-15A
#6 (MIN.) GROUND WIRE
GROUND LUG (TYP.)
GROUND CLAMP (TYP.)
WIRE EXITING CONDUIT
CONDUITWIRE ENTERING CONDUIT
BOLT CONNECTOR (TYP.)
#6 (MIN.) GROUND WIRE
#6 (MIN.) GROUND WIRE
#6 (MIN.) GROUND WIRE
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
BACKBONE CABLE SHIELDS DETAIL
1 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
ED-15B
ED-15B
3/26/02
JF
SAO
READY TO:
TERMINATE PAIRS
BOND SHIELD
PLACE:
OUTER CLAMP
FLAT WASHER
LOCK WASHER
NUT
TIGHTEN SECURELY
CUT SHEATH AND SHIELD
WITH TABBING SHEARS
PLACE INNER CLAMP BETWEEN
TAPE AND SHEILD
#6 (MIN.) GROUND WIRE TO BUSBAR
DO NOT REMOVE CORE
WRAP
WRAP TWO LAYERS OF
VINYL TAPE STICKY SIDE OUT
AND PUSH DOWN UNDER CABLE SHIELD
WRAP WITH TWO HALF-LAPPED
LAYERS OF VINYL TAPE
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
TMGB AND TGB BUSBAR DETAIL
GROUNDING AND BONDING
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
JF
3/26/02
ED-15C
ED-15C
#6 (MIN.) GROUND WIRE
OR #10 COUPLED BONDING
CONDUCTOR (CBC), (TYP.)
BUSBAR
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
CIRCA 1880B1-100 TIE
ELEVATION HARDWARE DETAIL
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
ED-16A
ED-16A
4/10/02
JF
SAO
CABLENUMBER
CABLENUMBER
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
CIRCA 1880B1-100 TIE/RISER
ELEVATION HARDWARE DETAIL
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
JF
4/10/02
ED-16B
ED-16B
CABLENUMBER
CABLENUMBER
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
TERMINATION LAYOUT - ER's
TYPICAL ISP BACKBONE FIBER
1 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
4/03/02
SAO
FTL-1
PR
FTL-1
B
SM
FROM 1st
TC
FROM 4th
TC
2
6
4
A
N
K
B
L
A
N
K
B
L
A
N
K
B
LL
B
K
N
A
B AB AB AB AB AB AAB
MM SM MM SM MM SM MM
FROM 4th
TC
FROM 3rd
TC
FROM 2nd
TC
4 3
6 5
12
4 3
6 5
12
4 3
6 5
12
4 3
6 5
12
4 3
6 5
12
4 3
6 5
12
4 3
6 5
12
SM MM
FROM 1st
TC
SM MM
FROM 2nd
TC
SM MM
FROM 3rd
TC
SM MM
ABAB
B
L
A
N
K
B
L
A
N
K
B AAB
K
N
A
L
B
B AB AB AB A
O
N
I
T
S
I
O
P
A
1
5
3
B
L
A
N
K
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
TERMINATION LAYOUT - TR's
TYPICAL ISP BACKBONE FIBER
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
PR
4/03/02
FTL-2
FTL-2
B
A
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
A
B
MM
R
W
MM
O
SM
SM
MM
MM
A
B
A
B
26
4
1
5 3
B
A
26
4
1
5 3
B
A
26
4
1
5 3
S.A.O.
FTL-3
DWG. #
CHECKED BY:
DRAWN BY:
DATE:
MS
4/03/02
FTL-03
TITLE:
ADM 2/10/14REVISED BY:
1 ADM
11/19/19UPDATED PER LATEST STANDARDS
DH
TYPICAL OSP FIBER
TERMINATION LAYOUTS
C-C (HOLDS 72)
B-C (HOLDS 72)
WALL MOUNTED SPLICE CABINET
A-C (HOLDS 72)
C-C - SENDING END (0SM/6MM)
B-C - B END (0SM/6MM)
A-C - A END (0SM/6MM)
B-C (0SM/6MM)
FIBEROPTIC SPLICE CASE
A-B (24SM/0MM)
C-C - SENDING END (12SM/24MM)
B-C - B END (12SM/24MM)
C-C - RECEIVING END (0SM/6MM)
B-C - C END (0SM/6MM)
A-C - C END (0SM/6MM)
A-C - A END (12SM/24MM)
A-C - A END (0SM/24MM)
MM
MM
MM
V-V (132SM/12MM)
A-A (132SM/12MM)
SMSM MMSM
A-B - (36SM/0MM)
OR
BL
SM
BL
OR
SM
A-C FOR SPLIT ER
A-B - (36SM/36MM)
MMSM SM
SM / MM
SM MMSM
B-B (36SM/36MM)
A-A (132SM/12MM) AT DAVIDSON
MM
V-V (132SM/12MM) AT DAVIDSON
SM SM SM SMSMSM SMSMSMSMSM
A-C - C END (12SM/24MM)
B-C - C END (12SM/24MM)
C-C - RECEIVING END (12SM/24MM)
MM
SM
SM MM
DWG. #
DATE:
CHECKED BY:
DRAWN BY:
TITLE:
INSTALLATION DETAIL
TYPICAL RISER POLE GUARD
1 ADM
11/19/19 UPDATED PER LATEST STANDARDS
DH
SAO
PR
5/09/02
RP-01
RP-1
EXTRA HIGH STRENGTH (EHS)
GALVANIZED STEEL SUSPENSION
STRAND
UTILITY POLE
2'
MINIMUM
LASHING WIRE CLAMP
PVC RISER DUCT
(POLE GUARD)
SEE NOTE 3
1'-6"
MAXIMUM
PVC CONDUIT TO RISER FITTING
PLUG CONDUIT AROUND
INNERDUCTS
ATTACH WITH 1/4" x 3"
LAG BOLTS (SEE NOTE 1)
NOTES:
1.
ATTACH POLE GUARD TO POLE USING 1/4" X 3" LAG BOLTS.
ATTACH 6" FROM EACH END OF GUARD AT EVERY 18".
EXTEND INNERDUCTS, TO POLE STRAND ATTACHMENT POINT.
EXTEND INNERDUCT A MINIMUM OF 24" PAST POLE. PLUG
INNERDUCT.
2.
PLUG END OF
RISER DUCT
IF USING METALLIC RISER DUCT, PROVIDE GROUND WIRE, AS
REQUIRED.
3.
FIBER CABLE
LASHING WIRE
(3) INNERDUCTS (SEE NOTE 2)
RESPONSE TO PATP - ###4/10/02GTM.P.
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
RESPONSE TO PATP - ###4/10/02GTM.P.
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
WP1
WP2
WP5
WP10
WP13
WP14
RESPONSE TO PATP - 234A4/10/02P.R.M.P.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2 3
4 1
3
2 1
1. REFER TO TELECOM FLOOR PLANS FOR WP TYPE, QUANTITY AND LOCATIONS.
REFER TO TELECOM FLOOR PLANS FOR STATION AND BACKBONE CABLE ROUTES.2.
ALL PENETRATIONS, EXCEPT FOR CONDUITS, SHALL REQUIRE A SLEEVES. PROVIDE
FIRESTOPPING FOR ALL CONDUIT AND SLEEVE PENETRATIONS.
3.
RESPONSE TO PATP - ###4/10/02GTM.P.
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
BACKBONE CABLE SHIELDSTYPICAL BONDING FOR GROUND WIRE IN CONDUIT
GROUNDING & BONDING RISER DIAGRAM
PBB & SBB BUSBAR DETAIL
1001D
1035D2001D
2005D2009D 2019D
2033D
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
RESPONSE TO PATP - ###4/5/02G.T.M.P.1
N.T.S.
VIEW A-A
T.M.G.B.
VIEW B-B
N.T.S.
EQUIPMENT ROOM 115 LAYOUT
SCALE: 3/8" = 1'-0"
9'-2"
10'
12'
3'-6"
4'-5"
SWDP
(1U) WIRE MANAGER
TYP 2 PLACES
VIEW C-C
N.T.S.
EQUIP. RACK
OSP/ISP
TYPICAL LAYOUT - FIELD VERIFIED
TYPICAL
FIELD VERIFIED
(1) 110 C5 CONNECTING BLOCK
4 PAIR CROSS CONNECT
TO VOICE BACKBONE
FROM VOICE STATION
(5) 110 C4 CONNECTING BLOCKS
TH-XXXX-XXX-XXX
1 PR 25 PR
3005D3009D
3035D
3015D
3019D
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
RESPONSE TO PATP - ###4/5/02G.T.M.P.1
N.T.S.
VIEW A-A
T.G.B.
VIEW B-B
N.T.S. N.T.S.
VIEW C-C
TELECOMMUNICATIONS ROOM XXX LAYOUT
SCALE: 3/8" = 1'-0"
9'-2"
10'
12'
3'-6"
4'-11"
SWDP
(1U) WIRE MANAGER
TYP 3 PLACES
EQUIP. RACK
ISP
TYPICAL LAYOUT - FIELD VERIFIED
TYPICAL
LAYOUT -
FIELD VERIFIED
RESPONSE TO PATP - 234A4/10/02P.R.M.P.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
CRV-8500-4
CRV-8500-4
CRV-8500-1
CRV-8500-1
TH-8500-115-200
TH-8500-115-200
CRV-8500-1
CRV-8500-1
(5) 110 C5 CONNECTING BLOCKS
1 PAIR CROSS CONNECT
TO DEMARC (BY OTHERS)
TO DEMARC (BY OTHERS)
1 PAIR CROSS CONNECT
(5) 110 C4 CONNECTING BLOCKS (1) 110 C5 CONNECTING BLOCK
TH-8500-345-200
TH-8500-345-200
(1) 110 C5 CONNECTING BLOCK
FROM VOICE STATION TO
1 PAIR CROSS CONNECT
VOICE TIE (BY OTHERS)
(5) 110 C4 CONNECTING BLOCKS
(5) 110 C5 CONNECTING BLOCKS
(1) 110 C5 CONNECTING BLOCK
4 PAIR CROSS CONNECT
FROM VOICE STATION
TO VOICE BACKBONE
(5) 110 C4 CONNECTING BLOCKS
CRV-8500-4
CRV-8500-4
VOICE TIE (BY OTHERS)
FROM VOICE BACKBONE TO
1 PAIR CROSS CONNECT
(5) 110 C4 CONNECTING BLOCKS
FROM VOICE STATION
4 PAIR CROSS CONNECT
TO VOICE BACKBONE
(1) 110 C5 CONNECTING BLOCK
RESPONSE TO PATP - 234A4/10/02P.R.M.P.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
(1) 100 PR. VOICE BACKBONE
CRV-xxxx-1
CRV-xxxx-1
CRV-xxxx-1
CRV-xxxx-7
CRV-xxxx-7
CRV-xxxx-7
CRV-xxxx-7
CRV-xxxx-7
CRV-xxxx-7
CRV-xxxx-7
CRV-xxxx-7
(1) 400 PR. VOICE BACKBONE
CRV-xxxx-7
110 BLOCK TO BE LABELED WITH BACKBONE CABLE ID (CRV-xxxx-x), STATION CABLE IDENTIFIERS (xxxV) AND WITH PAIR
COUNT OF BACKBONE CABLE (IN GROUPS OF 25: 1, 25, 26, 50, etc.).
110 BLOCK TO BE LABELED WITH BACKBONE CABLE ID (CRV-xxxx-x), STATION CABLE IDENTIFIERS (xxxV) AND WITH PAIR
COUNT OF BACKBONE CABLE (IN GROUPS OF 25: 1, 25, 26, 50, etc.).
WHEN A BACKBONE CABLE SPANS MULTIPLE 110 BLOCKS, LABELS ON 110 BLOCKS SHALL MATCH PAIR COUNT OF THE
BACKBONE CABLE (PAIR COUNT ON FIRST BLOCK STARTS AT 1, PAIR COUNT ON SUBSEQUENT BLOCKS STARTS WHERE THE
PREVIOUS BLOCK LEFT OFF: 1 THRU xxx ON FIRST BLOCK, xxx+1 THRU yyy ON SECOND BLOCK, etc. UP TO FINAL PAIR OF THE
BACKBONE CABLE).
(4) 1 PAIR CROSS CONNECTS TO
STATIONS IN TR
(BY COMMUNICATIONS CONTRACTOR),
1 PAIR CROSS CONNECTS TO
TIE/PBX IN ER
(BY OTHERS)
(4) 1 PAIR CROSS CONNECTS TO
STATIONS IN TR
(BY COMMUNICATIONS CONTRACTOR),
1 PAIR CROSS CONNECTS TO
TIE/PBX IN ER
(BY OTHERS)
CRV-xxxx-4
CRV-xxxx-4
CRV-xxxx-3
CRV-xxxx-3
110 BLOCK TO BE LABELED WITH BACKBONE CABLE ID (CRV-xxxx-x), STATION CABLE IDENTIFIERS (xxxV) AND WITH PAIR
COUNT OF BACKBONE CABLE (IN GROUPS OF 25: 1, 25, 26, 50, etc.).
FOR MULTIPLE BACKBONE CABLES, LABELS ON 110 BLOCKS SHALL MATCH PAIR COUNT OF THE INDIVIDUAL BACKBONE
CABLES (START PAIR COUNTS AT 1 FOR EACH CABLE).
110 BLOCK TO BE LABELED WITH TIE CABLE ID (CRV-xxxx-x) AND WITH PAIR COUNT OF TIE CABLE (IN GROUPS OF 5 PAIRS: 1,
5, 6, 10, 11, 15, 16, etc.).
FOR MULTIPLE TIE CABLES, LABELS ON 110 BLOCKS SHALL MATCH PAIR COUNT OF THE INDIVIDUAL TIE CABLES (START PAIR
COUNTS AT 1 FOR EACH CABLE).
CRV-xxxx-5
CRV-xxxx-5
CRV-xxxx-6
CRV-xxxx-6
2.
1.
1 PAIR CROSS CONNECT TO
DEMARC IN EF AND
TO PBX/BACKBONE/STATIONS
IN ER (BY OTHERS)
1.
2.
(1) 100 PR. VOICE TIE CABLE
CRV-xxxx-5
2.
1.
(1) 100 PR. VOICE TIE CABLE
CRV-xxxx-6
(4) 1 PAIR CROSS CONNECTS TO
STATIONS IN TR
(BY COMMUNICATIONS CONTRACTOR),
1 PAIR CROSS CONNECTS TO
TIE/PBX IN ER
(BY OTHERS)
1.
(1) 100 PR. VOICE BACKBONE
CRV-xxxx-3
(1) 100 PR. VOICE
BACKBONE
CRV-xxxx-4
1 PAIR CROSS CONNECT TO
DEMARC IN EF AND
TO PBX/BACKBONE/STATIONS
IN ER (BY OTHERS)
CRV-xxxx-8
CRV-xxxx-8
CRV-xxxx-2
CRV-xxxx-2
CRV-xxxx-8
CRV-xxxx-8
CRV-xxxx-8
CRV-xxxx-8
CRV-xxxx-8
CRV-xxxx-8
(1) 400 PR. VOICE TIE CABLE
CRV-xxxx-8
110 BLOCK TO BE LABELED WITH TIE CABLE ID (CRV-xxxx-x) AND WITH PAIR COUNT OF TIE CABLE (IN GROUPS OF 5 PAIRS: 1,
5, 6, 10, 11, 15, 16, etc.).
110 BLOCK TO BE LABELED WITH TIE CABLE ID (CRV-xxxx-x) AND WITH PAIR COUNT OF TIE CABLE (IN GROUPS OF 5 PAIRS: 1,
5, 6, 10, 11, 15, 16, etc.).
WHEN A TIE CABLE SPANS MULTIPLE 110 BLOCKS, LABELS ON 110 BLOCKS SHALL MATCH PAIR COUNT OF THE TIE CABLE
(PAIR COUNT ON FIRST BLOCK STARTS AT 1, PAIR COUNT ON SUBSEQUENT BLOCKS STARTS WHERE THE PREVIOUS BLOCK
LEFT OFF: 1 THRU xxx ON FIRST BLOCK, xxx+1 THRU yyy ON SECOND BLOCK, etc. UP TO FINAL PAIR OF THE TIE CABLE).
1.
2.
1 PAIR CROSS CONNECT TO
DEMARC IN EF AND
TO PBX/BACKBONE/STATIONS
IN ER (BY OTHERS)
1.
(1) 100 PR. VOICE TIE CABLE
CRV-xxxx-2
FOR LABELING INFO.
SEE NOTE #5
TYPICAL WP
FOR LABELING INFO.
SEE NOTE #3
1001C1001D 1002D
1002V1001V
FOR LABELING INFO.
SEE NOTES #4B & #6B
GROUNDING LABELING:
1. GROUND BARS WILL BE LABELED WITH A PANDUIT PLL22P01.
TMGB OR TGB-THE # OF THE GND BAR AND THE BUILDING.
2. GROUND CONDUCTORS WILL BE LABELED WITH A PANDUIT PLL-11-Y3-2.5
A.) BONDING CONDUCTORS (FROM TMGB TO THE TGB'S OR SERVICE GND AND
BLDG STEEL) WILL BE BC AND A SEQUENTIAL NUMBER THROUGHOUT THE ROOM.
B.) EQUIPMENT BONDING CONDUCTOR (LADDER RACKS FREESTANDING, SWING GATE, AND
CONDUITS) EC AND A SEQUENTIAL NUMBER THROUGHOUT THE ROOM.
C.) CABLE BONDING CONDUCTOR (THE BONDING CONDUCTOR THAT IS RUN
WITH THE BACKBONE CABLE) CC AND THE NUMBER OF THE TIE OR
RISER CABLE IT IS ASSOCIATED WITH.
FIBER LABELING:
THE LABEL WILL BE A P-TOUCH TZ-3/4" TAPE FROM THE P-TOUCH PT330 MACHINE.
1.) INSIDE PLANT LABEL WILL BE AS FOLLOWS:
CONNECTOR PANEL LOCATION IN HOUSING-CRF-BUILDING#-SEQUENTIAL#-TUBE#(s)
TO:RM# IT IS FEEDING.
2.) OUTSIDE PLANT LABEL AS FOLLOWS:
CONNECTOR PANEL LOCATION IN HOUSING-CBF-CAMPUS NAME-CABLE#-TUBE COLOR
TO:BLDG# - BLDG. NAME IT IS FEEDING.
8.
TERMINATION HARDWARE NUMBERS AND RACK NUMBER.
PANDUIT PLL22P01 WHITE.
THE TERMINATION HARDWARE NUMBERS WILL BE DETERMINED
THE FOLLOWING WAYS:
A.) DATA PATCH PANEL TH-BUILDING#-ER/TR ROOM#-100 THROUGH 199.
B.) VOICE PUNCHDOWN BLOCK (RISER) CRV-BUILDING#-SEQUENTIAL#
(TO MATCH RISER CABLE NUMBER).
C.) VOICE PUNCHDOWN BLOCK (TIE) CRV-BUILDING#-SEQUENTIAL#
(TO MATCH TIE CABLE NUMBER).
D.) VOICE PUNCHDOWN BLOCK (STATION) TH-BUILDING#-ER/TR ROOM#-200 THROUGH 299.
E.) ISP FIBER TH-BUILDING#-ER/TR ROOM#-300 THROUGH 399.
F.) OSP FIBER TH-BUILDING#-ER/TR ROOM#-400 THROUGH 499.
G.) VIDEO TH-BUILDING#-ER/TR ROOM#-500 THROUGH 599.
TIE, RISER AND BACKBONE CABLE SLEEVE.
PANDUIT SLCT-WH WHITE SELF-LAMINATING CABLE MARKER HOLDER
PANDUIT RECOMMENDED LABELS FOR THE MARKER HOLDER
(PLL-17-Y2-1) AND (JL41PO-0.2)
THE VOICE CABLE (RISER & TIE) ID WILL BE CRV-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE VOICE CABLE (BACKBONE) ID WILL BE CBV-CAMPUS NAME-SEQUNETIAL NUMBER.
THE FIBER CABLE (RISER) ID WILL BE CRF-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE FIBER CABLE (BACKBONE) ID WILL BE CBF-CAMPUS NAME-SEQUNETIAL NUMBER.
THE COAX CABLE (RISER) ID WILL BE CRC-BUILDING NUMBER-SEQUENTIAL NUMBER.
THE COAX CABLE (BACKBONE) ID WILL BE CBC-CAMPUS NAME-SEQUNETIAL NUMBER.
EACH DATA PATCH PANEL PORT WILL BE LABELED IN THE CENTER OF THE PATCH PANEL
PANDUIT TYPE CPPLF-5 WHITE.
EACH VOICE, DATA, COAX CABLE AND GROUND WIRE THAT IS PULLED WILL BE
LABELED ON BOTH ENDS OF THE CABLE WITH A COMPUTER GENERATED WRAP
AROUND CABLE PANDUIT LABEL #PLL-11-Y3-2.5
EACH 110 PUNCH DOWN BLOCK.
A.)PANDUIT DS110 FOR THE RISER CABLE. (WHITE)
B.)PANDUIT DS110-BU FOR THE HORIZONTAL CABLES. (BLUE)
C.)PANDUIT DS110-GR FOR THE TIE CABLE. (GREEN)
7.
6.
5.
EACH FACEPLATE WILL BE LABELED WITH THE FOLLOWING LABEL:
PANDUIT TYPE JLEFPS-1 FOR A SINGLE GANG PLATE
PANDUIT TYPE JLEFPD-1 FOR A DOUBLE GANG PLATE
4.
A)
3.
2.
1.
FACEPLATE LABELS CAN BE SHOWN AS FOLLOWS.
P-TOUCH PT-330 OR EQUAL
P-TOUCH TAPES TZ 9MM BLACK ON WHITE.
FONT SIZE IS 13 BOLD.
DATA STATION
VOICE STATION
COAX STATION
VOICE RISER
FIBER OPTIC RISER
COAX RISER
RISER CONDUIT DETAIL
CC
#2
8Aerial-RegularPanduit DS1104. Riser 110 Block
FOR LABELING INFO.
SEE NOTE #5
BoldPanduit SLCT-WH sleeve with P-Touch Label22. Fiber Optic Riser Cable
OSP Fiber terminations
OSP Fiber Cabinet TH
ISP Fiber terminations
ISP Fiber Cabinet TH
WP Station Double Gang
WP Station Single Gang
WP Station Double Gang
WP Station Single Gang
13.
20.
21.
18.
19.
Coax Riser Cable
Voice Riser Cable
Coax Station Cable
Voice Station Cable
17.
16.
14.
15.
Data Station Cable
Ground Cable
Ground Bar ID
11.
12.
10.
9.
Rack Panduit
8.
7.
5.
6.
Station 110 Block
Aerial Black-RegularPanduit PLL22P01
P-Touch Tape TZ-SE4 18MM Black on White
SLCT-WH sleeve with P-Touch Label
Panduit SLCT-WH sleeve with P-Touch Label
Panduit PLL-11-Y3-2.5
Panduit PLL-12-Y3-2.5
Panduit PLL-11-Y3-2.5
Panduit PLL-11-Y3-2.5
Panduit PLL22P01
Aerial Black-Regular
Aerial Black-Regular
Bold
Bold
Bold
Aerial Black-Regular
Aerial Black-Regular
Aerial Black-Regular
P-Touch Tape TZ-SE4 18MM Black on White
P-Touch Tape TZ-231 9MM Black on White
P-Touch Tape TZ-231 9MM Black on White
Panduit JLEFPD-1
Panduit PLL22P01
Panduit PLL22P01
Panduit JLEFPS-1
Panduit DS110-BU
Aerial Black-Regular
Aerial Black-Regular
Aerial Black-Regular
Bold
Bold
Aerial Black-Regular
Bold
Aerial-Regular
13
FOR LABELING INFO.
SEE NOTE #1
FOR LABELING INFO.
SEE NOTE #1
FOR LABELING INFO.
SEE NOTE #1
CRV-6617-2
24
13
13
12
12
12
12
24
10
24
10
24
11
12
13
8
13
1001C
CLOSET CONNECTOR HOUSING PANELS
SIECOR
12
53 7
64 8
11 12
9 10
7 8
SIE
CO
R
9 11
10
12
Equipment/Cable
2.
3.
1.
Patch Panel
Tie 110 Block
Patch Panel Port
VOICE STATION CABLE
110 DETAIL
Label
Panduit DS110-GR
Panduit PLL22P01
Panduit CPPLF-5
Font
Aerial-Regular
Aerial Black-Regular
Aerial Black-Regular
BLUE LABELS
FOR LABELING INFO.
SEE NOTE #5
CRF-6617-2
FOR LABELING INFO.
SEE NOTE #5
CRC-6617-2
Size
24
8
10
FOR LABELING INFO.
SEE NOTE #1
CR
V-6617-1
CR
V-6617-2
EC
#6
CC
#1
5 6
43
1 2
1001D 1001D
CRV-6617-2
1001V1001V
1001C
CRF-6617-2
VOICE RISER
FIBER RISER
CRC-6617-2
VIDEO RISER
CR
V-6617-3
EC
#7
CC
#3
FOR LABELING INFO.
SEE NOTE #5
SEE NOTE #8
FOR LABELING INFO.
SEE NOTE #6E
SEE NOTE #8
FOR LABELING INFO.
SEE NOTE #6F
FOR LABELING INFO.
SEE NOTES #4C & #6B
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTES #4A & #6B
FOR LABELING INFO.
SEE NOTE #1 & #7
NOTES:
FOR LABELING INFO.
SEE NOTE #7
TGB #01
FOR LABELING INFO.
SEE NOTE #6A
FOR LABELING INFO.
SEE NOTE #2
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #5
FOR LABELING INFO.
SEE NOTE #6
SEQUENTIAL NUMBER PER ROOM
INSIDE PLANT FIBER CABINET
OUTSIDE PLANT FIBER CABINET
TIE CABLE
VOICE TIE CABLE
110 DETAIL
CR
V-6
61
7-2
GREEN LABELS
VOICE RISER CABLE
110 DETAIL
F-CRF-6617-6 TUBE(S)3,4 TO:RM344B-CRF-6617-1 TUBE(S):3 TO:RM004
C-CRF-6617-2 TUBE(S)1,2 TO:RM215
D-CRF-6617-2 TUBE(S)3 TO:RM215
E-CRF-6617-5 TUBE(S)1,2 TO:RM344A-CRF-6617-1 TUBE(S):1,2 TO:RM004
TH-6617-003-300
F-B-CBF-BUS-1-OR TO:BLDG#6618-JONES HALL
C-
D-
A-CBF-BUS-1-BL TO:BLDG#6618-JONES HALL
TH-6617-003-400
E-CBF-BUS-1-YL TO:BLDG#6618-JONES HALL
SCAPELAN
SCAPELAN
RISER CABLE
CR
V-6
61
7-1
WHITE LABELS
FOR LABELING INFO.
SEE NOTE #7
EC
#6
EC
#7
TMGB #01
FOR LABELING INFO.
SEE NOTES #1 & 7
CC
#1
CC
#2
CC
#3
BC
#1
EC
#3
EC
#8
EC
#9
TMGB GROUND BAR
CB
F-B
US
-1
1024D
DATA PATCH PANEL
CR
F-6617-3
EC
#11
EC
#10
CC
#01
CC
#02
BC
#01
CC
#03
TGB GROUND BAR
TH-6617-003-100
1029D1030D
1005D1006D
1036D1035D
1011D1012D 1023D1017D1018D
1025D
1001D
1028D
1004D
1027D
1003D
1034D
1010D
1033D
1009D 1021D1022D1015D1016D
1026D
1002D
1032D1031D
1007D1008D 1019D1020D1013D1014D
EQUIPMENT RACK
SIECOR
SIECOR
RACK #1
CC
#4
EC
#2
BC
#2
CRV-6617-2
CRV-6617-2
TH-6617-003-202
TH-6617-003-202
CRV-6617-1
CRV-6617-1
RESPONSE TO PATP - 234A4/10/02P.R.M.P.
NOTE TO BIDDERS:
AS-BUILTS TO BE
HAND DRAWN
MARK-UPS OF
SHOP DRAWINGS.
2ADM 11/19/19
UPDATED PER LATEST STANDARDSDH
1
2" F.A.B.C. (TYP. FOR FINAL ASPHALT
4" STABILIZER BASE
6" DENSE GRADED AGGREGATE SUBBASE
12" TO 18"
2'-6" MIN.
4"
(TYP.)
4"
(TYP.)
"COMMUNICATIONS" METALLIC WARNING TAPE
COMPACTED EXCAVATED MATERIALS
CONCRETE ENCASEMENT
4" SCH. 40 PVC CONDUIT (TYP.)
(3) 1 1/4" INNERDUCT
12" TO 18"
4"
(TYP.)
4"
(TYP.)
2"
TO
4"
2'-0" MIN.
4" OF 3/4" CRUSHED STONE
"COMMUNICATIONS" METALLIC WARNING TAPE
COMPACTED EXCAVATED MATERIALS
CONCRETE CAP 6" NOM. THICK
SAND
4" SCH. 40 PVC CONDUIT (TYP.)
(3) 1 1/4" INNERDUCT
2'-0" MIN.
4"
(TYP.)
4"
(TYP.)
2"
TO
4"
(3) 1 1/4" INNERDUCT
4" SCH. 40 PVC CONDUIT (TYP.)
CONCRETE CAP 6" NOM. THICK
SAND
COMPACTED EXCAVATED MATERIALS
"COMMUNICATIONS" METALLIC WARNING TAPE
12" TO 18"
RESTORED GRASS
2-4" CONDUIT TRENCH
2'-6" MIN.
12" TO 18"
COMPACTED EXCAVATED MATERIALS
4"
(TYP.)
4"
(TYP.)
(3) 1 1/4" INNERDUCT
4" SCH. 40 PVC CONDUIT (TYP.)
CONCRETE ENCASEMENT
"COMMUNICATIONS" METALLIC WARNING TAPE
4" STABILIZER BASE
2" F.A.B.C.
2'-0" MIN.
12" TO 18"
4"
(TYP.)
4"
(TYP.)
4" SCH. 40 PVC CONDUIT (TYP.)
CONCRETE CAP 6" NOM. THICK
SAND
COMPACTED EXCAVATED MATERIALS
"COMMUNICATIONS" METALLIC WARNING TAPE
4" OF 3/4" CRUSHED STONE
(3) 1 1/4" INNERDUCT
(3) 1 1/4" INNERDUCT
2'-0" MIN.
CONCRETE CAP 6" NOM. THICK
4" SCH. 40 PVC CONDUIT (TYP.)
4"
(TYP.)
4"
(TYP.)
SAND
"COMMUNICATIONS" METALLIC WARNING TAPE
COMPACTED EXCAVATED MATERIALS
12" TO 18"
RESTORED GRASS
4-4" CONDUIT TRENCH
1-4" CONDUIT TRENCH
SAME AS ABOVE DETAILS
LESS ONE (1) 4" PVC CONDUIT.
3-4" CONDUIT TRENCH
SAME AS ABOVE DETAILS
LESS ONE (1) 4" PVC CONDUIT.
2" F.A.B.C.
4"
(TYP.)
4"
(TYP.)
12" TO 18"
2'-6" MIN.
4" STABILIZER BASE
"COMMUNICATIONS" METALLIC WARNING TAPE
CONCRETE ENCASEMENT
4" SCH. 40 PVC CONDUIT (TYP.)
(3) 1 1/4" INNERDUCT
COMPACTED EXCAVATED MATERIALS
2'-0" MIN.
12" TO 18"
4"
(TYP.)
4"
(TYP.)
4" 3/4" CRUSHED STONE
"COMMUNICATIONS" METALLIC WARNING TAPE
COMPACTED EXCAVATED MATERIALS
SAND
4" SCH. 40 PVC CONDUIT (TYP.)
(3) 1 1/4" INNERDUCT
2'-0" MIN.
4"
(TYP.)
4"
(TYP.)
12" TO 18"
RESTORED GRASS
2"
TO
4"
2"
TO
4"
2"
TO
4"
2"
TO
4"
5-4" CONDUIT TRENCH
6-4" CONDUIT TRENCH
SAME AS ABOVE DETAILS
LESS ONE (1) 4" PVC CONDUIT.
"COMMUNICATIONS" METALLIC WARNING TAPE
COMPACTED EXCAVATED MATERIALS
(3) 1 1/4" INNERDUCT
"COMMUNICATIONS" METALLIC WARNING TAPE
CONCRETE CAP 6" NOM. THICK
SAND
4" SCH. 40 PVC CONDUIT (TYP.)
RESTORE WALK, MATCH
ASPHALT OR 4"
CONCRETE (3,500 PSI) WITH
6 X 6 #10 W.W. MESH
RESTORE WALK, MATCH
ASPHALT OR 4"
CONCRETE (3,500 PSI) WITH
6 X 6 #10 W.W. MESH
RESTORE WALK, MATCH
ASPHALT OR 4"
CONCRETE (3,500 PSI) WITH
6 X 6 #10 W.W. MESH
TYPICAL ASPHALT DETAILS (1 HOUR SETUP)
NOTES:
1. ALL ELEVATIONS/DEPTHS ARE FROM O.G.
2. CONDUIT INSTALLATION PROCEDURE:
A. SAWCUT AND REMOVE EXISTING ASPHALT.
B. EXCAVATE TO REQUIRED DEPTH.
C. PLACE CONDUIT(S).
D. ENCASE CONDUIT(S) WITH CONCRETE.
E. INSTALL COMPACTED LIFTS OF SUITABLE BACKFILL
AFTER 'D'.
F. PLACE WARNING TAPE AT PROPER DEPTH.
G. CONTINUE 'E', RESTORE ASPHALT WITH SUB-BASE.
H. INSTALL (3) 1 1/4" FIBER OPTIC CABLE INNERDUCT.
TYPICAL WALKWAY DETAILS (1 HOUR SETUP)
NOTES:
1. ALL ELEVATIONS/DEPTHS ARE FROM O.G.
2. CONDUIT INSTALLATION PROCEDURE:
A. REMOVE SIDEWALK/ASPHALT.
B. EXCAVATE TO REQUIRED DEPTH.
C. PLACE CONDUIT(S) WITH SAND BED AND COVER.
D. CAP OVER CONDUIT(S) WITH CONCRETE.
E. INSTALL COMPACTED LIFTS OF SUITABLE BACKFILL
AFTER 'D'.
F. PLACE WARNING TAPE AT PROPER DEPTH.
G. CONTINUE 'E', RESTORE ASPHALT OR CONCRETE WALK.
H. INSTALL (3) 1 1/4" FIBER OPTIC CABLE INNERDUCT.
TYPICAL GRASS DETAILS (1 HOUR SETUP)
NOTES:
1. ALL ELEVATIONS/DEPTHS ARE FROM O.G.
2. CONDUIT INSTALLATION PROCEDURE:
A. REMOVE GRASS AND TOPSOIL.
B. EXCAVATE TO REQUIRED DEPTH.
C. PLACE CONDUIT(S) WITH SAND BED AND COVER.
D. CAP OVER CONDUIT(S) WITH CONCRETE.
E. INSTALL COMPACTED LIFTS OF SUITABLE BACKFILL
AFTER 'D'.
F. PLACE WARNING TAPE AT PROPER DEPTH.
G. CONTINUE 'E', RESTORE GRASS TURF.
H. INSTALL (3) 1 1/4" FIBER OPTIC CABLE INNERDUCT.
CONCRETE CAP 6" NOM. THICK
BITUMINOUS CONCRETE)
6" DENSE GRADED AGGREGATE SUBBASE 6" DENSE GRADED AGGREGATE SUBBASE