TRANSCRIPT
Remote BACnet® I/O Board
www.neptronic.com
The CMMB106 extends your BACnet network when
your application requires additional inputs and outputs
on a physical controller. Combining the 20 inputs and
outputs of the CMMB106 with your Building Automation
System provides simple expansion of a new or existing
controller and reduces unnecessary costs of additional
components.
Use the on-board override switches to manually force
the output states during start up or service calls that
demand immediate intervention on a controlled or
operated peripheral. All outputs are supervised, therefore,
if the output is “forced on” by the override switch, the
output status is sent via BACnet. On-board LEDs help
track and diagnose any input or output activity
during operation.
CMMB106Remote BACnet® I/O Board
Features
Power & Communication• 24Vac or 30Vdc supply• BACnet® MS/TP port• Modbus port (up to 2 STLD24
thermostats)Inputs & Outputs• Inputs: 8 universal and 2 digital• Outputs: 2 universal, 2 analog, and 6 digitalInstallation• 10 override switches to manually control each
output (auto, forced on, or forced off) • LED status for each input and output• DIN rail mounting• Removable, non-strip, raising clamp terminalsBACnet®• MS/TP @ 9600, 19200, 38400 or 76800 bps • Automatic baud rate detection• Automatic device instance configuration• Copy and broadcast configuration
STR1-11 10kΩ P
STC8-11 10kΩ P
SHR10 P P P
SHC80 P P P
SPD70 P
Model Temperaturesensor
Humiditysensor
DuctMount
WallMount Pressure
STR1 & STC8 SHR10 SHC80 SPD70
Accessories
www.neptronic.com120012_GB (120213)
HHeeaadd OOffffiiccee NNeeppttrroonniicc®®
400 Lebeau Blvd, Montreal, Quebec H4N 1R6Tel.: (514) 333-1433 Fax: (514) 333-3163Toll Free (Canada/USA): 1-800-361-2308
Manufacturer of actuators, actuated valves, controls, humidifiers and electric heaters.
UU..SS.. OOffffiicceeNNEEPP IInncc..
355 North Main Street, Suite 2Hiawassee, Georgia 30546
Tel.: (954) 421-6216 Fax: (954) 421-8785
MMiiddddllee EEaasstt && AAssiiaaNNEEPP IInntteerrnnaattiioonnaall
P.O. Box 125687, Dubai, UAETel.: +97155 8825487 Fax: +9714 3426772
email: [email protected]
Connections
Specifications
Power
• Input: 24 Vac or 27-33 Vdc• Consumption: 8VA (331mA @ 24 Vac)
Inputs
• 8 universal inputs (12-bit resolution): 0-10Vdc, 10KΩ (Thermistor type 3), on/off (dry contact), 4-20mA
• 2 digital inputs: NO/NC or direct/reverse
Outputs (supervised)
• 2 universal outputs (12-bit resolution): 0-10Vdc, pulsed signal (20mA drive), on/off, 4-20mA
• 2 analog outputs (12-bit resolution): 0-10Vdc
• 6 digital relay outputs (5A resistive): NO/NC with independent commonper relay
Communications
• BACnet® MS/TP @ 9600, 19200, 38400 ou 76800 bps
• BACnet® Application Specific Controller (B-ASC)
• Modbus (up to 2 STLD24 thermostats)
Wiring
• Communication: 24 AWG twisted-shield cable (Belden 9841 or equivalent)
• Electrical: 0.8 mm2 [18 AWG] minimum
Environmental
• Operational: 0ºC to 50ºC [32ºF to 122ºF]• Storage: -30ºC to 50ºC [-22ºF to 122ºF]• Relative Humidity: 5 to 95% Non condensed• Weight: 0.4 kg [0.9 lb]• Dimensions: 6.30” (160 mm) x 5.00” (126 mm) x
2.25” (57 mm)