class of fire reaction 1 (one) - pharos project · pdf filegreen metal usa llc. - 2317...

23
Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 Phone 256-489-7814 - [email protected] ENGLISH TRANSLATION OF THE TEST CERTIFICATE No. 170403/RF3588 ISSUED BY GIORDANO INSTITUTE s.p.a. - ITALY on the 31 March 2003 (Original on file. Available upon request) issued in accordance with Article 8 of the decree of the Ministry of Interior dated 26 June 1984 carrying “classification of reaction to fire and approval of materials for the purpose of fire prevention” (Ordinary supplement to the Official Journal No. 234 of 25 August 1984) amended by decree of the Ministry of Interior of 3 September 2001 (Official Journal No. 242 of 17 October 2001). With regard to the outcome of investigations executed, it is certified that the complement material produced by: ISOLANA SYSTEMS S.r.l.; Named: 3000°A; Used as: nonvisible insulation; Place of use: placed in incombustible cavity wall; it has been assigned, pursuant to the UNI 9177 (October 1987), the CLASS OF FIRE REACTION 1 (ONE) TEST REPORT UNI 8457 (October 1987) – UNI 8457/A1 (May 1996) D.M. 26/06/1984 modified with D.M. 03/09/2001 Descrip�on complement material Trade name 3000°A Prepara�on “D” method UNI 9176 (second edi�on – January 1998) Test tube posi�on ver�cal, supported by non-combus�ble support Flame applica�on �me 30 seconds Test date 03/25/2003 Test tube [no.] Time of post-combus�on Time of post-incandescence Damaged Area Dripping [s] [level] [s] [level] [mm] [level] [surveying] [level] 1 0 1 0 1 86 1 absent 1 2 0 1 0 1 81 1 absent 1 3 0 1 0 1 84 1 absent 1 4 0 1 0 1 88 1 absent 1 5 0 1 0 1 83 1 absent 1 6 0 1 0 1 92 1 absent 1 7 0 1 0 1 87 1 absent 1 8 0 1 0 1 85 1 absent 1 9 0 1 0 1 88 1 absent 1 10 0 1 0 1 90 1 absent 1 A�ributed level Category Post-combus�on �me 1 I Post-incandescence �me 1 Damaged area 1 Dripping 1 Notes: // FIRE RESISTANCE (1)

Upload: phamduong

Post on 23-Feb-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THE

TEST CERTIFICATE No. 170403/RF3588ISSUED BY GIORDANO INSTITUTE s.p.a. - ITALY on the 31 March 2003

(Original on file. Available upon request)

issued in accordance with Article 8 of the decree of the Ministry of Interior dated 26 June 1984 carrying “classification of reaction to fire and approval of materials for the purpose of fire prevention” (Ordinary supplement to the Official Journal No. 234 of 25 August 1984) amended by decree of the Ministry of Interior of 3 September 2001 (Official Journal No. 242 of 17 October 2001).With regard to the outcome of investigations executed, it is certified that the complement material produced by: ISOLANA SYSTEMS S.r.l.;

Named: 3000°A;Used as: nonvisible insulation;Place of use: placed in incombustible cavity wall;it has been assigned, pursuant to the UNI 9177 (October 1987), the

CLASS OF FIRE REACTION 1 (ONE)

TEST REPORTUNI 8457 (October 1987) – UNI 8457/A1 (May 1996)D.M. 26/06/1984 modified with D.M. 03/09/2001

Descrip�on complement materialTrade name 3000°APrepara�on “D” method UNI 9176 (second edi�on – January 1998)Test tube posi�on ver�cal, supported by non-combus�ble supportFlame applica�on �me 30 secondsTest date 03/25/2003

Test tube

[no.]

Timeof post-combus�on

Timeof post-incandescence

Damaged Area Dripping

[s] [level] [s] [level] [mm] [level] [surveying] [level]1 0 1 0 1 86 1 absent 12 0 1 0 1 81 1 absent 13 0 1 0 1 84 1 absent 14 0 1 0 1 88 1 absent 15 0 1 0 1 83 1 absent 16 0 1 0 1 92 1 absent 17 0 1 0 1 87 1 absent 18 0 1 0 1 85 1 absent 19 0 1 0 1 88 1 absent 1

10 0 1 0 1 90 1 absent 1

A�ributed level CategoryPost-combus�on �me 1

IPost-incandescence �me 1Damaged area 1Dripping 1

Notes: //

FIRE RESISTANCE (1)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

TEST REPORTUNI 9174 (October 1987) – UNI 9174/A1 (May 1996)D.M. 26/06/1984 modified with D.M. 03/09/2001

Descrip�on complement materialTrade name 3000°APrepara�on “D” method UNI 9176 (second edi�on – January 1998)Test tube posi�on wall, supported by non-combus�ble supportFlame applica�on �me 30 secondsTest date 03/25/2003

Tim

e us

ed b

y th

e fla

me

to re

ach

the

follo

win

g ta

rget

s [s

] Test tube no. 1 Test tube no. 2 Test tube no. 3Target 100mm 146 32 245Target 150mm 296 310 373Target 200mm // // //Target 250mmTarget 300mmTarget 350mmTarget 400mmTarget 450mmTarget 500mmTarget 550mmTarget 600mmTarget 650mmTarget 700mmTarget 750mmTarget 800mm

Average speed* [mm/min] 20.0 10.8 23.4Damaged area [mm] 150 150 150Post-incandescence �me [s] 0 0 0Dripping absent absent absent

(*) average speed of propagation of flame obtained by the partial average speed calculated each 50 mm starting from 100mm from the nearest board of the panel

Levels A�ributedlevel

CategoryTest tube

no. 1Test tube

no. 2Test tube

no. 3Flame propaga�on average speed 2 2 2 2

IDamaged area 1 1 1 1Post-incandescence 1 1 1 1Dripping 1 1 1 1

Notes: //

(Copy of the seal and signature as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THE

TEST CERTIFICATE N. 170737/RF3594ISSUED BY GIORDANO INSTITUTE s.p.a. - ITALY on the 11 April 2003

(Original on file. Available upon request)

issued in accordance with Article 8 of the decree of the Ministry of Interior dated 26 June 1984 carrying “classification of reaction to fire and approval of materials for the purpose of fire prevention” (Ordinary supplement to the Official Journal No. 234 of 25 August 1984) amended by decree of the Ministry of Interior of 3 September 2001 (Official Journal No. 242 of 17 October 2001).

With regard to the outcome of investigations executed, it is certified that the floor complement material produced by: ISOLANA SYSTEMS S.r.l;

Named: 3000°A;Used as: flooring;Place of use: supported by incombustible support;it has been assigned, pursuant to the UNI 9177 (October 1987), the

CLASS OF FIRE REACTION 1 (ONE)

TEST REPORTUNI 8457 (October 1987) – UNI 8457/A1 (May 1996)D.M. 26/06/1984 modified with D.M. 03/09/2001

Descrip�on floor complement materialTrade name 1500°APrepara�on “C” method UNI 9176 (second edi�on – January 1998)Test tube posi�on ver�cal, supported by non-combus�ble supportFlame applica�on �me 30 secondsTest date 04/02/2003

Test tube

[no.]

Timeof post-combus�on

Timeof post-incandescence

Damaged area Dripping

[s] [level] [s] [level] [mm] [level] [surveying] [level]1 0 1 0 1 82 1 off 12 0 1 0 1 125 1 off 13 0 1 0 1 87 1 off 14 0 1 0 1 84 1 off 15 0 1 0 1 94 1 off 16 0 1 0 1 88 1 off 17 0 1 0 1 90 1 off 18 0 1 0 1 83 1 off 19 0 1 0 1 92 1 off 1

10 0 1 0 1 89 1 off 1

A�ributed level CategoryPost-combus�on �me 1

IPost-incandescence �me 1Damaged area 1Dripping 1

Notes: //

FIRE RESISTANCE (2)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

TEST REPORTUNI 9174 (October 1987) – UNI 9174/A1 (May 1996)D.M. 26/06/1984 modified with D.M. 03/09/2001

Descrip�on floor complement materialTrade name 1500°APrepara�on “C” method UNI 9176 (second edi�on – January 1998)Test tube posi�on floor, supported by non-combus�ble supportTest date 04/02/2003

Tim

e us

ed b

y th

e fla

me

to re

ach

the

follo

win

g ta

rget

s [s

] Test tube no. 1 Test tube no. 2 Test tube no. 3Target 100mm // // //Target 150mmTarget 200mmTarget 250mmTarget 300mmTarget 350mmTarget 400mmTarget 450mmTarget 500mmTarget 550mmTarget 600mmTarget 650mmTarget 700mmTarget 750mmTarget 800mm

Average speed* [mm/min] n.c. n.c. n.c.Damaged area [mm] < 100 < 100 < 100Post-incandescence �me [s] 0 0 0Dripping absent absent absent

(*) average speed of propagation of flame obtained by the partial average speed calculated each 50 mm starting from 100mm from the nearest board of the panel

Levels A�ributedlevel

CategoryTest tube

no. 1Test tube

no. 2Test tube

no. 3Flame propaga�on average speed 1 1 1 1

IDamaged area 1 1 1 1Post-incandescence 1 1 1 1Dripping 1 1 1 1

Notes: //

(Copy of the seal and signature as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THE

TEST REPORT N. 1631.2DC0050/07ISSUED BY LAPI LABORATORIO PREVENZIONE INCENDI s.p.a. - ITALY on the 17 January 2008

(Original on file. Available upon request)

With reference to your order, please find enclosed our Test Report, containing the results of the test effected on your material.

Trade name Test method Laboratory Ref.

DENALI 23

Thermal performance of building materials and products.Determina�on of thermal resistance by means of guarded hot plate and heat flow meter methods. Products of high and medium resistance.

1631/07

TEST METHOD: UNI EN 12667: 2002 Thermal performance of building materials and products - Determination of thermal resistance by means of guarded hot plate and heat flow meter methods - Products of high and medium thermal resistance. SPONSOR: ISOLANA SYSTEMS S.r.l on behalf of GREEN METAL USA llc - 2317 Meridian Street, Suite 20 Huntsville, AL 35811

DENOMINATION OF THE MATERIAL: 100% NATURAL WOOL INSULATION

DATA OF SAMPLE RECEIPT: 19/12/2007

_______________________________________________________________________________________

This Test Report consists of:

n. 2 pages (including this one) n. 4 attachment (application form, unrelevant. Not included in this translation, available on request)

The results reported in this Test Report exclusively to the material submitted to test and supplied by the Sponsor (Ref. Laboratory code No. 1631/07). A sample of the material has been given back to the Sponsor marked by the Laboratory.

_______________________________________________________________________________________

THERMAL RESISTANCE

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

DESCRIPTION OF THE SPECIMEN

Appearence: beige wool panel Thickness: 100 mm Side in view (*): either (*) - Information supplied by the Sponsor

APPARATUSHeat fluxmeter apparatus with calibration specimen

PROCEDURE AND DEVIATION FROM THE TEST METHODAverage measurement temperature: 21° C.Average measurement relative humidity: 50%

RESULTS

Specimens Average thickness (m)

Density (lb/�3) Thermal conduc�vity (W/m.k)

Thermal resistance(m2.K/W)

1 0.1 2.029 0.0317 3.154

2 0.1 2.028 0.0319 3.135

Average 0.1 2.029 0.0318 3.144

Note: On demand of the sponsor, the test has been executed wholly into the climatic chamber as to contain the hygroscopic value of the material to determine thermal conductivity value (See Annex No. 4)

END TEST DATE: 15/02/2008

Specimens Average thickness (inches)

Density (lb/�3) Thermal conduc�vity (W/m.k)

R-Value(°F.�2-h/Btu)

1 4” 2.029 0.0317 17.91

2 4” 2.028 0.0319 17.80

Average 4” 2.029 0.0318 17.85

(Copy of the seals and signatures as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THE

TEST REPORT NO. 04/01845ISSUED BY BUZZI LABORATORIO ANALISI - ITALY on the 25 May 2004

(Original on file. Available upon request)

SAMPLES DESCRIPTION:A) DENALI 23 (SHEEP’S WOOL INSULATION– ISOLANA I)

THIS DOCUMENT IS COMPOSED OF THE FOLLOWING ANALYTICAL RESULTS:

Test Norm PageAnalysis as agreed internal procedure – CD02 2Aging test – in wet (Jungle test) internal procedure – CT0160 2

Test results refer exclusively to the materials presented by the customer, not sampled by the laboratory.In all the pages of this test report shall be affixed the stamp of the institute. All analyzed materials are kept for three months.

ACCELERATED AGING TEST (Jungle test)

ModeTemperature 70° +/- 2°CTime 14 daysHumidity to satura�on

DeviceWater�ght glass container – On the bo�om level of 2 CM in deionized water – Sample suspended, not in contact with water – Container placed in thermo ven�lated heater.

ACCELERATED AGING TEST (in dry heat)

ModeTemperature 80° +/- 2°CTime 14 daysDevice Thermo ven�lated heater.

SCANNING ELECTRONIC MICROSCOPY OBSERVATION (SEM)(Scanning Electron Microscopy Technique)

ModeEquipment Scanning Electron Microscopy – Leica Stereoscan 100 -Prepara�on technique Metaliza�on sample (gold)

AGING TEST

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Results Sample Microscopy observa�on

DENALI 23 AFTER AGING WITH WET HEAT (JUNGLE TEST)

The sample subject to aging test with wet heat does not highlight altera�ons of the morphological characteris�cs of the wool fibers. In par�cular are not observed the degrada�on of wool fibers typical of the a�acks from mold and/or micro-organisms (rupture of the cu�cle layer [scales] with the consequent leakage of cor�cal cells).

DENALI 23 AFTER AGING WITH DRY HEAT

The sample subject to aging test with dry heat does not highlight altera�ons of the morphological characteris�cs of the wool fibers. In par�cular are not observed the degrada�on of wool fibers typical of thermal altera�on. – photos 3, 4 –

Enclosed are SEM photos and part of the examined materials.

PHOTO 1

CT 688 INSULATING PANEL AFTER ARTIFICIAL AGING IN WET CONDITION

PHOTO 2

CT 688 INSULATING PANEL AFTER ARTIFICIAL AGING IN WET CONDITION

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

PHOTO 3

CT 688 INSULATING PANEL AFTER ARTIFICIAL AGING IN DRY CONDITION

PHOTO 4

CT 688 INSULATING PANEL AFTER ARTIFICIAL AGING IN DRY CONDITION

(Copy of the seals and signatures as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THETEST REPORT NO. 146417

ISSUED BY GIORDANO INSTITUTE s.p.a. - ITALY on the 26 March 2001(Original on file. Available upon request)

Place and date of issue: Bellaria, Italy, 03/26/2001Customer: MARTINI ENTERPRISE on behalf of GREEN METAL USA llc 2317 Meridian Street, Suite 20 Huntsville, AL 35811Request test date: 03/01/2001Contract number and date: 16527, 19/03/2001Sample receipt date: 03/01/2001Test esecution date: 03/15/2001Test subject: Measure in a reverberation room of sound absorption coefficient “as” of paneling in accordance with norm ISO 354 del 1985.Test place: Istituto Giordano S.p.A. – Blocco 3 – Via Verga, 19 – 47030 Gatteo (FO), Italy.Sample origin: provided by the Customer.Sample identification in acceptance: n. 2001/284.Sample name *: The sample to test is called “ISOLANA”.

(*) according to the statements of the customer.

Sample description*The sample to test is made up of a paneling laid on the floor made by the closeness of n. 3 batts in rolls, size 1000x4000 mm and thickness 60÷70 mm, in carded wool, superficial mass 3 KG/m3.The dimensional characteristics of the sample tested are the following:

- total nominal length: 4000 MM;- total nominal width: 3000 MM;- useful acoustic surface: 12.0 m2;

(*) according to the statements of the customer.

ACOUSTIC ABSORPTION TEST

PICTURE OF THE TESTED SAMPLE

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Legal referencesThe test was performed in accordance with the requirements of norm ISO 354, 1985 “Acoustic. Measurements of sound absorption in a reverberation room” using the internal procedure of detail PP016 revision 0 of 02-29-1996 “Measure of the sound absorption coefficient in a reverberation room”.

Test equipmentFor test execution, the following equipment was used:

- power amplifier model “PWA – 202/4” of the company Masters;- loudspeaker of the company Masters;- analyzer in real time model “2123” “2123” of the company Brüel & Kajer;- microphone ø 1⁄2” model “4192” of the company Brüel & Kajer;- microphone pre-amplifiers model “2669” of the company Brüel & Kajer;- pistonophone for microphone calibration model “4220” of the company Brüel & Kajer;- completion accessories.

Test modeTest environment is made up of a reverberation room in parallelepiped shape with a rectangular base, with the following dimensional characteristics:

- plan dimensions = 8 x 6.6 m;- height “H” = 3.9 m;- base surface “S

b” = 52.8 m2;

- total surface “St” = 219.5 m2;

- volume “V” = 200 m2;

All the areas of the test environment have been treated in order to cause the maximum sound reverberation; were also present, randomly distributed and oriented, n. 11 elements slightly curved, with total land area, including both sides, about 66 m2.The test consisted in measuring times of reverberation of empty reverberation room “T

1” and of reverberation room

containing the test sample “T2” in order to determine the sound absorption coefficient “as “ of the sample; the time of

reverberation ‘T’ corresponds to the range of time, expressed in s, during which the level of sound pressure decreases of 60dB from the arrest of the source of noise. For the test is being used a generator of pink noise, a power amplifier and two dodecahedral loudspeaker omnidirectional, operating alternately to each of the six microphone positions, so to detect 12 decay of sound pressure level for each band of frequency.During the test the sample was lying on the floor of the reverberation room with the absorbing face pointing up and with the perimetric board sealed; it was also verified that the sides of sample were not parallel to the walls of the reverberation room and that were placed at a distance of not less than 1 m from the same and from every microphonic position.The measures have been made in bands of 1/

3 of eighth in the interval between 100 Hz and 5000 60hz, as requested by

norm ISO 354, 1985. The acoustic absorption coefficient “as” was calculated using the following formulas:

“as”= A/S

A = A2

- A1 = 55.3 * V/c * (1/T

2 – 1/T

1)

c = 331+0.6*t

where: as = sound absorption coefficient; A = area of sound absorption equivalent to the sample in test, expressed in m2; S = tested sample area, expressed in m2; A

2 = area of sound absorption equivalent of the reverberation room containing the tested sample, expressed in m2

A1 = area of sound absorption equivalent of the EMPTY reverberation room, expressed in m2;

V = effective useful volume of the empty reverberation room, expressed in m3. c = speed of sound propagation in the air, expressed in m/s; T

2 = time of reverberation of the reverberation room containing the tested sample, expressed in s;

T1

= time of reverberation of the empty reverberation room, expressed in s; t = temperature of the air in the reverberation room, expressed in C°.

Environmental condition during the testEnvironment average temperature = 14° CRelative humidity = 55%

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Test results

(Copy of the seals and signatures as applied onto the original)

Frequency

[Hz]T1[s]

T2[s]

V[m3]

S[m2]

T[°C]

C[m/s]

A[m2]

as

100 4.80 100 200.0 12.00 14.0 339.4 0.9 0.08125 4.12 125 200.0 12.00 14.0 339.4 3.5 0.30160 4.50 160 200.0 12.00 14.0 339.4 7.3 0.60200 4.79 200 200.0 12.00 14.0 339.4 8.4 0.70250 5.35 250 200.0 12.00 14.0 339.4 8.4 0.70315 5.96 315 200.0 12.00 14.0 339.4 10.6 0.88400 5.92 400 200.0 12.00 14.0 339.4 11.6 0.96500 5.58 500 200.0 12.00 14.0 339.4 11.8 0.99630 5.66 630 200.0 12.00 14.0 339.4 11.3 0.94800 5.10 800 200.0 12.00 14.0 339.4 12.2 1.02

1000 4.89 1000 200.0 12.00 14.0 339.4 12.4 1.041250 5.05 1250 200.0 12.00 14.0 339.4 12.2 1.021600 4.65 1600 200.0 12.00 14.0 339.4 12.5 1.042000 4.06 2000 200.0 12.00 14.0 339.4 12.8 1.062500 3.74 2500 200.0 12.00 14.0 339.4 13.0 1.093150 3.41 3150 200.0 12.00 14.0 339.4 13.8 1.154000 1.27 4000 200.0 12.00 14.0 339.4 14.3 1.195000 1.12 5000 200.0 12.00 14.0 339.4 15.3 1.27

DEVELOPMENT OF SOUND ABSORPTION COEFFICIENT “as” FOR EACH THIRD OF EIGHTH

Frequency [Hz]

Soun

d ab

sorp

�on

coe

ffici

ent “a

s”

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ATTACHMENT “A”

ATTACHMENT “A” TO THE ACOUSTIC ABSORPTION TEST REPORT NO. 146417

Issue place and date: Bellaria, Italy, 26/03/2001Customer: MARTINI ENTERPRISE on behalf of GREEN METAL USA llc 2317 Meridian Street, Suite 20 Huntsville, AL 35811Object: Calculation of sound absorption coefficient weighed “aw” according to norm ISO 11654 of 1997.

Frequency[Hz]

ain 1/3 of eighth

ap*

in band of eighth (approximate value to

0.05 with maximum value equal to 1.00)

Reference curve

100 0.08125 0.30 0.35160 0.60200 0.70250 0.70 0.75 0.80315 0.88400 0.96500 0.99 0.95 1.00630 0.94800 1.02

1000 1.04 1.00 1.001250 1.021600 1.042000 1.06 1.00 1.002500 1.093150 1.154000 1.19 1.00 0.905000 1.27

(*)api = ai1 + ai2 + ai3

3

(Copy of the seal and signature as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Sound absorp�on coefficient weighed “aw”Value at 500 Hz of the reference curve

1

Shape indicator *Range of frequencies in which the curve “ap” is greater than 0.25 compared to that of reference

//

Class of sound absorp�on* A

(*) L = Low M = Medium H = High

(**) A: aw = 0.90, 0.95 or 1.00; B: aw = 0.80 or 0.85; C: aw = 0.60, 0.65, 0.70 or 0.75;

D: aw = 0.30, 0.35, 0.40, 0.45, 0.50, or 0.55;E: aw = 0.15, 0.20 or 0.25;Non classified: aw = 0.00, 0.05 or 0.10.

ap

Frequency [Hz]

Experimental reliefs Reference curve

(Copy of the seals and signatures as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THE

TEST REPORT NO. 148939ISSUED BY GIORDANO INSTITUTE s.p.a. - ITALY on the 12 June 2001

(Original on file. Available upon request)

Place and date of issue: Bellaria, Italy, 06/12/2001Customer: MARTINI ENTERPRISE on behalf of GREEN METAL USA llc 2317 Meridian Street, Suite 20, Huntsville, AL 35811Request test date: 05/15/2001Contract number and date: 17043, 05/25/2001Sample receipt date: 05/04/2001Test execution date: 06/05/2001Test subject: Determination of sound-insulation power of a dividing wall in accordance with norm ISO 140 3d part 1995 and ISO 717 1st part 1996.Test place: Giordano Institute S.p.A. – Blocco 3 – Via Verga, 19 – 47030 Gatteo (FO), Italy.Sample origin: Provided by the customer.Sample identification in acceptance: n. 2001/284.Sample name *: The sample to test is called “MULTI-LAYER PLASTERBOARD WALL.”

(*) according to the statements of the customer.

Sample description*

The sample to test is made up of a dividing wall,with the following dimensions:

- total nominal width = 1250 mm- total height = 1500 mm- total nominal thickness = 100 mm- useful acoustic area = 1.88 m2

The sample starting from the side exposed to noise,is composed of:

- plate plasterboard, thickness 12.5 mm- cavity, thickness 75 mm, inserted with pure carded wool batt called “ISOLANA”, having thickness of 60-70 mm and superficial mass 3 kg m3

- plasterboard plate, thickness 12.5 mm

SOUND-INSULATION TEST

Picture of wool batt “ISOLANA” used for the implementation of the sample to test.

(*) according to the statements of the customer.

(Copy of the seal as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

SECTION OF THE SAMPLE

Key

Symbol Descrip�on

1 Plasterboard plate, thickness 12. 5 mm

2 Ba� in pure carded wool called “ISOLANA”, thickness 60-70 mm and superficial mass 3 kg/ m3

Picture of the tested sample

(Copy of the seals as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Legal referencesThe test was performed in accordance with the following norms:

- ISO 140 3rd part,1995 “Acoustic measurements of sound insulation in building and of building elements. Part 3: Laboratory measurements of airborne sound insulation of building elements.”

- ISO 717 1st part, 1996 “Acoustics. Rating of sound insulation in buildings and of building elements. Part 1: Airborne sound insulation in buildings and of building elements.”

Test equipment

For test execution, the following equipment was used:

- noise generator model “1405” of the company Brüel & Kajer- power amplifier 1000 W model “ENERGY 2” of the company LEM- omnidirectional loudspeaker- third of octave equalizer model “HD-31” of the company Applied Research & Technology Inc.- microphones ø 1⁄2” model “4192” of the company Brüel & Kajer- microphone pre-amplifiers model “2669” of the company Brüel & Kajer- analyzer in real time model “2144” of the company Brüel & Kajer- analyzer in real time model “2123” of the company Brüel & Kajer- pistonophone for microphone calibration model “4220” of the company Brüel & Kajer- completion accessories

Test mode

Test environment is made up of two rooms, one of which, defined as “issuing room,” contains the noise source, while the other, defined as “receiving room,” is acoustically characterized through the equivalent acoustic absorption area.After having positioned the sample to test into the space in between the two rooms of the test area, it has been taken the sound pressure at different frequency levels, in a range between 100 Hz and 5000 Hz, both in the emitting room and in the receiving room, to verify the delay and attenuation of the sound wave for reason of the test material.

The index of evaluation “RW” of the phono insulating power “R” is equal to the value in dB of the reference curve at 500 Hz according to the proceedings of the norm ISO 717 part 1a.The phono insulating power “R”, equal to 10 times the decimal logarithm of the relationship between the incident sound power and the sound power transmitted through the sample, has been calculated using the following formula:

R= L1 – L2 + 10 z log S/A

where: R = phono insulating power, expressed in dB L1 = sound pressure medium level in the issuing room, expressed in dB L2 = sound pressure medium level in the receiving room, expressed in dB S = measuring useful surface of the sample to test, expressed in m2 A1 = acoustic absorption area equivalent to receiving room, expressed in m2, calculated by using the following formula

A = 0,163 x V T

where: V = receiving room volume, expressed in m3; T = reverberation time, expressed in s.

(Copy of the seals as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

It has also been calculated, as proposed by norm ISO 717 part 1, 2 corrective terms in dB which considers the features of particular sound spectra in source:

- corrective term “C” to add to the index of evaluation “RW” with spectrum in source relative to pink noise Pondered A- corrective term “C” to add to the index of evaluation “RW” with spectrum in source relative to traffic noise Pondered A

Environmental condition during the test

Environment average temperature = 22° CRelative humidity = 50%

Test results

Volume of the receiving room “V” 69,0 m3

Measurement useful surface of the sample to test “S” 1,88 m2

Microphonic posi�ons Rota�ng pole with circular path, radius 1 MGenera�on of sound field Mobile speaker with straight path, length 1, 6 m X 2 (round trip)

Frequency[Hz]

L1

[dB]L2*[dB]

T[s]

R[dB]

Reference curve [dB]

100 93.1 66.2 1.38 20.5 31.0125 95.6 61.9 1.48 27.5 34.0160 96.4 56.3 1.54 34.2 37.0200 99.6 55.7 1.58 38.1 40.0250 99.1 51.0 1.56 42.2 43.0315 98.9 48.3 1.67 45.1 46.0400 98.4 42.5 1.76 50.5 49.0500 98.8 38.8 1.65 54.5 50.0630 97.1 33.7 1.78 58.1 51.0800 98.7 34.3 1.70 58.9 52.0

1000 98.6 31.5 1.63 61.5 53.01250 98.2 29.6 1.55 62.7 54.01600 98.2 28.4 1.50 63.8 54.02000 98.5 29.0 1.45 63.3 54.02500 97.7 36.2 1.33 55.0 54.03150 97.4 39.5 1.28 51.2 54.04000 97.6 34.8 1.21 55.9 //5000 94.1 25.2 1.17 61.8 //

(*) Values not influenced by lateral side transmission and from background noise.

(Copy of the seals as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Measurement of useful surfaceof the sample: 1.88 m2

Issuing room volume: 57.0 m3

Receiving room volume: 69.0 m3

Type of noise: Pink

Type of filter: 1/3 of octave

Result of the test:Index of evaluation at 500 Hzin the band of frequency includedbetween 100 Hz and 3150 Hz

RW

= 50 dB

Band of frequency withunfavourable gap biggerthan 8 dB: 100 Hz

Correction terms:

C = -4 dB Ctr = -11 dB

(Copy of the seals and signatures as applied onto the original)

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811Phone 256-489-7814 - [email protected]

ENGLISH TRANSLATION OF THE

TEST REPORTISSUED BY GIORDANO INSTITUTE s.p.a. - ITALY on the 20 January 2003

(Original on file. Available upon request)

TELEFAX TRANSMISSION

Date: 01/20/2003To the company: ISOLANA SYSTEMS on behalf of GREEN METAL USA llc 2317 Meridian Street, Suite 20 Huntsville, AL 35811To the attention: Mr. Alessandro MartiniTelephone: 0574 – 984102 Telefax: 0574 – 984408

From: Andrea Bruschi Internal telephone number: 110Object: Phono insulating power measures results on your samples Pages No: 4 MESSAGE

As agreed we deliver the results of phono-insulating power tests, executed on various types of plasterboard/sheep wool panels. The following is a short description of the samples and the values:

- “R” phono-insulating power, in the field of frequencies between 100 and 5000 Hz, calculated in agreement with the ISO 140/3 of 1995- “R” index of evaluation of phono-insulating power, calculated in agreement with the ISO 717/1 of 1996;- “C” corrective term to add to “Rw” with spectrum at source relative to pink noise A weighted, calculated in agreement with the ISO 717/1 of 1996- “C” corrective term to add to “Rw” with spectrum at source relative to traffic noise A weighed, calculated in agreement with the ISO 717/1 of 1996

SOUND-INSULATION RESULTS

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Samples description

Sample 1:width = 1230 mmlength = 1480 mmthickness = 100 mm

The sample is made of:- plasterboard plate. thickness 12.5 mm- interspace thickness 75 mm filled with a sheep wool batt surface mass 1.5kg/m2 and thickness 70 mm

approximately- plasterboard plate thickness 12.5 mm

Sample 2:width = 1230 mmlength = 1480 mmthickness = 125 mm

The sample is made of:- plasterboard plate thickness 12.5 mm- plasterboard plate thickness 12.5 mm- interspace thickness 75 mm filled with a sheep wool batt surface mass 1.5 kg/m2 and thickness 70 mm- plasterboard plate thickness 12.5 mm- plasterboard plate thickness 12.5 mm

Sample 3:width = 1230 mmlength = 1480 mmthickness = 145 mm

The sample is made of:- plasterboard plate thickness 12.5 mm- sheep wool batt surface mass 0.5 kg/m2 and thickness 10 mm- plasterboard plate thickness 12. 5 mm- interspace thickness 75 mm filled with a sheep wool batt mass surface 1.5 kg/m2 and thickness 70 mm

approximately- plasterboard plate thickness 12.5 mm- sheep wool batt surface mass 0.5 kg/m2 and thickness 10 mm- plasterboard plate thickness 12.5 mm

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Test results

For all the samples the geometric/acoustic features of the test rooms were the following:

useful acoustic surface of the sample = 1.88 m2 (1250 x 1500 mm)issuing room volume = 57 m3receiving room volume = 69 m3

Phono-insulating power “R”

Sample 1Test on 01/08/03

Sample 2Test on 01/12/03

Sample 3Test on 01/14/03

Frequecy[Hz]

R[dB]

R[dB]

R[dB]

100 19.4 35.8 35.5125 22.6 36.5 36.6160 29.0 36.0 36.1200 33.9 36.4 37.2250 40.1 42.7 43.0315 45.3 45.2 46.5400 46.7 46.8 49.9500 48.9 48.9 54.1630 52.0 52.1 57.0800 56.2 55.5 60.1

1000 59.9 59.7 64.21250 62.1 62.2 66.11600 63.1 63.0 67.42000 62.5 63.7 67.22500 53.1 58.2 62.83150 50.7 58.0 62.44000 54.4 61.7 65.05000 60.1 62.4 64.0

Largeness Sample 1 Sample 2 Sample 3Rw 48 53 55C -4 -2 -3Ctr -11 -6 -7

Green Metal USA llc. - 2317 Meridian Street, Suite 20, Huntsville, AL 35811 - Phone 256-489-7814 - [email protected]

Graph of sound-insulation power “R” of the three samples