chillers; a brief treatise
TRANSCRIPT
-
7/30/2019 Chillers; a brief treatise
1/4
CHILLERS
Chillers consist of four main components:
1. The evaporator (the low temperature side of the system, i.e., the cooling
side)
2. The compressor
3. The condenser (the high temperature side of the system, i.e., the heat-
rejection side)
4. The expansion valve
TYPES OF CHILLERS
MECHANICAL COMPRESSOR CHILLERS
1. Reciprocating
2. Rotary screw
3. Centrifugal
4. Frictionless centrifugal
ABSORPTION CHILLERS
KEY COMPONENTS OF A MECHANICAL COMPRESSOR CHILLER
EVAPORATOR
Chillers produce chilled water in the evaporator where cold refrigerant
flows over the evaporator tube bundle. The refrigerant evaporates (changes into
vapour) as the heat is transferred from the water to the refrigerant. The chilled
water is then pumped, via the chilled-water distribution system to the buildings
air- handling units. The chilled water passes through coils in the air-handler to
remove heat from the air used to condition spaces throughout the building. The
warm water (warmed by the heat transferred from the building ventilation air)
returns to the evaporator and the cycle starts over.
Basically, there are two major categories of evaporators used in industrialrefrigeration practice. These are air coils and liquid chillers.
AIR-COILED EVAPORATORS
In the air coil, the refrigerant flows through the tubes and air passes over
the outside of the tubes. For effective heat transfer, fins are fastened to the
outside of the tubes and air flows between the fins.
LIQUID CHILLER EVAPORATORS
-
7/30/2019 Chillers; a brief treatise
2/4
The liquid-chilling evaporators in the figure below (fig. 1a & fig. 1b) are of
the shell-and-tube design, while fig. 2 is a plate-type chiller. In Fig. 1a the
refrigerant boils in the shell while the liquid flows through the tubes. In Fig. 1b
the roles of the tubes and shell are reversed. The plate-type evaporator in Fig. 2
is growing in market share and is an adaptation of the plate-type heat exchanger
used for many years in the food industry. Some of its popularity is attributable toits compactness and also that the refrigerant charge is less than in a shell-and-
tube evaporator. The reduced charge characteristic is attractive both when
ammonia and the new chlorine-free refrigerants are used. A low-charge ammonia
system is desirable for safety reasons, and a low-charge chlorine-free system
minimizes the cost of these expensive refrigerants.
Fig. 1 (a and b)
http://www.refrigers.com/content/view/31759/28/http://www.refrigers.com/content/view/31759/28/ -
7/30/2019 Chillers; a brief treatise
3/4
Fig. 2
COMPRESSOR
Vaporized refrigerant leaves the evaporator and travels to the compressor
where it is compressed mechanically, and changed into a high-pressure, high-
temperature vapour. Upon leaving the compressor, the refrigerant enters the
condenser side of the chiller.
CONDENSER
Inside the water-cooled condenser, hot refrigerant flows around the tubes
containing the condenser-loop water. The heat transfers to the water, causing
the refrigerant to condense into liquid form. The condenser water is pumped
from the condenser bundle to the cooling tower where heat is transferred from
the water to the atmosphere. The liquid refrigerant then travels to the expansion
valve.
EXPANSION VALVE
-
7/30/2019 Chillers; a brief treatise
4/4
The refrigerant flows into the evaporator through the expansion valve or
metering device. This valve controls the rate of cooling. Once through the valve,
the refrigerant expands to a lower pressure and a much lower temperature. It
flows around the evaporator tubes, absorbing the heat of the chilled water thats
been returned from the air handlers, completing the refrigeration cycle.