che designing spiral heat exchanger - may 1970

Upload: john-urdaneta

Post on 06-Jul-2018

245 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    1/10

    Designing

    Spiral-Plate

    Heat Exchangers

    Spiral-p,late e x ~ h n g e r s offer compactness, a variety of f,low arrangements,

    efficient heat transfer, and low maintenance costs. lihese

    and other features are described, along with a shortcut design method.

    P. E. MINTON, Union Carbide Corp.

    Spirall heat exchangers have a number of advan

    tages over conventional shell-and-tube exchangers:

    centrifugal forces increase heat transfer; the compact

    configuration results in a shorter undisturbed flow

    lengtH; relatively easy cleaning; and resistance to foul

    ing: These curved-flow units (spiral plate and spiral

    tube ) are particularly

    useful1

    for handing viscous

    or .solids-containing fluids .

    Spiral-Plate-Exchanger Fabrication

    A spiral-plate excHanger is fabt icated from two

    relatively long strips of plate, which, are spaced apart

    and wound around an

    open1

    split center to form a

    pair of concentric spiral

    1

    passages. Spacing is main

    tained uniformly along the length of the spiral by

    spacer· studs welded to the. plates.

    For most services, both, fluid-flow channels are

    closed by alternate channels welded

    at

    both sides of

    the spiral plate (Fig. 1

    ..

    In some applications, one

    of the channels is left completely open (Fig. 4)

    ,.

    the other closed at both sides of the plate

    .

    These

    two types of construction prevent the fluids from,

    mixing.

    Spiral-plate exchangers are fabricated from any

    material that can be cold worked and welded, such

    as:

    carbon steelj stainless steels, Hastelloy m and: C,

    nickel and nickel alloys, aluminum alloys, titanium,

    and copper alloys.. Baked phenolic-resin coatings,,

    among others, protecti against corrosion from· cooling

    • Although the spiral-plate and spiral-tutJe exchangers

    or•

    aimHar

    their applications. and methods of· fobricaticm ore. quit• different;

    T h i ~

    article i• devoted

    wholly.

    to the

    spital-plate

    exchanger; an article in

    tiM Ml ly

    18 i1we of hemical

    fnginH ;ng wilt

    take up the

    1-piral tul:Je

    exchanger. ·

    For

    infonnation

    on

    aheU-and-tvbe exchangen

    se. Ref. 8

    9

    The desion method presented is

    used:

    bf, Union Carbide Corp, for the

    thermal and hydraulic det ign of· IP irat-p ate exchangers, and is lOme·

    wllot,dilfe,...nt from that used by

    the

    fabricator.

    water. Electrodes may also be wound into the assem.

    bly

    to

    ano.dlcally protect surfaces a g ~ i n s t corrosion.

    Spiral-plate exchangers are normally designed

    for,

    the full pressure of each passage. Because the turns

    of the spirall are of relatively large diameter, each

    turn must. contain its design pressure,, and plate thick

    ness is somewhat restricted-for these three reasons,

    the maximum design pressure is 150 psi.,. although

    foX smaller diameters the pressure. may sometimes be

    higher.

    J.:.imitations

    of materials of construction gov•

    ern design temperature.

    Flow

    Arrangements

    and

    Applications

    The spiral assembly can be fitted with covers to

    provide three flow patterns:

    :1)

    both fluids in spiral

    flows;

    (2) one fluid in spiral

    flow

    andi the other in

    · axial flow across the spiral; ( 3), one fluid: in spiral

    flow and the other in a combination of axial and

    spiral flow.

    For spiral flow in both channels . the spiral assem.

    bly includes flat covers at both sides (Fig. 1). In

    this arrangement, the fluids usually

    flow·

    countercur

    rently., with the cold fluid entering at the periphery

    and Bowing toward the core; and the hot fluid enter

    ing at the core andi flowing toward the periphery.

    11his

    type of exchanger can

    be

    mounted with the

    axis either vertical or horizontal. It finds wide

    application in liquid-to-liquid service,. and for gases

    or condensing vapors if the volumes are not too large

    for. the maximum flow area of 72 sq. in.

    or spiral flow in one channel and axial

    low

    in

    the other the spiral assembly contains conical covers,

    diShed heads,

    or·

    extensions with, flat covers (Fig.

    2).

    h1 this design, the passage for axial flow

    is

    open. on,

    both sides, and the spiral flow channel is welded on·

    both sides.

    This type of exchanger

    is

    suitable for services in·

    Reprinted from CHEMICAL

    ENGINEERING, May 4,. 1970• Copyright

    ©• 1970

    by McGtaw·Hill I no.

    330·

    West

    42nd

    St

    New York,

    N.Y·. 10036

    2030368834

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    2/10

    SPI RAL·PLATE

    EXCHANGERS

    SPIR L

    FLOW

    in both channels is widely

    u s e ~ i g

    1

    which there is a large difference in the volt.unes

    of

    the two liquids. This includes liquid-liquid service,

    heating or rooling gases, condensing vapors,

    or

    as

    reboilers.

    It

    may

    be

    fabricated with one or more

    passes on the axial-flow side. And it can

    be mounted

    with the axis of the spiral either vertical or hori

    zontal (usually vertically' for condensing or boiling)'·

    For

    combiMtion flow a conical cover dist:ibutes

    the fluid into its passage (Fig. 3). Part of the spiral

    is closed at• the top, and the entering fluid flows

    only through the center part

    of,

    the assembly; A

    flat•

    cover at the bottom• forces the fluid to ow spirally

    before leaving the exchanger.

    This type is most· often used for condensing vapors

    (mounted

    vertically)'· Vapors rst flow axially until

    their volume is reduced sufficiently for finali condens

    ing and subcooling in spiral flow.

    A modification of this type:

    the

    column-mounted

    condenser (Fig. 4). A bottom extension

    is

    flanged

    to· mate wi th the column. flange. Vapo r flows

    upward

    through a large central tube and:

    then

    axially across

    the spiral, where t is condensed. Subcooling may

    be

    by f a l l i n g ~ f i l m cooling or by controlling a level

    of condensate in the channel. In

    the

    latter case, the

    vent• stream leaves in

    spiraf

    flow. This type is also

    designed to allow condensate to dropointo

    an

    accumu

    lator without appreciable subcooling.

    lOW

    is spiral in one channel axial in other .-Fig. 2

    The spiral-plate exchanger offers

    many

    advantages

    over

    the

    shell-and-tube exchanger·:

    (1) Single-flow passage makes

    it

    ideal for· cooling

    or heating sludges or slurries. Slurries can. be proc·

    essed in the spiral at velocities as low as 2 ft./sec.

    For

    some sizes and: design pressures, eliminating the

    spacer studs enables the exchanger to handle liquids

    having a h igh content. of fioers.

    (2) Distribution is good because of the single-Bow

    channel.

    {3) The spiraHplate exchanger. generally fouls at

    much lower rates tlian the shell-and-tube exchanger

    because of the single-How passage and curved-How.

    path. If it fouls, it can be effectively cleaned chemi

    cally because of the single-How path

    and

    reduced

    bypassing. Because the spiral can also be fabricated:

    with identical passages, it

    is

    used for services in•

    which the switching of fluids allows one fluid to

    remove the scale deposited by the

    other .

    Also, be

    cause the maximum' plate

    width is

    6

    ft. .

    it is easily

    cleaned with. High-pressure water or steam.

    (4). This exchanger is well suited for heating or

    cooling viscous fluids because its LID ratio is lower·

    than. that; of tubular exchangers. Consequently, lam•

    inar-flow heat .transfer is much higher for spiral plates.

    When' heat ing or cooling a viscous fluid,

    the

    spiral

    should be oriented with the axis horizontal.

    With

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    3/10

    COMBIN nON

    FLOW

    is

    used

    to condense vapors Fig. 3

    the

    uis

    verticaL the viscous fluid stratifies and

    t is

    reduces heat transfer

    as

    much

    as

    50%.

    (5)' With both fluids fl.owing spirally, flow can

    be countercurrent (although not truly so, because,

    throughout the unit, each channel is adjoined

    by

    an

    ascending and a· descending turn of the other

    chan-

    nel and because heat-transfer areas are not equal

    for each side of the channel, the diameters. being

    different). A correction factor may be applied;l

    o w ~

    ever, it

    is

    so

    small' it can generally be ignored.

    Countercurrent flow and' long passages make pos

    sible clbse temperature approaches and precise tem

    perature control.

    {6) The spiral-plate exchanger avoids problems

    associated with differential thennal expansion in non

    cyclic service.

    7) In axial flow, a large_flow area affords a low

    pressure. drop, which becomes especially important

    when condensing under vacuum.

    (8) This exchanger

    is

    compact:

    2;000

    sq. ft.

    of

    heat-transfer· surface in a 58-in.-dia. unit' with a 72-

    in.-wide plate .

    Umitations

    Besides

    Pressure

    In addition to the pressure limitation· noted earlier,

    the spiral-plate exchanger also

    has

    the followimg

    disadvantages:

    {1 ) Repairing it in the field

    is

    difficult. A leak

    cannot

    be

    plugged

    as

    in a s h e l l ~ a n d t u b e exchanger

    (however, the possibility of; leakage in a spiral is less

    because it is fabricated from' plate generally much

    thicker than tube walls). Should a spiral need repair

    ing, removing the covers exposes most of the welding

    CHEMICAL ENGINEERING/MAY

    4

    1970

    MODifiiED

    combination flow serves on c o l u m ~ g 4

    of the spiral assembly. However, repairs on the inner

    parts of the plates are complicated. ·

    (2) The spiral•plate exchanger

    is

    sometimes pre

    cluded

    from

    serviee in which thennal eyclmg

    is

    frequent. When used in cycling services, its mechani-.

    cal. design sometimes must• be altered to provide. for

    much higher stresses. Full-faced gaskets of com

    pressed asl:lestos are not generally acceptable for

    cycling services because the growth' of the spiral

    plates. cuts the g a s k e t ~ which results in' excessive

    bypassing and; in some cases,. erosion of the cover.

    Metal-to-metal seals are generally necessary.

    (3)

    This

    exchanger · usually should not

    be

    used

    when a hard deposit forms during operation,

    be- ·

    cause the spacer studs prevent such' deposits hom

    being easily· removed by drilling. When

    1

    as £or

    some

    pressures,. sucli studs can be omitted, this .imitatiOn

    is

    not present'

    (

    4)

    For spiral-axial' flow, the temperature difference

    must be corrected. The conventionali correction for

    cross

    flow

    applies. Fluids are not mixed\ flows are

    generally single pass. Axial B ow may be multipass.

    SHORT tUT RATING METHOD

    The shortcut rating method for spiral-plate ex-

    changers depends on the same technique as that

    2030368836

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    4/10

    SPIRAL-PLATE EXCHANGERS

    • • •

    Empirical Heat-Transfer

    and

    Pressure-Drop Rel ationshi .p

    Eq.

    No. Mechanism or Restriction

    EmpiricaliEquation-HeatTransfer

    Spiral Flow

    l ) No phase change

    ( l i q u i d ~ ' •

    N ••

    >

    N

    11

    u

    h

    =

    (11 + 3:54.D, Du) 0 ~ 0 2 3 c G

    (NM.)-• ~ P r ) - '

    {2)

    No phase change (gas),N11. > N

    11

    h =

    (11

    + 3.54 D /D

     

    } 0.0144

    cG• •(D,)

    -•.:

    (3)

    No phase change ( liquid), NR., < N

    < • · ·

    Spiral

    or

    Axial Flow

    (4) Condensing vapor, vertical,

    Na.

    < 2,100

    k

    = 0.925

    k

    [gcpL'IJ 10,000

    1

    n

    No phase change

    (gas). NRe

    >

    10,000

    (8) Condensing vapor, horizontaH N

    R•

    < 2,100

    (9) Nucleate boiling, vertical

    Plate

    (10)

    Plate , sensible heat

    transfer

    (11)

    Flate,

    latent

    heat

    transfer

    Fouling

    (12)

    Fouling, sensible

    heat transfer

    (13)

    Fouling, latent hea t transfer

    Eq.

    No.

    Mechanism or Restriction

    Spiral Flow

    (14)

    No phase change, N > N

    11..-

      1 5 ~ ,

    No phase change, 100 <

    N

    11

    , <

    Nt..c

    (Hi)

    No phase change,

    N11. < 100

    (17)

    Condensing

    AxiaJIFiow

    (18) No phase change, N

    11

    , > 10,000

    (19)

    Condensing

    Notes:

    1. NR..- =

    20,000(D,/D/1)

    0

    "

    2

    . G

    =

    W.pd(Ap,,)

    h

    =

    0.0144 c G · .

    (D.)

    -• :

    I t= 12 k ./p

    h =

    12 k. /p

    h

    =assumed

    h

    =assumed

    E Tlpirical E q u a t i o n > - ~ r e s s u r e Drop

    aP

    =

    0:0011

    [ d ~ r Ld,

    1

    1

    - ; ; 5 )

    ( ~ r · + 1.5

    + ~ ]

    L [-W Jl

    [

    1.035 Z '· ( ~ ) . · (.#-)'

    ,-

    ,1

    t> P

    =

    0

    ·

    001

    s

    d ~ H -t; 0.125)

    W

    + 1.;>

    -

    t> P

    = 3 , 3 8 ~ ~ ~ , :

    (i;J (

    L [ W ]• [ 1.3

    z•;•

    /,H)\ 1 6]

    t> P

    =

    0;0005

    -;

    d H

    (d,

    +

    0.125)

    \w

    '

    +

    1 .5

    +

    L

    t> P = 4 x 10-' (w)u 0.0115 z•' ..

    +

    1 + 0.03 H

    s d ~ '

    L d,

    t> P

    =

    2

    : d ~ ? ~ - . ( ~ ) '

    • [

    Oi0115,zo' ~

    +

    1

    +

    0.03 HJ

    3. Surface-condition factor ( ~ ' ) for copper and

    steel=

    LO; fo r stainless steel= 1.7; for pol.ished surfaces= 2.5.

    M A 2 0 ~ E E R I N G

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    5/10

    for

    Rating

    Spiral Plate

    Heat Exchangers Table I

    Physical

    Work

    MecHanical

    Factor

    Property Factor Factor

    Design

    Factor

    = 20.6

    z•·• M•·•••

    W ..

    (T;,-TL)

    X

    d,

    (See Note 1

    )

    X

    .....

    X

    fl T

    11

    LH•·•

    :,,

    = 19.6

    X

    W .. (T -T,,)

    X

    d,

    (See Note 1)

    .

    flT11

    LH•·•

    ..

    M'''(z,)•·

    X

    W

    2

     

    3

    (T

    11

    -TL}

    X

    d,

    (See Note

    1)

    =32.6

    X

    s '' (,z.p.u

    flT

    11

    LH i7•

    II

    = 3.8

    M'' Z'',

    X

    W'',A

    X

    1

    X

    cs•

    ll.T•

    £-I•H

    M'' Zl'

    11

    W•

    11

    (T Td

    1

    1.18

    X

    X

    X

    8

    . .

    l l T ~ r

    H•t•L•t•

    = 167

    z•·•4•M•· '

    X

    W

    0

    · (TH-TL)

    X

    d,

    X

    8

    ll.T.

    HL•·•

    J

    =

    158 X

    W•·•(TH-TL)

    X

    d,

    ll T11

    H£0·

    11

    z•l•M•ts

    W''

    3

    A

    X

    1

    =

    16.1

    X

    X

    ll.T.

    L•t3H•r•

    '

    C8

    2

    M•··•z•·•a•·'

    Pt·o r

    w···A

    X

    d, ·'I'

    (See Notes 2

    and

    3)

    ~ =

    0.619

    X

    P ···

    X

    ll T11

    L•·•H•·•

    r .

    cs•·•••

    500

    c

    X

    W ~ T H T d

    X

    p

    X

    k,

    ATM

    1Ii

    =

    278

    1

    X

    WA

    X

    _.1?._

    I

    k .

    ll T11

    LH

    =

    6 000

    c

    X

    W(Tit-Td

    X

    1

    ,

    X

    h. flT11

    LH

    =3,333

    1 WA

    1

    X

    h

    X

    ll T11

    X

    LH

    Note 1)

    Note 1:)

    CHEMICAL ENGINEERING/MAY 4 1970

    1

    2 3 368838

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    6/10

    SPIRAL·Pl.ATE

    . EXCHANGERS •

    for

    s h e U . a n d ~ t u b e

    heat exchangers (which were

    dis-

    cussed oy Lord, Minton

    and

    Slusser ).

    Primarily; the method combines into one relation

    ship• the classical' empirical equations for fihn, heat

    transfer coefficients with• heat'-ballmce equations and

    with correlations tHat describe

    tHe

    geometry of the

    heat e x c ~ g e r The resulting .overall; equation• is

    recast into three separate groups.

    that

    contain• factors

    relating to the physical properties of the fluid, the

    performance or

    duty

    of the exchanger,

    and

    the

    mechanical design or arrangement of the heat-transfer·

    surface. These groups are then multiplied tbgether'

    with• a numerical factor to obtain a product that is

    equal: to' the fraction of the total driving force-or

    log mean temperature difference b.Tll

    or

    LMTD)

    that

    is dissipated across each element of resistance

    in the. heat-How path1

    When the sum

    of the products for

    the

    individual

    resistance equa15 1,

    the

    trial design may be assumed

    to be satisfactory for heat: transfer. The physical

    significance is that the sum of the temperature drops.

    across each· resistance

    is

    equal to the total available

    t .Tll· The pressure. drops for both' f l u i d ~ flow paths

    must be checked: to ensure that: both are within

    acceptable limits

    .

    Usually, several trials are necessary

    to get a satisfactbry balance between heat transfer

    and pressure drop.

    Table I summarizes the equations used with the

    method for heat transfer and: pressure drop

    The

    columns on the left list the conditions to which each

    equation applies,

    and

    the second columns. gives the

    standard forms of the correlations for

    .6hn

    coefficients

    that are found in texts.

    The

    remaining columns in

    Table

    I:

    tabulate the numericaL physical property,

    work and mechanical design factors-all of which

    together. form tlie recast dimensional equation. 1'he

    product of these factors gives. the fraction of total

    temperature drop' or driving force ( J T

    1

    /b.T

    1

    )

    across

    the. resistance.

    As stated, the sum of

    t .Thl

    t .T

    11 (the

    hot-fluid

    factor),

    tJ.T./tJ.TM (the

    cold-fluid factor)', b.T,/b.TJI.

    (the fouling factor), and AT..,/ti.T

    11

    (the plate factor)

    determines the adequacy of: heat transfer. Any com

    binations of b.T

    1

    /

    b.T 1

    may

    be

    used, as long as

    the

    orientation specified: by the equation matches that

    of the exchanger's flowpath .

    The units in

    tHe

    pressure-drop

    eq1.1ations

    are con

    sistent with those used for heat transfer. Pressure drop

    is calculated directly in psi.

    Approximations and Assumptions

    For

    many organic liquids, thermal conductivity

    data

    are either· not available

    or

    difficult to obtain.

    JSecause molecular weights ('M) are known, the

    Weber equation, which, follows,. yields thermal con

    ductivities. whose accuracies are quite satisfactory

    for most design purposes: · ·

    k -

    0.86

    (q#'/M ')

    u;

    on the other hand, the thermal conductivity

    is lrnown, a pseudomolecular weight may be used:

    M = 0.636 c / k ) l ~

    In what follows, each of

    tHe

    equations in Table I'

    r e v i e w ~ d ,

    and the conditions in· which each equa

    tion apphes, as well as its limitations, are given

    1

    Jn, several' cases, numerical factors are inserted or

    a p p r ? x i m ~ t i o n s made,

    so

    as to

    adapt

    the empirlcal

    relationshtps to the. design of spiral-plate exchangers.

    Such modifications have been• made to increase the

    accuracy, to simplify, or to Broaden the use of

    the

    ~ e t h o d . Rather than by any simplifying approxima

    tions,.

    the

    accuracy of the method is limited

    by.

    that

    with which fouling factors, fluid properties and fab

    rication tolerances

    can be

    predicted.

    Eq:uations tor: Heat; Transfer-Spiral Flow

    . Eq; 1):.-No Phase Change Liquid), NR.. > Na • --

    for.

    liquids with Reynolds numbers greater

    than

    the critical Reynolds number. Because the term

    (1

    +

    3.54

    D,IDH)

    is

    not constant for any given

    heat, exchanger, a weighted average of 1.11 has oeen

    used for• this method. If a design is selected with

    a different value, the numerical factor can be. adjusted

    to reflect the new value.

    Eq. (2):..-No Phase Change ~ G a s ) , N

     

    , >

    NR.rc-is

    for gases with Reynolds numbers greater than the

    critical

    ReynoiCis

    number;. Because tlie Prandtl number

    of common• gases

    is

    appromately eq)Ja) to

    0178: and

    the viscosity enters only as

    l-'o.2,

    the relationship of

    physical' properties for gases is essentially a constant.

    This constant, when combined with the numerical

    coefficient in Eq. (I) to eliminate the physical prop.

    erty factors for gases, results ih Eq. (2). As in Eq. l ).,

    the term

    •1

    +

    3.54 D,/D'H) has been taken•

    ·as

    l L

    Eq. 3)-No Phase Change

    ,Liquid), N

     

    , < N

    11

      -

    is for liquids in laminar

    Bow,

    at moderate ~ and

    with' large kinematic viscosity

    p.Lfp). The

    accuracy

    of the correlation, decreases as the operating conditions

    or the geometry of, the heat-transfer surface are

    changed

    tQ

    increase the effect of natural convection.

    For a spiral

    plate:n

    (D/L)1

    11

    = [12

    112

    D,j(DHd,) •J '

    = 2 '

    (d,/dn)•

    The value

    of

    (d,/d; )1 6 varies from 0.4 to 0;6. A value

    of o s for

    d.ldH)

    1

    '

    8

    has been used for this method.

    Heat Tramsfer

    Equations-Spirator

    Axial Flow

    Eq. 4}-Cond.ensing Vapor,. Vertical, NR..

    <

    2,100

    - is for film condensation of vapors on a vertical

    plate with a terminal Reynolds number

    ( 4 1 J / ~ )

    of·

    less than'

    2,l00.

    Condensate loading

    (or)

    for veftical

    plates is II =

    W/2L.

    For Reynolds numbers above

    2,100,. or fbr high Ptandtl numbers, the equation

    should be • adjusted

    by

    means of the Dukler plot,

    as discussed by Lord, Minton, andi Slusser.s

    To

    use

    Eq. (4) most conveniently, the constant in it should

    be multiplied by the ratio of the value obtained

    by

    the Nusselt equation to the Dukler plot.

    1 he preceding only applies to the condensation

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    7/10

    of

    condensable vapors. Noncondensable gases in, the

    vapor decrease the 1m coefficient, the reduction

    depending on the relative sizes a£ the gas-cooling

    load and the total cooling and condensing duty.

    (A method for analyzing condensing in the presence

    of noncondensable g ~ ~ e s

    is discussed

    by Lord, Minton

    and S l u s s e r ~ }

    Eq

    5)-Condensate Subcooling, Vertical,.

    Na.

    <

    2,100-is fbr laminar films flowing in layer form down

    vertical plates.

    ThiS

    equation is used when, the. con

    densate

    from a vertical condenser is tb be cooled

    below the bubble point. In, such cases, it

    is

    con

    venient to treat the condenser-subcooler as two

    separate heat exchangers-the first operating only as

    a condenser, (no subcooling), and the second as a

    liquid cooler

    only.

    Fig. 5 shows the assumptions that

    must be made to determine the height of each section,

    so

    as to calculate intermediate temperatures that will

    permit in, fum the calculation of the LMTID. ·

    Eq. (4)

    is

    used in combination with appropriate

    expressions for other resistances to heat transfer, tb

    calirulate the height of the subcooling section. In tlle

    case of the subcooling section only (See Fig. 5), the

    arithmetic mean temperature · difference,, [ (

    Thm -

    T..,.) + ThL - T.L)]/2, of the two fluids should

    be used instead of the log mean temperature dif-

    ference .

    Equations for Heat

    Transfer-Axial

    Flow

    Eq.

    6)-No

    Phase Change Liquid)l NR., > 10;000

    - is for liquids. with Reynoltls numbers greater than

    Hl OOO;.

    Eq. 7)-No Phase Change Gas),. NR., > 10,000-

    is for. gases with Reynolds numbero greater than

    10,000 Again, because the physical property factor

    for common, gases is essentially a constant,

    thiS

    con

    stant

    is

    combined with the numerical factor in

    Eq.

    :6)

    to get Eq,

    7).

    stiBCOOUNG·ZONE calculations

    depend on arittlmetic·mean tem·

    perature difference of, the tWo

    fluids instead of log·mean tem·

    perature differenoes-Fig. 5

    CHEMICAL ENGINEERING/MAY 4,

    1970

    Condensing

    zone

    Eq.

    8)-CondenMg

    Vapor . HorU:ontal Na. <

    2,100-is for 1m condensation on spiral plates ar-

    ranged for horizontal axial flow witli a terminal

    Reynolds number a£ less than 2,100. For a spiral

    plate, eondensate loading

    r)

    depends on the length

    of the plate and spacing between adjacent plates.

    For

    any given plate length and channel spacing, the

    heat-transfer

    area

    for each 360-deg. winding of the

    spiral fucreases with the diameter

    of

    the spiral. The

    number of revolutions affects the eondensate load

    ing in two ways: (

    1

    the heat-transfer area changes,.

    resulting in more condensate being formed in the

    outer spirals; and (2) the effective length over which

    the condensate

    is

    formed is.determiiled by the number

    of revolutions and the plate width. Ilhe. equations

    presented depend: on a value for the effective number

    of spirals

    of: L/7.

    Therefore,. the eondensate load

    ing is given by:.

    W (1,000) 7 12)/4HL- 21,000 W/HL

    This equation can be corrected

    i f

    a design is. obtained

    with a significantly dilferent condensate loading.

    It

    does not include allowances for turbulence due

    to vapor-liquid sHearing or splashing

    of

    the con

    densate. At high condensate loadings, the liquid

    condensate on the bottom of the spiral channels may

    blanket part of the exchanger, s effective heat-transfer

    surface.

    Eq. 9)-Nucleate Boiling, Vertical-is for nucleate

    boiling on vertical plates. In a rigorous analysis of

    a thermosyphon reboiler, the calculation of heat

    transfer

    is

    combined with the hydrodynamics of the

    system to determine the circulating rate through the

    reboiler. How.ever,

    for

    most design purposes,

    tliis

    calculation is not necessary. For atmospheric pres

    sure and higher, the assumption, of nucleate boiling

    over the full height of the plate gives. satisfactory

    results.

    The

    assumption of nucleate boiling over the

    entire height of the plate in. vacuum service produces

    overly optimistic results. (The mechanism of thermo-

    2 3 36884

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    8/10

    SPIRAL·Pl.ATE EXCHANGERS • • •

    syphon reboilers has been already discussed by Lord,

    Minton and

    Slt1sser.s.

    )

    A surface condition factor, I, appears. in the empiri·

    cal

    correlations for boiling coefficients. This. is a

    measure

    of,

    the number of nucleation sites for, bubble

    formation on the heated surface. The equations

    for

    t .Tt/tl.TII contaim,I' (the reciprocal of I) , which

    Has

    values of 1.0 for copper and steel, 1.7 for stainless

    steel or chrome.nickel alloys, and 2.5 for polished

    surfaces.

    Equations for Heat Transfer-Plate

    Eq. ~ 1 0

    and

    llrHeat Transfer Through the

    Plate-are for calculating the plate factor. The inte

    grated form of the Fourier equation

    is QlfJ =

    k..,A

    tl.'Pw)/X, with X the plate thickness. Expressed in

    the form of a heat-transfer coefficient;

    hw

    = 12k..,/p.

    Eq. (10) is used whenever sensible heat transfer

    i. i

    involved for either fluid. Eq. (H) is usedi when

    there is latent heat transfer for each fluidl

    Equations for Heat Transfer-Fouling

    Eq.

    (12)

    and

    13)-Fouling-is

    for conduction of,

    heati through scale or solids deposits.. Fouling co•

    efficients are selected by the designer,. based upon

    his experience. Fouling coefficients of 1,000 to 500

    (fouling factors ofi 0.001 to 0.002) normally require

    exchangers 10 to' 30% larger than for

    clean

    service;

    The selection of, a fouling factor is arbitrary be-

    cause there is usually insufficient data for accurately

    assessing the degree of fouling that should

    be

    assumed

    for a

    (itiven

    design. Generally, fouling for a spiral

    plate exchanger' is considerably less than for shell

    and-tube exchangers. Because fouling varies with

    material. velocities and temperature, the extent to

    which this influences design depends on operating

    conditions and,

    to

    a great degree, the design· itself.

    Eq. (12)

    iS

    used for sensible heat transfer for

    either fluid, and Eq . (

    13)

    when latent heat is

    trans

    ferred' on both sides ofi the. plate;

    Equations for; Pressure

    r o ~ S p i r a l Flow

    Eq

    .

    U)-No

    PhDse

    Change Nth > N

    a

    ..

    iS

    based

    on equations proposed by Sander.

    4

    12

    'Ilerm A in

    Sander's equation €an be closely approximated by.

    the value of 28/(d.

    +

    0.125). Term

    B

    in Sander's

    equation accounts for the spacer studs. The factor

    1.5 assumes 18 studs/sq. ft. and a stud dia. of

    5/16

    in.

    Eq. 15)-No Phase Change 100 < Na, <

    Na,.

    again is based upon the equation proposed by Sander.

    For, this flow regime, the. term

    A can

    be closely

    approximated' by the 'lalue of

    103.5/(d, +

    0.125).

    As in Eq (14h the factor of

    1.5

    accounts for the

    spacer studs.

    Eq. 16)-No Phase Ch4nge N

    2

    ,

    <

    JOO:..aJso

    is

    based on the Sander eq1.1ations. For this flow regime,,

    term

    A

    can be closely approximated by the value of

    2,170

    d

    1

    I.'f5. For this flow regime, the studs have

    A

    B

    c

    c

    D.

    D.

    D.

    d

    I

    G

    g.

    H

    h

    k

    L

    M

    p

    p

    t:J

    Q

    s

    u

    w

    r

    z

    6

    Nomenclature

    Heat-transfer area,

    sq.

    ft.

    Filln thickness (:0J00187,

    z r/g

    r

    11

    ,.ft.

    Core dia., in.

    Specific liea.t, l3tu./ (lb.) ("F.)

    Equivalent dia.,

    ft.

    Helix

    or

    spi.ral dia ., R

    Exchanger

    outside

    dia.,in .

    Channel spacing, in.

    Fanning friction

    facto r, dimensionless

    Mass

    veloeity,lb./(hr.H Iq.

    Gravitational constant,

    ft,./. (hr.)• (4.18

    x

    1:0 )

    Channel plate wi.dtli, in.

    Film coefficient

    of heat

    t:ransfer.,.

    Btu./

    (hr.) (sq. ft.) (•F.)

    Thermal conductiVity, Btu./{hr.) (sq ft.)

    (•F;fft.)

    Plate

    length,

    ft.

    Molecular weight, dimensionless

    Pressure, psia.

    Plate

    thickness; in.

    Pressure

    drop,.psi.

    Heat transferred,

    Btu.

    Specific

    gravity (referred

    to water

    at

    20 C.)

    Logarithmic mean

    temperature

    difference

    ·· (LM'IlD),

    •c.

    Overalll

    heat-transfer

    coefficient, Btu./.

    (hr.)

    (sq.

    ft.) eF.)·

    Flowrate,

    (lb./hr.) /1,000

    Condensate loading, lb./.

    (hr.) (ft.)

    Viscosity, op.

    Time,

    hr.

    A

    I

    Heat of

    vaporization,

    Btu./lb.

    Viscosity, lb./.(hr.)

    (ft.)

    Liquidldensity, ll:L/cu1ft.

    Vapor density, lb.f.cu.ft.

    I

    P•

    I:, I:

    IT

    Surface

    condition factor, dimensionli ss

    Surface

    tension, dynes/em.

    Subscripts

    Built fluid propertie s

    c

    Cold

    stream

    I Film

    fluid properties

    . H

    High temperature

    h

    Hot

    stream

    L

    .IJ.ow temperature

    m Median

    temperature 1see

    Fig. 5)

    s Scale or fouling

    material

    w

    Wall, plate material

    Dimensionless Groups

    N

    •• Reynolds number

    N

    Critical Reynolds number

    Nr.r Prandtl number

    little effect· on the pressure drop,. and any such effect

    is included' in the Sander equation.

    Eq;

    17rCondensing-is

    for calculating the pres

    sure drop

    for·

    condensing vapors and is identical to

    that for

    no

    phase change, except for

    a

    facto11 of

    0.5 used with the condensing equation. For total

    condensers, the weight rate of

    flow

    used

    in

    the

    calculation should be the inlet flowrate. Because the

    average

    Bow

    for partial condensers is greater than

    MAY 4,.1970/CHEMICAL ENGINEERING

    2 3 368841

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    9/10

    far total condensers,. the multip]ymg factor should

    be 0.7 instead of 0.5. Because the estimation of the

    pressure drop for condensing vapors is not clear-cut,

    the equation should be used only to approximate

    the. pressure drop, so

    as

    to prevent the design of

    exchangers with, excessive. pressure losses.

    Equations for Pressure Drop--Axiali Flow

    Eq :18}-No Phase Change

    N., >

    10,000-is

    an

    expression• of the Fanning equation for

    n o n c o m p r e s s i ~

    ble fluids,.in which the friction factOr f in, the Fanning

    equation = 0.046/N.,u.

    The

    equation

    has

    been

    revised

    to•

    account for pressure lbsses in the inlet

    and outlet nozzles, and the irnlet and outlet

    heads.

    The equation also, includes the correction for the

    spacer studs in

    the flow. eliannels.

    Eq. (19}-Conden.ring-again

    is

    identical

    to, that

    for no phase change, except for a factor of 0.5. Again.

    for partial condensers,. a value of 0.7 should be used

    instead of 0.5. For condensing pressure drop, only

    approximate results. should:

    be

    expected, which them

    selves should be used only to prevent designs that

    would result

    in

    excessive pressure losses.

    For overhead condensers, the pressure drop in

    the center tube must

    be

    added to the pressure drop

    calculated from

    Eq.

    (19).

    SAMPLE CALCUlATIONS

    This example applies the rating method to the

    design of a

    l i q u i d ~ J i q u i d

    spiral-plate heat exchanger

    under the following conditions:

    ConditiODs

    Hot Side Coldi Side

    Flowrate,

    lb. /hr . . . . . . . . . . . . . . . . .

    6,225 5,,925

    Inlet temperature,

    •c.. . . . . . . . .

    200 60

    Outlet temperature, •c..

    . . . . .

    I20 I

    50.4

    V:iscoeity, cp. . . . . . . . . . . . . . . . . . .

    3.

    35' . 8

    Specific heat, Btu./lb.;oF.... ... . ... 0.71

    0.66

    Molecular, weight.... . . . . . . . . . . . . . 200.4 200.4

    Specific ~ V f o v i t y ... 0 843

    liL843

    Allowable yressure

    drop,

    psi.. . . . . . I I'

    Material o construction

    . . . . . . . . . . .

    stainless steel

    (k

    -

    Ul)

    Z,/z.)u•:

    . . . . . . . . . . . . . . . . . . . . . I I

    Preliminary Calculations

    Heat transferred

    = 6

    1

    225 X (200-120) X 1.8 X

    0,11: = 636,400 Btu./hr.

    t.T

    11

    (or LMTD)

    • -

    49.4)/ln 60/4U) •

    54.5

    C.

    For a flrst trial, the approximate surface can be

    calculated' using an assumed overall heat-transfer

    coefficient,

    U

    of

    50

    :Btu./(hr.)

    sq .

    ft.)

    °F.):

    A -

    636,400/(50 X I.8 X 54.5)

    =

    I30

    sq. ft.

    Because this is a small exchanger, a plate

    width

    of 24 in.

    is assumed. Therefore,

    L = i30/

    2 X

    2). =

    3 2 ~ 5

    ft.

    A channel spacing of

    in.

    for both. fluids

    is also assumed. The Reynolds number for spiral flow

    can be calculated from the expressiont

    N

    •• '

    IO,OOO (JV/HZ)

    Therefore:

    CHEMICAL ENGINEERING/MAY 4, 1970

    Hot side

    Na. • (10,( )()()

    X 6.225/ 24 X 3.35) •

    714

    CoiC I

    aide

    Na, •

    (lOiOOO X 5.925)/(24 X 8) • 309

    Because the ftuids willi be in· lamimar flow, spiral

    flow is selected for the heat exchanger design. From

    Table I, the appropriate expressions for rating are:

    Eq.

    (3)

    for both fluids, Eq.

    (10).

    for the plate,

    Eq, (12) for fouling

    and

    Eq. 15) far pressure drop.

    Heat-Transfer Calculations

    Now; substitute values:

    Hot side, Eq. 3):

    ~ T . . .

    -

    32.6[   ~ ] .

    X

    aTJI 0:843 ..

    ,

    [

    · ~ 5 ~

    80

    J

    ~ · ~ ~ 2 5 ]

    • 32.6 X3.775

    X

    4.967

    X

    0.001387, • 0.848

    Colli side, Eq.

    3):

    aT

    _ ·[ 200.4

    1

     

    111

    ] 5.925

    111

    X9C:U ] X

    t: TM

    32.6 0.843' ... . 54.5

    [

    0.375

    J

    24111

    X

    32.5,

    =

    32.6

    X

    3.775

    X

    5.431

    X

    0.001387 • 0.927

    Foulin.g, Eq. ( 12):

    t:.T,

    _

    6

    OOO f.

    0J66

    J [ 5.925

    X

    90.4 J [ . I J

    t TJI

    - ,

    L

    ,000 54.5 32.5

    X 24

    • 6,000 X 0;00066 X 9.828 X 0.001282 • 0.050

    Flate,. Eq. (10):

    E ·

    ..

    500

    [ ~ 6 6 - J f

    5.925 X

    9CMJ

    [ O.I25 ]

    t:. /111 10

    L

    54.5 32.5

    X 24

    = 500

    X

    01066

    X

    9.828

    X

    0.0001603 • 0.052

    Some Spi,r,ai-Piate

    Exchanger;

    Standar;ds-Table

    Ill

    Plate

    Outside 018.,

    Core

    Widths,, lin.

    Maximum, .lin.

    Dia.,ln

    .

    4

    32

    8

    6

    32

    8

    12

    32

    8

    12 58

    l2

    18

    32

    8

    18

    58

    12

    24

    32 8

    24

    58 12

    30

    58

    12

    36

    58

    12

    48

    58

    12

    6C 58 12

    72

    58

    12

    ahannel spacings, in.: 3/16 (12 in. maximum width.),

    114 48 ;n.

    maximum width),

    5/16,

    . . .

    3f4

    and:

    l

    Plate thiCknesses: stainless steel) 14-3 U.S. gage; car·

    bon steel, 3/16, 114 and 5/16 in.

    o3oasss4

  • 8/17/2019 CHE Designing Spiral Heat Exchanger - May 1970

    10/10

    SPIRAL·PLATE EXCHANGERS

    Sum of Products

    (SOP):

    SOP

    =

    0.848

    +

    0.927

    +

    0.050

    +

    0.052

    =

    1.877

    Because S0P

    is

    greater than

    1,

    the assumed: heat

    _xchanger is inadequate. The smface • area must

    be enlarged by increasing the plate width or the

    plate .length. Because, in all the equations

    1

    L applles

    directly, the follbwing new length is adopted:

    1.877 X 32.5 -

    61i

    ft.

    Pr essur;e-Drop

    Cal.culations

    Hot side, Eq. (15):

    p . .

    [

    0.001 X.61 ] [ - 6 · ~ ] X

    0;843 0.375 X 24

    [

    1.035 X 3.35

    112

    X 1 X 24

    112

    16 J

    (0.375+

    0.125) 6.225

    1

    12 +

    1.

    5

    + 6f

    t:.P

    · 0.07236

    X

    0.6917

    X

    9.202

    =- 0J461i

    psi.

    Cold side, Eq . (,15):

    t:.P

    .. [1).(101 X 61

    J [ - - 5 . 9 ~ ]

    X

    0.843 0.375 X 24

    f 1.035 X 8

    11

    : X 1 X 24

    112

    , 16]

    t

    (0.375

    +

    €1.125) 5.925112

    +

    LS+ 61

    t:.P = 0.07236 X 0.6583 X 13.55 = 0.645 psi.

    Because the pressure drop

    is

    less than the allowal:lle;

    the spacing

    can•

    be decreased. For the second trial,

    ¥ in. spacing for

    botH

    channels

    is

    adoptedl

    Because the Heat-transfer· equation for every factor

    except the plate varies directly witH

    d

    a new SOP·

    can be

    c a l c u l a t e d ~

    t:.Tl/llTM

    ""

    0.848 (0.25/0.375) = 0.565

    tJ.T;/tJ.7 M

    =

    0.927 (0;25/0.375) = 0.618

    t:.T /ATII

    =

    0.052 (0;25/0.375)

    =

    0.035

    tJ.T,./tJ.TM

    = 0.050

    SOP - 0;565 + 0.618 + 0.050 + 0.052 == 1.285

    L

    =

    1.285 X 32.5

    =

    41.8

    ft.

    A =

    41.8 X 2 X 2

    =

    167 sq.

    ft.

    The new pressure drop becomes:

    Hot side:

    l l

    [' 0.001 X41.8 J [ - · 6 · ~ ~ ~ - ] X

    0.843 0.25 X 24

    [

    1.035 X 3.35

    112

    X 1 X

    24

    112

    16 ]

    M75

    X 6.225112

    + ·1.

    5

    +

    411:8-

    tJ.P

    - 0;04958 X 1.037 X 11.80 = 0.607 psi.

    Colo· side:

    tJ.P _ [·

    o . o o ~ _ 4 h 8 ~ ]

    5.925_.]

    x

    0.843 ' 0.25 X 24

    [

    D.035 X 8

    112

    X 1 X 24

    112

    16 .]

    --o37sx 5.92511··- -- + 1.

    5

    + ·us

    AP

    =

    0.04958 X 0.9875•X 17.59

    =

    0.8611

    The pressure drops are less than the maximum

    allowable.

    The

    plate spacing cannot be less than

    ¥ in. for a 24 .in. plate width; decreasing the width

    would result:

    in

    a higher than allowable pressure drop.

    Therefore, the design is accept:able.

    The diameter of the outside spiral can now be

    calculated with Table and the following equation:

    Ds = [15.36 X L (d,.

    -t

    d;, + 2p) +

    Q2jtl•

    Ds

    =

    115,36

    4L8)

    [0,25 + 0:25 + 2 (0.125)) + 8

    1

    11

    2

    Ds-=

    23.4 in.

    For a spiral-plate exchanger, the best design• is

    often• that•

    in.

    which• the outside diameter approximately

    equals the plate width.

    Design summary:

    Plate

    width..

    . . . . .. .

    ..

    . .. . 24 in.

    Plate

    length..............

    . . . 41.8 f t

    Channel

    spacing... . . . . . . . . . 1/4

    in

    .

    (both sides)

    Spiral diameter.. .. . . . . . . . 23.4 in .

    Heat-transfer area... . . . . . . 167 sq. ft.

    Hot-side pressure drop . . . . . 0.607 psi.

    C o l d ~ s i d e pressure drop

    . . . .

    0. 861 psi.

    U... ... . . . . . . ... . . . . . . ... . . . 38.8 Btu./(hr.)(sq.ft.)("F.)•

    Acknowledgements

    The author thanks American

    Heat

    Reclaiming Corp.

    for.

    providing figures and for permission to use certain

    design.standards. He

    is

    also grateful to the Union Car

    bide Corp

    .

    for permission

    to

    publish this article.

    References

    H Baird, M. H. I..

    MoCrae,

    W .. Rumford. F .. and S l e .

    C. G. M.. Some Consldera.tlon"

    on

    Heat Tm.naofer

    In

    SpLI"al Plate Heat

    Exchangers, Chem. Eng.

    Science., 7,

    1 and 2, 1957, p. 112.

    2.

    BLasius,

    H..

    Dae .\hnlichkeit.sgesets bel Rlebunpvor

    gangzen

    in

    Flussigkeiten, Fonol uug81 e/t.

    Ul,

    1913.

    3.

    C o l b u ~ n , . A . P .. A Method of CoJ:TelaUng F o r c e d • C o n W ~ e

    tlon

    Heat

    TTansfer

    Da.ta

    and

    e.

    Comparison

    With

    Fluid

    F'rlot.lon, A.ICI F: TMM., 9, 1'933, p. 1174.

    4: HargiS, A. M ...

    Beok.mann, A.

    T.

    and Lola.oonoa., JL J.,.

    Applica.tion6 of

    Spiral'

    Plate

    Heat: Ex