charge panel

5
 EML MANUFACTURING, LLC. Engine ered Heaters a nd Controls.  Home  About Us  Products  Electric Heaters  Pr ocess Heater  I mmersion Heater  Circulation Heater  Speci alty Heater Heater Repair Fuel Gas Conditioning Filters & Separators  Process Equipment  Pressur e Vess el  Control Panel  Charge Panel   After market  FUSIBLE LOOP CHARGE PANEL  Fusible Loop Charge Panel What is a fusible loop charge panel? A fusible loop charge panel is a pneumatic panel that monitors a fusible loop system for the detection of fire. The fusible loop panel also complements a fire and gas detect ion sy stem. Fusible loop sy stem are inst alled on o ffshore platforms to det ect fire. T he installat ion of t he fusible lo op are in acco rdance with API RP 14C recommendation. The charge panel will regulate and meter a fix amount of instrument air to the fusible loop. During a fire, the heat generated by the fire will melt one or more of the fusible plug located in or near the fire. The 'melting' of t he plug will cause a release of air from fus ible loo p t hrough t he plug. Since t he release of this regulated air exceeds the amount of regulated/metered air supply, the pressure in the loop will decrease significantly. This decrease in pressure is monitored by a pressure switch on the charge panel. Th e signal from the switch is th en utilized to signal an ala rm to t he Fire and Gas Sy stem. I n addition, an additional pneumatic output is tied to the deluge valve pilot valve where it is use to open the deluge valve. We offer 3 standard panels with the following data sheet.  Customer:  Rev Date By  Tag#  EML Manufacturing  A 3/27/20 10 BW  Description:  P.O. Box 41935, Houston, TX 77241  

Upload: sanjeev-kumar-t-m

Post on 07-Oct-2015

217 views

Category:

Documents


0 download

DESCRIPTION

it requires all the data about panel.......

TRANSCRIPT

  • EML MANUFACTURING, LLC.Engineered Heaters and Controls.

    Home

    About Us

    Products

    Electric Heaters Process Heater

    Immersion Heater

    Circulation Heater

    Specialty Heater

    Heater Repair

    Fuel Gas Conditioning

    Filters & Separators

    Process Equipment

    Pressure Vessel

    Control Panel

    Charge Panel

    Aftermarket

    FUSIBLE LOOP CHARGE PANEL

    Fusible Loop Charge Panel

    What is a fusible loop charge panel? A fusible loop charge panel is a pneumatic panel that monitors a

    fusible loop system for the detection of fire. The fusible loop panel also complements a fire and gas

    detection system. Fusible loop system are installed on offshore platforms to detect fire. The installat ion of

    the fusible loop are in accordance with API RP 14C recommendation.

    The charge panel will regulate and meter a fix amount of instrument air to the fusible loop. During a fire,

    the heat generated by the fire will melt one or more of the fusible plug located in or near the fire. The

    'melt ing' of the plug will cause a release of air from fusible loop through the plug. Since the release of this

    regulated air exceeds the amount of regulated/metered air supply, the pressure in the loop will

    decrease significantly. This decrease in pressure is monitored by a pressure switch on the charge panel.

    The signal from the switch is then ut ilized to signal an alarm to the Fire and Gas System. In addit ion, an

    addit ional pneumatic output is t ied to the deluge valve pilot valve where it is use to open the deluge

    valve.

    We offer 3 standard panels with the following data sheet.

    Customer: Rev Date By

    Tag# EML Manufacturing A 3/27/2010 BW

    Description:

    P.O. Box 41935, Houston, TX 77241

  • Technical Guide

    Contact

    Sitemap

    Project: Ph 281-272-2066

    Doc#: CHARGE PANEL DATA SHEET www.emlmanufacturing.com

    CHARGE PANEL DATA SHEET

    Model FLCP-10 FLCP-20 FLCP-30

    Pneumatic Supply

    Media N2 / Inst. Air N2 / Inst. Air N2 / Inst. Air

    Max Pressure, psig 180@150F 180@150F 180@150F

    Connection

    Pneumatic Supply 1/4" FNPT 1/4" FNPT 1/4" FNPT

    Outlet to plugs 1/4" Tube 1/4" Tube 3/8" Tube

    Pressure Sensor 1/4" Tube 1/4" Tube Connected To Sensor

    Volume Bottle, Note 1

    Size N/A 0.5 gal (2L) 0.5 gal (2L)

    Material N/A 316/L 316/L

    Design, psig N/A 200@200F 200@200F

    Qty None 1 1

    Isolation Valve No No Yes

    Drain Connection N/A 1/4" NPT 1/4" NPT

    Pressure Gauge

    Supply, 0-200psig/(kg/cm 2^) No No Yes - Panel Mount

    Regulated, 0-60psig/(kg/cm 2^) Yes Yes Yes - Panel Mount

    Loop, 0-60psig/(kg/cm 2^) No Yes - Panel Mount Yes - Panel Mount

    Gauge Size & Material 2", 316SS 2" & 2.5", 316SS 2.5", 316SS

    Gauge Vibration Resistance Yes Yes Yes

    Gauge Isolation Valve, 316SS

    No No Yes - Panel Mount

    Construction

    Type Plate Panel - 4 sides enclosed Panel - 4 sides enclosed

    Sunshade No Optional Optional

    Material 316/L SS 316/L SS 316/L SS

  • Mounting Angle Stand Angle Stand Angle Stand

    Size, in (approx) 24"h x 20"w x 8"d 24"h x 20"w x 8"d 24"h x 20"w x 8"d

    Tubing Size 1/4" x 0.035" 1/4" x 0.035" 3/8' x 0.035"

    Tubing Material 316SS Seamless 316SS Seamless 316SS Seamless

    Tubing Fittings 316SS, Double Ferule 316SS, Double Ferule 316SS, Double Ferule

    Supply Isolation Valve Yes Yes Yes

    Filter Regulator

    Material 316SS 316SS 316SS

    Drain Manual Automatic Automatic

    Controls

    Inlet Check Valve, 316SS. Note 2. Single Single Double (Two)

    Manual Loading Valve, 316SS. Momentary. Note 3. No Yes Yes

    Auto lockout valve, 316SS. Note 4. No No Yes

    Metering Orifice, 316SS. Yes Yes Yes

    Pressure Sensor

    Sealed Pressure Switch Yes - Field Installed Yes - Field Installed Yes - Integral

    Note 1 - Volume bottle provides an air reservoir in the event of pneumatic supply interruption.

    Note 2 - Check valve prevents the loss of loop/reservoir pressure in the event of pneumatic supply interruption.

    Note 3 - Loading valve speeds up the start-up of the fusible loop.

    Note 4 - Valve isolates pneumatic supply from loop when a plug is activated.

    Note 5 - Explosion proof hermetically sealed pressure switch to indicate the activation of a fusible plug.

    Switch approved for Division 1 and 2; Class I, Groups A, B, C and D; Class II, Groups E, F and G Hazardous Locations.

    ATEX approved switch is available on request.

    Specificat ion for our high quality FLCP-30 charge panel includes

    a Single zone charge panel. Panel constructed out of 316/L with full depth enclosure on top and sides.

  • b Equipped with 2 liter (0.52 gallon) capacity volume bottle with double check as a back-up to interruption ofair/nitrogen supply. Volume bottle constructed out of 316/L stainless steel and design for 200 psig withhydro testing. Equipped with 316SS isolation valve and drain.

    c All 316SS filter regulator with automatic liquid drain feature.

    d Panel equipped with 316SS quick charge button to provide quickly and efficient start-up.

    e A 316SS low pressure cutoff switch is provided to remove air/nitrogen from the loop in the event of afusible plug activation to ensure a failsafe system.

    f Panel is equipped with an explosion proof hermetically sealed pressure switch to indicate the activation ofa fusible plug. Switch approved for Division 1 and 2; Class I, Groups A, B, C and D; Class II, Groups E, Fand G Hazardous Locations. ATEX approved switch is available on request.

    g Copper free aluminum pull box provided to facilitate wiring of pressure switch.

    h 2.5" Vibration resistant stainless steel pressure gauge for the indication of supply pressure. Dual scale 0to 200 psi/(kg/cm^2) range. Equipped with 316SS isolation valve mounted on front of panel with lockingprovision.

    i 2.5" Vibration resistant stainless steel pressure gauge for the indication of regulated pressure. Dual scale0 to 60 psi/(kg/cm^2) range. Equipped with 316SS isolation valve mounted on front of panel with lockingprovision.

    j 2.5" Vibration resistant stainless steel pressure gauge for the indication of loop pressure. Dual scale 0 to60 psi/(kg/cm^2) range. Equipped with 316SS isolation valve mounted on front of panel with lockingprovision.

    k 3/8" tube connection provide with 316SS inlet isolation valve with locking provision for customer'sincoming pneumatic supply.

    l 3/8" tube connection provide for connection to fusible loop. 1/2" tube connection available on request.

    m Tubing are 3/8"OD x 0.049" seamless 316/L stainless steel. Tube fittings are high quality double ferrule316SS tube fittings.

    n All wetted parts are constructed out of 316 Stainless Steel to prevent corrosion and contamination offusible loop.

    o Air or Nitrogen supply to range from 60 to 180 psig.

    p Size is approximately 20W x 24H x 8.5D.

    We also offer fusible plug and fusible tubing to complement our fusible loop panel.

  • Do contact us for your instrumentation needs.