chapter 2 control techniques for multilevel voltage source...
TRANSCRIPT
19
CHAPTER 2
CONTROL TECHNIQUES FOR MULTILEVEL
VOLTAGE SOURCE INVERTERS
2.1 INTRODUCTION
Pulse Width Modulation (PWM) techniques for two level inverters
have been studied extensively during the past decades. Many different PWM
methods have been developed to achieve the following aims; wide linear
modulation range, reduced switching loss, lesser total harmonic distortion in
the spectrum of switching waveform, easy implementation, less memory
space and computation time on implementing in digital processors for the
proposed work. The two most widely used PWM schemes for multi-level
inverters are the carrier based PWM (sine-triangle PWM or SPWM)
techniques and the space vector based PWM techniques. These modulation
techniques are extensively studied and compared for the performance
parameters with two level inverters.
The SPWM schemes are more flexible and simple to implement, but
the maximum peak of the fundamental component in the output voltage is
limited to 50% of the DC link voltage and the extension of the SPWM
schemes into over-modulation range is difficult. In SVPWM schemes, a
reference space vector is sampled at regular intervals for determination of the
inverter switching vectors and their time durations, in a sampling interval. A
space phasor based PWM scheme for multi-level inverters use only the
instantaneous amplitudes of reference phase voltages. The SVPWM scheme
20
presented for multi-level inverters can also work in the over-modulation
range, using only the instantaneous amplitudes of reference phase voltages.
In the recent past the multilevel power converters have drawn a
tremendous interest in the field of high voltage and high power applications
field in industries. The multilevel inverter approach allows the use of high
power and high voltage electric motor drive systems. Using the multilevel
inverter concept, a divide and conquer approach allows more flexibility and
control over the discrete components that makeup the system. In the
researches on multilevel inverters, their corresponding PWM control
strategies are the emerging research areas.
In high power and high voltage applications, the two level inverters,
however, have some limitations in operating at high frequency mainly due to
switching losses, dv/dt and di/dt stresses in power semiconductor devices and
constraint of the semiconductor power device ratings. For high voltage
applications two or more power devices can be connected in series to achieve
the desired voltage ratings and in parallel to achieve the current ratings.
Multilevel inverters can increase the power by (m-1) times than that of two
level inverter through the series connection of power semiconductor devices.
This research focuses on the different control strategies and a suitable
modulation strategy is selected based on the outputs obtained through the
simulations on the MATLAB SIMULINK software environment.
2.2 OPEN LOOP MODULATION
The control techniques for the multilevel voltage source inverter are
classified into three basic types as PWM, Selective Harmonics Elimination
Pulse Width Modulation (SHEPWM) and Optimized Harmonics Stepped
Waveform (OHSW). PWM can be classified into open and closed loop as
discussed by Carrara et al (1992).
21
The Sinusoidal Pulse Width Modulation (SPWM) has got a
few different supplementary names in relation with the triangular carrier
waveforms and are as shown in Figure 2.1. Symmetrical SPWM, when
triangular carrier was symmetric, as shown in Figure 2.1 (a). Leading edge
SPWM, when the initial slope of triangular carrier signal was infinite, as
shown in Figure 2.1 (b). Trailing edges SPWM, when the trailing edge
slope of triangular carrier signal was infinite, as shown in
Figure 2.1 (c).
(a) (b) (c)
Figure 2.1 a) Symmetrical SPWM carrier, b) Leading edge SPWM
carrier, c) Trailing edge SPWM carrier
Generally SPWM have got a few different supplementary names in
relationship with the position of the carrier signal to the modulation wave.
Synchronous SPWM, both signals were synchronous with each other if the
carrier frequency is a multiple of the sine wave frequency (fs = k*fm).
Asynchronous SPWM, both signals were asynchronous, when the carrier
frequency is not a multiple of the sine wave frequency (fs ≠ k*fm)
Based on the applications of PWM signals to multilevel inverters,
the multilevel sinusoidal PWM can be classified according to carrier and
modulating signals as shown in Figure 2.2.
22
Figure 2.2 Classification of SPWM
2.3 MULTICARRIER PWM TECHNIQUES
Multicarrier PWM techniques entail the natural sampling of a single
modulating or reference waveform typically being sinusoidal same as that of
output frequency of the inversion system, through several carrier signals
typically being triangular waveforms of higher frequencies of several kilo
Hertz discussed by McGrath et al (2002) and Samir Kouro et al (2008). They
can be categorized as follows
Sinusoidal Pulse
Width Modulation
Modulating Signal Carrier Signal
Phase Disposition
Super Imposed
Carrier
Phase Opposition
Disposition (POD)
Alternate POD
Hybrid (H)
Phase Shift (PS)
Other Techniques
Dead Band
Third Harmonic
Injection
Pure Sinusoidal
23
2.3.1 Alterative Phase Opposition Disposition (APOD)
This technique requires each of the (m – 1) carrier waveforms, for
an m-level phase waveform, to be phase displaced from each other by 1800
alternately as shown in Figure 2.3. The most significant harmonics are
centered as sidebands around the carrier frequency fc and therefore no
harmonics occur at fc.
Time (Seconds)
Mag
nit
ud
e (p
u)
Figure 2.3 APOD carrier technique
2.3.2 Phase Opposition Dispositions (POD)
The carrier waveforms are all in phase above and below the zero
reference value however, there is 1800 phase shift between the ones above and
below zero respectively as shown in Figure 2.4. The significant harmonics,
once again, are located around the carrier frequency fc for both the phase and
line voltage waveforms. The three disposition PWM techniques that are
APOD, PD and POD generate similar phase and line voltage waveforms.
Furthermore, for all of them, the decision signals have average frequency
much lower than the carrier frequency.
24
[
Mag
nit
ud
e (p
u)
Time (Seconds)
Figure 2.4 POD carrier technique
2.3.3 Hybrid (H)
This technique, as mentioned earlier, combines the previously
presented ones (disposition) and the well known phase shifted multicarrier
technique. The bands used for modulation are only two, however, each time
the level of the power converter is increased, and more triangular carriers are
introduced and phase shifted accordingly. The two carriers above zero have
the same peak to peak value and the same frequency fc. However, there is an
1800 phase shift between them. The same applies for the two carriers below
zero. In the case that the number of converter levels is higher, the carriers are
phase shifted accordingly, that is 1200 for a 7 level system and 90
0 for a 9
level system and so on and so forth.
It is important to note that the significant harmonics are
concentrated around multiples of (m - 1)/2 of the carrier frequency fc. For
instance, for a 5-level converter, the harmonics are located around 2fc, for a 7
level around 3fc
and for a 9 level around 4fc. The gap between the
fundamental and the first significant harmonics increases accordingly as
shown in Figure 2.5.
25
Figure 2.5 H carrier technique
2.4 MODULATING SIGNAL
Sinusoidal PWM can be classified according to the modulating
signal into, Pure Sinusoidal PWM (PSPWM), Third Harmonic Injection
PWM (THIPWM) and Dead Band PWM (DBPWM) by Salmon et al (2008),
Zhong Du et al (2008) and Zhou and Wang (2002). Sinusoidal PWM is the
most widely accepted PWM technique, where a triangular wave is compared
with a sinusoidal reference known as the modulating signal, shown in
Figure 2.6.
Figure 2.6 Pure sinusoidal modulating signal control technique
Mag
nit
ud
e (p
u)
Time (Seconds)
Time (Seconds)
Mag
nit
ud
e (p
u)
26
2.4.1 Third Harmonic Injection PWM (THIPWM)
A method to improve the gain of the pulse width modulator in a
multilevel inverter is to inject a third harmonic. This technique is derived
from conventional sinusoidal PWM with the addition of a 17% third harmonic
component to the sine reference waveform as shown in Figure 2.7. The
hardware implementation of this technique is straightforward. It should be
noted that the 15% increase in gain over the SPWM technique is achieved at
the expense of introducing third harmonics on the line to neutral waveforms.
However for a balanced load with a floating neutral point, third harmonic
current cannot flow and therefore third harmonic voltages are not present on
the line to line waveforms. Although, the above mentioned switching patterns
for PWM converters provide increased gain compared with the conventional
SPWM technique, they also imply the reference or modulating waveforms
have to be continuous regardless of their shape.
As a result they do not provide any reduction in switching frequency
compared with the SPWM. For third harmonic injection PWM, the reference
waveform is defined as f(ω,t) = 1.15Ma sin(ωot)+0.19 Ma sin(3ωot); 0 ≤ ωot ≤
2π Where, Ma is the modulation index ratio. The zero sequence voltage can
be expressed as,
Vzero = [max (Va, Vb, Vc) + min (Va, Vb, Vc)] / 2 (2.1)
;Figure 2.7 Third harmonic injection modulating signal control technique
Mag
nit
ud
e (p
u)
Time (Seconds)
27
A modulation scheme is presented by Aziz et al (2004), where a
fixed common mode voltage, is added to the reference phase voltage
throughout the duration range. It has been shown that this common mode
addition will not result in a SVPWM like performance, as it will not centre
the middle inverter vectors in a sampling interval. The common mode voltage
to be added in the reference phase voltages, to achieve SVPWM like
performance, is a function of the modulation index for multilevel inverters.
A SVPWM scheme based on the above principle has been
presented in Boys et al (1990), where the switching time for the inverter legs
is directly determined from sampled phase voltage amplitudes. This technique
reduces the computation time considerably more than the conventional
SVPWM techniques do, but it involves region identification based on
modulation indices. While this SVPWM scheme works well for a three-level
PWM generation, it cannot be extended to multilevel inverters of levels
higher than three, as the region identification becomes more complicated. A
carrier based PWM scheme has been presented Celanovic et al (2001), where
sinusoidal references are added with a proper offset voltage before being
compared with carriers, to achieve the performance of a SVPWM. The offset
voltage computation is based on a modulus function depending on the DC
link voltage, number of levels and the phase voltage amplitudes. The
implementation details and the operation of the proposed method in the over
modulation region remain unaddressed.
The objective of this work is to present an implementation scheme
for PWM signal generation for multilevel inverters, similar to the SVPWM
scheme, for the entire range of modulation indices including over modulation.
The PWM switching times for the inverter legs are directly derived from the
sampled amplitudes of the reference phase voltages. The SVPWM switching
pattern generation is not realized with offset voltage computation from a
28
modulus function. A simple way of adding a time offset to the inverter-gating
signal is to generate the SVPWM pattern from only the sampled amplitudes of
reference phase voltages. The proposed SVPWM signal generation does not
involve checks for region identification, as in the conventional SVPWM
scheme presented. Also, the algorithm does not require either sector
identification or look up tables for switching vector determination as are
required in the conventional multilevel SVPWM schemes. Thus the scheme is
computationally efficient when compared to conventional multilevel SVPWM
schemes, making it superior for real time implementation.
The proposed SVPWM algorithm can easily be extended to any
multilevel inverter configurations. For experimental verification of the
proposed SVPWM scheme, we are using a five level inverter of cascaded
multilevel inverter configuration.
2.5 PROPOSED SVPWM FOR MULTILEVEL INVERTER
The two most widely used PWM schemes for cascaded multilevel
inverters are the carrier-based sine-triangle PWM (SPWM) technique and the
space vector PWM (SVPWM) technique. These modulation techniques have
been extensively studied and compared for the performance parameters with
two-level inverters in Holtz (1992). The SPWM schemes are more flexible
and simpler to implement, but the maximum peak of the fundamental
component in the output voltage is limited to 50% of the DC link voltage in
Li Li et al (2000) and the extension of the SPWM schemes into the over-
modulation range is difficult. In SVPWM schemes, a reference space vector is
sampled at regular intervals to determine the inverter switching vectors and
their time durations, in a sampling interval.
The SVPWM scheme gives a more fundamental voltage and better
harmonic performance compared to the SPWM schemes. The maximum peak
29
of the fundamental component in the output voltage obtained with space
vector modulation is 15% greater than with the sine triangle modulation
scheme. But the conventional SVPWM requires sector identification and look
up tables to determine the timings for various switching vectors of the
inverter, in all the sectors by Subrata et al (2003). This makes the
implementation of the SVPWM scheme quite complicated. A SVPWM
scheme, extending the modulation range into the over modulation range, has
been presented by Holtz et al (1993), in which extensive offline computations
and look up tables are required, to determine the modified reference vector, in
the over modulation range, extending up to six-step operation. It has been
shown that, for two level inverters, a SVPWM like performance can be
obtained with a SPWM scheme by adding a common mode voltage of suitable
magnitude, to the sinusoidal reference phase voltage.
A simplified method, to determine the correct offset times for
centering the time durations of the middle inverter vectors, in a sampling
interval, is presented by Khambadkone et al (2002) and Holmes (1992), for
the two-level inverter. The inverter leg switching times are calculated directly
from the sampled amplitudes of the reference three-phase voltages with
considerable reduction in the computation time.
The SPWM technique, when applied to multilevel inverters, uses a
number of level shifted carrier waves to compare with the reference phase
voltage signals. The SVPWM for multilevel inverters involves mapping of the
outer sectors to an inner sub hexagon sector, to determine the switching time
duration, for various inverter vectors. Then the switching inverter vectors
corresponding to the actual sector are switched, for the time durations
calculated from the mapped inner sectors. It is obvious that such a scheme, in
multilevel inverters, will be very complex, as a large number of sectors and
inverter vectors are involved. This will also considerably increase the
30
computation time for real time implementation.
A modulation scheme is offered, where a fixed common mode
voltage is added to the reference phase voltage throughout the modulation
range. It has been shown that this common mode addition will not result in a
SVPWM like performance, as it will not centre the middle inverter vectors in
a sampling interval. The common mode voltage to be added in the reference
phase voltages, to achieve SVPWM like performance, is a function of the
modulation index for multilevel inverters. A carrier based PWM scheme has
been presented, where sinusoidal references are added with a proper offset
voltage before being compared with carriers, to achieve the performance of a
SVPWM. The offset voltage computation is based on a modulus function
depending on the DC link voltage, number of levels and the phase voltage
amplitudes.
In the SPWM scheme for two level inverters, each reference phase
voltage is compared with the triangular carrier and the individual pole
voltages are generated, independent of each other.
A novel method is developed to obtain an equivalent SVPWM
pulses for the proposed multilevel inverter from the conventional SPWM. The
offset voltage is obtained as shown in Figure 2.8.
Figure 2.8 Calculation of Voffset1 from phase voltage samples
31
To obtain the maximum possible peak amplitude of the fundamental
phase voltage in linear modulation, a common mode voltage, Voffset1, is added
to the reference phase voltages where the magnitude of Voffset1 is given by,
Voffset1= - (Vmax+Vmin)/2 (2.2)
Where,
Vmax = Maximum magnitude of the three sampled
reference phase voltages, in a sampling interval.
Vmin = Minimum magnitude of the three sampled reference
phase voltages, in a sampling interval.
i.e. Vmax = max (Van,Vbn,Vcn)
Vmin = min (Van,Vbn,Vcn)
The addition of the common mode voltage, Voffset1, results in the
active inverter switching vectors being centered in a sampling interval,
making the SPWM technique equivalent to the SVPWM technique.
Equation (2.2) is based on the fact that, in a sampling interval, the reference
phase which has lowest magnitude (termed the min phase) crosses the
triangular carrier first and causes the first transition in the inverter switching
state. While the reference phase, which has the maximum magnitude (termed
the max-phase), crosses the carrier last and causes the last switching transition
in the inverter switching states in a two level SVPWM scheme.
Figure 2.9 Reference voltages and triangular carriers for a five level
PWM scheme
32
Thus the switching periods of the active vectors can be determined
from the (max phase and min phase) sampled reference phase voltage
amplitudes in a two level inverter scheme. The SPWM technique for
multilevel inverters, involves comparing the reference phase voltage signals
with a number of symmetrical level shifted carrier waves for PWM
generation. It has been shown that for an n level inverter, ( n-1) level shifted
carrier waves are required for comparison with the sinusoidal references.
Because of the level shifted multi carriers as shown in Figure 2.9, the first
crossing (termed the first cross) of the reference phase voltage cannot always
be the min phase.
Similarly, the last crossing (termed the third cross) of the reference
phase voltage cannot always be the max phase. Thus the offset voltage
computation, based on Equation (2.2) is not sufficient to centre the middle
inverter switching vectors, in a multilevel PWM scheme during a sampling
period Ts shown in Figure 2.10. In this, a simple technique to determine the
offset voltage (to be added to the reference phase voltage for PWM generation
for the entire modulation range) is presented, based only on the sampled
amplitudes of the reference phase voltages.
The proposed scheme determines the sampled reference phases. The
obtained reference phase which crosses the triangular carrier first is defined as
first cross and the subsequent crosses are referred as second cross and the
third cross. Once the first cross and third cross phase is identified, the
principle of offset calculation given by Equation (2.2) is used to determine the
second cross. The same can be adopted for the multilevel SVPWM generation
scheme. This technique presents a simple way to determine the time instants
at which the three reference phases crosses the triangular carriers.
33
Figure 2.10 Determination of the Ta cross, Tb cross and Tc cross during
switching interval TS (MI=0.433)
These time instants are sorted to find the offset voltage to be added
to the reference phase voltages for SVPWM generation for multilevel
inverters for the entire linear modulation range, so that the middle inverter
switching vectors are centered (during a sampling interval), as in the case of
the conventional two level SPWM scheme.
2.5.1 Determination of Inverter Leg Switching Times
Figure 2.9 shows a reference voltage and four triangular carriers
used for PWM generation for a five level inverter. The modified reference
phase voltages are given by,
offset1XN
*
XN VVV += , X=A, B, C (2.3)
Where, VAN, VBN, VCN are sampled amplitudes of three reference
phase voltages during the current sampling interval. The reference phase
voltages are equally spaced between the four carriers as shown in Figure 2.9,
for a five-level inverter. For modulation indexes less than 0.433 (half of the
maximum Modulation Index in the linear range of modulation for a five level
34
inverter), the reference phase voltage spans inner two carriers. For modulation
indexes higher than 0.433, the reference phase voltages expand into the outer
carrier regions. The addition of Voffset1, obtained from Equation (2.2), to the
reference phase voltage ensures that the modified reference voltages always
remain within the carrier regions through the linear modulation range.
The reference phase voltages cross the triangular carriers at different
instants of a sampling period Ts shown in Figure 2.10. Each time a reference
phase voltage crosses the triangular carrier, it causes a change in the inverter
state. The phase voltage variations and their time durations are shown in
Figure 2.10. The sampling time interval Ts, can be divided into four time
intervals T01, T1, T2 and T03. T01 and T03 are defined as the time durations for
the start and end inverter switching vectors respectively in a sampling time
interval Ts. T1 and T2 are defined as the time durations for the middle inverter
switching vectors, in a sampling time interval Ts. It should be noted from
Figure 2.10 that the middle switching vectors are not centered in a sampling
interval Ts. So an additional offset (offset2) needs to be added to the reference
phase voltages, so that the middle inverter switching vectors can be centered
in a sampling interval.
The time duration, at which the A phase crosses the triangular
carrier, is defined as Ta cross. Similarly, the time durations, when the B phase
and C phase cross the triangular carrier, are defined as Tb cross and Tc cross
respectively. Figure 2.10 shows a sampling interval when the A phase is in
the carrier region C1 while the B phase and C phase are in carrier region C2,
the time duration, Ta cross, (measured from the start of the sampling interval)
at which the A phase crosses the triangular carrier is directly proportional to
the phase voltage amplitudes, VAN . The time duration Tb cross at which the B
phase crosses the triangular carrier is proportional to * DCBN
VV +
4
⎛ ⎞⎜ ⎟⎝ ⎠ and the
35
time duration, Tc cross, at which the C phase crosses the triangular carrier and
it is proportional to * DCCN
VV +
4
⎛ ⎞⎜ ⎟⎝ ⎠ . Therefore
* *DCa_cross AN as
VT = V + T
4= (2.4)
* *DC sc_cross CN cs s
DC
V TT = V + * T T
V4
4
⎛ ⎞ = +⎜ ⎟⎝ ⎠ (2.5)
* *DC sb_cross BN bs s
DC
V TT = V + * T T
V4
4
⎛ ⎞ = +⎜ ⎟⎝ ⎠ (2.6)
Where,
T*as, T
*bs, T
*cs are the time equivalents of the phase voltage
magnitudes.
The proportionality between the time equivalents and corresponding
voltage magnitudes is defined as follows:
DC*
AN
*
s as
VV4
T T=
DC*
BN
*
s bs
VV4
T T=
DC*
CN
*
s cs
VV4
T T= (2.6a)
36
Figure 2.11, shows the situation, where the reference phase voltages
span the entire carrier region for a five level inverter scheme. The time
durations, at which the reference phase voltages cross the carrier, can be
determined similarly. As shown in Figure 2.11, Tacross is proportional to
* DCAN
VV -
4
⎛ ⎞⎜ ⎟⎝ ⎠ whereas Tbcross is proportional to * DCBN
VV +
2
⎛ ⎞⎜ ⎟⎝ ⎠and Tccross is
proportional to * DCCN
VV +
4
⎛ ⎞⎜ ⎟⎝ ⎠ .
Figure 2.11 Determination of the Ta cross, Tb cross and Tc cross during
switching interval TS
Therefore, from Equation.(2.5)
Tfirst cross= min (Tx cross),
Tsecond cross = mid (Tx cross), (2.7)
Tthird cross = max (Tx cross), X= a, b, c
In the present work, the Ta cross, Tb cross and Tc cross time durations
obtained above are used to centre the middle switching vectors, as in the case
of two level inverters, in a sampling interval Ts. The time duration at which
the reference phases cross the triangular carriers for the first time, is defined
37
as Tfirst cross. Similarly, the time durations, at which the reference phases cross
the triangular carriers for the second and third time, are defined as, Tsecond cross
and Tthird cross respectively, in a sampling interval Ts. The time durations Tfirst
cross, Tsecond cross and Tthird cross decides the switching times for the different
inverter voltage vectors, forming a triangular sector, during one sampling
interval Ts.
The time durations for the start and end vectors are T01 = Tfirst cross,
T03 = Ts - Tthird cross respectively as shown in Figure 2.10. The middle vectors
are centered by adding a time offset Toffset2 to Tfirst cross, Tsecond cross and Tthird
cross. The time offset Toffset2 is determined as follows. The time duration for the
middle inverter switching vectors Tmiddle is given by,
Tmiddle = Tthird cross -Tfirst cross (2.8)
The time duration of the start and end vector is,
T0 =Ts - Tmiddle (2.9)
Thus the time duration of the start vector is given by,
T0/2 = Tfirst cross + Toffset2 (2.9a)
Therefore,
Toffset2 = T0/2 -Tfirst cross (2.10)
The addition of the time Toffset2 to Ta cross, Tb cross and Tc cross gives the
inverter leg switching times Tga, Tgb and Tgc for phase A, B and C,
respectively.
38
Tga = Ta cross+Toffset2
Tgb = Tb cross+Toffset2 (2.11)
Tgc = Tc cross+Toffset2
The traces of different timing signals, for the proposed PWM
scheme, are shown in Figure 2.13 and Figure 2.14, for a five level PWM
generation. The traces of Ta cross for various modulation indices are shown in
Figure 2.12. The traces of Tfirst cross, Tsecond cross and Tthird cross are shown in
Figure 2.13a while the traces of Tg first cross, Tg second cross and Tg third cross are
shown in Figure 2.13b. It can be seen from Figure 2.13b, that the time
durations for the start vector (Tg first cross) and for the end vector (Ts - Tg third cross)
are equal. Thus the middle vectors are always centered, in a sampling time
interval Ts. The corresponding traces of the total offset, *Tas
+ Toffset2, added to
the sinusoidal reference phase voltage to make the SPWM equivalent to the
SVPWM is shown in Figure 2.14.
2.5.2 Steps Involved in the Proposed Method
The following are the steps involved to find out the switching
periods of inverter legs for n level inverter scheme,
Step: 1 Read the sampled amplitudes of VAN, VBN and VCN from the
current sampling interval
Step: 2 Determine the time equivalents of phase voltages, i.e. Tas, Tbs and
Tcs.
Step: 3 Find Toffset1 using Tmax and Tmin, Tmax, Tmin are the maximum and
minimum of Tas, Tbs and Tcs.
39
Step: 4 Determine Teffective.
Step: 5 Determine Ta cross, Tb cross and Tc cross.
Step:6 Sort Ta cross,Tb cross and Tc cross to determine Tfirst cross,Tsecond cross and
Tthird cross.
i. The maximum of Ta cross,Tb cross and Tc cross is Tthird cross.
ii. The minimum of Ta cross,Tb cross and Tc cross is Tfirst cross.and the
remaining one is Tsecond cross.
Step:7 Assign first_cross_phase, second_cross_phase and third_cross_
phase according to the phase which determines Tfirst cross,Tsecond cross
and Tthird cross.
Step: 8 Determine Tga, Tgb and Tgc.
Figure 2.12 Trace of Ta cross for MI 0.41 and 0.83
40
(a)
(b)
Figure 2.13 Traces of Tfirst cross, Tsecond cross and Tthird cross (a) Non-centered
time duration for middle vectors (b) Centered time duration
for middle vectors, after addition of required offset, T offset2
Volt
age
(V)
Time (S)
Figure 2.14 Modulation index profile of Toffset1+ Toffset2 for modulation
index=0.85
41
2.6 COMPARISON OF SPWM AND SVPWM
Table 2.1 Comparison of SPWM and SVPWM
S.NO SPWM Proposed SVPWM
1 Generate high harmonic
distortion in the output voltage
or current
Generate low harmonic distortion
in the output voltage or current
2 Provides less efficient use of
supply voltage
Provides more efficient use of
supply voltage
3 For m=1, amplitude of
fundamental for Vao is Vdc/2
amplitude of line to line is 3/2
Vdc
Maximum possible phase voltage
without over modulation is 1/3
Vdc Amplitude of line to line isVdc
4 DC utilization of SPWM is
low
DC utilization of is better than
SPWM
5 It treats the three phase
quantities separately
In SVM, the three phase
quantities are treated using single
equation known as space vector
6 Extension of scheme into over
modulation range is difficult
Extension of scheme into over
modulation range is easy
7
Independent on number of
levels, number of phases, level
of dc voltage unbalance and
modulation modes
Depends on number of levels,
number of phases, level of dc
voltage unbalance and modulation
modes
42
2.7 SIMULATION OF CONTROL TECHNIQUES FOR
MULTILEVEL INVERTERS USING MATLAB/SIMULINK
Figure 2.15 shows the MATLAB/SIMULINK model for five level
PSPWM based cascaded multilevel inverter. In this model the two H bridge
inverters are connected in series in order to form five level cascaded
multilevel inverters.
The two level carrier based PWM techniques was extended to
multilevel inverters by making use of several triangular carrier signals and
one reference signal per phase. For m level inverter, (m-1) carriers with the
same frequency fc and same peak to peak amplitude Ac are disposed such that
the bands they occupy are contiguous. The reference is continuously
compared with each of the carrier signals. If the reference signal is greater
than a carrier signal, then the active device corresponding to that carrier is
switched ON, and if the reference signal is less than a carrier signal, then the
active device corresponding to that carrier is switched OFF. Figure 2.15(b)
THIPWM is quite similar to PSPWM, unlike PSPWM; in THIPWM third or
zero sequence voltage is added to pure sinusoidal modulating wave.
2.7.1 Simulation Results
A comparison between different carrier techniques for a 5 level
inverter using PSPWM and THIPWM modulating signal is performed. The
carrier and modulating signal frequencies are 5 kHz and 50 Hz respectively.
For the PSPWM and THIPWM technique, Figure 2.15(a) and 2.15(b) indicate
the multilevel SIC carrier based control technique which shows the carrier
bands. Modulation waveform and inverter output waveforms are obtained for
ma=1, mf =20.
43
(a)
(b)
Figure 2.15 MATLAB/SIMULINK model for 5-level cascaded multilevel
Inverter (a) PSPWM (b) THIPWM
44
2.7.2 Modeling of Proposed SVPWM
The SVPWM is implemented in the MATLAB/SIMULINK
environment based on the equations from Equation 2.1 to Equation 2.11. The
individual blocks are modeled with the corresponding equations and are
linked together to obtain the simulation results. The blocks used to simulate
the SVPWM control technique for three phase cascaded multilevel inverter
are shown in Figure 2.16.
Figure 2.16 Matlab/simulink model of a three phase cascaded multilevel
inverter with the proposed SVPWM
The offset voltage waveforms are derived based on the equations for
offset voltage and from the sampled intervals of phase voltages. The offset
voltages are obtained for individual crosses like first_cross, second_ cross and
etc., The obtained offset voltage waveform for three phase five level cascaded
multilevel inverter are as shown in Figure 2.17. This offset voltage waveform
45
is for the first_cross in similar way the other offset voltages are obtained for
every cross.
Time (Seconds)
M
agn
itu
de
(V)
Figure 2.17 Offset voltage waveform
After obtaining the offset voltages for individual crosses the time
equivalents are obtained with the addition of the time, Toffset2 to Ta cross, Tb cross
and Tc cross gives the inverter leg switching times Tga, Tgb and Tgc for phases A,
B and C, respectively which is shown in Figure 2.19. This switching time
intervals are given to the respective phase power switches and the effective
voltages for all the phases are obtained and the same is captured with the aid
of scope block in the MATLAB/SIMULINK editor and the same is shown in
Figure 2.18. The respective phases A, B, C are as shown in red, blue and
green respectively.
The phase sequence for the output effective voltage waveform is A,
B and C. The output waveform coincides with the desired pattern which
confirms that the respective switches are turned ON and OFF at correct
instances without any crossovers.
46
Figure 2.18 Effective voltage waveform
Figure 2.19 Four triangular waveforms and the time equivalents of the
phase voltages
To obtain the switching pulses for the five level cascaded
Configurations, the (n-1) triangular carrier waveforms are chosen and the
same is shown in Figure 2.19. The carrier waveforms and their respective
time equivalents obtained for the respective phase voltages are shown in
Figure 2.19. The same pattern is obtained for different time instances for
Time (Seconds)
M
agn
itu
de
(V)
M
agn
itu
de
(V)
Time (Seconds)
47
understanding purpose, a particular time instant with the desired phase
sequence is presented. The output phase voltage waveforms obtained with the
aid of the derived pulses from the modelling is shown in the Figure 2.20. The
Figure 2.21 shows the line voltage waveforms for the modelled system with
the SVPWM control algorithm for three phase five level inverter.
Time (Seconds)
M
agn
itu
de
(V)
Figure 2.20 Phase voltage waveforms
M
agn
itu
de
(V)
Time (Seconds)
Figure 2.21 Line voltage waveforms
48
2.7.3 Results
The simulation is done for all the discussed control techniques for
different frequencies, different modulation indices and the waveforms are
analyzed. The parameters such as output voltage level, various levels of THD
obtained for individual algorithm are captured at the required instances and
the same is plotted for the study of the particular control algorithm and the
selection of an suitable algorithm is done. The output line voltage levels of the
simulated system for different harmonics order is shown in Figure 2.22. Here
the output is plotted for all the control techniques employed for simulation.
Among these of these the APOD and SVPWM give the better fundamental
voltage magnitude when compared with the other techniques.
The plot also reveals that the lower order harmonics are also less for
these two techniques when compared to other control algorithms for
multilevel configuration. As the harmonics order increases the magnitude of
output harmonics is reduced significantly. At higher order harmonics the
APOD and SVPWM techniques give better results for the elimination of the
lower order harmonics. Even though the higher order components present at
the output can be easily filtered out with least values of L and C components
and the losses on the filtering.
Figure 2.22 Harmonic spectrum of phase voltage with different control
techniques
49
The output waveforms were analyzed in terms of percentage of
output THD by varying the modulation index for the different techniques
adopted for simulation of the multilevel inverter configuration. The MI is
varied from 0.1 to 1 and the output THD levels are captured and the same is
plotted as shown in Figure 2.23.
The percentage THD is very higher for lower MI and it is almost
seventy percentage when the MI = 0.1 and slightly differs for different control
techniques. As MI is increased progressively the output THD levels reduced
considerably for specific control techniques. As far as the output THD levels
are concerned the SVPWM technique is showcasing the better performance
when compared to the other control techniques adopted for simulation. From
the Figure 2.23 it is evident that SVPWM gives the least THD level when the
MI is greater than 0.866.
Figure 2.23 Output phase voltage % THD Vs modulation index with
different control technique
The current drawn by the load is noted for different modulation
indices for the different control techniques as shown in Figure 2.24. As the
50
MI increases the current drawn by the load is increased but it differs for
different control techniques. At MI is 0.8, all the control techniques almost
draws the same load current but for higher MI the few control strategies gives
the better results in terms of the magnitude of the current. If the current level
decreases the losses on the system will get decreased which is the indication
of the higher magnitude of fundamental component, which is a desired
outcome for the control techniques. The magnitude of the current is low at the
higher modulation index for certain control techniques (for APOD, PS and
SVPWM) as indicated in Figure 2.24. Among these proposed control
techniques the PS, APOD and SVPWM. The SVPWM gives at the better
performance in all the operating conditions.
Figure 2.24 Load current Vs modulation index with different control
technique
The graphs were plotted for output percentage THD for different
control techniques as shown in Figure 2.25. From the graph it is inferred that
for the given MI the output THD levels get differed based on the control
technique. As far as THD levels are concerned the control techniques such as
APOD, PD,SIC and SVPWM, only SVPWM shows the better performances,
51
of which the other techniques like PD and SIC are not satisfied in terms of
output voltage magnitude and load currents.
Figure 2.25 Output THD Vs various modulation techniques for MI =1.0
Even though some control techniques are showcasing the similar
results in certain aspects, it should be noted for the flexibility in
implementation for different levels, consistency in performance with slight
modifications in load parameters. Based on these, SVPWM control technique
is considered as a superior one for the hardware implementation with the
latest digital processors.
2.8 CONCLUSION
The performance of any power converter depends on the modulation
algorithm employed and so the multilevel inverters. Several works on the
modulation techniques for the two and three level inverters were implemented
but for higher level inverters. The modulation techniques are still mostly
unexplored because of large number of inverter switching states and they
increase the computational difficulties. The various modulation techniques
52
were simulated using the MATLAB/SIMULINK environment and the output
parameters were presented and elaborately discussed. The analysis is done
richly with respect to the fundamental output voltage levels, output total
harmonics distortion levels, different modulation indices for multilevel
configuration with the different control techniques.
In SVM for three phase five level inverter, five kinds of switching
states exist in each phase. The five level inverter has 53 = 125 switching
states/space vector combinations, 96 sectors, 61 locations and four layers. A
novel voltage modulation scheme of the SVPWM has been presented which
gives the performance like that of SVM techniques for cascaded multilevel
inverter. The implementation and performance of the proposed scheme yields
best results and also the centering of the middle inverter switching vectors of
the SVPWM is achieved by the addition of an offset time signal to the
inverter gating signals, derived from the sampled amplitudes of the reference
phase voltages.
The proposed SVPWM scheme covers the entire modulation range
and over-modulation too. The proposed technique does not need any sector
identification and voltage vectors as the case in conventional SVM schemes.
Complicated calculations for inverter switching vector times and look-up
tables for selecting the inverter switching vectors are also avoided in this
proposed method. This reduces the computation time required to determine
the switching times for inverter legs and memory requirement of the digital
processors making the algorithm suitable for real-time implementation. The
simulated output of the proposed method gives the least total harmonic
distortion and also the reduced losses on the power circuit.