changes for the new edition denise beachdenise … for the new edition denise beachdenise beach...

33
Changes for the New Edition Denise Beach Denise Beach Senior Engineer, NFPA © NFPA

Upload: leduong

Post on 10-Mar-2018

228 views

Category:

Documents


1 download

TRANSCRIPT

Changes for the New EditionDenise BeachDenise Beach

Senior Engineer, NFPA

© NFPA

OverviewNFPA 58-2014 Substantive Changes

TIAs

2017 Edition

NFPA 58-2014 Substantive Changes

Bulk and Industrial Plantsf G 3.3.10 Bulk Plant. A facility that stores LP-Gas in

containers of more than 4000 gal water capacity prior to further distribution as a liquid for use atprior to further distribution as a liquid for use at other facilities.

3.3.34* Industrial Plant. A facility that stores LP-Gas yin containers of more than 4000 gal water capacity for use at the facility or to distribute vapor to other facilitiesfacilities.

Bulk and Industrial Plants 3.3.10 Bulk Plant and 3.3.34 Industrial Plant are

modified to eliminate confusion in applying container appurtenance and site security requirementsappurtenance and site security requirements.

A.3.3.34 Industrial plant includes all facilities that use gas on site, including plants, farms, engine fueling g g p g gstations, schools, hotels, and other locations.

Container appurtenances now determined only by i i li icontainer size, not application.

5.7.4.1 – 4000 gal wc and less 5 7 4 2 Greater than 4000 gal wc 5.7.4.2 – Greater than 4000 gal wc

Cathodic Protection of Piping Underground steel piping larger than 1 in. nominal must

be protected by cathodic protection systemC f 1 Cathodic protection optional for piping 1 in. and smaller

South Carolina incidentLi id i i f il d t i Liquid piping failure due to corrosion

One fatality Aboveground piping constructed of corrosion resistant Aboveground piping constructed of corrosion-resistant

material, painted or otherwise protected

T k H tTank Heaters New definition added, requirements expanded 3.3.73 Tank Heater (Indirect and Direct Types). A

device used to apply heat either directly to a portion of th t i f i t t ith LP G li idthe container surface in contact with LP-Gas liquid or indirectly by circulating LP-Gas liquid from the container to the device and then back to the containercontainer to the device and then back to the container.

3.3.73.1 Direct Gas-Fired Tank Heater. A gas-fired device that applies heat directly to the container surface in contact with LP-Gas liquid.

T k H t 5 21 4Tank Heaters – 5.21.4 Tank heaters must be approved for the application Tank heaters must be marked with rated input and

maximum vaporizing capacity Manufacturer’s instructions must clearly indicate

use for heating LP-Gas containersLi it t l ( h d) Limit control (unchanged)

Electric immersion heaters must automatically shut off if liquid level falls below top of heateroff if liquid level falls below top of heater

Direct gas-fired tank heaters must be removable for tank inspectionp

T k H t 5 21 4Tank Heaters – 5.21.4 Direct gas-fired tank heaters for outdoor, aboveground g g

use only No direct flame impingement on the container Automatic safety shutoff (with manual reset) to stop

flow of gas to the heater if the pilot flame is extinguishedextinguished

On containers greater than 1000 gal wc, automatic safety shutoff to stop flow of gas if container becomessafety shutoff to stop flow of gas if container becomes empty of liquid

LP-Gas Pumps New equipment design requirements 3.3.19 Design Pressure. The maximum pressure at

which the equipment or system is designed to operate.

New 5 17 2 and 5 17 3 specify equipment design New 5.17.2 and 5.17.3 specify equipment design pressure for pump and bypass valve based on maximum differential pressure produced by the p p ypump

Installation requirements unchanged

Facility Hose 3 3 22 – a hose permanently installed for the 3.3.22 – a hose…permanently installed for the

purpose of unloading product from CTMVs in non-metered service into a bulk plant or industrial plant.

6.19.2.6 (formerly 6.18) – facility hose or the facility shall be equipped with an emergency discharge

t l t th t ill h t d th fl f LP Gcontrol system that will shut down the flow of LP-Gas caused by complete separation of the facility hose within 20 seconds without the need for humanwithin 20 seconds without the need for human intervention

Derived from DOT regs (49 CFR 173) for hoseinstalled on some CTMVs

Concrete Pad New definition – A foundation consisting of solid

concrete or masonry blocks, a placed concrete slab, or a poured concrete foundationor a poured concrete foundation.

Previously undefined Definition addresses enforcement problems related Definition addresses enforcement problems related

to 6.6.3.1(G)

Vehicular Barrier Protection Previous language was not consistent

Protection against vehicular impact Protect where vehicle traffic expected Protect against physical damage

Wid f i t t ti f t bl Wide range of interpretations for acceptable protection methods and scenarios

New definition and annex material intend to clarify New definition and annex material intend to clarify

V hi l B i P t tiVehicular Barrier Protection

3.3.79* A system or method to provide physical protection for LP-Gas storage areas or installations from p gvehicular incursion.

A.3.3.79 There are numerous effective means to provide protection for LP-gas installations from impact by motor vehicles. The system or method selected depends on local conditions ith regard to the kinds of traffic that can beconditions with regard to the kinds of traffic that can be reasonably expected and the environment surrounding the location. Examples of such protection include, but are not limited to the following:limited to, the following:

(1) Guard rails(2) Steel bollards(3) R i d id lk ( i i f 6 i i h i h )(3) Raised sidewalks (minimum of 6 in. in height)(4) Fencing(5) Ditches( )(6) Berms (not to exceed 50 percent of the container perimeter)(7) Jersey barriers(8) Parking bumpers (minimum of 6 in in height)(8) Parking bumpers (minimum of 6 in. in height) (9) Fencing/gates

Vehicular Barrier Protection Requirements made consistent: 6.6.6.1 – Underground or mounded containers 6.25.3.13 – Liquid dispensers 8.4.2.2 – Cylinder exchange cabinets 6.25.3.13 – also added prescriptive requirements

Concrete-filled steel guard posts S d t th 4 ft t Spaced not more than 4 ft apart

Set at least 3 ft deep in concrete footing At least 3 ft tall At least 3 ft tall At least 3 ft away from container

CLeak Check and Pressure Test New requirements added to ensure that

“outside” piping is tested for pressure containment and leakage.D fi iti d i t b t ti ll Definitions and requirements substantially extracted from NFPA 54-2012.

3 3 37 Leak Check An operation performed on 3.3.37 Leak Check. An operation performed on a gas piping system to verify that the system does not leak.

3.3.59. Pressure Test. An operation performed to verify the gastight integrity of gas piping f ll i it i t ll ti difi tifollowing its installation or modification.

Pressure Test – 6.14 After installation or modification Pressure test at normal operating pressure LP-Gas is permitted to be used as the test medium

NOTE: NFPA 54 does NOT allow LP-Gas to be used in the pressure testin the pressure test

Where branches are installed, only the branch must be pressure testedbe pressure tested

Where NFPA 54 applies, use NFPA 54

Leak Check – 6.15 Vapor systems operating at 20 psig or less only Immediately after gas is introduced to a new system

for following an interruption in service Sample method – Annex L

Wh NFPA 54 li NFPA 54 Where NFPA 54 applies, use NFPA 54 Where leakage is indicated, fuel supply must be

shutoff until necessary repairs are madeshutoff until necessary repairs are made

Small ASME Tank Location PRV on ASME container less than 125 gal wc

cannot discharge in or beneath a buildingS f S f Subject of Successful Appeal

6.3.4.1 (previously 6.3.7) restored which permits only cylinders to be installed under buildings w/ 50%cylinders to be installed under buildings w/ 50% perimeter open to atmosphere

New requirement explicit on installation of smallNew requirement explicit on installation of small ASME containers

Automated Cylinder Exchange New requirements – section 8.6 Must comply with requirements of 8.4 and 8.5 Electrical equipment inside storage cabinet must be

Class I, Div 2.D t i t l t i l l ifi ti f i t Does not impact electrical classification of equipment installed near the exchange cabinet

Cabinets designed to allow cylinder storage inCabinets designed to allow cylinder storage in upright position only

Unattended Facilities 14.2.1.6 – Facilities that are not attended

Remote locations No personnel stationed on site Internal valves and emergency shutoff valves must be

closed except when facility is in useclosed except when facility is in use Containers used for supplying a process or system

exempted Vehicle fuel dispenser locations exempted

Miscellaneous 6.4.4.3 Combustible materials shall not accumulate

or be stored within 10 ft of a container.L d d d l t d Long dry grass or weeds deleted

6.19.2.5… liquid inlet piping shall be designed to prevent debris from impeding the action of valvesprevent debris from impeding the action of valves…

8.5.2 Fire extinguisher having a 40-B:C or 80-B:Crating and a minimum capacity of 18 lb dry chemicalg p y y Consistent with NFPA 10 Distance from storage determined by rating

TIAs from 2011 Edition Now permanent parts of the code 4.4 Qualification of Personnel Cathodic Protection of Underground and Mounded

Tanks5 2 1 11 (C t i t ti ) 5.2.1.11 (Container construction)

6.6.6.1(I) (Installation) 6 17 3 1 (Periodic testing) 6.17.3.1 (Periodic testing)

Tentative Interim AmendmentsI d With th C dIssued With the Code

Testing ESVs 6 12 9 Testing of Emergency Shutoff Valves 6.12.9 Testing of Emergency Shutoff Valves Committee finalized language in ROC Concern that ROC language could be interpreted Concern that ROC language could be interpreted

to mean that non-mandatory ESVs must be tested TIA added language to clarify that only the TIA added language to clarify that only the

required ESVs specified in NFPA 58 must be tested

Stationary EnginesC f Chapter 11 scope modified to address only vehicle engine applications

Containers for stationary engines relocated to 6 26 Containers for stationary engines relocated to 6.26

Tentative Interim AmendmentsI d S b t t th C dIssued Subsequent to the Code

Valves & Appurtenances Restructured 5.7.4.1

Existing (A) and (B) combined into one paragraph (A). Deleted existing (C) so that all containers 4000 gal wc

and less are equipped the same regardless of applicationapplication

Existing (D) becomes (B). Existing (D)(3) now applies only to containers greater

than 125 gal wc.

Valves & Appurtenances Table 5.7.4.2 – delete column for 2001 – 4000 gal wc 5.7.4.3 – now applies only to containers over 4000

gal wc Existing 5.7.4.4 deleted in its entirety

R lt 5 7 4 5 b d 5 7 4 4 Result – 5.7.4.5 renumbered as 5.7.4.4 Chapter 11 updated to reflect new structure and

correct cross referencescorrect cross-references

2017 Editi2017 Edition

Schedule 2017 Edition Submittal Public Input:

PAPER – June 6, 2014 Electronic (e-PI) – July 7, 2014

Previously, 4 month period starting at Notice of Intent to Enter Cycleto Enter Cycle

Now, Notice of Intent published immediately after issuance of new editionissuance of new edition

TC Meeting held no later than Dec 12, 2014 First Draft published by March 6, 2015st a t pub s ed by a c 6, 0 5

Denise Beach, NFPA www nfpa org/58www.nfpa.org/58